End-of-life factors in high voltage gas insulated switchgear with SF6
or with non-SF6 gases
source: https://switchgearcontent.com
Photo from GE company SF6 free GIS product
In this article speak about brief overview of indicators for end-of-life of gas insulated
switchgear, and what has to be done when end-of-life is reached. Furthermore, options for
life extension of GIS with non SF6 gases and gas mixtures are discussed
Some parts of the GIS equipment are subject to ageing and deterioration mechanisms.
These ageing processes should be considered when determining future performance and
residual life of the equipment and should be targeted by condition monitoring programmes.
This section considers the following:
• Critical technical performance factors.
• How these factors might affect residual life.
• Diagnostic techniques that can help determine residual life.
There are two different indicators for end-of-life:
1- The specified end-of-life of the GIS is reached:
End-of-life factors in high voltage gas insulated switchgear with SF6
or with non-SF6 gases
source: https://switchgearcontent.com
End-of-life of GIS is either specified by the end user, reflecting the intended time until
replacement of the equipment should be done, or the end-of-life of GIS is specified by the
equipment manufacturer stating a minimum lifetime (which can be extended), or by an
increased failure rate indicating end-of life.
2-End-of-life of the insulation gas mixture is reached:
Non-SF6 gases or gas mixtures may age during lifetime e.g. due to decomposition and
reach an end-of-life stage. Here, a first indicator for end-of-life would be the gas lifetime
statement of the equipment manufacturer.
Exemplary life limiting factors in GIS equipments are listed as below:
1-Mechanical wear of circuit breakers:
The designed mechanical lifetime is usually defined by the permitted number of off-load
switching operations. It is limited by mechanical wear and/or fatigue life of highly stressed
parts The highest stressed parts of the circuit breaker are the energy storage system and
the mechanical chain between the energy storage element and the moving contacts. If
applicable, the impact of non-SF6 gases or gas mixtures on mechanical wear of different
circuit breaker designs (e.g. CO2-breaker, vacuum breaker) has to be discussed between the
end user and the equipment manufacturer.
The following diagnostic techniques may be helpful in assessing residual life:
Charging time
Contact timing
Static contact resistance
Travel records
Trip coil current
Vibration analysis
2-Electrical wear of circuit breakers:
The contact system has a limited capability to interrupt fault currents because of contact
erosion and nozzle ablation.
The wear of contacts caused by the arc during circuit-breaker switching operations may be
estimated by calculation. The physics of arc-induced contact wear is complex, but simplified
expressions have been derived that allow contact wear to be calculated with acceptable
End-of-life factors in high voltage gas insulated switchgear with SF6
or with non-SF6 gases
source: https://switchgearcontent.com
accuracy. The most commonly used methods assume the mass of contact material lost
during each operation to be proportional to the time integral of the arc current squared.
One of test method for measuring waer of circuit breakers is Dynamic (Contact) Resistance
Measurements (DRM).
In photo1 you can see DRM test curves:
Photo1: Dynamic (Contact) Resistance Measurements (DRM) curves in circuit
breaker
If applicable, the impact of non-SF6 gases or gas mixtures on electrical wear of different
circuit breaker design (e.g. CO2-breaker, vacuum breaker) has to be discussed between the
end user and the equipment manufacturer. If degradation of gases or gas mixtures during
switching is to be expected, the impact on lifetime of circuit breaker should be discussed as
well.
3-Deterioration of grading capacitors of circuit breakers:
Grading capacitors used in multi-break circuit breakers have been found to exhibit a
number of deterioration mechanisms, and in some cases mechanical
or electrical failure has occurred.
It has to be discussed between the end user and the equipment manufacturers if
deterioration of grading capacitors is a special issue for circuit breaker designs with non-
SF6 gases and gas mixtures.
Some deterioration mechanisms effecting GIS grading capacitors can be detected using
partial discharge techniques as described later. Other defects may only be detected by
End-of-life factors in high voltage gas insulated switchgear with SF6
or with non-SF6 gases
source: https://switchgearcontent.com
visual inspection.
4-High-speed earthing switches: For HV GIS, high speed earthing switches have the duty
to make rated short circuit currents for at least two times, and to switch rather small
induced currents. Thus, they are usually unlikely to be the life limiting factors of HV GIS
with SF6.
If application of non-SF6 gases and gas mixtures requires different high-speed earthing
switch design the impact on mechanical or electrical wear should be discussed between the
end user and the equipment manufacturer.
Besides visual inspection, resistance test, timing tests and travel curve measurement may
be useful for assessment of the device.
In photo2 we can see high speed earthing switch in GIS:
End-of-life factors in high voltage gas insulated switchgear with SF6
or with non-SF6 gases
source: https://switchgearcontent.com
Photo2: High speed earthing switch
End-of-life factors in high voltage gas insulated switchgear with SF6
or with non-SF6 gases
source: https://switchgearcontent.com
5-Disconnectors and (maintenance) earthing switches:
Disconnector and earthing switches mostly have no or small current making or breaking
capacity, and therefore have mainly a mechanical lifetime. Some disconnector/earthing
switches are fitted with arcing contacts and can make or break bus transfer currents, bus
charging currents or induced currents of transmission lines (earthing switches). For these
switching duties, electrical wear of arcing contacts can occur.
If additional gas ageing effects due to switching have to be considered, the impact on
lifetime should be discussed between the end users and the equipment manufacturer.
As in the case of circuit-breakers, an initial idea of mechanical wear of disconnectors and
earthing switches can be obtained from the operations counter and knowledge of the
mechanical endurance class of a device, while more specific indications may be obtained
using diagnostic techniques. Most frequently, the motor running times for ‘open’ and ‘close’
operations are measured. In some cases, the motor current and the contact resistance are
measured as well.
6-Current carrying components including contacts:
In SF6 GIS, as well as in non-SF6 GIS, if mechanical integrity is maintained,there is no
ageing mechanism affecting current carrying contacts.
The current carrying ability of the primary circuit can be tested by resistance measurement.
Since the resistance to be measured is of the order of micro Ohms, the measurement is
typically performed by passing a current of 100 A DC or higher through the primary circuit
and measuring the resulting voltage differences. The four wire method is used to prevent
the current supply leads and voltage probes from influencing the measurement. Commercial
micro Ohm meters that work on this principle are available.
The values obtained may be compared to those originally obtained during tests after
installation on site.
For GIS with SF6 gas: SF6 gas begins to decompose at high temperatures and the
techniques described below for monitoring decomposition products may reveal the presence
of a hot contact within a gas compartment. Additionally, once arcing and particulate debris
are present, the PD techniques described below may be able to detect and locate a
deteriorating contact.
End-of-life factors in high voltage gas insulated switchgear with SF6
or with non-SF6 gases
source: https://switchgearcontent.com
7-Gas quality :
A first indicator for end-of-life of non-SF6 gases and gas mixtures would be the gas lifetime
statement of the equipment manufacturer. A gas quality check (if possible) might indicate
that the equipment can be used longer, or that the gas has to be replaced if its end-of-life
condition is reached. As for SF6, this will require a replacement of the desiccants.
For GIS with SF6 gas :Gas can be tested for decomposition products on-site using chemical
reaction tubes
that change colour in the presence of certain reactive gases. Tubes sensitive to SO2 and to
