SlideShare a Scribd company logo
1 of 20
Download to read offline
PROJECT : GENERAL CONDITION ASSESSMENT AND PREDICTING THE
REMNANT LIFE OF TRANSFORMER
CLIENT :
CONTRACTOR :
ORDER NO :
REPORT No :
DIAGNOSTIC TEST REPORT OF 22kV/0.4kV TRANSFORMER
A1 TR 19
Page2
TABLE OF CONTENTS
S/No. Description Page No.
1 Name Plate detail of Transformer 3
2 Insulation Resistance Test 4
3. Magnetic Balance Test 5
4. Vector Group Test 5
5. Magnetising current Test 6
6. Voltage Ratio Test 6
7. % Impedance Test 6
8. Winding Resistance Test 7
9. Tan Delta Test 7
10. SFRA Test 8-13
11. DFRA Test 14
12. Turn Ratio Test 14-15
13. Oil BDV & DGA Test,Furan Analysis
14. Analysis
15. Conclusion & Recommendation
Page3
1.0 Nameplate detail of Transformer:
Transformer Manufacturer / Serial Number
FRANCE TRANSFO /
11014601
Rated Power 800 KVA
Rated voltage primary – Maximum / Normal / Minimum 23100/22000/20900 volts
Rated voltage secondary 395 V
Full load current HV 21 A
Full load current LV 1169 A
Vector Group Dyn11
Impedance at - Maximum / Normal / Minimum (%) 4.5 %
Tap Changer type OFTC
No of tap / % step value 01-05
Type of Cooling ONAN
Page4
2.0 Insulation Resistance Measurement
Ambient Temp: 20.9 0C RH : 58%
Winding
Applied
Voltage
PI
R60 sec(Manual
Observation)
R600 sec
HV TO EARTH 5000V 1.82 4.66 GΩ 9.91 GΩ
LV TO EARTH 500V 2.46 1.99 GΩ 3.98 GΩ
HV TO LV 2500V 2.14 5.22 GΩ 11.56 GΩ
According to IEEE C57.125-1991
R=C.E/√K.V.A (1 min)
R - Insulation Resistance in MΩ
C – 1.5 for oil filled Transformers
E – Voltage rating in Volts
K.V.A – Rating of the transformer
P.I. VALUE CONDITION OF INSULATION
Less than 1.0 Dangerous
1.0-1.1 Poor
1.1-1.25 Questionable
1.25-2.0 Fair
Above 2.0 Good
Page5
3.0 Magnetic Balance Test
Voltage Applied
Between
(Volts)
HV side
Voltage measured (Volts)
LV side
Voltage Measured (Volts)
1U-1V 1V-1W 1W-1U
2u-n 2v-n 2w-n
1U-1V 392.6 392.9 279.8 111.6 4.073 2.919 1.170
1V-1W 392.6 202.2 393.1 188.2 2.087 4.075 1.988
1W-1U 391.9 103.8 285.4 392.4 1.088 2.982 4.067
4.0 Vector Group Test
Short terminals: 1U & 2u TAP POSITION: 3
Applied Voltage
(V)
Measured Voltage
between (V)
1U-1V 393.0 1U-2u -------
IV-1W 393.2 1U-2v -------
1W-1U 392.5 1U-2w -------
Condition : 1V-2u -------
1W 2w<1W 2v 1V-2v 386.9
386.5<392.6 1V-2w 386.9
1V 2v=1V 2w 1W-2u -------
386.9=386.9 1W-2v 392.6
1U2n+1V2n=1U1V 1W-2w 386.5
4.073+389.0=393.07 1U-2n 4.073
1V-2n 389.0
Page6
5.0 Magnetising Current Test
TAP
Applied Voltage (V) HV MAGNETISING CURRENT (mA)
1U-1V 1V-1W 1W-1U U V W
3 393.1 393.2 392.5 2.09 1.48 1.59
6.0 Voltage Ratio Test
TAP
NO
Applied Voltage (V) Measured Voltage (V)
1U-1V 1V-1W 1W-1U 2u-2v 2v-2w 2w-2u 2u-n 2v-n 2w-n
3 393.0 393.2 392.5 7.07 7.06 7.06 4.047 4.076 4.069
Page7
7.0 % Impedance Test
Tap
No
Applied Voltage at HV in
Volts
Measured HV Current in A Measured
LV
current in
A
%
Impedance
1U-1V 1V-1W 1W-1U 1U 1V 1W
3 392.6 392.6 391.9 7.82 8.14 7.79 447 4.60
According to I.E.C 60076-1,
at Principal tapping, allowable tolerance value if % impedance is <10 % is ±10%
of the declared value.
8.0 Winding ResistanceTest
H.V Winding Amb Temp= 19.4°C
Tap
Position
1U-1V
(Ω)
1V-1W
(Ω)
1W-1U
(Ω)
3 8.220 8.231 8.229
L.V Winding
2u-n 2v-n 2w-n
1.345 mΩ 1.347 mΩ 1.377 mΩ
Page8
9.0 Tan Delta and Capacitance Measurement:
Oil temp= 22°C RH%= 58.0% K Value – 0.97
Sr.
No
Capacitance
being
measured
Test
Mode
Measured
capacitance
(nF)
Insulation
P.F (%)
Insulatio
n P.F
(%)
Amp.
Temp˚C
Humidity
( RH) %
1 HV-E GST G 1.034 0.317 0.307 21.6 58
2 HV-LV UST Y 2.583 0.532
0.516
21.6 58
3 HV-LV+E GST YG 3.618 0.474
0.459
21.6 58
4 LV-E GST G 6.638 0.564
0.547
21.6 58
5 LV-HV UST Y 2.584 0.525
0.509
21.6 58
6 LV-HV+E GST YG 9.220 0.546
0.529
21.6 58
10.0 SFRA ANALYSIS:
1U-1V (LV OPEN)
-20
-30
-40
-50
-60
-70
-80
-90
Magnitude(dB)
100 1 k 10 k 100 k 1 M
Frequency (Hz)
[H1-H2 [open]]
Page9
1V-1W(LV OPEN)
1W-1U(LV OPEN)
1U,1V,1W(LV OPEN)
-10
-20
-30
-40
-50
-60
-70
-80
-90
Magnitude(dB)
100 1 k 10 k 100 k 1 M
Frequency (Hz)
[H2-H3 [open]]
-10
-20
-30
-40
-50
-60
-70
-80
-90
Magnitude(dB)
100 1 k 10 k 100 k 1 M
Frequency (Hz)
[H3-H1 [open] (1)]
Page10
X1-X0
X2-X0
-10
-20
-30
-40
-50
-60
-70
-80
-90
Magnitude(dB)
100 1 k 10 k 100 k 1 M
Frequency (Hz)
[H1-H2 [open]] [H2-H3 [open]] [H3-H1 [open] (1)]
0
-5
-10
-15
-20
Magnitude(dB)
100 1 k 10 k 100 k 1 M
Frequency (Hz)
[X1-X0 [open]]
Page11
X3-X0
0
-5
-10
-15
-20
Magnitude(dB)
100 1 k 10 k 100 k 1 M
Frequency (Hz)
[X2-X0 [open]]
0
-5
-10
-15
-20
Magnitude(dB)
100 1 k 10 k 100 k 1 M
Frequency (Hz)
[X3-X0 [open]]
Page12
X1-X0,X2-X0,X3-X0
1U-1V (LV SHORT)
1V – 1W(LV SHORT)
0
-5
-10
-15
-20
Magnitude(dB)
100 1 k 10 k 100 k 1 M
Frequency (Hz)
[X1-X0 [open]] [X2-X0 [open]] [X3-X0 [open]]
-10
-20
-30
-40
-50
-60
Magnitude(dB)
