A Comparison of Contemporary Electrical
Distribution Equipment Standards
San Francisco IEEE
Industry Applications Society
May 26, 2009
What are “Standards”?
• Clearly defined performance characteristics
• Based on tested performance under expected worse case
parameters
• Generally based on third party certification of tested
performance
• Vendor or supplier independent
Provide the basis for objective based comparison of
performance under expected conditions of operation
An Example
Contemporary Standard -- Octane
• RON = Research Octane Number (fuel based); MON
= Motor Octane Number (load/timing based)
• PON = Pump Octane Number; PON = (RON +
MON)/2
• Uniform among suppliers to allow selection of
proper grade by users,
BUT,
• Does not prevent misapplication due to perception
• Does not insure all suppliers offer the same
product/features
• Can be revenue/margin tool for vendor
High Octane – Premium Unleaded
Low Octane – Regular Unleaded
What Rating is Required?
Electrical Distribution Equipment
• Divides Larger Amounts of Power into Smaller
“Chunks”
• Can contain control and metering/monitoring
devices
• Contains protective feeder devices whose prime
role is to protect feeders
• Low Voltage Application include Panelboards,
Switchboards, Switchgear
Watt’s Engine
James Watt
1736 -- 1819
E = IR
W = EI
746 Watts = 1 Horsepower
600 Amps @ 480V 3ph = 665 HP
10,000 Amps @ 120V 1ph = 1600 HP
Office Building
65,000 AIC @ 480V = 72,300 HP
Medium Voltage
40,000 AIC @ 13,800V = 1,300,000 HP
Fault Testing
Fault Testing
Interaction in Equipment
x
• Opening Contacts
Create Arcing
• Arcing Creates
Resistance
• Resistance Reduces
Current Flow
• Reduced Current Flow
Can Affect Opening
Speed
• Reduced Opening
Speed Will Affect Energy
Flow
Dynamic Interactions
• Individual devices react to what they see
▫ Circuit Breakers react to over current or short
circuit conditions
▫ Relays operate based on on conditions sensed
• Individual devices react to the reaction of other
devices
▫ A circuit breaker that is tripping (opening under
load) will affect the current and voltage seen by
other devices
Selectivity Can Be Impacted
x
• Depending on fault
level, more than one
device can open on a
downstream fault
• Loads without faults
can be affected or
interrupted
• Entire systems can be
shutdown by
downstream faults
• May be part of design
for series ratings
Possible Conditions of Operation
• High Energy Levels – Need to insure proper
operation at possible fault levels
• Dynamic Interaction – Need to understand possible
device interactions under fault conditions
• Selectivity – Need to insure required selectivity
under all potential fault conditions
BUT,
• Cost – Need to meet all performance requirements
within budgetary constraints
LV Equipment Standards
• NEMA –Switchboards PB-2/Switchgear SG-5
▫ No longer writing standards; still responsible for
certain breaker testing standards
• ANSI – Switchgear C37.20
▫ Publishes standards; no longer creates standards
for electrical equipment
• IEEE – Switchgear C 37.20
▫ Develops standards for equipment/breakers
• UL – Switchboards UL 891/Switchgear UL 1558
▫ Both develops standards and serves as third party
certifier of devices and systems
Switchboards or Switchgear
• Terms often used interchangeably by many in
industry; Switchgear is generic term
• Per NEC Article 100, difference is far from
contemporary.
• Objective differences now defined by UL/ANSI
standards for equipment
BUT,
• Many design elements can overlap
• Common components possible
Devices, not Equipment are Key
• OCPD (Over Current Protective Devices)
determine the operational characteristics of the
equipment
• Application of OCPDs determines equipment
type (equipment standards)
• As in most cases, compromises may be required
to obtain optimal solution for particular
situation
Circuit Breakers
LV Power Circuit Breakers Molded Case Circuit Breakers
• Since 1985, LV Power Circuit
Breakers listed under UL 1066
• Formerly under ANSI C37.13
and C37.50 (not UL)
• Classic design was iron frame;
most now enclosed with non-
metallic materials
• Allow for maintenance of
internal parts for long service
life
• Higher performance and
higher cost
• Listed under UL 489
• Includes “insulated” case
circuit breakers
• Classic design was toggle type
thermosetting or
thermoplastic sealed case
• Sealed case prevents normal
maintenance
• Tend to be lower cost than
Power Circuit Breakers
• High AIC ratings possible
LV Power Breakers Evolution
1999
1999?
2001 20052002
2007
?
Key Differences UL 489 vs. UL 1066
• Higher endurance testing for UL 1066 at all
ratings (e.g., 800A – 500 cycles UL 489; 800
cycles UL 1066 at FLA)
• Short time withstand test required for UL 1066
rating – maintain high level current for 0.5
seconds
• Single pole testing for UL 1066
• Different power factor requirements for testing
• Different heat rise requirements for testing
Switchboards or Switchgear -- UL
• Switchgear listed to UL 1558 since
1982
• Based on ANSI C37 standards
• Uses UL 1066 listed breakers
• Generally requires rear access for
load and incoming connections
• “Compartmentalized” Construction
with breaker compartment for each
device
• Tested to short circuit rating for 4
cycles (.067 seconds)
• Tested to short time rating for 30
cycles (0.5 seconds)
• Heat Rise tested Bussing
• Switchboards listed to UL 891
• Uses UL 891 or UL 1066 listed
breakers
• Can be front connected without rear
access requirements
• Devices can be individually
(vertically) or group
(panel/horizontally) mounted
• Tested to short circuit rating of 3
cycles (.05 seconds) or to
instantaneous trip of tested OCPD
or braced to UL configuration
standards
• Heat Rise Tested or Density Rated
Why Require UL1558/UL1066?
• Allows use of tested assemblies/devices without
instantaneous trips for selectivity
▫ May be required to allow for slower relays for
differential protection
▫ Will insure selectivity to limit of short time ratings
(to instantaneous over ride limits)
• May provide features/designs not available in
UL 891 products from some manufacturers
▫ Insulated and/or isolated bussing
▫ Protected wire ways for LV controls
Selectivity Can Be Restored
• By eliminating
instantaneous on one or
more levels, selectivity
can be maintained
• Arc Flash protection
can be enhanced by
differential relaying or
arc flash relays
•Requires UL 1558
equipment for LV
applications wherever
instantaneous
protections is eliminated
x
Why Not?
• Unless features/characteristics are not available in UL
891, UL 1558 equipment tends to be more costly.
▫ GE study showed 1.6 to 2.0 unit cost difference between
equivalent UL 891 and UL 1558 assemblies
• Rear access may not be available
▫ Foot prints may be similar in square footage; required
space may vary due to rear clearance requirements
• UL 1066 devices can be used in UL 891 equipment
▫ Some manufacturers offer equivalent UL 489 devices;
others only offer UL 1066 devices
▫ Can NOT “turn off” instantaneous trip and maintain UL
• Unusual busing configurations may not be available in
UL 1558 equipment
▫ Only tested configurations are possible in UL 1558; UL 891
can use approved bracing configurations to create “custom”
configurations.
Diesel – The European Standard
Standards Vary
IEC Standards
• IEC 60439 -1 (Low Voltage Switchgear and
Controlgear Assemblies)
▫ Can be either TTA (Type Tested Assembly) or PTTA
(Partially Type Tested Assembly)
▫ PTTA requires calculations for those parts not type
tested
▫ Includes both Switchgear and Switchboard equivalents
• IEC 60947 (Low Voltage Power Circuit Breakers)
• IEC 298 (Medium Voltage Switchgear and
Controlgear Assemblies
▫ Includes both metal enclosed and metal clad
equivalents
Significant Configuration Differences
Typical MV Configuration
LV Controls
Breaker Compartment
Cable Termination
Tie Bus
PT Compartment
IEC Adaptations
• Many components originally designed for IEC
markets successfully adapted/modified to meet
UL standards
• IEC electrical equipment products generally not
yet adapted to UL standards although efforts are
ongoing
• IEC MV equipment successfully adapted to CSA
standards (required some IEEE/ANSI testing)
• Increased demand for IEC equipment by users
• Often supplied as part of other equipment for
food processing or similar applications
Final Notes
• Knowledge of standards and implications will
drive most cost effective solutions for varied
applications – one size does NOT fit all
• Differentiating between what is required by
standards and what is desired for the particular
application (particularly on features) will allow
more choices as to suppliers
• Final acceptance of equipment is dependent on
local authorities (AHJ). Independent
certification of standards will usually insure
acceptance.

