International Research Journal of Engineering and Technology (IRJET) e-ISSN: 2395-0056
Volume: 06 Issue: 03 | Mar 2019 www.irjet.net p-ISSN: 2395-0072
© 2019, IRJET | Impact Factor value: 7.211 | ISO 9001:2008 Certified Journal | Page 892
Impact of Superconducting Fault Current Limiter on Passive Resonance
Circuit Breaker (PRCB) in HVDC System
Mr. A. A. Kalamkar1, Miss. K. L. Bari2, Prof .G. R. Lohote3
1PG Scholar, Dept of Operation Management, Shri Shivaji Marath Society’s Institute of Management & Research, Pune,
Maharashtra, India
2PG Scholar, Dept of Electrical Engineering, SSBT’S College of Engineering & Technology, Jalgaon, Maharashtra, India
3Assistant Professor, Dept of Electrical Engineering, JSPM’s Bhivarabai Sawant Institute of Technology and Research,
Pune, Maharashtra, India
----------------------------------------------------------------------------***--------------------------------------------------------------------------
Abstract:- For several decades HVDC technology was used primarily for point-to-point bulk power transmission. Although
multi-terminal HVDC systems are very few in number, it is expected that multiple HVDC links may be interconnected into
HVDC transmission grid. Since every meshed grid requires reliable protection solution, an HVDC circuit breaker must be
developed and introduced. When sudden short circuit fault is happened on transmission line, it will cause sudden increase in
current magnitude. Various electrical devices used for protection of such a transmission line against serious fault current.
Circuit breakers, current limiting reactor are used to protect the system from fault current, superconducting fault current
limiter is one of them. This paper focuses on the performance evaluation of Passive Resonance HVDC circuit breaker concepts.
The performance evaluation study is carried out by means of MATLAB simulations. The obtained quantitative results describe
capabilities and limitations of Passive Resonance circuit breaker concepts as well as the reaction of HVDC network on
switching operations. Different converter protection measures and in particular application of fault current limiter were
considered, too. In this paper comparative results of Passive Resonance circuit breaker without and with superconducting
fault current limiter (SFCL) are observed. For simulation two cases of PRCB are considered, PRCB without using SFCL and
PRCB with using SFCL.
Keywords: HVDC circuit breaker, Fault protection methods, Network response, Simulation-based performance evaluation.
Introduction:
As we see most of the time fault current interruption is easily achieved by AC circuit breakers or by using fault current
limiter. For AC circuit breakers it easily possible to limit that fault current level by natural zero current crossing but this
facility is not available in DC circuit breakers. To achieve that zero current by DC circuit breakers a forced commutation should
be used, this obtained by making some modifications. Several types of HVDC circuit breakers are available in market like
Mechanical Circuit Breaker (MCB), Passive Resonance Circuit Breaker (PRCB), Inverse Current Injection Circuit Breaker (I-CB),
and Hybrid Circuit Breaker. But in this paper we only were focusing on Passive Resonance Circuit Breaker (PRCB) to achieve
artificial zero current crossing. As an alternative the combining effect of Superconducting Fault current Limiter and HVDC
circuit breakers gives much reduction in fault current level, also improves the transmission line performance. SFCL is best
solution for transmitting a bulky High Voltage power over a long distance. [1]
Superconducting fault current limiter (SFCL) has capability to limit fault current level within first cycle and not only
decrease the stress on HVDC circuit breaker but also improves the transmission line performance. Superconducting fault
current limiter has three type’s Resistive type, Inductive type and Bridge type SFCL according to material used for
construction. In this paper here we used resistive type SFCL with Passive resonance circuit breaker (PRCB). For simulation
purpose a test bed model of PRCB with SFCL is used in MATLAB/Simulink [2]
A) HVDC transmission line model :
For analyzing the effect of superconducting fault current limiter on PRCB HVDC circuit breaker a test model of HVDC
transmission line is consider. This model is designed in MATLAB/Simulink as shown in Fig.1. The system test bed model is
designed with different components of different ratings. Initially three phase AC system is taken of 230 KV, the system voltage
is stepped down to 110 kV by transformer. AC voltage then convert to DC by rectifier. At both ends of system converter
International Research Journal of Engineering and Technology (IRJET) e-ISSN: 2395-0056
Volume: 06 Issue: 03 | Mar 2019 www.irjet.net p-ISSN: 2395-0072
© 2019, IRJET | Impact Factor value: 7.211 | ISO 9001:2008 Certified Journal | Page 893
stations are implemented. The required specifications of this system are transmission line length = 50 km, rated voltage 100
kV, Nominal current is of 1 kA, rated power 100 MW.
Fig. 1. Two-level point-to-point HVDC test bed model
In this system Passive Resonance circuit breaker (PRCB) is used in series with Resistive Superconducting Fault Current
Limiter (SFCL). [3]
B) Passive Resonance circuit breaker (PRCB):
Fig. 2. Passive Resonance Circuit Breaker
A passive resonance HVDC circuit breaker consists of a mechanical switch and a parallel coupled oscillating circuit
composed of capacitor and inductor as shown in Figure 2. To dissipate the energy stress on the MCB, the secondary path with
a series L-C circuit is added. When the fault occurred at 0.1 sec, MCB opens with 10 ms of delay considering opening delay. As
soon as the mechanical switch starts to open its contacts, an electric arc arises between them, and resonance occurs in the loop
formed by mechanical switch, inductor and capacitor. This phenomenon is possible owing to the electric arc property of
displaying negative differential resistance. Resonance developing within the HVDC circuit breaker entails increase in the
magnitude of the current oscillating in the L-C circuit. The DC current begins to commutate and resonate in the secondary path
after the arc impedance exceeds the L-C impedance. When a DC current of the primary path meets zero crossing, this current
being superimposed on the breaking current provides current zero and enables the mechanical switch to quench the arc. An
additional parallel surge arrester (SA) circuit is supplemented to prevent voltage stress across the PRCB during arc extinction.
This current being superimposed on the breaking current provides current zero and enables the mechanical switch to quench
the arc. [4]
International Research Journal of Engineering and Technology (IRJET) e-ISSN: 2395-0056
Volume: 06 Issue: 03 | Mar 2019 www.irjet.net p-ISSN: 2395-0072
© 2019, IRJET | Impact Factor value: 7.211 | ISO 9001:2008 Certified Journal | Page 894
C) Simulation results of PRCB without SFCL:
Following fig. 3 shows main current characteristics of PRCB without applying SFCL and its value is 24 kA. The fault current
interruption time of PRCB in this case is approximate 55 ms.
Fig.3. Main current of PRCB without SFCL
Fig. 4 shows secondary path current of PRCB without SFCL and its value is of 11 kA.
Fig. 4 Secondary path current of PRCB without SFCL
International Research Journal of Engineering and Technology (IRJET) e-ISSN: 2395-0056
Volume: 06 Issue: 03 | Mar 2019 www.irjet.net p-ISSN: 2395-0072
© 2019, IRJET | Impact Factor value: 7.211 | ISO 9001:2008 Certified Journal | Page 895
Absorber path current of PRCB without SFCL is 17.5 kA as shown below. This is current thorough surge arrester. This SA is
used for protection of whole system from high voltage.
Fig.5 Absorber path current of PRCB without SFCL
Now our intension is to find PRCB characteristics when SFCL is applied in this system. Here we observed much difference in
value of currents.
Given fig.6 shows main current of PRCB. The main current value is about 7.2 kA. Fault current interruption time is 25 ms and
achieves nearly 62.1 % reduction in fault current level.
Fig. 6 Main current of PRCB with SFCL
International Research Journal of Engineering and Technology (IRJET) e-ISSN: 2395-0056
Volume: 06 Issue: 03 | Mar 2019 www.irjet.net p-ISSN: 2395-0072
© 2019, IRJET | Impact Factor value: 7.211 | ISO 9001:2008 Certified Journal | Page 896
The secondary path current is the current through inductor and capacitor series branch. In this with SFCL case the value of
secondary path current is 4 kA.
Fig. 7 Secondary path current of PRCB with SFCL
Given fig. 8 shows absorber path current of PRCB when SFCL is used in HVDC transmission system. The value of these current
is 6.9 approximate 7 kA.
Fig. 8 Absorber path current of PRCB with SFCL
International Research Journal of Engineering and Technology (IRJET) e-ISSN: 2395-0056
Volume: 06 Issue: 03 | Mar 2019 www.irjet.net p-ISSN: 2395-0072
© 2019, IRJET | Impact Factor value: 7.211 | ISO 9001:2008 Certified Journal | Page 897
Where the main current is current through main path, secondary path means current through inductor and capacitor
components while absorber current is the current through surge srrester path [5]
Table I: Current values of PRCB without and with SFCL
Parameters PRCB without SFCL PRCB with SFCL
Main current 24 kA 7.2 kA
Secondary current 11 kA 4 kA
Absorber current 17.5 kA 6.9 kA
Conclusion:
Every time it is not possible to limit maximum value fault current by using circuit breaker only. For that purpose in
addition to HVDC circuit breaker a superconducting fault current limiter is applied and results are observed in this paper. The
noticeable improvements are observed in case of PRCB with using SFCL, without SFCL the maximum fault current interruption
was achieved, also the fault current values are more. When SFCL was applied, The L/R time constant of secondary path was
decreased, and therefore fast interruption with less oscillations are observed.
References:
1) Matthias K. Bucher, M. Frank, “Fault Current Interruption in Multi terminal HVDC Networks” IEEE Transaction on Power
Delivery, vol. X, 2015.
2) G Swetha, R. Sathish Kumar & B. Venkata Prasanth “Performance of Superconducting Fault Current Limiter in Power
System” International Journal of Research vol. 03 Issue 10 June 2016.
3) Jong-Geon Lee, Umer Amir Khan, Ho-Yun Lee, and Bang-Wook Lee, “Impact of SFCL on the Four Types of HVDC Circuit
Breakers by Simulation” IEEE Transactions on Applied Superconductivity, Vol. 26, No. 4, June 2016.
4) Mudar Abedrabbo, Willem Leterme and Dirk Van Hertem “Analysis and Enhanced Topologies of Active-Resonance DC
Circuit Breaker”.
5) Gen Li, Jun Liang, Carlos E Ugalde- Loo, “Impact of DC Circuit Breakers on AC/DC System Stability Subject to DC Faults”
2016 International High Voltage Direct Current Conference (HVDC 2016).
6) MD. Afser khan, Mr. V. Ganesh Kumar, “Fault Current Limiting Technologies of HVDC Circuit Breakers With Impact Of
SFCL” International Journal of Technology and Engineering Science [IJTES] vol. 5, Oct. 2017.

