SlideShare a Scribd company logo
1 of 9
Download to read offline
International Journal of Electrical and Computer Engineering (IJECE)
Vol. 11, No. 6, December 2021, pp. 4689~4697
ISSN: 2088-8708, DOI: 10.11591/ijece.v11i6.pp4689-4697  4689
Journal homepage: http://ijece.iaescore.com
Investigation of overvoltage on square, rectangular and
L-shaped ground grids of high voltage substations by
ATP/EMTP
Krung Luewattana1
, Paweena Rattanasena2
1
Sub-Department of Electrical Engineering, Faculty of Science and Technology, Phranakhon Si Ayutthaya Rajabhat
University, Ayutthaya, Thailand
2
Department of Applied Science, Faculty of Science and Technology, Phranakhon Si Ayutthaya Rajabhat University,
Ayutthaya, Thailand
Article Info ABSTRACT
Article history:
Received Aug 3, 2020
Revised Mar 11, 2021
Accepted Mar 23, 2021
Ground grid system is important for preventing the hazardous effects of
overvoltage in high voltage substations due to fault current perhaps from
lightning strike or device malfunction. Therefore, this study aimed to
investigate the effects of overvoltage on square, rectangular and L-shaped
ground grids with ground rods being distributed in mesh-pattern by using
alternate transients program/electromagnetic transients program
(ATP/EMTP) program. The models were simulated in the cases that 25 kA-
fault current being injected into the center or one of the corners of ground
grids. The results showed that the highest level of overvoltage (6.3349 kV)
was detected at the corner of rectangular ground grid when the fault current
was injected into its corner. However, the lowest level of overvoltage was
found when the fault current was injected into the center of square ground
grid. The results from this study indicated that ATP/EMTP program was
useful for preliminary investigation of overvoltage on ground grids of
different shapes. The obtained knowledge could be beneficial for further
designing of ground grid systems of high voltage substations to receive the
minimal damages due to fault current.
Keywords:
Ground grid system
Ground potential rise
High voltage substation
Overvoltage
This is an open access article under the CC BY-SA license.
Corresponding Author:
Krung Luewattana
Department of Electrical Engineering
Faculty of Science and Technology
Phranakhon Si Ayutthaya Rajabhat University
Ayutthaya, Thailand
Email: zaraburi@yahoo.com
1. INTRODUCTION
At present, the transmission and distribution systems of electrical power between substations are
extremely necessary for national development. These systems require the well-designed substations and
ground grids to maximize their efficiency and reliability as well as to protect the working staff and important
electrical devices that locating inside the substations or nearby proximity. Particularly, the reliable ground
grid can play very important role in the case of overvoltage due to the natural disaster, lightning strike and
switching device malfunction [1]. Since ground grid is a large system and too difficult to be created as
demonstrative model under laboratory conditions, the computer programs hence become very useful and
convenient for simulating such model. The computer programs, for example, current distribution in earth and
grounding system (CDEGS), power system computer aided design (PSCAD), fast Fourier transformation
 ISSN: 2088-8708
Int J Elec & Comp Eng, Vol. 11, No. 6, December 2021 : 4689 - 4697
4690
(FFT), COMSOL, and alternate transient program/electromagnetic transients program (ATP/EMTP), have
been applied with different advantages and disadvantages.
Initially, electromagnetic transients program (EMTP) was used for simulating the transmission line
and ground grid models and then analyzing their lightning protection systems and dynamic behaviors during
the occurrence of overvoltage on ground systems. The obtained results of this study were compared with the
calculated ground potential rise (GPR). EMTP was also used for designing the lightning protection system of
high voltage substation [2], [3]. In addition, the transient that occurred on ground grids and the frequency
dependent characteristics of large ground grids were simulated based on the electromagnetic field theory
approach by the computer model. This study also explored the effects of GPR, relative permeability of soil,
and depth of ground grids buried in soil on the electromagnetic compatibility (EMC) in the case of lightning
strike on ground grid [4]. Similar case of ground grid system that being injected with transient current has
been simulated by the computer model and then endorsed by the experiments under laboratory conditions [5].
Furthermore, EMTP program was used for developing a model of double exponential time function from the
inverse fast fourier transformation (IFFT) to analyze the response time of ground rod impulse and explore the
dynamics between lightning protection and ground and the effects of charge that dispersing into the ground
[6]. In addition, the effects of soil properties on impedance and transient responses of grounding electrode
were investigated by the frequency-dependent soil model, which integrating the frequency-dependent soil
electrical properties into the circuit model of grounding electrode and measuring the voltage response of
grounding electrode. Comparison was performed between the voltage responses of the grounding electrode
occurred in the circuit model and that in the electromagnetic model, which showing that the voltage peaks and
the wave shapes obtained from these two models were very similar with less than 1% difference [7].
Furthermore, power system computer aided design (PSCAD) and current distribution, electromagnetic
interference, grounding and soil structure analysis (CDEGS) programs were applied for investigating the
possible severity of lightning strike on transmission line tower and nearby gas pipeline. However, CDEGS
program was found to illustrate the effects of soil structure on induced voltage more accurately. Since
CDEGS could show the results in three-dimensional (3D) illustrations and perform integration of frequency
dependent soil electrical properties in grounding electrode circuit model, it was therefore used for examining
the impacts of different soil resistivity levels, conductor materials, lightning impulse voltage front time
waveforms, and soil profiles (uniform, 2-layer, and 3-layer) [8]-[12]. Interestingly, the use of CDEGS
program could help to create the 3D plots of power plant’s grounding system that was struck by lightning
current and illustrate that the scalar potentials and electric fields were seriously affected [13]. In addition, the
electrical transient analyzer program (ETAP) was used to optimize the similar parameters, especially the
conductors’ types, lengths, depths, and sizes [14]-[16].
In this study, the objective was to use ATP/EMTP for exploring the effects of overvoltage on three
different ground grids (square, rectangular, and L-shaped ground grids with the same size of 324 m2
) of high
voltage substation. This is because ATP/EMTP is a convenient and simple program with ease of access that
can help to preliminarily investigate the effects of overvoltage on various spots of ground grids with different
shapes. The ground grids were designed according to the IEEE 80-2000 standard and therefore the obtained
knowledge may be useful for designing the shape of ground grid that could protect the electrical equipment
and ensure the safety of personnel inside the substation against electric shocks. This study may also provide
the basic knowledge for further analysis by other advanced programs, and this could also help to understand
which spots of substation that were minimally affected by overvoltage and should be used for placing the
important electrical equipment [17]-[20].
This paper is organized is being as: Section 2 presents the designs of ground grid models and
simulation process. The levels of overvoltage from simulations were presented and compared with the
calculated GPR in section 3. Finally, section 4 presents the conclusions and reference list.
2. RESEARCH METHOD
2.1. Designs of ground grid systems of high voltage substation
Firstly, three models of ground grid systems of high voltage substation were designed, including
square with the dimension of 18×18 m, rectangular of 27×12 m, and L-shaped of 18×12+12×9 m, with the
equal size of 324 m2
. Even though these three models had different shapes, each of them was equipped with
24 ground rods distributed in mesh-pattern and had the same important parameters according to the standard
of IEEE Std. 80-2000 [21] as shown in Figure 1.
2.2. Devices and parameters for simulation by ATP/EMTP program
Next, the devices of ground grids were determined by ATP/EMTP program. Initially, the grid
conductor was chosen by the command ‘Line/Cable’ followed by ‘RLC Pi-equiv’. Then, ground rod was
Int J Elec & Comp Eng ISSN: 2088-8708 
Investigation of overvoltage on square, rectangular and l-shaped ground grids of… (Krung Luewattana)
4691
selected by the command ‘branch linear’ followed by ‘resistor’. Subsequently, the current sources for
injecting fault current into the ground grid system was selected by the command ‘Heidler type 15’. Finally,
all these devices were connected together to create the models of square, rectangular and L-shaped ground
grids as shown in the step 2.3. The parameters to be used in these models were shown in Table 1.
(a) (b) (c)
Figure 1. Three models of ground grid system, (a) square, (b) rectangular, and (c) L-shaped
Table 1. Parameters for ground grid models
Parameter Value Unit
Resistivity 1.7 × 10-8
Ω-m
Cross sectional area of conductor 95 mm2
Resistance 5.3685 × 10-4
Ω-m
Depth of ground rods 0.5 m
Span length of grid conductor 3 m
Inductance 1620.2087 mH/m
Earth permittivity 8 × 10-11
F/m
Capacitance 4.44387 × 10-4
µF/m
Soil resistivity 10 Ω-m
Length of ground rod 3 m
Diameter of ground rod 16 mm
Resistance of ground rod 3.508 Ω-m
Fault current 25 kA
2.3. Square, rectangular and L-shaped ground grids with ground rods distributed in mesh-pattern
From previous step, the devices and parameters were determined for creating the square, rectangular
and L-shaped ground grid models with ground rods distributed in mesh-pattern as shown in Figures 2-4.
Next, these models were used for simulating the case of 25 kA-fault current being injected directly into the
center or one of the corners of ground grid systems, example was shown in Figure 2. Subsequently, levels of
overvoltage measured on a diagonal line and at a corner of ground grids were recorded and plotted as shown
in the section 3.
Figure 2. Model of square ground grid with ground rods distributed in mesh pattern for simulation by
ATP/EMTP program
 ISSN: 2088-8708
Int J Elec & Comp Eng, Vol. 11, No. 6, December 2021 : 4689 - 4697
4692
Figure 3. Model of rectangular ground grid with ground rods distributed in mesh-pattern for simulation by
ATP/EMTP program
Figure 4. Model of L-shaped ground grid with ground rods distributed in mesh-pattern for simulation by
ATP/EMTP program
2.4. Equations for ground grid simulation
The levels of maximum GPR of square, rectangular and L-shaped ground grids were calculated
from the as described by [22]. Since the calculations of these cases gave only slightly different levels of GPR,
the maximum GPR (5.130 kV) was therefore used for comparing with the results obtained from simulations
of three cases by using ATP/EMTP program according to IEEE Std. 80-2000 [21], [22].
3. RESULTS AND DISCUSSION
By ATP/EMTP program, the cases of fault current being injected into the center or one of the
corners of each ground grid were simulated, and the levels of overvoltage on a diagonal line and at a corner
of that ground grid were measured as shown in Figures 5 and 6 for square, Figures 7 and 8 for rectangular,
Figures 9 and 10 for L-shaped ground grids. The levels of overvoltage from simulations of square,
rectangular and L-shaped ground grids were then compared with calculated GPR as shown in Figure 11. In
the case of square ground grid with ground rods distributed in mesh-pattern, the maximum overvoltage could
be detected when the fault current was injected into the corner of ground grid. The maximum overvoltage
Int J Elec & Comp Eng ISSN: 2088-8708 
Investigation of overvoltage on square, rectangular and l-shaped ground grids of… (Krung Luewattana)
4693
measured on diagonal line and at corner were 5.8528 kV Figure 6(a) and 5.9674 kV Figure 6(b), which were
higher than the calculated GPR 5.130 kV, Figure 11 for 14.09% and 16.32%, respectively. For the case of
rectangular and L-shaped ground grids, similar results of maximum overvoltage were detected when the fault
current was injected into the corner of ground grid. For rectangular ground grid, when the fault current was
injected into the corner, the maximum overvoltage measured on diagonal line and at corner were 6.2089 kV
Figure 8(a) and 6.3349 kV Figure 8(b), which were higher than the calculated GPR for 21.03% and 23.48%,
respectively. Also, In the case of L-shaped ground grid, when the fault current was injected into the corner,
the maximum overvoltage measured on diagonal line and at corner were 6.1407 Figure 10(a) and 6.1808 kV
Figure 10(b), which were higher than the calculated GPR for 19.70% and 20.48%, respectively.
(a) (b)
Figure 5. Voltage distribution; (a) on a diagonal line, (b) at a corner of square ground grid when the fault
current being injected into the center of ground grid
(a) (b)
Figure 6. Voltage distribution; (a) on a diagonal line, (b) at a corner of square ground grid when the fault
current being injected into the corner of ground grid
(a) (b)
Figure 7. Voltage distribution; (a) on a diagonal line, (b) at a corner of rectangular ground grid when the fault
current being injected into the center of ground grid
 ISSN: 2088-8708
