Design of a Single Phase Isolated Bidirectional AC to
DC Converter for Battery Energy Storage Systems
Queen’s University ELEC 497 Research Project
Tom Gibson 10163463 14tagg@queensu.ca
Completed with the assistance of Prof. Praveen K. Jain and Mr. Behnam Koushki.
Abstract— This paper analyses the design of a 3 kW isolated
bidirectional ac to dc converter for Battery Energy Storage
Systems (BESS). This is an increasingly popular solution to
overcome the differences seen in electricity supply and demand
introduced by renewable energy sources. In order to connect these
systems to the grid an ac to dc converter is required. In this paper
a converter is considered to interface a 300 V battery bank to the
grid at 110 V, 60 Hz ac. A dual active bridge is implemented with
a 100 kHz transformer. Control systems for the converter are also
considered allowing autonomous regulation of the power flow to
and from the storage.
Index Terms—Battery energy storage, dual active bridge,
bidirectional isolated ac-dc converter.
I. INTRODUCTION
Over recent years a huge increase has been seen in the use of
renewable power generation in our energy supply networks as
many governments aim to promote clean sources over fossil
fuels as a response to global climate change. While renewable
technologies are much cleaner than traditional methods of grid
scale generation they lack the controllability of traditional
generation. For example a wind farm will typically be more
productive at night when winds are stronger, but at this time
demand is low. The output of a coal or gas power plant can be
adjusted accordingly within reason, but this is more
complicated with renewable power sources so imbalances
between supply and demand often occur.
Figure 1. presents the typical electricity supply and demand
for a day in Ontario [1]. During the daytime demand is greater
than total supply, and at night demand is much lower than
supply. Where these imbalances occur power is normally
imported from or exported to other regions.
One approach to overcome these imbalances is to implement
an energy storage system. These can range in size from large
systems such as megawatt scale hydro storage to smaller
projects such as kilowatt scale flywheels. As battery technology
is improved and the demand for distributed generation is
increased, battery energy storage systems (BESS) are growing
in popularity. The high charge and discharge efficiency and
energy density of lithium-ion based battery systems makes
them a highly favorable solution [2].
Fig. 1. Ontario Power Supply and Demand over 8 April 2015 [1].
In order to connect the dc BESS to the ac grid some form of
voltage converter is required. A popular approach is to use the
bridge circuit in Fig. 2. [3]. This circuit uses four metal-oxide-
semiconductor field-effect-transistors (MOSFETs), each
paralleled with a lossless diode to alter the voltage signal.
The circuit operates as a boost rectifier when power needs to
be transferred from the ac grid to the dc batteries. The current
flows for this operation are shown in Fig. 2.(a). When the
MOSFET switches are off (or open) the current flows through
the diodes to reach Vdc. i.e. for the positive cycle of vac there is
current flow through the diodes D1 and D3 following the solid
blue lines. Similarly, during the negative cycle of vac there is
current flow through the diodes D2 and D4, in the direction of
the dashed orange lines. When the MOSFETs are turned on (or
are closed) current is allowed to flow through them, thus
bypassing the capacitor and charging the inductor (i.e. for the
positive ac cycle the current flow is through D1 and S2, along
the dotted green line). This stored charge is injected back into
the capacitor once the switches are opened again at a high
voltage. This allows Vdc to be much larger than vac. The
magnitude of the dc voltage can be controlled by altering the
duty cycle of the MOSFETs.
When operating in inverter mode (Fig. 2.(c)) the diodes
become redundant and the MOSFETS are used to control the ac
voltage frequency and RMS magnitude. The graph in Fig. 2.(d).
indicates when each of the switches is turned on and the ac
waveform which is subsequently produced. The ac voltage has
fundamental and odd harmonics and is given by Eq. 1.
Ontario demand
Projected
Actual
Market demand
Projected
Actual
2
Fig. 2. (a) Circuit schematic for bidirectional ac/dc converter in rectifier mode; (b) Rectifier input and output waveforms (vac and Vdc respectively);
(c) Circuit schematic for bidirectional ac/dc converter in inverter mode; (d) Inverter input and output waveforms (Vdc and vac respectively).
𝑣 𝑎𝑐 𝑝𝑒𝑎𝑘 =
4𝑉 𝑑𝑐
𝜋
∑
1
𝑛
sin (
𝑛𝜋
2
) sin (
𝑛𝛿
2
)sin(𝑛𝜔𝑡)∞
𝑛=1,3
(1) [4]
The RMS magnitude of vac can be controlled by adjusting the
pulse angle δ as shown in Fig. 3. Therefore adjusting the switch
period alters the voltage. The ac voltage frequency is half of the
switching frequency and can be controlled by adjusting the
switching frequency.
Fig. 3. Fundamental and harmonics of inverter ac output voltage against pulse
width angle δ.
While this makes an effective voltage converter it also
requires a high dc bus voltage, higher than the ac source
voltage. A reduction in the dc voltage would have the advantage
of reducing the battery pack voltage or the required number of
series battery cells. The system stability would also be
increased. One method of reducing the voltage would be to add
a transformer at the grid side, however at the low grid frequency
transformers need to be large and tend to be expensive. An
alternative solution is to add an isolated dc to dc converter to
the dc side, composed of two more bridges tied together by a
high frequency transformer, as in Fig. 4. [5]. This is known as
a dual active bridge (DAB) [6], [7]. The high frequency
transformer can be made much smaller and less expensive than
the low frequency equivalent and will have improved
efficiency.
The converter shown in Fig. 4. can be considered as a two
stage device. Stage 1 uses a single converter bridge to convert
the ac grid voltage to dc. In Stage 2, Bridge B converts the dc
voltage, Vo, back to ac but at a much higher frequency than the
source voltage. The ac voltage is reduced by the transformer
then converted back to dc by Bridge C for connection to the
batteries.
In this paper the analysis and design of this system is
considered for a BESS with the parameters outlined in Table I.
The DAB design is considered first before being applied to the
rest of the system.
0 20 40 60 80 100 120 140 160 180
0
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
1
delta (degrees)
|Vacrms|(pu)
n = 1
n = 3
n = 5
n = 7
Positive half cycle Negative half cycle
Positive cycle inductor charging
Vac
Vdc
(a)
(c)
-1.5
-1
-0.5
0
0.5
1
1.5
0 60 120 180 240 300 360
PerUnitVoltage
ωt (degrees)
vac Vdc
S1S3 S1S4 S2S4 S2S3
δ
(b)
(d)
δ
-2
0
2
4
6
0 60 120 180 240 300 360
PerUnitVoltage
ωt (degrees)
vac vdc Vdc
3
Fig. 4. Circuit schematic of a single phase isolated bidirectional ac/dc converter.
TABLE I. CONVERTER DESIGN PARAMETERS
Voltage Supply (vs) 110 VRMS, 60 Hz AC
Voltage Output (Vo) DC Batteries, 300 V nominal
(Range 250 – 400 V)
Power Output (Po) 3 kW
Stage 1 switching
frequency (fs1)
20 kHz
Stage 2 switching
frequency (fs2)
100 kHz
Switch type MOSFET
II. ANALYSIS AND DESIGN
A. Dual Active Bridge
Analysis of the system is carried out looking from the output
side, under idealized conditions the output power is given by
Eq. 2. [6]
𝑃𝑜 =
𝑉 𝑖
𝑋 𝐿
𝑑𝜑 (1 −
|𝜑|
𝜋
) (2)
where
𝑋 𝐿 = 𝜔𝐿 = 2𝜋𝑓𝑠2 𝐿, 𝑑 =
𝑉𝑜
𝑁𝑉 𝑖
In addition to the parameters in Table I., Vi is the dc bus voltage
(voltage over C1 in Fig. 1.), φ is the phase shift between Bridge
B and Bridge C, L is the primary referred leakage inductance of
the transformer and N is the transformer turns ratio.
Po, Vo and fs1 are known from the design parameters. For a
full range of zero voltage switching it is preferred that d = 1,
therefore N = Vo/Vi. Vi needs to be chosen as a value greater
than the maximum source voltage, so for the purpose of this
design Vi = 400 V dc was chosen, giving N = 3/4. With all other
variables (including L) being constant the output power varies
with the phase difference, φ. This relationship is shown in Fig.
5. It is seen that φ can be used to control the output power, and
the maximum occurs when φ = 90°. For the design under
consideration a nominal phase shift of 60° is considered
appropriate so that the output power can be increased slightly if
required or if the system is overloaded. Also, L varies to φ in
the same manner as Po so a smaller φ means smaller L.
Taking these values into consideration the leakage reactance,
XL, can be calculated from Eq. 2 and is found to be 37.23 Ω.
Therefore from this value and at fs2 = 100 kHz, L = 59.26 μH.
Fig. 5. Converter output power (magnitude and direction of flow) against the
phase shift between Bridge B and Bridge C.
Also seen in the above figure is that the direction of power
flow can be controlled by φ as well as its magnitude. Therefore
a closed loop control system can be designed to adjust the phase
shift based on the battery state of charge (SOC) and grid power
requirements. Since the output side is constant voltage the
current flow varies directly with power, so this control system
will also regulate the current flow.
Following the analysis of the DAB converter system it was
assembled in PSIM for proof of concept. The design was
configured as in Fig. 6. with a simple control system. The
capacitors C1 and C2 are introduced to suppress the dc current
ripple caused by switching and for the simulation these were
each set to 1 nF. L represents the transformer primary referred
leakage inductance and was set at 60 μH based on the previous
calculation. The dc voltage sources VDC and Vbattery represent
the desired dc bus and battery voltages respectively. A small
inductor and resistor are connected in series with Vbattery to
represent non-ideal battery characteristics.
Fig. 6. PSIM circuit diagram for dual active bridge.
-1
-0.5
0
0.5
1
-120 -90 -60 -30 0 30 60 90 120
OutputPower,Po(pu) Phase Shift φ°Backwards Power Flow Forwards Power Flow
dc bus
Bridge A Bridge B Bridge C
Stage 1: Bidirectional
AC/DC Converter
Stage 2: Dual Active Bridge DC/DC Converter
High Frequency
Transformer
4
Control of the system was achieved using step voltage inputs
to control each MOSFET bridge. These sources, labelled
VBridgeB and VBridgeC were set to 100 kHz to match the
switching frequency of this stage. The phase delay between
bridges B and C was also controlled using these sources and thus
allowed control over the output current and direction of power
flow. For example under idealised conditions when the phase
delay, φ, is equal to zero degrees the overall power flow should
also be zero, according to Eq. 2. This is observed in Fig. 7.(a).
where the average values of primary transformer current, Ires,
and battery current, Ibattery, are also near zero. When the phase
delay of VBridgeB is set to 60°, i.e. φ =-60°, the result in Fig.
7.(b). is observed. In this case the average current flowing into
the battery is negative, this is the discharging mode. When the
phase delay is applied to VBridgeC, i.e. φ = 60°, the power flow
is reversed and the battery current is positive as in Fig. 7.(c).
This is the charging mode.
(a)
(b)
(c)
(d)
Fig. 7. PSIM simulation results for DAB, (a) when φ = 0°; (b) φ = -60°;
(c) φ = 60°; (d) dc link and battery voltages (similar for each case).
Note that the battery current is not strictly dc due to the
switching effects and phase delay. The resonant circuit current
remains above or below zero in each case due to the leakage
reactance, and has a frequency of 100 kHz, the same as fs2.
