SEISMIC PERFORMANCE OF SYMMETRICAL BUILDING WITH &
WITHOUT ISOLATORS
Miss. Sushma G.Sawadatkar1, Prof.M.M.Joshi2
1 Student, Dept. Of Civil Engineering, PLITMS Buldana, Maharashtra, India
2Assistant Professor, Dept. of Civil Engineering, PLITMS Buldana, Maharashtra, India
---------------------------------------------------------------------***---------------------------------------------------------------------
Abstract - Earthquake is one of the nature’s greatest
hazards, throughout historic timetheyhavecausedsignificant
loss of life and severe damage to property, especially to Man-
Made Structures. Base Isolation is an effective method for
earthquake resistant design to reduce vibration transmitted
from ground to the structure. Base isolation, is also known as
seismic base isolation or base isolation system, Is one of the
most popular means protecting a structure against
earthquake forces. It is a collection of Structural elements
which should substantially decouple a Superstructurefromits
substructure resting on a shaking Ground. In this paper, An
G+6 Storey building is modeledandanalyzed withand without
base isolators by using Finite Element Based Software. The
main purpose of this work is to study the Dynamic response of
the building with fixed base and same building with Base
isolation System Such as Lead Rubber Bearing isolator. In this
project, the Seismic performances, Shear force, Bending
moment and steel Consumptions of the fixedbasebuildingand
Lead Rubber Base Isolation System is presented.
Key Words: Lead Rubber bearing Isolator
(LRB), Analysis, Seismic, SAP 2000, Base
Isolator
1. INTRODUCTION
Base isolation is an effective means for protection of
structure during earthquake events. The concept of Base
isolation is to insert a flexible layer between foundation and
superstructure thus decoupling the building from damaging
action of ground motion. This results in reduced frequency
range and dissipates energy through damping.
In this study an attempt is made to improvetheperformance
of symmetrical and asymmetrical buildingsbyincorporating
lead rubber base isolators at bottom level of columns. for
this, symmetrical and asymmetrical buildings models with
and without base isolators are considered. The 3D analysis
of building is carried out for earthquake zone III. The
response spectrum analysis is carried out on all the
mathematical 3D models using the software SAP 2000. The
results obtain from the analysis are discussed in next
sections.
1.1 Seismic Performance of Symmetrical Building
with & without Isolators
There are total two symmetrical models under
consideration, out of which first model iswithoutisolator i.e.
fixed base and in second models, lead rubber base isolator
with all properties provided by manufacturer are used at
base storey to improve seismic performance of such type of
building. For comparison purpose, lateral displacements,
storey drifts, base shear, time period,frequencies,maximum
forces in columns at bottom are chosen.
Fig -1: Symmetrical Building without Isolator
Fig -1: Symmetrical Building with Isolator
International Research Journal of Engineering and Technology (IRJET) e-ISSN: 2395-0056
Volume: 04 Issue: 11 | Nov -2017 www.irjet.net p-ISSN: 2395-0072
© 2017, IRJET | Impact Factor value: 6.171 | ISO 9001:2008 Certified Journal | Page 1873
2. Comparison of results for symmetrical type
buildings
Response spectrum analysis is carried out on all the models.
The results are presented in the form of graphs and tables.
2.1 Lateral Displacement
The floor wise lateral displacements are tabulated in table
2.1 for both models i.e. building without isolator and
building without isolator. Also a graph is plotted takingfloor
level as the abscissa and the displacementastheordinatefor
both models in both the longitudinal and transverse
direction as shown in Chart 1
Table 2.1: Displacement at Floor Levels for Both with
and Without Isolator Building (Symmetrical)
Storey Without Isolator
(mm)
With Isolator(mm)
6 15.73 33.90
5 14.90 33.61
4 13.50 33.12
3 11.55 32.41
2 9.12 31.47
1 6.30 30.25
G 3.25 28.47
Chart -1: Displacement Profile for Both with and Without
Isolator Building (Symmetrical)
From the displacement profile it is observed that there is
considerable increase in displacementafterincorporation of
base isolator as compared to fixed base without isolator
building. The maximum displacement at top level is
increased 115%.
2.2 Storey Drift
The floor wise storey drift are tabulated in table 2.2 for both
models i.e. building without isolator and building without
isolator. Also a graph is plotted taking floor level as the
abscissa and the drift as the ordinate for both modelsinboth
the longitudinal and transverse direction as shown in Chart
2
Table 2.2: Drift at Floor Levels for Both with and
Without Isolator Building (Symmetrical)
Storey Without Isolator
(mm)
With Isolator (mm)
6 0.83 0.29
5 1.4 0.49
4 1.95 0.71
3 2.43 0.94
2 2.82 1.22
1 3.05 1.78
Chart -2: Drift Profile for Both with and Without Isolator
Building (Symmetrical)
From the drift profile it is observed that there is sufficient
decrement in drift after incorporation of base isolator as
compared to fixed base without isolator building which is
very beneficial from stability point of view. The drift at all
the levels are decreased by 40-65%.
2.3 Base Shear
The base shear for both building models with and without
isolator are tabulated in table 2.3 also the graphical
representation of the same is shown in Chart 3
International Research Journal of Engineering and Technology (IRJET) e-ISSN: 2395-0056
Volume: 04 Issue: 11 | Nov -2017 www.irjet.net p-ISSN: 2395-0072
© 2017, IRJET | Impact Factor value: 6.171 | ISO 9001:2008 Certified Journal | Page 1874
Table 5.3: Base Shear for Both with and Without
Isolator Building (Symmetrical)
Storey Without Isolator
(kN)
With Isolator (kN)
Base 1050 463.19
Chart -3: Base Shear for Both with and Without Isolator
Building (Symmetrical)
Base shear of the building considerably decreases after
incorporation of base isolator which is due to flexible
behavior of building. The base shear is decreasedby56%for
building with isolator.
2.4 Time Period
The time period for both building models with and without
isolator are tabulated in table 2.4 Also a graph is plotted
taking modes on the X axis and time period in second on Y
axis for both the building models as shown in the Chart 4
below.
Table 5.4: Time Period for Different Modes for Both
with and Without Isolator Building (Symmetrical)
Mode Without Isolator
(Sec)
With Isolator (Sec)
1 0.459 2.682
2 0.459 2.682
3 0.430 2.524
4 0.084 0.468
5 0.080 0.468
6 0.080 0.425
7 0.076 0.222
8 0.075 0.222
9 0.075 0.206
10 0.072 0.140
11 0.072 0.140
12 0.071 0.131
Chart -4: Time Period for Both with and Without Isolator
Building (Symmetrical)
It is observed that the time period of vibration is more for
building with isolator. The increment is of 484%.
2.5 Frequency
The frequencies for both building models with and without
isolator are tabulated in table 2.5 Also a graph is plotted
taking modes on the X axis and time period in second on Y
axis for both the building models as shown in the Chart 5
below.
Table 5.5: Frequency for Different Modes for Both with