Int J Elec & Comp Eng, Vol. 11, No. 6, December 2021 : 4689 - 4697
4694
(a) (b)
Figure 8. Voltage distribution; (a) on a diagonal line, (b) at a corner of rectangular ground grid when the fault
current being injected into the corner of ground grid
(a) (b)
Figure 9. Voltage distribution; (a) on a diagonal line, (b) at a corner of L-shaped ground grid when the fault
current being injected into the center of ground grid
(a) (b)
Figure 10. Voltage distribution; (a) on a diagonal line, (b) at a corner of L-shaped ground grid when the fault
current being injected into the corner of ground grid
According to these three models, the square ground grid was found to have the lowest overvoltage.
This may be because square shape is symmetrical, and when the fault current has flown through the
conductor in the center of this ground grid system, the connecting points of system’s intersection between
ground grid and ground rods, which are symmetrically joined together by exothermic welding both
horizontally and vertically, may help to release the fault current very rapidly in spherical radius.
Consequently, the overvoltage occurring on square ground grid may return back to the surface of the earth at
the levels lower than that of rectangular and L-shaped ground grids and quickly disperse into the earth. It
could be shown in the case of injecting the fault current into the center of square ground grid and measuring
the overvoltage on a diagonal line that resulting in the overvoltage of 5.6254 kV Figure 5(a) which being
lower than that of rectangular and L-shaped ground grids for 3.1% and 5.28%, respectively.
Int J Elec & Comp Eng ISSN: 2088-8708 
Investigation of overvoltage on square, rectangular and l-shaped ground grids of… (Krung Luewattana)
4695
Figure 11. Comparison of overvoltage on three shapes of ground grids with calculated GPR. The first
abbreviations were the spots for injecting fault current (Ct = center, Cn = corner) and the second
abbreviations were the spots for measuring overvoltage (Di = diagonal line, Cn = corner)
In contrast, the rectangular model was shown to have the highest overvoltage at 6.3349 kV
Figure 8(b) in the case of injecting the fault current into the corner and measuring the overvoltage also at the
corner. This may be because the rectangular shape is not symmetrical and, when the large amount of fault
current has been injected into the corner, high intensity magnetic field may be induced. The reason may be
due to that the conductor used in this study is copper, which is diamagnetic and highly capable of inducing
magnetic field, especially at the corner of system’s intersection where the ground grid and ground rods are
joined together by exothermic welding in unsymmetrically pattern. The overvoltage may not well disperse to
the underground earth, resulting in the overvoltage at levels higher than that of square and L-shaped ground
grids for 5.8 and 2.43%, respectively. However, the L-shaped ground grid was demonstrated to have average
overvoltage when being compared with the other two ground grids. This may be due to that L-shaped ground
grid has both symmetrical and unsymmetrical areas and therefore the overvoltage may disperse either
effectively or poorly to the underground earth Figure 4.
From this study, the results may suggest that ATP/EMTP, a widely-used and simple program, can be
beneficial for investigating the effects of overvoltage on ground grids of three different shapes, especially
when the fault current was injected into the corner of rectangular ground grid that resulting in the highest
overvoltage at the corner. There are the other programs that can be used for simulating the ground grid
systems. For example, CDEGS, which is a specialized program with high performance, can define the type of
laydown materials, simulate 2 layers of such materials, and also give the illustrative results in 2-and 3-D
formats, but it has disadvantage in high cost and requirement for very effective computer resources and
operating systems. Apart from that, the fast Fourier transformation (FFT) program has been used for
calculating the frequency and time response values and illustrating the magnetic fields in the case of lightning
strike on power plant’s ground grid [13]. Moreover, PSCAD program has been applied for analyzing the
effects of induced voltage due to lightning strike on overhead transmission line that affecting below gas
pipeline [8]. However, both FFT and PSCAD have limitations in creating the models and determining the
parameters. Currently, analysis of soil grounding materials with different levels of resistivity due to physical
and chemical compositions may be performed by the advanced programs, such as COMSOL that use 3D
finite element method (FEM) for simulating and displaying the ground grids and their electric and magnetic
fields in 3D illustrations. COMSOL may also be useful for analyzing the effects of overvoltage on various
designs of ground grids as well as the workers and equipment locating inside or nearby high voltage
substation [7], [23]-[25], but it has drawbacks in its cost, requirement for highly effective computer resources
and operating systems as well as time-consuming for generating the models and determining the parameters.
From the results in this study, it would recommend ATP/EMTP to be used for preliminary investigation of
the overvoltage on ground grids of different shapes and the obtained findings could be beneficial and critical
for making decision in further investment for analysis by more advanced simulation programs.
4. CONCLUSION
The models created by ATP/EMTP program to investigate the effects of injected fault current and
resulting overvoltage on ground grids of three different shapes (square, rectangular and L-shaped) showed
that rectangular ground grid had the highest level of overvoltage, particularly at its corner, when the fault
current was injected into its corner. On the contrary, square ground grid was found the have the lowest
overvoltage, especially when the fault current was injected at its center. This study showed that ATP/EMTP
 ISSN: 2088-8708
Int J Elec & Comp Eng, Vol. 11, No. 6, December 2021 : 4689 - 4697
4696
is a simple simulation program with ease of accessibility and uses, particularly in creating the ground grid
models and adding the important parameters. Moreover, it has benefits in less time-consuming and low cost
for computer resources and operating systems. This study concluded that preliminary investigation of
possible overvoltage on ground grid models of different shapes could be achieved by ATP/EMTP program,
which may be suitable for further in-depth analysis by other advanced programs.
REFERENCES
[1] T. Chalardsakul, “Analysis overvoltage in the grounding system of high voltage substation by using ATP/EMTP
program,” Technology Promotion and InnoMag Magazine, vol. 202, pp. 88-93, 2008.
[2] F. E. Mentre and L. Grcev, "EMTP-based model for grounding system analysis," in IEEE Transactions on Power
Delivery, vol. 9, no. 4, pp. 1838-1849, Oct. 1994, doi: 10.1109/61.329517.
[3] R. Shariatinasab and J. Gholinezhad, “The effect of grounding system modeling on lightning-related studies of
transmission lines,” Journal of Applied Research and Technology, vol. 15, no. 6, pp. 545-554, 2017,
doi: 10.1016/j.jart.2017.06.003.
[4] L. D. Grcev and M. Heimbach, "Frequency dependent and transient characteristics of substation grounding
systems," in IEEE Transactions on Power Delivery, vol. 12, no. 1, pp. 172-178, Jan. 1997, doi: 10.1109/61.568238.
[5] A. Geri, "Behaviour of grounding systems excited by high impulse currents: the model and its validation," in IEEE
Transactions on Power Delivery, vol. 14, no. 3, pp. 1008-1017, July 1999, doi: 10.1109/61.772347.
[6] M. I. Lorentzou, N. D. Hatziargyriou, and B. C. Papadias, "Time domain analysis of grounding electrodes impulse
response," in IEEE Transactions on Power Delivery, vol. 18, no. 2, pp. 517-524, April 2003,
doi: 10.1109/TPWRD.2003.809686.
[7] Y. Liu, N. Theethayi, and R. Thottappillil, "An engineering model for transient analysis of grounding system under
lightning strikes: nonuniform transmission-line approach," in IEEE Transactions on Power Delivery, vol. 20, no. 2,
pp. 722-730, Apr. 2005, doi: 10.1109/TPWRD.2004.843437.
[8] A.I. Elgayar and Z. Abdul-Malek, “Induced voltages on a gas pipeline due to lightning strikes on nearby overhead
transmission line,” International Journal of Electrical and Computer Engineering, vol. 6, no. 2, pp. 495-503, 2016.
doi: 10.11591/ijece.v6i2.9395.
[9] M. Adnan, Z. Abdul-Malek, N. S. M. Din, M. I. Jambak, Z. Nawawi, M. A. B. Sidik, “Effect of Lightning impulse
front time on substation grounding system performance,” Indonesian Journal of Electrical Engineering and
Computer Science, vol. 20, no. 2, pp. 569-574, 2020, doi: 10.11591/ijeecs.v20.i2.pp569-574.
[10] Z. Abdul-Malek, M. S. A. Yaman, M. Adnan, “Effects of soil profile on the transient performance of substation
grounding system,” Indonesian Journal of Electrical Engineering and Computer Science, vol. 20, no. 2,
pp. 870-877, 2020, doi: 10.11591/ijeecs.v20.i2.pp870-877.
[11] S. Nikolovski, G. Knezevic, and Z. Baus, “Assessment of step and touch voltages for different multilayer soil
models of complex grounding grid,” International Journal of Electrical and Computer Engineering, vol. 6, no. 4,
pp. 1441-1455, 2016, doi: 10.11591/ijece.v6i4.pp1441-1455.
[12] M. Mokhtari, Z. Abdul-Malek, and C. L. Wooi, “Integration of frequency dependent soil electrical properties in
grounding electrode circuit model,” International Journal of Electrical and Computer Engineering, vol. 6, no. 2,
pp. 792-799, 2016, doi: 10.11591/ijece.v6i2.pp792-799.
[13] S. N. Nikolovski, Z. Baus, and G. Knežević, “Frequency and time response of power plant grounding system
exposed to lightning strike,” International Journal of Electrical and Computer Engineering, vol. 6, no. 2, pp. 512-
525, 2016, doi: 10.11591/ijece.v6i1.9356.
[14] N. M. Tabatabaei and S. R. Mortezaeei, “Design of grounding systems in substation by ETAP intelligent software,”
International Journal on Technical and Physical Problems of Engineering, vol. 2, pp. 45-49, 2010.
[15] D. Prasad and H. C. Sharma, “Designing of Grounding System for High Voltage Substation,” International Journal
of Engineering and Advanced Technology, vol. 2, pp. 61-65, 2013.
[16] M. U. Aslam, M. U. Cheema, M. B. Cheema, and M. Samran, "Design analysis and optimization of ground grid
mesh of extra high voltage substation using an intelligent software," 2014 The 1st International Conference on
Information Technology, Computer, and Electrical Engineering, Semarang, Indonesia, 2014, pp. 339-345,
doi: 10.1109/ICITACEE.2014.7065768.
[17] S. G. Farkoush, A. Wadood, T. Khurshaid, C. Kim, M. Irfan, and S. Rhee, "Reducing the Effect of Lightning on
Step and Touch Voltages in a Grounding Grid Using a Nature-Inspired Genetic Algorithm With ATP-EMTP," in
IEEE Access, vol. 7, pp. 81903-81910, 2019, doi: 10.1109/ACCESS.2019.2923656.
[18] H. N. Amadi, “Design of grounding system for A.C. substations with critical consideration of the mesh, touch and
step potentials,” European Journal of Engineering and Technology, vol. 5, no. 4, pp. 44-57, 2017.
[19] D. D. Vuckovic, N. N. Cvetkovic, and M. S. Stojanovic, “Study on a standard for grounding systems realization,”
Serbian Journal of Electrical Engineering, vol. 9, pp. 393-401, 2012, doi: 10.2298/SJEE1203393V.
[20] A. Phayomhom, S. Sirisumrannukul, and T. Kasirawat, “Safety design of ground grid in distribution substation:
Case study of metropolitan electricity authority’s system,” GMSARN International Journal, vol. 4, pp. 67-74, 2010.
[21] An American National Standard, “IEEE guide for safety in AC substation grounding,” in IEEE Std 80-2000,
pp.1-192, 4 Aug. 2000, doi: 10.1109/IEEESTD.2000.91902.
[22] A. B. Patel and K. Velani, "Digital application for grounding grid design calculations of substation," 2017
Innovations in Power and Advanced Computing Technologies (i-PACT), Vellore, 2017, pp. 1-6,
doi: 10.1109/IPACT.2017.8244947.
Int J Elec & Comp Eng ISSN: 2088-8708 
Investigation of overvoltage on square, rectangular and l-shaped ground grids of… (Krung Luewattana)
4697
[23] N. A. M. Hasni, R. Abd-Rahman, H. Ahmad, N. A. M. Jamail, M. S. Kamaruddin, and S. S. Ridzwan,
“Investigation of potential grounding compound for portable applications,” International Journal of Electrical and
Computer Engineering, vol. 7, no. 6, pp. 3140-3146, 2017, doi: 10.11591/ijece.v7i6.pp3140-3146.
[24] A. J. L. M. Siang, E. H. Sfoog, N. Naji, S. S. Yi, N. A. A. Guntor, and J. Prasetijo, “Ground improvement using
granular pile anchor system resistance to heave and uplift pressure,” Indonesian Journal of Electrical Engineering
and Computer Science, vol. 19, no. 1, pp. 403-411, 2020, doi: 10.11591/ijeecs.v19.i1.pp403-411.
[25] A. A. Salem, R. Abd-Rahman, M. S. Kamarudin, H. Ahmed, and N. A. M. Jamail, “The effect of insulator
geometrical profile on electric field distributions,” Indonesian Journal of Electrical Engineering and Computer
Science, vol. 14, no. 2, pp. 618-627, 2019, doi: 10.11591/ijeecs.v14.i2.pp618-627.
BIBLIOGRAPHIES OF AUTHORS
Krung Luewattana graduated B.Eng., M.Eng., and Ph.D. degrees in Electrical Engineering
(with emphasis on Electrical Power Engineering). His research interests include high voltage,
engineering and insulation, electrical grounding systems, power engineering and power systems,
electromagnetic compatibility, transient in power system and renewable/alternative energy.
Paweena Rattanasena graduated B.Sc. in Microbiology (Chulalongkorn University, Thailand),
M.Sc. in Tropical Infectious Diseases and Ph.D. in Tropical Health (both degrees from the
University of Queensland, Australia). Her research interests include public health and safety,
infectious diseases, and biotechnology.

