Potential and Electric Field Characteristics of Broken Porcelain
Insulator
H. Rosli, N. A. Othman, N. A. M. Jamail, M. N. Ismail
Department of Electrical Power Engineering, Faculty of Electrical & Electronic Engineering,
Universiti Tun Hussein Onn Malaysia (UTHM), 86400 Batu Pahat, Malaysia
Article Info ABSTRACT
Article history:
Received Jul 10, 2017
Revised Oct 14, 2017
Accepted Oct 26, 2017
Overhead line insulators can be damaged for various reasons during their
service life. Porcelain or glass insulators once damaged can affect the
reliability of power system networks. This paper presents the study of
voltage and electric characteristics along the surface of a broken porcelain
insulator located in a string of 10 unit insulators. Three models of broken
porcelain insulators were being proposed and the analysis results on voltage
and electric characteristics were individually collected. The broken porcelain
insulator with the most significant effect were then being investigated in the
strings of 10 unit insulators. The finite element software of Quickfield was
used to analyze the voltage and electric characteristics. Form the presented
results, it is proven that the single porcelain insulators with broken shed at
the nearest to the electrode terminal gave the most significant effect of
voltage and electric field distribution pattern along the creepage distance.
However, when this type of broken insulator was included in a string of 10
unit insulators, maximum average value of voltage achieved once the broken
insulator was located at the HV terminal. Meanwhile, the highest electric
field strength was recorded when the broken insulator was located in the
middle of the string.
Keyword:
Broken
Electric field characteristics
Finite element software
Porcelain insulator
Voltage distribution
Copyright © 2017 Institute of Advanced Engineering and Science.
All rights reserved.
Corresponding Author:
N. A. Othman,
Department of Electrical Power Engineering,
Faculty of Electrical & Electronic Engineering,
Universiti Tun Hussein Onn Malaysia (UTHM),
86400 Batu Pahat, Malaysia.
Email: ndiana@uthm.edu.my
1. INTRODUCTION
Overhead transmission lines can carry alternate current (AC) or direct current (DC) or both in an
electric power system. Overhead AC transmission lines carry three phase current and the transmission
voltages are between the range of 69kV and 765kV. However, the DC voltage transmission tower lines are
revolve in pairs for positive and negative current [1].
High voltage (HV) power lines have been widely used to transmit the electric energy from the
power stations to the consumers. Since a large part of power generation takes place at significant distances
from consumer, transmission lines must be employed to carry the power generated to its destination. It is well
known that overhead transmission generally consists of three primary components which are conductors,
insulators and tower structures.
Overhead transmission insulators can be considered cheap when compared with other HV
equipment. However, these insulators play an important role in protecting the most expensive equipment
which subsists in the power system network. Moreover, a reliable transmission network is partly dependent
on overhead transmission insulators [2]. More than a million units of overhead insulators have been
providing an excellent service over than 25 years in both transmission and distribution lines. However, these
IJECE ISSN: 2088-8708 
Potential and Electric Field Characteristics of Broken Porcelain Insulator (H. Rosli)
3115
insulators must be designed not only to withstand electrical stress but also to tolerate the mechanical forces
applied by the surroundings to successfully fulfil their functions. There are two main types of insulators that
is commonly used in power system network which are ceramic and polymeric insulators.
Ceramic insulators which consist of glass and porcelain are the earliest insulators used in the power
system transmission lines [3]. The pictorial view of glass and porcelain insulators is depicted in Figure 1.
Both insulators have been used for over a century and their application can be considered as a safe choice.
The raw materials for glass insulators includes soda ash, feldspar and cullet as well as a few other ingredients
that crushed to form powder and melted in a furnace [4]. Toughening significantly increases the mechanical
strength, making the glass shell suitable for the use of HV insulator. Meanwhile, high strength electrical
grade porcelain for line insulators is usually made by the classical wet process. Raw materials like clay are
mixed in water to facilitate blending. Therefore, even a small crack in the porcelain insulator may effect on
the puncture strength of the insulator [5].
(a) (b)
Figure 1. Example of (a) glass insulator and (b) porcelain insulator
The common types of insulators like porcelain, glass and polymer have been used according to their
respective capabilities. However, there are many factors that can bring to the insulators failure. The examples
of intrinsic and external factors of the insulation failures includes radial cracking, pin corrosion, brittle
fracture, damage to bulk dielectric and spontaneous shattering [6]. Since the outdoor insulators particularly
porcelain are subjects to electric stress and weather conditions, the insulator tends to be broken due to
unequal rate of expansion and contraction of porcelain, steel and cement caused by climate conditions. Apart
from that, improper glazing on the insulator surface also can cause the moisture to stick on it with the
deposited dust; hence a conducting path may be produced and lead to the flashover occurrence. The flashover
occurrence may cause overheat on the insulator and may result in cracking and shattering process. Besides, it
is accepted that the insulator may break the weak portion when experiencing a mechanical stress [7].
In the presence of higher stress or over-voltage, glass insulators in a string may result in completely
broken sheds. However, porcelain insulator only can be broken in chunk and leaves a large remaining pieces
of their shed under same conditions. It is worth mentioning that the porcelain insulators still can serve the
transmission line even though in broken or partially broken condition. However, how long these insulators
can withstand to serve the line is still questioned since the broken insulator may cause other insulator to
withstand the remaining voltage allocated for that particular insulator. This situation may results in the
voltage and electric field distribution alteration. The alteration of voltage and electric field distribution may
affect the insulator in terms of the life span and ultimately lead to the insulation breakdown after a certain
period of time. Therefore, this paper presents an analysis of broken porcelain insulator on voltage and electric
characteristics.
2. SIMULATION WORKS
In this paper, cap and pin type porcelain insulator of ANSI 52-3 type is used as main subject [8].
The insulator is miniature in free space using QuickField software for the simulation purpose. Technical
parameters of the porcelain insulator [9] is tabulated in Table 1 while the cross section area of porcelain
insulator is presented in Figure 2 [10]. The simulation was conducted in AC analysis problem type with the
voltage of 11kV and 132kV was applied to the insulator pin for single insulator and insulator string,
respectively. It is important highlighting that the simulation was conducted in axisymmetric axis which
require only a cross section area in the simulation works
In order to analyse the voltage and electric characteristics of broken porcelain insulator subjected
dissimilarity of the broken types, three distinct configurations are used namely;
1. Case A1: Broken porcelain insulator with broken shed 1.
2. Case A2: Broken porcelain insulator with broken shed 2.
 ISSN: 2088-8708
IJECE Vol. 7, No. 6, December 2017 : 3114 – 3123
3116
3. Case A3: Broken porcelain insulator with broken shed 3.
For each case, the number of broken shed is different as indicated in black circles in Figure 3. As clearly seen
from the figure, the number of mesh is increased at the broken part approaches the insulator pin.
Table 1. Technical parameters of the simulated porcelain insulator [10]
Material Relative Electric Permittivity, ε (Ω•m) Conductivity, σ (S/m)
Cement 2 0
Porcelain 6.0 1.0-10
Air 1 3×10−15
Figure 2. The cross section area of a porcelain insulator [10]
(a) (b) (c) (d)
Figure 3. The configuration of broken insulator for (a) Perfect, (b) Case A1, (c) Case A2, (d) Case A3
3. RESULTS AND ANALYSIS
All results presented in this section was obtained based on contour plot that measured along the
insulator creepage distance. The discussion is divided into four sections mainly concern on single broken
porcelain insulator and its effects on an insulator string.
3.1. Voltage Distribution of Single Porcelain Insulator
All results presented in this section was obtained based on contour plot that measured along the
creepage distance. However, it is predicted that the performance of the string will be a little affected by
varying the location of broken insulator in string [11]. Figure 4 shows the contour of potential distribution
across single porcelain insulator. From the simulation contour in Figure 4(a), it can be seen that the perfect
porcelain insulator has the highest potential in the region nearest to steel pin (around shed 4). The potential
pattern can be said as uniformly decreased when the measured distance get further from the shed 4. However,
IJECE ISSN: 2088-8708 
Potential and Electric Field Characteristics of Broken Porcelain Insulator (H. Rosli)
3117
when the insulator shed is broken, it is observed in Figure 4(b) to Figure 4(d) that the high potential was
distributed more near the steel pin. It is also apparent that the equipotential lines getting narrower when the
insulator shed is broken. It is worth stating that the colour pattern of the contour indicates the different
potential value across each insulator.
Figure 5 illustrates the potential distribution along creepage distance for all cases of broken
porcelain insulators when compared to the perfect insulator. It is apparent that the potential distribution of
perfect insulator retain the highest value compared to the broken insulators; this findings affirmed by [12].
Generally, the potential distribution pattern can be said as non-uniform along the creepage distance when
measured from HV electrode for all cases. However, the broken shed of case A3 bears the most significant
potential value and contribute the highest percentage reduction of potential compared to other cases as the
reduction value is the highest when compared to perfect case.
Table 2 shows the maximum and minimum value of voltage for perfect and all cases of broken
porcelain insulators. From the tabulated data in Table 2, it can be said that the maximum reduction of potential
value occurred in case A3 when almost all shed is broken. Therefore, it can be summarized that the nearer the
broken of shed of an insulator to the HV electrode, the more potential value will be fluctuated.
(a) (b) (c) (d)
Figure 4. Contour of potential distribution across single insulator for (a) Perfect; (b) Case A1; (c) Case A2;
and (d) Case A3
Figure 5. Potential distribution for all cases of broken porcelain insulators when compared to the perfect
insulator
Table 2. The highest and lowest value of voltage
Insulator Voltage (V)
Max Min
Perfect 5934.69 2366.38
Case A1 4219.12 1576.54
Case A2 4098.83 1466.89
Case A3 4008.28 1041.81
 ISSN: 2088-8708
IJECE Vol. 7, No. 6, December 2017 : 3114 – 3123
3118
3.2. Electric Field Distribution of Single Porcelain Insulator
Based on R. Krishnan study, it has been proven that the insulators do not conduct any current from
the current density profile through insulators [13]. Therefore, in this paper, the maximum electric field across
the creepage distance of each insulator is taken by placing the contour line on it. Figure 6 shows the colour
pattern of electric field distribution for single perfect porcelain insulator and all cases of broken porcelain
insulators. From the simulation contour in Figure 6(a), it can be seen that the perfect insulator has the most
narrowed equipotential lines of electric field distribution in the region nearest to steel pin. However, the
equipotential lines of electric field distribution is increased when the shed of the insulator is broken as shown
in Figure 6(b) to Figure 6(d) which is similar to the findings in [14].
Figure 7 illustrates the graphs of electrical field distribution of single porcelain insulator compared
with all cases of broken porcelain insulators. Generally, the distribution of electric field for perfect and all
broken cases single porcelain insulator presents the similar pattern along the creepage distance. However,
there is a slight decrease in the electric filed strength value at beginning before become almost constant in the
middle of the contour across insulators and experienced a fast develop at the end for perfect insulator.
Contrarily for all broken case where the electric field strength is much higher at the beginning and lower at
the end when compared to perfect insulator.
(a) (b) (c) (d)
Figure 6. Contour of electric field distribution across single insulator for (a) Perfect; (b) Case A1; (c) Case
A2; (d) and Case A3
Figure 7. Electrical field distribution of single porcelain insulator compared with all cases of broken
porcelain insulators
Table 3 shows the maximum and minimum value of electrical field of the four cases of single
porcelain insulator. It is appear to indicate that the broken of insulator in the shed nearest to the electrode
bears the most effect of electric field distribution across the insulator.
IJECE ISSN: 2088-8708 
Potential and Electric Field Characteristics of Broken Porcelain Insulator (H. Rosli)
3119
Table 3. The highest and lowest value of electric field
Insulator E-Field (kV/cm)
Max Min
Perfect 3821.07 14.25
Case A1 2210.09 17.32
Case A2 2256.44 12.74
Case A3 2099.28 14.56
Different cases of broken porcelain insulators presented has been concluded that the porcelain
