SlideShare a Scribd company logo
1 of 184
Download to read offline
Mount Zion College of Engineering and
Technology
BE8254 Basics of Electrical and
Instrumentation Engineering
P. Maria Sheeba
AP/ECE
OOBJECTIVE
 To analyze the operation of Three phase electrical circuits
and power measurement.
 To deal with the working principles of Electrical machines.
 To understand the principle of various measuring
instruments.
MZCET- ECE
OUTCOMES
 Concept of three phase power circuits and measurement.
 Comprehend the concepts in electrical generators, motors
and transformers.
 Choose appropriate measuring instruments for given
application.
• 1.1 Three phase power supply
• 1.2 Inter Connection of windings
• 1.3 Balanced and Unbalanced loads
• 1.4 Power Equation
• 1.5 Star Delta Conversion
• 1.6 Three phase power measurement
• 1.7 Transmission and Distribution of electrical energy
• 1.8 Over head Vs Underground system
• 1.9 Protection of power system
• 1.10 Types of Tariff
• 1.11 Power factor improvement
MZCET-ECE
Unit-I AC Circuits and Power Systems
1.1 Three phase power supply
IMPORTANCE OF THREE PHASE SYSTEM
• Uniform power transmission and less vibration of
three phase machines.
– The instantaneous power in a 3φ system can be
constant (not pulsating).
– High power motors prefer a steady torque especially
one created by a rotating magnetic field.
IMPORTANCE OF THREE PHASE SYSTEM
• Three phase system is more economical than the
single phase.
– The amount of wire required for a three phase system
is less than required for an equivalent single phase
system.
– Conductor: Copper, Aluminum, etc
Differences
Single Phase Power Supply
 230 V, 50 Hz
 Not sufficient for producing large amount
of power.
 With single-phase current, the voltage
rises to a peak in one direction of flow,
subsides to zero, reverses, rises to a peak
in the opposite direction, subsides to zero,
and so on.
 Single-phase current requires the use of
one transformer.
Three Phase Power
Supply
 440 V, 50 Hz
 Sufficient for producing large amount of
power.
 There are three separate and distinct
single-phase currents, which are combined
so they can be transmitted over three or
four wires and these rise to a peak in one
direction, subside, reverse, and so on;
however they do not peak at the same
time.
 Three-phase current requires two or three
transformers.
Three Phase CirCuiTs
9
1.1.1 Introduction:
• The generator , motor , transformer or rectifier have only one winding is
called a single phase system
• If the current or voltage follows a phase difference 900
in a two windings,
called two phase systems
• If the phase difference is 1200
between voltages or currents in a three winding,
called as Three phase systems
• In poly-phase systems , there are more than three windings
Advantages of three phase system:
• More efficient than single phase system
• Cost is less
• Size is small . Compared to single phase system
10
Advantages of Three Phase Circuits
• The amount of conductor material is required less for transmitting same power,
over the same distance , under same power loss
• Three phase motors produce uniform torque , where as torque produced by
single motor is pulsating
• Three phase generators not produce the harmonics when they are connected in
parallel
• Three phase motors are self starting whereas single phase motors are not self
starting
MZCET 11
THREE PHASE GENERATION
FARADAYS LAW
• Three things must be present in order to
produce electrical current:
a) Magnetic field
b) Conductor
c) Relative motion
• Conductor cuts lines of magnetic flux, a voltage is
induced in the conductor
• Direction and Speed are important
GENERATING A SINGLE PHASE
Motion is parallel to the flux.
No voltage is induced.
N
S
x
N
S
Motion is 45° to flux.
Induced voltage is 0.707 of maximum.
GENERATING A SINGLE PHASE
GENERATING A SINGLE PHASE
x
N
S
Motion is perpendicular to flux.
Induced voltage is maximum.
GENERATING A SINGLE PHASE
Motion is 45° to flux.
x
N
S
Induced voltage is 0.707 of maximum.
GENERATING A SINGLE PHASE
N
S
Motion is parallel to flux.
No voltage is induced.
GENERATING A SINGLE PHASE
x
N
S
Notice current in the
conductor has reversed.
Induced voltage is
0.707 of maximum.
Motion is 45° to flux.
GENERATING A SINGLE PHASE
N
S
x
Motion is perpendicular to flux.
Induced voltage is maximum.
GENERATING A SINGLE PHASE
N
S
x
Motion is 45° to flux.
Induced voltage is 0.707 of maximum.
GENERATING A SINGLE PHASE
Motion is parallel to flux.
N
S
No voltage is induced.
Ready to produce another cycle.
THREE PHASE GENERATOR
GENERATOR WORK
• The generator consists of a rotating magnet
(rotor) surrounded by a stationary winding
(stator).
• Three separate windings or coils with terminals a-
a’, b-b’, and c-c’ are physically placed 120° apart
around the stator.
• As the rotor rotates, its magnetic field cuts the
flux from the three coils and induces voltages in
the coils.
• The induced voltage have equal magnitude but
out of phase by 120°.
GENERATION OF THREE-PHASE AC
N
x
x
S
THREE-PHASE WAVEFORM
Phase 2 lags phase 1 by 120°. Phase 2 leads phase 3 by 120°.
Phase 3 lags phase 1 by 240°. Phase 1 leads phase 3 by 240°.
Phase 1 Phase 2 Phase 3
120° 120° 120°
240°
120° 120° 120°
240°
Phase 1 Phase 2 Phase 3
GENERATION OF 3φ VOLTAGES
Phase 1 is ready to go positive.
Phase 2 is going more negative.
Phase 3 is going less positive.
N
x
x
S
1.1.2 Generation of Three Phase Voltages
MZCET 29
BALANCED 3φ VOLTAGES
• Balanced three phase voltages:
– same magnitude (VM)
– 120° phase shift
( )
( )
( ) ( )
°
+
=
°
−
=
°
−
=
=
120
cos
240
cos
)
(
120
cos
)
(
cos
)
(
t
V
t
V
t
v
t
V
t
v
t
V
t
v
M
M
cn
M
bn
M
an
ω
ω
ω
ω
• Vectorially r.m.s values of voltages
induced in three windings are represented
in the diagram
• ER = E ∟0o
v,
• EY = E ∟-120o
v
• EB= E ∟+120o
v MZCET 31
 Three voltages are not in phase, since there is a phase difference
of
 The order of voltage waveform sequences in a polyphase system
is called phase rotation or phase sequence.
 This sequence of phase shifts has a definite order. For clockwise
rotation, the order is 1-2-3 (i.e) RYB (winding 1 peaks first, them
winding 2, then winding 3), which is known as a positive phase
sequence.
MZCET
1.1.3 PHASE SEQUENCE