HF are available. However, since HF reacts rapidly with metals to form metal fluorides, the
use of tubes sensitive to HF is not recommended. The tubes sensitive to SO2 are also
sensitive to SOF2.
A gas sample may also be sent off-site for laboratory analysis by gas chromatography or
infra red spectrography. Stainless steel cylinders with a volume of less than 1litre are
recommended for this purpose. This method provides a more accurate analysis but is more
expensive and the results are not immediately available.
In photo3 we can see an example SF6 gas purity and analyzer device:
End-of-life factors in high voltage gas insulated switchgear with SF6
or with non-SF6 gases
source: https://switchgearcontent.com
Photo3: SF6 gas purity and analyzer device
8- Particulate contamination of gas:
The insulating performance of a gas or gas mixture and of insulator surfaces may be
compromised if field-enhancing defects, such as particles, are present.
Particles may be generated by the wear of moving parts, such as conductor sliding contacts
and the contacts of switching devices. If particles can also be generated by other ways, e.g.
decomposition of non-SF6 gases or gas
mixtures, their impact on the insulation performance of GIS should be discussed between
the end user and the GIS manufacturer.
For GIS with SF6 gas: Defects such as small conducting particles generate partial
discharges, which are
End-of-life factors in high voltage gas insulated switchgear with SF6
or with non-SF6 gases
source: https://switchgearcontent.com
accompanied by electromagnetic transients and acoustic vibrations. Both of these have
formed the basis of sensitive methods that have been developed for detection, recognition
and location of defects.
Hampton and Meats developed a diagnostic technique that makes use of the
electromagnetic radiation in the UHF band generated by discharging defects. UHF signals
may be detected with comparatively simple, purpose built coupling devices installed within
the GIS. Where no such provision has been made it is sometimes possible
to detect signals using external sensors that can be applied at breaks in the conducting
enclosure, such as contact viewing windows, through which electromagnetic radiation can
pass.
9-Gas leakage:
Possible origins and causes of gas leakage in GIS include pipework connections, corrosion
at bolted flange enclosure joints (outdoor equipment), damaged or degraded seals or
bushings (insulators), adherence of dust, particulate or other foreign material to dynamic
seals, and porosity in enclosure castings or welds. These causes are rather general and
mainly independent from the gas being used inside the GIS.
For GIS with SF6 gas : Where a loss of gas from a compartment is identified, external
checks with leak detection methods may allow the source of the leak to be determined. by
the methods applicable to locating leaks in service, negative ion capture detectors and
electron capture detectors are stated to have sensitivities of 20 mg/a SF6 or 1 ppmv and 2
mg/a SF6 or 100 ppbv, respectively.
In photo 4 we can see Electron Capture Detector(ECD) Method For Sf6 Gas
End-of-life factors in high voltage gas insulated switchgear with SF6
or with non-SF6 gases
source: https://switchgearcontent.com
Photo 4: Electron Capture Detector
Gas leakages may become an important life limiting factor if the required leakage rates can
not be achieved. In the future the leakage rates may be defined by
environmental regulations.
In photo 5 we can see a SF6 gas detector device:
End-of-life factors in high voltage gas insulated switchgear with SF6
or with non-SF6 gases
source: https://switchgearcontent.com
Photo 5: SF6 gas leakage detector equipment
10-Filters:
Depending on the installed amount and filter type, filters themselves are usually not life-
limiting, but they are relevant for maintenance (to be replaced after opening of
compartments). Filters generally adsorb both humidity and decomposition products and
should be specified with respect to the type and amount of filter material needed for each
gas or gas mixture.
For GIS with SF6 gas:
An indication that the molecular sieve is becoming exhausted may be given by the gas
quality measurements.
Filters themselves are not a life limiting factor rather they are a maintenance issue.
11-Solid insulating parts (GIS internal parts):
With state-of-the-art manufacturing technology and quality control (no voids or metallic
inclusions), solid insulating parts are usually not subject to any ageing.
End-of-life factors in high voltage gas insulated switchgear with SF6
or with non-SF6 gases
source: https://switchgearcontent.com
If any contamination from the gas can be excluded, solid insulating parts may not be life-
limiting components of the GIS.
For GIS with sf6 gas:
The guide takes only GIS internal insulation into consideration. It does not apply to SF6-
Air and SF6-Oil bushings as the life limiting factor may well be on the non SF6-side.
In their work on the long term performance of SF6 insulated systems, Task Force observed
that partial discharge measurement may be able to detect voids in solid insulation, provided
sufficient sensitivity can be achieved and pulsed discharge activity occurs. The sensitivity
that can be normally achieved in on-site tests with UHF technique will allow critical voids to
be detected.
Evolution of PD intensity can be used as an indicator of ageing of epoxy impregnated paper
insulated air bushings or epoxy resin filled voltage transformers. If the observed level of PD
increases it is a sign that critical ageing is occurring.
12-Metallic enclosures:
Deterioration of flanges due to moisture ingress can be seen as a critical ageing mechanism,
which is independent of the gas or gas mixture inside the GIS. Hence, metallic enclosures
may be life-limiting components.
For GIS with sf6 gas:
Signs of corrosion and moisture ingress at the enclosure flanges, particularly for outdoor
compartments, can be obtained by visual inspection. The condition of any protective coating
may similarly be checked. SF6 leakage may be an indication of flange corrosion.
13- Gas seals:
The material used for the sealing function must be able to provide sufficient gas tightness
over the lifetime under application conditions. Main factors causing ageing are the material
used, temperature, UV radiation, exposure to oxygen and their combination. If only
materials are applied which are qualified for every gas or gas mixture, seals may not be life-
limiting components.
For GIS with SF6 gas:
End-of-life factors in high voltage gas insulated switchgear with SF6
or with non-SF6 gases
source: https://switchgearcontent.com
The performance of gas seals can be monitored by SF6 leakage detection methods.
When any work requiring internal access to the GIS is performed, the opportunity should be
taken to establish the condition of the seals. The seals may be examined or analysed and
residual life estimations made. An investigation into the deterioration of O-rings sampled
from GIS and gas circuit-breakers aged 20 to 30 years has been reported.
In the investigation, compression set cs, as defined in the following equation, was used as
an indicator of degradation.
14-Pressure relief device:
Two main ageing mechanisms of pressure relief devices are corrosion (e.g. due to attack by
moisture) and/or fatigue (e.g. due to temperature cycles).
Both mechanisms are rather independent from the gas inside GIS.
There is no non-destructive method suitable to monitor / check the actual state of
the pressure relief devices in service. The visual inspection is useful, but it can check
the visible traces of the corrosion only. However monitoring gas leakage can identify
corrosion that is not visible. In case of any deterioration observed repair shall be considered
as soon as possible.
The ageing caused by fatigue can cause the decrease of the operating pressure of the
bursting disc. In case of any unintentional operation the rupture discs of the affected GIS
shall be tested. Several pieces shall be delivered to the laboratory of the manufacturer and
checked very thoroughly. If necessary all rupture discs shall be exchanged (this procedure
can be applied in other cases as well, if there is any suspicion of ageing).
The condition of the bursting disks will generally not be a life limiting factor. However it will
certainly be taken into account when considering whether to refurbish or replace the GIS.
If refurbishment of a GIS compartment is being undertaken for other reasons, it is
recommended that bursting disks of the graphite type will be replaced to ensure that target
life extension is achieved.

