1. HIGH POTENTIAL TEST
General:
The high potential test (applied voltage test) is used to detect weak spots in the insulation of stator
windings, or rotor windings (wound rotor windings, field windings) and of some machine components
(e.g. bearing insulation).
Introduction
During the service-life-time of machines a degradation of the dielectric strength of the insulation
cannot be excluded. To minimize unexpected forced outages, the high-potential test is used: weak
spots in the insulation will lead to a voltage-break-down during this test; now the insulation at these
spots of failure can be reinforced and can be tested again. Doing this gives some certainty that the
insulation under test will withstand the normal operation voltage during the following operation period
till the next scheduled inspection.
The High-Potential Test
The high-potential test preferable is done by applying an AC voltage of normal frequency to the
winding under test; the advantage of AC is given by the fact that all dielectric stresses in the
insulation correspond to the stresses under normal operating conditions (exception: field winding;
use a DC voltage in this case).
Although AC voltage is preferable, sometimes the application of AC is inconvenient (particularly in
cases where an appropriate regulator step-up-transformer is not available) and thus a DC source is
used. To ensure equivalent stresses, the AC and DC test voltages correlate as follows:
VDC = 1.6 x VAC r.m.s
(Note: Sometimes an equivalence factor of 1.7 is used, according to national specifications)
The AC test voltage used normally for newly fabricated armature windings (stator windings) is given
by
VAC r.m.s = 2 VL + 1 kV
Where VL = nominal line-to-line operating voltage. The test voltage has to be reduced for the
application to old windings; the reduction factor normally is
0.75
For old and/or partially refreshed windings (in such cases the test voltage often simplified is laid
down to be 1.5 VL ) and is
0.80
for renewed windings or in case of a repeated high-potential test on a new winding.
The application of the test voltage has to be done according to the relevant standards; Starting with
maximally 50%of the test level, the voltage has to be increased from 50% up to 100% within more
Page 1