IV. Three-Phase Transfomers
The majority of the power generation/distribution systems in the world are 3-
phase systems. The transformers for such circuits can be constructed either as a
3-phase bank of independent identical transformers (can be replaced
independently) or as a single transformer wound on a single 3-legged core
(lighter, smaller, cheaper and slightly more efficient).
Three-Phase Transfomers
We assume that any single transformer in a 3-phase transformer (bank) behaves
exactly as a single-phase transformer. The impedance, voltage regulation,
efficiency, and other calculations for 3-phase transformers are done on a per-
phase basis, using the techniques studied previously for single-phase
transformers.
Four possible connections for a 3-phase transformer bank are:
1) Y-Y
2) Y-Δ
3) Δ-Δ
4) Δ-Y
Common three-phase transformer connections. The transformer
windings are indicated by the heavy lines.
1) Y-Y connection
The primary voltage on each phase
of the transformer is:
3
LP
P
V
V 
The secondary phase voltage is:
3
LS S
V V

The overall voltage ratio is:
3
3
P
LP
LS S
V
V
a
V V


 
The Y-Y connection is seldom used as it has two very serious problems:
a) If loads on one of the transformer circuits are unbalanced, the voltages on
the phases of the transformer can become severely unbalanced.
b) The third harmonic issue. The voltages in any phase of an Y-Y transformer are
120 apart from the voltages in any other phase. However, the third-harmonic
components of each phase will be in phase with each other. Nonlinearities in
the transformer core always lead to generation of third harmonic! These
components will add up resulting in large (can be even larger than the
fundamental component) third harmonic component.
Both problems can be solved by one of two techniques:
i) Solidly ground the neutral of the transformers (especially, the primary
side). The third harmonic will flow in the neutral and a return path will be
established for the unbalanced loads.
ii) Add a third Δ-connected winding. A circulating current at the third
harmonic will flow through it suppressing the third harmonic in other windings.
2) Y-Δ connection
The primary voltage on each phase
of the transformer is:
3
LP
P
V
V 
The secondary phase voltage is:
The overall voltage ratio is:
LS S
V V

3
3
P
LP
LS S
V
V
a
V V


 
The Y-Δ connection has no problem with third harmonic components, since
they are consumed in a circulating current on the Δ side. It is also more
stable to unbalanced loads since the Δ partially redistributes any imbalance
that occurs.
One problem associated with this connection is that the secondary voltage
is shifted by 30 with respect to the primary voltage. This can cause
problems when paralleling 3-phase transformers since transformers
secondary voltages must be in-phase to be paralleled. Therefore, we must
pay attention to these shifts.
In the U.S., it is common (actually it is a standard now) to make the
secondary voltage to lag the primary voltage. The connection shown in the
previous slide will do it.
The Y-Δ connection is generally used in stepping down from a high
voltage to a medium or low voltage. One reason is that a neutral is thereby
provided for grounding on the high-voltage side, a procedure which can be
shown to be desirable in many cases.
3) Δ-Y connection
The primary voltage on each phase
of the transformer is:
The secondary phase voltage is:
The overall voltage ratio is:
P LP
V V
 
3
LS S
V V

3 3
P
LP
LS S
V
V a
V V


 
The Δ-Y connection has the same advantages and the same phase shift as the
Y-Δ connection.
The Δ-Y connection is commonly used for stepping up to a high voltage.
4) Δ-Δ connection
The primary voltage on each phase
of the transformer is:
The secondary phase voltage is:
The overall voltage ratio is:
P LP
V V
 