More Related Content

What's hot

Power Electronics Basic by Engr.Rajesh Roy
Power Electronics Basic by  Engr.Rajesh RoyPower Electronics Basic by  Engr.Rajesh Roy
Power Electronics Basic by Engr.Rajesh Royrajesh roy
 
Gas insulated auto sectionalizer
Gas insulated auto sectionalizerGas insulated auto sectionalizer
Gas insulated auto sectionalizerJoeChueng
 
Practical Power System Protection for Engineers and Technicians
Practical Power System Protection for Engineers and TechniciansPractical Power System Protection for Engineers and Technicians
Practical Power System Protection for Engineers and TechniciansLiving Online
 
LV 124 & LV 148 Solutions - WKS Informatik
LV 124 & LV 148 Solutions - WKS InformatikLV 124 & LV 148 Solutions - WKS Informatik
LV 124 & LV 148 Solutions - WKS InformatikAndreea Solomon
 
Design and Development of 5MW Solar PV Grid Connected Power Plant using PVsyst
Design and Development of 5MW Solar PV Grid Connected Power Plant using PVsystDesign and Development of 5MW Solar PV Grid Connected Power Plant using PVsyst
Design and Development of 5MW Solar PV Grid Connected Power Plant using PVsystIRJET Journal
 
Presentation on electrical and automation system of cgl plant (CRM-2) JSW KR.
Presentation on electrical and automation system of cgl plant (CRM-2) JSW KR.Presentation on electrical and automation system of cgl plant (CRM-2) JSW KR.
Presentation on electrical and automation system of cgl plant (CRM-2) JSW KR.neeraj mishra
 
ETAP - Short circuit ansi standard
ETAP - Short circuit ansi standardETAP - Short circuit ansi standard
ETAP - Short circuit ansi standardHimmelstern
 
Low voltage switchgear ansi (distib. prim. bt)
Low voltage switchgear ansi (distib. prim. bt)Low voltage switchgear ansi (distib. prim. bt)
Low voltage switchgear ansi (distib. prim. bt)Moi Reyes
 
RTStand LV 124 - fully-automated testing system for LV 124
RTStand LV 124 - fully-automated testing system for LV 124RTStand LV 124 - fully-automated testing system for LV 124
RTStand LV 124 - fully-automated testing system for LV 124Andreea Solomon
 
Iec 61439 for_low_voltage_switchgear_and
Iec 61439 for_low_voltage_switchgear_andIec 61439 for_low_voltage_switchgear_and
Iec 61439 for_low_voltage_switchgear_andssuserfd2587
 
Circuit Breakers Interrupting Capacity and Short-Time Current Rating
Circuit Breakers Interrupting Capacity and Short-Time Current Rating Circuit Breakers Interrupting Capacity and Short-Time Current Rating
Circuit Breakers Interrupting Capacity and Short-Time Current Rating michaeljmack
 
