Electric Field Analysis and Impact Study with Shrubbery on the 11 kV
Distribution System fed by a 132 kV/220 kV Transmission Feeder
Dr. T. Murali Mohan1, B. Chinni2
1Professor, Dept. of Electrical and Electronics Engineering, UCEK, JNTU Kakinada, India
2M. Tech, Dept. of Electrical and Electronics Engineering, UCEK, JNTU Kakinada, India
----------------------------------------------------------------------***---------------------------------------------------------------------
Abstract - In this paper impact of vegetation growth in
rural distribution net networks is studied in FEM-2D
software. The impact of vegetation growth, along with the
Transmission & The model, utilizes parameters of an 11kV,
three-phase distribution feeder, PCC poles, metallic cross-
arms, and 160kN pin insulators. A pole span of 100 meters is
considered for subject simulation. In this paper, a second
case scenario regarding the Electric field analysis on 132kv
transmission line tower and 220kv transmission line tower
is studied in FEM-2D software. The FEM-based simulation
and study indicate an increase in electrical field stresses for
vegetation in the vicinity of the line.
Key Words: Vegetation, Pin Insulator, Polymeric Insulator
132 kV Transmission Tower, 220kV Transmission Tower,
FEM (Finite Element Method).
1. INTRODUCTION:
In the latest days, there has been a significant
increase in the electricity demand. To fulfill this demand,
switchgear, transmission, and distribution networks must
be done more efficiently. The effectiveness of any system
is primarily determined by the continuity of service while
avoiding faults. The performance and properties of
insulators must be good to ensure continuity. Ceramic
insulators have long been utilized in power transmission
and distribution systems. In nowadays ceramic insulator
has been slowly replaced by composite insulator in power
grid nowadays. However, flashover fault still occurs on
this insulator type. Under certain conditions, partial
discharges may occur on the insulator and lead to a
complete flashover. The flashover can cause a breakdown
and damage the whole power system. Compared to
porcelain suspension insulators, composite insulators
have many advantages, such as being lightweight, higher
mechanical strength to weight ratio, higher resistance to
vandalism, better performance in the presence of heavy
pollution in wet conditions and better withstand voltage.
Therefore, outdoor composite insulators are now
preferable and widely used in maintaining the reliability of
the power system. With the increase of demand and the
use of composite insulators, factors of the occurrence of
the fault have drawn wider attention.
Transmission and distribution of power are
accomplished using overhead lines and UG Cables. In OH
lines, metallic and non-metallic structures are used for
supporting insulation (string or pin insulators) and the
conductors. For capital costs involved, the use of strong
metallic structures is restricted to high and ultra-high
voltage transmission systems. Whereas, for most, medium
voltage power distribution systems wooden, cement
structures, or poles are recommended. It is worth noting
that both wooden and cement poles not only provide
requisite mechanical support, they also minimize charge
leakage from the conductor, for their higher specific
resistance. In the case of T&D systems, this neighborhood
rendered by the metallic tower/ pole structure, the guard
wire, and most importantly by the vegetation and creepers
in the vicinity of T&D systems.
This project, model utilizes parameters of an
11kV, three-phase distribution feeder, PCC poles, metallic
cross-arms, and, 160kN pin insulators. A pole span of 100
meters is considered for subject simulation. The
simulation is carried out using the FEM model for an 11kV,
3-φ distribution feeder, PCC poles, metallic cross arms,
and 160kN pin insulators. A pole span of 100 meters is
considered for subject simulation for four different
configurations. The power losses are aggregated for a line
length of 10km [1]. In this paper, a second case scenario
regarding the Electric field analysis on 132kv transmission
line tower and 220kv transmission line tower is studied in
FEM-2D software [2]-[3]. The FEM-based simulation and
study indicate an increase in electrical field stresses for
vegetation in the vicinity of the line.[1]
2. IMPACT OF VEGETATION GROWTH IN 11KV
DISTRIBUTION NETWORK:
The analysis has been carried out using FEMM
software. FEMM is a FEFEM-based simulation tool. The
distribution system chosen is a rural section fed by a
33/11kV Shanthi Nagar substation in the Kakinada district
of Andhra Pradesh State, India. The section consists of
cement poles and cross-arms, the AutoCAD design is
shown in Figure.1. Vegetation like trees, bushes, and
creepers are found to grow during rainy seasons. The
growth if abundant can reach alarming heights
endangering short circuits. Such developments are
modeled and resulting variations in electric field
intensities, effective line capacity, once, and leakage
current are studied. The results are compared with the
standard line without such intrusion. The power and
energy losses and additional line loading are determined
and shown as the additional burden on distribution utility
[1].
International Research Journal of Engineering and Technology (IRJET) e-ISSN: 2395-0056
Volume: 09 Issue: 02 | Feb 2022 www.irjet.net p-ISSN: 2395-0072
© 2022, IRJET | Impact Factor value: 7.529 | ISO 9001:2008 Certified Journal | Page 765
TABLE 1: Dimension of Electric pole
S.no Particulars Length(mm)
1. 1. Electric pole height 12500
2. 2. Width 300
Fig-1:11kV distribution line cross arm design
Thus, the Simulation includes the following two
cases:
Case1. A Clean distribution line
Case2. Unclean distribution line
2.1. FEM Simulation Analysis:
The analysis was carried out for all the two
conditions and was discussed below.
2.2. Case1: A Clean distribution Line:
The 11kV, three-phase distribution feeder,
metallic cross arms, and pin insulator were designed by
using FEMM 2D software as per geometrical
conFigurations shown in Fig 2.[9] The electric field
distribution in and around the insulator is necessary for
the optimal design of the insulator. The accurate
computation of electric field distribution can be computed
using the Finite element method (FEM). For this insulator,
dimensions are very useful. 11kv Electric pole dimensions
are shown in Fig 1 and Table1.
Fig-2:11kV pin insulator
Geometrical configurations 11kv pin insulator
dimensions are shown in Fig 2. 11kv pin insulator design
in FEM 2D software [9].
2.2.1. ASSIGNING MATERIALS:
As per the geometrical configurations, the
insulator is designed by using FEMM 2D package. After
designing, insulator materials like ceramic, steel, and air
are assigned to the model with help of relative permittivity
values. Insulator material properties are given in the table
shown Table 2 and Fig2. After assigning materials to the
model, the line to the ground voltage (i.e.,12/√3 =7kv) is
applied to the energized high voltage end fitting and zero
(0V) volts to the grounded end fitting of the insulator.
TABLE 2: Material properties
Particulars Material Relative
permittivity
value
Insulator
housing
Ceramic 5.9
Electric pole Steel 1
Boundary
surface
Air 1
2.2.2. ASSIGNING 2D TRIANGULAR ELEMENTS:
Then 2D Triangular elements are assigned to the
insulator. Triangular elements at the HV end and ground
end are as shown in Fig 2. The boundaries in the model
need to be split into individual sections, referred to as
boundary elements. The distribution, number, and shape
of these elements are the key factors that determine the
accuracy of the solution. FEM generally uses 2D elements
for analysis purposes. Names of Insulator 1 and Insulator
2 and Insulator 3 are shown in Fig 2.
International Research Journal of Engineering and Technology (IRJET) e-ISSN: 2395-0056
Volume: 09 Issue: 02 | Feb 2022 www.irjet.net p-ISSN: 2395-0072
© 2022, IRJET | Impact Factor value: 7.529 | ISO 9001:2008 Certified Journal | Page 766
2.2.3. ASSIGNING BOUNDARY CONDITIONS:
After assigning boundary elements 2D triangular
elements are generated throughout the mode. A FEM
model design for the clean distribution assuming that no
tree/creeper is surrounding the pole. The results are
showing that the stress is now varied between the top of
the tree to the transmission line by treating the tree as the
ground is as shown in Fig.3.By running the model electric
field contours developed. In this electric field contours, the
HV end is shown red color and the ground end is shown
blue color.
The rated line-to-ground voltage is 12/√3=7kV to
the high voltage end fittings. Zero volts to the grounded
end fitting/Air is assigned as a surrounding medium. After
assigning boundary elements 2D triangular elements are
generated throughout the mode.
Fig-3: Electric field contours
Electric field contours are as shown in Fig 3. After
assigning materials to the model, the line to the ground
voltage (i.e 12/√3 =7kv) is applied to the energized high
voltage end fitting and zero (0V) volts to the grounded end
fitting of the insulator. Field analysis results of 11kv
electric pole with cross-arm. Electric fields along the
insulators are plotted. By running the model electric field
contours developed. In this electric field contours, the HV
end is shown red color and the ground end is shown blue
color The insulator top is given as high voltage and the
insulator ground is given ground voltage. The Fig. 3 shows
different colors in which each color corresponds to a
different voltage level.
In the Fig. 4, a graph is plotted between the
voltage across insulator and the length of insulator(mm).
This Fig. 4 is also known as Voltage Distribution along
insulator length.
Fig-4: Voltage Distribution along the insulator
In Fig. 5, the Electric field Distribution along
insulator1 has been presented. Maximum Electric field
Distribution along insulator 1 is 8.53×e4 V/mm.
Fig-5: Electric field Distribution along insulator 1
In this Fig6 graph drawn between Electric field
intensity vs length of insulator(mm). The maximum
Electric field Distribution along insulator 2 is 7.67×e4
(v/mm).
International Research Journal of Engineering and Technology (IRJET) e-ISSN: 2395-0056
Volume: 09 Issue: 02 | Feb 2022 www.irjet.net p-ISSN: 2395-0072
© 2022, IRJET | Impact Factor value: 7.529 | ISO 9001:2008 Certified Journal | Page 767
Fig-6: Electric field Distribution along insulator 2
In this Fig7 graph is drawn between Electric field
intensity vs length of insulator(mm). Maximum Electric
field Distribution along insulator3 is 2.47×e5 (v/mm).
Fig-7: Electric field Distribution along insulator3
Table 3: Electric Field analysis Results
S.NO FIELD REGION ELECTRIC FIELD
INTENSTY(V/mm)
1. Insulator1 8.53×e4
2. Insulator2 7.67×e4
3. Insulator3 2.47×e4
The maximum Electric field intensity on the
surface of insulator 1, insulator 2 and insulator 3 are
presented in Table 3.
The comparison bar chart of EFA results for 11kv
electric pole with clean distribution is shown in Fig 8.
Fig-8: Electric field Results analysis
2.3. Case2. For Unclean Distribution Line:
The 11kV, three-phase distribution feeder, metallic
cross arms and pin insulator was designed by using FEMM
2D software as per geometrical configurations shown in
Fig 1. The geometrical configurations 11kv pin insulator
dimensions are shown in Fig 2.
If the vegetation growth increased in steps of 10%
from 40% to 100%, the electric field was found to be
increasing.
 Tree height increased 40% of the total height of
electric pole height = 4 m.
 Tree height increased 50% of the total height of
electric pole height = 5 m.
 Tree height increased 60% of the total height of
electric pole height = 6 m.
 Tree height increased 70% of the total height of
electric pole height = 7 m.
 Tree height increased 80% of the total height of
electric pole height = 8 m.
 Tree height increased 90% of the total height of
electric pole height = 9 m.
 Tree height increased 100% of the total height of
electric pole height = 10 m.
A FEM model design for the clean distribution
assuming that no tree/creeper is surrounding the pole has
been already presented in section 2.2. For a 50% grown
tree/shrubbery, analysis has been primarily carried out in
the FEM model. The results are showing that the stress is
now varied between the top of the tree to the transmission
line by treating the tree as the ground. is as shown in Fig. 9
i.e., the ground plane has increased increasing the electric
field stress [1].
International Research Journal of Engineering and Technology (IRJET) e-ISSN: 2395-0056
Volume: 09 Issue: 02 | Feb 2022 www.irjet.net p-ISSN: 2395-0072
© 2022, IRJET | Impact Factor value: 7.529 | ISO 9001:2008 Certified Journal | Page 768
Fig-9: Electric field contours
Electric field contours are as shown in Fig 9. After
assigning materials to the model, the line to the ground
voltage (i.e 12/√3 =7kv) is applied to the energized high
voltage end fitting and zero (0V) volts to the grounded end
fitting of the insulator. Field analysis results of 11kv
electric pole with cross arm. Electric fields along the
insulators are plotted. By running the model electric field
contours developed. In this electric field contours, the HV
end is shown red color and the ground end is shown blue
color. The insulator top is given as high voltage and the
insulator ground is given ground voltage. In this Fig 9
shows different colors corresponds to its voltage intensity.
Fig-10: Voltage Distribution along insulator1
If the vegetation growth increased in steps of 10%
from 40% to 100%, the electric field was found to be
increasing.
a. Electric field Distribution along insulator2 with
40% of tree height increase
In the Fig10.1, the graph is drawn between Electric
field intensity vs length of insulator(mm). Maximum
Electric field Distribution along insulator 2 with 40% of
tree height increase is 7.75×e4 (v/mm).
Fig-10.1: Electric field Distribution along insulator 2
with 40 % Tree height
b. Electric field Distribution along insulator2 with
50% of tree height increase:
In the Fig 10.2, the graph is drawn between
Electric field intensity vs length of insulator(mm).
Maximum Electric field Distribution along insulator2 with
50% of tree height increase is 7.80×e4 (v/mm).
Fig-10.2: Electric field Distribution along insulator 2
with 50 % Tree Height
c. Electric field Distribution along insulator2 with
60% of tree height increase:
In this Fig10.3 graph drawn between Electric field
intensity vs length of insulator(mm). Maximum Electric
field Distribution along insulator2 with 60% of tree height
increase is 7.90×e4 (v/mm).
International Research Journal of Engineering and Technology (IRJET) e-ISSN: 2395-0056
Volume: 09 Issue: 02 | Feb 2022 www.irjet.net p-ISSN: 2395-0072
© 2022, IRJET | Impact Factor value: 7.529 | ISO 9001:2008 Certified Journal | Page 769
Fig-10.3. Electric field Distribution along insulator 2
with 60 % Tree Height
d. Electric field Distribution along insulator2 with
70% of tree height increase:
In the Fig10.4 graph drawn between Electric field
intensity vs length of insulator(mm). Maximum Electric
field Distribution along insulator2 with 70% of tree height
increase is 8.00×e4 (v/mm).
Fig-10.4: Electric field Distribution along insulator 2
with 70 % Tree Height
e. Electric field Distribution along insulator2 with
80% of Tree height increase:
In this Fig10.5 graph is drawn between Electric
field intensity vs length of insulator(mm). Maximum
Electric field Distribution along insulator 2 with 80% of
tree height increase is 8.04×e4 (v/mm).
Fig-10.5: Electric field Distribution along insulator-2
with 80 % Tree Height
f. Electric field Distribution along insulator2 with
90% of tree height increase:
The Maximum Electric Field Distribution along
insulator2 with 90% of tree height increase is 8.20×e4
(v/mm) as shown in Fig. 10.6.
Fig-10.6: Electric field Distribution along insulator 2
with 90 % Tree Height
g. Electric field Distribution along insulator2 with
100% of tree height increase:
Maximum Electric field Distribution along insulator2
with 100% of tree height increase is 8.40×e4 (V/mm) as
shown in Fig. 10.7.
Fig-10.7: Electric field Distribution along insulator 2
with 100 % Tree Height.
International Research Journal of Engineering and Technology (IRJET) e-ISSN: 2395-0056
Volume: 09 Issue: 02 | Feb 2022 www.irjet.net p-ISSN: 2395-0072
© 2022, IRJET | Impact Factor value: 7.529 | ISO 9001:2008 Certified Journal | Page 770
Table 4: Electric Field Intensity (vs) Percentage
Increasing tree height (%)
