Utilization of System Generated LG Fault on Ground
Grid Mesh and Analysis of existing GGS using
IEEE 80-2000 and Finite Element Method
Akash Patel
Electrical Engineering
California State University Northridge
Northridge, USA
akash.patel.296@my.csun.edu
Professor Bruno Osorno
Electrical Engineering
California State University Northridge
Northridge, USA
bruno@csun.edu
Abstract—the 750kv substation is chosen for given particular
type of soil to design square ground grid mesh. By using line to
ground fault current generated on 750kv substation by ETAP
short circuit analysis, ground grid parameters are determined
using simple hand calculations and results are verified by
modeling same ground grid using ETAP ground grid system.
After getting general idea about effect on system generated fault
on GGS, system data from existing 50kv Rawat substation is
collected to verify all-important parameters are within the limit
or not. To evaluate important GGS parameters, mesh analysis is
carried out using both IEEE 80-2000 and Finite Element
Methods by using ETAP-12 GGS Module. Shortcoming in
existing mesh are highlighted by ETAP warning and alert dialog
box and remedial actions are suggested to rectify the problems.
Increase in fault current by expansion of substation is consider
with possible solution and optimization of ground grid mesh is
presented based on modern technology. Finally, comparison is
done between IEEE 80-2000 and FEM method to design GGS
and effect of ground grid area, number of conductors/rods and
spacing between conductors is explained by help of several case
study results.
Keywords— Ground Potential Rise, Step Voltage, Touch
Voltage, Ground Mesh, Electrical Transient Analysis Program,
Ground Grid System Module
I. INTRODUCTION
Under normal and faulty condition, grounding can carry
electrical currents into earth with maintaining operating and
equipment limits and protect person from danger of electrical
shock. After analyzing effects of electrical current on human
body, researchers have developed different IEEE standards for
earth resistance measurement, surface gradients, grid
conductors continuity, equipment grounding, cable routing,
cable sheath grounding, indoor installations, lighting
protection, current division, generating station grounding
practices, testing and different connections of grounding
system. Use of single electrode for grounding is not sufficient
for safe grounding. Rather than using single electrode if we use
grid, we can represent excellent grounding system. To protect
human from surface gradients when high current dissipated
into the earth, installation of grid with law resistant is required.
Horizontal ground grid can reduce danger of high step and
touch voltages on the earth surface by using only, when grid is
installed in narrow depth. For many installations where soil
resistivity change due to freezing or drying effect and
resistivity of lower soil remains constant, ground electrodes are
useful to stabilize the performance. So, in case of multilevel
soil, rods which are penetrating in low resistivity soil more
effectively dissipate fault currents. Installation of rods along
grid perimeter in uniform or high-to-low soil conditions can
moderate steep rise of surface gradient near peripheral meshes.
Sometimes size of substation is large or soil has high
resistivity. Rather than using large grounding system, we have
to use fraction of the land area for grounding purpose and then
all areas can be connected with each other by connecting rods.
Computer algorithms are based on modeling the individual
components comprising the grounding system, developing set
of equations which describe the interconnection of these
equipments, determine ground fault current flowing from each
component into the earth, calculating the potential at any
desired surface point due to all individual components-TAP
ground grid module is very useful software for design and
implementation of ground grid system and it utilizes Finite
Element Method,IEEE 80-1986, IEEE 80-2000, IEEE 665-
1995 methods of computation. Existing 500 kv Rawat
substation is design and analyze by ETAP-12 using IEEE 80-
2000 and Finite Element method and new 750 kv substation is
designed by using data from IEEE safety guide for substation
grounding and short circuit analysis of grid.
II. SHORT CIRCUIT ANALYSIS AND GROUND GRID SYSTEM
There are 9 buses,3 generators,3 transformers,6 transmission
lines and 3 loads are connected as shown in figure 1. After
creating line to ground fault on bus 5, E-TAP short circuit
analysis generate fault currents and voltages as shown in
circuit below.Design of square ground grid represented by
green area is possible for 750kv substation at bus 5 by
updating fault current value at bus 5 and we can easily verify
the results with ETAP software. System data for
bus,transmission lines,transformers and generators are
presented in Appendix A.
2
Figure 1 [5] developing grounding grid on faulted bus 5
ETAP give short-circuit result as shown in table 3.5.
Contribution Line to Ground Fault
From Bus To
Bus
%Voltage At
From
Bus kA
Symm.
rms
ID ID Va Vb Vc Ia 3
Bus5 Total 0 92.91 91.61 10.106 10.106
Bus4 Bus5 0.11 92.91 90.61 5.137 6.252
Bus7 Bus5 0.37 92.87 90.49 4.993 4.004
Table 1 short circuit result
So, 10.106 kA fault current is contribution of Bus 5 to whole
network.By using this fault current value we can design
square grid for Bus 5 by using simple equations as shown
below.data of square grid is presented in Appendix B.
a) Touch and Step criteria:
K= =-0.72
=
b) Determination of grid resistance:
c) Maximum grid current :
d) Ground Potential rise:
GPR=
e) Correction factors:
=1.225.
f) Spacing factors:
g) Mesh voltage:
h) Step voltage:
Result Summary:
Calculated Volts Tolerable Volts
Touch 3184.382 V 840.5836 V
Step 1452.7945 V 2696.2398 V
GPR
Table 2 hand calculation result summary
Here the maximum touch voltage exceeds the tolerable limits.
We can verify above result by ETAP. After updating the value
of and X/R from short circuit analysis,we can design
square ground grid by using ETAP as shown in figure 3.7.
3
Figure 2 top view of ETAP square ground grid
The result of ground grid analysis for square grid is shown in
figure 3.
Figure 3 results of ETAP GGS analysis
The value of touch, step voltages, GPR and are similar for
hand calculation as well as ETAP calculation. Even in both
cases calculated touch voltage is higher than tolerable limit.
III.IEEE 80-2000 METHODS CASE STUDIES
By using the same 9 bus power system,designing of 500kv
substation is possible at bus1 by using ETAP IEEE 80-2000
method as shown in figure 4 [5],
Figure 4[5] sample connection diagram for IEEE 80-2000 method grid
design
Actually ground grid system for 500kv substation is already
laid and functioning in Rawat substation,so existing data is
collected to verify whether all important parameters are with
in the described limits or not.The collected data from actual
substation are represented in Appendix C.
a) IEEE 80-2000 Method Case 1:
Initially after specifing surface material,soil resistivity and
