SlideShare a Scribd company logo
1 of 92
Fundamentals of
Bus Bar Protection
GE Multilin
2
GE Consumer & Industrial
Multilin
29-Oct-22
Outline
• Bus arrangements
• Bus components
• Bus protection techniques
• CT Saturation
• Application Considerations:
 High impedance bus differential relaying
 Low impedance bus differential relaying
 Special topics
3
GE Consumer & Industrial
Multilin
29-Oct-22
1 2 3 n-1 n
ZONE 1
- - - -
• Distribution and lower transmission voltage levels
• No operating flexibility
• Fault on the bus trips all circuit breakers
Single bus - single breaker
4
GE Consumer & Industrial
Multilin
29-Oct-22
ZONE 1
ZONE 2
• Distribution and lower transmission voltage levels
• Limited operating flexibility
Multiple bus sections - single breaker with
bus tie
5
GE Consumer & Industrial
Multilin
29-Oct-22
ZONE 1
ZONE 2
• Transmission and distribution voltage levels
• Breaker maintenance without circuit removal
• Fault on a bus disconnects only the circuits being connected
to that bus
Double bus - single breaker with bus tie
6
GE Consumer & Industrial
Multilin
29-Oct-22
ZONE 1
MAIN BUS
TRANFER BUS
• Increased operating flexibility
• A bus fault requires tripping all breakers
• Transfer bus for breaker maintenance
Main and transfer buses
7
GE Consumer & Industrial
Multilin
29-Oct-22
ZONE 1
ZONE 2
• Very high operating flexibility
• Transfer bus for breaker maintenance
Double bus – single breaker w/ transfer bus
8
GE Consumer & Industrial
Multilin
29-Oct-22
ZONE 1
ZONE 2
• High operating flexibility
• Line protection covers bus section between two CTs
• Fault on a bus does not disturb the power to circuits
Double bus - double breaker
9
GE Consumer & Industrial
Multilin
29-Oct-22
ZONE 1
ZONE 2
• Used on higher voltage levels
• More operating flexibility
• Requires more breakers
• Middle bus sections covered by line or other equipment
protection
Breaker-and-a-half bus
10
GE Consumer & Industrial
Multilin
29-Oct-22
• Higher voltage levels
• High operating flexibility with minimum breakers
• Separate bus protection not required at line positions
B1 B2
TB1
L1 L2
L3 L4
TB1
Ring bus
11
GE Consumer & Industrial
Multilin
29-Oct-22
Bus components breakers
SF6, EHV & HV - Synchropuff
Low Voltage circuit breakers
BUS 2
CB 1
BUS 1
ISO 1 ISO 2
ISO 3
BYPASS
12
GE Consumer & Industrial
Multilin
29-Oct-22
-
+
F1a
F1c
Contact Input F1a On
Contact Input F1c On
F1b
ISOLATOR
1
ISOLATOR 1 OPEN
7B 7A
BUS 1
-
+
F1a
F1c
Contact Input F1a On
Contact Input F1c On
F1b
ISOLATOR
1
ISOLATOR 1 CLOSED
7B 7A
BUS 1
Disconnect switches & auxiliary contacts
BUS 2
CB 1
BUS 1
ISO 1 ISO 2
ISO 3
BYPASS
13
GE Consumer & Industrial
Multilin
29-Oct-22
BUS 2
CB 1
BUS 1
ISO 1 ISO 2
ISO 3
BYPASS
Current Transformers
Oil insulated current transformer
(35kV up to 800kV)
Gas (SF6) insulated current
transformer
Bushing type (medium
voltage switchgear)
14
GE Consumer & Industrial
Multilin
29-Oct-22
Protection Requirements
High bus fault currents due to large number of circuits
connected:
• CT saturation often becomes a problem as CTs may not be sufficiently
rated for worst fault condition case
• large dynamic forces associated with bus faults require fast clearing
times in order to reduce equipment damage
False trip by bus protection may create serious problems:
• service interruption to a large number of circuits (distribution and sub-
transmission voltage levels)
• system-wide stability problems (transmission voltage levels)
With both dependability and security important, preference is
always given to security
15
GE Consumer & Industrial
Multilin
29-Oct-22
Bus Protection Techniques
• Interlocking schemes
• Overcurrent (“unrestrained” or “unbiased”)
differential
• Overcurrent percent (“restrained” or “biased”)
differential
• Linear couplers
• High-impedance bus differential schemes
• Low-impedance bus differential schemes
16
GE Consumer & Industrial
Multilin
29-Oct-22
Interlocking Schemes
• Blocking scheme typically
used
• Short coordination time
required
• Care must be taken with
possible saturation of feeder
CTs
• Blocking signal could be sent
over communications ports
(peer-to-peer)
• This technique is limited to
simple one-incomer
distribution buses
50
50 50 50 50 50
BLOCK
17
GE Consumer & Industrial
Multilin
29-Oct-22
Overcurrent (unrestrained) Differential
• Differential signal formed by
summation of all currents feeding
the bus
• CT ratio matching may be
required
• On external faults, saturated CTs
yield spurious differential current
• Time delay used to cope with CT
saturation
• Instantaneous differential OC
function useful on integrated
microprocessor-based relays
51
18
GE Consumer & Industrial
Multilin
29-Oct-22
59
Linear Couplers
ZC = 2  – 20  - typical coil impedance
(5V per 1000Amps => 0.005 @ 60Hz )
If = 8000 A
40 V 10 V 10 V 0 V 20 V
2000 A 2000 A 4000 A
0 A
0 V
External
Fault
19
GE Consumer & Industrial
Multilin
29-Oct-22
59
Linear Couplers
Esec= Iprim*Xm - secondary voltage on relay terminals
IR= Iprim*Xm /(ZR+ZC) – minimum operating current
where,
Iprim – primary current in each circuit
Xm – liner coupler mutual reactance (5V per 1000Amps => 0.005 @ 60Hz )
ZR – relay tap impedance
ZC – sum of all linear coupler self impedances
If = 8000 A
0 A
0 V 10 V 10 V 0 V 20 V
40 V
2000 A 2000 A 4000 A
0 A
Internal Bus
Fault
20
GE Consumer & Industrial
Multilin
29-Oct-22
• Fast, secure and proven
• Require dedicated air gap CTs, which may not be used for
any other protection
• Cannot be easily applied to reconfigurable buses
• The scheme uses a simple voltage detector – it does not
provide benefits of a microprocessor-based relay (e.g.
oscillography, breaker failure protection, other functions)
Linear Couplers
21
GE Consumer & Industrial
Multilin
29-Oct-22
High Impedance Differential
• Operating signal created by
connecting all CT secondaries in
parallel
o CTs must all have the same ratio
o Must have dedicated CTs
• Overvoltage element operates on
voltage developed across resistor
connected in secondary circuit
o Requires varistors or AC shorting
relays to limit energy during faults
• Accuracy dependent on secondary
circuit resistance
o Usually requires larger CT cables to
reduce errors  higher cost
Cannot easily be applied to reconfigurable buses and
offers no advanced functionality
59
22
GE Consumer & Industrial
Multilin
29-Oct-22
Percent Differential
• Percent characteristic used
to cope with CT saturation
and other errors
• Restraining signal can be
formed in a number of
ways
• No dedicated CTs needed
• Used for protection of re-
configurable buses
possible
51
87
n
DIF I
I
I
I 