insulator with broken shed 3 has the most significant effect on potential and electric field distribution.
Therefore, further investigation of the most significant effect of broken porcelain insulator on voltage and
electric characteristics were tested on 10 units of insulator strings in different location of the broken insulator
which are near the electrode, in the middle, near the ground and alternate position.
3.3. Voltage Distribution across a Porcelain Insulator String
Insulator strings with different locations of broken single porcelain insulator were simulated and
produced a contour plot of the string with different colour patterns. The colour patterns of the contour
indicate the diverse potential value across each insulator in the string [15]. In order to analyse the effect of
broken Case A3 on voltage and electric characteristics in a string insulator, four dissimilar configurations are
used. Each configuration are assigned as shown in Table 4 for each cases the location of the broken porcelain
insulator from Case A3 in the previous section.
Table 4. The designation of string insulator with broken porcelain insulator
String with 10 units of porcelain insulators Designation
No broken porcelain insulator present Perfect
Broken porcelain insulator located alternately with perfect insulator B1
Broken porcelain insulator located near HV electrode terminal B2
Broken porcelain insulator located near ground terminal B3
Broken porcelain insulator located in the middle of the string B4
From the simulation contour of Figure 8, it can be observed that perfect insulator string the
distribution of potential is gradually decreased from the insulator pin to the insulator cap. However, in the
presence of broken insulator in the string, the potential pattern increased in variant with different location of
the broken insulator approached to transmission line. Based on the graph, the potential is not uniformly
distributed across each insulator. The first insulator that is located at the HV electrode (near the transmission
line) bears the highest potential value for all cases. The potential is then decreases in the next insulators along
to the ground electrode.
Figure 9 shows the potential distribution of 10 units of porcelain insulator in a string. It is obvious
from the figure that the voltage distribution is affected when broken insulator exists in the string. This finding
is supported by Xiu-chen [16] which concluded that the insulators near the earth are sensitive to the voltage-
change of the insulator near the power line, but the latter are not sensitive to that of the frontier. By their
analysis, it can be concluded that the sensitivity of string insulator is most affected when broken insulator
exist near the ground (earth).
According to Azordegan et al. [17], the electromagnetic radiations are stronger at the end of positive
cycle for a cracked insulator while the electromagnetic radiations are stronger at the end of negative cycle for
a polluted insulator. This supported the observation from the present findings when the potential distribution
decreases along the string due to cracks on the porcelain insulator shed. Besides that, the mechanical strength
reduction of insulator also causing undesired partial discharges.
The lowest average potential value of 50kV was recorded at the B1 case string with 35.06%
reduction from the perfect string insulator can be calculated from Figure 9. The graph is then dramatically
decrease for all the cases. It can be shown that the potential which should bear by the first insulator have been
transferred to the second insulator and so on. Table 5 tabulates the average, maximum and minimum value of
voltage across string with 10 units of porcelain insulator in all cases. It is noticed that the average value
indicate that the presents of broken insulator in a string affects the voltage across the string insulator. But, the
result shows that the B4 case bears the most significant effect on the potential distribution of string with 10
units of porcelain insulator due to the highest reduction value of voltage at the end of the string insulator in
ground terminal.
 ISSN: 2088-8708
IJECE Vol. 7, No. 6, December 2017 : 3114 – 3123
3120
(a) (b) (c) (d) (e)
Figure 8. Potential distribution of string porcelain insulator for (a) Perfect string insulator, (b) B1 string
insulator, (c) B2 string insulator, (d) B3 string insulator, and (e) B4 string insulator
Figure 9. Potential distribution of all cases of string insulators
Table 5. The highest and lowest value of voltage in string insulator
String Voltage (kV) Average (kV)
Max Min
Perfect 116 11 77
B1 86 13 50
B2 88 13 51
B3 84 17 55
B4 86 16 56
3.4. Electric Field Distribution across a Porcelain Insulator String
The maximum electric field across the contour distance of each insulator along the string is taken as
the strength across each insulator. Figure 10 shows the electric field distribution in string with 10 unit of
insulator. It is observed that the present of the broken shed in the insulator has decreased the average electric
field distribution in string; this findings is agreed by Shahat [18]. Figure 11 shows the electric field
distribution of 10 units of porcelain insulator in a string. From Figure 11, the distribution pattern can be said
as similar for all cases of strings. The first insulator that is located nearest to the line for Case B3 has the
highest electric field.
According to the research lead by Akbari [10], who studied on finite element analysis of disc
insulator type and corona ring effect on electric field distribution over 230kV insulator string. They found
that as the distance from insulator string increases, the dependency of electric field to insulator material and
profile decreases. Apart from that, Anjum [11] has proved that varying the position of the insulator disc
IJECE ISSN: 2088-8708 
Potential and Electric Field Characteristics of Broken Porcelain Insulator (H. Rosli)
3121
within the string has little or no effect on the level of classification performance. By relating to the
conclusion, it has confirmed the similarity patterns in the present findings in Figure 10.
In addition, a study conducted by Palhade [19] found that the high temperature produced in current
carrying conductor is not enough to transfer over an insulator assembly component during a short period of
time. It could be safe to assume that the temperature is not high enough to significantly affect the
performance in terms of mechanical and thermal characteristics of an insulator assembly for short duration in
this study. Hence, the data obtained from broken porcelain insulators in all cases of string insulator has not
been affected much by the temperature of the current. However, in real operation of overhead HV insulators,
electrical and mechanical loading, variable atmospheric condition and environmental pollution may degrade
the bonding characteristics of cement, even disc material which is basically brittle in nature leading to failure
of insulator assembly.
(a) (b) (c) (d) (e)
Figure 10. Electric field distribution of string porcelain insulator for (a) Perfect string insulator, (b) B1 string
insulator, (c) B2 string insulator, (d) B3 string insulator, and (e) B4 string insulator
Figure 11. Electric field of broken insulator in string
Table 6. The highest and lowest value of electric field in string insulator
String Electric Field (kV/cm) Average (kV/cm)
Max Min
Perfect 1791.2 1.0 313.5
B1 2513.5 1.3 454.4
B2 2510.1 0.8 465.8
B3 2186.3 1.4 488.4
B4 2883.8 1.1 484.2
 ISSN: 2088-8708
IJECE Vol. 7, No. 6, December 2017 : 3114 – 3123
3122
Table 6 shows the electric field value in all cases of string insulator with and without broken
porcelain insulator. The result shows that highest value of electric field distribution is found in the first
insulator in Case B3 based on Figure 11. Meanwhile, highest value of electric field was found in case B4 at
the tenth insulator as mentioned in Table 6.
4. CONCLUSION
This paper set out to explore the influence of broken shed in porcelain insulator in terms of voltage
and electrical characteristics. From the results obtained, a few conclusions had been made concerning the
purpose of this investigation.
1. The single porcelain insulator denoted a bulk reduction of voltage and electric field when the broken of
the shed in the insulator was near the electrode.
2. In HV string insulator with 10 units of porcelain insulator, the potential distribution experienced the most
diminutive value when the broken porcelain insulator were located in the string near the ground. In
addition, the potential distribution average were the least when the broken and perfect insulator were
arranged alternately in the string.
3. Consequently, the investigation of electric field distribution has shown that a hulking strength of average
when the broken insulator was ascertain near the ground when assimilated to the string insulator without
any broken insulator.
ACKNOWLEDGEMENTS
The authors express their sincere gratitude to Universiti Tun Hussein Onn Malaysia (UTHM) for the
use of facilities and equipment supports.
REFERENCES
[1] Masoud F, Shahab F, and William C, Electrical Design of Overhead Power Transmission Lines: McGraw-Hill
Professional, 2012.
[2] Sims S, “High-voltage Overhead Transmission Lines (HVOTLs) and House Prices,” Towers, Turbines Transm.
Lines Impacts Prop. Value, pp. 45–53, 2013.
[3] Gencoglu M. T, “The Comparison of Ceramic and Non-Ceramic Insulators,” E-Journal of New World Sciences
Academy, vol 2, no 4, pp. 274–294, 2007.
[4] “A Review of Insulator Failure Modes.” [Online]. Available: http://www.inmr.com/review-insulator-failure-
modes/.
[5] George J, Prat S, Tartier S, and Lodi Z, "Electrical characteristics and properties of a stub (damaged toughened
glass insulator)," in 18th Int. Symp. High Voltage Insulator Seoul, Korea, 2013.
[6] Munz D and Fett T, “Ceramics: mechanical properties, failure behaviour, materials selection,” Springer Science &
Business Media, vol. 36, 2013.
[7] Mathis H. A, “Technical Article,” Shock Vib. Dig., vol. 25, no. 6, pp. 10–14, 1993.
[8] “Catalog No. 8255, Suspension Insulators Ball and socket type” Gamma Insulators Corp., United States.
[9] “Disc insulator-QuickField FEA Software,” [Online]. Available:
http://www.quickfield.com/advanced/insulator.htm. [Accessed: October, 2016]
[10] Rahimnejad A, Asadpoor M. B, Akbari E, and Mirzaie M, “Finite Element Analysis of Disc Insulator Type and
Corona Ring Effect on Electric Field Distribution over 230-kV Insulator Strings,” Iranian Journal of Electrical &
Electronic Engineering, vol. 9, no. 1, March 2013.
[11] Anjum S, "A Study of the Detection of Defects in Ceramic Insulators Based on Radio Frequency Signatures,"
UWSpace, 2014.
[12] Shinohara A. H, et al, "Defects detection in electrical insulators and breaker for high voltage by low cost computed
radiography systems," International Symposium on Digital industrial Radiology and Computed Tomography.
Lyon, France. 2007.
[13] R. Krishnan, S. Samanta, R. Sudha, and K. Govardhan, “Electric Field Analysis of High Voltage Insulators,”
pp. 31–35, 2012.
[14] Razali M. H, “Electric Field Modeling of Outdoor Insulator for Optimized Performance,” Master dissertation.
Universiti Tun Hussein Onn, Malaysia, 2014.
[15] F. Hanani et al., “Analysis of Potential Distribution of a Glass Insulators String with Different Number of Broken
Units,” Bachelor dissertation. Universiti Teknologi Malaysia, 2015.
[16] Xue L.L and Chen J. X, “Detection Methods of the Faulty Porcelain Insulators,” Proceedings of the 2006
IASME/WSEAS International Conference on Energy & Environmental Systems, Chalkida, Greece, pp. 333-342,
2006.
[17] E. Azordegan, B. Kordi, and D. R. Swatek, “Radiated electromagnetic field signature of faulty and polluted
porcelain insulators,” 2010 Int. Conf. High Volt. Eng. Appl. ICHVE 2010, pp. 449–452, 2010.
IJECE ISSN: 2088-8708 
Potential and Electric Field Characteristics of Broken Porcelain Insulator (H. Rosli)
3123
[18] M. El-shahat and H. Anis, “Risk assessment of desert pollution on composite high voltage insulators,” J. Adv. Res.,
vol. 5, no. 5, pp. 569–576, 2014.
[19] R. D. Palhade, V. B. Tungikar, G. M. Dhole, and S. M. Kherde, “Transient Thermal Conduction Analysis of High
Voltage Cap and Pin Type Ceramic Disc Insulator Assembly,” Int. J. Adv. Sci. Technol., vol. 56, pp. 73–86, 2013.
BIOGRAPHIES OF AUTHORS
Hanan Rosli was born and raised in Sungai Petani, Kedah, Malaysia on January 24, 1994. After
completing high school in MARA Junior Science College (MJSC) Kepala Batas (2011), she went
to Kedah Matriculation College for a year and pursue her study in Bachelor of Electrical
Engineering (Hons) in UTHM, Johor (2017). Her research interest is more focus in high voltage
insulation field.
Nordiana Azlin Othman was born in Johor, Malaysia on January 19, 1986. She received Diploma
in Electrical Communication and B.Eng in Electrical Engineering from Universiti Teknologi
Malaysia (UTM) respectively in 2007 and 2010. She completed her PhD in Space Charge
Distirbution at Institute of High Voltage and High Current (IVAT) in Faculty of Electrical
Engineering, UTM. Her research interest includes the detection and diagnostics of partial
discharge and space charge in insulation for condition monitoring.
Nor Akmal Mohd Jamail is a lecturer of Universiti Tun Hussein Onn Malaysia since 2008. She
received the Bachelor degree in Electrical Engineering from Universiti Teknologi Malaysia in
2005, M.Eng in Power System from Universiti Tun Hussein Onn Malaysia in 2007 and Ph.D. in
High Voltage Engineering from Universiti Teknologi Malaysia, in 2015. Her research interests
include condition monitoring of polymer nanocomposite insulation for HV purpose, dielectrics and
electrical insulation. She is registered with the Board of Engineers Malaysia (BEM).
Muhammad Nafis Ismail was born on 1982 in Johor, Malaysia. He received B.Eng in Electrical
Engineering fron Universiti Teknologi Malaysia (UTM) in 2005. He previously worked as an
Electrical Engineer at BQE Engineering from 2005 to 2007 and currently work as an Electrical
Instructor at University Tun Hussein Onn Malaysia.