More Related Content

What's hot

Mitigation of Power Quality Issues by Nine Switches UPQC Using PI & ANN with ...
Mitigation of Power Quality Issues by Nine Switches UPQC Using PI & ANN with ...Mitigation of Power Quality Issues by Nine Switches UPQC Using PI & ANN with ...
Mitigation of Power Quality Issues by Nine Switches UPQC Using PI & ANN with ...
MABUSUBANI SHAIK
 
Comparison of PI and ANN Control Techniques for Nine Switches UPQC to Improve...
Comparison of PI and ANN Control Techniques for Nine Switches UPQC to Improve...Comparison of PI and ANN Control Techniques for Nine Switches UPQC to Improve...
Comparison of PI and ANN Control Techniques for Nine Switches UPQC to Improve...
MABUSUBANI SHAIK
 

What's hot (20)

IRJET- Power Quality Improvement by Harmonic Reduction using Compact Desi...
IRJET-  	  Power Quality Improvement by Harmonic Reduction using Compact Desi...IRJET-  	  Power Quality Improvement by Harmonic Reduction using Compact Desi...
IRJET- Power Quality Improvement by Harmonic Reduction using Compact Desi...
 
IRJET- High Efficiency Bridge-Less Battery Charger for Light Electric Veh...
IRJET-  	  High Efficiency Bridge-Less Battery Charger for Light Electric Veh...IRJET-  	  High Efficiency Bridge-Less Battery Charger for Light Electric Veh...
IRJET- High Efficiency Bridge-Less Battery Charger for Light Electric Veh...
 
