/ Short Circuit and
;oordination Analysis
Glyn J. Lewis, P.E.
Applied Power
Redwood Shores, California
Glyn J Lewis, P.E. Applied Power
2/28/2006
1
/
2/28/2006
2
,
HV ahd MV Circuit Breakers
/• AtJSI C37.010
• are nominally rated in MVA.
• by symmetrical interrupting
and withstand. Withstand is
always 1.6 current.
• Use K Factor for lower voltages than breaker
rating.
Glyn J. Lewis, P E Applied Power
/
SHORl/CIRCUIT ANALYSIS
,.eclosers and Fault
/ Interrupters
• C37.60
opening asymmetrical current for
closing and withstand.
• X/R ratios vary b' size.

Glyn J. Lewis, P.E. Applied Power
2/28/2006
3
//
SHORT/CIRCUIT ANALYSIS
Cutouts
• A'SI C37.40/41/42/44/48
• based upon Symmetrical and
currents.
• Maximum X/R"fatio is 15.
Glyn J. Lewis, PE Applied Powe
2/28/2006
4
Mediu Voltage Switches and
Fuses
• ANSI C37.40/46/47
• symmetrical and asymmetrical
amperes.
• Asymmetrical r:atings are 1.6 times
symmetrical ratin'g.
Glyn J. Lewis, PE Applied Power
2/28/2006
5
/
Mediu,n; Voltage Conductors
• 240-100
• Fuse protection is limited to 300% ampacity
rating
• Relay pick seth g is limited to 600% of
ampacity rating.
• Size or setting must pmtect cable against F
heating curve.
Glyn J. Lewis, PE. Applied Powe
2/28/2006
6
/
/<
• 450-3 and ANSI G57.1 09 for oil filled units
and C57.12.0 for dry type units.
• shown in NEG.
• Verify that primary protection protects against
short circuit with'5tand and combination primary
and secondary proteds against thermal
withstand per ANSI Standards.
Glyn J. Lewis, P.E Applied Powe
2/28/2006
7
SHORT ANALYSIS
LOW yOLTAGE SYSTEMS
AND POWER
/CIRCUIT BREAKERS
• C37.13/16/20.1 and UL1558
• is rated in symmetrical amperes with
derate for high X/R ratios over 4.9 for
"fused and 6.6 for unfused breakers. (VI'i;;V
•. "'" 5t. t"tr{"<
• Derate applied to the calculated
symmetrical can be as high as
1.15.
Glyn J. Lewis, P.E. Applied Power
2/28/2006
8
CIRCUIT ANALYSIS
PANELBOARDS,
AND INSULATED CASE
< BREAKERS
• EqbJipment rated in symmetrical amperes
with"d€rates for high X/R ratios.
• applied to the breaker rating
and can be"as low as 0.62 for X/R ratios
above 20. Ca;eful consideration must be
given to where the
X/R ratios are high.
Glyn J Lewis, P.E. Applied Powe
2/28/2006
9
ANALYSIS
SWITCtlBOARDS, PANELBOARDS,
MOL ED AND INSULATED CASE
BREAKERS
• Ttieze are serious limitations per UL489
case and insulated case
applied on ungrounded,
delta and high resistance
grounded systems.
Glyn J Lewis, P.E. Applied Powe
2/28/2006
10
LOW VOLTAGE SERIES RATINGS
• Equipment can be rated with a line side
device. That is, a breaker of
higher"i, terrupting capacity or a fuse.
UL67 or NEG 110.22;
• Series tested com'tJlnations as listed i
the UL "Yellow BOOK' only apply.
Glyn J. Lewis, PE. Applied Powe
2/28/2006
11
LOW' OLTAGE CONDUCTORS
• Use"ampacities from NEe Table 310-16 and
• Use 60 degree column for less than 125A.
• Use 75 for 125A and over.
• Up to 800A use trip equal or up.
• Over 800A use equal OF next size trip down.
Glyn J. Lewis, P.E. Applied Power
2/28/2006
12
/// LV FUSE
2128/2006
Glyn J. Lewis, P.E. Applied Power 13
2/28/2006
14
--
, ., . .• • •• • •• •
•
•••
He OF 20C"J.GE
•••
.'0
., t _.J.__;,__ ..•.,
..
. Q<tl_-I _
·..l-+-,
...
/ FUSE - FUSE
COORDINATION
2/28/2006
Glyn J Lewis, P.E. Applied Powe 15
2/28/2006
16
,
••••
••••
,
•••
--lot•••
•••
,
••
...
.. I
I
.,
•.U ......•...- -,
Ii
I
... t-
." I I, , ,
/
/ FUSE-BREAKER
COORDINATION
/
2/28/2006
Glyn J. Lewis, PE Applied Power 17
2/28/2006
18
I
I
,,
, , J.
• • •
• • •
,
• • • •
• •••
"1'-'
I
Pl'.GE 16C OF
'"
lIC"'-t';: 10·'...
,
",--j--+--
,.
." :
." !
., , ,
,
:!-ri-I
,
MOLDED CASE BREAKER
2/28/2006
Glyn J. Lewis, P.E Applied Power 19
2/28/2006
20
,
••••
••••
,
•••
,
•••
PAGE lOC 0' >0O
•••
." __..L.
.......--.'
I...r-
//MOLDED CASE -
( MOLDED CASE
COORDINATION
2/28/2006
Glyn J Lewis, P.E. Applied Powe 21
,
••••
,
•••
,
•••
,
•••
,
••
,
••
L
I
..
........OT EU.,
"
,
"--+-
"'----'---
,.
L_-'-_
,.
-ilil-l-"L
" . I
'r- I_"_--r
I I 1 '
,,-
''';---,--1.lii
,.....L .,
lle at 2QC
2/28/2006
22
/
/
///POWER CIRCUIT
BREAKER
2/28/2006
Glyn J. Lewis, P.E. Applied Power 23
2/28/2006
24PAGE 12C OF
_L_--,
, , , , , , ,
• • • • • • •• • • • • • •• • • ••e, U"i!
I" ••T'CCc::r::c:::r--T-
R CI1I.CU11j
--,
..
...p.Or
"
.,
"1'·---+--+_·-----1+11
---------
1
'''''.---..,--+-------i
6. t
"'---------1-
:iU1l-------I--j
I "",n,-
/MEDIUM VOLTAGE
 FUSE
(),HARACTERISTICS
2/28/2006
Glyn J. Lewis, P.E. Applied Power 25
2/28/2006
26
••••
••••
PAGE 1C OF 20e
•••
,
••
•••
...."••
• J;N """"''''':5
n , , ,
KEpIUM fOLTA9E FU1ES ,
• ------,----------i--
I
I
NOTE IN
''''''''' m"to. '1"
,
FUSEs
•
S0pRCB ISIDE "K";t.ND 'T" LI II:
• .. J'U!>ES IN A UTOU S
or;
TH LO SIpE
'[::0;::.
_ _C_ E LIHY!'ING TYP S SO H
1.8 • E' fAND "CO'. I
• ln L. I I
lUll' "T"
0
I·.1 I ,, ,
i I I "•
I
,
I
", ,
I •
'1--
,
f- I
0
"0
,
I .JJ
,
• 0 -
,ttl I I
· I
,
·.. - --
I
-±• -
I
•
• I I
•
•
·...
.,
..
..
".
/
/
COORDINATION
2/28/2006
Glyn J. Lewis, PE Applied Power 27
...
...I
H
I
...
...LlIo" -E- I !-"0" - :--
1
· · A T l l -
t .-
..,·'·-1·- --20 I .:. .........,.....
,
•••
PAGE 2C 0' >OC
•••••
2/28/2006
28
/
COORDINATION
2/28/2006
Glyn J. Lewis, PE. Applied Power 29
1'1C;2 5C OF 2.IlC
2/28/2006
30
., , • "
,. .. , , , , ,, • • • •• • • • •• • •
l)P""'mG
'" "EJ,'"YS ".ll.: u·,"'. ""....E: ..-,
2/28/2006
Glyn J. Lewis, P.E. Applied Power 31
//
/
COORDINATION
SOLID STATE
2/28/2006
32
,,
",
,
",,,
"
"o,
••••
,
•••
,
•••
PAGE lie OF 20C
,
••
,
••
,.
... 0'; · I
LAC(
""" ETING.
--L..,._1
!
!
I
. I--I , 1
, 
,.
. ":-', II •._._. "-t' .
'-
_. ... .._...........•-,.•..,--_.. ,

