BS 7671: Requirements for Electrical
Installations
The IET and the Proposed changes
What we know so far…
By Paul Meenan
PAUL MEENAN
• So why are you here?
• Who are The Institute of Engineering and Technology (IET)?
• History of BS 7671
• What are the wiring regulations to me?
• What are the duties under law?
• 18th Edition Draft for Public Comment (DPC), What do we know so far?
• Impacts of changes; Industry and the Client perspective!
• Next Steps!
Topics to Consider
PAUL MEENAN
• You are a duty holder and because ‘The ‘Wiring Regulations’, also known
as British Standard 7671 are being updated.
• As Duty Holders / Electricians etc. You want to discover how this ‘may’
impact your staff and the wider business.
• What as a business and individuals we need to do to prepare.
Why are you here?
• Originally called the Institute of Electrical
Engineers (IEE) formed in 1871.
• Then in 2006 the IEE merged with the Institute
of Incorporated Engineers (IIE).
• This formed the Institution of Engineering and
Technology (IET).
• The IET represents the engineering profession
in matters of public concern and assists
governments to make the public aware of
engineering and technological issues.
• It provides advice on all areas of engineering,
regularly advising Parliament and other
agencies.
Who are the IET?
• The Wiring Regulations were first issued in 1882 by the Society of Telegraph Engineers and of Electricians.
• Consisting of four pages and 21 regulations entitled - ‘Rules and Regulations for the Prevention of Fire Risks Arising from
Electric Lighting’; this is now referred to as the ‘first edition’.
History of BS 7671
• The first edition had requirements' for;
• Isolation, Regulation 7
• Mechanical protection and labelling, Regulation 17
• Periodic Inspection and Testing (now called EICR)
History of BS 7671
• The ‘rules’ document was updated many times until the 8th edition came out in 1924 where it was reprinted with the title
‘Regulations for the Electrical Equipment of Buildings’.
• It kept the name until 1981 when the ‘Fifteenth Edition’ was printed where it became known as the ‘Requirements for
Electrical Installations’.
• The ‘regs’, as they are known in the trade were again amended on numerous occasions until in 1991 they were re-
issued again under the title,
‘Requirements for Electrical Installations’ ~ IEE Wiring Regulations 16th Edition.
• In 1992 they gained the status of a British Standard and became know as BS 7671.
• They were amended three times, after which they were re-issued as BS 7671: 2001, after this two more amendments
(AMD) followed.
History of BS 7671
• There is a new edition out in 1st July 2018, This is to be called,
‘BS 7671: 2018 Requirements for Electrical Installations’ ~ IET Wiring Regulations Eighteenth Edition’
• Since the 15th edition the ‘regs’ have always been republished in a sequence of colour bound books;
Red, Green, Yellow, Blue, Brown.
History of BS 7671
1991
1994
1997
2001
2011
2015
2004
2008
2018
PAUL MEENAN
• They are defined as a Code of Practice, even though they are called ‘Regulations’ and are deemed a non-statutory
standard published by the BSi, they are used in the UK and across the world.
• The standard relates to design, selection and errection; and inspection and testing of electrical systems regardless of
whether the system is permanent or temporary.
• The regulations are the national standard used for electrical installations across the UK on voltages up to 1000V a.c. or
1500V d.c.
• Even though they are non-statutory, the have been referred to in extensive HSE/HSC guidance notes and the Electricity
Safety, Quality and Continuity Regulations 2002 used by the electricity supply industry.
• You can be prosecuted for failure to comply under the Health and safety at work act section 17! It is universally accepted
that compliance with the document and its ‘requirements’ will enable you to comply with the Electricity at Work Regulations
1989.
What are theWiring Regulations to me?
What are duties under law?
• Legislation in layers!
• EAWR 1989, CDM 2015
• HSG Notes, memorandum on EAWR
• BS standards (7671)
• IET Guidance Notes 1-8
PAUL MEENAN
What are duties under law?
• In 1974 the Health and safety at Work Act etc. was published.
This imposes duties on employers and employees (Inc. self employed).
“It shall be the duty of every employer to ensure, so far as is reasonably practicable, the health,
safety and welfare at work of all his employees”
• On April 1st 1990 The Electricity at Work Regulations 1989 were published.
This imposed a duty on people or ‘duty holders’, in respects of work activities on or near, systems,
electrical equipment and conductors.
PAUL MEENAN
Electricity at Work Regulations 1989
“ If a requirement of the regulation is
‘absolute’, for example if the
requirement is not qualified by the
words so far as is reasonably
practicable, the requirement must be
met regardless of cost or any other
consideration”.
Hence the use of the word shall!....
What are duties under law?
So what regulations are an absolute...?
• 4 Systems, activities and protective equipment
• 5 Strength and capability of electrical equipment
• 8 Earthing
• 9 Integrity of conductors
• 10 Connections
• 11 Means of Protecting from Excess Current
• 12 Means of cutting off the supply for isolation
• 13 Precautions for work on equipment made dead
• 14 Working on or near live conductors
• 15 Work space access and lighting
• 16 Person to be Competent to undertake works
PAUL MEENAN
EAWR – Regulation 29
• In any proceedings for an offence consisting of
a contravention of regulations 4, 5, 8, 9, 10, 11,
12, 13, 14, 15, 16, it shall be a defence for any
person to prove that he took all reasonable
steps and exercised all due diligence to avoid
the commission of that offence.
Also review
• The Engineering Council, Competence Criteria
E5 for professional registered engineers!
What are duties under law?
In most cases,
designers/electricians/engineers are
employed to take all reasonable steps!
PAUL MEENAN
What we know so far!
• The UK National Committee responsible for the Wiring Regulations is known as
JPEL 64
• CENELEC harmonisation mandates this committee to review and update BS 7671
accordingly to ensure alignment with the HD 60364 which is the EU version of IEC
60364.
• HD = Harmonised Documents
J Joint
P Power
EL Electrical
64 IEC designation for committees
dealing with low voltage
electrical installations
• Four panels inform the JPEL/64 board, who are the decision-making
committee of BS 7671:
Panel A –
Covers verification and inspection and testing (Part 6 and Appendix 6 of BS 7671) plus any work relating
to Parts 1, 2 and 3 of BS 7671.
Panel B –
Covers cable sizing and installation and related matters (some of Parts 4 and 5, Appendices 3 and 4
and some Part 7 items of BS 7671).
Panel C –
Covers earthing installations and related matters (some of Parts 4 and 5 and some Part 7 items of BS
7671).
Panel D –
Covers the remainder of Parts 4 and 5, some Part 7 items (and some Appendices of BS 7671).
What we know so far!
PAUL MEENAN
What we know so far!
Will Brexit effect the new version of the Regulations?
NO!
• CENELEC is a European organisation which has a membership of 33 European states.
• This is more than just the EU States and they all contribute to the CENELEC Standards.
• The consequences of Britain leaving the EU will not affect the UK membership of CENELEC,
subject to change! We Hope!
• While it is correct that the 18th Edition was being written and amended before the UK left the
European Union there is no significant indication at present that Brexit will change the
publication dates of the 18th Edition for July 2018 or the content of the new document.
What we know so far!
18th Edition Draft for Public Comment
The Proposed changes
PAUL MEENAN
What we know so far
18th Edition
8 Chapters
886 Pages
New Definitions
New Regulations
17TH Edition
7 Chapters
496 Pages
PAUL MEENAN
What we know so far!
Chapter 1 – Scope, Objectives and Fundamental Principles
• The use of the lower case a.c. & d.c.
• Now capitalised ‘AC & DC’ throughout the entire document!
PAUL MEENAN
What we know so far!
Chapter 1 – Scope, Objectives and Fundamental Principles
• Regulation 133.1.3 has been added to.
• Where equipment is not in accordance with Regulation 133.1.1 or is
used outside the scope of its standard, the designer or other person
responsible for specifying the installation shall conform that the
equipment provides at least the same degree of safety as that
afforded by compliance with the Regulations.
Such use is to be noted on the Electrical Installation Certificate
specified in part 6.
PAUL MEENAN
What we know so far!
Chapter 1 – Scope, Objectives and Fundamental Principles
• Regulation 110.11 - The long list of areas in scope now
includes onshore units for navigation vessels within scope.
• Regulation 120.3 – The list of chapters within the book now
includes first reference to a possible chapter 8 on energy
efficiency
PAUL MEENAN
What we know so far!
Chapter 2 – Expanded and Modified Definitions
• Combined Short Circuit Current Capability – Maximum short circuit current
which can be handled by two short circuit protective devices in series.
Combined short circuit protection.
• Overcurrent Co-ordination – In short circuit conditions, of two OCPDs in series,
resulting in a combined short circuit current capability higher than one OCPD
alone.
• Discrimination, replaced by Selectivity – Co-ordination of the operating
characteristics' of two or more protective devices such that, on the incidence of
overcurrents’ or residual currents within stated limits, the device intended to
operate within these limits does so, while the other(s) does (do) not.
PAUL MEENAN
What we know so far!
Chapter 2 – Expanded and Modified Definitions
• Foundation Earth Electrode – ‘Conductive part buried in the soil under a
building foundation or, preferably embedded in concrete of a building
foundation, generally in the form of a closed loop’.
• Non Compliance – A non conformity that may give rise to danger.
• Bonding Conductor – ‘a protective conductor providing equipotential bonding’.
Now ‘a protective conductor providing equipotential bonding for the purpose of
equalising potential differences of exposed and extraneous conductive parts’.
PAUL MEENAN
What we know so far!
Chapter 2 – Expanded and Modified Definitions
• Departure – Deliberate decision to not fully comply with the
requirements' of this standard, for which the designer must declare
that the resultant degree of safety is not less than that achievable by
full compliance’.
PAUL MEENAN
PAUL MEENAN
What we know so far!
Chapter 4 – Protection against electric shock
• Chapter 41 Lots of changes!
• RCDs – Regulation 411.3.3 The regulations requires RCD protection on all
socket outlets, risk assessment exemption is now deleted.
• RCDs – New Regulation 411.3.4 requires in domestic premises additional
protection by 30mA RCD for AC Final circuits supplying luminaires!
• Regulation 411.3.2.2 The maximum disconnection time shown in Table 41.1
now applies to circuits up to 63A with one or more socket outlets and 32A for
final circuits supplying fixed current using equipment. Used to be 32A
• TN 0.4s
• TT 0.2s
PAUL MEENAN
What we know so far!
Chapter 4 – Protection against electric shock
• Regulation 411.3.1.2 List metallic items that are
to be equipotential bonded within an installation,
however it now adds/states;
‘Metallic pipes entering the building having an
insulating section at their point of entry need not be
connected to the protective equipotential bonding’.
SO NO BONDING WATER AND GAS PIPE IF
INSULATED!
• Chapter 42 New Technology!
• A new regulation 421.1.7 – ARC fault protection devices (AFDD) conforming to BS
EN 62606 may be used to provide additional protection against fire caused by arc
faults in AC final circuits’
This was due to concerns around protection relating to fire caused by electrical
equipment, RCDs cannot detect series or parallel arcing because these faults do not