More Related Content

What's hot

Resource aware wind farm and D-STATCOM optimal sizing and placement in a dist...
Resource aware wind farm and D-STATCOM optimal sizing and placement in a dist...Resource aware wind farm and D-STATCOM optimal sizing and placement in a dist...
Resource aware wind farm and D-STATCOM optimal sizing and placement in a dist...IJECEIAES
 
Heuristic remedial actions in the reliability assessment of high voltage dire...
Heuristic remedial actions in the reliability assessment of high voltage dire...Heuristic remedial actions in the reliability assessment of high voltage dire...
Heuristic remedial actions in the reliability assessment of high voltage dire...IJECEIAES
 
Intelligent control of battery energy storage for microgrid energy management...
Intelligent control of battery energy storage for microgrid energy management...Intelligent control of battery energy storage for microgrid energy management...
Intelligent control of battery energy storage for microgrid energy management...IJECEIAES
 
Various demand side management techniques and its role in smart grid–the stat...
Various demand side management techniques and its role in smart grid–the stat...Various demand side management techniques and its role in smart grid–the stat...
Various demand side management techniques and its role in smart grid–the stat...IJECEIAES
 
Hybrid bypass technique to mitigate leakage current in the grid-tied inverter
Hybrid bypass technique to mitigate leakage current in the grid-tied inverterHybrid bypass technique to mitigate leakage current in the grid-tied inverter
Hybrid bypass technique to mitigate leakage current in the grid-tied inverterIJECEIAES
 
Critical Review of Different Methods for Siting and Sizing Distributed-genera...
Critical Review of Different Methods for Siting and Sizing Distributed-genera...Critical Review of Different Methods for Siting and Sizing Distributed-genera...
Critical Review of Different Methods for Siting and Sizing Distributed-genera...TELKOMNIKA JOURNAL
 
A NOVEL CONTROL STRATEGY FOR POWER QUALITY IMPROVEMENT USING ANN TECHNIQUE FO...
A NOVEL CONTROL STRATEGY FOR POWER QUALITY IMPROVEMENT USING ANN TECHNIQUE FO...A NOVEL CONTROL STRATEGY FOR POWER QUALITY IMPROVEMENT USING ANN TECHNIQUE FO...
A NOVEL CONTROL STRATEGY FOR POWER QUALITY IMPROVEMENT USING ANN TECHNIQUE FO...IJERD Editor
 
IRJET- Comparison between Ideal and Estimated PV Parameters using Evolutionar...
IRJET- Comparison between Ideal and Estimated PV Parameters using Evolutionar...IRJET- Comparison between Ideal and Estimated PV Parameters using Evolutionar...
IRJET- Comparison between Ideal and Estimated PV Parameters using Evolutionar...IRJET Journal
 
Reconfigurable of current-mode differentiator and integrator based-on current...
Reconfigurable of current-mode differentiator and integrator based-on current...Reconfigurable of current-mode differentiator and integrator based-on current...
Reconfigurable of current-mode differentiator and integrator based-on current...IJECEIAES
 
Optimal Integration of the Renewable Energy to the Grid by Considering Small ...
Optimal Integration of the Renewable Energy to the Grid by Considering Small ...Optimal Integration of the Renewable Energy to the Grid by Considering Small ...
Optimal Integration of the Renewable Energy to the Grid by Considering Small ...IJECEIAES
 
Paper id 37201503
Paper id 37201503Paper id 37201503
Paper id 37201503IJRAT
 
Power Flow Analysis of Island Business District 33KV Distribution Grid System...
Power Flow Analysis of Island Business District 33KV Distribution Grid System...Power Flow Analysis of Island Business District 33KV Distribution Grid System...
Power Flow Analysis of Island Business District 33KV Distribution Grid System...IJERA Editor
 
Stochastic control for optimal power flow in islanded microgrid
Stochastic control for optimal power flow in islanded microgridStochastic control for optimal power flow in islanded microgrid
Stochastic control for optimal power flow in islanded microgridIJECEIAES
 
IRJET- Review of Power Quality Problem Improvement by Integration of Solar PV...
IRJET- Review of Power Quality Problem Improvement by Integration of Solar PV...IRJET- Review of Power Quality Problem Improvement by Integration of Solar PV...
IRJET- Review of Power Quality Problem Improvement by Integration of Solar PV...IRJET Journal
 
IRJET- Design and Simulation of Solar PV DC Microgrid for Rural Electrification
IRJET- Design and Simulation of Solar PV DC Microgrid for Rural ElectrificationIRJET- Design and Simulation of Solar PV DC Microgrid for Rural Electrification
IRJET- Design and Simulation of Solar PV DC Microgrid for Rural ElectrificationIRJET Journal
 

What's hot (20)

Resource aware wind farm and D-STATCOM optimal sizing and placement in a dist...
Resource aware wind farm and D-STATCOM optimal sizing and placement in a dist...Resource aware wind farm and D-STATCOM optimal sizing and placement in a dist...
Resource aware wind farm and D-STATCOM optimal sizing and placement in a dist...
 
Heuristic remedial actions in the reliability assessment of high voltage dire...
Heuristic remedial actions in the reliability assessment of high voltage dire...Heuristic remedial actions in the reliability assessment of high voltage dire...
Heuristic remedial actions in the reliability assessment of high voltage dire...
 
Intelligent control of battery energy storage for microgrid energy management...
Intelligent control of battery energy storage for microgrid energy management...Intelligent control of battery energy storage for microgrid energy management...
Intelligent control of battery energy storage for microgrid energy management...
 
Various demand side management techniques and its role in smart grid–the stat...
Various demand side management techniques and its role in smart grid–the stat...Various demand side management techniques and its role in smart grid–the stat...
Various demand side management techniques and its role in smart grid–the stat...
 
Hybrid bypass technique to mitigate leakage current in the grid-tied inverter
Hybrid bypass technique to mitigate leakage current in the grid-tied inverterHybrid bypass technique to mitigate leakage current in the grid-tied inverter
Hybrid bypass technique to mitigate leakage current in the grid-tied inverter
 
A comprehensive review of distributed power system architecture for telecom a...
A comprehensive review of distributed power system architecture for telecom a...A comprehensive review of distributed power system architecture for telecom a...
A comprehensive review of distributed power system architecture for telecom a...
 
Critical Review of Different Methods for Siting and Sizing Distributed-genera...
Critical Review of Different Methods for Siting and Sizing Distributed-genera...Critical Review of Different Methods for Siting and Sizing Distributed-genera...
Critical Review of Different Methods for Siting and Sizing Distributed-genera...
 