.
lJ'  
,
1 . I
-- -'---'f.-'-
I
• i I
I , I • I..
1'..
. , .. . .- "
I 'J.... ".I
"
I
.. "',1--- -- ---_...., .
1
• I 
I ,,, ,
II ..1 ,, I
I, ,
t .1 j
!
I I I,
I
I
,
,.
"f--+---'f··
-,.-+--l 1, ,, .
III
VTTL'._i'f! I'"
p ....
1_-1--'--
'.1---1 -1--1
+-"-"··1.-
j-
------
__
. ,
,Ql_.__L,
'''I---j--'-.-
'''1--,-I---+-'----t-
-'-,...u,
I , 1 I, RELAY i RELA COOaOINA ION
5ul 1"-- -,1-' I
,__+-_+ --j__j-__j-.;;ClHIVE8 ! l8 PREVIOUSLY
ilUr- EFCRTBED.·
PlJ NOTE.. I THAT, I
PROVIDE --
SEfECTivE TRrPPIN
1·
CLOSER D THAN
DUE TO
/
/
/
/
// RELAY-FUSE
COORDINATION
2/28/2006
Glyn J. Lewis, PE Applied Power 33
2/28/2006
34i'lI.OE 01' 20t'
, , , , ,
• • • • •• • • • •• • •
SC"'-E, I.- 1
2/28/2006
Glyn J. Lewis, P.E. Applied Powe 35
/
/
/
/.v GROUND RELAY
COORDINATION
2/28/2006
36
I"
,
,--
, ,. r
,1 ". " •,
" • ., n >
" •• . " "
,
.. • "
,,
"'1
4-'lot.'1'·:m.w;u, C"O Jt.:n;'H: ffr:rm"
lO&1Il1 -
"!UllluRl ;
,-Ot'll-'ft.fl;::DlJrlI. iJ::L:.;<L
<r.ir"
mwr:.t&llMII;:r;II;' _IlID..:uill
-
, ';'1:':::1' 111.!'U}. ",::,rr.>"ll :l"ioJ nUl]. 'I'tl' ,t,
It
,x'llJJ?'---_lfc::;'ml,u.:.
2:iC«U:Z"iH:!.'lO I {In1UiEll ..
' j , ,
<r
r
w
r(
"
1,1
!
'''''''''''''''' ;;.. _!:J'C!'
....r.,}L: fl:l>r:lUi
--,.---.-----==:r=:.==--_*ctlrun:J ,'dl. 7n:i!!CUuu:t
;'CUCnmoy.
, I
:lOiVS JtlHm'I!!....m:/·:l1U
,. .. fl:l::JJltX'l la'u:":!i)U
"'- '-"'·----- ...
H __
••
., __1
''"-------....
j
'r
,
(!Oil' __.__, .LWM•. .. _
/
/
DESIGNING
/ FOR
/ COORDINATION
AND
SEL "CTIVE TRIPPING
2/28/2006
Glyn J. Lewis, PE. Applied Power 37
2/28/2006
38
TT
LACK OF SELECTIVE TRIPPING
WITH G. F. RELAv
//
.7ADD
• I ,r-••----I
v "
1 (
T
c:;
./
« 'j
50 DEVICE TO BE
SET AT 1, 6 SYM
SECONDARY FAULT
CURRENT
MR t:-O-O50/51 50/5! N
T
50/51 50/51 N
MRJ::-o-o
f 50/51 50151N
¢
MR
/
/
/
LACK OF SELECTIVE TRIPPING
DUE TO INSTANTANEOUS ELEMENTS
V
I
MR ::-0-0
50/51 50/51N
T
¢
k
¢
J---OMR MR
51 51N 51 SIN 51 51N
DELETE INSTANTANEOUS TRIPS (IT)
(IF POSSIBLD
UTILITY MAY FORCE USE OF IT'S
Glyn J. Lewis, PEApplied
t:;j" SIN
¢
T T
LILU/LUUU
40
• 51 SIN
MR MR MR
50/51 SO/SiN
T
50/51 SOISIN
T
50/51 SOISIN
T
ADD DIFFERENTIAL PROTECTION
(UTILITIES WTLL ACCEPT THIS TN LIEU OF IT ON MAIN)
/MAIN) LSG
t
DB
FEEDER) LSIG
TMAIN) LSG
__lI M_S-'-B
LSIG
tFEEDER) LSG
1
...... ':1" ............... ,.... , ' ...... , .t-' ..... " ......... , ............ ' VWHAT ARE THE LI MIT AT TONS OF TH I S SYSTEM? 006
42
'06
ZONE INTERLOCKING TO RESOLVE COORDINATION43
V
/
/
TMAIN ) LSG 0.3 SECS 0,3 SECS
r nnn-----<1: -§nn-t>
r
r TIE
: MSB f:-{---'»>-_ _
I
I 1-----------
I I tI I
g 2 _SECS
l
r
IZ:31 0,2 SECS
r
-.J
MAIN )/LSG
DB t
FEEDER }:SlG n_n __@0 1 SECS
t t t)LS(]) )LS(]) )LS(])
_1 1 1-
ALL GENERATORS THE SAME SIZE,
WHICH BREAKER TRIPS FOR A GENERATOR
ALL BREAKERS ARE SET THE SAME,
Glyn J. Lewis, PE Applied powerV
/
12006
44
FAUL 17
)
G3
)
G2
/
)
Gl
ADD HS GENERATOR DIFFERENTIAL TO
PROVIDE SELECTIVE TRIPPING,
DELETE IT OR SET HIGHER THAN ASYMMETRICAL
FAULT CURRENT FROM ONE GENERATOR,
Glyn J. Lewis, P.E. Applied
i"'U'I (
87G
y)
,
I
) LS( [)
1
(
87G
G2
/"
87G
t) LS( ])
1
G3
)
t) LS( I)
1v
(
2/28/2006
45
/

