Protection Settings
Calculations
PROTECTION SETTINGS CALCULATIONS
Useful information
- Base MVA = 100MVA
- Rating of the TX 2 = 7.5MVA
- Percentage Impedance of the TX 2 at Tap 9 and Tap 17 is 7.70% and 7.47%
respectively
- Fault MVA at Chemosit 33kV bus = 0
62.10426.258 −∠
- Conductor size of the 33kV Kericho feeder and length from Chemosit is 2
75mm
ACSR and 20KM respectively
- Settings for 5L5 at Chemosit (Back up O/C & E/F);
 O/C : PSM = 300A, & TMS = 0.3
 E/F: PSM = 50A, & TMS = 0.4
Source Impedance`Calculation
0
62.104
26.258
100
)33( ∠=
MVA
MVA
kVZs
.3747.0098.0 puj−−=
Total Z p.u of the 33kV Kericho feeder upto the 33kV bus at Kericho 33/11kV s/s
)0365.00375.0(20)33(2
75
jxkVZ mm
+=
puj 73.075.0 +=
Impedance p.u. of the 7.5MVA TX 2 as expressed to the new MVA base (Tap 17)
= upj .996.0
The resultant Total impedance p.u. upto 11kV bus
)2()33()( 5.77511 2 TXZkVZZbusZ MVAmmskV ++=
= puj 3513.16523.0 +
Resultant fault MVA
= MVA0
23.6464.66 −∠
Fault Current at the 11kV bus
7.5MVA TX 2 – Kericho 33/11kV s/s
Calculations by: afanda rodgers
)3513.16523.0(
100
j
MVA
MVAf
+
=
1005.7
10047.7
)2(5.7
xMVA
MVAx
jTXZ MVA =
April
2016
4
Protection Settings
Calculations
A
kVx
MVAx
I f
113
100064.66
=
= A89.3497
Protection relays/equipment operating times calculations on the 11kV fault current of
3497.89A (ph – ph)
1. 5L5 O/C relay
sec
1)
3003
89.3497(
3.014.0
)/( 02.055
−
=
x
x
cot L
=1.5260 sec
2. New 7.5MVA TX 2 HV O/C relay
sec
1)
1503
89.3497(
35.014.0
)/( 02.0
−
=
x
x
cotHV
=1.1704 sec
Operating margin between the two units above is 0.357 sec
3. New 7.5MVA TX 2 LV O/C relay
sec
1)
396
89.3497(
25.014.0
)/( 02.0
−
=
x
cotLV
=0.7860 sec
Operating margin between LV and HV over current is 0.385 sec
4. All 11kV feeder reclosers
sec
1)
300
89.3497(
14.014.0
)/( 02.011
−
=
x
cot recloserskv
7.5MVA TX 2 – Kericho 33/11kV s/s
Calculations by: afanda rodgers
April
2016
4
Protection Settings
Calculations
=0.3893 sec
Operating Margin between TX 2 LV O/C and 11kV reclosers is 0.397 sec
Operating times of protection units on 11kV Earthfaults of 1165.96A
1. 5L5 E/F relay
sec
1)
50
6.388(
3.014.0
)/( 02.055
−
=
x
FEt L
=1.3376 sec
2. 7.5MVA TX 2 SBEF relay
sec
1)
80
96.1165(
38.014.0
)/( 02.0
−
=
x
FEtSBEF
= 0.9664 sec
Operating margin between 5L5 and the 7.5MVA TX 2 SBEF is 0.3712 sec
3. TX 2 LV E/F
sec
1)
45
96.1165(
3.014.0
)/( 02.0
−
=
x
FEtTX
=0.6245 sec
Operating margin between the TX 2 SBEF and TX 2 LV E/F is 0.3420 sec
4. 11kV feeder reclosers
7.5MVA TX 2 – Kericho 33/11kV s/s
Calculations by: afanda rodgers
April
2016
4
Protection Settings
Calculations
sec
1)
15
96.1165(
15.014.0
)/( 02.011
−
=
x
FEt recloserskV
= 0.2310 sec
Operating Margin between the TX 2 LV E/F and the 11kV reclosers is 0.3936 sec
Table
Protection Relay/Equipment Over Current Settings Earthfault settings
1 33kV Feeder 5L5 PSM =300A, TMS = 0.3 PSM = 50A, TMS = 0.4
2 7.5MVA TX 2 HV PSM = 150A, TMS = 0.35 Not Enabled
3 7.5MVA TX 2 LV PSM = 396A, TMS = 0.25 PSM = 45A, TMS =0.3
4 TX 2 SBEF ------------------------- PSM = 80A, TMS = 0.38
5 11kV Feeder Reclosers PSM = 300A, TMS = 0.14 PSM = 15A, TMS = 0.15
7.5MVA TX 2 – Kericho 33/11kV s/s
Calculations by: afanda rodgers

