SlideShare a Scribd company logo
1 of 27
Fire and Gas Detection System
(Offshore Facilities)
(Part 1 : The Field Devices and Its Panels)
Chun Chet Gan (Ir.)
MSc Operations Management
[Manchester School Management]
University of Manchester Institute of Science and Technology (UMIST),
United Kingdom.
BEng (Hons) Mechanical Engineering
[Simon Building]
University of Manchester, United Kingdom
The Purpose of Fire and Gas Detection
• The purpose of Fire and Gas Detection System, with the detectors located at
outdoor and indoor areas of the platform, is to protect the platform from a gas leak
or a fire. These areas are segregated into two (2) areas:-
1) outdoor, and
2) indoor areas.
• Outdoor areas are zoned into hazard open process or non hazard utility areas.
• Enclosed rooms are indoor areas (inside a closed structure or a building).
The Detection Area – Outdoor and Indoor
• In general, process areas (outdoor) are highly hazardous. It contains hydrocarbon
inventories and these areas are regarded as hazard areas on the platform. The
classification of these hazardous areas are defined by Safety.
- Hazard equipment are vessels, pumps, hydrocarbon pipelines, turbine generators,
etc.
• Utilities areas (are considered as outdoor areas) are non-hazardous zones of a
platform.
- Example of equipment in these areas are firewater pumps, diesel tanks, instrument
air compressors.
- Others equipment like water storage tank, sewage macerator, etc. are also
regarded as non-hazardous area.
• Indoor areas are safe areas on the platform.
• Example of these areas are:
- Control Room,
- Switchgear Room,
- Motor Control Centre MCC
• However, battery rooms are hazardous areas.
Fire and Gas Detection System in Two Parts
- Field Devices and Control Panels
• The detection system is segregated into two parts. These are:-
1) Field Devices - located outside in the process areas, utility areas or inside rooms,
and
2) Control Panels – these are logic solvers (or programmable logic controllers PLC,
addressable controllers), with graphic screens, to perform the required functions
(alarm and shutdown) in case of a detection.
• The following are pictures of fire and gas detectors and detection panels.
• Flame detectors
– Ultraviolet (UV)
– Ultraviolet and Infrared (UV/IR)
– Infrared (Triple IR)
Model X3301
(Triple IR)
Courtesy of DETRONICS
Model S251f+
(Triple IR)
Courtesy of THORN
Type of Field Devices
(this slide is from previous internal lecture)
• Smoke detectors
– Optical
– Ionization
(being phased out due to
!stringent! disposal requirements
of radioactive substances)
• Heat detectors
– rate of rise
– fixed
Model 601P
Smoke Detector
Model 601H-R Model 601H-F
Heat Detector
Courtesy of THORN
Type of Field Devices
(this slide is from previous internal lecture)
Type of Field Devices
(this slide is from previous internal lecture)
• Pneumatic fusible plugs
(pressure sensors will send a signal to
fire and gas system FGS upon
detection of low air pressure)
– Melt at 71 degree celsius
• Manual alarm callpoint
– Breakglass or pushbutton
Model SS-6-FTA-160
Fusible Plug
MODEL SM87 BG
MODEL SM87 PB
Courtesy of MEDC
Courtesy of SWAGELOK
Type of Field Devices
(this slide is from previous internal lecture)
• Gas detectors
– Infrared, electrochemical,
catalytic (point detectors)
– Infrared (line-of-sight)
Courtesy of DRAEGER
Model Polytron 2IR
Model Pulsar
Model Polytron FX
Model APEX
Model ECLIPSE
Courtesy of DETRONICS
Model OPECL
Courtesy of DETRONICS
Courtesy of SIEGER
Types of Fire and Gas Panel
(this slide is from previous internal lecture)
• Programmable Logic Controller (PLC based)
- Main Panel
- Addressable Panel
Model MINERVA
Courtesy of THORN
Courtesy of Honeywell
Model Honeywell Icon
Series Console MMI
Model Honeywell Fail
Safe
Controller (FSC)
ANIMATION OF A GAS LEAK
V-1
WIND
GD-1
GD-2
Tx
Rx
ANIMATION OF PLACING
FLAME DETECTORS
FD-1
FD-2
V-1
FD-3
ANIMATION OF A SHUTDOWN
GD
2oo3
GD
GD
&
Maintenance
Enabled
Reset w latched
Alarm
Shutdown
Principle of Gas Detection (1)
(this slide is from previous internal lecture)
100
Principle of Gas Detection (2)
• The principle of detection is based on absorption of infrared light by hydrocarbon
gas in the measurement chamber.
• For open path (or line-of-sight) gas detectors, the measurement area in between the
receiver and the transmitter unit is the hazardous area that required to be monitored
by these units. It is this area that this set of detectors are aligned diagonally across
or straight over the equipment. The unit of measurement is LEL.m or LFL.m
• LEL is the abbreviation for lower explosive limit whereas LFL is lower
flammability limit.
• LEL.m or LFL.m is the concentration of the gas cloud multiply by the distance
between the receiver and the transmitter unit.
- For example, if the gas cloud is 20 %LEL or %LFL, and the distance between the
receiver and the transmitter unit is 5 metres, then the measurement reading is about
20 %LEL x 5.0m = 1.0 LEL.m (0.20x5 = 1.0LEL.m). If the gas cloud is 60%LEL
and the distance is 5 metres, the reading is 60 %LEL x 5m = 3.0 LEL.m
Principle of Flame Detection (1)
(Ultraviolet & Infrared Wavelengths) (this slide is from previous internal
lecture)
Extracted from NFPA 72
recommended guide on Code of
Practice
Principle of Flame Detection (2)
• UV Flame Detector – This detector detects UV light source in a fire. UV light
source are found in hydrogen flame.
• UV/IR Flame Detector – This detector must detects both UV and IR light source
before this detector considers the target/detection area as a confirmed detection.
• Triple IR Flame Detector – This detector has three (3) infrared sensors. Infrared
light source are found in hydrocarbon flame.
Principle of Activation (1)
GD
FD
2ooN
Maintenance
Override
&
Alarm
or
Shutdown
Latched
Reset
Principle of Activation (2)
• The controller is either an electronic and pneumatic panel.
• The electronic panels are as below:
1) main panel (redundant/triplicated TMR),
2) addressable panel, and
3) instrument package panels (like turbine generators, firewater pumps, instrument
air compressor, etc.).
• 4) Others panels, shutdown panel or Public Address General Alarm PAGA panel
• Fire and gas signals to/from various panels (item 2 - 4) will be connected to the
main panel.
• Pneumatic panels (only pressure transmitter/switch signal connected to the PLC) is
a sub-system to the main panel.
• Also known as an electro/pneumatic panel (partial electronic), e.g. fusible plug
panel, deluge panel, etc., the instrument air is used to pressurized fusible tubes.
The Method of Detection of Field Detectors (1)
The principle of measurement/detection for field devices are:-
• Gas detectors (point HC or open path) – By infrared sensor(s). The concentrated
gas will block the light from reaching the sensor. The detection of an early warning
below the Lower Explosive Limits LEL will enable the controller to perform a
shutdown and sound the alarms.
• Flame detectors – A fire will be detected by the sensor (infrared wavelength). The
detector will detect a fire only after it develops.
• Manual call points – It is a detection by manual activation. The call points are
located at the edge of the platform or exit in the room visible to inhabitant of the
platform.
• Heat detectors – It detects the change in temperature rise (Rate-of-rise) or
temperature in exceed of a fixed setpoint in a room.
• Smoke detectors (optical) – Smoke particles in measurement chamber block light
from an internal source to the sensor. It detects smoke particles before a fire
develops.
• Fusible plugs – Melting of plugs at fixed elevated temperature due to heat. It is an
outdoor protection device.
The Method of Activation (1)
• Non-Fail Safe (i.e. an energized output on alarm/activation) - This non-fail safe
activation will activate output signals only if it is required to be activated.
(In normal practice, when the deluge valve is required to be activated, an output
signal will be sent to the solenoid that is part of the deluge valve).
• Fail Safe – otherwise, the fail safe outputs are de-energized on alarm/activation.
(If it is a fail safe application, the output signal will be deactivated when it is
required to perform a function. Example of this application is the fire and gas
outputs to a shutdown panel/system).
• Other applications like a fault signal, has to be supervised to ensure that this signal
is noticed when there is a failure in the panel.
• The detection system has to safe guard the platform from a gas leak or a fire. When
it occurs, the system must work.
• It is very unlikely that the redundant device fails when a shutdown is required.
Other means has to be sorted to ASSURE a safe operation.
The Methods of Detection of Electronic &
Pneumatic Panel (2)
• Electronic panels – are complete platform solution, with calculated failures (low
failure and with redundant I/Os and processors). It takes into account of redundant
failure(s), if it occurs.
• Pneumatic panels – has become a partial, but proven reliable solution due to its
depressurization mode. Air line leakages will bring the platform to a safe condition.
The Location of the Detectors
(and Its Application)
• The types of detectors and its recommended location are in the next slide.
• This table shows the type of detectors in the areas mentioned in the previous slides.
- Gas and flame detectors are mainly outdoor devices.
- Smoke and heat detectors are indoor devices.
- Manual call point can be located either in indoor and/or outdoor areas.
- Fusible Plugs are outdoor fire detection devices, location as per API RP 14C
guidelines.
(You can locate flame detectors inside a room if it is appropriate. However, smoke
and heat detectors are always located inside an enclosure(s).
• These are the devices to detect gas (early warning) or fire (either early warning or
after the fire is fully developed).
The Location of the Detectors
(and Its Application)
(this slide is from previous internal lecture)
The Location of the Panels
(and Its Application)
• The control panels are located either in the control room or outside in the open
areas.
• Electronic Panels with its redundant processors and safe failures have proven its use
on offshore platform, with proper design considerations.
• Pneumatic Panel, the oldest method, has is rigid and reliable (mechanically) method
of shutting down a platform.
• The detection system is connected to the deluge system (sometimes, not always) to
cool the equipment when the platform is undergoing depressurization through the
vent pipes.
• At the same time fire and gas signals from other system/panels will send signals to
the fire and gas detection panel for fault alarm or shutdown purposes.
(e.g. gas turbine panel upon detection of gas or fire will send signal to fire and gas
panel to close the fuel lines)
Part 1 : The Field Devices and Its
Panels
• End of Lesson 1
• Questions
Own Notes (1)
• Part 1 : The Field Devices and Its Panels
• The Purpose of Fire and Gas Detection
• The Detection Area – Outdoor and Indoor
• Fire and Gas Detection System in Two Parts - Field Devices and Control Panels
• Type of Field Devices
(this slide is from previous internal lecture)
• Types of Fire and Gas Panel
(this slide is from previous internal lecture)
• ANIMATION OF A GAS LEAK
• ANIMATION OF PLACING FLAME DETECTORS
• ANIMATION OF A SHUTDOWN
Own Notes (2)
• PRINCIPLES OF GAS DETECTION
(this slide is from previous internal lecture)
• PRINCIPLES OF FLAME DETECTION
(Ultraviolet & Infrared Wavelengths) (this slide is from previous internal
lecture)
• PRINCIPLE OF AN ACTIVATION
• The Method of Detection of Field Detectors
• The Methods of Activation (Detection of Electronic & Pneumatic Panel)
• The Location of the Detectors
(and Its Application)
(this slide is from previous internal lecture)
• The Location of the Panels
(and Its Application)