 ...
2
1
n
RES I
I
I
I 


 ...
2
1  
n
RES I
I
I
I ...,
,
,
max 2
1

23
GE Consumer & Industrial
Multilin
29-Oct-22
Low Impedance Percent Differential
• Individual currents sampled by protection and summated digitally
o CT ratio matching done internally (no auxiliary CTs)
o Dedicated CTs not necessary
• Additional algorithms improve security of percent differential
characteristic during CT saturation
• Dynamic bus replica allows application to reconfigurable buses
o Done digitally with logic to add/remove current inputs from differential
computation
o Switching of CT secondary circuits not required
• Low secondary burdens
• Additional functionality available
o Digital oscillography and monitoring of each circuit connected to bus zone
o Time-stamped event recording
o Breaker failure protection
24
GE Consumer & Industrial
Multilin
29-Oct-22
Digital Differential Algorithm Goals
• Improve the main differential algorithm operation
o Better filtering
o Faster response
o Better restraint techniques
o Switching transient blocking
• Provide dynamic bus replica for reconfigurable bus bars
• Dependably detect CT saturation in a fast and reliable manner,
especially for external faults
• Implement additional security to the main differential algorithm to
prevent incorrect operation
o External faults with CT saturation
o CT secondary circuit trouble (e.g. short circuits)
25
GE Consumer & Industrial
Multilin
29-Oct-22
Low Impedance Differential (Distributed)
• Data Acquisition Units (DAUs)
installed in bays
• Central Processing Unit (CPU)
processes all data from DAUs
• Communications between DAUs
and CPU over fiber using
proprietary protocol
• Sampling synchronisation
between DAUs is required
• Perceived less reliable (more
hardware needed)
• Difficult to apply in retrofit
applications
52
DAU
52
DAU
52
DAU
CU
copper
fiber
26
GE Consumer & Industrial
Multilin
29-Oct-22
Low Impedance Differential (Centralized)
• All currents applied to a single
central processor
• No communications, external
sampling synchronisation
necessary
• Perceived more reliable (less
hardware needed)
• Well suited to both new and
retrofit applications.
52 52 52
CU
copper
27
GE Consumer & Industrial
Multilin
29-Oct-22
CT Saturation
28
GE Consumer & Industrial
Multilin
29-Oct-22
CT Saturation Concepts
• CT saturation depends on a number of factors
o Physical CT characteristics (size, rating, winding resistance,
saturation voltage)
o Connected CT secondary burden (wires + relays)
o Primary current magnitude, DC offset (system X/R)
o Residual flux in CT core
• Actual CT secondary currents may not behave in the same manner as
the ratio (scaled primary) current during faults
• End result is spurious differential current appearing in the summation
of the secondary currents which may cause differential elements to
operate if additional security is not applied
29
GE Consumer & Industrial
Multilin
29-Oct-22
CT Saturation
Ratio Current CT Current
Ratio Current CT Current
No DC Offset
• Waveform remains fairly
symmetrical
With DC Offset
• Waveform starts off being
asymmetrical, then
symmetrical in steady
state
30
GE Consumer & Industrial
Multilin
29-Oct-22
External Fault & Ideal CTs
• Fault starts at t0
• Steady-state fault conditions occur at t1
differential
restraining
t0
t1
Ideal CTs have no saturation or mismatch errors thus
produce no differential current
31
GE Consumer & Industrial
Multilin
29-Oct-22
External Fault & Actual CTs
• Fault starts at t0
• Steady-state fault conditions occur at t1
differential
restraining
t0
t1
Actual CTs do introduce errors, producing some differential
current (without CT saturation)
32
GE Consumer & Industrial
Multilin
29-Oct-22
External Fault with CT Saturation
• Fault starts at t0, CT begins to saturate at t1
• CT fully saturated at t2
differential
restraining
t0
t1
t2
CT saturation causes increasing differential current that
may enter the differential element operate region.
33
GE Consumer & Industrial
Multilin
29-Oct-22
Some Methods of Securing Bus Differential
• Block the bus differential for a period of time (intentional delay)
o Increases security as bus zone will not trip when CT saturation is present
o Prevents high-speed clearance for internal faults with CT saturation or
evolving faults
• Change settings of the percent differential characteristic (usually Slope 2)
o Improves security of differential element by increasing the amount of
spurious differential current needed to incorrectly trip
o Difficult to explicitly develop settings (Is 60% slope enough? Should it be
75%?)
• Apply directional (phase comparison) supervision
o Improves security by requiring all currents flow into the bus zone before
asserting the differential element
o Easy to implement and test
o Stable even under severe CT saturation during external faults
34
GE Consumer & Industrial
Multilin
29-Oct-22