120
PHASE SEQUENCE
 For anti-clockwise rotation, the
order is 3-2-1 (i.e) RBY (winding 3
peaks first, them winding 2, then
winding 1), which is known as a
negative phase sequence.
 If we’re using a polyphase voltage
source to power resistive loads,
phase rotation will make no
difference at all.
 Whether 1-2-3 or 3-2-1, the
voltage and current magnitudes
will all be the same.
PHASE SEQUENCE
( )
( )
°
+
=
°
−
=
=
120
cos
)
(
120
cos
)
(
cos
)
(
t
V
t
v
t
V
t
v
t
V
t
v
M
cn
M
bn
M
an
ω
ω
ω
°
+
∠
=
°
−
∠
=
°
∠
=
120
120
0
M
cn
M
bn
M
an
V
V
V
V
V
V
POSITIVE
SEQUENCE
NEGATIVE
SEQUENCE
°
−
∠
=
°
+
∠
=
°
∠
=
120
120
0
M
cn
M
bn
M
an
V
V
V
V
V
V
1.2 INTERCONNECTION OF
WINDINGS
36
THREE PHASE QUANTITIES
QUANTITY SYMBOL
Phase current Iφ
Line current IL
Phase voltage Vφ
Line voltage VL
1.2.1 PHASE VOLTAGES and LINE
VOLTAGES
• Phase voltage is measured between the neutral
and any line: line to neutral voltage
• Line voltage is measured between any two of the
three lines: line to line voltage.
1.2.2 PHASE CURRENTS and LINE
CURRENTS
• Line current (IL) is the current in each line of the
source or load.
• Phase current (Iφ) is the current in each phase
of the source or load.
Interconnection of windings
Three phase connections:
• There are two types of three phase connections
• Star connection (Y)
• Delta connection (Δ)
1.2.3 Star connection (Y):
• In this method of inter-connection, the similar ends, say, “start”
ends of three coils (it could be “finishing” ends also) are joined
together at point ‘N’
40
• The point ‘N’ is known as star point or
neutral point
• If this three-phase voltage is applied across
a balanced symmetrical load, the neutral wire
will be carrying three currents which are exactly
equal in magnitude but are 120o
out of phase
with each other. Hence, their vector sum is zero
IR + IY + IB = 0
Voltages and Currents in Y-Connection:
• The voltage induced in each winding is called the
‘phase’ voltage and current in each winding is
known as ‘phase’ current.
MZCET 41
• The vector diagram for phase voltages and currents in a star connection shows
that
ER = EY = EB = Eph (phase e.m.f)
• Line voltage VRY between line 1 and line 2 is the vector difference of ER and EY.
• Line voltage VYB between line 2 and line 3 is the vector difference of EY and EB.
• Line voltage VBR between line 3 and line 1 is the vector difference of EB and ER.
MZCET 42
• The p.d. between lines 1 and 2 is
VRY = ER - EY (Vector difference)
• VRY is found by compounding ER and EY
reversed and its value is given by the
diagonal of the paral1elogram in figure.
• The angle between ER and EY reversed is 60°.
If ER = EY = EB = Ephthe Phase e.m.f then,
•
MZCET 43
C
O
ph
RY
o
E
V
2
30
cos =
o
ph
RY E
V 30
cos
2 ×
×
=
ph
ph E
E 3
2
3
2 =
×
×
=
• Hence, in star connection
It will be noted from figure that
• (a) Line voltages are 120° apart.
• (b) Line voltages are 30° ahead of their respective phase voltages.
• (c) The angle between the line currents and the corresponding line voltages is (30 + )
ɸ
with current lagging.
44
ph
B
Y
YB
E
Difference
Vector
E
E
V
similarly
3
)
(
=
−
=
ph
R
B
BR
E
Difference
Vector
E
E
V
and
3
)
(
=
−
=
L
BR
YB
RY
V
voltage
line
V
V
V
,
=
=
=
ph
L E
V 3
=
Line Currents and Phase Currents:
• Current in line 1 = IR
• Current in line 2 = IY
• Current in line 3 = IB
Since IR = IY = IB = say,
Iph - the phase current
Line current IL = Iph
Power:
• The total power in the circuit is the sum of the three phase powers. Hence
• Total Power =3 x phase power=
•
45
1.2.4 Delta (Δ) or Mesh Connection:
• Phase sequence is R, Y, B
• R leads Y by 120° and Y leads B by 120°.
• The voltage between lines 1 and 2 as VRY
• The voltage between lines 2 and 3 as VYB
VRY leads VYB by 120
VYB leads VBR by 120°.
• VRY =VYB = VBR = line voltage VL
• Then, it VL = Vph
MZCET 46
MZCET 47
Line Currents and Phase Currents:
• Current in line 1 is I1 = IR – IB
• Current in line 2 is I2= IY – IR
• Current in line 3 is I3= IB - IY
• Current in line 1 is found by
compounding IR with IB reversed
and its value is given by the diagonal
of the parallelogram
• The angle between IR and IB reversed (-IB) is 60°.
• If IB = IR = IY = Iph phase current, then current in line 1 is
48
Contd..
Since all line currents are equal in magnitude i.e., I1= I2 = I3= IL
From Vector diagram, it should be noted that
• (a) Line currents are 120o
apart.
• (b) Line currents are 30o
behind the respective phase currents.
• (c) The angle between the line current and the corresponding line voltage is 49
Power:
MZCET 50
φ
cos
3 ph
ph I
E
P ×
=
L
ph V
E
but =
3
L
ph
I
I =
φ
cos
3
3 ×
×
×
= L
L
I
V
P
φ
cos
3 L
L I
V
P =
1.3 Balanced and unbalanced loads
51
1.3.1 Balanced three phase supply:
• A three phase supply is said to be balanced, when all the
three voltages have the same magnitude but differ in
phase by 120° with respect to one another.
• The three phase supply is said to be unbalanced, even if
one of the above conditions is not satisfied.
MZCET 52
Balanced Supply
MZCET 53
1.3.2 Balanced Load:
• A three phase load is said to be balanced, when the impedances
of all the three phases are exactly the same. Even if one of them
is different from the other, then the three phase load is said to be
unbalanced
• In a three phase balanced load, whether star connected or delta connected, the
magnitudes of the phase currents are the same but differ in phase by 120o
with
respected to one another
1.3.3 Unbalanced Load
• But in an unbalanced load, when a three phase balanced supply is given, the
magnitudes and phases of all the three phase currents will be different.
MZCET 54
1.4 Power Equation
55
1.4 Power Equation
1.4.1 Star Connection
The total power in the circuit is the sum of the three phase powers.
Hence ,
Total Power =3 x phase power=
56
1.4.2 Power for delta connection
MZCET 57
φ
cos
3 ph
ph I
E
P ×
=
L
ph V
E
but =
3
L
ph
I
I =
φ
cos
3
3 ×
×
×
= L
L
I
V
P
φ
cos
3 L
L I
V
P =
1.5 Star Delta Conversion
58
Resistive Circuits (Basics)
 Resistors in parallel:
 Resistors in series:
R1
R2
R3
Current Division in Parallel Circuits
R
1
R
2
V
I I 2
I 1
Voltage Division in Series Circuits
R 1
R 2
V
+ V 1 -
- V 2 +
I
1.5.1 Star -> Delta Conversion
A
B
C
Rab
Rbc
Rca
B
C
Ra
Rb
Rc
A
Star Connection Delta Connection
Star- Delta conversion
Advantages
1. The primary side is star connected. Hence fewer number of
turns are required. This makes the connection economical
2. The neutral available on the primary can be earthed to avoid
distortion.
3. Large unbalanced loads can be handled satisfactory.
63
Star- Delta conversion
• Disadvantages
• The secondary voltage is not in phase with the primary. (30 ⁰
phase difference )
• Hence it is not possible to operate this connection in parallel
with star-star or delta-delta connected transformer.
64
Wye(star) to Delta Transformation:
Consider the following:
•
•
• • • •
a
b
c
a
b
c
R a
R b
R c
R 1 R 2
R 3
( a ) w y e c o n f i g u r a t i o n ( b ) d e l t a c o n f i g u r a t i o n
a
a
c
c
b
b
a
c
a
c
c
b
b
a
b
a
c
c
b
b
a
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
+
+
=
+
+
=
+
+
=
3
2
1
3
2
1
3
1
3
2
1
3
2
3
2
1
2
1
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
c
b
a
+
+
=
+
+
=
+
+
=
Using the following circuit. Find Req.
9 Ω
1 0 Ω 5 Ω
8 Ω 4 Ω
V
+
_
R e q 1 0 Ω
I
a
b
c
Convert the delta around a – b – c to a wye.
Continued….
2 Ω
2 Ω
4 Ω
4 Ω
8 Ω
9 Ω
R e q
It is easy to see that Req = 15 Ω
1.5.2 Delta-star Transformation
B
C
Ra
Rb
Rc
A
A
B
C
Rab
Rbc
Rca
 Delta to Star Transformation:
Delta - Star Transformation
Features
 secondary Phase voltage is 1/√3 times of line voltage
 neutral in secondary can be grounded for 3 phase 4 wire system
 Neutral shifting and 3rd
harmonics are there
 Phase shift of 30⁰ between secondary and primary currents and
voltages
69
1.6 THREE PHASE POWER MEASUREMENT
WHAT IS THREE-PHASE power?
 Three-phase power is a common method of alternating-
current electric
power generation, transmission, and distribution.
 It is a type of polyphase system and is the most common
method used by electric grids worldwide to transfer power.
 A polyphase system is a means
of distributing alternating-current electrical power.
 An electrical grid is an interconnected network for
delivering electricity from suppliers to consumers.
1.6.1 Measure of power in Three Phase Circuits:
• Wattmeter is the instrument which
is used to measure power in an electrical circuit.
• It consists of (i) a current coil ML’
through which the line current flows
• (ii) a potential coil PV, which is connected
across the circuit.
• The full voltage is applied across the potential coil and it carries a very small
current proportional to the applied voltage.
• Three single phase watt-meters may be connected in each phase
• The algebraic sum of their readings gives the total power consumed by the three
phase circuit.
• It can be proved that only two watt-meters are sufficient to measure power in a
three phase circuit.
MZCET 73
 Various methods are used measurement of three
phase power in three phase circuits on the basis of
number of wattmeter used.
 We have three methods:-
1) Three wattmeter method
2) Two wattmeter method
3) Single wattmeter method
1.6.2 MEASUREMENT OF THREE
PHASE POWER BY THREE
WATTMETER METHOD
 Three Wattmeter method is used to measure
power in a 3 phase, 4 wire system.
 However, this method can also be used in a 3
phase, 3 wire delta connected load, where
power consumed by each load is required to
be determined separately.
 The Three-wattmeter method can be used for
star and delta connected unbalnced loads.
• The connections for Star/Delta
connected loads for measuring
power by Three wattmeter
method is shown below:-
 The pressure coil of all
• the Three wattmeter namely W1,
W2and W3are connected to a
• common terminal known as the
neutral point. The product of the
phase current and line voltage
represents as phase power and is
recorded by individual
wattmeter.
77
 The total power in a Three wattmeter method of
power measurement is given by the algebraic sum
of the readings of Three wattmeter. i.e.
 Where, W1 = V1I1 W2 = V2I2 W3 = V3I3
 Except for 3 phase, 4 wire unbalanced load, 3
phase power can be measured by using only Two
Wattmeter Method.
1.6.3 MEASUREMENT OF THREE
PHASE POWER BY TWO
WATTMETER METHOD
 Two Wattmeter Method can be used to measure
the power in a 3 phase, 3 wire star or delta
connected balanced or unbalanced load.
 In Two wattmeter method the current coils of the
wattmeter are connected with any two lines, say R
and Y and the potential coil of each wattmeter is
joined across the same line, the third line i.e. B.
 The two wattmeter method is used for the power
measurement in the 3-phase system, irrespective of
whether the load is balanced or unbalanced.
MEASUREMENT OF POWER
BY TWO WATTMETER
METHOD IN STAR
CONNECTION
Let W1 and W2 Be the two
wattmeter.
Let andthe
phase voltages across the
three loads
be the phase currents
respectively.
 The instantaneous current through the current coil
of Wattmeter, W1 is given by the equation shown
below.
 Instantaneous potential difference across the
potential coil of Wattmeter, W1 is given as
 Instantaneous power measured by the Wattmeter,
W1 is
 The instantaneous current through the current coil
of Wattmeter, W2 is given by the equation
 Instantaneous potential difference across the
potential coil of Wattmeter, W2 is given as
 Instantaneous power measured by the Wattmeter,
W2 is
 Therefore, the Total Power Measured by the Two
Wattmeter W1 and W2 will be obtained by adding the
equation (1) and (2).
 Here P is the total power absorbed in the three loads at
any instant.
MEASUREMENT OF POWER BY
TWO WATTMETER METHOD IN
DELTA CONNECTION
There are similar notations for delta also.
 The instantaneous current through the coil of the
Wattmeter, W1 is given by the equation
 Instantaneous Power measured by the Wattmeter,
W1 will be
 Therefore, the instantaneous power measured by
the Wattmeter, W1 will be given as
 The instantaneous current through the current coil
of the Wattmeter, W2 is given as
 The instantaneous potential difference across the
potential coil of Wattmeter, W2 is
 Therefore, the instantaneous power measured by
Wattmeter, W2 will be
 Hence, to obtain the total power measured by the Two
Wattmeter the two equations, i.e. equation (3) and (4)
has to be added.
 Here P is the total power absorbed in the three loads at
any instant.
 The power measured by the Two Wattmeter at any
instant is the instantaneous power absorbed by the
three loads connected in three phases.
 In fact, this power is the average power drawn by the
load since the Wattmeter reads the average power
because of the inertia of their moving system.
1.6.4 MEASUREMENT OF POWER BY SINGLE
PHASE WATTMETER METHOD
 Power is measured in the electric
circuit using a wattmeter.
 A single phase wattmeter
consists of two coils; namely the
current coil and the pressure coil.
 The Current coil is connected in
series with the line and thus
carries the line current.
 The Pressure coil is connected in
parallel with the line.
 The Wattmeter gives the power
per phase.
25
• The wattmeter gives the value of power per phase.
• Therefore, Total power = 3 X Power per phase
= 3 X wattmeter reading
•The one wattmeter method is used for power
measurement in the 3-phase star connected balanced
load.
1.7 Transmission and Distribution of
Electrical Energy
95
9/20/2015
1
BY 01,02,03,04,05,06,12604
2 9/20/2015
1.7.1 Introduction
01,02,03,04,05,06,12604
3
9/20/2015
4
1.7.2 Structure of Electrical Power System
9/20/2015
1.7.3 Distribution System
“The part of power system which distributes
electrical power for local use is known as
DISTRIBUTION SYSTEM.”
This system is the electrical system between the
substation fed by the transmission system and
consumer meter.
Distribution line generally consist of
Feeders
Distributers
Service mains
9/20/2015
FEEDERS DISTRIBUTORS SERVICE MAINS
Distribution
Feeder
 A Feeder is conductor which connects the substation to the
area where power is to be distributed
 Feeder are used to feed the electrical power from the
generating station to the substation
 No tapings are taken from the feeder
 So the current in it remains the same throughout
 Main consideration in the design of feeder is
the Current carrying capacity.
9/20/2015
8
Distributer
 A distributer is a conductor from which tapings
are taken from pole mounted transformer to the
consumer
 The current through a distributer is not constant
because tapings are taken at various places along
its length
 Voltage drop is main consideration
 Limit of variation is 6% of rated at
consumer
9/20/2015
9
Service mains
 A service mains is a generally a small cable which
connects the distributer to the consumer ‘s meter.
 The connecting links between the distributor and
the consumer terminals.
9/20/2015
10
11
9/20/2015
12
9/20/2015
13
1.7.4 classification of dc
distribution
 Distribution system is a part of power system,
existing between distribution substations and
consumers.
 It is further classified on the basis of voltage
 Primary distribution system- 11 KV or 6.6 KV or 3.3 KV
 Secondary distribution system- 415 V or 230 V
9/20/2015
16
Classification Of Distribution
System:
It can be classified under different considerations as;
1. Type Of Current:
a)AC Distribution System
b)DC Distribution System
2. Type Of Construction:
a)Overhead System
b)Underground System
9/20/2015
17
3. Type Of Service:
a)General Lighting & Power
b)Industrial Power
c)Railway
d)Streetlight etc
c) Interconnected Distribution System
4. Number Of Wires:
a)Two Wire
b)Three Wire
c)Four Wire
5. Scheme Of Connection:
a)Radial Distribution System
b)Ring or Loop Distribution System
9/20/2015
18
Ac distribution
 A.c. distribution system is the electrical system
between the step-down substation fed by the
transmission system and the consumers’ meters. The
a.c. distribution
system is classified into
 ( i) primary distribution system and
 ( ii) secondary distribution system.
9/20/2015
19
1.7.5 Primary distribution system
 voltages somewhat higher than general utilisation and
handles large blocks of electrical energy than the average
low-voltage consumer uses.
 Commonly used primary distribution voltage 11KV, 6.6
KV,3.3 KV.
 Electric power from the generating station is transmitted at
high voltage to the substation located in or near the city.
 At this substation, voltage is stepped down to 11 kV with the
help of step-down transformer.
 Power is supplied to various substations for distribution or
to big consumers at this voltage.
 This forms the high voltage distribution or primary
distribution.
9/20/2015
20
9/20/201
21
1.7.6 Secondary distribution system
 It is that part of a.c. distribution system which includes
the range of voltages at which the ultimate consumer
utilizes the electrical energy delivered to him.
 The secondary distribution employs 400/230 V, 3-
phase, 4-wire system.
22
23
D.C. Distribution
 D.c. supply is required for the operation of variable speed
machinery ( i.e., d.c. motors), for electro-chemical work and
for congested areas where storage battery reserves are
necessary.
 For this purpose, a.c. power is converted into
d.c. power at the substation by using converting machinery
e.g., mercury arc rectifiers, and motor-generator sets.
24
Type of DC distributor
 The dc supply from the substation may be
obtained in form of
 ( i) 2-wire or
 ( ii) 3-wire for distribution.
25
2 wire 3 wire
9/20/2015
26
27
 Two outer and a middle or neutral wire is earthed at
the s/s.
 Voltage between the outer is twice the voltage
between either outer and neutral wire.
 Advantage – available two voltage at the consumer
terminal.
 Loads requiring high voltage connected across the
outers.
 Lamps and heating circuits requiring less voltage are