LS S
V V

P
LP
LS S
V
V
a
V V


 
The Δ-Δ connection has no phase shift and no problems with unbalanced
loads or harmonics.
The Δ-Δ connection has the advantage that one transformer can be
removed for repair or maintenance while the remaining tow continue to
function as a three-phase bank with the rating reduced to 58% of that of the
original bank; this is known as the open-delta, or V, connection.
Analyzing Three-Phase Transformer Circuits
1. For fixed line-to-line voltages and total fixed kVA rating of the 3-phase
transformer, the kVA rating of each transformer is 1/3rd of total kVA rating
of bank regardless of the connection type.
2. Voltage and current values of individual transformers depend on connection
type (Y or Δ)
3. Circuit computations involving 3-phase transformer banks can be made by
dealing with only one phase and recognizing that condition are same for
other 3 phases except a 120 phase displacement
4. Computations are carried out on a per-phase Y line-to-neutral basis, since
the transformer impedances in a Y-connected can be added directly in series
with transmission line impedance
5. The impedances of transmission lines can be referred from one side to other
by the use of square of ideal line-to-line voltage ratio of the bank.
6. In dealing with Y-Δ or Δ-Y banks, all quantities should be referred to Y-
connected side for simplicity
7. In dealing with Δ-Δ banks in series with transmission lines, it is convenient
to replace Δ-connected transformer impedance into Y-connected ones.
The per-unit system applies to the 3-phase transformers as well as to single-
phase transformers.
Per-Unit System for Three-Phase Transfomers
Therefore, the base phase current and impedance of the transformer are
1 ,
3
base
base
S
S  
1 ,
,
,
,
3
base
b
base
ba
as
s
ba
e
e
se
S
V
S
I
V



 
 
   
2
,
1
,
,
2
3
base
bas
base
base
base
e
V
Z
S
V
S
 

 
If the total base VA value of the transformer bank is Sbase, the base VA value of
one of the transformers will be
The line quantities on 3-phase transformer banks can also be represented in per-
unit system.
, ,
L base base
V V

If the windings are in Y: , ,
3
L base base
V V

And the base line current in a 3-phase transformer bank is:
,
,
3
base
L base
L base
S
I
V

The application of the per-unit system to 3-phase transformer problems is similar
to its application in single-phase situations.
The voltage regulation of the transformer bank is the same.
If the windings are in Δ:
Ex 1. A 50 kVA, 13800/208V Δ-Y transformer has a resistance of 1% and a
reactance of 7% per unit.
a) What is the transformer’s phase impedance referred to the high voltage side?
b) What is the transformer’s voltage regulation at full load and 0.8 pf lagging,
using the calculated high-side impedance?
c) What is the transformer’s voltage regulation under the same conditions, using
the per-unit system?
a) The high-voltage side of the transformer has the base voltage 13 800 V and a
base apparent power of 50 kVA. Since the primary side is Δ-connected, its
phase voltage and the line voltage are the same.
The base impedance is:
   
2 2
,
3 3 13800
11426
50 000
base
base
base
V
Z
S
 
    

The per-unit impedance of the transformer is:
Therefore, the high-side impedance in ohms is:
b) The voltage regulation of a 3-phase transformer equals to a voltage regulation
of a single transformer:
, 0.01 0.07
eq pu
Z j pu
  
 
, 0.01 0.07 11426 114 800
eq eq pu base
Z Z Z j j
       
100%
P S
S
V aV
VR
aV
 


 
The rated phase current on the primary side can be found as:
50 000
1.208
3 3 13800
S
I A
V



   
 
The rated phase voltage on the secondary of the transformer is
When referred to the primary (high-voltage) side, this voltage becomes
Assuming that the transformer secondary winding is working at the rated voltage
and current, the resulting primary phase voltage is
The voltage regulation, therefore, is
208
120
3
S
V V
   
' 13800
S S
V aV V
 
   
1 1
13800 0 114.2 1.208 cos ( 0.8) 800 1.208 cos ( 0.8)
14490 690.3 14506 2.73
P S eq eq
V aV R I jX I j
j V
   
 
              
      
14 506 13800
100% 100% 5.1%
13800
P S
S
V aV
VR
aV
 

   
    

c) In the per-unit system, the output voltage is 10, and the current is
1  cos-1(-0.8). Therefore, the input voltage is
Thus, the voltage regulation in per-unit system will be
1 1
1 0 0.01 1 cos (0.8) 0.07 1 cos (0.8) 1.051 2.73
P
V j

