This document provides an overview of a fire protection training session at QPS in Vadodara, India. It introduces the trainer, Abhijit Haldankar, who has over 25 years of experience in process and environmental safety. The agenda covers fire basics, regulations and standards, fire protection system design, fire water demand calculations, fire water pumps, and other fire protection topics. A recent fire incident at an FRP coating company is also described, where a fire started in a sheet metal coating machine and spread to a nearby resin storage area.
This document provides information on fire protection equipment used in electric substations. It discusses the importance of electricity as critical infrastructure and the objectives of transmission utilities. It then covers various aspects of fire prevention and fighting including standards, elimination of electric fire hazards, grounding practices, and maintenance procedures. The document also describes classifications of fires according to different materials involved and appropriate extinguishing methods. Finally, it explains different types of fire extinguishing equipment like water, foam, dry chemical powder, carbon dioxide, and their mechanisms of fire extinction.
The document outlines rules for fire alarm systems, including general requirements for submission plans. Plans must be clear, labeled, and to scale. They must show all buildings, openings, and boundaries. Installation layout drawings must be to a scale of at least 1:100 and include north point, construction details, elevations, false ceilings/floors, and equipment locations. Various system components must be approved. Inspections are required and discounts provided once systems are found in working order. Detector types - heat, smoke, and flame - are described along with their appropriate uses.
This document compares the classification systems and requirements for fire protection systems between the TAC and OISD 116 rules. Some key differences include:
- TAC classifies occupancies as light, ordinary, or high hazard while OISD 116 uses sub-categories A and B.
- OISD 116 has additional requirements for dry chemical powder extinguishers of larger capacities and the placement of at least one extinguisher every 750 sqm.
- For hydrants, TAC requires spacing of every 30m for high hazard risks while OISD 116 requires a minimum of 15m from protected equipment and locations along roadsides for easy accessibility.
- OISD 116 has additional requirements for
This document summarizes the fire fighting system for the PN02 medical college buildings. It describes that water is supplied from the PNU station at 120 PSI and delivered to each building through alarm check valves and zone control valves. Sprinklers are located throughout the buildings and are connected to the fire alarm system. Landing valves in staircases and fire hose cabinets are also supplied water to aid in firefighting. The system is tested and meets UL and FM approval standards.
This document provides rules and guidelines for high velocity water spray systems used to extinguish fires involving liquids with flash points of 650°C or higher. It focuses on protections for transformers, discussing general layout and design, including requirements for projectors, detectors, piping, and water supplies. Detailed information is required to be submitted for approval of individual transformer protection systems, including dimensions, equipment locations, and sprinkler/piping details. Medium velocity spray systems used for lower flash point liquids are also addressed.
This document provides an overview of a fire protection training session at QPS in Vadodara, India. It introduces the trainer, Abhijit Haldankar, who has over 25 years of experience in process and environmental safety. The agenda covers fire basics, regulations and standards, fire protection system design, fire water demand calculations, fire water pumps, and other fire protection topics. A recent fire incident at an FRP coating company is also described, where a fire started in a sheet metal coating machine and spread to a nearby resin storage area.
This document provides information on fire protection equipment used in electric substations. It discusses the importance of electricity as critical infrastructure and the objectives of transmission utilities. It then covers various aspects of fire prevention and fighting including standards, elimination of electric fire hazards, grounding practices, and maintenance procedures. The document also describes classifications of fires according to different materials involved and appropriate extinguishing methods. Finally, it explains different types of fire extinguishing equipment like water, foam, dry chemical powder, carbon dioxide, and their mechanisms of fire extinction.
The document outlines rules for fire alarm systems, including general requirements for submission plans. Plans must be clear, labeled, and to scale. They must show all buildings, openings, and boundaries. Installation layout drawings must be to a scale of at least 1:100 and include north point, construction details, elevations, false ceilings/floors, and equipment locations. Various system components must be approved. Inspections are required and discounts provided once systems are found in working order. Detector types - heat, smoke, and flame - are described along with their appropriate uses.
This document compares the classification systems and requirements for fire protection systems between the TAC and OISD 116 rules. Some key differences include:
- TAC classifies occupancies as light, ordinary, or high hazard while OISD 116 uses sub-categories A and B.
- OISD 116 has additional requirements for dry chemical powder extinguishers of larger capacities and the placement of at least one extinguisher every 750 sqm.
- For hydrants, TAC requires spacing of every 30m for high hazard risks while OISD 116 requires a minimum of 15m from protected equipment and locations along roadsides for easy accessibility.
- OISD 116 has additional requirements for
This document summarizes the fire fighting system for the PN02 medical college buildings. It describes that water is supplied from the PNU station at 120 PSI and delivered to each building through alarm check valves and zone control valves. Sprinklers are located throughout the buildings and are connected to the fire alarm system. Landing valves in staircases and fire hose cabinets are also supplied water to aid in firefighting. The system is tested and meets UL and FM approval standards.
This document provides rules and guidelines for high velocity water spray systems used to extinguish fires involving liquids with flash points of 650°C or higher. It focuses on protections for transformers, discussing general layout and design, including requirements for projectors, detectors, piping, and water supplies. Detailed information is required to be submitted for approval of individual transformer protection systems, including dimensions, equipment locations, and sprinkler/piping details. Medium velocity spray systems used for lower flash point liquids are also addressed.
This presentation by David Sylvester of the Mircom Group of Companies discusses CSA-B44 and NFPA 101 - the Canadian and American elevator recall codes. Learn how they relate to life safety and fire protection.
Building services project 2 presentation slidesTan Jaden
This document provides information on the proposed mechanical ventilation system for a public building project. It discusses the benefits of a balanced ventilation system to ventilate the building. The system uses two sets of ductwork and fans to supply fresh air into the building and extract stale air out, maintaining neutral pressure. Floor plans show the layout of the ventilation system on each level, including components like exhaust fans, filters, galvanized steel ducts, fire dampers, and diffusers. Details are provided on the types and purposes of fans, ducts, dampers and other components. Regulations on required fresh air changes are also cited.
