SlideShare a Scribd company logo
1 of 66
LENDI INSTITUTE OF ENGINEERING AND TECHNOLOGY
Jonnada, Andhra Pradesh- 535005
UNIT -I
CIRCUIT BREAKERS (PART II)
Presented by,
Dr. Rohit Babu, Associate Professor
Department of Electrical and Electronics Engineering
Syllabus
Department of Electrical and Electronics Engineering
Miniature Circuit Breaker (MCB)– Elementary principles of arc interruption–
Restriking Voltage and Recovery voltages– Restriking phenomenon - RRRV–
Average and Max. RRRV– Current chopping and Resistance switching–
Introduction to oil circuit breakers– Description and operation of Air Blast–
Vacuum and SF6 circuit breakers– CB ratings and specifications– Concept of
Auto reclosing.
Classification of Circuit Breakers
Department of Electrical and Electronics Engineering
• Classification Based on Voltage
i. Low Voltage Circuit Breaker (less than 1 kV)
ii. Medium Voltage Circuit Breaker (1 kV to 52 kV)
iii. High Voltage Circuit Breakers (66 kV to 220 kV)
iv. Extra High Voltage (EHV) Circuit Breaker (300 kV to 765 kV)
v. Ultra High Voltage (UHV) Circuit Breaker (above 765 kV)
• Classification Based on Location
Circuit breakers based on their location are classified as
i. Indoor type
ii. Outdoor type
Classification of Circuit Breakers
Department of Electrical and Electronics Engineering
• Classification Based on External Design
Circuit breakers can be classified into following categories depending on their external design.
i. Dead tank type
ii. Live-tank type
• Classification Based on Medium Used for Arc Quenching
Depending on the arc quenching medium employed, the following are important types of circuit
breakers
i. Air-break circuit breakers:
ii. Oil circuit breakers
iii. Air blast circuit breakers
iv. Sulphur hexafluoride (SF6) circuit breakers
v. Vacuum circuit breakers
Substation Circuit Breaker Testing Video 1
Department of Electrical and Electronics Engineering
Introduction to oil circuit breakers
Department of Electrical and Electronics Engineering
Oil circuit breaker is such type of circuit breaker which
used oil as a dielectric or insulating medium for arc
extinction.
The oil circuit breaker is divided into two categories
•Bulk Oil Circuit Breaker
•Low Oil Circuit Breaker
Construction of oil circuit breakers
Department of Electrical and Electronics Engineering
• Oil circuit breaker is very easy in
construction.
• It consists of current carrying contacts
enclosed in a strong, weather-tight earth
metal tank and the tank is filled with
transformer oil.
• The oil is both acts as an arc extinguishing
medium and as an insulator between the
live part and earth.
Working Principle of oil circuit breakers
Department of Electrical and Electronics Engineering
• During the normal operating
conditions, the contact of the oil
circuit breaker is closed and carry
the current.
• When the fault occurs in the
system, the contacts of the
breaker are moving apart, and an
arc is struck between the contacts.
Advantage and Disadvantage of oil circuit breakers
Department of Electrical and Electronics Engineering
Advantages of Oil as an Arc Quenching
• The oil has a high dielectric strength
and provides insulation between the
contact after the arc has been
extinguished.
• The oil used in circuit breaker provides
a small clearance between the
conductors and the earth components.
• The hydrogen gas is formed in the
tank which has a high diffusion rate
and good cooling properties.
Disadvantages of Oil as an Arc Quenching
• The oil used in oil circuit breaker is
inflammable and hence, cause a fire
hazard.
• There is a risk of formation of explosive
mixture with air.
• Due to decomposition of oil in the arc,
the carbon particles is generated which
polluted the oil and hence the dielectric
strength of the oil decreases.
Bulk Oil Circuit Breaker
Department of Electrical and Electronics Engineering
A breaker which uses a large quantity of oil for arc extinction is called a bulk oil circuit breaker.
• Such type of circuit breaker is also known as dead
tank-type circuit breaker because their tank is held at
ground potential.
• The quantity of oil requires in bulk oil circuit
breaker depends on the system voltage.
• If the output rating of the voltage is 110 KV, then it
requires 8 to 10 thousand kg of oil, and if their output
rating is 220 KV, then breakers need 50 thousand Kg of
oil.
Minimum Oil Circuit Breaker
Department of Electrical and Electronics Engineering
• In this type of circuit breaker minimum oil is used as
an arc quenching medium and it is mounted on a
porcelain insulator to insulate it from the earth.
• The arc chamber of such type of circuit breaker is
enclosed in a bakelised paper.
• The lower portion of this breaker is supported by the
porcelain and the upper porcelain enclosed the
contacts.
• There are two different designs of the arcing
chambers (i) axial and (ii) radial venting.
Air Circuit Breaker (or Air Blast Circuit Breaker)
Department of Electrical and Electronics Engineering
What is Air Circuit Breaker?
• An Air Circuit Breaker (also known as an Air Blast Circuit Breaker or ACB) is an automatically
operated electrical switch that uses air to protect an electrical circuit from damage caused by
excess current from an overload or short circuit.
• Its primary function is to interrupt current flow after a fault is detected.
• When this happens, an arc will appear between the contacts that have broken the circuit.
• Air circuit breakers use compressed air to blow out the arc, or alternatively, the contacts are
rapidly swung into a small sealed chamber, the escaping of the displaced air, thus blowing out
the arc.
Working Principle of Air Circuit Breaker
Department of Electrical and Electronics Engineering
This circuit breaker increases the arc voltage by mainly three different ways
i. It may increase the arc voltage by cooling the arc plasma. As the temperature of arc plasma is
decreased, the mobility of the particle in arc plasma is reduced; hence more voltage gradient is
required to maintain the arc.
ii. It may increase the arc voltage by lengthening the arc path. As the length of arc path is
increased, the resistance of the path is increased, and hence to maintain the same arc current
more voltage is required to be applied across the arc path. That means arc voltage is increased.
iii. Splitting up the arc into a number of series arcs also increases the arc voltage.
Operation of Air Circuit Breaker
Department of Electrical and Electronics Engineering
The operation of an ACB can be broken down into three steps:
1. The first objective is usually achieved by forcing the arc
into contact with as large an area as possible of insulating
material. Every air circuit breaker is fitted with a chamber
surrounding the contact. This chamber is called ‘arc chute’.
The arc is driven into it. If inside of the arc chute is suitably
shaped, and if the arc can be made conform to the shape,
the arc chute wall will help to achieve cooling. This type of
arc chute should be made from some kind of refractory
material. High temperature plastics reinforced with glass
fiber and ceramics are preferable materials for making arc
chute.
How Air Circuit Breaker Work? Video 2
Department of Electrical and Electronics Engineering
Operation of Air Circuit Breaker contd.
Department of Electrical and Electronics Engineering
2. The second objective that is lengthening the arc path, is achieved concurrently with fist objective.
If the inner walls of the arc chute is shaped in such a way that the arc is not only forced into close
proximity with it but also driven into a serpentine channel projected on the arc chute wall. The
lengthening of the arc path increases the arc resistance.
3. The third technique is achieved by using metal arc slitter inside the arc chute. The main arc chute
is divided into numbers of small compartments by using metallic separation plates. These
metallic separation plates are actually the arc splitters and each of the small compartments
behaves as individual mini arc chute. In this system the initial arc is split into a number of series
arcs, each of which will have its own mini arc chute. So each of the split arcs has its own cooling
and lengthening effect due to its own mini arc chute and hence individual split arc voltage
becomes high. These collectively, make the overall arc voltage, much higher than the
system voltage.
Air Circuit Breaker
Department of Electrical and Electronics Engineering
Advantages
1. There is no chance of fire hazard caused by oil.
2. The breaking speed of circuit breaker is much
higher during operation of air blast circuit breaker.
3. Arc quenching is much faster during operation of
air blast circuit breaker.
4. The duration of arc is same for all values of small
as well as high currents interruptions.
5. As the duration of arc is smaller, so lesser amount
of heat realized from arc to current carrying
contacts hence the service life of the contacts
becomes longer.
6. The stability of the system can be well maintained
as it depends on the speed of operation of circuit
breaker.
7. Requires much less maintenance compared to oil
circuit breaker.
Disadvantages
1. In order to have frequent operations, it is
necessary to have sufficiently high capacity
air compressor.
2. Frequent maintenance of compressor,
associated air pipes and automatic control
equipment's is also required.
3. Due to high speed current interruption
there is always a chance of high rate of rise
of re-striking voltage and current
chopping.
4. There also a chance of air pressure leakage
from air pipes junctions.
Air Circuit Breaker
Department of Electrical and Electronics Engineering
It can be sub divided further into three different categories.
1. Axial Blast ACB.
2. Axial Blast ACB with side moving contact.
3. Cross Blast ACB.
Air Circuit Breaker- Video 3
Department of Electrical and Electronics Engineering
Axial Blast Air Circuit Breaker
Department of Electrical and Electronics Engineering
• In axial blast ACB the moving contact is in
contact with fixed contact with the help of a
spring pressure as shown in the figure.
• There is a nozzle orifice in the fixed contact
which is blocked by tip of the moving contact
at normal closed condition of the breaker.
• When fault occurs, the high pressure air is
introduced into the arcing chamber.
Axial Blast ACB with Side Moving Contact
Department of Electrical and Electronics Engineering
• In this type of axial blast air circuit breaker
the moving contact is fitted over a piston
supported over a spring.
• In order to open the circuit breaker the air
is admitted into the arcing chamber when
pressure reaches to a predetermined value,
it presses down the moving contact; an arc
is drawn between the fixed and moving
contacts.
Cross Blast Air Circuit Breaker
Department of Electrical and Electronics Engineering
• The working principle of cross blast air circuit breaker is
quite simple.
• In this system of air blast circuit breaker the blast pipe is
fixed in perpendicular to the movement of moving
contact in the arcing chamber and on the opposite side of
the arcing chamber one exhaust chamber is also fitted at
the same alignment of blast pipe, so that the air comes
from blast pipe can straightly enter into exhaust chamber
through the contact gap of the breaker.
Vacuum Circuit Breaker or VCB and Vacuum
Interrupter
Department of Electrical and Electronics Engineering
• A vacuum circuit breaker is such kind of circuit
breaker where the arc quenching takes place in
vacuum.
• The technology is suitable for mainly medium
voltage application. For higher voltage vacuum
technology has been developed but not
commercially viable.
• The operation of opening and closing of current
carrying contacts and associated arc interruption
take place in a vacuum chamber in the breaker
which is called vacuum interrupter.
Advantages of Vacuum Circuit Breaker or VCB
Department of Electrical and Electronics Engineering
Service life of vacuum circuit breaker is much longer than other types of circuit breakers.
There is no chance of fire hazard like oil circuit breaker.
It is much environment friendly than SF6 Circuit breaker.