More Related Content

What's hot

27072013140225 gas-insulated-substations
27072013140225 gas-insulated-substations27072013140225 gas-insulated-substations
27072013140225 gas-insulated-substationsMugdha Jhanjhote
 
Gas insulated substation
Gas insulated substationGas insulated substation
Gas insulated substationAjay Kuriakose
 
Seminar on Gas Insulated Substation
Seminar on Gas Insulated SubstationSeminar on Gas Insulated Substation
Seminar on Gas Insulated SubstationSoumya Raj Poddar
 
Gas insulated substation
Gas insulated substationGas insulated substation
Gas insulated substationhimanshu kumar
 
Gas insulated substation
Gas insulated substationGas insulated substation
Gas insulated substationsharique_64
 
Gis substation
Gis substationGis substation
Gis substationAsif Eqbal
 
Vacuum Circuit Breakers Testing Methods
Vacuum Circuit Breakers Testing MethodsVacuum Circuit Breakers Testing Methods
Vacuum Circuit Breakers Testing MethodsAli Sepehri
 
FACULTY OF ENGINEERING & TECHNOLOGY , GURUKULA KANGARI UNIVERSITY ,HARIDWAR
FACULTY OF ENGINEERING & TECHNOLOGY , GURUKULA KANGARI UNIVERSITY ,HARIDWARFACULTY OF ENGINEERING & TECHNOLOGY , GURUKULA KANGARI UNIVERSITY ,HARIDWAR
FACULTY OF ENGINEERING & TECHNOLOGY , GURUKULA KANGARI UNIVERSITY ,HARIDWARashwini kumar
 
Gas insulated substation 1
Gas insulated substation 1Gas insulated substation 1
Gas insulated substation 1Ronal Parmar
 
Modern substation design
Modern substation designModern substation design
Modern substation designrajesh18001 R
 
Gas insulated sub station 3
Gas insulated sub station 3Gas insulated sub station 3
Gas insulated sub station 3Ronal Parmar
 
Gas insulated sub station 2
Gas insulated sub station 2Gas insulated sub station 2
Gas insulated sub station 2Ronal Parmar
 
AC Circuit Breakers Routine Tests according to IEC 62271-100
AC Circuit Breakers Routine Tests according to IEC 62271-100AC Circuit Breakers Routine Tests according to IEC 62271-100
AC Circuit Breakers Routine Tests according to IEC 62271-100Ali Sepehri
 
AC High voltage Air Break Disconnector Switch Routine Test According to IEC 6...
AC High voltage Air Break Disconnector Switch Routine Test According to IEC 6...AC High voltage Air Break Disconnector Switch Routine Test According to IEC 6...
AC High voltage Air Break Disconnector Switch Routine Test According to IEC 6...Ali Sepehri
 

What's hot (20)

27072013140225 gas-insulated-substations
27072013140225 gas-insulated-substations27072013140225 gas-insulated-substations
27072013140225 gas-insulated-substations
 
Gas insulated substation
Gas insulated substationGas insulated substation
Gas insulated substation
 
Seminar on Gas Insulated Substation
Seminar on Gas Insulated SubstationSeminar on Gas Insulated Substation
Seminar on Gas Insulated Substation
 
Gas insulated substation
Gas insulated substationGas insulated substation
Gas insulated substation
 
Gas insulated substation
Gas insulated substationGas insulated substation
Gas insulated substation
 
GIS 400kv substation
GIS  400kv substationGIS  400kv substation
GIS 400kv substation
 
Gis substation
Gis substationGis substation
Gis substation
 
Gas insulated substation.
Gas insulated substation.Gas insulated substation.
Gas insulated substation.
 
Gagan
GaganGagan
Gagan
 
GIS-NESCL-6
GIS-NESCL-6GIS-NESCL-6
GIS-NESCL-6
 
Deepak kumar
Deepak kumarDeepak kumar
Deepak kumar
 
Ppt
PptPpt
Ppt
 
Vacuum Circuit Breakers Testing Methods
Vacuum Circuit Breakers Testing MethodsVacuum Circuit Breakers Testing Methods
Vacuum Circuit Breakers Testing Methods
 
FACULTY OF ENGINEERING & TECHNOLOGY , GURUKULA KANGARI UNIVERSITY ,HARIDWAR
FACULTY OF ENGINEERING & TECHNOLOGY , GURUKULA KANGARI UNIVERSITY ,HARIDWARFACULTY OF ENGINEERING & TECHNOLOGY , GURUKULA KANGARI UNIVERSITY ,HARIDWAR
FACULTY OF ENGINEERING & TECHNOLOGY , GURUKULA KANGARI UNIVERSITY ,HARIDWAR
 
Gas insulated substation 1
Gas insulated substation 1Gas insulated substation 1
Gas insulated substation 1
 
Modern substation design
Modern substation designModern substation design
Modern substation design
 
Gas insulated sub station 3
Gas insulated sub station 3Gas insulated sub station 3
Gas insulated sub station 3
 
Gas insulated sub station 2
Gas insulated sub station 2Gas insulated sub station 2
Gas insulated sub station 2
 
AC Circuit Breakers Routine Tests according to IEC 62271-100
AC Circuit Breakers Routine Tests according to IEC 62271-100AC Circuit Breakers Routine Tests according to IEC 62271-100
AC Circuit Breakers Routine Tests according to IEC 62271-100
 
AC High voltage Air Break Disconnector Switch Routine Test According to IEC 6...
AC High voltage Air Break Disconnector Switch Routine Test According to IEC 6...AC High voltage Air Break Disconnector Switch Routine Test According to IEC 6...
AC High voltage Air Break Disconnector Switch Routine Test According to IEC 6...
 