More Related Content

What's hot

Transformer differential protection
Transformer differential protection Transformer differential protection
Transformer differential protection
michaeljmack
 
Symmetrical Components Fault Calculations
Symmetrical Components Fault CalculationsSymmetrical Components Fault Calculations
Symmetrical Components Fault Calculations
michaeljmack
 
Generator protection gers
Generator protection gersGenerator protection gers
Generator protection gers
Habudin Hassan
 
180degree conduction mode of 3 phase inverter
180degree conduction mode of  3 phase inverter180degree conduction mode of  3 phase inverter
180degree conduction mode of 3 phase inverter
dineshanand810
 
Transformer protection commissioning tools
Transformer protection commissioning toolsTransformer protection commissioning tools
Transformer protection commissioning tools
michaeljmack
 

What's hot (20)

Motor & generator protection example settings
Motor & generator protection example settingsMotor & generator protection example settings
Motor & generator protection example settings
 
Over-current-earth-fault-relay-MC-31
 Over-current-earth-fault-relay-MC-31 Over-current-earth-fault-relay-MC-31
Over-current-earth-fault-relay-MC-31
 
Oscillography analysis
Oscillography analysisOscillography analysis
Oscillography analysis
 
Lv genset protection
Lv genset protectionLv genset protection
Lv genset protection
 
Fat procedure for lv switchboards
Fat procedure for lv switchboardsFat procedure for lv switchboards
Fat procedure for lv switchboards
 
Transformer Fundamentals
Transformer FundamentalsTransformer Fundamentals
Transformer Fundamentals
 
L8 thyristor gate characteristics
L8 thyristor gate characteristicsL8 thyristor gate characteristics
L8 thyristor gate characteristics
 
Transformer differential protection
Transformer differential protection Transformer differential protection
Transformer differential protection
 
nithin seminar
nithin seminarnithin seminar
nithin seminar
 
Symmetrical Components Fault Calculations
Symmetrical Components Fault CalculationsSymmetrical Components Fault Calculations
Symmetrical Components Fault Calculations
 
Tutorial on Distance and Over Current Protection
Tutorial on Distance and Over  Current ProtectionTutorial on Distance and Over  Current Protection
Tutorial on Distance and Over Current Protection
 
Generator protection gers
Generator protection gersGenerator protection gers
Generator protection gers
 
Detection of Generator Loss of Excitation (LOE)
Detection of Generator Loss of Excitation (LOE)Detection of Generator Loss of Excitation (LOE)
Detection of Generator Loss of Excitation (LOE)
 
Substation Maintenance
Substation MaintenanceSubstation Maintenance
Substation Maintenance
 
180degree conduction mode of 3 phase inverter
180degree conduction mode of  3 phase inverter180degree conduction mode of  3 phase inverter
180degree conduction mode of 3 phase inverter
 
L10 res triggering circuit
L10 res triggering circuitL10 res triggering circuit
L10 res triggering circuit
 
Transistion from TVSS to SPD
Transistion from TVSS to SPDTransistion from TVSS to SPD
Transistion from TVSS to SPD
 
Transformer protection commissioning tools
Transformer protection commissioning toolsTransformer protection commissioning tools
Transformer protection commissioning tools
 
Out of step
Out of stepOut of step
Out of step
 
Simple Current Transformer (CT) Testing for Switchyard Equipment.
Simple Current Transformer (CT) Testing for Switchyard Equipment.Simple Current Transformer (CT) Testing for Switchyard Equipment.
Simple Current Transformer (CT) Testing for Switchyard Equipment.
 

