5. 4Q Regenerative IGBT Inverter
• General data:
– Range of Power:
• 200‐3,1MVA 3,3kV
• 400‐6,2MVA 6,6kV
– Drive type: Regenerative (4Q)
– Power components: HV IGBT by Mitsubishi
– Line side grid connections:
• AFE (Active Front End)
• Three phases/three levels
– Available control types:
• Sensorless
• V/F
• Vector Control
9. General data:
• Transformer Primary Voltage: TBD
• Transformer secondary Voltage: (TBD)
• Transformer secondary Voltage: 3300 Vca
• Connection type: D/YD or D/Y11 (TBD)
• Supply voltage tolerance: +/‐ 10% (1)
• Mains frequency: 50/60Hz
• Supply frequency tolerance: +/‐ 3%
• Auxiliary voltage: 400Vca (3 phases) (2)
• Ambient temperature: 0°C to +40°C (3)
• Aux. circuit voltage: 110 V 50Hz
• Environment: TBD
• Signal. Circuit: 24 Vdc
• Altitude: < 1000 m a.s.l.
• Installation: Indoor
• Humidity: 5 to 95 % non condensing
• Options heaters
Notes:
(1) in case of LVRT request see the options
(2) in case of LVRT a UPS feeder is required
(3) solution available for different temperature range
10. Data sheet 3,3kV
• Cooling form: Water cooling
• Enclosure Class: IP 3X (STD)
• Finishing/colour supplied in RAL 7032 Epoxy powder painting (other
colours on request)
• Cabinet: is metal enclosed type built by sheets
20/10 mm thick, double side access,
water to air heat cooling system is
included into the cabinet dimension
• Dimension: W4400xH2200xD1000 (mm)
16. Data sheet
Functions:
• Over‐current
• Short circuit
• Ground fault
• Phase loss detection
• Over voltage
• Under voltage
• Over temperature
• Generator/grid sides overload
detection
• Others under request
Bus Interface and MMI:
• RS 485 (built in communication)
• Ethernet connection:
– Modbus TCP (Option)
– Web server (Option)
• CAN Bus (built in communication)
• Profibus DP ™ (Option)
• Front door Operator interface
complete of touch screen keypad 7”
• Others under request