and Without Isolator Building (Symmetrical)
Mode Without Isolator
(m/sec)
With Isolator
(m/sec)
1 2.1773 0.3729
2 2.1773 0.3729
3 2.3248 0.3963
4 11.861 2.1362
5 12.474 2.1362
6 12.474 2.3539
7 13.106 4.4986
8 13.297 4.4986
9 13.304 4.8486
10 13.955 7.1579
11 13.955 7.1579
12 14.033 7.6190
International Research Journal of Engineering and Technology (IRJET) e-ISSN: 2395-0056
Volume: 04 Issue: 11 | Nov -2017 www.irjet.net p-ISSN: 2395-0072
© 2017, IRJET | Impact Factor value: 6.171 | ISO 9001:2008 Certified Journal | Page 1875
Chart -5: Frequencies for Both with and Without Isolator
Building (Symmetrical)
It is observed that the frequency is reduced for buildingwith
isolator. The decrement is of 82%.
2.6 Maximum Bending Moment in Columns
The maximum bending moment in column at bottom storey
for both building models with and without isolator are
tabulated in table 5.6 also the graphical representationofthe
same is shown in Chart 6
Table 5.6: Maximum Bending Moment in Column at
Bottom Storey for Both with and Without Isolator
Building (Symmetrical)
Storey Without Isolator
(kNm)
With Isolator (kNm)
G 45.23 18.62
Chart -6: Maximum Bending Moment in Columns at
Bottom Storey for Both with and Without Isolator Building
(Symmetrical)
Maximum bending moment in bottom storey of the building
significantly decreases after incorporation of base isolator
which is due to flexible behavior of building. The moment is
decreased by 58% for building with isolator.
2.7 Maximum Shear in Columns
The maximum shear in column at bottom storey for both
building models with and without isolator are tabulated in
table 2.7 also the graphical representation of the same is
shown in Chart 7
Table 5.7: Maximum Shear in Column at Bottom Storey
for Both with and Without Isolator Building
(Symmetrical)
Storey
Without Isolator
(kN)
With Isolator (kN)
G 116.87 74.47
Chart -7: Maximum Shear Force in Columns at Bottom
Storey for Both with and Without Isolator Building
(Symmetrical)
Maximum shear force in bottom storey of the building
significantly decreases after incorporation of base isolator
which is due to flexible behavior of building. The shear is
decreased by 36% for building with isolator.
2.8 Maximum reinforcement in Columns
The maximum reinforcement in column at bottomstorey for
both building modelswithandwithoutisolatoraretabulated
in table 2.8 also the graphical representation of the same is
shown in Chart 8
International Research Journal of Engineering and Technology (IRJET) e-ISSN: 2395-0056
Volume: 04 Issue: 11 | Nov -2017 www.irjet.net p-ISSN: 2395-0072
© 2017, IRJET | Impact Factor value: 6.171 | ISO 9001:2008 Certified Journal | Page 1876
Table 5.8: Maximum Reinforcement in Column at
Bottom Storey for Both with and Without Isolator
Building (Symmetrical)
Storey
Without Isolator (sq
mm.)
With Isolator (sq
mm.)
G 2000 2357
Chart -8: Maximum Reinforcement in Columns at Bottom
Storey for Both with and Without Isolator Building
(Symmetrical)
Maximum reinforcement in bottom storey of the building
slightly increases after incorporation of base isolator which
is due to flexible behavior of building. The reinforcement is
increased by 17% for building with isolator.
3. CONCLUSIONS
Based on the analysis results following conclusions are
drawn;
1. Building becomes more flexible as compared to
fixed base building which will improve the
performance in earthquake excitation.
2. Base isolation system is the effective one in
reducing the structural response as compared to
fixed base building.
3. From the analytical results, it is observed that how
effective seismic isolation works by considering
various aspects such as: base shear, maximum
bending moments, & column shears, etc. Analysis
results of the study suggestthatrubberisolatorsare
better option to improve performance of buildings.
4. Base isolation basically reduces the demand forces
by shifting the time period of the structure.
5. Storey drift also reduced from 40% to 65% for both
symmetrical and asymmetrical building.
6. The Base isolation considerably increases the
lateral displacement. As observed the lateral
displacement at top storey is increased up to 115%
for both symmetrical and asymmetrical building as
that of fixed one.
7. The Base isolation substantially increases the time
period of the building & hence correspondingly
reduces the base shear. As observedthetimeperiod
is being increased by 484% for symmetrical
building and 155% for asymmetrical building &
base shear is reduced up to 55% for both
symmetrical and asymmetrical building of that of
fixed one.
8. By considering the bending moment values of
columns, it is clearly observed that for isolated case
the maximum bending moment is reduced up to
58% as that of fixed case.
9. The shear force values of columns shows that the
ground storey columns are reduced up to 36% for
isolated frame when compared fixed base building.
10. The reinforcement requirement of columns shows
that the ground storey columns are increased up to
17% for isolated frame when compared fixed base
building.
REFERENCES
[1] Satish Nagarajaiah (Journal of Structural
Engineering, Vol. 119, No. 10) October, 1993
(Torsion in base-isolated structures with
elastomeric isolation systems)
[2] J. C. Ramallo (JOURNAL OF ENGINEERING
MECHANICS ) OCTOBER 2002 (Smart’’ Base
Isolation Systems)
[3] Xi-Yuan Zhou (ISET Journal of Earthquake
Technology, Paper No. 436) Vol. 40, No. 2- 4, June-
December 2003,( Study on protection measures for
seismic isolation rubber bearings , pp. 137-160)
[4] Khante.S.N, Lavkesh R.Wankhade, ‘, International
journal of civil and structural engineering) Volume
X, No X, 2010 (Study of seismic response of
symmetric and asymmetric base isolated building
with mass asymmetry in plan)
[5] A. B. M. Saiful Islam , Mohammed Jameel
(International Journal of the Physical Sciences) Vol.
6(11), ,4 June, 2011 (Study on corollary of seismic
base isolation system on buildings with soft storey,
pp. 2654-2661)
[6] KS Sable, J S Khose, V P Kulkarni (International
Journal of Engineering and Innovative Technology
,IJEIT) Volume 1, Issue 4, April 2012(Comparisonof
International Research Journal of Engineering and Technology (IRJET) e-ISSN: 2395-0056
Volume: 04 Issue: 11 | Nov -2017 www.irjet.net p-ISSN: 2395-0072
© 2017, IRJET | Impact Factor value: 6.171 | ISO 9001:2008 Certified Journal | Page 1877
Different Bearing Types Performance in
Multistoried Building).
[7] S.J.Patil (International Journal of Emerging
Technology and Advanced Engineering) ISSN 2250-
2459, Volume 2, Issue 7,July 2012 (State Of Art
Review - Base Isolation Systems For Structures).
[8] Shirule Pravin Ashok (International Journal ofCivil,
Structural, Environmental and Infrastructure
Engineering Research and Development ) ISSN
2249-6866 Vol.2, Issue 3, Sep2012 (Response
spectrum analysis of multi storeyed base-isolated
building, 66-75)
[9] Chauhan Kalpesh M. (International Journal of
Advanced EngineeringResearchand Studies)Vol.II,
April-June, 2013 (Excel spreadsheet for design of
lead rubber bearing uses for seismic Isolation of
bridges, P.P 60-62)
[10] Ashish R. Akhare, Tejas R.Wankhade (International
journal of engineering sciences & research) 3(5)
(Seismic Performance of RC Structure Using
Different Base Isolator, May, 2014)