S.NO Percentage
Increasing tree
height
ELECTRIC FIELD
INTENSTY(V/mm)
1 40% 7.75×e4
2 50% 7.80×e4
3 60% 7.90×e4
4 70% 8.00×e4
5 80% 8.04×e4
6 90% 8.20×e4
7. 100% 8.40×e4
The comparison of EFA results for 11kv electric
pole for various tree heights is presented in Fig 11.
Fig-11: Electric Field Results Analysis
3. Electric field analysis of 132kv Overhead
transmission line tower (Case-3):
In this case 3, the electric field distributions and
voltage in 132kv overhead transmission line tower
studied Fem 2D software. 132kv overhead transmission
line tower with polymeric was designed by using Fem 2D
software as per geometrical configuration shown in table
5 and Fig 12.
3.1. Geometrical Configurations:
The electric field distribution in and around the
insulator is necessary for the optimal design of the
insulator. The accurate computation of electric field
distribution can be computed using the Finite element
method (FEM). For this insulator, dimensions are very
useful. Insulator dimensions are tabulated in table 5.
Fig- 12: Geometric Configuration of the Tower
Table 5: Geometrical ConFigurations-132kV polymeric
insulator
S.no Critical Regions Dimensions in
mm
1. Insualtor length 1060
2. Diameter of bigger shed 135
3. Diameter of smaller shed 105
4. FRP Rod length 960
5. Core Diameter 28
6. No Discs bigger shed 17
7. No Discs smaller shed 16
8. Pitch 52
9. FRP diameter 20
10. Thickness shed 3
3.2. Design of 132kV Overhead transmission line
tower:
In this case3, the electric field distributions and
voltage in 132kv overhead transmission line tower
studied Fem 2d software.132kv overhead transmission
line tower with polymeric was designed by using Fem 2d
software as per geometrical configuration shown in Fig12.
3.3. ASSIGNING MATERIALS:
As per the geometrical configurations, the insulator
is designed by using FEMM 2D package. After designing,
insulator materials like SiR, FRP, and steel are assigned to
the model with help of relative permittivity values.
Insulator material properties are given in the table shown
table 6.
International Research Journal of Engineering and Technology (IRJET) e-ISSN: 2395-0056
Volume: 09 Issue: 02 | Feb 2022 www.irjet.net p-ISSN: 2395-0072
© 2022, IRJET | Impact Factor value: 7.529 | ISO 9001:2008 Certified Journal | Page 771
Table 6: Material properties
Particulars Material Relative
permittivity
value
Insulator housing
and weather sheds
Silicone 3
FRP Rod Fibre glass 5
Tower Steel 1
Boundary surface Air 1
The rated line-to-ground voltage as
145/√3=83.71kV to the high voltage end fitting. Zero volts
to the grounded end fitting. Air is assigned as a
surrounding medium.
Fig-13: Electric field contours
Then 2D triangular elements are assigned to the
insulator. Electric field contours are as shown in Fig 13. By
running the model electric field contours developed. In
this electric field contours HV, the end is shown red color,
and the ground end is shown blur color. The insulator top
is given as high voltage and the insulator ground is given
ground voltage. In this Fig 13 shows different colors &
each color shows different voltages.132Kv overhead
transmission line bottom of the tower is grounded shown
blue color in Fig13.
3.4. ELECTRIC FIELD DISTRIBUTION ALONG
INSULATOR:
Fig-14: Electric field Distribution along Insulator1
Electric field distribution along the surface of
insulator1 is shown in Fig 18. The rated line-to-ground
voltage as 145/√3=83.71kV to the high voltage end fitting.
Zero volts to the grounded end fitting/Air is assigned as a
surrounding medium. Electric field distribution along the
surface of insulator1 is shown in Fig 14. 132Kv overhead
transmission tower is grounded shown blue color in Fig
14.
3.5. ELECTRIC FIELD LINES DIRECTION:
Fig-15: Electric field lines direction
International Research Journal of Engineering and Technology (IRJET) e-ISSN: 2395-0056
Volume: 09 Issue: 02 | Feb 2022 www.irjet.net p-ISSN: 2395-0072
© 2022, IRJET | Impact Factor value: 7.529 | ISO 9001:2008 Certified Journal | Page 772
Electric field lines direction shown in Fig 15. This
Figure shows Electric field lines flow from hv end to
ground end.
3.6. EQUIPOTENTIAL LINES:
Fig-16: Equipotential lines direction
Equipotential lines direction shown in Fig 16.
This, the Figure shows Equipotential lines flow from hv
end to ground end
3.7. VOLTAGE DISTRIBUTION ALONG INSULATOR1:
Fig-17.1: Voltage Distribution along insulator1
In this Fig17.1 graph drawn between voltage vs
length of insulator(mm). Maximum Voltage Distribution
along insulator3 is 8.00×e4 (v/mm).
3.8. VOLTAGE DISTRIBUTION ALONG INSULATOR2
In the Fig17.2 graph drawn between voltage vs length of
insulator(mm). Maximum Voltage Distribution along
insulator3 is 8.26×e4 (v/mm).
Fig-17.2: Voltage Distribution along insulator2
3.9. VOLTAGE DISTRIBUTION ALONG INSULATOR3:
Fig-17.3: Voltage Distribution along insulator3
Maximum Voltage Distribution along insulator3 is
8.26×e4 (v/mm). In this Fig17.3 graph drawn between
voltage vs length of insulator(mm).
3.10. ELECTRIC FIELD DISTRIBUTION ALONG
INSULATOR1
Maximum Electric field Distribution along insulator1 is
1.74×e5 (v/mm). In this Fig18 graph drawn between
Electric field intensity vs length of insulator(mm).
International Research Journal of Engineering and Technology (IRJET) e-ISSN: 2395-0056
Volume: 09 Issue: 02 | Feb 2022 www.irjet.net p-ISSN: 2395-0072
© 2022, IRJET | Impact Factor value: 7.529 | ISO 9001:2008 Certified Journal | Page 773
Fig-18: Electric field Distribution along insulator1
3.11. ELECTRIC FIELD DISTRIBUTION ALONG
INSULATOR2:
Maximum Electric field Distribution along
insulator2 is 2.28×e5 (v/mm). In this Fig. 19 graph drawn
between Electric field intensity vs length of
insulator(mm).
Fig-19: Electric field Distribution along insulator2
3.12. ELECTRIC FIELD DISTRIBUTION ALONG
INSULATOR 3:
Fig-20: Electric field Distribution along insulator3
Maximum Electric field Distribution along
insulator3 is 2.47×e5 (v/mm). In this Fig20 graph drawn
between Electric field intensity vs length of
insulator(mm).
EFA results for 132kV overhead transmission line
tower insulator1, insulator2 & insualtor3 are shown in
table 7.
Table 7: EFA results for 132kV overhead transmission
line tower
S.NO FIELD REGION ELECTRIC FIELD
INTENSTY (V/mm)
1. Insulator1 1.74×e5
2. Insulator2 2.28×e5
3. Insulator3 2.47×e5
Table 8: Voltage results for 132kV overhead
transmission line tower
S.NO FIELD REGION VOLTAGE (Volt)
1. Insulator1 8.00×e4
2. Insulator2 8.26e4
3. Insulator3 8.26×e4
3.13. EFA RESULTS COMPARISION:
Fig-21: Electric Field Results Analysis
3.14. VOLTAGE RESULTS COMPARISION:
Fig-22: Voltage Results Analysis
International Research Journal of Engineering and Technology (IRJET) e-ISSN: 2395-0056
Volume: 09 Issue: 02 | Feb 2022 www.irjet.net p-ISSN: 2395-0072
© 2022, IRJET | Impact Factor value: 7.529 | ISO 9001:2008 Certified Journal | Page 774
4. Electric field analysis of 220kv Overhead
transmission line tower (Case - 4):
In this case4, the electric field distributions and
voltage in 220 kV overhead transmission line tower
studied Fem 2d software.220kv overhead transmission
line tower with polymeric was designed by using Fem 2d
software as per geometrical configuration shown in Fig23.
4.1. Geometrical Configurations:
The electric field distribution in and around the
insulator is necessary for the optimal design of the
insulator. The accurate computation of electric field
distribution can be computed using the Finite element
method (FEM). For this insulator, dimensions are very
useful. Insulator dimensions are tabulated in table 9 and
Fig 23.
Fig-23: Geometric Configuration of the 220 kV Tower
Table 9: Geometrical ConFigurations-220kV polymeric
insulator
S.no Critical Regions Dimensions
in mm
1. 1. Insualtor length 2200
2. 2. Diameter of bigger shed 135
3. 3. Diameter of smaller shed 105
4. 4. FRP Rod length 2100
5. 5. Core Diameter 26
6. 6. No Discs bigger shed 46
7. 7. No Discs smaller shed 45
8. 8. Pitch 52
9. FRP diameter 20
10. Thickness shed 3
4.1.1. ASSIGNING MATERIALS
As per the geometrical configurations, the
insulator is designed by using FEMM 2D package. After
designing, insulator materials like SiR, FRP, and steel are
assigned to the model with help of relative permittivity
values. Insulator material properties are given in the
table8.
4.2. ASSIGNING 2D TRIANGULAR ELEMENTS:
The boundaries in the model need to be split into
individual sections, referred to as boundary elements.
The distribution, number, and shape of these
elements are the key factors that determine the accuracy
of the solution. FEM generally uses 2D elements for
analysis purpose purposes.
4.3. ASSIGNING BOUNDARY CONDITIONS:
The rated line-to-ground voltage is
220/√3=142kV to the high voltage end fittings. Zero volts
to the grounded end fitting/Air is assigned as a
surrounding medium. After assigning boundary elements
2D triangular elements are generated throughout the
mode.
In this electric field contours HV, the end is shown
red color, and the ground end is shown blue color. The
insulator top is given as high voltage and the insulator
ground is given ground voltage. In this Fig 9 shows
different colors.
Each colors shows different voltages shown in
Fig24. 220Kv overhead transmission line bottom of the
tower is grounded shown blue color in Fig24.
4.4. Electric field contours:
Fig-24: Electric field contours
International Research Journal of Engineering and Technology (IRJET) e-ISSN: 2395-0056
Volume: 09 Issue: 02 | Feb 2022 www.irjet.net p-ISSN: 2395-0072
© 2022, IRJET | Impact Factor value: 7.529 | ISO 9001:2008 Certified Journal | Page 775
4.5. ELECTRIC FIELD DISTRIBUTION ALONG
INSULATOR1:
Fig-25: Electric field Distribution along insulator1
Electric field Distribution along the surface of
insulator1 is shown in Fig 25. The rated line-to-ground
voltage is 220/√3=142kV to the high voltage end fittin.
Zero volts to the grounded end fittingAir is assigned as a
surrounding medium.
4.6. VOLTAGE DISTRIBUTION ALONG
INSULATOR1:
Fig-26.1: Voltage Distribution along insulator1
Maximum Voltage Distribution along insulator1 is
2.56×e5 (v/mm). In this Fig26.1 graph drawn between
voltage vs length of insulator(mm).
4.7. VOLTAGE DISTRIBUTION ALONG INSULATOR2
Fig-26.2: Voltage Distribution along insulator2
Maximum Voltage Distribution along insulator2 is
2.56×e5 (v/mm). In this Fig26.2 graph drawn between
voltage vs length of insulator(mm).
4.8. VOLTAGE DISTRIBUTION ALONG
INSULATOR3:
Fig-26.3: Voltage Distribution along insulator3
Maximum Voltage Distribution along insulator3 is
2.56×e5 (v/mm). In this Fig26.3 graph drawn between
voltage vs length of insulator(mm).
4.9. ELECTRIC FIELD DISTRIBUTION ALONG
INSULATOR1
Fig-27.1: Electric field Distribution along insulator1
International Research Journal of Engineering and Technology (IRJET) e-ISSN: 2395-0056
Volume: 09 Issue: 02 | Feb 2022 www.irjet.net p-ISSN: 2395-0072
© 2022, IRJET | Impact Factor value: 7.529 | ISO 9001:2008 Certified Journal | Page 776
Maximum Electric field Distribution along
insulator1 is 2.49×e5 (v/mm). In this Fig27.1 graph is
drawn between Electric field intensity vs length of
insulator(mm).
4.10. ELECTRIC FIELD DISTRIBUTION ALONG
INSULATOR 2:
Fig-27.2: Electric field Distribution along insulator2
Maximum Electric field Distribution along
insulator2 is 2.56×e5 (v/mm). In this Fig27.2 graph drawn
between Electric field intensity vs length of
insulator(mm).
4.11. ELECTRIC FIELD DISTRIBUTION ALONG
INSULATOR3:
Fig-27.3: Electric field Distribution along insulator3
From Fig. 27.3, the Maximum Electric field
Distribution along insulator3 is 2.90×e5 (v/mm).
Table 11: EFA results for 220 kV overhead
transmission line tower
S.NO FIELD REGION ELECTRIC FIELD
INTENSTY (V/mm)
1. Insulator1 2.49×e5
2. Insulator2 2.56×e5
3. Insulator3 2.90×e5
Table 12: Voltage results for 220 kV overhead
transmission line tower
S.NO FIELD REGION VOLTAGE (Volt)
1. Insulator1 1.30×e5
2. Insulator2 1.33×e5
3. Insulator3 1.33×e5
4.12. EFA RESULTS COMPARISION:
Fig-28: Electric Field Results Analysis
4.13. VOLTAGE RESULTS COMPARISON:
Fig-29: Voltage Results Analysis
5. CONCLUSION:
In this project, an electric field Analysis has been
carried out and an 11 kV Distribution system. To enhance
the study, three 11kv insulators are chosen and tests are
conducted under clean and unclean environments. Later
on, the study is extended to include the effects of
shrubbery, we have chosen different levels of tree heights
concerning the pole heights. The effectiveness of these
analyses is proven by taking 132 kV and 220 kV feeders
that are powering our 11 kV distribution system. By series
of tests, it is confirmed that the shrubbery has the least
effect on the Extra High voltage transmission systems due
to their humungous tower heights. Thus the study is
constricted to 11 kV system Electric field distribution
under four cases. By comparison, case1 and case 2 results
in electric field stress more in case2.
International Research Journal of Engineering and Technology (IRJET) e-ISSN: 2395-0056
Volume: 09 Issue: 02 | Feb 2022 www.irjet.net p-ISSN: 2395-0072
© 2022, IRJET | Impact Factor value: 7.529 | ISO 9001:2008 Certified Journal | Page 777
In the case2 of the electric field fields, stress
increases with increasing vegetation growth. In case2
vegetation growth is 10% electric field stress is less. If the
vegetation growth increased in steps of 10% from 40% to
100%, the electric field was found to be increasing. At
vegetation growth of 100% pole height, the electric field
stresses are very high. In case 3, three insulators of the
same ratings are compared. The electric field stress is high
in insulator3 compared to insulator 1 and insulator 2. In
case 4 electric field stress is high in insulator3 compared
to insualtor1 and insulator 2.
From this testing and simulation of electric field
analysis, it is found that electric field stress is different
even for insulators of the same rating and manufacturers.
It is also affected by shrubbery and its height compared to
pole height. From these tests, it is confirmed that
shrubbery is a minor player in electric field stress of 132
kV and greater voltages due to high tower heights. Its
effects are high for distribution systems of voltage 11 kV
and under as their cross arms may be accessible near
shrubbery.
REFERENCES
[1]S.Devabhaktuni, H. Shankar Jain and P. K. Vujjin,
"Impact of Shrubbery in Rural Transmission and
Distribution Networks," 2017 IEEE International
Conference on Computational Intelligence and Computing
Research (ICCIC), 2017, pp. 1-5, DOI DOI:
10.1109/ICCIC.2017.8524259.
[2]Rao, M. Nageswara, V. S. N. K. Chaitanya, and P. Vijaya
Haritha. "Study of Hydrophobicity Effect on 220kV Double
Tension Insulator String Surface Using Finite Element
Method." International Journal of Electronics and
Communication Engineering 14, no. 3 (2020): 70-75.
[3]Supriya Khedkar, Shilpa Kewate, Sneha Hirkane
“Analysis and Design of 220kV transmission line tower
with hot rolled and cold-formed cold-formed section”
Volume 6, Issue 12, December-2015
[4]Z. G. Datsios, P. N. Mikropoulos, T. E. Tsovilis, V. T.
Karakostas, and S. P. Mavidou “ESTIMATION OF THE
MINIMUM BACKFLASHOVER CURRENT OF 150 AND 400
kV OVERHEAD TRANSMISSION LINES THROUGH ATP-
EMTP SIMULATIONS: EFFECT OF THE LIGHTNING
STROKE LOCATION ALONG LINE SPANS” August 26-30,
2019
[5]Rao, M. V. Durga, and K., K. Asokan and Kumar, R Ashok,
Analysis of Electric Field on Composite Silicone Insulators
Used in High Voltage Transmission Lines (October 2,
2019). Proceedings of International Conference on
Advancements in Computing & Management (ICACM)
2019
[6]Zacharias G. Datsios, Pantelis N. Mikropoulos, Thomas
E.Tsovilis “Estimation of the Minimum Shielding Failure
Current Causing Flashover in Overhead Lines of the
Hellenic Transmission System through ATP-EMTP
Simulations”
[7]Mr.M.V.DurgaRao.S aDr.K.AsokanbDr.R.Ashok Kumar
“Analysis of Electric Field on Composite Silicone Insulators
Used in High Voltage Transmission Lines”
[8]C. Zacharias’s, S. M. Rowland, I. Cotton, V. Peesapati and
D. Chambers, "Development of Electric-Field Stress
Control Devices for a 132 kV Insulating Cross-Arm Using
Finite-Element Analysis," in IEEE Transactions on Power
Delivery, vol. 31, no. 5, pp. 2105-2113, Oct. 2016, DOI DOI:
10.1109/TPWRD.2015.2499795.
[9]S. Deb, R. Ghosh, S. Dutta, S. Dalai, and B. Chatterjee,
"Effect of humidity on leakage current of a contaminated
11 kV Porcelain Pin Insulator," 2017 6th International
Conference on Computer Applications In Electrical
Engineering-Recent Advances (CERA), 2017, pp. 215-219,
DOI DOI: 10.1109/CERA.2017.8343329.

