Voltage drop and power–loss calculations:
Derivation for voltage drop and power loss in lines
Uniformly distributed loads and non-uniformly distributed loads
Numerical problems
Three phase balanced primary lines
Introduction to IEEE STANDARDS and its different types.pptx
EDS Unit 3 (Part 2).pptx
1. LENDI INSTITUTE OF ENGINEERING AND TECHNOLOGY
Jonnada, Andhra Pradesh- 535005
UNIT –3
System Analysis
Presented by
Dr. Rohit Babu, Associate Professor
Department of Electrical and Electronics Engineering
2. SYLLABUS
Department of Electrical and Electronics Engineering
Voltage drop and power–loss calculations:
Derivation for voltage drop and power loss in lines
Uniformly distributed loads and non-uniformly distributed loads
Numerical problems
Three phase balanced primary lines
3. Three phase balanced primary lines
Department of Electrical and Electronics Engineering
Classification of lines
1. three-phase three-wire,
2. three-phase four-wire,
3. single phase with line-to-line voltage, ungrounded,
4. single phase with line-to-neutral voltage, grounded, or
5. two-phase plus neutral, open wye.
Usually there are many laterals on a primary feeder that are not necessarily in three phase, for example,
single phase, which causes the voltage drop and power loss due to load current not only in the phase
conductor but also in the return path.
4. Single-Phase Two-Wire Laterals with Ungrounded Neutral
Department of Electrical and Electronics Engineering
Assume that an overloaded single-phase lateral is to be changed to an equivalent three-phase three
wire and balanced lateral, holding the load constant.
Since the power input to the lateral is the same as before,
1 3
S S
(1)
Eqn. (1) can be rewritten as
1 3
( 3 ) 3
s s
V I V I
(2)
where Vs is the line-to-neutral voltage
Therefore, from Eqn. (2),
1 3
3
I I
(3)
5. Single-Phase Two-Wire Laterals with Ungrounded Neutral
Department of Electrical and Electronics Engineering
Eqn. (3) that the current in the single-phase lateral is 1.73 times larger than the one in the equivalent
three-phase lateral.
The voltage drop in the three-phase lateral can be expressed as
3 3 ( cos sin )
D
V I R X
(4)
and in the single-phase lateral as
1 1 ( cos sin )
D R X
V I K R K X
(5)
where
KR and KX are conversion constants of R and X and are used to convert them from their three phase
values to the equivalent single-phase values
KR = 2.0
KX = 2.0 when underground (UG) cable is used
KX ≅ 2.0 when overhead line is used, with approximately a ±10% accuracy
6. Single-Phase Two-Wire Laterals with Ungrounded Neutral
Department of Electrical and Electronics Engineering
Therefore, Eqn. (5) can be rewritten as
1 1 (2 cos 2 sin )
D
V I R X
(6)
or substituting Eqn. (3) into Eqn. (6),