A NOVEL CONTROL STRATEGY FOR POWER QUALITY IMPROVEMENT USING ANN TECHNIQUE FO...
A NOVEL CONTROL STRATEGY FOR POWER QUALITY IMPROVEMENT USING ANN TECHNIQUE FO...A NOVEL CONTROL STRATEGY FOR POWER QUALITY IMPROVEMENT USING ANN TECHNIQUE FO...
A NOVEL CONTROL STRATEGY FOR POWER QUALITY IMPROVEMENT USING ANN TECHNIQUE FO...
 
IRJET- Comparison between Ideal and Estimated PV Parameters using Evolutionar...
IRJET- Comparison between Ideal and Estimated PV Parameters using Evolutionar...IRJET- Comparison between Ideal and Estimated PV Parameters using Evolutionar...
IRJET- Comparison between Ideal and Estimated PV Parameters using Evolutionar...
 
Online efficiency optimization of IPMSM for electric vehicles
Online efficiency optimization of IPMSM for electric vehiclesOnline efficiency optimization of IPMSM for electric vehicles
Online efficiency optimization of IPMSM for electric vehicles
 
Reconfigurable of current-mode differentiator and integrator based-on current...
Reconfigurable of current-mode differentiator and integrator based-on current...Reconfigurable of current-mode differentiator and integrator based-on current...
Reconfigurable of current-mode differentiator and integrator based-on current...
 
07116665
0711666507116665
07116665
 
Optimal Integration of the Renewable Energy to the Grid by Considering Small ...
Optimal Integration of the Renewable Energy to the Grid by Considering Small ...Optimal Integration of the Renewable Energy to the Grid by Considering Small ...
Optimal Integration of the Renewable Energy to the Grid by Considering Small ...
 
Paper id 37201503
Paper id 37201503Paper id 37201503
Paper id 37201503
 
Adaptive backstepping controller design based on neural network for PMSM spee...
Adaptive backstepping controller design based on neural network for PMSM spee...Adaptive backstepping controller design based on neural network for PMSM spee...
Adaptive backstepping controller design based on neural network for PMSM spee...
 
Power Flow Analysis of Island Business District 33KV Distribution Grid System...
Power Flow Analysis of Island Business District 33KV Distribution Grid System...Power Flow Analysis of Island Business District 33KV Distribution Grid System...
Power Flow Analysis of Island Business District 33KV Distribution Grid System...
 
Stochastic control for optimal power flow in islanded microgrid
Stochastic control for optimal power flow in islanded microgridStochastic control for optimal power flow in islanded microgrid
Stochastic control for optimal power flow in islanded microgrid
 
IRJET- Review of Power Quality Problem Improvement by Integration of Solar PV...
IRJET- Review of Power Quality Problem Improvement by Integration of Solar PV...IRJET- Review of Power Quality Problem Improvement by Integration of Solar PV...
IRJET- Review of Power Quality Problem Improvement by Integration of Solar PV...
 
Db34623630
Db34623630Db34623630
Db34623630
 
IRJET- Design and Simulation of Solar PV DC Microgrid for Rural Electrification
IRJET- Design and Simulation of Solar PV DC Microgrid for Rural ElectrificationIRJET- Design and Simulation of Solar PV DC Microgrid for Rural Electrification
IRJET- Design and Simulation of Solar PV DC Microgrid for Rural Electrification
 

Similar to Investigation of overvoltage on square, rectangular and L-shaped ground grids of high voltage substations by ATP/EMTP

Design of Earthing System for 230 kV High Voltage Substation by ETAP 12.6 Sof...
Design of Earthing System for 230 kV High Voltage Substation by ETAP 12.6 Sof...Design of Earthing System for 230 kV High Voltage Substation by ETAP 12.6 Sof...
Design of Earthing System for 230 kV High Voltage Substation by ETAP 12.6 Sof...ijtsrd
 
Transient response of grounding systems under impulse lightning current
Transient response of grounding systems under impulse lightning currentTransient response of grounding systems under impulse lightning current
Transient response of grounding systems under impulse lightning currentHimmelstern
 
Machine learning for prediction models to mitigate the voltage deviation in ...
Machine learning for prediction models to mitigate the voltage  deviation in ...Machine learning for prediction models to mitigate the voltage  deviation in ...
Machine learning for prediction models to mitigate the voltage deviation in ...IJECEIAES
 
A Technique for Shunt Active Filter meld micro grid System
A Technique for Shunt Active Filter meld micro grid SystemA Technique for Shunt Active Filter meld micro grid System
A Technique for Shunt Active Filter meld micro grid SystemIJERA Editor
 
A new configuration of patch antenna array for rectenna array applications
A new configuration of patch antenna array for rectenna array applicationsA new configuration of patch antenna array for rectenna array applications
A new configuration of patch antenna array for rectenna array applicationsTELKOMNIKA JOURNAL
 
Power System Problems in Teaching Control Theory on Simulink
Power System Problems in Teaching Control Theory on SimulinkPower System Problems in Teaching Control Theory on Simulink
Power System Problems in Teaching Control Theory on Simulinkijctcm
 
POWER SYSTEM PROBLEMS IN TEACHING CONTROL THEORY ON SIMULINK
POWER SYSTEM PROBLEMS IN TEACHING CONTROL THEORY ON SIMULINKPOWER SYSTEM PROBLEMS IN TEACHING CONTROL THEORY ON SIMULINK
POWER SYSTEM PROBLEMS IN TEACHING CONTROL THEORY ON SIMULINKijctcm
 
Fault analysis in power system using power systems computer aided design
Fault analysis in power system using power systems computer aided designFault analysis in power system using power systems computer aided design
Fault analysis in power system using power systems computer aided designIJAAS Team
 
A HYBRID AC/DC SOLAR POWERED STANDALONE SYSTEM WITHOUT INVERTER BASED ON LOAD...
A HYBRID AC/DC SOLAR POWERED STANDALONE SYSTEM WITHOUT INVERTER BASED ON LOAD...A HYBRID AC/DC SOLAR POWERED STANDALONE SYSTEM WITHOUT INVERTER BASED ON LOAD...
A HYBRID AC/DC SOLAR POWERED STANDALONE SYSTEM WITHOUT INVERTER BASED ON LOAD...Iaetsd Iaetsd
 
Improved Power Quality by using STATCOM Under Various Loading Conditions
Improved Power Quality by using STATCOM Under Various Loading ConditionsImproved Power Quality by using STATCOM Under Various Loading Conditions
Improved Power Quality by using STATCOM Under Various Loading ConditionsIJMTST Journal
 
Optimal_Location_of_Distributed_Generation_and_its.pdf
Optimal_Location_of_Distributed_Generation_and_its.pdfOptimal_Location_of_Distributed_Generation_and_its.pdf
Optimal_Location_of_Distributed_Generation_and_its.pdfTesloachKongGilo
 
Failure Detection in Energized High Voltage Substation Grounding Grids - A Ca...
Failure Detection in Energized High Voltage Substation Grounding Grids - A Ca...Failure Detection in Energized High Voltage Substation Grounding Grids - A Ca...
Failure Detection in Energized High Voltage Substation Grounding Grids - A Ca...inventionjournals
 
Failure Detection in Energized High Voltage Substation Grounding Grids - A Ca...
Failure Detection in Energized High Voltage Substation Grounding Grids - A Ca...Failure Detection in Energized High Voltage Substation Grounding Grids - A Ca...
Failure Detection in Energized High Voltage Substation Grounding Grids - A Ca...inventionjournals
 
IRJET- Feed-Forward Neural Network Based Transient Stability Assessment o...
IRJET-  	  Feed-Forward Neural Network Based Transient Stability Assessment o...IRJET-  	  Feed-Forward Neural Network Based Transient Stability Assessment o...
IRJET- Feed-Forward Neural Network Based Transient Stability Assessment o...IRJET Journal
 
Frequency control in a microgrid including controllable load
Frequency control in a microgrid including controllable loadFrequency control in a microgrid including controllable load
Frequency control in a microgrid including controllable loadIAEME Publication
 

Similar to Investigation of overvoltage on square, rectangular and L-shaped ground grids of high voltage substations by ATP/EMTP (20)

Ieee depth
Ieee depthIeee depth
Ieee depth
 
Design of Earthing System for 230 kV High Voltage Substation by ETAP 12.6 Sof...
Design of Earthing System for 230 kV High Voltage Substation by ETAP 12.6 Sof...Design of Earthing System for 230 kV High Voltage Substation by ETAP 12.6 Sof...
Design of Earthing System for 230 kV High Voltage Substation by ETAP 12.6 Sof...
 
Transient response of grounding systems under impulse lightning current
Transient response of grounding systems under impulse lightning currentTransient response of grounding systems under impulse lightning current
Transient response of grounding systems under impulse lightning current
 
Machine learning for prediction models to mitigate the voltage deviation in ...
Machine learning for prediction models to mitigate the voltage  deviation in ...Machine learning for prediction models to mitigate the voltage  deviation in ...
Machine learning for prediction models to mitigate the voltage deviation in ...
 
A Technique for Shunt Active Filter meld micro grid System
A Technique for Shunt Active Filter meld micro grid SystemA Technique for Shunt Active Filter meld micro grid System
A Technique for Shunt Active Filter meld micro grid System
 
A new configuration of patch antenna array for rectenna array applications
A new configuration of patch antenna array for rectenna array applicationsA new configuration of patch antenna array for rectenna array applications
A new configuration of patch antenna array for rectenna array applications
 
Power System Problems in Teaching Control Theory on Simulink
Power System Problems in Teaching Control Theory on SimulinkPower System Problems in Teaching Control Theory on Simulink
Power System Problems in Teaching Control Theory on Simulink
 
POWER SYSTEM PROBLEMS IN TEACHING CONTROL THEORY ON SIMULINK
POWER SYSTEM PROBLEMS IN TEACHING CONTROL THEORY ON SIMULINKPOWER SYSTEM PROBLEMS IN TEACHING CONTROL THEORY ON SIMULINK
POWER SYSTEM PROBLEMS IN TEACHING CONTROL THEORY ON SIMULINK
 
Fault analysis in power system using power systems computer aided design
Fault analysis in power system using power systems computer aided designFault analysis in power system using power systems computer aided design
Fault analysis in power system using power systems computer aided design
 
Half Cycle Discrete Transformation for Voltage Sag Improvement in an Islanded...
Half Cycle Discrete Transformation for Voltage Sag Improvement in an Islanded...Half Cycle Discrete Transformation for Voltage Sag Improvement in an Islanded...
Half Cycle Discrete Transformation for Voltage Sag Improvement in an Islanded...
 
A HYBRID AC/DC SOLAR POWERED STANDALONE SYSTEM WITHOUT INVERTER BASED ON LOAD...
A HYBRID AC/DC SOLAR POWERED STANDALONE SYSTEM WITHOUT INVERTER BASED ON LOAD...A HYBRID AC/DC SOLAR POWERED STANDALONE SYSTEM WITHOUT INVERTER BASED ON LOAD...
A HYBRID AC/DC SOLAR POWERED STANDALONE SYSTEM WITHOUT INVERTER BASED ON LOAD...
 