More Related Content

Viewers also liked

Transformer Fundamentals
Transformer FundamentalsTransformer Fundamentals
Transformer Fundamentalsmichaeljmack
 
Transformer Failure Due to Circuit Breaker Induced Switching Transients
Transformer Failure Due to Circuit Breaker Induced Switching TransientsTransformer Failure Due to Circuit Breaker Induced Switching Transients
Transformer Failure Due to Circuit Breaker Induced Switching Transientsmichaeljmack
 
UPS Batteries By BatteryClerk
UPS Batteries By BatteryClerkUPS Batteries By BatteryClerk
UPS Batteries By BatteryClerkBattery Clerk
 
15 years of experience stator ground fault protection
15 years of experience stator ground fault protection15 years of experience stator ground fault protection
15 years of experience stator ground fault protectionmichaeljmack
 
Short Circuit, Protective Device Coordination
Short Circuit, Protective Device CoordinationShort Circuit, Protective Device Coordination
Short Circuit, Protective Device Coordinationmichaeljmack
 
Fundamentals of transformer inrush
Fundamentals of transformer inrushFundamentals of transformer inrush
Fundamentals of transformer inrushmichaeljmack
 
Modeling and analysis of power transformers under ferroresonance phenomenon
Modeling and analysis of power transformers under ferroresonance phenomenonModeling and analysis of power transformers under ferroresonance phenomenon
Modeling and analysis of power transformers under ferroresonance phenomenonGilberto Mejía
 
Design of Industrial Automation Functional Specifications for PLCs, DCs and S...
Design of Industrial Automation Functional Specifications for PLCs, DCs and S...Design of Industrial Automation Functional Specifications for PLCs, DCs and S...
Design of Industrial Automation Functional Specifications for PLCs, DCs and S...Living Online
 
ABB - TRANSFORMERS-PROTECTION-COURSE (2001)
ABB - TRANSFORMERS-PROTECTION-COURSE (2001)ABB - TRANSFORMERS-PROTECTION-COURSE (2001)
ABB - TRANSFORMERS-PROTECTION-COURSE (2001)J. FR
 