More Related Content

What's hot

FIRE WATER DEMAND CALCULATION.pdf
FIRE WATER DEMAND CALCULATION.pdfFIRE WATER DEMAND CALCULATION.pdf
FIRE WATER DEMAND CALCULATION.pdf
rhamset
 
Burner management-systems-a-technical-discussion-ppt
Burner management-systems-a-technical-discussion-pptBurner management-systems-a-technical-discussion-ppt
Burner management-systems-a-technical-discussion-ppt
mkpq pasha
 
On scene reports and size up
On scene reports and size upOn scene reports and size up
On scene reports and size up
res1cuenyc
 

What's hot (20)

Fire safety FM 200
Fire safety FM 200Fire safety FM 200
Fire safety FM 200
 
FIRE WATER DEMAND CALCULATION.pdf
FIRE WATER DEMAND CALCULATION.pdfFIRE WATER DEMAND CALCULATION.pdf
FIRE WATER DEMAND CALCULATION.pdf
 
Fire, flame & smoke detectors
Fire, flame & smoke detectorsFire, flame & smoke detectors
Fire, flame & smoke detectors
 
14-Hazardous Area Classification.ppt
14-Hazardous Area Classification.ppt14-Hazardous Area Classification.ppt
14-Hazardous Area Classification.ppt
 
Foam Use Class PP
Foam Use Class PPFoam Use Class PP
Foam Use Class PP
 
Intro to basic fire alarm technology
Intro to basic fire alarm technologyIntro to basic fire alarm technology
Intro to basic fire alarm technology
 
Burner management-systems-a-technical-discussion-ppt
Burner management-systems-a-technical-discussion-pptBurner management-systems-a-technical-discussion-ppt
Burner management-systems-a-technical-discussion-ppt
 
Fire Fighting Theory
Fire Fighting TheoryFire Fighting Theory
Fire Fighting Theory
 
Back to Basics
Back to BasicsBack to Basics
Back to Basics
 
very early smoke detection apparatus system - Vesda
very early smoke detection apparatus system - Vesdavery early smoke detection apparatus system - Vesda
very early smoke detection apparatus system - Vesda
 
Chapter 06
Chapter 06Chapter 06
Chapter 06
 
Fundamental training on Fire Detection & Alarm System
Fundamental training on Fire Detection & Alarm SystemFundamental training on Fire Detection & Alarm System
Fundamental training on Fire Detection & Alarm System
 
Clean Agent & Inert Gas Fire Suppression
Clean Agent & Inert Gas Fire SuppressionClean Agent & Inert Gas Fire Suppression
Clean Agent & Inert Gas Fire Suppression
 
Hazardous area classification
Hazardous area classificationHazardous area classification
Hazardous area classification
 
FIRE ALARM SYSTEM
FIRE ALARM SYSTEM FIRE ALARM SYSTEM
FIRE ALARM SYSTEM
 
Hazardous area module- Zones, Method of Determination of Hazardous area Radiu...
Hazardous area module- Zones, Method of Determination of Hazardous area Radiu...Hazardous area module- Zones, Method of Determination of Hazardous area Radiu...
Hazardous area module- Zones, Method of Determination of Hazardous area Radiu...
 
Surpermec Ex-proof Presentation.pptx
Surpermec Ex-proof Presentation.pptxSurpermec Ex-proof Presentation.pptx
Surpermec Ex-proof Presentation.pptx
 
On scene reports and size up
On scene reports and size upOn scene reports and size up
On scene reports and size up
 
Sevo Systems
Sevo Systems Sevo Systems
Sevo Systems
 
Fire alarm system and common types of detectors
Fire alarm system and common types of detectorsFire alarm system and common types of detectors
Fire alarm system and common types of detectors
 

Similar to Fire and Gas Detection System : Part 1_The Field Devices and Its Panels

cdocumentsandsettingsdeedesktopfda-1-090226130600-phpapp01 (2).pdf
cdocumentsandsettingsdeedesktopfda-1-090226130600-phpapp01 (2).pdfcdocumentsandsettingsdeedesktopfda-1-090226130600-phpapp01 (2).pdf
cdocumentsandsettingsdeedesktopfda-1-090226130600-phpapp01 (2).pdf
nipunwijewardhana
 
Omni Guard 660 Flame Detector Presentation
Omni Guard 660 Flame Detector PresentationOmni Guard 660 Flame Detector Presentation
Omni Guard 660 Flame Detector Presentation
Mustafa Ali
 
Fire and Gas Detection System_ - Simplified_Revised
Fire and Gas Detection System_ - Simplified_RevisedFire and Gas Detection System_ - Simplified_Revised
Fire and Gas Detection System_ - Simplified_Revised
Gan Chun Chet
 

Similar to Fire and Gas Detection System : Part 1_The Field Devices and Its Panels (20)