Improved Power Quality by using STATCOM Under Various Loading Conditions
Improved Power Quality by using STATCOM Under Various Loading ConditionsImproved Power Quality by using STATCOM Under Various Loading Conditions
Improved Power Quality by using STATCOM Under Various Loading Conditions
 
10.1.1.192.9435(1)
10.1.1.192.9435(1)10.1.1.192.9435(1)
10.1.1.192.9435(1)
 
Ee33783786
Ee33783786Ee33783786
Ee33783786
 
Ee33783786
Ee33783786Ee33783786
Ee33783786
 
Optimal_Location_of_Distributed_Generation_and_its.pdf
Optimal_Location_of_Distributed_Generation_and_its.pdfOptimal_Location_of_Distributed_Generation_and_its.pdf
Optimal_Location_of_Distributed_Generation_and_its.pdf
 
Failure Detection in Energized High Voltage Substation Grounding Grids - A Ca...
Failure Detection in Energized High Voltage Substation Grounding Grids - A Ca...Failure Detection in Energized High Voltage Substation Grounding Grids - A Ca...
Failure Detection in Energized High Voltage Substation Grounding Grids - A Ca...
 
Failure Detection in Energized High Voltage Substation Grounding Grids - A Ca...
Failure Detection in Energized High Voltage Substation Grounding Grids - A Ca...Failure Detection in Energized High Voltage Substation Grounding Grids - A Ca...
Failure Detection in Energized High Voltage Substation Grounding Grids - A Ca...
 
IRJET- Feed-Forward Neural Network Based Transient Stability Assessment o...
IRJET-  	  Feed-Forward Neural Network Based Transient Stability Assessment o...IRJET-  	  Feed-Forward Neural Network Based Transient Stability Assessment o...
IRJET- Feed-Forward Neural Network Based Transient Stability Assessment o...
 
Frequency control in a microgrid including controllable load
Frequency control in a microgrid including controllable loadFrequency control in a microgrid including controllable load
Frequency control in a microgrid including controllable load
 

More from IJECEIAES

Cloud service ranking with an integration of k-means algorithm and decision-m...
Cloud service ranking with an integration of k-means algorithm and decision-m...Cloud service ranking with an integration of k-means algorithm and decision-m...
Cloud service ranking with an integration of k-means algorithm and decision-m...IJECEIAES
 
Prediction of the risk of developing heart disease using logistic regression
Prediction of the risk of developing heart disease using logistic regressionPrediction of the risk of developing heart disease using logistic regression
Prediction of the risk of developing heart disease using logistic regressionIJECEIAES
 
Predictive analysis of terrorist activities in Thailand's Southern provinces:...
Predictive analysis of terrorist activities in Thailand's Southern provinces:...Predictive analysis of terrorist activities in Thailand's Southern provinces:...
Predictive analysis of terrorist activities in Thailand's Southern provinces:...IJECEIAES
 
Optimal model of vehicular ad-hoc network assisted by unmanned aerial vehicl...
Optimal model of vehicular ad-hoc network assisted by  unmanned aerial vehicl...Optimal model of vehicular ad-hoc network assisted by  unmanned aerial vehicl...
Optimal model of vehicular ad-hoc network assisted by unmanned aerial vehicl...IJECEIAES
 
Improving cyberbullying detection through multi-level machine learning
Improving cyberbullying detection through multi-level machine learningImproving cyberbullying detection through multi-level machine learning
Improving cyberbullying detection through multi-level machine learningIJECEIAES
 
Comparison of time series temperature prediction with autoregressive integrat...
Comparison of time series temperature prediction with autoregressive integrat...Comparison of time series temperature prediction with autoregressive integrat...
Comparison of time series temperature prediction with autoregressive integrat...IJECEIAES
 
Strengthening data integrity in academic document recording with blockchain a...
Strengthening data integrity in academic document recording with blockchain a...Strengthening data integrity in academic document recording with blockchain a...
Strengthening data integrity in academic document recording with blockchain a...IJECEIAES
 
Design of storage benchmark kit framework for supporting the file storage ret...
Design of storage benchmark kit framework for supporting the file storage ret...Design of storage benchmark kit framework for supporting the file storage ret...
Design of storage benchmark kit framework for supporting the file storage ret...IJECEIAES
 
Detection of diseases in rice leaf using convolutional neural network with tr...
Detection of diseases in rice leaf using convolutional neural network with tr...Detection of diseases in rice leaf using convolutional neural network with tr...
Detection of diseases in rice leaf using convolutional neural network with tr...IJECEIAES
 
A systematic review of in-memory database over multi-tenancy
A systematic review of in-memory database over multi-tenancyA systematic review of in-memory database over multi-tenancy
A systematic review of in-memory database over multi-tenancyIJECEIAES
 
Agriculture crop yield prediction using inertia based cat swarm optimization
Agriculture crop yield prediction using inertia based cat swarm optimizationAgriculture crop yield prediction using inertia based cat swarm optimization
Agriculture crop yield prediction using inertia based cat swarm optimizationIJECEIAES
 
Three layer hybrid learning to improve intrusion detection system performance
Three layer hybrid learning to improve intrusion detection system performanceThree layer hybrid learning to improve intrusion detection system performance
Three layer hybrid learning to improve intrusion detection system performanceIJECEIAES
 
Non-binary codes approach on the performance of short-packet full-duplex tran...
Non-binary codes approach on the performance of short-packet full-duplex tran...Non-binary codes approach on the performance of short-packet full-duplex tran...
Non-binary codes approach on the performance of short-packet full-duplex tran...IJECEIAES
 
Improved design and performance of the global rectenna system for wireless po...
Improved design and performance of the global rectenna system for wireless po...Improved design and performance of the global rectenna system for wireless po...
Improved design and performance of the global rectenna system for wireless po...IJECEIAES
 
Advanced hybrid algorithms for precise multipath channel estimation in next-g...
Advanced hybrid algorithms for precise multipath channel estimation in next-g...Advanced hybrid algorithms for precise multipath channel estimation in next-g...
Advanced hybrid algorithms for precise multipath channel estimation in next-g...IJECEIAES
 
Performance analysis of 2D optical code division multiple access through unde...
Performance analysis of 2D optical code division multiple access through unde...Performance analysis of 2D optical code division multiple access through unde...
Performance analysis of 2D optical code division multiple access through unde...IJECEIAES
 
On performance analysis of non-orthogonal multiple access downlink for cellul...
On performance analysis of non-orthogonal multiple access downlink for cellul...On performance analysis of non-orthogonal multiple access downlink for cellul...
On performance analysis of non-orthogonal multiple access downlink for cellul...IJECEIAES
 
Phase delay through slot-line beam switching microstrip patch array antenna d...
Phase delay through slot-line beam switching microstrip patch array antenna d...Phase delay through slot-line beam switching microstrip patch array antenna d...
Phase delay through slot-line beam switching microstrip patch array antenna d...IJECEIAES
 
A simple feed orthogonal excitation X-band dual circular polarized microstrip...
A simple feed orthogonal excitation X-band dual circular polarized microstrip...A simple feed orthogonal excitation X-band dual circular polarized microstrip...
A simple feed orthogonal excitation X-band dual circular polarized microstrip...IJECEIAES
 
A taxonomy on power optimization techniques for fifthgeneration heterogenous ...
A taxonomy on power optimization techniques for fifthgeneration heterogenous ...A taxonomy on power optimization techniques for fifthgeneration heterogenous ...
A taxonomy on power optimization techniques for fifthgeneration heterogenous ...IJECEIAES
 

More from IJECEIAES (20)

Cloud service ranking with an integration of k-means algorithm and decision-m...
Cloud service ranking with an integration of k-means algorithm and decision-m...Cloud service ranking with an integration of k-means algorithm and decision-m...
Cloud service ranking with an integration of k-means algorithm and decision-m...
 
Prediction of the risk of developing heart disease using logistic regression
Prediction of the risk of developing heart disease using logistic regressionPrediction of the risk of developing heart disease using logistic regression
Prediction of the risk of developing heart disease using logistic regression
 
Predictive analysis of terrorist activities in Thailand's Southern provinces:...
Predictive analysis of terrorist activities in Thailand's Southern provinces:...Predictive analysis of terrorist activities in Thailand's Southern provinces:...
Predictive analysis of terrorist activities in Thailand's Southern provinces:...
 
Optimal model of vehicular ad-hoc network assisted by unmanned aerial vehicl...
Optimal model of vehicular ad-hoc network assisted by  unmanned aerial vehicl...Optimal model of vehicular ad-hoc network assisted by  unmanned aerial vehicl...
Optimal model of vehicular ad-hoc network assisted by unmanned aerial vehicl...
 
Improving cyberbullying detection through multi-level machine learning
Improving cyberbullying detection through multi-level machine learningImproving cyberbullying detection through multi-level machine learning
Improving cyberbullying detection through multi-level machine learning
 
Comparison of time series temperature prediction with autoregressive integrat...
Comparison of time series temperature prediction with autoregressive integrat...Comparison of time series temperature prediction with autoregressive integrat...
Comparison of time series temperature prediction with autoregressive integrat...
 
Strengthening data integrity in academic document recording with blockchain a...
Strengthening data integrity in academic document recording with blockchain a...Strengthening data integrity in academic document recording with blockchain a...
Strengthening data integrity in academic document recording with blockchain a...
 
Design of storage benchmark kit framework for supporting the file storage ret...
Design of storage benchmark kit framework for supporting the file storage ret...Design of storage benchmark kit framework for supporting the file storage ret...
Design of storage benchmark kit framework for supporting the file storage ret...
 
Detection of diseases in rice leaf using convolutional neural network with tr...
Detection of diseases in rice leaf using convolutional neural network with tr...Detection of diseases in rice leaf using convolutional neural network with tr...
Detection of diseases in rice leaf using convolutional neural network with tr...
 
A systematic review of in-memory database over multi-tenancy
A systematic review of in-memory database over multi-tenancyA systematic review of in-memory database over multi-tenancy
A systematic review of in-memory database over multi-tenancy
 
Agriculture crop yield prediction using inertia based cat swarm optimization
Agriculture crop yield prediction using inertia based cat swarm optimizationAgriculture crop yield prediction using inertia based cat swarm optimization
Agriculture crop yield prediction using inertia based cat swarm optimization
 
Three layer hybrid learning to improve intrusion detection system performance
Three layer hybrid learning to improve intrusion detection system performanceThree layer hybrid learning to improve intrusion detection system performance
Three layer hybrid learning to improve intrusion detection system performance
 
Non-binary codes approach on the performance of short-packet full-duplex tran...
Non-binary codes approach on the performance of short-packet full-duplex tran...Non-binary codes approach on the performance of short-packet full-duplex tran...
Non-binary codes approach on the performance of short-packet full-duplex tran...
 
Improved design and performance of the global rectenna system for wireless po...
Improved design and performance of the global rectenna system for wireless po...Improved design and performance of the global rectenna system for wireless po...
Improved design and performance of the global rectenna system for wireless po...
 