More Related Content

Similar to Electric Field Analysis and Impact Study with Shrubbery on the 11 kV Distribution System fed by a 132 kV/220 kV Transmission Feeder

Analysis of Electric Field and Current Density on XLPE Insulator
Analysis of Electric Field and Current Density on XLPE Insulator Analysis of Electric Field and Current Density on XLPE Insulator
Analysis of Electric Field and Current Density on XLPE Insulator IJECEIAES
 
WIRELESS POWER TRANSMISSION Project
WIRELESS POWER TRANSMISSION ProjectWIRELESS POWER TRANSMISSION Project
WIRELESS POWER TRANSMISSION Projectsagnikchoudhury
 
IRJET- Modeling and Simulation of Electric Discharge Machine (EDM) and WEDM u...
IRJET- Modeling and Simulation of Electric Discharge Machine (EDM) and WEDM u...IRJET- Modeling and Simulation of Electric Discharge Machine (EDM) and WEDM u...
IRJET- Modeling and Simulation of Electric Discharge Machine (EDM) and WEDM u...IRJET Journal
 
Design and Simulation of a Fractal Micro-Transformer
Design and Simulation of a Fractal Micro-TransformerDesign and Simulation of a Fractal Micro-Transformer
Design and Simulation of a Fractal Micro-TransformerIJERA Editor
 
Some Aspects of Stress Distribution and Effect of Voids Having Different Gase...
Some Aspects of Stress Distribution and Effect of Voids Having Different Gase...Some Aspects of Stress Distribution and Effect of Voids Having Different Gase...
Some Aspects of Stress Distribution and Effect of Voids Having Different Gase...IOSR Journals
 
Active Grounding of the Photovoltaic Power PlantSafeguarded by Lightning Rods
Active Grounding of the Photovoltaic Power PlantSafeguarded by Lightning RodsActive Grounding of the Photovoltaic Power PlantSafeguarded by Lightning Rods
Active Grounding of the Photovoltaic Power PlantSafeguarded by Lightning RodsIRJET Journal
 
Analysis of Stranded Multi-Conductor Cable in Multilayered Dielectric Media
Analysis of Stranded Multi-Conductor Cable in Multilayered Dielectric MediaAnalysis of Stranded Multi-Conductor Cable in Multilayered Dielectric Media
Analysis of Stranded Multi-Conductor Cable in Multilayered Dielectric MediaJimmi James
 
Paper Electron Tube Afs Epri R5
Paper   Electron Tube   Afs Epri R5Paper   Electron Tube   Afs Epri R5
Paper Electron Tube Afs Epri R5John Kappenman
 
Power loss due to Corona on High Voltage Transmission Lines
Power loss due to Corona on High Voltage Transmission LinesPower loss due to Corona on High Voltage Transmission Lines
Power loss due to Corona on High Voltage Transmission LinesIOSR Journals
 
Design and modeling of solenoid inductor integrated with FeNiCo in high frequ...
Design and modeling of solenoid inductor integrated with FeNiCo in high frequ...Design and modeling of solenoid inductor integrated with FeNiCo in high frequ...
Design and modeling of solenoid inductor integrated with FeNiCo in high frequ...TELKOMNIKA JOURNAL
 
Dq31551563
Dq31551563Dq31551563
Dq31551563IJMER
 
ethodology for determining the parameters of hightemperature superconducting...
ethodology for determining the parameters of hightemperature superconducting...ethodology for determining the parameters of hightemperature superconducting...
ethodology for determining the parameters of hightemperature superconducting...IJECEIAES
 
Electric field effect in the formation of water treeing in mv power cables
Electric field effect in the formation of water treeing in mv power cablesElectric field effect in the formation of water treeing in mv power cables
Electric field effect in the formation of water treeing in mv power cableseSAT Publishing House
 