IRJET- Improved Power Quality Switched Inductor Cuk Converter for Battery Cha...
IRJET- Improved Power Quality Switched Inductor Cuk Converter for Battery Cha...IRJET- Improved Power Quality Switched Inductor Cuk Converter for Battery Cha...
IRJET- Improved Power Quality Switched Inductor Cuk Converter for Battery Cha...
 
PERFORMANCE ANALYSIS OF MODIFIED QSERL CIRCUIT
PERFORMANCE ANALYSIS OF MODIFIED QSERL CIRCUITPERFORMANCE ANALYSIS OF MODIFIED QSERL CIRCUIT
PERFORMANCE ANALYSIS OF MODIFIED QSERL CIRCUIT
 
Mitigation of Power Quality Issues by Nine Switches UPQC Using PI & ANN with ...
Mitigation of Power Quality Issues by Nine Switches UPQC Using PI & ANN with ...Mitigation of Power Quality Issues by Nine Switches UPQC Using PI & ANN with ...
Mitigation of Power Quality Issues by Nine Switches UPQC Using PI & ANN with ...
 
Improved Grid Synchronization Algorithm for DG System using DSRF PLL under Gr...
Improved Grid Synchronization Algorithm for DG System using DSRF PLL under Gr...Improved Grid Synchronization Algorithm for DG System using DSRF PLL under Gr...
Improved Grid Synchronization Algorithm for DG System using DSRF PLL under Gr...
 
Development of Multilevel Inverters for Control Applications
Development of Multilevel Inverters for Control ApplicationsDevelopment of Multilevel Inverters for Control Applications
Development of Multilevel Inverters for Control Applications
 
Comparison of PI and ANN Control Techniques for Nine Switches UPQC to Improve...
Comparison of PI and ANN Control Techniques for Nine Switches UPQC to Improve...Comparison of PI and ANN Control Techniques for Nine Switches UPQC to Improve...
Comparison of PI and ANN Control Techniques for Nine Switches UPQC to Improve...
 
IRJET- Design and Analysis of Single Ended Primary Inductance Converter (SEPI...
IRJET- Design and Analysis of Single Ended Primary Inductance Converter (SEPI...IRJET- Design and Analysis of Single Ended Primary Inductance Converter (SEPI...
IRJET- Design and Analysis of Single Ended Primary Inductance Converter (SEPI...
 
A low power front end analog multiplexing unit for 12 lead ecg signal acquisi...
A low power front end analog multiplexing unit for 12 lead ecg signal acquisi...A low power front end analog multiplexing unit for 12 lead ecg signal acquisi...
A low power front end analog multiplexing unit for 12 lead ecg signal acquisi...
 
International Journal of Engineering Research and Development
International Journal of Engineering Research and DevelopmentInternational Journal of Engineering Research and Development
International Journal of Engineering Research and Development
 
20120140506014
2012014050601420120140506014
20120140506014
 
Closed Loop Controlled Solar Cell Powered Embedded EZ-Source Inverter fed Ind...
Closed Loop Controlled Solar Cell Powered Embedded EZ-Source Inverter fed Ind...Closed Loop Controlled Solar Cell Powered Embedded EZ-Source Inverter fed Ind...
Closed Loop Controlled Solar Cell Powered Embedded EZ-Source Inverter fed Ind...
 
Study and Review on Various Current Comparators
Study and Review on Various Current ComparatorsStudy and Review on Various Current Comparators
Study and Review on Various Current Comparators
 
D04462128
D04462128D04462128
D04462128
 
A Novel Approach of Position Estimation and Power Factor Corrector Converter ...
A Novel Approach of Position Estimation and Power Factor Corrector Converter ...A Novel Approach of Position Estimation and Power Factor Corrector Converter ...
A Novel Approach of Position Estimation and Power Factor Corrector Converter ...
 
A High-Swing OTA with wide Linearity for design of self-tunable linear resistor
A High-Swing OTA with wide Linearity for design of self-tunable linear resistorA High-Swing OTA with wide Linearity for design of self-tunable linear resistor
A High-Swing OTA with wide Linearity for design of self-tunable linear resistor
 
HBT
HBTHBT
HBT
 
A bridgeless bhb zvs pwm ac-ac converter for high-frequency induction heating...
A bridgeless bhb zvs pwm ac-ac converter for high-frequency induction heating...A bridgeless bhb zvs pwm ac-ac converter for high-frequency induction heating...
A bridgeless bhb zvs pwm ac-ac converter for high-frequency induction heating...
 
IRJET- Simulation of Energization and De-Energization of Capacitor Banks and ...
IRJET- Simulation of Energization and De-Energization of Capacitor Banks and ...IRJET- Simulation of Energization and De-Energization of Capacitor Banks and ...
IRJET- Simulation of Energization and De-Energization of Capacitor Banks and ...
 

Similar to IRJET- Impact of Superconducting Fault Current Limiter on Passive Resonance Circuit Breaker (PRCB) in HVDC System

Analysis of multi terminal hvdc transmission system feeding very weak ac netw...
Analysis of multi terminal hvdc transmission system feeding very weak ac netw...Analysis of multi terminal hvdc transmission system feeding very weak ac netw...
Analysis of multi terminal hvdc transmission system feeding very weak ac netw...
eSAT Journals
 
Student_01_Ankit Kherodia_Nirma Univ_Ahmedabad
Student_01_Ankit Kherodia_Nirma Univ_AhmedabadStudent_01_Ankit Kherodia_Nirma Univ_Ahmedabad
Student_01_Ankit Kherodia_Nirma Univ_Ahmedabad
ankit kherodiya
 
Design and implementation of a series switching SPSI for PV cell to use in ca...
Design and implementation of a series switching SPSI for PV cell to use in ca...Design and implementation of a series switching SPSI for PV cell to use in ca...
Design and implementation of a series switching SPSI for PV cell to use in ca...
journalBEEI
 