result in leakage current to earth.
What we know so far!
Chapter 4 – Protection against thermal effects
• Arc Fault Detection is known around the world as;
• AFD = Arc Fault Detection;
• AFDD = Arc Fault Detection Device;
• AFI = Arc Fault Interrupter;
• They are marketed as a Fire prevention device. They
are also seen as closing the gap in terms of electrical
protection, and can be used in domestic and non-
domestic installations.
• Made to standard BS EN 62606:2013
What we know so far!
What is Arc Fault Detection?
What we know so far!
What is Arc Fault Detection
• AFDD monitor three types of scenarios that could result in fire. They are;
1. Parallel arc detection, insulation between cores and phases cause a short circuit to weak
to be detected by a circuit breaker and with no earth leakage that would be picked up
by an RCD!
2. Series arc detection, a damaged conductor or connection that causes part of the current
to pass into its carbonized insulation due to temperature rise.
3. Overheating of electronic components in loads, when exposed to over voltage for
several seconds.
What we know so far!
What is Arc Fault Detection?
PAUL MEENAN
What we know so far!
PAUL MEENAN
What we know so far!
PAUL MEENAN
What we know so far!
Protection against overvoltages: will be changed fairly radically.
Clause 443
• Both IEC and CENELEC have published updates concerning overvoltage.
It is also apparent that protection against transient overvoltage will be
significantly changed in BS7671.
• AQ Criteria of App 5 is no longer needed (conditions of external influence
for lightning)
• Protection would have to be provided where the consequences affect
human life, public services and commercial &/or industrial activity.
• Risk assessment will need to be made as to whether protection is required
having considered the potential human and commercial consequences of
no protection.
PAUL MEENAN
What we know so far!
Chapter 5 – Selection and Erection
• 17th edition Amd 3 introduced,
Regulation 521.11 – ‘wiring in escape routes shall be supported such that they will
not be liable to collapse in the event of fire’
• This is now replaced by a new regulation
521.10.202 - Wiring systems shall be supported such that they will not be liable to
premature collapse in the event of a fire.
• This is huge change and applies throughout the install not just escape routes.
PAUL MEENAN
What we know so far!
Chapter 5 – Selection and Erection
• Bad Practice!
• Avoid please!
PAUL MEENAN
What we know so far!
Chapter 5 – Selection and Erection
• Chapter 53 Protection, isolation, switching, control and monitoring, this has been
extensively rewritten. Not a worry it brings back old parts once removed.
• 531.3.2 – Unwanted Tripping; requires designer to limit amount of downstream
current to not more than 30% of the RCD rating! It asks us to subdivide circuits
to eliminate or avoid nuisance tripping.
• 30mA = 9mA
• 100mA = 30mA
• 300mA = 90mA
PAUL MEENAN
What we know so far!
Chapter 5 – Selection and Erection
• Chapter 54 Earthing arrangements. MAJOR CHANGE!
• Regulation 542.1.201 states. ‘ The main earthing terminal shall be
connected with earth by one of the methods described in regulations 542.1
to 3.
• It then adds…
Additionally, there shall be an earth electrode, supplementing any earth
facility provided by the distributor, in accordance with requirements of
regulation 542.2.3, to prevent the appearance of dangerous step and touch
voltage in the event of the loss of the main connection to earth.
PAUL MEENAN
What we know so far!
Chapter 5 – Selection and Erection
• So, a 100A TN-S supply has a maximum allowed Ze of 0.8Ω
230V = 2.3Ω
100A
• So any earth rods would need to be 2.3Ω or below to enable supply fuse disconnection.
PAUL MEENAN
What we know so far!
Chapter 6 – Inspection and Testing
• Completely restructured to allow for CENELEC harmonisation!
• Chapters 61, 62, 63 have been deleted!
• Content of those chapters have been transferred into Chapters 64 and 65
• 64 - Initial Verification, 65 - Periodic Inspection and Testing.
• Regulation 641.5 For an addition or alteration to an existing installation, it shall
be verified that the addition or alteration complies with the regulations and does
not impair the safety of the existing installation. This links to 132.16!
• New requirement for polarity checks at origin of installation before energisation
required.
PAUL MEENAN
What we know so far!
Chapter 6 – Inspection and Testing
• Regulation 612.6 (17th edition) used to cover requirements for polarity testing,
• Regulation 643.6 add to this and states, Where relevant, the polarity of the supply at the
origin of the installation shall be verified before the installation is energised. Where single
pole switching devices are not permitted in the neutral conductor, a test shall be made to
verify that all such devices are connected in the line conductor(s) only. During the polarity
test, it should be verified that:
PAUL MEENAN
What we know so far!
Chapter 6 – Inspection and Testing
• New Regulations?
• 653.1 Upon completion of the periodic inspection and testing of an existing installation, an electrical
installation condition report shall be provided.
• 653.2 The report shall include the following:
• Details of those parts of the installation that have been inspected;
• Any limitations of the inspection and testing;
• Any damage, deterioration, defects or dangerous conditions;
• Schedules of inspection;
• Schedules of results of the appropriate test detailed in 643
• 653.3 The reports shall contain a recommendation for the interval until the next periodic inspection.
• 653.5 The report shall be compiled and signed or otherwise authenticated by one or more skilled
persons.
• 653.6 The report shall be given by a skilled person responsible for carrying out the inspection and
testing, or a skilled person authorised to act on their behalf, to the person ordering the inspection
and testing.
PAUL MEENAN
What we know so far! Chapter 6 – Enhanced Minor works form
PAUL MEENAN
PAUL MEENAN
What we know so far!
PAUL MEENAN
What we know so far!
Chapter 7 – Special Locations
Section 753
Electrical Embedded heating
• Section 753 will be extended to include embedded electrical heating systems
for surface heating, and will include de-icing and frost prevention systems.
• Revisions will include regulations relating to the protection against the effects of
overheating caused by electrical short-circuits in embedded units and relating
to harmful influence between the heating system and other electrical and non-
electrical installations.
PAUL MEENAN
What we know so far!
NEW CHAPTER 8
Energy efficiency
• This will form Section 8 of the Regulations – there are currently 7
sections
NEW CHAPTER!
Energy efficiency
• The brand new section will also be covering various topics, such as: electric
vehicles, smart metering, lighting, cable losses (loss of energy through cable),
transformer losses (loss of energy through the transformer) and power-factor
correction (how efficient the power generated is being converted into useful
energy)
• It will also cover how installations will be awarded points for their “energy
efficiency performance levels”. The points are added up along with points for
“efficiency measures”, which the installer can then give the electrical installation
an overall efficiency class (EIEC0 to EIEC4).
PAUL MEENAN
What we know so far!
PAUL MEENAN
What we know so far!
NEW CHAPTER!
New Terminology
• Active electrical energy efficiency measures – measures for the optimisation of
electrical energy produced, supplied, flowing and consumed by an electrical
installation for the best permanent functionally equivalent service.
• Distribution system design. Design of cables and associated electrical equipment
for the distribution of electrical energy.
• Current using equipment – electrical equipment intended to convert electrical
energy into another form of energy, for example light, heat mechanical energy.
PAUL MEENAN
What we know so far!
NEW CHAPTER 8
Energy efficiency
• Recent surveys have branded this section not required nor wanted from
the trade.
• Some think its….
• Fact is the regulations are about safety and not energy efficiency.
Final Thoughts, an Impact Assessment
PAUL MEENAN
Impact of Changes, Positive and negative
Ask yourself… what is a safe installation anymore!
• So now have to think to yourself; how does the changes effect me, my business?
• Ask yourself, why have the BSi and IET made the commenting system so difficult, when it was
more simple before! It is also less accessible by anyone who is not IT savvy!
• Who benefits from the changes proposed?
• Who has the time to read this, and then cross check between new and current editions to
understand the changes/Impacts before August deadline! Do clients, contractors?
• Does my installation now not comply? And does this mean I am in breach of the Electricity at
Work Regulations 1989….One would suggest NO!
• The next two slides are items you may wish to use to stimulate conversations' in your business.
PAUL MEENAN
Impact of Changes, Positive and negative
Clients / Industry / Electricians / Manufacturers
• Costs for re-training; - individuals, employers, client cost impacts.
• Costs for new books will be? More no doubt.. plus 9 guidance notes? Who pays
• New standard must be reviewed against ISO 55000 standard as to impact on bringing
current asset portfolio into compliance.
• All installations ‘may’ fail EICRs! Insurers may demand compliance at client costs!
• Revise specifications to define departures from whole sections of the standard?
• Should we seek to attain compliance with past standards, BS 7671 16th or 17th edition?
PAUL MEENAN
Impact of Changes, Positive and negative
Clients / Industry / Electricians / Manufacturers
• Should we seek to attain compliance with past standards, BS 7671 16th or 17th edition?
• New (possible sub-standard) products and points of failure being introduced.
• Manufacturers and governing bodies reputations’ could be being branded as self
perpetuating their own economy! Most committees are sat on by manufacturers.
• Designer has cart blanche to make decisions based on supply chain need and not clients
• Could have huge impact to Business Operations
• Huge confusion in supply chain as to CDM application as to design liability of roles!
PAUL MEENAN
Impact of Changes, positive and negative
• Seen to show lack of strong fundamental principles and being led by a lower standard, EU
driven mandate.
• BREXIT is also a mind-set! Users will push back post Brexit surely.
• Railways/Social Housing/Sectors will have to update standards, specifications and
guidance notes, who pays for that?
• Can be manipulated by suppliers, exemptions not checked, client may want full
compliance, designer may not have time!
• The current regulations are being breached by a weakened industry which is suffering with
competence issues, what makes these regs any better?
• How will these make the individuals better, hence improving the problem being seen
across the entire industry..
PAUL MEENAN
Impact of Changes, positive and negative
• Seen as sole opportunity to sell new products.
• Opportunity to import cheap products.
• Manufactures' can mark up new technology to cover cost of compliance testing.
• Industry will leave a huge gap between those trained on first principles!
• Possible rejection of the IET and Voluntary Regulatory bodies. Creation of unregulated
silos!
• Cause change fatigue across the industry!
• Reputational damage as new books will cost more!
PAUL MEENAN
So what Next
• Well lets hope the governing bodies are flat out trying to help all in the industry understand
and summarise the impacts so we may have a fair time to freely comment!
• Lets also hope all comments offered online are public for all to see and not censored nor
ignored.
• Look at your own businesses, finances and determine for yourself the impact..
18th Edition IET Wiring Regulations
PAUL MEENAN
Questions?
Paul Meenan
CEng FIET MIAM MILP PCQI
paulmeenan@me.com
#E5