Unit 1, Power system Analysis
Unit 1, Power system AnalysisUnit 1, Power system Analysis
Unit 1, Power system AnalysisAbha Tripathi
 
Ee 1351 power system analysis
Ee 1351 power system analysisEe 1351 power system analysis
Ee 1351 power system analysisHari Kumar
 
File 1 power system fault analysis
File 1 power system fault analysisFile 1 power system fault analysis
File 1 power system fault analysiskirkusawi
 
Short circuit calculations
Short circuit calculationsShort circuit calculations
Short circuit calculationsMustafa Ismail
 
Power System Analysis!
Power System Analysis!Power System Analysis!
Power System Analysis!PRABHAHARAN429
 
Substation protection devices
Substation protection devicesSubstation protection devices
Substation protection devicesRahul Aman
 

Viewers also liked (17)

Transformer Fundamentals
Transformer FundamentalsTransformer Fundamentals
Transformer Fundamentals
 
Soft starters
Soft startersSoft starters
Soft starters
 
Transformer Failure Due to Circuit Breaker Induced Switching Transients
Transformer Failure Due to Circuit Breaker Induced Switching TransientsTransformer Failure Due to Circuit Breaker Induced Switching Transients
Transformer Failure Due to Circuit Breaker Induced Switching Transients
 
UPS Batteries By BatteryClerk
UPS Batteries By BatteryClerkUPS Batteries By BatteryClerk
UPS Batteries By BatteryClerk
 
15 years of experience stator ground fault protection
15 years of experience stator ground fault protection15 years of experience stator ground fault protection
15 years of experience stator ground fault protection
 
Short Circuit, Protective Device Coordination
Short Circuit, Protective Device CoordinationShort Circuit, Protective Device Coordination
Short Circuit, Protective Device Coordination
 
Fundamentals of transformer inrush
Fundamentals of transformer inrushFundamentals of transformer inrush
Fundamentals of transformer inrush
 
Modeling and analysis of power transformers under ferroresonance phenomenon
Modeling and analysis of power transformers under ferroresonance phenomenonModeling and analysis of power transformers under ferroresonance phenomenon
Modeling and analysis of power transformers under ferroresonance phenomenon
 
Wye delta transformations
Wye delta transformationsWye delta transformations
Wye delta transformations
 
Design of Industrial Automation Functional Specifications for PLCs, DCs and S...
Design of Industrial Automation Functional Specifications for PLCs, DCs and S...Design of Industrial Automation Functional Specifications for PLCs, DCs and S...
Design of Industrial Automation Functional Specifications for PLCs, DCs and S...
 
ABB - TRANSFORMERS-PROTECTION-COURSE (2001)
ABB - TRANSFORMERS-PROTECTION-COURSE (2001)ABB - TRANSFORMERS-PROTECTION-COURSE (2001)
ABB - TRANSFORMERS-PROTECTION-COURSE (2001)
 
Unit 1, Power system Analysis
Unit 1, Power system AnalysisUnit 1, Power system Analysis
Unit 1, Power system Analysis
 
Ee 1351 power system analysis
Ee 1351 power system analysisEe 1351 power system analysis
Ee 1351 power system analysis
 
File 1 power system fault analysis
File 1 power system fault analysisFile 1 power system fault analysis
File 1 power system fault analysis
 
Short circuit calculations
Short circuit calculationsShort circuit calculations
Short circuit calculations
 
Power System Analysis!
Power System Analysis!Power System Analysis!
Power System Analysis!
 
Substation protection devices
Substation protection devicesSubstation protection devices
Substation protection devices
 

More from michaeljmack

Auburn, NY - 200 Years of History 1793-1993
Auburn, NY - 200 Years of History  1793-1993Auburn, NY - 200 Years of History  1793-1993
Auburn, NY - 200 Years of History 1793-1993michaeljmack
 
Auburn High School, Auburn, NY, 1982 Yearbook
Auburn High School, Auburn, NY, 1982 YearbookAuburn High School, Auburn, NY, 1982 Yearbook
Auburn High School, Auburn, NY, 1982 Yearbookmichaeljmack
 
Auburn High School, Auburn, NY, 1980 Yearbook
Auburn High School, Auburn, NY, 1980 YearbookAuburn High School, Auburn, NY, 1980 Yearbook
Auburn High School, Auburn, NY, 1980 Yearbookmichaeljmack
 
Diesel Particulate Filters Control Systems
Diesel Particulate Filters Control SystemsDiesel Particulate Filters Control Systems
Diesel Particulate Filters Control Systemsmichaeljmack
 
Understanding Arc Flash
Understanding Arc FlashUnderstanding Arc Flash
Understanding Arc Flashmichaeljmack
 
Siemens MV GIS Switchgear
Siemens MV GIS SwitchgearSiemens MV GIS Switchgear
Siemens MV GIS Switchgearmichaeljmack
 
Building information modeling
Building information modelingBuilding information modeling
Building information modelingmichaeljmack
 
Emergency, Legally Required and Optional Standby Systems
Emergency, Legally Required and Optional Standby SystemsEmergency, Legally Required and Optional Standby Systems
Emergency, Legally Required and Optional Standby Systemsmichaeljmack
 
Lighting Control Solutions for Daylit Spaces
Lighting Control Solutions for Daylit SpacesLighting Control Solutions for Daylit Spaces
Lighting Control Solutions for Daylit Spacesmichaeljmack
 
