SlideShare a Scribd company logo
1 of 20
Download to read offline
IEC 61439
The new standard for low-voltage
switchgear and controlgear assEmblies
11 | 2010
2 IEC 61439 – The new standard
IEC 61439 – The new standard 3
Content
	 Page
	
Introduction .
....................................................................... 4
The current IEC 60439 .
....................................................... 5
The new IEC 61439 ............................................................ 6
Main changes ..................................................................... 7
Responsibilities .................................................................12
FAQ ..................................................................................14
Summary and conclusion....................................................16
4 IEC 61439 – The new standard
A low-voltage switchgear and controlgear assembly
(ASSEMBLY) is a combination of low-voltage switching
devices together with associated equipment (for control-
ling, measuring, signalling, etc.) complete with all the
internal mechanical and electrical interconnections and
structural parts. As with every component of an electrical
installation, the ASSEMBLY also has to comply with its
appropriate standard.
In January 2009 the IEC 61439, the new standard for low-
voltage switchgear and controlgear ASSEMBLIES, was
published. This was the aim of an international project group
which had been working on a task named ”radical restructuring
and revision of IEC 60439 series” since 1998. This initiative
was introduced by several countries following dissatisfaction
with the IEC 60439 series. The purpose was to harmonise
and define all general requirements for low-voltage electrical
ASSEMBLIES.
Reaching an agreement has proven extremely challenging,
but the first parts of the new standards have been published.
For each type of electrical ASSEMBLY only two parts of the
standard are necessary to determine all requirements:
the basic standard IEC 61439-1 “General rules”
−
−
the specific ASSEMBLY standard
−
−
The aim of this guide is to allow panel builders, electrical
installers, planners or purchasers to familiarise themselves
with the new standards and to point out the main changes
that have been introduced as well as elements that remain
unchanged.
Introduction
IEC 61439 – The new standard 5
The current IEC 60439
The current IEC 60439 standard applies to enclosures
for which the rated voltage is under or equal to 1000 V AC
(at frequencies not exceeding 1000 Hz) or 1500 V DC.
The standard makes a distinction between type-tested
assemblies (TTA) and partially type-tested assemblies
(PTTA).The following parts are mentioned and have equal
weighting. There is not a formal hierarchy. Each part is a
complete entity and can be used on an individual basis:
IEC 60439-1
type-tested and partially type-tested assemblies
IEC 60439-2
particular requirements for busbar trunking systems
(busways)
IEC 60439-3
particular requirements for low-voltage switchgear and
controlgear assemblies which are to be installed in locations
where unskilled persons have access for their use.
IEC 60439-4
particular requirements for assemblies for
construction sites (ACS)
IEC 60439-5
particular requirements for assemblies intended
to be installed outdoors in public places – Cable distribution
cabinets (CDCs) for power distribution in networks
The standard remains valid until 2014
6 IEC 61439 – The new standard
IEC 61439-1
Relationship between the two standards
is as shown in the table below:
IEC 61439-2 replaces
IEC 60439-1
(still valid until 2014)
IEC 61439-6 will replace
IEC 60439-2
(still valid)
IEC 61439-3 will replace
IEC 60439-3
(still valid)
IEC 61439-4 will replace
IEC 60439-4
(still valid)
IEC 61439-5 will replace
IEC 60439-5
(still valid)
The new IEC 61439 standard applies to enclosures
for which the rated voltage is under 1000 V AC
(at frequencies not exceeding 1000 Hz) or 1500 V DC.
The standard defines the design verified ASSEMBLIES
and eliminates completely the categories TTA and PTTA.
In order to conform to the standard, type tests have been
replaced by a design verification which can be carried
out by the three following equivalent and alternative
methods: testing, calculation/measurement or
application of design rules.
The following parts are mentioned and do not have equal
weighting. There is a formal hierarchy. Each part can not be
used individually:
IEC 61439-1
−
− “General rules“
IEC 61439-2
−
− “Power switchgear and
controlgear ASSEMBLIES”
IEC 61439-3
−
− “Distribution boards“
IEC 61439-4
−
− “ASSEMBLIES for construction sites”
IEC 61439-5
−
− “ASSEMBLIES for power distribution”
IEC 61439-6
−
− “Busbar trunking systems”
Part 1 is the general rules part and cannot be used alone to
specify an ASSEMBLY.
Part 2 defines the specific requirements of power switchgear
and controlgear ASSEMBLIES (PSC ASSEMBLIES) and must
be used with Part 1. This is the only part that has a double
role, it covers PSC ASSEMBLIES and any ASSEMBLY which
is not covered by any other specific parts.
Parts 3-X are still under preparation but are already men-
tioned in Part 1. These could be more than four, as additional
parts may be developed as the need arises.
Summarising: With the currently used IEC 60439, the rule
is “one part for each type of ASSEMBLY”. With the new
IEC 61439 the rule is “two parts for each type of ASSEM-
BLY”. The compliance of an ASSEMBLY is declared refer-
ring to the specific ASSEMBLY standard (e.g. IEC 61439-2),
and the compliance with the general rules (IEC 61439-1) is
always implicit. The sentence “TTA switchgear according to
IEC 60439-1“ is now replaced by “Power switchgear and
controlgear ASSEMBLIES according to IEC 61439-2, design
verified ASSEMBLY“.
The validity of the two standards will overlap until 2014 and
prior to this date, ASSEMBLIES can be manufactured accord-
ing to IEC 61439 or IEC 60439.
The new IEC 61439
IEC 61439 – The new standard 7
The new IEC 61439 includes the following significant
technical changes with respect to the last edition of
IEC 60439.
Responsibility split:
New terms have been introduced and there is a split in
product responsibility between the “Original manufacturer”
(e.g. ABB, responsible for carrying out the original design
and the associated verification of an ASSEMBLY)
and the “ASSEMBLY manufacturer” (e.g panel builder
using an ASSEMBLY system from an Original Manufacturer)
assuming responsibility for the completed ASSEMBLY.
The Assembly Manufacturer may be a different organisation
to the Original Manufacturer. Where the ASSEMBLY Manu-
facturer introduces changes to the ASSEMBLY configuration
tested by the Original Manufacturer, he is deemed to be the
Original Manufacturer in respect of these changes and has to
carry out the design verification.
Design verification replaces TTA and PTTA categories:
Design verification replaces type tests so the discrimination
between type-tested assemblies (TTA) and partially type-
tested assemblies (PTTA) is eliminated.
Three different but equivalent types of verification of
requirements are introduced:
Verification by testing (test made on a sample of an ASSEM-
BLY or on parts of ASSEMBLIES to verify that the design
meets the appropriate requirements. This method is equiva-
lent to the currently implemented type tests).
Verification by calculation/measurement (calculations applied
to a sample of an ASSEMBLY or to parts of ASSEMBLIES to
show that the design meets the appropriate requirements).
Verification by application of design rules (specified rule to
verify the design of an ASSEMBLY).
The selection of the appropriate verification method has to be
made according to annex D, which explains the available veri-
fication options for each characteristic which is to be verified,
as shown in the table below:
Main changes –
More than a single digit change…
Characteristic to be verified
Verification options available
Verification
by testing
Verification
by calculation
Verification
by design rules
10.2 Strength of material and parts Yes No No
10.3 Degree of protection of enclosures Yes No Yes
10.4 Clearances and creepage distances Yes Yes Yes
10.5.2 Effective continuity between parts and PE Yes No No
