AC High voltage Air Break Disconnector Switch Routine Test According to IEC 62271-102 Standard
Article 9(09.10.2018) direct link: https://lnkd.in/gX_aVqq
AC High voltage Air Break Disconnector Switch Routine Test According to IEC 62271-102 Standard
1. AC High voltage Air Break Disconnector Switch Routine
Test According to IEC 62271-102 Standard
2. Article 9(09.10.2018)
The function of air-break disconnectors in high voltage power systems is to provide
electrical and visible isolation of one part of the system. The isolation generally
takes two forms:
Isolation related to normal day-to-day operation of the power system. For
example, shunt reactors required only during light load periods are switched out
using circuit breakers and then isolated by disconnectors during peak load periods.
Isolation related to repair or maintenance on transmission lines or station
equipment such as transformers, circuit breakers and so on.
High voltage air-break disconnectors and earthing switch come in a variety of types
and mounting arrangements. The four most commonly used types are:
• Vertical break type
• Centre side break type
• Double side break type
3. The high voltage disconnector and earthing switch routine tests are for the
purpose of revealing faults in material or construction. They do not impair the
properties and reliability of a test object. The routine tests shall be made wherever
reasonably practicable at the manufacturer's works on each apparatus
manufactured, to ensure that the product is in accordance with the equipment on
which the type tests have been passed. By agreement, any routine test may be
made on site.
The following items are the routine testing items of high voltage disconnector
switch according to IEC 62271-1,IEC 62271-102 Standards:
1-Dielectric test on the main circuit:
A dry, short-duration power-frequency with 50 or 60 Hz voltage test
shall be applied.The test voltage shall be that specified in column 2 of
the following tables , according to the relevant IEC standards.In these
values, the altitude factor should be considered.
5. When the insulation of disconnector and earth switch is
provided only by solid-core insulators and air at ambient
pressure, the power-frequency voltage withstand test may be
omitted if the dimensions between the conductive parts –
between phases, across open switching devices and between
conductive parts and the frame – are checked by dimensional
measurements.
8. When dielectric test applied on earthing switches, the test voltage shall
be applied with the earthing switch in the open position in these
condition:
– between adjacent insulated terminals with the bases earthed.
– between all the insulated terminals connected together and the bases
earthed.
2-Dielectric test on auxiliary and control circuits in operating
mechanism:
A:Inspection of auxiliary and control circuits, and verification of conformity to the
circuit diagrams and wiring diagrams:
The nature of the materials, the quality of assembly, the finish and, if necessary,
the protective coatings against corrosion shall be checked. A visual inspection is
also necessary to check the satisfactory installation of the thermal insulation.The
conductors and cables and heaters(resistance check)shall be checked for proper
routing.
9. B:Functional tests:
A functional test of all low-voltage circuits(such relays , contactor,
interlocking magnet) shall be made to verify the proper functioning of
auxiliary and control circuits in conjunction with the other parts of the
disconnector switch . interlocking cassette must be checked.
C:Verification of protection against electrical shock:
Protection against direct contact with the main circuit and safe
accessibility to the auxiliary and control equipment parts liable to be
touched during normal operation shall be checked by visual inspection.
D:Dielectric tests:
Only power frequency tests shall be performed. The test voltage shall be
1 kV or 2 kV with a duration of 1 s with 50 or 60 HZ frequency.
10. 3-Measurement of the resistance of the main circuit:
For the routine test, the DC voltage drop or resistance of each pole of the main
circuit shall be measured under conditions as nearly as possible similar, with regard
to ambient air temperature and points of measurement, to those under which the
corresponding type test was made. The measured resistance shall not exceed 1,2 ×
Ru, where Ru is equal to the resistance measured before the temperature-rise test.
Contact
resistance
measurement
equipment
manufacture by
vanguard
instrument
company
11. 4-Design and visual checks:
The disconnector and earthing switches shall be checked to verify its
compliance with the purchase specification.
5-Mechanical operating tests:
Operating tests are made to ensure that the disconnectors or earthing
switches show the specified operating behavior within the specified
voltage and supply pressure limits of their operating mechanisms.
During these tests, which are performed without voltage on, or current
flowing through the main circuit, it shall be verified that the
disconnectors or earthing switches open and close correctly when their
operating mechanisms are energized.
12. This item also must be check:
*angle of operating mechanism out put shaft.
*measuring torque of operating mechanism output.
*operating mechanism motor current.
*operating times.
– 10 close-open operating cycles at the minimum(85%)supply voltage.
– 10 close-open operating cycles at the maximum (110%)supply
voltage.
–50 close-open operating cycles at the nominal (100%)supply voltage.
During these operating cycles the operating characteristics such as operating
time and maximum energy consumption shall be recorded or evaluated. With
disconnectors having manual mechanisms only, the maximum forces shall be
recorded. Satisfactory operation of the auxiliary contacts and position
indicating devices (if any) shall be verified.
13. After these tests, no parts of the disconnector or earthing switch shall
be damaged. For disconnectors and earthing switches with a rated
voltage of 52 kV and above, the mechanical operating routine tests may
be performed on sub-assemblies.
The main circuit resistance shall be measured before and after the
mechanical endurance test. The resistance shall not vary by more than
20 % from the value measured before the test.
14. References:
* International Standard :IEC 62271-1 High-voltage switchgear and
controlgear
Part 1: Common specifications .
* International Standard :IEC 62271-102 High-voltage switchgear and
controlgear –
Part 102: Alternating current disconnectors and earthing switches.
* Current interruption using high voltage air-break disconnectors
Article by Peelo, D.F. hindhoven: Technische Universiteit Eindhoven
* High Volt Company catalogue.
*vanguard instruments company(doble) catalogue.
*Alpha Elektrotechnik AG Company disconnector switch catalogue.