depths for various layers in ETAP soil editor and selecting
weight of person, proper IEEE method and details of short
circuit current and fault duration by using ETAP GRD study
case editor and specifying conductor/ rod parameters for grid
and ground grid dimentions by using in ETAP IEEE group
editor with the data given in table 3 ,we can design and
analyze protection scheme for priliminary gound grid mesh by
finding ground potential rise,ground system resistance,touch
and step potentials using IEEE 80-2000 method.
Gri
d
Len
gth
(ft)
Numbe
r of
conduct
ors
Rod
Data
Conduc
tor
Size
AWG/k
cmil
De
pth
ft
ft
ft
In X
Directio
n
In Y
Direc
tion
Diam
eter
inch
Len
gth
ft
N
o
Of
Ro
ds
4/0 0.9
8
472.
44
32
8.0
8
14 10 0.472 6.56 50
Table 3[4] input ground grid parameters of IEEE 80-2000 method case 1.
The ground grid system is presented by a top view,a soil
view,a 3-D view for graphical arrangement of the conductors
and rods as shown in figures 5,6 and 7.the soil view is used to
edit the soil properties of the surface, top, and lower layers of
soil. The 3-D view is used for the three-dimensional display of
the ground grid which can be rotate or view by any angle. The
Top View is used to edit the ground conductors/rods of a
ground grid.
Figure 5 soil view of GGS case 1.
Figure 6. 3-D view of GGS case 1.
Figure 7 top view of GGS case 1.
4
The result of ground grid analysis case 1 is shown in figure 8.
Figure 8 results of case 1 analysis
As shown in figure 8, ground grid is not functioning properly
due to higher touch voltage and temperature rise than safer
limits. Moreover, either we should have to increase or
decrease area to design proper ground grid.
b)IEEE 80-2000 Method Case 2:
To overcome issue created in case 1, redesign of ground grid
system is possible by changing number of conductors and
number of rods as shown in table 4[4].
Gr
id
Le
ngt
h
(ft)
Number
of
conduct
ors
Rod Data
Conduc
tor
Size
AWG/k
cmil
De
pth
ft ft
ft
In X
Direct
ion
In Y
Dire
ctio
n
Diameter
inch
Len
gth
ft
N
o
Of
R
od
s
4/0 0.9
8
47
2.4
4
3
2
8.
0
8
20 16 0.598 6.5
6
54
Table 4 [4] input ground grid parameters of IEEE 80-2000 method case
2.
3-D View of grid and the results of ground grid analysis case
2 are shown in figure 9 and 10.
Figure 9. 3-D view of GGS case 2.
Figure 10 results of case 2 analysis
So, temperature rise issue can be solved by changing number
of conductors and rods. But, higher touch voltage and grid size
issues are still exist.
c)IEEE 80-2000 Method Case 3:
There is an expansion in actual substation by replacing old
power transformer with new one which increase fault current
from 40 A to 45 A.To fulfill this new requirement,changes are
required in ground grid mesh as shown in table 5[4].
Gri
d
Len
gth
(ft)
Numbe
r
Of
conduc
tors
Rod
Data
Condu
ctor
Size
AWG/
kcmil
D
ep
th
ft
ft ft
In X
Directi
on
In Y
Directi
on
Diamet
er
inch
Length
ft
No
Of
Ro
ds
4/0 0.
9
8
472.
44
328.
08
22 19 0.634 6.56 65
Table 5[4] input ground grid parameters of IEEE 80-2000 method case 3.
3-D View and the result of ground grid analysis case 3 is
shown in figure 11 and 12.
Figure 11. 3-D view of GGS case 3.
5
Figure 12 results of case 3 analysis
ETAP ground grid analyzer show warning signal related to
size of ground grid area and higher touch voltage than
allowable limit due to larger than 10000 sq.m grid area. So,
for safety purpose we have to minimize the grid area.
d)IEEE 80-2000 Method Case 4:
when ground grid mesh of this substation is designed , very
less methods for designing ground grid are available.In this
case study, new modern analysis and optimization techniques
are applied for ground grid design by using the details
presented in table 6 [4].
Gri
d
Le
ngt
h
(ft)
Numbe
r
Of
conduct
ors
Rod
Data
Con
duct
or
Size
AW
G/kc
mil
De
pth
ft ft ft
In X
Directio
n
In Y
Direction
Diam
eter
inch
Le
ngt
h
ft
No
Of
Ro
ds
4/0 2 393
.7
272
.31
25 23 0.63 6.5
6
42
Table 6[4] input ground grid parameters of IEEE 80-2000 method case 4.
3-D View and the results of ground grid analysis case 4 is
shown in figure 13 and 14.
Figure 13. 3-D view of GGS case 4.
Figure 14 results of case 4 analysis
By decreasing size of ground grid area and proper utilization
of ground conductors and rods,we can design ground grid
mesh which fullfill all required limits of touch potential,step
potential and temperature.
IV.FEM CASE STUDIES
Using the same data from Appendix C ,we can design ground
grid mesh for 500kv substation at bus 3 by using ETAP FEM.
Figure 15 [5] ground grid representation for FEM.
a)FEM Case 1:
By using ETAP ground grid Finite Element module and input
datas given in table 7[4], design and analyze of priliminary
ground grid design is possible.we can modify each individual
conductor/rod parameter by using FEM group editor and rod
editor.
Grid
Lengt
h
(ft)
Numb
er
Of
condu
ctors
Rod
Data
Con
duct
or
Size
AW
G/kc
mil
Dep
th
ft
ft ft
In X
Direct
ion
In Y
Directio
n
Diam
eter
inch
Len
gth
ft
No
Of
Ro
ds
4/0 0.9
8
472.4
4
328.08 20 15 0.472 6.56 50
Table 7[4] input ground grid parameters of FEM case 1.
6
Different views of ground grid are shown in figure 16, 17, 18.
Figure 16. 3-D view of GGS case 1.
Figure 17 top view of GGS case 1.
Figure 18 soil view of GGS case 1.
The result of ground grid analysis case 1 is shown in figure
19.
Figure 19 results of case 1 analysis
As shown in figure 19, ground grid is not functioning properly
due to higher touch voltage and temperature rise than safer
limits.3-D Plots are used only with the FEM method, and are
available for Absolute/Step/Touch Voltages. As shown in
figure 20, some voltages are quite high on voltage axies
represented by red colour in step potential profile,while in
case of touch potential as shown in figure 21, most of area is
green which represent that touch voltage is very low.
Figure 20 step potential profile of case 1.
Figure 21 touch potential profile of case 1.
Figure 22.absolute potential profile of case 1.
b)FEM Case 2:
To overcome issue created in case 1, redesign of ground grid
system is possible by changing number of conductors and
number of rods is as shown in table 8.[4].
Grid
Lengt
h
(ft)
Num
ber
Of
condu
ctors
Rod
Data
Cond
uctor
Size
AW
G/kc
mil
De
pth
ft
ft ft
In X
Direct
ion
In Y
Directio
n
Diam
eter
inch
Le
ng
th
ft
No
Of
Rods
4/0 0.9
8
472.4
4
328.0
8
25 20 0.614 6.
6
57
Table 8[4] input ground grid parameters of FEM case 2.
3-D View and The result of ground grid analysis case 2 is
shown in figure 23 and 24.
7
Figure 23. 3-D view of GGS case 2.
The result of ground grid analysis is shown in figure 5.13.
Figure 24.results of case 2 analysis
So, by changing number of conductors and rods, we resolve
temperature rise issue. But, still we need to focus on higher
touch voltage.3-D voltage profiles are shown in figure 25, 25
and 27.
Figure 25.step potential profile of case 2
Figure 26.touch potential profile of case 2
Figure 27.absolute potential profile of case 2
c) FEM Case 3:
There is an expansion in actual substation by replacing old
power transformer with new one which increase fault current