Wireless Power Transfer Project
Wireless Power Transfer  ProjectWireless Power Transfer  Project
Wireless Power Transfer Projectsagnikchoudhury
 
Application Note – Resilient and Reliable Power Supply in a Modern Office Bui...
Application Note – Resilient and Reliable Power Supply in a Modern Office Bui...Application Note – Resilient and Reliable Power Supply in a Modern Office Bui...
Application Note – Resilient and Reliable Power Supply in a Modern Office Bui...Leonardo ENERGY
 
Micro-alloyed copper overhead line conductors - Wire & Cable Technology Inter...
Micro-alloyed copper overhead line conductors - Wire & Cable Technology Inter...Micro-alloyed copper overhead line conductors - Wire & Cable Technology Inter...
Micro-alloyed copper overhead line conductors - Wire & Cable Technology Inter...Leonardo ENERGY
 
Effect of Series Resistance and Layer Thickness on PCE & Fill Factor in Pervo...
Effect of Series Resistance and Layer Thickness on PCE & Fill Factor in Pervo...Effect of Series Resistance and Layer Thickness on PCE & Fill Factor in Pervo...
Effect of Series Resistance and Layer Thickness on PCE & Fill Factor in Pervo...IRJET Journal
 
System design-engineering-j jicable11-0279_final-evolution-in-method-performa...
System design-engineering-j jicable11-0279_final-evolution-in-method-performa...System design-engineering-j jicable11-0279_final-evolution-in-method-performa...
System design-engineering-j jicable11-0279_final-evolution-in-method-performa...nak maneth
 
Voltage Profile Improvement using Switched Capacitors: Case of Single Wire Ea...
Voltage Profile Improvement using Switched Capacitors: Case of Single Wire Ea...Voltage Profile Improvement using Switched Capacitors: Case of Single Wire Ea...
Voltage Profile Improvement using Switched Capacitors: Case of Single Wire Ea...IJMERJOURNAL
 

Similar to Electric Field Analysis and Impact Study with Shrubbery on the 11 kV Distribution System fed by a 132 kV/220 kV Transmission Feeder (20)

Analysis of Electric Field and Current Density on XLPE Insulator
Analysis of Electric Field and Current Density on XLPE Insulator Analysis of Electric Field and Current Density on XLPE Insulator
Analysis of Electric Field and Current Density on XLPE Insulator
 
A5230104
A5230104A5230104
A5230104
 
WIRELESS POWER TRANSMISSION Project
WIRELESS POWER TRANSMISSION ProjectWIRELESS POWER TRANSMISSION Project
WIRELESS POWER TRANSMISSION Project
 
IRJET- Modeling and Simulation of Electric Discharge Machine (EDM) and WEDM u...
IRJET- Modeling and Simulation of Electric Discharge Machine (EDM) and WEDM u...IRJET- Modeling and Simulation of Electric Discharge Machine (EDM) and WEDM u...
IRJET- Modeling and Simulation of Electric Discharge Machine (EDM) and WEDM u...
 
Design and Simulation of a Fractal Micro-Transformer
Design and Simulation of a Fractal Micro-TransformerDesign and Simulation of a Fractal Micro-Transformer
Design and Simulation of a Fractal Micro-Transformer
 
Some Aspects of Stress Distribution and Effect of Voids Having Different Gase...
Some Aspects of Stress Distribution and Effect of Voids Having Different Gase...Some Aspects of Stress Distribution and Effect of Voids Having Different Gase...
Some Aspects of Stress Distribution and Effect of Voids Having Different Gase...
 
Active Grounding of the Photovoltaic Power PlantSafeguarded by Lightning Rods
Active Grounding of the Photovoltaic Power PlantSafeguarded by Lightning RodsActive Grounding of the Photovoltaic Power PlantSafeguarded by Lightning Rods
Active Grounding of the Photovoltaic Power PlantSafeguarded by Lightning Rods
 
Analysis of Stranded Multi-Conductor Cable in Multilayered Dielectric Media
Analysis of Stranded Multi-Conductor Cable in Multilayered Dielectric MediaAnalysis of Stranded Multi-Conductor Cable in Multilayered Dielectric Media
Analysis of Stranded Multi-Conductor Cable in Multilayered Dielectric Media
 
Paper Electron Tube Afs Epri R5
Paper   Electron Tube   Afs Epri R5Paper   Electron Tube   Afs Epri R5
Paper Electron Tube Afs Epri R5
 
Power loss due to Corona on High Voltage Transmission Lines
Power loss due to Corona on High Voltage Transmission LinesPower loss due to Corona on High Voltage Transmission Lines
Power loss due to Corona on High Voltage Transmission Lines
 
Design and modeling of solenoid inductor integrated with FeNiCo in high frequ...
Design and modeling of solenoid inductor integrated with FeNiCo in high frequ...Design and modeling of solenoid inductor integrated with FeNiCo in high frequ...
Design and modeling of solenoid inductor integrated with FeNiCo in high frequ...
 
Dq31551563
Dq31551563Dq31551563
Dq31551563
 
ethodology for determining the parameters of hightemperature superconducting...
ethodology for determining the parameters of hightemperature superconducting...ethodology for determining the parameters of hightemperature superconducting...
ethodology for determining the parameters of hightemperature superconducting...
 
Electric field effect in the formation of water treeing in mv power cables
Electric field effect in the formation of water treeing in mv power cablesElectric field effect in the formation of water treeing in mv power cables
Electric field effect in the formation of water treeing in mv power cables
 
Wireless Power Transfer Project
Wireless Power Transfer  ProjectWireless Power Transfer  Project
Wireless Power Transfer Project
 
Application Note – Resilient and Reliable Power Supply in a Modern Office Bui...
Application Note – Resilient and Reliable Power Supply in a Modern Office Bui...Application Note – Resilient and Reliable Power Supply in a Modern Office Bui...
Application Note – Resilient and Reliable Power Supply in a Modern Office Bui...
 
Micro-alloyed copper overhead line conductors - Wire & Cable Technology Inter...
Micro-alloyed copper overhead line conductors - Wire & Cable Technology Inter...Micro-alloyed copper overhead line conductors - Wire & Cable Technology Inter...
Micro-alloyed copper overhead line conductors - Wire & Cable Technology Inter...
 
Effect of Series Resistance and Layer Thickness on PCE & Fill Factor in Pervo...
Effect of Series Resistance and Layer Thickness on PCE & Fill Factor in Pervo...Effect of Series Resistance and Layer Thickness on PCE & Fill Factor in Pervo...
Effect of Series Resistance and Layer Thickness on PCE & Fill Factor in Pervo...
 
System design-engineering-j jicable11-0279_final-evolution-in-method-performa...
System design-engineering-j jicable11-0279_final-evolution-in-method-performa...System design-engineering-j jicable11-0279_final-evolution-in-method-performa...
System design-engineering-j jicable11-0279_final-evolution-in-method-performa...
 
Voltage Profile Improvement using Switched Capacitors: Case of Single Wire Ea...
Voltage Profile Improvement using Switched Capacitors: Case of Single Wire Ea...Voltage Profile Improvement using Switched Capacitors: Case of Single Wire Ea...
Voltage Profile Improvement using Switched Capacitors: Case of Single Wire Ea...
 

More from IRJET Journal

TUNNELING IN HIMALAYAS WITH NATM METHOD: A SPECIAL REFERENCES TO SUNGAL TUNNE...
TUNNELING IN HIMALAYAS WITH NATM METHOD: A SPECIAL REFERENCES TO SUNGAL TUNNE...TUNNELING IN HIMALAYAS WITH NATM METHOD: A SPECIAL REFERENCES TO SUNGAL TUNNE...
TUNNELING IN HIMALAYAS WITH NATM METHOD: A SPECIAL REFERENCES TO SUNGAL TUNNE...IRJET Journal
 
STUDY THE EFFECT OF RESPONSE REDUCTION FACTOR ON RC FRAMED STRUCTURE
STUDY THE EFFECT OF RESPONSE REDUCTION FACTOR ON RC FRAMED STRUCTURESTUDY THE EFFECT OF RESPONSE REDUCTION FACTOR ON RC FRAMED STRUCTURE
STUDY THE EFFECT OF RESPONSE REDUCTION FACTOR ON RC FRAMED STRUCTUREIRJET Journal
 
A COMPARATIVE ANALYSIS OF RCC ELEMENT OF SLAB WITH STARK STEEL (HYSD STEEL) A...
A COMPARATIVE ANALYSIS OF RCC ELEMENT OF SLAB WITH STARK STEEL (HYSD STEEL) A...A COMPARATIVE ANALYSIS OF RCC ELEMENT OF SLAB WITH STARK STEEL (HYSD STEEL) A...
A COMPARATIVE ANALYSIS OF RCC ELEMENT OF SLAB WITH STARK STEEL (HYSD STEEL) A...IRJET Journal
 
Effect of Camber and Angles of Attack on Airfoil Characteristics
Effect of Camber and Angles of Attack on Airfoil CharacteristicsEffect of Camber and Angles of Attack on Airfoil Characteristics
Effect of Camber and Angles of Attack on Airfoil CharacteristicsIRJET Journal
 
A Review on the Progress and Challenges of Aluminum-Based Metal Matrix Compos...
A Review on the Progress and Challenges of Aluminum-Based Metal Matrix Compos...A Review on the Progress and Challenges of Aluminum-Based Metal Matrix Compos...
A Review on the Progress and Challenges of Aluminum-Based Metal Matrix Compos...IRJET Journal
 
Dynamic Urban Transit Optimization: A Graph Neural Network Approach for Real-...
Dynamic Urban Transit Optimization: A Graph Neural Network Approach for Real-...Dynamic Urban Transit Optimization: A Graph Neural Network Approach for Real-...
Dynamic Urban Transit Optimization: A Graph Neural Network Approach for Real-...IRJET Journal
 
Structural Analysis and Design of Multi-Storey Symmetric and Asymmetric Shape...
Structural Analysis and Design of Multi-Storey Symmetric and Asymmetric Shape...Structural Analysis and Design of Multi-Storey Symmetric and Asymmetric Shape...
Structural Analysis and Design of Multi-Storey Symmetric and Asymmetric Shape...IRJET Journal
 
A Review of “Seismic Response of RC Structures Having Plan and Vertical Irreg...
A Review of “Seismic Response of RC Structures Having Plan and Vertical Irreg...A Review of “Seismic Response of RC Structures Having Plan and Vertical Irreg...
A Review of “Seismic Response of RC Structures Having Plan and Vertical Irreg...IRJET Journal
 
A REVIEW ON MACHINE LEARNING IN ADAS
A REVIEW ON MACHINE LEARNING IN ADASA REVIEW ON MACHINE LEARNING IN ADAS
A REVIEW ON MACHINE LEARNING IN ADASIRJET Journal
 
Long Term Trend Analysis of Precipitation and Temperature for Asosa district,...
Long Term Trend Analysis of Precipitation and Temperature for Asosa district,...Long Term Trend Analysis of Precipitation and Temperature for Asosa district,...
Long Term Trend Analysis of Precipitation and Temperature for Asosa district,...IRJET Journal
 
P.E.B. Framed Structure Design and Analysis Using STAAD Pro
P.E.B. Framed Structure Design and Analysis Using STAAD ProP.E.B. Framed Structure Design and Analysis Using STAAD Pro
P.E.B. Framed Structure Design and Analysis Using STAAD ProIRJET Journal
 
A Review on Innovative Fiber Integration for Enhanced Reinforcement of Concre...
A Review on Innovative Fiber Integration for Enhanced Reinforcement of Concre...A Review on Innovative Fiber Integration for Enhanced Reinforcement of Concre...
A Review on Innovative Fiber Integration for Enhanced Reinforcement of Concre...IRJET Journal
 
Survey Paper on Cloud-Based Secured Healthcare System
Survey Paper on Cloud-Based Secured Healthcare SystemSurvey Paper on Cloud-Based Secured Healthcare System
Survey Paper on Cloud-Based Secured Healthcare SystemIRJET Journal
 
Review on studies and research on widening of existing concrete bridges
Review on studies and research on widening of existing concrete bridgesReview on studies and research on widening of existing concrete bridges
Review on studies and research on widening of existing concrete bridgesIRJET Journal
 
React based fullstack edtech web application
React based fullstack edtech web applicationReact based fullstack edtech web application
React based fullstack edtech web applicationIRJET Journal
 