Viewers also liked

Short Circuit and Coordination Anaylsis
Short Circuit and Coordination AnaylsisShort Circuit and Coordination Anaylsis
Short Circuit and Coordination Anaylsis
michaeljmack
 
Transformer Failure Due to Circuit Breaker Induced Switching Transients
Transformer Failure Due to Circuit Breaker Induced Switching TransientsTransformer Failure Due to Circuit Breaker Induced Switching Transients
Transformer Failure Due to Circuit Breaker Induced Switching Transients
michaeljmack
 
15 years of experience stator ground fault protection
15 years of experience stator ground fault protection15 years of experience stator ground fault protection
15 years of experience stator ground fault protection
michaeljmack
 
Short Circuit, Protective Device Coordination
Short Circuit, Protective Device CoordinationShort Circuit, Protective Device Coordination
Short Circuit, Protective Device Coordination
michaeljmack
 
Fundamentals of transformer inrush
Fundamentals of transformer inrushFundamentals of transformer inrush
Fundamentals of transformer inrush
michaeljmack
 
ABB - TRANSFORMERS-PROTECTION-COURSE (2001)
ABB - TRANSFORMERS-PROTECTION-COURSE (2001)ABB - TRANSFORMERS-PROTECTION-COURSE (2001)
ABB - TRANSFORMERS-PROTECTION-COURSE (2001)
J. FR
 

Viewers also liked (20)

Generator Set Transient Performance
Generator Set Transient PerformanceGenerator Set Transient Performance
Generator Set Transient Performance
 
Short Circuit and Coordination Anaylsis
Short Circuit and Coordination AnaylsisShort Circuit and Coordination Anaylsis
Short Circuit and Coordination Anaylsis
 
Power Plant Horror Stories
Power Plant Horror StoriesPower Plant Horror Stories
Power Plant Horror Stories
 
Ieee inrush tutorial
Ieee inrush tutorialIeee inrush tutorial
Ieee inrush tutorial
 
Soft starters
Soft startersSoft starters
Soft starters
 
Transformer Failure Due to Circuit Breaker Induced Switching Transients
Transformer Failure Due to Circuit Breaker Induced Switching TransientsTransformer Failure Due to Circuit Breaker Induced Switching Transients
Transformer Failure Due to Circuit Breaker Induced Switching Transients
 
UPS Batteries By BatteryClerk
UPS Batteries By BatteryClerkUPS Batteries By BatteryClerk
UPS Batteries By BatteryClerk
 
15 years of experience stator ground fault protection
15 years of experience stator ground fault protection15 years of experience stator ground fault protection
15 years of experience stator ground fault protection
 
Short Circuit, Protective Device Coordination
Short Circuit, Protective Device CoordinationShort Circuit, Protective Device Coordination
Short Circuit, Protective Device Coordination
 
Fundamentals of transformer inrush
Fundamentals of transformer inrushFundamentals of transformer inrush
Fundamentals of transformer inrush
 
Modeling and analysis of power transformers under ferroresonance phenomenon
Modeling and analysis of power transformers under ferroresonance phenomenonModeling and analysis of power transformers under ferroresonance phenomenon
Modeling and analysis of power transformers under ferroresonance phenomenon
 
Wye delta transformations
Wye delta transformationsWye delta transformations
Wye delta transformations
 
Design of Industrial Automation Functional Specifications for PLCs, DCs and S...
Design of Industrial Automation Functional Specifications for PLCs, DCs and S...Design of Industrial Automation Functional Specifications for PLCs, DCs and S...
Design of Industrial Automation Functional Specifications for PLCs, DCs and S...
 