In the above analysis it is considered that the winding
resistances are negligible compared to the transformer leakage
reactance. It is also assumed that the magnetizing inductance of
the transformer is infinitely large however this may not be the
case in a real system. The effect of this on the range of soft
switching for the system is considered in the literature [6].
It is given that the magnetizing inductance can be
approximated as Lm = K*L given that L is the leakage
inductance calculated above and K ≥ 1. Therefore for this
system to remain stable Lm ≥ 60 μH.
Simulating the circuit again for stage 2 with the given and
calculated parameters produced the waveforms in Fig. 8. for
K >> 1 and K = 1. It is indicated that the magnetizing
inductance has an effect on the circuit currents. When K >> 1,
i.e. Lm >> L, the currents through the systems follow fairly
smooth and ideal characteristics. As K is reduced the current
edges become sharper with a more triangular waveform
developing. Therefore as K is decreased the region for soft
switching is increased but comes with a trade-off of low
transformer utilization.
(a)
(b)
(c)
Fig. 8. Simulated dual active bridge converter: (a) Primary and secondary
transformer voltages; (b) Input and output current for K >> 1; (c) Input and
output current for K = 1.
5
B. AC Grid Interface
After designing the DAB part of the system the grid and
battery connections may be considered. On the grid side another
converter bridge is connected as mentioned before, indicated as
Stage 1 in Fig. 4. This controls the voltage of the dc bus as well
as acting as a rectifier/inverter between the ac grid and dc bus
[8].
As previously noted when operating as an inverter the ac
voltage magnitude can be adjusted by altering the pulse width,
δ. In this mode the inverter will produce harmonics, the
magnitudes of which are also shown in Fig. 3. However, it is
desirable to have only the fundamental voltage component, so
an LC filter could be implemented at the grid side. In this case
the required pulse width angle to achieve the desired ac voltage
can be found from Eq. 1 where n = 1:
vac1 RMS =
4Vdc
π
𝑠𝑖𝑛 (
δ
2
) ∗
1
√2
𝛿 = 2𝑠𝑖𝑛−1
(
𝑣 𝑎𝑐1∗𝜋
2√2𝑉 𝑑𝑐
)
Therefore for this system where Vdc = 400 V and vac RMS = 110
V it is required that δ = 35.57°. This would switch at the source
frequency, i.e. 60 Hz. A control system can be implemented to
adjust this angle when required based on the grid and battery
conditions, for instance if the dc bus voltage was to change as
the batteries discharge.
In rectifier mode the dc voltage can be given by Eq. 3:
𝑉𝑑𝑐 =
2vac
π
cosα −
2𝐼 𝑑𝑐 𝜔𝐿 𝑠
𝜋
(3)
In this equation α is the control angle and is the phase
difference between vac and the MOSFET firing pulses and Ls is
the source inductance. Therefore the dc voltage varies with Idc
and α, assuming all other parameters are constant. The control
angle is required to be adjusted by a closed loop controller
depending on the required current.
C. Energy Storage Considerations
A number of energy storage solutions are considered by
Vazquez in [3], with their main characteristics outlined in Table
II. For similar applications Li-ion batteries are the preferred
technology thanks to their relatively high energy and power
densities, meaning that more energy can be stored per kilogram
of mass in Li-ion batteries compared to their lead acid or nickel
based counterparts. However due to the relatively low
availability of lithium and the increasing popularity of lithium
based batteries in applications such as electric vehicles the raw
material cost of lithium is likely to increase [9]. In this case
cheaper battery technologies may be used for lower power
applications.
In [8] Li-ion batteries are used for experimental testing of the
isolated bidirectional ac to dc converter. Battery modules are
used, each containing seven cells. With each cell rated at 3.8 V,
each module can supply 26.6 V. Therefore for the system
considered here fifteen series connected batteries are required
TABLE II. Comparison of Energy Storage Systems [3].
to provide the maximum battery voltage of 400 V. Each battery
module is rated at 40 Ah and can be connected to additional
modules in parallel to boost the capacity.
D. Control System
It is preferable for the system to be autonomous and self-
regulate its operation, especially where used in smaller scale or
smart-grid applications. Each stage of the converter requires a
control systemto maintain the desired voltage and current levels.
For stage 1 the system must regulate the dc bus voltage as well
as the grid current to maintain the correct voltage phase and
maintain unity power factor. Meanwhile the control system for
stage 2 maintains the battery current and voltage by means of
controlling φ to regulate the charging and discharging of the
batteries. A potential control strategy is outlined in [5] as
depicted in Fig. 9.
In this example each control system implements a double
closed loop, each with an inner current loop and outer voltage
loop. For Stage 1 (Bridge A) the voltages V1 and vs are
monitored as well as the grid current is. Through altering the
gate signal of each MOSFET (i.e. adjusting δ) control over the
phase and amplitude of vso can be achieved, thus enabling
control over the phase and amplitude of is. This allows for
control over the power flow between the grid and the dc bus,
and regulation of the dc bus voltage, V1. As mentioned
previously the switching frequency is the frequency of vac when
operating in inverter mode, therefore in this mode the switching
frequency should be 60 Hz.
The controller for stage 2 controls the switching signals for
bridges B and C. It does this through monitoring the battery
current and voltage and adjusting d accordingly to regulate the
magnitude and phase of iL. Using these values the state of
charge (SOC) of the batteries can be estimated. However,
determining the exact SOC can be challenging [2] so
monitoring current and voltage can improve the system
accuracy.
Additional control parameters may be applied to the
batteries to provide protection against undervoltage or
overvoltage, overheating and overcurrent. This is necessary
with Li-ion batteries to prevent the internal resistance of the
cells from heating up and failing [3]. Measures to balance the
cell voltages and SOCs are also favorable to maintain the cell
lifetime [2], [3].
6
Fig. 9. Control Strategy for Grid Connected Isolated
Bidirectional AC to DC Converter [5].
E. Converter Efficiency
As with most electronic circuits the considered converter
design is susceptible to energy losses. These losses will mainly
occur in the MOSFETs and the transformer coils. Each switch
will exhibit switching losses due to its rise and fall times,
particularly at high frequencies. However, since this system uses
zero voltage switching these losses should be minimised. There
are also conduction losses through each switch due to the finite
switch resistance. This can be a disadvantage for the converter
using the DAB compared to the single bridge converter since
three times the number of switches are required, tripling the
switching power loss. However since the efficiency of the high
frequency transformer is expected to be much higher than the
equivalent low frequency design the power loss savings here
may outweigh the switching losses, meaning that the isolated
system operates at a higher efficiency overall.
As outlined in [5], with traditional power and magnetic
components it can be difficult to achieve high efficiency and
power density. For this reason it is suggested that newer
switching and transformer technologies are introduced. These
include using silicon carbide (SiC) devices as opposed to the
traditional silicon (Si) devices, as well as replacing ferrite with
nanocrystalline soft magnetic material in transformers and
inductors. However the use ofthese materials will incur a greater
expense when building the system so may not be advised for
lower power applications. From similar reports an efficiency of
around 95% can be expected [5], [8].
III. CONCLUSION
This paper has discussed the role of battery energy storage
systems in our electricity grids for peak shaving and grid
stabilization. The requirement of a bidirectional ac to dc
converter was reviewed in the role of connecting the BESS to
the electricity grid. Furthermore the isolated bidirectional ac to
dc converter was taken into consideration for analysis and
design, the benefits of this system being stated as reducing the
battery bank voltage and the required number of series cells, as
well as increasing system safety by isolating the battery bank
from the grid. This was a two stage converter, with stage one
being a basic full bridge bidirectional ac to dc converter, and
stage two being a dual active bridge dc to dc converter.
During the design process the ideal leakage inductance of the
high frequency transformer was calculated to be L = 59.26 μH.
This would allow for nominal operating conditions when the
phase shift across the DAB was 60°. Simulation of this stage
confirmed that these values were appropriate. Following this a
control method was considered which could adjust the phase
shift on order to regulating the power flow across the DAB,
thereby controlling the charging or discharging of the batteries.
For the battery bank, lithium ion cells were chosen for their high
efficiency and high power density.
Finally the estimated power losses of the system were
discussed and it was noted that the efficiency could be increased
using more advanced switching and transformer materials.
Future work to be carried out could include a more detailed
analysis and design of the control system to devise a solution of
fully automated control. A full system simulation could be
completed and analyzed under various loading conditions,
comparing this converter to alternative designs, before a real
converter is built.
REFERENCES
[1] “IESO Power Data,” The Independent Electricity System
Operator (IESO), 2015. [Online]. Available:
http://www.ieso.ca/Pages/Power-Data/default.aspx#.
[Accessed 09 April 2015].
[2] H. Qian, J. Zhang, J. Lai and W. Yu, “A High-Efficiency
Grid-Tie Battery Energy Storage System,” IEEE
Transactions on Power Electroinics, vol. 26, no. 3, pp.
886-896, 2011.
[3] S. Vazquez, S. Lukic, E. Galvan, L. Franquelo and J.
Carrasco, “Energy Storage Systems for Transport and
Grid Application,” IEEE Transactions on Industrial
Electronics, vol. 57, no. 12, pp. 3881-3895, 2010.
[4] N. Mohan, Power Electronics: Converters, Applications,
And Design, 3rd ed., John Wiley & Sons, 2002.
[5] B. Zhao, Q. Song, W. Liu and Y. Sun, “A Synthetic
Discrete Design Methodology of High-Frequency
Isolated Bidirectional DC/DC Converter for Grid-
Connected Battery Energy Storage System Using
Advanced Components,” Industrial Electronics, IEEE
Transactions on, vol. 61, no. 10, pp. 5402-5410, 2014.
[6] M. Kheraluwala, R. Gascoigne, D. Divan and E.
Baumann, “Performance Characterization of a High-
Power Dual Active Bridge dc-to-dc Converter,” IEEE
Transactions on Industry Applications, vol. 28, no. 6, pp.
1294-1301, 1992.
[7] R. W. A. A. De Doncker, D. M. Divan and M. H.
Kheraluwala, “A Three-phase Soft-Switched High-
Power-Density dc /dc Converter for High-Power
7
Applications,” IEEE Transactions on Industry
Applications, vol. 27, no. 1, pp. 63-73, 1991.
[8] N. Tan, T. Abe and H. Akagi, “Design and Performance
of a Bidirectional Isolated DC–DC Converter for a
Battery Energy Storage System,” IEEE Transactions on
Power Electronics, vol. 27, no. 3, pp. 1237-1248, 2012.
[9] W. Tahil, “The Trouble With Lithium - Implications of
Future PHEV Production for Lithium Demand,” Meridian
International Research, Martainville, France, 2006.