More Related Content

What's hot

Seismic response of rc frame structure with soft storey
Seismic response of rc frame structure with soft storeySeismic response of rc frame structure with soft storey
Seismic response of rc frame structure with soft storey
eSAT Publishing House
 
Optimisation of earth quake response of tall building by using different fram...
Optimisation of earth quake response of tall building by using different fram...Optimisation of earth quake response of tall building by using different fram...
Optimisation of earth quake response of tall building by using different fram...
eSAT Journals
 
Cost optimization of reinforced concrete chimney
Cost optimization of reinforced concrete chimneyCost optimization of reinforced concrete chimney
Cost optimization of reinforced concrete chimney
IAEME Publication
 

What's hot (20)

Effect of User Defined Plastic Hinges on Nonlinear Modelling of Reinforced Co...
Effect of User Defined Plastic Hinges on Nonlinear Modelling of Reinforced Co...Effect of User Defined Plastic Hinges on Nonlinear Modelling of Reinforced Co...
Effect of User Defined Plastic Hinges on Nonlinear Modelling of Reinforced Co...
 
IRJET- Effect of Core Wall on Torsional and Dynamic Behaviour of High –Rise F...
IRJET- Effect of Core Wall on Torsional and Dynamic Behaviour of High –Rise F...IRJET- Effect of Core Wall on Torsional and Dynamic Behaviour of High –Rise F...
IRJET- Effect of Core Wall on Torsional and Dynamic Behaviour of High –Rise F...
 
IRJET- Comparative Evaluation of Performance of Multistoreyed RC Special Mome...
IRJET- Comparative Evaluation of Performance of Multistoreyed RC Special Mome...IRJET- Comparative Evaluation of Performance of Multistoreyed RC Special Mome...
IRJET- Comparative Evaluation of Performance of Multistoreyed RC Special Mome...
 
Design of G+8 RCC Training Institute & Hostel Block
Design of G+8 RCC Training Institute & Hostel BlockDesign of G+8 RCC Training Institute & Hostel Block
Design of G+8 RCC Training Institute & Hostel Block
 
Diagrid structural system strategies to reduce lateral forces on high rise bu...
Diagrid structural system strategies to reduce lateral forces on high rise bu...Diagrid structural system strategies to reduce lateral forces on high rise bu...
Diagrid structural system strategies to reduce lateral forces on high rise bu...
 
IRJET- Behaviour of Asymmetric Building During Earthquake
IRJET-  	  Behaviour of Asymmetric Building During EarthquakeIRJET-  	  Behaviour of Asymmetric Building During Earthquake
IRJET- Behaviour of Asymmetric Building During Earthquake
 
IRJET- Analysis of Steel Braced Symmetrical RCC Building with Designed I-Sect...
IRJET- Analysis of Steel Braced Symmetrical RCC Building with Designed I-Sect...IRJET- Analysis of Steel Braced Symmetrical RCC Building with Designed I-Sect...
IRJET- Analysis of Steel Braced Symmetrical RCC Building with Designed I-Sect...
 
IRJET- Comparative Study on Braced Unbraced Regular and Re-Entrant Corners Ir...
IRJET- Comparative Study on Braced Unbraced Regular and Re-Entrant Corners Ir...IRJET- Comparative Study on Braced Unbraced Regular and Re-Entrant Corners Ir...
IRJET- Comparative Study on Braced Unbraced Regular and Re-Entrant Corners Ir...
 
Lp3519841988
Lp3519841988Lp3519841988
Lp3519841988
 
Seismic response of rc frame structure with soft storey
Seismic response of rc frame structure with soft storeySeismic response of rc frame structure with soft storey
Seismic response of rc frame structure with soft storey
 
A Comparative Seismic Evaluation of GFRP Reinforced and Steel Reinforced Conc...
A Comparative Seismic Evaluation of GFRP Reinforced and Steel Reinforced Conc...A Comparative Seismic Evaluation of GFRP Reinforced and Steel Reinforced Conc...
A Comparative Seismic Evaluation of GFRP Reinforced and Steel Reinforced Conc...
 
Study of Seismic Performance of RC Building with Flat Plate Influenced by Con...
Study of Seismic Performance of RC Building with Flat Plate Influenced by Con...Study of Seismic Performance of RC Building with Flat Plate Influenced by Con...
Study of Seismic Performance of RC Building with Flat Plate Influenced by Con...
 
IRJET- Design and Analysis of Residential Multistory Building (G+5) by using ...
IRJET- Design and Analysis of Residential Multistory Building (G+5) by using ...IRJET- Design and Analysis of Residential Multistory Building (G+5) by using ...
IRJET- Design and Analysis of Residential Multistory Building (G+5) by using ...
 
IRJET- Analysis and Design of High-Rise RC Structure in Different Seismic Zones
IRJET- Analysis and Design of High-Rise RC Structure in Different Seismic ZonesIRJET- Analysis and Design of High-Rise RC Structure in Different Seismic Zones
IRJET- Analysis and Design of High-Rise RC Structure in Different Seismic Zones
 
IRJET- Seismic Response of Flat Slab Buildings with Shear Wall
IRJET-  	  Seismic Response of Flat Slab Buildings with Shear WallIRJET-  	  Seismic Response of Flat Slab Buildings with Shear Wall
IRJET- Seismic Response of Flat Slab Buildings with Shear Wall
 
Optimisation of earth quake response of tall building by using different fram...
Optimisation of earth quake response of tall building by using different fram...Optimisation of earth quake response of tall building by using different fram...
Optimisation of earth quake response of tall building by using different fram...
 
IRJET- Progressive Collapse Resistance of Flat Slab Building
IRJET- Progressive Collapse Resistance of Flat Slab BuildingIRJET- Progressive Collapse Resistance of Flat Slab Building
IRJET- Progressive Collapse Resistance of Flat Slab Building
 
20320140503034
2032014050303420320140503034
20320140503034
 
Cost optimization of reinforced concrete chimney
Cost optimization of reinforced concrete chimneyCost optimization of reinforced concrete chimney
Cost optimization of reinforced concrete chimney
 
IRJET- A Technical Approach to Flat Slab Multistorey Building under Wind Spee...
IRJET- A Technical Approach to Flat Slab Multistorey Building under Wind Spee...IRJET- A Technical Approach to Flat Slab Multistorey Building under Wind Spee...
IRJET- A Technical Approach to Flat Slab Multistorey Building under Wind Spee...
 