Advanced hybrid algorithms for precise multipath channel estimation in next-g...
Advanced hybrid algorithms for precise multipath channel estimation in next-g...Advanced hybrid algorithms for precise multipath channel estimation in next-g...
Advanced hybrid algorithms for precise multipath channel estimation in next-g...
 
Performance analysis of 2D optical code division multiple access through unde...
Performance analysis of 2D optical code division multiple access through unde...Performance analysis of 2D optical code division multiple access through unde...
Performance analysis of 2D optical code division multiple access through unde...
 
On performance analysis of non-orthogonal multiple access downlink for cellul...
On performance analysis of non-orthogonal multiple access downlink for cellul...On performance analysis of non-orthogonal multiple access downlink for cellul...
On performance analysis of non-orthogonal multiple access downlink for cellul...
 
Phase delay through slot-line beam switching microstrip patch array antenna d...
Phase delay through slot-line beam switching microstrip patch array antenna d...Phase delay through slot-line beam switching microstrip patch array antenna d...
Phase delay through slot-line beam switching microstrip patch array antenna d...
 
A simple feed orthogonal excitation X-band dual circular polarized microstrip...
A simple feed orthogonal excitation X-band dual circular polarized microstrip...A simple feed orthogonal excitation X-band dual circular polarized microstrip...
A simple feed orthogonal excitation X-band dual circular polarized microstrip...
 
A taxonomy on power optimization techniques for fifthgeneration heterogenous ...
A taxonomy on power optimization techniques for fifthgeneration heterogenous ...A taxonomy on power optimization techniques for fifthgeneration heterogenous ...
A taxonomy on power optimization techniques for fifthgeneration heterogenous ...
 

Recently uploaded

the ladakh protest in leh ladakh 2024 sonam wangchuk.pptx
the ladakh protest in leh ladakh 2024 sonam wangchuk.pptxthe ladakh protest in leh ladakh 2024 sonam wangchuk.pptx
the ladakh protest in leh ladakh 2024 sonam wangchuk.pptxhumanexperienceaaa
 
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...ranjana rawat
 
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICSAPPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICSKurinjimalarL3
 
Software Development Life Cycle By Team Orange (Dept. of Pharmacy)
Software Development Life Cycle By  Team Orange (Dept. of Pharmacy)Software Development Life Cycle By  Team Orange (Dept. of Pharmacy)
Software Development Life Cycle By Team Orange (Dept. of Pharmacy)Suman Mia
 
IMPLICATIONS OF THE ABOVE HOLISTIC UNDERSTANDING OF HARMONY ON PROFESSIONAL E...
IMPLICATIONS OF THE ABOVE HOLISTIC UNDERSTANDING OF HARMONY ON PROFESSIONAL E...IMPLICATIONS OF THE ABOVE HOLISTIC UNDERSTANDING OF HARMONY ON PROFESSIONAL E...
IMPLICATIONS OF THE ABOVE HOLISTIC UNDERSTANDING OF HARMONY ON PROFESSIONAL E...RajaP95
 
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur High Profile
 
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130Suhani Kapoor
 
Call Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service Nashik
Call Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service NashikCall Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service Nashik
Call Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service NashikCall Girls in Nagpur High Profile
 
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escortsranjana rawat
 
Introduction to Multiple Access Protocol.pptx
Introduction to Multiple Access Protocol.pptxIntroduction to Multiple Access Protocol.pptx
Introduction to Multiple Access Protocol.pptxupamatechverse
 
(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service
(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service
(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Serviceranjana rawat
 
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur High Profile
 
Extrusion Processes and Their Limitations
Extrusion Processes and Their LimitationsExtrusion Processes and Their Limitations
Extrusion Processes and Their Limitations120cr0395
 
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...ranjana rawat
 
College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service NashikCollege Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service NashikCall Girls in Nagpur High Profile
 
247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).ppt
247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).ppt247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).ppt
247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).pptssuser5c9d4b1
 
Porous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writingPorous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writingrakeshbaidya232001
 
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINE
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINEMANUFACTURING PROCESS-II UNIT-2 LATHE MACHINE
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINESIVASHANKAR N
 
(TARA) Talegaon Dabhade Call Girls Just Call 7001035870 [ Cash on Delivery ] ...
(TARA) Talegaon Dabhade Call Girls Just Call 7001035870 [ Cash on Delivery ] ...(TARA) Talegaon Dabhade Call Girls Just Call 7001035870 [ Cash on Delivery ] ...
(TARA) Talegaon Dabhade Call Girls Just Call 7001035870 [ Cash on Delivery ] ...ranjana rawat
 

Recently uploaded (20)

the ladakh protest in leh ladakh 2024 sonam wangchuk.pptx
the ladakh protest in leh ladakh 2024 sonam wangchuk.pptxthe ladakh protest in leh ladakh 2024 sonam wangchuk.pptx
the ladakh protest in leh ladakh 2024 sonam wangchuk.pptx
 
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
 
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICSAPPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
 
Call Us -/9953056974- Call Girls In Vikaspuri-/- Delhi NCR
Call Us -/9953056974- Call Girls In Vikaspuri-/- Delhi NCRCall Us -/9953056974- Call Girls In Vikaspuri-/- Delhi NCR
Call Us -/9953056974- Call Girls In Vikaspuri-/- Delhi NCR
 
Software Development Life Cycle By Team Orange (Dept. of Pharmacy)
Software Development Life Cycle By  Team Orange (Dept. of Pharmacy)Software Development Life Cycle By  Team Orange (Dept. of Pharmacy)
Software Development Life Cycle By Team Orange (Dept. of Pharmacy)
 
IMPLICATIONS OF THE ABOVE HOLISTIC UNDERSTANDING OF HARMONY ON PROFESSIONAL E...
IMPLICATIONS OF THE ABOVE HOLISTIC UNDERSTANDING OF HARMONY ON PROFESSIONAL E...IMPLICATIONS OF THE ABOVE HOLISTIC UNDERSTANDING OF HARMONY ON PROFESSIONAL E...
IMPLICATIONS OF THE ABOVE HOLISTIC UNDERSTANDING OF HARMONY ON PROFESSIONAL E...
 
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
 
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
 
Call Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service Nashik
Call Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service NashikCall Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service Nashik
Call Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service Nashik
 
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
 
Introduction to Multiple Access Protocol.pptx
Introduction to Multiple Access Protocol.pptxIntroduction to Multiple Access Protocol.pptx
Introduction to Multiple Access Protocol.pptx
 
(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service
(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service
(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service
 
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
 
Extrusion Processes and Their Limitations
Extrusion Processes and Their LimitationsExtrusion Processes and Their Limitations
Extrusion Processes and Their Limitations
 
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
 
College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service NashikCollege Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
 
247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).ppt
247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).ppt247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).ppt
247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).ppt
 
Porous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writingPorous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writing
 
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINE
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINEMANUFACTURING PROCESS-II UNIT-2 LATHE MACHINE
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINE
 
(TARA) Talegaon Dabhade Call Girls Just Call 7001035870 [ Cash on Delivery ] ...
(TARA) Talegaon Dabhade Call Girls Just Call 7001035870 [ Cash on Delivery ] ...(TARA) Talegaon Dabhade Call Girls Just Call 7001035870 [ Cash on Delivery ] ...
(TARA) Talegaon Dabhade Call Girls Just Call 7001035870 [ Cash on Delivery ] ...
 

Investigation of overvoltage on square, rectangular and L-shaped ground grids of high voltage substations by ATP/EMTP

