FAULT LEVEL CALCULATION
Dinesh Kumar Sarda
Fault level at any given point of the
Electric Power Supply Network is the
maximum current that would flow in case of
a short circuit fault at that point.
The circuit breaker should be capable of
Breaking & Making current as per their
ratings & should also have Rated short time
capacity. So, for proper selection of circuit
breaker & other switchgear components,
Knowledge of current during normal &
abnormal conditions is necessary.
The design of machines, bus bars, isolators,
circuit breaker etc. is based on the
consideration of Normal & Short Circuit
Currents.
The Protective Relaying Schemes can be
selected only after ascertaining the fault
levels and normal currents at various
locations. Fault calculations are also
necessary for System Design, stability
considerations, selection of Layout etc.
Purpose of Fault Level Calculations:-
a) For selecting short circuit protective
devices of adequate short circuit Breaking
capacity.
b) For selecting circuit breakers and
switches of Adequate short circuit Making
capacity.
c) for selecting Bus Bars, cable and
switchgear, designed to withstand thermal
and mechanical stresses because of short
circuit.
Types of Short Circuits:-
1) L-E (Single Line to Earth)
2) L-L ( Line to Line)
3) L-L-E ( Line to Line to Earth)
4) L-L-L ( Three Phase)
 In Fault Calculations, many assumptions
are made for simplifying the calculations.
Resistances are neglected when their
values are negligible as compared to the
Reactance.
Capacitance is neglected. Machine
reactance are assumed to be constants.
Saturation effects are neglected.
Generated voltages are assumed to be
constant. Contribution of Shunt capacitor
banks are neglected.
 Impedences of BusBar, Switchgear, C.Ts
are neglected.
Transformer tap is in the main position.
Short circuit current waveform is a pure
Sine wave.
Resistance of short transmission line are
neglected.
Fault calculations are always done assuming
Three Phase bolted short circuit fault.
Procedure for Fault Level Calculation.
 Fault calculations begin with drawing
Single line or One line diagram of the given
network with Ratings of all the
transformers & Generators in the network.
 Suitable Base MVA is chosen. For ex. 100
MVA.
 Per Unit reactance (impedence) is
calculated for every Transformer &
Generator in the given network by using-
Formula P.u reactance =
[(% impedence)/100] x [Base MVA/Actual
MVA]
 Then redraw the network putting the P.u
reactance values.
 Calculate the Equivalent reactance for the
for the network as seen from the source to
the fault point.
 Then, Calculate Fault MVA using formula-
Fault MVA= Base MVA/ Eq. Impedence
 Calculate Fault Current using formula=
Fault Current =
Fault MVA / (1.732x Phase to Phase
Voltage at the fault point)
Current Limiting Reactors:-
Current Limiting Reactors ( Series Reactors)
are inserted in series with the line, to limit
the current flow in the event of a short
Circuit & thereby, bring down the fault
level. The current Limiting Reactors are
also called Series Reactors.
A current Limiting Reactor is an inductive
coil having a large inductive reactance (wL)
and is used for limiting short-circuit
currents to be interrupted by circuit
breaker.
 If X is the reactance of a circuit , E is
the voltage then by neglecting the
resistance , the short circuit current is
given by Isc= E / X.
Therefore, by increasing the series
reactance of the system, the short circuit
current can be decreased.
The short circuit current depends upon the
generating capacity, voltage at the fault
point and the total reactance between the
generator and the fault point.
The circuit breaker should have enough
breaking current capacity such that the
fault current are less than the breaking
current capacity. IF the fault currents are
beyond the capacity of the circuit breaker,
the circuit breaker may not interrupt the
fault current.
Then the fault current should be limited by
some means so that the existing circuit
breaker can be used safely.
Also when the system is extended by
adding more generating stations, the Fault
current to be interrupted by the same
circuit breaker will be greater than before.
In these cases, the circuit breaker should
be replaced by another of higher breaking
current capacity or the fault current can
be limited by the means of REACTORS.
The current limiting reactors are useful in
limiting short circuit current so that the
circuit breaker can interrupt them.
1) Reactors limit the Short Circuit Current.
2) Reactors are used in the systems when
extensions are made and the circuit
breaker breaking current capacities
become inadequate.
3) Reactors are employed in Large Systems
so as to limit the short circuit MVA to
match with the breaking current capacity
of the circuit breaker.
Location of Series Reactor:-
 Generator Reactors-
Reactors are inserted between the
generator and the generator bus. The high
reactance is provided to safeguard the
generators in case of dead three phase
short circuits at its terminals.
When new generators are installed ,
generator reactors can be added to the old
generators.
GENERATOR REACTOR:-
Feeder Reactors-
The reactors in this case are connected in
series with the feeders. The advantage is
that the voltage of the bus does not drop
substantially in the event of fault on the
feeder.
 The Busbar Reactor-
The busbar reactor is placed between two
sections of busbar.
BUSBAR REACTOR-
FEEDER REACTORS-
QUESTIONS:-
1) Why Fault Calculation is required?
2) What is meant by Breaking Current
capacity & Making Current Capacity of
Circuit Breaker?
3) What is the formula for Calculating
Fault MVA?
4) What is the Formula for Calculating
Fault Current?
5) What should be used to decrease
Fault Level at any point?