100 1 k 10 k 100 k 1 M
Frequency (Hz)
[H1-H2 [short X1-X2-X3]]
Page13
1W-1U (LV SHORT)
1U-1V,1V-1W,1W-1U (LV SHORT)
-10
-20
-30
-40
-50
-60
Magnitude(dB)
100 1 k 10 k 100 k 1 M
Frequency (Hz)
[H2-H3 [short X1-X2-X3]]
-10
-20
-30
-40
-50
-60
Magnitude(dB)
100 1 k 10 k 100 k 1 M
Frequency (Hz)
[H3-H1 [short X1-X2-X3]]
Page14
11.0 DFRA ANALYSIS:
Measured Graphs Vs Frequency (Attached Graphs)
✓ Oil Conductivity
✓ Polarisation Depolaraisation
✓ Tan Delta & Capacitance
✓ Tan Delta
✓ Powerfactor
✓ Impedance
-10
-20
-30
-40
-50
-60
Magnitude(dB)
100 1 k 10 k 100 k 1 M
Frequency (Hz)
[H1-H2 [short X1-X2-X3]] [H2-H3 [short X1-X2-X3]] [H3-H1 [short X1-X2-X3]]
Page15
12.0 TURNS RATIO TEST:
Reference Calculated Ratio Measured Ratio
H1-H3, X0-X3 96.469 96.463
H2-H1,X0-X1 96.469 96.494
H3-H2,X0-X2 96.469 96.505
Page16
Dissolved Gas Analysis
RECS uses American Standard C57.104-1991 and DUVAL Ratio Analysis technique to identify the
various faults within the transformer based on DGA Results.
Presence of the Key Gases
Hydrogen
Methane
Ethane
Ethylene
Carbon Monoxide(CO)
Carbon Dioxide (CO2)
Possible Faults
Based on the presence of the above gases, the possible faults are Partial Discharges (Corona), low
energy Discharges resulting in formation of gases and pressure inside the transformer. Also,
moisture content found is 5 mg/KG which indicates higher % of moisture content in oil.
Page17
Possible Findings & Observation at Site.
The transformer winding is in good condition. The defect and possible cause of DGPT Alarm can
be summarised with the following points.
1. A1TR19 is hermatically sealed transformer. It was found that transformer LV Bushings was
leaking and had oil spillage. During high atmospheric pressure present outside in comparison
to transformer tank pressure , it is assumed that oil has been contaminated with moisture
and other contaminations. Moisture has level has been indicated in DGA Report ( 6mg/KG)
which is higher.
2. Because of the oil filling practices from the top of DGPT, it is noted that moisture and
contaminations of atmosphere is dissolved. Filling of the DGTP has certain method as per the
manufacturer. Please refer to the attached documents of the manufaturer (AUTOMATION
2000 FRANCE ).
3. Based on the presence of the TDCG gases, the possible faults are Partial Discharges (Corona),
low energy Discharges resulting in formation of gases and pressure inside the transformer.
This is the reason for the DGPT Alarm.
4. DGPT was not grounded.
5. Calibration of DGPT is not up to the mark. DGPT Calibration should be of 1 year validity.
Calibration date should be marked properly. Also, Fault simulation synchronised with DGTP
should be done after reinstalling of DGPT after calibration.
6. Transformer should have been retrofitted with Breather and Pressure Relief Device ( PRD).
7. The maintenance practice of O&M Dept. at Zirku was not up to satisfactory level. The
maintenance pratice adopted is lead to failure maintenance which is also not fololwing any
international standard and engineering pratice.
The process of predictive maintenance should be followed and data trending process should
be implemted.
Page18
Analysis:
The analysis is based on the C75.104-1991 and DUVAL Ratio Analysis and they are summarized
as follows;
American Standard C57.104.1991
Table 4 and Table listed below has been used and taken from the above standard and being used
for the analysis purpose to find out the type of fault which transformer has.
Page19
DUVAL TRIANGLE:
The analysis using the DUVAL Triangle shows that the transformer has PD.
Conclusions and Recommendations:
1. It is concluded that the transformer is in Condition 4 and in critical stage. Transformer should
be taken out of service. The possible findings are weekend insulation due to electrical stress,
distintegration of paper insulation in oil with carbon and carbon tracking, possible loose
shield and poor grounding of metal objects.
2. Based on the above international standards and technique, It is concluded that there are
active fault inside the transformers. The Transformer should be isolated and should be taken
out of service.
3. It is recommeded to perform oil filtration, sludge bath with prescribed pressure and retrofit
the transformer.
4. While retrofitting , it should be fitted with Pressure Releif Device , Temperature Gauge,
Presssure Gauge & Breather .
5. It is recommeded to comply with DGPT Standard to fill the oil from the top. Hermatically
sealed transformer once opened by any means for e.g. DGPT are subject to oil filtration and
fault simulation of DGPT.
Page20
References
1. C57.104.1991
2. DUVAL Triangle
3. IEC 60076-1, IEC 60076-3, IEC 60076-5
4. CIGRE 342, 445, 343,349
Disclaimer