Thermography test of electrical panels
Thermography test of electrical panelsThermography test of electrical panels
Thermography test of electrical panelsPower System Operation
 
Paralleling Switchgear
Paralleling SwitchgearParalleling Switchgear
Paralleling Switchgearmichaeljmack
 
Short-Circuit Protective Device Coordination & Arc Flash Analysis
Short-Circuit Protective Device Coordination & Arc Flash AnalysisShort-Circuit Protective Device Coordination & Arc Flash Analysis
Short-Circuit Protective Device Coordination & Arc Flash AnalysisPower System Operation
 
Nec emergency requirements
Nec emergency requirementsNec emergency requirements
Nec emergency requirementsmichaeljmack
 
A project report on Remote Monitoring of a Power Station using GSM and Arduino
A project report on Remote Monitoring of a Power Station using GSM and ArduinoA project report on Remote Monitoring of a Power Station using GSM and Arduino
A project report on Remote Monitoring of a Power Station using GSM and ArduinoJawwad Sadiq Ayon
 
Liebert RG UPS for Regenerative Load Applications
Liebert RG UPS for Regenerative Load ApplicationsLiebert RG UPS for Regenerative Load Applications
Liebert RG UPS for Regenerative Load ApplicationsAbigail Kwok
 

What's hot (20)

Power Electronics Basic by Engr.Rajesh Roy
Power Electronics Basic by  Engr.Rajesh RoyPower Electronics Basic by  Engr.Rajesh Roy
Power Electronics Basic by Engr.Rajesh Roy
 
Gas insulated auto sectionalizer
Gas insulated auto sectionalizerGas insulated auto sectionalizer
Gas insulated auto sectionalizer
 
Practical Power System Protection for Engineers and Technicians
Practical Power System Protection for Engineers and TechniciansPractical Power System Protection for Engineers and Technicians
Practical Power System Protection for Engineers and Technicians
 
LV 124 & LV 148 Solutions - WKS Informatik
LV 124 & LV 148 Solutions - WKS InformatikLV 124 & LV 148 Solutions - WKS Informatik
LV 124 & LV 148 Solutions - WKS Informatik
 
EIT_Presentation
EIT_PresentationEIT_Presentation
EIT_Presentation
 
Design and Development of 5MW Solar PV Grid Connected Power Plant using PVsyst
Design and Development of 5MW Solar PV Grid Connected Power Plant using PVsystDesign and Development of 5MW Solar PV Grid Connected Power Plant using PVsyst
Design and Development of 5MW Solar PV Grid Connected Power Plant using PVsyst
 
Presentation on electrical and automation system of cgl plant (CRM-2) JSW KR.
Presentation on electrical and automation system of cgl plant (CRM-2) JSW KR.Presentation on electrical and automation system of cgl plant (CRM-2) JSW KR.
Presentation on electrical and automation system of cgl plant (CRM-2) JSW KR.
 
EIT_Presentation
EIT_PresentationEIT_Presentation
EIT_Presentation
 
ETAP - Short circuit ansi standard
ETAP - Short circuit ansi standardETAP - Short circuit ansi standard
ETAP - Short circuit ansi standard
 
Low voltage switchgear ansi (distib. prim. bt)
Low voltage switchgear ansi (distib. prim. bt)Low voltage switchgear ansi (distib. prim. bt)
Low voltage switchgear ansi (distib. prim. bt)
 
RTStand LV 124 - fully-automated testing system for LV 124
RTStand LV 124 - fully-automated testing system for LV 124RTStand LV 124 - fully-automated testing system for LV 124
RTStand LV 124 - fully-automated testing system for LV 124
 
Iec 61439 for_low_voltage_switchgear_and
Iec 61439 for_low_voltage_switchgear_andIec 61439 for_low_voltage_switchgear_and
Iec 61439 for_low_voltage_switchgear_and
 
Circuit Breakers Interrupting Capacity and Short-Time Current Rating
Circuit Breakers Interrupting Capacity and Short-Time Current Rating Circuit Breakers Interrupting Capacity and Short-Time Current Rating
Circuit Breakers Interrupting Capacity and Short-Time Current Rating
 
Thermography test of electrical panels
Thermography test of electrical panelsThermography test of electrical panels
Thermography test of electrical panels
 
Paralleling Switchgear
Paralleling SwitchgearParalleling Switchgear
Paralleling Switchgear
 
Short-Circuit Protective Device Coordination & Arc Flash Analysis
Short-Circuit Protective Device Coordination & Arc Flash AnalysisShort-Circuit Protective Device Coordination & Arc Flash Analysis
Short-Circuit Protective Device Coordination & Arc Flash Analysis
 
Nec emergency requirements
Nec emergency requirementsNec emergency requirements
Nec emergency requirements
 
EIT_Presentation
EIT_PresentationEIT_Presentation
EIT_Presentation
 
A project report on Remote Monitoring of a Power Station using GSM and Arduino
A project report on Remote Monitoring of a Power Station using GSM and ArduinoA project report on Remote Monitoring of a Power Station using GSM and Arduino
A project report on Remote Monitoring of a Power Station using GSM and Arduino
 
Liebert RG UPS for Regenerative Load Applications
Liebert RG UPS for Regenerative Load ApplicationsLiebert RG UPS for Regenerative Load Applications
Liebert RG UPS for Regenerative Load Applications
 

Similar to A Comparison of Contemporary Electrical Distribution Equipment Standards

Tools and Techniques for Commissioning and Maintaining PV Systems
Tools and Techniques for Commissioning and Maintaining PV SystemsTools and Techniques for Commissioning and Maintaining PV Systems
Tools and Techniques for Commissioning and Maintaining PV SystemsTranscat
 