from 40 A to 45 A.To fulfill this new requirements ,
modifications are required in grid configuration as shown in
Table 9.[4].
Gri
d
Len
gth
(ft)
Num
ber
Of
cond
uctor
s
Rod
Dat
a
Co
ndu
ctor
Siz
e
A
W
G/k
cmi
l
De
pth
ft
ft ft
In X
Direc
tion
In Y
Directio
n
Dia
met
er
inch
Len
gth
ft
N
o
O
f
R
o
ds
4/0 0.9
8
472.
44
328.
08
29 26 0.64
2
6.8
9
6
0
Table 9.[4] input ground grid parameters of FEM case 3.
3-D View and the result of ground grid analysis case 3 is
shown in figure 28 and 29.
Figure 28. 3-D view of GGS case 3.
8
Figure 29.results of case 3 analysis
When I analyze the new designed grid after expanding
existing substation, E-TAP ground grid analyzer showing
warning signal related to higher touch voltage than allowable
limit.3-D voltage profiles are shown in figure 30, 31 and 32.
Figure 30.step potential profile of case 3.
Figure 31.touch potential profile of case 3.
Figure 32.absolute potential profile of case 3.
d)FEM Case 4:
when ground grid mesh of this substation is designed , very
less methods for designing ground grid are available.In this
case study,new modern analysis and optimization techniques
are applied for ground grid design by using the details
presented in Table 5.4. [4].
Gri
d
Len
gth
(ft)
Num
ber
Of
cond
uctor
s
Rod
Dat
a
Con
duct
or
Size
AW
G/k
cmil
Dep
th
ft
ft ft
In X
Direc
tion
In Y
Directi
on
Dia
mete
r
inch
Leng
th
ft
N
o
Of
Ro
ds
4/0 1.6
4
393.
7
272.31 26 22 0.47
2
6.56 50
Table 10.[4] input ground grid parameters of FEM case 4.
3-D View and ETAP ground analysis is presented in figure 33
and 34.
Figure 33. 3-D view of GGS case 4.
Figure 34.results of case 4 analysis
3-D view of different potential profiles are shown in figure 35,
36 and 37.
9
Figure 35.step potential profile of case 4.
Figure 36.touch potential profile of case 4.
Figure 37.absolute potential profile of case 4.
By decreasing size of ground grid area and proper utilization
of ground conductors and rods,I design ground grid mesh
which fullfill all required limits of touch potential,step
potential and temperature.
V. CONCLUSION
From the result of ETAP simulation on several case studies,
we can derive below aspects, magnitude of touch potential,
step potential, absolute potential, and ground resistance
decrease with increase in grid area. So, it’s better to use larger
grid in the area where land is cheap. Effect of spacing on touch
and step potential is opposite. If we reduce the spacing between
conductors, mesh potential decrease, while step potential may
be increase and effect of mesh potential is severe than step
potential. The effect of increasing conductors can be varied for
different cases, but mainly installation of horizontal conductors
decreases the touch potential. Normally if we install more
number of vertical rods, temperature rise, mesh potential,
ground impedance decrease. Simulated results are nearer to
actual value by using IEEE 80-2000 and FEM method; in
addition results are more accurate than hand calculation ETAP
simulate ground grid system within a second, while for FEM
method E-TAP took around 5-6 minutes.so, we can do faster
calculation by using IEEE 80-2000 method compare to FEM
method. Ground grid design using FEM is costlier than IEEE
80-2000 method because greater number of conductors and
rods are required in FEM compare to IEEE 80-2000 For the
same size grid. Mesh designed by FEM method will be more
durable, long lasting and have ability to withstand the
excessive fault currents more effectively. In FEM method we
can modify the data for individual conductor or rod by
conductor/rod editor, while in IEEE 80-2000 method we can’t
change data for individual conductor/rod.
VI.BIBLIOGRAPHY
[1] Design analysis and optimization of ground grid mesh of extra high
voltage substation using an intelligent software.
[2] IEEE guide for safety in AC substation grounding.
[3] IEEE guide for measuring earth resistivity, ground impedance and earth
surface potentials of a grounding system.
[4] A comparison of ground grid mesh design and optimization for 500kv
substation using IEEE 80-2000 and finite element methods.
[5] Transient stability analysis of IEEE 9 bus electric power system.
[6] Engineering design and rapid prototyping.
[7] Introduction to finite element modeling.
10
Appendix A. 9 bus system data
2-Winding Transformer Input Data:
T/f Rating Phase Shift
ID MVA Prim
kV
Sec kV %Z X/R Type Angle
T1 1000 750 500 10 34.1 Dyn 30
T2 1000 250 750 10 34.1 yNd 30
T3 1000 500 750 10 34.1 yNd -30
Synchronous Generator Input Data:
Ra
tin
g
Pos
itie
Impe
dance
Zero
Seq.
Impe
danc
e
ID M
VA
k
V
RP
M
X’/
R
%R %
Xd’
X/R %R0 %
X0
Ge
n1
772
.53
2
50
0
1800 19 1 28 19 0.368 7
Ge
n2
163
0.8
15
25
0
1800 19 1 28 19 0.368 7
Ge
n3
857
.11
4
45
0
1800 19 1 28 19 0.368 7
Bus Input Data:
Bus Initial Voltage
ID Type Nom kv Base kv %Mag Ang
Bus 1 Swing. 500 500 100 0
Bus 2 Gen. 250 250 100 0
Bus 3 Gen. 500 500 90 60
Bus 4 Load 750 750 100 30
Bus 5 Load 750 750 100 30
Bus 6 Load 750 750 100 30
Bus 7 Load 750 750 100 30
Bus 8 Load 750 750 100 30
Bus 9 Load 750 750 100 30
Line Input Data:
Li
ne
Leng
th
Ohms
per
phase
ID Adj(f
t)
R1 X1 Y1 R0 X0 Y0
Lin
e 1
5280 0.00
3219
7
0.0174
242
0 0.00240
9
0.01647
73
0
Lin
e 2
5280 0.00
7364
0.0321
97
0.000
0001
0.00928
03
0.05113
64
0.0000
001
Lin
e 3
5280 0.00
2253
8
0.0190
909
0 0.00452
65
0.17196
97
0
Lin
e 4
5280 0.00
1893
9
0.0304
924
0 0.00378
79
0.01136
36
0
Lin
e 5
5280 0.00
6060
6
0.0136
364
0.000
0001
0.05909
09
0.02670
46
0.0000
001
Lin
e 6
5280 0.00
0947
0.0136
364
0 0.06174
2
0.00984
85
0.0000
001
Appendix B.
Design data for 750 kv substation:
S
r.
N
o.
Description of Parameter Value
1. soil resistivity ( ⍴) 400 Ω m
2. Crushed rock resistivity 2500 Ω m
3. Thickness of crushed rock 0.102 m
4. Available grounding area (A) 70 m*70 m=4900
5. depth of grid burial (h) 0.5 m
6. Total length of buried conductor
( )
2*11*70=1540m
7. Current devision factor( ) 0.6
8. Fault current from E-TAP short
circuit analysis( )
10106 A
In design, D =7 m, =0.5 s, =1.0, n=11, d=0.01 is used.
Appendix C.
Design data for 500 kv substation:
Sr.
No.
Description of Parameter Value
1. Level of Voltage 500 KV
2. Maximum Fault Current 40 KA
3. Ground Grid Mesh Area 144 x 100 m2
4. Ground Grid Horizontal Distance 144m
5. Ground Grid Mesh Vertical
Distance
100m
6. Horizontally Installed Conductors 14
7. Vertically Installed Conductors 10
8. Conductors Size 4/0
9. Conductors Type Copper Annealed Soft Drawn
10. Maximum Temperature of
Conductors
40 °C
11. Rods Installed in Vertical Direction 50
12. Rod Diameter of Vertical Rods 1.2 centimeter
13. Rod Steel Rod Copper Clad
14. Duration of Fault 1 second
15. Temperature Outside -5 – 50 °C
16. Temperature of Rod 40 °C
17. X/Rratio Reactance over Resistance 50
18. Person Weight 50 kg
19. Soil Type at Surface Gravel
20. Resistivity 9976 Ω.m
21. Height 0.2m
22. Top Soil Moist Layer
23. Resistivity 130 Ω.m
24. Height 2m
25. Soil Bottom Layer Type Moist Soil
26. Soil Bottom Layer Resistivity 200 Ω.m
27. Soil Bottom Layer Height Infinity
28. Level of Fault in Relation to Earth
Sr
60
29. Increase in Fault Level Cp 100