Similar to End-of-life Factors in High Voltage GIS

substation 101
substation 101substation 101
substation 101danica11
 
Protection & switchgear
Protection & switchgear   Protection & switchgear
Protection & switchgear johny renoald
 
03 8 jun17 4apr 16176 chem by prod ijeecs(edit)
03 8 jun17 4apr 16176 chem by prod ijeecs(edit)03 8 jun17 4apr 16176 chem by prod ijeecs(edit)
03 8 jun17 4apr 16176 chem by prod ijeecs(edit)IAESIJEECS
 
Corrosion resistantalloysintheoilandgasindustryselectionguidelinesupdate 10073
Corrosion resistantalloysintheoilandgasindustryselectionguidelinesupdate 10073Corrosion resistantalloysintheoilandgasindustryselectionguidelinesupdate 10073
Corrosion resistantalloysintheoilandgasindustryselectionguidelinesupdate 10073Ratheesh manhacheri
 
Chapter 11 Introduction to Gas Insulation Substation (GIS).pptx
Chapter 11 Introduction to Gas Insulation Substation (GIS).pptxChapter 11 Introduction to Gas Insulation Substation (GIS).pptx
Chapter 11 Introduction to Gas Insulation Substation (GIS).pptxborapring
 
Proposal Technique for an Static Var Compensator
Proposal Technique for an Static Var CompensatorProposal Technique for an Static Var Compensator
Proposal Technique for an Static Var CompensatorIOSR Journals
 
Internship ppt(santhosh).pptx
Internship ppt(santhosh).pptxInternship ppt(santhosh).pptx
Internship ppt(santhosh).pptxBasavarajbanakar6
 
Actis maina-tumiatti v4-final-1 4383
Actis maina-tumiatti v4-final-1 4383Actis maina-tumiatti v4-final-1 4383
Actis maina-tumiatti v4-final-1 4383Alessandro Capo
 
01 Overview of Power transformers - Remedial Measures.ppt
01 Overview of Power transformers - Remedial Measures.ppt01 Overview of Power transformers - Remedial Measures.ppt
01 Overview of Power transformers - Remedial Measures.pptvikram desai
 
Analysis of example_capacitor_bank_switching_solution_and_recommendations_for...
Analysis of example_capacitor_bank_switching_solution_and_recommendations_for...Analysis of example_capacitor_bank_switching_solution_and_recommendations_for...
Analysis of example_capacitor_bank_switching_solution_and_recommendations_for...f95346
 
Gases insulation powerstation
Gases  insulation powerstationGases  insulation powerstation
Gases insulation powerstationraja sukumar
 
Erosion and Cavitation Tests Applied to Coating Welded with Blends of Stainle...
Erosion and Cavitation Tests Applied to Coating Welded with Blends of Stainle...Erosion and Cavitation Tests Applied to Coating Welded with Blends of Stainle...
Erosion and Cavitation Tests Applied to Coating Welded with Blends of Stainle...CSCJournals
 
06612 iec zerti_rz11_e
06612 iec zerti_rz11_e06612 iec zerti_rz11_e
06612 iec zerti_rz11_eCesar Chilet
 
Gas insulated substation
Gas insulated substationGas insulated substation
Gas insulated substationRaushanKumar582
 

Similar to End-of-life Factors in High Voltage GIS (20)

Gi e
Gi eGi e
Gi e
 
Kaizenreport
KaizenreportKaizenreport
Kaizenreport
 
substation 101
substation 101substation 101
substation 101
 
Protection & switchgear
Protection & switchgear   Protection & switchgear
Protection & switchgear
 
03 8 jun17 4apr 16176 chem by prod ijeecs(edit)
03 8 jun17 4apr 16176 chem by prod ijeecs(edit)03 8 jun17 4apr 16176 chem by prod ijeecs(edit)
03 8 jun17 4apr 16176 chem by prod ijeecs(edit)
 
H010514852
H010514852H010514852
H010514852
 
RPS-SF6LBS-PKE
RPS-SF6LBS-PKERPS-SF6LBS-PKE
RPS-SF6LBS-PKE
 
GIS PRESENTATION.pdf
GIS PRESENTATION.pdfGIS PRESENTATION.pdf
GIS PRESENTATION.pdf
 
Corrosion resistantalloysintheoilandgasindustryselectionguidelinesupdate 10073
Corrosion resistantalloysintheoilandgasindustryselectionguidelinesupdate 10073Corrosion resistantalloysintheoilandgasindustryselectionguidelinesupdate 10073
Corrosion resistantalloysintheoilandgasindustryselectionguidelinesupdate 10073
 
Chapter 11 Introduction to Gas Insulation Substation (GIS).pptx
Chapter 11 Introduction to Gas Insulation Substation (GIS).pptxChapter 11 Introduction to Gas Insulation Substation (GIS).pptx
Chapter 11 Introduction to Gas Insulation Substation (GIS).pptx
 
Proposal Technique for an Static Var Compensator
Proposal Technique for an Static Var CompensatorProposal Technique for an Static Var Compensator
Proposal Technique for an Static Var Compensator
 
Internship ppt(santhosh).pptx
Internship ppt(santhosh).pptxInternship ppt(santhosh).pptx
Internship ppt(santhosh).pptx
 
Pipeline repair techniques
Pipeline repair techniquesPipeline repair techniques
Pipeline repair techniques
 
Actis maina-tumiatti v4-final-1 4383
Actis maina-tumiatti v4-final-1 4383Actis maina-tumiatti v4-final-1 4383
Actis maina-tumiatti v4-final-1 4383
 
01 Overview of Power transformers - Remedial Measures.ppt
01 Overview of Power transformers - Remedial Measures.ppt01 Overview of Power transformers - Remedial Measures.ppt
01 Overview of Power transformers - Remedial Measures.ppt
 
Analysis of example_capacitor_bank_switching_solution_and_recommendations_for...
Analysis of example_capacitor_bank_switching_solution_and_recommendations_for...Analysis of example_capacitor_bank_switching_solution_and_recommendations_for...
Analysis of example_capacitor_bank_switching_solution_and_recommendations_for...
 