connected between either outer and neutral.
Method of obtaining 3 wire D.c
system
 Two generator method.
 3-wire D.c. generator.
 Balancer set
9/20/2015
28
Two generator method
29
Two generator method
 D.c generator G1 and G2 are connected in series and
the neutral is obtained from the common point btwn
generator
 G1 supplies a I1, G2 supplies a I2
 Difference of load current on both side (I1-I2) flow
through the neutral wire.
 Disad.:two separate generator are required.
9/20/2015
30
3-wire D.c. generator.
9/20/2015
31
3-wire D.c. generator.
 Consist of a standard 2 wire machine with one
or two coils of high reactance and low
resistance that connected to opposite points of
the armature winding.
 Neutral wire is obtained from common
point.
9/20/2015
32
Connection schemes of
distribution system
 Radial system
 Ring main system
 Interconnected system
9/20/2015
33
Radial Distribution System:
9/20/2015
 separate feeders radiate from a single substation and feed the
distributors at one end only.
 Only one path is connected between each customer and
substation.
 Electrical power flows along a single path.
 If interrupted, results in complete loss of power to the customer.
.
34
• Advantages:
 Low cost .
 Simple planning.
• Disadvantages :
 The radial system is employed only when power is generated at low
voltage and the substation is located at the centre of the load.
 Distributor nearer to feeding end is heavily loaded.
 Consumers at far end of feeder would be subjected to serious
• voltage fluctuations
128
9/20/215
35
9/20/2015
36
Ring or Loop Distribution System:
 It consists of two or more paths between
• power sources and the customer.
 The loop circuit starts from the substation bus-bars, makes a loop
through the area to be served, and returns to the substation
• Advantages:
 Less conductor material is required.
 Less voltage fluctuations.
 More reliable.
• Disadvantages:
 It is difficult to design as compared to the
design of radial system.
37 9/20/2015
38
Interconnected Distribution System:
 It is supplied by a number of feeders.
 Radial primary feeders can be tapped off from the
interconnecting tie feeders.
 They can also serve directly from the substation.
Advantages:
 Increases the reliability of supply
 Losses are less
 Quality of service is improved.
Disadvantages:
 Its initial cost is more.
 Difficult in planning, design and operation.
9/20/2015
39
9/20/2015
40
1.7.7 D.C. Distribution
 D.c. supply is required for the operation of variable
speed machinery ( i.e., d.c. motors),
 for electro-chemical work and for congested areas
where storage battery reserves are necessary.
 For this purpose, a.c. power is converted into d.c.
power at the substation by using converting machinery
e.g., mercury arc rectifiers, rotary converters and motor-
generator sets. The d.c. supply from the substation may
be obtained in the form of
9/20/2015
43
DC Distribution:
 Voltage drop along distributor is considered as a
main factorwhile designing a distributor.
 It depends upon the nature of load and also on
feeding, whether it is fed at one or both ends.
According to loading, a distributor can be classified
as:
i. Fed at one end.
ii. Fed at both ends. a). With equal voltages.
b). With unequal voltages.
iii. Fed at centre.
Ring mains.
9/20/2015
DC Distribution Feed at one end
9/20/2015
 a) The current in the various sections of the
distributor away from feeding point goes on
decreasing. Thus current in section AC is more than
the current in section CD and current in section CD is
more than the current in section DE.
 (b) The voltage across the loads away from the
feeding point goes on decreasing. Thus in Fig. 13.1,
the minimum voltage occurs at the load point E.
 (c) In case a fault occurs on any section of the
distributor, the whole distributor will have to be
disconnected from the supply mains. Therefore,
continuity of supply is interrupted
Distributor fed at center
47
 In this type of feeding the distributor is connected to the supply mains at
both ends and loads are tapped off at different points along the length of the
distributor.
The voltage at the feeding points may or may not be equal. distributor A B
fed at the ends A and B and loads of I1, I2 and I3 tapped off at points C
respectively.
 Here, the load voltage goes on decreasing as we move away from one
feeding point say A , reaches minimum value and then again starts rising
and reaches maximum value when we reach the other feeding point B.
 The minimum voltage occurs at some load point and is never fixed. It is
shifted with the variation of load on different sections of the distributor.
48 9/20/2015
Advantages
 (a) If a fault occurs on any feeding point of the
distributor, the continuity of supply is main-tained from
the other feeding point.
 (b) In case of fault on any section of the distributor,
the continuity of supply is maintained from the other
feeding point.
 (C)The area of X-section required for a doubly fed
distributor is much less than that of a singly fed
distributor.
9/20/2015
49
Ring Distributor
9/20/2015
50
9/20/2015
51
 In this type of feeding, the centre of the distributor
is connected to the supply mains as shown in Fig.
 It is equivalent to two singly fed distributors,
each distributor having a common feeding point
and length equal to half of the total length
1.8 Overhead Vs Underground
System
144
Transmission and
Distribution
 Transmission lines
connect power
generation plants
to substations,
other power
generating plants,
and other utilities
at high voltages.
 Distributes electricity
to each customer's
residence, business,
or industrial plant at
lower voltages.
Transmission System Distribution System
Transmission and
Distribution
Transmission Distribution
Underground and Overhead
 Undergrounding
transmission lines is
less common
 Underground cables
have different
technical
requirements than
overhead and have
different impacts
 Undergrounding
distributions lines
is more common
Transmission Distribution
Underground vs. Overhead
Transmission
 Design Issues
 Specialized engineering skills required
 Extensive study required to determine site-
specific subsurface obstructions or obstacles
 Longer timeframe for design
 Need to provide larger budget contingency
 Flood plain and wetland issues require special
consideration
 Environmental impacts
Underground vs. Overhead
Transmission
 Construction Concerns
 Space for large vaults (8’ x 10’ X 20’)
 Longer construction time frame
 Dewatering in wet areas during construction
 Significantly more impacts to surrounding
properties
 Open trenches
 min. 5’ wide x 5’ deep
 Specialized backfill
Underground vs. Overhead
Transmission
 Operational Concerns
 Difficult to identify outage location
 Requires specialized work force
 Long lead time for delivery of materials
 Need to warehouse specialized spare materials
 Increased maintenance
 Shorter life span
 Dewatering and cleaning of equipment in
vaults
Underground vs. Overhead
Transmission
 Cost
 Typical underground costs are 8 to 10 times the cost of
overhead construction
 Typical life of underground is approximately one-half
the life of overhead construction
 Depending on route may have significantly more
unanticipated problems with associated costs
 4-Cable system required to increase reliability which
adds cost
 Specialized workforce increases cost
 Wetland mitigation may be substantially more
depending on route
 Warehousing of spare materials and equipment
Underground
Transmission
 Generally used:
 in densely populated and urban settings
 where sufficient right-of-way is not available
 to reduce visual impacts
 riser poles at each end of the underground cable are large
and support additional equipment that create visual impacts
 Reliability
 May have fewer outages than overhead
 When outages occur they will be more difficult to
locate and may take significantly more time to repair
comparison
comparison
1.9 Protection of Power System
157
Power-system protection
 Power-system protection is a branch of electrical power engineering that deals with the
protection of electrical power systems from faults through the isolation of faulted parts from
the rest of the electrical network.
 The objective of a protection scheme is to keep the power system stable by isolating only
the components that are under fault, whilst leaving as much of the network as possible still in
operation.
 Thus, protection schemes must apply a very pragmatic and pessimistic approach to
clearing system faults. For this reason, the technology and philosophies utilized in protection
schemes can often be old and well-established because they must be very reliable.
Components
Protection systems usually comprise five components:
•Current and voltage transformers to step down the high voltages and currents of the
electrical power system to convenient levels for the relays to deal with
•Protective relays to sense the fault and initiate a trip, or disconnection, order;
•Circuit breakers to open/close the system based on relay and autorecloser commands;
•Batteries to provide power in case of power disconnection in the system.
•Communication channels to allow analysis of current and voltage at remote terminals of a
line and to allow remote tripping of equipment.
 For parts of a distribution system, fuses are capable of both sensing and disconnecting
faults.
 Failures may occur in each part, such as insulation failure, fallen or broken transmission
lines, incorrect operation of circuit breakers, short circuits and open circuits. Protection
devices are installed with the aims of protection of assets, and ensure continued supply of
energy.
Switchgear is a combination of electrical disconnect switches, fuses or circuit breakers
used to control, protect and isolate electrical equipment. Switches are safe to open under
normal load current, while protective devices are safe to open under fault current.
Protective devices
Protective relays control the tripping of the circuit breakers surrounding the faulted part of
the network
Automatic operation, such as auto-re-closing or system restart
Monitoring equipment which collects data on the system for post event analysis
While the operating quality of these devices, and especially of protective relays, is always
critical, different strategies are considered for protecting the different parts of the system.
Very important equipment may have completely redundant and independent protective
systems, while a minor branch distribution line may have very simple low-cost protection.
There are three parts of protective devices:
•Instrument transformer: current or potential (CT or VT)
•Relay
•Circuit breaker
Advantages of protected devices with these three basic components include safety,
economy, and accuracy.
Safety:
Instrument transformers create electrical isolation from the power system, and thus
establishing a safer environment for personnel working with the relays.
Economy:
Relays are able to be simpler, smaller, and cheaper given lower-level relay inputs.
Accuracy:
Power system voltages and currents are accurately reproduced by instrument transformers
over large operating ranges.
Performance and design criteria for system-protection devices include reliability, selectivity,
speed, cost, and simplicity.
Reliability: Devices must function consistently when fault conditions occur, regardless of
possibly being idle for months or years. Without this reliability, systems may result in high
costly damages.
Selectivity: Devices must avoid unwarranted, false trips.
Speed: Devices must function quickly to reduce equipment damage and fault duration, with
only very precise intentional time delays.
Economy: Devices must provide maximum protection at minimum cost.
Simplicity: Devices must minimize protection circuitry and equipment.
Protective relays
These are compact analog or digital networks, connected to various points of an
electrical system, to detect abnormal conditions occurring within their assigned
areas.
 They initiate disconnection of the trouble area by circuit breakers. These relays
range from the simple overload unit on house circuit breakers to complex systems
used to protect extra high voltage power transmission lines.
They operate on voltage, current, current direction, power factor, power,
impedance, temperature.
In all cases there must be a measurable difference between the normal or
tolerable operation and the intolerable or unwanted condition.
 System faults for which the relays respond are generally short circuits
between the phase conductors, or between the phases and grounds.
 Some relays operate on unbalances between the phases, such as an open or
reversed phase.
 A fault in one part of the system affects all other parts. Therefore relay sand
fuses throughout the power system must be coordinated to ensure the best
quality of service to the loads and to avoid operation in the non-faulted
areas unless the trouble is not adequately cleared in a specified time.
165
1.10 Types of Tariff
166
The tariff is the rate at which the
electrical energy is sold. There are various types of
tariffs followed in the market. This post will give the
brief idea about different tariff types.
VARIOUS TYPES OF TARIFFS
1- Simple Tariff
2- Flat rate Tariff
3 - Block Rate Tariff
4 - Two Part Tariff/Maximum Demand Tariff
5 - Power Factor Tariff
6 – Three Part Tariff
SIMPLE TARIFF
The tariff which has a fixed rate, per unit energy consumed.
ADVANTAGES
:- This is simplest tariff.
:- Even a simple consumer can understand it.
DISADVANTAGES
:- There is no differentiation between small and big
consumers.
:- The cost is per unit is very high.
FLAT RATE TARIFF
It is a type in which different consumers have different rates. A
discrimination exists between small and large consumers.
ADVANTAGES
:- Large consumers are encouraged in this type.
:- This tariff is simple and easy to calculate.
DISADVANTAGES
:- Different energy meters are required to be installed at
consumer’s premises.
:- The supplier doesn’t get any return for the connection given
to the consumer If he doesn’t consume any energy in a
particular period.
BLOCK RATE TARIFF
When the total energy consumed is divided into
blocks for the purpose of tariff.
ADVANTAGES
:- The consumers are encouraged to consume more
energy. This increase load factor of
the system and the cost of generation is reduced.
DISADVANTAGES
:- This doesn’t take into account the maximum
demand of the consumer.
TWO PART TARIFF
This is the system in which the tariff is related to the consumer’s
maximum demand, and then, to his consumption of energy.
ADVANTAGES
:-This tariff is very suitable for industrial consumers who have higher
maximum demand.
:-It takes into considerations the maximum demand of the consumer.
DISADVANTAGES
:-A maximum demand indicator is to be installed at the premises for
assessing the maximum demand of the consumer.
:-The consumer has to pay some fixed amount per kw whether he
consumes energy or not in a particular period.
POWER FACTOR TARIFF
The tariff in which the power factor of the consumer is
taken into consideration.
In this there are following types:-
(i)KVA maximum demand tariff
(ii)Sliding scale tariff/Average P.F Tariff
(iii)KWh and KVAR Tariff
THREE PART TARIFF
The tariff which charges a consumer in 3 parts.
First Part
This represents fixed charge which includes interest
and depreciation.
Second Part
This is a semi-fixed charge which is calculated on
per kw of the maximum demand.
Third Part
This is a running charge which is calculated per kwh
of power consumed by the consumer
1.11 Power Factor Improvement
175
Active power actually performs the work and is measured in kW. This is also
what is read on a wattmeter.
Reactive power sustains the electromagnetic field and is measured in kvar.
 Power Factor is the measurement of how effectively your business uses the
electricity supplied to your site
 Ideal Power Factor is unity or 1, anything less than 1 means that extra power
is required to achieve the necessary tasks.
The higher the power factor, the more effectively electrical power is
being used and vice versa.
 Low Power Factor is expensive and inefficient, with many utility companies
charging extra, (reactive power charge), for sites with a poor power factor
 Low Power Factor can also reduce the capacity of your electrical
distribution system by increasing current flow and causing voltage drops.
Power Factor is the ratio of true power to apparent power
Power Factor = KW
KVA
 Power Factor Correction is the term given to a technology to restore Power
Factor to as close to unity as economically viable
 This can be achieved by adding Power Factor Correction capacitors to the
distribution system which provide or compensate for the Reactive Power
demand of the inductive load, and thus reduce the burden on the supply
 Capacitors work as reactive current generators “providing” needed reactive
power (KVAr) into the power supply
 By supplying their own source of reactive power, the industrial user frees the
utility from having to supply it, and therefore the total amount of apparent
power supplied by the utility will be less.
 Power Factor Correction Capacitors reduce the total current drawn from the
distribution system and subsequently increase the system’s capacity by raising
the Power Factor level.
 A reduction in electricity charges
 Elimination of utility power factor penalties, which can increase electrical bills
by up to 20%
 Reduction in I²R losses of transformers and distribution equipment
 Prolonging the life of equipment from reduced heat in cables, switchgear,
transformers and alternators
 Reduced voltage drop in cables, allowing the same cable to supply a
larger motor and improving the starting of motors at the end of the long
cable runs
Thank You
184