More Related Content

What's hot

Power system protection
Power system protectionPower system protection
Power system protection
Anu Priya
 
Power System Operation and Control
Power System Operation and ControlPower System Operation and Control
Power System Operation and Control
Biswajit Pratihari
 

What's hot (20)

Testing of circuit breakers
Testing of circuit breakersTesting of circuit breakers
Testing of circuit breakers
 
Transformer protection
Transformer protectionTransformer protection
Transformer protection
 
Series & shunt compensation and FACTs Devices
Series & shunt compensation and FACTs DevicesSeries & shunt compensation and FACTs Devices
Series & shunt compensation and FACTs Devices
 
Power Transformer Protection
Power Transformer ProtectionPower Transformer Protection
Power Transformer Protection
 
Relay Setting Calculation For REF615/ REJ601
Relay Setting Calculation For REF615/ REJ601Relay Setting Calculation For REF615/ REJ601
Relay Setting Calculation For REF615/ REJ601
 
3. INTRODUCTION TO PROTECTIVE RELAYING.pptx
3. INTRODUCTION TO PROTECTIVE RELAYING.pptx3. INTRODUCTION TO PROTECTIVE RELAYING.pptx
3. INTRODUCTION TO PROTECTIVE RELAYING.pptx
 
Basics of overcurrent protection
Basics of overcurrent protectionBasics of overcurrent protection
Basics of overcurrent protection
 
INTERLINE FLOW CONTROLLER
INTERLINE FLOW CONTROLLERINTERLINE FLOW CONTROLLER
INTERLINE FLOW CONTROLLER
 
Power system protection
Power system protectionPower system protection
Power system protection
 
Relays and its types - complete guide
Relays and its types - complete guideRelays and its types - complete guide
Relays and its types - complete guide
 
Switchgear presentation
Switchgear presentationSwitchgear presentation
Switchgear presentation
 
Ppt on protection of power transformers
Ppt on protection of power transformersPpt on protection of power transformers
Ppt on protection of power transformers
 
Motor protection principles
Motor protection principlesMotor protection principles
Motor protection principles
 
Practical handbook-for-relay-protection-engineers
Practical handbook-for-relay-protection-engineersPractical handbook-for-relay-protection-engineers
Practical handbook-for-relay-protection-engineers
 
Power System Operation and Control
Power System Operation and ControlPower System Operation and Control
Power System Operation and Control
 
Factors to be considered while selecting CT
Factors to be considered while selecting CTFactors to be considered while selecting CT
Factors to be considered while selecting CT
 
Cable Sizing Calculations
Cable Sizing CalculationsCable Sizing Calculations
Cable Sizing Calculations
 
Load Frequency Control of Two Area System
Load Frequency Control of Two Area SystemLoad Frequency Control of Two Area System
Load Frequency Control of Two Area System
 