More Related Content

What's hot

Hybrid Two Quasi Z-Source Converter for Photovoltaic Application
Hybrid Two Quasi Z-Source Converter for Photovoltaic ApplicationHybrid Two Quasi Z-Source Converter for Photovoltaic Application
Hybrid Two Quasi Z-Source Converter for Photovoltaic ApplicationPremier Publishers
 
A Novel Three Phase Multi-string Multilevel Inverter with High DC-DC Closed o...
A Novel Three Phase Multi-string Multilevel Inverter with High DC-DC Closed o...A Novel Three Phase Multi-string Multilevel Inverter with High DC-DC Closed o...
A Novel Three Phase Multi-string Multilevel Inverter with High DC-DC Closed o...rnvsubbarao koppineni
 
Matlab simulink based-analysis of photovoltaic array fed multilevel boost con...
Matlab simulink based-analysis of photovoltaic array fed multilevel boost con...Matlab simulink based-analysis of photovoltaic array fed multilevel boost con...
Matlab simulink based-analysis of photovoltaic array fed multilevel boost con...Alexander Decker
 
Transformerless DC-DC Converter Using Cockcroft-Walton Voltage Multiplier to ...
Transformerless DC-DC Converter Using Cockcroft-Walton Voltage Multiplier to ...Transformerless DC-DC Converter Using Cockcroft-Walton Voltage Multiplier to ...
Transformerless DC-DC Converter Using Cockcroft-Walton Voltage Multiplier to ...IJERA Editor
 
IRJET-Solar Power Generation with Capacitor Based Seven Level Inverter System
IRJET-Solar Power Generation with Capacitor Based Seven Level Inverter SystemIRJET-Solar Power Generation with Capacitor Based Seven Level Inverter System
IRJET-Solar Power Generation with Capacitor Based Seven Level Inverter SystemIRJET Journal
 
High Efficiency Dc-Dc Converter for Renewable Energy Applications and High Vo...
High Efficiency Dc-Dc Converter for Renewable Energy Applications and High Vo...High Efficiency Dc-Dc Converter for Renewable Energy Applications and High Vo...
High Efficiency Dc-Dc Converter for Renewable Energy Applications and High Vo...IOSRJEEE
 
An improved closed loop hybrid phase shift controller for dual active bridge ...
An improved closed loop hybrid phase shift controller for dual active bridge ...An improved closed loop hybrid phase shift controller for dual active bridge ...
An improved closed loop hybrid phase shift controller for dual active bridge ...IJECEIAES
 
DESIGN OF A MULTIFUNCTIONAL FLYBACK DC-DC CONVERTER WITH CURRENT CONTROL
DESIGN OF A MULTIFUNCTIONAL FLYBACK DC-DC CONVERTER WITH CURRENT CONTROLDESIGN OF A MULTIFUNCTIONAL FLYBACK DC-DC CONVERTER WITH CURRENT CONTROL
DESIGN OF A MULTIFUNCTIONAL FLYBACK DC-DC CONVERTER WITH CURRENT CONTROLIAEME Publication
 
Mitigation of Power Quality Issues by Nine Switches UPQC Using PI & ANN with ...
Mitigation of Power Quality Issues by Nine Switches UPQC Using PI & ANN with ...Mitigation of Power Quality Issues by Nine Switches UPQC Using PI & ANN with ...
Mitigation of Power Quality Issues by Nine Switches UPQC Using PI & ANN with ...IJERA Editor
 
An Active Input Current Waveshaping with Zero Switching Losses for Three-Phas...
An Active Input Current Waveshaping with Zero Switching Losses for Three-Phas...An Active Input Current Waveshaping with Zero Switching Losses for Three-Phas...
An Active Input Current Waveshaping with Zero Switching Losses for Three-Phas...IDES Editor
 
Design and analysis of boost converter with cld cell
Design and analysis of boost converter with cld cellDesign and analysis of boost converter with cld cell
Design and analysis of boost converter with cld celleSAT Journals
 
MODELING, ANALYSIS AND SIMULATION OF POLY-PHASE BOOST CONVERTER
MODELING, ANALYSIS AND SIMULATION OF POLY-PHASE BOOST CONVERTERMODELING, ANALYSIS AND SIMULATION OF POLY-PHASE BOOST CONVERTER
MODELING, ANALYSIS AND SIMULATION OF POLY-PHASE BOOST CONVERTERijsrd.com
 
Modeling and Analysis of Transformerless High Gain Buck-boost DC-DC Converters
Modeling and Analysis of Transformerless High Gain Buck-boost DC-DC ConvertersModeling and Analysis of Transformerless High Gain Buck-boost DC-DC Converters
Modeling and Analysis of Transformerless High Gain Buck-boost DC-DC ConvertersIAES-IJPEDS
 
Control and Analysis of VSC Based High Voltage DC Transmission
Control and Analysis of VSC Based High Voltage DC TransmissionControl and Analysis of VSC Based High Voltage DC Transmission
Control and Analysis of VSC Based High Voltage DC Transmissionijsrd.com
 
PF correction using SEPIC
PF correction using SEPICPF correction using SEPIC
PF correction using SEPICSoumya Dash
 

What's hot (19)

Hybrid Two Quasi Z-Source Converter for Photovoltaic Application
Hybrid Two Quasi Z-Source Converter for Photovoltaic ApplicationHybrid Two Quasi Z-Source Converter for Photovoltaic Application
Hybrid Two Quasi Z-Source Converter for Photovoltaic Application
 
A Novel Three Phase Multi-string Multilevel Inverter with High DC-DC Closed o...
A Novel Three Phase Multi-string Multilevel Inverter with High DC-DC Closed o...A Novel Three Phase Multi-string Multilevel Inverter with High DC-DC Closed o...
A Novel Three Phase Multi-string Multilevel Inverter with High DC-DC Closed o...
 
Matlab simulink based-analysis of photovoltaic array fed multilevel boost con...
Matlab simulink based-analysis of photovoltaic array fed multilevel boost con...Matlab simulink based-analysis of photovoltaic array fed multilevel boost con...
Matlab simulink based-analysis of photovoltaic array fed multilevel boost con...
 
Transformerless DC-DC Converter Using Cockcroft-Walton Voltage Multiplier to ...
Transformerless DC-DC Converter Using Cockcroft-Walton Voltage Multiplier to ...Transformerless DC-DC Converter Using Cockcroft-Walton Voltage Multiplier to ...
Transformerless DC-DC Converter Using Cockcroft-Walton Voltage Multiplier to ...
 