High-Impedance
Bus Differential
Considerations
35
GE Consumer & Industrial
Multilin
29-Oct-22
High Impedance Voltage-operated Relay
External Fault
• 59 element set above max possible voltage developed across
relay during external fault causing worst case CT saturation
• For internal faults, extremely high voltages (well above 59
element pickup) will develop across relay
36
GE Consumer & Industrial
Multilin
29-Oct-22
High Impedance Voltage Operated Relay
Ratio matching with Multi-ratio CTs
• Application of high impedance differential relays with CTs of
different ratios but ratio matching taps is possible, but could
lead to voltage magnification.
• Voltage developed across full winding of tapped CT does not
exceed CT rating, terminal blocks, etc.
37
GE Consumer & Industrial
Multilin
29-Oct-22
High Impedance Voltage Operated Relay
Ratio matching with Multi-ratio CTs
• Use of auxiliary CTs to obtain correct ratio matching is also
possible, but these CTs must be able to deliver enough voltage
necessary to produce relay operation for internal faults.
38
GE Consumer & Industrial
Multilin
29-Oct-22
Electromechanical High Impedance Bus
Differential Relays
• Single phase relays
• High-speed
• High impedance voltage sensing
• High seismic IOC unit
39
GE Consumer & Industrial
Multilin
29-Oct-22
Operating time: 20 – 30ms @ I > 1.5xPKP
P -based High-Impedance Bus Differential
Protection Relays
40
GE Consumer & Industrial
Multilin
29-Oct-22
RST = 2000 - stabilizing resistor to limit the current
through the relay, and force it to the lower impedance CT
windings.
MOV – Metal Oxide Varistor to limit the voltage to
1900 Volts
86 – latching contact preventing the resistors from
overheating after the fault is detected
High Impedance Module for Digital
Relays
41
GE Consumer & Industrial
Multilin
29-Oct-22
High-Impedance Module
+
Overcurrent Relay
42
GE Consumer & Industrial
Multilin
29-Oct-22
• Fast, secure and proven
• Requires dedicated CTs, preferably with the same CT ratio
and using full tap
• Can be applied to small buses
• Depending on bus internal and external fault currents, high
impedance bus diff may not provide adequate settings for
both sensitivity and security
• Cannot be easily applied to reconfigurable buses
• Require voltage limiting varistor capable of absorbing
significant energy
• May require auxiliary CTs
• Do not provide full benefits of microprocessor-based relay
system (e.g. metering, monitoring, oscillography, etc.)
High Impedance Bus Protection - Summary
43
GE Consumer & Industrial
Multilin
29-Oct-22
Low-Impedance
Bus Differential
Considerations
44
GE Consumer & Industrial
Multilin
29-Oct-22
P-based Low-Impedance Relays
• No need for dedicated CTs
• Internal CT ratio mismatch compensation
• Advanced algorithms supplement percent differential
protection function making the relay very secure
• Dynamic bus replica (bus image) principle is used in
protection of reconfigurable bus bars, eliminating the need
for switching physically secondary current circuits
• Integrated Breaker Failure (BF) function can provide
optimal tripping strategy depending on the actual
configuration of a bus bar
45
GE Consumer & Industrial
Multilin
29-Oct-22
• Up to 24 Current Inputs
• 4 Zones
• Zone 1 = Phase A
• Zone 2 = Phase B
• Zone 3 = Phase C
• Zone 4 = Not used
• Different CT Ratio Capability for
Each Circuit
• Largest CT Primary is Base in
Relay
2-8 Circuit Applications
Small Bus Applications
46
GE Consumer & Industrial
Multilin
29-Oct-22
• Relay 1 - 24 Current Inputs
• 4 Zones
• Zone 1 = Phase A (12 currents)
• Zone 2 = Phase B (12 currents)
• Zone 3 = Not used
• Zone 4 = Not used
CB 12
CB 11
• Different CT Ratio Capability for Each Circuit
• Largest CT Primary is Base in Relay
• Relay 2 - 24 Current Inputs
• 4 Zones
• Zone 1 = Not used
• Zone 2 = Not used
• Zone 3 = Phase C (12 currents)
• Zone 4 = Not used
9-12 Circuit Applications
Medium to Large Bus Applications
47
GE Consumer & Industrial
Multilin
29-Oct-22
Large Bus Applications
87B phase A
87B phase B
87B phase C
Logic relay
(switch status,
optional BF)
48
GE Consumer & Industrial
Multilin
29-Oct-22
Large Bus Applications
For buses with up to 24 circuits
49
GE Consumer & Industrial
Multilin
29-Oct-22
Summing External Currents
Not Recommended for Low-Z 87B relays
• Relay becomes combination
of restrained and unrestrained
elements
•In order to parallel CTs:
• CT performance must be closely
matched
o Any errors will appear as
differential currents
• Associated feeders must be radial
o No backfeeds possible
• Pickup setting must be raised to
accommodate any errors
CT-1
CT-2
CT-3
CT-4
I
3
=
0
I
2
=
0
I
1
=
Error
IDIFF
= Error
IREST
= Error
Maloperation if
Error > PICKUP
50
GE Consumer & Industrial
Multilin
29-Oct-22
Definitions of Restraint Signals
“maximum of”
“geometrical average”
“scaled sum of”
“sum of”
n
R i
i
i
i
i 



