More Related Content Similar to 05_Acoustic PD detection.pdf Similar to 05_Acoustic PD detection.pdf (20) 05_Acoustic PD detection.pdf2. Introduction
Partial Discharges (PD)
"…local electrical discharges which only partially bridge the insulation
between electrical conductors ....”
[IEC 60270:2000]
…generate electromagnetic signals
…generate acoustic signals
measurable
Page 2
© OMICRON
4. Acoustic signal emission
Page 4
© OMICRON
• PD signals emit part of the energy converted as a sound wave.
• The propagation medium and sound transducer have strong
influence on the shape of the measured signal.
• Acoustic data does not provide any direct information on type of
fault or intensity of Partial Discharge activity.
• Unlike electrical PD measurement, it is not possible to define limit
values.
• Used for fault localization determined through differences in signal
arrival time at sensor location.
5. Acoustic Signal Propagation from Source to Tank Wall
Time-base Localization
Page 5
© OMICRON
Source: IEEE Std C57.127-2007 „IEEE Guide for the Detection and Location of Acoustic
Emissions from Partial Discharges in Oil-Immersed Power Transformers and Reactors”
6. Page: 6
Sensors
AES 075
Resonance frequency 75 kHz
Lower frequency limit 30 kHz
Upper frequency limit 120 kHz
Gain 40dB
Source: L.E.Lundgaard „Partial Discharge – Part XIV: Acoustic
Partial Discharge Detection – Practical Application“, IEEE El.
Insulation Magazine Sep 1992 Vol.8,No.5
7. 1250
1260
1270
1280
1290
1300
1310
0 200 400 600 800 1000 1200
Velocity
(m/s)
Frequency (kHz)
Acoustic Signal Propagation Speed in Oil
Howells, E. ; Norton, E.T.: “Parameters affecting the velocity of sound in transformer oil”
IEEE Transactions on Power Apparatus and Systems (1984)”
1000
1100
1200
1300
1400
1500
1600
-40 -20 0 20 40 60 80 100 120 140
Velocity
(m/s)
Temperature ( °
C)
@150 kHz
@ 65 °
C
8. Propagation Path
Material Speed [m/s]
Steel Longitudinal 5900
Steel Transversal 3200
Oil 20°
C 1413
Oil 80°
C 1200
8
© OMICRON
Source: IEEE Std C57.127-2007 „IEEE Guide for the Detection and Location of Acoustic
Emissions from Partial Discharges in Oil-Immersed Power Transformers and Reactors”
10. Propagation Path
10
© OMICRON
Winding
Transformer Tank
Steel Part
Direct Oil Part
Source: Lue RiCheng, Li WeiGou, Lie ChenRong and Xiong Hao „Study
on PD Localization by Ultrasonic Measuring im Power Transformer
Based on Particle Swarm Optimization” G-003, ISH, Beijing, China
Aug 2005
12. Localization Algorithm - Triangulation
Page 12
© OMICRON
Source: L.E.Lundgaard „Partial Discharge – Part XIV: Acoustic Partial Discharge
Detection – Practical Application“, IEEE El. Insulation Magazine Sep 1992 Vol.8,No.5
Absolute times tx Relative times ∆txy
13. Test Set-up
13
© OMICRON
• Approx. 2 – 3 hours usually required
• Place the sensors on transformer tank
• Perform operational check; ensure sensitivity of all
sensors
• To start with, place sensors in general area of bottom
connection of each bushings
• Place the sensors below the oil level
• Prepare Transformer model as accurate as possible
• Measure correct distances where the sensors are
mounted
14. Test Set-up
14
© OMICRON
Do’s & Don’ts:
• Contact between transducer and transformer tank is critical. It is
advisable to clean the area free of dirt, oil etc. and polish with
abrasive cloth before placing the sensors.
• Acoustic couplant is essential for enhancing the mechanical &
acoustic coupling between transducer & tank surface. It should
be evenly applied to the clean mounting surface of sensor.
• If possible, avoid locations where there is magnetic or non-
magnetic tank shielding, which will cause signal attenuation.
• Avoid mounting sensors on tank stiffeners
• For safety reasons, do not place sensors in areas of high voltage
• Do not mount sensors on control boxes
• Provide sufficient spacing between sensors to insure
independent signals.