More Related Content

Similar to unit-1-Three phase circuits and power systems.pdf

4.three phase circuits
4.three phase circuits 4.three phase circuits
4.three phase circuits Ekeeda
 
Lecture6_Electrical engingveering_AC.pptx
Lecture6_Electrical engingveering_AC.pptxLecture6_Electrical engingveering_AC.pptx
Lecture6_Electrical engingveering_AC.pptxAlmasifidi
 
Three phase delta connection
Three phase delta connectionThree phase delta connection
Three phase delta connectionMayur Ekhande
 
Three phase circuits
Three phase circuitsThree phase circuits
Three phase circuitsEkeeda
 
3phase unit 2.ppt
3phase unit 2.ppt3phase unit 2.ppt
3phase unit 2.pptmanoraa2107
 
Polyphase circuit electrical maintenace
Polyphase circuit   electrical maintenacePolyphase circuit   electrical maintenace
Polyphase circuit electrical maintenaceVijay Raskar
 
three_phase_transformers-1p protection concept.pdf
three_phase_transformers-1p protection concept.pdfthree_phase_transformers-1p protection concept.pdf
three_phase_transformers-1p protection concept.pdfkanimol143me
 
Ac circuits 15 april 2013(1)
Ac circuits 15 april 2013(1)Ac circuits 15 april 2013(1)
Ac circuits 15 april 2013(1)Malusela Ndivhuwo
 
Ac circuits 15 april 2013(1)
Ac circuits 15 april 2013(1)Ac circuits 15 april 2013(1)
Ac circuits 15 april 2013(1)TRL4EVER
 
Ac circuits 15 april 2013(1)
Ac circuits 15 april 2013(1)Ac circuits 15 april 2013(1)
Ac circuits 15 april 2013(1)MDUDUZI MABENA
 
Ac circuits 15 april 2013(1)
Ac circuits 15 april 2013(1)Ac circuits 15 april 2013(1)
Ac circuits 15 april 2013(1)Majoro
 
Electromagnetic induction
Electromagnetic inductionElectromagnetic induction
Electromagnetic inductionwengsung60
 
Electrical Troubleshooting
Electrical TroubleshootingElectrical Troubleshooting
Electrical TroubleshootingNabeel Hassan
 
ELECTRICAL WIRING.pptx
ELECTRICAL WIRING.pptxELECTRICAL WIRING.pptx
ELECTRICAL WIRING.pptxMalayMaurya
 

Similar to unit-1-Three phase circuits and power systems.pdf (20)

4.three phase circuits
4.three phase circuits 4.three phase circuits
4.three phase circuits
 
Lecture6_Electrical engingveering_AC.pptx
Lecture6_Electrical engingveering_AC.pptxLecture6_Electrical engingveering_AC.pptx
Lecture6_Electrical engingveering_AC.pptx
 
Three phase delta connection
Three phase delta connectionThree phase delta connection
Three phase delta connection
 
Three phase circuits
Three phase circuitsThree phase circuits
Three phase circuits
 
Wattmeter
WattmeterWattmeter
Wattmeter
 
3phase unit 2.ppt
3phase unit 2.ppt3phase unit 2.ppt
3phase unit 2.ppt
 
Measurement of various line and phase quantities for a three phase ac circuit
Measurement of various line and phase quantities for a three phase ac circuitMeasurement of various line and phase quantities for a three phase ac circuit
Measurement of various line and phase quantities for a three phase ac circuit
 
Polyphase circuit electrical maintenace
Polyphase circuit   electrical maintenacePolyphase circuit   electrical maintenace
Polyphase circuit electrical maintenace
 
H06 elo f
H06 elo fH06 elo f
H06 elo f
 
Ac circuits
Ac circuitsAc circuits
Ac circuits
 
three_phase_transformers-1p protection concept.pdf
three_phase_transformers-1p protection concept.pdfthree_phase_transformers-1p protection concept.pdf
three_phase_transformers-1p protection concept.pdf
 
Ac circuits 15 april 2013(1)
Ac circuits 15 april 2013(1)Ac circuits 15 april 2013(1)
Ac circuits 15 april 2013(1)
 
Ac circuits 15 april 2013(1)
Ac circuits 15 april 2013(1)Ac circuits 15 april 2013(1)
Ac circuits 15 april 2013(1)
 
Ac circuits 15 april 2013(1)
Ac circuits 15 april 2013(1)Ac circuits 15 april 2013(1)
Ac circuits 15 april 2013(1)
 
Ac circuits 15 april 2013(1)
Ac circuits 15 april 2013(1)Ac circuits 15 april 2013(1)
Ac circuits 15 april 2013(1)
 
Electromagnetic induction
Electromagnetic inductionElectromagnetic induction
Electromagnetic induction
 
Electrical Troubleshooting
Electrical TroubleshootingElectrical Troubleshooting
Electrical Troubleshooting
 
Lec 20.pptx
Lec 20.pptxLec 20.pptx
Lec 20.pptx
 
3 phase ac circuit
3 phase ac circuit3 phase ac circuit
3 phase ac circuit
 
ELECTRICAL WIRING.pptx
ELECTRICAL WIRING.pptxELECTRICAL WIRING.pptx
ELECTRICAL WIRING.pptx
 

More from deepaMS4

the cop and the anthem.pptx
the cop and the anthem.pptxthe cop and the anthem.pptx
the cop and the anthem.pptxdeepaMS4
 
FRAME RELAY NETWORK.ppt
FRAME RELAY NETWORK.pptFRAME RELAY NETWORK.ppt
FRAME RELAY NETWORK.pptdeepaMS4
 
Chapter17.ppt
Chapter17.pptChapter17.ppt
Chapter17.pptdeepaMS4
 
time domain analysis.pptx
time domain analysis.pptxtime domain analysis.pptx
time domain analysis.pptxdeepaMS4
 
dtei-180910104911-converted.pptx
dtei-180910104911-converted.pptxdtei-180910104911-converted.pptx
dtei-180910104911-converted.pptxdeepaMS4
 