More Related Content

What's hot

Air circuit breakers
Air circuit breakersAir circuit breakers
Air circuit breakers
Prasant Kumar
 
Electrical Troubleshooting
Electrical TroubleshootingElectrical Troubleshooting
Electrical Troubleshooting
Nabeel Hassan
 
Earthing system
Earthing system   Earthing system
Earthing system
Dr Ashok Tiwari
 
Electrical protective devices ec
Electrical protective devices ecElectrical protective devices ec
Electrical protective devices ec
trg12345
 
NS2 5.3 Basic Electricity
NS2 5.3 Basic ElectricityNS2 5.3 Basic Electricity
NS2 5.3 Basic Electricity
Bishop Kenny NJROTC NS1/NS2
 
Basic of electrical
Basic of electricalBasic of electrical
Basic of electrical
hrishikesh kulkarni
 
Electrical testing
Electrical testingElectrical testing
Electrical testing
Aarjun Singh Panesar
 
Earthing, grounding and isolation
Earthing, grounding and isolation Earthing, grounding and isolation
Earthing, grounding and isolation
Dhananjaysinh Jhala
 
Electrical safety
Electrical safetyElectrical safety
Electrical safety
SUDHEER KUMAR KALYANAM
 
Electrical Safety by OSHA
Electrical Safety by OSHAElectrical Safety by OSHA
Electrical Safety by OSHA
Atlantic Training, LLC.
 
Electrical Safety
Electrical  Safety Electrical  Safety
Electrical Safety
Reliance
 
Cable joint n end connector
Cable joint n end connectorCable joint n end connector
Cable joint n end connector
BHAGWAN PRASAD
 
Basic electrical system
Basic electrical systemBasic electrical system
Basic electrical system
MLCalver
 
Power system earthing
Power system earthingPower system earthing
Power system earthing
Nisarg Amin
 
Electrical Risk Management
Electrical Risk ManagementElectrical Risk Management
Electrical Risk Managementguest81e1c7
 
Electrical hazards and safety measures
Electrical hazards and safety measuresElectrical hazards and safety measures
Electrical hazards and safety measures
Rock Wood
 
Design and construction of underground cable transmission line
Design and construction of underground cable transmission lineDesign and construction of underground cable transmission line
Design and construction of underground cable transmission line
Fazlur Rahman
 
Switchgear and protection lecture 2 type of circuit breakers and applications
Switchgear and protection lecture 2 type of circuit breakers and applicationsSwitchgear and protection lecture 2 type of circuit breakers and applications
Switchgear and protection lecture 2 type of circuit breakers and applications
anuphowlader1
 
Complete Guide to Electrical Safety in the Workplace
Complete Guide to Electrical Safety in the WorkplaceComplete Guide to Electrical Safety in the Workplace
Complete Guide to Electrical Safety in the Workplace
hudsonelectrical
 

What's hot (20)

Air circuit breakers
Air circuit breakersAir circuit breakers
Air circuit breakers
 
Electrical Troubleshooting
Electrical TroubleshootingElectrical Troubleshooting
Electrical Troubleshooting
 
Earthing system
Earthing system   Earthing system
Earthing system
 
Electrical protective devices ec
Electrical protective devices ecElectrical protective devices ec
Electrical protective devices ec
 
NS2 5.3 Basic Electricity
NS2 5.3 Basic ElectricityNS2 5.3 Basic Electricity
NS2 5.3 Basic Electricity
 
Basic of electrical
Basic of electricalBasic of electrical
Basic of electrical
 
Electrical testing
Electrical testingElectrical testing
Electrical testing
 
Earthing, grounding and isolation
Earthing, grounding and isolation Earthing, grounding and isolation
Earthing, grounding and isolation
 
Electrical safety
Electrical safetyElectrical safety
Electrical safety
 
Electrical Safety by OSHA
Electrical Safety by OSHAElectrical Safety by OSHA
Electrical Safety by OSHA
 
Electrical Safety
Electrical  Safety Electrical  Safety
Electrical Safety
 
Cable joint n end connector
Cable joint n end connectorCable joint n end connector
Cable joint n end connector
 
Basic electrical system
Basic electrical systemBasic electrical system
Basic electrical system
 
Power system earthing
Power system earthingPower system earthing
Power system earthing
 
Electrical Risk Management
Electrical Risk ManagementElectrical Risk Management
Electrical Risk Management
 
Electrical hazards and safety measures
Electrical hazards and safety measuresElectrical hazards and safety measures
Electrical hazards and safety measures
 
Design and construction of underground cable transmission line
Design and construction of underground cable transmission lineDesign and construction of underground cable transmission line
Design and construction of underground cable transmission line
 
Domestic wiring
Domestic wiringDomestic wiring
Domestic wiring
 
Switchgear and protection lecture 2 type of circuit breakers and applications
Switchgear and protection lecture 2 type of circuit breakers and applicationsSwitchgear and protection lecture 2 type of circuit breakers and applications
Switchgear and protection lecture 2 type of circuit breakers and applications
 