COPS: An Arresting Look at NEC Article 708
COPS: An Arresting Look at NEC Article 708COPS: An Arresting Look at NEC Article 708
COPS: An Arresting Look at NEC Article 708michaeljmack
 
Seismic Compliance of Electrical Distribution
Seismic Compliance of Electrical DistributionSeismic Compliance of Electrical Distribution
Seismic Compliance of Electrical Distributionmichaeljmack
 
Modeling of a digital protective relay in a RT Digital Simulator
Modeling of a digital protective relay in a RT Digital SimulatorModeling of a digital protective relay in a RT Digital Simulator
Modeling of a digital protective relay in a RT Digital Simulatormichaeljmack
 
Facts on Grid Friendly Wind Plants
Facts on Grid Friendly Wind PlantsFacts on Grid Friendly Wind Plants
Facts on Grid Friendly Wind Plantsmichaeljmack
 
Blackout Avoidance & Undervoltage Load Shedding
Blackout Avoidance & Undervoltage Load SheddingBlackout Avoidance & Undervoltage Load Shedding
Blackout Avoidance & Undervoltage Load Sheddingmichaeljmack
 
Selectivity and Coodination
Selectivity and CoodinationSelectivity and Coodination
Selectivity and Coodinationmichaeljmack
 
Cathodic Protection
Cathodic ProtectionCathodic Protection
Cathodic Protectionmichaeljmack
 
Synchronous machines
Synchronous machinesSynchronous machines
Synchronous machinesmichaeljmack
 
Synchronous machines
Synchronous machinesSynchronous machines
Synchronous machinesmichaeljmack
 

More from michaeljmack (20)

Auburn, NY - 200 Years of History 1793-1993
Auburn, NY - 200 Years of History  1793-1993Auburn, NY - 200 Years of History  1793-1993
Auburn, NY - 200 Years of History 1793-1993
 
Auburn High School, Auburn, NY, 1982 Yearbook
Auburn High School, Auburn, NY, 1982 YearbookAuburn High School, Auburn, NY, 1982 Yearbook
Auburn High School, Auburn, NY, 1982 Yearbook
 
Auburn High School, Auburn, NY, 1980 Yearbook
Auburn High School, Auburn, NY, 1980 YearbookAuburn High School, Auburn, NY, 1980 Yearbook
Auburn High School, Auburn, NY, 1980 Yearbook
 
Surge Protection
Surge ProtectionSurge Protection
Surge Protection
 
Diesel Particulate Filters Control Systems
Diesel Particulate Filters Control SystemsDiesel Particulate Filters Control Systems
Diesel Particulate Filters Control Systems
 
Understanding Arc Flash
Understanding Arc FlashUnderstanding Arc Flash
Understanding Arc Flash
 
Siemens MV GIS Switchgear
Siemens MV GIS SwitchgearSiemens MV GIS Switchgear
Siemens MV GIS Switchgear
 
Building information modeling
Building information modelingBuilding information modeling
Building information modeling
 
Emergency, Legally Required and Optional Standby Systems
Emergency, Legally Required and Optional Standby SystemsEmergency, Legally Required and Optional Standby Systems
Emergency, Legally Required and Optional Standby Systems
 
Lighting Control Solutions for Daylit Spaces
Lighting Control Solutions for Daylit SpacesLighting Control Solutions for Daylit Spaces
Lighting Control Solutions for Daylit Spaces
 
COPS: An Arresting Look at NEC Article 708
COPS: An Arresting Look at NEC Article 708COPS: An Arresting Look at NEC Article 708
COPS: An Arresting Look at NEC Article 708
 
Seismic Compliance of Electrical Distribution
Seismic Compliance of Electrical DistributionSeismic Compliance of Electrical Distribution
Seismic Compliance of Electrical Distribution
 
Modeling of a digital protective relay in a RT Digital Simulator
Modeling of a digital protective relay in a RT Digital SimulatorModeling of a digital protective relay in a RT Digital Simulator
Modeling of a digital protective relay in a RT Digital Simulator
 
Facts on Grid Friendly Wind Plants
Facts on Grid Friendly Wind PlantsFacts on Grid Friendly Wind Plants
Facts on Grid Friendly Wind Plants
 
Blackout Avoidance & Undervoltage Load Shedding
Blackout Avoidance & Undervoltage Load SheddingBlackout Avoidance & Undervoltage Load Shedding
Blackout Avoidance & Undervoltage Load Shedding
 
Arc Flash
Arc FlashArc Flash
Arc Flash
 
Selectivity and Coodination
Selectivity and CoodinationSelectivity and Coodination
Selectivity and Coodination
 
Cathodic Protection
Cathodic ProtectionCathodic Protection
Cathodic Protection
 
Synchronous machines
Synchronous machinesSynchronous machines
Synchronous machines
 
Synchronous machines
Synchronous machinesSynchronous machines
Synchronous machines
 

Recently uploaded

Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...Dr.Costas Sachpazis
 
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur High Profile
 
SPICE PARK APR2024 ( 6,793 SPICE Models )
SPICE PARK APR2024 ( 6,793 SPICE Models )SPICE PARK APR2024 ( 6,793 SPICE Models )
SPICE PARK APR2024 ( 6,793 SPICE Models )Tsuyoshi Horigome
 
UNIT-II FMM-Flow Through Circular Conduits
UNIT-II FMM-Flow Through Circular ConduitsUNIT-II FMM-Flow Through Circular Conduits
UNIT-II FMM-Flow Through Circular Conduitsrknatarajan
 