More Related Content

What's hot

Transformer overcurrent
Transformer overcurrentTransformer overcurrent
Transformer overcurrentmichaeljmack
 
Transformer maintenance
Transformer maintenance Transformer maintenance
Transformer maintenance Molla Morshad
 
Power transformer maintenance
Power transformer maintenancePower transformer maintenance
Power transformer maintenanceLucian Lazar
 
Switchgear - complete guide
Switchgear - complete guideSwitchgear - complete guide
Switchgear - complete guideSlides Hub
 
Presentation_Power_Transformers-1
Presentation_Power_Transformers-1Presentation_Power_Transformers-1
Presentation_Power_Transformers-1Nageswar Rao
 
Operation and maintenance of transformer
Operation and maintenance of transformerOperation and maintenance of transformer
Operation and maintenance of transformerKapil Singh
 
Transformer testing on sight and off sight
Transformer testing on sight and off sightTransformer testing on sight and off sight
Transformer testing on sight and off sightDHAVALKUMAR JULASANA
 
PRESENTATION ON MANUFACTURING OF TRANSFORMER By Dhruv Jimit
PRESENTATION ON MANUFACTURING OF TRANSFORMER By Dhruv JimitPRESENTATION ON MANUFACTURING OF TRANSFORMER By Dhruv Jimit
PRESENTATION ON MANUFACTURING OF TRANSFORMER By Dhruv JimitJimit Dhruv
 
Transformer Oil Testing
Transformer Oil TestingTransformer Oil Testing
Transformer Oil Testingengrsurif
 
ECNG 3015 - Overcurrent Protection
ECNG 3015 - Overcurrent ProtectionECNG 3015 - Overcurrent Protection
ECNG 3015 - Overcurrent ProtectionChandrabhan Sharma
 
Generator Protection Relay Setting Calculations
Generator Protection Relay Setting CalculationsGenerator Protection Relay Setting Calculations
Generator Protection Relay Setting CalculationsPower System Operation
 
Testing,maintenance&protection
Testing,maintenance&protectionTesting,maintenance&protection
Testing,maintenance&protectionRakesh Joshi
 
Transformer oil-specifications new
Transformer oil-specifications newTransformer oil-specifications new
Transformer oil-specifications newMolla Morshad
 
Transformer Diagnostics | Sweep Frequency Response Analysis
Transformer Diagnostics | Sweep Frequency Response AnalysisTransformer Diagnostics | Sweep Frequency Response Analysis
Transformer Diagnostics | Sweep Frequency Response AnalysisHamedPasha1
 
Transformer factory acceptance tests
Transformer factory acceptance testsTransformer factory acceptance tests
Transformer factory acceptance testsengrsurif
 
Power Transformer Protection
Power Transformer ProtectionPower Transformer Protection
Power Transformer ProtectionAng Sovann
 

What's hot (20)

Transformer overcurrent
Transformer overcurrentTransformer overcurrent
Transformer overcurrent
 
Transformer maintenance
Transformer maintenance Transformer maintenance
Transformer maintenance
 
Power transformer maintenance
Power transformer maintenancePower transformer maintenance
Power transformer maintenance
 
Switchgear - complete guide
Switchgear - complete guideSwitchgear - complete guide
Switchgear - complete guide
 
Presentation_Power_Transformers-1
Presentation_Power_Transformers-1Presentation_Power_Transformers-1
Presentation_Power_Transformers-1
 
Operation and maintenance of transformer
Operation and maintenance of transformerOperation and maintenance of transformer
Operation and maintenance of transformer
 
Transformer testing on sight and off sight
Transformer testing on sight and off sightTransformer testing on sight and off sight
Transformer testing on sight and off sight
 
PRESENTATION ON MANUFACTURING OF TRANSFORMER By Dhruv Jimit
PRESENTATION ON MANUFACTURING OF TRANSFORMER By Dhruv JimitPRESENTATION ON MANUFACTURING OF TRANSFORMER By Dhruv Jimit
PRESENTATION ON MANUFACTURING OF TRANSFORMER By Dhruv Jimit
 
Transformer Oil Testing
Transformer Oil TestingTransformer Oil Testing
Transformer Oil Testing
 
Transformer
TransformerTransformer
Transformer
 
ECNG 3015 - Overcurrent Protection
ECNG 3015 - Overcurrent ProtectionECNG 3015 - Overcurrent Protection
ECNG 3015 - Overcurrent Protection
 
Generator Protection Relay Setting Calculations
Generator Protection Relay Setting CalculationsGenerator Protection Relay Setting Calculations
Generator Protection Relay Setting Calculations
 
Testing,maintenance&protection
Testing,maintenance&protectionTesting,maintenance&protection
Testing,maintenance&protection
 
Transformer oil-specifications new
Transformer oil-specifications newTransformer oil-specifications new
Transformer oil-specifications new
 