DE UNIT1.pptx
DE UNIT1.pptxDE UNIT1.pptx
DE UNIT1.pptxdeepaMS4
 
Unit 3- DC Machines.pdf
Unit 3- DC Machines.pdfUnit 3- DC Machines.pdf
Unit 3- DC Machines.pdfdeepaMS4
 
Unit 2 - Transformers.pdf
Unit 2 - Transformers.pdfUnit 2 - Transformers.pdf
Unit 2 - Transformers.pdfdeepaMS4
 
MOSFET.ppt
MOSFET.pptMOSFET.ppt
MOSFET.pptdeepaMS4
 
Synchmachine-1.ppt
Synchmachine-1.pptSynchmachine-1.ppt
Synchmachine-1.pptdeepaMS4
 
chapter 5 (1).pptx
chapter 5 (1).pptxchapter 5 (1).pptx
chapter 5 (1).pptxdeepaMS4
 

More from deepaMS4 (12)

the cop and the anthem.pptx
the cop and the anthem.pptxthe cop and the anthem.pptx
the cop and the anthem.pptx
 
FRAME RELAY NETWORK.ppt
FRAME RELAY NETWORK.pptFRAME RELAY NETWORK.ppt
FRAME RELAY NETWORK.ppt
 
Chapter17.ppt
Chapter17.pptChapter17.ppt
Chapter17.ppt
 
time domain analysis.pptx
time domain analysis.pptxtime domain analysis.pptx
time domain analysis.pptx
 
dtei-180910104911-converted.pptx
dtei-180910104911-converted.pptxdtei-180910104911-converted.pptx
dtei-180910104911-converted.pptx
 
DE UNIT1.pptx
DE UNIT1.pptxDE UNIT1.pptx
DE UNIT1.pptx
 
Unit 3- DC Machines.pdf
Unit 3- DC Machines.pdfUnit 3- DC Machines.pdf
Unit 3- DC Machines.pdf
 
Unit 2 - Transformers.pdf
Unit 2 - Transformers.pdfUnit 2 - Transformers.pdf
Unit 2 - Transformers.pdf
 
MOSFET.ppt
MOSFET.pptMOSFET.ppt
MOSFET.ppt
 
bjt1.ppt
bjt1.pptbjt1.ppt
bjt1.ppt
 
Synchmachine-1.ppt
Synchmachine-1.pptSynchmachine-1.ppt
Synchmachine-1.ppt
 
chapter 5 (1).pptx
chapter 5 (1).pptxchapter 5 (1).pptx
chapter 5 (1).pptx
 

Recently uploaded

HARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICS
HARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICSHARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICS
HARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICSRajkumarAkumalla
 
Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...
Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...
Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...srsj9000
 
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...Christo Ananth
 
the ladakh protest in leh ladakh 2024 sonam wangchuk.pptx
the ladakh protest in leh ladakh 2024 sonam wangchuk.pptxthe ladakh protest in leh ladakh 2024 sonam wangchuk.pptx
the ladakh protest in leh ladakh 2024 sonam wangchuk.pptxhumanexperienceaaa
 
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINE
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINEMANUFACTURING PROCESS-II UNIT-2 LATHE MACHINE
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINESIVASHANKAR N
 
Architect Hassan Khalil Portfolio for 2024
Architect Hassan Khalil Portfolio for 2024Architect Hassan Khalil Portfolio for 2024
Architect Hassan Khalil Portfolio for 2024hassan khalil
 
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escortsranjana rawat
 
chaitra-1.pptx fake news detection using machine learning
chaitra-1.pptx  fake news detection using machine learningchaitra-1.pptx  fake news detection using machine learning
chaitra-1.pptx fake news detection using machine learningmisbanausheenparvam
 
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...ranjana rawat
 
Introduction to IEEE STANDARDS and its different types.pptx
Introduction to IEEE STANDARDS and its different types.pptxIntroduction to IEEE STANDARDS and its different types.pptx
Introduction to IEEE STANDARDS and its different types.pptxupamatechverse
 
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...Dr.Costas Sachpazis
 
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...Soham Mondal
 
Coefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptxCoefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptxAsutosh Ranjan
 
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...Dr.Costas Sachpazis
 
What are the advantages and disadvantages of membrane structures.pptx
What are the advantages and disadvantages of membrane structures.pptxWhat are the advantages and disadvantages of membrane structures.pptx
What are the advantages and disadvantages of membrane structures.pptxwendy cai
 
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...ranjana rawat
 
GDSC ASEB Gen AI study jams presentation
GDSC ASEB Gen AI study jams presentationGDSC ASEB Gen AI study jams presentation
GDSC ASEB Gen AI study jams presentationGDSCAESB
 

Recently uploaded (20)

HARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICS
HARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICSHARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICS
HARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICS
 
Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...
Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...
Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...
 
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
 
the ladakh protest in leh ladakh 2024 sonam wangchuk.pptx
the ladakh protest in leh ladakh 2024 sonam wangchuk.pptxthe ladakh protest in leh ladakh 2024 sonam wangchuk.pptx
the ladakh protest in leh ladakh 2024 sonam wangchuk.pptx
 
Call Us -/9953056974- Call Girls In Vikaspuri-/- Delhi NCR
Call Us -/9953056974- Call Girls In Vikaspuri-/- Delhi NCRCall Us -/9953056974- Call Girls In Vikaspuri-/- Delhi NCR
Call Us -/9953056974- Call Girls In Vikaspuri-/- Delhi NCR
 
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINE
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINEMANUFACTURING PROCESS-II UNIT-2 LATHE MACHINE
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINE
 
Exploring_Network_Security_with_JA3_by_Rakesh Seal.pptx
Exploring_Network_Security_with_JA3_by_Rakesh Seal.pptxExploring_Network_Security_with_JA3_by_Rakesh Seal.pptx
Exploring_Network_Security_with_JA3_by_Rakesh Seal.pptx
 
Architect Hassan Khalil Portfolio for 2024
Architect Hassan Khalil Portfolio for 2024Architect Hassan Khalil Portfolio for 2024
Architect Hassan Khalil Portfolio for 2024
 
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
 
9953056974 Call Girls In South Ex, Escorts (Delhi) NCR.pdf
9953056974 Call Girls In South Ex, Escorts (Delhi) NCR.pdf9953056974 Call Girls In South Ex, Escorts (Delhi) NCR.pdf
9953056974 Call Girls In South Ex, Escorts (Delhi) NCR.pdf
 
chaitra-1.pptx fake news detection using machine learning
chaitra-1.pptx  fake news detection using machine learningchaitra-1.pptx  fake news detection using machine learning
chaitra-1.pptx fake news detection using machine learning
 
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
 
Introduction to IEEE STANDARDS and its different types.pptx
Introduction to IEEE STANDARDS and its different types.pptxIntroduction to IEEE STANDARDS and its different types.pptx
Introduction to IEEE STANDARDS and its different types.pptx
 
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
 
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
 
Coefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptxCoefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptx
 
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
 
What are the advantages and disadvantages of membrane structures.pptx
What are the advantages and disadvantages of membrane structures.pptxWhat are the advantages and disadvantages of membrane structures.pptx
What are the advantages and disadvantages of membrane structures.pptx
 
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
 
GDSC ASEB Gen AI study jams presentation
GDSC ASEB Gen AI study jams presentationGDSC ASEB Gen AI study jams presentation
GDSC ASEB Gen AI study jams presentation
 