 ...
3
2
1
 
n
R i
i
i
i
n
i 



 ...
1
3
2
1
 
n
R i
i
i
i
Max
i ,...,
,
, 3
2
1

n
n
R i
i
i
i
i 



 ...
3
2
1
51
GE Consumer & Industrial
Multilin
29-Oct-22
“Sum Of” vs. “Max Of” Restraint Methods
“Sum Of” Approach
• More restraint on external faults;
less sensitive for internal faults
• “Scaled-Sum Of” approach takes
into account number of connected
circuits and may increase
sensitivity
• Breakpoint settings for the percent
differential characteristic more
difficult to set
“Max Of” Approach
• Less restraint on external faults;
more sensitive for internal faults
• Breakpoint settings for the percent
differential characteristic easier to
set
• Better handles situation where one
CT may saturate completely (99%
slope settings possible)
52
GE Consumer & Industrial
Multilin
29-Oct-22
Bus Differential Adaptive Approach
differential
restraining
Region 1
(low differential
currents)
Region 2
(high differential
currents)
53
GE Consumer & Industrial
Multilin
29-Oct-22
Bus Differential Adaptive Logic Diagram
DIFL
DIR
SAT
DIFH
OR
AND
OR
87B BIASED OP
AND
54
GE Consumer & Industrial
Multilin
29-Oct-22
Phase Comparison Principle
• Internal Faults: All fault (“large”) currents are approximately in
phase.
• External Faults: One fault (“large”) current will be out of phase
• No Voltages are required or needed
Secondary Current of
Faulted Circuit
(Severe CT Saturation)
55
GE Consumer & Industrial
Multilin
29-Oct-22
Phase Comparison Principle Continued…
BLOCK
OPERATE
BLOCK