ABB - TRANSFORMERS-PROTECTION-COURSE (2001)
ABB - TRANSFORMERS-PROTECTION-COURSE (2001)ABB - TRANSFORMERS-PROTECTION-COURSE (2001)
ABB - TRANSFORMERS-PROTECTION-COURSE (2001)
 
Unit 1, Power system Analysis
Unit 1, Power system AnalysisUnit 1, Power system Analysis
Unit 1, Power system Analysis
 
Ee 1351 power system analysis
Ee 1351 power system analysisEe 1351 power system analysis
Ee 1351 power system analysis
 
File 1 power system fault analysis
File 1 power system fault analysisFile 1 power system fault analysis
File 1 power system fault analysis
 
Short circuit calculations
Short circuit calculationsShort circuit calculations
Short circuit calculations
 
Power System Analysis!
Power System Analysis!Power System Analysis!
Power System Analysis!
 
Substation protection devices
Substation protection devicesSubstation protection devices
Substation protection devices
 

Similar to Protection settings calculation

Cable sizing to withstand short-circuit current - Example
Cable sizing to withstand short-circuit current - ExampleCable sizing to withstand short-circuit current - Example
Cable sizing to withstand short-circuit current - Example
Leonardo ENERGY
 
Electrical Systems Safety
Electrical Systems SafetyElectrical Systems Safety
Electrical Systems Safety
Talia Carbis
 
As built and proposed SLD
As built and proposed SLDAs built and proposed SLD
As built and proposed SLD
Qasim Muhammad
 

Similar to Protection settings calculation (20)

Cable sizing to withstand short-circuit current - Example
Cable sizing to withstand short-circuit current - ExampleCable sizing to withstand short-circuit current - Example
Cable sizing to withstand short-circuit current - Example
 
1,5 ke6v8
1,5 ke6v81,5 ke6v8
1,5 ke6v8
 
132kv-substation-settings_compress.pdf
132kv-substation-settings_compress.pdf132kv-substation-settings_compress.pdf
132kv-substation-settings_compress.pdf
 
Transformer overcurrent
Transformer overcurrentTransformer overcurrent
Transformer overcurrent
 
ABB Medium Voltage Indoor Fuses - ABB CEF-S High Voltage Current Limiting Fus...
ABB Medium Voltage Indoor Fuses - ABB CEF-S High Voltage Current Limiting Fus...ABB Medium Voltage Indoor Fuses - ABB CEF-S High Voltage Current Limiting Fus...
ABB Medium Voltage Indoor Fuses - ABB CEF-S High Voltage Current Limiting Fus...
 
Original MOSFET N-CHANNEL FQPF11N70 11N70 TO-220 11A 700V New Fairchild
Original MOSFET N-CHANNEL FQPF11N70 11N70 TO-220 11A 700V New FairchildOriginal MOSFET N-CHANNEL FQPF11N70 11N70 TO-220 11A 700V New Fairchild
Original MOSFET N-CHANNEL FQPF11N70 11N70 TO-220 11A 700V New Fairchild
 
Original MOSFET N-Channel STGF10NC60KD GF10NC60KD 10NC60 10N60 10A 600V New
Original MOSFET N-Channel STGF10NC60KD GF10NC60KD 10NC60 10N60 10A 600V NewOriginal MOSFET N-Channel STGF10NC60KD GF10NC60KD 10NC60 10N60 10A 600V New
Original MOSFET N-Channel STGF10NC60KD GF10NC60KD 10NC60 10N60 10A 600V New
 
Electrical Systems Safety
Electrical Systems SafetyElectrical Systems Safety
Electrical Systems Safety
 
Catalog ls metasol mc e_1004
Catalog ls metasol mc e_1004Catalog ls metasol mc e_1004
Catalog ls metasol mc e_1004
 
Catalog ls metasol mc_e_1008
Catalog ls metasol mc_e_1008Catalog ls metasol mc_e_1008
Catalog ls metasol mc_e_1008
 
Catalog ls metasol mc e_1004_denhathe.vn
Catalog ls metasol mc e_1004_denhathe.vnCatalog ls metasol mc e_1004_denhathe.vn
Catalog ls metasol mc e_1004_denhathe.vn
 