Complete Guide to Electrical Safety in the Workplace
Complete Guide to Electrical Safety in the WorkplaceComplete Guide to Electrical Safety in the Workplace
Complete Guide to Electrical Safety in the Workplace
 

Similar to BS 7671 - 18th Edition Widescreen PP Rev 4

Final_NFE,May23-Lenin-CEA-Safety- Regulations PPT.pptx
Final_NFE,May23-Lenin-CEA-Safety- Regulations PPT.pptxFinal_NFE,May23-Lenin-CEA-Safety- Regulations PPT.pptx
Final_NFE,May23-Lenin-CEA-Safety- Regulations PPT.pptx
ssuser4bcf3b
 
Abb electrical installation handbook 6th edition2010
Abb electrical installation handbook 6th edition2010Abb electrical installation handbook 6th edition2010
Abb electrical installation handbook 6th edition2010
Miguel Pedre
 
The electricity at work reg 1989
The electricity at work reg 1989The electricity at work reg 1989
The electricity at work reg 1989
Isis Arsenio Singer, CEng MIET
 
Electrical safety in power stations
Electrical safety in power stationsElectrical safety in power stations
Electrical safety in power stations
Manohar Tatwawadi
 
Jeep AS 2067 Presentation By Peter Willis
Jeep AS 2067 Presentation By Peter WillisJeep AS 2067 Presentation By Peter Willis
Jeep AS 2067 Presentation By Peter WillisEngineers Australia
 
Universal Cables Ltd
Universal Cables LtdUniversal Cables Ltd
Universal Cables LtdAnil Nair
 
Electrical condition report
Electrical condition reportElectrical condition report
Electrical condition reportelectrician2hire
 
What is an EICR, and Why Does Every Landlord Need One?
What is an EICR, and Why Does Every Landlord Need One?What is an EICR, and Why Does Every Landlord Need One?
What is an EICR, and Why Does Every Landlord Need One?
Electric Works London
 
Electrical installation handbook part-1
Electrical installation handbook part-1Electrical installation handbook part-1
Electrical installation handbook part-1
Souvik Dutta
 
1 3 amec
1 3 amec1 3 amec
1 3 amec
Ahmed Awaise
 
Bs 3871 mcb and mccb in ac circuits
Bs 3871 mcb and mccb in ac circuitsBs 3871 mcb and mccb in ac circuits
Bs 3871 mcb and mccb in ac circuits
Vasudev Mogili
 
Introduction on indian codes as applied in electrical design
Introduction on indian codes as applied in electrical designIntroduction on indian codes as applied in electrical design
Introduction on indian codes as applied in electrical design
Asif Eqbal
 
PSI-TECH-PRO-0001 Rev 01 Legal Booklet Electric Fencing and Labour Department
PSI-TECH-PRO-0001 Rev 01 Legal Booklet Electric Fencing and Labour DepartmentPSI-TECH-PRO-0001 Rev 01 Legal Booklet Electric Fencing and Labour Department
PSI-TECH-PRO-0001 Rev 01 Legal Booklet Electric Fencing and Labour Departmentjames loxton
 
RoHS_WEEE Presentation Sept06.ppt
RoHS_WEEE Presentation Sept06.pptRoHS_WEEE Presentation Sept06.ppt
RoHS_WEEE Presentation Sept06.ppt
WatcharaphonLordthon
 
The electricity at work regulations 1989
The electricity at work regulations 1989The electricity at work regulations 1989
The electricity at work regulations 1989electrician2hire
 
TSS-TECH-PRO-0001 Rev 01 Legal Booklet Electric Fencing and Labour Department
TSS-TECH-PRO-0001 Rev 01 Legal Booklet Electric Fencing and Labour DepartmentTSS-TECH-PRO-0001 Rev 01 Legal Booklet Electric Fencing and Labour Department
TSS-TECH-PRO-0001 Rev 01 Legal Booklet Electric Fencing and Labour DepartmentTrusted Security Solutions
 

Similar to BS 7671 - 18th Edition Widescreen PP Rev 4 (20)

Final_NFE,May23-Lenin-CEA-Safety- Regulations PPT.pptx
Final_NFE,May23-Lenin-CEA-Safety- Regulations PPT.pptxFinal_NFE,May23-Lenin-CEA-Safety- Regulations PPT.pptx
Final_NFE,May23-Lenin-CEA-Safety- Regulations PPT.pptx
 
Abb electrical installation handbook 6th edition2010
Abb electrical installation handbook 6th edition2010Abb electrical installation handbook 6th edition2010
Abb electrical installation handbook 6th edition2010
 
AN10912
AN10912AN10912
AN10912
 
The electricity at work reg 1989
The electricity at work reg 1989The electricity at work reg 1989
The electricity at work reg 1989
 
Electrical safety in power stations
Electrical safety in power stationsElectrical safety in power stations
Electrical safety in power stations
 
Jeep AS 2067 Presentation By Peter Willis
Jeep AS 2067 Presentation By Peter WillisJeep AS 2067 Presentation By Peter Willis
Jeep AS 2067 Presentation By Peter Willis
 
Universal Cables Ltd
Universal Cables LtdUniversal Cables Ltd
Universal Cables Ltd
 
Electrical condition report
Electrical condition reportElectrical condition report
Electrical condition report
 
What is an EICR, and Why Does Every Landlord Need One?
What is an EICR, and Why Does Every Landlord Need One?What is an EICR, and Why Does Every Landlord Need One?
What is an EICR, and Why Does Every Landlord Need One?
 
WHO final
WHO  finalWHO  final
WHO final
 
Electrical installation handbook part-1
Electrical installation handbook part-1Electrical installation handbook part-1
Electrical installation handbook part-1
 
1 3 amec
1 3 amec1 3 amec
1 3 amec
 
Bs 3871 mcb and mccb in ac circuits
Bs 3871 mcb and mccb in ac circuitsBs 3871 mcb and mccb in ac circuits
Bs 3871 mcb and mccb in ac circuits
 
04 Report
04 Report04 Report
04 Report
 
Introduction on indian codes as applied in electrical design
Introduction on indian codes as applied in electrical designIntroduction on indian codes as applied in electrical design
Introduction on indian codes as applied in electrical design
 
PSI-TECH-PRO-0001 Rev 01 Legal Booklet Electric Fencing and Labour Department
PSI-TECH-PRO-0001 Rev 01 Legal Booklet Electric Fencing and Labour DepartmentPSI-TECH-PRO-0001 Rev 01 Legal Booklet Electric Fencing and Labour Department
PSI-TECH-PRO-0001 Rev 01 Legal Booklet Electric Fencing and Labour Department
 
RoHS_WEEE Presentation Sept06.ppt
RoHS_WEEE Presentation Sept06.pptRoHS_WEEE Presentation Sept06.ppt
RoHS_WEEE Presentation Sept06.ppt
 
The electricity at work regulations 1989
The electricity at work regulations 1989The electricity at work regulations 1989
The electricity at work regulations 1989
 
Stephen-Hayles
Stephen-HaylesStephen-Hayles
Stephen-Hayles
 
TSS-TECH-PRO-0001 Rev 01 Legal Booklet Electric Fencing and Labour Department
TSS-TECH-PRO-0001 Rev 01 Legal Booklet Electric Fencing and Labour DepartmentTSS-TECH-PRO-0001 Rev 01 Legal Booklet Electric Fencing and Labour Department
TSS-TECH-PRO-0001 Rev 01 Legal Booklet Electric Fencing and Labour Department
 

Recently uploaded

DESIGN A COTTON SEED SEPARATION MACHINE.docx
DESIGN A COTTON SEED SEPARATION MACHINE.docxDESIGN A COTTON SEED SEPARATION MACHINE.docx
DESIGN A COTTON SEED SEPARATION MACHINE.docx
FluxPrime1
 
Courier management system project report.pdf
Courier management system project report.pdfCourier management system project report.pdf
Courier management system project report.pdf
Kamal Acharya
 
Sachpazis:Terzaghi Bearing Capacity Estimation in simple terms with Calculati...
Sachpazis:Terzaghi Bearing Capacity Estimation in simple terms with Calculati...Sachpazis:Terzaghi Bearing Capacity Estimation in simple terms with Calculati...
Sachpazis:Terzaghi Bearing Capacity Estimation in simple terms with Calculati...
Dr.Costas Sachpazis
 
LIGA(E)11111111111111111111111111111111111111111.ppt
LIGA(E)11111111111111111111111111111111111111111.pptLIGA(E)11111111111111111111111111111111111111111.ppt
LIGA(E)11111111111111111111111111111111111111111.ppt
ssuser9bd3ba
 
Vaccine management system project report documentation..pdf
Vaccine management system project report documentation..pdfVaccine management system project report documentation..pdf
Vaccine management system project report documentation..pdf
Kamal Acharya
 
WATER CRISIS and its solutions-pptx 1234
WATER CRISIS and its solutions-pptx 1234WATER CRISIS and its solutions-pptx 1234
WATER CRISIS and its solutions-pptx 1234
AafreenAbuthahir2
 