unit-1-Three phase circuits and power systems.pdf

  • 1. Mount Zion College of Engineering and Technology BE8254 Basics of Electrical and Instrumentation Engineering P. Maria Sheeba AP/ECE
  • 2. OOBJECTIVE  To analyze the operation of Three phase electrical circuits and power measurement.  To deal with the working principles of Electrical machines.  To understand the principle of various measuring instruments. MZCET- ECE
  • 3. OUTCOMES  Concept of three phase power circuits and measurement.  Comprehend the concepts in electrical generators, motors and transformers.  Choose appropriate measuring instruments for given application.
  • 4. • 1.1 Three phase power supply • 1.2 Inter Connection of windings • 1.3 Balanced and Unbalanced loads • 1.4 Power Equation • 1.5 Star Delta Conversion • 1.6 Three phase power measurement • 1.7 Transmission and Distribution of electrical energy • 1.8 Over head Vs Underground system • 1.9 Protection of power system • 1.10 Types of Tariff • 1.11 Power factor improvement MZCET-ECE Unit-I AC Circuits and Power Systems
  • 5. 1.1 Three phase power supply
  • 6. IMPORTANCE OF THREE PHASE SYSTEM • Uniform power transmission and less vibration of three phase machines. – The instantaneous power in a 3φ system can be constant (not pulsating). – High power motors prefer a steady torque especially one created by a rotating magnetic field.
  • 7. IMPORTANCE OF THREE PHASE SYSTEM • Three phase system is more economical than the single phase. – The amount of wire required for a three phase system is less than required for an equivalent single phase system. – Conductor: Copper, Aluminum, etc
  • 8. Differences Single Phase Power Supply  230 V, 50 Hz  Not sufficient for producing large amount of power.  With single-phase current, the voltage rises to a peak in one direction of flow, subsides to zero, reverses, rises to a peak in the opposite direction, subsides to zero, and so on.  Single-phase current requires the use of one transformer. Three Phase Power Supply  440 V, 50 Hz  Sufficient for producing large amount of power.  There are three separate and distinct single-phase currents, which are combined so they can be transmitted over three or four wires and these rise to a peak in one direction, subside, reverse, and so on; however they do not peak at the same time.  Three-phase current requires two or three transformers.
  • 10. 1.1.1 Introduction: • The generator , motor , transformer or rectifier have only one winding is called a single phase system • If the current or voltage follows a phase difference 900 in a two windings, called two phase systems • If the phase difference is 1200 between voltages or currents in a three winding, called as Three phase systems • In poly-phase systems , there are more than three windings Advantages of three phase system: • More efficient than single phase system • Cost is less • Size is small . Compared to single phase system 10
  • 11. Advantages of Three Phase Circuits • The amount of conductor material is required less for transmitting same power, over the same distance , under same power loss • Three phase motors produce uniform torque , where as torque produced by single motor is pulsating • Three phase generators not produce the harmonics when they are connected in parallel • Three phase motors are self starting whereas single phase motors are not self starting MZCET 11
  • 13. FARADAYS LAW • Three things must be present in order to produce electrical current: a) Magnetic field b) Conductor c) Relative motion • Conductor cuts lines of magnetic flux, a voltage is induced in the conductor • Direction and Speed are important
  • 14. GENERATING A SINGLE PHASE Motion is parallel to the flux. No voltage is induced. N S
  • 15. x N S Motion is 45° to flux. Induced voltage is 0.707 of maximum. GENERATING A SINGLE PHASE
  • 16. GENERATING A SINGLE PHASE x N S Motion is perpendicular to flux. Induced voltage is maximum.
  • 17. GENERATING A SINGLE PHASE Motion is 45° to flux. x N S Induced voltage is 0.707 of maximum.
  • 18. GENERATING A SINGLE PHASE N S Motion is parallel to flux. No voltage is induced.
  • 19. GENERATING A SINGLE PHASE x N S Notice current in the conductor has reversed. Induced voltage is 0.707 of maximum. Motion is 45° to flux.
  • 20. GENERATING A SINGLE PHASE N S x Motion is perpendicular to flux. Induced voltage is maximum.
  • 21. GENERATING A SINGLE PHASE N S x Motion is 45° to flux. Induced voltage is 0.707 of maximum.
  • 22. GENERATING A SINGLE PHASE Motion is parallel to flux. N S No voltage is induced. Ready to produce another cycle.
  • 24. GENERATOR WORK • The generator consists of a rotating magnet (rotor) surrounded by a stationary winding (stator). • Three separate windings or coils with terminals a- a’, b-b’, and c-c’ are physically placed 120° apart around the stator.
  • 25. • As the rotor rotates, its magnetic field cuts the flux from the three coils and induces voltages in the coils. • The induced voltage have equal magnitude but out of phase by 120°.
  • 27. THREE-PHASE WAVEFORM Phase 2 lags phase 1 by 120°. Phase 2 leads phase 3 by 120°. Phase 3 lags phase 1 by 240°. Phase 1 leads phase 3 by 240°. Phase 1 Phase 2 Phase 3 120° 120° 120° 240° 120° 120° 120° 240°
  • 28. Phase 1 Phase 2 Phase 3 GENERATION OF 3φ VOLTAGES Phase 1 is ready to go positive. Phase 2 is going more negative. Phase 3 is going less positive. N x x S
  • 29. 1.1.2 Generation of Three Phase Voltages MZCET 29
  • 30. BALANCED 3φ VOLTAGES • Balanced three phase voltages: – same magnitude (VM) – 120° phase shift ( ) ( ) ( ) ( ) ° + = ° − = ° − = = 120 cos 240 cos ) ( 120 cos ) ( cos ) ( t V t V t v t V t v t V t v M M cn M bn M an ω ω ω ω
  • 31. • Vectorially r.m.s values of voltages induced in three windings are represented in the diagram • ER = E ∟0o v, • EY = E ∟-120o v • EB= E ∟+120o v MZCET 31
  • 32.  Three voltages are not in phase, since there is a phase difference of  The order of voltage waveform sequences in a polyphase system is called phase rotation or phase sequence.  This sequence of phase shifts has a definite order. For clockwise rotation, the order is 1-2-3 (i.e) RYB (winding 1 peaks first, them winding 2, then winding 3), which is known as a positive phase sequence. MZCET 1.1.3 PHASE SEQUENCE  120
  • 34.  For anti-clockwise rotation, the order is 3-2-1 (i.e) RBY (winding 3 peaks first, them winding 2, then winding 1), which is known as a negative phase sequence.  If we’re using a polyphase voltage source to power resistive loads, phase rotation will make no difference at all.  Whether 1-2-3 or 3-2-1, the voltage and current magnitudes will all be the same.
  • 35. PHASE SEQUENCE ( ) ( ) ° + = ° − = = 120 cos ) ( 120 cos ) ( cos ) ( t V t v t V t v t V t v M cn M bn M an ω ω ω ° + ∠ = ° − ∠ = ° ∠ = 120 120 0 M cn M bn M an V V V V V V POSITIVE SEQUENCE NEGATIVE SEQUENCE ° − ∠ = ° + ∠ = ° ∠ = 120 120 0 M cn M bn M an V V V V V V
  • 37. THREE PHASE QUANTITIES QUANTITY SYMBOL Phase current Iφ Line current IL Phase voltage Vφ Line voltage VL
  • 38. 1.2.1 PHASE VOLTAGES and LINE VOLTAGES • Phase voltage is measured between the neutral and any line: line to neutral voltage • Line voltage is measured between any two of the three lines: line to line voltage.
  • 39. 1.2.2 PHASE CURRENTS and LINE CURRENTS • Line current (IL) is the current in each line of the source or load. • Phase current (Iφ) is the current in each phase of the source or load.
  • 40. Interconnection of windings Three phase connections: • There are two types of three phase connections • Star connection (Y) • Delta connection (Δ) 1.2.3 Star connection (Y): • In this method of inter-connection, the similar ends, say, “start” ends of three coils (it could be “finishing” ends also) are joined together at point ‘N’ 40
  • 41. • The point ‘N’ is known as star point or neutral point • If this three-phase voltage is applied across a balanced symmetrical load, the neutral wire will be carrying three currents which are exactly equal in magnitude but are 120o out of phase with each other. Hence, their vector sum is zero IR + IY + IB = 0 Voltages and Currents in Y-Connection: • The voltage induced in each winding is called the ‘phase’ voltage and current in each winding is known as ‘phase’ current. MZCET 41
  • 42. • The vector diagram for phase voltages and currents in a star connection shows that ER = EY = EB = Eph (phase e.m.f) • Line voltage VRY between line 1 and line 2 is the vector difference of ER and EY. • Line voltage VYB between line 2 and line 3 is the vector difference of EY and EB. • Line voltage VBR between line 3 and line 1 is the vector difference of EB and ER. MZCET 42
  • 43. • The p.d. between lines 1 and 2 is VRY = ER - EY (Vector difference) • VRY is found by compounding ER and EY reversed and its value is given by the diagonal of the paral1elogram in figure. • The angle between ER and EY reversed is 60°. If ER = EY = EB = Ephthe Phase e.m.f then, • MZCET 43 C O ph RY o E V 2 30 cos = o ph RY E V 30 cos 2 × × = ph ph E E 3 2 3 2 = × × =
  • 44. • Hence, in star connection It will be noted from figure that • (a) Line voltages are 120° apart. • (b) Line voltages are 30° ahead of their respective phase voltages. • (c) The angle between the line currents and the corresponding line voltages is (30 + ) ɸ with current lagging. 44 ph B Y YB E Difference Vector E E V similarly 3 ) ( = − = ph R B BR E Difference Vector E E V and 3 ) ( = − = L BR YB RY V voltage line V V V , = = = ph L E V 3 =
  • 45. Line Currents and Phase Currents: • Current in line 1 = IR • Current in line 2 = IY • Current in line 3 = IB Since IR = IY = IB = say, Iph - the phase current Line current IL = Iph Power: • The total power in the circuit is the sum of the three phase powers. Hence • Total Power =3 x phase power= • 45
  • 46. 1.2.4 Delta (Δ) or Mesh Connection: • Phase sequence is R, Y, B • R leads Y by 120° and Y leads B by 120°. • The voltage between lines 1 and 2 as VRY • The voltage between lines 2 and 3 as VYB VRY leads VYB by 120 VYB leads VBR by 120°. • VRY =VYB = VBR = line voltage VL • Then, it VL = Vph MZCET 46
  • 48. Line Currents and Phase Currents: • Current in line 1 is I1 = IR – IB • Current in line 2 is I2= IY – IR • Current in line 3 is I3= IB - IY • Current in line 1 is found by compounding IR with IB reversed and its value is given by the diagonal of the parallelogram • The angle between IR and IB reversed (-IB) is 60°. • If IB = IR = IY = Iph phase current, then current in line 1 is 48
  • 49. Contd.. Since all line currents are equal in magnitude i.e., I1= I2 = I3= IL From Vector diagram, it should be noted that • (a) Line currents are 120o apart. • (b) Line currents are 30o behind the respective phase currents. • (c) The angle between the line current and the corresponding line voltage is 49
  • 50. Power: MZCET 50 φ cos 3 ph ph I E P × = L ph V E but = 3 L ph I I = φ cos 3 3 × × × = L L I V P φ cos 3 L L I V P =
  • 51. 1.3 Balanced and unbalanced loads 51
  • 52. 1.3.1 Balanced three phase supply: • A three phase supply is said to be balanced, when all the three voltages have the same magnitude but differ in phase by 120° with respect to one another. • The three phase supply is said to be unbalanced, even if one of the above conditions is not satisfied. MZCET 52 Balanced Supply
  • 53. MZCET 53 1.3.2 Balanced Load: • A three phase load is said to be balanced, when the impedances of all the three phases are exactly the same. Even if one of them is different from the other, then the three phase load is said to be unbalanced
  • 54. • In a three phase balanced load, whether star connected or delta connected, the magnitudes of the phase currents are the same but differ in phase by 120o with respected to one another 1.3.3 Unbalanced Load • But in an unbalanced load, when a three phase balanced supply is given, the magnitudes and phases of all the three phase currents will be different. MZCET 54
  • 56. 1.4 Power Equation 1.4.1 Star Connection The total power in the circuit is the sum of the three phase powers. Hence , Total Power =3 x phase power= 56
  • 57. 1.4.2 Power for delta connection MZCET 57 φ cos 3 ph ph I E P × = L ph V E but = 3 L ph I I = φ cos 3 3 × × × = L L I V P φ cos 3 L L I V P =
  • 58. 1.5 Star Delta Conversion 58
  • 59. Resistive Circuits (Basics)  Resistors in parallel:  Resistors in series: R1 R2 R3
  • 60. Current Division in Parallel Circuits R 1 R 2 V I I 2 I 1
  • 61. Voltage Division in Series Circuits R 1 R 2 V + V 1 - - V 2 + I
  • 62. 1.5.1 Star -> Delta Conversion A B C Rab Rbc Rca B C Ra Rb Rc A Star Connection Delta Connection
  • 63. Star- Delta conversion Advantages 1. The primary side is star connected. Hence fewer number of turns are required. This makes the connection economical 2. The neutral available on the primary can be earthed to avoid distortion. 3. Large unbalanced loads can be handled satisfactory. 63
  • 64. Star- Delta conversion • Disadvantages • The secondary voltage is not in phase with the primary. (30 ⁰ phase difference ) • Hence it is not possible to operate this connection in parallel with star-star or delta-delta connected transformer. 64
  • 65. Wye(star) to Delta Transformation: Consider the following: • • • • • • a b c a b c R a R b R c R 1 R 2 R 3 ( a ) w y e c o n f i g u r a t i o n ( b ) d e l t a c o n f i g u r a t i o n a a c c b b a c a c c b b a b a c c b b a R R R R R R R R R R R R R R R R R R R R R R R R + + = + + = + + = 3 2 1 3 2 1 3 1 3 2 1 3 2 3 2 1 2 1 R R R R R R R R R R R R R R R R R R c b a + + = + + = + + =
  • 66. Using the following circuit. Find Req. 9 Ω 1 0 Ω 5 Ω 8 Ω 4 Ω V + _ R e q 1 0 Ω I a b c Convert the delta around a – b – c to a wye.
  • 67. Continued…. 2 Ω 2 Ω 4 Ω 4 Ω 8 Ω 9 Ω R e q It is easy to see that Req = 15 Ω
  • 69. Delta - Star Transformation Features  secondary Phase voltage is 1/√3 times of line voltage  neutral in secondary can be grounded for 3 phase 4 wire system  Neutral shifting and 3rd harmonics are there  Phase shift of 30⁰ between secondary and primary currents and voltages 69