Catalog ls metasol mc_e_1008_denhathe.vn
Catalog ls metasol mc_e_1008_denhathe.vnCatalog ls metasol mc_e_1008_denhathe.vn
Catalog ls metasol mc_e_1008_denhathe.vn
 
As built and proposed SLD
As built and proposed SLDAs built and proposed SLD
As built and proposed SLD
 
Original N-Channel Mosfet 2SK3484 3484 16A 100V TO-252 New Renesas Electronics
Original N-Channel Mosfet 2SK3484 3484 16A 100V TO-252 New Renesas ElectronicsOriginal N-Channel Mosfet 2SK3484 3484 16A 100V TO-252 New Renesas Electronics
Original N-Channel Mosfet 2SK3484 3484 16A 100V TO-252 New Renesas Electronics
 
12-Examples on Compression Members (Steel Structural Design & Prof. Shehab Mo...
12-Examples on Compression Members (Steel Structural Design & Prof. Shehab Mo...12-Examples on Compression Members (Steel Structural Design & Prof. Shehab Mo...
12-Examples on Compression Members (Steel Structural Design & Prof. Shehab Mo...
 
Original IGBT N-CHANNEL STGP7NC60HD GP7NC60HD 7NC60 14A 600V TO-220 New
Original IGBT N-CHANNEL STGP7NC60HD GP7NC60HD 7NC60 14A 600V TO-220 NewOriginal IGBT N-CHANNEL STGP7NC60HD GP7NC60HD 7NC60 14A 600V TO-220 New
Original IGBT N-CHANNEL STGP7NC60HD GP7NC60HD 7NC60 14A 600V TO-220 New
 
Transmission and distribution system design
Transmission and distribution system designTransmission and distribution system design
Transmission and distribution system design
 
Original Transistor NPN MJE13003 KSE13003 E13003 13003 1.5A 400V TO-126 New
Original Transistor NPN MJE13003 KSE13003 E13003 13003 1.5A 400V TO-126 NewOriginal Transistor NPN MJE13003 KSE13003 E13003 13003 1.5A 400V TO-126 New
Original Transistor NPN MJE13003 KSE13003 E13003 13003 1.5A 400V TO-126 New
 
Original N-Channel Mosfet STP10NK70ZFP P10NK70ZFP 10NK70 700V 8.6A TO-220F Ne...
Original N-Channel Mosfet STP10NK70ZFP P10NK70ZFP 10NK70 700V 8.6A TO-220F Ne...Original N-Channel Mosfet STP10NK70ZFP P10NK70ZFP 10NK70 700V 8.6A TO-220F Ne...
Original N-Channel Mosfet STP10NK70ZFP P10NK70ZFP 10NK70 700V 8.6A TO-220F Ne...
 
Original Transistor NPN MPS A06 MPSA06 TO 92 New
Original Transistor NPN MPS A06 MPSA06 TO 92 NewOriginal Transistor NPN MPS A06 MPSA06 TO 92 New
Original Transistor NPN MPS A06 MPSA06 TO 92 New
 

Recently uploaded

Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Christo Ananth
 
Call Girls in Ramesh Nagar Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
Call Girls in Ramesh Nagar Delhi 💯 Call Us 🔝9953056974 🔝 Escort ServiceCall Girls in Ramesh Nagar Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
Call Girls in Ramesh Nagar Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
9953056974 Low Rate Call Girls In Saket, Delhi NCR
 

Recently uploaded (20)

UNIT - IV - Air Compressors and its Performance
UNIT - IV - Air Compressors and its PerformanceUNIT - IV - Air Compressors and its Performance
UNIT - IV - Air Compressors and its Performance
 
Extrusion Processes and Their Limitations
Extrusion Processes and Their LimitationsExtrusion Processes and Their Limitations
Extrusion Processes and Their Limitations
 