Building Electronics (Fire Detection and Alarm System and CCTV)
Building Electronics (Fire Detection and Alarm System and CCTV)Building Electronics (Fire Detection and Alarm System and CCTV)
Building Electronics (Fire Detection and Alarm System and CCTV)
 
cdocumentsandsettingsdeedesktopfda-1-090226130600-phpapp01 (2).pdf
cdocumentsandsettingsdeedesktopfda-1-090226130600-phpapp01 (2).pdfcdocumentsandsettingsdeedesktopfda-1-090226130600-phpapp01 (2).pdf
cdocumentsandsettingsdeedesktopfda-1-090226130600-phpapp01 (2).pdf
 
1-Operate Fire and Gas Detection System.ppt
1-Operate Fire and Gas Detection System.ppt1-Operate Fire and Gas Detection System.ppt
1-Operate Fire and Gas Detection System.ppt
 
Fire alarm systems
Fire alarm systemsFire alarm systems
Fire alarm systems
 
fire detection and alarm system
fire detection and alarm systemfire detection and alarm system
fire detection and alarm system
 
FDA-Fire detection and alarm system
FDA-Fire detection and alarm systemFDA-Fire detection and alarm system
FDA-Fire detection and alarm system
 
Omni Guard 660 Flame Detector Presentation
Omni Guard 660 Flame Detector PresentationOmni Guard 660 Flame Detector Presentation
Omni Guard 660 Flame Detector Presentation
 
Fire detectionand alarm systems 090512042400-phpapp01(1)
Fire detectionand alarm systems 090512042400-phpapp01(1)Fire detectionand alarm systems 090512042400-phpapp01(1)
Fire detectionand alarm systems 090512042400-phpapp01(1)
 
Why are fire detection & alarm system is required in buildings?
Why are fire detection & alarm system is required in buildings?Why are fire detection & alarm system is required in buildings?
Why are fire detection & alarm system is required in buildings?
 
gersgtsedgdfgsrqw3terydrh
gersgtsedgdfgsrqw3terydrhgersgtsedgdfgsrqw3terydrh
gersgtsedgdfgsrqw3terydrh
 
FIRE ALARM SYSTEM.pdf
FIRE ALARM SYSTEM.pdfFIRE ALARM SYSTEM.pdf
FIRE ALARM SYSTEM.pdf
 
Fire Alarm System.pdf
Fire Alarm System.pdfFire Alarm System.pdf
Fire Alarm System.pdf
 
Lecture 5 Fire Alarm System.pdf
Lecture 5 Fire Alarm System.pdfLecture 5 Fire Alarm System.pdf
Lecture 5 Fire Alarm System.pdf
 
UNIT-V FIRE SAFETY INSTALLATION
UNIT-V    FIRE SAFETY INSTALLATIONUNIT-V    FIRE SAFETY INSTALLATION
UNIT-V FIRE SAFETY INSTALLATION
 
UNIT-5.pptx
UNIT-5.pptxUNIT-5.pptx
UNIT-5.pptx
 
Fundamentals of Fire Alarm System
Fundamentals of Fire Alarm SystemFundamentals of Fire Alarm System
Fundamentals of Fire Alarm System
 
Fire and Gas Detection System_ - Simplified_Revised
Fire and Gas Detection System_ - Simplified_RevisedFire and Gas Detection System_ - Simplified_Revised
Fire and Gas Detection System_ - Simplified_Revised
 
Fire detection and alarm system
Fire detection and alarm systemFire detection and alarm system
Fire detection and alarm system
 
Fire detection and alarm system
Fire detection and alarm systemFire detection and alarm system
Fire detection and alarm system
 
Fire alarm and bildge alarm system
Fire alarm and bildge alarm systemFire alarm and bildge alarm system
Fire alarm and bildge alarm system
 

More from Gan Chun Chet

More from Gan Chun Chet (20)

Trust Measurement Presentation_Part 3
Trust Measurement Presentation_Part 3Trust Measurement Presentation_Part 3
Trust Measurement Presentation_Part 3
 
Predicting Machine Setup Time_Suggeting A Limit Determiner, Institute of Engi...
Predicting Machine Setup Time_Suggeting A Limit Determiner, Institute of Engi...Predicting Machine Setup Time_Suggeting A Limit Determiner, Institute of Engi...
Predicting Machine Setup Time_Suggeting A Limit Determiner, Institute of Engi...
 
Predictive Method in Analyzing Past Data_(May_09), Institute of Engineers Mal...
Predictive Method in Analyzing Past Data_(May_09), Institute of Engineers Mal...Predictive Method in Analyzing Past Data_(May_09), Institute of Engineers Mal...
Predictive Method in Analyzing Past Data_(May_09), Institute of Engineers Mal...
 
Modelling Trust of Customer and Supplier Interaction_2023 Vol 10 Issue 1.pdf
Modelling Trust of Customer and Supplier Interaction_2023 Vol 10 Issue 1.pdfModelling Trust of Customer and Supplier Interaction_2023 Vol 10 Issue 1.pdf
Modelling Trust of Customer and Supplier Interaction_2023 Vol 10 Issue 1.pdf
 
Oil and Gas Industry : Datasheet for Fire and Gas Detectors.pdf
Oil and Gas Industry : Datasheet for Fire and Gas Detectors.pdfOil and Gas Industry : Datasheet for Fire and Gas Detectors.pdf
Oil and Gas Industry : Datasheet for Fire and Gas Detectors.pdf
 
Trust Measurement Presentation_2.pptx
Trust Measurement Presentation_2.pptxTrust Measurement Presentation_2.pptx
Trust Measurement Presentation_2.pptx
 
Boundary Layer Oscillation for Aircraft Cavity/Surfaces
Boundary Layer Oscillation for Aircraft Cavity/SurfacesBoundary Layer Oscillation for Aircraft Cavity/Surfaces
Boundary Layer Oscillation for Aircraft Cavity/Surfaces
 