10.5.3 Effectiveness of the ASSEMBLY for external faults Yes Yes Yes
10.6 Incorporating of apparatus No No Yes
10.7 Internal electrical circuits and connections No No Yes
10.8 Terminals for external conductors No No Yes
10.9.2 Power frequency withstand voltage Yes No No
10.9.3 Impulse withstand voltage Yes No Yes
10.10 Temperature rise limits Yes Yes Yes
10.11 Short-circuit withstand strength Yes Yes Yes
10.12 EMC Yes No Yes
10.13 Mechanical operation Yes No No
8 IEC 61439 – The new standard
system
manufacturer
manufacturer
of
the
ASSEMBLY
ASSEMBLY
low-voltage switchgear and controlgear ASSEMBLIES
type tests for verification of conformity
TTA
type-tested ASSEMBLIES
type-tested units not type-tested units
PTTA
partial type-tested
ASSEMBLIES
routine test
completed ASSEMBLY
IEC 60439
Tests that have been made in accordance with IEC 60439
and that fulfil the requirements of the new IEC 61439 need
NOT be repeated.
The second stage verification is the routine verification. This
is performed to verify that the materials and workmanship are
in accordance with the requirements of the standard. Rou-
tine verification replaces the current “routine test”. It is more
detailed but essentially the new requirements are the same
as in the IEC 60439. This verification has to be carried out for
each completed ASSEMBLY and it is the responsibility of the
ASSEMBLY Manufacturer.
Main changes –
More than a single digit change…
Comparison between the current and the new verification “flow”:
IEC 61439 – The new standard 9
original
manufacturer
ASSEMBLY
manufacturer
original
manufacturer
ASSEMBLY
low-voltage switchgear and controlgear ASSEMBLIES
testing calculation
ASSEMBLY system
application of design rules
routine verification
The ASSEMBLY manufacturer can decide:
– to manufacture the ASSEMBLY according to the guidelines of the original manufacturer
– t
o deviate from the guidelines of the original manufacturer. Where the ASSEMBLY
	 manufacturer incorporates his own arrangements not included in the original manufacturer’s 	
	 verification, the ASSEMBLY manufacturer is deemed to be the original manufacturer
	 in respect of these arrangements.
completed ASSEMBLY
IEC 61439
design verification carried out by the original manufacturer
10 IEC 61439 – The new standard
Tests described in IEC 61439-1 in comparison with the type tests described in IEC 60439
Additional verification:
New requirements from the standard IEC 62208
(Empty enclosures for ASSEMBLIES) have been added:
verification of resistance to UV radiation for
−
−
outdoor plastic enclosures
verification of corrosion resistance
−
−
mandatory declaration and confirmation of
−
−
an impulse rating
lifting, mechanical impact and marking
−
−
Other changes
Temperature rise
Temperature rise requirements have been explained more
clearly and have been adapted to the state of the art.
One of the following methods is allowed for verification:
testing with current
−
−
derivation (from a tested design)
−
−
of ratings for similar variants
calculation
−
−
(see also “FAQ” chapter)
Main changes –
More than a single digit change…
No. Characteristics to be verified Clause/Subclause
Comparable type test
from 60439-1
1 Strength of material and parts 10.2 Not required as
“Type test” but as
“Design and
construction” rules
on paragraph 7 or on
subsidiary standard
Resistance to corrosion 10.2.2
Properties of insulating materials 10.2.3
Thermal stability 10.2.3.1
Resistance of insulating materials to normal heat 10.2.3.2
Resistance to abnormal heat and fire due to internal electric effects 10.2.3.3
Resistance to ultra-violet (UV) radiation 10.2.4
Lifting 10.2.5
Mechanical impact 10.2.6
Marking 10.2.7
2 Degree of protection of enclosures 10.3 8.2.7
3 Clearances and creepage distances 10.4 8.2.5
4 Protection against electric shock and integrity of protective circuits 10.5
8.2.4
Effective continuity between the exposed conductive
parts of the ASSEMBLY and the protective circuit
10.5.2
Effectiveness of the ASSEMBLY for external faults 10.5.3
5 Incorporation of switching devices and components 10.6 Not required as
“Type test” but as
“Design and
construction” rules
on paragraph 7 or on
subsidiary standard
6 Internal electrical circuits and connections 10.7
7 Terminals for external conductors 10.8
8 Dielectric properties 10.9
8.2.2
Power -frequency withstand voltage 10.9.2
Impulse withstand voltage 10.9.3
9 Temperature rise limits 10.10 8.2.1
10 Short-circuit withstand strength 10.11 8.2.3
11 Electromagnetic compatibility (EMC) 10.12 + Annex J 8.2.8 + Annex H
12 Mechanical operation 10.13 8.2.6
IEC 61439 – The new standard 11
RDF
The rated diversity factor is covered in more detail. In
practice it is assumed that multiple functional units are not
fully loaded simultaneously. (see also “FAQ” chapter)
Labels
Labels have to be subjected to testing to verify their legibility.
The following information is required on the label:
ASSEMBLY Manufacturer‘s name
−
−
Identification number
−
−
Date of manufacture (NEW!)
−
−
IEC 61439-X (the specific part “X” has to be specified)
−
−
(NEW!)
“Grey” areas
A number of “grey” areas have been clarified:
neutral conductors will have a current rating equal to 50%
−
−
of the corresponding phases if not otherwise specified
agreements between Customer and Manufacturer have
−
−
been more detailed, extended and listed in annex C
it is mandatory to specify the rated current of the
−
−
ASSEMBLY
a technical report IEC 61439-0 “Guide for specifying
−
−
ASSEMBLIES” is under development for a better
understanding of the new standard
questions regarding the internal form of separation
−
−
have been clarified
(e.g. a moulded case circuit breaker’s casing provides
separation from other functional units)
Summary table with the main changes
IEC 60439	 IEC 61439
IEC 60439-1
Type-tested and partially type-tested assemblies
IEC 61439-2
Design verified ASSEMBLIES
Mix of different rules and demands in each part Clear structure:
IEC 61439-1	 “General rules“
IEC 61439-2 … -6	 “Subsidiary parts” (product standard)
Each part is a complete entity and can be used on an individual basis Each “subsidiary part” is based on the “general rules” (Part 1)
and includes only the specific additional rules for the specific product
Testing each type of assembly:
Partially type-tested or type-tested
Three alternative methods for verification:
Test, calculation/measurement, design rules
Annex E:
Agreements between Customer and Manufacturer
Annex C:
Agreements between Customer and Manufacturer are
more detailed and extended
Shared responsibility:
Original Manufacturer vs. ASSEMBLY Manufacturer
Technical changes and clarifications:
Diversity factor, verification of temperature rise,
mechanical characteristics, neutral conductor 50%,
additional verification (from IEC 62208)
12 IEC 61439 – The new standard
Some hypothetical examples:
An Original Manufacturer (e.g. ABB) assembles a
complete ASSEMBLY and sells it to a panel builder
–	
the panel builder is only the ASSEMBLY Manufacturer,
if he installs the ASSEMBLY as it is.
– 	
the panel builder is the ASSEMBLY Manufacturer and
becomes the Original Manufacturer if he makes some
modifications to the ASSEMBLY.
A panel builder assembles a complete ASSEMBLY
(according to the rules of the Original manufacturer)
–	
the panelbuilder is the ASSEMBLY Manufacturer and
is responsible for the ASSEMBLY, providing the electrical
installer installs the ASSEMBLY without making any
alterations.
A panel builder assembles a complete ASSEMBLY
(according to the rules of the Original manufacturer) that
has been partially assembled by an external supplier
–	
the panel builder is the ASSEMBLY Manufacturer and
is responsible for the ASSEMBLY.
With regard to responsibilities, the general and obvious
rule is: the manufacturer of the ASSEMBLY is responsible
for the ASSEMBLY!
For a better explanation of this concept we can say:
the Original Manufacturer usually makes design verifications
and assumes responsibility for the proper functionality of
prototype ASSEMBLIES. He provides a portfolio of verified
ASSEMBLIES and each “actor” in the electrical market, who
becomes the ASSEMBLY Manufacturer, can manufacture