More Related Content

What's hot

Improving Transient Stability of the Nigerian 330kv Transmission System on Aj...
Improving Transient Stability of the Nigerian 330kv Transmission System on Aj...Improving Transient Stability of the Nigerian 330kv Transmission System on Aj...
Improving Transient Stability of the Nigerian 330kv Transmission System on Aj...IJAEMSJORNAL
 
Vector control of wind driven self excited induction generator connected to g...
Vector control of wind driven self excited induction generator connected to g...Vector control of wind driven self excited induction generator connected to g...
Vector control of wind driven self excited induction generator connected to g...Alexander Decker
 
11.vector control of wind driven self excited induction generator connected t...
11.vector control of wind driven self excited induction generator connected t...11.vector control of wind driven self excited induction generator connected t...
11.vector control of wind driven self excited induction generator connected t...Alexander Decker
 
Local Backup Protection Algorithm For HVDC Grids
Local Backup Protection Algorithm For HVDC GridsLocal Backup Protection Algorithm For HVDC Grids
Local Backup Protection Algorithm For HVDC Gridsyash Natani
 
Voltage Profile Improvement using Switched Capacitors: Case of Single Wire Ea...
Voltage Profile Improvement using Switched Capacitors: Case of Single Wire Ea...Voltage Profile Improvement using Switched Capacitors: Case of Single Wire Ea...
Voltage Profile Improvement using Switched Capacitors: Case of Single Wire Ea...IJMERJOURNAL
 
Kenny samaroo methodology of selection, setting and analysis of anti-islandin...
Kenny samaroo methodology of selection, setting and analysis of anti-islandin...Kenny samaroo methodology of selection, setting and analysis of anti-islandin...
Kenny samaroo methodology of selection, setting and analysis of anti-islandin...Kenny Samaroo
 
Control for Grid-Connected and Intentional Islanding Operations of Distribute...
Control for Grid-Connected and Intentional Islanding Operations of Distribute...Control for Grid-Connected and Intentional Islanding Operations of Distribute...
Control for Grid-Connected and Intentional Islanding Operations of Distribute...Asoka Technologies
 
Three Phase AC to DC Boost Converter Using D-Q Theory
Three Phase AC to DC Boost Converter Using D-Q TheoryThree Phase AC to DC Boost Converter Using D-Q Theory
Three Phase AC to DC Boost Converter Using D-Q TheoryIRJET Journal
 
IRJET- A Implementation of High Speed On-Chip Monitoring Circuit by using SAR...
IRJET- A Implementation of High Speed On-Chip Monitoring Circuit by using SAR...IRJET- A Implementation of High Speed On-Chip Monitoring Circuit by using SAR...
IRJET- A Implementation of High Speed On-Chip Monitoring Circuit by using SAR...IRJET Journal
 
anti islanding technology(passive)
anti islanding technology(passive)anti islanding technology(passive)
anti islanding technology(passive)minu Yacob
 
Power Quality Enhancement using Fuzzy Control Based DVR
Power Quality Enhancement using Fuzzy Control Based DVRPower Quality Enhancement using Fuzzy Control Based DVR
Power Quality Enhancement using Fuzzy Control Based DVRIRJET Journal
 
Modeling and simulation of three phases cascaded H-bridge grid-tied PV inverter
Modeling and simulation of three phases cascaded H-bridge grid-tied PV inverterModeling and simulation of three phases cascaded H-bridge grid-tied PV inverter
Modeling and simulation of three phases cascaded H-bridge grid-tied PV inverterjournalBEEI
 
Reliability analysis of pmu using hidden markov model
Reliability analysis of pmu using hidden markov modelReliability analysis of pmu using hidden markov model
Reliability analysis of pmu using hidden markov modelamaresh1234
 
Analysis of CMOS Comparator in 90nm Technology with Different Power Reduction...
Analysis of CMOS Comparator in 90nm Technology with Different Power Reduction...Analysis of CMOS Comparator in 90nm Technology with Different Power Reduction...
Analysis of CMOS Comparator in 90nm Technology with Different Power Reduction...IJECEIAES
 
Stability study of a multi machine system using modified robust co ordinate a...
Stability study of a multi machine system using modified robust co ordinate a...Stability study of a multi machine system using modified robust co ordinate a...
Stability study of a multi machine system using modified robust co ordinate a...IAEME Publication
 

What's hot (20)

RPI_Research_Overview
RPI_Research_OverviewRPI_Research_Overview
RPI_Research_Overview
 
C1103031822
C1103031822C1103031822
C1103031822
 
Improving Transient Stability of the Nigerian 330kv Transmission System on Aj...
Improving Transient Stability of the Nigerian 330kv Transmission System on Aj...Improving Transient Stability of the Nigerian 330kv Transmission System on Aj...
Improving Transient Stability of the Nigerian 330kv Transmission System on Aj...
 
E1103032933
E1103032933E1103032933
E1103032933
 
Vector control of wind driven self excited induction generator connected to g...
Vector control of wind driven self excited induction generator connected to g...Vector control of wind driven self excited induction generator connected to g...
Vector control of wind driven self excited induction generator connected to g...
 
11.vector control of wind driven self excited induction generator connected t...
11.vector control of wind driven self excited induction generator connected t...11.vector control of wind driven self excited induction generator connected t...
11.vector control of wind driven self excited induction generator connected t...
 
Local Backup Protection Algorithm For HVDC Grids
Local Backup Protection Algorithm For HVDC GridsLocal Backup Protection Algorithm For HVDC Grids
Local Backup Protection Algorithm For HVDC Grids
 
Voltage Profile Improvement using Switched Capacitors: Case of Single Wire Ea...
Voltage Profile Improvement using Switched Capacitors: Case of Single Wire Ea...Voltage Profile Improvement using Switched Capacitors: Case of Single Wire Ea...
Voltage Profile Improvement using Switched Capacitors: Case of Single Wire Ea...
 
Kenny samaroo methodology of selection, setting and analysis of anti-islandin...
Kenny samaroo methodology of selection, setting and analysis of anti-islandin...Kenny samaroo methodology of selection, setting and analysis of anti-islandin...
Kenny samaroo methodology of selection, setting and analysis of anti-islandin...
 
Fractional PID controlled cascaded flyback switched mode power supply with en...
Fractional PID controlled cascaded flyback switched mode power supply with en...Fractional PID controlled cascaded flyback switched mode power supply with en...
Fractional PID controlled cascaded flyback switched mode power supply with en...
 
Control for Grid-Connected and Intentional Islanding Operations of Distribute...
Control for Grid-Connected and Intentional Islanding Operations of Distribute...Control for Grid-Connected and Intentional Islanding Operations of Distribute...
Control for Grid-Connected and Intentional Islanding Operations of Distribute...
 
EEE M.E/M.Tech 2014-2015
EEE M.E/M.Tech 2014-2015EEE M.E/M.Tech 2014-2015
EEE M.E/M.Tech 2014-2015
 
Three Phase AC to DC Boost Converter Using D-Q Theory
Three Phase AC to DC Boost Converter Using D-Q TheoryThree Phase AC to DC Boost Converter Using D-Q Theory
Three Phase AC to DC Boost Converter Using D-Q Theory
 
IRJET- A Implementation of High Speed On-Chip Monitoring Circuit by using SAR...
IRJET- A Implementation of High Speed On-Chip Monitoring Circuit by using SAR...IRJET- A Implementation of High Speed On-Chip Monitoring Circuit by using SAR...
IRJET- A Implementation of High Speed On-Chip Monitoring Circuit by using SAR...
 
anti islanding technology(passive)
anti islanding technology(passive)anti islanding technology(passive)
anti islanding technology(passive)
 
Power Quality Enhancement using Fuzzy Control Based DVR
Power Quality Enhancement using Fuzzy Control Based DVRPower Quality Enhancement using Fuzzy Control Based DVR
Power Quality Enhancement using Fuzzy Control Based DVR
 
Modeling and simulation of three phases cascaded H-bridge grid-tied PV inverter
Modeling and simulation of three phases cascaded H-bridge grid-tied PV inverterModeling and simulation of three phases cascaded H-bridge grid-tied PV inverter
Modeling and simulation of three phases cascaded H-bridge grid-tied PV inverter
 
Reliability analysis of pmu using hidden markov model
Reliability analysis of pmu using hidden markov modelReliability analysis of pmu using hidden markov model
Reliability analysis of pmu using hidden markov model
 
Analysis of CMOS Comparator in 90nm Technology with Different Power Reduction...
Analysis of CMOS Comparator in 90nm Technology with Different Power Reduction...Analysis of CMOS Comparator in 90nm Technology with Different Power Reduction...
Analysis of CMOS Comparator in 90nm Technology with Different Power Reduction...
 