Novel pwm modulation technique for minimizing circulation current and zero cr...
Novel pwm modulation technique for minimizing circulation current and zero cr...Novel pwm modulation technique for minimizing circulation current and zero cr...
Novel pwm modulation technique for minimizing circulation current and zero cr...
IAEME Publication
 
Chapter 8 (synny katyara-ashfaq hashmani-bs chowdhry)(1)
Chapter 8 (synny katyara-ashfaq hashmani-bs chowdhry)(1)Chapter 8 (synny katyara-ashfaq hashmani-bs chowdhry)(1)
Chapter 8 (synny katyara-ashfaq hashmani-bs chowdhry)(1)
sunny katyara
 

Similar to IRJET- Impact of Superconducting Fault Current Limiter on Passive Resonance Circuit Breaker (PRCB) in HVDC System (20)

IRJET- Comparison of H5 and HERIC Trasformerless Inverter Topology Conserning...
IRJET- Comparison of H5 and HERIC Trasformerless Inverter Topology Conserning...IRJET- Comparison of H5 and HERIC Trasformerless Inverter Topology Conserning...
IRJET- Comparison of H5 and HERIC Trasformerless Inverter Topology Conserning...
 
A fuzzy logic controlled dc dc converter for an
A fuzzy logic controlled dc dc converter for anA fuzzy logic controlled dc dc converter for an
A fuzzy logic controlled dc dc converter for an
 
Analysis of multi terminal hvdc transmission system feeding very weak ac netw...
Analysis of multi terminal hvdc transmission system feeding very weak ac netw...Analysis of multi terminal hvdc transmission system feeding very weak ac netw...
Analysis of multi terminal hvdc transmission system feeding very weak ac netw...
 
IRJET - Comparative Study of Different AC-DC Converter for High Step Down
IRJET - Comparative Study of Different AC-DC Converter for High Step DownIRJET - Comparative Study of Different AC-DC Converter for High Step Down
IRJET - Comparative Study of Different AC-DC Converter for High Step Down
 
IMPROVING POWER QUALITY AND FAST ENERGY SAVING METHODS IN POWER DISTRIBUTION ...
IMPROVING POWER QUALITY AND FAST ENERGY SAVING METHODS IN POWER DISTRIBUTION ...IMPROVING POWER QUALITY AND FAST ENERGY SAVING METHODS IN POWER DISTRIBUTION ...
IMPROVING POWER QUALITY AND FAST ENERGY SAVING METHODS IN POWER DISTRIBUTION ...
 
Student_01_Ankit Kherodia_Nirma Univ_Ahmedabad
Student_01_Ankit Kherodia_Nirma Univ_AhmedabadStudent_01_Ankit Kherodia_Nirma Univ_Ahmedabad
Student_01_Ankit Kherodia_Nirma Univ_Ahmedabad
 
E010623545
E010623545E010623545
E010623545
 
Single Phase Matrix Converter for Input Power Factor Improvement
Single Phase Matrix Converter for Input Power Factor ImprovementSingle Phase Matrix Converter for Input Power Factor Improvement
Single Phase Matrix Converter for Input Power Factor Improvement
 
Studies On Switching Losses In Electric Vehicle Drive Train System
Studies On Switching Losses In Electric Vehicle Drive Train SystemStudies On Switching Losses In Electric Vehicle Drive Train System
Studies On Switching Losses In Electric Vehicle Drive Train System
 
CONTROL OF BATTERY OPERATED SYSTEM WITH A DC-DC BOOSTCONVERTER FED DSTATCOM U...
CONTROL OF BATTERY OPERATED SYSTEM WITH A DC-DC BOOSTCONVERTER FED DSTATCOM U...CONTROL OF BATTERY OPERATED SYSTEM WITH A DC-DC BOOSTCONVERTER FED DSTATCOM U...
CONTROL OF BATTERY OPERATED SYSTEM WITH A DC-DC BOOSTCONVERTER FED DSTATCOM U...
 
1st paper
1st paper1st paper
1st paper
 
Design and implementation of a series switching SPSI for PV cell to use in ca...
Design and implementation of a series switching SPSI for PV cell to use in ca...Design and implementation of a series switching SPSI for PV cell to use in ca...
Design and implementation of a series switching SPSI for PV cell to use in ca...
 
Novel pwm modulation technique for minimizing circulation current and zero cr...
Novel pwm modulation technique for minimizing circulation current and zero cr...Novel pwm modulation technique for minimizing circulation current and zero cr...
Novel pwm modulation technique for minimizing circulation current and zero cr...
 
Novel pwm modulation technique for minimizing circulation current and zero cr...
Novel pwm modulation technique for minimizing circulation current and zero cr...Novel pwm modulation technique for minimizing circulation current and zero cr...
Novel pwm modulation technique for minimizing circulation current and zero cr...
 
Y04408126132
Y04408126132Y04408126132
Y04408126132
 
E04501041049
E04501041049E04501041049
E04501041049
 
Techno economic study of series current limiting reactor and its impact in th...
Techno economic study of series current limiting reactor and its impact in th...Techno economic study of series current limiting reactor and its impact in th...
Techno economic study of series current limiting reactor and its impact in th...
 
A Review of Analysis and Modeling of Grid Connected Three Phase Multilevel Un...
A Review of Analysis and Modeling of Grid Connected Three Phase Multilevel Un...A Review of Analysis and Modeling of Grid Connected Three Phase Multilevel Un...
A Review of Analysis and Modeling of Grid Connected Three Phase Multilevel Un...
 
Fault Modeling and Parametric Fault Detection in Analog VLSI Circuits using D...
Fault Modeling and Parametric Fault Detection in Analog VLSI Circuits using D...Fault Modeling and Parametric Fault Detection in Analog VLSI Circuits using D...
Fault Modeling and Parametric Fault Detection in Analog VLSI Circuits using D...
 