This document discusses fire prevention and control systems. It defines fire prevention and control systems as protecting an area from fire based on its risks. Both passive and active systems are covered, including building design, portable extinguishers, alarm detection, hose reels, hydrants, automatic extinguishers like sprinklers, and smoke extraction/ventilation. Details are provided on types, installation, and operation of these various fire prevention and control components.
The document provides details on conducting a fire risk assessment for a construction site. It outlines the objectives to evaluate fire hazards, likelihood of fire, and consequences. The assessment involves inspecting the site to identify potential fire sources and those at risk, then evaluating the level of risk and adequacy of existing precautions. The assessment also reviews fire prevention, protection, precautions, staff training, and ensures findings are recorded and the assessment is reviewed periodically.
This document provides an overview of fire protection recommendations for a thermal power plant. It identifies various areas of the plant and their associated fire risks. Recommendations are provided for both automatic and manual fire suppression systems in each area, including the coal yard, coal conveyor, boiler, turbine, cable gallery, electrical panel, central control room, transformer, lube oil tank, and switchyard. Detection methods and extinguishing agents are suggested based on the class of fire risk. The document also recommends an early warning manual call point fire alarm system, portable extinguishers, and water hydrant systems to provide common fire protection across the entire plant. Drawings, calculations and cost estimates would be prepared as part of the survey,
Fire Fighting basics in Arabic and English, fire tetrahedron, fire fighting methods fire extinguishers types and properties and how to use them, desition making criteria
O documento descreve conceitos básicos de fogo, seus elementos constituintes e métodos de combate e prevenção de incêndios. Aborda combustíveis, comburente, calor, propagação do fogo, classes de incêndio, métodos de extinção, extintores e agentes extintores.
1. Sprinkler system Type
WET PIPE SPRINKLER SYSTEM
DRY PIPE SPRINKLER SYSTEM
PRE-ACTION SYSTEM
DELUGE SYSTEM
WET PIPE ANTI FREEZE SYSTEM
FOAM WATER SPRINKLER SYSTEM
2. Sprinkler Selection
For COMPLETE PREMIUM BOOK PLZZ
Check out my product on Instamojo:https://www.instamojo.com/ezazsidd1993/fire-fighting-a-complete-handbook/
Ēku elektroinstalācija. Kļūdas un ieteikumi.
Uldis Dērics, Latvijas Elektroenerģētiķu un Energobūvnieku asociācija SIA “Pirtel”
Video: https://www.facebook.com/dzivosiltak/videos/2547315372021766/
2019.gada 17.oktobris, Rīga
seminārs "Ēku iekšējo inženiertīklu atjaunošana"
described definition ..all types of fire protection devices...fire alarm systems..fire detector systems..standards for designing building in case of afire,emergency exit,safety factors...
very early smoke detection apparatus system - VesdaKamran Hassan
VESDA is an advanced laser-based aspirating smoke detection system that can detect smoke more effectively than conventional smoke detectors. It works by sucking air samples from the protected environment through a pipe network and analyzing them in the VESDA detection chamber. Key benefits include greater reliability, flexibility in installation locations, and the ability to detect smoke earlier than traditional systems. VESDA is particularly suitable for environments where access for detector maintenance is limited, such as warehouses, or where conditions may impact other detectors, like cold rooms or areas with high airflow.
This document discusses specialized water-based fire protection systems as alternatives to standard sprinkler systems. It describes fixed foam, water spray, foam-water, and water mist systems, noting their components, applications, and inspection requirements. These systems provide targeted protection for hazards where sprinklers would be inadequate, such as flammable liquid storage, using methods like foam application or ultra-fine water mist. Proper design, installation, and maintenance are needed to ensure effective performance.
The document discusses fire protection systems. It covers types of fires and fire extinguishers, fire detection equipment, fire suppression systems like sprinklers and standpipes, and safety measures. It provides details on different classes of fires and types of extinguishers like water, powder, foam, CO2, and wet chemical. It also covers fire detection, alarm systems, pumps, and features of sprinkler, dry riser, and wet riser systems. Training and maintenance of these systems is important for fire safety.
Portable fire extinguishers and rising main systems are required fire fighting systems in buildings. Portable extinguishers must be installed according to specifications and maintained properly. Rising mains must be either dry or wet depending on the building height, with dry mains used in buildings up to 60m tall and wet mains for taller buildings. The number, size and location of rising mains must meet requirements to ensure adequate coverage of building floors. Breeching inlets providing access for fire engines must be within 18m of access ways. Wet rising main systems require sufficient water supply and storage capacity according to standards.
FIre Fighting Elite Fire hydraulic Calculation As per NFPA Standardsureshvsvg
This document discusses mechanical, electrical, and plumbing (MEP) systems and fire protection systems. It covers topics such as the need for MEP systems, fire triangles, causes and classifications of fires, National Fire Protection Association (NFPA) codes, firefighting systems like sprinklers and pumps, and sizing of fire water tanks and diesel tanks. The document is intended as training material for fire protection system design and hydraulic calculations using Elite software.
OISD-STD-117 Fire Protection Facilities for Petroleum Depots, Terminals, Pipe...AnupamaPanoli
The document outlines standards for fire protection facilities at petroleum depots, terminals, and pipeline installations in India. It discusses requirements for fire water systems, foam systems, control room protection, firefighting equipment, alarm systems, and organization of fire safety resources. The standards aim to minimize loss of life and property from fire through rapid containment and extinguishment. Requirements include fixed water spray and foam systems for large storage tanks, monitors and hydrants in hazardous areas, and clean agent systems for control rooms.
Fire and Gas Detection System : Part 2_Block Diagram_Philosophy, Signal Types...Gan Chun Chet
Fire and Gas Detection System Requirements for the Oil and Gas Industry. Offshore Platforms are also applicable for onshore plants/terminals. Safeguarding and Protective System to ensure oil and gas facilities are safe to operate.