DISTANCE PROTECTION RELAY
DISTANCE PROTECTION RELAYDISTANCE PROTECTION RELAY
DISTANCE PROTECTION RELAY
 
Directional over current relay
Directional over current relayDirectional over current relay
Directional over current relay
 

Viewers also liked

Central Nervous System 1
Central Nervous System 1Central Nervous System 1
Central Nervous System 1
MBBS IMS MSU
 
Nervous System
Nervous SystemNervous System
Nervous System
itutor
 

Viewers also liked (17)

SAP Training ( PS , Material PR , Service PR ,Cost Planning , Budgeting , PO...
SAP Training ( PS , Material PR , Service PR ,Cost Planning , Budgeting ,  PO...SAP Training ( PS , Material PR , Service PR ,Cost Planning , Budgeting ,  PO...
SAP Training ( PS , Material PR , Service PR ,Cost Planning , Budgeting , PO...
 
Switch gear and protection
Switch gear and protectionSwitch gear and protection
Switch gear and protection
 
Mikrotik advanced
Mikrotik advancedMikrotik advanced
Mikrotik advanced
 
File 1 power system fault analysis
File 1 power system fault analysisFile 1 power system fault analysis
File 1 power system fault analysis
 
Basic short circuit calculation procedure
Basic short circuit calculation procedureBasic short circuit calculation procedure
Basic short circuit calculation procedure
 
Table etiquette
Table etiquetteTable etiquette
Table etiquette
 
Transportation Systems In Buildings
Transportation Systems In BuildingsTransportation Systems In Buildings
Transportation Systems In Buildings
 
Modal Verbs
Modal VerbsModal Verbs
Modal Verbs
 
Gsm architecture
Gsm architectureGsm architecture
Gsm architecture
 
Basic Baking Ingredients and Their Functions
Basic Baking Ingredients and Their FunctionsBasic Baking Ingredients and Their Functions
Basic Baking Ingredients and Their Functions
 
Chapter 1: Fundamentals of Accounting
Chapter 1: Fundamentals of AccountingChapter 1: Fundamentals of Accounting
Chapter 1: Fundamentals of Accounting
 
Types of Lighting and Luminaire
Types of Lighting and LuminaireTypes of Lighting and Luminaire
Types of Lighting and Luminaire
 
K to 12 Bread and Pastry Learning Module
K to 12 Bread and Pastry Learning ModuleK to 12 Bread and Pastry Learning Module
K to 12 Bread and Pastry Learning Module
 
Central Nervous System 1
Central Nervous System 1Central Nervous System 1
Central Nervous System 1
 
The Nervous System Parts And Functions
The Nervous System Parts And FunctionsThe Nervous System Parts And Functions
The Nervous System Parts And Functions
 
Nervous System
Nervous SystemNervous System
Nervous System
 
The Nervous System (Slide Show)
The Nervous System (Slide Show)The Nervous System (Slide Show)
The Nervous System (Slide Show)
 

Similar to Fault Level Calculation

fault location estimator in series compensator
fault location estimator in series compensatorfault location estimator in series compensator
fault location estimator in series compensator
ABHISHEK RAI
 

Similar to Fault Level Calculation (20)

RAJARAM PPT
RAJARAM PPTRAJARAM PPT
RAJARAM PPT
 
HVDC and FACTS for Improved Power Delivery Through Long Transmission Lines
HVDC and FACTS for Improved Power Delivery Through Long Transmission LinesHVDC and FACTS for Improved Power Delivery Through Long Transmission Lines
HVDC and FACTS for Improved Power Delivery Through Long Transmission Lines
 
Power quality 5
Power quality 5Power quality 5
Power quality 5
 
Electrical Protection Schemes in detail
Electrical Protection Schemes in detailElectrical Protection Schemes in detail
Electrical Protection Schemes in detail
 
Report on 220kv substation at Jassure
Report on 220kv substation at JassureReport on 220kv substation at Jassure
Report on 220kv substation at Jassure
 
Dynamic Performance of Distance Relayson Series Compensated Transmission Line...
Dynamic Performance of Distance Relayson Series Compensated Transmission Line...Dynamic Performance of Distance Relayson Series Compensated Transmission Line...
Dynamic Performance of Distance Relayson Series Compensated Transmission Line...
 