Architectural Portfolio Sean Lockwood
Architectural Portfolio Sean LockwoodArchitectural Portfolio Sean Lockwood
Architectural Portfolio Sean Lockwood
seandesed
 
在线办理(ANU毕业证书)澳洲国立大学毕业证录取通知书一模一样
在线办理(ANU毕业证书)澳洲国立大学毕业证录取通知书一模一样在线办理(ANU毕业证书)澳洲国立大学毕业证录取通知书一模一样
在线办理(ANU毕业证书)澳洲国立大学毕业证录取通知书一模一样
obonagu
 
一比一原版(SFU毕业证)西蒙菲莎大学毕业证成绩单如何办理
一比一原版(SFU毕业证)西蒙菲莎大学毕业证成绩单如何办理一比一原版(SFU毕业证)西蒙菲莎大学毕业证成绩单如何办理
一比一原版(SFU毕业证)西蒙菲莎大学毕业证成绩单如何办理
bakpo1
 
Pile Foundation by Venkatesh Taduvai (Sub Geotechnical Engineering II)-conver...
Pile Foundation by Venkatesh Taduvai (Sub Geotechnical Engineering II)-conver...Pile Foundation by Venkatesh Taduvai (Sub Geotechnical Engineering II)-conver...
Pile Foundation by Venkatesh Taduvai (Sub Geotechnical Engineering II)-conver...
AJAYKUMARPUND1
 
power quality voltage fluctuation UNIT - I.pptx
power quality voltage fluctuation UNIT - I.pptxpower quality voltage fluctuation UNIT - I.pptx
power quality voltage fluctuation UNIT - I.pptx
ViniHema
 
Immunizing Image Classifiers Against Localized Adversary Attacks
Immunizing Image Classifiers Against Localized Adversary AttacksImmunizing Image Classifiers Against Localized Adversary Attacks
Immunizing Image Classifiers Against Localized Adversary Attacks
gerogepatton
 
ethical hacking in wireless-hacking1.ppt
ethical hacking in wireless-hacking1.pptethical hacking in wireless-hacking1.ppt
ethical hacking in wireless-hacking1.ppt
Jayaprasanna4
 
Halogenation process of chemical process industries
Halogenation process of chemical process industriesHalogenation process of chemical process industries
Halogenation process of chemical process industries
MuhammadTufail242431
 
Nuclear Power Economics and Structuring 2024
Nuclear Power Economics and Structuring 2024Nuclear Power Economics and Structuring 2024
Nuclear Power Economics and Structuring 2024
Massimo Talia
 
Planning Of Procurement o different goods and services
Planning Of Procurement o different goods and servicesPlanning Of Procurement o different goods and services
Planning Of Procurement o different goods and services
JoytuBarua2
 
Quality defects in TMT Bars, Possible causes and Potential Solutions.
Quality defects in TMT Bars, Possible causes and Potential Solutions.Quality defects in TMT Bars, Possible causes and Potential Solutions.
Quality defects in TMT Bars, Possible causes and Potential Solutions.
PrashantGoswami42
 
Top 10 Oil and Gas Projects in Saudi Arabia 2024.pdf
Top 10 Oil and Gas Projects in Saudi Arabia 2024.pdfTop 10 Oil and Gas Projects in Saudi Arabia 2024.pdf
Top 10 Oil and Gas Projects in Saudi Arabia 2024.pdf
Teleport Manpower Consultant
 
weather web application report.pdf
weather web application report.pdfweather web application report.pdf
weather web application report.pdf
Pratik Pawar
 
Gen AI Study Jams _ For the GDSC Leads in India.pdf
Gen AI Study Jams _ For the GDSC Leads in India.pdfGen AI Study Jams _ For the GDSC Leads in India.pdf
Gen AI Study Jams _ For the GDSC Leads in India.pdf
gdsczhcet
 

Recently uploaded (20)

DESIGN A COTTON SEED SEPARATION MACHINE.docx
DESIGN A COTTON SEED SEPARATION MACHINE.docxDESIGN A COTTON SEED SEPARATION MACHINE.docx
DESIGN A COTTON SEED SEPARATION MACHINE.docx
 
Courier management system project report.pdf
Courier management system project report.pdfCourier management system project report.pdf
Courier management system project report.pdf
 
Sachpazis:Terzaghi Bearing Capacity Estimation in simple terms with Calculati...
Sachpazis:Terzaghi Bearing Capacity Estimation in simple terms with Calculati...Sachpazis:Terzaghi Bearing Capacity Estimation in simple terms with Calculati...
Sachpazis:Terzaghi Bearing Capacity Estimation in simple terms with Calculati...
 
LIGA(E)11111111111111111111111111111111111111111.ppt
LIGA(E)11111111111111111111111111111111111111111.pptLIGA(E)11111111111111111111111111111111111111111.ppt
LIGA(E)11111111111111111111111111111111111111111.ppt
 
Vaccine management system project report documentation..pdf
Vaccine management system project report documentation..pdfVaccine management system project report documentation..pdf
Vaccine management system project report documentation..pdf
 
WATER CRISIS and its solutions-pptx 1234
WATER CRISIS and its solutions-pptx 1234WATER CRISIS and its solutions-pptx 1234
WATER CRISIS and its solutions-pptx 1234
 
Architectural Portfolio Sean Lockwood
Architectural Portfolio Sean LockwoodArchitectural Portfolio Sean Lockwood
Architectural Portfolio Sean Lockwood
 
在线办理(ANU毕业证书)澳洲国立大学毕业证录取通知书一模一样
在线办理(ANU毕业证书)澳洲国立大学毕业证录取通知书一模一样在线办理(ANU毕业证书)澳洲国立大学毕业证录取通知书一模一样
在线办理(ANU毕业证书)澳洲国立大学毕业证录取通知书一模一样
 
一比一原版(SFU毕业证)西蒙菲莎大学毕业证成绩单如何办理
一比一原版(SFU毕业证)西蒙菲莎大学毕业证成绩单如何办理一比一原版(SFU毕业证)西蒙菲莎大学毕业证成绩单如何办理
一比一原版(SFU毕业证)西蒙菲莎大学毕业证成绩单如何办理
 
Pile Foundation by Venkatesh Taduvai (Sub Geotechnical Engineering II)-conver...
Pile Foundation by Venkatesh Taduvai (Sub Geotechnical Engineering II)-conver...Pile Foundation by Venkatesh Taduvai (Sub Geotechnical Engineering II)-conver...
Pile Foundation by Venkatesh Taduvai (Sub Geotechnical Engineering II)-conver...
 
power quality voltage fluctuation UNIT - I.pptx
power quality voltage fluctuation UNIT - I.pptxpower quality voltage fluctuation UNIT - I.pptx
power quality voltage fluctuation UNIT - I.pptx
 
Immunizing Image Classifiers Against Localized Adversary Attacks
Immunizing Image Classifiers Against Localized Adversary AttacksImmunizing Image Classifiers Against Localized Adversary Attacks
Immunizing Image Classifiers Against Localized Adversary Attacks
 
ethical hacking in wireless-hacking1.ppt
ethical hacking in wireless-hacking1.pptethical hacking in wireless-hacking1.ppt
ethical hacking in wireless-hacking1.ppt
 
Halogenation process of chemical process industries
Halogenation process of chemical process industriesHalogenation process of chemical process industries
Halogenation process of chemical process industries
 
Nuclear Power Economics and Structuring 2024
Nuclear Power Economics and Structuring 2024Nuclear Power Economics and Structuring 2024
Nuclear Power Economics and Structuring 2024
 
Planning Of Procurement o different goods and services
Planning Of Procurement o different goods and servicesPlanning Of Procurement o different goods and services
Planning Of Procurement o different goods and services
 
Quality defects in TMT Bars, Possible causes and Potential Solutions.
Quality defects in TMT Bars, Possible causes and Potential Solutions.Quality defects in TMT Bars, Possible causes and Potential Solutions.
Quality defects in TMT Bars, Possible causes and Potential Solutions.
 