Distribution transformer
Distribution transformerDistribution transformer
Distribution transformer
 
Power Transformer Protection
Power Transformer ProtectionPower Transformer Protection
Power Transformer Protection
 
Transformer Diagnostics | Sweep Frequency Response Analysis
Transformer Diagnostics | Sweep Frequency Response AnalysisTransformer Diagnostics | Sweep Frequency Response Analysis
Transformer Diagnostics | Sweep Frequency Response Analysis
 
Transformer basic
Transformer basicTransformer basic
Transformer basic
 
Transformer factory acceptance tests
Transformer factory acceptance testsTransformer factory acceptance tests
Transformer factory acceptance tests
 
Power Transformer Protection
Power Transformer ProtectionPower Transformer Protection
Power Transformer Protection
 

Similar to TRANSFORMER SAMPLE REPORT DGA PHYSICAL CONDITION

Bushing test tap
Bushing test tapBushing test tap
Bushing test tapbijumt
 
Original Mosfet N-Channel FQA9N90 9N90C 9N90 900V 8.6A TO-3P New Fairchild
Original Mosfet N-Channel FQA9N90 9N90C 9N90 900V 8.6A TO-3P New FairchildOriginal Mosfet N-Channel FQA9N90 9N90C 9N90 900V 8.6A TO-3P New Fairchild
Original Mosfet N-Channel FQA9N90 9N90C 9N90 900V 8.6A TO-3P New FairchildAUTHELECTRONIC
 
KEMET Webinar - C4AQ/C4AF power box film capacitors
KEMET Webinar -  C4AQ/C4AF power box film capacitorsKEMET Webinar -  C4AQ/C4AF power box film capacitors
KEMET Webinar - C4AQ/C4AF power box film capacitorsIvana Ivanovska
 
WEG Contactors Oveload Relays
WEG Contactors Oveload RelaysWEG Contactors Oveload Relays
WEG Contactors Oveload RelaysAllan Bernardino
 
VHIA - 071122.pdf
VHIA -  071122.pdfVHIA -  071122.pdf
VHIA - 071122.pdfhtrindia
 
Original MOSFET P20NM60 20NM60 20N60C3 20N60 New
Original MOSFET P20NM60 20NM60 20N60C3 20N60 NewOriginal MOSFET P20NM60 20NM60 20N60C3 20N60 New
Original MOSFET P20NM60 20NM60 20N60C3 20N60 NewAUTHELECTRONIC
 
Original MOSFET N-Channel STGF10NC60KD GF10NC60KD 10NC60 10N60 10A 600V New
Original MOSFET N-Channel STGF10NC60KD GF10NC60KD 10NC60 10N60 10A 600V NewOriginal MOSFET N-Channel STGF10NC60KD GF10NC60KD 10NC60 10N60 10A 600V New
Original MOSFET N-Channel STGF10NC60KD GF10NC60KD 10NC60 10N60 10A 600V NewAUTHELECTRONIC
 
Original N-Channel Mosfet STF9NK90Z F9NK90Z 8A 900V TO-220F New STMicroelectr...
Original N-Channel Mosfet STF9NK90Z F9NK90Z 8A 900V TO-220F New STMicroelectr...Original N-Channel Mosfet STF9NK90Z F9NK90Z 8A 900V TO-220F New STMicroelectr...
Original N-Channel Mosfet STF9NK90Z F9NK90Z 8A 900V TO-220F New STMicroelectr...AUTHELECTRONIC
 
KEMET Webinar - Long Life and Humidity Grade New Film Box AC Filters
KEMET Webinar - Long Life and Humidity Grade New Film Box AC FiltersKEMET Webinar - Long Life and Humidity Grade New Film Box AC Filters
KEMET Webinar - Long Life and Humidity Grade New Film Box AC FiltersMarkus Trautz
 
Original N-CHANNEL Mosfet FQPF10N60 10N60 10A 600V TO-220F New Fairchild
Original N-CHANNEL Mosfet FQPF10N60 10N60 10A 600V TO-220F New FairchildOriginal N-CHANNEL Mosfet FQPF10N60 10N60 10A 600V TO-220F New Fairchild
Original N-CHANNEL Mosfet FQPF10N60 10N60 10A 600V TO-220F New FairchildAUTHELECTRONIC
 
Diagnostics Chart with Trouble Code - Subaru Legacy
Diagnostics Chart with Trouble Code - Subaru LegacyDiagnostics Chart with Trouble Code - Subaru Legacy
Diagnostics Chart with Trouble Code - Subaru LegacyOBD Codex
 
Diagnostics Chart with Trouble Code
Diagnostics Chart with Trouble CodeDiagnostics Chart with Trouble Code
Diagnostics Chart with Trouble CodeOBD Codex
 
Optimization of H2 Production in a Hydrogen Generation Unit
Optimization of H2 Production in a Hydrogen Generation UnitOptimization of H2 Production in a Hydrogen Generation Unit
Optimization of H2 Production in a Hydrogen Generation UnitMárcio Garcia
 
Toyota 30 5 fbch20 battery forklift service repair manual
Toyota 30 5 fbch20 battery forklift service repair manualToyota 30 5 fbch20 battery forklift service repair manual
Toyota 30 5 fbch20 battery forklift service repair manualufsiekdolskek
 

Similar to TRANSFORMER SAMPLE REPORT DGA PHYSICAL CONDITION (20)

Bushing test tap
Bushing test tapBushing test tap
Bushing test tap
 
H010514852
H010514852H010514852
H010514852
 
Original Mosfet N-Channel FQA9N90 9N90C 9N90 900V 8.6A TO-3P New Fairchild
Original Mosfet N-Channel FQA9N90 9N90C 9N90 900V 8.6A TO-3P New FairchildOriginal Mosfet N-Channel FQA9N90 9N90C 9N90 900V 8.6A TO-3P New Fairchild
Original Mosfet N-Channel FQA9N90 9N90C 9N90 900V 8.6A TO-3P New Fairchild
 