IRJET-Solar Power Generation with Capacitor Based Seven Level Inverter System
IRJET-Solar Power Generation with Capacitor Based Seven Level Inverter SystemIRJET-Solar Power Generation with Capacitor Based Seven Level Inverter System
IRJET-Solar Power Generation with Capacitor Based Seven Level Inverter System
 
J0372049056
J0372049056J0372049056
J0372049056
 
Ix2616991704
Ix2616991704Ix2616991704
Ix2616991704
 
High Efficiency Dc-Dc Converter for Renewable Energy Applications and High Vo...
High Efficiency Dc-Dc Converter for Renewable Energy Applications and High Vo...High Efficiency Dc-Dc Converter for Renewable Energy Applications and High Vo...
High Efficiency Dc-Dc Converter for Renewable Energy Applications and High Vo...
 
An improved closed loop hybrid phase shift controller for dual active bridge ...
An improved closed loop hybrid phase shift controller for dual active bridge ...An improved closed loop hybrid phase shift controller for dual active bridge ...
An improved closed loop hybrid phase shift controller for dual active bridge ...
 
Bidirectional Resonant DC-DC converter for Microgrid Applications
Bidirectional Resonant DC-DC converter for Microgrid ApplicationsBidirectional Resonant DC-DC converter for Microgrid Applications
Bidirectional Resonant DC-DC converter for Microgrid Applications
 
C010242128
C010242128C010242128
C010242128
 
DESIGN OF A MULTIFUNCTIONAL FLYBACK DC-DC CONVERTER WITH CURRENT CONTROL
DESIGN OF A MULTIFUNCTIONAL FLYBACK DC-DC CONVERTER WITH CURRENT CONTROLDESIGN OF A MULTIFUNCTIONAL FLYBACK DC-DC CONVERTER WITH CURRENT CONTROL
DESIGN OF A MULTIFUNCTIONAL FLYBACK DC-DC CONVERTER WITH CURRENT CONTROL
 
Mitigation of Power Quality Issues by Nine Switches UPQC Using PI & ANN with ...
Mitigation of Power Quality Issues by Nine Switches UPQC Using PI & ANN with ...Mitigation of Power Quality Issues by Nine Switches UPQC Using PI & ANN with ...
Mitigation of Power Quality Issues by Nine Switches UPQC Using PI & ANN with ...
 
An Active Input Current Waveshaping with Zero Switching Losses for Three-Phas...
An Active Input Current Waveshaping with Zero Switching Losses for Three-Phas...An Active Input Current Waveshaping with Zero Switching Losses for Three-Phas...
An Active Input Current Waveshaping with Zero Switching Losses for Three-Phas...
 
Design and analysis of boost converter with cld cell
Design and analysis of boost converter with cld cellDesign and analysis of boost converter with cld cell
Design and analysis of boost converter with cld cell
 
MODELING, ANALYSIS AND SIMULATION OF POLY-PHASE BOOST CONVERTER
MODELING, ANALYSIS AND SIMULATION OF POLY-PHASE BOOST CONVERTERMODELING, ANALYSIS AND SIMULATION OF POLY-PHASE BOOST CONVERTER
MODELING, ANALYSIS AND SIMULATION OF POLY-PHASE BOOST CONVERTER
 
Modeling and Analysis of Transformerless High Gain Buck-boost DC-DC Converters
Modeling and Analysis of Transformerless High Gain Buck-boost DC-DC ConvertersModeling and Analysis of Transformerless High Gain Buck-boost DC-DC Converters
Modeling and Analysis of Transformerless High Gain Buck-boost DC-DC Converters
 
Control and Analysis of VSC Based High Voltage DC Transmission
Control and Analysis of VSC Based High Voltage DC TransmissionControl and Analysis of VSC Based High Voltage DC Transmission
Control and Analysis of VSC Based High Voltage DC Transmission
 
PF correction using SEPIC
PF correction using SEPICPF correction using SEPIC
PF correction using SEPIC
 

Viewers also liked

Bidirectional DC-DC isolated converter
Bidirectional DC-DC isolated converterBidirectional DC-DC isolated converter
Bidirectional DC-DC isolated converterVasudeva Guptha
 
NELC-POCT20120930a
NELC-POCT20120930aNELC-POCT20120930a
NELC-POCT20120930aMark Gusack
 
Critial thinking week 2
Critial thinking week 2Critial thinking week 2
Critial thinking week 2Greg Wells
 
NELC-A1C20120930a
NELC-A1C20120930aNELC-A1C20120930a
NELC-A1C20120930aMark Gusack
 
Design and implementation of high power dc dc converter and speed control of ...
Design and implementation of high power dc dc converter and speed control of ...Design and implementation of high power dc dc converter and speed control of ...
Design and implementation of high power dc dc converter and speed control of ...anbarasuasokan
 
Article Summaries and Critiques
Article Summaries and CritiquesArticle Summaries and Critiques
Article Summaries and Critiquescjturner011075
 
Writing an article review
Writing an article reviewWriting an article review
Writing an article reviewdapuchak
 
Literature Based Research Methodology
Literature Based Research MethodologyLiterature Based Research Methodology
Literature Based Research Methodologyhuguette_comerasamy
 
Article Review-Writing Sample
Article Review-Writing SampleArticle Review-Writing Sample
Article Review-Writing SampleDawn Drake, Ph.D.
 
Literature review in research
Literature review in researchLiterature review in research
Literature review in researchNursing Path
 
Literature Review (Review of Related Literature - Research Methodology)
Literature Review (Review of Related Literature - Research Methodology)Literature Review (Review of Related Literature - Research Methodology)
Literature Review (Review of Related Literature - Research Methodology)Dilip Barad
 
Speed control of DC Machine
Speed control of DC MachineSpeed control of DC Machine
Speed control of DC MachineSHAHBAAZ AHMED
 
Literature review in research methodology
Literature review in research methodologyLiterature review in research methodology
Literature review in research methodologyraison sam raju
 

Viewers also liked (15)

Bidirectional DC-DC isolated converter
Bidirectional DC-DC isolated converterBidirectional DC-DC isolated converter
Bidirectional DC-DC isolated converter
 
NELC-POCT20120930a
NELC-POCT20120930aNELC-POCT20120930a
NELC-POCT20120930a
 
Critial thinking week 2
Critial thinking week 2Critial thinking week 2
Critial thinking week 2
 
NELC-A1C20120930a
NELC-A1C20120930aNELC-A1C20120930a
NELC-A1C20120930a
 
Design and implementation of high power dc dc converter and speed control of ...
Design and implementation of high power dc dc converter and speed control of ...Design and implementation of high power dc dc converter and speed control of ...
Design and implementation of high power dc dc converter and speed control of ...
 
Bone morphogentic protein
Bone morphogentic proteinBone morphogentic protein
Bone morphogentic protein
 
Article Summaries and Critiques
Article Summaries and CritiquesArticle Summaries and Critiques
Article Summaries and Critiques
 
Article review
Article reviewArticle review
Article review
 
Writing an article review
Writing an article reviewWriting an article review
Writing an article review
 
Literature Based Research Methodology
Literature Based Research MethodologyLiterature Based Research Methodology
Literature Based Research Methodology
 
Article Review-Writing Sample
Article Review-Writing SampleArticle Review-Writing Sample
Article Review-Writing Sample
 
Literature review in research
Literature review in researchLiterature review in research
Literature review in research
 
Literature Review (Review of Related Literature - Research Methodology)
Literature Review (Review of Related Literature - Research Methodology)Literature Review (Review of Related Literature - Research Methodology)
Literature Review (Review of Related Literature - Research Methodology)
 
Speed control of DC Machine
Speed control of DC MachineSpeed control of DC Machine
Speed control of DC Machine
 
Literature review in research methodology
Literature review in research methodologyLiterature review in research methodology
Literature review in research methodology
 

Similar to Design of a Single Phase Isolated Bidirectional AC to DC Converter for Battery Energy Storage Systems

International Journal of Engineering Research and Development (IJERD)
International Journal of Engineering Research and Development (IJERD)International Journal of Engineering Research and Development (IJERD)
International Journal of Engineering Research and Development (IJERD)IJERD Editor
 
Design and Performance of a Bidirectional Isolated Dc-Dc Converter for Renewa...
Design and Performance of a Bidirectional Isolated Dc-Dc Converter for Renewa...Design and Performance of a Bidirectional Isolated Dc-Dc Converter for Renewa...
Design and Performance of a Bidirectional Isolated Dc-Dc Converter for Renewa...IOSR Journals
 
A ZVS Interleaved Boost AC/DC Converter Using Super Capacitor Power for Hybri...
A ZVS Interleaved Boost AC/DC Converter Using Super Capacitor Power for Hybri...A ZVS Interleaved Boost AC/DC Converter Using Super Capacitor Power for Hybri...
A ZVS Interleaved Boost AC/DC Converter Using Super Capacitor Power for Hybri...IJMER
 
Single-Switch Soft-Switched Boost Power Factor Corrector for Modular Applicat...
Single-Switch Soft-Switched Boost Power Factor Corrector for Modular Applicat...Single-Switch Soft-Switched Boost Power Factor Corrector for Modular Applicat...
Single-Switch Soft-Switched Boost Power Factor Corrector for Modular Applicat...IAES-IJPEDS
 