 p
D
p
I
I
I
real








 p
D
p
I
I
I
imag
Ip
ID - Ip
External Fault Conditions
OPERATE
BLOCK
BLOCK








 p
D
p
I
I
I
real








 p
D
p
I
I
I
imag
Ip
ID - Ip
Internal Fault Conditions
OPERATE
OPERATE
56
GE Consumer & Industrial
Multilin
29-Oct-22
CT Saturation
• Fault starts at t0, CT begins to saturate at t1
• CT fully saturated at t2
differential
restraining
t0
t1
t2
57
GE Consumer & Industrial
Multilin
29-Oct-22
CT Saturation Detector State Machine
NORMAL
SAT := 0
EXTERNAL
FAULT
SAT := 1
EXTERNAL
FAULT & CT
SATURATION
SAT := 1
The differential
characteristic
entered
The differential-
restraining trajectory
out of the differential
characteristic for
certain period of time
saturation
condition
The differential
current below the
first slope for
certain period of
time
58
GE Consumer & Industrial
Multilin
29-Oct-22
CT Saturation Detector Operating
Principles
• The 87B SAT flag WILL NOT be set during internal faults,
regardless of whether or not any of the CTs saturate.
• The 87B SAT flag WILL be set during external faults,
regardless of whether or not any of the CTs saturate.
• By design, the 87B SAT flag WILL force the relay to use
the additional 87B DIR phase comparison for Region 2
The Saturation Detector WILL NOT Block the Operation of
the Differential Element – it will only Force 2-out-of-2
Operation
59
GE Consumer & Industrial
Multilin
29-Oct-22
CT Saturation Detector - Examples
• The oscillography records on the next two slides were captured from a
B30 relay under test on a real-time digital power system simulator
• First slide shows an external fault with deep CT saturation (~1.5 msec of
good CT performance)
o SAT saturation detector flag asserts prior to BIASED PKP bus
differential pickup
o DIR directional flag does not assert (one current flows out of zone),
so even though bus differential picks up, no trip results
• Second slide shows an internal fault with mild CT saturation
o BIASED PKP and BIASED OP both assert before DIR asserts
o CT saturation does not block bus differential
• More examples available (COMTRADE files) upon request
60
GE Consumer & Industrial
Multilin
29-Oct-22
The bus differential
protection element
picks up due to heavy
CT saturation
The CT saturation flag
is set safely before the
pickup flag
The
directional flag
is not set
The element
does not
maloperate
Despite heavy CT
saturation the
external fault current
is seen in the
opposite direction
CT Saturation Example – External Fault
0.06 0.07 0.08 0.09 0.1 0.11 0.12
-200
-150
-100
-50
0
50
100
150
200
time, sec
current,
A
~1 ms
61
GE Consumer & Industrial
Multilin
29-Oct-22
The bus differential
protection element
picks up
The saturation
flag is not set - no
directional
decision required
The element
operates in
10ms
The
directional
flag is set
All the fault currents
are seen in one
direction
CT Saturation – Internal Fault Example
62
GE Consumer & Industrial
Multilin
29-Oct-22
Applying Low-Impedance Differential
Relays for Busbar Protection
Basic Topics
• Configure physical CT Inputs
• Configure Bus Zone and Dynamic Bus Replica
• Calculating Bus Differential Element settings
Advanced Topics
• Isolator switch monitoring for reconfigurable buses
• Differential Zone CT Trouble
• Integrated Breaker Failure protection
63
GE Consumer & Industrial
Multilin
29-Oct-22
Configuring CT Inputs
• For each connected CT circuit enter Primary rating and
select Secondary rating.
• Each 3-phase bank of CT inputs must be assigned to a
Signal Source that is used to define the Bus Zone and
Dynamic Bus Replica
Some relays define 1 p.u. as the maximum
primary current of all of the CTs connected in the
given Bus Zone
64
GE Consumer & Industrial
Multilin
29-Oct-22
Per-Unit Current Definition - Example
Current
Channel
Primary Secondary Zone
CT-1 F1 3200 A 1 A 1
CT-2 F2 2400 A 5 A 1
CT-3 F3 1200 A 1 A 1
CT-4 F4 3200 A 1 A 2
CT-5 F5 1200 A 5 A 2
CT-6 F6 5000 A 5 A 2
• For Zone 1, 1 p.u. = 3200 AP
• For Zone 2, 1 p.u. = 5000 AP
65
GE Consumer & Industrial
Multilin
29-Oct-22
Configuration of Bus Zone
• Dynamic Bus Replica associates a status signal with each
current in the Bus Differential Zone
• Status signal can be any logic operand
o Status signals can be developed in programmable logic
to provide additional checks or security as required
o Status signal can be set to ‘ON’ if current is always in the
bus zone or ‘OFF’ if current is never in the bus zone
• CT connections/polarities for a particular bus zone must be
properly configured in the relay, via either hardwire or
software
66
GE Consumer & Industrial
Multilin
29-Oct-22
Configuring the Bus Differential Zone
1. Configure the physical CT Inputs
o CT Primary and Secondary values