More Related Content

What's hot

Highly thermally conductive dielectric coatings produced by Plasma Electrolyt...
Highly thermally conductive dielectric coatings produced by Plasma Electrolyt...Highly thermally conductive dielectric coatings produced by Plasma Electrolyt...
Highly thermally conductive dielectric coatings produced by Plasma Electrolyt...
Tamires Tah
 
IMAPS 2003 Manuscript - E
IMAPS 2003 Manuscript - EIMAPS 2003 Manuscript - E
IMAPS 2003 Manuscript - E
David Stark
 
Electromigration Poster 2
Electromigration Poster 2Electromigration Poster 2
Electromigration Poster 2
Alejandro Cota
 
Cerma Clad Introduction December 2010
Cerma Clad Introduction December 2010Cerma Clad Introduction December 2010
Cerma Clad Introduction December 2010
Mario Medanic
 
Impact of gamma-ray irradiation on dynamic characteristics of Si and SiC powe...
Impact of gamma-ray irradiation on dynamic characteristics of Si and SiC powe...Impact of gamma-ray irradiation on dynamic characteristics of Si and SiC powe...
Impact of gamma-ray irradiation on dynamic characteristics of Si and SiC powe...
IJECEIAES
 

What's hot (20)

Highly thermally conductive dielectric coatings produced by Plasma Electrolyt...
Highly thermally conductive dielectric coatings produced by Plasma Electrolyt...Highly thermally conductive dielectric coatings produced by Plasma Electrolyt...
Highly thermally conductive dielectric coatings produced by Plasma Electrolyt...
 
Metallic glass
Metallic glassMetallic glass
Metallic glass
 
Simulation study of single event effects sensitivity on commercial power MOSF...
Simulation study of single event effects sensitivity on commercial power MOSF...Simulation study of single event effects sensitivity on commercial power MOSF...
Simulation study of single event effects sensitivity on commercial power MOSF...
 