Similar to Seismic Performance of Symmetrical Building with & without Isolators

Effect of infill walls on the seismic performance of the multistoried buildings
Effect of infill walls on the seismic performance of the multistoried buildingsEffect of infill walls on the seismic performance of the multistoried buildings
Effect of infill walls on the seismic performance of the multistoried buildings
eSAT Journals
 

Similar to Seismic Performance of Symmetrical Building with & without Isolators (20)

IRJET- Analysis of G+20 RCC Bare Framed Structures with Different Types o...
IRJET-  	  Analysis of G+20 RCC Bare Framed Structures with Different Types o...IRJET-  	  Analysis of G+20 RCC Bare Framed Structures with Different Types o...
IRJET- Analysis of G+20 RCC Bare Framed Structures with Different Types o...
 
Static Analysis and Optimization of Outriggers in A Tall Building
Static Analysis and Optimization of Outriggers in A Tall BuildingStatic Analysis and Optimization of Outriggers in A Tall Building
Static Analysis and Optimization of Outriggers in A Tall Building
 
Comparative Study of Different Types of Bracing Systems by Placing at Differe...
Comparative Study of Different Types of Bracing Systems by Placing at Differe...Comparative Study of Different Types of Bracing Systems by Placing at Differe...
Comparative Study of Different Types of Bracing Systems by Placing at Differe...
 
Effect of Base Isolation on Seismic Performance of RC Irregular Buildings
Effect of Base Isolation on Seismic Performance of RC Irregular BuildingsEffect of Base Isolation on Seismic Performance of RC Irregular Buildings
Effect of Base Isolation on Seismic Performance of RC Irregular Buildings
 
IRJET- Seismic Behaviour of Buildings Resting on Sloping Ground
IRJET- Seismic Behaviour of Buildings Resting on Sloping GroundIRJET- Seismic Behaviour of Buildings Resting on Sloping Ground
IRJET- Seismic Behaviour of Buildings Resting on Sloping Ground
 
IRJET- Seismic Analysis of Asymmetric RCC Buildings using Passive Energy Diss...
IRJET- Seismic Analysis of Asymmetric RCC Buildings using Passive Energy Diss...IRJET- Seismic Analysis of Asymmetric RCC Buildings using Passive Energy Diss...
IRJET- Seismic Analysis of Asymmetric RCC Buildings using Passive Energy Diss...
 
IRJET- Analysis of Steel Braced Symmetrical RCC Building with Designed I-...
IRJET-  	  Analysis of Steel Braced Symmetrical RCC Building with Designed I-...IRJET-  	  Analysis of Steel Braced Symmetrical RCC Building with Designed I-...
IRJET- Analysis of Steel Braced Symmetrical RCC Building with Designed I-...
 
An analysis of multi-storey building with floating and non-floating column un...
An analysis of multi-storey building with floating and non-floating column un...An analysis of multi-storey building with floating and non-floating column un...
An analysis of multi-storey building with floating and non-floating column un...
 
Effect of Oblique Column and Viscous Damper on Podium Structure Using Etabs
Effect of Oblique Column and Viscous Damper on Podium Structure Using EtabsEffect of Oblique Column and Viscous Damper on Podium Structure Using Etabs
Effect of Oblique Column and Viscous Damper on Podium Structure Using Etabs
 
Effect of Brick Infill Wall and Shear Wall in the Design of RC Framed Regular...
Effect of Brick Infill Wall and Shear Wall in the Design of RC Framed Regular...Effect of Brick Infill Wall and Shear Wall in the Design of RC Framed Regular...
Effect of Brick Infill Wall and Shear Wall in the Design of RC Framed Regular...
 
IRJET - Seismic Analysis of RCC Framed Structure using Different Isolator
IRJET -  	  Seismic Analysis of RCC Framed Structure using Different IsolatorIRJET -  	  Seismic Analysis of RCC Framed Structure using Different Isolator
IRJET - Seismic Analysis of RCC Framed Structure using Different Isolator
 
Comparative Parametric Study of Seismic Behaviour of RC Framed Building With ...
Comparative Parametric Study of Seismic Behaviour of RC Framed Building With ...Comparative Parametric Study of Seismic Behaviour of RC Framed Building With ...
Comparative Parametric Study of Seismic Behaviour of RC Framed Building With ...
 
Seismic Analysis of Multistoreyed RC Building Due to Mass Irregularity by Tim...
Seismic Analysis of Multistoreyed RC Building Due to Mass Irregularity by Tim...Seismic Analysis of Multistoreyed RC Building Due to Mass Irregularity by Tim...
Seismic Analysis of Multistoreyed RC Building Due to Mass Irregularity by Tim...
 
IRJET- Comparative Study of RC Building with Different Bracing System and Fri...
IRJET- Comparative Study of RC Building with Different Bracing System and Fri...IRJET- Comparative Study of RC Building with Different Bracing System and Fri...
IRJET- Comparative Study of RC Building with Different Bracing System and Fri...
 
Analysis and Design of G+3 Residential Building using STRUDS
Analysis and Design of G+3 Residential Building using STRUDSAnalysis and Design of G+3 Residential Building using STRUDS
Analysis and Design of G+3 Residential Building using STRUDS
 
Effect of Presence of Infills in Ground Storey on Seismic Performance of R.C....
Effect of Presence of Infills in Ground Storey on Seismic Performance of R.C....Effect of Presence of Infills in Ground Storey on Seismic Performance of R.C....
Effect of Presence of Infills in Ground Storey on Seismic Performance of R.C....
 
Seismic optimization of horizontally irregular buildings with floating column...
Seismic optimization of horizontally irregular buildings with floating column...Seismic optimization of horizontally irregular buildings with floating column...
Seismic optimization of horizontally irregular buildings with floating column...
 
IRJET- Analysis of G+15 Building Different Seismic Zones of India
IRJET-  	  Analysis of G+15 Building Different Seismic Zones of IndiaIRJET-  	  Analysis of G+15 Building Different Seismic Zones of India
IRJET- Analysis of G+15 Building Different Seismic Zones of India
 
IRJET- Analysis the Behavior of Coupled Shear Wall in High Rise Building with...
IRJET- Analysis the Behavior of Coupled Shear Wall in High Rise Building with...IRJET- Analysis the Behavior of Coupled Shear Wall in High Rise Building with...
IRJET- Analysis the Behavior of Coupled Shear Wall in High Rise Building with...
 