Vortex flow meter manual
Vortex flow meter manualVortex flow meter manual
Vortex flow meter manual
 
KEMET Webinar - C4AQ/C4AF power box film capacitors
KEMET Webinar -  C4AQ/C4AF power box film capacitorsKEMET Webinar -  C4AQ/C4AF power box film capacitors
KEMET Webinar - C4AQ/C4AF power box film capacitors
 
WEG Contactors Oveload Relays
WEG Contactors Oveload RelaysWEG Contactors Oveload Relays
WEG Contactors Oveload Relays
 
VHIA - 071122.pdf
VHIA -  071122.pdfVHIA -  071122.pdf
VHIA - 071122.pdf
 
Original MOSFET P20NM60 20NM60 20N60C3 20N60 New
Original MOSFET P20NM60 20NM60 20N60C3 20N60 NewOriginal MOSFET P20NM60 20NM60 20N60C3 20N60 New
Original MOSFET P20NM60 20NM60 20N60C3 20N60 New
 
Original MOSFET N-Channel STGF10NC60KD GF10NC60KD 10NC60 10N60 10A 600V New
Original MOSFET N-Channel STGF10NC60KD GF10NC60KD 10NC60 10N60 10A 600V NewOriginal MOSFET N-Channel STGF10NC60KD GF10NC60KD 10NC60 10N60 10A 600V New
Original MOSFET N-Channel STGF10NC60KD GF10NC60KD 10NC60 10N60 10A 600V New
 
Original N-Channel Mosfet STF9NK90Z F9NK90Z 8A 900V TO-220F New STMicroelectr...
Original N-Channel Mosfet STF9NK90Z F9NK90Z 8A 900V TO-220F New STMicroelectr...Original N-Channel Mosfet STF9NK90Z F9NK90Z 8A 900V TO-220F New STMicroelectr...
Original N-Channel Mosfet STF9NK90Z F9NK90Z 8A 900V TO-220F New STMicroelectr...
 
Ucc 3895 dw
Ucc 3895 dwUcc 3895 dw
Ucc 3895 dw
 
KEMET Webinar - Long Life and Humidity Grade New Film Box AC Filters
KEMET Webinar - Long Life and Humidity Grade New Film Box AC FiltersKEMET Webinar - Long Life and Humidity Grade New Film Box AC Filters
KEMET Webinar - Long Life and Humidity Grade New Film Box AC Filters
 
Original N-CHANNEL Mosfet FQPF10N60 10N60 10A 600V TO-220F New Fairchild
Original N-CHANNEL Mosfet FQPF10N60 10N60 10A 600V TO-220F New FairchildOriginal N-CHANNEL Mosfet FQPF10N60 10N60 10A 600V TO-220F New Fairchild
Original N-CHANNEL Mosfet FQPF10N60 10N60 10A 600V TO-220F New Fairchild
 
Mr j2-a separate-specification_installationmanual_ib-67315-a
Mr j2-a separate-specification_installationmanual_ib-67315-aMr j2-a separate-specification_installationmanual_ib-67315-a
Mr j2-a separate-specification_installationmanual_ib-67315-a
 
1.1 ron 1
1.1 ron 11.1 ron 1
1.1 ron 1
 
Diagnostics Chart with Trouble Code - Subaru Legacy
Diagnostics Chart with Trouble Code - Subaru LegacyDiagnostics Chart with Trouble Code - Subaru Legacy
Diagnostics Chart with Trouble Code - Subaru Legacy
 
Diagnostics Chart with Trouble Code
Diagnostics Chart with Trouble CodeDiagnostics Chart with Trouble Code
Diagnostics Chart with Trouble Code
 
3 condition monitoring of oil
3 condition monitoring of oil3 condition monitoring of oil
3 condition monitoring of oil
 
Optimization of H2 Production in a Hydrogen Generation Unit
Optimization of H2 Production in a Hydrogen Generation UnitOptimization of H2 Production in a Hydrogen Generation Unit
Optimization of H2 Production in a Hydrogen Generation Unit
 
Toyota 30 5 fbch20 battery forklift service repair manual
Toyota 30 5 fbch20 battery forklift service repair manualToyota 30 5 fbch20 battery forklift service repair manual
Toyota 30 5 fbch20 battery forklift service repair manual
 

Recently uploaded

VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130Suhani Kapoor
 
VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...
VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...
VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...VICTOR MAESTRE RAMIREZ
 
Call Girls Delhi {Jodhpur} 9711199012 high profile service
Call Girls Delhi {Jodhpur} 9711199012 high profile serviceCall Girls Delhi {Jodhpur} 9711199012 high profile service
Call Girls Delhi {Jodhpur} 9711199012 high profile servicerehmti665
 
Gurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort service
Gurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort serviceGurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort service
Gurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort servicejennyeacort
 
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...ranjana rawat
 
CCS355 Neural Network & Deep Learning UNIT III notes and Question bank .pdf
CCS355 Neural Network & Deep Learning UNIT III notes and Question bank .pdfCCS355 Neural Network & Deep Learning UNIT III notes and Question bank .pdf
CCS355 Neural Network & Deep Learning UNIT III notes and Question bank .pdfAsst.prof M.Gokilavani
 
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝soniya singh
 
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escortsranjana rawat
 
SPICE PARK APR2024 ( 6,793 SPICE Models )
SPICE PARK APR2024 ( 6,793 SPICE Models )SPICE PARK APR2024 ( 6,793 SPICE Models )
SPICE PARK APR2024 ( 6,793 SPICE Models )Tsuyoshi Horigome
 
Application of Residue Theorem to evaluate real integrations.pptx
Application of Residue Theorem to evaluate real integrations.pptxApplication of Residue Theorem to evaluate real integrations.pptx
Application of Residue Theorem to evaluate real integrations.pptx959SahilShah
 