Beside that contraction of VCB is user-friendly.
Replacement of vacuum interrupter (VI) is much convenient.
Vacuum Circuit Breaker- Video 4
Department of Electrical and Electronics Engineering
Operation of Vacuum Circuit Breaker
Department of Electrical and Electronics Engineering
The main aim of any circuit breaker is to quench arc during
current zero crossing, by establishing high dielectric strength
in between the contacts so that reestablishment of arc after
current zero becomes impossible.
The dielectric strength of vacuum is eight times greater than
that of air and four times greater than that of SF6 gas. This
high dielectric strength makes it possible to quench a
vacuum arc within very small contact gap. For short contact
gap, low contact mass and no compression of the medium
the drive energy required in vacuum circuit breaker is
minimum.
Vacuum Circuit Breaker- Video 5
Department of Electrical and Electronics Engineering
SF6 Circuit Breaker Types and Operation of SF6
Circuit Breaker
Department of Electrical and Electronics Engineering
A circuit breaker in which sulphur hexafluoride gas or SF6 gas is used as the arc quenching
medium, known as an SF6 circuit breaker.
• Sulphur hexafluoride (SF6) has good dielectric strength and excellent arc quenching property.
• It is an inert, nontoxic, nonflammable and heavy gas.
• At atmospheric pressure, its dielectric strength is about 2.35 times that of air.
• At 3 atmospheric pressure its dielectric strength is more than that of transformer oil.
• It is an electronegative gas, i.e. it has high affinity for electrons.
• When a free electron comes in collision with a neutral gas molecule, the electron is absorbed by
the neutral gas molecule and a negative ion is formed.
• As the negative ions so formed are heavy they do not attain sufficient energy to contribute to
ionisation of the gas.
SF6 Circuit Breaker Types and Operation of SF6
Circuit Breaker
Department of Electrical and Electronics Engineering
• Under normal conditions, SF6 is chemically inert and it does not attack metals or glass.
• However, it decomposes to SF4, SF2, S2, F2, S and F at temperatures of the order of 1000°C.
• One major disadvantage of SF6 is its condensation at low temperature.
• SF6 gas because of its excellent insulating and arc-quenching properties has revolutionized the
design of high and extra high voltage (EHV) circuit breakers.
• SF6 gas because of its excellent insulating and arc-quenching properties has revolutionized the
design of high and extra high voltage (EHV) circuit breakers.
SF6 Circuit Breaker Video 6
Department of Electrical and Electronics Engineering
Properties of SF6 Gas
Department of Electrical and Electronics Engineering
The properties of SF6 gas can be divided as
(i) Physical properties
(ii) Chemical properties
(iii) Electrical properties
1. Physical Properties of SF6 Gas
The physical properties of SF6 gas are as follows:
(i) It is a colourless, odourless, non-toxic and non-inflammable gas.
(ii) Pure gas is not harmful to health.
(iii) It is in gas state at normal temperature and pressure.
(iv) It is heavy gas having density 5 times that of air at 20°C and atmospheric pressure.
Properties of SF6 Gas
Department of Electrical and Electronics Engineering
2. Chemical Properties of SF6 Gas
(i) It is chemically stable at atmospheric pressure and at temperatures up to 500°C.
(ii) It is a chemically inert gas.
(iii) Moisture is very harmful to the properties of this gas.
(iv) It is non-corrosive on all metals at ambient temperatures.
(v) It is an electronegative gas.
(vi) The products of decomposition of SF6 recombine in a short time after arc extinction.
Properties of SF6 Gas
Department of Electrical and Electronics Engineering
3. Electrical Properties of SF6 Gas
(i) Dielectric properties
Its dielectric strength at atmospheric pressure is 2.35 times that of air and 30% less than that of
dielectric oil used in oil circuit breakers. The excellent dielectric strength of SF6 gas is because of
electronegativity (electron attachment) property of SF6 molecules. In the attachment process, free
electrons collide with the neutral gas molecules to form negative ions by the following processes.
SF6 gas maintains high dielectric strength even after mixing with air. A mixture of 30% SF6 and 70%
air by volume has a dielectric strength twice that of air at the same pressure. Below 30% of SF6 by
volume, the dielectric strength falls sharply.
Properties of SF6 Gas
Department of Electrical and Electronics Engineering
Breakdown voltages of SF6,
air and dielectric oil as a
function of pressure
Properties of SF6 Gas
Department of Electrical and Electronics Engineering
(ii) Corona inception voltage
Corona inception voltage for SF6 in a non-uniform
electric field is also considerably higher than that for
air.
(iii) Dielectric constant
Because of being non-polar (i.e., dipole moment is
zero), the dielectric constant of SF6 is independent of
the frequency of the applied voltage. Further, the
dielectric constant changes by only 7% over a pressure
range of 0 to 22 atmospheres.
(iv) Arc-interrupting capacity
Current interrupting capacity of SF6, air and a
mixture of both gases
Type of SF6 Circuit Breaker
Department of Electrical and Electronics Engineering
The following are two principal types of SF6 circuit breakers:
(i) Double Pressure Type SF6 Circuit Breaker
This type of circuit breaker employs a double pressure system in which the gas from a high-pressure
compartment is released into the low-pressure compartment through a nozzle during the arc
extinction process.
(ii) Puffer-type (Single-pressure Type) SF6 Circuit Breaker
In this type of circuit breaker the SF6 gas is compressed by the moving cylinder system and is
released through a nozzle during arc extinction.
Type of SF6 Circuit Breaker
Department of Electrical and Electronics Engineering
Puffer-type SF6 circuit breaker
Advantages of SF6 Circuit Breakers
Department of Electrical and Electronics Engineering
(i) Low gas velocities and pressures employed in the SF6 circuit breakers prevent current chopping
and capacitive currents are interrupted without restriking.
(ii) These circuit breakers are compact, and have smaller overall dimensions and shorter contact gaps.
They have less number of interrupters and require less mantenance.
(iii) Since the gas is non-inflammable, and chemically stable and the products of decomposition are
not explosive, there is no danger of fire or explosion.
(iv) Since the same gas is recirculated in the circuit, the requirement of SF6 gas is small.
(v) The operation of the circuit breaker is noiseless because there is no exhaust to atmosphere as in
case of air blast circuit breakers
(vi) Because of excellent arc quenching properties of SF6, the arcing time is very short and hence the
contact erosion is less. The contacts can be run at higher temperatures without deterioration.
Advantages of SF6 Circuit Breakers
Department of Electrical and Electronics Engineering
(vii) Because of inertness of the SF6 gas, the contact corrosion is very small. Hence contacts do not
suffer oxidation.
(viii) The sealed construction of the circuit breaker avoids the contamination by moisture, dust, sand
etc. Hence the performance of the circuit breaker is not affected by the atmospheric conditions.
(ix) Tracking or insulation breakdown is eliminated, because there are no carbon deposits following
an arcing inside the system.
(x) Because of the excellent insulating properties of the SF6, contact gap is drastically reduced.
(xi) As these circuit breakers are totally enclosed and sealed from atmosphere, they are particularly
suitable for use in such environments where explosion hazards exist.
Disadvantages of SF6 Circuit Breakers
Department of Electrical and Electronics Engineering
(i) Problems of perfect sealing. There may be leakage of SF6 gas because of imperfect joints.
(ii) SF6 gas is suffocating to some extent. In case of leakage in the breaker tank, SF6 gas may lead to
suffocation of the operating personnel.
(iii) Arced SF6 gas is poisonous and should not be inhaled or let out.
(iv) Influx of moisture in the breaker is very harmful to SF6 circuit breaker. There are several cases of
failures because of it.
(v) There is necessity of mechanism of higher energy level for puffer-types SF6 circuit breakers. Lower
speeds due to friction, misalignment can cause failure of the breaker.
(vi) Internal parts should be cleaned thoroughly during periodic maintenance under clean and dry
environment.
(vii) Special facilities are required for transporting the gas, transferring the gas and maintaining the quality
of the gas. The performance and reliability of the SF6 circuit breaker is affected due to deterioration of
quality of the gas.
OPERATING MECHANISM
Department of Electrical and Electronics Engineering
To open and close the contacts of a circuit breaker, one of the following mechanisms is employed.
(1) Spring
(2) Solenoid
(3) Compressed air
• In SF6 circuit breaker, compressed air may be used for closing and a spring for opening or
compressed air for both closing as well as opening.
• Springs are very good for opening as their force is large in the beginning and gradually
decreases as the distance of travel of the moving contact increases.
 In small circuit breakers, the spring can be charged by hand.
 For large ones, it is charged by means of a motor.
OPERATING MECHANISM Contd.
Department of Electrical and Electronics Engineering
• Solenoids are very good for closing.
 The force of attraction increases when the distance between the contacts decreases.
 Compressed air is suitable for both closing as well as opening.
SELECTION OF CIRCUIT BREAKERS
Department of Electrical and Electronics Engineering
SELECTION OF CIRCUIT BREAKERS Contd.
Department of Electrical and Electronics Engineering
Circuit Breaker Ratings and Specifications
Department of Electrical and Electronics Engineering
Stress on circuit breakers:
Usually under abnormal conditions circuit breaker undergo large thermal and mechanical stress.
It is very important to understand the stress that the C.B. usually undergo before studying about
its Ratings and Specifications.
Thermal Stress:
During the short circuit or faulty conditions the current through the circuit breakers are about 2.5-
3 times that of rated current. Which can melt the metal having diameter of 10cm, According to
Joule’s law of heating.
Mechanical Stress:
This type of stress happens at the moving parts of the circuit breakers during its operation of
preventing fault currents.
Circuit Breaker Ratings and Specifications Contd.
Department of Electrical and Electronics Engineering
Duties of circuit breakers:
• It must be capable of opening on the occurrence of a fault and of clearing the fault.
• It must be capable of being closed on to a fault.
• It must be capable of carrying fault current for short time while another circuit breaker is
clearing the fault.
These duties are classified as follows:
1. Breaking capacity.
2. Making capacity.
3. Short-time capacity.
Other features of the duty include Rated voltage, Normal current rating, Operating duty and
Thermal parameters.
Circuit Breaker Ratings and Specifications Contd.
Department of Electrical and Electronics Engineering
1. Breaking Capacity
The breaking capacity of a circuit breaker is of two types.
(i) Symmetrical breaking capacity
(ii) Asymmetrical breaking capacity
Symmetrical Breaking Capacity
It is the rms value of the ac component of the fault current that the circuit breaker is capable of
breaking under specified conditions of recovery voltage.
Asymmetrical Breaking Capacity
It is the rms value of the total current comprising of both ac and dc components of the fault current
that the circuit breaker can break under specified conditions of recovery voltage.
Circuit Breaker Ratings and Specifications Contd.
Department of Electrical and Electronics Engineering
• The line X-X indicates the instant of contact separation.
• AB is the peak value of the ac component of the current
at this instant.
• Therefore, the symmetrical breaking current which is
the rms value of the ac component of the current at the