Electric drives and controls
Electric drives and controlsElectric drives and controls
Electric drives and controlsAnandKumar2123
 
Power_System_Protection Lecture-1.pdf
Power_System_Protection Lecture-1.pdfPower_System_Protection Lecture-1.pdf
Power_System_Protection Lecture-1.pdfYogeshGairola2
 
Product presentation usa
Product presentation  usaProduct presentation  usa
Product presentation usameltric
 
Selective Coordination "The Rest of the Story"
Selective Coordination "The Rest of the Story"Selective Coordination "The Rest of the Story"
Selective Coordination "The Rest of the Story"michaeljmack
 
ETAP - Coordination and protecion 2
ETAP -  Coordination and protecion 2ETAP -  Coordination and protecion 2
ETAP - Coordination and protecion 2Himmelstern
 
Selective Coodination
Selective CoodinationSelective Coodination
Selective Coodinationmichaeljmack
 
Short Circuit, Protective Device Coordination
Short Circuit, Protective Device CoordinationShort Circuit, Protective Device Coordination
Short Circuit, Protective Device Coordinationmichaeljmack
 
Ohiri-Principles-and-Philosophy-of-Protective-Relaying.pptx
Ohiri-Principles-and-Philosophy-of-Protective-Relaying.pptxOhiri-Principles-and-Philosophy-of-Protective-Relaying.pptx
Ohiri-Principles-and-Philosophy-of-Protective-Relaying.pptxGodwin308555
 
Rectifier Operations & Maintenance - Don Olson - 2.4.2020
Rectifier Operations & Maintenance - Don Olson - 2.4.2020Rectifier Operations & Maintenance - Don Olson - 2.4.2020
Rectifier Operations & Maintenance - Don Olson - 2.4.2020nacetwincities
 
ETAP - Arcflash analysis & mitigation methods
ETAP - Arcflash analysis &  mitigation  methodsETAP - Arcflash analysis &  mitigation  methods
ETAP - Arcflash analysis & mitigation methodsHimmelstern
 
DIGITAL TESTING OF HIGH VOLTAGE CIRCUIT BREAKER
DIGITAL TESTING OF HIGH VOLTAGE CIRCUIT BREAKERDIGITAL TESTING OF HIGH VOLTAGE CIRCUIT BREAKER
DIGITAL TESTING OF HIGH VOLTAGE CIRCUIT BREAKERRitesh Kumawat
 
Power factor corrector
Power factor correctorPower factor corrector
Power factor correctorJoeChueng
 
DPL Transmission And Distribution
DPL Transmission And DistributionDPL Transmission And Distribution
DPL Transmission And DistributionSubhojeet Sinha ☁
 

Similar to A Comparison of Contemporary Electrical Distribution Equipment Standards (20)

Fusing Metering Voltages for High Capacity Circuits
Fusing Metering Voltages for High Capacity CircuitsFusing Metering Voltages for High Capacity Circuits
Fusing Metering Voltages for High Capacity Circuits
 
Tools and Techniques for Commissioning and Maintaining PV Systems
Tools and Techniques for Commissioning and Maintaining PV SystemsTools and Techniques for Commissioning and Maintaining PV Systems
Tools and Techniques for Commissioning and Maintaining PV Systems
 
Electric drives and controls
Electric drives and controlsElectric drives and controls
Electric drives and controls
 
Power_System_Protection Lecture-1.pdf
Power_System_Protection Lecture-1.pdfPower_System_Protection Lecture-1.pdf
Power_System_Protection Lecture-1.pdf
 
Product presentation usa
Product presentation  usaProduct presentation  usa
Product presentation usa
 
Selective Coordination "The Rest of the Story"
Selective Coordination "The Rest of the Story"Selective Coordination "The Rest of the Story"
Selective Coordination "The Rest of the Story"
 
IEEE Blue Book
IEEE Blue BookIEEE Blue Book
IEEE Blue Book
 
ETAP - Coordination and protecion 2
ETAP -  Coordination and protecion 2ETAP -  Coordination and protecion 2
ETAP - Coordination and protecion 2
 
Selective Coodination
Selective CoodinationSelective Coodination
Selective Coodination
 
Short Circuit, Protective Device Coordination
Short Circuit, Protective Device CoordinationShort Circuit, Protective Device Coordination
Short Circuit, Protective Device Coordination
 
Time current curves
Time current curvesTime current curves
Time current curves
 
Ohiri-Principles-and-Philosophy-of-Protective-Relaying.pptx
Ohiri-Principles-and-Philosophy-of-Protective-Relaying.pptxOhiri-Principles-and-Philosophy-of-Protective-Relaying.pptx
Ohiri-Principles-and-Philosophy-of-Protective-Relaying.pptx
 
Rectifier Operations & Maintenance - Don Olson - 2.4.2020
Rectifier Operations & Maintenance - Don Olson - 2.4.2020Rectifier Operations & Maintenance - Don Olson - 2.4.2020
Rectifier Operations & Maintenance - Don Olson - 2.4.2020
 
Standards
StandardsStandards
Standards
 
ETAP - Arcflash analysis & mitigation methods
ETAP - Arcflash analysis &  mitigation  methodsETAP - Arcflash analysis &  mitigation  methods
ETAP - Arcflash analysis & mitigation methods
 
DIGITAL TESTING OF HIGH VOLTAGE CIRCUIT BREAKER
DIGITAL TESTING OF HIGH VOLTAGE CIRCUIT BREAKERDIGITAL TESTING OF HIGH VOLTAGE CIRCUIT BREAKER
DIGITAL TESTING OF HIGH VOLTAGE CIRCUIT BREAKER
 
Protection and Switchgear
Protection and SwitchgearProtection and Switchgear
Protection and Switchgear
 