Introduction to Microprocesso programming and interfacing.pptx
Introduction to Microprocesso programming and interfacing.pptxIntroduction to Microprocesso programming and interfacing.pptx
Introduction to Microprocesso programming and interfacing.pptxvipinkmenon1
 
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptxDecoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptxJoão Esperancinha
 
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escortsranjana rawat
 
What are the advantages and disadvantages of membrane structures.pptx
What are the advantages and disadvantages of membrane structures.pptxWhat are the advantages and disadvantages of membrane structures.pptx
What are the advantages and disadvantages of membrane structures.pptxwendy cai
 
CCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdf
CCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdfCCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdf
CCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdfAsst.prof M.Gokilavani
 
HARMONY IN THE NATURE AND EXISTENCE - Unit-IV
HARMONY IN THE NATURE AND EXISTENCE - Unit-IVHARMONY IN THE NATURE AND EXISTENCE - Unit-IV
HARMONY IN THE NATURE AND EXISTENCE - Unit-IVRajaP95
 
Study on Air-Water & Water-Water Heat Exchange in a Finned Tube Exchanger
Study on Air-Water & Water-Water Heat Exchange in a Finned Tube ExchangerStudy on Air-Water & Water-Water Heat Exchange in a Finned Tube Exchanger
Study on Air-Water & Water-Water Heat Exchange in a Finned Tube ExchangerAnamika Sarkar
 

Recently uploaded (20)

VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130
 
Call Us -/9953056974- Call Girls In Vikaspuri-/- Delhi NCR
Call Us -/9953056974- Call Girls In Vikaspuri-/- Delhi NCRCall Us -/9953056974- Call Girls In Vikaspuri-/- Delhi NCR
Call Us -/9953056974- Call Girls In Vikaspuri-/- Delhi NCR
 
VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...
VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...
VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...
 
Call Girls Delhi {Jodhpur} 9711199012 high profile service
Call Girls Delhi {Jodhpur} 9711199012 high profile serviceCall Girls Delhi {Jodhpur} 9711199012 high profile service
Call Girls Delhi {Jodhpur} 9711199012 high profile service
 
Gurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort service
Gurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort serviceGurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort service
Gurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort service
 
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
 
CCS355 Neural Network & Deep Learning UNIT III notes and Question bank .pdf
CCS355 Neural Network & Deep Learning UNIT III notes and Question bank .pdfCCS355 Neural Network & Deep Learning UNIT III notes and Question bank .pdf
CCS355 Neural Network & Deep Learning UNIT III notes and Question bank .pdf
 
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝
 
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
 
SPICE PARK APR2024 ( 6,793 SPICE Models )
SPICE PARK APR2024 ( 6,793 SPICE Models )SPICE PARK APR2024 ( 6,793 SPICE Models )
SPICE PARK APR2024 ( 6,793 SPICE Models )
 
Application of Residue Theorem to evaluate real integrations.pptx
Application of Residue Theorem to evaluate real integrations.pptxApplication of Residue Theorem to evaluate real integrations.pptx
Application of Residue Theorem to evaluate real integrations.pptx
 
9953056974 Call Girls In South Ex, Escorts (Delhi) NCR.pdf
9953056974 Call Girls In South Ex, Escorts (Delhi) NCR.pdf9953056974 Call Girls In South Ex, Escorts (Delhi) NCR.pdf
9953056974 Call Girls In South Ex, Escorts (Delhi) NCR.pdf
 
Introduction to Microprocesso programming and interfacing.pptx
Introduction to Microprocesso programming and interfacing.pptxIntroduction to Microprocesso programming and interfacing.pptx
Introduction to Microprocesso programming and interfacing.pptx
 
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptxDecoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
 
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
 
What are the advantages and disadvantages of membrane structures.pptx
What are the advantages and disadvantages of membrane structures.pptxWhat are the advantages and disadvantages of membrane structures.pptx
What are the advantages and disadvantages of membrane structures.pptx
 
CCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdf
CCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdfCCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdf
CCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdf
 
HARMONY IN THE NATURE AND EXISTENCE - Unit-IV
HARMONY IN THE NATURE AND EXISTENCE - Unit-IVHARMONY IN THE NATURE AND EXISTENCE - Unit-IV
HARMONY IN THE NATURE AND EXISTENCE - Unit-IV
 
Study on Air-Water & Water-Water Heat Exchange in a Finned Tube Exchanger
Study on Air-Water & Water-Water Heat Exchange in a Finned Tube ExchangerStudy on Air-Water & Water-Water Heat Exchange in a Finned Tube Exchanger
Study on Air-Water & Water-Water Heat Exchange in a Finned Tube Exchanger
 
Exploring_Network_Security_with_JA3_by_Rakesh Seal.pptx
Exploring_Network_Security_with_JA3_by_Rakesh Seal.pptxExploring_Network_Security_with_JA3_by_Rakesh Seal.pptx
Exploring_Network_Security_with_JA3_by_Rakesh Seal.pptx
 