A Comprehensive Review of Integrating IoT and Blockchain Technologies in the ...
A Comprehensive Review of Integrating IoT and Blockchain Technologies in the ...A Comprehensive Review of Integrating IoT and Blockchain Technologies in the ...
A Comprehensive Review of Integrating IoT and Blockchain Technologies in the ...IRJET Journal
 
A REVIEW ON THE PERFORMANCE OF COCONUT FIBRE REINFORCED CONCRETE.
A REVIEW ON THE PERFORMANCE OF COCONUT FIBRE REINFORCED CONCRETE.A REVIEW ON THE PERFORMANCE OF COCONUT FIBRE REINFORCED CONCRETE.
A REVIEW ON THE PERFORMANCE OF COCONUT FIBRE REINFORCED CONCRETE.IRJET Journal
 
Optimizing Business Management Process Workflows: The Dynamic Influence of Mi...
Optimizing Business Management Process Workflows: The Dynamic Influence of Mi...Optimizing Business Management Process Workflows: The Dynamic Influence of Mi...
Optimizing Business Management Process Workflows: The Dynamic Influence of Mi...IRJET Journal
 
Multistoried and Multi Bay Steel Building Frame by using Seismic Design
Multistoried and Multi Bay Steel Building Frame by using Seismic DesignMultistoried and Multi Bay Steel Building Frame by using Seismic Design
Multistoried and Multi Bay Steel Building Frame by using Seismic DesignIRJET Journal
 
Cost Optimization of Construction Using Plastic Waste as a Sustainable Constr...
Cost Optimization of Construction Using Plastic Waste as a Sustainable Constr...Cost Optimization of Construction Using Plastic Waste as a Sustainable Constr...
Cost Optimization of Construction Using Plastic Waste as a Sustainable Constr...IRJET Journal
 

More from IRJET Journal (20)

TUNNELING IN HIMALAYAS WITH NATM METHOD: A SPECIAL REFERENCES TO SUNGAL TUNNE...
TUNNELING IN HIMALAYAS WITH NATM METHOD: A SPECIAL REFERENCES TO SUNGAL TUNNE...TUNNELING IN HIMALAYAS WITH NATM METHOD: A SPECIAL REFERENCES TO SUNGAL TUNNE...
TUNNELING IN HIMALAYAS WITH NATM METHOD: A SPECIAL REFERENCES TO SUNGAL TUNNE...
 
STUDY THE EFFECT OF RESPONSE REDUCTION FACTOR ON RC FRAMED STRUCTURE
STUDY THE EFFECT OF RESPONSE REDUCTION FACTOR ON RC FRAMED STRUCTURESTUDY THE EFFECT OF RESPONSE REDUCTION FACTOR ON RC FRAMED STRUCTURE
STUDY THE EFFECT OF RESPONSE REDUCTION FACTOR ON RC FRAMED STRUCTURE
 
A COMPARATIVE ANALYSIS OF RCC ELEMENT OF SLAB WITH STARK STEEL (HYSD STEEL) A...
A COMPARATIVE ANALYSIS OF RCC ELEMENT OF SLAB WITH STARK STEEL (HYSD STEEL) A...A COMPARATIVE ANALYSIS OF RCC ELEMENT OF SLAB WITH STARK STEEL (HYSD STEEL) A...
A COMPARATIVE ANALYSIS OF RCC ELEMENT OF SLAB WITH STARK STEEL (HYSD STEEL) A...
 
Effect of Camber and Angles of Attack on Airfoil Characteristics
Effect of Camber and Angles of Attack on Airfoil CharacteristicsEffect of Camber and Angles of Attack on Airfoil Characteristics
Effect of Camber and Angles of Attack on Airfoil Characteristics
 
A Review on the Progress and Challenges of Aluminum-Based Metal Matrix Compos...
A Review on the Progress and Challenges of Aluminum-Based Metal Matrix Compos...A Review on the Progress and Challenges of Aluminum-Based Metal Matrix Compos...
A Review on the Progress and Challenges of Aluminum-Based Metal Matrix Compos...
 
Dynamic Urban Transit Optimization: A Graph Neural Network Approach for Real-...
Dynamic Urban Transit Optimization: A Graph Neural Network Approach for Real-...Dynamic Urban Transit Optimization: A Graph Neural Network Approach for Real-...
Dynamic Urban Transit Optimization: A Graph Neural Network Approach for Real-...
 
Structural Analysis and Design of Multi-Storey Symmetric and Asymmetric Shape...
Structural Analysis and Design of Multi-Storey Symmetric and Asymmetric Shape...Structural Analysis and Design of Multi-Storey Symmetric and Asymmetric Shape...
Structural Analysis and Design of Multi-Storey Symmetric and Asymmetric Shape...
 
A Review of “Seismic Response of RC Structures Having Plan and Vertical Irreg...
A Review of “Seismic Response of RC Structures Having Plan and Vertical Irreg...A Review of “Seismic Response of RC Structures Having Plan and Vertical Irreg...
A Review of “Seismic Response of RC Structures Having Plan and Vertical Irreg...
 
A REVIEW ON MACHINE LEARNING IN ADAS
A REVIEW ON MACHINE LEARNING IN ADASA REVIEW ON MACHINE LEARNING IN ADAS
A REVIEW ON MACHINE LEARNING IN ADAS
 
Long Term Trend Analysis of Precipitation and Temperature for Asosa district,...
Long Term Trend Analysis of Precipitation and Temperature for Asosa district,...Long Term Trend Analysis of Precipitation and Temperature for Asosa district,...
Long Term Trend Analysis of Precipitation and Temperature for Asosa district,...
 
P.E.B. Framed Structure Design and Analysis Using STAAD Pro
P.E.B. Framed Structure Design and Analysis Using STAAD ProP.E.B. Framed Structure Design and Analysis Using STAAD Pro
P.E.B. Framed Structure Design and Analysis Using STAAD Pro
 
A Review on Innovative Fiber Integration for Enhanced Reinforcement of Concre...
A Review on Innovative Fiber Integration for Enhanced Reinforcement of Concre...A Review on Innovative Fiber Integration for Enhanced Reinforcement of Concre...
A Review on Innovative Fiber Integration for Enhanced Reinforcement of Concre...
 
Survey Paper on Cloud-Based Secured Healthcare System
Survey Paper on Cloud-Based Secured Healthcare SystemSurvey Paper on Cloud-Based Secured Healthcare System
Survey Paper on Cloud-Based Secured Healthcare System
 
Review on studies and research on widening of existing concrete bridges
Review on studies and research on widening of existing concrete bridgesReview on studies and research on widening of existing concrete bridges
Review on studies and research on widening of existing concrete bridges
 
React based fullstack edtech web application
React based fullstack edtech web applicationReact based fullstack edtech web application
React based fullstack edtech web application
 
A Comprehensive Review of Integrating IoT and Blockchain Technologies in the ...
A Comprehensive Review of Integrating IoT and Blockchain Technologies in the ...A Comprehensive Review of Integrating IoT and Blockchain Technologies in the ...
A Comprehensive Review of Integrating IoT and Blockchain Technologies in the ...
 
A REVIEW ON THE PERFORMANCE OF COCONUT FIBRE REINFORCED CONCRETE.
A REVIEW ON THE PERFORMANCE OF COCONUT FIBRE REINFORCED CONCRETE.A REVIEW ON THE PERFORMANCE OF COCONUT FIBRE REINFORCED CONCRETE.
A REVIEW ON THE PERFORMANCE OF COCONUT FIBRE REINFORCED CONCRETE.
 
Optimizing Business Management Process Workflows: The Dynamic Influence of Mi...
Optimizing Business Management Process Workflows: The Dynamic Influence of Mi...Optimizing Business Management Process Workflows: The Dynamic Influence of Mi...
Optimizing Business Management Process Workflows: The Dynamic Influence of Mi...
 
Multistoried and Multi Bay Steel Building Frame by using Seismic Design
Multistoried and Multi Bay Steel Building Frame by using Seismic DesignMultistoried and Multi Bay Steel Building Frame by using Seismic Design
Multistoried and Multi Bay Steel Building Frame by using Seismic Design
 
Cost Optimization of Construction Using Plastic Waste as a Sustainable Constr...
Cost Optimization of Construction Using Plastic Waste as a Sustainable Constr...Cost Optimization of Construction Using Plastic Waste as a Sustainable Constr...
Cost Optimization of Construction Using Plastic Waste as a Sustainable Constr...
 

Recently uploaded

What are the advantages and disadvantages of membrane structures.pptx
What are the advantages and disadvantages of membrane structures.pptxWhat are the advantages and disadvantages of membrane structures.pptx
What are the advantages and disadvantages of membrane structures.pptxwendy cai
 
Study on Air-Water & Water-Water Heat Exchange in a Finned Tube Exchanger
Study on Air-Water & Water-Water Heat Exchange in a Finned Tube ExchangerStudy on Air-Water & Water-Water Heat Exchange in a Finned Tube Exchanger
Study on Air-Water & Water-Water Heat Exchange in a Finned Tube ExchangerAnamika Sarkar
 
Introduction to Microprocesso programming and interfacing.pptx
Introduction to Microprocesso programming and interfacing.pptxIntroduction to Microprocesso programming and interfacing.pptx
Introduction to Microprocesso programming and interfacing.pptxvipinkmenon1
 
HARMONY IN THE NATURE AND EXISTENCE - Unit-IV
HARMONY IN THE NATURE AND EXISTENCE - Unit-IVHARMONY IN THE NATURE AND EXISTENCE - Unit-IV
HARMONY IN THE NATURE AND EXISTENCE - Unit-IVRajaP95
 
Current Transformer Drawing and GTP for MSETCL
Current Transformer Drawing and GTP for MSETCLCurrent Transformer Drawing and GTP for MSETCL
Current Transformer Drawing and GTP for MSETCLDeelipZope
 
Past, Present and Future of Generative AI
Past, Present and Future of Generative AIPast, Present and Future of Generative AI
Past, Present and Future of Generative AIabhishek36461
 
Heart Disease Prediction using machine learning.pptx
Heart Disease Prediction using machine learning.pptxHeart Disease Prediction using machine learning.pptx
Heart Disease Prediction using machine learning.pptxPoojaBan
 
ZXCTN 5804 / ZTE PTN / ZTE POTN / ZTE 5804 PTN / ZTE POTN 5804 ( 100/200 GE Z...
ZXCTN 5804 / ZTE PTN / ZTE POTN / ZTE 5804 PTN / ZTE POTN 5804 ( 100/200 GE Z...ZXCTN 5804 / ZTE PTN / ZTE POTN / ZTE 5804 PTN / ZTE POTN 5804 ( 100/200 GE Z...
ZXCTN 5804 / ZTE PTN / ZTE POTN / ZTE 5804 PTN / ZTE POTN 5804 ( 100/200 GE Z...ZTE
 
Artificial-Intelligence-in-Electronics (K).pptx
Artificial-Intelligence-in-Electronics (K).pptxArtificial-Intelligence-in-Electronics (K).pptx
Artificial-Intelligence-in-Electronics (K).pptxbritheesh05
 
Architect Hassan Khalil Portfolio for 2024
Architect Hassan Khalil Portfolio for 2024Architect Hassan Khalil Portfolio for 2024
Architect Hassan Khalil Portfolio for 2024hassan khalil
 
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...ranjana rawat
 
Biology for Computer Engineers Course Handout.pptx
Biology for Computer Engineers Course Handout.pptxBiology for Computer Engineers Course Handout.pptx
Biology for Computer Engineers Course Handout.pptxDeepakSakkari2
 
VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...
VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...
VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...VICTOR MAESTRE RAMIREZ
 
power system scada applications and uses
power system scada applications and usespower system scada applications and uses
power system scada applications and usesDevarapalliHaritha
 
Sachpazis Costas: Geotechnical Engineering: A student's Perspective Introduction
Sachpazis Costas: Geotechnical Engineering: A student's Perspective IntroductionSachpazis Costas: Geotechnical Engineering: A student's Perspective Introduction
Sachpazis Costas: Geotechnical Engineering: A student's Perspective IntroductionDr.Costas Sachpazis
 
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escortsranjana rawat
 
Gurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort service
Gurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort serviceGurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort service
Gurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort servicejennyeacort
 
microprocessor 8085 and its interfacing
microprocessor 8085  and its interfacingmicroprocessor 8085  and its interfacing
microprocessor 8085 and its interfacingjaychoudhary37
 
main PPT.pptx of girls hostel security using rfid
main PPT.pptx of girls hostel security using rfidmain PPT.pptx of girls hostel security using rfid
main PPT.pptx of girls hostel security using rfidNikhilNagaraju
 