Power Shunts - Copper Braided Shunts For Switchgear & Transformers
Power Shunts - Copper Braided Shunts For Switchgear & TransformersPower Shunts - Copper Braided Shunts For Switchgear & Transformers
Power Shunts - Copper Braided Shunts For Switchgear & Transformers
 
ASM 2013 Fluxtrol Paper - Innovations in Soft Magnetic Composites and their A...
ASM 2013 Fluxtrol Paper - Innovations in Soft Magnetic Composites and their A...ASM 2013 Fluxtrol Paper - Innovations in Soft Magnetic Composites and their A...
ASM 2013 Fluxtrol Paper - Innovations in Soft Magnetic Composites and their A...
 
composites applications in electrical and electronics
composites applications in electrical and electronicscomposites applications in electrical and electronics
composites applications in electrical and electronics
 
Composites in electrical and electronic applications
Composites in electrical and electronic applicationsComposites in electrical and electronic applications
Composites in electrical and electronic applications
 
Power cables-160211193139
Power cables-160211193139Power cables-160211193139
Power cables-160211193139
 
Mac Medical Overview Presentation
Mac Medical Overview PresentationMac Medical Overview Presentation
Mac Medical Overview Presentation
 
IMAPS 2003 Manuscript - E
IMAPS 2003 Manuscript - EIMAPS 2003 Manuscript - E
IMAPS 2003 Manuscript - E
 
Underground cables
Underground cablesUnderground cables
Underground cables
 
Energy applications of polymer nanocomposites
Energy applications of polymer nanocompositesEnergy applications of polymer nanocomposites
Energy applications of polymer nanocomposites
 
Electromigration Poster 2
Electromigration Poster 2Electromigration Poster 2
Electromigration Poster 2
 
Cerma Clad Introduction December 2010
Cerma Clad Introduction December 2010Cerma Clad Introduction December 2010
Cerma Clad Introduction December 2010
 
Under ground cables
Under ground cablesUnder ground cables
Under ground cables
 
ASM 2013 Fluxtrol Presentation - Innovations in Soft Magnetic Composites and ...
ASM 2013 Fluxtrol Presentation - Innovations in Soft Magnetic Composites and ...ASM 2013 Fluxtrol Presentation - Innovations in Soft Magnetic Composites and ...
ASM 2013 Fluxtrol Presentation - Innovations in Soft Magnetic Composites and ...
 
Impact of gamma-ray irradiation on dynamic characteristics of Si and SiC powe...
Impact of gamma-ray irradiation on dynamic characteristics of Si and SiC powe...Impact of gamma-ray irradiation on dynamic characteristics of Si and SiC powe...
Impact of gamma-ray irradiation on dynamic characteristics of Si and SiC powe...
 
Manufacture and Testing of Building Integrated Photovoltaic system
Manufacture and Testing of Building Integrated Photovoltaic systemManufacture and Testing of Building Integrated Photovoltaic system
Manufacture and Testing of Building Integrated Photovoltaic system
 
Induction Heat Staking White Paper
Induction Heat Staking White PaperInduction Heat Staking White Paper
Induction Heat Staking White Paper
 
METAL MATRIX COMPOSITE
METAL MATRIX COMPOSITEMETAL MATRIX COMPOSITE
METAL MATRIX COMPOSITE
 

Similar to Potential and Electric Field Characteristics of Broken Porcelain Insulator

Similar to Potential and Electric Field Characteristics of Broken Porcelain Insulator (20)

Analysis of Electric Field and Current Density on XLPE Insulator
Analysis of Electric Field and Current Density on XLPE Insulator Analysis of Electric Field and Current Density on XLPE Insulator
Analysis of Electric Field and Current Density on XLPE Insulator
 
Electric Field Analysis and Impact Study with Shrubbery on the 11 kV Distribu...
Electric Field Analysis and Impact Study with Shrubbery on the 11 kV Distribu...Electric Field Analysis and Impact Study with Shrubbery on the 11 kV Distribu...
Electric Field Analysis and Impact Study with Shrubbery on the 11 kV Distribu...
 
Aq36257262
Aq36257262Aq36257262
Aq36257262
 
Electric Stress Analysis on 11kv Insulator
Electric Stress Analysis on 11kv InsulatorElectric Stress Analysis on 11kv Insulator
Electric Stress Analysis on 11kv Insulator
 
manufacturing of porcelain insulators
manufacturing of porcelain insulators  manufacturing of porcelain insulators
manufacturing of porcelain insulators
 
Some Aspects of Stress Distribution and Effect of Voids Having Different Gase...
Some Aspects of Stress Distribution and Effect of Voids Having Different Gase...Some Aspects of Stress Distribution and Effect of Voids Having Different Gase...
Some Aspects of Stress Distribution and Effect of Voids Having Different Gase...
 
Paper Electron Tube Afs Epri R5
Paper   Electron Tube   Afs Epri R5Paper   Electron Tube   Afs Epri R5
Paper Electron Tube Afs Epri R5
 
Lec no. 01
Lec no. 01Lec no. 01
Lec no. 01
 
Electrostatic stress analysis of high voltage cables
Electrostatic stress analysis of high voltage cablesElectrostatic stress analysis of high voltage cables
Electrostatic stress analysis of high voltage cables
 
A Training Report Of Saltlake 132/33kv Substation
A Training Report Of Saltlake 132/33kv SubstationA Training Report Of Saltlake 132/33kv Substation
A Training Report Of Saltlake 132/33kv Substation
 
26 15059 conductive ijeecs 1570310622(edit)
26 15059 conductive ijeecs 1570310622(edit)26 15059 conductive ijeecs 1570310622(edit)
26 15059 conductive ijeecs 1570310622(edit)
 
04a Breakdown of Solid Insulation.pdf
04a Breakdown of Solid Insulation.pdf04a Breakdown of Solid Insulation.pdf
04a Breakdown of Solid Insulation.pdf
 
Performance of 400 kv line insulators under pollution.
Performance of 400 kv line insulators under pollution.Performance of 400 kv line insulators under pollution.
Performance of 400 kv line insulators under pollution.
 
over head insulators
over head insulatorsover head insulators
over head insulators
 
Hv presentation
Hv presentationHv presentation
Hv presentation
 
Iec 62305 for lightning and surge protection follow in india nbc 2016 by bis(...
Iec 62305 for lightning and surge protection follow in india nbc 2016 by bis(...Iec 62305 for lightning and surge protection follow in india nbc 2016 by bis(...
Iec 62305 for lightning and surge protection follow in india nbc 2016 by bis(...
 
espp32.pdf
espp32.pdfespp32.pdf
espp32.pdf
 
Investigation into possible electrical fire outbreaks at welders’ worksho...
Investigation into possible electrical fire outbreaks at welders’     worksho...Investigation into possible electrical fire outbreaks at welders’     worksho...
Investigation into possible electrical fire outbreaks at welders’ worksho...
 
Unit I.pdf
Unit I.pdfUnit I.pdf
Unit I.pdf
 
Ageing of Medium Voltage Cables
Ageing of Medium Voltage CablesAgeing of Medium Voltage Cables
Ageing of Medium Voltage Cables
 

More from IJECEIAES

Remote field-programmable gate array laboratory for signal acquisition and de...
Remote field-programmable gate array laboratory for signal acquisition and de...Remote field-programmable gate array laboratory for signal acquisition and de...
Remote field-programmable gate array laboratory for signal acquisition and de...
IJECEIAES
 
An efficient security framework for intrusion detection and prevention in int...
An efficient security framework for intrusion detection and prevention in int...An efficient security framework for intrusion detection and prevention in int...
An efficient security framework for intrusion detection and prevention in int...
IJECEIAES
 
A review on internet of things-based stingless bee's honey production with im...
A review on internet of things-based stingless bee's honey production with im...A review on internet of things-based stingless bee's honey production with im...
A review on internet of things-based stingless bee's honey production with im...
IJECEIAES
 
Seizure stage detection of epileptic seizure using convolutional neural networks
Seizure stage detection of epileptic seizure using convolutional neural networksSeizure stage detection of epileptic seizure using convolutional neural networks
Seizure stage detection of epileptic seizure using convolutional neural networks
IJECEIAES
 
Hyperspectral object classification using hybrid spectral-spatial fusion and ...
Hyperspectral object classification using hybrid spectral-spatial fusion and ...Hyperspectral object classification using hybrid spectral-spatial fusion and ...
Hyperspectral object classification using hybrid spectral-spatial fusion and ...
IJECEIAES
 
SADCNN-ORBM: a hybrid deep learning model based citrus disease detection and ...
SADCNN-ORBM: a hybrid deep learning model based citrus disease detection and ...SADCNN-ORBM: a hybrid deep learning model based citrus disease detection and ...
SADCNN-ORBM: a hybrid deep learning model based citrus disease detection and ...
IJECEIAES
 
Performance enhancement of machine learning algorithm for breast cancer diagn...
Performance enhancement of machine learning algorithm for breast cancer diagn...Performance enhancement of machine learning algorithm for breast cancer diagn...
Performance enhancement of machine learning algorithm for breast cancer diagn...
IJECEIAES
 
A deep learning framework for accurate diagnosis of colorectal cancer using h...
A deep learning framework for accurate diagnosis of colorectal cancer using h...A deep learning framework for accurate diagnosis of colorectal cancer using h...
A deep learning framework for accurate diagnosis of colorectal cancer using h...
IJECEIAES
 
Predicting churn with filter-based techniques and deep learning
Predicting churn with filter-based techniques and deep learningPredicting churn with filter-based techniques and deep learning
Predicting churn with filter-based techniques and deep learning
IJECEIAES
 
Automatic customer review summarization using deep learningbased hybrid senti...
Automatic customer review summarization using deep learningbased hybrid senti...Automatic customer review summarization using deep learningbased hybrid senti...
Automatic customer review summarization using deep learningbased hybrid senti...
IJECEIAES
 

More from IJECEIAES (20)

Remote field-programmable gate array laboratory for signal acquisition and de...
Remote field-programmable gate array laboratory for signal acquisition and de...Remote field-programmable gate array laboratory for signal acquisition and de...
Remote field-programmable gate array laboratory for signal acquisition and de...
 