a design verified ASSEMBLY by following the instructions
supplied in the Original Manufacturer´s instruction manual or
catalogue; the ASSEMBLY Manufacturer assumes responsibil-
ity for the ASSEMBLY, he labels the ASSEMBLY and it is his
responsibility to declare that the ASSEMBLY complies with the
relevant standards. In practice he has two options:
he decides to manufacture the ASSEMBLY according to
−
−
the rules of the Original Manufacturer. In this case, the
ASSEMBLY Manufacturer has to perform only the second
stage verification, namely routine verification.
he decides NOT to manufacture the ASSEMBLY according
−
−
to the rules of the Original Manufacturer. In this case, the
ASSEMBLY Manufacturer incorporates his own arrange-
ments, so that he is deemed to be the Original Manufacturer.
Regarding these arrangements and he must then carry
out both the first and the second stage verification: design
verification and routine verification.
Responsibilities
IEC 61439 – The new standard 13
14 IEC 61439 – The new standard
FAQ
Is it possible to substitute a device within an
ASSEMBLY? What about temperature rise and short
circuit strength?
The new IEC 61439 clearly defines a device substitution in
respect of temperature rise and short circuit strength.
Temperature rise: it is possible to substitute a device without
repeating the design verification, provided that the new device
from the same or another series has identical or better values,
regarding power loss and terminal temperature rise, in com-
parison with those of the original device, as tested in accord-
ance with the product standard.
Short circuit: it is possible to substitute a device without
repeating the design verification, provided that the new device
is identical. If different, it has to be from the same manufactur-
er who has to certify that it is equivalent or better with regard
to all relevant short circuit characteristics.
Is the verification of the short circuit withstand strength
required for all circuits of an ASSEMBLY?
No, it is not required for:
An ASSEMBLY having a rated short-time withstand current
−
−
or rated conditional short circuit current not exceeding
10 kA r.m.s.
An ASSEMBLY protected by current-limiting devices having
−
−
a cut-off current not exceeding 17 kA at the maximum
permitted prospective short-circuit current at the terminals
of the incoming circuit of the ASSEMBLY.
Auxillary circuits of an ASSEMBLY intended to be connect-
−
−
ed to transformers whose rated power does not exceed
10 kVA for a rated secondary voltage of not less than 110 V,
or 1.6 kVA for a rated secondary voltage less than 110 V,
and whose short circuit impedance is not less than 4%.
All other circuits have to be verified.
Until what point is it possible to manufacture and to
install ASSEMBLIES in accordance with IEC 60439?
The validity of the two standards will overlap until 2014 and
prior to this date, ASSEMBLIES can be manufactured accord-
ing to IEC 61439 or IEC 60439.
If tests on the ASSEMBLY have been conducted in
accordance with IEC 60439, is it necessary to repeat
them in accordance with the new IEC 61439?
No, if the conducted test results fulfil the requirements of
the new IEC 61439 it is not necessary to repeat them.
It is necessary to test only the additional verification that
has been introduced by the new standard.
Is it possible to manufacture an ASSEMBLY in accordance
with the new IEC 61439, with enclosures from ABB,
busbars from another manufacturer, circuit breakers from
another manufacturer, etc.?
Yes, it is possible but it is not easy and it is expensive. The
panel builder that decides to mix different “elements” from dif-
ferent manufacturers is not only the ASSEMBLY Manufacturer,
but becomes the Original Manufacturer and has to perform
both the first and the second stage verification: design verifi-
cation and routine verification.
The routine verification is similar to the present routine test
and is relatively straightforward. The design verification how-
ever includes some characteristics which are easily verified,
and others that can only be verified through laboratory
testing.
What is the Rated Diversity Factor (RDF)?
The RDF is the per unit value of the rated current, to which
outgoing circuits of an ASSEMBLY can be continuously and
simultaneously loaded (the mutual thermal influences have to
be taken into account). It can be declared for groups of
circuits or for the whole ASSEMBLY. The RDF has to be as-
signed by the ASSEMBLY Manufacturer (if not specified it is
assumed to be equal to 1). In practice it is recognised that not
all circuits in an ASSEMBLY operate at rated current
continuously and this allows efficient use of materials and
resources.
IEC 61439 – The new standard 15
Does the verification of temperature
rise remain unchanged?
Temperature rise requirements have been explained in further
detail. Three different methods are now allowed for verification
(the Original Manufacturer is responsible for choosing the
suitable verification methods):
1) 
Testing with current:
Three different test methods are permitted and the Original
Manufacturer has to determine the best method. When
a number of variants of an ASSEMBLY have to be verified,
the most onerous configuration has to be tested and the
ratings of the less onerous (and similar) variants can be
derived without testing.
2) 
Derivation:
(from a tested design) of ratings for similar variants
The standard defines a series of sub-clauses that help
define, how non-tested variants can be verified by
derivation from similar arrangements verified by test.
3) 
Calculation:
two calculation methods are allowed
Single compartment ASSEMBLY with rated current not
−
−
exceeding 630 A (done by calculating the total power loss
of the ASSEMBLY if certain conditions are fulfilled).
Multiple compartment ASSEMBLY with rated current not
−
−
exceeding 1600 A (done by calculation in accordance with
the method of IEC 60890 if certain conditions are fulfilled).
Flow chart to establish how to verify the temperature rise
InA
≤ 630 A
Single
compartment?
Yes
Yes
Yes
Yes No
Yes
No
No
No
No
InA
≤ 1600 A
Are the IEC 61439
and IEC 60890
conditions fulfilled?
Are the IEC 61439
conditions fulfilled?
Calculation in accordance
with IEC 60890
Testing with current OR
derivation (if a tested prototype is available)
Calculation of the
total power loss
16 IEC 61439 – The new standard
Summary and conclusion
The new standard IEC 61439 introduces important
modifications in comparison with the current standard
IEC 60439 on low-voltage switchgear and controlgear
ASSEMBLIES.
The structure of the new standard is clearer with a general
part and product specific parts. New definitions have been
written (e.g. “Original Manufacturer” and “ASSEMBLY Manu-
facturer”). New compulsory characteristics have to be specified
(e.g. rated current of the ASSEMBLY).
A new “design verified ASSEMBLY” concept has been speci-
fied. This new concept completely discards the categories
TTA and PTTA, and the compliance of an ASSEMBLY can now
not only be verified by means of tests, but also with alterna-
tive methods: calculation/measurement and design rules.
The new standard is more precise, eradicating the “grey”
areas contained in the previous standard. The responsibilities
for an ASSEMBLY are clearly defined, making the job of each
“actor” on the electrical market easier nowadays.
18 IEC 61439 – The new standard
Notes
Contact us
You can find the address of your local sales organisation
on the ABB homepage:
www.abb.com/contacts
 Low Voltage Products and Systems
K-0119-KM-11/2010-V1
·
2CPC
000
119
L0201
Note: We reserve the right to make technical changes or modify
the contents of this document without prior notice. With regard
to purchase orders, the agreed particulars shall prevail.
ABB AG does not accept any responsibility whatsoever for poten-
tial errors or possible lack of information in this document.
We reserve all rights in this document and in the subject matter
and illustrations contained therein. Any reproduction, disclosure to
third parties or utilization of its contents – in whole or in parts – is
forbidden without prior written consent of ABB AG.
Copyright © 2010 ABB
All rights reserved