instant of contact separation is equal to current
AB/sqrt(2) .
• The section BC is the dc component of the short-circuit current at this instant.
• Therefore, asymmetrical breaking current is given by
Circuit Breaker Ratings and Specifications Contd.
Department of Electrical and Electronics Engineering
The breaking capacity of a circuit breaker is generally expressed in MVA. For a three-phase circuit
breaker, it is given by
2. Making Capacity
The capacity of a circuit breaker to be closed onto a short-circuit depends upon its ability to
withstand the effects of electromagnetic forces.
The multiplication by sqrt (2) is to obtain the peak value and again by 1.8 to take the dc component
into account.
Circuit Breaker Ratings and Specifications Contd.
Department of Electrical and Electronics Engineering
3. Short-time Current Rating
• The short-time current rating is based on thermal and mechanical limitations.
• The circuit breaker must be capable of carrying short-circuit current for a short period while
another circuit breaker (in series) is clearing the fault.
• The rated short-time current is the rms value (total current, both ac and dc components) of the
current that the circuit breaker can carry safely for a specified short period.
• According to British standard, the time is 3 seconds if the ratio of symmetrical breaking current
to rated normal current is equal to or less than 40 and 1 second if this ratio is more than 40.
Circuit Breaker Ratings and Specifications Contd.
Department of Electrical and Electronics Engineering
4. Rated Voltage, Current and Frequency
• In a power system, the voltage level at all points is not the same. It varies, depending upon the
system operating conditions. Due to this reason manufacturers have specified a rated maximum
voltage at which the operation of the circuit breaker is guaranteed.
• The rated current is the rms value of the current that a circuit breaker can carry continuously
without any temperature rise in excess of its specified limit.
• The rated frequency is also mentioned by the manufacture. It is the frequency at which the circuit
breaker has been designed to operate.
Circuit Breaker Ratings and Specifications Contd.
Department of Electrical and Electronics Engineering
5. Rated Operating Duty
This is mechanical duty requirement of circuit breaker operating mechanism. The sequence of rated
operating duty of a circuit breaker has been specified as
• O – t – CO - t' - CO
where O indicates opening operation of CB. CO represents closing operation immediately followed
by an opening operation without any intentional time delay. t' is time between two operations which
is necessary to restore the initial conditions and / or to prevent undue heating of conducting parts of
circuit breaker. t = 0.3 sec for circuit breaker intended for first auto re closing duty, if not otherwise
specified.
Circuit Breaker Ratings and Specifications Contd.
Department of Electrical and Electronics Engineering
•Suppose rated duty circle of a circuit breaker is 0 – 0.3 sec – CO – 3 min – CO. This means, an
opening operation of circuit breaker is followed by a closing operation after a time interval of 0.3 sec,
then the circuit breaker again opens without any intentional time delay. After this opening operation
the CB is again closed after 3 minutes and then instantly trips without any intentional time delay.
Thermal Parameters:
It is the maximum temperature rise that is permissible for the individual parts of the equipment.
It equals to the sum of the maximum temperature rise and the fixed temperature of the ambient air.
Rated interrupting time: It is the mean time for interruption of any current not exceeding the rated
interrupting current of the breaker.
Classification of Circuit Breakers
Department of Electrical and Electronics Engineering
The circuit breakers are classified by various ways. The different criteria for classification of
circuit breakers are as follows
1. Interrupting medium.
2. According to service.
3. Way of operation.
4. Action.
5. Method of control.
6. Way of mounting.
7. Tank construction.
8. Contacts.
Classification of Circuit Breakers Contd.
Department of Electrical and Electronics Engineering
According to Interrupting Medium: Again according to interrupting medium the circuit breakers
are classified as follows:
1. Air Circuit Breakers
2. Air Blast circuit breakers.
3. Oil Circuit breakers
4. Magnetic Blast circuit breakers.
According to service: Basically there are two types, they are:
1. Indoor Circuit Breaker.
2. Outdoor Circuit Breaker.
Classification of Circuit Breakers Contd.
Department of Electrical and Electronics Engineering
Depending upon Operation: According to this classification the types of circuit breakers are
1. Gravity Opened, Gravity Closed Circuit Breaker.
2. Horizontal Break Circuit Breaker.
Based on Action: This is nothing but,
1. Automatic C.B.
2. Manual C.B.
According to method of control:
According to the method of control, the circuit breaker may be controlled directly or it may be
operated remotely. The remote control may be manual, pneumatic or electrical.
Classification of Circuit Breakers Contd.
Department of Electrical and Electronics Engineering
The way of Mounting: According to this,
• Panel Mounted and,
• Rear of panel or remote from panel type.
Depending upon Tank construction:
• This classification is born only due to the liquid dielectric medium of separation so we can
classify it into “ A separate tank for each pole type or one tank for all poles type.
On basis of Contacts: On this type of classification the circuit breakers are classified into
1. Butt type contacts.
2. Wedge type.
3. Laminated flat contact and
4. Explosion chamber.
Auto Reclosing Scheme of Transmission System
Department of Electrical and Electronics Engineering
• The extra high voltage transmission lines transmit huge amount of electric power. Hence, it is
always desirable that the continuation of power flow through the lines should not be interrupted
for a long time.
• There may be a temporary or permanent fault in the lines.
• Temporary faults get automatically cleared, and these do not require any attempt for fault
rectification.
• It is normal practice by the operators that after each initial faulty tripping of the line, they close
the line.
• If the fault is transient, the line holds after the second attempt of closing the circuit breaker, but if
the fault persists, the protection system again trips the line and then it is declared as permanent
fault.
Auto Reclosing Scheme of Transmission
System Contd.
Department of Electrical and Electronics Engineering
We categorize the faults in electrical transmission system in three ways,
1. Transient Fault
2. Semi Permanent Fault
3. Permanent Fault
• The transient faults are those which automatically removed momentarily.
• Semi permanent faults are also transient in nature but there take few moments to remove.
• Semi-permanent faults may get occurred due to the falling of things on the live conductors.
• Semi-permanent faults get removed after the cause of faults is burnt away.
• During both of the above mentioned faults, line is tripped but the line can be restored if the
circuit breakers associated with the line are closed.
Numerical Example- 1
Department of Electrical and Electronics Engineering
1. A circuit breaker is rated at 1500 amps, 2000 MVA, 33 kV, 3 sec, 3- phase, oil circuit breaker.
Determine the rated normal current, breaking current, making current and short time rating
(current).
Ans: The rated normal current is 1500 amps.
Making current = 2.55 x Symmetrical
breaking current
If the symmetrical braking current capacity
of the breaker is 40 KA(RMS), the making
current of the breaker must be 2.55*40=102
KA(peak).
Numerical Example- 2
Department of Electrical and Electronics Engineering
2. A generator connected through a 3-cycle C.B. to a transformer is rated 10 MVA, 13.8 kV with
reactances of Xd″ = 10%, Xd′ = 15% and Xd = 100%. It is operating at no load and rated voltage when a
3-phase short circuit occurs between the breaker and the transformer. Determine (i) the sustained
short circuit current in the breaker; (ii) the initial symmetrical r.m.s. current in the breaker; (iii) the
maximum possible d.c. component of the short circuit current in the breaker; (iv) the momentary
current rating of the breaker; (v) the current to be interrupted by the breaker; and (vi) the
interrupting kVA.
Ans: (i) Since the steady reactance is 100%
The steady state short circuit MVA = 10 MVA
(ii) The initial symmetrical r.m.s. current is the current corresponding to sub-transient state
where the % reactance is 10.
Numerical Example- 2 Contd.
Department of Electrical and Electronics Engineering
(iii) The maximum possible d.c. component = peak value of the subtransient current = sqrt (2) × 4180
= 5910 amps.
(iv) Momentary current rating = 1.6 × 4180 = 6688 amps
(v) Since it is a 3-cycle breaker the current to be interrupted by the breaker = 1.2 × symmetrical
breaking current = 1.2 × 4180 = 5019 amps.
(vi) The interrupting kVA = sqrt (3) × 13.8 × 5016 = 119897 kVA or 119.897 MVA
Assignment 1.1
(Submission date: 14/09/2020)
Department of Electrical and Electronics Engineering
1. Explain how arc is initiated and sustained in a circuit breaker when the circuit breaker contacts
separate.
2. Discuss the principle of arc interruption in (i) an oil C.B.; and (ii) air blast circuit breaker.
3. Compare the performance and characteristics of (i) minimum oil breakers and air blast C.B.; (ii) air
blast C.B. and bulk oil C.B.
4. Explain the terms (i) Symmetrical breaking current; (ii) Asymmetrical breaking current; and (iii)
making current. Explain clearly how these currents can be determined from oscillograms taken
during short circuit tests on a 3-phase C.B.
5. Explain the terms (i) restriking voltage; (ii) recovery voltage; and (iii) RRRV. Derive an expression
for the restriking voltage in terms of system voltage, inductance and capacitance, across a C.B.
contact when a 3-phase fault takes place. Assume the neutral of the system to be solidly grounded.
Assignment 1.2
(Submission date: 21/09/2020)
Department of Electrical and Electronics Engineering
1. Differentiate between type tests and routine tests. What different tests are carried out to prove the
ability of a C.B.?
2. What are the requirements of the contact material for a vacuum circuit breaker? Why is current
chopping not a serious problem with such circuit breakers?
3. Describe the construction, principle of operation and application of a vacuum breaker.
4. Compare the performance of SF6 gas with air when used for circuit breaking.
5. Explain the process of ‘current chopping’ in SF6 breakers.
6. Describe the construction, principle of operation and application of SF6 circuit breaker. How does
this breaker essentially differ from an air blast breaker?
Assignment 1.3
(Submission date: 28/09/2020)
Department of Electrical and Electronics Engineering
1. In a short circuit test on a C.B. the following readings were obtained on a single frequency transient: (i)
Time to reach the peak restriking voltage 40 μsec; (ii) the peak restriking voltage 100 kV. Determine the
average RRRV and the frequency of oscillation.
2. An 11 kV, 50 Hz alternator is connected to a system which has inductance and capacitance per phase of 10
mH and 0.01 μF respectively. Determine (i) the maximum voltage across the breaker contacts; (ii) Frequency
of transient oscillation; (iii) the average RRRV; and (iv) the maximum RRRV.
3. A 66 kV, 50 Hz, 3-phase alternator has an earthed neutral. The inductance and capacitance per phase of the
system are 7 mH and 0.01 μF respectively. The short circuit test gave the following results: Power factor of
fault 0.25, fault current symmetrical recovery voltage is 90% of full line voltage. Assuming that the fault is
isolated from the ground, calculate the RRRV.
4. A circuit breaker is rated as 2500 A, 1500 MVA, 33 kV, 3 secs, 3-phase oil C.B. Determine the rated
symmetrical breaking current, rated making current, short time rating and rated service voltage.
Circuit Breaker: Part 2