60232804 ppt-compensation-techniques-in-ac-transmission-system-using-c
60232804 ppt-compensation-techniques-in-ac-transmission-system-using-c60232804 ppt-compensation-techniques-in-ac-transmission-system-using-c
60232804 ppt-compensation-techniques-in-ac-transmission-system-using-c
 
fault location estimator in series compensator
fault location estimator in series compensatorfault location estimator in series compensator
fault location estimator in series compensator
 
Simulation and Modeling of Dynamic Voltage Restorer for Compensation Of Volta...
Simulation and Modeling of Dynamic Voltage Restorer for Compensation Of Volta...Simulation and Modeling of Dynamic Voltage Restorer for Compensation Of Volta...
Simulation and Modeling of Dynamic Voltage Restorer for Compensation Of Volta...
 
IRJET-Simulation and Modeling of Dynamic Voltage Restorer for Compensation Of...
IRJET-Simulation and Modeling of Dynamic Voltage Restorer for Compensation Of...IRJET-Simulation and Modeling of Dynamic Voltage Restorer for Compensation Of...
IRJET-Simulation and Modeling of Dynamic Voltage Restorer for Compensation Of...
 
Determination of voltage regulation and power system losses
Determination of voltage regulation and power system lossesDetermination of voltage regulation and power system losses
Determination of voltage regulation and power system losses
 
Determination of Voltage Regulation and Power system losses
Determination of Voltage Regulation and Power system lossesDetermination of Voltage Regulation and Power system losses
Determination of Voltage Regulation and Power system losses
 
283481961-POWER-SYSTEM-FAULTS-ppt.ppt
283481961-POWER-SYSTEM-FAULTS-ppt.ppt283481961-POWER-SYSTEM-FAULTS-ppt.ppt
283481961-POWER-SYSTEM-FAULTS-ppt.ppt
 
1660034363151685.pptx
1660034363151685.pptx1660034363151685.pptx
1660034363151685.pptx
 
The important use of reactors in substations
The important use of reactors in substationsThe important use of reactors in substations
The important use of reactors in substations
 
Bo36390397
Bo36390397Bo36390397
Bo36390397
 
Application of Capacitors to Distribution System and Voltage Regulation
Application of Capacitors to Distribution System and Voltage RegulationApplication of Capacitors to Distribution System and Voltage Regulation
Application of Capacitors to Distribution System and Voltage Regulation
 
COMPENSATION OF REACTIVE POWER
COMPENSATION OF REACTIVE POWERCOMPENSATION OF REACTIVE POWER
COMPENSATION OF REACTIVE POWER
 
Facts unit-5_and_6
Facts  unit-5_and_6Facts  unit-5_and_6
Facts unit-5_and_6
 
facts__unit-5_and_6.pptx
facts__unit-5_and_6.pptxfacts__unit-5_and_6.pptx
facts__unit-5_and_6.pptx
 

More from Dinesh Sarda

RESUME_Dinesh Sarda 2
RESUME_Dinesh Sarda 2RESUME_Dinesh Sarda 2
RESUME_Dinesh Sarda 2
Dinesh Sarda
 

More from Dinesh Sarda (15)

Basic Fundamental Electronics by D-Sarda PART X
Basic Fundamental Electronics by D-Sarda PART XBasic Fundamental Electronics by D-Sarda PART X
Basic Fundamental Electronics by D-Sarda PART X
 
Basic Fundamental Electronics by D-Sarda PART IX
Basic Fundamental Electronics by D-Sarda PART IXBasic Fundamental Electronics by D-Sarda PART IX
Basic Fundamental Electronics by D-Sarda PART IX
 