Noise dB to dBA Calculation_Gan Chun Chet.pptx
Noise dB to dBA Calculation_Gan Chun Chet.pptxNoise dB to dBA Calculation_Gan Chun Chet.pptx
Noise dB to dBA Calculation_Gan Chun Chet.pptx
 
Noise Error Calculation_Gan Chun Chet.pptx
Noise Error Calculation_Gan Chun Chet.pptxNoise Error Calculation_Gan Chun Chet.pptx
Noise Error Calculation_Gan Chun Chet.pptx
 
Noise_Proofing Linking Equations.pdf
Noise_Proofing Linking Equations.pdfNoise_Proofing Linking Equations.pdf
Noise_Proofing Linking Equations.pdf
 
The Prediction of Time Trending Techniques in Manufacuturing
The Prediction of Time Trending Techniques in ManufacuturingThe Prediction of Time Trending Techniques in Manufacuturing
The Prediction of Time Trending Techniques in Manufacuturing
 
The Philosophy and Characteristics of Trust Measurement in Practice.docx
The Philosophy and Characteristics of Trust Measurement in Practice.docxThe Philosophy and Characteristics of Trust Measurement in Practice.docx
The Philosophy and Characteristics of Trust Measurement in Practice.docx
 
Trust Measurement Gan Chun Chet 07.01.2022
Trust Measurement Gan Chun Chet 07.01.2022Trust Measurement Gan Chun Chet 07.01.2022
Trust Measurement Gan Chun Chet 07.01.2022
 
mV to dBm Airflow Across Cavity_Gan Chun Chet_07.01.2021
mV to dBm Airflow Across Cavity_Gan Chun Chet_07.01.2021mV to dBm Airflow Across Cavity_Gan Chun Chet_07.01.2021
mV to dBm Airflow Across Cavity_Gan Chun Chet_07.01.2021
 
Control System_3rd Order System_Root Locus Method
Control System_3rd Order System_Root Locus MethodControl System_3rd Order System_Root Locus Method
Control System_3rd Order System_Root Locus Method
 
PID Controllers Control Engineering
PID Controllers Control EngineeringPID Controllers Control Engineering
PID Controllers Control Engineering
 
Noise Reduction Modelling Study for Aircraft Cavity - Chun C Gan
Noise Reduction Modelling Study for Aircraft Cavity  - Chun C GanNoise Reduction Modelling Study for Aircraft Cavity  - Chun C Gan
Noise Reduction Modelling Study for Aircraft Cavity - Chun C Gan
 
Calculation worksheet air flow across rectangular cavity low mach
Calculation worksheet air flow across rectangular cavity low machCalculation worksheet air flow across rectangular cavity low mach
Calculation worksheet air flow across rectangular cavity low mach
 
Noise Error Calculation : Averaging and Industrial Standards (Formula)
Noise Error Calculation : Averaging and Industrial Standards (Formula)Noise Error Calculation : Averaging and Industrial Standards (Formula)
Noise Error Calculation : Averaging and Industrial Standards (Formula)
 
Fluid dynamics 02 tank control system single_cascade
Fluid dynamics 02 tank control system single_cascadeFluid dynamics 02 tank control system single_cascade
Fluid dynamics 02 tank control system single_cascade
 

Recently uploaded

Al Mizhar Dubai Escorts +971561403006 Escorts Service In Al Mizhar
Al Mizhar Dubai Escorts +971561403006 Escorts Service In Al MizharAl Mizhar Dubai Escorts +971561403006 Escorts Service In Al Mizhar
Al Mizhar Dubai Escorts +971561403006 Escorts Service In Al Mizhar
allensay1
 

Recently uploaded (20)

GUWAHATI 💋 Call Girl 9827461493 Call Girls in Escort service book now
GUWAHATI 💋 Call Girl 9827461493 Call Girls in  Escort service book nowGUWAHATI 💋 Call Girl 9827461493 Call Girls in  Escort service book now
GUWAHATI 💋 Call Girl 9827461493 Call Girls in Escort service book now
 
JAJPUR CALL GIRL ❤ 82729*64427❤ CALL GIRLS IN JAJPUR ESCORTS
JAJPUR CALL GIRL ❤ 82729*64427❤ CALL GIRLS IN JAJPUR  ESCORTSJAJPUR CALL GIRL ❤ 82729*64427❤ CALL GIRLS IN JAJPUR  ESCORTS
JAJPUR CALL GIRL ❤ 82729*64427❤ CALL GIRLS IN JAJPUR ESCORTS
 
Berhampur 70918*19311 CALL GIRLS IN ESCORT SERVICE WE ARE PROVIDING
Berhampur 70918*19311 CALL GIRLS IN ESCORT SERVICE WE ARE PROVIDINGBerhampur 70918*19311 CALL GIRLS IN ESCORT SERVICE WE ARE PROVIDING
Berhampur 70918*19311 CALL GIRLS IN ESCORT SERVICE WE ARE PROVIDING
 
Bankura Call Girl Just Call♥️ 8084732287 ♥️Top Class Call Girl Service Available
Bankura Call Girl Just Call♥️ 8084732287 ♥️Top Class Call Girl Service AvailableBankura Call Girl Just Call♥️ 8084732287 ♥️Top Class Call Girl Service Available
Bankura Call Girl Just Call♥️ 8084732287 ♥️Top Class Call Girl Service Available
 
Ooty Call Gril 80022//12248 Only For Sex And High Profile Best Gril Sex Avail...
Ooty Call Gril 80022//12248 Only For Sex And High Profile Best Gril Sex Avail...Ooty Call Gril 80022//12248 Only For Sex And High Profile Best Gril Sex Avail...
Ooty Call Gril 80022//12248 Only For Sex And High Profile Best Gril Sex Avail...
 