This document discusses fire pump system design according to NFPA 20 standards. It provides information on the purpose of fire pumps, acceptable pump types, sizing requirements, accessories, and operation. Fire pumps are designed to supply adequate water for sprinkler or standpipe systems by automatically starting when pressure drops and operating at 150% of rated capacity and 65% of rated head. Acceptable pump types include horizontal split case, vertical in-line, end suction, and vertical turbine configurations.
Parafudrlar Nedir?
Parafudrlar Nasıl Üretilmektedir?
Parafudrlar Neden Kullanılır?
Parafudrlar Nerede Kullanılmaktadır?
Parafudrlar Ne Zaman İhtiyaç Duyarız?
Parafudrlar Kim Üretir?
This presentation by David Sylvester of the Mircom Group of Companies discusses CSA-B44 and NFPA 101 - the Canadian and American elevator recall codes. Learn how they relate to life safety and fire protection.
Building services project 2 presentation slidesTan Jaden
This document provides information on the proposed mechanical ventilation system for a public building project. It discusses the benefits of a balanced ventilation system to ventilate the building. The system uses two sets of ductwork and fans to supply fresh air into the building and extract stale air out, maintaining neutral pressure. Floor plans show the layout of the ventilation system on each level, including components like exhaust fans, filters, galvanized steel ducts, fire dampers, and diffusers. Details are provided on the types and purposes of fans, ducts, dampers and other components. Regulations on required fresh air changes are also cited.
This document discusses fire prevention and control systems. It defines fire prevention and control systems as protecting an area from fire based on its risks. Both passive and active systems are covered, including building design, portable extinguishers, alarm detection, hose reels, hydrants, automatic extinguishers like sprinklers, and smoke extraction/ventilation. Details are provided on types, installation, and operation of these various fire prevention and control components.
The document provides details on conducting a fire risk assessment for a construction site. It outlines the objectives to evaluate fire hazards, likelihood of fire, and consequences. The assessment involves inspecting the site to identify potential fire sources and those at risk, then evaluating the level of risk and adequacy of existing precautions. The assessment also reviews fire prevention, protection, precautions, staff training, and ensures findings are recorded and the assessment is reviewed periodically.
This document provides an overview of fire protection recommendations for a thermal power plant. It identifies various areas of the plant and their associated fire risks. Recommendations are provided for both automatic and manual fire suppression systems in each area, including the coal yard, coal conveyor, boiler, turbine, cable gallery, electrical panel, central control room, transformer, lube oil tank, and switchyard. Detection methods and extinguishing agents are suggested based on the class of fire risk. The document also recommends an early warning manual call point fire alarm system, portable extinguishers, and water hydrant systems to provide common fire protection across the entire plant. Drawings, calculations and cost estimates would be prepared as part of the survey,
Fire Fighting basics in Arabic and English, fire tetrahedron, fire fighting methods fire extinguishers types and properties and how to use them, desition making criteria
O documento descreve conceitos básicos de fogo, seus elementos constituintes e métodos de combate e prevenção de incêndios. Aborda combustíveis, comburente, calor, propagação do fogo, classes de incêndio, métodos de extinção, extintores e agentes extintores.
1. Sprinkler system Type
WET PIPE SPRINKLER SYSTEM
DRY PIPE SPRINKLER SYSTEM
PRE-ACTION SYSTEM
DELUGE SYSTEM
WET PIPE ANTI FREEZE SYSTEM
FOAM WATER SPRINKLER SYSTEM
2. Sprinkler Selection
For COMPLETE PREMIUM BOOK PLZZ
Check out my product on Instamojo:https://www.instamojo.com/ezazsidd1993/fire-fighting-a-complete-handbook/
Ēku elektroinstalācija. Kļūdas un ieteikumi.
Uldis Dērics, Latvijas Elektroenerģētiķu un Energobūvnieku asociācija SIA “Pirtel”
Video: https://www.facebook.com/dzivosiltak/videos/2547315372021766/
2019.gada 17.oktobris, Rīga
seminārs "Ēku iekšējo inženiertīklu atjaunošana"
described definition ..all types of fire protection devices...fire alarm systems..fire detector systems..standards for designing building in case of afire,emergency exit,safety factors...
very early smoke detection apparatus system - VesdaKamran Hassan
VESDA is an advanced laser-based aspirating smoke detection system that can detect smoke more effectively than conventional smoke detectors. It works by sucking air samples from the protected environment through a pipe network and analyzing them in the VESDA detection chamber. Key benefits include greater reliability, flexibility in installation locations, and the ability to detect smoke earlier than traditional systems. VESDA is particularly suitable for environments where access for detector maintenance is limited, such as warehouses, or where conditions may impact other detectors, like cold rooms or areas with high airflow.
This document discusses specialized water-based fire protection systems as alternatives to standard sprinkler systems. It describes fixed foam, water spray, foam-water, and water mist systems, noting their components, applications, and inspection requirements. These systems provide targeted protection for hazards where sprinklers would be inadequate, such as flammable liquid storage, using methods like foam application or ultra-fine water mist. Proper design, installation, and maintenance are needed to ensure effective performance.
The document discusses fire protection systems. It covers types of fires and fire extinguishers, fire detection equipment, fire suppression systems like sprinklers and standpipes, and safety measures. It provides details on different classes of fires and types of extinguishers like water, powder, foam, CO2, and wet chemical. It also covers fire detection, alarm systems, pumps, and features of sprinkler, dry riser, and wet riser systems. Training and maintenance of these systems is important for fire safety.
Portable fire extinguishers and rising main systems are required fire fighting systems in buildings. Portable extinguishers must be installed according to specifications and maintained properly. Rising mains must be either dry or wet depending on the building height, with dry mains used in buildings up to 60m tall and wet mains for taller buildings. The number, size and location of rising mains must meet requirements to ensure adequate coverage of building floors. Breeching inlets providing access for fire engines must be within 18m of access ways. Wet rising main systems require sufficient water supply and storage capacity according to standards.