More Related Content

What's hot

Switchgear presentation
Switchgear presentationSwitchgear presentation
Switchgear presentationNadir Baloch
 
protection of transmission lines[distance relay protection scheme]
protection of transmission lines[distance relay protection scheme]protection of transmission lines[distance relay protection scheme]
protection of transmission lines[distance relay protection scheme]moiz89
 
Power system protection topic 1
Power system protection topic 1Power system protection topic 1
Power system protection topic 1Siswoyo Edo
 
Unit 03 Protective relays
Unit  03 Protective relaysUnit  03 Protective relays
Unit 03 Protective relaysPremanandDesai
 
Transformer protection
Transformer protectionTransformer protection
Transformer protectionjawaharramaya
 
Measuring earth resistance
Measuring earth resistanceMeasuring earth resistance
Measuring earth resistanceBruno De Wachter
 
Generator protection calculations settings
Generator protection calculations settingsGenerator protection calculations settings
Generator protection calculations settingsmichaeljmack
 
power system transients.pptx
power system transients.pptxpower system transients.pptx
power system transients.pptxsameed4
 
Measurement of hvac (High Voltage Engineering )
Measurement  of  hvac (High Voltage Engineering )Measurement  of  hvac (High Voltage Engineering )
Measurement of hvac (High Voltage Engineering )Abhishek Choksi
 
basics of busbar and lbb protection
basics of busbar and lbb protection basics of busbar and lbb protection
basics of busbar and lbb protection Salim Palayi
 
ABCB(air blast circuit breaker)
ABCB(air blast circuit breaker)ABCB(air blast circuit breaker)
ABCB(air blast circuit breaker)AB Amit
 
Low Voltage Circuit Breaker
Low Voltage Circuit BreakerLow Voltage Circuit Breaker
Low Voltage Circuit BreakerAbdul Haseeb
 
HV testing of insulator
HV testing of insulatorHV testing of insulator
HV testing of insulatorJawad Ali
 

What's hot (20)

Switchgear presentation
Switchgear presentationSwitchgear presentation
Switchgear presentation
 
Insulation Resistance Test
Insulation Resistance TestInsulation Resistance Test
Insulation Resistance Test
 
protection of transmission lines[distance relay protection scheme]
protection of transmission lines[distance relay protection scheme]protection of transmission lines[distance relay protection scheme]
protection of transmission lines[distance relay protection scheme]
 
Power system protection topic 1
Power system protection topic 1Power system protection topic 1
Power system protection topic 1
 
Unit 03 Protective relays
Unit  03 Protective relaysUnit  03 Protective relays
Unit 03 Protective relays
 
Transformer protection
Transformer protectionTransformer protection
Transformer protection
 
Ac voltage
Ac voltageAc voltage
Ac voltage
 
Measuring earth resistance
Measuring earth resistanceMeasuring earth resistance
Measuring earth resistance
 
Generator protection calculations settings
Generator protection calculations settingsGenerator protection calculations settings
Generator protection calculations settings
 
power system transients.pptx
power system transients.pptxpower system transients.pptx
power system transients.pptx
 
Neutral grounding
Neutral groundingNeutral grounding
Neutral grounding
 
Circuit breaker
Circuit breakerCircuit breaker
Circuit breaker
 
Measurement of hvac (High Voltage Engineering )
Measurement  of  hvac (High Voltage Engineering )Measurement  of  hvac (High Voltage Engineering )
Measurement of hvac (High Voltage Engineering )
 
Protection and Switchgear
Protection and SwitchgearProtection and Switchgear
Protection and Switchgear
 
What's short circuit level
What's short circuit levelWhat's short circuit level
What's short circuit level
 
basics of busbar and lbb protection
basics of busbar and lbb protection basics of busbar and lbb protection
basics of busbar and lbb protection
 
ABCB(air blast circuit breaker)
ABCB(air blast circuit breaker)ABCB(air blast circuit breaker)
ABCB(air blast circuit breaker)
 
Low Voltage Circuit Breaker
Low Voltage Circuit BreakerLow Voltage Circuit Breaker
Low Voltage Circuit Breaker
 
Low voltage circuit breakers
Low voltage circuit breakersLow voltage circuit breakers
Low voltage circuit breakers
 
HV testing of insulator
HV testing of insulatorHV testing of insulator
HV testing of insulator
 

Similar to Circuit Breaker: Part 2

Protection & switchgear
Protection & switchgear   Protection & switchgear
Protection & switchgear johny renoald
 
Relay and switchgear protection
Relay and switchgear protectionRelay and switchgear protection
Relay and switchgear protectionBinit Das
 
Switchgear and protection engineering Lecture 03.pptx
Switchgear and protection engineering Lecture 03.pptxSwitchgear and protection engineering Lecture 03.pptx
Switchgear and protection engineering Lecture 03.pptxLoitaFredy
 
27 9759 types paper id 0027 (ed l)
27 9759 types paper id 0027 (ed l)27 9759 types paper id 0027 (ed l)
27 9759 types paper id 0027 (ed l)IAESIJEECS
 
Oil circuit breakers
Oil circuit breakersOil circuit breakers
Oil circuit breakersjawaharramaya
 
Circuit_breakers_I.ppt
Circuit_breakers_I.pptCircuit_breakers_I.ppt
Circuit_breakers_I.pptssuser4c4e76
 
Switchgear and protection lecture 2 type of circuit breakers and applications
Switchgear and protection lecture 2 type of circuit breakers and applicationsSwitchgear and protection lecture 2 type of circuit breakers and applications
Switchgear and protection lecture 2 type of circuit breakers and applicationsanuphowlader1
 
Air Blast & SF6 Circuit Breaker Design and Construction
Air Blast & SF6 Circuit Breaker Design and Construction Air Blast & SF6 Circuit Breaker Design and Construction
Air Blast & SF6 Circuit Breaker Design and Construction anuphowlader1
 
Circuitbreakers 140829234332-phpapp01
Circuitbreakers 140829234332-phpapp01Circuitbreakers 140829234332-phpapp01
Circuitbreakers 140829234332-phpapp01rana usman
 
Vaccum Circuit Breaker
Vaccum Circuit BreakerVaccum Circuit Breaker
Vaccum Circuit BreakerRAHUL-GOPU
 
Bulk oil and min oil circuit breaker
Bulk oil and min oil circuit breakerBulk oil and min oil circuit breaker
Bulk oil and min oil circuit breakerSAURAV DAYAL SING
 

Similar to Circuit Breaker: Part 2 (20)

Protection & switchgear
Protection & switchgear   Protection & switchgear
Protection & switchgear
 
Circuit Breakers
Circuit BreakersCircuit Breakers
Circuit Breakers
 
Relay and switchgear protection
Relay and switchgear protectionRelay and switchgear protection
Relay and switchgear protection
 
Circuit breaker
Circuit breakerCircuit breaker
Circuit breaker
 
Switchgear and protection engineering Lecture 03.pptx
Switchgear and protection engineering Lecture 03.pptxSwitchgear and protection engineering Lecture 03.pptx
Switchgear and protection engineering Lecture 03.pptx
 
CIRCUIT BREAKERS
CIRCUIT BREAKERSCIRCUIT BREAKERS
CIRCUIT BREAKERS
 
27 9759 types paper id 0027 (ed l)
27 9759 types paper id 0027 (ed l)27 9759 types paper id 0027 (ed l)
27 9759 types paper id 0027 (ed l)
 
Psg 5 2 mark
Psg 5 2 markPsg 5 2 mark
Psg 5 2 mark
 
Oil circuit breakers
Oil circuit breakersOil circuit breakers
Oil circuit breakers
 
Circuit breakers
Circuit breakersCircuit breakers
Circuit breakers
 
Circuit_breakers_I.ppt
Circuit_breakers_I.pptCircuit_breakers_I.ppt
Circuit_breakers_I.ppt
 
Air Circuit breaker
Air Circuit breakerAir Circuit breaker
Air Circuit breaker
 
air type circuit breaker
air type circuit breakerair type circuit breaker
air type circuit breaker
 
Switchgear and protection lecture 2 type of circuit breakers and applications
Switchgear and protection lecture 2 type of circuit breakers and applicationsSwitchgear and protection lecture 2 type of circuit breakers and applications
Switchgear and protection lecture 2 type of circuit breakers and applications
 
Air Blast & SF6 Circuit Breaker Design and Construction
Air Blast & SF6 Circuit Breaker Design and Construction Air Blast & SF6 Circuit Breaker Design and Construction
Air Blast & SF6 Circuit Breaker Design and Construction
 
Circuit Breaker
Circuit BreakerCircuit Breaker
Circuit Breaker
 
UNIT IV Circuit Breaker.pptx
UNIT IV Circuit Breaker.pptxUNIT IV Circuit Breaker.pptx
UNIT IV Circuit Breaker.pptx
 
Circuitbreakers 140829234332-phpapp01
Circuitbreakers 140829234332-phpapp01Circuitbreakers 140829234332-phpapp01
Circuitbreakers 140829234332-phpapp01
 
Vaccum Circuit Breaker
Vaccum Circuit BreakerVaccum Circuit Breaker
Vaccum Circuit Breaker
 
Bulk oil and min oil circuit breaker
Bulk oil and min oil circuit breakerBulk oil and min oil circuit breaker
Bulk oil and min oil circuit breaker
 

More from Dr. Rohit Babu

EDS Unit 1 (Part 1).pptx
EDS Unit 1 (Part 1).pptxEDS Unit 1 (Part 1).pptx
EDS Unit 1 (Part 1).pptxDr. Rohit Babu
 
EDS Unit 3 (Part 1).pptx
EDS Unit 3 (Part 1).pptxEDS Unit 3 (Part 1).pptx
EDS Unit 3 (Part 1).pptxDr. Rohit Babu
 
EDS Unit 4 (Protection and Coordination).pptx
EDS Unit 4 (Protection and Coordination).pptxEDS Unit 4 (Protection and Coordination).pptx
EDS Unit 4 (Protection and Coordination).pptxDr. Rohit Babu
 
EDS Unit 3 (Part 2).pptx
EDS Unit 3 (Part 2).pptxEDS Unit 3 (Part 2).pptx
EDS Unit 3 (Part 2).pptxDr. Rohit Babu
 
Electrical Distribution Systems: Syllabus
Electrical Distribution Systems: SyllabusElectrical Distribution Systems: Syllabus
Electrical Distribution Systems: SyllabusDr. Rohit Babu
 
PROTECTION AGAINST OVER VOLTAGE AND GROUNDING Part 2
PROTECTION AGAINST OVER VOLTAGE AND GROUNDING Part 2PROTECTION AGAINST OVER VOLTAGE AND GROUNDING Part 2
PROTECTION AGAINST OVER VOLTAGE AND GROUNDING Part 2Dr. Rohit Babu
 
PROTECTION AGAINST OVER VOLTAGE AND GROUNDING Part 1
PROTECTION AGAINST OVER VOLTAGE AND GROUNDING Part 1PROTECTION AGAINST OVER VOLTAGE AND GROUNDING Part 1
PROTECTION AGAINST OVER VOLTAGE AND GROUNDING Part 1Dr. Rohit Babu
 
STATIC AND DIGITAL RELAYS
STATIC AND DIGITAL RELAYSSTATIC AND DIGITAL RELAYS
STATIC AND DIGITAL RELAYSDr. Rohit Babu
 
FEEDER AND BUS BAR PROTECTION
FEEDER AND BUS BAR PROTECTION FEEDER AND BUS BAR PROTECTION
FEEDER AND BUS BAR PROTECTION Dr. Rohit Babu
 