Top 10 Oil and Gas Projects in Saudi Arabia 2024.pdf
Top 10 Oil and Gas Projects in Saudi Arabia 2024.pdfTop 10 Oil and Gas Projects in Saudi Arabia 2024.pdf
Top 10 Oil and Gas Projects in Saudi Arabia 2024.pdf
 
weather web application report.pdf
weather web application report.pdfweather web application report.pdf
weather web application report.pdf
 
Gen AI Study Jams _ For the GDSC Leads in India.pdf
Gen AI Study Jams _ For the GDSC Leads in India.pdfGen AI Study Jams _ For the GDSC Leads in India.pdf
Gen AI Study Jams _ For the GDSC Leads in India.pdf
 

BS 7671 - 18th Edition Widescreen PP Rev 4

  • 1. BS 7671: Requirements for Electrical Installations The IET and the Proposed changes What we know so far… By Paul Meenan
  • 2. PAUL MEENAN • So why are you here? • Who are The Institute of Engineering and Technology (IET)? • History of BS 7671 • What are the wiring regulations to me? • What are the duties under law? • 18th Edition Draft for Public Comment (DPC), What do we know so far? • Impacts of changes; Industry and the Client perspective! • Next Steps! Topics to Consider
  • 3. PAUL MEENAN • You are a duty holder and because ‘The ‘Wiring Regulations’, also known as British Standard 7671 are being updated. • As Duty Holders / Electricians etc. You want to discover how this ‘may’ impact your staff and the wider business. • What as a business and individuals we need to do to prepare. Why are you here?
  • 4. • Originally called the Institute of Electrical Engineers (IEE) formed in 1871. • Then in 2006 the IEE merged with the Institute of Incorporated Engineers (IIE). • This formed the Institution of Engineering and Technology (IET). • The IET represents the engineering profession in matters of public concern and assists governments to make the public aware of engineering and technological issues. • It provides advice on all areas of engineering, regularly advising Parliament and other agencies. Who are the IET?
  • 5. • The Wiring Regulations were first issued in 1882 by the Society of Telegraph Engineers and of Electricians. • Consisting of four pages and 21 regulations entitled - ‘Rules and Regulations for the Prevention of Fire Risks Arising from Electric Lighting’; this is now referred to as the ‘first edition’. History of BS 7671
  • 6. • The first edition had requirements' for; • Isolation, Regulation 7 • Mechanical protection and labelling, Regulation 17 • Periodic Inspection and Testing (now called EICR) History of BS 7671
  • 7. • The ‘rules’ document was updated many times until the 8th edition came out in 1924 where it was reprinted with the title ‘Regulations for the Electrical Equipment of Buildings’. • It kept the name until 1981 when the ‘Fifteenth Edition’ was printed where it became known as the ‘Requirements for Electrical Installations’. • The ‘regs’, as they are known in the trade were again amended on numerous occasions until in 1991 they were re- issued again under the title, ‘Requirements for Electrical Installations’ ~ IEE Wiring Regulations 16th Edition. • In 1992 they gained the status of a British Standard and became know as BS 7671. • They were amended three times, after which they were re-issued as BS 7671: 2001, after this two more amendments (AMD) followed. History of BS 7671
  • 8. • There is a new edition out in 1st July 2018, This is to be called, ‘BS 7671: 2018 Requirements for Electrical Installations’ ~ IET Wiring Regulations Eighteenth Edition’ • Since the 15th edition the ‘regs’ have always been republished in a sequence of colour bound books; Red, Green, Yellow, Blue, Brown. History of BS 7671 1991 1994 1997 2001 2011 2015 2004 2008 2018
  • 9. PAUL MEENAN • They are defined as a Code of Practice, even though they are called ‘Regulations’ and are deemed a non-statutory standard published by the BSi, they are used in the UK and across the world. • The standard relates to design, selection and errection; and inspection and testing of electrical systems regardless of whether the system is permanent or temporary. • The regulations are the national standard used for electrical installations across the UK on voltages up to 1000V a.c. or 1500V d.c. • Even though they are non-statutory, the have been referred to in extensive HSE/HSC guidance notes and the Electricity Safety, Quality and Continuity Regulations 2002 used by the electricity supply industry. • You can be prosecuted for failure to comply under the Health and safety at work act section 17! It is universally accepted that compliance with the document and its ‘requirements’ will enable you to comply with the Electricity at Work Regulations 1989. What are theWiring Regulations to me?
  • 10. What are duties under law? • Legislation in layers! • EAWR 1989, CDM 2015 • HSG Notes, memorandum on EAWR • BS standards (7671) • IET Guidance Notes 1-8
  • 11. PAUL MEENAN What are duties under law? • In 1974 the Health and safety at Work Act etc. was published. This imposes duties on employers and employees (Inc. self employed). “It shall be the duty of every employer to ensure, so far as is reasonably practicable, the health, safety and welfare at work of all his employees” • On April 1st 1990 The Electricity at Work Regulations 1989 were published. This imposed a duty on people or ‘duty holders’, in respects of work activities on or near, systems, electrical equipment and conductors.
  • 12. PAUL MEENAN Electricity at Work Regulations 1989 “ If a requirement of the regulation is ‘absolute’, for example if the requirement is not qualified by the words so far as is reasonably practicable, the requirement must be met regardless of cost or any other consideration”. Hence the use of the word shall!.... What are duties under law? So what regulations are an absolute...? • 4 Systems, activities and protective equipment • 5 Strength and capability of electrical equipment • 8 Earthing • 9 Integrity of conductors • 10 Connections • 11 Means of Protecting from Excess Current • 12 Means of cutting off the supply for isolation • 13 Precautions for work on equipment made dead • 14 Working on or near live conductors • 15 Work space access and lighting • 16 Person to be Competent to undertake works
  • 13. PAUL MEENAN EAWR – Regulation 29 • In any proceedings for an offence consisting of a contravention of regulations 4, 5, 8, 9, 10, 11, 12, 13, 14, 15, 16, it shall be a defence for any person to prove that he took all reasonable steps and exercised all due diligence to avoid the commission of that offence. Also review • The Engineering Council, Competence Criteria E5 for professional registered engineers! What are duties under law? In most cases, designers/electricians/engineers are employed to take all reasonable steps!
  • 14. PAUL MEENAN What we know so far! • The UK National Committee responsible for the Wiring Regulations is known as JPEL 64 • CENELEC harmonisation mandates this committee to review and update BS 7671 accordingly to ensure alignment with the HD 60364 which is the EU version of IEC 60364. • HD = Harmonised Documents J Joint P Power EL Electrical 64 IEC designation for committees dealing with low voltage electrical installations
  • 15. • Four panels inform the JPEL/64 board, who are the decision-making committee of BS 7671: Panel A – Covers verification and inspection and testing (Part 6 and Appendix 6 of BS 7671) plus any work relating to Parts 1, 2 and 3 of BS 7671. Panel B – Covers cable sizing and installation and related matters (some of Parts 4 and 5, Appendices 3 and 4 and some Part 7 items of BS 7671). Panel C – Covers earthing installations and related matters (some of Parts 4 and 5 and some Part 7 items of BS 7671). Panel D – Covers the remainder of Parts 4 and 5, some Part 7 items (and some Appendices of BS 7671). What we know so far!
  • 16. PAUL MEENAN What we know so far! Will Brexit effect the new version of the Regulations?
  • 17. NO! • CENELEC is a European organisation which has a membership of 33 European states. • This is more than just the EU States and they all contribute to the CENELEC Standards. • The consequences of Britain leaving the EU will not affect the UK membership of CENELEC, subject to change! We Hope! • While it is correct that the 18th Edition was being written and amended before the UK left the European Union there is no significant indication at present that Brexit will change the publication dates of the 18th Edition for July 2018 or the content of the new document. What we know so far!
  • 18. 18th Edition Draft for Public Comment The Proposed changes
  • 19. PAUL MEENAN What we know so far 18th Edition 8 Chapters 886 Pages New Definitions New Regulations 17TH Edition 7 Chapters 496 Pages
  • 20. PAUL MEENAN What we know so far! Chapter 1 – Scope, Objectives and Fundamental Principles • The use of the lower case a.c. & d.c. • Now capitalised ‘AC & DC’ throughout the entire document!
  • 21. PAUL MEENAN What we know so far! Chapter 1 – Scope, Objectives and Fundamental Principles • Regulation 133.1.3 has been added to. • Where equipment is not in accordance with Regulation 133.1.1 or is used outside the scope of its standard, the designer or other person responsible for specifying the installation shall conform that the equipment provides at least the same degree of safety as that afforded by compliance with the Regulations. Such use is to be noted on the Electrical Installation Certificate specified in part 6.
  • 22. PAUL MEENAN What we know so far! Chapter 1 – Scope, Objectives and Fundamental Principles • Regulation 110.11 - The long list of areas in scope now includes onshore units for navigation vessels within scope. • Regulation 120.3 – The list of chapters within the book now includes first reference to a possible chapter 8 on energy efficiency
  • 23. PAUL MEENAN What we know so far! Chapter 2 – Expanded and Modified Definitions • Combined Short Circuit Current Capability – Maximum short circuit current which can be handled by two short circuit protective devices in series. Combined short circuit protection. • Overcurrent Co-ordination – In short circuit conditions, of two OCPDs in series, resulting in a combined short circuit current capability higher than one OCPD alone. • Discrimination, replaced by Selectivity – Co-ordination of the operating characteristics' of two or more protective devices such that, on the incidence of overcurrents’ or residual currents within stated limits, the device intended to operate within these limits does so, while the other(s) does (do) not.
  • 24. PAUL MEENAN What we know so far! Chapter 2 – Expanded and Modified Definitions • Foundation Earth Electrode – ‘Conductive part buried in the soil under a building foundation or, preferably embedded in concrete of a building foundation, generally in the form of a closed loop’. • Non Compliance – A non conformity that may give rise to danger. • Bonding Conductor – ‘a protective conductor providing equipotential bonding’. Now ‘a protective conductor providing equipotential bonding for the purpose of equalising potential differences of exposed and extraneous conductive parts’.
  • 25. PAUL MEENAN What we know so far! Chapter 2 – Expanded and Modified Definitions • Departure – Deliberate decision to not fully comply with the requirements' of this standard, for which the designer must declare that the resultant degree of safety is not less than that achievable by full compliance’.
  • 27. PAUL MEENAN What we know so far! Chapter 4 – Protection against electric shock • Chapter 41 Lots of changes! • RCDs – Regulation 411.3.3 The regulations requires RCD protection on all socket outlets, risk assessment exemption is now deleted. • RCDs – New Regulation 411.3.4 requires in domestic premises additional protection by 30mA RCD for AC Final circuits supplying luminaires! • Regulation 411.3.2.2 The maximum disconnection time shown in Table 41.1 now applies to circuits up to 63A with one or more socket outlets and 32A for final circuits supplying fixed current using equipment. Used to be 32A • TN 0.4s • TT 0.2s
  • 28. PAUL MEENAN What we know so far! Chapter 4 – Protection against electric shock • Regulation 411.3.1.2 List metallic items that are to be equipotential bonded within an installation, however it now adds/states; ‘Metallic pipes entering the building having an insulating section at their point of entry need not be connected to the protective equipotential bonding’. SO NO BONDING WATER AND GAS PIPE IF INSULATED!