 
          
1.051 1.0
100% 5.1%
1.0
VR

  
The voltage regulation in per-unit system is the same as computed in volts…
Ex 2. Three 2400:240V single-phase transformers connected in Δ-Δ and supplied
with power through a 3-phase feeder (i.e. cable) connected at high-voltage side
whose reactance is j0.8 /phase. The equivalent reactance of each transformer
referred to high-voltage side is j1.82 /phase. Other circuit resistances are
negligible. At its sending end (i.e. primary-side), the feeder is connected to the
secondary terminals of a Y-Δ connected 3-phase transformer whose rating is
500kVA 24000:2400V. The equivalent reactance of sending end transformer is
j2.76/phase referred to 2400V side. The voltage applied to primary of the
sending end transformer is 24kV. A 3-phase short-circuit occurs at 240V terminals
of the receiving end transformer (i.e. load side). Compute the steady-state short-
circuit current in the feeder wires, primary of receiving end and actual value of the
short circuit current.

More Related Content

Similar to three_phase_transformers-1p protection concept.pdf

Three Phase Star Delta.pptx
Three Phase Star Delta.pptxThree Phase Star Delta.pptx
Three Phase Star Delta.pptxgyanendraGs1
 
1_Intro + Per Unit.pdf
1_Intro + Per Unit.pdf1_Intro + Per Unit.pdf
1_Intro + Per Unit.pdfLiewChiaPing
 
unit-1-Three phase circuits and power systems.pdf
unit-1-Three phase circuits and power systems.pdfunit-1-Three phase circuits and power systems.pdf
unit-1-Three phase circuits and power systems.pdfdeepaMS4
 
Power electronics Uncontrolled Rectifiers - Diode Rectifiers
Power electronics   Uncontrolled Rectifiers - Diode RectifiersPower electronics   Uncontrolled Rectifiers - Diode Rectifiers
Power electronics Uncontrolled Rectifiers - Diode RectifiersBurdwan University
 
Short Circuit Calculation Symmetrical & Asymmetrical Fault Currents ?
Short Circuit Calculation Symmetrical & Asymmetrical Fault Currents ?Short Circuit Calculation Symmetrical & Asymmetrical Fault Currents ?
Short Circuit Calculation Symmetrical & Asymmetrical Fault Currents ?Power System Operation
 
per_unit_system.pptx
per_unit_system.pptxper_unit_system.pptx
per_unit_system.pptxPaylamKanal
 
Three phase circuits
Three phase circuitsThree phase circuits
Three phase circuitsEkeeda
 
Symmetrical components in transient regime
Symmetrical components in transient regimeSymmetrical components in transient regime
Symmetrical components in transient regimegaonioni
 
CHAPTER 3 - Three Phase Network.ppt
CHAPTER 3 - Three Phase Network.pptCHAPTER 3 - Three Phase Network.ppt
CHAPTER 3 - Three Phase Network.pptLiewChiaPing
 
Parall Operation Transformers
Parall Operation TransformersParall Operation Transformers
Parall Operation TransformersSatish Pydimarla
 
Three phase delta connection
Three phase delta connectionThree phase delta connection
Three phase delta connectionMayur Ekhande
 
4.three phase circuits
4.three phase circuits 4.three phase circuits
4.three phase circuits Ekeeda
 
Sc and oc test on transformer
Sc and oc test on transformerSc and oc test on transformer
Sc and oc test on transformerPooja Dubey
 
Transformer part-1
Transformer part-1Transformer part-1
Transformer part-1NizarTayem2
 
Single and three phase Transformers
Single and three phase TransformersSingle and three phase Transformers
Single and three phase TransformersMohammed Waris Senan
 

Similar to three_phase_transformers-1p protection concept.pdf (20)

Three Phase Star Delta.pptx
Three Phase Star Delta.pptxThree Phase Star Delta.pptx
Three Phase Star Delta.pptx
 