Basic Fundamental Electronics by D-Sarda PART VIII
Basic Fundamental Electronics by D-Sarda PART VIIIBasic Fundamental Electronics by D-Sarda PART VIII
Basic Fundamental Electronics by D-Sarda PART VIII
 
Basic Fundamental Electronics by D-Sarda PART VII
Basic Fundamental Electronics by D-Sarda PART VIIBasic Fundamental Electronics by D-Sarda PART VII
Basic Fundamental Electronics by D-Sarda PART VII
 
Basic Fundamental Electronics by D-Sarda PART VI
Basic Fundamental Electronics by D-Sarda PART VIBasic Fundamental Electronics by D-Sarda PART VI
Basic Fundamental Electronics by D-Sarda PART VI
 
Basic Fundamental Electronics by D-Sarda PART V
Basic Fundamental Electronics by D-Sarda PART VBasic Fundamental Electronics by D-Sarda PART V
Basic Fundamental Electronics by D-Sarda PART V
 
Basic Fundamental Electronics by D-Sarda PART IV
Basic Fundamental Electronics by D-Sarda PART IVBasic Fundamental Electronics by D-Sarda PART IV
Basic Fundamental Electronics by D-Sarda PART IV
 
Basic Fundamental Electronics by D-Sarda PART IV
Basic Fundamental Electronics by D-Sarda PART IVBasic Fundamental Electronics by D-Sarda PART IV
Basic Fundamental Electronics by D-Sarda PART IV
 
Basic Fundamental Of Transistors by D-Sarda
Basic Fundamental Of Transistors by D-SardaBasic Fundamental Of Transistors by D-Sarda
Basic Fundamental Of Transistors by D-Sarda
 
Basic Fundamental Electronics by D-Sarda PART III
Basic Fundamental Electronics by D-Sarda PART IIIBasic Fundamental Electronics by D-Sarda PART III
Basic Fundamental Electronics by D-Sarda PART III
 
Basic Fundamental Electronics by D-Sarda PART II
Basic Fundamental Electronics by D-Sarda PART IIBasic Fundamental Electronics by D-Sarda PART II
Basic Fundamental Electronics by D-Sarda PART II
 
Basic Fundamental Electronics by D-Sarda
Basic Fundamental Electronics by D-Sarda Basic Fundamental Electronics by D-Sarda
Basic Fundamental Electronics by D-Sarda
 
MICOM P 632
MICOM P 632MICOM P 632
MICOM P 632
 
BUSBAR PROTECTION
BUSBAR PROTECTIONBUSBAR PROTECTION
BUSBAR PROTECTION
 
RESUME_Dinesh Sarda 2
RESUME_Dinesh Sarda 2RESUME_Dinesh Sarda 2
RESUME_Dinesh Sarda 2
 