  • 29. • Chapter 42 New Technology! • A new regulation 421.1.7 – ARC fault protection devices (AFDD) conforming to BS EN 62606 may be used to provide additional protection against fire caused by arc faults in AC final circuits’ This was due to concerns around protection relating to fire caused by electrical equipment, RCDs cannot detect series or parallel arcing because these faults do not result in leakage current to earth. What we know so far! Chapter 4 – Protection against thermal effects
  • 30. • Arc Fault Detection is known around the world as; • AFD = Arc Fault Detection; • AFDD = Arc Fault Detection Device; • AFI = Arc Fault Interrupter; • They are marketed as a Fire prevention device. They are also seen as closing the gap in terms of electrical protection, and can be used in domestic and non- domestic installations. • Made to standard BS EN 62606:2013 What we know so far! What is Arc Fault Detection?
  • 31. What we know so far! What is Arc Fault Detection
  • 32. • AFDD monitor three types of scenarios that could result in fire. They are; 1. Parallel arc detection, insulation between cores and phases cause a short circuit to weak to be detected by a circuit breaker and with no earth leakage that would be picked up by an RCD! 2. Series arc detection, a damaged conductor or connection that causes part of the current to pass into its carbonized insulation due to temperature rise. 3. Overheating of electronic components in loads, when exposed to over voltage for several seconds. What we know so far! What is Arc Fault Detection?
  • 33. PAUL MEENAN What we know so far!
  • 34. PAUL MEENAN What we know so far!
  • 35. PAUL MEENAN What we know so far! Protection against overvoltages: will be changed fairly radically. Clause 443 • Both IEC and CENELEC have published updates concerning overvoltage. It is also apparent that protection against transient overvoltage will be significantly changed in BS7671. • AQ Criteria of App 5 is no longer needed (conditions of external influence for lightning) • Protection would have to be provided where the consequences affect human life, public services and commercial &/or industrial activity. • Risk assessment will need to be made as to whether protection is required having considered the potential human and commercial consequences of no protection.
  • 36. PAUL MEENAN What we know so far! Chapter 5 – Selection and Erection • 17th edition Amd 3 introduced, Regulation 521.11 – ‘wiring in escape routes shall be supported such that they will not be liable to collapse in the event of fire’ • This is now replaced by a new regulation 521.10.202 - Wiring systems shall be supported such that they will not be liable to premature collapse in the event of a fire. • This is huge change and applies throughout the install not just escape routes.
  • 37. PAUL MEENAN What we know so far! Chapter 5 – Selection and Erection • Bad Practice! • Avoid please!
  • 38. PAUL MEENAN What we know so far! Chapter 5 – Selection and Erection • Chapter 53 Protection, isolation, switching, control and monitoring, this has been extensively rewritten. Not a worry it brings back old parts once removed. • 531.3.2 – Unwanted Tripping; requires designer to limit amount of downstream current to not more than 30% of the RCD rating! It asks us to subdivide circuits to eliminate or avoid nuisance tripping. • 30mA = 9mA • 100mA = 30mA • 300mA = 90mA
  • 39. PAUL MEENAN What we know so far! Chapter 5 – Selection and Erection • Chapter 54 Earthing arrangements. MAJOR CHANGE! • Regulation 542.1.201 states. ‘ The main earthing terminal shall be connected with earth by one of the methods described in regulations 542.1 to 3. • It then adds… Additionally, there shall be an earth electrode, supplementing any earth facility provided by the distributor, in accordance with requirements of regulation 542.2.3, to prevent the appearance of dangerous step and touch voltage in the event of the loss of the main connection to earth.
  • 40. PAUL MEENAN What we know so far! Chapter 5 – Selection and Erection • So, a 100A TN-S supply has a maximum allowed Ze of 0.8Ω 230V = 2.3Ω 100A • So any earth rods would need to be 2.3Ω or below to enable supply fuse disconnection.
  • 41. PAUL MEENAN What we know so far! Chapter 6 – Inspection and Testing • Completely restructured to allow for CENELEC harmonisation! • Chapters 61, 62, 63 have been deleted! • Content of those chapters have been transferred into Chapters 64 and 65 • 64 - Initial Verification, 65 - Periodic Inspection and Testing. • Regulation 641.5 For an addition or alteration to an existing installation, it shall be verified that the addition or alteration complies with the regulations and does not impair the safety of the existing installation. This links to 132.16! • New requirement for polarity checks at origin of installation before energisation required.
  • 42. PAUL MEENAN What we know so far! Chapter 6 – Inspection and Testing • Regulation 612.6 (17th edition) used to cover requirements for polarity testing, • Regulation 643.6 add to this and states, Where relevant, the polarity of the supply at the origin of the installation shall be verified before the installation is energised. Where single pole switching devices are not permitted in the neutral conductor, a test shall be made to verify that all such devices are connected in the line conductor(s) only. During the polarity test, it should be verified that:
  • 43. PAUL MEENAN What we know so far! Chapter 6 – Inspection and Testing • New Regulations? • 653.1 Upon completion of the periodic inspection and testing of an existing installation, an electrical installation condition report shall be provided. • 653.2 The report shall include the following: • Details of those parts of the installation that have been inspected; • Any limitations of the inspection and testing; • Any damage, deterioration, defects or dangerous conditions; • Schedules of inspection; • Schedules of results of the appropriate test detailed in 643 • 653.3 The reports shall contain a recommendation for the interval until the next periodic inspection. • 653.5 The report shall be compiled and signed or otherwise authenticated by one or more skilled persons. • 653.6 The report shall be given by a skilled person responsible for carrying out the inspection and testing, or a skilled person authorised to act on their behalf, to the person ordering the inspection and testing.
  • 44. PAUL MEENAN What we know so far! Chapter 6 – Enhanced Minor works form
  • 46. PAUL MEENAN What we know so far!
  • 47. PAUL MEENAN What we know so far! Chapter 7 – Special Locations Section 753 Electrical Embedded heating • Section 753 will be extended to include embedded electrical heating systems for surface heating, and will include de-icing and frost prevention systems. • Revisions will include regulations relating to the protection against the effects of overheating caused by electrical short-circuits in embedded units and relating to harmful influence between the heating system and other electrical and non- electrical installations.
  • 48. PAUL MEENAN What we know so far! NEW CHAPTER 8 Energy efficiency • This will form Section 8 of the Regulations – there are currently 7 sections
  • 49. NEW CHAPTER! Energy efficiency • The brand new section will also be covering various topics, such as: electric vehicles, smart metering, lighting, cable losses (loss of energy through cable), transformer losses (loss of energy through the transformer) and power-factor correction (how efficient the power generated is being converted into useful energy) • It will also cover how installations will be awarded points for their “energy efficiency performance levels”. The points are added up along with points for “efficiency measures”, which the installer can then give the electrical installation an overall efficiency class (EIEC0 to EIEC4). PAUL MEENAN What we know so far!
  • 50. PAUL MEENAN What we know so far! NEW CHAPTER! New Terminology • Active electrical energy efficiency measures – measures for the optimisation of electrical energy produced, supplied, flowing and consumed by an electrical installation for the best permanent functionally equivalent service. • Distribution system design. Design of cables and associated electrical equipment for the distribution of electrical energy. • Current using equipment – electrical equipment intended to convert electrical energy into another form of energy, for example light, heat mechanical energy.
  • 51. PAUL MEENAN What we know so far! NEW CHAPTER 8 Energy efficiency • Recent surveys have branded this section not required nor wanted from the trade. • Some think its…. • Fact is the regulations are about safety and not energy efficiency.
  • 52. Final Thoughts, an Impact Assessment
  • 53. PAUL MEENAN Impact of Changes, Positive and negative Ask yourself… what is a safe installation anymore! • So now have to think to yourself; how does the changes effect me, my business? • Ask yourself, why have the BSi and IET made the commenting system so difficult, when it was more simple before! It is also less accessible by anyone who is not IT savvy! • Who benefits from the changes proposed? • Who has the time to read this, and then cross check between new and current editions to understand the changes/Impacts before August deadline! Do clients, contractors? • Does my installation now not comply? And does this mean I am in breach of the Electricity at Work Regulations 1989….One would suggest NO! • The next two slides are items you may wish to use to stimulate conversations' in your business.
  • 54. PAUL MEENAN Impact of Changes, Positive and negative Clients / Industry / Electricians / Manufacturers • Costs for re-training; - individuals, employers, client cost impacts. • Costs for new books will be? More no doubt.. plus 9 guidance notes? Who pays • New standard must be reviewed against ISO 55000 standard as to impact on bringing current asset portfolio into compliance. • All installations ‘may’ fail EICRs! Insurers may demand compliance at client costs! • Revise specifications to define departures from whole sections of the standard? • Should we seek to attain compliance with past standards, BS 7671 16th or 17th edition?
  • 55. PAUL MEENAN Impact of Changes, Positive and negative Clients / Industry / Electricians / Manufacturers • Should we seek to attain compliance with past standards, BS 7671 16th or 17th edition? • New (possible sub-standard) products and points of failure being introduced. • Manufacturers and governing bodies reputations’ could be being branded as self perpetuating their own economy! Most committees are sat on by manufacturers. • Designer has cart blanche to make decisions based on supply chain need and not clients • Could have huge impact to Business Operations • Huge confusion in supply chain as to CDM application as to design liability of roles!
  • 56. PAUL MEENAN Impact of Changes, positive and negative • Seen to show lack of strong fundamental principles and being led by a lower standard, EU driven mandate. • BREXIT is also a mind-set! Users will push back post Brexit surely. • Railways/Social Housing/Sectors will have to update standards, specifications and guidance notes, who pays for that? • Can be manipulated by suppliers, exemptions not checked, client may want full compliance, designer may not have time! • The current regulations are being breached by a weakened industry which is suffering with competence issues, what makes these regs any better? • How will these make the individuals better, hence improving the problem being seen across the entire industry..
  • 57. PAUL MEENAN Impact of Changes, positive and negative • Seen as sole opportunity to sell new products. • Opportunity to import cheap products. • Manufactures' can mark up new technology to cover cost of compliance testing. • Industry will leave a huge gap between those trained on first principles! • Possible rejection of the IET and Voluntary Regulatory bodies. Creation of unregulated silos! • Cause change fatigue across the industry! • Reputational damage as new books will cost more!
  • 58. PAUL MEENAN So what Next • Well lets hope the governing bodies are flat out trying to help all in the industry understand and summarise the impacts so we may have a fair time to freely comment! • Lets also hope all comments offered online are public for all to see and not censored nor ignored. • Look at your own businesses, finances and determine for yourself the impact..
  • 59. 18th Edition IET Wiring Regulations PAUL MEENAN Questions? Paul Meenan CEng FIET MIAM MILP PCQI paulmeenan@me.com #E5