Oxy acetylene welding presentation note.
Oxy acetylene welding presentation note.Oxy acetylene welding presentation note.
Oxy acetylene welding presentation note.eptoze12
 

Recently uploaded (20)

What are the advantages and disadvantages of membrane structures.pptx
What are the advantages and disadvantages of membrane structures.pptxWhat are the advantages and disadvantages of membrane structures.pptx
What are the advantages and disadvantages of membrane structures.pptx
 
Study on Air-Water & Water-Water Heat Exchange in a Finned Tube Exchanger
Study on Air-Water & Water-Water Heat Exchange in a Finned Tube ExchangerStudy on Air-Water & Water-Water Heat Exchange in a Finned Tube Exchanger
Study on Air-Water & Water-Water Heat Exchange in a Finned Tube Exchanger
 
Introduction to Microprocesso programming and interfacing.pptx
Introduction to Microprocesso programming and interfacing.pptxIntroduction to Microprocesso programming and interfacing.pptx
Introduction to Microprocesso programming and interfacing.pptx
 
HARMONY IN THE NATURE AND EXISTENCE - Unit-IV
HARMONY IN THE NATURE AND EXISTENCE - Unit-IVHARMONY IN THE NATURE AND EXISTENCE - Unit-IV
HARMONY IN THE NATURE AND EXISTENCE - Unit-IV
 
Current Transformer Drawing and GTP for MSETCL
Current Transformer Drawing and GTP for MSETCLCurrent Transformer Drawing and GTP for MSETCL
Current Transformer Drawing and GTP for MSETCL
 
Past, Present and Future of Generative AI
Past, Present and Future of Generative AIPast, Present and Future of Generative AI
Past, Present and Future of Generative AI
 
Heart Disease Prediction using machine learning.pptx
Heart Disease Prediction using machine learning.pptxHeart Disease Prediction using machine learning.pptx
Heart Disease Prediction using machine learning.pptx
 
ZXCTN 5804 / ZTE PTN / ZTE POTN / ZTE 5804 PTN / ZTE POTN 5804 ( 100/200 GE Z...
ZXCTN 5804 / ZTE PTN / ZTE POTN / ZTE 5804 PTN / ZTE POTN 5804 ( 100/200 GE Z...ZXCTN 5804 / ZTE PTN / ZTE POTN / ZTE 5804 PTN / ZTE POTN 5804 ( 100/200 GE Z...
ZXCTN 5804 / ZTE PTN / ZTE POTN / ZTE 5804 PTN / ZTE POTN 5804 ( 100/200 GE Z...
 
Artificial-Intelligence-in-Electronics (K).pptx
Artificial-Intelligence-in-Electronics (K).pptxArtificial-Intelligence-in-Electronics (K).pptx
Artificial-Intelligence-in-Electronics (K).pptx
 
Architect Hassan Khalil Portfolio for 2024
Architect Hassan Khalil Portfolio for 2024Architect Hassan Khalil Portfolio for 2024
Architect Hassan Khalil Portfolio for 2024
 
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
 
Biology for Computer Engineers Course Handout.pptx
Biology for Computer Engineers Course Handout.pptxBiology for Computer Engineers Course Handout.pptx
Biology for Computer Engineers Course Handout.pptx
 
VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...
VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...
VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...
 
power system scada applications and uses
power system scada applications and usespower system scada applications and uses
power system scada applications and uses
 
Sachpazis Costas: Geotechnical Engineering: A student's Perspective Introduction
Sachpazis Costas: Geotechnical Engineering: A student's Perspective IntroductionSachpazis Costas: Geotechnical Engineering: A student's Perspective Introduction
Sachpazis Costas: Geotechnical Engineering: A student's Perspective Introduction
 
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
 
Gurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort service
Gurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort serviceGurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort service
Gurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort service
 
microprocessor 8085 and its interfacing
microprocessor 8085  and its interfacingmicroprocessor 8085  and its interfacing
microprocessor 8085 and its interfacing
 
main PPT.pptx of girls hostel security using rfid
main PPT.pptx of girls hostel security using rfidmain PPT.pptx of girls hostel security using rfid
main PPT.pptx of girls hostel security using rfid
 
Oxy acetylene welding presentation note.
Oxy acetylene welding presentation note.Oxy acetylene welding presentation note.
Oxy acetylene welding presentation note.
 

Electric Field Analysis and Impact Study with Shrubbery on the 11 kV Distribution System fed by a 132 kV/220 kV Transmission Feeder