Closed Loop Controlled Solar Cell Powered Embedded EZ-Source Inverter fed Ind...
Closed Loop Controlled Solar Cell Powered Embedded EZ-Source Inverter fed Ind...Closed Loop Controlled Solar Cell Powered Embedded EZ-Source Inverter fed Ind...
Closed Loop Controlled Solar Cell Powered Embedded EZ-Source Inverter fed Ind...IDES Editor
 
Design and Simulation of Efficient DC-DC Converter Topology for a Solar PV Mo...
Design and Simulation of Efficient DC-DC Converter Topology for a Solar PV Mo...Design and Simulation of Efficient DC-DC Converter Topology for a Solar PV Mo...
Design and Simulation of Efficient DC-DC Converter Topology for a Solar PV Mo...Sajin Ismail
 
High Proficiency Grid ConnectedPhotovoltaic Power Generation System
High Proficiency Grid ConnectedPhotovoltaic Power Generation SystemHigh Proficiency Grid ConnectedPhotovoltaic Power Generation System
High Proficiency Grid ConnectedPhotovoltaic Power Generation SystemIJRES Journal
 
Low Speed Surface Aerator Controller
Low Speed Surface Aerator ControllerLow Speed Surface Aerator Controller
Low Speed Surface Aerator ControllerJack Wong
 
Push-Pull Converter Fed Three-Phase Inverter for Residential and Motor Load
Push-Pull Converter Fed Three-Phase Inverter for Residential and Motor LoadPush-Pull Converter Fed Three-Phase Inverter for Residential and Motor Load
Push-Pull Converter Fed Three-Phase Inverter for Residential and Motor LoadIJPEDS-IAES
 
Real and Reactive Power Compensation by using Diode Clamped Multilevel Invert...
Real and Reactive Power Compensation by using Diode Clamped Multilevel Invert...Real and Reactive Power Compensation by using Diode Clamped Multilevel Invert...
Real and Reactive Power Compensation by using Diode Clamped Multilevel Invert...IRJET Journal
 
International Journal of Engineering Research and Development
International Journal of Engineering Research and DevelopmentInternational Journal of Engineering Research and Development
International Journal of Engineering Research and DevelopmentIJERD Editor
 
DG FED MULTILEVEL INVERTER BASED D-STATCOM FOR VARIOUS LOADING CONDITIONS
DG FED MULTILEVEL INVERTER BASED D-STATCOM FOR VARIOUS LOADING CONDITIONSDG FED MULTILEVEL INVERTER BASED D-STATCOM FOR VARIOUS LOADING CONDITIONS
DG FED MULTILEVEL INVERTER BASED D-STATCOM FOR VARIOUS LOADING CONDITIONSIJCI JOURNAL
 
Voltage Sag Mitigation in Utility Connected System Using Current Source Conve...
Voltage Sag Mitigation in Utility Connected System Using Current Source Conve...Voltage Sag Mitigation in Utility Connected System Using Current Source Conve...
Voltage Sag Mitigation in Utility Connected System Using Current Source Conve...IDES Editor
 

Similar to Design of a Single Phase Isolated Bidirectional AC to DC Converter for Battery Energy Storage Systems (20)

International Journal of Engineering Research and Development (IJERD)
International Journal of Engineering Research and Development (IJERD)International Journal of Engineering Research and Development (IJERD)
International Journal of Engineering Research and Development (IJERD)
 
Design and Performance of a Bidirectional Isolated Dc-Dc Converter for Renewa...
Design and Performance of a Bidirectional Isolated Dc-Dc Converter for Renewa...Design and Performance of a Bidirectional Isolated Dc-Dc Converter for Renewa...
Design and Performance of a Bidirectional Isolated Dc-Dc Converter for Renewa...
 
A ZVS Interleaved Boost AC/DC Converter Using Super Capacitor Power for Hybri...
A ZVS Interleaved Boost AC/DC Converter Using Super Capacitor Power for Hybri...A ZVS Interleaved Boost AC/DC Converter Using Super Capacitor Power for Hybri...
A ZVS Interleaved Boost AC/DC Converter Using Super Capacitor Power for Hybri...
 
R01043105113
R01043105113R01043105113
R01043105113
 
Reduction of single DC bus capacitance in photovoltaic cascaded multilevel co...
Reduction of single DC bus capacitance in photovoltaic cascaded multilevel co...Reduction of single DC bus capacitance in photovoltaic cascaded multilevel co...
Reduction of single DC bus capacitance in photovoltaic cascaded multilevel co...
 
Single-Switch Soft-Switched Boost Power Factor Corrector for Modular Applicat...
Single-Switch Soft-Switched Boost Power Factor Corrector for Modular Applicat...Single-Switch Soft-Switched Boost Power Factor Corrector for Modular Applicat...
Single-Switch Soft-Switched Boost Power Factor Corrector for Modular Applicat...
 
I41045662
I41045662I41045662
I41045662
 
Closed Loop Controlled Solar Cell Powered Embedded EZ-Source Inverter fed Ind...
Closed Loop Controlled Solar Cell Powered Embedded EZ-Source Inverter fed Ind...Closed Loop Controlled Solar Cell Powered Embedded EZ-Source Inverter fed Ind...
Closed Loop Controlled Solar Cell Powered Embedded EZ-Source Inverter fed Ind...
 
Design and Simulation of Efficient DC-DC Converter Topology for a Solar PV Mo...
Design and Simulation of Efficient DC-DC Converter Topology for a Solar PV Mo...Design and Simulation of Efficient DC-DC Converter Topology for a Solar PV Mo...
Design and Simulation of Efficient DC-DC Converter Topology for a Solar PV Mo...
 
High Proficiency Grid ConnectedPhotovoltaic Power Generation System
High Proficiency Grid ConnectedPhotovoltaic Power Generation SystemHigh Proficiency Grid ConnectedPhotovoltaic Power Generation System
High Proficiency Grid ConnectedPhotovoltaic Power Generation System
 
Low Speed Surface Aerator Controller
Low Speed Surface Aerator ControllerLow Speed Surface Aerator Controller
Low Speed Surface Aerator Controller
 
Push-Pull Converter Fed Three-Phase Inverter for Residential and Motor Load
Push-Pull Converter Fed Three-Phase Inverter for Residential and Motor LoadPush-Pull Converter Fed Three-Phase Inverter for Residential and Motor Load
Push-Pull Converter Fed Three-Phase Inverter for Residential and Motor Load
 
Simplified cascade multiphase DC-DC buck power converter for low voltage larg...
Simplified cascade multiphase DC-DC buck power converter for low voltage larg...Simplified cascade multiphase DC-DC buck power converter for low voltage larg...
Simplified cascade multiphase DC-DC buck power converter for low voltage larg...
 
Real and Reactive Power Compensation by using Diode Clamped Multilevel Invert...
Real and Reactive Power Compensation by using Diode Clamped Multilevel Invert...Real and Reactive Power Compensation by using Diode Clamped Multilevel Invert...
Real and Reactive Power Compensation by using Diode Clamped Multilevel Invert...
 
International Journal of Engineering Research and Development
International Journal of Engineering Research and DevelopmentInternational Journal of Engineering Research and Development
International Journal of Engineering Research and Development
 
Gran importancia
Gran importanciaGran importancia
Gran importancia
 
N367984
N367984N367984
N367984
 
C04721623
C04721623C04721623
C04721623
 
DG FED MULTILEVEL INVERTER BASED D-STATCOM FOR VARIOUS LOADING CONDITIONS
DG FED MULTILEVEL INVERTER BASED D-STATCOM FOR VARIOUS LOADING CONDITIONSDG FED MULTILEVEL INVERTER BASED D-STATCOM FOR VARIOUS LOADING CONDITIONS
DG FED MULTILEVEL INVERTER BASED D-STATCOM FOR VARIOUS LOADING CONDITIONS
 
Voltage Sag Mitigation in Utility Connected System Using Current Source Conve...
Voltage Sag Mitigation in Utility Connected System Using Current Source Conve...Voltage Sag Mitigation in Utility Connected System Using Current Source Conve...
Voltage Sag Mitigation in Utility Connected System Using Current Source Conve...
 