More Related Content

What's hot

SWITCHYARD EQUIPMENTS & PROTECTION SYSTEMS
SWITCHYARD EQUIPMENTS & PROTECTION SYSTEMSSWITCHYARD EQUIPMENTS & PROTECTION SYSTEMS
SWITCHYARD EQUIPMENTS & PROTECTION SYSTEMS
Partha Parida
 
Transformer & OLTC
Transformer & OLTCTransformer & OLTC
Transformer & OLTC
Rohit Dave
 
Transformer design and protection
Transformer design and protectionTransformer design and protection
Transformer design and protection
ashwin fcc
 

What's hot (20)

220 KV Substation Operation & Maintenance
220 KV Substation Operation & Maintenance220 KV Substation Operation & Maintenance
220 KV Substation Operation & Maintenance
 
UNIT - 05 DISTRIBUTION LINES AND TRANSFORMER CENTRE
UNIT - 05 DISTRIBUTION LINES AND TRANSFORMER CENTREUNIT - 05 DISTRIBUTION LINES AND TRANSFORMER CENTRE
UNIT - 05 DISTRIBUTION LINES AND TRANSFORMER CENTRE
 
Power System Protection basics
Power System Protection basicsPower System Protection basics
Power System Protection basics
 
Power system protection topic 1
Power system protection topic 1Power system protection topic 1
Power system protection topic 1
 
Iec standards
Iec standardsIec standards
Iec standards
 
SWITCHYARD EQUIPMENTS & PROTECTION SYSTEMS
SWITCHYARD EQUIPMENTS & PROTECTION SYSTEMSSWITCHYARD EQUIPMENTS & PROTECTION SYSTEMS
SWITCHYARD EQUIPMENTS & PROTECTION SYSTEMS
 
Introduction to mv switchgear
Introduction to mv switchgearIntroduction to mv switchgear
Introduction to mv switchgear
 
Load list calculation
Load list calculationLoad list calculation
Load list calculation
 
ELECTRICAL SYSTEMS
ELECTRICAL SYSTEMSELECTRICAL SYSTEMS
ELECTRICAL SYSTEMS
 
Bill of Material of 132/33 KV 15 MVA Pooling Substation (15-07-2019)
Bill of Material of 132/33 KV 15 MVA Pooling Substation (15-07-2019)Bill of Material of 132/33 KV 15 MVA Pooling Substation (15-07-2019)
Bill of Material of 132/33 KV 15 MVA Pooling Substation (15-07-2019)
 
Transformer & OLTC
Transformer & OLTCTransformer & OLTC
Transformer & OLTC
 
Power system protection
Power system protectionPower system protection
Power system protection
 
HT and LT SWITCHGEAR
HT and LT SWITCHGEARHT and LT SWITCHGEAR
HT and LT SWITCHGEAR
 
Design of substation
Design of substationDesign of substation
Design of substation
 
SUB-STATION DESIGN AND PROTECTION (AN OVERVIEW)
SUB-STATION DESIGN AND PROTECTION  (AN OVERVIEW)SUB-STATION DESIGN AND PROTECTION  (AN OVERVIEW)
SUB-STATION DESIGN AND PROTECTION (AN OVERVIEW)
 
Transformers protection, an introduction
Transformers protection, an introductionTransformers protection, an introduction
Transformers protection, an introduction
 
Protective relaying
Protective relayingProtective relaying
Protective relaying
 
Lightning arrester
Lightning arresterLightning arrester
Lightning arrester
 
Transformer design and protection
Transformer design and protectionTransformer design and protection
Transformer design and protection
 
Protection and Switchgear
Protection and SwitchgearProtection and Switchgear
Protection and Switchgear
 

Similar to Iec 61439 for_low_voltage_switchgear_and

Analysis and Design of Low-Voltage Power Systems An Engineers Field Guide by ...
Analysis and Design of Low-Voltage Power Systems An Engineers Field Guide by ...Analysis and Design of Low-Voltage Power Systems An Engineers Field Guide by ...
Analysis and Design of Low-Voltage Power Systems An Engineers Field Guide by ...
ssuser1492d5
 
1sdc007106g0201(1)
1sdc007106g0201(1)1sdc007106g0201(1)
1sdc007106g0201(1)
ELIMENG
 
1sdc007106g0201
1sdc007106g02011sdc007106g0201
1sdc007106g0201
ELIMENG
 
17th Edition Part 6
17th Edition  Part 617th Edition  Part 6
17th Edition Part 6
Paul Holden
 

Similar to Iec 61439 for_low_voltage_switchgear_and (20)

A study on IEC 60947- 2 amendments
A study on IEC 60947- 2 amendmentsA study on IEC 60947- 2 amendments
A study on IEC 60947- 2 amendments
 
FAQ's: new-switchboard-standard-as-nzs-61439
FAQ's: new-switchboard-standard-as-nzs-61439FAQ's: new-switchboard-standard-as-nzs-61439
FAQ's: new-switchboard-standard-as-nzs-61439
 
Benefits of using iec 61439 standard in electrical busbar systems
Benefits of using iec 61439 standard in electrical busbar systemsBenefits of using iec 61439 standard in electrical busbar systems
Benefits of using iec 61439 standard in electrical busbar systems
 
Abb lv breakers working with trip curves
Abb lv breakers working with trip curvesAbb lv breakers working with trip curves
Abb lv breakers working with trip curves
 
DIGITAL TESTING OF HIGH VOLTAGE CIRCUIT BREAKER
DIGITAL TESTING OF HIGH VOLTAGE CIRCUIT BREAKERDIGITAL TESTING OF HIGH VOLTAGE CIRCUIT BREAKER
DIGITAL TESTING OF HIGH VOLTAGE CIRCUIT BREAKER
 
Analysis and Design of Low-Voltage Power Systems An Engineers Field Guide by ...
Analysis and Design of Low-Voltage Power Systems An Engineers Field Guide by ...Analysis and Design of Low-Voltage Power Systems An Engineers Field Guide by ...
Analysis and Design of Low-Voltage Power Systems An Engineers Field Guide by ...
 