ET 5 LESSON 2 TEST EQUIPMENT.pptx
ET 5 LESSON 2 TEST EQUIPMENT.pptxET 5 LESSON 2 TEST EQUIPMENT.pptx
ET 5 LESSON 2 TEST EQUIPMENT.pptx
 
Power factor corrector
Power factor correctorPower factor corrector
Power factor corrector
 
DPL Transmission And Distribution
DPL Transmission And DistributionDPL Transmission And Distribution
DPL Transmission And Distribution
 

More from michaeljmack

Auburn, NY - 200 Years of History 1793-1993
Auburn, NY - 200 Years of History  1793-1993Auburn, NY - 200 Years of History  1793-1993
Auburn, NY - 200 Years of History 1793-1993michaeljmack
 
Auburn High School, Auburn, NY, 1982 Yearbook
Auburn High School, Auburn, NY, 1982 YearbookAuburn High School, Auburn, NY, 1982 Yearbook
Auburn High School, Auburn, NY, 1982 Yearbookmichaeljmack
 
Auburn High School, Auburn, NY, 1980 Yearbook
Auburn High School, Auburn, NY, 1980 YearbookAuburn High School, Auburn, NY, 1980 Yearbook
Auburn High School, Auburn, NY, 1980 Yearbookmichaeljmack
 
Diesel Particulate Filters Control Systems
Diesel Particulate Filters Control SystemsDiesel Particulate Filters Control Systems
Diesel Particulate Filters Control Systemsmichaeljmack
 
Understanding Arc Flash
Understanding Arc FlashUnderstanding Arc Flash
Understanding Arc Flashmichaeljmack
 
Siemens MV GIS Switchgear
Siemens MV GIS SwitchgearSiemens MV GIS Switchgear
Siemens MV GIS Switchgearmichaeljmack
 
Fundamentals of transformer inrush
Fundamentals of transformer inrushFundamentals of transformer inrush
Fundamentals of transformer inrushmichaeljmack
 
Building information modeling
Building information modelingBuilding information modeling
Building information modelingmichaeljmack
 
15 years of experience stator ground fault protection
15 years of experience stator ground fault protection15 years of experience stator ground fault protection
15 years of experience stator ground fault protectionmichaeljmack
 
Emergency, Legally Required and Optional Standby Systems
Emergency, Legally Required and Optional Standby SystemsEmergency, Legally Required and Optional Standby Systems
Emergency, Legally Required and Optional Standby Systemsmichaeljmack
 
Lighting Control Solutions for Daylit Spaces
Lighting Control Solutions for Daylit SpacesLighting Control Solutions for Daylit Spaces
Lighting Control Solutions for Daylit Spacesmichaeljmack
 
COPS: An Arresting Look at NEC Article 708
COPS: An Arresting Look at NEC Article 708COPS: An Arresting Look at NEC Article 708
COPS: An Arresting Look at NEC Article 708michaeljmack
 
Seismic Compliance of Electrical Distribution
Seismic Compliance of Electrical DistributionSeismic Compliance of Electrical Distribution
Seismic Compliance of Electrical Distributionmichaeljmack
 
Generator Set Transient Performance
Generator Set Transient PerformanceGenerator Set Transient Performance
Generator Set Transient Performancemichaeljmack
 
Modeling of a digital protective relay in a RT Digital Simulator
Modeling of a digital protective relay in a RT Digital SimulatorModeling of a digital protective relay in a RT Digital Simulator
Modeling of a digital protective relay in a RT Digital Simulatormichaeljmack
 
Facts on Grid Friendly Wind Plants
Facts on Grid Friendly Wind PlantsFacts on Grid Friendly Wind Plants
Facts on Grid Friendly Wind Plantsmichaeljmack
 
Power Plant Horror Stories
Power Plant Horror StoriesPower Plant Horror Stories
Power Plant Horror Storiesmichaeljmack
 
Blackout Avoidance & Undervoltage Load Shedding
Blackout Avoidance & Undervoltage Load SheddingBlackout Avoidance & Undervoltage Load Shedding
Blackout Avoidance & Undervoltage Load Sheddingmichaeljmack
 
Transformer Fundamentals
Transformer FundamentalsTransformer Fundamentals
Transformer Fundamentalsmichaeljmack
 

More from michaeljmack (20)

Auburn, NY - 200 Years of History 1793-1993
Auburn, NY - 200 Years of History  1793-1993Auburn, NY - 200 Years of History  1793-1993
Auburn, NY - 200 Years of History 1793-1993
 
Auburn High School, Auburn, NY, 1982 Yearbook
Auburn High School, Auburn, NY, 1982 YearbookAuburn High School, Auburn, NY, 1982 Yearbook
Auburn High School, Auburn, NY, 1982 Yearbook
 
Auburn High School, Auburn, NY, 1980 Yearbook
Auburn High School, Auburn, NY, 1980 YearbookAuburn High School, Auburn, NY, 1980 Yearbook
Auburn High School, Auburn, NY, 1980 Yearbook
 
Diesel Particulate Filters Control Systems
Diesel Particulate Filters Control SystemsDiesel Particulate Filters Control Systems
Diesel Particulate Filters Control Systems
 
Understanding Arc Flash
Understanding Arc FlashUnderstanding Arc Flash
Understanding Arc Flash
 
Siemens MV GIS Switchgear
Siemens MV GIS SwitchgearSiemens MV GIS Switchgear
Siemens MV GIS Switchgear
 
Fundamentals of transformer inrush
Fundamentals of transformer inrushFundamentals of transformer inrush
Fundamentals of transformer inrush
 
Building information modeling
Building information modelingBuilding information modeling
Building information modeling
 