Arti Languages Pre Seed Teaser Deck 2024.pdf
Arti Languages Pre Seed Teaser Deck 2024.pdfArti Languages Pre Seed Teaser Deck 2024.pdf
Arti Languages Pre Seed Teaser Deck 2024.pdf
 
JHARSUGUDA CALL GIRL ❤ 82729*64427❤ CALL GIRLS IN JHARSUGUDA ESCORTS
JHARSUGUDA CALL GIRL ❤ 82729*64427❤ CALL GIRLS IN JHARSUGUDA ESCORTSJHARSUGUDA CALL GIRL ❤ 82729*64427❤ CALL GIRLS IN JHARSUGUDA ESCORTS
JHARSUGUDA CALL GIRL ❤ 82729*64427❤ CALL GIRLS IN JHARSUGUDA ESCORTS
 
Paradip CALL GIRL❤7091819311❤CALL GIRLS IN ESCORT SERVICE WE ARE PROVIDING
Paradip CALL GIRL❤7091819311❤CALL GIRLS IN ESCORT SERVICE WE ARE PROVIDINGParadip CALL GIRL❤7091819311❤CALL GIRLS IN ESCORT SERVICE WE ARE PROVIDING
Paradip CALL GIRL❤7091819311❤CALL GIRLS IN ESCORT SERVICE WE ARE PROVIDING
 
Falcon Invoice Discounting: The best investment platform in india for investors
Falcon Invoice Discounting: The best investment platform in india for investorsFalcon Invoice Discounting: The best investment platform in india for investors
Falcon Invoice Discounting: The best investment platform in india for investors
 
Home Furnishings Ecommerce Platform Short Pitch 2024
Home Furnishings Ecommerce Platform Short Pitch 2024Home Furnishings Ecommerce Platform Short Pitch 2024
Home Furnishings Ecommerce Platform Short Pitch 2024
 
ALWAR 💋 Call Girl 9827461493 Call Girls in Escort service book now
ALWAR 💋 Call Girl 9827461493 Call Girls in  Escort service book nowALWAR 💋 Call Girl 9827461493 Call Girls in  Escort service book now
ALWAR 💋 Call Girl 9827461493 Call Girls in Escort service book now
 
Cuttack Call Girl Just Call 8084732287 Top Class Call Girl Service Available
Cuttack Call Girl Just Call 8084732287 Top Class Call Girl Service AvailableCuttack Call Girl Just Call 8084732287 Top Class Call Girl Service Available
Cuttack Call Girl Just Call 8084732287 Top Class Call Girl Service Available
 
HomeRoots Pitch Deck | Investor Insights | April 2024
HomeRoots Pitch Deck | Investor Insights | April 2024HomeRoots Pitch Deck | Investor Insights | April 2024
HomeRoots Pitch Deck | Investor Insights | April 2024
 
Pre Engineered Building Manufacturers Hyderabad.pptx
Pre Engineered  Building Manufacturers Hyderabad.pptxPre Engineered  Building Manufacturers Hyderabad.pptx
Pre Engineered Building Manufacturers Hyderabad.pptx
 
BADDI 💋 Call Girl 9827461493 Call Girls in Escort service book now
BADDI 💋 Call Girl 9827461493 Call Girls in  Escort service book nowBADDI 💋 Call Girl 9827461493 Call Girls in  Escort service book now
BADDI 💋 Call Girl 9827461493 Call Girls in Escort service book now
 
Al Mizhar Dubai Escorts +971561403006 Escorts Service In Al Mizhar
Al Mizhar Dubai Escorts +971561403006 Escorts Service In Al MizharAl Mizhar Dubai Escorts +971561403006 Escorts Service In Al Mizhar
Al Mizhar Dubai Escorts +971561403006 Escorts Service In Al Mizhar
 
Falcon Invoice Discounting: Empowering Your Business Growth
Falcon Invoice Discounting: Empowering Your Business GrowthFalcon Invoice Discounting: Empowering Your Business Growth
Falcon Invoice Discounting: Empowering Your Business Growth
 
Getting Real with AI - Columbus DAW - May 2024 - Nick Woo from AlignAI
Getting Real with AI - Columbus DAW - May 2024 - Nick Woo from AlignAIGetting Real with AI - Columbus DAW - May 2024 - Nick Woo from AlignAI
Getting Real with AI - Columbus DAW - May 2024 - Nick Woo from AlignAI
 
Unveiling Falcon Invoice Discounting: Leading the Way as India's Premier Bill...
Unveiling Falcon Invoice Discounting: Leading the Way as India's Premier Bill...Unveiling Falcon Invoice Discounting: Leading the Way as India's Premier Bill...
Unveiling Falcon Invoice Discounting: Leading the Way as India's Premier Bill...
 