Editor's Notes

  1. The Institution of Engineering and Technology (IET) is the largest multidisciplinary professional engineering institution in the world. The IET was formed in 2006 from two separate institutions: the Institution of Electrical Engineers (IEE), dating back to 1871,[1] and the Institution of Incorporated Engineers (IIE) dating back to 1884. Its worldwide membership is currently in excess of 167,000. The IET's main offices are in Savoy Placein London, England and at Michael Faraday House in Stevenage, England. The IET has the authority to establish professional registration for the titles of Chartered Engineer, Incorporated Engineer, Engineering Technician, and ICT Technician, as a Licensed Member institution of the Engineering Council. The IET is registered as a charity in England and Wales, and in Scotland.
  2. So above is the original wiring regs, first principles defined!
  3. Since it became a BS standard in 1991, now 9 reissues over 27 years, so a new version every 3 years on average!
  4. Since it became a BS standard in 1991, now 9 reissues over 27 years, so a new version every 3 years on average!
  5. So non- statutory. However be careful, every section or regulation is designed to underpin a section of the EAWR which in turn is compliance with HASAWA 1974. A failure on the part of any person to observe any provision of an approved code of practice shall not of itself render him liable to any civil or criminal proceedings; but where in any criminal proceedings a party is alleged to have committed an offence by reason of a contravention of any requirement for which there was an approved code of practice at the time of the alleged contravention, the following subsection shall have effect with respect to that code in relation to those proceedings. (2) Any provision of the code of practice which appears to the court to be relevant to the requirement alleged to have been contravened shall be admissible in evidence in the proceedings; and if it is proved that there was at any material time a failure to observe any provision of the code which appears to the court to be relevant to any matter which it is necessary for the prosecution to prove in order to establish a contravention of that requirement or prohibition, that matter shall be taken as proved unless the court is satisfied that the requirement was in respect of that matter complied with otherwise than by way of observance of that provision of the code.
  6. Two key pieces of legislation we follow amongst others are shown here, the first an act of parliament the second a set of regulations under that act.
  7. Two key pieces of legislation we follow amongst others are shown here, the first an act of parliament the second a set of regulations under that act.
  8. Page 2 observes the committee names. HD 60364 is the EU implementation of IEC 60364 which is a higher level international document which feeds into for example the Aus/NZ wiring standards also. As the UK is a member of the IEC and ISO, any standards that are issued by them we are duty bound to implement, it’s just because we are CENELEC also, we implement the CENELEC versions.
  9. Page 8 observes the committee names.
  10. HD 60364 is the EU implementation of IEC 60364 which is a higher level international document which feeds into for example the Aus/NZ wiring standards also. As the UK is a member of the IEC and ISO, any standards that are issued by them we are duty bound to implement, it’s just because we are CENELEC also, we implement the CENELEC versions.
  11. This is likely to cost a fortune, another cost increase to end users!
  12. People may be confused and run bonds to all exposed metal works!
  13. Chapter 3 nothing of great merit!
  14. Chapter 41
  15. Foundation earthing strongly recommended also
  16. Chapter 42
  17. Chapter 42
  18. Chapter 42
  19. Chapter 42
  20. Chapter 42
  21. So single to double, double to triple!! FFS! Possibly!!!!!!!!!!!!!!!
  22. Human life (hospitals and medical facilities, safety services) Public Services and Cultural Heritage (loss of public services, IT centres and museums) Commercial or industrial activity (farms, industries, hotels, banks, etc)
  23. Chapter 52
  24. Chapter 52
  25. Designer must understand usage of circuits! More bigger boards!
  26. MAJOR CHANGE! So we are doing the DNOs job for them in case of loss of PEN conductor. this reg is just there so that the DNO can allow their network to deteriorate more, thus make more profit, and thus ship this profit to their parent companies outside the UK, at the detriment of the UK economy, the UK public purse, and UK consumers who all lose out because of the profit re-allocation, and, the impact on individual consumers and the public purse do to the implications of this regulation. This reg, is simply there to allow the DNO’s to ignore their statute law duty under esqcr, and therefore make more profit at the detriment of the UK as a whole. Also, it means that HSE don’t have to do anything to police them.
  27. MAJOR CHANGE! So we are doing the DNOs job for them in case of loss of PEN conductor
  28. 641.5 is not new, was 610.4 in amd 3 17th edition; but it is important to highlight!!!
  29. 641.5 is not new, was 610.4 in Amd 3 17th edition; but it is important to highlight!!!
  30. 641.5 is not new, was 610.4 in Amd 3 17th edition; but it is important to highlight!!!
  31. 641.5 is not new, was 610.4 in Amd 3 17th edition; but it is important to highlight!!!
  32. So non- statutory. However be careful, every section or regulation is designed to underpin a section of the EAWR which in turn is compliance with HASAWA 1974. A failure on the part of any person to observe any provision of an approved code of practice shall not of itself render him liable to any civil or criminal proceedings; but where in any criminal proceedings a party is alleged to have committed an offence by reason of a contravention of any requirement for which there was an approved code of practice at the time of the alleged contravention, the following subsection shall have effect with respect to that code in relation to those proceedings. (2) Any provision of the code of practice which appears to the court to be relevant to the requirement alleged to have been contravened shall be admissible in evidence in the proceedings; and if it is proved that there was at any material time a failure to observe any provision of the code which appears to the court to be relevant to any matter which it is necessary for the prosecution to prove in order to establish a contravention of that requirement or prohibition, that matter shall be taken as proved unless the court is satisfied that the requirement was in respect of that matter complied with otherwise than by way of observance of that provision of the code.