TRANSFORMER SAMPLE REPORT DGA PHYSICAL CONDITION

  • 1. PROJECT : GENERAL CONDITION ASSESSMENT AND PREDICTING THE REMNANT LIFE OF TRANSFORMER CLIENT : CONTRACTOR : ORDER NO : REPORT No : DIAGNOSTIC TEST REPORT OF 22kV/0.4kV TRANSFORMER A1 TR 19
  • 2. Page2 TABLE OF CONTENTS S/No. Description Page No. 1 Name Plate detail of Transformer 3 2 Insulation Resistance Test 4 3. Magnetic Balance Test 5 4. Vector Group Test 5 5. Magnetising current Test 6 6. Voltage Ratio Test 6 7. % Impedance Test 6 8. Winding Resistance Test 7 9. Tan Delta Test 7 10. SFRA Test 8-13 11. DFRA Test 14 12. Turn Ratio Test 14-15 13. Oil BDV & DGA Test,Furan Analysis 14. Analysis 15. Conclusion & Recommendation
  • 3. Page3 1.0 Nameplate detail of Transformer: Transformer Manufacturer / Serial Number FRANCE TRANSFO / 11014601 Rated Power 800 KVA Rated voltage primary – Maximum / Normal / Minimum 23100/22000/20900 volts Rated voltage secondary 395 V Full load current HV 21 A Full load current LV 1169 A Vector Group Dyn11 Impedance at - Maximum / Normal / Minimum (%) 4.5 % Tap Changer type OFTC No of tap / % step value 01-05 Type of Cooling ONAN
  • 4. Page4 2.0 Insulation Resistance Measurement Ambient Temp: 20.9 0C RH : 58% Winding Applied Voltage PI R60 sec(Manual Observation) R600 sec HV TO EARTH 5000V 1.82 4.66 GΩ 9.91 GΩ LV TO EARTH 500V 2.46 1.99 GΩ 3.98 GΩ HV TO LV 2500V 2.14 5.22 GΩ 11.56 GΩ According to IEEE C57.125-1991 R=C.E/√K.V.A (1 min) R - Insulation Resistance in MΩ C – 1.5 for oil filled Transformers E – Voltage rating in Volts K.V.A – Rating of the transformer P.I. VALUE CONDITION OF INSULATION Less than 1.0 Dangerous 1.0-1.1 Poor 1.1-1.25 Questionable 1.25-2.0 Fair Above 2.0 Good
  • 5. Page5 3.0 Magnetic Balance Test Voltage Applied Between (Volts) HV side Voltage measured (Volts) LV side Voltage Measured (Volts) 1U-1V 1V-1W 1W-1U 2u-n 2v-n 2w-n 1U-1V 392.6 392.9 279.8 111.6 4.073 2.919 1.170 1V-1W 392.6 202.2 393.1 188.2 2.087 4.075 1.988 1W-1U 391.9 103.8 285.4 392.4 1.088 2.982 4.067 4.0 Vector Group Test Short terminals: 1U & 2u TAP POSITION: 3 Applied Voltage (V) Measured Voltage between (V) 1U-1V 393.0 1U-2u ------- IV-1W 393.2 1U-2v ------- 1W-1U 392.5 1U-2w ------- Condition : 1V-2u ------- 1W 2w<1W 2v 1V-2v 386.9 386.5<392.6 1V-2w 386.9 1V 2v=1V 2w 1W-2u ------- 386.9=386.9 1W-2v 392.6 1U2n+1V2n=1U1V 1W-2w 386.5 4.073+389.0=393.07 1U-2n 4.073 1V-2n 389.0
  • 6. Page6 5.0 Magnetising Current Test TAP Applied Voltage (V) HV MAGNETISING CURRENT (mA) 1U-1V 1V-1W 1W-1U U V W 3 393.1 393.2 392.5 2.09 1.48 1.59 6.0 Voltage Ratio Test TAP NO Applied Voltage (V) Measured Voltage (V) 1U-1V 1V-1W 1W-1U 2u-2v 2v-2w 2w-2u 2u-n 2v-n 2w-n 3 393.0 393.2 392.5 7.07 7.06 7.06 4.047 4.076 4.069
  • 7. Page7 7.0 % Impedance Test Tap No Applied Voltage at HV in Volts Measured HV Current in A Measured LV current in A % Impedance 1U-1V 1V-1W 1W-1U 1U 1V 1W 3 392.6 392.6 391.9 7.82 8.14 7.79 447 4.60 According to I.E.C 60076-1, at Principal tapping, allowable tolerance value if % impedance is <10 % is ±10% of the declared value. 8.0 Winding ResistanceTest H.V Winding Amb Temp= 19.4°C Tap Position 1U-1V (Ω) 1V-1W (Ω) 1W-1U (Ω) 3 8.220 8.231 8.229 L.V Winding 2u-n 2v-n 2w-n 1.345 mΩ 1.347 mΩ 1.377 mΩ
  • 8. Page8 9.0 Tan Delta and Capacitance Measurement: Oil temp= 22°C RH%= 58.0% K Value – 0.97 Sr. No Capacitance being measured Test Mode Measured capacitance (nF) Insulation P.F (%) Insulatio n P.F (%) Amp. Temp˚C Humidity ( RH) % 1 HV-E GST G 1.034 0.317 0.307 21.6 58 2 HV-LV UST Y 2.583 0.532 0.516 21.6 58 3 HV-LV+E GST YG 3.618 0.474 0.459 21.6 58 4 LV-E GST G 6.638 0.564 0.547 21.6 58 5 LV-HV UST Y 2.584 0.525 0.509 21.6 58 6 LV-HV+E GST YG 9.220 0.546 0.529 21.6 58 10.0 SFRA ANALYSIS: 1U-1V (LV OPEN) -20 -30 -40 -50 -60 -70 -80 -90 Magnitude(dB) 100 1 k 10 k 100 k 1 M Frequency (Hz) [H1-H2 [open]]
  • 9. Page9 1V-1W(LV OPEN) 1W-1U(LV OPEN) 1U,1V,1W(LV OPEN) -10 -20 -30 -40 -50 -60 -70 -80 -90 Magnitude(dB) 100 1 k 10 k 100 k 1 M Frequency (Hz) [H2-H3 [open]] -10 -20 -30 -40 -50 -60 -70 -80 -90 Magnitude(dB) 100 1 k 10 k 100 k 1 M Frequency (Hz) [H3-H1 [open] (1)]
  • 10. Page10 X1-X0 X2-X0 -10 -20 -30 -40 -50 -60 -70 -80 -90 Magnitude(dB) 100 1 k 10 k 100 k 1 M Frequency (Hz) [H1-H2 [open]] [H2-H3 [open]] [H3-H1 [open] (1)] 0 -5 -10 -15 -20 Magnitude(dB) 100 1 k 10 k 100 k 1 M Frequency (Hz) [X1-X0 [open]]
  • 11. Page11 X3-X0 0 -5 -10 -15 -20 Magnitude(dB) 100 1 k 10 k 100 k 1 M Frequency (Hz) [X2-X0 [open]] 0 -5 -10 -15 -20 Magnitude(dB) 100 1 k 10 k 100 k 1 M Frequency (Hz) [X3-X0 [open]]
  • 12. Page12 X1-X0,X2-X0,X3-X0 1U-1V (LV SHORT) 1V – 1W(LV SHORT) 0 -5 -10 -15 -20 Magnitude(dB) 100 1 k 10 k 100 k 1 M Frequency (Hz) [X1-X0 [open]] [X2-X0 [open]] [X3-X0 [open]] -10 -20 -30 -40 -50 -60 Magnitude(dB) 100 1 k 10 k 100 k 1 M Frequency (Hz) [H1-H2 [short X1-X2-X3]]