23. Measurement Setup
• 16 MVA three-phase power transformer 150 kV / 20 kV (Yyn0)
• PDL 650 (PDLocator) for acoustic PD measurements/localization
• MPD 600 for PD measurements according to IEC 60270
N
U
V
W
U V W
CPL
542A
CPL
542A
MPD
600
PDL
650
PC
MPD
600
Fig.1 Localization of PD sensors
25. Results of Conventional PD Measurement
Figure The measurement was performed at 85 kV.
• Due to the high PD level on phase W it is assumed that the PD is located near
phase W
• Measurement Frequency 175-825kHz
Phase V
Phase W
26. Conclusion: Yellow and Black sensor are nearer to the PD defect, red sensor is farther
away and blue the farthest. Decision to change of position of sensor red was undertaken.
Calculated defect location: 2.7 m | 1.2 m | 1.7 m.
Results of Acoustic Localization
Sensor Arrival
time
Max. Amplitude (roughly)
Blue 0.804 ms 420 mV
Yellow 0.175 ms 825 mV
Red 0.746 ms 630 mV
Black 0.409 ms 770 mV
27. Sensor Arrival
time
Max. Amplitude (roughly)
Blue 0.515 ms 610 mV
Yellow 0.183 ms 680 mV
Red 0.567 ms 585 mV
Black 0.447 ms 655 mV
Conclusion: Yellow sensor is nearest to the PD defect, black sensor is farther away and
blue and red the farthest. Calculated defect location: 2.6 m | 1.1 m | 1.4 m.
Results of Acoustic Localization
29. 500 MVA Autotransformer
Page 29
© OMICRON
Autotransformer:
400kV/220kV/33kV
YNa0d11 (50Hz)
500 MVA
Installation Date:
Oct 2011
Red
Yellow
Blue
LV
HV
30. DGA – Anomaly
> Sharp rise of H2
> Methane is still quite low and Acetylene is zero.
> Assumption: no arcing and no heavy discharges, but PD
Page 30
© OMICRON
31. Electrical and Acoustic Measurement
Page 31
© OMICRON
Red
Yellow
Blue
LV
HV
Neutral
MPD600
1.1
MPD600
1.2
MPD600
1.3
MPD600
1.4
Acoustic
Sensors
PDL 650
tap changer
32. Acoustic Measurement at transformer tank
Page 32
© OMICRON
Non of the electrical
measured impulse were
convenient to trigger a
acoustic measurement
-> Next step are
all acoustic measurement
33. Acoustic Measurement
at transformer tank (top)
Page 33
© OMICRON
Acoustic measurements at
the side walls of the tank
was not successful
-> Acoustic sensors on top
of the transformer
34. 1. Trial:
Page 34
© OMICRON
4 Sensors on the Top
Sensor X [m] Y [m] Z [m]
Blue 2.64 1.74 3.99
Yellow 4.06 3.22 3.99
Red 6.63 3.27 3.99
Black 8.08 1.95 3.99
0/0/0
36. © OMICRON 36
1. Trial
Interpretation:
PD source is likely at tap changer, bushing or at the connection to
the winding of the yellow phase.
-> rearrange the sensor position close to Bushing and tap changer
37. 2. Trial
Page 37
© OMICRON
Rearranged position of the sensors
Sensor X [m] Y [m] Z [m]
Blue 4.84 1.40 3.99
Yellow 5.60 0.00 3.60
Red
(attached to the
bushing / LV Yellow)
4.52 0.62 4.10
Black 5.50 1.00 3.99
38. 4/14/2019 38
Acoustic signal arrives first at
sensor Black and Blue and
later Yellow and than Red
Acoustic
Sensor
1 Blue 56 us
2 Yellow 473 us
3 Red 561 us
4 Black 0 us
41. Summary
> Acoustic measurement / localization
> can localize PD inside of power transformer.
> can help to reduce repair time of a transformer at
the factory.
> can help assess the transformer on-site.
> Important is
> understanding of the acoustic propagation.
> knowledge about the inner construction.
> sufficient workflow.
Page 41
© OMICRON