Gases insulation powerstation
Gases  insulation powerstationGases  insulation powerstation
Gases insulation powerstation
 
Erosion and Cavitation Tests Applied to Coating Welded with Blends of Stainle...
Erosion and Cavitation Tests Applied to Coating Welded with Blends of Stainle...Erosion and Cavitation Tests Applied to Coating Welded with Blends of Stainle...
Erosion and Cavitation Tests Applied to Coating Welded with Blends of Stainle...
 
06612 iec zerti_rz11_e
06612 iec zerti_rz11_e06612 iec zerti_rz11_e
06612 iec zerti_rz11_e
 
Gas insulated substation
Gas insulated substationGas insulated substation
Gas insulated substation
 

More from Ali Sepehri

My CV with photo
My CV with photoMy CV with photo
My CV with photoAli Sepehri
 
Technical information for high voltage disconnector & earthing switch in enqu...
Technical information for high voltage disconnector & earthing switch in enqu...Technical information for high voltage disconnector & earthing switch in enqu...
Technical information for high voltage disconnector & earthing switch in enqu...Ali Sepehri
 
Out of phase current switching in High Voltage Circuit Breakers
Out of phase current switching in High Voltage Circuit BreakersOut of phase current switching in High Voltage Circuit Breakers
Out of phase current switching in High Voltage Circuit BreakersAli Sepehri
 
Transient Recovery Voltage(TRV) in Interruption of Small Inductive Currents b...
Transient Recovery Voltage(TRV) in Interruption of Small Inductive Currents b...Transient Recovery Voltage(TRV) in Interruption of Small Inductive Currents b...
Transient Recovery Voltage(TRV) in Interruption of Small Inductive Currents b...Ali Sepehri
 
Voltage Escalation in Shunt Reactor Switching in Circuit Breakers
Voltage Escalation in Shunt Reactor Switching in Circuit BreakersVoltage Escalation in Shunt Reactor Switching in Circuit Breakers
Voltage Escalation in Shunt Reactor Switching in Circuit BreakersAli Sepehri
 
Hybrid HVDC Circuit Breaker Definitions
Hybrid HVDC Circuit Breaker  DefinitionsHybrid HVDC Circuit Breaker  Definitions
Hybrid HVDC Circuit Breaker DefinitionsAli Sepehri
 

More from Ali Sepehri (6)

My CV with photo
My CV with photoMy CV with photo
My CV with photo
 
Technical information for high voltage disconnector & earthing switch in enqu...
Technical information for high voltage disconnector & earthing switch in enqu...Technical information for high voltage disconnector & earthing switch in enqu...
Technical information for high voltage disconnector & earthing switch in enqu...
 
Out of phase current switching in High Voltage Circuit Breakers
Out of phase current switching in High Voltage Circuit BreakersOut of phase current switching in High Voltage Circuit Breakers
Out of phase current switching in High Voltage Circuit Breakers
 
Transient Recovery Voltage(TRV) in Interruption of Small Inductive Currents b...
Transient Recovery Voltage(TRV) in Interruption of Small Inductive Currents b...Transient Recovery Voltage(TRV) in Interruption of Small Inductive Currents b...
Transient Recovery Voltage(TRV) in Interruption of Small Inductive Currents b...
 
Voltage Escalation in Shunt Reactor Switching in Circuit Breakers
Voltage Escalation in Shunt Reactor Switching in Circuit BreakersVoltage Escalation in Shunt Reactor Switching in Circuit Breakers
Voltage Escalation in Shunt Reactor Switching in Circuit Breakers
 
Hybrid HVDC Circuit Breaker Definitions
Hybrid HVDC Circuit Breaker  DefinitionsHybrid HVDC Circuit Breaker  Definitions
Hybrid HVDC Circuit Breaker Definitions
 

Recently uploaded

College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service NashikCollege Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service NashikCall Girls in Nagpur High Profile
 
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...Dr.Costas Sachpazis
 
Introduction to Multiple Access Protocol.pptx
Introduction to Multiple Access Protocol.pptxIntroduction to Multiple Access Protocol.pptx
Introduction to Multiple Access Protocol.pptxupamatechverse
 
Call Girls Delhi {Jodhpur} 9711199012 high profile service
Call Girls Delhi {Jodhpur} 9711199012 high profile serviceCall Girls Delhi {Jodhpur} 9711199012 high profile service
Call Girls Delhi {Jodhpur} 9711199012 high profile servicerehmti665
 
Call Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur Escorts
Call Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur EscortsCall Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur Escorts
Call Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur High Profile
 
Current Transformer Drawing and GTP for MSETCL
Current Transformer Drawing and GTP for MSETCLCurrent Transformer Drawing and GTP for MSETCL
Current Transformer Drawing and GTP for MSETCLDeelipZope
 
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...ranjana rawat
 
Architect Hassan Khalil Portfolio for 2024
Architect Hassan Khalil Portfolio for 2024Architect Hassan Khalil Portfolio for 2024
Architect Hassan Khalil Portfolio for 2024hassan khalil
 
Coefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptxCoefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptxAsutosh Ranjan
 
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICSAPPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICSKurinjimalarL3
 
ZXCTN 5804 / ZTE PTN / ZTE POTN / ZTE 5804 PTN / ZTE POTN 5804 ( 100/200 GE Z...
ZXCTN 5804 / ZTE PTN / ZTE POTN / ZTE 5804 PTN / ZTE POTN 5804 ( 100/200 GE Z...ZXCTN 5804 / ZTE PTN / ZTE POTN / ZTE 5804 PTN / ZTE POTN 5804 ( 100/200 GE Z...
ZXCTN 5804 / ZTE PTN / ZTE POTN / ZTE 5804 PTN / ZTE POTN 5804 ( 100/200 GE Z...ZTE
 