Stability study of a multi machine system using modified robust co ordinate a...
Stability study of a multi machine system using modified robust co ordinate a...Stability study of a multi machine system using modified robust co ordinate a...
Stability study of a multi machine system using modified robust co ordinate a...
 

Similar to grad project IEEE paper

Substation grounding grid design using Alternative Transients Program-ATP and...
Substation grounding grid design using Alternative Transients Program-ATP and...Substation grounding grid design using Alternative Transients Program-ATP and...
Substation grounding grid design using Alternative Transients Program-ATP and...Jose Dariel Arcila
 
Design of Earthing System for 230 kV High Voltage Substation by ETAP 12.6 Sof...
Design of Earthing System for 230 kV High Voltage Substation by ETAP 12.6 Sof...Design of Earthing System for 230 kV High Voltage Substation by ETAP 12.6 Sof...
Design of Earthing System for 230 kV High Voltage Substation by ETAP 12.6 Sof...ijtsrd
 
Voltage Control Using Statcom in Dg Integrated With Distribution Network
Voltage Control Using Statcom in Dg Integrated With Distribution NetworkVoltage Control Using Statcom in Dg Integrated With Distribution Network
Voltage Control Using Statcom in Dg Integrated With Distribution Networkiosrjce
 
Failure Detection in Energized High Voltage Substation Grounding Grids - A Ca...
Failure Detection in Energized High Voltage Substation Grounding Grids - A Ca...Failure Detection in Energized High Voltage Substation Grounding Grids - A Ca...
Failure Detection in Energized High Voltage Substation Grounding Grids - A Ca...inventionjournals
 
Failure Detection in Energized High Voltage Substation Grounding Grids - A Ca...
Failure Detection in Energized High Voltage Substation Grounding Grids - A Ca...Failure Detection in Energized High Voltage Substation Grounding Grids - A Ca...
Failure Detection in Energized High Voltage Substation Grounding Grids - A Ca...inventionjournals
 
Analysis of Fault Detection and its Location using Microcontroller for Underg...
Analysis of Fault Detection and its Location using Microcontroller for Underg...Analysis of Fault Detection and its Location using Microcontroller for Underg...
Analysis of Fault Detection and its Location using Microcontroller for Underg...IRJET Journal
 
Investigation of overvoltage on square, rectangular and L-shaped ground grid...
Investigation of overvoltage on square, rectangular and  L-shaped ground grid...Investigation of overvoltage on square, rectangular and  L-shaped ground grid...
Investigation of overvoltage on square, rectangular and L-shaped ground grid...IJECEIAES
 
Technical presentation on modern earthing
Technical presentation on modern earthingTechnical presentation on modern earthing
Technical presentation on modern earthingPankaj Chakraborty
 
A 60 GHz CMOS Power Amplifier for Wireless Communications
A 60 GHz CMOS Power Amplifier for Wireless CommunicationsA 60 GHz CMOS Power Amplifier for Wireless Communications
A 60 GHz CMOS Power Amplifier for Wireless CommunicationsIJECEIAES
 
A Novel Study on Bipolar High Voltage Direct Current Transmission Lines Prote...
A Novel Study on Bipolar High Voltage Direct Current Transmission Lines Prote...A Novel Study on Bipolar High Voltage Direct Current Transmission Lines Prote...
A Novel Study on Bipolar High Voltage Direct Current Transmission Lines Prote...IJECEIAES
 
Capacitive voltage and current induction phenomena in GIS substation
Capacitive voltage and current induction phenomena in GIS substationCapacitive voltage and current induction phenomena in GIS substation
Capacitive voltage and current induction phenomena in GIS substationIOSR Journals
 
Grounding pad mounted transformers
Grounding   pad mounted transformersGrounding   pad mounted transformers
Grounding pad mounted transformersJimmy Chaparro
 
Grounding pad mounted transformers
Grounding   pad mounted transformersGrounding   pad mounted transformers
Grounding pad mounted transformersJimmy Chaparro
 
OPTIMAL RECONFIGURATION OF POWER DISTRIBUTION RADIAL NETWORK USING HYBRID MET...
OPTIMAL RECONFIGURATION OF POWER DISTRIBUTION RADIAL NETWORK USING HYBRID MET...OPTIMAL RECONFIGURATION OF POWER DISTRIBUTION RADIAL NETWORK USING HYBRID MET...
OPTIMAL RECONFIGURATION OF POWER DISTRIBUTION RADIAL NETWORK USING HYBRID MET...IAEME Publication
 

Similar to grad project IEEE paper (20)

Substation grounding grid design using Alternative Transients Program-ATP and...
Substation grounding grid design using Alternative Transients Program-ATP and...Substation grounding grid design using Alternative Transients Program-ATP and...
Substation grounding grid design using Alternative Transients Program-ATP and...
 
Design of Earthing System for 230 kV High Voltage Substation by ETAP 12.6 Sof...
Design of Earthing System for 230 kV High Voltage Substation by ETAP 12.6 Sof...Design of Earthing System for 230 kV High Voltage Substation by ETAP 12.6 Sof...
Design of Earthing System for 230 kV High Voltage Substation by ETAP 12.6 Sof...
 
B1102030610
B1102030610B1102030610
B1102030610
 
Ieee depth
Ieee depthIeee depth
Ieee depth
 
I010616064
I010616064I010616064
I010616064
 
Voltage Control Using Statcom in Dg Integrated With Distribution Network
Voltage Control Using Statcom in Dg Integrated With Distribution NetworkVoltage Control Using Statcom in Dg Integrated With Distribution Network
Voltage Control Using Statcom in Dg Integrated With Distribution Network
 
Failure Detection in Energized High Voltage Substation Grounding Grids - A Ca...
Failure Detection in Energized High Voltage Substation Grounding Grids - A Ca...Failure Detection in Energized High Voltage Substation Grounding Grids - A Ca...
Failure Detection in Energized High Voltage Substation Grounding Grids - A Ca...
 
Failure Detection in Energized High Voltage Substation Grounding Grids - A Ca...
Failure Detection in Energized High Voltage Substation Grounding Grids - A Ca...Failure Detection in Energized High Voltage Substation Grounding Grids - A Ca...
Failure Detection in Energized High Voltage Substation Grounding Grids - A Ca...
 
A modeling and performance of the triple field plate HEMT
A modeling and performance of the triple field plate HEMTA modeling and performance of the triple field plate HEMT
A modeling and performance of the triple field plate HEMT
 
Analysis of Fault Detection and its Location using Microcontroller for Underg...
Analysis of Fault Detection and its Location using Microcontroller for Underg...Analysis of Fault Detection and its Location using Microcontroller for Underg...
Analysis of Fault Detection and its Location using Microcontroller for Underg...
 
Investigation of overvoltage on square, rectangular and L-shaped ground grid...
Investigation of overvoltage on square, rectangular and  L-shaped ground grid...Investigation of overvoltage on square, rectangular and  L-shaped ground grid...
Investigation of overvoltage on square, rectangular and L-shaped ground grid...
 