Detecting and resolving feature envy through automated machine learning and m...
Detecting and resolving feature envy through automated machine learning and m...Detecting and resolving feature envy through automated machine learning and m...
Detecting and resolving feature envy through automated machine learning and m...
 
Smart monitoring technique for solar cell systems using internet of things ba...
Smart monitoring technique for solar cell systems using internet of things ba...Smart monitoring technique for solar cell systems using internet of things ba...
Smart monitoring technique for solar cell systems using internet of things ba...
 
An efficient security framework for intrusion detection and prevention in int...
An efficient security framework for intrusion detection and prevention in int...An efficient security framework for intrusion detection and prevention in int...
An efficient security framework for intrusion detection and prevention in int...
 
Developing a smart system for infant incubators using the internet of things ...
Developing a smart system for infant incubators using the internet of things ...Developing a smart system for infant incubators using the internet of things ...
Developing a smart system for infant incubators using the internet of things ...
 
A review on internet of things-based stingless bee's honey production with im...
A review on internet of things-based stingless bee's honey production with im...A review on internet of things-based stingless bee's honey production with im...
A review on internet of things-based stingless bee's honey production with im...
 
A trust based secure access control using authentication mechanism for intero...
A trust based secure access control using authentication mechanism for intero...A trust based secure access control using authentication mechanism for intero...
A trust based secure access control using authentication mechanism for intero...
 
Fuzzy linear programming with the intuitionistic polygonal fuzzy numbers
Fuzzy linear programming with the intuitionistic polygonal fuzzy numbersFuzzy linear programming with the intuitionistic polygonal fuzzy numbers
Fuzzy linear programming with the intuitionistic polygonal fuzzy numbers
 
The performance of artificial intelligence in prostate magnetic resonance im...
The performance of artificial intelligence in prostate  magnetic resonance im...The performance of artificial intelligence in prostate  magnetic resonance im...
The performance of artificial intelligence in prostate magnetic resonance im...
 
Seizure stage detection of epileptic seizure using convolutional neural networks
Seizure stage detection of epileptic seizure using convolutional neural networksSeizure stage detection of epileptic seizure using convolutional neural networks
Seizure stage detection of epileptic seizure using convolutional neural networks
 
Analysis of driving style using self-organizing maps to analyze driver behavior
Analysis of driving style using self-organizing maps to analyze driver behaviorAnalysis of driving style using self-organizing maps to analyze driver behavior
Analysis of driving style using self-organizing maps to analyze driver behavior
 
Hyperspectral object classification using hybrid spectral-spatial fusion and ...
Hyperspectral object classification using hybrid spectral-spatial fusion and ...Hyperspectral object classification using hybrid spectral-spatial fusion and ...
Hyperspectral object classification using hybrid spectral-spatial fusion and ...
 
Fuzzy logic method-based stress detector with blood pressure and body tempera...
Fuzzy logic method-based stress detector with blood pressure and body tempera...Fuzzy logic method-based stress detector with blood pressure and body tempera...
Fuzzy logic method-based stress detector with blood pressure and body tempera...
 
SADCNN-ORBM: a hybrid deep learning model based citrus disease detection and ...
SADCNN-ORBM: a hybrid deep learning model based citrus disease detection and ...SADCNN-ORBM: a hybrid deep learning model based citrus disease detection and ...
SADCNN-ORBM: a hybrid deep learning model based citrus disease detection and ...
 
Performance enhancement of machine learning algorithm for breast cancer diagn...
Performance enhancement of machine learning algorithm for breast cancer diagn...Performance enhancement of machine learning algorithm for breast cancer diagn...
Performance enhancement of machine learning algorithm for breast cancer diagn...
 
A deep learning framework for accurate diagnosis of colorectal cancer using h...
A deep learning framework for accurate diagnosis of colorectal cancer using h...A deep learning framework for accurate diagnosis of colorectal cancer using h...
A deep learning framework for accurate diagnosis of colorectal cancer using h...
 
Swarm flip-crossover algorithm: a new swarm-based metaheuristic enriched with...
Swarm flip-crossover algorithm: a new swarm-based metaheuristic enriched with...Swarm flip-crossover algorithm: a new swarm-based metaheuristic enriched with...
Swarm flip-crossover algorithm: a new swarm-based metaheuristic enriched with...
 
Predicting churn with filter-based techniques and deep learning
Predicting churn with filter-based techniques and deep learningPredicting churn with filter-based techniques and deep learning
Predicting churn with filter-based techniques and deep learning
 
Taxi-out time prediction at Mohammed V Casablanca Airport
Taxi-out time prediction at Mohammed V Casablanca AirportTaxi-out time prediction at Mohammed V Casablanca Airport
Taxi-out time prediction at Mohammed V Casablanca Airport
 
Automatic customer review summarization using deep learningbased hybrid senti...
Automatic customer review summarization using deep learningbased hybrid senti...Automatic customer review summarization using deep learningbased hybrid senti...
Automatic customer review summarization using deep learningbased hybrid senti...
 

Recently uploaded

Tembisa Central Terminating Pills +27838792658 PHOMOLONG Top Abortion Pills F...
Tembisa Central Terminating Pills +27838792658 PHOMOLONG Top Abortion Pills F...Tembisa Central Terminating Pills +27838792658 PHOMOLONG Top Abortion Pills F...
Tembisa Central Terminating Pills +27838792658 PHOMOLONG Top Abortion Pills F...
drjose256
 

Recently uploaded (20)

Diploma Engineering Drawing Qp-2024 Ece .pdf
Diploma Engineering Drawing Qp-2024 Ece .pdfDiploma Engineering Drawing Qp-2024 Ece .pdf
Diploma Engineering Drawing Qp-2024 Ece .pdf
 
Adsorption (mass transfer operations 2) ppt
Adsorption (mass transfer operations 2) pptAdsorption (mass transfer operations 2) ppt
Adsorption (mass transfer operations 2) ppt
 
CLOUD COMPUTING SERVICES - Cloud Reference Modal
CLOUD COMPUTING SERVICES - Cloud Reference ModalCLOUD COMPUTING SERVICES - Cloud Reference Modal
CLOUD COMPUTING SERVICES - Cloud Reference Modal
 
UNIT-2 image enhancement.pdf Image Processing Unit 2 AKTU
UNIT-2 image enhancement.pdf Image Processing Unit 2 AKTUUNIT-2 image enhancement.pdf Image Processing Unit 2 AKTU
UNIT-2 image enhancement.pdf Image Processing Unit 2 AKTU
 
Autodesk Construction Cloud (Autodesk Build).pptx
Autodesk Construction Cloud (Autodesk Build).pptxAutodesk Construction Cloud (Autodesk Build).pptx
Autodesk Construction Cloud (Autodesk Build).pptx
 
8th International Conference on Soft Computing, Mathematics and Control (SMC ...
8th International Conference on Soft Computing, Mathematics and Control (SMC ...8th International Conference on Soft Computing, Mathematics and Control (SMC ...
8th International Conference on Soft Computing, Mathematics and Control (SMC ...
 