Recently uploaded

ZXCTN 5804 / ZTE PTN / ZTE POTN / ZTE 5804 PTN / ZTE POTN 5804 ( 100/200 GE Z...
ZXCTN 5804 / ZTE PTN / ZTE POTN / ZTE 5804 PTN / ZTE POTN 5804 ( 100/200 GE Z...ZXCTN 5804 / ZTE PTN / ZTE POTN / ZTE 5804 PTN / ZTE POTN 5804 ( 100/200 GE Z...
ZXCTN 5804 / ZTE PTN / ZTE POTN / ZTE 5804 PTN / ZTE POTN 5804 ( 100/200 GE Z...ZTE
 
Internship report on mechanical engineering
Internship report on mechanical engineeringInternship report on mechanical engineering
Internship report on mechanical engineeringmalavadedarshan25
 
Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...
Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...
Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...srsj9000
 
power system scada applications and uses
power system scada applications and usespower system scada applications and uses
power system scada applications and usesDevarapalliHaritha
 
Architect Hassan Khalil Portfolio for 2024
Architect Hassan Khalil Portfolio for 2024Architect Hassan Khalil Portfolio for 2024
Architect Hassan Khalil Portfolio for 2024hassan khalil
 
HARMONY IN THE HUMAN BEING - Unit-II UHV-2
HARMONY IN THE HUMAN BEING - Unit-II UHV-2HARMONY IN THE HUMAN BEING - Unit-II UHV-2
HARMONY IN THE HUMAN BEING - Unit-II UHV-2RajaP95
 
Study on Air-Water & Water-Water Heat Exchange in a Finned Tube Exchanger
Study on Air-Water & Water-Water Heat Exchange in a Finned Tube ExchangerStudy on Air-Water & Water-Water Heat Exchange in a Finned Tube Exchanger
Study on Air-Water & Water-Water Heat Exchange in a Finned Tube ExchangerAnamika Sarkar
 
CCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdf
CCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdfCCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdf
CCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdfAsst.prof M.Gokilavani
 
CCS355 Neural Network & Deep Learning UNIT III notes and Question bank .pdf
CCS355 Neural Network & Deep Learning UNIT III notes and Question bank .pdfCCS355 Neural Network & Deep Learning UNIT III notes and Question bank .pdf
CCS355 Neural Network & Deep Learning UNIT III notes and Question bank .pdfAsst.prof M.Gokilavani
 
Biology for Computer Engineers Course Handout.pptx
Biology for Computer Engineers Course Handout.pptxBiology for Computer Engineers Course Handout.pptx
Biology for Computer Engineers Course Handout.pptxDeepakSakkari2
 
Software and Systems Engineering Standards: Verification and Validation of Sy...
Software and Systems Engineering Standards: Verification and Validation of Sy...Software and Systems Engineering Standards: Verification and Validation of Sy...
Software and Systems Engineering Standards: Verification and Validation of Sy...VICTOR MAESTRE RAMIREZ
 
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...Soham Mondal
 
Heart Disease Prediction using machine learning.pptx
Heart Disease Prediction using machine learning.pptxHeart Disease Prediction using machine learning.pptx
Heart Disease Prediction using machine learning.pptxPoojaBan
 
GDSC ASEB Gen AI study jams presentation
GDSC ASEB Gen AI study jams presentationGDSC ASEB Gen AI study jams presentation
GDSC ASEB Gen AI study jams presentationGDSCAESB
 
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICSAPPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICSKurinjimalarL3
 
main PPT.pptx of girls hostel security using rfid
main PPT.pptx of girls hostel security using rfidmain PPT.pptx of girls hostel security using rfid
main PPT.pptx of girls hostel security using rfidNikhilNagaraju
 
microprocessor 8085 and its interfacing
microprocessor 8085  and its interfacingmicroprocessor 8085  and its interfacing
microprocessor 8085 and its interfacingjaychoudhary37
 
Microscopic Analysis of Ceramic Materials.pptx
Microscopic Analysis of Ceramic Materials.pptxMicroscopic Analysis of Ceramic Materials.pptx
Microscopic Analysis of Ceramic Materials.pptxpurnimasatapathy1234
 

Recently uploaded (20)

ZXCTN 5804 / ZTE PTN / ZTE POTN / ZTE 5804 PTN / ZTE POTN 5804 ( 100/200 GE Z...
ZXCTN 5804 / ZTE PTN / ZTE POTN / ZTE 5804 PTN / ZTE POTN 5804 ( 100/200 GE Z...ZXCTN 5804 / ZTE PTN / ZTE POTN / ZTE 5804 PTN / ZTE POTN 5804 ( 100/200 GE Z...
ZXCTN 5804 / ZTE PTN / ZTE POTN / ZTE 5804 PTN / ZTE POTN 5804 ( 100/200 GE Z...
 
Call Us -/9953056974- Call Girls In Vikaspuri-/- Delhi NCR
Call Us -/9953056974- Call Girls In Vikaspuri-/- Delhi NCRCall Us -/9953056974- Call Girls In Vikaspuri-/- Delhi NCR
Call Us -/9953056974- Call Girls In Vikaspuri-/- Delhi NCR
 
Internship report on mechanical engineering
Internship report on mechanical engineeringInternship report on mechanical engineering
Internship report on mechanical engineering
 
Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...
Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...
Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...
 
★ CALL US 9953330565 ( HOT Young Call Girls In Badarpur delhi NCR
★ CALL US 9953330565 ( HOT Young Call Girls In Badarpur delhi NCR★ CALL US 9953330565 ( HOT Young Call Girls In Badarpur delhi NCR
★ CALL US 9953330565 ( HOT Young Call Girls In Badarpur delhi NCR
 
power system scada applications and uses
power system scada applications and usespower system scada applications and uses
power system scada applications and uses
 
Architect Hassan Khalil Portfolio for 2024
Architect Hassan Khalil Portfolio for 2024Architect Hassan Khalil Portfolio for 2024
Architect Hassan Khalil Portfolio for 2024
 
HARMONY IN THE HUMAN BEING - Unit-II UHV-2
HARMONY IN THE HUMAN BEING - Unit-II UHV-2HARMONY IN THE HUMAN BEING - Unit-II UHV-2
HARMONY IN THE HUMAN BEING - Unit-II UHV-2
 
Study on Air-Water & Water-Water Heat Exchange in a Finned Tube Exchanger
Study on Air-Water & Water-Water Heat Exchange in a Finned Tube ExchangerStudy on Air-Water & Water-Water Heat Exchange in a Finned Tube Exchanger
Study on Air-Water & Water-Water Heat Exchange in a Finned Tube Exchanger
 
CCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdf
CCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdfCCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdf
CCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdf
 
CCS355 Neural Network & Deep Learning UNIT III notes and Question bank .pdf
CCS355 Neural Network & Deep Learning UNIT III notes and Question bank .pdfCCS355 Neural Network & Deep Learning UNIT III notes and Question bank .pdf
CCS355 Neural Network & Deep Learning UNIT III notes and Question bank .pdf
 
Biology for Computer Engineers Course Handout.pptx
Biology for Computer Engineers Course Handout.pptxBiology for Computer Engineers Course Handout.pptx
Biology for Computer Engineers Course Handout.pptx
 
Software and Systems Engineering Standards: Verification and Validation of Sy...
Software and Systems Engineering Standards: Verification and Validation of Sy...Software and Systems Engineering Standards: Verification and Validation of Sy...
Software and Systems Engineering Standards: Verification and Validation of Sy...
 
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
 
Heart Disease Prediction using machine learning.pptx
Heart Disease Prediction using machine learning.pptxHeart Disease Prediction using machine learning.pptx
Heart Disease Prediction using machine learning.pptx
 
GDSC ASEB Gen AI study jams presentation
GDSC ASEB Gen AI study jams presentationGDSC ASEB Gen AI study jams presentation
GDSC ASEB Gen AI study jams presentation
 
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICSAPPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
 
main PPT.pptx of girls hostel security using rfid
main PPT.pptx of girls hostel security using rfidmain PPT.pptx of girls hostel security using rfid
main PPT.pptx of girls hostel security using rfid
 
microprocessor 8085 and its interfacing
microprocessor 8085  and its interfacingmicroprocessor 8085  and its interfacing
microprocessor 8085 and its interfacing
 
Microscopic Analysis of Ceramic Materials.pptx
Microscopic Analysis of Ceramic Materials.pptxMicroscopic Analysis of Ceramic Materials.pptx
Microscopic Analysis of Ceramic Materials.pptx
 

Design of a Single Phase Isolated Bidirectional AC to DC Converter for Battery Energy Storage Systems