o Both 5 A and 1 A inputs are supported by the UR hardware
o Ratio compensation done automatically for CT ratio differences up to 32:1
2. Configure AC Signal Sources
3. Configure Bus Zone with Dynamic Bus Replica
Bus Zone settings defines the boundaries of the Differential
Protection and CT Trouble Monitoring.
67
GE Consumer & Industrial
Multilin
29-Oct-22
Dual Percent Differential Characteristic
High
Breakpoint
Low
Breakpoint
Low Slope
High Slope
High Set
(Unrestrained)
Min Pickup
68
GE Consumer & Industrial
Multilin
29-Oct-22
Calculating Bus Differential Settings
• The following Bus Zone Differential element parameters need to be set:
o Differential Pickup
o Restraint Low Slope
o Restraint Low Break Point
o Restraint High Breakpoint
o Restraint High Slope
o Differential High Set (if needed)
• All settings entered in per unit (maximum CT primary in the zone)
• Slope settings entered in percent
• Low Slope, High Slope and High Breakpoint settings are used by the CT
Saturation Detector and define the Region 1 Area (2-out-of-2 operation
with Directional)
69
GE Consumer & Industrial
Multilin
29-Oct-22
Calculating Bus Differential Settings –
Minimum Pickup
• Defines the minimum differential current required for
operation of the Bus Zone Differential element
• Must be set above maximum leakage current not zoned off
in the bus differential zone
• May also be set above maximum load conditions for added
security in case of CT trouble, but better alternatives exist
70
GE Consumer & Industrial
Multilin
29-Oct-22
Calculating Bus Differential Settings –
Low Slope
• Defines the percent bias for the restraint currents from
IREST=0 to IREST=Low Breakpoint
• Setting determines the sensitivity of the differential element
for low-current internal faults
• Must be set above maximum error introduced by the CTs in
their normal linear operating mode
• Range: 15% to 100% in 1%. increments
71
GE Consumer & Industrial
Multilin
29-Oct-22
Calculating Bus Differential Settings –
Low Breakpoint
• Defines the upper limit to restraint currents that will be
biased according to the Low Slope setting
• Should be set to be above the maximum load but not more
than the maximum current where the CTs still operate
linearly (including residual flux)
• Assumption is that the CTs will be operating linearly (no
significant saturation effects up to 80% residual flux) up to
the Low Breakpoint setting
72
GE Consumer & Industrial
Multilin
29-Oct-22
Calculating Bus Differential Settings –
High Breakpoint
• Defines the minimum restraint currents that will be biased
according to the High Slope setting
• Should be set to be below the minimum current where the
weakest CT will saturate with no residual flux
• Assumption is that the CTs will be operating linearly (no
significant saturation effects up to 80% residual flux) up to
the Low Breakpoint setting
73
GE Consumer & Industrial
Multilin
29-Oct-22
Calculating Bus Differential Settings –
High Slope
• Defines the percent bias for the restraint currents IRESTHigh
Breakpoint
• Setting determines the stability of the differential element
for high current external faults
• Traditionally, should be set high enough to accommodate
the spurious differential current resulting from saturation
of the CTs during heavy external faults
• Setting can be relaxed in favour of sensitivity and speed as
the relay detects CT saturation and applies the directional
principle to prevent maloperation
• Range: 50% to 100% in 1%. increments
74
GE Consumer & Industrial
Multilin
29-Oct-22
Calculating Unrestrained Bus Differential
Settings
• Defines the minimum differential current for unrestrained
operation
• Should be set to be above the maximum differential current
under worst case CT saturation
• Range: 2.00 to 99.99 p.u. in 0.01 p.u. increments
• Can be effectively disabled by setting to 99.99 p.u.
75
GE Consumer & Industrial
Multilin
29-Oct-22
Dual Percent Differential Characteristic
High
Breakpoint
Low
Breakpoint
Low Slope
High Slope
High Set
(Unrestrained)
Min Pickup
76
GE Consumer & Industrial
Multilin
29-Oct-22
NORTH BUS
SOUTH BUS
CT-8
B-5
B-6
CT-5
CT-6
S-5
S-6
B-4
CT-4
S-3
S-4
B-3
CT-3
S-1
S-2
B-2
CT-2
CT-1
B-1
C-1 C-2 C-4
C-3 C-5
CT-7
B-7
Protecting re-configurable buses
Reconfigurable Buses
77
GE Consumer & Industrial
Multilin
29-Oct-22
NORTH BUS
SOUTH BUS
CT-7
CT-8
B-7
B-5
B-6
CT-5
CT-6
S-5
S-6
B-4
CT-4
S-3
S-4
B-3
CT-3
S-1
S-2
B-2
CT-2
CT-1
B-1
C-1 C-2 C-4
C-3 C-5
Protecting re-configurable buses
Reconfigurable Buses
78
GE Consumer & Industrial
Multilin
29-Oct-22
NORTH BUS
SOUTH BUS
CT-7
CT-8
B-7
B-5
B-6
CT-5
CT-6
S-5
S-6
B-4
CT-4
S-3
S-4
B-3
CT-3
S-1
S-2
B-2
CT-2
CT-1
B-1
C-1 C-2 C-4
C-3 C-5
Protecting re-configurable buses