Chapter 8 (synny katyara-ashfaq hashmani-bs chowdhry)(1)
Chapter 8 (synny katyara-ashfaq hashmani-bs chowdhry)(1)Chapter 8 (synny katyara-ashfaq hashmani-bs chowdhry)(1)
Chapter 8 (synny katyara-ashfaq hashmani-bs chowdhry)(1)
 

More from IRJET Journal

More from IRJET Journal (20)

TUNNELING IN HIMALAYAS WITH NATM METHOD: A SPECIAL REFERENCES TO SUNGAL TUNNE...
TUNNELING IN HIMALAYAS WITH NATM METHOD: A SPECIAL REFERENCES TO SUNGAL TUNNE...TUNNELING IN HIMALAYAS WITH NATM METHOD: A SPECIAL REFERENCES TO SUNGAL TUNNE...
TUNNELING IN HIMALAYAS WITH NATM METHOD: A SPECIAL REFERENCES TO SUNGAL TUNNE...
 
STUDY THE EFFECT OF RESPONSE REDUCTION FACTOR ON RC FRAMED STRUCTURE
STUDY THE EFFECT OF RESPONSE REDUCTION FACTOR ON RC FRAMED STRUCTURESTUDY THE EFFECT OF RESPONSE REDUCTION FACTOR ON RC FRAMED STRUCTURE
STUDY THE EFFECT OF RESPONSE REDUCTION FACTOR ON RC FRAMED STRUCTURE
 
A COMPARATIVE ANALYSIS OF RCC ELEMENT OF SLAB WITH STARK STEEL (HYSD STEEL) A...
A COMPARATIVE ANALYSIS OF RCC ELEMENT OF SLAB WITH STARK STEEL (HYSD STEEL) A...A COMPARATIVE ANALYSIS OF RCC ELEMENT OF SLAB WITH STARK STEEL (HYSD STEEL) A...
A COMPARATIVE ANALYSIS OF RCC ELEMENT OF SLAB WITH STARK STEEL (HYSD STEEL) A...
 
Effect of Camber and Angles of Attack on Airfoil Characteristics
Effect of Camber and Angles of Attack on Airfoil CharacteristicsEffect of Camber and Angles of Attack on Airfoil Characteristics
Effect of Camber and Angles of Attack on Airfoil Characteristics
 
A Review on the Progress and Challenges of Aluminum-Based Metal Matrix Compos...
A Review on the Progress and Challenges of Aluminum-Based Metal Matrix Compos...A Review on the Progress and Challenges of Aluminum-Based Metal Matrix Compos...
A Review on the Progress and Challenges of Aluminum-Based Metal Matrix Compos...
 
Dynamic Urban Transit Optimization: A Graph Neural Network Approach for Real-...
Dynamic Urban Transit Optimization: A Graph Neural Network Approach for Real-...Dynamic Urban Transit Optimization: A Graph Neural Network Approach for Real-...
Dynamic Urban Transit Optimization: A Graph Neural Network Approach for Real-...
 
Structural Analysis and Design of Multi-Storey Symmetric and Asymmetric Shape...
Structural Analysis and Design of Multi-Storey Symmetric and Asymmetric Shape...Structural Analysis and Design of Multi-Storey Symmetric and Asymmetric Shape...
Structural Analysis and Design of Multi-Storey Symmetric and Asymmetric Shape...
 
A Review of “Seismic Response of RC Structures Having Plan and Vertical Irreg...
A Review of “Seismic Response of RC Structures Having Plan and Vertical Irreg...A Review of “Seismic Response of RC Structures Having Plan and Vertical Irreg...
A Review of “Seismic Response of RC Structures Having Plan and Vertical Irreg...
 
A REVIEW ON MACHINE LEARNING IN ADAS
A REVIEW ON MACHINE LEARNING IN ADASA REVIEW ON MACHINE LEARNING IN ADAS
A REVIEW ON MACHINE LEARNING IN ADAS
 
Long Term Trend Analysis of Precipitation and Temperature for Asosa district,...
Long Term Trend Analysis of Precipitation and Temperature for Asosa district,...Long Term Trend Analysis of Precipitation and Temperature for Asosa district,...
Long Term Trend Analysis of Precipitation and Temperature for Asosa district,...
 
P.E.B. Framed Structure Design and Analysis Using STAAD Pro
P.E.B. Framed Structure Design and Analysis Using STAAD ProP.E.B. Framed Structure Design and Analysis Using STAAD Pro
P.E.B. Framed Structure Design and Analysis Using STAAD Pro
 
A Review on Innovative Fiber Integration for Enhanced Reinforcement of Concre...
A Review on Innovative Fiber Integration for Enhanced Reinforcement of Concre...A Review on Innovative Fiber Integration for Enhanced Reinforcement of Concre...
A Review on Innovative Fiber Integration for Enhanced Reinforcement of Concre...
 
Survey Paper on Cloud-Based Secured Healthcare System
Survey Paper on Cloud-Based Secured Healthcare SystemSurvey Paper on Cloud-Based Secured Healthcare System
Survey Paper on Cloud-Based Secured Healthcare System
 
Review on studies and research on widening of existing concrete bridges
Review on studies and research on widening of existing concrete bridgesReview on studies and research on widening of existing concrete bridges
Review on studies and research on widening of existing concrete bridges
 
React based fullstack edtech web application
React based fullstack edtech web applicationReact based fullstack edtech web application
React based fullstack edtech web application
 
A Comprehensive Review of Integrating IoT and Blockchain Technologies in the ...
A Comprehensive Review of Integrating IoT and Blockchain Technologies in the ...A Comprehensive Review of Integrating IoT and Blockchain Technologies in the ...
A Comprehensive Review of Integrating IoT and Blockchain Technologies in the ...
 
A REVIEW ON THE PERFORMANCE OF COCONUT FIBRE REINFORCED CONCRETE.
A REVIEW ON THE PERFORMANCE OF COCONUT FIBRE REINFORCED CONCRETE.A REVIEW ON THE PERFORMANCE OF COCONUT FIBRE REINFORCED CONCRETE.
A REVIEW ON THE PERFORMANCE OF COCONUT FIBRE REINFORCED CONCRETE.
 