06612 iec zerti_rz11_e
06612 iec zerti_rz11_e06612 iec zerti_rz11_e
06612 iec zerti_rz11_e
 
Three-phase asynchronous motors
Three-phase asynchronous motorsThree-phase asynchronous motors
Three-phase asynchronous motors
 
1sdc007106g0201(1)
1sdc007106g0201(1)1sdc007106g0201(1)
1sdc007106g0201(1)
 
1sdc007106g0201
1sdc007106g02011sdc007106g0201
1sdc007106g0201
 
Is 2026 spec
Is 2026 specIs 2026 spec
Is 2026 spec
 
Power factor correction
Power factor correctionPower factor correction
Power factor correction
 
CRITERIA FOR OVERHEAD TRANSMISSION LINE AMPACITY RATINGS
CRITERIA FOR OVERHEAD TRANSMISSION LINE AMPACITY RATINGSCRITERIA FOR OVERHEAD TRANSMISSION LINE AMPACITY RATINGS
CRITERIA FOR OVERHEAD TRANSMISSION LINE AMPACITY RATINGS
 
ABB WBT Indoor Fuses IEC Standard 1.9kV-4kV - ABB Medium Voltage Indoor Railw...
ABB WBT Indoor Fuses IEC Standard 1.9kV-4kV - ABB Medium Voltage Indoor Railw...ABB WBT Indoor Fuses IEC Standard 1.9kV-4kV - ABB Medium Voltage Indoor Railw...
ABB WBT Indoor Fuses IEC Standard 1.9kV-4kV - ABB Medium Voltage Indoor Railw...
 
Articulo subestaciones-bn
Articulo   subestaciones-bnArticulo   subestaciones-bn
Articulo subestaciones-bn
 
Ellis Patents Cable Cleats Guide - Black Book
Ellis Patents Cable Cleats Guide - Black BookEllis Patents Cable Cleats Guide - Black Book
Ellis Patents Cable Cleats Guide - Black Book
 
17th Edition Part 6
17th Edition  Part 617th Edition  Part 6
17th Edition Part 6
 
Kaizenreport
KaizenreportKaizenreport
Kaizenreport
 
KYN28 12kV Medium voltage metal clad switchgear
KYN28 12kV Medium voltage metal clad switchgearKYN28 12kV Medium voltage metal clad switchgear
KYN28 12kV Medium voltage metal clad switchgear
 
pdfslide.net_iec-61439pptx.pptx
pdfslide.net_iec-61439pptx.pptxpdfslide.net_iec-61439pptx.pptx
pdfslide.net_iec-61439pptx.pptx
 

Recently uploaded

FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
dollysharma2066
 
notes on Evolution Of Analytic Scalability.ppt
notes on Evolution Of Analytic Scalability.pptnotes on Evolution Of Analytic Scalability.ppt
notes on Evolution Of Analytic Scalability.ppt
MsecMca
 
Call Girls In Bangalore ☎ 7737669865 🥵 Book Your One night Stand
Call Girls In Bangalore ☎ 7737669865 🥵 Book Your One night StandCall Girls In Bangalore ☎ 7737669865 🥵 Book Your One night Stand
Call Girls In Bangalore ☎ 7737669865 🥵 Book Your One night Stand
amitlee9823
 
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Christo Ananth
 
VIP Call Girls Palanpur 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Palanpur 7001035870 Whatsapp Number, 24/07 BookingVIP Call Girls Palanpur 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Palanpur 7001035870 Whatsapp Number, 24/07 Booking
dharasingh5698
 

Recently uploaded (20)

Booking open Available Pune Call Girls Pargaon 6297143586 Call Hot Indian Gi...
Booking open Available Pune Call Girls Pargaon  6297143586 Call Hot Indian Gi...Booking open Available Pune Call Girls Pargaon  6297143586 Call Hot Indian Gi...
Booking open Available Pune Call Girls Pargaon 6297143586 Call Hot Indian Gi...
 
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
 
KubeKraft presentation @CloudNativeHooghly
KubeKraft presentation @CloudNativeHooghlyKubeKraft presentation @CloudNativeHooghly
KubeKraft presentation @CloudNativeHooghly
 
Roadmap to Membership of RICS - Pathways and Routes
Roadmap to Membership of RICS - Pathways and RoutesRoadmap to Membership of RICS - Pathways and Routes
Roadmap to Membership of RICS - Pathways and Routes
 
Thermal Engineering -unit - III & IV.ppt
Thermal Engineering -unit - III & IV.pptThermal Engineering -unit - III & IV.ppt
Thermal Engineering -unit - III & IV.ppt
 
Unit 1 - Soil Classification and Compaction.pdf
Unit 1 - Soil Classification and Compaction.pdfUnit 1 - Soil Classification and Compaction.pdf
Unit 1 - Soil Classification and Compaction.pdf
 
Double rodded leveling 1 pdf activity 01
Double rodded leveling 1 pdf activity 01Double rodded leveling 1 pdf activity 01
Double rodded leveling 1 pdf activity 01
 
Java Programming :Event Handling(Types of Events)
Java Programming :Event Handling(Types of Events)Java Programming :Event Handling(Types of Events)
Java Programming :Event Handling(Types of Events)
 
notes on Evolution Of Analytic Scalability.ppt
notes on Evolution Of Analytic Scalability.pptnotes on Evolution Of Analytic Scalability.ppt
notes on Evolution Of Analytic Scalability.ppt
 
VIP Model Call Girls Kothrud ( Pune ) Call ON 8005736733 Starting From 5K to ...
VIP Model Call Girls Kothrud ( Pune ) Call ON 8005736733 Starting From 5K to ...VIP Model Call Girls Kothrud ( Pune ) Call ON 8005736733 Starting From 5K to ...
VIP Model Call Girls Kothrud ( Pune ) Call ON 8005736733 Starting From 5K to ...
 
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete RecordCCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
 
Booking open Available Pune Call Girls Koregaon Park 6297143586 Call Hot Ind...
Booking open Available Pune Call Girls Koregaon Park  6297143586 Call Hot Ind...Booking open Available Pune Call Girls Koregaon Park  6297143586 Call Hot Ind...
Booking open Available Pune Call Girls Koregaon Park 6297143586 Call Hot Ind...
 
Thermal Engineering Unit - I & II . ppt
Thermal Engineering  Unit - I & II . pptThermal Engineering  Unit - I & II . ppt
Thermal Engineering Unit - I & II . ppt
 
Call Girls In Bangalore ☎ 7737669865 🥵 Book Your One night Stand
Call Girls In Bangalore ☎ 7737669865 🥵 Book Your One night StandCall Girls In Bangalore ☎ 7737669865 🥵 Book Your One night Stand
Call Girls In Bangalore ☎ 7737669865 🥵 Book Your One night Stand
 
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
 
Call Girls Wakad Call Me 7737669865 Budget Friendly No Advance Booking
Call Girls Wakad Call Me 7737669865 Budget Friendly No Advance BookingCall Girls Wakad Call Me 7737669865 Budget Friendly No Advance Booking
Call Girls Wakad Call Me 7737669865 Budget Friendly No Advance Booking
 
VIP Call Girls Palanpur 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Palanpur 7001035870 Whatsapp Number, 24/07 BookingVIP Call Girls Palanpur 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Palanpur 7001035870 Whatsapp Number, 24/07 Booking
 
Online banking management system project.pdf
Online banking management system project.pdfOnline banking management system project.pdf
Online banking management system project.pdf
 
(INDIRA) Call Girl Aurangabad Call Now 8617697112 Aurangabad Escorts 24x7
(INDIRA) Call Girl Aurangabad Call Now 8617697112 Aurangabad Escorts 24x7(INDIRA) Call Girl Aurangabad Call Now 8617697112 Aurangabad Escorts 24x7
(INDIRA) Call Girl Aurangabad Call Now 8617697112 Aurangabad Escorts 24x7
 