Transformers TR.pptx
Transformers TR.pptxTransformers TR.pptx
Transformers TR.pptx
 
1_Intro + Per Unit.pdf
1_Intro + Per Unit.pdf1_Intro + Per Unit.pdf
1_Intro + Per Unit.pdf
 
unit-1-Three phase circuits and power systems.pdf
unit-1-Three phase circuits and power systems.pdfunit-1-Three phase circuits and power systems.pdf
unit-1-Three phase circuits and power systems.pdf
 
Lecture 3
Lecture 3Lecture 3
Lecture 3
 
Power electronics Uncontrolled Rectifiers - Diode Rectifiers
Power electronics   Uncontrolled Rectifiers - Diode RectifiersPower electronics   Uncontrolled Rectifiers - Diode Rectifiers
Power electronics Uncontrolled Rectifiers - Diode Rectifiers
 
Short Circuit Calculation Symmetrical & Asymmetrical Fault Currents ?
Short Circuit Calculation Symmetrical & Asymmetrical Fault Currents ?Short Circuit Calculation Symmetrical & Asymmetrical Fault Currents ?
Short Circuit Calculation Symmetrical & Asymmetrical Fault Currents ?
 
Transformer 2
Transformer 2Transformer 2
Transformer 2
 
Transformer 2
Transformer 2Transformer 2
Transformer 2
 
per_unit_system.pptx
per_unit_system.pptxper_unit_system.pptx
per_unit_system.pptx
 
Three phase circuits
Three phase circuitsThree phase circuits
Three phase circuits
 
Symmetrical components in transient regime
Symmetrical components in transient regimeSymmetrical components in transient regime
Symmetrical components in transient regime
 
CHAPTER 3 - Three Phase Network.ppt
CHAPTER 3 - Three Phase Network.pptCHAPTER 3 - Three Phase Network.ppt
CHAPTER 3 - Three Phase Network.ppt
 
Parall Operation Transformers
Parall Operation TransformersParall Operation Transformers
Parall Operation Transformers
 
Three phase delta connection
Three phase delta connectionThree phase delta connection
Three phase delta connection
 
4.three phase circuits
4.three phase circuits 4.three phase circuits
4.three phase circuits
 
Shazab
ShazabShazab
Shazab
 
Sc and oc test on transformer
Sc and oc test on transformerSc and oc test on transformer
Sc and oc test on transformer
 
Transformer part-1
Transformer part-1Transformer part-1
Transformer part-1
 
Single and three phase Transformers
Single and three phase TransformersSingle and three phase Transformers
Single and three phase Transformers
 

Recently uploaded

UNIT - IV - Air Compressors and its Performance
UNIT - IV - Air Compressors and its PerformanceUNIT - IV - Air Compressors and its Performance
UNIT - IV - Air Compressors and its Performancesivaprakash250
 
Booking open Available Pune Call Girls Koregaon Park 6297143586 Call Hot Ind...
Booking open Available Pune Call Girls Koregaon Park  6297143586 Call Hot Ind...Booking open Available Pune Call Girls Koregaon Park  6297143586 Call Hot Ind...
Booking open Available Pune Call Girls Koregaon Park 6297143586 Call Hot Ind...Call Girls in Nagpur High Profile
 
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...ranjana rawat
 
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...Christo Ananth
 
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130Suhani Kapoor
 
Call Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur Escorts
Call Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur EscortsCall Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur Escorts
Call Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur High Profile
 
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escortsranjana rawat
 
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur High Profile
 
UNIT-III FMM. DIMENSIONAL ANALYSIS
UNIT-III FMM.        DIMENSIONAL ANALYSISUNIT-III FMM.        DIMENSIONAL ANALYSIS
UNIT-III FMM. DIMENSIONAL ANALYSISrknatarajan
 
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...Christo Ananth
 
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...ranjana rawat
 
result management system report for college project
result management system report for college projectresult management system report for college project
result management system report for college projectTonystark477637
 