  • 1. 1 Design of a Single Phase Isolated Bidirectional AC to DC Converter for Battery Energy Storage Systems Queen’s University ELEC 497 Research Project Tom Gibson 10163463 14tagg@queensu.ca Completed with the assistance of Prof. Praveen K. Jain and Mr. Behnam Koushki. Abstract— This paper analyses the design of a 3 kW isolated bidirectional ac to dc converter for Battery Energy Storage Systems (BESS). This is an increasingly popular solution to overcome the differences seen in electricity supply and demand introduced by renewable energy sources. In order to connect these systems to the grid an ac to dc converter is required. In this paper a converter is considered to interface a 300 V battery bank to the grid at 110 V, 60 Hz ac. A dual active bridge is implemented with a 100 kHz transformer. Control systems for the converter are also considered allowing autonomous regulation of the power flow to and from the storage. Index Terms—Battery energy storage, dual active bridge, bidirectional isolated ac-dc converter. I. INTRODUCTION Over recent years a huge increase has been seen in the use of renewable power generation in our energy supply networks as many governments aim to promote clean sources over fossil fuels as a response to global climate change. While renewable technologies are much cleaner than traditional methods of grid scale generation they lack the controllability of traditional generation. For example a wind farm will typically be more productive at night when winds are stronger, but at this time demand is low. The output of a coal or gas power plant can be adjusted accordingly within reason, but this is more complicated with renewable power sources so imbalances between supply and demand often occur. Figure 1. presents the typical electricity supply and demand for a day in Ontario [1]. During the daytime demand is greater than total supply, and at night demand is much lower than supply. Where these imbalances occur power is normally imported from or exported to other regions. One approach to overcome these imbalances is to implement an energy storage system. These can range in size from large systems such as megawatt scale hydro storage to smaller projects such as kilowatt scale flywheels. As battery technology is improved and the demand for distributed generation is increased, battery energy storage systems (BESS) are growing in popularity. The high charge and discharge efficiency and energy density of lithium-ion based battery systems makes them a highly favorable solution [2]. Fig. 1. Ontario Power Supply and Demand over 8 April 2015 [1]. In order to connect the dc BESS to the ac grid some form of voltage converter is required. A popular approach is to use the bridge circuit in Fig. 2. [3]. This circuit uses four metal-oxide- semiconductor field-effect-transistors (MOSFETs), each paralleled with a lossless diode to alter the voltage signal. The circuit operates as a boost rectifier when power needs to be transferred from the ac grid to the dc batteries. The current flows for this operation are shown in Fig. 2.(a). When the MOSFET switches are off (or open) the current flows through the diodes to reach Vdc. i.e. for the positive cycle of vac there is current flow through the diodes D1 and D3 following the solid blue lines. Similarly, during the negative cycle of vac there is current flow through the diodes D2 and D4, in the direction of the dashed orange lines. When the MOSFETs are turned on (or are closed) current is allowed to flow through them, thus bypassing the capacitor and charging the inductor (i.e. for the positive ac cycle the current flow is through D1 and S2, along the dotted green line). This stored charge is injected back into the capacitor once the switches are opened again at a high voltage. This allows Vdc to be much larger than vac. The magnitude of the dc voltage can be controlled by altering the duty cycle of the MOSFETs. When operating in inverter mode (Fig. 2.(c)) the diodes become redundant and the MOSFETS are used to control the ac voltage frequency and RMS magnitude. The graph in Fig. 2.(d). indicates when each of the switches is turned on and the ac waveform which is subsequently produced. The ac voltage has fundamental and odd harmonics and is given by Eq. 1. Ontario demand Projected Actual Market demand Projected Actual
  • 2. 2 Fig. 2. (a) Circuit schematic for bidirectional ac/dc converter in rectifier mode; (b) Rectifier input and output waveforms (vac and Vdc respectively); (c) Circuit schematic for bidirectional ac/dc converter in inverter mode; (d) Inverter input and output waveforms (Vdc and vac respectively). 𝑣 𝑎𝑐 𝑝𝑒𝑎𝑘 = 4𝑉 𝑑𝑐 𝜋 ∑ 1 𝑛 sin ( 𝑛𝜋 2 ) sin ( 𝑛𝛿 2 )sin(𝑛𝜔𝑡)∞ 𝑛=1,3 (1) [4] The RMS magnitude of vac can be controlled by adjusting the pulse angle δ as shown in Fig. 3. Therefore adjusting the switch period alters the voltage. The ac voltage frequency is half of the switching frequency and can be controlled by adjusting the switching frequency. Fig. 3. Fundamental and harmonics of inverter ac output voltage against pulse width angle δ. While this makes an effective voltage converter it also requires a high dc bus voltage, higher than the ac source voltage. A reduction in the dc voltage would have the advantage of reducing the battery pack voltage or the required number of series battery cells. The system stability would also be increased. One method of reducing the voltage would be to add a transformer at the grid side, however at the low grid frequency transformers need to be large and tend to be expensive. An alternative solution is to add an isolated dc to dc converter to the dc side, composed of two more bridges tied together by a high frequency transformer, as in Fig. 4. [5]. This is known as a dual active bridge (DAB) [6], [7]. The high frequency transformer can be made much smaller and less expensive than the low frequency equivalent and will have improved efficiency. The converter shown in Fig. 4. can be considered as a two stage device. Stage 1 uses a single converter bridge to convert the ac grid voltage to dc. In Stage 2, Bridge B converts the dc voltage, Vo, back to ac but at a much higher frequency than the source voltage. The ac voltage is reduced by the transformer then converted back to dc by Bridge C for connection to the batteries. In this paper the analysis and design of this system is considered for a BESS with the parameters outlined in Table I. The DAB design is considered first before being applied to the rest of the system. 0 20 40 60 80 100 120 140 160 180 0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 delta (degrees) |Vacrms|(pu) n = 1 n = 3 n = 5 n = 7 Positive half cycle Negative half cycle Positive cycle inductor charging Vac Vdc (a) (c) -1.5 -1 -0.5 0 0.5 1 1.5 0 60 120 180 240 300 360 PerUnitVoltage ωt (degrees) vac Vdc S1S3 S1S4 S2S4 S2S3 δ (b) (d) δ -2 0 2 4 6 0 60 120 180 240 300 360 PerUnitVoltage ωt (degrees) vac vdc Vdc
  • 3. 3 Fig. 4. Circuit schematic of a single phase isolated bidirectional ac/dc converter. TABLE I. CONVERTER DESIGN PARAMETERS Voltage Supply (vs) 110 VRMS, 60 Hz AC Voltage Output (Vo) DC Batteries, 300 V nominal (Range 250 – 400 V) Power Output (Po) 3 kW Stage 1 switching frequency (fs1) 20 kHz Stage 2 switching frequency (fs2) 100 kHz Switch type MOSFET II. ANALYSIS AND DESIGN A. Dual Active Bridge Analysis of the system is carried out looking from the output side, under idealized conditions the output power is given by Eq. 2. [6] 𝑃𝑜 = 𝑉 𝑖 𝑋 𝐿 𝑑𝜑 (1 − |𝜑| 𝜋 ) (2) where 𝑋 𝐿 = 𝜔𝐿 = 2𝜋𝑓𝑠2 𝐿, 𝑑 = 𝑉𝑜 𝑁𝑉 𝑖 In addition to the parameters in Table I., Vi is the dc bus voltage (voltage over C1 in Fig. 1.), φ is the phase shift between Bridge B and Bridge C, L is the primary referred leakage inductance of the transformer and N is the transformer turns ratio. Po, Vo and fs1 are known from the design parameters. For a full range of zero voltage switching it is preferred that d = 1, therefore N = Vo/Vi. Vi needs to be chosen as a value greater than the maximum source voltage, so for the purpose of this design Vi = 400 V dc was chosen, giving N = 3/4. With all other variables (including L) being constant the output power varies with the phase difference, φ. This relationship is shown in Fig. 5. It is seen that φ can be used to control the output power, and the maximum occurs when φ = 90°. For the design under consideration a nominal phase shift of 60° is considered appropriate so that the output power can be increased slightly if required or if the system is overloaded. Also, L varies to φ in the same manner as Po so a smaller φ means smaller L. Taking these values into consideration the leakage reactance, XL, can be calculated from Eq. 2 and is found to be 37.23 Ω. Therefore from this value and at fs2 = 100 kHz, L = 59.26 μH. Fig. 5. Converter output power (magnitude and direction of flow) against the phase shift between Bridge B and Bridge C. Also seen in the above figure is that the direction of power flow can be controlled by φ as well as its magnitude. Therefore a closed loop control system can be designed to adjust the phase shift based on the battery state of charge (SOC) and grid power requirements. Since the output side is constant voltage the current flow varies directly with power, so this control system will also regulate the current flow. Following the analysis of the DAB converter system it was assembled in PSIM for proof of concept. The design was configured as in Fig. 6. with a simple control system. The capacitors C1 and C2 are introduced to suppress the dc current ripple caused by switching and for the simulation these were each set to 1 nF. L represents the transformer primary referred leakage inductance and was set at 60 μH based on the previous calculation. The dc voltage sources VDC and Vbattery represent the desired dc bus and battery voltages respectively. A small inductor and resistor are connected in series with Vbattery to represent non-ideal battery characteristics. Fig. 6. PSIM circuit diagram for dual active bridge. -1 -0.5 0 0.5 1 -120 -90 -60 -30 0 30 60 90 120 OutputPower,Po(pu) Phase Shift φ°Backwards Power Flow Forwards Power Flow dc bus Bridge A Bridge B Bridge C Stage 1: Bidirectional AC/DC Converter Stage 2: Dual Active Bridge DC/DC Converter High Frequency Transformer
  • 4. 4 Control of the system was achieved using step voltage inputs to control each MOSFET bridge. These sources, labelled VBridgeB and VBridgeC were set to 100 kHz to match the switching frequency of this stage. The phase delay between bridges B and C was also controlled using these sources and thus allowed control over the output current and direction of power flow. For example under idealised conditions when the phase delay, φ, is equal to zero degrees the overall power flow should also be zero, according to Eq. 2. This is observed in Fig. 7.(a). where the average values of primary transformer current, Ires, and battery current, Ibattery, are also near zero. When the phase delay of VBridgeB is set to 60°, i.e. φ =-60°, the result in Fig. 7.(b). is observed. In this case the average current flowing into the battery is negative, this is the discharging mode. When the phase delay is applied to VBridgeC, i.e. φ = 60°, the power flow is reversed and the battery current is positive as in Fig. 7.(c). This is the charging mode. (a) (b) (c) (d) Fig. 7. PSIM simulation results for DAB, (a) when φ = 0°; (b) φ = -60°; (c) φ = 60°; (d) dc link and battery voltages (similar for each case). Note that the battery current is not strictly dc due to the switching effects and phase delay. The resonant circuit current remains above or below zero in each case due to the leakage reactance, and has a frequency of 100 kHz, the same as fs2. In the above analysis it is considered that the winding resistances are negligible compared to the transformer leakage reactance. It is also assumed that the magnetizing inductance of the transformer is infinitely large however this may not be the case in a real system. The effect of this on the range of soft switching for the system is considered in the literature [6]. It is given that the magnetizing inductance can be approximated as Lm = K*L given that L is the leakage inductance calculated above and K ≥ 1. Therefore for this system to remain stable Lm ≥ 60 μH. Simulating the circuit again for stage 2 with the given and calculated parameters produced the waveforms in Fig. 8. for K >> 1 and K = 1. It is indicated that the magnetizing inductance has an effect on the circuit currents. When K >> 1, i.e. Lm >> L, the currents through the systems follow fairly smooth and ideal characteristics. As K is reduced the current edges become sharper with a more triangular waveform developing. Therefore as K is decreased the region for soft switching is increased but comes with a trade-off of low transformer utilization. (a) (b) (c) Fig. 8. Simulated dual active bridge converter: (a) Primary and secondary transformer voltages; (b) Input and output current for K >> 1; (c) Input and output current for K = 1.