Technical presentation on modern earthing
Technical presentation on modern earthingTechnical presentation on modern earthing
Technical presentation on modern earthing
 
10.1.1.192.9435(1)
10.1.1.192.9435(1)10.1.1.192.9435(1)
10.1.1.192.9435(1)
 
A 60 GHz CMOS Power Amplifier for Wireless Communications
A 60 GHz CMOS Power Amplifier for Wireless CommunicationsA 60 GHz CMOS Power Amplifier for Wireless Communications
A 60 GHz CMOS Power Amplifier for Wireless Communications
 
A Novel Study on Bipolar High Voltage Direct Current Transmission Lines Prote...
A Novel Study on Bipolar High Voltage Direct Current Transmission Lines Prote...A Novel Study on Bipolar High Voltage Direct Current Transmission Lines Prote...
A Novel Study on Bipolar High Voltage Direct Current Transmission Lines Prote...
 
Capacitive voltage and current induction phenomena in GIS substation
Capacitive voltage and current induction phenomena in GIS substationCapacitive voltage and current induction phenomena in GIS substation
Capacitive voltage and current induction phenomena in GIS substation
 
Grounding pad mounted transformers
Grounding   pad mounted transformersGrounding   pad mounted transformers
Grounding pad mounted transformers
 
Grounding pad mounted transformers
Grounding   pad mounted transformersGrounding   pad mounted transformers
Grounding pad mounted transformers
 
voltage scaling
voltage scalingvoltage scaling
voltage scaling
 
OPTIMAL RECONFIGURATION OF POWER DISTRIBUTION RADIAL NETWORK USING HYBRID MET...
OPTIMAL RECONFIGURATION OF POWER DISTRIBUTION RADIAL NETWORK USING HYBRID MET...OPTIMAL RECONFIGURATION OF POWER DISTRIBUTION RADIAL NETWORK USING HYBRID MET...
OPTIMAL RECONFIGURATION OF POWER DISTRIBUTION RADIAL NETWORK USING HYBRID MET...
 