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...ranjana rawat
 
HARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICS
HARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICSHARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICS
HARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICSRajkumarAkumalla
 
UNIT-III FMM. DIMENSIONAL ANALYSIS
UNIT-III FMM.        DIMENSIONAL ANALYSISUNIT-III FMM.        DIMENSIONAL ANALYSIS
UNIT-III FMM. DIMENSIONAL ANALYSISrknatarajan
 
Top Rated Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...
Top Rated  Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...Top Rated  Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...
Top Rated Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...Call Girls in Nagpur High Profile
 
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...ranjana rawat
 
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...Dr.Costas Sachpazis
 
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICSAPPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICSKurinjimalarL3
 
Extrusion Processes and Their Limitations
Extrusion Processes and Their LimitationsExtrusion Processes and Their Limitations
Extrusion Processes and Their Limitations120cr0395
 
AKTU Computer Networks notes --- Unit 3.pdf
AKTU Computer Networks notes ---  Unit 3.pdfAKTU Computer Networks notes ---  Unit 3.pdf
AKTU Computer Networks notes --- Unit 3.pdfankushspencer015
 
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur High Profile
 
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...Soham Mondal
 
Coefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptxCoefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptxAsutosh Ranjan
 
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete RecordCCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete RecordAsst.prof M.Gokilavani
 
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130Suhani Kapoor
 
UNIT - IV - Air Compressors and its Performance
UNIT - IV - Air Compressors and its PerformanceUNIT - IV - Air Compressors and its Performance
UNIT - IV - Air Compressors and its Performancesivaprakash250
 
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...ranjana rawat
 

Recently uploaded (20)

Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
 
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
 
SPICE PARK APR2024 ( 6,793 SPICE Models )
SPICE PARK APR2024 ( 6,793 SPICE Models )SPICE PARK APR2024 ( 6,793 SPICE Models )
SPICE PARK APR2024 ( 6,793 SPICE Models )
 
UNIT-II FMM-Flow Through Circular Conduits
UNIT-II FMM-Flow Through Circular ConduitsUNIT-II FMM-Flow Through Circular Conduits
UNIT-II FMM-Flow Through Circular Conduits
 
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
 
HARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICS
HARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICSHARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICS
HARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICS
 
UNIT-III FMM. DIMENSIONAL ANALYSIS
UNIT-III FMM.        DIMENSIONAL ANALYSISUNIT-III FMM.        DIMENSIONAL ANALYSIS
UNIT-III FMM. DIMENSIONAL ANALYSIS
 
Top Rated Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...
Top Rated  Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...Top Rated  Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...
Top Rated Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...
 
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
 
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
 
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICSAPPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
 
Extrusion Processes and Their Limitations
Extrusion Processes and Their LimitationsExtrusion Processes and Their Limitations
Extrusion Processes and Their Limitations
 
AKTU Computer Networks notes --- Unit 3.pdf
AKTU Computer Networks notes ---  Unit 3.pdfAKTU Computer Networks notes ---  Unit 3.pdf
AKTU Computer Networks notes --- Unit 3.pdf
 
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
 
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
 
Coefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptxCoefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptx
 
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete RecordCCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
 
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130
 
UNIT - IV - Air Compressors and its Performance
UNIT - IV - Air Compressors and its PerformanceUNIT - IV - Air Compressors and its Performance
UNIT - IV - Air Compressors and its Performance
 