FIre Fighting Elite Fire hydraulic Calculation As per NFPA Standardsureshvsvg
This document discusses mechanical, electrical, and plumbing (MEP) systems and fire protection systems. It covers topics such as the need for MEP systems, fire triangles, causes and classifications of fires, National Fire Protection Association (NFPA) codes, firefighting systems like sprinklers and pumps, and sizing of fire water tanks and diesel tanks. The document is intended as training material for fire protection system design and hydraulic calculations using Elite software.
OISD-STD-117 Fire Protection Facilities for Petroleum Depots, Terminals, Pipe...AnupamaPanoli
The document outlines standards for fire protection facilities at petroleum depots, terminals, and pipeline installations in India. It discusses requirements for fire water systems, foam systems, control room protection, firefighting equipment, alarm systems, and organization of fire safety resources. The standards aim to minimize loss of life and property from fire through rapid containment and extinguishment. Requirements include fixed water spray and foam systems for large storage tanks, monitors and hydrants in hazardous areas, and clean agent systems for control rooms.
Fire and Gas Detection System : Part 2_Block Diagram_Philosophy, Signal Types...Gan Chun Chet
Fire and Gas Detection System Requirements for the Oil and Gas Industry. Offshore Platforms are also applicable for onshore plants/terminals. Safeguarding and Protective System to ensure oil and gas facilities are safe to operate.
This document discusses fire pump system design according to NFPA 20 standards. It provides information on the purpose of fire pumps, acceptable pump types, sizing requirements, accessories, and operation. Fire pumps are designed to supply adequate water for sprinkler or standpipe systems by automatically starting when pressure drops and operating at 150% of rated capacity and 65% of rated head. Acceptable pump types include horizontal split case, vertical in-line, end suction, and vertical turbine configurations.
Parafudrlar Nedir?
Parafudrlar Nasıl Üretilmektedir?
Parafudrlar Neden Kullanılır?
Parafudrlar Nerede Kullanılmaktadır?
Parafudrlar Ne Zaman İhtiyaç Duyarız?
Parafudrlar Kim Üretir?
Federal Elektrik - Sigortalı, Sigortasız ve Enversör Tip Yük AyırıcılarMehmet Emin Korkmaz
Sigortalı, Sigortasız ve Enversör Tip Yük Ayırıcılar Nedir?
Sigortalı, Sigortasız ve Enversör Tip Yük Ayırıcılar Nasıl Üretilmektedir?
Sigortalı, Sigortasız ve Enversör Tip Yük Ayırıcılar Neden Kullanılır?
Sigortalı, Sigortasız ve Enversör Tip Yük Ayırıcılar Nerede Kullanılmaktadır?
Sigortalı, Sigortasız ve Enversör Tip Yük Ayırıcılar Ne Zaman İhtiyaç Duyarız?
Sigortalı, Sigortasız ve Enversör Tip Yük Ayırıcılar Kim Üretir?
Kontaktörler Nedir?
Kontaktörler Nasıl Üretilmektedir?
Kontaktörler Neden Kullanılır?
Nerede Kontaktörler Kullanırız?
Ne Zaman Kontaktörlere İhtiyaç Duyarız?
Kontaktörler Kim Tarafından Üretilir?
elektrikli kombi kullanma klavuzu
Tam Modülasyonlu Çalışma İle Yüksek Verim
Dokunmatik ve Kullanımı Kolay Lcd panel
3 Fazlı veya Tek Fazlı Olarak Çalışabilme
7 Gün 21 Program Özelliği
Her Program İçin Ayrı Sıcaklık Değeri Belirleme
Yerden Isıtma veya Radyatörlü Isıtma Seçeneği
Güneş Enerjisiyle Uyumlu Çalışabilme
İstenirse 3 Kademe Ayarı
Yaz - Kış Konum Seçeneği
Anti Blokaj ve Donma Koruma Sistemi
6 Farklı Emniyet Sistemi
3 Kademeli Pompa ve İlave Pompa Seçeneği
2 Yıl garanti
2. YANGIN !!!!!
ISI
OKSİJEN
YAKIT
OXSİJEN YAKIT
ISI
•Yanma olayı, ısı, oksijen ve
yanıcı maddelerden oluşan üç
faktörün bir arada olmasıyla
meydana gelir.
•Yanma olayı için ısının 260 - 400
C’ den, oksijenin ise % 15' den
fazla olması şarttır.
•Yangının sönmesi için de bu üç
faktörden birinin ortadan
kaldırılması gerekmektedir.
4. Yangın Standartları ve Yönetmelikleri
TS EN 12845
TS EN 12259
TS ISO 14520
NFPA (13-14-20)
Yönetmelik
Standartlar
• Türkiye Yangından Korunma Yönetmeliği-2007
ÜLKE TASARIM STANDARDI ÜRÜN ONAYI
ABD NFPA UL ve FM
ALMANYA DIN/Vds Vds
İNGİLTERE LPC LPCB
RUSYA SNIP SNIP
Otomatik Sprinkler Sistemleri Standartları
5. Uygulanması Gereken Alanlar
Yapı yüksekliği 30.50 m’den fazla olan konut haricindeki bütün yapılar,
Yapı yüksekliği 51.50 m’yi veya 17 katı geçen konutlarda,
Toplam alanı 600 m2 den büyük kapalı otoparklarda,
Birden fazla katlı bir bina içerisindeki yatılan oda sayısı 100’ü veya yatak sayısı 200’ü geçen
otellerde, yurtlarda, pansiyonlarda, misafirhanelerde ve yapı yüksekliği 21.50 m’den fazla
olan bütün yataklı tesislerde,
Toplam alanı 2000 m2’nin üzerinde olan katlı mağazalarda, alışveriş, ticaret, eğlence ve
toplanma yerlerinde,
Toplam alanı 1000 m2’den fazla olan, kolay alevlenici ve parlayıcı madde üretilen veya
bulundurulan yapılarda.