  • 5. 5 B. AC Grid Interface After designing the DAB part of the system the grid and battery connections may be considered. On the grid side another converter bridge is connected as mentioned before, indicated as Stage 1 in Fig. 4. This controls the voltage of the dc bus as well as acting as a rectifier/inverter between the ac grid and dc bus [8]. As previously noted when operating as an inverter the ac voltage magnitude can be adjusted by altering the pulse width, δ. In this mode the inverter will produce harmonics, the magnitudes of which are also shown in Fig. 3. However, it is desirable to have only the fundamental voltage component, so an LC filter could be implemented at the grid side. In this case the required pulse width angle to achieve the desired ac voltage can be found from Eq. 1 where n = 1: vac1 RMS = 4Vdc π 𝑠𝑖𝑛 ( δ 2 ) ∗ 1 √2 𝛿 = 2𝑠𝑖𝑛−1 ( 𝑣 𝑎𝑐1∗𝜋 2√2𝑉 𝑑𝑐 ) Therefore for this system where Vdc = 400 V and vac RMS = 110 V it is required that δ = 35.57°. This would switch at the source frequency, i.e. 60 Hz. A control system can be implemented to adjust this angle when required based on the grid and battery conditions, for instance if the dc bus voltage was to change as the batteries discharge. In rectifier mode the dc voltage can be given by Eq. 3: 𝑉𝑑𝑐 = 2vac π cosα − 2𝐼 𝑑𝑐 𝜔𝐿 𝑠 𝜋 (3) In this equation α is the control angle and is the phase difference between vac and the MOSFET firing pulses and Ls is the source inductance. Therefore the dc voltage varies with Idc and α, assuming all other parameters are constant. The control angle is required to be adjusted by a closed loop controller depending on the required current. C. Energy Storage Considerations A number of energy storage solutions are considered by Vazquez in [3], with their main characteristics outlined in Table II. For similar applications Li-ion batteries are the preferred technology thanks to their relatively high energy and power densities, meaning that more energy can be stored per kilogram of mass in Li-ion batteries compared to their lead acid or nickel based counterparts. However due to the relatively low availability of lithium and the increasing popularity of lithium based batteries in applications such as electric vehicles the raw material cost of lithium is likely to increase [9]. In this case cheaper battery technologies may be used for lower power applications. In [8] Li-ion batteries are used for experimental testing of the isolated bidirectional ac to dc converter. Battery modules are used, each containing seven cells. With each cell rated at 3.8 V, each module can supply 26.6 V. Therefore for the system considered here fifteen series connected batteries are required TABLE II. Comparison of Energy Storage Systems [3]. to provide the maximum battery voltage of 400 V. Each battery module is rated at 40 Ah and can be connected to additional modules in parallel to boost the capacity. D. Control System It is preferable for the system to be autonomous and self- regulate its operation, especially where used in smaller scale or smart-grid applications. Each stage of the converter requires a control systemto maintain the desired voltage and current levels. For stage 1 the system must regulate the dc bus voltage as well as the grid current to maintain the correct voltage phase and maintain unity power factor. Meanwhile the control system for stage 2 maintains the battery current and voltage by means of controlling φ to regulate the charging and discharging of the batteries. A potential control strategy is outlined in [5] as depicted in Fig. 9. In this example each control system implements a double closed loop, each with an inner current loop and outer voltage loop. For Stage 1 (Bridge A) the voltages V1 and vs are monitored as well as the grid current is. Through altering the gate signal of each MOSFET (i.e. adjusting δ) control over the phase and amplitude of vso can be achieved, thus enabling control over the phase and amplitude of is. This allows for control over the power flow between the grid and the dc bus, and regulation of the dc bus voltage, V1. As mentioned previously the switching frequency is the frequency of vac when operating in inverter mode, therefore in this mode the switching frequency should be 60 Hz. The controller for stage 2 controls the switching signals for bridges B and C. It does this through monitoring the battery current and voltage and adjusting d accordingly to regulate the magnitude and phase of iL. Using these values the state of charge (SOC) of the batteries can be estimated. However, determining the exact SOC can be challenging [2] so monitoring current and voltage can improve the system accuracy. Additional control parameters may be applied to the batteries to provide protection against undervoltage or overvoltage, overheating and overcurrent. This is necessary with Li-ion batteries to prevent the internal resistance of the cells from heating up and failing [3]. Measures to balance the cell voltages and SOCs are also favorable to maintain the cell lifetime [2], [3].
  • 6. 6 Fig. 9. Control Strategy for Grid Connected Isolated Bidirectional AC to DC Converter [5]. E. Converter Efficiency As with most electronic circuits the considered converter design is susceptible to energy losses. These losses will mainly occur in the MOSFETs and the transformer coils. Each switch will exhibit switching losses due to its rise and fall times, particularly at high frequencies. However, since this system uses zero voltage switching these losses should be minimised. There are also conduction losses through each switch due to the finite switch resistance. This can be a disadvantage for the converter using the DAB compared to the single bridge converter since three times the number of switches are required, tripling the switching power loss. However since the efficiency of the high frequency transformer is expected to be much higher than the equivalent low frequency design the power loss savings here may outweigh the switching losses, meaning that the isolated system operates at a higher efficiency overall. As outlined in [5], with traditional power and magnetic components it can be difficult to achieve high efficiency and power density. For this reason it is suggested that newer switching and transformer technologies are introduced. These include using silicon carbide (SiC) devices as opposed to the traditional silicon (Si) devices, as well as replacing ferrite with nanocrystalline soft magnetic material in transformers and inductors. However the use ofthese materials will incur a greater expense when building the system so may not be advised for lower power applications. From similar reports an efficiency of around 95% can be expected [5], [8]. III. CONCLUSION This paper has discussed the role of battery energy storage systems in our electricity grids for peak shaving and grid stabilization. The requirement of a bidirectional ac to dc converter was reviewed in the role of connecting the BESS to the electricity grid. Furthermore the isolated bidirectional ac to dc converter was taken into consideration for analysis and design, the benefits of this system being stated as reducing the battery bank voltage and the required number of series cells, as well as increasing system safety by isolating the battery bank from the grid. This was a two stage converter, with stage one being a basic full bridge bidirectional ac to dc converter, and stage two being a dual active bridge dc to dc converter. During the design process the ideal leakage inductance of the high frequency transformer was calculated to be L = 59.26 μH. This would allow for nominal operating conditions when the phase shift across the DAB was 60°. Simulation of this stage confirmed that these values were appropriate. Following this a control method was considered which could adjust the phase shift on order to regulating the power flow across the DAB, thereby controlling the charging or discharging of the batteries. For the battery bank, lithium ion cells were chosen for their high efficiency and high power density. Finally the estimated power losses of the system were discussed and it was noted that the efficiency could be increased using more advanced switching and transformer materials. Future work to be carried out could include a more detailed analysis and design of the control system to devise a solution of fully automated control. A full system simulation could be completed and analyzed under various loading conditions, comparing this converter to alternative designs, before a real converter is built. REFERENCES [1] “IESO Power Data,” The Independent Electricity System Operator (IESO), 2015. [Online]. Available: http://www.ieso.ca/Pages/Power-Data/default.aspx#. [Accessed 09 April 2015]. [2] H. Qian, J. Zhang, J. Lai and W. Yu, “A High-Efficiency Grid-Tie Battery Energy Storage System,” IEEE Transactions on Power Electroinics, vol. 26, no. 3, pp. 886-896, 2011. [3] S. Vazquez, S. Lukic, E. Galvan, L. Franquelo and J. Carrasco, “Energy Storage Systems for Transport and Grid Application,” IEEE Transactions on Industrial Electronics, vol. 57, no. 12, pp. 3881-3895, 2010. [4] N. Mohan, Power Electronics: Converters, Applications, And Design, 3rd ed., John Wiley & Sons, 2002. [5] B. Zhao, Q. Song, W. Liu and Y. Sun, “A Synthetic Discrete Design Methodology of High-Frequency Isolated Bidirectional DC/DC Converter for Grid- Connected Battery Energy Storage System Using Advanced Components,” Industrial Electronics, IEEE Transactions on, vol. 61, no. 10, pp. 5402-5410, 2014. [6] M. Kheraluwala, R. Gascoigne, D. Divan and E. Baumann, “Performance Characterization of a High- Power Dual Active Bridge dc-to-dc Converter,” IEEE Transactions on Industry Applications, vol. 28, no. 6, pp. 1294-1301, 1992. [7] R. W. A. A. De Doncker, D. M. Divan and M. H. Kheraluwala, “A Three-phase Soft-Switched High- Power-Density dc /dc Converter for High-Power
  • 7. 7 Applications,” IEEE Transactions on Industry Applications, vol. 27, no. 1, pp. 63-73, 1991. [8] N. Tan, T. Abe and H. Akagi, “Design and Performance of a Bidirectional Isolated DC–DC Converter for a Battery Energy Storage System,” IEEE Transactions on Power Electronics, vol. 27, no. 3, pp. 1237-1248, 2012. [9] W. Tahil, “The Trouble With Lithium - Implications of Future PHEV Production for Lithium Demand,” Meridian International Research, Martainville, France, 2006.