IMPLICATIONS OF THE ABOVE HOLISTIC UNDERSTANDING OF HARMONY ON PROFESSIONAL E...
IMPLICATIONS OF THE ABOVE HOLISTIC UNDERSTANDING OF HARMONY ON PROFESSIONAL E...IMPLICATIONS OF THE ABOVE HOLISTIC UNDERSTANDING OF HARMONY ON PROFESSIONAL E...
IMPLICATIONS OF THE ABOVE HOLISTIC UNDERSTANDING OF HARMONY ON PROFESSIONAL E...RajaP95
 
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escortsranjana rawat
 
High Profile Call Girls Nashik Megha 7001305949 Independent Escort Service Na...
High Profile Call Girls Nashik Megha 7001305949 Independent Escort Service Na...High Profile Call Girls Nashik Megha 7001305949 Independent Escort Service Na...
High Profile Call Girls Nashik Megha 7001305949 Independent Escort Service Na...Call Girls in Nagpur High Profile
 
Introduction and different types of Ethernet.pptx
Introduction and different types of Ethernet.pptxIntroduction and different types of Ethernet.pptx
Introduction and different types of Ethernet.pptxupamatechverse
 
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...Dr.Costas Sachpazis
 
247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).ppt
247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).ppt247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).ppt
247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).pptssuser5c9d4b1
 
Software Development Life Cycle By Team Orange (Dept. of Pharmacy)
Software Development Life Cycle By  Team Orange (Dept. of Pharmacy)Software Development Life Cycle By  Team Orange (Dept. of Pharmacy)
Software Development Life Cycle By Team Orange (Dept. of Pharmacy)Suman Mia
 

Recently uploaded (20)

College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service NashikCollege Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
 
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
 
Introduction to Multiple Access Protocol.pptx
Introduction to Multiple Access Protocol.pptxIntroduction to Multiple Access Protocol.pptx
Introduction to Multiple Access Protocol.pptx
 
Call Girls Delhi {Jodhpur} 9711199012 high profile service
Call Girls Delhi {Jodhpur} 9711199012 high profile serviceCall Girls Delhi {Jodhpur} 9711199012 high profile service
Call Girls Delhi {Jodhpur} 9711199012 high profile service
 
Call Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur Escorts
Call Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur EscortsCall Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur Escorts
Call Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur Escorts
 
Current Transformer Drawing and GTP for MSETCL
Current Transformer Drawing and GTP for MSETCLCurrent Transformer Drawing and GTP for MSETCL
Current Transformer Drawing and GTP for MSETCL
 
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
 
Architect Hassan Khalil Portfolio for 2024
Architect Hassan Khalil Portfolio for 2024Architect Hassan Khalil Portfolio for 2024
Architect Hassan Khalil Portfolio for 2024
 
Coefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptxCoefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptx
 
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICSAPPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
 
ZXCTN 5804 / ZTE PTN / ZTE POTN / ZTE 5804 PTN / ZTE POTN 5804 ( 100/200 GE Z...
ZXCTN 5804 / ZTE PTN / ZTE POTN / ZTE 5804 PTN / ZTE POTN 5804 ( 100/200 GE Z...ZXCTN 5804 / ZTE PTN / ZTE POTN / ZTE 5804 PTN / ZTE POTN 5804 ( 100/200 GE Z...
ZXCTN 5804 / ZTE PTN / ZTE POTN / ZTE 5804 PTN / ZTE POTN 5804 ( 100/200 GE Z...
 
IMPLICATIONS OF THE ABOVE HOLISTIC UNDERSTANDING OF HARMONY ON PROFESSIONAL E...
IMPLICATIONS OF THE ABOVE HOLISTIC UNDERSTANDING OF HARMONY ON PROFESSIONAL E...IMPLICATIONS OF THE ABOVE HOLISTIC UNDERSTANDING OF HARMONY ON PROFESSIONAL E...
IMPLICATIONS OF THE ABOVE HOLISTIC UNDERSTANDING OF HARMONY ON PROFESSIONAL E...
 
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
 
High Profile Call Girls Nashik Megha 7001305949 Independent Escort Service Na...
High Profile Call Girls Nashik Megha 7001305949 Independent Escort Service Na...High Profile Call Girls Nashik Megha 7001305949 Independent Escort Service Na...
High Profile Call Girls Nashik Megha 7001305949 Independent Escort Service Na...
 
Introduction and different types of Ethernet.pptx
Introduction and different types of Ethernet.pptxIntroduction and different types of Ethernet.pptx
Introduction and different types of Ethernet.pptx
 
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
 
247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).ppt
247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).ppt247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).ppt
247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).ppt
 
Call Us -/9953056974- Call Girls In Vikaspuri-/- Delhi NCR
Call Us -/9953056974- Call Girls In Vikaspuri-/- Delhi NCRCall Us -/9953056974- Call Girls In Vikaspuri-/- Delhi NCR
Call Us -/9953056974- Call Girls In Vikaspuri-/- Delhi NCR
 
Software Development Life Cycle By Team Orange (Dept. of Pharmacy)
Software Development Life Cycle By  Team Orange (Dept. of Pharmacy)Software Development Life Cycle By  Team Orange (Dept. of Pharmacy)
Software Development Life Cycle By Team Orange (Dept. of Pharmacy)
 
DJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINE
DJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINEDJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINE
DJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINE
 