Sprinkler
15. Yangın Dolapları
Yüksek binalar ile toplam kapalı kullanım
alanı 1000 m2’den büyük imalathane,
atölye, depo, otel, motel, sağlık, toplanma
amaçlı ve eğitim binalarında ve kapalı
kullanım alanı 2000 m2’den büyük bütün
binalarda yangın dolabı yapılması mecburidir.
Yangın dolapları her katta ve yangın duvarları
ile ayrılmış her bölümde aralarındaki uzaklık
30 m'den fazla olmayacak şekilde
düzenlenecektir.
16. Hidrantlar
İmar planlama alanı 5000 m2’den büyük olan ve
içerisinde her türlü kullanım alanı bulunan
yerleşim alanlarında dış hidrant sistemi yapılması
şarttır.
HİDRANTLAR ARASI UZAKLIK ÇOK YÜKSEK
TEHLİKELİ BÖLGELERDE 50, YÜKSEK TEHLİKELİ
BÖLGELERDE 100, ORTA TEHLİKELİ BÖLGELERDE
125, DÜŞÜK TEHLİKELİ BÖLGELERDE İSE 150
METRE ALINIR.
17. Yangın Tehlike Sınıflarına Göre Debiler
Yangın Dolabı
Debisi (l/dak)
Hidrant Debisi
(l/dak)
Süre
(dak)
Düşük tehlike
sınıfı
100 400 30
Orta tehlike
sınıfı
100 1000 60
Yüksek tehlike
sınıfı
200 1500 90
19. Tehlike Sınıfının Belirlenmesi
YANGIN TEHLİKE SINIFLARI
Sprinkler tasarımına başlamadan önce, tasarım yapılacak mahalin
tehlike sınıfı belirlenmelidir. Otomatik sprinkler sistemi ile
korunacak alan ve binalar düşük, orta ve yüksek tehlike olarak
sınıflandırılır. Eğer aynı bina veya alanda birden fazla tehlike sınıfı
varsa en yüksek tehlikeye sahip olan sınıfa göre çözülür.
20. Düşük Tehlike Sınıfı
Düşük yangın yüküne sahip, düşük yanabilirliği
olan ve yangın dayanımı en az 30 dk olan 126
m2’den büyük bölümü olmayan mahalleri
kapsar.
Okullar ve diğer eğitim kurumları
Bürolar
Hapishaneler
Tablo – Düşük Tehlike Sınıfı Mahaller
21. Orta Tehlike Sınıfı
Orta yangın yüküne ve orta yanabilirliğe sahip olan ve yanabilen malzemelerin işlendiği veya
üretildiği mahalleri kapsar. Orta tehlike sınıfı alanlar 4 alt gruba ayrılır.
1. (a) OT4 sınıfına giren mahallerde yeralan depolama alanları,YüksekTehlike Depolama
Sınıfına göre belirlenmelidir.
2. (b) OT1 ve OT2 mahalleri içinde boyama ve benzeri yangın yükü içeren alanlar
bulunuyorsa, OT3 sınıfı olarak değerlendirilmelidir.
3. (c) OT1-2-3 olarak sınıflandırılan alanlarda aşağıdaki koşullar sağlandığında depolama
yapılabilir.
- Odanın tümünde en az OT3 olarak tasarım yapılmalıdır.
- Maksimum depolama yükseklikleri belirtilen değerlerin üzerinde
olmamalıdır.Bu değerlerde OT3’e göre tasarım yapılmalıdır.
- Etrafında 2,4 m’den az olmayan aralıkların olduğu her bir blok için, maksimum
depolama alanı 50 m2 olmalıdır.
22. OT-1 OT-2 OT-3 OT-4
Çimento işleri Fotoğraf lab. AVM. Sinema ve
Tiyatrolar
Mezbahalar ArabaAtölye Mobilya Mağ. Konser Salonları
Hastaneler Bisküvi
Fabrikaları
Örme
Fabrikaları
Sigara Fabrikaları
Oteller Bira Fabrikası Ayakkabı Fab İçki Fabrikası
Kütüphaneler Çikolata
Fabrikaları
Halı Fab. Fuar salonları
Restoranlar Laboratuvar Kumaş ve giyim
Fab.
Sunta Fabrikaları
Okullar Şekerleme
Fabrikaları
Baskı işleri Mum Fabrikaları
Ofisler Otoparklar Yem Fab. Kibrit Fab.
Metal fabrika Müzeler Buzdolabı
Fabrikaları
Boya atölyeleri
Mandıralar Çamaşırhane Elektronik
Fabrikaları
Bıçkı milleri
Bilgi işlem Fotografik Film
Fab.
Cam Fab. Kontraplak Fab.
23. Yüksek Tehlike Sınıfı
Yüksek tehlikeli işlem, yüksek yangın yükü ve yüksek yanabilirliğe sahip ve hızla yayılma
veya yoğun yangın şeklinde gelişme gösterebilen malzemelerin bulunduğu mahalleri
kapsar. Yüksek tehlike sınıfı, işlem 4 alt gruba ayrılır. Yüksek Tehlike Sınıfı İşlem Grup 4
mahallerde, genellikle baskın sistemlerle koruma sağlanır.
YT-1 YT-2 YT-3 YT-4
kumaş ve yer
döşemesi
imalatı
Çakmak
imalathaneleri
Selüloz Nitrat
imalatı
Havai fişek
imalatı
Boya, boyama
ve vernik
imalatı
Otobüs deposu
Kauçuk
türevleri
imalatı
Yüksüz
kamyon ve tren
vagonları
05/2009 Çin’de Havai Fişek Fabrikasında Yangın
Tablo – Yüksek Tehlike Sınıfı Mahaller
25. Islak Borulu Sprinkler Sistemi Seçim Kriterleri
• Islak borulu sprinkler sisteminde borular, sürekli olarak basınçlı su ile dolu
durumda tutulur.