Effect of infill walls on the seismic performance of the multistoried buildings
Effect of infill walls on the seismic performance of the multistoried buildingsEffect of infill walls on the seismic performance of the multistoried buildings
Effect of infill walls on the seismic performance of the multistoried buildings
 

More from IRJET Journal

More from IRJET Journal (20)

TUNNELING IN HIMALAYAS WITH NATM METHOD: A SPECIAL REFERENCES TO SUNGAL TUNNE...
TUNNELING IN HIMALAYAS WITH NATM METHOD: A SPECIAL REFERENCES TO SUNGAL TUNNE...TUNNELING IN HIMALAYAS WITH NATM METHOD: A SPECIAL REFERENCES TO SUNGAL TUNNE...
TUNNELING IN HIMALAYAS WITH NATM METHOD: A SPECIAL REFERENCES TO SUNGAL TUNNE...
 
STUDY THE EFFECT OF RESPONSE REDUCTION FACTOR ON RC FRAMED STRUCTURE
STUDY THE EFFECT OF RESPONSE REDUCTION FACTOR ON RC FRAMED STRUCTURESTUDY THE EFFECT OF RESPONSE REDUCTION FACTOR ON RC FRAMED STRUCTURE
STUDY THE EFFECT OF RESPONSE REDUCTION FACTOR ON RC FRAMED STRUCTURE
 
A COMPARATIVE ANALYSIS OF RCC ELEMENT OF SLAB WITH STARK STEEL (HYSD STEEL) A...
A COMPARATIVE ANALYSIS OF RCC ELEMENT OF SLAB WITH STARK STEEL (HYSD STEEL) A...A COMPARATIVE ANALYSIS OF RCC ELEMENT OF SLAB WITH STARK STEEL (HYSD STEEL) A...
A COMPARATIVE ANALYSIS OF RCC ELEMENT OF SLAB WITH STARK STEEL (HYSD STEEL) A...
 
Effect of Camber and Angles of Attack on Airfoil Characteristics
Effect of Camber and Angles of Attack on Airfoil CharacteristicsEffect of Camber and Angles of Attack on Airfoil Characteristics
Effect of Camber and Angles of Attack on Airfoil Characteristics
 
A Review on the Progress and Challenges of Aluminum-Based Metal Matrix Compos...
A Review on the Progress and Challenges of Aluminum-Based Metal Matrix Compos...A Review on the Progress and Challenges of Aluminum-Based Metal Matrix Compos...
A Review on the Progress and Challenges of Aluminum-Based Metal Matrix Compos...
 
Dynamic Urban Transit Optimization: A Graph Neural Network Approach for Real-...
Dynamic Urban Transit Optimization: A Graph Neural Network Approach for Real-...Dynamic Urban Transit Optimization: A Graph Neural Network Approach for Real-...
Dynamic Urban Transit Optimization: A Graph Neural Network Approach for Real-...
 
Structural Analysis and Design of Multi-Storey Symmetric and Asymmetric Shape...
Structural Analysis and Design of Multi-Storey Symmetric and Asymmetric Shape...Structural Analysis and Design of Multi-Storey Symmetric and Asymmetric Shape...
Structural Analysis and Design of Multi-Storey Symmetric and Asymmetric Shape...
 
A Review of “Seismic Response of RC Structures Having Plan and Vertical Irreg...
A Review of “Seismic Response of RC Structures Having Plan and Vertical Irreg...A Review of “Seismic Response of RC Structures Having Plan and Vertical Irreg...
A Review of “Seismic Response of RC Structures Having Plan and Vertical Irreg...
 
A REVIEW ON MACHINE LEARNING IN ADAS
A REVIEW ON MACHINE LEARNING IN ADASA REVIEW ON MACHINE LEARNING IN ADAS
A REVIEW ON MACHINE LEARNING IN ADAS
 
Long Term Trend Analysis of Precipitation and Temperature for Asosa district,...
Long Term Trend Analysis of Precipitation and Temperature for Asosa district,...Long Term Trend Analysis of Precipitation and Temperature for Asosa district,...
Long Term Trend Analysis of Precipitation and Temperature for Asosa district,...
 
P.E.B. Framed Structure Design and Analysis Using STAAD Pro
P.E.B. Framed Structure Design and Analysis Using STAAD ProP.E.B. Framed Structure Design and Analysis Using STAAD Pro
P.E.B. Framed Structure Design and Analysis Using STAAD Pro
 
A Review on Innovative Fiber Integration for Enhanced Reinforcement of Concre...
A Review on Innovative Fiber Integration for Enhanced Reinforcement of Concre...A Review on Innovative Fiber Integration for Enhanced Reinforcement of Concre...
A Review on Innovative Fiber Integration for Enhanced Reinforcement of Concre...
 
Survey Paper on Cloud-Based Secured Healthcare System
Survey Paper on Cloud-Based Secured Healthcare SystemSurvey Paper on Cloud-Based Secured Healthcare System
Survey Paper on Cloud-Based Secured Healthcare System
 
Review on studies and research on widening of existing concrete bridges
Review on studies and research on widening of existing concrete bridgesReview on studies and research on widening of existing concrete bridges
Review on studies and research on widening of existing concrete bridges
 
React based fullstack edtech web application
React based fullstack edtech web applicationReact based fullstack edtech web application
React based fullstack edtech web application
 
A Comprehensive Review of Integrating IoT and Blockchain Technologies in the ...
A Comprehensive Review of Integrating IoT and Blockchain Technologies in the ...A Comprehensive Review of Integrating IoT and Blockchain Technologies in the ...
A Comprehensive Review of Integrating IoT and Blockchain Technologies in the ...
 
A REVIEW ON THE PERFORMANCE OF COCONUT FIBRE REINFORCED CONCRETE.
A REVIEW ON THE PERFORMANCE OF COCONUT FIBRE REINFORCED CONCRETE.A REVIEW ON THE PERFORMANCE OF COCONUT FIBRE REINFORCED CONCRETE.
A REVIEW ON THE PERFORMANCE OF COCONUT FIBRE REINFORCED CONCRETE.
 
Optimizing Business Management Process Workflows: The Dynamic Influence of Mi...
Optimizing Business Management Process Workflows: The Dynamic Influence of Mi...Optimizing Business Management Process Workflows: The Dynamic Influence of Mi...
Optimizing Business Management Process Workflows: The Dynamic Influence of Mi...
 
Multistoried and Multi Bay Steel Building Frame by using Seismic Design
Multistoried and Multi Bay Steel Building Frame by using Seismic DesignMultistoried and Multi Bay Steel Building Frame by using Seismic Design
Multistoried and Multi Bay Steel Building Frame by using Seismic Design
 
Cost Optimization of Construction Using Plastic Waste as a Sustainable Constr...
Cost Optimization of Construction Using Plastic Waste as a Sustainable Constr...Cost Optimization of Construction Using Plastic Waste as a Sustainable Constr...
Cost Optimization of Construction Using Plastic Waste as a Sustainable Constr...
 