Solan Call Girl Just Call 8084732287 Top Class Call Girl Service Available
Solan Call Girl Just Call 8084732287 Top Class Call Girl Service AvailableSolan Call Girl Just Call 8084732287 Top Class Call Girl Service Available
Solan Call Girl Just Call 8084732287 Top Class Call Girl Service Available
 

Fire and Gas Detection System : Part 1_The Field Devices and Its Panels

  • 1. Fire and Gas Detection System (Offshore Facilities) (Part 1 : The Field Devices and Its Panels) Chun Chet Gan (Ir.) MSc Operations Management [Manchester School Management] University of Manchester Institute of Science and Technology (UMIST), United Kingdom. BEng (Hons) Mechanical Engineering [Simon Building] University of Manchester, United Kingdom
  • 2. The Purpose of Fire and Gas Detection • The purpose of Fire and Gas Detection System, with the detectors located at outdoor and indoor areas of the platform, is to protect the platform from a gas leak or a fire. These areas are segregated into two (2) areas:- 1) outdoor, and 2) indoor areas. • Outdoor areas are zoned into hazard open process or non hazard utility areas. • Enclosed rooms are indoor areas (inside a closed structure or a building).
  • 3. The Detection Area – Outdoor and Indoor • In general, process areas (outdoor) are highly hazardous. It contains hydrocarbon inventories and these areas are regarded as hazard areas on the platform. The classification of these hazardous areas are defined by Safety. - Hazard equipment are vessels, pumps, hydrocarbon pipelines, turbine generators, etc. • Utilities areas (are considered as outdoor areas) are non-hazardous zones of a platform. - Example of equipment in these areas are firewater pumps, diesel tanks, instrument air compressors. - Others equipment like water storage tank, sewage macerator, etc. are also regarded as non-hazardous area. • Indoor areas are safe areas on the platform. • Example of these areas are: - Control Room, - Switchgear Room, - Motor Control Centre MCC • However, battery rooms are hazardous areas.
  • 4. Fire and Gas Detection System in Two Parts - Field Devices and Control Panels • The detection system is segregated into two parts. These are:- 1) Field Devices - located outside in the process areas, utility areas or inside rooms, and 2) Control Panels – these are logic solvers (or programmable logic controllers PLC, addressable controllers), with graphic screens, to perform the required functions (alarm and shutdown) in case of a detection. • The following are pictures of fire and gas detectors and detection panels.
  • 5. • Flame detectors – Ultraviolet (UV) – Ultraviolet and Infrared (UV/IR) – Infrared (Triple IR) Model X3301 (Triple IR) Courtesy of DETRONICS Model S251f+ (Triple IR) Courtesy of THORN Type of Field Devices (this slide is from previous internal lecture)
  • 6. • Smoke detectors – Optical – Ionization (being phased out due to !stringent! disposal requirements of radioactive substances) • Heat detectors – rate of rise – fixed Model 601P Smoke Detector Model 601H-R Model 601H-F Heat Detector Courtesy of THORN Type of Field Devices (this slide is from previous internal lecture)
  • 7. Type of Field Devices (this slide is from previous internal lecture) • Pneumatic fusible plugs (pressure sensors will send a signal to fire and gas system FGS upon detection of low air pressure) – Melt at 71 degree celsius • Manual alarm callpoint – Breakglass or pushbutton Model SS-6-FTA-160 Fusible Plug MODEL SM87 BG MODEL SM87 PB Courtesy of MEDC Courtesy of SWAGELOK
  • 8. Type of Field Devices (this slide is from previous internal lecture) • Gas detectors – Infrared, electrochemical, catalytic (point detectors) – Infrared (line-of-sight) Courtesy of DRAEGER Model Polytron 2IR Model Pulsar Model Polytron FX Model APEX Model ECLIPSE Courtesy of DETRONICS Model OPECL Courtesy of DETRONICS Courtesy of SIEGER
  • 9. Types of Fire and Gas Panel (this slide is from previous internal lecture) • Programmable Logic Controller (PLC based) - Main Panel - Addressable Panel Model MINERVA Courtesy of THORN Courtesy of Honeywell Model Honeywell Icon Series Console MMI Model Honeywell Fail Safe Controller (FSC)
  • 10. ANIMATION OF A GAS LEAK V-1 WIND GD-1 GD-2 Tx Rx
  • 11. ANIMATION OF PLACING FLAME DETECTORS FD-1 FD-2 V-1 FD-3
  • 12. ANIMATION OF A SHUTDOWN GD 2oo3 GD GD & Maintenance Enabled Reset w latched Alarm Shutdown
  • 13. Principle of Gas Detection (1) (this slide is from previous internal lecture) 100
  • 14. Principle of Gas Detection (2) • The principle of detection is based on absorption of infrared light by hydrocarbon gas in the measurement chamber. • For open path (or line-of-sight) gas detectors, the measurement area in between the receiver and the transmitter unit is the hazardous area that required to be monitored by these units. It is this area that this set of detectors are aligned diagonally across or straight over the equipment. The unit of measurement is LEL.m or LFL.m • LEL is the abbreviation for lower explosive limit whereas LFL is lower flammability limit. • LEL.m or LFL.m is the concentration of the gas cloud multiply by the distance between the receiver and the transmitter unit. - For example, if the gas cloud is 20 %LEL or %LFL, and the distance between the receiver and the transmitter unit is 5 metres, then the measurement reading is about 20 %LEL x 5.0m = 1.0 LEL.m (0.20x5 = 1.0LEL.m). If the gas cloud is 60%LEL and the distance is 5 metres, the reading is 60 %LEL x 5m = 3.0 LEL.m
  • 15. Principle of Flame Detection (1) (Ultraviolet & Infrared Wavelengths) (this slide is from previous internal lecture) Extracted from NFPA 72 recommended guide on Code of Practice
  • 16. Principle of Flame Detection (2) • UV Flame Detector – This detector detects UV light source in a fire. UV light source are found in hydrogen flame. • UV/IR Flame Detector – This detector must detects both UV and IR light source before this detector considers the target/detection area as a confirmed detection. • Triple IR Flame Detector – This detector has three (3) infrared sensors. Infrared light source are found in hydrocarbon flame.
  • 17. Principle of Activation (1) GD FD 2ooN Maintenance Override & Alarm or Shutdown Latched Reset