PROTECTION AGAINST OVER VOLTAGE AND GROUNDING
PROTECTION AGAINST OVER VOLTAGE AND GROUNDINGPROTECTION AGAINST OVER VOLTAGE AND GROUNDING
PROTECTION AGAINST OVER VOLTAGE AND GROUNDINGDr. Rohit Babu
 
FEEDER AND BUS BAR PROTECTION
FEEDER AND BUS BAR PROTECTIONFEEDER AND BUS BAR PROTECTION
FEEDER AND BUS BAR PROTECTIONDr. Rohit Babu
 
Generator and Transformer Protection (PART 2)
Generator and Transformer Protection (PART 2)Generator and Transformer Protection (PART 2)
Generator and Transformer Protection (PART 2)Dr. Rohit Babu
 
Generator and Transformer Protection (PART 1)
Generator and Transformer Protection (PART 1)Generator and Transformer Protection (PART 1)
Generator and Transformer Protection (PART 1)Dr. Rohit Babu
 
Electromagnetic Protection (PART III)
Electromagnetic Protection (PART III)Electromagnetic Protection (PART III)
Electromagnetic Protection (PART III)Dr. Rohit Babu
 
Electromagnetic Protection (PART 2)
Electromagnetic Protection (PART 2)Electromagnetic Protection (PART 2)
Electromagnetic Protection (PART 2)Dr. Rohit Babu
 
SGP Syllabus as per JNTU-K
SGP Syllabus as per JNTU-KSGP Syllabus as per JNTU-K
SGP Syllabus as per JNTU-KDr. Rohit Babu
 
Electromagnetic Protection (PART I)
Electromagnetic Protection (PART I)Electromagnetic Protection (PART I)
Electromagnetic Protection (PART I)Dr. Rohit Babu
 

More from Dr. Rohit Babu (20)

EDS Unit 6.pptx
EDS Unit 6.pptxEDS Unit 6.pptx
EDS Unit 6.pptx
 
EDS Unit 5.pptx
EDS Unit 5.pptxEDS Unit 5.pptx
EDS Unit 5.pptx
 
EDS Unit 1 (Part 1).pptx
EDS Unit 1 (Part 1).pptxEDS Unit 1 (Part 1).pptx
EDS Unit 1 (Part 1).pptx
 
EDS Unit 3 (Part 1).pptx
EDS Unit 3 (Part 1).pptxEDS Unit 3 (Part 1).pptx
EDS Unit 3 (Part 1).pptx
 
EDS Unit 4 (Protection and Coordination).pptx
EDS Unit 4 (Protection and Coordination).pptxEDS Unit 4 (Protection and Coordination).pptx
EDS Unit 4 (Protection and Coordination).pptx
 
EDS Unit 3 (Part 2).pptx
EDS Unit 3 (Part 2).pptxEDS Unit 3 (Part 2).pptx
EDS Unit 3 (Part 2).pptx
 
HVDC Syllabus.pptx
HVDC Syllabus.pptxHVDC Syllabus.pptx
HVDC Syllabus.pptx
 
Electrical Distribution Systems: Syllabus
Electrical Distribution Systems: SyllabusElectrical Distribution Systems: Syllabus
Electrical Distribution Systems: Syllabus
 
PROTECTION AGAINST OVER VOLTAGE AND GROUNDING Part 2
PROTECTION AGAINST OVER VOLTAGE AND GROUNDING Part 2PROTECTION AGAINST OVER VOLTAGE AND GROUNDING Part 2
PROTECTION AGAINST OVER VOLTAGE AND GROUNDING Part 2
 
PROTECTION AGAINST OVER VOLTAGE AND GROUNDING Part 1
PROTECTION AGAINST OVER VOLTAGE AND GROUNDING Part 1PROTECTION AGAINST OVER VOLTAGE AND GROUNDING Part 1
PROTECTION AGAINST OVER VOLTAGE AND GROUNDING Part 1
 
STATIC AND DIGITAL RELAYS
STATIC AND DIGITAL RELAYSSTATIC AND DIGITAL RELAYS
STATIC AND DIGITAL RELAYS
 
FEEDER AND BUS BAR PROTECTION
FEEDER AND BUS BAR PROTECTION FEEDER AND BUS BAR PROTECTION
FEEDER AND BUS BAR PROTECTION
 
PROTECTION AGAINST OVER VOLTAGE AND GROUNDING
PROTECTION AGAINST OVER VOLTAGE AND GROUNDINGPROTECTION AGAINST OVER VOLTAGE AND GROUNDING
PROTECTION AGAINST OVER VOLTAGE AND GROUNDING
 
FEEDER AND BUS BAR PROTECTION
FEEDER AND BUS BAR PROTECTIONFEEDER AND BUS BAR PROTECTION
FEEDER AND BUS BAR PROTECTION
 
Generator and Transformer Protection (PART 2)
Generator and Transformer Protection (PART 2)Generator and Transformer Protection (PART 2)
Generator and Transformer Protection (PART 2)
 
Generator and Transformer Protection (PART 1)
Generator and Transformer Protection (PART 1)Generator and Transformer Protection (PART 1)
Generator and Transformer Protection (PART 1)
 
Electromagnetic Protection (PART III)
Electromagnetic Protection (PART III)Electromagnetic Protection (PART III)
Electromagnetic Protection (PART III)
 
Electromagnetic Protection (PART 2)
Electromagnetic Protection (PART 2)Electromagnetic Protection (PART 2)
Electromagnetic Protection (PART 2)
 
SGP Syllabus as per JNTU-K
SGP Syllabus as per JNTU-KSGP Syllabus as per JNTU-K
SGP Syllabus as per JNTU-K
 
Electromagnetic Protection (PART I)
Electromagnetic Protection (PART I)Electromagnetic Protection (PART I)
Electromagnetic Protection (PART I)
 

Recently uploaded

High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur High Profile
 
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur High Profile
 
GDSC ASEB Gen AI study jams presentation
GDSC ASEB Gen AI study jams presentationGDSC ASEB Gen AI study jams presentation
GDSC ASEB Gen AI study jams presentationGDSCAESB
 
Study on Air-Water & Water-Water Heat Exchange in a Finned Tube Exchanger
Study on Air-Water & Water-Water Heat Exchange in a Finned Tube ExchangerStudy on Air-Water & Water-Water Heat Exchange in a Finned Tube Exchanger
Study on Air-Water & Water-Water Heat Exchange in a Finned Tube ExchangerAnamika Sarkar
 
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptxDecoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptxJoão Esperancinha
 
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...Dr.Costas Sachpazis
 
IMPLICATIONS OF THE ABOVE HOLISTIC UNDERSTANDING OF HARMONY ON PROFESSIONAL E...
IMPLICATIONS OF THE ABOVE HOLISTIC UNDERSTANDING OF HARMONY ON PROFESSIONAL E...IMPLICATIONS OF THE ABOVE HOLISTIC UNDERSTANDING OF HARMONY ON PROFESSIONAL E...
IMPLICATIONS OF THE ABOVE HOLISTIC UNDERSTANDING OF HARMONY ON PROFESSIONAL E...RajaP95
 
ZXCTN 5804 / ZTE PTN / ZTE POTN / ZTE 5804 PTN / ZTE POTN 5804 ( 100/200 GE Z...
ZXCTN 5804 / ZTE PTN / ZTE POTN / ZTE 5804 PTN / ZTE POTN 5804 ( 100/200 GE Z...ZXCTN 5804 / ZTE PTN / ZTE POTN / ZTE 5804 PTN / ZTE POTN 5804 ( 100/200 GE Z...
ZXCTN 5804 / ZTE PTN / ZTE POTN / ZTE 5804 PTN / ZTE POTN 5804 ( 100/200 GE Z...ZTE
 
Coefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptxCoefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptxAsutosh Ranjan
 
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...Dr.Costas Sachpazis
 
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...ranjana rawat
 
Current Transformer Drawing and GTP for MSETCL
Current Transformer Drawing and GTP for MSETCLCurrent Transformer Drawing and GTP for MSETCL
Current Transformer Drawing and GTP for MSETCLDeelipZope
 
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escortsranjana rawat
 
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝soniya singh
 
College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service NashikCollege Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service NashikCall Girls in Nagpur High Profile
 
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escortsranjana rawat
 
What are the advantages and disadvantages of membrane structures.pptx
What are the advantages and disadvantages of membrane structures.pptxWhat are the advantages and disadvantages of membrane structures.pptx
What are the advantages and disadvantages of membrane structures.pptxwendy cai
 
Processing & Properties of Floor and Wall Tiles.pptx
Processing & Properties of Floor and Wall Tiles.pptxProcessing & Properties of Floor and Wall Tiles.pptx
Processing & Properties of Floor and Wall Tiles.pptxpranjaldaimarysona
 
Porous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writingPorous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writingrakeshbaidya232001
 

Recently uploaded (20)

High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
 
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
 
GDSC ASEB Gen AI study jams presentation
GDSC ASEB Gen AI study jams presentationGDSC ASEB Gen AI study jams presentation
GDSC ASEB Gen AI study jams presentation
 
Study on Air-Water & Water-Water Heat Exchange in a Finned Tube Exchanger
Study on Air-Water & Water-Water Heat Exchange in a Finned Tube ExchangerStudy on Air-Water & Water-Water Heat Exchange in a Finned Tube Exchanger
Study on Air-Water & Water-Water Heat Exchange in a Finned Tube Exchanger
 
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptxDecoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
 
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
 
IMPLICATIONS OF THE ABOVE HOLISTIC UNDERSTANDING OF HARMONY ON PROFESSIONAL E...
IMPLICATIONS OF THE ABOVE HOLISTIC UNDERSTANDING OF HARMONY ON PROFESSIONAL E...IMPLICATIONS OF THE ABOVE HOLISTIC UNDERSTANDING OF HARMONY ON PROFESSIONAL E...
IMPLICATIONS OF THE ABOVE HOLISTIC UNDERSTANDING OF HARMONY ON PROFESSIONAL E...
 
ZXCTN 5804 / ZTE PTN / ZTE POTN / ZTE 5804 PTN / ZTE POTN 5804 ( 100/200 GE Z...
ZXCTN 5804 / ZTE PTN / ZTE POTN / ZTE 5804 PTN / ZTE POTN 5804 ( 100/200 GE Z...ZXCTN 5804 / ZTE PTN / ZTE POTN / ZTE 5804 PTN / ZTE POTN 5804 ( 100/200 GE Z...
ZXCTN 5804 / ZTE PTN / ZTE POTN / ZTE 5804 PTN / ZTE POTN 5804 ( 100/200 GE Z...
 
Coefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptxCoefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptx
 
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
 
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
 
Current Transformer Drawing and GTP for MSETCL
Current Transformer Drawing and GTP for MSETCLCurrent Transformer Drawing and GTP for MSETCL
Current Transformer Drawing and GTP for MSETCL
 
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
 
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝
 
College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service NashikCollege Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
 
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
 
What are the advantages and disadvantages of membrane structures.pptx
What are the advantages and disadvantages of membrane structures.pptxWhat are the advantages and disadvantages of membrane structures.pptx
What are the advantages and disadvantages of membrane structures.pptx
 
Call Us -/9953056974- Call Girls In Vikaspuri-/- Delhi NCR
Call Us -/9953056974- Call Girls In Vikaspuri-/- Delhi NCRCall Us -/9953056974- Call Girls In Vikaspuri-/- Delhi NCR
Call Us -/9953056974- Call Girls In Vikaspuri-/- Delhi NCR
 
Processing & Properties of Floor and Wall Tiles.pptx
Processing & Properties of Floor and Wall Tiles.pptxProcessing & Properties of Floor and Wall Tiles.pptx
Processing & Properties of Floor and Wall Tiles.pptx
 
Porous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writingPorous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writing
 

Circuit Breaker: Part 2

  • 1. LENDI INSTITUTE OF ENGINEERING AND TECHNOLOGY Jonnada, Andhra Pradesh- 535005 UNIT -I CIRCUIT BREAKERS (PART II) Presented by, Dr. Rohit Babu, Associate Professor Department of Electrical and Electronics Engineering
  • 2. Syllabus Department of Electrical and Electronics Engineering Miniature Circuit Breaker (MCB)– Elementary principles of arc interruption– Restriking Voltage and Recovery voltages– Restriking phenomenon - RRRV– Average and Max. RRRV– Current chopping and Resistance switching– Introduction to oil circuit breakers– Description and operation of Air Blast– Vacuum and SF6 circuit breakers– CB ratings and specifications– Concept of Auto reclosing.
  • 3. Classification of Circuit Breakers Department of Electrical and Electronics Engineering • Classification Based on Voltage i. Low Voltage Circuit Breaker (less than 1 kV) ii. Medium Voltage Circuit Breaker (1 kV to 52 kV) iii. High Voltage Circuit Breakers (66 kV to 220 kV) iv. Extra High Voltage (EHV) Circuit Breaker (300 kV to 765 kV) v. Ultra High Voltage (UHV) Circuit Breaker (above 765 kV) • Classification Based on Location Circuit breakers based on their location are classified as i. Indoor type ii. Outdoor type
  • 4. Classification of Circuit Breakers Department of Electrical and Electronics Engineering • Classification Based on External Design Circuit breakers can be classified into following categories depending on their external design. i. Dead tank type ii. Live-tank type • Classification Based on Medium Used for Arc Quenching Depending on the arc quenching medium employed, the following are important types of circuit breakers i. Air-break circuit breakers: ii. Oil circuit breakers iii. Air blast circuit breakers iv. Sulphur hexafluoride (SF6) circuit breakers v. Vacuum circuit breakers
  • 5. Substation Circuit Breaker Testing Video 1 Department of Electrical and Electronics Engineering
  • 6. Introduction to oil circuit breakers Department of Electrical and Electronics Engineering Oil circuit breaker is such type of circuit breaker which used oil as a dielectric or insulating medium for arc extinction. The oil circuit breaker is divided into two categories •Bulk Oil Circuit Breaker •Low Oil Circuit Breaker
  • 7. Construction of oil circuit breakers Department of Electrical and Electronics Engineering • Oil circuit breaker is very easy in construction. • It consists of current carrying contacts enclosed in a strong, weather-tight earth metal tank and the tank is filled with transformer oil. • The oil is both acts as an arc extinguishing medium and as an insulator between the live part and earth.
  • 8. Working Principle of oil circuit breakers Department of Electrical and Electronics Engineering • During the normal operating conditions, the contact of the oil circuit breaker is closed and carry the current. • When the fault occurs in the system, the contacts of the breaker are moving apart, and an arc is struck between the contacts.
  • 9. Advantage and Disadvantage of oil circuit breakers Department of Electrical and Electronics Engineering Advantages of Oil as an Arc Quenching • The oil has a high dielectric strength and provides insulation between the contact after the arc has been extinguished. • The oil used in circuit breaker provides a small clearance between the conductors and the earth components. • The hydrogen gas is formed in the tank which has a high diffusion rate and good cooling properties. Disadvantages of Oil as an Arc Quenching • The oil used in oil circuit breaker is inflammable and hence, cause a fire hazard. • There is a risk of formation of explosive mixture with air. • Due to decomposition of oil in the arc, the carbon particles is generated which polluted the oil and hence the dielectric strength of the oil decreases.
  • 10. Bulk Oil Circuit Breaker Department of Electrical and Electronics Engineering A breaker which uses a large quantity of oil for arc extinction is called a bulk oil circuit breaker. • Such type of circuit breaker is also known as dead tank-type circuit breaker because their tank is held at ground potential. • The quantity of oil requires in bulk oil circuit breaker depends on the system voltage. • If the output rating of the voltage is 110 KV, then it requires 8 to 10 thousand kg of oil, and if their output rating is 220 KV, then breakers need 50 thousand Kg of oil.
  • 11. Minimum Oil Circuit Breaker Department of Electrical and Electronics Engineering • In this type of circuit breaker minimum oil is used as an arc quenching medium and it is mounted on a porcelain insulator to insulate it from the earth. • The arc chamber of such type of circuit breaker is enclosed in a bakelised paper. • The lower portion of this breaker is supported by the porcelain and the upper porcelain enclosed the contacts. • There are two different designs of the arcing chambers (i) axial and (ii) radial venting.
  • 12. Air Circuit Breaker (or Air Blast Circuit Breaker) Department of Electrical and Electronics Engineering What is Air Circuit Breaker? • An Air Circuit Breaker (also known as an Air Blast Circuit Breaker or ACB) is an automatically operated electrical switch that uses air to protect an electrical circuit from damage caused by excess current from an overload or short circuit. • Its primary function is to interrupt current flow after a fault is detected. • When this happens, an arc will appear between the contacts that have broken the circuit. • Air circuit breakers use compressed air to blow out the arc, or alternatively, the contacts are rapidly swung into a small sealed chamber, the escaping of the displaced air, thus blowing out the arc.
  • 13. Working Principle of Air Circuit Breaker Department of Electrical and Electronics Engineering This circuit breaker increases the arc voltage by mainly three different ways i. It may increase the arc voltage by cooling the arc plasma. As the temperature of arc plasma is decreased, the mobility of the particle in arc plasma is reduced; hence more voltage gradient is required to maintain the arc. ii. It may increase the arc voltage by lengthening the arc path. As the length of arc path is increased, the resistance of the path is increased, and hence to maintain the same arc current more voltage is required to be applied across the arc path. That means arc voltage is increased. iii. Splitting up the arc into a number of series arcs also increases the arc voltage.
  • 14. Operation of Air Circuit Breaker Department of Electrical and Electronics Engineering The operation of an ACB can be broken down into three steps: 1. The first objective is usually achieved by forcing the arc into contact with as large an area as possible of insulating material. Every air circuit breaker is fitted with a chamber surrounding the contact. This chamber is called ‘arc chute’. The arc is driven into it. If inside of the arc chute is suitably shaped, and if the arc can be made conform to the shape, the arc chute wall will help to achieve cooling. This type of arc chute should be made from some kind of refractory material. High temperature plastics reinforced with glass fiber and ceramics are preferable materials for making arc chute.
  • 15. How Air Circuit Breaker Work? Video 2 Department of Electrical and Electronics Engineering
  • 16. Operation of Air Circuit Breaker contd. Department of Electrical and Electronics Engineering 2. The second objective that is lengthening the arc path, is achieved concurrently with fist objective. If the inner walls of the arc chute is shaped in such a way that the arc is not only forced into close proximity with it but also driven into a serpentine channel projected on the arc chute wall. The lengthening of the arc path increases the arc resistance. 3. The third technique is achieved by using metal arc slitter inside the arc chute. The main arc chute is divided into numbers of small compartments by using metallic separation plates. These metallic separation plates are actually the arc splitters and each of the small compartments behaves as individual mini arc chute. In this system the initial arc is split into a number of series arcs, each of which will have its own mini arc chute. So each of the split arcs has its own cooling and lengthening effect due to its own mini arc chute and hence individual split arc voltage becomes high. These collectively, make the overall arc voltage, much higher than the system voltage.
  • 17. Air Circuit Breaker Department of Electrical and Electronics Engineering Advantages 1. There is no chance of fire hazard caused by oil. 2. The breaking speed of circuit breaker is much higher during operation of air blast circuit breaker. 3. Arc quenching is much faster during operation of air blast circuit breaker. 4. The duration of arc is same for all values of small as well as high currents interruptions. 5. As the duration of arc is smaller, so lesser amount of heat realized from arc to current carrying contacts hence the service life of the contacts becomes longer. 6. The stability of the system can be well maintained as it depends on the speed of operation of circuit breaker. 7. Requires much less maintenance compared to oil circuit breaker. Disadvantages 1. In order to have frequent operations, it is necessary to have sufficiently high capacity air compressor. 2. Frequent maintenance of compressor, associated air pipes and automatic control equipment's is also required. 3. Due to high speed current interruption there is always a chance of high rate of rise of re-striking voltage and current chopping. 4. There also a chance of air pressure leakage from air pipes junctions.
  • 18. Air Circuit Breaker Department of Electrical and Electronics Engineering It can be sub divided further into three different categories. 1. Axial Blast ACB. 2. Axial Blast ACB with side moving contact. 3. Cross Blast ACB.
  • 19. Air Circuit Breaker- Video 3 Department of Electrical and Electronics Engineering
  • 20. Axial Blast Air Circuit Breaker Department of Electrical and Electronics Engineering • In axial blast ACB the moving contact is in contact with fixed contact with the help of a spring pressure as shown in the figure. • There is a nozzle orifice in the fixed contact which is blocked by tip of the moving contact at normal closed condition of the breaker. • When fault occurs, the high pressure air is introduced into the arcing chamber.
  • 21. Axial Blast ACB with Side Moving Contact Department of Electrical and Electronics Engineering • In this type of axial blast air circuit breaker the moving contact is fitted over a piston supported over a spring. • In order to open the circuit breaker the air is admitted into the arcing chamber when pressure reaches to a predetermined value, it presses down the moving contact; an arc is drawn between the fixed and moving contacts.
  • 22. Cross Blast Air Circuit Breaker Department of Electrical and Electronics Engineering • The working principle of cross blast air circuit breaker is quite simple. • In this system of air blast circuit breaker the blast pipe is fixed in perpendicular to the movement of moving contact in the arcing chamber and on the opposite side of the arcing chamber one exhaust chamber is also fitted at the same alignment of blast pipe, so that the air comes from blast pipe can straightly enter into exhaust chamber through the contact gap of the breaker.