Optimizing Business Management Process Workflows: The Dynamic Influence of Mi...
Optimizing Business Management Process Workflows: The Dynamic Influence of Mi...Optimizing Business Management Process Workflows: The Dynamic Influence of Mi...
Optimizing Business Management Process Workflows: The Dynamic Influence of Mi...
 
Multistoried and Multi Bay Steel Building Frame by using Seismic Design
Multistoried and Multi Bay Steel Building Frame by using Seismic DesignMultistoried and Multi Bay Steel Building Frame by using Seismic Design
Multistoried and Multi Bay Steel Building Frame by using Seismic Design
 
Cost Optimization of Construction Using Plastic Waste as a Sustainable Constr...
Cost Optimization of Construction Using Plastic Waste as a Sustainable Constr...Cost Optimization of Construction Using Plastic Waste as a Sustainable Constr...
Cost Optimization of Construction Using Plastic Waste as a Sustainable Constr...
 

Recently uploaded

Cara Menggugurkan Sperma Yang Masuk Rahim Biyar Tidak Hamil
Cara Menggugurkan Sperma Yang Masuk Rahim Biyar Tidak HamilCara Menggugurkan Sperma Yang Masuk Rahim Biyar Tidak Hamil
Cara Menggugurkan Sperma Yang Masuk Rahim Biyar Tidak Hamil
Cara Menggugurkan Kandungan 087776558899
 
Hospital management system project report.pdf
Hospital management system project report.pdfHospital management system project report.pdf
Hospital management system project report.pdf
Kamal Acharya
 
Kuwait City MTP kit ((+919101817206)) Buy Abortion Pills Kuwait
Kuwait City MTP kit ((+919101817206)) Buy Abortion Pills KuwaitKuwait City MTP kit ((+919101817206)) Buy Abortion Pills Kuwait
Kuwait City MTP kit ((+919101817206)) Buy Abortion Pills Kuwait
jaanualu31
 
Call Girls in South Ex (delhi) call me [🔝9953056974🔝] escort service 24X7
Call Girls in South Ex (delhi) call me [🔝9953056974🔝] escort service 24X7Call Girls in South Ex (delhi) call me [🔝9953056974🔝] escort service 24X7
Call Girls in South Ex (delhi) call me [🔝9953056974🔝] escort service 24X7
9953056974 Low Rate Call Girls In Saket, Delhi NCR
 

Recently uploaded (20)

Unit 4_Part 1 CSE2001 Exception Handling and Function Template and Class Temp...
Unit 4_Part 1 CSE2001 Exception Handling and Function Template and Class Temp...Unit 4_Part 1 CSE2001 Exception Handling and Function Template and Class Temp...
Unit 4_Part 1 CSE2001 Exception Handling and Function Template and Class Temp...
 
Online food ordering system project report.pdf
Online food ordering system project report.pdfOnline food ordering system project report.pdf
Online food ordering system project report.pdf
 
Cara Menggugurkan Sperma Yang Masuk Rahim Biyar Tidak Hamil
Cara Menggugurkan Sperma Yang Masuk Rahim Biyar Tidak HamilCara Menggugurkan Sperma Yang Masuk Rahim Biyar Tidak Hamil
Cara Menggugurkan Sperma Yang Masuk Rahim Biyar Tidak Hamil
 
Hospital management system project report.pdf
Hospital management system project report.pdfHospital management system project report.pdf
Hospital management system project report.pdf
 
Thermal Engineering -unit - III & IV.ppt
Thermal Engineering -unit - III & IV.pptThermal Engineering -unit - III & IV.ppt
Thermal Engineering -unit - III & IV.ppt
 
AIRCANVAS[1].pdf mini project for btech students
AIRCANVAS[1].pdf mini project for btech studentsAIRCANVAS[1].pdf mini project for btech students
AIRCANVAS[1].pdf mini project for btech students
 
COST-EFFETIVE and Energy Efficient BUILDINGS ptx
COST-EFFETIVE  and Energy Efficient BUILDINGS ptxCOST-EFFETIVE  and Energy Efficient BUILDINGS ptx
COST-EFFETIVE and Energy Efficient BUILDINGS ptx
 
Computer Lecture 01.pptxIntroduction to Computers
Computer Lecture 01.pptxIntroduction to ComputersComputer Lecture 01.pptxIntroduction to Computers
Computer Lecture 01.pptxIntroduction to Computers
 
School management system project Report.pdf
School management system project Report.pdfSchool management system project Report.pdf
School management system project Report.pdf
 
Kuwait City MTP kit ((+919101817206)) Buy Abortion Pills Kuwait
Kuwait City MTP kit ((+919101817206)) Buy Abortion Pills KuwaitKuwait City MTP kit ((+919101817206)) Buy Abortion Pills Kuwait
Kuwait City MTP kit ((+919101817206)) Buy Abortion Pills Kuwait
 
Call Girls in South Ex (delhi) call me [🔝9953056974🔝] escort service 24X7
Call Girls in South Ex (delhi) call me [🔝9953056974🔝] escort service 24X7Call Girls in South Ex (delhi) call me [🔝9953056974🔝] escort service 24X7
Call Girls in South Ex (delhi) call me [🔝9953056974🔝] escort service 24X7
 
Work-Permit-Receiver-in-Saudi-Aramco.pptx
Work-Permit-Receiver-in-Saudi-Aramco.pptxWork-Permit-Receiver-in-Saudi-Aramco.pptx
Work-Permit-Receiver-in-Saudi-Aramco.pptx
 
Thermal Engineering Unit - I & II . ppt
Thermal Engineering  Unit - I & II . pptThermal Engineering  Unit - I & II . ppt
Thermal Engineering Unit - I & II . ppt
 
Generative AI or GenAI technology based PPT
Generative AI or GenAI technology based PPTGenerative AI or GenAI technology based PPT
Generative AI or GenAI technology based PPT
 
NO1 Top No1 Amil Baba In Azad Kashmir, Kashmir Black Magic Specialist Expert ...
NO1 Top No1 Amil Baba In Azad Kashmir, Kashmir Black Magic Specialist Expert ...NO1 Top No1 Amil Baba In Azad Kashmir, Kashmir Black Magic Specialist Expert ...
NO1 Top No1 Amil Baba In Azad Kashmir, Kashmir Black Magic Specialist Expert ...
 