• Sadece donma riski olmayan ve çevre sıcaklığının 95C’yi geçmediği yerlerde
uygulanır.
• Islak sprinkler sistemleri ortak bir kolondan beslenen zonlara ayrılabilir.
• Tesis ve yapının yangın tehlike sınıfına bağlı olarak sprinkler
sistemini tek bir sistem kolonu veya birleşik sistem kolonuna
bağlanan sprinklerin koruduğu herhangi bir kattaki maksimum
kat alanıTablo ’de verilen değerlerin üzerinde olmamalıdır.
Tehlike Sınıfı Islak Alarm Vana Seti için maksimum zon alanı (m²)
DT 4800
OT 4800
YT 2300
Tablo – Islak Borulu Sistemlerde Maksimum Zon Büyüklüğü
26. • Yüksek depolama alanlarında, herhangi bir besleme kolonuna bağlanan her
bir kattaki maksimum kat alanı 3716m²’nin üzerinde olmamalıdır.
• Sprinkler sistemi ana besleme borusu birden fazla yangın zonuna
hitap ediyorsa; her bir zon veya kolon hattına akış anahtarları, test
ve drenaj vanası ve izleme anahtarlı hat kesme vanası konulmalıdır.
• Yüksek binalarda, maksimum statik basıncın sprinkler sistemi ekipmanının
limit değerleri içinde kalmasını sağlanmalıdır.
• Zonlara ayrılmış sprinkler tesisatlarında vanaların açık veya kapalı durumu
ile zon su akış durumunu izlemek için gerekli cihazlar teçhiz edilmeli ve
tesiste ulaşılabilir bir yerde bulunan bir kontrol ve gösterge paneline
elektrik bağlantılı olmalıdır.
• Loop ve ızgara borulama sistemleri sadece ıslak borulu sprinkler
sistemlerinde kullanılabilir.
27. Kuru Borulu Sprinkler Sistemi Seçim Kriterleri
• Kuru borulu sprinkler sistemleri, kuru alarm vanasının üst kısmının basınçlı
hava veya inert gaz ile sürekli olarak basınç altında tutulduğu ve kuru alarm
vanasının alt kısmının su ile basınç altında tutulduğu sistemlerdir.
• Kuru borulu sistemler sadece donma hasarı olasılığı bulunan mahallerde ve
sıcaklığın 70C’nin üzerinde olduğu kurutma fırını benzeri mahallerde
uygulanmalıdır.
• Tek bir kuru alarm vanası ile kontrol edilen sistem büyüklüğü; aşağıdaki
maddelerden herhangi birine uygun olarak belirlenmelidir. İstisna olarak,
(c) ve (d) maddeleri yaşam ünitelerinde uygulanamaz.
(a) En uzak noktada bulunan test vanası tamamen açıldığında, suyun
boşalması için geçen süre en fazla 60sn olmalıdır.
(b) Kuru alarm vanasının üstündeki net boru iç hacmi Tablo’de verilen
değerlerin üzerinde olmamalıdır.
29. (c) Net boru iç hacminin 500galon(1839lt)’den az olduğu sistemlerde
hızlandırıcı kullanılması gerekli değildir ve suyun boşalması için geçen
süre limitine uyulması gerekmez.
(d) Net boru iç hacminin 750galon(2839lt)’den az olduğu sistemlerde
hızlandırıcı kullanılması durumunda, suyun boşalması için geçen süre
limitine uyulması gerekmez.
(e) Sistem büyüklüğü; suyun boşalması için geçen süreye bağlı olarak
hesap programı ile yapılmalıdır. Hesap programı ve metodu ulusal olarak
tanınmış bir laboratuvar tarafından onaylanmış olmalıdır. Hesaplama,
Tablo’de verilen değerlere uygun olmalıdır.
Tehlike Sınıfı Maksimum Boru Hacmi (m 3)
Hızlandırıcılı Hızlandırıcısız
Düşük Tehlike Sınıfı 4 1,5
Orta Tehlike Sınıfı 4 1,5
Yüksek Tehlike Sınıfı 3 -
Tablo – Kuru Borulu Sistemlerde Maksimum Zon Büyüklüğü
30. (f) Sistemin büyüklüğü akış testleri yapıldığında tablo’de suyun
boşalması için geçen süre ile ilgili olarak verilen değerleri sağlayacak
ölçüde olmalıdır. Akış testleri, açılacak sprinkler sayısını simüle edilerek
yapılmalıdır. Tek sprinkler açılaması istenen mahaller için, en uzak
noktadaki test vanası açılır. Daha fazla sayıda sprinkler açılma durumunu
simüle etmek için test manifoldu düzenlenmesi gereklidir. 4 sprinkler
açılması durumunu test etmek için; her iki branşman kolundan iki adet
sprinkler akışına uygun manifold düzenlemesi yapılır. Yapılan testlerle
gerekli su boşalma süreleri karşılanıyorsa, (a) ve (e) maddesindeki
şartlar aranmaz
• Kuru borulu sistemlerde, ızgara borulama tesisatı kullanılmamalıdır.
Tablo – Kuru Borulu Sistemlerde Maksimum Zon Büyüklüğü
Tehlike Sınıfı En uzak noktada açılacak
sprinkler sayısı
Maksimum Su Boşalma Süresi
(sn)
Yaşam ünitesi 1 15
Düşük Tehlike Sınıfı 1 60
Orta Tehlike Sınıfı 2 50
Yüksek Tehlike Sınıfı 4 45
Yüksek Depolama 4 40
31. Ön Tepkili Sprinkler Sistemi Seçim Kriterleri
• Ön tepkili sprinkler sistemleri aşağıdaki tiplerden biri olmalıdır.
(a) Tek Kilitlemeli Ön Tepkili Sprinkler Sistemi
Su geçişi sadece otomatik bir algılama sisteminin devreye girmesi ile
başlar.
(b) Kilitlemesiz Ön Tepkili Sprinkler Sistemi
Su geçişi sprinklerin açılması ile veya otomatik bir algılama sisteminin
devreye girmesi ile başlar.