Recently uploaded

DeepFakes presentation : brief idea of DeepFakes
DeepFakes presentation : brief idea of DeepFakesDeepFakes presentation : brief idea of DeepFakes
DeepFakes presentation : brief idea of DeepFakes
MayuraD1
 
Hospital management system project report.pdf
Hospital management system project report.pdfHospital management system project report.pdf
Hospital management system project report.pdf
Kamal Acharya
 

Recently uploaded (20)

Linux Systems Programming: Inter Process Communication (IPC) using Pipes
Linux Systems Programming: Inter Process Communication (IPC) using PipesLinux Systems Programming: Inter Process Communication (IPC) using Pipes
Linux Systems Programming: Inter Process Communication (IPC) using Pipes
 
Ground Improvement Technique: Earth Reinforcement
Ground Improvement Technique: Earth ReinforcementGround Improvement Technique: Earth Reinforcement
Ground Improvement Technique: Earth Reinforcement
 
Introduction to Serverless with AWS Lambda
Introduction to Serverless with AWS LambdaIntroduction to Serverless with AWS Lambda
Introduction to Serverless with AWS Lambda
 
457503602-5-Gas-Well-Testing-and-Analysis-pptx.pptx
457503602-5-Gas-Well-Testing-and-Analysis-pptx.pptx457503602-5-Gas-Well-Testing-and-Analysis-pptx.pptx
457503602-5-Gas-Well-Testing-and-Analysis-pptx.pptx
 
DeepFakes presentation : brief idea of DeepFakes
DeepFakes presentation : brief idea of DeepFakesDeepFakes presentation : brief idea of DeepFakes
DeepFakes presentation : brief idea of DeepFakes
 
NO1 Top No1 Amil Baba In Azad Kashmir, Kashmir Black Magic Specialist Expert ...
NO1 Top No1 Amil Baba In Azad Kashmir, Kashmir Black Magic Specialist Expert ...NO1 Top No1 Amil Baba In Azad Kashmir, Kashmir Black Magic Specialist Expert ...
NO1 Top No1 Amil Baba In Azad Kashmir, Kashmir Black Magic Specialist Expert ...
 
Hospital management system project report.pdf
Hospital management system project report.pdfHospital management system project report.pdf
Hospital management system project report.pdf
 
Unit 4_Part 1 CSE2001 Exception Handling and Function Template and Class Temp...
Unit 4_Part 1 CSE2001 Exception Handling and Function Template and Class Temp...Unit 4_Part 1 CSE2001 Exception Handling and Function Template and Class Temp...
Unit 4_Part 1 CSE2001 Exception Handling and Function Template and Class Temp...
 
Ghuma $ Russian Call Girls Ahmedabad ₹7.5k Pick Up & Drop With Cash Payment 8...
Ghuma $ Russian Call Girls Ahmedabad ₹7.5k Pick Up & Drop With Cash Payment 8...Ghuma $ Russian Call Girls Ahmedabad ₹7.5k Pick Up & Drop With Cash Payment 8...
Ghuma $ Russian Call Girls Ahmedabad ₹7.5k Pick Up & Drop With Cash Payment 8...
 
UNIT 4 PTRP final Convergence in probability.pptx
UNIT 4 PTRP final Convergence in probability.pptxUNIT 4 PTRP final Convergence in probability.pptx
UNIT 4 PTRP final Convergence in probability.pptx
 
Computer Networks Basics of Network Devices
Computer Networks  Basics of Network DevicesComputer Networks  Basics of Network Devices
Computer Networks Basics of Network Devices
 
Theory of Time 2024 (Universal Theory for Everything)
Theory of Time 2024 (Universal Theory for Everything)Theory of Time 2024 (Universal Theory for Everything)
Theory of Time 2024 (Universal Theory for Everything)
 
Bhubaneswar🌹Call Girls Bhubaneswar ❤Komal 9777949614 💟 Full Trusted CALL GIRL...
Bhubaneswar🌹Call Girls Bhubaneswar ❤Komal 9777949614 💟 Full Trusted CALL GIRL...Bhubaneswar🌹Call Girls Bhubaneswar ❤Komal 9777949614 💟 Full Trusted CALL GIRL...
Bhubaneswar🌹Call Girls Bhubaneswar ❤Komal 9777949614 💟 Full Trusted CALL GIRL...
 
Tamil Call Girls Bhayandar WhatsApp +91-9930687706, Best Service
Tamil Call Girls Bhayandar WhatsApp +91-9930687706, Best ServiceTamil Call Girls Bhayandar WhatsApp +91-9930687706, Best Service
Tamil Call Girls Bhayandar WhatsApp +91-9930687706, Best Service
 
FEA Based Level 3 Assessment of Deformed Tanks with Fluid Induced Loads
FEA Based Level 3 Assessment of Deformed Tanks with Fluid Induced LoadsFEA Based Level 3 Assessment of Deformed Tanks with Fluid Induced Loads
FEA Based Level 3 Assessment of Deformed Tanks with Fluid Induced Loads
 
Basic Electronics for diploma students as per technical education Kerala Syll...
Basic Electronics for diploma students as per technical education Kerala Syll...Basic Electronics for diploma students as per technical education Kerala Syll...
Basic Electronics for diploma students as per technical education Kerala Syll...
 
HOA1&2 - Module 3 - PREHISTORCI ARCHITECTURE OF KERALA.pptx
HOA1&2 - Module 3 - PREHISTORCI ARCHITECTURE OF KERALA.pptxHOA1&2 - Module 3 - PREHISTORCI ARCHITECTURE OF KERALA.pptx
HOA1&2 - Module 3 - PREHISTORCI ARCHITECTURE OF KERALA.pptx
 
Max. shear stress theory-Maximum Shear Stress Theory ​ Maximum Distortional ...
Max. shear stress theory-Maximum Shear Stress Theory ​  Maximum Distortional ...Max. shear stress theory-Maximum Shear Stress Theory ​  Maximum Distortional ...
Max. shear stress theory-Maximum Shear Stress Theory ​ Maximum Distortional ...
 
DC MACHINE-Motoring and generation, Armature circuit equation
DC MACHINE-Motoring and generation, Armature circuit equationDC MACHINE-Motoring and generation, Armature circuit equation
DC MACHINE-Motoring and generation, Armature circuit equation
 
Orlando’s Arnold Palmer Hospital Layout Strategy-1.pptx
Orlando’s Arnold Palmer Hospital Layout Strategy-1.pptxOrlando’s Arnold Palmer Hospital Layout Strategy-1.pptx
Orlando’s Arnold Palmer Hospital Layout Strategy-1.pptx
 