Water Industry Process Automation & Control Monthly - April 2024
Water Industry Process Automation & Control Monthly - April 2024Water Industry Process Automation & Control Monthly - April 2024
Water Industry Process Automation & Control Monthly - April 2024
 
chapter 5.pptx: drainage and irrigation engineering
chapter 5.pptx: drainage and irrigation engineeringchapter 5.pptx: drainage and irrigation engineering
chapter 5.pptx: drainage and irrigation engineering
 
BSides Seattle 2024 - Stopping Ethan Hunt From Taking Your Data.pptx
BSides Seattle 2024 - Stopping Ethan Hunt From Taking Your Data.pptxBSides Seattle 2024 - Stopping Ethan Hunt From Taking Your Data.pptx
BSides Seattle 2024 - Stopping Ethan Hunt From Taking Your Data.pptx
 
(INDIRA) Call Girl Aurangabad Call Now 8617697112 Aurangabad Escorts 24x7
(INDIRA) Call Girl Aurangabad Call Now 8617697112 Aurangabad Escorts 24x7(INDIRA) Call Girl Aurangabad Call Now 8617697112 Aurangabad Escorts 24x7
(INDIRA) Call Girl Aurangabad Call Now 8617697112 Aurangabad Escorts 24x7
 
The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...
The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...
The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...
 
UNIT-II FMM-Flow Through Circular Conduits
UNIT-II FMM-Flow Through Circular ConduitsUNIT-II FMM-Flow Through Circular Conduits
UNIT-II FMM-Flow Through Circular Conduits
 
data_management_and _data_science_cheat_sheet.pdf
data_management_and _data_science_cheat_sheet.pdfdata_management_and _data_science_cheat_sheet.pdf
data_management_and _data_science_cheat_sheet.pdf
 
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
 
PVC VS. FIBERGLASS (FRP) GRAVITY SEWER - UNI BELL
PVC VS. FIBERGLASS (FRP) GRAVITY SEWER - UNI BELLPVC VS. FIBERGLASS (FRP) GRAVITY SEWER - UNI BELL
PVC VS. FIBERGLASS (FRP) GRAVITY SEWER - UNI BELL
 
Glass Ceramics: Processing and Properties
Glass Ceramics: Processing and PropertiesGlass Ceramics: Processing and Properties
Glass Ceramics: Processing and Properties
 
NFPA 5000 2024 standard .
NFPA 5000 2024 standard                                  .NFPA 5000 2024 standard                                  .
NFPA 5000 2024 standard .
 
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
 
University management System project report..pdf
University management System project report..pdfUniversity management System project report..pdf
University management System project report..pdf
 
KubeKraft presentation @CloudNativeHooghly
KubeKraft presentation @CloudNativeHooghlyKubeKraft presentation @CloudNativeHooghly
KubeKraft presentation @CloudNativeHooghly
 
Call Girls in Ramesh Nagar Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
Call Girls in Ramesh Nagar Delhi 💯 Call Us 🔝9953056974 🔝 Escort ServiceCall Girls in Ramesh Nagar Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
Call Girls in Ramesh Nagar Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
 
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
 
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete RecordCCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
 
Booking open Available Pune Call Girls Pargaon 6297143586 Call Hot Indian Gi...
Booking open Available Pune Call Girls Pargaon  6297143586 Call Hot Indian Gi...Booking open Available Pune Call Girls Pargaon  6297143586 Call Hot Indian Gi...
Booking open Available Pune Call Girls Pargaon 6297143586 Call Hot Indian Gi...
 