  • 18. Principle of Activation (2) • The controller is either an electronic and pneumatic panel. • The electronic panels are as below: 1) main panel (redundant/triplicated TMR), 2) addressable panel, and 3) instrument package panels (like turbine generators, firewater pumps, instrument air compressor, etc.). • 4) Others panels, shutdown panel or Public Address General Alarm PAGA panel • Fire and gas signals to/from various panels (item 2 - 4) will be connected to the main panel. • Pneumatic panels (only pressure transmitter/switch signal connected to the PLC) is a sub-system to the main panel. • Also known as an electro/pneumatic panel (partial electronic), e.g. fusible plug panel, deluge panel, etc., the instrument air is used to pressurized fusible tubes.
  • 19. The Method of Detection of Field Detectors (1) The principle of measurement/detection for field devices are:- • Gas detectors (point HC or open path) – By infrared sensor(s). The concentrated gas will block the light from reaching the sensor. The detection of an early warning below the Lower Explosive Limits LEL will enable the controller to perform a shutdown and sound the alarms. • Flame detectors – A fire will be detected by the sensor (infrared wavelength). The detector will detect a fire only after it develops. • Manual call points – It is a detection by manual activation. The call points are located at the edge of the platform or exit in the room visible to inhabitant of the platform. • Heat detectors – It detects the change in temperature rise (Rate-of-rise) or temperature in exceed of a fixed setpoint in a room. • Smoke detectors (optical) – Smoke particles in measurement chamber block light from an internal source to the sensor. It detects smoke particles before a fire develops. • Fusible plugs – Melting of plugs at fixed elevated temperature due to heat. It is an outdoor protection device.
  • 20. The Method of Activation (1) • Non-Fail Safe (i.e. an energized output on alarm/activation) - This non-fail safe activation will activate output signals only if it is required to be activated. (In normal practice, when the deluge valve is required to be activated, an output signal will be sent to the solenoid that is part of the deluge valve). • Fail Safe – otherwise, the fail safe outputs are de-energized on alarm/activation. (If it is a fail safe application, the output signal will be deactivated when it is required to perform a function. Example of this application is the fire and gas outputs to a shutdown panel/system). • Other applications like a fault signal, has to be supervised to ensure that this signal is noticed when there is a failure in the panel. • The detection system has to safe guard the platform from a gas leak or a fire. When it occurs, the system must work. • It is very unlikely that the redundant device fails when a shutdown is required. Other means has to be sorted to ASSURE a safe operation.
  • 21. The Methods of Detection of Electronic & Pneumatic Panel (2) • Electronic panels – are complete platform solution, with calculated failures (low failure and with redundant I/Os and processors). It takes into account of redundant failure(s), if it occurs. • Pneumatic panels – has become a partial, but proven reliable solution due to its depressurization mode. Air line leakages will bring the platform to a safe condition.
  • 22. The Location of the Detectors (and Its Application) • The types of detectors and its recommended location are in the next slide. • This table shows the type of detectors in the areas mentioned in the previous slides. - Gas and flame detectors are mainly outdoor devices. - Smoke and heat detectors are indoor devices. - Manual call point can be located either in indoor and/or outdoor areas. - Fusible Plugs are outdoor fire detection devices, location as per API RP 14C guidelines. (You can locate flame detectors inside a room if it is appropriate. However, smoke and heat detectors are always located inside an enclosure(s). • These are the devices to detect gas (early warning) or fire (either early warning or after the fire is fully developed).
  • 23. The Location of the Detectors (and Its Application) (this slide is from previous internal lecture)
  • 24. The Location of the Panels (and Its Application) • The control panels are located either in the control room or outside in the open areas. • Electronic Panels with its redundant processors and safe failures have proven its use on offshore platform, with proper design considerations. • Pneumatic Panel, the oldest method, has is rigid and reliable (mechanically) method of shutting down a platform. • The detection system is connected to the deluge system (sometimes, not always) to cool the equipment when the platform is undergoing depressurization through the vent pipes. • At the same time fire and gas signals from other system/panels will send signals to the fire and gas detection panel for fault alarm or shutdown purposes. (e.g. gas turbine panel upon detection of gas or fire will send signal to fire and gas panel to close the fuel lines)
  • 25. Part 1 : The Field Devices and Its Panels • End of Lesson 1 • Questions
  • 26. Own Notes (1) • Part 1 : The Field Devices and Its Panels • The Purpose of Fire and Gas Detection • The Detection Area – Outdoor and Indoor • Fire and Gas Detection System in Two Parts - Field Devices and Control Panels • Type of Field Devices (this slide is from previous internal lecture) • Types of Fire and Gas Panel (this slide is from previous internal lecture) • ANIMATION OF A GAS LEAK • ANIMATION OF PLACING FLAME DETECTORS • ANIMATION OF A SHUTDOWN
  • 27. Own Notes (2) • PRINCIPLES OF GAS DETECTION (this slide is from previous internal lecture) • PRINCIPLES OF FLAME DETECTION (Ultraviolet & Infrared Wavelengths) (this slide is from previous internal lecture) • PRINCIPLE OF AN ACTIVATION • The Method of Detection of Field Detectors • The Methods of Activation (Detection of Electronic & Pneumatic Panel) • The Location of the Detectors (and Its Application) (this slide is from previous internal lecture) • The Location of the Panels (and Its Application)