Reconfigurable Buses
79
GE Consumer & Industrial
Multilin
29-Oct-22
NORTH BUS
SOUTH BUS
CT-8
B-5
B-6
CT-5
CT-6
S-5
S-6
B-4
CT-4
S-3
S-4
B-3
CT-3
S-1
S-2
B-2
CT-2
CT-1
B-1
C-1 C-2 C-4
C-3 C-5
CT-7
B-7
Protecting re-configurable buses
Reconfigurable Buses
80
GE Consumer & Industrial
Multilin
29-Oct-22
Isolators
• Reliable “Isolator Closed” signals are needed for the Dynamic
Bus Replica
• In simple applications, a single normally closed contact may
be sufficient
• For maximum safety:
o Both N.O. and N.C. contacts should be used
o Isolator Alarm should be established and non-valid combinations
(open-open, closed-closed) should be sorted out
o Switching operations should be inhibited until bus image is recognized
with 100% accuracy
o Optionally block 87B operation from Isolator Alarm
• Each isolator position signal decides:
o Whether or not the associated current is to be included in the
differential calculations
o Whether or not the associated breaker is to be tripped
81
GE Consumer & Industrial
Multilin
29-Oct-22
Isolator – Typical Open/Closed
Connections
82
GE Consumer & Industrial
Multilin
29-Oct-22
Isolator Open
Auxiliary
Contact
Isolator Closed
Auxiliary
Contact
Isolator Position Alarm Block Switching
Off On CLOSED No No
Off Off LAST VALID After time delay
until
acknowledged
Until Isolator
Position is valid
On On CLOSED
On Off OPEN No No
NOTE: Isolator monitoring function may be a built-in feature or user-
programmable in low impedance bus differential digital relays
Switch Status Logic and Dyanamic Bus
Replica
83
GE Consumer & Industrial
Multilin
29-Oct-22
Differential Zone CT Trouble
• Each Bus Differential Zone may a dedicated CT Trouble
Monitor
• Definite time delay overcurrent element operating on the
zone differential current, based on the configured Dynamic
Bus Replica
• Three strategies to deal with CT problems:
1. Trip the bus zone as the problem with a CT will likely
evolve into a bus fault anyway
2. Do not trip the bus, raise an alarm and try to correct
the problem manually
3. Switch to setting group with 87B minimum pickup
setting above the maximum load current.
84
GE Consumer & Industrial
Multilin
29-Oct-22
• Strategies 2 and 3 can be accomplished by:
 Using undervoltage supervision to ride through the period
from the beginning of the problem with a CT until declaring a
CT trouble condition
 Using an external check zone to supervise the 87B function
 Using CT Trouble to prevent the Bus Differential tripping (2)
 Using setting groups to increase the pickup value for the 87B
function (3)
Differential Zone CT Trouble
85
GE Consumer & Industrial
Multilin
29-Oct-22
Differential Zone CT Trouble – Strategy #2
Example
• CT Trouble operand is used to rise an alarm
• The 87B trip is inhibited after CT Trouble
element operates
• The relay may misoperate if an external fault
occurs after CT trouble but before the CT trouble
condition is declared (double-contingency)
87B operates
Undervoltage condition
CT OK
86
GE Consumer & Industrial
Multilin
29-Oct-22
Example Architecture for Large Busbars
Dual (redundant) fiber with
3msec delivery time between
neighbouring IEDs. Up to 8
relays in the ring
Phase A AC signals and
trip contacts
Phase B AC signals and
trip contacts
Phase C AC signals and
trip contacts
Digital Inputs for isolator
monitoring and BF
87
GE Consumer & Industrial
Multilin
29-Oct-22
Phase A AC signals wired
here, bus replica configured
here
Phase B AC signals wired
here, bus replica configured
here
Phase C AC signals wired
here, bus replica configured
here
Auxuliary switches wired here;
Isolator Monitoring function
configured here
Example Architecture – Dynamic Bus
Replica and Isolator Position
88
GE Consumer & Industrial
Multilin
29-Oct-22
Phase A AC signals wired
here, current status
monitored here
Phase B AC signals wired
here, current status
monitored here
Phase C AC signals wired
here, current status
monitored here
Breaker Failure
elements configured
here
Example Architecture – BF Initiation &
Current Supervision
89
GE Consumer & Industrial
Multilin
29-Oct-22
Phase A AC signals wired
here, current status
monitored here
Phase B AC signals wired
here, current status
monitored here
Phase C AC signals wired
here, current status
monitored here
Breaker Fail Op command
generated here and send to trip
appropriate breakers
Trip
Trip
Trip
Example Architecture – Breaker Failure
Tripping Trip
90
GE Consumer & Industrial
Multilin
29-Oct-22
IEEE 37.234
• “Guide for Protective Relay Applications to Power
System Buses” is currently being revised by the K14
Working Group of the IEEE Power System Relaying
Committee.
91
GE Consumer & Industrial
Multilin
29-Oct-22
21955068-High-Low-Impedance-BusBar-Protection.ppt