  • 1. International Journal of Electrical and Computer Engineering (IJECE) Vol. 11, No. 6, December 2021, pp. 4689~4697 ISSN: 2088-8708, DOI: 10.11591/ijece.v11i6.pp4689-4697  4689 Journal homepage: http://ijece.iaescore.com Investigation of overvoltage on square, rectangular and L-shaped ground grids of high voltage substations by ATP/EMTP Krung Luewattana1 , Paweena Rattanasena2 1 Sub-Department of Electrical Engineering, Faculty of Science and Technology, Phranakhon Si Ayutthaya Rajabhat University, Ayutthaya, Thailand 2 Department of Applied Science, Faculty of Science and Technology, Phranakhon Si Ayutthaya Rajabhat University, Ayutthaya, Thailand Article Info ABSTRACT Article history: Received Aug 3, 2020 Revised Mar 11, 2021 Accepted Mar 23, 2021 Ground grid system is important for preventing the hazardous effects of overvoltage in high voltage substations due to fault current perhaps from lightning strike or device malfunction. Therefore, this study aimed to investigate the effects of overvoltage on square, rectangular and L-shaped ground grids with ground rods being distributed in mesh-pattern by using alternate transients program/electromagnetic transients program (ATP/EMTP) program. The models were simulated in the cases that 25 kA- fault current being injected into the center or one of the corners of ground grids. The results showed that the highest level of overvoltage (6.3349 kV) was detected at the corner of rectangular ground grid when the fault current was injected into its corner. However, the lowest level of overvoltage was found when the fault current was injected into the center of square ground grid. The results from this study indicated that ATP/EMTP program was useful for preliminary investigation of overvoltage on ground grids of different shapes. The obtained knowledge could be beneficial for further designing of ground grid systems of high voltage substations to receive the minimal damages due to fault current. Keywords: Ground grid system Ground potential rise High voltage substation Overvoltage This is an open access article under the CC BY-SA license. Corresponding Author: Krung Luewattana Department of Electrical Engineering Faculty of Science and Technology Phranakhon Si Ayutthaya Rajabhat University Ayutthaya, Thailand Email: zaraburi@yahoo.com 1. INTRODUCTION At present, the transmission and distribution systems of electrical power between substations are extremely necessary for national development. These systems require the well-designed substations and ground grids to maximize their efficiency and reliability as well as to protect the working staff and important electrical devices that locating inside the substations or nearby proximity. Particularly, the reliable ground grid can play very important role in the case of overvoltage due to the natural disaster, lightning strike and switching device malfunction [1]. Since ground grid is a large system and too difficult to be created as demonstrative model under laboratory conditions, the computer programs hence become very useful and convenient for simulating such model. The computer programs, for example, current distribution in earth and grounding system (CDEGS), power system computer aided design (PSCAD), fast Fourier transformation
  • 2.  ISSN: 2088-8708 Int J Elec & Comp Eng, Vol. 11, No. 6, December 2021 : 4689 - 4697 4690 (FFT), COMSOL, and alternate transient program/electromagnetic transients program (ATP/EMTP), have been applied with different advantages and disadvantages. Initially, electromagnetic transients program (EMTP) was used for simulating the transmission line and ground grid models and then analyzing their lightning protection systems and dynamic behaviors during the occurrence of overvoltage on ground systems. The obtained results of this study were compared with the calculated ground potential rise (GPR). EMTP was also used for designing the lightning protection system of high voltage substation [2], [3]. In addition, the transient that occurred on ground grids and the frequency dependent characteristics of large ground grids were simulated based on the electromagnetic field theory approach by the computer model. This study also explored the effects of GPR, relative permeability of soil, and depth of ground grids buried in soil on the electromagnetic compatibility (EMC) in the case of lightning strike on ground grid [4]. Similar case of ground grid system that being injected with transient current has been simulated by the computer model and then endorsed by the experiments under laboratory conditions [5]. Furthermore, EMTP program was used for developing a model of double exponential time function from the inverse fast fourier transformation (IFFT) to analyze the response time of ground rod impulse and explore the dynamics between lightning protection and ground and the effects of charge that dispersing into the ground [6]. In addition, the effects of soil properties on impedance and transient responses of grounding electrode were investigated by the frequency-dependent soil model, which integrating the frequency-dependent soil electrical properties into the circuit model of grounding electrode and measuring the voltage response of grounding electrode. Comparison was performed between the voltage responses of the grounding electrode occurred in the circuit model and that in the electromagnetic model, which showing that the voltage peaks and the wave shapes obtained from these two models were very similar with less than 1% difference [7]. Furthermore, power system computer aided design (PSCAD) and current distribution, electromagnetic interference, grounding and soil structure analysis (CDEGS) programs were applied for investigating the possible severity of lightning strike on transmission line tower and nearby gas pipeline. However, CDEGS program was found to illustrate the effects of soil structure on induced voltage more accurately. Since CDEGS could show the results in three-dimensional (3D) illustrations and perform integration of frequency dependent soil electrical properties in grounding electrode circuit model, it was therefore used for examining the impacts of different soil resistivity levels, conductor materials, lightning impulse voltage front time waveforms, and soil profiles (uniform, 2-layer, and 3-layer) [8]-[12]. Interestingly, the use of CDEGS program could help to create the 3D plots of power plant’s grounding system that was struck by lightning current and illustrate that the scalar potentials and electric fields were seriously affected [13]. In addition, the electrical transient analyzer program (ETAP) was used to optimize the similar parameters, especially the conductors’ types, lengths, depths, and sizes [14]-[16]. In this study, the objective was to use ATP/EMTP for exploring the effects of overvoltage on three different ground grids (square, rectangular, and L-shaped ground grids with the same size of 324 m2 ) of high voltage substation. This is because ATP/EMTP is a convenient and simple program with ease of access that can help to preliminarily investigate the effects of overvoltage on various spots of ground grids with different shapes. The ground grids were designed according to the IEEE 80-2000 standard and therefore the obtained knowledge may be useful for designing the shape of ground grid that could protect the electrical equipment and ensure the safety of personnel inside the substation against electric shocks. This study may also provide the basic knowledge for further analysis by other advanced programs, and this could also help to understand which spots of substation that were minimally affected by overvoltage and should be used for placing the important electrical equipment [17]-[20]. This paper is organized is being as: Section 2 presents the designs of ground grid models and simulation process. The levels of overvoltage from simulations were presented and compared with the calculated GPR in section 3. Finally, section 4 presents the conclusions and reference list. 2. RESEARCH METHOD 2.1. Designs of ground grid systems of high voltage substation Firstly, three models of ground grid systems of high voltage substation were designed, including square with the dimension of 18×18 m, rectangular of 27×12 m, and L-shaped of 18×12+12×9 m, with the equal size of 324 m2 . Even though these three models had different shapes, each of them was equipped with 24 ground rods distributed in mesh-pattern and had the same important parameters according to the standard of IEEE Std. 80-2000 [21] as shown in Figure 1. 2.2. Devices and parameters for simulation by ATP/EMTP program Next, the devices of ground grids were determined by ATP/EMTP program. Initially, the grid conductor was chosen by the command ‘Line/Cable’ followed by ‘RLC Pi-equiv’. Then, ground rod was
  • 3. Int J Elec & Comp Eng ISSN: 2088-8708  Investigation of overvoltage on square, rectangular and l-shaped ground grids of… (Krung Luewattana) 4691 selected by the command ‘branch linear’ followed by ‘resistor’. Subsequently, the current sources for injecting fault current into the ground grid system was selected by the command ‘Heidler type 15’. Finally, all these devices were connected together to create the models of square, rectangular and L-shaped ground grids as shown in the step 2.3. The parameters to be used in these models were shown in Table 1. (a) (b) (c) Figure 1. Three models of ground grid system, (a) square, (b) rectangular, and (c) L-shaped Table 1. Parameters for ground grid models Parameter Value Unit Resistivity 1.7 × 10-8 Ω-m Cross sectional area of conductor 95 mm2 Resistance 5.3685 × 10-4 Ω-m Depth of ground rods 0.5 m Span length of grid conductor 3 m Inductance 1620.2087 mH/m Earth permittivity 8 × 10-11 F/m Capacitance 4.44387 × 10-4 µF/m Soil resistivity 10 Ω-m Length of ground rod 3 m Diameter of ground rod 16 mm Resistance of ground rod 3.508 Ω-m Fault current 25 kA 2.3. Square, rectangular and L-shaped ground grids with ground rods distributed in mesh-pattern From previous step, the devices and parameters were determined for creating the square, rectangular and L-shaped ground grid models with ground rods distributed in mesh-pattern as shown in Figures 2-4. Next, these models were used for simulating the case of 25 kA-fault current being injected directly into the center or one of the corners of ground grid systems, example was shown in Figure 2. Subsequently, levels of overvoltage measured on a diagonal line and at a corner of ground grids were recorded and plotted as shown in the section 3. Figure 2. Model of square ground grid with ground rods distributed in mesh pattern for simulation by ATP/EMTP program
  • 4.  ISSN: 2088-8708 Int J Elec & Comp Eng, Vol. 11, No. 6, December 2021 : 4689 - 4697 4692 Figure 3. Model of rectangular ground grid with ground rods distributed in mesh-pattern for simulation by ATP/EMTP program Figure 4. Model of L-shaped ground grid with ground rods distributed in mesh-pattern for simulation by ATP/EMTP program 2.4. Equations for ground grid simulation The levels of maximum GPR of square, rectangular and L-shaped ground grids were calculated from the as described by [22]. Since the calculations of these cases gave only slightly different levels of GPR, the maximum GPR (5.130 kV) was therefore used for comparing with the results obtained from simulations of three cases by using ATP/EMTP program according to IEEE Std. 80-2000 [21], [22]. 3. RESULTS AND DISCUSSION By ATP/EMTP program, the cases of fault current being injected into the center or one of the corners of each ground grid were simulated, and the levels of overvoltage on a diagonal line and at a corner of that ground grid were measured as shown in Figures 5 and 6 for square, Figures 7 and 8 for rectangular, Figures 9 and 10 for L-shaped ground grids. The levels of overvoltage from simulations of square, rectangular and L-shaped ground grids were then compared with calculated GPR as shown in Figure 11. In the case of square ground grid with ground rods distributed in mesh-pattern, the maximum overvoltage could be detected when the fault current was injected into the corner of ground grid. The maximum overvoltage
  • 5. Int J Elec & Comp Eng ISSN: 2088-8708  Investigation of overvoltage on square, rectangular and l-shaped ground grids of… (Krung Luewattana) 4693 measured on diagonal line and at corner were 5.8528 kV Figure 6(a) and 5.9674 kV Figure 6(b), which were higher than the calculated GPR 5.130 kV, Figure 11 for 14.09% and 16.32%, respectively. For the case of rectangular and L-shaped ground grids, similar results of maximum overvoltage were detected when the fault current was injected into the corner of ground grid. For rectangular ground grid, when the fault current was injected into the corner, the maximum overvoltage measured on diagonal line and at corner were 6.2089 kV Figure 8(a) and 6.3349 kV Figure 8(b), which were higher than the calculated GPR for 21.03% and 23.48%, respectively. Also, In the case of L-shaped ground grid, when the fault current was injected into the corner, the maximum overvoltage measured on diagonal line and at corner were 6.1407 Figure 10(a) and 6.1808 kV Figure 10(b), which were higher than the calculated GPR for 19.70% and 20.48%, respectively. (a) (b) Figure 5. Voltage distribution; (a) on a diagonal line, (b) at a corner of square ground grid when the fault current being injected into the center of ground grid (a) (b) Figure 6. Voltage distribution; (a) on a diagonal line, (b) at a corner of square ground grid when the fault current being injected into the corner of ground grid (a) (b) Figure 7. Voltage distribution; (a) on a diagonal line, (b) at a corner of rectangular ground grid when the fault current being injected into the center of ground grid