Protection settings calculation

  • 1. April 2016 4 Protection Settings Calculations PROTECTION SETTINGS CALCULATIONS Useful information - Base MVA = 100MVA - Rating of the TX 2 = 7.5MVA - Percentage Impedance of the TX 2 at Tap 9 and Tap 17 is 7.70% and 7.47% respectively - Fault MVA at Chemosit 33kV bus = 0 62.10426.258 −∠ - Conductor size of the 33kV Kericho feeder and length from Chemosit is 2 75mm ACSR and 20KM respectively - Settings for 5L5 at Chemosit (Back up O/C & E/F);  O/C : PSM = 300A, & TMS = 0.3  E/F: PSM = 50A, & TMS = 0.4 Source Impedance`Calculation 0 62.104 26.258 100 )33( ∠= MVA MVA kVZs .3747.0098.0 puj−−= Total Z p.u of the 33kV Kericho feeder upto the 33kV bus at Kericho 33/11kV s/s )0365.00375.0(20)33(2 75 jxkVZ mm += puj 73.075.0 += Impedance p.u. of the 7.5MVA TX 2 as expressed to the new MVA base (Tap 17) = upj .996.0 The resultant Total impedance p.u. upto 11kV bus )2()33()( 5.77511 2 TXZkVZZbusZ MVAmmskV ++= = puj 3513.16523.0 + Resultant fault MVA = MVA0 23.6464.66 −∠ Fault Current at the 11kV bus 7.5MVA TX 2 – Kericho 33/11kV s/s Calculations by: afanda rodgers )3513.16523.0( 100 j MVA MVAf + = 1005.7 10047.7 )2(5.7 xMVA MVAx jTXZ MVA =
  • 2. April 2016 4 Protection Settings Calculations A kVx MVAx I f 113 100064.66 = = A89.3497 Protection relays/equipment operating times calculations on the 11kV fault current of 3497.89A (ph – ph) 1. 5L5 O/C relay sec 1) 3003 89.3497( 3.014.0 )/( 02.055 − = x x cot L =1.5260 sec 2. New 7.5MVA TX 2 HV O/C relay sec 1) 1503 89.3497( 35.014.0 )/( 02.0 − = x x cotHV =1.1704 sec Operating margin between the two units above is 0.357 sec 3. New 7.5MVA TX 2 LV O/C relay sec 1) 396 89.3497( 25.014.0 )/( 02.0 − = x cotLV =0.7860 sec Operating margin between LV and HV over current is 0.385 sec 4. All 11kV feeder reclosers sec 1) 300 89.3497( 14.014.0 )/( 02.011 − = x cot recloserskv 7.5MVA TX 2 – Kericho 33/11kV s/s Calculations by: afanda rodgers
  • 3. April 2016 4 Protection Settings Calculations =0.3893 sec Operating Margin between TX 2 LV O/C and 11kV reclosers is 0.397 sec Operating times of protection units on 11kV Earthfaults of 1165.96A 1. 5L5 E/F relay sec 1) 50 6.388( 3.014.0 )/( 02.055 − = x FEt L =1.3376 sec 2. 7.5MVA TX 2 SBEF relay sec 1) 80 96.1165( 38.014.0 )/( 02.0 − = x FEtSBEF = 0.9664 sec Operating margin between 5L5 and the 7.5MVA TX 2 SBEF is 0.3712 sec 3. TX 2 LV E/F sec 1) 45 96.1165( 3.014.0 )/( 02.0 − = x FEtTX =0.6245 sec Operating margin between the TX 2 SBEF and TX 2 LV E/F is 0.3420 sec 4. 11kV feeder reclosers 7.5MVA TX 2 – Kericho 33/11kV s/s Calculations by: afanda rodgers
  • 4. April 2016 4 Protection Settings Calculations sec 1) 15 96.1165( 15.014.0 )/( 02.011 − = x FEt recloserskV = 0.2310 sec Operating Margin between the TX 2 LV E/F and the 11kV reclosers is 0.3936 sec Table Protection Relay/Equipment Over Current Settings Earthfault settings 1 33kV Feeder 5L5 PSM =300A, TMS = 0.3 PSM = 50A, TMS = 0.4 2 7.5MVA TX 2 HV PSM = 150A, TMS = 0.35 Not Enabled 3 7.5MVA TX 2 LV PSM = 396A, TMS = 0.25 PSM = 45A, TMS =0.3 4 TX 2 SBEF ------------------------- PSM = 80A, TMS = 0.38 5 11kV Feeder Reclosers PSM = 300A, TMS = 0.14 PSM = 15A, TMS = 0.15 7.5MVA TX 2 – Kericho 33/11kV s/s Calculations by: afanda rodgers