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...Soham Mondal
 
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escortsranjana rawat
 
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete RecordCCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete RecordAsst.prof M.Gokilavani
 
247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).ppt
247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).ppt247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).ppt
247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).pptssuser5c9d4b1
 
Microscopic Analysis of Ceramic Materials.pptx
Microscopic Analysis of Ceramic Materials.pptxMicroscopic Analysis of Ceramic Materials.pptx
Microscopic Analysis of Ceramic Materials.pptxpurnimasatapathy1234
 
UNIT-V FMM.HYDRAULIC TURBINE - Construction and working
UNIT-V FMM.HYDRAULIC TURBINE - Construction and workingUNIT-V FMM.HYDRAULIC TURBINE - Construction and working
UNIT-V FMM.HYDRAULIC TURBINE - Construction and workingrknatarajan
 
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...Dr.Costas Sachpazis
 
Processing & Properties of Floor and Wall Tiles.pptx
Processing & Properties of Floor and Wall Tiles.pptxProcessing & Properties of Floor and Wall Tiles.pptx
Processing & Properties of Floor and Wall Tiles.pptxpranjaldaimarysona
 

Recently uploaded (20)

UNIT - IV - Air Compressors and its Performance
UNIT - IV - Air Compressors and its PerformanceUNIT - IV - Air Compressors and its Performance
UNIT - IV - Air Compressors and its Performance
 
Booking open Available Pune Call Girls Koregaon Park 6297143586 Call Hot Ind...
Booking open Available Pune Call Girls Koregaon Park  6297143586 Call Hot Ind...Booking open Available Pune Call Girls Koregaon Park  6297143586 Call Hot Ind...
Booking open Available Pune Call Girls Koregaon Park 6297143586 Call Hot Ind...
 
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
 
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
 
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
 
Call Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur Escorts
Call Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur EscortsCall Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur Escorts
Call Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur Escorts
 
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
 
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
 
UNIT-III FMM. DIMENSIONAL ANALYSIS
UNIT-III FMM.        DIMENSIONAL ANALYSISUNIT-III FMM.        DIMENSIONAL ANALYSIS
UNIT-III FMM. DIMENSIONAL ANALYSIS
 
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
 
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
 
result management system report for college project
result management system report for college projectresult management system report for college project
result management system report for college project
 
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
 
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
 
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete RecordCCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
 
247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).ppt
247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).ppt247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).ppt
247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).ppt
 
Microscopic Analysis of Ceramic Materials.pptx
Microscopic Analysis of Ceramic Materials.pptxMicroscopic Analysis of Ceramic Materials.pptx
Microscopic Analysis of Ceramic Materials.pptx
 
UNIT-V FMM.HYDRAULIC TURBINE - Construction and working
UNIT-V FMM.HYDRAULIC TURBINE - Construction and workingUNIT-V FMM.HYDRAULIC TURBINE - Construction and working
UNIT-V FMM.HYDRAULIC TURBINE - Construction and working
 
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
 
Processing & Properties of Floor and Wall Tiles.pptx
Processing & Properties of Floor and Wall Tiles.pptxProcessing & Properties of Floor and Wall Tiles.pptx
Processing & Properties of Floor and Wall Tiles.pptx
 