grad project IEEE paper

  • 1. 1 Utilization of System Generated LG Fault on Ground Grid Mesh and Analysis of existing GGS using IEEE 80-2000 and Finite Element Method Akash Patel Electrical Engineering California State University Northridge Northridge, USA akash.patel.296@my.csun.edu Professor Bruno Osorno Electrical Engineering California State University Northridge Northridge, USA bruno@csun.edu Abstract—the 750kv substation is chosen for given particular type of soil to design square ground grid mesh. By using line to ground fault current generated on 750kv substation by ETAP short circuit analysis, ground grid parameters are determined using simple hand calculations and results are verified by modeling same ground grid using ETAP ground grid system. After getting general idea about effect on system generated fault on GGS, system data from existing 50kv Rawat substation is collected to verify all-important parameters are within the limit or not. To evaluate important GGS parameters, mesh analysis is carried out using both IEEE 80-2000 and Finite Element Methods by using ETAP-12 GGS Module. Shortcoming in existing mesh are highlighted by ETAP warning and alert dialog box and remedial actions are suggested to rectify the problems. Increase in fault current by expansion of substation is consider with possible solution and optimization of ground grid mesh is presented based on modern technology. Finally, comparison is done between IEEE 80-2000 and FEM method to design GGS and effect of ground grid area, number of conductors/rods and spacing between conductors is explained by help of several case study results. Keywords— Ground Potential Rise, Step Voltage, Touch Voltage, Ground Mesh, Electrical Transient Analysis Program, Ground Grid System Module I. INTRODUCTION Under normal and faulty condition, grounding can carry electrical currents into earth with maintaining operating and equipment limits and protect person from danger of electrical shock. After analyzing effects of electrical current on human body, researchers have developed different IEEE standards for earth resistance measurement, surface gradients, grid conductors continuity, equipment grounding, cable routing, cable sheath grounding, indoor installations, lighting protection, current division, generating station grounding practices, testing and different connections of grounding system. Use of single electrode for grounding is not sufficient for safe grounding. Rather than using single electrode if we use grid, we can represent excellent grounding system. To protect human from surface gradients when high current dissipated into the earth, installation of grid with law resistant is required. Horizontal ground grid can reduce danger of high step and touch voltages on the earth surface by using only, when grid is installed in narrow depth. For many installations where soil resistivity change due to freezing or drying effect and resistivity of lower soil remains constant, ground electrodes are useful to stabilize the performance. So, in case of multilevel soil, rods which are penetrating in low resistivity soil more effectively dissipate fault currents. Installation of rods along grid perimeter in uniform or high-to-low soil conditions can moderate steep rise of surface gradient near peripheral meshes. Sometimes size of substation is large or soil has high resistivity. Rather than using large grounding system, we have to use fraction of the land area for grounding purpose and then all areas can be connected with each other by connecting rods. Computer algorithms are based on modeling the individual components comprising the grounding system, developing set of equations which describe the interconnection of these equipments, determine ground fault current flowing from each component into the earth, calculating the potential at any desired surface point due to all individual components-TAP ground grid module is very useful software for design and implementation of ground grid system and it utilizes Finite Element Method,IEEE 80-1986, IEEE 80-2000, IEEE 665- 1995 methods of computation. Existing 500 kv Rawat substation is design and analyze by ETAP-12 using IEEE 80- 2000 and Finite Element method and new 750 kv substation is designed by using data from IEEE safety guide for substation grounding and short circuit analysis of grid. II. SHORT CIRCUIT ANALYSIS AND GROUND GRID SYSTEM There are 9 buses,3 generators,3 transformers,6 transmission lines and 3 loads are connected as shown in figure 1. After creating line to ground fault on bus 5, E-TAP short circuit analysis generate fault currents and voltages as shown in circuit below.Design of square ground grid represented by green area is possible for 750kv substation at bus 5 by updating fault current value at bus 5 and we can easily verify the results with ETAP software. System data for bus,transmission lines,transformers and generators are presented in Appendix A.
  • 2. 2 Figure 1 [5] developing grounding grid on faulted bus 5 ETAP give short-circuit result as shown in table 3.5. Contribution Line to Ground Fault From Bus To Bus %Voltage At From Bus kA Symm. rms ID ID Va Vb Vc Ia 3 Bus5 Total 0 92.91 91.61 10.106 10.106 Bus4 Bus5 0.11 92.91 90.61 5.137 6.252 Bus7 Bus5 0.37 92.87 90.49 4.993 4.004 Table 1 short circuit result So, 10.106 kA fault current is contribution of Bus 5 to whole network.By using this fault current value we can design square grid for Bus 5 by using simple equations as shown below.data of square grid is presented in Appendix B. a) Touch and Step criteria: K= =-0.72 = b) Determination of grid resistance: c) Maximum grid current : d) Ground Potential rise: GPR= e) Correction factors: =1.225. f) Spacing factors: g) Mesh voltage: h) Step voltage: Result Summary: Calculated Volts Tolerable Volts Touch 3184.382 V 840.5836 V Step 1452.7945 V 2696.2398 V GPR Table 2 hand calculation result summary Here the maximum touch voltage exceeds the tolerable limits. We can verify above result by ETAP. After updating the value of and X/R from short circuit analysis,we can design square ground grid by using ETAP as shown in figure 3.7.
  • 3. 3 Figure 2 top view of ETAP square ground grid The result of ground grid analysis for square grid is shown in figure 3. Figure 3 results of ETAP GGS analysis The value of touch, step voltages, GPR and are similar for hand calculation as well as ETAP calculation. Even in both cases calculated touch voltage is higher than tolerable limit. III.IEEE 80-2000 METHODS CASE STUDIES By using the same 9 bus power system,designing of 500kv substation is possible at bus1 by using ETAP IEEE 80-2000 method as shown in figure 4 [5], Figure 4[5] sample connection diagram for IEEE 80-2000 method grid design Actually ground grid system for 500kv substation is already laid and functioning in Rawat substation,so existing data is collected to verify whether all important parameters are with in the described limits or not.The collected data from actual substation are represented in Appendix C. a) IEEE 80-2000 Method Case 1: Initially after specifing surface material,soil resistivity and depths for various layers in ETAP soil editor and selecting weight of person, proper IEEE method and details of short circuit current and fault duration by using ETAP GRD study case editor and specifying conductor/ rod parameters for grid and ground grid dimentions by using in ETAP IEEE group editor with the data given in table 3 ,we can design and analyze protection scheme for priliminary gound grid mesh by finding ground potential rise,ground system resistance,touch and step potentials using IEEE 80-2000 method. Gri d Len gth (ft) Numbe r of conduct ors Rod Data Conduc tor Size AWG/k cmil De pth ft ft ft In X Directio n In Y Direc tion Diam eter inch Len gth ft N o Of Ro ds 4/0 0.9 8 472. 44 32 8.0 8 14 10 0.472 6.56 50 Table 3[4] input ground grid parameters of IEEE 80-2000 method case 1. The ground grid system is presented by a top view,a soil view,a 3-D view for graphical arrangement of the conductors and rods as shown in figures 5,6 and 7.the soil view is used to edit the soil properties of the surface, top, and lower layers of soil. The 3-D view is used for the three-dimensional display of the ground grid which can be rotate or view by any angle. The Top View is used to edit the ground conductors/rods of a ground grid. Figure 5 soil view of GGS case 1. Figure 6. 3-D view of GGS case 1. Figure 7 top view of GGS case 1.
  • 4. 4 The result of ground grid analysis case 1 is shown in figure 8. Figure 8 results of case 1 analysis As shown in figure 8, ground grid is not functioning properly due to higher touch voltage and temperature rise than safer limits. Moreover, either we should have to increase or decrease area to design proper ground grid. b)IEEE 80-2000 Method Case 2: To overcome issue created in case 1, redesign of ground grid system is possible by changing number of conductors and number of rods as shown in table 4[4]. Gr id Le ngt h (ft) Number of conduct ors Rod Data Conduc tor Size AWG/k cmil De pth ft ft ft In X Direct ion In Y Dire ctio n Diameter inch Len gth ft N o Of R od s 4/0 0.9 8 47 2.4 4 3 2 8. 0 8 20 16 0.598 6.5 6 54 Table 4 [4] input ground grid parameters of IEEE 80-2000 method case 2. 3-D View of grid and the results of ground grid analysis case 2 are shown in figure 9 and 10. Figure 9. 3-D view of GGS case 2. Figure 10 results of case 2 analysis So, temperature rise issue can be solved by changing number of conductors and rods. But, higher touch voltage and grid size issues are still exist. c)IEEE 80-2000 Method Case 3: There is an expansion in actual substation by replacing old power transformer with new one which increase fault current from 40 A to 45 A.To fulfill this new requirement,changes are required in ground grid mesh as shown in table 5[4]. Gri d Len gth (ft) Numbe r Of conduc tors Rod Data Condu ctor Size AWG/ kcmil D ep th ft ft ft In X Directi on In Y Directi on Diamet er inch Length ft No Of Ro ds 4/0 0. 9 8 472. 44 328. 08 22 19 0.634 6.56 65 Table 5[4] input ground grid parameters of IEEE 80-2000 method case 3. 3-D View and the result of ground grid analysis case 3 is shown in figure 11 and 12. Figure 11. 3-D view of GGS case 3.