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
 

Iec 61439 for_low_voltage_switchgear_and

  • 1. IEC 61439 The new standard for low-voltage switchgear and controlgear assEmblies 11 | 2010
  • 2. 2 IEC 61439 – The new standard
  • 3. IEC 61439 – The new standard 3 Content Page Introduction . ....................................................................... 4 The current IEC 60439 . ....................................................... 5 The new IEC 61439 ............................................................ 6 Main changes ..................................................................... 7 Responsibilities .................................................................12 FAQ ..................................................................................14 Summary and conclusion....................................................16
  • 4. 4 IEC 61439 – The new standard A low-voltage switchgear and controlgear assembly (ASSEMBLY) is a combination of low-voltage switching devices together with associated equipment (for control- ling, measuring, signalling, etc.) complete with all the internal mechanical and electrical interconnections and structural parts. As with every component of an electrical installation, the ASSEMBLY also has to comply with its appropriate standard. In January 2009 the IEC 61439, the new standard for low- voltage switchgear and controlgear ASSEMBLIES, was published. This was the aim of an international project group which had been working on a task named ”radical restructuring and revision of IEC 60439 series” since 1998. This initiative was introduced by several countries following dissatisfaction with the IEC 60439 series. The purpose was to harmonise and define all general requirements for low-voltage electrical ASSEMBLIES. Reaching an agreement has proven extremely challenging, but the first parts of the new standards have been published. For each type of electrical ASSEMBLY only two parts of the standard are necessary to determine all requirements: the basic standard IEC 61439-1 “General rules” − − the specific ASSEMBLY standard − − The aim of this guide is to allow panel builders, electrical installers, planners or purchasers to familiarise themselves with the new standards and to point out the main changes that have been introduced as well as elements that remain unchanged. Introduction
  • 5. IEC 61439 – The new standard 5 The current IEC 60439 The current IEC 60439 standard applies to enclosures for which the rated voltage is under or equal to 1000 V AC (at frequencies not exceeding 1000 Hz) or 1500 V DC. The standard makes a distinction between type-tested assemblies (TTA) and partially type-tested assemblies (PTTA).The following parts are mentioned and have equal weighting. There is not a formal hierarchy. Each part is a complete entity and can be used on an individual basis: IEC 60439-1 type-tested and partially type-tested assemblies IEC 60439-2 particular requirements for busbar trunking systems (busways) IEC 60439-3 particular requirements for low-voltage switchgear and controlgear assemblies which are to be installed in locations where unskilled persons have access for their use. IEC 60439-4 particular requirements for assemblies for construction sites (ACS) IEC 60439-5 particular requirements for assemblies intended to be installed outdoors in public places – Cable distribution cabinets (CDCs) for power distribution in networks The standard remains valid until 2014
  • 6. 6 IEC 61439 – The new standard IEC 61439-1 Relationship between the two standards is as shown in the table below: IEC 61439-2 replaces IEC 60439-1 (still valid until 2014) IEC 61439-6 will replace IEC 60439-2 (still valid) IEC 61439-3 will replace IEC 60439-3 (still valid) IEC 61439-4 will replace IEC 60439-4 (still valid) IEC 61439-5 will replace IEC 60439-5 (still valid) The new IEC 61439 standard applies to enclosures for which the rated voltage is under 1000 V AC (at frequencies not exceeding 1000 Hz) or 1500 V DC. The standard defines the design verified ASSEMBLIES and eliminates completely the categories TTA and PTTA. In order to conform to the standard, type tests have been replaced by a design verification which can be carried out by the three following equivalent and alternative methods: testing, calculation/measurement or application of design rules. The following parts are mentioned and do not have equal weighting. There is a formal hierarchy. Each part can not be used individually: IEC 61439-1 − − “General rules“ IEC 61439-2 − − “Power switchgear and controlgear ASSEMBLIES” IEC 61439-3 − − “Distribution boards“ IEC 61439-4 − − “ASSEMBLIES for construction sites” IEC 61439-5 − − “ASSEMBLIES for power distribution” IEC 61439-6 − − “Busbar trunking systems” Part 1 is the general rules part and cannot be used alone to specify an ASSEMBLY. Part 2 defines the specific requirements of power switchgear and controlgear ASSEMBLIES (PSC ASSEMBLIES) and must be used with Part 1. This is the only part that has a double role, it covers PSC ASSEMBLIES and any ASSEMBLY which is not covered by any other specific parts. Parts 3-X are still under preparation but are already men- tioned in Part 1. These could be more than four, as additional parts may be developed as the need arises. Summarising: With the currently used IEC 60439, the rule is “one part for each type of ASSEMBLY”. With the new IEC 61439 the rule is “two parts for each type of ASSEM- BLY”. The compliance of an ASSEMBLY is declared refer- ring to the specific ASSEMBLY standard (e.g. IEC 61439-2), and the compliance with the general rules (IEC 61439-1) is always implicit. The sentence “TTA switchgear according to IEC 60439-1“ is now replaced by “Power switchgear and controlgear ASSEMBLIES according to IEC 61439-2, design verified ASSEMBLY“. The validity of the two standards will overlap until 2014 and prior to this date, ASSEMBLIES can be manufactured accord- ing to IEC 61439 or IEC 60439. The new IEC 61439
  • 7. IEC 61439 – The new standard 7 The new IEC 61439 includes the following significant technical changes with respect to the last edition of IEC 60439. Responsibility split: New terms have been introduced and there is a split in product responsibility between the “Original manufacturer” (e.g. ABB, responsible for carrying out the original design and the associated verification of an ASSEMBLY) and the “ASSEMBLY manufacturer” (e.g panel builder using an ASSEMBLY system from an Original Manufacturer) assuming responsibility for the completed ASSEMBLY. The Assembly Manufacturer may be a different organisation to the Original Manufacturer. Where the ASSEMBLY Manu- facturer introduces changes to the ASSEMBLY configuration tested by the Original Manufacturer, he is deemed to be the Original Manufacturer in respect of these changes and has to carry out the design verification. Design verification replaces TTA and PTTA categories: Design verification replaces type tests so the discrimination between type-tested assemblies (TTA) and partially type- tested assemblies (PTTA) is eliminated. Three different but equivalent types of verification of requirements are introduced: Verification by testing (test made on a sample of an ASSEM- BLY or on parts of ASSEMBLIES to verify that the design meets the appropriate requirements. This method is equiva- lent to the currently implemented type tests). Verification by calculation/measurement (calculations applied to a sample of an ASSEMBLY or to parts of ASSEMBLIES to show that the design meets the appropriate requirements). Verification by application of design rules (specified rule to verify the design of an ASSEMBLY). The selection of the appropriate verification method has to be made according to annex D, which explains the available veri- fication options for each characteristic which is to be verified, as shown in the table below: Main changes – More than a single digit change… Characteristic to be verified Verification options available Verification by testing Verification by calculation Verification by design rules 10.2 Strength of material and parts Yes No No 10.3 Degree of protection of enclosures Yes No Yes 10.4 Clearances and creepage distances Yes Yes Yes 10.5.2 Effective continuity between parts and PE Yes No No 10.5.3 Effectiveness of the ASSEMBLY for external faults Yes Yes Yes 10.6 Incorporating of apparatus No No Yes 10.7 Internal electrical circuits and connections No No Yes 10.8 Terminals for external conductors No No Yes 10.9.2 Power frequency withstand voltage Yes No No 10.9.3 Impulse withstand voltage Yes No Yes 10.10 Temperature rise limits Yes Yes Yes 10.11 Short-circuit withstand strength Yes Yes Yes 10.12 EMC Yes No Yes 10.13 Mechanical operation Yes No No