three_phase_transformers-1p protection concept.pdf

  • 2. The majority of the power generation/distribution systems in the world are 3- phase systems. The transformers for such circuits can be constructed either as a 3-phase bank of independent identical transformers (can be replaced independently) or as a single transformer wound on a single 3-legged core (lighter, smaller, cheaper and slightly more efficient). Three-Phase Transfomers
  • 3. We assume that any single transformer in a 3-phase transformer (bank) behaves exactly as a single-phase transformer. The impedance, voltage regulation, efficiency, and other calculations for 3-phase transformers are done on a per- phase basis, using the techniques studied previously for single-phase transformers. Four possible connections for a 3-phase transformer bank are: 1) Y-Y 2) Y-Δ 3) Δ-Δ 4) Δ-Y
  • 4. Common three-phase transformer connections. The transformer windings are indicated by the heavy lines.
  • 5. 1) Y-Y connection The primary voltage on each phase of the transformer is: 3 LP P V V  The secondary phase voltage is: 3 LS S V V  The overall voltage ratio is: 3 3 P LP LS S V V a V V    
  • 6. The Y-Y connection is seldom used as it has two very serious problems: a) If loads on one of the transformer circuits are unbalanced, the voltages on the phases of the transformer can become severely unbalanced. b) The third harmonic issue. The voltages in any phase of an Y-Y transformer are 120 apart from the voltages in any other phase. However, the third-harmonic components of each phase will be in phase with each other. Nonlinearities in the transformer core always lead to generation of third harmonic! These components will add up resulting in large (can be even larger than the fundamental component) third harmonic component. Both problems can be solved by one of two techniques: i) Solidly ground the neutral of the transformers (especially, the primary side). The third harmonic will flow in the neutral and a return path will be established for the unbalanced loads. ii) Add a third Δ-connected winding. A circulating current at the third harmonic will flow through it suppressing the third harmonic in other windings.
  • 7. 2) Y-Δ connection The primary voltage on each phase of the transformer is: 3 LP P V V  The secondary phase voltage is: The overall voltage ratio is: LS S V V  3 3 P LP LS S V V a V V    
  • 8. The Y-Δ connection has no problem with third harmonic components, since they are consumed in a circulating current on the Δ side. It is also more stable to unbalanced loads since the Δ partially redistributes any imbalance that occurs. One problem associated with this connection is that the secondary voltage is shifted by 30 with respect to the primary voltage. This can cause problems when paralleling 3-phase transformers since transformers secondary voltages must be in-phase to be paralleled. Therefore, we must pay attention to these shifts. In the U.S., it is common (actually it is a standard now) to make the secondary voltage to lag the primary voltage. The connection shown in the previous slide will do it. The Y-Δ connection is generally used in stepping down from a high voltage to a medium or low voltage. One reason is that a neutral is thereby provided for grounding on the high-voltage side, a procedure which can be shown to be desirable in many cases.
  • 9. 3) Δ-Y connection The primary voltage on each phase of the transformer is: The secondary phase voltage is: The overall voltage ratio is: P LP V V   3 LS S V V  3 3 P LP LS S V V a V V    
  • 10. The Δ-Y connection has the same advantages and the same phase shift as the Y-Δ connection. The Δ-Y connection is commonly used for stepping up to a high voltage.
  • 11. 4) Δ-Δ connection The primary voltage on each phase of the transformer is: The secondary phase voltage is: The overall voltage ratio is: P LP V V   LS S V V  P LP LS S V V a V V    
  • 12. The Δ-Δ connection has no phase shift and no problems with unbalanced loads or harmonics. The Δ-Δ connection has the advantage that one transformer can be removed for repair or maintenance while the remaining tow continue to function as a three-phase bank with the rating reduced to 58% of that of the original bank; this is known as the open-delta, or V, connection.