  • 1. International Research Journal of Engineering and Technology (IRJET) e-ISSN: 2395-0056 Volume: 09 Issue: 02 | Feb 2022 www.irjet.net p-ISSN: 2395-0072 © 2022, IRJET | Impact Factor value: 7.529 | ISO 9001:2008 Certified Journal | Page 764 Electric Field Analysis and Impact Study with Shrubbery on the 11 kV Distribution System fed by a 132 kV/220 kV Transmission Feeder Dr. T. Murali Mohan1, B. Chinni2 1Professor, Dept. of Electrical and Electronics Engineering, UCEK, JNTU Kakinada, India 2M. Tech, Dept. of Electrical and Electronics Engineering, UCEK, JNTU Kakinada, India ----------------------------------------------------------------------***--------------------------------------------------------------------- Abstract - In this paper impact of vegetation growth in rural distribution net networks is studied in FEM-2D software. The impact of vegetation growth, along with the Transmission & The model, utilizes parameters of an 11kV, three-phase distribution feeder, PCC poles, metallic cross- arms, and 160kN pin insulators. A pole span of 100 meters is considered for subject simulation. In this paper, a second case scenario regarding the Electric field analysis on 132kv transmission line tower and 220kv transmission line tower is studied in FEM-2D software. The FEM-based simulation and study indicate an increase in electrical field stresses for vegetation in the vicinity of the line. Key Words: Vegetation, Pin Insulator, Polymeric Insulator 132 kV Transmission Tower, 220kV Transmission Tower, FEM (Finite Element Method). 1. INTRODUCTION: In the latest days, there has been a significant increase in the electricity demand. To fulfill this demand, switchgear, transmission, and distribution networks must be done more efficiently. The effectiveness of any system is primarily determined by the continuity of service while avoiding faults. The performance and properties of insulators must be good to ensure continuity. Ceramic insulators have long been utilized in power transmission and distribution systems. In nowadays ceramic insulator has been slowly replaced by composite insulator in power grid nowadays. However, flashover fault still occurs on this insulator type. Under certain conditions, partial discharges may occur on the insulator and lead to a complete flashover. The flashover can cause a breakdown and damage the whole power system. Compared to porcelain suspension insulators, composite insulators have many advantages, such as being lightweight, higher mechanical strength to weight ratio, higher resistance to vandalism, better performance in the presence of heavy pollution in wet conditions and better withstand voltage. Therefore, outdoor composite insulators are now preferable and widely used in maintaining the reliability of the power system. With the increase of demand and the use of composite insulators, factors of the occurrence of the fault have drawn wider attention. Transmission and distribution of power are accomplished using overhead lines and UG Cables. In OH lines, metallic and non-metallic structures are used for supporting insulation (string or pin insulators) and the conductors. For capital costs involved, the use of strong metallic structures is restricted to high and ultra-high voltage transmission systems. Whereas, for most, medium voltage power distribution systems wooden, cement structures, or poles are recommended. It is worth noting that both wooden and cement poles not only provide requisite mechanical support, they also minimize charge leakage from the conductor, for their higher specific resistance. In the case of T&D systems, this neighborhood rendered by the metallic tower/ pole structure, the guard wire, and most importantly by the vegetation and creepers in the vicinity of T&D systems. This project, model utilizes parameters of an 11kV, three-phase distribution feeder, PCC poles, metallic cross-arms, and, 160kN pin insulators. A pole span of 100 meters is considered for subject simulation. The simulation is carried out using the FEM model for an 11kV, 3-φ distribution feeder, PCC poles, metallic cross arms, and 160kN pin insulators. A pole span of 100 meters is considered for subject simulation for four different configurations. The power losses are aggregated for a line length of 10km [1]. In this paper, a second case scenario regarding the Electric field analysis on 132kv transmission line tower and 220kv transmission line tower is studied in FEM-2D software [2]-[3]. The FEM-based simulation and study indicate an increase in electrical field stresses for vegetation in the vicinity of the line.[1] 2. IMPACT OF VEGETATION GROWTH IN 11KV DISTRIBUTION NETWORK: The analysis has been carried out using FEMM software. FEMM is a FEFEM-based simulation tool. The distribution system chosen is a rural section fed by a 33/11kV Shanthi Nagar substation in the Kakinada district of Andhra Pradesh State, India. The section consists of cement poles and cross-arms, the AutoCAD design is shown in Figure.1. Vegetation like trees, bushes, and creepers are found to grow during rainy seasons. The growth if abundant can reach alarming heights endangering short circuits. Such developments are modeled and resulting variations in electric field intensities, effective line capacity, once, and leakage current are studied. The results are compared with the standard line without such intrusion. The power and energy losses and additional line loading are determined and shown as the additional burden on distribution utility [1].
  • 2. International Research Journal of Engineering and Technology (IRJET) e-ISSN: 2395-0056 Volume: 09 Issue: 02 | Feb 2022 www.irjet.net p-ISSN: 2395-0072 © 2022, IRJET | Impact Factor value: 7.529 | ISO 9001:2008 Certified Journal | Page 765 TABLE 1: Dimension of Electric pole S.no Particulars Length(mm) 1. 1. Electric pole height 12500 2. 2. Width 300 Fig-1:11kV distribution line cross arm design Thus, the Simulation includes the following two cases: Case1. A Clean distribution line Case2. Unclean distribution line 2.1. FEM Simulation Analysis: The analysis was carried out for all the two conditions and was discussed below. 2.2. Case1: A Clean distribution Line: The 11kV, three-phase distribution feeder, metallic cross arms, and pin insulator were designed by using FEMM 2D software as per geometrical conFigurations shown in Fig 2.[9] The electric field distribution in and around the insulator is necessary for the optimal design of the insulator. The accurate computation of electric field distribution can be computed using the Finite element method (FEM). For this insulator, dimensions are very useful. 11kv Electric pole dimensions are shown in Fig 1 and Table1. Fig-2:11kV pin insulator Geometrical configurations 11kv pin insulator dimensions are shown in Fig 2. 11kv pin insulator design in FEM 2D software [9]. 2.2.1. ASSIGNING MATERIALS: As per the geometrical configurations, the insulator is designed by using FEMM 2D package. After designing, insulator materials like ceramic, steel, and air are assigned to the model with help of relative permittivity values. Insulator material properties are given in the table shown Table 2 and Fig2. After assigning materials to the model, the line to the ground voltage (i.e.,12/√3 =7kv) is applied to the energized high voltage end fitting and zero (0V) volts to the grounded end fitting of the insulator. TABLE 2: Material properties Particulars Material Relative permittivity value Insulator housing Ceramic 5.9 Electric pole Steel 1 Boundary surface Air 1 2.2.2. ASSIGNING 2D TRIANGULAR ELEMENTS: Then 2D Triangular elements are assigned to the insulator. Triangular elements at the HV end and ground end are as shown in Fig 2. The boundaries in the model need to be split into individual sections, referred to as boundary elements. The distribution, number, and shape of these elements are the key factors that determine the accuracy of the solution. FEM generally uses 2D elements for analysis purposes. Names of Insulator 1 and Insulator 2 and Insulator 3 are shown in Fig 2.
  • 3. International Research Journal of Engineering and Technology (IRJET) e-ISSN: 2395-0056 Volume: 09 Issue: 02 | Feb 2022 www.irjet.net p-ISSN: 2395-0072 © 2022, IRJET | Impact Factor value: 7.529 | ISO 9001:2008 Certified Journal | Page 766 2.2.3. ASSIGNING BOUNDARY CONDITIONS: After assigning boundary elements 2D triangular elements are generated throughout the mode. A FEM model design for the clean distribution assuming that no tree/creeper is surrounding the pole. The results are showing that the stress is now varied between the top of the tree to the transmission line by treating the tree as the ground is as shown in Fig.3.By running the model electric field contours developed. In this electric field contours, the HV end is shown red color and the ground end is shown blue color. The rated line-to-ground voltage is 12/√3=7kV to the high voltage end fittings. Zero volts to the grounded end fitting/Air is assigned as a surrounding medium. After assigning boundary elements 2D triangular elements are generated throughout the mode. Fig-3: Electric field contours Electric field contours are as shown in Fig 3. After assigning materials to the model, the line to the ground voltage (i.e 12/√3 =7kv) is applied to the energized high voltage end fitting and zero (0V) volts to the grounded end fitting of the insulator. Field analysis results of 11kv electric pole with cross-arm. Electric fields along the insulators are plotted. By running the model electric field contours developed. In this electric field contours, the HV end is shown red color and the ground end is shown blue color The insulator top is given as high voltage and the insulator ground is given ground voltage. The Fig. 3 shows different colors in which each color corresponds to a different voltage level. In the Fig. 4, a graph is plotted between the voltage across insulator and the length of insulator(mm). This Fig. 4 is also known as Voltage Distribution along insulator length. Fig-4: Voltage Distribution along the insulator In Fig. 5, the Electric field Distribution along insulator1 has been presented. Maximum Electric field Distribution along insulator 1 is 8.53×e4 V/mm. Fig-5: Electric field Distribution along insulator 1 In this Fig6 graph drawn between Electric field intensity vs length of insulator(mm). The maximum Electric field Distribution along insulator 2 is 7.67×e4 (v/mm).
  • 4. International Research Journal of Engineering and Technology (IRJET) e-ISSN: 2395-0056 Volume: 09 Issue: 02 | Feb 2022 www.irjet.net p-ISSN: 2395-0072 © 2022, IRJET | Impact Factor value: 7.529 | ISO 9001:2008 Certified Journal | Page 767 Fig-6: Electric field Distribution along insulator 2 In this Fig7 graph is drawn between Electric field intensity vs length of insulator(mm). Maximum Electric field Distribution along insulator3 is 2.47×e5 (v/mm). Fig-7: Electric field Distribution along insulator3 Table 3: Electric Field analysis Results S.NO FIELD REGION ELECTRIC FIELD INTENSTY(V/mm) 1. Insulator1 8.53×e4 2. Insulator2 7.67×e4 3. Insulator3 2.47×e4 The maximum Electric field intensity on the surface of insulator 1, insulator 2 and insulator 3 are presented in Table 3. The comparison bar chart of EFA results for 11kv electric pole with clean distribution is shown in Fig 8. Fig-8: Electric field Results analysis 2.3. Case2. For Unclean Distribution Line: The 11kV, three-phase distribution feeder, metallic cross arms and pin insulator was designed by using FEMM 2D software as per geometrical configurations shown in Fig 1. The geometrical configurations 11kv pin insulator dimensions are shown in Fig 2. If the vegetation growth increased in steps of 10% from 40% to 100%, the electric field was found to be increasing.  Tree height increased 40% of the total height of electric pole height = 4 m.  Tree height increased 50% of the total height of electric pole height = 5 m.  Tree height increased 60% of the total height of electric pole height = 6 m.  Tree height increased 70% of the total height of electric pole height = 7 m.  Tree height increased 80% of the total height of electric pole height = 8 m.  Tree height increased 90% of the total height of electric pole height = 9 m.  Tree height increased 100% of the total height of electric pole height = 10 m. A FEM model design for the clean distribution assuming that no tree/creeper is surrounding the pole has been already presented in section 2.2. For a 50% grown tree/shrubbery, analysis has been primarily carried out in the FEM model. The results are showing that the stress is now varied between the top of the tree to the transmission line by treating the tree as the ground. is as shown in Fig. 9 i.e., the ground plane has increased increasing the electric field stress [1].
  • 5. International Research Journal of Engineering and Technology (IRJET) e-ISSN: 2395-0056 Volume: 09 Issue: 02 | Feb 2022 www.irjet.net p-ISSN: 2395-0072 © 2022, IRJET | Impact Factor value: 7.529 | ISO 9001:2008 Certified Journal | Page 768 Fig-9: Electric field contours Electric field contours are as shown in Fig 9. After assigning materials to the model, the line to the ground voltage (i.e 12/√3 =7kv) is applied to the energized high voltage end fitting and zero (0V) volts to the grounded end fitting of the insulator. Field analysis results of 11kv electric pole with cross arm. Electric fields along the insulators are plotted. By running the model electric field contours developed. In this electric field contours, the HV end is shown red color and the ground end is shown blue color. The insulator top is given as high voltage and the insulator ground is given ground voltage. In this Fig 9 shows different colors corresponds to its voltage intensity. Fig-10: Voltage Distribution along insulator1 If the vegetation growth increased in steps of 10% from 40% to 100%, the electric field was found to be increasing. a. Electric field Distribution along insulator2 with 40% of tree height increase In the Fig10.1, the graph is drawn between Electric field intensity vs length of insulator(mm). Maximum Electric field Distribution along insulator 2 with 40% of tree height increase is 7.75×e4 (v/mm). Fig-10.1: Electric field Distribution along insulator 2 with 40 % Tree height b. Electric field Distribution along insulator2 with 50% of tree height increase: In the Fig 10.2, the graph is drawn between Electric field intensity vs length of insulator(mm). Maximum Electric field Distribution along insulator2 with 50% of tree height increase is 7.80×e4 (v/mm). Fig-10.2: Electric field Distribution along insulator 2 with 50 % Tree Height c. Electric field Distribution along insulator2 with 60% of tree height increase: In this Fig10.3 graph drawn between Electric field intensity vs length of insulator(mm). Maximum Electric field Distribution along insulator2 with 60% of tree height increase is 7.90×e4 (v/mm).
  • 6. International Research Journal of Engineering and Technology (IRJET) e-ISSN: 2395-0056 Volume: 09 Issue: 02 | Feb 2022 www.irjet.net p-ISSN: 2395-0072 © 2022, IRJET | Impact Factor value: 7.529 | ISO 9001:2008 Certified Journal | Page 769 Fig-10.3. Electric field Distribution along insulator 2 with 60 % Tree Height d. Electric field Distribution along insulator2 with 70% of tree height increase: In the Fig10.4 graph drawn between Electric field intensity vs length of insulator(mm). Maximum Electric field Distribution along insulator2 with 70% of tree height increase is 8.00×e4 (v/mm). Fig-10.4: Electric field Distribution along insulator 2 with 70 % Tree Height e. Electric field Distribution along insulator2 with 80% of Tree height increase: In this Fig10.5 graph is drawn between Electric field intensity vs length of insulator(mm). Maximum Electric field Distribution along insulator 2 with 80% of tree height increase is 8.04×e4 (v/mm). Fig-10.5: Electric field Distribution along insulator-2 with 80 % Tree Height f. Electric field Distribution along insulator2 with 90% of tree height increase: The Maximum Electric Field Distribution along insulator2 with 90% of tree height increase is 8.20×e4 (v/mm) as shown in Fig. 10.6. Fig-10.6: Electric field Distribution along insulator 2 with 90 % Tree Height g. Electric field Distribution along insulator2 with 100% of tree height increase: Maximum Electric field Distribution along insulator2 with 100% of tree height increase is 8.40×e4 (V/mm) as shown in Fig. 10.7. Fig-10.7: Electric field Distribution along insulator 2 with 100 % Tree Height.