Instruct Nirmaana 24-Smart and Lean Construction Through Technology.pdf
Instruct Nirmaana 24-Smart and Lean Construction Through Technology.pdfInstruct Nirmaana 24-Smart and Lean Construction Through Technology.pdf
Instruct Nirmaana 24-Smart and Lean Construction Through Technology.pdf
 
Circuit Breakers for Engineering Students
Circuit Breakers for Engineering StudentsCircuit Breakers for Engineering Students
Circuit Breakers for Engineering Students
 
Independent Solar-Powered Electric Vehicle Charging Station
Independent Solar-Powered Electric Vehicle Charging StationIndependent Solar-Powered Electric Vehicle Charging Station
Independent Solar-Powered Electric Vehicle Charging Station
 
21scheme vtu syllabus of visveraya technological university
21scheme vtu syllabus of visveraya technological university21scheme vtu syllabus of visveraya technological university
21scheme vtu syllabus of visveraya technological university
 
The Entity-Relationship Model(ER Diagram).pptx
The Entity-Relationship Model(ER Diagram).pptxThe Entity-Relationship Model(ER Diagram).pptx
The Entity-Relationship Model(ER Diagram).pptx
 
UNIT 4 PTRP final Convergence in probability.pptx
UNIT 4 PTRP final Convergence in probability.pptxUNIT 4 PTRP final Convergence in probability.pptx
UNIT 4 PTRP final Convergence in probability.pptx
 
Interfacing Analog to Digital Data Converters ee3404.pdf
Interfacing Analog to Digital Data Converters ee3404.pdfInterfacing Analog to Digital Data Converters ee3404.pdf
Interfacing Analog to Digital Data Converters ee3404.pdf
 
Raashid final report on Embedded Systems
Raashid final report on Embedded SystemsRaashid final report on Embedded Systems
Raashid final report on Embedded Systems
 
History of Indian Railways - the story of Growth & Modernization
History of Indian Railways - the story of Growth & ModernizationHistory of Indian Railways - the story of Growth & Modernization
History of Indian Railways - the story of Growth & Modernization
 
litvinenko_Henry_Intrusion_Hong-Kong_2024.pdf
litvinenko_Henry_Intrusion_Hong-Kong_2024.pdflitvinenko_Henry_Intrusion_Hong-Kong_2024.pdf
litvinenko_Henry_Intrusion_Hong-Kong_2024.pdf
 
analog-vs-digital-communication (concept of analog and digital).pptx
analog-vs-digital-communication (concept of analog and digital).pptxanalog-vs-digital-communication (concept of analog and digital).pptx
analog-vs-digital-communication (concept of analog and digital).pptx
 
Basics of Relay for Engineering Students
Basics of Relay for Engineering StudentsBasics of Relay for Engineering Students
Basics of Relay for Engineering Students
 
Worksharing and 3D Modeling with Revit.pptx
Worksharing and 3D Modeling with Revit.pptxWorksharing and 3D Modeling with Revit.pptx
Worksharing and 3D Modeling with Revit.pptx
 
Tembisa Central Terminating Pills +27838792658 PHOMOLONG Top Abortion Pills F...
Tembisa Central Terminating Pills +27838792658 PHOMOLONG Top Abortion Pills F...Tembisa Central Terminating Pills +27838792658 PHOMOLONG Top Abortion Pills F...
Tembisa Central Terminating Pills +27838792658 PHOMOLONG Top Abortion Pills F...
 