Employee leave management system project.
Employee leave management system project.Employee leave management system project.
Employee leave management system project.
 
Introduction to Serverless with AWS Lambda
Introduction to Serverless with AWS LambdaIntroduction to Serverless with AWS Lambda
Introduction to Serverless with AWS Lambda
 
HAND TOOLS USED AT ELECTRONICS WORK PRESENTED BY KOUSTAV SARKAR
HAND TOOLS USED AT ELECTRONICS WORK PRESENTED BY KOUSTAV SARKARHAND TOOLS USED AT ELECTRONICS WORK PRESENTED BY KOUSTAV SARKAR
HAND TOOLS USED AT ELECTRONICS WORK PRESENTED BY KOUSTAV SARKAR
 
GEAR TRAIN- BASIC CONCEPTS AND WORKING PRINCIPLE
GEAR TRAIN- BASIC CONCEPTS AND WORKING PRINCIPLEGEAR TRAIN- BASIC CONCEPTS AND WORKING PRINCIPLE
GEAR TRAIN- BASIC CONCEPTS AND WORKING PRINCIPLE
 
Unleashing the Power of the SORA AI lastest leap
Unleashing the Power of the SORA AI lastest leapUnleashing the Power of the SORA AI lastest leap
Unleashing the Power of the SORA AI lastest leap
 

IRJET- Impact of Superconducting Fault Current Limiter on Passive Resonance Circuit Breaker (PRCB) in HVDC System