  • 6.  ISSN: 2088-8708 Int J Elec & Comp Eng, Vol. 11, No. 6, December 2021 : 4689 - 4697 4694 (a) (b) Figure 8. Voltage distribution; (a) on a diagonal line, (b) at a corner of rectangular ground grid when the fault current being injected into the corner of ground grid (a) (b) Figure 9. Voltage distribution; (a) on a diagonal line, (b) at a corner of L-shaped ground grid when the fault current being injected into the center of ground grid (a) (b) Figure 10. Voltage distribution; (a) on a diagonal line, (b) at a corner of L-shaped ground grid when the fault current being injected into the corner of ground grid According to these three models, the square ground grid was found to have the lowest overvoltage. This may be because square shape is symmetrical, and when the fault current has flown through the conductor in the center of this ground grid system, the connecting points of system’s intersection between ground grid and ground rods, which are symmetrically joined together by exothermic welding both horizontally and vertically, may help to release the fault current very rapidly in spherical radius. Consequently, the overvoltage occurring on square ground grid may return back to the surface of the earth at the levels lower than that of rectangular and L-shaped ground grids and quickly disperse into the earth. It could be shown in the case of injecting the fault current into the center of square ground grid and measuring the overvoltage on a diagonal line that resulting in the overvoltage of 5.6254 kV Figure 5(a) which being lower than that of rectangular and L-shaped ground grids for 3.1% and 5.28%, respectively.
  • 7. Int J Elec & Comp Eng ISSN: 2088-8708  Investigation of overvoltage on square, rectangular and l-shaped ground grids of… (Krung Luewattana) 4695 Figure 11. Comparison of overvoltage on three shapes of ground grids with calculated GPR. The first abbreviations were the spots for injecting fault current (Ct = center, Cn = corner) and the second abbreviations were the spots for measuring overvoltage (Di = diagonal line, Cn = corner) In contrast, the rectangular model was shown to have the highest overvoltage at 6.3349 kV Figure 8(b) in the case of injecting the fault current into the corner and measuring the overvoltage also at the corner. This may be because the rectangular shape is not symmetrical and, when the large amount of fault current has been injected into the corner, high intensity magnetic field may be induced. The reason may be due to that the conductor used in this study is copper, which is diamagnetic and highly capable of inducing magnetic field, especially at the corner of system’s intersection where the ground grid and ground rods are joined together by exothermic welding in unsymmetrically pattern. The overvoltage may not well disperse to the underground earth, resulting in the overvoltage at levels higher than that of square and L-shaped ground grids for 5.8 and 2.43%, respectively. However, the L-shaped ground grid was demonstrated to have average overvoltage when being compared with the other two ground grids. This may be due to that L-shaped ground grid has both symmetrical and unsymmetrical areas and therefore the overvoltage may disperse either effectively or poorly to the underground earth Figure 4. From this study, the results may suggest that ATP/EMTP, a widely-used and simple program, can be beneficial for investigating the effects of overvoltage on ground grids of three different shapes, especially when the fault current was injected into the corner of rectangular ground grid that resulting in the highest overvoltage at the corner. There are the other programs that can be used for simulating the ground grid systems. For example, CDEGS, which is a specialized program with high performance, can define the type of laydown materials, simulate 2 layers of such materials, and also give the illustrative results in 2-and 3-D formats, but it has disadvantage in high cost and requirement for very effective computer resources and operating systems. Apart from that, the fast Fourier transformation (FFT) program has been used for calculating the frequency and time response values and illustrating the magnetic fields in the case of lightning strike on power plant’s ground grid [13]. Moreover, PSCAD program has been applied for analyzing the effects of induced voltage due to lightning strike on overhead transmission line that affecting below gas pipeline [8]. However, both FFT and PSCAD have limitations in creating the models and determining the parameters. Currently, analysis of soil grounding materials with different levels of resistivity due to physical and chemical compositions may be performed by the advanced programs, such as COMSOL that use 3D finite element method (FEM) for simulating and displaying the ground grids and their electric and magnetic fields in 3D illustrations. COMSOL may also be useful for analyzing the effects of overvoltage on various designs of ground grids as well as the workers and equipment locating inside or nearby high voltage substation [7], [23]-[25], but it has drawbacks in its cost, requirement for highly effective computer resources and operating systems as well as time-consuming for generating the models and determining the parameters. From the results in this study, it would recommend ATP/EMTP to be used for preliminary investigation of the overvoltage on ground grids of different shapes and the obtained findings could be beneficial and critical for making decision in further investment for analysis by more advanced simulation programs. 4. CONCLUSION The models created by ATP/EMTP program to investigate the effects of injected fault current and resulting overvoltage on ground grids of three different shapes (square, rectangular and L-shaped) showed that rectangular ground grid had the highest level of overvoltage, particularly at its corner, when the fault current was injected into its corner. On the contrary, square ground grid was found the have the lowest overvoltage, especially when the fault current was injected at its center. This study showed that ATP/EMTP
  • 8.  ISSN: 2088-8708 Int J Elec & Comp Eng, Vol. 11, No. 6, December 2021 : 4689 - 4697 4696 is a simple simulation program with ease of accessibility and uses, particularly in creating the ground grid models and adding the important parameters. Moreover, it has benefits in less time-consuming and low cost for computer resources and operating systems. This study concluded that preliminary investigation of possible overvoltage on ground grid models of different shapes could be achieved by ATP/EMTP program, which may be suitable for further in-depth analysis by other advanced programs. REFERENCES [1] T. Chalardsakul, “Analysis overvoltage in the grounding system of high voltage substation by using ATP/EMTP program,” Technology Promotion and InnoMag Magazine, vol. 202, pp. 88-93, 2008. [2] F. E. Mentre and L. Grcev, "EMTP-based model for grounding system analysis," in IEEE Transactions on Power Delivery, vol. 9, no. 4, pp. 1838-1849, Oct. 1994, doi: 10.1109/61.329517. [3] R. Shariatinasab and J. Gholinezhad, “The effect of grounding system modeling on lightning-related studies of transmission lines,” Journal of Applied Research and Technology, vol. 15, no. 6, pp. 545-554, 2017, doi: 10.1016/j.jart.2017.06.003. [4] L. D. Grcev and M. Heimbach, "Frequency dependent and transient characteristics of substation grounding systems," in IEEE Transactions on Power Delivery, vol. 12, no. 1, pp. 172-178, Jan. 1997, doi: 10.1109/61.568238. [5] A. Geri, "Behaviour of grounding systems excited by high impulse currents: the model and its validation," in IEEE Transactions on Power Delivery, vol. 14, no. 3, pp. 1008-1017, July 1999, doi: 10.1109/61.772347. [6] M. I. Lorentzou, N. D. Hatziargyriou, and B. C. Papadias, "Time domain analysis of grounding electrodes impulse response," in IEEE Transactions on Power Delivery, vol. 18, no. 2, pp. 517-524, April 2003, doi: 10.1109/TPWRD.2003.809686. [7] Y. Liu, N. Theethayi, and R. Thottappillil, "An engineering model for transient analysis of grounding system under lightning strikes: nonuniform transmission-line approach," in IEEE Transactions on Power Delivery, vol. 20, no. 2, pp. 722-730, Apr. 2005, doi: 10.1109/TPWRD.2004.843437. [8] A.I. Elgayar and Z. Abdul-Malek, “Induced voltages on a gas pipeline due to lightning strikes on nearby overhead transmission line,” International Journal of Electrical and Computer Engineering, vol. 6, no. 2, pp. 495-503, 2016. doi: 10.11591/ijece.v6i2.9395. [9] M. Adnan, Z. Abdul-Malek, N. S. M. Din, M. I. Jambak, Z. Nawawi, M. A. B. Sidik, “Effect of Lightning impulse front time on substation grounding system performance,” Indonesian Journal of Electrical Engineering and Computer Science, vol. 20, no. 2, pp. 569-574, 2020, doi: 10.11591/ijeecs.v20.i2.pp569-574. [10] Z. Abdul-Malek, M. S. A. Yaman, M. Adnan, “Effects of soil profile on the transient performance of substation grounding system,” Indonesian Journal of Electrical Engineering and Computer Science, vol. 20, no. 2, pp. 870-877, 2020, doi: 10.11591/ijeecs.v20.i2.pp870-877. [11] S. Nikolovski, G. Knezevic, and Z. Baus, “Assessment of step and touch voltages for different multilayer soil models of complex grounding grid,” International Journal of Electrical and Computer Engineering, vol. 6, no. 4, pp. 1441-1455, 2016, doi: 10.11591/ijece.v6i4.pp1441-1455. [12] M. Mokhtari, Z. Abdul-Malek, and C. L. Wooi, “Integration of frequency dependent soil electrical properties in grounding electrode circuit model,” International Journal of Electrical and Computer Engineering, vol. 6, no. 2, pp. 792-799, 2016, doi: 10.11591/ijece.v6i2.pp792-799. [13] S. N. Nikolovski, Z. Baus, and G. Knežević, “Frequency and time response of power plant grounding system exposed to lightning strike,” International Journal of Electrical and Computer Engineering, vol. 6, no. 2, pp. 512- 525, 2016, doi: 10.11591/ijece.v6i1.9356. [14] N. M. Tabatabaei and S. R. Mortezaeei, “Design of grounding systems in substation by ETAP intelligent software,” International Journal on Technical and Physical Problems of Engineering, vol. 2, pp. 45-49, 2010. [15] D. Prasad and H. C. Sharma, “Designing of Grounding System for High Voltage Substation,” International Journal of Engineering and Advanced Technology, vol. 2, pp. 61-65, 2013. [16] M. U. Aslam, M. U. Cheema, M. B. Cheema, and M. Samran, "Design analysis and optimization of ground grid mesh of extra high voltage substation using an intelligent software," 2014 The 1st International Conference on Information Technology, Computer, and Electrical Engineering, Semarang, Indonesia, 2014, pp. 339-345, doi: 10.1109/ICITACEE.2014.7065768. [17] S. G. Farkoush, A. Wadood, T. Khurshaid, C. Kim, M. Irfan, and S. Rhee, "Reducing the Effect of Lightning on Step and Touch Voltages in a Grounding Grid Using a Nature-Inspired Genetic Algorithm With ATP-EMTP," in IEEE Access, vol. 7, pp. 81903-81910, 2019, doi: 10.1109/ACCESS.2019.2923656. [18] H. N. Amadi, “Design of grounding system for A.C. substations with critical consideration of the mesh, touch and step potentials,” European Journal of Engineering and Technology, vol. 5, no. 4, pp. 44-57, 2017. [19] D. D. Vuckovic, N. N. Cvetkovic, and M. S. Stojanovic, “Study on a standard for grounding systems realization,” Serbian Journal of Electrical Engineering, vol. 9, pp. 393-401, 2012, doi: 10.2298/SJEE1203393V. [20] A. Phayomhom, S. Sirisumrannukul, and T. Kasirawat, “Safety design of ground grid in distribution substation: Case study of metropolitan electricity authority’s system,” GMSARN International Journal, vol. 4, pp. 67-74, 2010. [21] An American National Standard, “IEEE guide for safety in AC substation grounding,” in IEEE Std 80-2000, pp.1-192, 4 Aug. 2000, doi: 10.1109/IEEESTD.2000.91902. [22] A. B. Patel and K. Velani, "Digital application for grounding grid design calculations of substation," 2017 Innovations in Power and Advanced Computing Technologies (i-PACT), Vellore, 2017, pp. 1-6, doi: 10.1109/IPACT.2017.8244947.
  • 9. Int J Elec & Comp Eng ISSN: 2088-8708  Investigation of overvoltage on square, rectangular and l-shaped ground grids of… (Krung Luewattana) 4697 [23] N. A. M. Hasni, R. Abd-Rahman, H. Ahmad, N. A. M. Jamail, M. S. Kamaruddin, and S. S. Ridzwan, “Investigation of potential grounding compound for portable applications,” International Journal of Electrical and Computer Engineering, vol. 7, no. 6, pp. 3140-3146, 2017, doi: 10.11591/ijece.v7i6.pp3140-3146. [24] A. J. L. M. Siang, E. H. Sfoog, N. Naji, S. S. Yi, N. A. A. Guntor, and J. Prasetijo, “Ground improvement using granular pile anchor system resistance to heave and uplift pressure,” Indonesian Journal of Electrical Engineering and Computer Science, vol. 19, no. 1, pp. 403-411, 2020, doi: 10.11591/ijeecs.v19.i1.pp403-411. [25] A. A. Salem, R. Abd-Rahman, M. S. Kamarudin, H. Ahmed, and N. A. M. Jamail, “The effect of insulator geometrical profile on electric field distributions,” Indonesian Journal of Electrical Engineering and Computer Science, vol. 14, no. 2, pp. 618-627, 2019, doi: 10.11591/ijeecs.v14.i2.pp618-627. BIBLIOGRAPHIES OF AUTHORS Krung Luewattana graduated B.Eng., M.Eng., and Ph.D. degrees in Electrical Engineering (with emphasis on Electrical Power Engineering). His research interests include high voltage, engineering and insulation, electrical grounding systems, power engineering and power systems, electromagnetic compatibility, transient in power system and renewable/alternative energy. Paweena Rattanasena graduated B.Sc. in Microbiology (Chulalongkorn University, Thailand), M.Sc. in Tropical Infectious Diseases and Ph.D. in Tropical Health (both degrees from the University of Queensland, Australia). Her research interests include public health and safety, infectious diseases, and biotechnology.