  • 23. Vacuum Circuit Breaker or VCB and Vacuum Interrupter Department of Electrical and Electronics Engineering • A vacuum circuit breaker is such kind of circuit breaker where the arc quenching takes place in vacuum. • The technology is suitable for mainly medium voltage application. For higher voltage vacuum technology has been developed but not commercially viable. • The operation of opening and closing of current carrying contacts and associated arc interruption take place in a vacuum chamber in the breaker which is called vacuum interrupter.
  • 24. Advantages of Vacuum Circuit Breaker or VCB Department of Electrical and Electronics Engineering Service life of vacuum circuit breaker is much longer than other types of circuit breakers. There is no chance of fire hazard like oil circuit breaker. It is much environment friendly than SF6 Circuit breaker. Beside that contraction of VCB is user-friendly. Replacement of vacuum interrupter (VI) is much convenient.
  • 25. Vacuum Circuit Breaker- Video 4 Department of Electrical and Electronics Engineering
  • 26. Operation of Vacuum Circuit Breaker Department of Electrical and Electronics Engineering The main aim of any circuit breaker is to quench arc during current zero crossing, by establishing high dielectric strength in between the contacts so that reestablishment of arc after current zero becomes impossible. The dielectric strength of vacuum is eight times greater than that of air and four times greater than that of SF6 gas. This high dielectric strength makes it possible to quench a vacuum arc within very small contact gap. For short contact gap, low contact mass and no compression of the medium the drive energy required in vacuum circuit breaker is minimum.
  • 27. Vacuum Circuit Breaker- Video 5 Department of Electrical and Electronics Engineering
  • 28. SF6 Circuit Breaker Types and Operation of SF6 Circuit Breaker Department of Electrical and Electronics Engineering A circuit breaker in which sulphur hexafluoride gas or SF6 gas is used as the arc quenching medium, known as an SF6 circuit breaker. • Sulphur hexafluoride (SF6) has good dielectric strength and excellent arc quenching property. • It is an inert, nontoxic, nonflammable and heavy gas. • At atmospheric pressure, its dielectric strength is about 2.35 times that of air. • At 3 atmospheric pressure its dielectric strength is more than that of transformer oil. • It is an electronegative gas, i.e. it has high affinity for electrons. • When a free electron comes in collision with a neutral gas molecule, the electron is absorbed by the neutral gas molecule and a negative ion is formed. • As the negative ions so formed are heavy they do not attain sufficient energy to contribute to ionisation of the gas.
  • 29. SF6 Circuit Breaker Types and Operation of SF6 Circuit Breaker Department of Electrical and Electronics Engineering • Under normal conditions, SF6 is chemically inert and it does not attack metals or glass. • However, it decomposes to SF4, SF2, S2, F2, S and F at temperatures of the order of 1000°C. • One major disadvantage of SF6 is its condensation at low temperature. • SF6 gas because of its excellent insulating and arc-quenching properties has revolutionized the design of high and extra high voltage (EHV) circuit breakers. • SF6 gas because of its excellent insulating and arc-quenching properties has revolutionized the design of high and extra high voltage (EHV) circuit breakers.
  • 30. SF6 Circuit Breaker Video 6 Department of Electrical and Electronics Engineering
  • 31. Properties of SF6 Gas Department of Electrical and Electronics Engineering The properties of SF6 gas can be divided as (i) Physical properties (ii) Chemical properties (iii) Electrical properties 1. Physical Properties of SF6 Gas The physical properties of SF6 gas are as follows: (i) It is a colourless, odourless, non-toxic and non-inflammable gas. (ii) Pure gas is not harmful to health. (iii) It is in gas state at normal temperature and pressure. (iv) It is heavy gas having density 5 times that of air at 20°C and atmospheric pressure.
  • 32. Properties of SF6 Gas Department of Electrical and Electronics Engineering 2. Chemical Properties of SF6 Gas (i) It is chemically stable at atmospheric pressure and at temperatures up to 500°C. (ii) It is a chemically inert gas. (iii) Moisture is very harmful to the properties of this gas. (iv) It is non-corrosive on all metals at ambient temperatures. (v) It is an electronegative gas. (vi) The products of decomposition of SF6 recombine in a short time after arc extinction.
  • 33. Properties of SF6 Gas Department of Electrical and Electronics Engineering 3. Electrical Properties of SF6 Gas (i) Dielectric properties Its dielectric strength at atmospheric pressure is 2.35 times that of air and 30% less than that of dielectric oil used in oil circuit breakers. The excellent dielectric strength of SF6 gas is because of electronegativity (electron attachment) property of SF6 molecules. In the attachment process, free electrons collide with the neutral gas molecules to form negative ions by the following processes. SF6 gas maintains high dielectric strength even after mixing with air. A mixture of 30% SF6 and 70% air by volume has a dielectric strength twice that of air at the same pressure. Below 30% of SF6 by volume, the dielectric strength falls sharply.
  • 34. Properties of SF6 Gas Department of Electrical and Electronics Engineering Breakdown voltages of SF6, air and dielectric oil as a function of pressure
  • 35. Properties of SF6 Gas Department of Electrical and Electronics Engineering (ii) Corona inception voltage Corona inception voltage for SF6 in a non-uniform electric field is also considerably higher than that for air. (iii) Dielectric constant Because of being non-polar (i.e., dipole moment is zero), the dielectric constant of SF6 is independent of the frequency of the applied voltage. Further, the dielectric constant changes by only 7% over a pressure range of 0 to 22 atmospheres. (iv) Arc-interrupting capacity Current interrupting capacity of SF6, air and a mixture of both gases
  • 36. Type of SF6 Circuit Breaker Department of Electrical and Electronics Engineering The following are two principal types of SF6 circuit breakers: (i) Double Pressure Type SF6 Circuit Breaker This type of circuit breaker employs a double pressure system in which the gas from a high-pressure compartment is released into the low-pressure compartment through a nozzle during the arc extinction process. (ii) Puffer-type (Single-pressure Type) SF6 Circuit Breaker In this type of circuit breaker the SF6 gas is compressed by the moving cylinder system and is released through a nozzle during arc extinction.
  • 37. Type of SF6 Circuit Breaker Department of Electrical and Electronics Engineering Puffer-type SF6 circuit breaker
  • 38. Advantages of SF6 Circuit Breakers Department of Electrical and Electronics Engineering (i) Low gas velocities and pressures employed in the SF6 circuit breakers prevent current chopping and capacitive currents are interrupted without restriking. (ii) These circuit breakers are compact, and have smaller overall dimensions and shorter contact gaps. They have less number of interrupters and require less mantenance. (iii) Since the gas is non-inflammable, and chemically stable and the products of decomposition are not explosive, there is no danger of fire or explosion. (iv) Since the same gas is recirculated in the circuit, the requirement of SF6 gas is small. (v) The operation of the circuit breaker is noiseless because there is no exhaust to atmosphere as in case of air blast circuit breakers (vi) Because of excellent arc quenching properties of SF6, the arcing time is very short and hence the contact erosion is less. The contacts can be run at higher temperatures without deterioration.
  • 39. Advantages of SF6 Circuit Breakers Department of Electrical and Electronics Engineering (vii) Because of inertness of the SF6 gas, the contact corrosion is very small. Hence contacts do not suffer oxidation. (viii) The sealed construction of the circuit breaker avoids the contamination by moisture, dust, sand etc. Hence the performance of the circuit breaker is not affected by the atmospheric conditions. (ix) Tracking or insulation breakdown is eliminated, because there are no carbon deposits following an arcing inside the system. (x) Because of the excellent insulating properties of the SF6, contact gap is drastically reduced. (xi) As these circuit breakers are totally enclosed and sealed from atmosphere, they are particularly suitable for use in such environments where explosion hazards exist.
  • 40. Disadvantages of SF6 Circuit Breakers Department of Electrical and Electronics Engineering (i) Problems of perfect sealing. There may be leakage of SF6 gas because of imperfect joints. (ii) SF6 gas is suffocating to some extent. In case of leakage in the breaker tank, SF6 gas may lead to suffocation of the operating personnel. (iii) Arced SF6 gas is poisonous and should not be inhaled or let out. (iv) Influx of moisture in the breaker is very harmful to SF6 circuit breaker. There are several cases of failures because of it. (v) There is necessity of mechanism of higher energy level for puffer-types SF6 circuit breakers. Lower speeds due to friction, misalignment can cause failure of the breaker. (vi) Internal parts should be cleaned thoroughly during periodic maintenance under clean and dry environment. (vii) Special facilities are required for transporting the gas, transferring the gas and maintaining the quality of the gas. The performance and reliability of the SF6 circuit breaker is affected due to deterioration of quality of the gas.
  • 41. OPERATING MECHANISM Department of Electrical and Electronics Engineering To open and close the contacts of a circuit breaker, one of the following mechanisms is employed. (1) Spring (2) Solenoid (3) Compressed air • In SF6 circuit breaker, compressed air may be used for closing and a spring for opening or compressed air for both closing as well as opening. • Springs are very good for opening as their force is large in the beginning and gradually decreases as the distance of travel of the moving contact increases.  In small circuit breakers, the spring can be charged by hand.  For large ones, it is charged by means of a motor.
  • 42. OPERATING MECHANISM Contd. Department of Electrical and Electronics Engineering • Solenoids are very good for closing.  The force of attraction increases when the distance between the contacts decreases.  Compressed air is suitable for both closing as well as opening.
  • 43. SELECTION OF CIRCUIT BREAKERS Department of Electrical and Electronics Engineering
  • 44. SELECTION OF CIRCUIT BREAKERS Contd. Department of Electrical and Electronics Engineering
  • 45. Circuit Breaker Ratings and Specifications Department of Electrical and Electronics Engineering Stress on circuit breakers: Usually under abnormal conditions circuit breaker undergo large thermal and mechanical stress. It is very important to understand the stress that the C.B. usually undergo before studying about its Ratings and Specifications. Thermal Stress: During the short circuit or faulty conditions the current through the circuit breakers are about 2.5- 3 times that of rated current. Which can melt the metal having diameter of 10cm, According to Joule’s law of heating. Mechanical Stress: This type of stress happens at the moving parts of the circuit breakers during its operation of preventing fault currents.
  • 46. Circuit Breaker Ratings and Specifications Contd. Department of Electrical and Electronics Engineering Duties of circuit breakers: • It must be capable of opening on the occurrence of a fault and of clearing the fault. • It must be capable of being closed on to a fault. • It must be capable of carrying fault current for short time while another circuit breaker is clearing the fault. These duties are classified as follows: 1. Breaking capacity. 2. Making capacity. 3. Short-time capacity. Other features of the duty include Rated voltage, Normal current rating, Operating duty and Thermal parameters.
  • 47. Circuit Breaker Ratings and Specifications Contd. Department of Electrical and Electronics Engineering 1. Breaking Capacity The breaking capacity of a circuit breaker is of two types. (i) Symmetrical breaking capacity (ii) Asymmetrical breaking capacity Symmetrical Breaking Capacity It is the rms value of the ac component of the fault current that the circuit breaker is capable of breaking under specified conditions of recovery voltage. Asymmetrical Breaking Capacity It is the rms value of the total current comprising of both ac and dc components of the fault current that the circuit breaker can break under specified conditions of recovery voltage.