  • 70. 1.6 THREE PHASE POWER MEASUREMENT
  • 72.  Three-phase power is a common method of alternating- current electric power generation, transmission, and distribution.  It is a type of polyphase system and is the most common method used by electric grids worldwide to transfer power.  A polyphase system is a means of distributing alternating-current electrical power.  An electrical grid is an interconnected network for delivering electricity from suppliers to consumers.
  • 73. 1.6.1 Measure of power in Three Phase Circuits: • Wattmeter is the instrument which is used to measure power in an electrical circuit. • It consists of (i) a current coil ML’ through which the line current flows • (ii) a potential coil PV, which is connected across the circuit. • The full voltage is applied across the potential coil and it carries a very small current proportional to the applied voltage. • Three single phase watt-meters may be connected in each phase • The algebraic sum of their readings gives the total power consumed by the three phase circuit. • It can be proved that only two watt-meters are sufficient to measure power in a three phase circuit. MZCET 73
  • 74.  Various methods are used measurement of three phase power in three phase circuits on the basis of number of wattmeter used.  We have three methods:- 1) Three wattmeter method 2) Two wattmeter method 3) Single wattmeter method
  • 75. 1.6.2 MEASUREMENT OF THREE PHASE POWER BY THREE WATTMETER METHOD
  • 76.  Three Wattmeter method is used to measure power in a 3 phase, 4 wire system.  However, this method can also be used in a 3 phase, 3 wire delta connected load, where power consumed by each load is required to be determined separately.  The Three-wattmeter method can be used for star and delta connected unbalnced loads.
  • 77. • The connections for Star/Delta connected loads for measuring power by Three wattmeter method is shown below:-  The pressure coil of all • the Three wattmeter namely W1, W2and W3are connected to a • common terminal known as the neutral point. The product of the phase current and line voltage represents as phase power and is recorded by individual wattmeter. 77
  • 78.  The total power in a Three wattmeter method of power measurement is given by the algebraic sum of the readings of Three wattmeter. i.e.  Where, W1 = V1I1 W2 = V2I2 W3 = V3I3  Except for 3 phase, 4 wire unbalanced load, 3 phase power can be measured by using only Two Wattmeter Method.
  • 79. 1.6.3 MEASUREMENT OF THREE PHASE POWER BY TWO WATTMETER METHOD
  • 80.  Two Wattmeter Method can be used to measure the power in a 3 phase, 3 wire star or delta connected balanced or unbalanced load.  In Two wattmeter method the current coils of the wattmeter are connected with any two lines, say R and Y and the potential coil of each wattmeter is joined across the same line, the third line i.e. B.  The two wattmeter method is used for the power measurement in the 3-phase system, irrespective of whether the load is balanced or unbalanced.
  • 81. MEASUREMENT OF POWER BY TWO WATTMETER METHOD IN STAR CONNECTION
  • 82. Let W1 and W2 Be the two wattmeter. Let andthe phase voltages across the three loads be the phase currents respectively.
  • 83.  The instantaneous current through the current coil of Wattmeter, W1 is given by the equation shown below.  Instantaneous potential difference across the potential coil of Wattmeter, W1 is given as  Instantaneous power measured by the Wattmeter, W1 is
  • 84.  The instantaneous current through the current coil of Wattmeter, W2 is given by the equation  Instantaneous potential difference across the potential coil of Wattmeter, W2 is given as  Instantaneous power measured by the Wattmeter, W2 is
  • 85.  Therefore, the Total Power Measured by the Two Wattmeter W1 and W2 will be obtained by adding the equation (1) and (2).  Here P is the total power absorbed in the three loads at any instant.
  • 86. MEASUREMENT OF POWER BY TWO WATTMETER METHOD IN DELTA CONNECTION
  • 87. There are similar notations for delta also.
  • 88.  The instantaneous current through the coil of the Wattmeter, W1 is given by the equation  Instantaneous Power measured by the Wattmeter, W1 will be  Therefore, the instantaneous power measured by the Wattmeter, W1 will be given as
  • 89.  The instantaneous current through the current coil of the Wattmeter, W2 is given as  The instantaneous potential difference across the potential coil of Wattmeter, W2 is  Therefore, the instantaneous power measured by Wattmeter, W2 will be
  • 90.  Hence, to obtain the total power measured by the Two Wattmeter the two equations, i.e. equation (3) and (4) has to be added.  Here P is the total power absorbed in the three loads at any instant.
  • 91.  The power measured by the Two Wattmeter at any instant is the instantaneous power absorbed by the three loads connected in three phases.  In fact, this power is the average power drawn by the load since the Wattmeter reads the average power because of the inertia of their moving system.
  • 92. 1.6.4 MEASUREMENT OF POWER BY SINGLE PHASE WATTMETER METHOD
  • 93.  Power is measured in the electric circuit using a wattmeter.  A single phase wattmeter consists of two coils; namely the current coil and the pressure coil.  The Current coil is connected in series with the line and thus carries the line current.  The Pressure coil is connected in parallel with the line.  The Wattmeter gives the power per phase.
  • 94. 25 • The wattmeter gives the value of power per phase. • Therefore, Total power = 3 X Power per phase = 3 X wattmeter reading •The one wattmeter method is used for power measurement in the 3-phase star connected balanced load.
  • 95. 1.7 Transmission and Distribution of Electrical Energy 95
  • 99. 9/20/2015 4 1.7.2 Structure of Electrical Power System
  • 101. 1.7.3 Distribution System “The part of power system which distributes electrical power for local use is known as DISTRIBUTION SYSTEM.” This system is the electrical system between the substation fed by the transmission system and consumer meter. Distribution line generally consist of Feeders Distributers Service mains 9/20/2015
  • 102. FEEDERS DISTRIBUTORS SERVICE MAINS Distribution
  • 103. Feeder  A Feeder is conductor which connects the substation to the area where power is to be distributed  Feeder are used to feed the electrical power from the generating station to the substation  No tapings are taken from the feeder  So the current in it remains the same throughout  Main consideration in the design of feeder is the Current carrying capacity. 9/20/2015 8
  • 104. Distributer  A distributer is a conductor from which tapings are taken from pole mounted transformer to the consumer  The current through a distributer is not constant because tapings are taken at various places along its length  Voltage drop is main consideration  Limit of variation is 6% of rated at consumer 9/20/2015 9
  • 105. Service mains  A service mains is a generally a small cable which connects the distributer to the consumer ‘s meter.  The connecting links between the distributor and the consumer terminals. 9/20/2015 10
  • 106. 11
  • 109. 1.7.4 classification of dc distribution  Distribution system is a part of power system, existing between distribution substations and consumers.  It is further classified on the basis of voltage  Primary distribution system- 11 KV or 6.6 KV or 3.3 KV  Secondary distribution system- 415 V or 230 V 9/20/2015 16
  • 110. Classification Of Distribution System: It can be classified under different considerations as; 1. Type Of Current: a)AC Distribution System b)DC Distribution System 2. Type Of Construction: a)Overhead System b)Underground System 9/20/2015 17
  • 111. 3. Type Of Service: a)General Lighting & Power b)Industrial Power c)Railway d)Streetlight etc c) Interconnected Distribution System 4. Number Of Wires: a)Two Wire b)Three Wire c)Four Wire 5. Scheme Of Connection: a)Radial Distribution System b)Ring or Loop Distribution System 9/20/2015 18
  • 112. Ac distribution  A.c. distribution system is the electrical system between the step-down substation fed by the transmission system and the consumers’ meters. The a.c. distribution system is classified into  ( i) primary distribution system and  ( ii) secondary distribution system. 9/20/2015 19
  • 113. 1.7.5 Primary distribution system  voltages somewhat higher than general utilisation and handles large blocks of electrical energy than the average low-voltage consumer uses.  Commonly used primary distribution voltage 11KV, 6.6 KV,3.3 KV.  Electric power from the generating station is transmitted at high voltage to the substation located in or near the city.  At this substation, voltage is stepped down to 11 kV with the help of step-down transformer.  Power is supplied to various substations for distribution or to big consumers at this voltage.  This forms the high voltage distribution or primary distribution. 9/20/2015 20
  • 115. 1.7.6 Secondary distribution system  It is that part of a.c. distribution system which includes the range of voltages at which the ultimate consumer utilizes the electrical energy delivered to him.  The secondary distribution employs 400/230 V, 3- phase, 4-wire system. 22
  • 116. 23
  • 117. D.C. Distribution  D.c. supply is required for the operation of variable speed machinery ( i.e., d.c. motors), for electro-chemical work and for congested areas where storage battery reserves are necessary.  For this purpose, a.c. power is converted into d.c. power at the substation by using converting machinery e.g., mercury arc rectifiers, and motor-generator sets. 24
  • 118. Type of DC distributor  The dc supply from the substation may be obtained in form of  ( i) 2-wire or  ( ii) 3-wire for distribution. 25
  • 119. 2 wire 3 wire 9/20/2015 26
  • 120. 27  Two outer and a middle or neutral wire is earthed at the s/s.  Voltage between the outer is twice the voltage between either outer and neutral wire.  Advantage – available two voltage at the consumer terminal.  Loads requiring high voltage connected across the outers.  Lamps and heating circuits requiring less voltage are connected between either outer and neutral.
  • 121. Method of obtaining 3 wire D.c system  Two generator method.  3-wire D.c. generator.  Balancer set 9/20/2015 28
  • 123. Two generator method  D.c generator G1 and G2 are connected in series and the neutral is obtained from the common point btwn generator  G1 supplies a I1, G2 supplies a I2  Difference of load current on both side (I1-I2) flow through the neutral wire.  Disad.:two separate generator are required. 9/20/2015 30
  • 125. 3-wire D.c. generator.  Consist of a standard 2 wire machine with one or two coils of high reactance and low resistance that connected to opposite points of the armature winding.  Neutral wire is obtained from common point. 9/20/2015 32
  • 126. Connection schemes of distribution system  Radial system  Ring main system  Interconnected system 9/20/2015 33
  • 127. Radial Distribution System: 9/20/2015  separate feeders radiate from a single substation and feed the distributors at one end only.  Only one path is connected between each customer and substation.  Electrical power flows along a single path.  If interrupted, results in complete loss of power to the customer. . 34
  • 128. • Advantages:  Low cost .  Simple planning. • Disadvantages :  The radial system is employed only when power is generated at low voltage and the substation is located at the centre of the load.  Distributor nearer to feeding end is heavily loaded.  Consumers at far end of feeder would be subjected to serious • voltage fluctuations 128
  • 131. Ring or Loop Distribution System:  It consists of two or more paths between • power sources and the customer.  The loop circuit starts from the substation bus-bars, makes a loop through the area to be served, and returns to the substation • Advantages:  Less conductor material is required.  Less voltage fluctuations.  More reliable. • Disadvantages:  It is difficult to design as compared to the design of radial system. 37 9/20/2015
  • 132. 38
  • 133. Interconnected Distribution System:  It is supplied by a number of feeders.  Radial primary feeders can be tapped off from the interconnecting tie feeders.  They can also serve directly from the substation. Advantages:  Increases the reliability of supply  Losses are less  Quality of service is improved. Disadvantages:  Its initial cost is more.  Difficult in planning, design and operation. 9/20/2015 39
  • 135. 1.7.7 D.C. Distribution  D.c. supply is required for the operation of variable speed machinery ( i.e., d.c. motors),  for electro-chemical work and for congested areas where storage battery reserves are necessary.  For this purpose, a.c. power is converted into d.c. power at the substation by using converting machinery e.g., mercury arc rectifiers, rotary converters and motor- generator sets. The d.c. supply from the substation may be obtained in the form of 9/20/2015 43
  • 136. DC Distribution:  Voltage drop along distributor is considered as a main factorwhile designing a distributor.  It depends upon the nature of load and also on feeding, whether it is fed at one or both ends. According to loading, a distributor can be classified as: i. Fed at one end. ii. Fed at both ends. a). With equal voltages. b). With unequal voltages. iii. Fed at centre. Ring mains. 9/20/2015
  • 137. DC Distribution Feed at one end 9/20/2015
  • 138.  a) The current in the various sections of the distributor away from feeding point goes on decreasing. Thus current in section AC is more than the current in section CD and current in section CD is more than the current in section DE.  (b) The voltage across the loads away from the feeding point goes on decreasing. Thus in Fig. 13.1, the minimum voltage occurs at the load point E.  (c) In case a fault occurs on any section of the distributor, the whole distributor will have to be disconnected from the supply mains. Therefore, continuity of supply is interrupted