Potential and Electric Field Characteristics of Broken Porcelain Insulator

  • 1. International Journal of Electrical and Computer Engineering (IJECE) Vol. 7, No. 6, December 2017, pp. 3114~3123 ISSN: 2088-8708, DOI: 10.11591/ijece.v7i6.pp3114-3123  3114 Journal homepage: http://iaesjournal.com/online/index.php/IJECE Potential and Electric Field Characteristics of Broken Porcelain Insulator H. Rosli, N. A. Othman, N. A. M. Jamail, M. N. Ismail Department of Electrical Power Engineering, Faculty of Electrical & Electronic Engineering, Universiti Tun Hussein Onn Malaysia (UTHM), 86400 Batu Pahat, Malaysia Article Info ABSTRACT Article history: Received Jul 10, 2017 Revised Oct 14, 2017 Accepted Oct 26, 2017 Overhead line insulators can be damaged for various reasons during their service life. Porcelain or glass insulators once damaged can affect the reliability of power system networks. This paper presents the study of voltage and electric characteristics along the surface of a broken porcelain insulator located in a string of 10 unit insulators. Three models of broken porcelain insulators were being proposed and the analysis results on voltage and electric characteristics were individually collected. The broken porcelain insulator with the most significant effect were then being investigated in the strings of 10 unit insulators. The finite element software of Quickfield was used to analyze the voltage and electric characteristics. Form the presented results, it is proven that the single porcelain insulators with broken shed at the nearest to the electrode terminal gave the most significant effect of voltage and electric field distribution pattern along the creepage distance. However, when this type of broken insulator was included in a string of 10 unit insulators, maximum average value of voltage achieved once the broken insulator was located at the HV terminal. Meanwhile, the highest electric field strength was recorded when the broken insulator was located in the middle of the string. Keyword: Broken Electric field characteristics Finite element software Porcelain insulator Voltage distribution Copyright © 2017 Institute of Advanced Engineering and Science. All rights reserved. Corresponding Author: N. A. Othman, Department of Electrical Power Engineering, Faculty of Electrical & Electronic Engineering, Universiti Tun Hussein Onn Malaysia (UTHM), 86400 Batu Pahat, Malaysia. Email: ndiana@uthm.edu.my 1. INTRODUCTION Overhead transmission lines can carry alternate current (AC) or direct current (DC) or both in an electric power system. Overhead AC transmission lines carry three phase current and the transmission voltages are between the range of 69kV and 765kV. However, the DC voltage transmission tower lines are revolve in pairs for positive and negative current [1]. High voltage (HV) power lines have been widely used to transmit the electric energy from the power stations to the consumers. Since a large part of power generation takes place at significant distances from consumer, transmission lines must be employed to carry the power generated to its destination. It is well known that overhead transmission generally consists of three primary components which are conductors, insulators and tower structures. Overhead transmission insulators can be considered cheap when compared with other HV equipment. However, these insulators play an important role in protecting the most expensive equipment which subsists in the power system network. Moreover, a reliable transmission network is partly dependent on overhead transmission insulators [2]. More than a million units of overhead insulators have been providing an excellent service over than 25 years in both transmission and distribution lines. However, these
  • 2. IJECE ISSN: 2088-8708  Potential and Electric Field Characteristics of Broken Porcelain Insulator (H. Rosli) 3115 insulators must be designed not only to withstand electrical stress but also to tolerate the mechanical forces applied by the surroundings to successfully fulfil their functions. There are two main types of insulators that is commonly used in power system network which are ceramic and polymeric insulators. Ceramic insulators which consist of glass and porcelain are the earliest insulators used in the power system transmission lines [3]. The pictorial view of glass and porcelain insulators is depicted in Figure 1. Both insulators have been used for over a century and their application can be considered as a safe choice. The raw materials for glass insulators includes soda ash, feldspar and cullet as well as a few other ingredients that crushed to form powder and melted in a furnace [4]. Toughening significantly increases the mechanical strength, making the glass shell suitable for the use of HV insulator. Meanwhile, high strength electrical grade porcelain for line insulators is usually made by the classical wet process. Raw materials like clay are mixed in water to facilitate blending. Therefore, even a small crack in the porcelain insulator may effect on the puncture strength of the insulator [5]. (a) (b) Figure 1. Example of (a) glass insulator and (b) porcelain insulator The common types of insulators like porcelain, glass and polymer have been used according to their respective capabilities. However, there are many factors that can bring to the insulators failure. The examples of intrinsic and external factors of the insulation failures includes radial cracking, pin corrosion, brittle fracture, damage to bulk dielectric and spontaneous shattering [6]. Since the outdoor insulators particularly porcelain are subjects to electric stress and weather conditions, the insulator tends to be broken due to unequal rate of expansion and contraction of porcelain, steel and cement caused by climate conditions. Apart from that, improper glazing on the insulator surface also can cause the moisture to stick on it with the deposited dust; hence a conducting path may be produced and lead to the flashover occurrence. The flashover occurrence may cause overheat on the insulator and may result in cracking and shattering process. Besides, it is accepted that the insulator may break the weak portion when experiencing a mechanical stress [7]. In the presence of higher stress or over-voltage, glass insulators in a string may result in completely broken sheds. However, porcelain insulator only can be broken in chunk and leaves a large remaining pieces of their shed under same conditions. It is worth mentioning that the porcelain insulators still can serve the transmission line even though in broken or partially broken condition. However, how long these insulators can withstand to serve the line is still questioned since the broken insulator may cause other insulator to withstand the remaining voltage allocated for that particular insulator. This situation may results in the voltage and electric field distribution alteration. The alteration of voltage and electric field distribution may affect the insulator in terms of the life span and ultimately lead to the insulation breakdown after a certain period of time. Therefore, this paper presents an analysis of broken porcelain insulator on voltage and electric characteristics. 2. SIMULATION WORKS In this paper, cap and pin type porcelain insulator of ANSI 52-3 type is used as main subject [8]. The insulator is miniature in free space using QuickField software for the simulation purpose. Technical parameters of the porcelain insulator [9] is tabulated in Table 1 while the cross section area of porcelain insulator is presented in Figure 2 [10]. The simulation was conducted in AC analysis problem type with the voltage of 11kV and 132kV was applied to the insulator pin for single insulator and insulator string, respectively. It is important highlighting that the simulation was conducted in axisymmetric axis which require only a cross section area in the simulation works In order to analyse the voltage and electric characteristics of broken porcelain insulator subjected dissimilarity of the broken types, three distinct configurations are used namely; 1. Case A1: Broken porcelain insulator with broken shed 1. 2. Case A2: Broken porcelain insulator with broken shed 2.
  • 3.  ISSN: 2088-8708 IJECE Vol. 7, No. 6, December 2017 : 3114 – 3123 3116 3. Case A3: Broken porcelain insulator with broken shed 3. For each case, the number of broken shed is different as indicated in black circles in Figure 3. As clearly seen from the figure, the number of mesh is increased at the broken part approaches the insulator pin. Table 1. Technical parameters of the simulated porcelain insulator [10] Material Relative Electric Permittivity, ε (Ω•m) Conductivity, σ (S/m) Cement 2 0 Porcelain 6.0 1.0-10 Air 1 3×10−15 Figure 2. The cross section area of a porcelain insulator [10] (a) (b) (c) (d) Figure 3. The configuration of broken insulator for (a) Perfect, (b) Case A1, (c) Case A2, (d) Case A3 3. RESULTS AND ANALYSIS All results presented in this section was obtained based on contour plot that measured along the insulator creepage distance. The discussion is divided into four sections mainly concern on single broken porcelain insulator and its effects on an insulator string. 3.1. Voltage Distribution of Single Porcelain Insulator All results presented in this section was obtained based on contour plot that measured along the creepage distance. However, it is predicted that the performance of the string will be a little affected by varying the location of broken insulator in string [11]. Figure 4 shows the contour of potential distribution across single porcelain insulator. From the simulation contour in Figure 4(a), it can be seen that the perfect porcelain insulator has the highest potential in the region nearest to steel pin (around shed 4). The potential pattern can be said as uniformly decreased when the measured distance get further from the shed 4. However,
  • 4. IJECE ISSN: 2088-8708  Potential and Electric Field Characteristics of Broken Porcelain Insulator (H. Rosli) 3117 when the insulator shed is broken, it is observed in Figure 4(b) to Figure 4(d) that the high potential was distributed more near the steel pin. It is also apparent that the equipotential lines getting narrower when the insulator shed is broken. It is worth stating that the colour pattern of the contour indicates the different potential value across each insulator. Figure 5 illustrates the potential distribution along creepage distance for all cases of broken porcelain insulators when compared to the perfect insulator. It is apparent that the potential distribution of perfect insulator retain the highest value compared to the broken insulators; this findings affirmed by [12]. Generally, the potential distribution pattern can be said as non-uniform along the creepage distance when measured from HV electrode for all cases. However, the broken shed of case A3 bears the most significant potential value and contribute the highest percentage reduction of potential compared to other cases as the reduction value is the highest when compared to perfect case. Table 2 shows the maximum and minimum value of voltage for perfect and all cases of broken porcelain insulators. From the tabulated data in Table 2, it can be said that the maximum reduction of potential value occurred in case A3 when almost all shed is broken. Therefore, it can be summarized that the nearer the broken of shed of an insulator to the HV electrode, the more potential value will be fluctuated. (a) (b) (c) (d) Figure 4. Contour of potential distribution across single insulator for (a) Perfect; (b) Case A1; (c) Case A2; and (d) Case A3 Figure 5. Potential distribution for all cases of broken porcelain insulators when compared to the perfect insulator Table 2. The highest and lowest value of voltage Insulator Voltage (V) Max Min Perfect 5934.69 2366.38 Case A1 4219.12 1576.54 Case A2 4098.83 1466.89 Case A3 4008.28 1041.81
  • 5.  ISSN: 2088-8708 IJECE Vol. 7, No. 6, December 2017 : 3114 – 3123 3118 3.2. Electric Field Distribution of Single Porcelain Insulator Based on R. Krishnan study, it has been proven that the insulators do not conduct any current from the current density profile through insulators [13]. Therefore, in this paper, the maximum electric field across the creepage distance of each insulator is taken by placing the contour line on it. Figure 6 shows the colour pattern of electric field distribution for single perfect porcelain insulator and all cases of broken porcelain insulators. From the simulation contour in Figure 6(a), it can be seen that the perfect insulator has the most narrowed equipotential lines of electric field distribution in the region nearest to steel pin. However, the equipotential lines of electric field distribution is increased when the shed of the insulator is broken as shown in Figure 6(b) to Figure 6(d) which is similar to the findings in [14]. Figure 7 illustrates the graphs of electrical field distribution of single porcelain insulator compared with all cases of broken porcelain insulators. Generally, the distribution of electric field for perfect and all broken cases single porcelain insulator presents the similar pattern along the creepage distance. However, there is a slight decrease in the electric filed strength value at beginning before become almost constant in the middle of the contour across insulators and experienced a fast develop at the end for perfect insulator. Contrarily for all broken case where the electric field strength is much higher at the beginning and lower at the end when compared to perfect insulator. (a) (b) (c) (d) Figure 6. Contour of electric field distribution across single insulator for (a) Perfect; (b) Case A1; (c) Case A2; (d) and Case A3 Figure 7. Electrical field distribution of single porcelain insulator compared with all cases of broken porcelain insulators Table 3 shows the maximum and minimum value of electrical field of the four cases of single porcelain insulator. It is appear to indicate that the broken of insulator in the shed nearest to the electrode bears the most effect of electric field distribution across the insulator.