  • 8. 8 IEC 61439 – The new standard system manufacturer manufacturer of the ASSEMBLY ASSEMBLY low-voltage switchgear and controlgear ASSEMBLIES type tests for verification of conformity TTA type-tested ASSEMBLIES type-tested units not type-tested units PTTA partial type-tested ASSEMBLIES routine test completed ASSEMBLY IEC 60439 Tests that have been made in accordance with IEC 60439 and that fulfil the requirements of the new IEC 61439 need NOT be repeated. The second stage verification is the routine verification. This is performed to verify that the materials and workmanship are in accordance with the requirements of the standard. Rou- tine verification replaces the current “routine test”. It is more detailed but essentially the new requirements are the same as in the IEC 60439. This verification has to be carried out for each completed ASSEMBLY and it is the responsibility of the ASSEMBLY Manufacturer. Main changes – More than a single digit change… Comparison between the current and the new verification “flow”:
  • 9. IEC 61439 – The new standard 9 original manufacturer ASSEMBLY manufacturer original manufacturer ASSEMBLY low-voltage switchgear and controlgear ASSEMBLIES testing calculation ASSEMBLY system application of design rules routine verification The ASSEMBLY manufacturer can decide: – to manufacture the ASSEMBLY according to the guidelines of the original manufacturer – t o deviate from the guidelines of the original manufacturer. Where the ASSEMBLY manufacturer incorporates his own arrangements not included in the original manufacturer’s verification, the ASSEMBLY manufacturer is deemed to be the original manufacturer in respect of these arrangements. completed ASSEMBLY IEC 61439 design verification carried out by the original manufacturer
  • 10. 10 IEC 61439 – The new standard Tests described in IEC 61439-1 in comparison with the type tests described in IEC 60439 Additional verification: New requirements from the standard IEC 62208 (Empty enclosures for ASSEMBLIES) have been added: verification of resistance to UV radiation for − − outdoor plastic enclosures verification of corrosion resistance − − mandatory declaration and confirmation of − − an impulse rating lifting, mechanical impact and marking − − Other changes Temperature rise Temperature rise requirements have been explained more clearly and have been adapted to the state of the art. One of the following methods is allowed for verification: testing with current − − derivation (from a tested design) − − of ratings for similar variants calculation − − (see also “FAQ” chapter) Main changes – More than a single digit change… No. Characteristics to be verified Clause/Subclause Comparable type test from 60439-1 1 Strength of material and parts 10.2 Not required as “Type test” but as “Design and construction” rules on paragraph 7 or on subsidiary standard Resistance to corrosion 10.2.2 Properties of insulating materials 10.2.3 Thermal stability 10.2.3.1 Resistance of insulating materials to normal heat 10.2.3.2 Resistance to abnormal heat and fire due to internal electric effects 10.2.3.3 Resistance to ultra-violet (UV) radiation 10.2.4 Lifting 10.2.5 Mechanical impact 10.2.6 Marking 10.2.7 2 Degree of protection of enclosures 10.3 8.2.7 3 Clearances and creepage distances 10.4 8.2.5 4 Protection against electric shock and integrity of protective circuits 10.5 8.2.4 Effective continuity between the exposed conductive parts of the ASSEMBLY and the protective circuit 10.5.2 Effectiveness of the ASSEMBLY for external faults 10.5.3 5 Incorporation of switching devices and components 10.6 Not required as “Type test” but as “Design and construction” rules on paragraph 7 or on subsidiary standard 6 Internal electrical circuits and connections 10.7 7 Terminals for external conductors 10.8 8 Dielectric properties 10.9 8.2.2 Power -frequency withstand voltage 10.9.2 Impulse withstand voltage 10.9.3 9 Temperature rise limits 10.10 8.2.1 10 Short-circuit withstand strength 10.11 8.2.3 11 Electromagnetic compatibility (EMC) 10.12 + Annex J 8.2.8 + Annex H 12 Mechanical operation 10.13 8.2.6
  • 11. IEC 61439 – The new standard 11 RDF The rated diversity factor is covered in more detail. In practice it is assumed that multiple functional units are not fully loaded simultaneously. (see also “FAQ” chapter) Labels Labels have to be subjected to testing to verify their legibility. The following information is required on the label: ASSEMBLY Manufacturer‘s name − − Identification number − − Date of manufacture (NEW!) − − IEC 61439-X (the specific part “X” has to be specified) − − (NEW!) “Grey” areas A number of “grey” areas have been clarified: neutral conductors will have a current rating equal to 50% − − of the corresponding phases if not otherwise specified agreements between Customer and Manufacturer have − − been more detailed, extended and listed in annex C it is mandatory to specify the rated current of the − − ASSEMBLY a technical report IEC 61439-0 “Guide for specifying − − ASSEMBLIES” is under development for a better understanding of the new standard questions regarding the internal form of separation − − have been clarified (e.g. a moulded case circuit breaker’s casing provides separation from other functional units) Summary table with the main changes IEC 60439 IEC 61439 IEC 60439-1 Type-tested and partially type-tested assemblies IEC 61439-2 Design verified ASSEMBLIES Mix of different rules and demands in each part Clear structure: IEC 61439-1 “General rules“ IEC 61439-2 … -6 “Subsidiary parts” (product standard) Each part is a complete entity and can be used on an individual basis Each “subsidiary part” is based on the “general rules” (Part 1) and includes only the specific additional rules for the specific product Testing each type of assembly: Partially type-tested or type-tested Three alternative methods for verification: Test, calculation/measurement, design rules Annex E: Agreements between Customer and Manufacturer Annex C: Agreements between Customer and Manufacturer are more detailed and extended Shared responsibility: Original Manufacturer vs. ASSEMBLY Manufacturer Technical changes and clarifications: Diversity factor, verification of temperature rise, mechanical characteristics, neutral conductor 50%, additional verification (from IEC 62208)
  • 12. 12 IEC 61439 – The new standard Some hypothetical examples: An Original Manufacturer (e.g. ABB) assembles a complete ASSEMBLY and sells it to a panel builder – the panel builder is only the ASSEMBLY Manufacturer, if he installs the ASSEMBLY as it is. – the panel builder is the ASSEMBLY Manufacturer and becomes the Original Manufacturer if he makes some modifications to the ASSEMBLY. A panel builder assembles a complete ASSEMBLY (according to the rules of the Original manufacturer) – the panelbuilder is the ASSEMBLY Manufacturer and is responsible for the ASSEMBLY, providing the electrical installer installs the ASSEMBLY without making any alterations. A panel builder assembles a complete ASSEMBLY (according to the rules of the Original manufacturer) that has been partially assembled by an external supplier – the panel builder is the ASSEMBLY Manufacturer and is responsible for the ASSEMBLY. With regard to responsibilities, the general and obvious rule is: the manufacturer of the ASSEMBLY is responsible for the ASSEMBLY! For a better explanation of this concept we can say: the Original Manufacturer usually makes design verifications and assumes responsibility for the proper functionality of prototype ASSEMBLIES. He provides a portfolio of verified ASSEMBLIES and each “actor” in the electrical market, who becomes the ASSEMBLY Manufacturer, can manufacture a design verified ASSEMBLY by following the instructions supplied in the Original Manufacturer´s instruction manual or catalogue; the ASSEMBLY Manufacturer assumes responsibil- ity for the ASSEMBLY, he labels the ASSEMBLY and it is his responsibility to declare that the ASSEMBLY complies with the relevant standards. In practice he has two options: he decides to manufacture the ASSEMBLY according to − − the rules of the Original Manufacturer. In this case, the ASSEMBLY Manufacturer has to perform only the second stage verification, namely routine verification. he decides NOT to manufacture the ASSEMBLY according − − to the rules of the Original Manufacturer. In this case, the ASSEMBLY Manufacturer incorporates his own arrange- ments, so that he is deemed to be the Original Manufacturer. Regarding these arrangements and he must then carry out both the first and the second stage verification: design verification and routine verification. Responsibilities