Seismic Performance of Symmetrical Building with & without Isolators

  • 1. International Research Journal of Engineering and Technology (IRJET) e-ISSN: 2395-0056 Volume: 04 Issue: 11 | Nov -2017 www.irjet.net p-ISSN: 2395-0072 © 2017, IRJET | Impact Factor value: 6.171 | ISO 9001:2008 Certified Journal | Page 1872 SEISMIC PERFORMANCE OF SYMMETRICAL BUILDING WITH & WITHOUT ISOLATORS Miss. Sushma G.Sawadatkar1, Prof.M.M.Joshi2 1 Student, Dept. Of Civil Engineering, PLITMS Buldana, Maharashtra, India 2Assistant Professor, Dept. of Civil Engineering, PLITMS Buldana, Maharashtra, India ---------------------------------------------------------------------***--------------------------------------------------------------------- Abstract - Earthquake is one of the nature’s greatest hazards, throughout historic timetheyhavecausedsignificant loss of life and severe damage to property, especially to Man- Made Structures. Base Isolation is an effective method for earthquake resistant design to reduce vibration transmitted from ground to the structure. Base isolation, is also known as seismic base isolation or base isolation system, Is one of the most popular means protecting a structure against earthquake forces. It is a collection of Structural elements which should substantially decouple a Superstructurefromits substructure resting on a shaking Ground. In this paper, An G+6 Storey building is modeledandanalyzed withand without base isolators by using Finite Element Based Software. The main purpose of this work is to study the Dynamic response of the building with fixed base and same building with Base isolation System Such as Lead Rubber Bearing isolator. In this project, the Seismic performances, Shear force, Bending moment and steel Consumptions of the fixedbasebuildingand Lead Rubber Base Isolation System is presented. Key Words: Lead Rubber bearing Isolator (LRB), Analysis, Seismic, SAP 2000, Base Isolator 1. INTRODUCTION Base isolation is an effective means for protection of structure during earthquake events. The concept of Base isolation is to insert a flexible layer between foundation and superstructure thus decoupling the building from damaging action of ground motion. This results in reduced frequency range and dissipates energy through damping. In this study an attempt is made to improvetheperformance of symmetrical and asymmetrical buildingsbyincorporating lead rubber base isolators at bottom level of columns. for this, symmetrical and asymmetrical buildings models with and without base isolators are considered. The 3D analysis of building is carried out for earthquake zone III. The response spectrum analysis is carried out on all the mathematical 3D models using the software SAP 2000. The results obtain from the analysis are discussed in next sections. 1.1 Seismic Performance of Symmetrical Building with & without Isolators There are total two symmetrical models under consideration, out of which first model iswithoutisolator i.e. fixed base and in second models, lead rubber base isolator with all properties provided by manufacturer are used at base storey to improve seismic performance of such type of building. For comparison purpose, lateral displacements, storey drifts, base shear, time period,frequencies,maximum forces in columns at bottom are chosen. Fig -1: Symmetrical Building without Isolator Fig -1: Symmetrical Building with Isolator
  • 2. International Research Journal of Engineering and Technology (IRJET) e-ISSN: 2395-0056 Volume: 04 Issue: 11 | Nov -2017 www.irjet.net p-ISSN: 2395-0072 © 2017, IRJET | Impact Factor value: 6.171 | ISO 9001:2008 Certified Journal | Page 1873 2. Comparison of results for symmetrical type buildings Response spectrum analysis is carried out on all the models. The results are presented in the form of graphs and tables. 2.1 Lateral Displacement The floor wise lateral displacements are tabulated in table 2.1 for both models i.e. building without isolator and building without isolator. Also a graph is plotted takingfloor level as the abscissa and the displacementastheordinatefor both models in both the longitudinal and transverse direction as shown in Chart 1 Table 2.1: Displacement at Floor Levels for Both with and Without Isolator Building (Symmetrical) Storey Without Isolator (mm) With Isolator(mm) 6 15.73 33.90 5 14.90 33.61 4 13.50 33.12 3 11.55 32.41 2 9.12 31.47 1 6.30 30.25 G 3.25 28.47 Chart -1: Displacement Profile for Both with and Without Isolator Building (Symmetrical) From the displacement profile it is observed that there is considerable increase in displacementafterincorporation of base isolator as compared to fixed base without isolator building. The maximum displacement at top level is increased 115%. 2.2 Storey Drift The floor wise storey drift are tabulated in table 2.2 for both models i.e. building without isolator and building without isolator. Also a graph is plotted taking floor level as the abscissa and the drift as the ordinate for both modelsinboth the longitudinal and transverse direction as shown in Chart 2 Table 2.2: Drift at Floor Levels for Both with and Without Isolator Building (Symmetrical) Storey Without Isolator (mm) With Isolator (mm) 6 0.83 0.29 5 1.4 0.49 4 1.95 0.71 3 2.43 0.94 2 2.82 1.22 1 3.05 1.78 Chart -2: Drift Profile for Both with and Without Isolator Building (Symmetrical) From the drift profile it is observed that there is sufficient decrement in drift after incorporation of base isolator as compared to fixed base without isolator building which is very beneficial from stability point of view. The drift at all the levels are decreased by 40-65%. 2.3 Base Shear The base shear for both building models with and without isolator are tabulated in table 2.3 also the graphical representation of the same is shown in Chart 3
  • 3. International Research Journal of Engineering and Technology (IRJET) e-ISSN: 2395-0056 Volume: 04 Issue: 11 | Nov -2017 www.irjet.net p-ISSN: 2395-0072 © 2017, IRJET | Impact Factor value: 6.171 | ISO 9001:2008 Certified Journal | Page 1874 Table 5.3: Base Shear for Both with and Without Isolator Building (Symmetrical) Storey Without Isolator (kN) With Isolator (kN) Base 1050 463.19 Chart -3: Base Shear for Both with and Without Isolator Building (Symmetrical) Base shear of the building considerably decreases after incorporation of base isolator which is due to flexible behavior of building. The base shear is decreasedby56%for building with isolator. 2.4 Time Period The time period for both building models with and without isolator are tabulated in table 2.4 Also a graph is plotted taking modes on the X axis and time period in second on Y axis for both the building models as shown in the Chart 4 below. Table 5.4: Time Period for Different Modes for Both with and Without Isolator Building (Symmetrical) Mode Without Isolator (Sec) With Isolator (Sec) 1 0.459 2.682 2 0.459 2.682 3 0.430 2.524 4 0.084 0.468 5 0.080 0.468 6 0.080 0.425 7 0.076 0.222 8 0.075 0.222 9 0.075 0.206 10 0.072 0.140 11 0.072 0.140 12 0.071 0.131 Chart -4: Time Period for Both with and Without Isolator Building (Symmetrical) It is observed that the time period of vibration is more for building with isolator. The increment is of 484%. 2.5 Frequency The frequencies for both building models with and without isolator are tabulated in table 2.5 Also a graph is plotted taking modes on the X axis and time period in second on Y axis for both the building models as shown in the Chart 5 below. Table 5.5: Frequency for Different Modes for Both with and Without Isolator Building (Symmetrical) Mode Without Isolator (m/sec) With Isolator (m/sec) 1 2.1773 0.3729 2 2.1773 0.3729 3 2.3248 0.3963 4 11.861 2.1362 5 12.474 2.1362 6 12.474 2.3539 7 13.106 4.4986 8 13.297 4.4986 9 13.304 4.8486 10 13.955 7.1579 11 13.955 7.1579 12 14.033 7.6190