  • 6. IJECE ISSN: 2088-8708  Potential and Electric Field Characteristics of Broken Porcelain Insulator (H. Rosli) 3119 Table 3. The highest and lowest value of electric field Insulator E-Field (kV/cm) Max Min Perfect 3821.07 14.25 Case A1 2210.09 17.32 Case A2 2256.44 12.74 Case A3 2099.28 14.56 Different cases of broken porcelain insulators presented has been concluded that the porcelain insulator with broken shed 3 has the most significant effect on potential and electric field distribution. Therefore, further investigation of the most significant effect of broken porcelain insulator on voltage and electric characteristics were tested on 10 units of insulator strings in different location of the broken insulator which are near the electrode, in the middle, near the ground and alternate position. 3.3. Voltage Distribution across a Porcelain Insulator String Insulator strings with different locations of broken single porcelain insulator were simulated and produced a contour plot of the string with different colour patterns. The colour patterns of the contour indicate the diverse potential value across each insulator in the string [15]. In order to analyse the effect of broken Case A3 on voltage and electric characteristics in a string insulator, four dissimilar configurations are used. Each configuration are assigned as shown in Table 4 for each cases the location of the broken porcelain insulator from Case A3 in the previous section. Table 4. The designation of string insulator with broken porcelain insulator String with 10 units of porcelain insulators Designation No broken porcelain insulator present Perfect Broken porcelain insulator located alternately with perfect insulator B1 Broken porcelain insulator located near HV electrode terminal B2 Broken porcelain insulator located near ground terminal B3 Broken porcelain insulator located in the middle of the string B4 From the simulation contour of Figure 8, it can be observed that perfect insulator string the distribution of potential is gradually decreased from the insulator pin to the insulator cap. However, in the presence of broken insulator in the string, the potential pattern increased in variant with different location of the broken insulator approached to transmission line. Based on the graph, the potential is not uniformly distributed across each insulator. The first insulator that is located at the HV electrode (near the transmission line) bears the highest potential value for all cases. The potential is then decreases in the next insulators along to the ground electrode. Figure 9 shows the potential distribution of 10 units of porcelain insulator in a string. It is obvious from the figure that the voltage distribution is affected when broken insulator exists in the string. This finding is supported by Xiu-chen [16] which concluded that the insulators near the earth are sensitive to the voltage- change of the insulator near the power line, but the latter are not sensitive to that of the frontier. By their analysis, it can be concluded that the sensitivity of string insulator is most affected when broken insulator exist near the ground (earth). According to Azordegan et al. [17], the electromagnetic radiations are stronger at the end of positive cycle for a cracked insulator while the electromagnetic radiations are stronger at the end of negative cycle for a polluted insulator. This supported the observation from the present findings when the potential distribution decreases along the string due to cracks on the porcelain insulator shed. Besides that, the mechanical strength reduction of insulator also causing undesired partial discharges. The lowest average potential value of 50kV was recorded at the B1 case string with 35.06% reduction from the perfect string insulator can be calculated from Figure 9. The graph is then dramatically decrease for all the cases. It can be shown that the potential which should bear by the first insulator have been transferred to the second insulator and so on. Table 5 tabulates the average, maximum and minimum value of voltage across string with 10 units of porcelain insulator in all cases. It is noticed that the average value indicate that the presents of broken insulator in a string affects the voltage across the string insulator. But, the result shows that the B4 case bears the most significant effect on the potential distribution of string with 10 units of porcelain insulator due to the highest reduction value of voltage at the end of the string insulator in ground terminal.
  • 7.  ISSN: 2088-8708 IJECE Vol. 7, No. 6, December 2017 : 3114 – 3123 3120 (a) (b) (c) (d) (e) Figure 8. Potential distribution of string porcelain insulator for (a) Perfect string insulator, (b) B1 string insulator, (c) B2 string insulator, (d) B3 string insulator, and (e) B4 string insulator Figure 9. Potential distribution of all cases of string insulators Table 5. The highest and lowest value of voltage in string insulator String Voltage (kV) Average (kV) Max Min Perfect 116 11 77 B1 86 13 50 B2 88 13 51 B3 84 17 55 B4 86 16 56 3.4. Electric Field Distribution across a Porcelain Insulator String The maximum electric field across the contour distance of each insulator along the string is taken as the strength across each insulator. Figure 10 shows the electric field distribution in string with 10 unit of insulator. It is observed that the present of the broken shed in the insulator has decreased the average electric field distribution in string; this findings is agreed by Shahat [18]. Figure 11 shows the electric field distribution of 10 units of porcelain insulator in a string. From Figure 11, the distribution pattern can be said as similar for all cases of strings. The first insulator that is located nearest to the line for Case B3 has the highest electric field. According to the research lead by Akbari [10], who studied on finite element analysis of disc insulator type and corona ring effect on electric field distribution over 230kV insulator string. They found that as the distance from insulator string increases, the dependency of electric field to insulator material and profile decreases. Apart from that, Anjum [11] has proved that varying the position of the insulator disc
  • 8. IJECE ISSN: 2088-8708  Potential and Electric Field Characteristics of Broken Porcelain Insulator (H. Rosli) 3121 within the string has little or no effect on the level of classification performance. By relating to the conclusion, it has confirmed the similarity patterns in the present findings in Figure 10. In addition, a study conducted by Palhade [19] found that the high temperature produced in current carrying conductor is not enough to transfer over an insulator assembly component during a short period of time. It could be safe to assume that the temperature is not high enough to significantly affect the performance in terms of mechanical and thermal characteristics of an insulator assembly for short duration in this study. Hence, the data obtained from broken porcelain insulators in all cases of string insulator has not been affected much by the temperature of the current. However, in real operation of overhead HV insulators, electrical and mechanical loading, variable atmospheric condition and environmental pollution may degrade the bonding characteristics of cement, even disc material which is basically brittle in nature leading to failure of insulator assembly. (a) (b) (c) (d) (e) Figure 10. Electric field distribution of string porcelain insulator for (a) Perfect string insulator, (b) B1 string insulator, (c) B2 string insulator, (d) B3 string insulator, and (e) B4 string insulator Figure 11. Electric field of broken insulator in string Table 6. The highest and lowest value of electric field in string insulator String Electric Field (kV/cm) Average (kV/cm) Max Min Perfect 1791.2 1.0 313.5 B1 2513.5 1.3 454.4 B2 2510.1 0.8 465.8 B3 2186.3 1.4 488.4 B4 2883.8 1.1 484.2
  • 9.  ISSN: 2088-8708 IJECE Vol. 7, No. 6, December 2017 : 3114 – 3123 3122 Table 6 shows the electric field value in all cases of string insulator with and without broken porcelain insulator. The result shows that highest value of electric field distribution is found in the first insulator in Case B3 based on Figure 11. Meanwhile, highest value of electric field was found in case B4 at the tenth insulator as mentioned in Table 6. 4. CONCLUSION This paper set out to explore the influence of broken shed in porcelain insulator in terms of voltage and electrical characteristics. From the results obtained, a few conclusions had been made concerning the purpose of this investigation. 1. The single porcelain insulator denoted a bulk reduction of voltage and electric field when the broken of the shed in the insulator was near the electrode. 2. In HV string insulator with 10 units of porcelain insulator, the potential distribution experienced the most diminutive value when the broken porcelain insulator were located in the string near the ground. In addition, the potential distribution average were the least when the broken and perfect insulator were arranged alternately in the string. 3. Consequently, the investigation of electric field distribution has shown that a hulking strength of average when the broken insulator was ascertain near the ground when assimilated to the string insulator without any broken insulator. ACKNOWLEDGEMENTS The authors express their sincere gratitude to Universiti Tun Hussein Onn Malaysia (UTHM) for the use of facilities and equipment supports. REFERENCES [1] Masoud F, Shahab F, and William C, Electrical Design of Overhead Power Transmission Lines: McGraw-Hill Professional, 2012. [2] Sims S, “High-voltage Overhead Transmission Lines (HVOTLs) and House Prices,” Towers, Turbines Transm. Lines Impacts Prop. Value, pp. 45–53, 2013. [3] Gencoglu M. T, “The Comparison of Ceramic and Non-Ceramic Insulators,” E-Journal of New World Sciences Academy, vol 2, no 4, pp. 274–294, 2007. [4] “A Review of Insulator Failure Modes.” [Online]. Available: http://www.inmr.com/review-insulator-failure- modes/. [5] George J, Prat S, Tartier S, and Lodi Z, "Electrical characteristics and properties of a stub (damaged toughened glass insulator)," in 18th Int. Symp. High Voltage Insulator Seoul, Korea, 2013. [6] Munz D and Fett T, “Ceramics: mechanical properties, failure behaviour, materials selection,” Springer Science & Business Media, vol. 36, 2013. [7] Mathis H. A, “Technical Article,” Shock Vib. Dig., vol. 25, no. 6, pp. 10–14, 1993. [8] “Catalog No. 8255, Suspension Insulators Ball and socket type” Gamma Insulators Corp., United States. [9] “Disc insulator-QuickField FEA Software,” [Online]. Available: http://www.quickfield.com/advanced/insulator.htm. [Accessed: October, 2016] [10] Rahimnejad A, Asadpoor M. B, Akbari E, and Mirzaie M, “Finite Element Analysis of Disc Insulator Type and Corona Ring Effect on Electric Field Distribution over 230-kV Insulator Strings,” Iranian Journal of Electrical & Electronic Engineering, vol. 9, no. 1, March 2013. [11] Anjum S, "A Study of the Detection of Defects in Ceramic Insulators Based on Radio Frequency Signatures," UWSpace, 2014. [12] Shinohara A. H, et al, "Defects detection in electrical insulators and breaker for high voltage by low cost computed radiography systems," International Symposium on Digital industrial Radiology and Computed Tomography. Lyon, France. 2007. [13] R. Krishnan, S. Samanta, R. Sudha, and K. Govardhan, “Electric Field Analysis of High Voltage Insulators,” pp. 31–35, 2012. [14] Razali M. H, “Electric Field Modeling of Outdoor Insulator for Optimized Performance,” Master dissertation. Universiti Tun Hussein Onn, Malaysia, 2014. [15] F. Hanani et al., “Analysis of Potential Distribution of a Glass Insulators String with Different Number of Broken Units,” Bachelor dissertation. Universiti Teknologi Malaysia, 2015. [16] Xue L.L and Chen J. X, “Detection Methods of the Faulty Porcelain Insulators,” Proceedings of the 2006 IASME/WSEAS International Conference on Energy & Environmental Systems, Chalkida, Greece, pp. 333-342, 2006. [17] E. Azordegan, B. Kordi, and D. R. Swatek, “Radiated electromagnetic field signature of faulty and polluted porcelain insulators,” 2010 Int. Conf. High Volt. Eng. Appl. ICHVE 2010, pp. 449–452, 2010.
  • 10. IJECE ISSN: 2088-8708  Potential and Electric Field Characteristics of Broken Porcelain Insulator (H. Rosli) 3123 [18] M. El-shahat and H. Anis, “Risk assessment of desert pollution on composite high voltage insulators,” J. Adv. Res., vol. 5, no. 5, pp. 569–576, 2014. [19] R. D. Palhade, V. B. Tungikar, G. M. Dhole, and S. M. Kherde, “Transient Thermal Conduction Analysis of High Voltage Cap and Pin Type Ceramic Disc Insulator Assembly,” Int. J. Adv. Sci. Technol., vol. 56, pp. 73–86, 2013. BIOGRAPHIES OF AUTHORS Hanan Rosli was born and raised in Sungai Petani, Kedah, Malaysia on January 24, 1994. After completing high school in MARA Junior Science College (MJSC) Kepala Batas (2011), she went to Kedah Matriculation College for a year and pursue her study in Bachelor of Electrical Engineering (Hons) in UTHM, Johor (2017). Her research interest is more focus in high voltage insulation field. Nordiana Azlin Othman was born in Johor, Malaysia on January 19, 1986. She received Diploma in Electrical Communication and B.Eng in Electrical Engineering from Universiti Teknologi Malaysia (UTM) respectively in 2007 and 2010. She completed her PhD in Space Charge Distirbution at Institute of High Voltage and High Current (IVAT) in Faculty of Electrical Engineering, UTM. Her research interest includes the detection and diagnostics of partial discharge and space charge in insulation for condition monitoring. Nor Akmal Mohd Jamail is a lecturer of Universiti Tun Hussein Onn Malaysia since 2008. She received the Bachelor degree in Electrical Engineering from Universiti Teknologi Malaysia in 2005, M.Eng in Power System from Universiti Tun Hussein Onn Malaysia in 2007 and Ph.D. in High Voltage Engineering from Universiti Teknologi Malaysia, in 2015. Her research interests include condition monitoring of polymer nanocomposite insulation for HV purpose, dielectrics and electrical insulation. She is registered with the Board of Engineers Malaysia (BEM). Muhammad Nafis Ismail was born on 1982 in Johor, Malaysia. He received B.Eng in Electrical Engineering fron Universiti Teknologi Malaysia (UTM) in 2005. He previously worked as an Electrical Engineer at BQE Engineering from 2005 to 2007 and currently work as an Electrical Instructor at University Tun Hussein Onn Malaysia.