15 years of experience stator ground fault protection
15 years of experience stator ground fault protection15 years of experience stator ground fault protection
15 years of experience stator ground fault protection
 
Emergency, Legally Required and Optional Standby Systems
Emergency, Legally Required and Optional Standby SystemsEmergency, Legally Required and Optional Standby Systems
Emergency, Legally Required and Optional Standby Systems
 
Lighting Control Solutions for Daylit Spaces
Lighting Control Solutions for Daylit SpacesLighting Control Solutions for Daylit Spaces
Lighting Control Solutions for Daylit Spaces
 
COPS: An Arresting Look at NEC Article 708
COPS: An Arresting Look at NEC Article 708COPS: An Arresting Look at NEC Article 708
COPS: An Arresting Look at NEC Article 708
 
Seismic Compliance of Electrical Distribution
Seismic Compliance of Electrical DistributionSeismic Compliance of Electrical Distribution
Seismic Compliance of Electrical Distribution
 
Generator Set Transient Performance
Generator Set Transient PerformanceGenerator Set Transient Performance
Generator Set Transient Performance
 
Modeling of a digital protective relay in a RT Digital Simulator
Modeling of a digital protective relay in a RT Digital SimulatorModeling of a digital protective relay in a RT Digital Simulator
Modeling of a digital protective relay in a RT Digital Simulator
 
Facts on Grid Friendly Wind Plants
Facts on Grid Friendly Wind PlantsFacts on Grid Friendly Wind Plants
Facts on Grid Friendly Wind Plants
 
Power Plant Horror Stories
Power Plant Horror StoriesPower Plant Horror Stories
Power Plant Horror Stories
 
Blackout Avoidance & Undervoltage Load Shedding
Blackout Avoidance & Undervoltage Load SheddingBlackout Avoidance & Undervoltage Load Shedding
Blackout Avoidance & Undervoltage Load Shedding
 
Transformer Fundamentals
Transformer FundamentalsTransformer Fundamentals
Transformer Fundamentals
 
Arc Flash
Arc FlashArc Flash
Arc Flash
 

Recently uploaded

(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...ranjana rawat
 
SPICE PARK APR2024 ( 6,793 SPICE Models )
SPICE PARK APR2024 ( 6,793 SPICE Models )SPICE PARK APR2024 ( 6,793 SPICE Models )
SPICE PARK APR2024 ( 6,793 SPICE Models )Tsuyoshi Horigome
 
Architect Hassan Khalil Portfolio for 2024
Architect Hassan Khalil Portfolio for 2024Architect Hassan Khalil Portfolio for 2024
Architect Hassan Khalil Portfolio for 2024hassan khalil
 
College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service NashikCollege Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service NashikCall Girls in Nagpur High Profile
 
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur High Profile
 
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130Suhani Kapoor
 
IMPLICATIONS OF THE ABOVE HOLISTIC UNDERSTANDING OF HARMONY ON PROFESSIONAL E...
IMPLICATIONS OF THE ABOVE HOLISTIC UNDERSTANDING OF HARMONY ON PROFESSIONAL E...IMPLICATIONS OF THE ABOVE HOLISTIC UNDERSTANDING OF HARMONY ON PROFESSIONAL E...
IMPLICATIONS OF THE ABOVE HOLISTIC UNDERSTANDING OF HARMONY ON PROFESSIONAL E...RajaP95
 
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130Suhani Kapoor
 
Biology for Computer Engineers Course Handout.pptx
Biology for Computer Engineers Course Handout.pptxBiology for Computer Engineers Course Handout.pptx
Biology for Computer Engineers Course Handout.pptxDeepakSakkari2
 
Processing & Properties of Floor and Wall Tiles.pptx
Processing & Properties of Floor and Wall Tiles.pptxProcessing & Properties of Floor and Wall Tiles.pptx
Processing & Properties of Floor and Wall Tiles.pptxpranjaldaimarysona
 
Study on Air-Water & Water-Water Heat Exchange in a Finned Tube Exchanger
Study on Air-Water & Water-Water Heat Exchange in a Finned Tube ExchangerStudy on Air-Water & Water-Water Heat Exchange in a Finned Tube Exchanger
Study on Air-Water & Water-Water Heat Exchange in a Finned Tube ExchangerAnamika Sarkar
 
Porous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writingPorous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writingrakeshbaidya232001
 
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur High Profile
 
Introduction to Multiple Access Protocol.pptx
Introduction to Multiple Access Protocol.pptxIntroduction to Multiple Access Protocol.pptx
Introduction to Multiple Access Protocol.pptxupamatechverse
 
IVE Industry Focused Event - Defence Sector 2024
IVE Industry Focused Event - Defence Sector 2024IVE Industry Focused Event - Defence Sector 2024
IVE Industry Focused Event - Defence Sector 2024Mark Billinghurst
 
GDSC ASEB Gen AI study jams presentation
GDSC ASEB Gen AI study jams presentationGDSC ASEB Gen AI study jams presentation
GDSC ASEB Gen AI study jams presentationGDSCAESB
 
What are the advantages and disadvantages of membrane structures.pptx
What are the advantages and disadvantages of membrane structures.pptxWhat are the advantages and disadvantages of membrane structures.pptx
What are the advantages and disadvantages of membrane structures.pptxwendy cai
 
Analog to Digital and Digital to Analog Converter
Analog to Digital and Digital to Analog ConverterAnalog to Digital and Digital to Analog Converter
Analog to Digital and Digital to Analog ConverterAbhinavSharma374939
 
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝soniya singh
 

Recently uploaded (20)