End-of-life Factors in High Voltage GIS

  • 1. End-of-life factors in high voltage gas insulated switchgear with SF6 or with non-SF6 gases source: https://switchgearcontent.com Photo from GE company SF6 free GIS product In this article speak about brief overview of indicators for end-of-life of gas insulated switchgear, and what has to be done when end-of-life is reached. Furthermore, options for life extension of GIS with non SF6 gases and gas mixtures are discussed Some parts of the GIS equipment are subject to ageing and deterioration mechanisms. These ageing processes should be considered when determining future performance and residual life of the equipment and should be targeted by condition monitoring programmes. This section considers the following: • Critical technical performance factors. • How these factors might affect residual life. • Diagnostic techniques that can help determine residual life. There are two different indicators for end-of-life: 1- The specified end-of-life of the GIS is reached:
  • 2. End-of-life factors in high voltage gas insulated switchgear with SF6 or with non-SF6 gases source: https://switchgearcontent.com End-of-life of GIS is either specified by the end user, reflecting the intended time until replacement of the equipment should be done, or the end-of-life of GIS is specified by the equipment manufacturer stating a minimum lifetime (which can be extended), or by an increased failure rate indicating end-of life. 2-End-of-life of the insulation gas mixture is reached: Non-SF6 gases or gas mixtures may age during lifetime e.g. due to decomposition and reach an end-of-life stage. Here, a first indicator for end-of-life would be the gas lifetime statement of the equipment manufacturer. Exemplary life limiting factors in GIS equipments are listed as below: 1-Mechanical wear of circuit breakers: The designed mechanical lifetime is usually defined by the permitted number of off-load switching operations. It is limited by mechanical wear and/or fatigue life of highly stressed parts The highest stressed parts of the circuit breaker are the energy storage system and the mechanical chain between the energy storage element and the moving contacts. If applicable, the impact of non-SF6 gases or gas mixtures on mechanical wear of different circuit breaker designs (e.g. CO2-breaker, vacuum breaker) has to be discussed between the end user and the equipment manufacturer. The following diagnostic techniques may be helpful in assessing residual life: Charging time Contact timing Static contact resistance Travel records Trip coil current Vibration analysis 2-Electrical wear of circuit breakers: The contact system has a limited capability to interrupt fault currents because of contact erosion and nozzle ablation. The wear of contacts caused by the arc during circuit-breaker switching operations may be estimated by calculation. The physics of arc-induced contact wear is complex, but simplified expressions have been derived that allow contact wear to be calculated with acceptable
  • 3. End-of-life factors in high voltage gas insulated switchgear with SF6 or with non-SF6 gases source: https://switchgearcontent.com accuracy. The most commonly used methods assume the mass of contact material lost during each operation to be proportional to the time integral of the arc current squared. One of test method for measuring waer of circuit breakers is Dynamic (Contact) Resistance Measurements (DRM). In photo1 you can see DRM test curves: Photo1: Dynamic (Contact) Resistance Measurements (DRM) curves in circuit breaker If applicable, the impact of non-SF6 gases or gas mixtures on electrical wear of different circuit breaker design (e.g. CO2-breaker, vacuum breaker) has to be discussed between the end user and the equipment manufacturer. If degradation of gases or gas mixtures during switching is to be expected, the impact on lifetime of circuit breaker should be discussed as well. 3-Deterioration of grading capacitors of circuit breakers: Grading capacitors used in multi-break circuit breakers have been found to exhibit a number of deterioration mechanisms, and in some cases mechanical or electrical failure has occurred. It has to be discussed between the end user and the equipment manufacturers if deterioration of grading capacitors is a special issue for circuit breaker designs with non- SF6 gases and gas mixtures. Some deterioration mechanisms effecting GIS grading capacitors can be detected using partial discharge techniques as described later. Other defects may only be detected by
  • 4. End-of-life factors in high voltage gas insulated switchgear with SF6 or with non-SF6 gases source: https://switchgearcontent.com visual inspection. 4-High-speed earthing switches: For HV GIS, high speed earthing switches have the duty to make rated short circuit currents for at least two times, and to switch rather small induced currents. Thus, they are usually unlikely to be the life limiting factors of HV GIS with SF6. If application of non-SF6 gases and gas mixtures requires different high-speed earthing switch design the impact on mechanical or electrical wear should be discussed between the end user and the equipment manufacturer. Besides visual inspection, resistance test, timing tests and travel curve measurement may be useful for assessment of the device. In photo2 we can see high speed earthing switch in GIS:
  • 5. End-of-life factors in high voltage gas insulated switchgear with SF6 or with non-SF6 gases source: https://switchgearcontent.com Photo2: High speed earthing switch
  • 6. End-of-life factors in high voltage gas insulated switchgear with SF6 or with non-SF6 gases source: https://switchgearcontent.com 5-Disconnectors and (maintenance) earthing switches: Disconnector and earthing switches mostly have no or small current making or breaking capacity, and therefore have mainly a mechanical lifetime. Some disconnector/earthing switches are fitted with arcing contacts and can make or break bus transfer currents, bus charging currents or induced currents of transmission lines (earthing switches). For these switching duties, electrical wear of arcing contacts can occur. If additional gas ageing effects due to switching have to be considered, the impact on lifetime should be discussed between the end users and the equipment manufacturer. As in the case of circuit-breakers, an initial idea of mechanical wear of disconnectors and earthing switches can be obtained from the operations counter and knowledge of the mechanical endurance class of a device, while more specific indications may be obtained using diagnostic techniques. Most frequently, the motor running times for ‘open’ and ‘close’ operations are measured. In some cases, the motor current and the contact resistance are measured as well. 6-Current carrying components including contacts: In SF6 GIS, as well as in non-SF6 GIS, if mechanical integrity is maintained,there is no ageing mechanism affecting current carrying contacts. The current carrying ability of the primary circuit can be tested by resistance measurement. Since the resistance to be measured is of the order of micro Ohms, the measurement is typically performed by passing a current of 100 A DC or higher through the primary circuit and measuring the resulting voltage differences. The four wire method is used to prevent the current supply leads and voltage probes from influencing the measurement. Commercial micro Ohm meters that work on this principle are available. The values obtained may be compared to those originally obtained during tests after installation on site. For GIS with SF6 gas: SF6 gas begins to decompose at high temperatures and the techniques described below for monitoring decomposition products may reveal the presence of a hot contact within a gas compartment. Additionally, once arcing and particulate debris are present, the PD techniques described below may be able to detect and locate a deteriorating contact.
  • 7. End-of-life factors in high voltage gas insulated switchgear with SF6 or with non-SF6 gases source: https://switchgearcontent.com 7-Gas quality : A first indicator for end-of-life of non-SF6 gases and gas mixtures would be the gas lifetime statement of the equipment manufacturer. A gas quality check (if possible) might indicate that the equipment can be used longer, or that the gas has to be replaced if its end-of-life condition is reached. As for SF6, this will require a replacement of the desiccants. For GIS with SF6 gas :Gas can be tested for decomposition products on-site using chemical reaction tubes that change colour in the presence of certain reactive gases. Tubes sensitive to SO2 and to HF are available. However, since HF reacts rapidly with metals to form metal fluorides, the use of tubes sensitive to HF is not recommended. The tubes sensitive to SO2 are also sensitive to SOF2. A gas sample may also be sent off-site for laboratory analysis by gas chromatography or infra red spectrography. Stainless steel cylinders with a volume of less than 1litre are recommended for this purpose. This method provides a more accurate analysis but is more expensive and the results are not immediately available. In photo3 we can see an example SF6 gas purity and analyzer device:
  • 8. End-of-life factors in high voltage gas insulated switchgear with SF6 or with non-SF6 gases source: https://switchgearcontent.com Photo3: SF6 gas purity and analyzer device 8- Particulate contamination of gas: The insulating performance of a gas or gas mixture and of insulator surfaces may be compromised if field-enhancing defects, such as particles, are present. Particles may be generated by the wear of moving parts, such as conductor sliding contacts and the contacts of switching devices. If particles can also be generated by other ways, e.g. decomposition of non-SF6 gases or gas mixtures, their impact on the insulation performance of GIS should be discussed between the end user and the GIS manufacturer. For GIS with SF6 gas: Defects such as small conducting particles generate partial discharges, which are
  • 9. End-of-life factors in high voltage gas insulated switchgear with SF6 or with non-SF6 gases source: https://switchgearcontent.com accompanied by electromagnetic transients and acoustic vibrations. Both of these have formed the basis of sensitive methods that have been developed for detection, recognition and location of defects. Hampton and Meats developed a diagnostic technique that makes use of the electromagnetic radiation in the UHF band generated by discharging defects. UHF signals may be detected with comparatively simple, purpose built coupling devices installed within the GIS. Where no such provision has been made it is sometimes possible to detect signals using external sensors that can be applied at breaks in the conducting enclosure, such as contact viewing windows, through which electromagnetic radiation can pass. 9-Gas leakage: Possible origins and causes of gas leakage in GIS include pipework connections, corrosion at bolted flange enclosure joints (outdoor equipment), damaged or degraded seals or bushings (insulators), adherence of dust, particulate or other foreign material to dynamic seals, and porosity in enclosure castings or welds. These causes are rather general and mainly independent from the gas being used inside the GIS. For GIS with SF6 gas : Where a loss of gas from a compartment is identified, external checks with leak detection methods may allow the source of the leak to be determined. by the methods applicable to locating leaks in service, negative ion capture detectors and electron capture detectors are stated to have sensitivities of 20 mg/a SF6 or 1 ppmv and 2 mg/a SF6 or 100 ppbv, respectively. In photo 4 we can see Electron Capture Detector(ECD) Method For Sf6 Gas
  • 10. End-of-life factors in high voltage gas insulated switchgear with SF6 or with non-SF6 gases source: https://switchgearcontent.com Photo 4: Electron Capture Detector Gas leakages may become an important life limiting factor if the required leakage rates can not be achieved. In the future the leakage rates may be defined by environmental regulations. In photo 5 we can see a SF6 gas detector device:
  • 11. End-of-life factors in high voltage gas insulated switchgear with SF6 or with non-SF6 gases source: https://switchgearcontent.com Photo 5: SF6 gas leakage detector equipment 10-Filters: Depending on the installed amount and filter type, filters themselves are usually not life- limiting, but they are relevant for maintenance (to be replaced after opening of compartments). Filters generally adsorb both humidity and decomposition products and should be specified with respect to the type and amount of filter material needed for each gas or gas mixture. For GIS with SF6 gas: An indication that the molecular sieve is becoming exhausted may be given by the gas quality measurements. Filters themselves are not a life limiting factor rather they are a maintenance issue. 11-Solid insulating parts (GIS internal parts): With state-of-the-art manufacturing technology and quality control (no voids or metallic inclusions), solid insulating parts are usually not subject to any ageing.
  • 12. End-of-life factors in high voltage gas insulated switchgear with SF6 or with non-SF6 gases source: https://switchgearcontent.com If any contamination from the gas can be excluded, solid insulating parts may not be life- limiting components of the GIS. For GIS with sf6 gas: The guide takes only GIS internal insulation into consideration. It does not apply to SF6- Air and SF6-Oil bushings as the life limiting factor may well be on the non SF6-side. In their work on the long term performance of SF6 insulated systems, Task Force observed that partial discharge measurement may be able to detect voids in solid insulation, provided sufficient sensitivity can be achieved and pulsed discharge activity occurs. The sensitivity that can be normally achieved in on-site tests with UHF technique will allow critical voids to be detected. Evolution of PD intensity can be used as an indicator of ageing of epoxy impregnated paper insulated air bushings or epoxy resin filled voltage transformers. If the observed level of PD increases it is a sign that critical ageing is occurring. 12-Metallic enclosures: Deterioration of flanges due to moisture ingress can be seen as a critical ageing mechanism, which is independent of the gas or gas mixture inside the GIS. Hence, metallic enclosures may be life-limiting components. For GIS with sf6 gas: Signs of corrosion and moisture ingress at the enclosure flanges, particularly for outdoor compartments, can be obtained by visual inspection. The condition of any protective coating may similarly be checked. SF6 leakage may be an indication of flange corrosion. 13- Gas seals: The material used for the sealing function must be able to provide sufficient gas tightness over the lifetime under application conditions. Main factors causing ageing are the material used, temperature, UV radiation, exposure to oxygen and their combination. If only materials are applied which are qualified for every gas or gas mixture, seals may not be life- limiting components. For GIS with SF6 gas:
  • 13. End-of-life factors in high voltage gas insulated switchgear with SF6 or with non-SF6 gases source: https://switchgearcontent.com The performance of gas seals can be monitored by SF6 leakage detection methods. When any work requiring internal access to the GIS is performed, the opportunity should be taken to establish the condition of the seals. The seals may be examined or analysed and residual life estimations made. An investigation into the deterioration of O-rings sampled from GIS and gas circuit-breakers aged 20 to 30 years has been reported. In the investigation, compression set cs, as defined in the following equation, was used as an indicator of degradation. 14-Pressure relief device: Two main ageing mechanisms of pressure relief devices are corrosion (e.g. due to attack by moisture) and/or fatigue (e.g. due to temperature cycles). Both mechanisms are rather independent from the gas inside GIS. There is no non-destructive method suitable to monitor / check the actual state of the pressure relief devices in service. The visual inspection is useful, but it can check the visible traces of the corrosion only. However monitoring gas leakage can identify corrosion that is not visible. In case of any deterioration observed repair shall be considered as soon as possible. The ageing caused by fatigue can cause the decrease of the operating pressure of the bursting disc. In case of any unintentional operation the rupture discs of the affected GIS shall be tested. Several pieces shall be delivered to the laboratory of the manufacturer and checked very thoroughly. If necessary all rupture discs shall be exchanged (this procedure can be applied in other cases as well, if there is any suspicion of ageing). The condition of the bursting disks will generally not be a life limiting factor. However it will certainly be taken into account when considering whether to refurbish or replace the GIS. If refurbishment of a GIS compartment is being undertaken for other reasons, it is recommended that bursting disks of the graphite type will be replaced to ensure that target life extension is achieved.