  • 48. Circuit Breaker Ratings and Specifications Contd. Department of Electrical and Electronics Engineering • The line X-X indicates the instant of contact separation. • AB is the peak value of the ac component of the current at this instant. • Therefore, the symmetrical breaking current which is the rms value of the ac component of the current at the instant of contact separation is equal to current AB/sqrt(2) . • The section BC is the dc component of the short-circuit current at this instant. • Therefore, asymmetrical breaking current is given by
  • 49. Circuit Breaker Ratings and Specifications Contd. Department of Electrical and Electronics Engineering The breaking capacity of a circuit breaker is generally expressed in MVA. For a three-phase circuit breaker, it is given by 2. Making Capacity The capacity of a circuit breaker to be closed onto a short-circuit depends upon its ability to withstand the effects of electromagnetic forces. The multiplication by sqrt (2) is to obtain the peak value and again by 1.8 to take the dc component into account.
  • 50. Circuit Breaker Ratings and Specifications Contd. Department of Electrical and Electronics Engineering 3. Short-time Current Rating • The short-time current rating is based on thermal and mechanical limitations. • The circuit breaker must be capable of carrying short-circuit current for a short period while another circuit breaker (in series) is clearing the fault. • The rated short-time current is the rms value (total current, both ac and dc components) of the current that the circuit breaker can carry safely for a specified short period. • According to British standard, the time is 3 seconds if the ratio of symmetrical breaking current to rated normal current is equal to or less than 40 and 1 second if this ratio is more than 40.
  • 51. Circuit Breaker Ratings and Specifications Contd. Department of Electrical and Electronics Engineering 4. Rated Voltage, Current and Frequency • In a power system, the voltage level at all points is not the same. It varies, depending upon the system operating conditions. Due to this reason manufacturers have specified a rated maximum voltage at which the operation of the circuit breaker is guaranteed. • The rated current is the rms value of the current that a circuit breaker can carry continuously without any temperature rise in excess of its specified limit. • The rated frequency is also mentioned by the manufacture. It is the frequency at which the circuit breaker has been designed to operate.
  • 52. Circuit Breaker Ratings and Specifications Contd. Department of Electrical and Electronics Engineering 5. Rated Operating Duty This is mechanical duty requirement of circuit breaker operating mechanism. The sequence of rated operating duty of a circuit breaker has been specified as • O – t – CO - t' - CO where O indicates opening operation of CB. CO represents closing operation immediately followed by an opening operation without any intentional time delay. t' is time between two operations which is necessary to restore the initial conditions and / or to prevent undue heating of conducting parts of circuit breaker. t = 0.3 sec for circuit breaker intended for first auto re closing duty, if not otherwise specified.
  • 53. Circuit Breaker Ratings and Specifications Contd. Department of Electrical and Electronics Engineering •Suppose rated duty circle of a circuit breaker is 0 – 0.3 sec – CO – 3 min – CO. This means, an opening operation of circuit breaker is followed by a closing operation after a time interval of 0.3 sec, then the circuit breaker again opens without any intentional time delay. After this opening operation the CB is again closed after 3 minutes and then instantly trips without any intentional time delay. Thermal Parameters: It is the maximum temperature rise that is permissible for the individual parts of the equipment. It equals to the sum of the maximum temperature rise and the fixed temperature of the ambient air. Rated interrupting time: It is the mean time for interruption of any current not exceeding the rated interrupting current of the breaker.
  • 54. Classification of Circuit Breakers Department of Electrical and Electronics Engineering The circuit breakers are classified by various ways. The different criteria for classification of circuit breakers are as follows 1. Interrupting medium. 2. According to service. 3. Way of operation. 4. Action. 5. Method of control. 6. Way of mounting. 7. Tank construction. 8. Contacts.
  • 55. Classification of Circuit Breakers Contd. Department of Electrical and Electronics Engineering According to Interrupting Medium: Again according to interrupting medium the circuit breakers are classified as follows: 1. Air Circuit Breakers 2. Air Blast circuit breakers. 3. Oil Circuit breakers 4. Magnetic Blast circuit breakers. According to service: Basically there are two types, they are: 1. Indoor Circuit Breaker. 2. Outdoor Circuit Breaker.
  • 56. Classification of Circuit Breakers Contd. Department of Electrical and Electronics Engineering Depending upon Operation: According to this classification the types of circuit breakers are 1. Gravity Opened, Gravity Closed Circuit Breaker. 2. Horizontal Break Circuit Breaker. Based on Action: This is nothing but, 1. Automatic C.B. 2. Manual C.B. According to method of control: According to the method of control, the circuit breaker may be controlled directly or it may be operated remotely. The remote control may be manual, pneumatic or electrical.
  • 57. Classification of Circuit Breakers Contd. Department of Electrical and Electronics Engineering The way of Mounting: According to this, • Panel Mounted and, • Rear of panel or remote from panel type. Depending upon Tank construction: • This classification is born only due to the liquid dielectric medium of separation so we can classify it into “ A separate tank for each pole type or one tank for all poles type. On basis of Contacts: On this type of classification the circuit breakers are classified into 1. Butt type contacts. 2. Wedge type. 3. Laminated flat contact and 4. Explosion chamber.
  • 58. Auto Reclosing Scheme of Transmission System Department of Electrical and Electronics Engineering • The extra high voltage transmission lines transmit huge amount of electric power. Hence, it is always desirable that the continuation of power flow through the lines should not be interrupted for a long time. • There may be a temporary or permanent fault in the lines. • Temporary faults get automatically cleared, and these do not require any attempt for fault rectification. • It is normal practice by the operators that after each initial faulty tripping of the line, they close the line. • If the fault is transient, the line holds after the second attempt of closing the circuit breaker, but if the fault persists, the protection system again trips the line and then it is declared as permanent fault.
  • 59. Auto Reclosing Scheme of Transmission System Contd. Department of Electrical and Electronics Engineering We categorize the faults in electrical transmission system in three ways, 1. Transient Fault 2. Semi Permanent Fault 3. Permanent Fault • The transient faults are those which automatically removed momentarily. • Semi permanent faults are also transient in nature but there take few moments to remove. • Semi-permanent faults may get occurred due to the falling of things on the live conductors. • Semi-permanent faults get removed after the cause of faults is burnt away. • During both of the above mentioned faults, line is tripped but the line can be restored if the circuit breakers associated with the line are closed.
  • 60. Numerical Example- 1 Department of Electrical and Electronics Engineering 1. A circuit breaker is rated at 1500 amps, 2000 MVA, 33 kV, 3 sec, 3- phase, oil circuit breaker. Determine the rated normal current, breaking current, making current and short time rating (current). Ans: The rated normal current is 1500 amps. Making current = 2.55 x Symmetrical breaking current If the symmetrical braking current capacity of the breaker is 40 KA(RMS), the making current of the breaker must be 2.55*40=102 KA(peak).
  • 61. Numerical Example- 2 Department of Electrical and Electronics Engineering 2. A generator connected through a 3-cycle C.B. to a transformer is rated 10 MVA, 13.8 kV with reactances of Xd″ = 10%, Xd′ = 15% and Xd = 100%. It is operating at no load and rated voltage when a 3-phase short circuit occurs between the breaker and the transformer. Determine (i) the sustained short circuit current in the breaker; (ii) the initial symmetrical r.m.s. current in the breaker; (iii) the maximum possible d.c. component of the short circuit current in the breaker; (iv) the momentary current rating of the breaker; (v) the current to be interrupted by the breaker; and (vi) the interrupting kVA. Ans: (i) Since the steady reactance is 100% The steady state short circuit MVA = 10 MVA (ii) The initial symmetrical r.m.s. current is the current corresponding to sub-transient state where the % reactance is 10.
  • 62. Numerical Example- 2 Contd. Department of Electrical and Electronics Engineering (iii) The maximum possible d.c. component = peak value of the subtransient current = sqrt (2) × 4180 = 5910 amps. (iv) Momentary current rating = 1.6 × 4180 = 6688 amps (v) Since it is a 3-cycle breaker the current to be interrupted by the breaker = 1.2 × symmetrical breaking current = 1.2 × 4180 = 5019 amps. (vi) The interrupting kVA = sqrt (3) × 13.8 × 5016 = 119897 kVA or 119.897 MVA
  • 63. Assignment 1.1 (Submission date: 14/09/2020) Department of Electrical and Electronics Engineering 1. Explain how arc is initiated and sustained in a circuit breaker when the circuit breaker contacts separate. 2. Discuss the principle of arc interruption in (i) an oil C.B.; and (ii) air blast circuit breaker. 3. Compare the performance and characteristics of (i) minimum oil breakers and air blast C.B.; (ii) air blast C.B. and bulk oil C.B. 4. Explain the terms (i) Symmetrical breaking current; (ii) Asymmetrical breaking current; and (iii) making current. Explain clearly how these currents can be determined from oscillograms taken during short circuit tests on a 3-phase C.B. 5. Explain the terms (i) restriking voltage; (ii) recovery voltage; and (iii) RRRV. Derive an expression for the restriking voltage in terms of system voltage, inductance and capacitance, across a C.B. contact when a 3-phase fault takes place. Assume the neutral of the system to be solidly grounded.
  • 64. Assignment 1.2 (Submission date: 21/09/2020) Department of Electrical and Electronics Engineering 1. Differentiate between type tests and routine tests. What different tests are carried out to prove the ability of a C.B.? 2. What are the requirements of the contact material for a vacuum circuit breaker? Why is current chopping not a serious problem with such circuit breakers? 3. Describe the construction, principle of operation and application of a vacuum breaker. 4. Compare the performance of SF6 gas with air when used for circuit breaking. 5. Explain the process of ‘current chopping’ in SF6 breakers. 6. Describe the construction, principle of operation and application of SF6 circuit breaker. How does this breaker essentially differ from an air blast breaker?
  • 65. Assignment 1.3 (Submission date: 28/09/2020) Department of Electrical and Electronics Engineering 1. In a short circuit test on a C.B. the following readings were obtained on a single frequency transient: (i) Time to reach the peak restriking voltage 40 μsec; (ii) the peak restriking voltage 100 kV. Determine the average RRRV and the frequency of oscillation. 2. An 11 kV, 50 Hz alternator is connected to a system which has inductance and capacitance per phase of 10 mH and 0.01 μF respectively. Determine (i) the maximum voltage across the breaker contacts; (ii) Frequency of transient oscillation; (iii) the average RRRV; and (iv) the maximum RRRV. 3. A 66 kV, 50 Hz, 3-phase alternator has an earthed neutral. The inductance and capacitance per phase of the system are 7 mH and 0.01 μF respectively. The short circuit test gave the following results: Power factor of fault 0.25, fault current symmetrical recovery voltage is 90% of full line voltage. Assuming that the fault is isolated from the ground, calculate the RRRV. 4. A circuit breaker is rated as 2500 A, 1500 MVA, 33 kV, 3 secs, 3-phase oil C.B. Determine the rated symmetrical breaking current, rated making current, short time rating and rated service voltage.