  • 7. International Research Journal of Engineering and Technology (IRJET) e-ISSN: 2395-0056 Volume: 09 Issue: 02 | Feb 2022 www.irjet.net p-ISSN: 2395-0072 © 2022, IRJET | Impact Factor value: 7.529 | ISO 9001:2008 Certified Journal | Page 770 Table 4: Electric Field Intensity (vs) Percentage Increasing tree height (%) S.NO Percentage Increasing tree height ELECTRIC FIELD INTENSTY(V/mm) 1 40% 7.75×e4 2 50% 7.80×e4 3 60% 7.90×e4 4 70% 8.00×e4 5 80% 8.04×e4 6 90% 8.20×e4 7. 100% 8.40×e4 The comparison of EFA results for 11kv electric pole for various tree heights is presented in Fig 11. Fig-11: Electric Field Results Analysis 3. Electric field analysis of 132kv Overhead transmission line tower (Case-3): In this case 3, the electric field distributions and voltage in 132kv overhead transmission line tower studied Fem 2D software. 132kv overhead transmission line tower with polymeric was designed by using Fem 2D software as per geometrical configuration shown in table 5 and Fig 12. 3.1. Geometrical Configurations: The electric field distribution in and around the insulator is necessary for the optimal design of the insulator. The accurate computation of electric field distribution can be computed using the Finite element method (FEM). For this insulator, dimensions are very useful. Insulator dimensions are tabulated in table 5. Fig- 12: Geometric Configuration of the Tower Table 5: Geometrical ConFigurations-132kV polymeric insulator S.no Critical Regions Dimensions in mm 1. Insualtor length 1060 2. Diameter of bigger shed 135 3. Diameter of smaller shed 105 4. FRP Rod length 960 5. Core Diameter 28 6. No Discs bigger shed 17 7. No Discs smaller shed 16 8. Pitch 52 9. FRP diameter 20 10. Thickness shed 3 3.2. Design of 132kV Overhead transmission line tower: In this case3, the electric field distributions and voltage in 132kv overhead transmission line tower studied Fem 2d software.132kv overhead transmission line tower with polymeric was designed by using Fem 2d software as per geometrical configuration shown in Fig12. 3.3. ASSIGNING MATERIALS: As per the geometrical configurations, the insulator is designed by using FEMM 2D package. After designing, insulator materials like SiR, FRP, and steel are assigned to the model with help of relative permittivity values. Insulator material properties are given in the table shown table 6.
  • 8. International Research Journal of Engineering and Technology (IRJET) e-ISSN: 2395-0056 Volume: 09 Issue: 02 | Feb 2022 www.irjet.net p-ISSN: 2395-0072 © 2022, IRJET | Impact Factor value: 7.529 | ISO 9001:2008 Certified Journal | Page 771 Table 6: Material properties Particulars Material Relative permittivity value Insulator housing and weather sheds Silicone 3 FRP Rod Fibre glass 5 Tower Steel 1 Boundary surface Air 1 The rated line-to-ground voltage as 145/√3=83.71kV to the high voltage end fitting. Zero volts to the grounded end fitting. Air is assigned as a surrounding medium. Fig-13: Electric field contours Then 2D triangular elements are assigned to the insulator. Electric field contours are as shown in Fig 13. By running the model electric field contours developed. In this electric field contours HV, the end is shown red color, and the ground end is shown blur color. The insulator top is given as high voltage and the insulator ground is given ground voltage. In this Fig 13 shows different colors & each color shows different voltages.132Kv overhead transmission line bottom of the tower is grounded shown blue color in Fig13. 3.4. ELECTRIC FIELD DISTRIBUTION ALONG INSULATOR: Fig-14: Electric field Distribution along Insulator1 Electric field distribution along the surface of insulator1 is shown in Fig 18. The rated line-to-ground voltage as 145/√3=83.71kV to the high voltage end fitting. Zero volts to the grounded end fitting/Air is assigned as a surrounding medium. Electric field distribution along the surface of insulator1 is shown in Fig 14. 132Kv overhead transmission tower is grounded shown blue color in Fig 14. 3.5. ELECTRIC FIELD LINES DIRECTION: Fig-15: Electric field lines direction
  • 9. International Research Journal of Engineering and Technology (IRJET) e-ISSN: 2395-0056 Volume: 09 Issue: 02 | Feb 2022 www.irjet.net p-ISSN: 2395-0072 © 2022, IRJET | Impact Factor value: 7.529 | ISO 9001:2008 Certified Journal | Page 772 Electric field lines direction shown in Fig 15. This Figure shows Electric field lines flow from hv end to ground end. 3.6. EQUIPOTENTIAL LINES: Fig-16: Equipotential lines direction Equipotential lines direction shown in Fig 16. This, the Figure shows Equipotential lines flow from hv end to ground end 3.7. VOLTAGE DISTRIBUTION ALONG INSULATOR1: Fig-17.1: Voltage Distribution along insulator1 In this Fig17.1 graph drawn between voltage vs length of insulator(mm). Maximum Voltage Distribution along insulator3 is 8.00×e4 (v/mm). 3.8. VOLTAGE DISTRIBUTION ALONG INSULATOR2 In the Fig17.2 graph drawn between voltage vs length of insulator(mm). Maximum Voltage Distribution along insulator3 is 8.26×e4 (v/mm). Fig-17.2: Voltage Distribution along insulator2 3.9. VOLTAGE DISTRIBUTION ALONG INSULATOR3: Fig-17.3: Voltage Distribution along insulator3 Maximum Voltage Distribution along insulator3 is 8.26×e4 (v/mm). In this Fig17.3 graph drawn between voltage vs length of insulator(mm). 3.10. ELECTRIC FIELD DISTRIBUTION ALONG INSULATOR1 Maximum Electric field Distribution along insulator1 is 1.74×e5 (v/mm). In this Fig18 graph drawn between Electric field intensity vs length of insulator(mm).
  • 10. International Research Journal of Engineering and Technology (IRJET) e-ISSN: 2395-0056 Volume: 09 Issue: 02 | Feb 2022 www.irjet.net p-ISSN: 2395-0072 © 2022, IRJET | Impact Factor value: 7.529 | ISO 9001:2008 Certified Journal | Page 773 Fig-18: Electric field Distribution along insulator1 3.11. ELECTRIC FIELD DISTRIBUTION ALONG INSULATOR2: Maximum Electric field Distribution along insulator2 is 2.28×e5 (v/mm). In this Fig. 19 graph drawn between Electric field intensity vs length of insulator(mm). Fig-19: Electric field Distribution along insulator2 3.12. ELECTRIC FIELD DISTRIBUTION ALONG INSULATOR 3: Fig-20: Electric field Distribution along insulator3 Maximum Electric field Distribution along insulator3 is 2.47×e5 (v/mm). In this Fig20 graph drawn between Electric field intensity vs length of insulator(mm). EFA results for 132kV overhead transmission line tower insulator1, insulator2 & insualtor3 are shown in table 7. Table 7: EFA results for 132kV overhead transmission line tower S.NO FIELD REGION ELECTRIC FIELD INTENSTY (V/mm) 1. Insulator1 1.74×e5 2. Insulator2 2.28×e5 3. Insulator3 2.47×e5 Table 8: Voltage results for 132kV overhead transmission line tower S.NO FIELD REGION VOLTAGE (Volt) 1. Insulator1 8.00×e4 2. Insulator2 8.26e4 3. Insulator3 8.26×e4 3.13. EFA RESULTS COMPARISION: Fig-21: Electric Field Results Analysis 3.14. VOLTAGE RESULTS COMPARISION: Fig-22: Voltage Results Analysis
  • 11. International Research Journal of Engineering and Technology (IRJET) e-ISSN: 2395-0056 Volume: 09 Issue: 02 | Feb 2022 www.irjet.net p-ISSN: 2395-0072 © 2022, IRJET | Impact Factor value: 7.529 | ISO 9001:2008 Certified Journal | Page 774 4. Electric field analysis of 220kv Overhead transmission line tower (Case - 4): In this case4, the electric field distributions and voltage in 220 kV overhead transmission line tower studied Fem 2d software.220kv overhead transmission line tower with polymeric was designed by using Fem 2d software as per geometrical configuration shown in Fig23. 4.1. Geometrical Configurations: The electric field distribution in and around the insulator is necessary for the optimal design of the insulator. The accurate computation of electric field distribution can be computed using the Finite element method (FEM). For this insulator, dimensions are very useful. Insulator dimensions are tabulated in table 9 and Fig 23. Fig-23: Geometric Configuration of the 220 kV Tower Table 9: Geometrical ConFigurations-220kV polymeric insulator S.no Critical Regions Dimensions in mm 1. 1. Insualtor length 2200 2. 2. Diameter of bigger shed 135 3. 3. Diameter of smaller shed 105 4. 4. FRP Rod length 2100 5. 5. Core Diameter 26 6. 6. No Discs bigger shed 46 7. 7. No Discs smaller shed 45 8. 8. Pitch 52 9. FRP diameter 20 10. Thickness shed 3 4.1.1. ASSIGNING MATERIALS As per the geometrical configurations, the insulator is designed by using FEMM 2D package. After designing, insulator materials like SiR, FRP, and steel are assigned to the model with help of relative permittivity values. Insulator material properties are given in the table8. 4.2. ASSIGNING 2D TRIANGULAR ELEMENTS: The boundaries in the model need to be split into individual sections, referred to as boundary elements. The distribution, number, and shape of these elements are the key factors that determine the accuracy of the solution. FEM generally uses 2D elements for analysis purpose purposes. 4.3. ASSIGNING BOUNDARY CONDITIONS: The rated line-to-ground voltage is 220/√3=142kV to the high voltage end fittings. Zero volts to the grounded end fitting/Air is assigned as a surrounding medium. After assigning boundary elements 2D triangular elements are generated throughout the mode. In this electric field contours HV, the end is shown red color, and the ground end is shown blue color. The insulator top is given as high voltage and the insulator ground is given ground voltage. In this Fig 9 shows different colors. Each colors shows different voltages shown in Fig24. 220Kv overhead transmission line bottom of the tower is grounded shown blue color in Fig24. 4.4. Electric field contours: Fig-24: Electric field contours
  • 12. International Research Journal of Engineering and Technology (IRJET) e-ISSN: 2395-0056 Volume: 09 Issue: 02 | Feb 2022 www.irjet.net p-ISSN: 2395-0072 © 2022, IRJET | Impact Factor value: 7.529 | ISO 9001:2008 Certified Journal | Page 775 4.5. ELECTRIC FIELD DISTRIBUTION ALONG INSULATOR1: Fig-25: Electric field Distribution along insulator1 Electric field Distribution along the surface of insulator1 is shown in Fig 25. The rated line-to-ground voltage is 220/√3=142kV to the high voltage end fittin. Zero volts to the grounded end fittingAir is assigned as a surrounding medium. 4.6. VOLTAGE DISTRIBUTION ALONG INSULATOR1: Fig-26.1: Voltage Distribution along insulator1 Maximum Voltage Distribution along insulator1 is 2.56×e5 (v/mm). In this Fig26.1 graph drawn between voltage vs length of insulator(mm). 4.7. VOLTAGE DISTRIBUTION ALONG INSULATOR2 Fig-26.2: Voltage Distribution along insulator2 Maximum Voltage Distribution along insulator2 is 2.56×e5 (v/mm). In this Fig26.2 graph drawn between voltage vs length of insulator(mm). 4.8. VOLTAGE DISTRIBUTION ALONG INSULATOR3: Fig-26.3: Voltage Distribution along insulator3 Maximum Voltage Distribution along insulator3 is 2.56×e5 (v/mm). In this Fig26.3 graph drawn between voltage vs length of insulator(mm). 4.9. ELECTRIC FIELD DISTRIBUTION ALONG INSULATOR1 Fig-27.1: Electric field Distribution along insulator1
  • 13. International Research Journal of Engineering and Technology (IRJET) e-ISSN: 2395-0056 Volume: 09 Issue: 02 | Feb 2022 www.irjet.net p-ISSN: 2395-0072 © 2022, IRJET | Impact Factor value: 7.529 | ISO 9001:2008 Certified Journal | Page 776 Maximum Electric field Distribution along insulator1 is 2.49×e5 (v/mm). In this Fig27.1 graph is drawn between Electric field intensity vs length of insulator(mm). 4.10. ELECTRIC FIELD DISTRIBUTION ALONG INSULATOR 2: Fig-27.2: Electric field Distribution along insulator2 Maximum Electric field Distribution along insulator2 is 2.56×e5 (v/mm). In this Fig27.2 graph drawn between Electric field intensity vs length of insulator(mm). 4.11. ELECTRIC FIELD DISTRIBUTION ALONG INSULATOR3: Fig-27.3: Electric field Distribution along insulator3 From Fig. 27.3, the Maximum Electric field Distribution along insulator3 is 2.90×e5 (v/mm). Table 11: EFA results for 220 kV overhead transmission line tower S.NO FIELD REGION ELECTRIC FIELD INTENSTY (V/mm) 1. Insulator1 2.49×e5 2. Insulator2 2.56×e5 3. Insulator3 2.90×e5 Table 12: Voltage results for 220 kV overhead transmission line tower S.NO FIELD REGION VOLTAGE (Volt) 1. Insulator1 1.30×e5 2. Insulator2 1.33×e5 3. Insulator3 1.33×e5 4.12. EFA RESULTS COMPARISION: Fig-28: Electric Field Results Analysis 4.13. VOLTAGE RESULTS COMPARISON: Fig-29: Voltage Results Analysis 5. CONCLUSION: In this project, an electric field Analysis has been carried out and an 11 kV Distribution system. To enhance the study, three 11kv insulators are chosen and tests are conducted under clean and unclean environments. Later on, the study is extended to include the effects of shrubbery, we have chosen different levels of tree heights concerning the pole heights. The effectiveness of these analyses is proven by taking 132 kV and 220 kV feeders that are powering our 11 kV distribution system. By series of tests, it is confirmed that the shrubbery has the least effect on the Extra High voltage transmission systems due to their humungous tower heights. Thus the study is constricted to 11 kV system Electric field distribution under four cases. By comparison, case1 and case 2 results in electric field stress more in case2.
  • 14. International Research Journal of Engineering and Technology (IRJET) e-ISSN: 2395-0056 Volume: 09 Issue: 02 | Feb 2022 www.irjet.net p-ISSN: 2395-0072 © 2022, IRJET | Impact Factor value: 7.529 | ISO 9001:2008 Certified Journal | Page 777 In the case2 of the electric field fields, stress increases with increasing vegetation growth. In case2 vegetation growth is 10% electric field stress is less. If the vegetation growth increased in steps of 10% from 40% to 100%, the electric field was found to be increasing. At vegetation growth of 100% pole height, the electric field stresses are very high. In case 3, three insulators of the same ratings are compared. The electric field stress is high in insulator3 compared to insulator 1 and insulator 2. In case 4 electric field stress is high in insulator3 compared to insualtor1 and insulator 2. From this testing and simulation of electric field analysis, it is found that electric field stress is different even for insulators of the same rating and manufacturers. It is also affected by shrubbery and its height compared to pole height. From these tests, it is confirmed that shrubbery is a minor player in electric field stress of 132 kV and greater voltages due to high tower heights. Its effects are high for distribution systems of voltage 11 kV and under as their cross arms may be accessible near shrubbery. REFERENCES [1]S.Devabhaktuni, H. Shankar Jain and P. K. Vujjin, "Impact of Shrubbery in Rural Transmission and Distribution Networks," 2017 IEEE International Conference on Computational Intelligence and Computing Research (ICCIC), 2017, pp. 1-5, DOI DOI: 10.1109/ICCIC.2017.8524259. [2]Rao, M. Nageswara, V. S. N. K. Chaitanya, and P. Vijaya Haritha. "Study of Hydrophobicity Effect on 220kV Double Tension Insulator String Surface Using Finite Element Method." International Journal of Electronics and Communication Engineering 14, no. 3 (2020): 70-75. [3]Supriya Khedkar, Shilpa Kewate, Sneha Hirkane “Analysis and Design of 220kV transmission line tower with hot rolled and cold-formed cold-formed section” Volume 6, Issue 12, December-2015 [4]Z. G. Datsios, P. N. Mikropoulos, T. E. Tsovilis, V. T. Karakostas, and S. P. Mavidou “ESTIMATION OF THE MINIMUM BACKFLASHOVER CURRENT OF 150 AND 400 kV OVERHEAD TRANSMISSION LINES THROUGH ATP- EMTP SIMULATIONS: EFFECT OF THE LIGHTNING STROKE LOCATION ALONG LINE SPANS” August 26-30, 2019 [5]Rao, M. V. Durga, and K., K. Asokan and Kumar, R Ashok, Analysis of Electric Field on Composite Silicone Insulators Used in High Voltage Transmission Lines (October 2, 2019). Proceedings of International Conference on Advancements in Computing & Management (ICACM) 2019 [6]Zacharias G. Datsios, Pantelis N. Mikropoulos, Thomas E.Tsovilis “Estimation of the Minimum Shielding Failure Current Causing Flashover in Overhead Lines of the Hellenic Transmission System through ATP-EMTP Simulations” [7]Mr.M.V.DurgaRao.S aDr.K.AsokanbDr.R.Ashok Kumar “Analysis of Electric Field on Composite Silicone Insulators Used in High Voltage Transmission Lines” [8]C. Zacharias’s, S. M. Rowland, I. Cotton, V. Peesapati and D. Chambers, "Development of Electric-Field Stress Control Devices for a 132 kV Insulating Cross-Arm Using Finite-Element Analysis," in IEEE Transactions on Power Delivery, vol. 31, no. 5, pp. 2105-2113, Oct. 2016, DOI DOI: 10.1109/TPWRD.2015.2499795. [9]S. Deb, R. Ghosh, S. Dutta, S. Dalai, and B. Chatterjee, "Effect of humidity on leakage current of a contaminated 11 kV Porcelain Pin Insulator," 2017 6th International Conference on Computer Applications In Electrical Engineering-Recent Advances (CERA), 2017, pp. 215-219, DOI DOI: 10.1109/CERA.2017.8343329.