  • 13. IEC 61439 – The new standard 13
  • 14. 14 IEC 61439 – The new standard FAQ Is it possible to substitute a device within an ASSEMBLY? What about temperature rise and short circuit strength? The new IEC 61439 clearly defines a device substitution in respect of temperature rise and short circuit strength. Temperature rise: it is possible to substitute a device without repeating the design verification, provided that the new device from the same or another series has identical or better values, regarding power loss and terminal temperature rise, in com- parison with those of the original device, as tested in accord- ance with the product standard. Short circuit: it is possible to substitute a device without repeating the design verification, provided that the new device is identical. If different, it has to be from the same manufactur- er who has to certify that it is equivalent or better with regard to all relevant short circuit characteristics. Is the verification of the short circuit withstand strength required for all circuits of an ASSEMBLY? No, it is not required for: An ASSEMBLY having a rated short-time withstand current − − or rated conditional short circuit current not exceeding 10 kA r.m.s. An ASSEMBLY protected by current-limiting devices having − − a cut-off current not exceeding 17 kA at the maximum permitted prospective short-circuit current at the terminals of the incoming circuit of the ASSEMBLY. Auxillary circuits of an ASSEMBLY intended to be connect- − − ed to transformers whose rated power does not exceed 10 kVA for a rated secondary voltage of not less than 110 V, or 1.6 kVA for a rated secondary voltage less than 110 V, and whose short circuit impedance is not less than 4%. All other circuits have to be verified. Until what point is it possible to manufacture and to install ASSEMBLIES in accordance with IEC 60439? The validity of the two standards will overlap until 2014 and prior to this date, ASSEMBLIES can be manufactured accord- ing to IEC 61439 or IEC 60439. If tests on the ASSEMBLY have been conducted in accordance with IEC 60439, is it necessary to repeat them in accordance with the new IEC 61439? No, if the conducted test results fulfil the requirements of the new IEC 61439 it is not necessary to repeat them. It is necessary to test only the additional verification that has been introduced by the new standard. Is it possible to manufacture an ASSEMBLY in accordance with the new IEC 61439, with enclosures from ABB, busbars from another manufacturer, circuit breakers from another manufacturer, etc.? Yes, it is possible but it is not easy and it is expensive. The panel builder that decides to mix different “elements” from dif- ferent manufacturers is not only the ASSEMBLY Manufacturer, but becomes the Original Manufacturer and has to perform both the first and the second stage verification: design verifi- cation and routine verification. The routine verification is similar to the present routine test and is relatively straightforward. The design verification how- ever includes some characteristics which are easily verified, and others that can only be verified through laboratory testing. What is the Rated Diversity Factor (RDF)? The RDF is the per unit value of the rated current, to which outgoing circuits of an ASSEMBLY can be continuously and simultaneously loaded (the mutual thermal influences have to be taken into account). It can be declared for groups of circuits or for the whole ASSEMBLY. The RDF has to be as- signed by the ASSEMBLY Manufacturer (if not specified it is assumed to be equal to 1). In practice it is recognised that not all circuits in an ASSEMBLY operate at rated current continuously and this allows efficient use of materials and resources.
  • 15. IEC 61439 – The new standard 15 Does the verification of temperature rise remain unchanged? Temperature rise requirements have been explained in further detail. Three different methods are now allowed for verification (the Original Manufacturer is responsible for choosing the suitable verification methods): 1) Testing with current: Three different test methods are permitted and the Original Manufacturer has to determine the best method. When a number of variants of an ASSEMBLY have to be verified, the most onerous configuration has to be tested and the ratings of the less onerous (and similar) variants can be derived without testing. 2) Derivation: (from a tested design) of ratings for similar variants The standard defines a series of sub-clauses that help define, how non-tested variants can be verified by derivation from similar arrangements verified by test. 3) Calculation: two calculation methods are allowed Single compartment ASSEMBLY with rated current not − − exceeding 630 A (done by calculating the total power loss of the ASSEMBLY if certain conditions are fulfilled). Multiple compartment ASSEMBLY with rated current not − − exceeding 1600 A (done by calculation in accordance with the method of IEC 60890 if certain conditions are fulfilled). Flow chart to establish how to verify the temperature rise InA ≤ 630 A Single compartment? Yes Yes Yes Yes No Yes No No No No InA ≤ 1600 A Are the IEC 61439 and IEC 60890 conditions fulfilled? Are the IEC 61439 conditions fulfilled? Calculation in accordance with IEC 60890 Testing with current OR derivation (if a tested prototype is available) Calculation of the total power loss
  • 16. 16 IEC 61439 – The new standard Summary and conclusion The new standard IEC 61439 introduces important modifications in comparison with the current standard IEC 60439 on low-voltage switchgear and controlgear ASSEMBLIES. The structure of the new standard is clearer with a general part and product specific parts. New definitions have been written (e.g. “Original Manufacturer” and “ASSEMBLY Manu- facturer”). New compulsory characteristics have to be specified (e.g. rated current of the ASSEMBLY). A new “design verified ASSEMBLY” concept has been speci- fied. This new concept completely discards the categories TTA and PTTA, and the compliance of an ASSEMBLY can now not only be verified by means of tests, but also with alterna- tive methods: calculation/measurement and design rules. The new standard is more precise, eradicating the “grey” areas contained in the previous standard. The responsibilities for an ASSEMBLY are clearly defined, making the job of each “actor” on the electrical market easier nowadays.
  • 17.
  • 18. 18 IEC 61439 – The new standard Notes
  • 19.
  • 20. Contact us You can find the address of your local sales organisation on the ABB homepage: www.abb.com/contacts Low Voltage Products and Systems K-0119-KM-11/2010-V1 · 2CPC 000 119 L0201 Note: We reserve the right to make technical changes or modify the contents of this document without prior notice. With regard to purchase orders, the agreed particulars shall prevail. ABB AG does not accept any responsibility whatsoever for poten- tial errors or possible lack of information in this document. We reserve all rights in this document and in the subject matter and illustrations contained therein. Any reproduction, disclosure to third parties or utilization of its contents – in whole or in parts – is forbidden without prior written consent of ABB AG. Copyright © 2010 ABB All rights reserved