(c) Çift Kilitlemeli Ön Tepkili Sprinkler Sistemi
Su geçişi sprinklerin açılması ile ve aynı zamanda otomatik bir algılama
sisteminin devreye girmesi ile başlar.
32. 2. BORULAMAVE SPRINKLERTİPİ
BELİRLEME
- TEHLİKE SINIFIVE SEÇİLEN SİSTEMTİPİNE
GÖRE SİSTEM SU İHTİYACI
BELİRLENDİKTEN SONRA ÖNCELİKLE
SPRINKLERYERLEŞİMİYANİ BORULAMA
BELİRLENİR.
- BORULAMA,AĞAÇ, LOOPVE IZGARA ADI
VERİLEN 3TİPTE OLABİLİR. GRIDVE LOOP
YALNIZCA ISLAK SİSTEMLERDE
KULLANILABİLİR.
- SPRINKLER SICAKLIK DERECESİ,
BEKLENEN ENYÜKSEK ORTAM
SICAKLIĞININ EN A 30 ˚C ÜZERİNDE
OLACAK ŞEKİLDE SEÇİLMELİDİR
35. 4. BORU ÇAPLARININ BELİRLENMESİVE HİDROLİK HESAP
- 465 M2’Yİ AŞMAYAN ALANA SAHİP BİNALARDA BORU ÇAPLARITABLO
ARACILIĞI İLE BELİRLENİR.
- HİDROLİK HESAP İÇİN EN KÖTÜ DURUM SENARYOSUYARATILIR. BU
SENARYODA EN UZAK NOKTADAKİ SPRINKLERİN AÇILACAĞI
DÜŞÜNÜLÜRVE TEHLİKE SINIFINA GÖRE KAÇ SPRINKLER AÇILACAĞI
HESAP EDİLİR. BUNUN ÜZERİNE BORULARDA OLUŞACAK OLAN BASINÇ
KAYIPLARI DA EKLENEREK SİSTEMİN ÇALIŞABİLMESİ İÇİN GEREKEN
BASINÇVE DEBİ DEĞERİNE ULAŞILIR.
- HİDROLİK HESAP SONUCUNDA ÖNGÖRÜLEN BORU ÇAPLARININ DA
DOĞRULUĞUTESPİT EDİLMİŞ OLUR.
- HİDROLİK HESAP AĞAÇTİPİ BORULAMA İÇİN EL İLEYAPILABİLİRKEN
LOOPVE IZGARATİPLERİ İÇİN ÖZEL HİDROLİK HESAP PROGRAMLARI
ARACILIĞI İLEYAPILMASI MÜMKÜNDÜR.
39. MOTOR GONG
39
•Su etkisi ile mekanik alarm verir.
•¾” pislik tutucu ile birlikte kullanılır.
•Çok yüksek ses üretme kapasitesine sahiptir.
•Mekanik bakım gerektirmez.
•Maksimum çalışma basıncı 300 psi (20,7 bar).
48. Baskın Alarm Vanası(Deluge)
Açık Sprinklerler
Dedektör sistemi sistemi
harekete geçirir
Su bütün sprinklerlere
gider
49. Baskın Alarm Vana
Uygulamaları
• Uçak Hangarları
• Donanım Depoları
• Su Perdeleri
• Çabuk Tutuşabilecek Depolar
• Parlayıcı Sıvı Kullanılan Alanlar
50. Baskın Alarm Vanası (Deluge
Sistem)
Baskın Vana
Operasyon:
Tepkime Çesitleri
Pnömatik
Hidrolik
Elektriksel
Dedectör ile uyarılır
Su bütün sprinklerlerden boşalır
53. Ön-Tepkili Alarm Sistemleri
• Bilgisayar Odaları
• Telekominikasyon Olanakları
• Soğuk Odalar
• Kütüphaneler
• Müzeler
54. Ön-Tepkili Sistem
Ön-Tepkili Vana
Operasyon:
Diyafram Su Basıncı ile genleşir
Mekanizma Çeşitleri
Pnömatik
Elektriksel
Her İkisi
Dedektörler tarafından uyarılır
Su bütün açık sprinklerlerden boşalır
58. SPRİNKLER TİPLERİ
58
Pendent (Aşağı) Sprinkler
•En çok tercih edilen üç tipden biridir.
• Çoğunlukla asma tavan olan mahallerde
asma tavanlara sıfır hizada montajı yapılır.
• Maksimum çalışma yükseklikleri 6 mt. dir.
•Bu yükseklikten sonra yağmurlama
yoğunluğu izin verilen sınırların altına iner.
60. SPRİNKLER TİPLERİ
60
Upright (Yukarı) Sprinkler
•En çok tercih edilen üç tipden biridir.
•Asma tavan olmayan mahallerde tercih
edilir.
•Maksimum çalışma yükseklikleri 6 mt. dir.
•Sprinklerin tavandan maksimum ve
minimum mesafeleri önemlidir.
•Suyun %40 ı tavana kala kısmı zemine
deşarj olur.
62. SPRİNKLER TİPLERİ
62
Sidewall (Duvar) Sprinkler
•En çok tercih edilen üç tipden biridir.
• Asma tavan olmayan ve borulamanın
yapılamayacağı mahallerde duvar
üzerine montajı yapılır.
•Deşarz hem ileri yönde hem de aşağı
yönde gerçekleşir.
64. SPRİNKLER ROZETLERİ
64
•Tavan ve duvarlardaki boşlukları
kapatmak ve ayarlama yapabilmek için
kullanılır.
•Pendent ve Sidewall tipler için tercih
edilmektedir.
•Beyaz boyalı ve krom kaplı üretilirler.
•İki parçalı, ayalanabilir veya tek parçalı
•1/2” ve 3/4” olarak üretilir.
65. SPRİNKLER TEPKİME SÜRELERİ
65
•Sıcaklığa duyarlıklıkları daha fazladır.