  • 139. Distributor fed at center 47
  • 140.  In this type of feeding the distributor is connected to the supply mains at both ends and loads are tapped off at different points along the length of the distributor. The voltage at the feeding points may or may not be equal. distributor A B fed at the ends A and B and loads of I1, I2 and I3 tapped off at points C respectively.  Here, the load voltage goes on decreasing as we move away from one feeding point say A , reaches minimum value and then again starts rising and reaches maximum value when we reach the other feeding point B.  The minimum voltage occurs at some load point and is never fixed. It is shifted with the variation of load on different sections of the distributor. 48 9/20/2015
  • 141. Advantages  (a) If a fault occurs on any feeding point of the distributor, the continuity of supply is main-tained from the other feeding point.  (b) In case of fault on any section of the distributor, the continuity of supply is maintained from the other feeding point.  (C)The area of X-section required for a doubly fed distributor is much less than that of a singly fed distributor. 9/20/2015 49
  • 143. 9/20/2015 51  In this type of feeding, the centre of the distributor is connected to the supply mains as shown in Fig.  It is equivalent to two singly fed distributors, each distributor having a common feeding point and length equal to half of the total length
  • 144. 1.8 Overhead Vs Underground System 144
  • 145. Transmission and Distribution  Transmission lines connect power generation plants to substations, other power generating plants, and other utilities at high voltages.  Distributes electricity to each customer's residence, business, or industrial plant at lower voltages. Transmission System Distribution System
  • 147. Underground and Overhead  Undergrounding transmission lines is less common  Underground cables have different technical requirements than overhead and have different impacts  Undergrounding distributions lines is more common Transmission Distribution
  • 148. Underground vs. Overhead Transmission  Design Issues  Specialized engineering skills required  Extensive study required to determine site- specific subsurface obstructions or obstacles  Longer timeframe for design  Need to provide larger budget contingency  Flood plain and wetland issues require special consideration  Environmental impacts
  • 149.
  • 150. Underground vs. Overhead Transmission  Construction Concerns  Space for large vaults (8’ x 10’ X 20’)  Longer construction time frame  Dewatering in wet areas during construction  Significantly more impacts to surrounding properties  Open trenches  min. 5’ wide x 5’ deep  Specialized backfill
  • 151.
  • 152. Underground vs. Overhead Transmission  Operational Concerns  Difficult to identify outage location  Requires specialized work force  Long lead time for delivery of materials  Need to warehouse specialized spare materials  Increased maintenance  Shorter life span  Dewatering and cleaning of equipment in vaults
  • 153. Underground vs. Overhead Transmission  Cost  Typical underground costs are 8 to 10 times the cost of overhead construction  Typical life of underground is approximately one-half the life of overhead construction  Depending on route may have significantly more unanticipated problems with associated costs  4-Cable system required to increase reliability which adds cost  Specialized workforce increases cost  Wetland mitigation may be substantially more depending on route  Warehousing of spare materials and equipment
  • 154. Underground Transmission  Generally used:  in densely populated and urban settings  where sufficient right-of-way is not available  to reduce visual impacts  riser poles at each end of the underground cable are large and support additional equipment that create visual impacts  Reliability  May have fewer outages than overhead  When outages occur they will be more difficult to locate and may take significantly more time to repair
  • 157. 1.9 Protection of Power System 157
  • 158. Power-system protection  Power-system protection is a branch of electrical power engineering that deals with the protection of electrical power systems from faults through the isolation of faulted parts from the rest of the electrical network.  The objective of a protection scheme is to keep the power system stable by isolating only the components that are under fault, whilst leaving as much of the network as possible still in operation.  Thus, protection schemes must apply a very pragmatic and pessimistic approach to clearing system faults. For this reason, the technology and philosophies utilized in protection schemes can often be old and well-established because they must be very reliable.
  • 159. Components Protection systems usually comprise five components: •Current and voltage transformers to step down the high voltages and currents of the electrical power system to convenient levels for the relays to deal with •Protective relays to sense the fault and initiate a trip, or disconnection, order; •Circuit breakers to open/close the system based on relay and autorecloser commands; •Batteries to provide power in case of power disconnection in the system. •Communication channels to allow analysis of current and voltage at remote terminals of a line and to allow remote tripping of equipment.
  • 160.  For parts of a distribution system, fuses are capable of both sensing and disconnecting faults.  Failures may occur in each part, such as insulation failure, fallen or broken transmission lines, incorrect operation of circuit breakers, short circuits and open circuits. Protection devices are installed with the aims of protection of assets, and ensure continued supply of energy. Switchgear is a combination of electrical disconnect switches, fuses or circuit breakers used to control, protect and isolate electrical equipment. Switches are safe to open under normal load current, while protective devices are safe to open under fault current.
  • 161. Protective devices Protective relays control the tripping of the circuit breakers surrounding the faulted part of the network Automatic operation, such as auto-re-closing or system restart Monitoring equipment which collects data on the system for post event analysis While the operating quality of these devices, and especially of protective relays, is always critical, different strategies are considered for protecting the different parts of the system. Very important equipment may have completely redundant and independent protective systems, while a minor branch distribution line may have very simple low-cost protection.
  • 162. There are three parts of protective devices: •Instrument transformer: current or potential (CT or VT) •Relay •Circuit breaker Advantages of protected devices with these three basic components include safety, economy, and accuracy. Safety: Instrument transformers create electrical isolation from the power system, and thus establishing a safer environment for personnel working with the relays. Economy: Relays are able to be simpler, smaller, and cheaper given lower-level relay inputs. Accuracy: Power system voltages and currents are accurately reproduced by instrument transformers over large operating ranges.
  • 163. Performance and design criteria for system-protection devices include reliability, selectivity, speed, cost, and simplicity. Reliability: Devices must function consistently when fault conditions occur, regardless of possibly being idle for months or years. Without this reliability, systems may result in high costly damages. Selectivity: Devices must avoid unwarranted, false trips. Speed: Devices must function quickly to reduce equipment damage and fault duration, with only very precise intentional time delays. Economy: Devices must provide maximum protection at minimum cost. Simplicity: Devices must minimize protection circuitry and equipment.
  • 164. Protective relays These are compact analog or digital networks, connected to various points of an electrical system, to detect abnormal conditions occurring within their assigned areas.  They initiate disconnection of the trouble area by circuit breakers. These relays range from the simple overload unit on house circuit breakers to complex systems used to protect extra high voltage power transmission lines. They operate on voltage, current, current direction, power factor, power, impedance, temperature. In all cases there must be a measurable difference between the normal or tolerable operation and the intolerable or unwanted condition.
  • 165.  System faults for which the relays respond are generally short circuits between the phase conductors, or between the phases and grounds.  Some relays operate on unbalances between the phases, such as an open or reversed phase.  A fault in one part of the system affects all other parts. Therefore relay sand fuses throughout the power system must be coordinated to ensure the best quality of service to the loads and to avoid operation in the non-faulted areas unless the trouble is not adequately cleared in a specified time. 165
  • 166. 1.10 Types of Tariff 166
  • 167. The tariff is the rate at which the electrical energy is sold. There are various types of tariffs followed in the market. This post will give the brief idea about different tariff types.
  • 168. VARIOUS TYPES OF TARIFFS 1- Simple Tariff 2- Flat rate Tariff 3 - Block Rate Tariff 4 - Two Part Tariff/Maximum Demand Tariff 5 - Power Factor Tariff 6 – Three Part Tariff
  • 169. SIMPLE TARIFF The tariff which has a fixed rate, per unit energy consumed. ADVANTAGES :- This is simplest tariff. :- Even a simple consumer can understand it. DISADVANTAGES :- There is no differentiation between small and big consumers. :- The cost is per unit is very high.
  • 170. FLAT RATE TARIFF It is a type in which different consumers have different rates. A discrimination exists between small and large consumers. ADVANTAGES :- Large consumers are encouraged in this type. :- This tariff is simple and easy to calculate. DISADVANTAGES :- Different energy meters are required to be installed at consumer’s premises. :- The supplier doesn’t get any return for the connection given to the consumer If he doesn’t consume any energy in a particular period.
  • 171. BLOCK RATE TARIFF When the total energy consumed is divided into blocks for the purpose of tariff. ADVANTAGES :- The consumers are encouraged to consume more energy. This increase load factor of the system and the cost of generation is reduced. DISADVANTAGES :- This doesn’t take into account the maximum demand of the consumer.
  • 172. TWO PART TARIFF This is the system in which the tariff is related to the consumer’s maximum demand, and then, to his consumption of energy. ADVANTAGES :-This tariff is very suitable for industrial consumers who have higher maximum demand. :-It takes into considerations the maximum demand of the consumer. DISADVANTAGES :-A maximum demand indicator is to be installed at the premises for assessing the maximum demand of the consumer. :-The consumer has to pay some fixed amount per kw whether he consumes energy or not in a particular period.
  • 173. POWER FACTOR TARIFF The tariff in which the power factor of the consumer is taken into consideration. In this there are following types:- (i)KVA maximum demand tariff (ii)Sliding scale tariff/Average P.F Tariff (iii)KWh and KVAR Tariff
  • 174. THREE PART TARIFF The tariff which charges a consumer in 3 parts. First Part This represents fixed charge which includes interest and depreciation. Second Part This is a semi-fixed charge which is calculated on per kw of the maximum demand. Third Part This is a running charge which is calculated per kwh of power consumed by the consumer
  • 175. 1.11 Power Factor Improvement 175
  • 176. Active power actually performs the work and is measured in kW. This is also what is read on a wattmeter. Reactive power sustains the electromagnetic field and is measured in kvar.
  • 177.  Power Factor is the measurement of how effectively your business uses the electricity supplied to your site  Ideal Power Factor is unity or 1, anything less than 1 means that extra power is required to achieve the necessary tasks. The higher the power factor, the more effectively electrical power is being used and vice versa.  Low Power Factor is expensive and inefficient, with many utility companies charging extra, (reactive power charge), for sites with a poor power factor  Low Power Factor can also reduce the capacity of your electrical distribution system by increasing current flow and causing voltage drops.
  • 178. Power Factor is the ratio of true power to apparent power Power Factor = KW KVA
  • 179.  Power Factor Correction is the term given to a technology to restore Power Factor to as close to unity as economically viable  This can be achieved by adding Power Factor Correction capacitors to the distribution system which provide or compensate for the Reactive Power demand of the inductive load, and thus reduce the burden on the supply  Capacitors work as reactive current generators “providing” needed reactive power (KVAr) into the power supply  By supplying their own source of reactive power, the industrial user frees the utility from having to supply it, and therefore the total amount of apparent power supplied by the utility will be less.  Power Factor Correction Capacitors reduce the total current drawn from the distribution system and subsequently increase the system’s capacity by raising the Power Factor level.
  • 180.
  • 181.  A reduction in electricity charges  Elimination of utility power factor penalties, which can increase electrical bills by up to 20%  Reduction in I²R losses of transformers and distribution equipment  Prolonging the life of equipment from reduced heat in cables, switchgear, transformers and alternators  Reduced voltage drop in cables, allowing the same cable to supply a larger motor and improving the starting of motors at the end of the long cable runs
  • 182.
  • 183.