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
 

Short Circuit and Coordination Anaylsis

  • 1. // / / / Short Circuit and ;oordination Analysis Glyn J. Lewis, P.E. Applied Power Redwood Shores, California Glyn J Lewis, P.E. Applied Power 2/28/2006 1
  • 2. / 2/28/2006 2 , HV ahd MV Circuit Breakers /• AtJSI C37.010 • are nominally rated in MVA. • by symmetrical interrupting and withstand. Withstand is always 1.6 current. • Use K Factor for lower voltages than breaker rating. Glyn J. Lewis, P E Applied Power
  • 3. / SHORl/CIRCUIT ANALYSIS ,.eclosers and Fault / Interrupters • C37.60 opening asymmetrical current for closing and withstand. • X/R ratios vary b' size. Glyn J. Lewis, P.E. Applied Power 2/28/2006 3
  • 4. // SHORT/CIRCUIT ANALYSIS Cutouts • A'SI C37.40/41/42/44/48 • based upon Symmetrical and currents. • Maximum X/R"fatio is 15. Glyn J. Lewis, PE Applied Powe 2/28/2006 4
  • 5. Mediu Voltage Switches and Fuses • ANSI C37.40/46/47 • symmetrical and asymmetrical amperes. • Asymmetrical r:atings are 1.6 times symmetrical ratin'g. Glyn J. Lewis, PE Applied Power 2/28/2006 5
  • 6. / Mediu,n; Voltage Conductors • 240-100 • Fuse protection is limited to 300% ampacity rating • Relay pick seth g is limited to 600% of ampacity rating. • Size or setting must pmtect cable against F heating curve. Glyn J. Lewis, PE. Applied Powe 2/28/2006 6
  • 7. / /< • 450-3 and ANSI G57.1 09 for oil filled units and C57.12.0 for dry type units. • shown in NEG. • Verify that primary protection protects against short circuit with'5tand and combination primary and secondary proteds against thermal withstand per ANSI Standards. Glyn J. Lewis, P.E Applied Powe 2/28/2006 7
  • 8. SHORT ANALYSIS LOW yOLTAGE SYSTEMS AND POWER /CIRCUIT BREAKERS • C37.13/16/20.1 and UL1558 • is rated in symmetrical amperes with derate for high X/R ratios over 4.9 for "fused and 6.6 for unfused breakers. (VI'i;;V •. "'" 5t. t"tr{"< • Derate applied to the calculated symmetrical can be as high as 1.15. Glyn J. Lewis, P.E. Applied Power 2/28/2006 8
  • 9. CIRCUIT ANALYSIS PANELBOARDS, AND INSULATED CASE < BREAKERS • EqbJipment rated in symmetrical amperes with"d€rates for high X/R ratios. • applied to the breaker rating and can be"as low as 0.62 for X/R ratios above 20. Ca;eful consideration must be given to where the X/R ratios are high. Glyn J Lewis, P.E. Applied Powe 2/28/2006 9
  • 10. ANALYSIS SWITCtlBOARDS, PANELBOARDS, MOL ED AND INSULATED CASE BREAKERS • Ttieze are serious limitations per UL489 case and insulated case applied on ungrounded, delta and high resistance grounded systems. Glyn J Lewis, P.E. Applied Powe 2/28/2006 10
  • 11. LOW VOLTAGE SERIES RATINGS • Equipment can be rated with a line side device. That is, a breaker of higher"i, terrupting capacity or a fuse. UL67 or NEG 110.22; • Series tested com'tJlnations as listed i the UL "Yellow BOOK' only apply. Glyn J. Lewis, PE. Applied Powe 2/28/2006 11
  • 12. LOW' OLTAGE CONDUCTORS • Use"ampacities from NEe Table 310-16 and • Use 60 degree column for less than 125A. • Use 75 for 125A and over. • Up to 800A use trip equal or up. • Over 800A use equal OF next size trip down. Glyn J. Lewis, P.E. Applied Power 2/28/2006 12
  • 13. /// LV FUSE 2128/2006 Glyn J. Lewis, P.E. Applied Power 13
  • 14. 2/28/2006 14 -- , ., . .• • •• • •• • • ••• He OF 20C"J.GE ••• .'0 ., t _.J.__;,__ ..•., .. . Q<tl_-I _ ·..l-+-, ...
  • 15. / FUSE - FUSE COORDINATION 2/28/2006 Glyn J Lewis, P.E. Applied Powe 15
  • 18. 2/28/2006 18 I I ,, , , J. • • • • • • , • • • • • ••• "1'-' I Pl'.GE 16C OF '" lIC"'-t';: 10·'... , ",--j--+-- ,. ." : ." ! ., , , , :!-ri-I ,
  • 19. MOLDED CASE BREAKER 2/28/2006 Glyn J. Lewis, P.E Applied Power 19
  • 21. //MOLDED CASE - ( MOLDED CASE COORDINATION 2/28/2006 Glyn J Lewis, P.E. Applied Powe 21
  • 23. / / ///POWER CIRCUIT BREAKER 2/28/2006 Glyn J. Lewis, P.E. Applied Power 23
  • 24. 2/28/2006 24PAGE 12C OF _L_--, , , , , , , , • • • • • • •• • • • • • •• • • ••e, U"i! I" ••T'CCc::r::c:::r--T- R CI1I.CU11j --, .. ...p.Or " ., "1'·---+--+_·-----1+11 --------- 1 '''''.---..,--+-------i 6. t "'---------1- :iU1l-------I--j I "",n,-