  • 13. Analyzing Three-Phase Transformer Circuits 1. For fixed line-to-line voltages and total fixed kVA rating of the 3-phase transformer, the kVA rating of each transformer is 1/3rd of total kVA rating of bank regardless of the connection type. 2. Voltage and current values of individual transformers depend on connection type (Y or Δ) 3. Circuit computations involving 3-phase transformer banks can be made by dealing with only one phase and recognizing that condition are same for other 3 phases except a 120 phase displacement 4. Computations are carried out on a per-phase Y line-to-neutral basis, since the transformer impedances in a Y-connected can be added directly in series with transmission line impedance 5. The impedances of transmission lines can be referred from one side to other by the use of square of ideal line-to-line voltage ratio of the bank. 6. In dealing with Y-Δ or Δ-Y banks, all quantities should be referred to Y- connected side for simplicity 7. In dealing with Δ-Δ banks in series with transmission lines, it is convenient to replace Δ-connected transformer impedance into Y-connected ones.
  • 14. The per-unit system applies to the 3-phase transformers as well as to single- phase transformers. Per-Unit System for Three-Phase Transfomers Therefore, the base phase current and impedance of the transformer are 1 , 3 base base S S   1 , , , , 3 base b base ba as s ba e e se S V S I V            2 , 1 , , 2 3 base bas base base base e V Z S V S      If the total base VA value of the transformer bank is Sbase, the base VA value of one of the transformers will be
  • 15. The line quantities on 3-phase transformer banks can also be represented in per- unit system. , , L base base V V  If the windings are in Y: , , 3 L base base V V  And the base line current in a 3-phase transformer bank is: , , 3 base L base L base S I V  The application of the per-unit system to 3-phase transformer problems is similar to its application in single-phase situations. The voltage regulation of the transformer bank is the same. If the windings are in Δ:
  • 16. Ex 1. A 50 kVA, 13800/208V Δ-Y transformer has a resistance of 1% and a reactance of 7% per unit. a) What is the transformer’s phase impedance referred to the high voltage side? b) What is the transformer’s voltage regulation at full load and 0.8 pf lagging, using the calculated high-side impedance? c) What is the transformer’s voltage regulation under the same conditions, using the per-unit system? a) The high-voltage side of the transformer has the base voltage 13 800 V and a base apparent power of 50 kVA. Since the primary side is Δ-connected, its phase voltage and the line voltage are the same. The base impedance is:     2 2 , 3 3 13800 11426 50 000 base base base V Z S        
  • 17. The per-unit impedance of the transformer is: Therefore, the high-side impedance in ohms is: b) The voltage regulation of a 3-phase transformer equals to a voltage regulation of a single transformer: , 0.01 0.07 eq pu Z j pu      , 0.01 0.07 11426 114 800 eq eq pu base Z Z Z j j         100% P S S V aV VR aV       The rated phase current on the primary side can be found as: 50 000 1.208 3 3 13800 S I A V         
  • 18. The rated phase voltage on the secondary of the transformer is When referred to the primary (high-voltage) side, this voltage becomes Assuming that the transformer secondary winding is working at the rated voltage and current, the resulting primary phase voltage is The voltage regulation, therefore, is 208 120 3 S V V     ' 13800 S S V aV V       1 1 13800 0 114.2 1.208 cos ( 0.8) 800 1.208 cos ( 0.8) 14490 690.3 14506 2.73 P S eq eq V aV R I jX I j j V                             14 506 13800 100% 100% 5.1% 13800 P S S V aV VR aV             
  • 19. c) In the per-unit system, the output voltage is 10, and the current is 1  cos-1(-0.8). Therefore, the input voltage is Thus, the voltage regulation in per-unit system will be 1 1 1 0 0.01 1 cos (0.8) 0.07 1 cos (0.8) 1.051 2.73 P V j               1.051 1.0 100% 5.1% 1.0 VR     The voltage regulation in per-unit system is the same as computed in volts…
  • 20. Ex 2. Three 2400:240V single-phase transformers connected in Δ-Δ and supplied with power through a 3-phase feeder (i.e. cable) connected at high-voltage side whose reactance is j0.8 /phase. The equivalent reactance of each transformer referred to high-voltage side is j1.82 /phase. Other circuit resistances are negligible. At its sending end (i.e. primary-side), the feeder is connected to the secondary terminals of a Y-Δ connected 3-phase transformer whose rating is 500kVA 24000:2400V. The equivalent reactance of sending end transformer is j2.76/phase referred to 2400V side. The voltage applied to primary of the sending end transformer is 24kV. A 3-phase short-circuit occurs at 240V terminals of the receiving end transformer (i.e. load side). Compute the steady-state short- circuit current in the feeder wires, primary of receiving end and actual value of the short circuit current.