(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
 
SPICE PARK APR2024 ( 6,793 SPICE Models )
SPICE PARK APR2024 ( 6,793 SPICE Models )SPICE PARK APR2024 ( 6,793 SPICE Models )
SPICE PARK APR2024 ( 6,793 SPICE Models )
 
DJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINE
DJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINEDJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINE
DJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINE
 
Architect Hassan Khalil Portfolio for 2024
Architect Hassan Khalil Portfolio for 2024Architect Hassan Khalil Portfolio for 2024
Architect Hassan Khalil Portfolio for 2024
 
College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service NashikCollege Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
 
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
 
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
 
IMPLICATIONS OF THE ABOVE HOLISTIC UNDERSTANDING OF HARMONY ON PROFESSIONAL E...
IMPLICATIONS OF THE ABOVE HOLISTIC UNDERSTANDING OF HARMONY ON PROFESSIONAL E...IMPLICATIONS OF THE ABOVE HOLISTIC UNDERSTANDING OF HARMONY ON PROFESSIONAL E...
IMPLICATIONS OF THE ABOVE HOLISTIC UNDERSTANDING OF HARMONY ON PROFESSIONAL E...
 
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130
 
Biology for Computer Engineers Course Handout.pptx
Biology for Computer Engineers Course Handout.pptxBiology for Computer Engineers Course Handout.pptx
Biology for Computer Engineers Course Handout.pptx
 
Processing & Properties of Floor and Wall Tiles.pptx
Processing & Properties of Floor and Wall Tiles.pptxProcessing & Properties of Floor and Wall Tiles.pptx
Processing & Properties of Floor and Wall Tiles.pptx
 
Study on Air-Water & Water-Water Heat Exchange in a Finned Tube Exchanger
Study on Air-Water & Water-Water Heat Exchange in a Finned Tube ExchangerStudy on Air-Water & Water-Water Heat Exchange in a Finned Tube Exchanger
Study on Air-Water & Water-Water Heat Exchange in a Finned Tube Exchanger
 
Porous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writingPorous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writing
 
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
 
Introduction to Multiple Access Protocol.pptx
Introduction to Multiple Access Protocol.pptxIntroduction to Multiple Access Protocol.pptx
Introduction to Multiple Access Protocol.pptx
 
IVE Industry Focused Event - Defence Sector 2024
IVE Industry Focused Event - Defence Sector 2024IVE Industry Focused Event - Defence Sector 2024
IVE Industry Focused Event - Defence Sector 2024
 
GDSC ASEB Gen AI study jams presentation
GDSC ASEB Gen AI study jams presentationGDSC ASEB Gen AI study jams presentation
GDSC ASEB Gen AI study jams presentation
 
What are the advantages and disadvantages of membrane structures.pptx
What are the advantages and disadvantages of membrane structures.pptxWhat are the advantages and disadvantages of membrane structures.pptx
What are the advantages and disadvantages of membrane structures.pptx
 
Analog to Digital and Digital to Analog Converter
Analog to Digital and Digital to Analog ConverterAnalog to Digital and Digital to Analog Converter
Analog to Digital and Digital to Analog Converter
 