  • 5. 5 Figure 12 results of case 3 analysis ETAP ground grid analyzer show warning signal related to size of ground grid area and higher touch voltage than allowable limit due to larger than 10000 sq.m grid area. So, for safety purpose we have to minimize the grid area. d)IEEE 80-2000 Method Case 4: when ground grid mesh of this substation is designed , very less methods for designing ground grid are available.In this case study, new modern analysis and optimization techniques are applied for ground grid design by using the details presented in table 6 [4]. Gri d Le ngt h (ft) Numbe r Of conduct ors Rod Data Con duct or Size AW G/kc mil De pth ft ft ft In X Directio n In Y Direction Diam eter inch Le ngt h ft No Of Ro ds 4/0 2 393 .7 272 .31 25 23 0.63 6.5 6 42 Table 6[4] input ground grid parameters of IEEE 80-2000 method case 4. 3-D View and the results of ground grid analysis case 4 is shown in figure 13 and 14. Figure 13. 3-D view of GGS case 4. Figure 14 results of case 4 analysis By decreasing size of ground grid area and proper utilization of ground conductors and rods,we can design ground grid mesh which fullfill all required limits of touch potential,step potential and temperature. IV.FEM CASE STUDIES Using the same data from Appendix C ,we can design ground grid mesh for 500kv substation at bus 3 by using ETAP FEM. Figure 15 [5] ground grid representation for FEM. a)FEM Case 1: By using ETAP ground grid Finite Element module and input datas given in table 7[4], design and analyze of priliminary ground grid design is possible.we can modify each individual conductor/rod parameter by using FEM group editor and rod editor. Grid Lengt h (ft) Numb er Of condu ctors Rod Data Con duct or Size AW G/kc mil Dep th ft ft ft In X Direct ion In Y Directio n Diam eter inch Len gth ft No Of Ro ds 4/0 0.9 8 472.4 4 328.08 20 15 0.472 6.56 50 Table 7[4] input ground grid parameters of FEM case 1.
  • 6. 6 Different views of ground grid are shown in figure 16, 17, 18. Figure 16. 3-D view of GGS case 1. Figure 17 top view of GGS case 1. Figure 18 soil view of GGS case 1. The result of ground grid analysis case 1 is shown in figure 19. Figure 19 results of case 1 analysis As shown in figure 19, ground grid is not functioning properly due to higher touch voltage and temperature rise than safer limits.3-D Plots are used only with the FEM method, and are available for Absolute/Step/Touch Voltages. As shown in figure 20, some voltages are quite high on voltage axies represented by red colour in step potential profile,while in case of touch potential as shown in figure 21, most of area is green which represent that touch voltage is very low. Figure 20 step potential profile of case 1. Figure 21 touch potential profile of case 1. Figure 22.absolute potential profile of case 1. b)FEM Case 2: To overcome issue created in case 1, redesign of ground grid system is possible by changing number of conductors and number of rods is as shown in table 8.[4]. Grid Lengt h (ft) Num ber Of condu ctors Rod Data Cond uctor Size AW G/kc mil De pth ft ft ft In X Direct ion In Y Directio n Diam eter inch Le ng th ft No Of Rods 4/0 0.9 8 472.4 4 328.0 8 25 20 0.614 6. 6 57 Table 8[4] input ground grid parameters of FEM case 2. 3-D View and The result of ground grid analysis case 2 is shown in figure 23 and 24.
  • 7. 7 Figure 23. 3-D view of GGS case 2. The result of ground grid analysis is shown in figure 5.13. Figure 24.results of case 2 analysis So, by changing number of conductors and rods, we resolve temperature rise issue. But, still we need to focus on higher touch voltage.3-D voltage profiles are shown in figure 25, 25 and 27. Figure 25.step potential profile of case 2 Figure 26.touch potential profile of case 2 Figure 27.absolute potential profile of case 2 c) FEM Case 3: There is an expansion in actual substation by replacing old power transformer with new one which increase fault current from 40 A to 45 A.To fulfill this new requirements , modifications are required in grid configuration as shown in Table 9.[4]. Gri d Len gth (ft) Num ber Of cond uctor s Rod Dat a Co ndu ctor Siz e A W G/k cmi l De pth ft ft ft In X Direc tion In Y Directio n Dia met er inch Len gth ft N o O f R o ds 4/0 0.9 8 472. 44 328. 08 29 26 0.64 2 6.8 9 6 0 Table 9.[4] input ground grid parameters of FEM case 3. 3-D View and the result of ground grid analysis case 3 is shown in figure 28 and 29. Figure 28. 3-D view of GGS case 3.
  • 8. 8 Figure 29.results of case 3 analysis When I analyze the new designed grid after expanding existing substation, E-TAP ground grid analyzer showing warning signal related to higher touch voltage than allowable limit.3-D voltage profiles are shown in figure 30, 31 and 32. Figure 30.step potential profile of case 3. Figure 31.touch potential profile of case 3. Figure 32.absolute potential profile of case 3. d)FEM Case 4: when ground grid mesh of this substation is designed , very less methods for designing ground grid are available.In this case study,new modern analysis and optimization techniques are applied for ground grid design by using the details presented in Table 5.4. [4]. Gri d Len gth (ft) Num ber Of cond uctor s Rod Dat a Con duct or Size AW G/k cmil Dep th ft ft ft In X Direc tion In Y Directi on Dia mete r inch Leng th ft N o Of Ro ds 4/0 1.6 4 393. 7 272.31 26 22 0.47 2 6.56 50 Table 10.[4] input ground grid parameters of FEM case 4. 3-D View and ETAP ground analysis is presented in figure 33 and 34. Figure 33. 3-D view of GGS case 4. Figure 34.results of case 4 analysis 3-D view of different potential profiles are shown in figure 35, 36 and 37.
  • 9. 9 Figure 35.step potential profile of case 4. Figure 36.touch potential profile of case 4. Figure 37.absolute potential profile of case 4. By decreasing size of ground grid area and proper utilization of ground conductors and rods,I design ground grid mesh which fullfill all required limits of touch potential,step potential and temperature. V. CONCLUSION From the result of ETAP simulation on several case studies, we can derive below aspects, magnitude of touch potential, step potential, absolute potential, and ground resistance decrease with increase in grid area. So, it’s better to use larger grid in the area where land is cheap. Effect of spacing on touch and step potential is opposite. If we reduce the spacing between conductors, mesh potential decrease, while step potential may be increase and effect of mesh potential is severe than step potential. The effect of increasing conductors can be varied for different cases, but mainly installation of horizontal conductors decreases the touch potential. Normally if we install more number of vertical rods, temperature rise, mesh potential, ground impedance decrease. Simulated results are nearer to actual value by using IEEE 80-2000 and FEM method; in addition results are more accurate than hand calculation ETAP simulate ground grid system within a second, while for FEM method E-TAP took around 5-6 minutes.so, we can do faster calculation by using IEEE 80-2000 method compare to FEM method. Ground grid design using FEM is costlier than IEEE 80-2000 method because greater number of conductors and rods are required in FEM compare to IEEE 80-2000 For the same size grid. Mesh designed by FEM method will be more durable, long lasting and have ability to withstand the excessive fault currents more effectively. In FEM method we can modify the data for individual conductor or rod by conductor/rod editor, while in IEEE 80-2000 method we can’t change data for individual conductor/rod. VI.BIBLIOGRAPHY [1] Design analysis and optimization of ground grid mesh of extra high voltage substation using an intelligent software. [2] IEEE guide for safety in AC substation grounding. [3] IEEE guide for measuring earth resistivity, ground impedance and earth surface potentials of a grounding system. [4] A comparison of ground grid mesh design and optimization for 500kv substation using IEEE 80-2000 and finite element methods. [5] Transient stability analysis of IEEE 9 bus electric power system. [6] Engineering design and rapid prototyping. [7] Introduction to finite element modeling.
  • 10. 10 Appendix A. 9 bus system data 2-Winding Transformer Input Data: T/f Rating Phase Shift ID MVA Prim kV Sec kV %Z X/R Type Angle T1 1000 750 500 10 34.1 Dyn 30 T2 1000 250 750 10 34.1 yNd 30 T3 1000 500 750 10 34.1 yNd -30 Synchronous Generator Input Data: Ra tin g Pos itie Impe dance Zero Seq. Impe danc e ID M VA k V RP M X’/ R %R % Xd’ X/R %R0 % X0 Ge n1 772 .53 2 50 0 1800 19 1 28 19 0.368 7 Ge n2 163 0.8 15 25 0 1800 19 1 28 19 0.368 7 Ge n3 857 .11 4 45 0 1800 19 1 28 19 0.368 7 Bus Input Data: Bus Initial Voltage ID Type Nom kv Base kv %Mag Ang Bus 1 Swing. 500 500 100 0 Bus 2 Gen. 250 250 100 0 Bus 3 Gen. 500 500 90 60 Bus 4 Load 750 750 100 30 Bus 5 Load 750 750 100 30 Bus 6 Load 750 750 100 30 Bus 7 Load 750 750 100 30 Bus 8 Load 750 750 100 30 Bus 9 Load 750 750 100 30 Line Input Data: Li ne Leng th Ohms per phase ID Adj(f t) R1 X1 Y1 R0 X0 Y0 Lin e 1 5280 0.00 3219 7 0.0174 242 0 0.00240 9 0.01647 73 0 Lin e 2 5280 0.00 7364 0.0321 97 0.000 0001 0.00928 03 0.05113 64 0.0000 001 Lin e 3 5280 0.00 2253 8 0.0190 909 0 0.00452 65 0.17196 97 0 Lin e 4 5280 0.00 1893 9 0.0304 924 0 0.00378 79 0.01136 36 0 Lin e 5 5280 0.00 6060 6 0.0136 364 0.000 0001 0.05909 09 0.02670 46 0.0000 001 Lin e 6 5280 0.00 0947 0.0136 364 0 0.06174 2 0.00984 85 0.0000 001 Appendix B. Design data for 750 kv substation: S r. N o. Description of Parameter Value 1. soil resistivity ( ⍴) 400 Ω m 2. Crushed rock resistivity 2500 Ω m 3. Thickness of crushed rock 0.102 m 4. Available grounding area (A) 70 m*70 m=4900 5. depth of grid burial (h) 0.5 m 6. Total length of buried conductor ( ) 2*11*70=1540m 7. Current devision factor( ) 0.6 8. Fault current from E-TAP short circuit analysis( ) 10106 A In design, D =7 m, =0.5 s, =1.0, n=11, d=0.01 is used. Appendix C. Design data for 500 kv substation: Sr. No. Description of Parameter Value 1. Level of Voltage 500 KV 2. Maximum Fault Current 40 KA 3. Ground Grid Mesh Area 144 x 100 m2 4. Ground Grid Horizontal Distance 144m 5. Ground Grid Mesh Vertical Distance 100m 6. Horizontally Installed Conductors 14 7. Vertically Installed Conductors 10 8. Conductors Size 4/0 9. Conductors Type Copper Annealed Soft Drawn 10. Maximum Temperature of Conductors 40 °C 11. Rods Installed in Vertical Direction 50 12. Rod Diameter of Vertical Rods 1.2 centimeter 13. Rod Steel Rod Copper Clad 14. Duration of Fault 1 second 15. Temperature Outside -5 – 50 °C 16. Temperature of Rod 40 °C 17. X/Rratio Reactance over Resistance 50 18. Person Weight 50 kg 19. Soil Type at Surface Gravel 20. Resistivity 9976 Ω.m 21. Height 0.2m 22. Top Soil Moist Layer 23. Resistivity 130 Ω.m 24. Height 2m 25. Soil Bottom Layer Type Moist Soil 26. Soil Bottom Layer Resistivity 200 Ω.m 27. Soil Bottom Layer Height Infinity 28. Level of Fault in Relation to Earth Sr 60 29. Increase in Fault Level Cp 100