  • 1. International Research Journal of Engineering and Technology (IRJET) e-ISSN: 2395-0056 Volume: 06 Issue: 03 | Mar 2019 www.irjet.net p-ISSN: 2395-0072 © 2019, IRJET | Impact Factor value: 7.211 | ISO 9001:2008 Certified Journal | Page 892 Impact of Superconducting Fault Current Limiter on Passive Resonance Circuit Breaker (PRCB) in HVDC System Mr. A. A. Kalamkar1, Miss. K. L. Bari2, Prof .G. R. Lohote3 1PG Scholar, Dept of Operation Management, Shri Shivaji Marath Society’s Institute of Management & Research, Pune, Maharashtra, India 2PG Scholar, Dept of Electrical Engineering, SSBT’S College of Engineering & Technology, Jalgaon, Maharashtra, India 3Assistant Professor, Dept of Electrical Engineering, JSPM’s Bhivarabai Sawant Institute of Technology and Research, Pune, Maharashtra, India ----------------------------------------------------------------------------***-------------------------------------------------------------------------- Abstract:- For several decades HVDC technology was used primarily for point-to-point bulk power transmission. Although multi-terminal HVDC systems are very few in number, it is expected that multiple HVDC links may be interconnected into HVDC transmission grid. Since every meshed grid requires reliable protection solution, an HVDC circuit breaker must be developed and introduced. When sudden short circuit fault is happened on transmission line, it will cause sudden increase in current magnitude. Various electrical devices used for protection of such a transmission line against serious fault current. Circuit breakers, current limiting reactor are used to protect the system from fault current, superconducting fault current limiter is one of them. This paper focuses on the performance evaluation of Passive Resonance HVDC circuit breaker concepts. The performance evaluation study is carried out by means of MATLAB simulations. The obtained quantitative results describe capabilities and limitations of Passive Resonance circuit breaker concepts as well as the reaction of HVDC network on switching operations. Different converter protection measures and in particular application of fault current limiter were considered, too. In this paper comparative results of Passive Resonance circuit breaker without and with superconducting fault current limiter (SFCL) are observed. For simulation two cases of PRCB are considered, PRCB without using SFCL and PRCB with using SFCL. Keywords: HVDC circuit breaker, Fault protection methods, Network response, Simulation-based performance evaluation. Introduction: As we see most of the time fault current interruption is easily achieved by AC circuit breakers or by using fault current limiter. For AC circuit breakers it easily possible to limit that fault current level by natural zero current crossing but this facility is not available in DC circuit breakers. To achieve that zero current by DC circuit breakers a forced commutation should be used, this obtained by making some modifications. Several types of HVDC circuit breakers are available in market like Mechanical Circuit Breaker (MCB), Passive Resonance Circuit Breaker (PRCB), Inverse Current Injection Circuit Breaker (I-CB), and Hybrid Circuit Breaker. But in this paper we only were focusing on Passive Resonance Circuit Breaker (PRCB) to achieve artificial zero current crossing. As an alternative the combining effect of Superconducting Fault current Limiter and HVDC circuit breakers gives much reduction in fault current level, also improves the transmission line performance. SFCL is best solution for transmitting a bulky High Voltage power over a long distance. [1] Superconducting fault current limiter (SFCL) has capability to limit fault current level within first cycle and not only decrease the stress on HVDC circuit breaker but also improves the transmission line performance. Superconducting fault current limiter has three type’s Resistive type, Inductive type and Bridge type SFCL according to material used for construction. In this paper here we used resistive type SFCL with Passive resonance circuit breaker (PRCB). For simulation purpose a test bed model of PRCB with SFCL is used in MATLAB/Simulink [2] A) HVDC transmission line model : For analyzing the effect of superconducting fault current limiter on PRCB HVDC circuit breaker a test model of HVDC transmission line is consider. This model is designed in MATLAB/Simulink as shown in Fig.1. The system test bed model is designed with different components of different ratings. Initially three phase AC system is taken of 230 KV, the system voltage is stepped down to 110 kV by transformer. AC voltage then convert to DC by rectifier. At both ends of system converter
  • 2. International Research Journal of Engineering and Technology (IRJET) e-ISSN: 2395-0056 Volume: 06 Issue: 03 | Mar 2019 www.irjet.net p-ISSN: 2395-0072 © 2019, IRJET | Impact Factor value: 7.211 | ISO 9001:2008 Certified Journal | Page 893 stations are implemented. The required specifications of this system are transmission line length = 50 km, rated voltage 100 kV, Nominal current is of 1 kA, rated power 100 MW. Fig. 1. Two-level point-to-point HVDC test bed model In this system Passive Resonance circuit breaker (PRCB) is used in series with Resistive Superconducting Fault Current Limiter (SFCL). [3] B) Passive Resonance circuit breaker (PRCB): Fig. 2. Passive Resonance Circuit Breaker A passive resonance HVDC circuit breaker consists of a mechanical switch and a parallel coupled oscillating circuit composed of capacitor and inductor as shown in Figure 2. To dissipate the energy stress on the MCB, the secondary path with a series L-C circuit is added. When the fault occurred at 0.1 sec, MCB opens with 10 ms of delay considering opening delay. As soon as the mechanical switch starts to open its contacts, an electric arc arises between them, and resonance occurs in the loop formed by mechanical switch, inductor and capacitor. This phenomenon is possible owing to the electric arc property of displaying negative differential resistance. Resonance developing within the HVDC circuit breaker entails increase in the magnitude of the current oscillating in the L-C circuit. The DC current begins to commutate and resonate in the secondary path after the arc impedance exceeds the L-C impedance. When a DC current of the primary path meets zero crossing, this current being superimposed on the breaking current provides current zero and enables the mechanical switch to quench the arc. An additional parallel surge arrester (SA) circuit is supplemented to prevent voltage stress across the PRCB during arc extinction. This current being superimposed on the breaking current provides current zero and enables the mechanical switch to quench the arc. [4]
  • 3. International Research Journal of Engineering and Technology (IRJET) e-ISSN: 2395-0056 Volume: 06 Issue: 03 | Mar 2019 www.irjet.net p-ISSN: 2395-0072 © 2019, IRJET | Impact Factor value: 7.211 | ISO 9001:2008 Certified Journal | Page 894 C) Simulation results of PRCB without SFCL: Following fig. 3 shows main current characteristics of PRCB without applying SFCL and its value is 24 kA. The fault current interruption time of PRCB in this case is approximate 55 ms. Fig.3. Main current of PRCB without SFCL Fig. 4 shows secondary path current of PRCB without SFCL and its value is of 11 kA. Fig. 4 Secondary path current of PRCB without SFCL
  • 4. International Research Journal of Engineering and Technology (IRJET) e-ISSN: 2395-0056 Volume: 06 Issue: 03 | Mar 2019 www.irjet.net p-ISSN: 2395-0072 © 2019, IRJET | Impact Factor value: 7.211 | ISO 9001:2008 Certified Journal | Page 895 Absorber path current of PRCB without SFCL is 17.5 kA as shown below. This is current thorough surge arrester. This SA is used for protection of whole system from high voltage. Fig.5 Absorber path current of PRCB without SFCL Now our intension is to find PRCB characteristics when SFCL is applied in this system. Here we observed much difference in value of currents. Given fig.6 shows main current of PRCB. The main current value is about 7.2 kA. Fault current interruption time is 25 ms and achieves nearly 62.1 % reduction in fault current level. Fig. 6 Main current of PRCB with SFCL
  • 5. International Research Journal of Engineering and Technology (IRJET) e-ISSN: 2395-0056 Volume: 06 Issue: 03 | Mar 2019 www.irjet.net p-ISSN: 2395-0072 © 2019, IRJET | Impact Factor value: 7.211 | ISO 9001:2008 Certified Journal | Page 896 The secondary path current is the current through inductor and capacitor series branch. In this with SFCL case the value of secondary path current is 4 kA. Fig. 7 Secondary path current of PRCB with SFCL Given fig. 8 shows absorber path current of PRCB when SFCL is used in HVDC transmission system. The value of these current is 6.9 approximate 7 kA. Fig. 8 Absorber path current of PRCB with SFCL
  • 6. International Research Journal of Engineering and Technology (IRJET) e-ISSN: 2395-0056 Volume: 06 Issue: 03 | Mar 2019 www.irjet.net p-ISSN: 2395-0072 © 2019, IRJET | Impact Factor value: 7.211 | ISO 9001:2008 Certified Journal | Page 897 Where the main current is current through main path, secondary path means current through inductor and capacitor components while absorber current is the current through surge srrester path [5] Table I: Current values of PRCB without and with SFCL Parameters PRCB without SFCL PRCB with SFCL Main current 24 kA 7.2 kA Secondary current 11 kA 4 kA Absorber current 17.5 kA 6.9 kA Conclusion: Every time it is not possible to limit maximum value fault current by using circuit breaker only. For that purpose in addition to HVDC circuit breaker a superconducting fault current limiter is applied and results are observed in this paper. The noticeable improvements are observed in case of PRCB with using SFCL, without SFCL the maximum fault current interruption was achieved, also the fault current values are more. When SFCL was applied, The L/R time constant of secondary path was decreased, and therefore fast interruption with less oscillations are observed. References: 1) Matthias K. Bucher, M. Frank, “Fault Current Interruption in Multi terminal HVDC Networks” IEEE Transaction on Power Delivery, vol. X, 2015. 2) G Swetha, R. Sathish Kumar & B. Venkata Prasanth “Performance of Superconducting Fault Current Limiter in Power System” International Journal of Research vol. 03 Issue 10 June 2016. 3) Jong-Geon Lee, Umer Amir Khan, Ho-Yun Lee, and Bang-Wook Lee, “Impact of SFCL on the Four Types of HVDC Circuit Breakers by Simulation” IEEE Transactions on Applied Superconductivity, Vol. 26, No. 4, June 2016. 4) Mudar Abedrabbo, Willem Leterme and Dirk Van Hertem “Analysis and Enhanced Topologies of Active-Resonance DC Circuit Breaker”. 5) Gen Li, Jun Liang, Carlos E Ugalde- Loo, “Impact of DC Circuit Breakers on AC/DC System Stability Subject to DC Faults” 2016 International High Voltage Direct Current Conference (HVDC 2016). 6) MD. Afser khan, Mr. V. Ganesh Kumar, “Fault Current Limiting Technologies of HVDC Circuit Breakers With Impact Of SFCL” International Journal of Technology and Engineering Science [IJTES] vol. 5, Oct. 2017.