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝
 

A Comparison of Contemporary Electrical Distribution Equipment Standards

  • 1. A Comparison of Contemporary Electrical Distribution Equipment Standards San Francisco IEEE Industry Applications Society May 26, 2009
  • 2. What are “Standards”? • Clearly defined performance characteristics • Based on tested performance under expected worse case parameters • Generally based on third party certification of tested performance • Vendor or supplier independent Provide the basis for objective based comparison of performance under expected conditions of operation
  • 4. Contemporary Standard -- Octane • RON = Research Octane Number (fuel based); MON = Motor Octane Number (load/timing based) • PON = Pump Octane Number; PON = (RON + MON)/2 • Uniform among suppliers to allow selection of proper grade by users, BUT, • Does not prevent misapplication due to perception • Does not insure all suppliers offer the same product/features • Can be revenue/margin tool for vendor
  • 5. High Octane – Premium Unleaded
  • 6. Low Octane – Regular Unleaded
  • 7. What Rating is Required?
  • 8. Electrical Distribution Equipment • Divides Larger Amounts of Power into Smaller “Chunks” • Can contain control and metering/monitoring devices • Contains protective feeder devices whose prime role is to protect feeders • Low Voltage Application include Panelboards, Switchboards, Switchgear
  • 9. Watt’s Engine James Watt 1736 -- 1819 E = IR W = EI 746 Watts = 1 Horsepower 600 Amps @ 480V 3ph = 665 HP 10,000 Amps @ 120V 1ph = 1600 HP
  • 10. Office Building 65,000 AIC @ 480V = 72,300 HP
  • 11. Medium Voltage 40,000 AIC @ 13,800V = 1,300,000 HP
  • 14. Interaction in Equipment x • Opening Contacts Create Arcing • Arcing Creates Resistance • Resistance Reduces Current Flow • Reduced Current Flow Can Affect Opening Speed • Reduced Opening Speed Will Affect Energy Flow
  • 15. Dynamic Interactions • Individual devices react to what they see ▫ Circuit Breakers react to over current or short circuit conditions ▫ Relays operate based on on conditions sensed • Individual devices react to the reaction of other devices ▫ A circuit breaker that is tripping (opening under load) will affect the current and voltage seen by other devices
  • 16. Selectivity Can Be Impacted x • Depending on fault level, more than one device can open on a downstream fault • Loads without faults can be affected or interrupted • Entire systems can be shutdown by downstream faults • May be part of design for series ratings
  • 17. Possible Conditions of Operation • High Energy Levels – Need to insure proper operation at possible fault levels • Dynamic Interaction – Need to understand possible device interactions under fault conditions • Selectivity – Need to insure required selectivity under all potential fault conditions BUT, • Cost – Need to meet all performance requirements within budgetary constraints
  • 18. LV Equipment Standards • NEMA –Switchboards PB-2/Switchgear SG-5 ▫ No longer writing standards; still responsible for certain breaker testing standards • ANSI – Switchgear C37.20 ▫ Publishes standards; no longer creates standards for electrical equipment • IEEE – Switchgear C 37.20 ▫ Develops standards for equipment/breakers • UL – Switchboards UL 891/Switchgear UL 1558 ▫ Both develops standards and serves as third party certifier of devices and systems
  • 19. Switchboards or Switchgear • Terms often used interchangeably by many in industry; Switchgear is generic term • Per NEC Article 100, difference is far from contemporary. • Objective differences now defined by UL/ANSI standards for equipment BUT, • Many design elements can overlap • Common components possible
  • 20. Devices, not Equipment are Key • OCPD (Over Current Protective Devices) determine the operational characteristics of the equipment • Application of OCPDs determines equipment type (equipment standards) • As in most cases, compromises may be required to obtain optimal solution for particular situation
  • 21. Circuit Breakers LV Power Circuit Breakers Molded Case Circuit Breakers • Since 1985, LV Power Circuit Breakers listed under UL 1066 • Formerly under ANSI C37.13 and C37.50 (not UL) • Classic design was iron frame; most now enclosed with non- metallic materials • Allow for maintenance of internal parts for long service life • Higher performance and higher cost • Listed under UL 489 • Includes “insulated” case circuit breakers • Classic design was toggle type thermosetting or thermoplastic sealed case • Sealed case prevents normal maintenance • Tend to be lower cost than Power Circuit Breakers • High AIC ratings possible
  • 22. LV Power Breakers Evolution 1999 1999? 2001 20052002 2007 ?
  • 23. Key Differences UL 489 vs. UL 1066 • Higher endurance testing for UL 1066 at all ratings (e.g., 800A – 500 cycles UL 489; 800 cycles UL 1066 at FLA) • Short time withstand test required for UL 1066 rating – maintain high level current for 0.5 seconds • Single pole testing for UL 1066 • Different power factor requirements for testing • Different heat rise requirements for testing
  • 24. Switchboards or Switchgear -- UL • Switchgear listed to UL 1558 since 1982 • Based on ANSI C37 standards • Uses UL 1066 listed breakers • Generally requires rear access for load and incoming connections • “Compartmentalized” Construction with breaker compartment for each device • Tested to short circuit rating for 4 cycles (.067 seconds) • Tested to short time rating for 30 cycles (0.5 seconds) • Heat Rise tested Bussing • Switchboards listed to UL 891 • Uses UL 891 or UL 1066 listed breakers • Can be front connected without rear access requirements • Devices can be individually (vertically) or group (panel/horizontally) mounted • Tested to short circuit rating of 3 cycles (.05 seconds) or to instantaneous trip of tested OCPD or braced to UL configuration standards • Heat Rise Tested or Density Rated
  • 25. Why Require UL1558/UL1066? • Allows use of tested assemblies/devices without instantaneous trips for selectivity ▫ May be required to allow for slower relays for differential protection ▫ Will insure selectivity to limit of short time ratings (to instantaneous over ride limits) • May provide features/designs not available in UL 891 products from some manufacturers ▫ Insulated and/or isolated bussing ▫ Protected wire ways for LV controls
  • 26. Selectivity Can Be Restored • By eliminating instantaneous on one or more levels, selectivity can be maintained • Arc Flash protection can be enhanced by differential relaying or arc flash relays •Requires UL 1558 equipment for LV applications wherever instantaneous protections is eliminated x
  • 27. Why Not? • Unless features/characteristics are not available in UL 891, UL 1558 equipment tends to be more costly. ▫ GE study showed 1.6 to 2.0 unit cost difference between equivalent UL 891 and UL 1558 assemblies • Rear access may not be available ▫ Foot prints may be similar in square footage; required space may vary due to rear clearance requirements • UL 1066 devices can be used in UL 891 equipment ▫ Some manufacturers offer equivalent UL 489 devices; others only offer UL 1066 devices ▫ Can NOT “turn off” instantaneous trip and maintain UL • Unusual busing configurations may not be available in UL 1558 equipment ▫ Only tested configurations are possible in UL 1558; UL 891 can use approved bracing configurations to create “custom” configurations.
  • 28. Diesel – The European Standard
  • 30. IEC Standards • IEC 60439 -1 (Low Voltage Switchgear and Controlgear Assemblies) ▫ Can be either TTA (Type Tested Assembly) or PTTA (Partially Type Tested Assembly) ▫ PTTA requires calculations for those parts not type tested ▫ Includes both Switchgear and Switchboard equivalents • IEC 60947 (Low Voltage Power Circuit Breakers) • IEC 298 (Medium Voltage Switchgear and Controlgear Assemblies ▫ Includes both metal enclosed and metal clad equivalents
  • 32. Typical MV Configuration LV Controls Breaker Compartment Cable Termination Tie Bus PT Compartment
  • 33. IEC Adaptations • Many components originally designed for IEC markets successfully adapted/modified to meet UL standards • IEC electrical equipment products generally not yet adapted to UL standards although efforts are ongoing • IEC MV equipment successfully adapted to CSA standards (required some IEEE/ANSI testing) • Increased demand for IEC equipment by users • Often supplied as part of other equipment for food processing or similar applications
  • 34. Final Notes • Knowledge of standards and implications will drive most cost effective solutions for varied applications – one size does NOT fit all • Differentiating between what is required by standards and what is desired for the particular application (particularly on features) will allow more choices as to suppliers • Final acceptance of equipment is dependent on local authorities (AHJ). Independent certification of standards will usually insure acceptance.