  • 13. Page13 1W-1U (LV SHORT) 1U-1V,1V-1W,1W-1U (LV SHORT) -10 -20 -30 -40 -50 -60 Magnitude(dB) 100 1 k 10 k 100 k 1 M Frequency (Hz) [H2-H3 [short X1-X2-X3]] -10 -20 -30 -40 -50 -60 Magnitude(dB) 100 1 k 10 k 100 k 1 M Frequency (Hz) [H3-H1 [short X1-X2-X3]]
  • 14. Page14 11.0 DFRA ANALYSIS: Measured Graphs Vs Frequency (Attached Graphs) ✓ Oil Conductivity ✓ Polarisation Depolaraisation ✓ Tan Delta & Capacitance ✓ Tan Delta ✓ Powerfactor ✓ Impedance -10 -20 -30 -40 -50 -60 Magnitude(dB) 100 1 k 10 k 100 k 1 M Frequency (Hz) [H1-H2 [short X1-X2-X3]] [H2-H3 [short X1-X2-X3]] [H3-H1 [short X1-X2-X3]]
  • 15. Page15 12.0 TURNS RATIO TEST: Reference Calculated Ratio Measured Ratio H1-H3, X0-X3 96.469 96.463 H2-H1,X0-X1 96.469 96.494 H3-H2,X0-X2 96.469 96.505
  • 16. Page16 Dissolved Gas Analysis RECS uses American Standard C57.104-1991 and DUVAL Ratio Analysis technique to identify the various faults within the transformer based on DGA Results. Presence of the Key Gases Hydrogen Methane Ethane Ethylene Carbon Monoxide(CO) Carbon Dioxide (CO2) Possible Faults Based on the presence of the above gases, the possible faults are Partial Discharges (Corona), low energy Discharges resulting in formation of gases and pressure inside the transformer. Also, moisture content found is 5 mg/KG which indicates higher % of moisture content in oil.
  • 17. Page17 Possible Findings & Observation at Site. The transformer winding is in good condition. The defect and possible cause of DGPT Alarm can be summarised with the following points. 1. A1TR19 is hermatically sealed transformer. It was found that transformer LV Bushings was leaking and had oil spillage. During high atmospheric pressure present outside in comparison to transformer tank pressure , it is assumed that oil has been contaminated with moisture and other contaminations. Moisture has level has been indicated in DGA Report ( 6mg/KG) which is higher. 2. Because of the oil filling practices from the top of DGPT, it is noted that moisture and contaminations of atmosphere is dissolved. Filling of the DGTP has certain method as per the manufacturer. Please refer to the attached documents of the manufaturer (AUTOMATION 2000 FRANCE ). 3. Based on the presence of the TDCG gases, the possible faults are Partial Discharges (Corona), low energy Discharges resulting in formation of gases and pressure inside the transformer. This is the reason for the DGPT Alarm. 4. DGPT was not grounded. 5. Calibration of DGPT is not up to the mark. DGPT Calibration should be of 1 year validity. Calibration date should be marked properly. Also, Fault simulation synchronised with DGTP should be done after reinstalling of DGPT after calibration. 6. Transformer should have been retrofitted with Breather and Pressure Relief Device ( PRD). 7. The maintenance practice of O&M Dept. at Zirku was not up to satisfactory level. The maintenance pratice adopted is lead to failure maintenance which is also not fololwing any international standard and engineering pratice. The process of predictive maintenance should be followed and data trending process should be implemted.
  • 18. Page18 Analysis: The analysis is based on the C75.104-1991 and DUVAL Ratio Analysis and they are summarized as follows; American Standard C57.104.1991 Table 4 and Table listed below has been used and taken from the above standard and being used for the analysis purpose to find out the type of fault which transformer has.
  • 19. Page19 DUVAL TRIANGLE: The analysis using the DUVAL Triangle shows that the transformer has PD. Conclusions and Recommendations: 1. It is concluded that the transformer is in Condition 4 and in critical stage. Transformer should be taken out of service. The possible findings are weekend insulation due to electrical stress, distintegration of paper insulation in oil with carbon and carbon tracking, possible loose shield and poor grounding of metal objects. 2. Based on the above international standards and technique, It is concluded that there are active fault inside the transformers. The Transformer should be isolated and should be taken out of service. 3. It is recommeded to perform oil filtration, sludge bath with prescribed pressure and retrofit the transformer. 4. While retrofitting , it should be fitted with Pressure Releif Device , Temperature Gauge, Presssure Gauge & Breather . 5. It is recommeded to comply with DGPT Standard to fill the oil from the top. Hermatically sealed transformer once opened by any means for e.g. DGPT are subject to oil filtration and fault simulation of DGPT.
  • 20. Page20 References 1. C57.104.1991 2. DUVAL Triangle 3. IEC 60076-1, IEC 60076-3, IEC 60076-5 4. CIGRE 342, 445, 343,349 Disclaimer