Fault Level Calculation

  • 2. Fault level at any given point of the Electric Power Supply Network is the maximum current that would flow in case of a short circuit fault at that point. The circuit breaker should be capable of Breaking & Making current as per their ratings & should also have Rated short time capacity. So, for proper selection of circuit breaker & other switchgear components, Knowledge of current during normal & abnormal conditions is necessary.
  • 3. The design of machines, bus bars, isolators, circuit breaker etc. is based on the consideration of Normal & Short Circuit Currents. The Protective Relaying Schemes can be selected only after ascertaining the fault levels and normal currents at various locations. Fault calculations are also necessary for System Design, stability considerations, selection of Layout etc.
  • 4. Purpose of Fault Level Calculations:- a) For selecting short circuit protective devices of adequate short circuit Breaking capacity. b) For selecting circuit breakers and switches of Adequate short circuit Making capacity. c) for selecting Bus Bars, cable and switchgear, designed to withstand thermal and mechanical stresses because of short circuit.
  • 5. Types of Short Circuits:- 1) L-E (Single Line to Earth) 2) L-L ( Line to Line) 3) L-L-E ( Line to Line to Earth) 4) L-L-L ( Three Phase)
  • 6.  In Fault Calculations, many assumptions are made for simplifying the calculations. Resistances are neglected when their values are negligible as compared to the Reactance. Capacitance is neglected. Machine reactance are assumed to be constants. Saturation effects are neglected.
  • 7. Generated voltages are assumed to be constant. Contribution of Shunt capacitor banks are neglected.  Impedences of BusBar, Switchgear, C.Ts are neglected. Transformer tap is in the main position. Short circuit current waveform is a pure Sine wave.
  • 8. Resistance of short transmission line are neglected. Fault calculations are always done assuming Three Phase bolted short circuit fault.
  • 9. Procedure for Fault Level Calculation.  Fault calculations begin with drawing Single line or One line diagram of the given network with Ratings of all the transformers & Generators in the network.  Suitable Base MVA is chosen. For ex. 100 MVA.  Per Unit reactance (impedence) is calculated for every Transformer & Generator in the given network by using-
  • 10. Formula P.u reactance = [(% impedence)/100] x [Base MVA/Actual MVA]  Then redraw the network putting the P.u reactance values.  Calculate the Equivalent reactance for the for the network as seen from the source to the fault point.
  • 11.  Then, Calculate Fault MVA using formula- Fault MVA= Base MVA/ Eq. Impedence  Calculate Fault Current using formula= Fault Current = Fault MVA / (1.732x Phase to Phase Voltage at the fault point)
  • 12.
  • 13.
  • 14.
  • 15.
  • 16.
  • 17.
  • 18.
  • 19.
  • 20.
  • 21.
  • 22.
  • 23.
  • 24.
  • 25.
  • 26.
  • 27.
  • 28.
  • 29.
  • 30.
  • 31.
  • 32. Current Limiting Reactors:- Current Limiting Reactors ( Series Reactors) are inserted in series with the line, to limit the current flow in the event of a short Circuit & thereby, bring down the fault level. The current Limiting Reactors are also called Series Reactors. A current Limiting Reactor is an inductive coil having a large inductive reactance (wL) and is used for limiting short-circuit currents to be interrupted by circuit breaker.
  • 33.
  • 34.  If X is the reactance of a circuit , E is the voltage then by neglecting the resistance , the short circuit current is given by Isc= E / X. Therefore, by increasing the series reactance of the system, the short circuit current can be decreased. The short circuit current depends upon the generating capacity, voltage at the fault point and the total reactance between the generator and the fault point.
  • 35. The circuit breaker should have enough breaking current capacity such that the fault current are less than the breaking current capacity. IF the fault currents are beyond the capacity of the circuit breaker, the circuit breaker may not interrupt the fault current. Then the fault current should be limited by some means so that the existing circuit breaker can be used safely.
  • 36. Also when the system is extended by adding more generating stations, the Fault current to be interrupted by the same circuit breaker will be greater than before. In these cases, the circuit breaker should be replaced by another of higher breaking current capacity or the fault current can be limited by the means of REACTORS. The current limiting reactors are useful in limiting short circuit current so that the circuit breaker can interrupt them.
  • 37. 1) Reactors limit the Short Circuit Current. 2) Reactors are used in the systems when extensions are made and the circuit breaker breaking current capacities become inadequate. 3) Reactors are employed in Large Systems so as to limit the short circuit MVA to match with the breaking current capacity of the circuit breaker.
  • 38. Location of Series Reactor:-  Generator Reactors- Reactors are inserted between the generator and the generator bus. The high reactance is provided to safeguard the generators in case of dead three phase short circuits at its terminals. When new generators are installed , generator reactors can be added to the old generators.
  • 40. Feeder Reactors- The reactors in this case are connected in series with the feeders. The advantage is that the voltage of the bus does not drop substantially in the event of fault on the feeder.  The Busbar Reactor- The busbar reactor is placed between two sections of busbar.
  • 43. QUESTIONS:- 1) Why Fault Calculation is required? 2) What is meant by Breaking Current capacity & Making Current Capacity of Circuit Breaker? 3) What is the formula for Calculating Fault MVA? 4) What is the Formula for Calculating Fault Current? 5) What should be used to decrease Fault Level at any point?