1) The document discusses improvements to voltage regulation systems at electricity plants in Thailand from 2554 to 2555.
2) A new Automatic Line Voltage Controller (ALVC) was installed to work alongside the existing Automatic Voltage Regulator (AVR) systems to better maintain voltages within allowed ranges.
3) Over this period three kaizen or continuous improvement projects were conducted to refine the performance of the ALVC system - improving its reactive power control, PID function, and resolving issues with power supply and I/O configuration.
4. PA-PLUS
. (Planned Outage
Maintenance) (Unplanned Outage / Breakdown
Maintenance)
Automatic Voltage Regulator (AVR)
(Generator Voltage)
(Generator)
Static Frequency Converter (SFC)
Startup Gas Turbine
SFC
Start
On Load Tap Changer (OLTC)
Tap
(Service Station
Transformer)
Automatic Synchronizer (ASS)
PA-PLUS
5. Active Power
Reactive Power
Capacitor Bank
Static VAR Compensator
Capacitor Bank
Micro Controller
Programmable Logic Control (PLC)
Distributed Control System (DCS)
8. (Generator)
/
Automatic Voltage Regulator (AVR)
Capacitor Bank
Capacitor Bank
Capacitor Bank
Static VAR
compensator
Static VAR Compensator
Static VAR
Compensator
G AVR
16. WHAT WHAT TO DO WHERE 2554 2555 - WHO HOW
11 12 01 02 03 04 05 06 07 08 09-
P
-
-
-
-
, -
-
-
PDCA.
- -
- -
D (
)
-
C /
-
-
A
-
-
-
-
-
1-2
1 2,3 4,5 6 7 8 9
9 90 %
Plan
Actual
21. Automatic Line Voltage Controller
Planned Outage
Local Control Panel
Operator
NCC
PLCLine Voltage
Power Transducer
Industrial Ethernet
PLC
AVR
Automatic Line Voltage Controller (ALVC)
23. Automatic Line Voltage Controller
4 5
KAIZEN 1
Automatic Line Voltage Controller
-10
10
30
50
70
1
MVAR
Time
Reactive Power
220
225
230
235
240
1
kV
Time
Bus Voltage
Actual
Setpoint
KAIZEN
ALVC Reactive Power
24. • WHY WHY Analysis
1
ALVC
Reactive Power
ALVC*
Reactive Power
PID**
PLC
output PLC
OMRON
output
2
Reactive Power
1
Power Transducer
Reactive
Power
* ALVC Automatic Line Voltage Controller
(Kaizen 2)
** PID Function
Output
25. 1 Reactive Power :
Static test Power Transducer
• AVLC Reactive Power
Power Transducer Output Test
(Kaizen 2)
0
1
2
3
4
5
6
0 0.5 1 1.5
PowerTransducerOutput(V)
ReactivePower (P.U.)
Reactive Power
(Leading -)
Reactive Power
Lagging (+)
26. 2 PID PLC OMRON Output :
PID Output
• AVLC Reactive Power
PID(190)
Setpoint
feedback
max
min
PID Output
Max, Min
(Kaizen 2)
** PID Function Output
28. (Kaizen 2)
KAIZEN 2
Automatic Line Voltage Controller
6 5
230
231
232
233
234
235
236
237
238
239
240
1
kV
Time
Bus Voltage
Actual
Setpoint
-25
-20
-15
-10
-5
0
Reactive Power
GEN1
GEN2
GEN3
Automatic Line Voltage Controller KAIZEN 2
Time
MVAR
29. (Kaizen 2)
Automatic Line Voltage Controller
5
25 5
KAIZEN 2
Automatic Line Voltage Controller KAIZEN 2
Set Point
Actual Bus Voltage
Bus Voltage 230 KV Set point
30. . OFF Power Supply ALVC On
12 2555
ALVC Bus 230 kV
Alarm “I/O
Configuration
Error” PLC
KAIZEN 3
( 2)
Analog Input Modules
31. • WHY WHY Analysis
1
Hardware PLC
Analog Input
PLC
2
Battery
Back Up
1
Off Power
Supply
* ALVC Automatic Line Voltage Controller
Software PLC
Kaizen 3
32. 1 Battery PLC I/O
Configuration Power OFF
:
Battery 3.58 Volt Spec. 3.6 Volt
•
Kaizen 3
33. 2 PLC :
Default I/O Configuration Program Analog Input
Kaizen 3
Ch.8 BUS
0-10 Volt Default 10Volt)
I/O Table
•
34. PLC Default I/O Configuration
“ON, OFF” Power Supply ALVC
Disable Function
(Kaizen 3)
I/O Table Setting
38. :
Design
Site Installation
Static Function Test
Factory Test
Commissioning Test
Loop Wiring Test
Interface ALVC
Run Simulator Mode
Site
Interface
Function
Parameter
39. : 230 kV 220 volt 2%
Command from NCC
Synchronizing
Enable ALVC Mode
Start up unit
Set voltage setpoint
Select unit
Start up unit
unit
ALVC
HMI
จึงสรุปว่า การควบคุมแรงดันในระบบไฟฟ้าด้วย Automatic Line Voltage Controller สามารถควบคุมแรงดัน Bus Voltage 230 KV ได้ตาม ค่า Set point
หลังการติดตามผลการนำ ALVC เข้าใช้งานพบว่า ถ้าเกิดมีการ Off Power Supply ที่จ่ายให้กับ ALVC หรือระบบไฟฟ้าดับ ค่าต่างๆที่เราเซ็ตโปรแกรมไว้ในตัว ALVC จะถูกเปลี่ยนคืนสถานะกลับไปเป็นค่าเดิมที่ถูกเซ็ตค่าเริ่มจนมาจากบริษัทผู้ผลิต เป็นผลทำให้การประมวลผลและอ่านค่าหลัง On Power Supply ผิดเพี้ยน ไม่ถูกต้อง ปัญหานี้จึงนำไปสู่กิจกรรม Kaizen ครั้งที่ 3
จากการวิเคราะห์การอ่านค่าสัญญาณแรงดันไฟฟ้า Bus 230 KV ได้ไม่ถูกต้องนั้นกลุ่มให้ข้อสังเกตุไว้ 2 สาเหตุ ก็คือ Battery ที่ให้ Back up ข้อมูลเสื่อมสภาพ หรือมีความผิดปกติของการตั้งค่า Analog Input ของ PLC เราจะไปพิสูจน์ร่วมกันดังนี้ครับ
การติดตามผลหลังการติดตั้งใช้งาน ทางกลุ่มได้ทำการติดตามผลการใช้งาน Automatic Line Voltage Controllerโดยการสอบถาม Operator ทุกเดือนพบว่ายังสามารถใช้งานได้เป็นปกติ