  • 25. /MEDIUM VOLTAGE FUSE (),HARACTERISTICS 2/28/2006 Glyn J. Lewis, P.E. Applied Power 25
  • 26. 2/28/2006 26 •••• •••• PAGE 1C OF 20e ••• , •• ••• ...."•• • J;N """"''''':5 n , , , KEpIUM fOLTA9E FU1ES , • ------,----------i-- I I NOTE IN ''''''''' m"to. '1" , FUSEs • S0pRCB ISIDE "K";t.ND 'T" LI II: • .. J'U!>ES IN A UTOU S or; TH LO SIpE '[::0;::. _ _C_ E LIHY!'ING TYP S SO H 1.8 • E' fAND "CO'. I • ln L. I I lUll' "T" 0 I·.1 I ,, , i I I "• I , I ", , I • '1-- , f- I 0 "0 , I .JJ , • 0 - ,ttl I I · I , ·.. - -- I -±• - I • • I I • • ·... ., .. .. ".
  • 28. ... ...I H I ... ...LlIo" -E- I !-"0" - :-- 1 · · A T l l - t .- ..,·'·-1·- --20 I .:. .........,..... , ••• PAGE 2C 0' >OC ••••• 2/28/2006 28
  • 30. 1'1C;2 5C OF 2.IlC 2/28/2006 30 ., , • " ,. .. , , , , ,, • • • •• • • • •• • • l)P""'mG '" "EJ,'"YS ".ll.: u·,"'. ""....E: ..-,
  • 31. 2/28/2006 Glyn J. Lewis, P.E. Applied Power 31 // / COORDINATION SOLID STATE
  • 32. 2/28/2006 32 ,, ", , ",,, " "o, •••• , ••• , ••• PAGE lie OF 20C , •• , •• ,. ... 0'; · I LAC( """ ETING. --L..,._1 ! ! I . I--I , 1 , ,. . ":-', II •._._. "-t' . '- _. ... .._...........•-,.•..,--_.. , . lJ' , 1 . I -- -'---'f.-'- I • i I I , I • I.. 1'.. . , .. . .- " I 'J.... ".I " I .. "',1--- -- ---_...., . 1 • I I ,,, , II ..1 ,, I I, , t .1 j ! I I I, I I , ,. "f--+---'f·· -,.-+--l 1, ,, . III VTTL'._i'f! I'" p .... 1_-1--'-- '.1---1 -1--1 +-"-"··1.- j- ------ __ . , ,Ql_.__L, '''I---j--'-.- '''1--,-I---+-'----t- -'-,...u, I , 1 I, RELAY i RELA COOaOINA ION 5ul 1"-- -,1-' I ,__+-_+ --j__j-__j-.;;ClHIVE8 ! l8 PREVIOUSLY ilUr- EFCRTBED.· PlJ NOTE.. I THAT, I PROVIDE -- SEfECTivE TRrPPIN 1· CLOSER D THAN DUE TO
  • 34. 2/28/2006 34i'lI.OE 01' 20t' , , , , , • • • • •• • • • •• • • SC"'-E, I.- 1
  • 35. 2/28/2006 Glyn J. Lewis, P.E. Applied Powe 35 / / / /.v GROUND RELAY COORDINATION
  • 36. 2/28/2006 36 I" , ,-- , ,. r ,1 ". " •, " • ., n > " •• . " " , .. • " ,, "'1 4-'lot.'1'·:m.w;u, C"O Jt.:n;'H: ffr:rm" lO&1Il1 - "!UllluRl ; ,-Ot'll-'ft.fl;::DlJrlI. iJ::L:.;<L <r.ir" mwr:.t&llMII;:r;II;' _IlID..:uill - , ';'1:':::1' 111.!'U}. ",::,rr.>"ll :l"ioJ nUl]. 'I'tl' ,t, It ,x'llJJ?'---_lfc::;'ml,u.:. 2:iC«U:Z"iH:!.'lO I {In1UiEll .. ' j , , <r r w r( " 1,1 ! '''''''''''''''' ;;.. _!:J'C!' ....r.,}L: fl:l>r:lUi --,.---.-----==:r=:.==--_*ctlrun:J ,'dl. 7n:i!!CUuu:t ;'CUCnmoy. , I :lOiVS JtlHm'I!!....m:/·:l1U ,. .. fl:l::JJltX'l la'u:":!i)U "'- '-"'·----- ... H __ •• ., __1 ''"-------.... j 'r , (!Oil' __.__, .LWM•. .. _ /
  • 37. / DESIGNING / FOR / COORDINATION AND SEL "CTIVE TRIPPING 2/28/2006 Glyn J. Lewis, PE. Applied Power 37
  • 38. 2/28/2006 38 TT LACK OF SELECTIVE TRIPPING WITH G. F. RELAv // .7ADD • I ,r-••----I v " 1 ( T c:; ./ « 'j
  • 39. 50 DEVICE TO BE SET AT 1, 6 SYM SECONDARY FAULT CURRENT MR t:-O-O50/51 50/5! N T 50/51 50/51 N MRJ::-o-o f 50/51 50151N ¢ MR / / / LACK OF SELECTIVE TRIPPING DUE TO INSTANTANEOUS ELEMENTS V I MR ::-0-0 50/51 50/51N T
  • 40. ¢ k ¢ J---OMR MR 51 51N 51 SIN 51 51N DELETE INSTANTANEOUS TRIPS (IT) (IF POSSIBLD UTILITY MAY FORCE USE OF IT'S Glyn J. Lewis, PEApplied t:;j" SIN ¢ T T LILU/LUUU 40
  • 41. • 51 SIN MR MR MR 50/51 SO/SiN T 50/51 SOISIN T 50/51 SOISIN T ADD DIFFERENTIAL PROTECTION (UTILITIES WTLL ACCEPT THIS TN LIEU OF IT ON MAIN)
  • 42. /MAIN) LSG t DB FEEDER) LSIG TMAIN) LSG __lI M_S-'-B LSIG tFEEDER) LSG 1 ...... ':1" ............... ,.... , ' ...... , .t-' ..... " ......... , ............ ' VWHAT ARE THE LI MIT AT TONS OF TH I S SYSTEM? 006 42
  • 43. '06 ZONE INTERLOCKING TO RESOLVE COORDINATION43 V / / TMAIN ) LSG 0.3 SECS 0,3 SECS r nnn-----<1: -§nn-t> r r TIE : MSB f:-{---'»>-_ _ I I 1----------- I I tI I g 2 _SECS l r IZ:31 0,2 SECS r -.J MAIN )/LSG DB t FEEDER }:SlG n_n __@0 1 SECS
  • 44. t t t)LS(]) )LS(]) )LS(]) _1 1 1- ALL GENERATORS THE SAME SIZE, WHICH BREAKER TRIPS FOR A GENERATOR ALL BREAKERS ARE SET THE SAME, Glyn J. Lewis, PE Applied powerV / 12006 44 FAUL 17 ) G3 ) G2 / ) Gl
  • 45. ADD HS GENERATOR DIFFERENTIAL TO PROVIDE SELECTIVE TRIPPING, DELETE IT OR SET HIGHER THAN ASYMMETRICAL FAULT CURRENT FROM ONE GENERATOR, Glyn J. Lewis, P.E. Applied i"'U'I ( 87G y) , I ) LS( [) 1 ( 87G G2 /" 87G t) LS( ]) 1 G3 ) t) LS( I) 1v ( 2/28/2006 45 /