•Genellikle konutlar için tercih edilirler.
•Yüksek tehlike sınıflarında kullanılmaz
Hızlı TepkimeliStandart Tepkimeli
68. SPRİNKLER “K” DEĞERLERİ
68
Her sprinklerin orifis çapına bağlı olarak bir “K” değeri mevcuttur.
• K5,6 = K80 = 80 lt /dk – 1 bar bağlantı çapı 1/2”
• K8,0 = K115 = 115 lt/dk – 1 bar bağlantı çapı 3/4”
• K14,0 = K200 = 200 lt/dk – 1 bar bağlantı çapı 3/4”
• K25,0 = K360 = 360 lt/dk – 1 bar bağlantı çapı 1”
69. SPRİNKLER HAKKINDA
69
•Sprinkler yangını söndürmek ve
kontrol altına almak amaçlı olarak
tasarlanır.
•Sprinkler Sıcaklıkları belirlenirken
mahalin yıl içinde ulaşabileceği
maksimum sıcaklıktan 30C fazla seçilir.
•Yüksek tehlike mahallerde kuru
sistem uygulanmaz.
•Yüksek tehlike mahallerde hızlı
tepkimeli sprinkler kullanılmaz.
70. SPRİNKLER HAKKINDA
70
•Bir sprinklerin maksimum koruma alanı 21 m2 dir.
•Kuru sistemde pendent sprinkler kullanılmaz.
•Duvar tip sprinkler depo alanlarında kullanılmaz.
•Sprinkler minimum çalışma basıncı 0,35 bar dır.
•Sprinkler maksimum çalışma basıncı 12 bar dır.
71. TEST ve DRENAJ VANASI
71
•İçindeki değişik ölçülerdeki orifis
sayesinde sadece bir sprinklerden geçen
akışa eşit akış oluşturarak, bir sprinkler
su akışı durumunda hatlardaki alarm
cihazlarının kontrol amaçlı testlerinin
yapılması sağlanır.
•Sistemdeki en küçük sprinkler ve test
drenaj vanasının orifis çapları eşit
olmalıdır.
72. İZLENEBİLİR KELEBEK VANA
72
•Mahal içi zonları birbirinden ayırmak için, su
besleme hatları üzerinde kesme vanası olarak
kullanılırlar.
•Yangın sistemlerinde kullanılan tüm vanaların
konumu görülebilir ve elektriksel olarak
izlenebilir olmalıdır.
•Kelebek vanalar dişli kutulu volanlı tiptedir.
•Kelebek vanaların izleme anahtarı vana
içindedir ve üzerinde açık kapalı konum
göstergesi bulunur.
73. YÜKSELEN MİLLİ (OS&Y) VANA
73
Yükselen milli vanalar; tam açık konumunda
düzgün akışı bozmayan, açık konumu milin
yukarı aşağı hareketi ile gözle izlenebilen,
izleme anahtarı takılarak elektriksel izleme
yapılabilen sürgülü vana tipidir. Kelebek
vanalara oran ile daha az hidrolik kayıp
oluştururlar.
74. YÜKSELMEYEN MİLLİ (NRS) VANA
74
Yükselmeyen milli vanalar; ana hatlar ve
hidrant sistemlerinde toprak altı su hatlarını
kesmek ve kontrol etmek amaçlı kullanılan
vanalardır. Açık/Kapalı konumu görülebilen
post indikatörleri ile birlikte kullanılabilir. Yer
altında post indikatörü ile birlikte kullanılması
durumunda vana odasına gerek duyulmaz.
75. AKIŞ ANAHTARLARI (FLOW SWİCTH)
75
Islak borulu sistemlerde tek sprinklerin
açılması durumundaki su akışı ile yangın
alarm bilgisi alınarak, hangi bölgede yangın
olduğunun tespit edilmesiyle müdahale olanağı
sağlanır.
•Su akış alarm anahtarları sadece sulu
tesisatlarda kullanılmalıdır.
•Dikey ve yatay olarak monte edilebilir.
•Otomasyona elektriksel alarm verir.
•Zamanlayıcısı sayesinde yanlış alarm vermez.
76. İTFAİYE BAĞLANTI AĞZI
76
1000 m2’den büyük binalarda itfaiyenin
sisteme dışarıdan su basabilmesi
içindir,
Sulu yangın söndürme sistemlerine en
az 100 mm nominal Çapında itfaiye su
verme bağlantısı yapılması şarttır.
Sistemde bir çekvalf bulunması ve suyun
otomatik olarak boşalmasını sağlayacak
elemanlar konulması gerekmektedir.
77. İTFAİYE KAT BAĞLANTI VANASI
77
•İtfaiyenin bina içinden su sağlayabilmesi için
dizayn edilmiştir.
•DN50 veya DN65 olarak üretilebilir.
•Bina içinde yangın dolaplarına yakın
yerleştirilmelidir.
•Yüksek katlı binalarda en az her iki katta bir
kullanılması zorunludur.
78. DEBİ ÖLÇER (FLOW METER)
78
Üzerinde bulunduğu hattaki suyun debisinin
ölçümü için yangın pompası performans
testlerinde kullanılan cihazdır.
Her pompa setinin durumu her yıl performans
testi ile kontrol edilmelidir.
Performans testlerinde debi okuması için debi
ölçer kullanılır.
Debi ölçer çapı pompa kapasitesine göre
belirlenmelidir.
79. RELİEF VANA
79
•Relief vanalar; sistemdeki basıncın belli bir
limit değerin üzerine çıktığında, açılarak fazla
basıncın dışarı atılması ile sistemi rahatlatmak
için kullanılır. Sistem basıncı vananın ayarlı
olduğu limit değere düştüğünde vana tekrar
kapanır.
•Sistem elemanlarını yüksek basınca karşı
korumak için relief vana kullanılır.
•Relief vana çapı ve boşaltım hattı çapı pompa
kapasitesine göre belirlenmelidir.