  • 4. International Research Journal of Engineering and Technology (IRJET) e-ISSN: 2395-0056 Volume: 04 Issue: 11 | Nov -2017 www.irjet.net p-ISSN: 2395-0072 © 2017, IRJET | Impact Factor value: 6.171 | ISO 9001:2008 Certified Journal | Page 1875 Chart -5: Frequencies for Both with and Without Isolator Building (Symmetrical) It is observed that the frequency is reduced for buildingwith isolator. The decrement is of 82%. 2.6 Maximum Bending Moment in Columns The maximum bending moment in column at bottom storey for both building models with and without isolator are tabulated in table 5.6 also the graphical representationofthe same is shown in Chart 6 Table 5.6: Maximum Bending Moment in Column at Bottom Storey for Both with and Without Isolator Building (Symmetrical) Storey Without Isolator (kNm) With Isolator (kNm) G 45.23 18.62 Chart -6: Maximum Bending Moment in Columns at Bottom Storey for Both with and Without Isolator Building (Symmetrical) Maximum bending moment in bottom storey of the building significantly decreases after incorporation of base isolator which is due to flexible behavior of building. The moment is decreased by 58% for building with isolator. 2.7 Maximum Shear in Columns The maximum shear in column at bottom storey for both building models with and without isolator are tabulated in table 2.7 also the graphical representation of the same is shown in Chart 7 Table 5.7: Maximum Shear in Column at Bottom Storey for Both with and Without Isolator Building (Symmetrical) Storey Without Isolator (kN) With Isolator (kN) G 116.87 74.47 Chart -7: Maximum Shear Force in Columns at Bottom Storey for Both with and Without Isolator Building (Symmetrical) Maximum shear force in bottom storey of the building significantly decreases after incorporation of base isolator which is due to flexible behavior of building. The shear is decreased by 36% for building with isolator. 2.8 Maximum reinforcement in Columns The maximum reinforcement in column at bottomstorey for both building modelswithandwithoutisolatoraretabulated in table 2.8 also the graphical representation of the same is shown in Chart 8
  • 5. International Research Journal of Engineering and Technology (IRJET) e-ISSN: 2395-0056 Volume: 04 Issue: 11 | Nov -2017 www.irjet.net p-ISSN: 2395-0072 © 2017, IRJET | Impact Factor value: 6.171 | ISO 9001:2008 Certified Journal | Page 1876 Table 5.8: Maximum Reinforcement in Column at Bottom Storey for Both with and Without Isolator Building (Symmetrical) Storey Without Isolator (sq mm.) With Isolator (sq mm.) G 2000 2357 Chart -8: Maximum Reinforcement in Columns at Bottom Storey for Both with and Without Isolator Building (Symmetrical) Maximum reinforcement in bottom storey of the building slightly increases after incorporation of base isolator which is due to flexible behavior of building. The reinforcement is increased by 17% for building with isolator. 3. CONCLUSIONS Based on the analysis results following conclusions are drawn; 1. Building becomes more flexible as compared to fixed base building which will improve the performance in earthquake excitation. 2. Base isolation system is the effective one in reducing the structural response as compared to fixed base building. 3. From the analytical results, it is observed that how effective seismic isolation works by considering various aspects such as: base shear, maximum bending moments, & column shears, etc. Analysis results of the study suggestthatrubberisolatorsare better option to improve performance of buildings. 4. Base isolation basically reduces the demand forces by shifting the time period of the structure. 5. Storey drift also reduced from 40% to 65% for both symmetrical and asymmetrical building. 6. The Base isolation considerably increases the lateral displacement. As observed the lateral displacement at top storey is increased up to 115% for both symmetrical and asymmetrical building as that of fixed one. 7. The Base isolation substantially increases the time period of the building & hence correspondingly reduces the base shear. As observedthetimeperiod is being increased by 484% for symmetrical building and 155% for asymmetrical building & base shear is reduced up to 55% for both symmetrical and asymmetrical building of that of fixed one. 8. By considering the bending moment values of columns, it is clearly observed that for isolated case the maximum bending moment is reduced up to 58% as that of fixed case. 9. The shear force values of columns shows that the ground storey columns are reduced up to 36% for isolated frame when compared fixed base building. 10. The reinforcement requirement of columns shows that the ground storey columns are increased up to 17% for isolated frame when compared fixed base building. REFERENCES [1] Satish Nagarajaiah (Journal of Structural Engineering, Vol. 119, No. 10) October, 1993 (Torsion in base-isolated structures with elastomeric isolation systems) [2] J. C. Ramallo (JOURNAL OF ENGINEERING MECHANICS ) OCTOBER 2002 (Smart’’ Base Isolation Systems) [3] Xi-Yuan Zhou (ISET Journal of Earthquake Technology, Paper No. 436) Vol. 40, No. 2- 4, June- December 2003,( Study on protection measures for seismic isolation rubber bearings , pp. 137-160) [4] Khante.S.N, Lavkesh R.Wankhade, ‘, International journal of civil and structural engineering) Volume X, No X, 2010 (Study of seismic response of symmetric and asymmetric base isolated building with mass asymmetry in plan) [5] A. B. M. Saiful Islam , Mohammed Jameel (International Journal of the Physical Sciences) Vol. 6(11), ,4 June, 2011 (Study on corollary of seismic base isolation system on buildings with soft storey, pp. 2654-2661) [6] KS Sable, J S Khose, V P Kulkarni (International Journal of Engineering and Innovative Technology ,IJEIT) Volume 1, Issue 4, April 2012(Comparisonof
  • 6. International Research Journal of Engineering and Technology (IRJET) e-ISSN: 2395-0056 Volume: 04 Issue: 11 | Nov -2017 www.irjet.net p-ISSN: 2395-0072 © 2017, IRJET | Impact Factor value: 6.171 | ISO 9001:2008 Certified Journal | Page 1877 Different Bearing Types Performance in Multistoried Building). [7] S.J.Patil (International Journal of Emerging Technology and Advanced Engineering) ISSN 2250- 2459, Volume 2, Issue 7,July 2012 (State Of Art Review - Base Isolation Systems For Structures). [8] Shirule Pravin Ashok (International Journal ofCivil, Structural, Environmental and Infrastructure Engineering Research and Development ) ISSN 2249-6866 Vol.2, Issue 3, Sep2012 (Response spectrum analysis of multi storeyed base-isolated building, 66-75) [9] Chauhan Kalpesh M. (International Journal of Advanced EngineeringResearchand Studies)Vol.II, April-June, 2013 (Excel spreadsheet for design of lead rubber bearing uses for seismic Isolation of bridges, P.P 60-62) [10] Ashish R. Akhare, Tejas R.Wankhade (International journal of engineering sciences & research) 3(5) (Seismic Performance of RC Structure Using Different Base Isolator, May, 2014)