More Related Content

What's hot

Power Transformer Protection
Power Transformer ProtectionPower Transformer Protection
Power Transformer ProtectionAng Sovann
 
Switchgear and protection 3
Switchgear and protection 3Switchgear and protection 3
Switchgear and protection 3Md Irshad Ahmad
 
Differential Protection Relay
DifferentialProtection RelayDifferentialProtection Relay
Differential Protection Relaykishore kish
 
Reactors and its types
Reactors and its typesReactors and its types
Reactors and its typesSlides Hub
 
36-DGSG-Mod 6-Lec 33 Harmonic Indices.pdf
36-DGSG-Mod 6-Lec 33 Harmonic Indices.pdf36-DGSG-Mod 6-Lec 33 Harmonic Indices.pdf
36-DGSG-Mod 6-Lec 33 Harmonic Indices.pdfvikip35
 
Numerical protection 2
Numerical protection 2Numerical protection 2
Numerical protection 2angila95
 
Relay Setting Calculation For REF615/ REJ601
Relay Setting Calculation For REF615/ REJ601Relay Setting Calculation For REF615/ REJ601
Relay Setting Calculation For REF615/ REJ601SARAVANAN A
 
Short Circuit, Protective Device Coordination
Short Circuit, Protective Device CoordinationShort Circuit, Protective Device Coordination
Short Circuit, Protective Device Coordinationmichaeljmack
 
Unit 03 Protective relays
Unit  03 Protective relaysUnit  03 Protective relays
Unit 03 Protective relaysPremanandDesai
 
Measurement of high_voltage_and_high_currentunit_iv_full_version
Measurement of high_voltage_and_high_currentunit_iv_full_versionMeasurement of high_voltage_and_high_currentunit_iv_full_version
Measurement of high_voltage_and_high_currentunit_iv_full_versionAman Ansari
 
Blackout Avoidance & Undervoltage Load Shedding
Blackout Avoidance & Undervoltage Load SheddingBlackout Avoidance & Undervoltage Load Shedding
Blackout Avoidance & Undervoltage Load Sheddingmichaeljmack
 
Unit 4 Automatic Generation Control
Unit 4 Automatic Generation ControlUnit 4 Automatic Generation Control
Unit 4 Automatic Generation ControlSANTOSH GADEKAR
 
Fault Calculations
Fault CalculationsFault Calculations
Fault Calculationsmichaeljmack
 
NGR & Zig-Zag Transformer.pptx
NGR & Zig-Zag Transformer.pptxNGR & Zig-Zag Transformer.pptx
NGR & Zig-Zag Transformer.pptxMUHAMMAD TAHIR
 
Transformers protection, an introduction
Transformers protection, an introductionTransformers protection, an introduction
Transformers protection, an introductionH. Kheir
 
Design of substation
Design of substationDesign of substation
Design of substationSayanSarkar55
 
FUNDAMENTALS OF POWER SYSTEM PROTECTION
FUNDAMENTALS OF POWER SYSTEM PROTECTIONFUNDAMENTALS OF POWER SYSTEM PROTECTION
FUNDAMENTALS OF POWER SYSTEM PROTECTIONPower System Operation
 
3. INTRODUCTION TO PROTECTIVE RELAYING.pptx
3. INTRODUCTION TO PROTECTIVE RELAYING.pptx3. INTRODUCTION TO PROTECTIVE RELAYING.pptx
3. INTRODUCTION TO PROTECTIVE RELAYING.pptxMuhd Hafizi Idris
 

What's hot (20)

Power Transformer Protection
Power Transformer ProtectionPower Transformer Protection
Power Transformer Protection
 
Switchgear and protection 3
Switchgear and protection 3Switchgear and protection 3
Switchgear and protection 3
 
Differential Protection Relay
DifferentialProtection RelayDifferentialProtection Relay
Differential Protection Relay
 
Reactors and its types
Reactors and its typesReactors and its types
Reactors and its types
 
Lighting arrester
Lighting arresterLighting arrester
Lighting arrester
 
36-DGSG-Mod 6-Lec 33 Harmonic Indices.pdf
36-DGSG-Mod 6-Lec 33 Harmonic Indices.pdf36-DGSG-Mod 6-Lec 33 Harmonic Indices.pdf
36-DGSG-Mod 6-Lec 33 Harmonic Indices.pdf
 
Numerical protection 2
Numerical protection 2Numerical protection 2
Numerical protection 2
 
Relay Setting Calculation For REF615/ REJ601
Relay Setting Calculation For REF615/ REJ601Relay Setting Calculation For REF615/ REJ601
Relay Setting Calculation For REF615/ REJ601
 
Short Circuit, Protective Device Coordination
Short Circuit, Protective Device CoordinationShort Circuit, Protective Device Coordination
Short Circuit, Protective Device Coordination
 
Unit 03 Protective relays
Unit  03 Protective relaysUnit  03 Protective relays
Unit 03 Protective relays
 
Measurement of high_voltage_and_high_currentunit_iv_full_version
Measurement of high_voltage_and_high_currentunit_iv_full_versionMeasurement of high_voltage_and_high_currentunit_iv_full_version
Measurement of high_voltage_and_high_currentunit_iv_full_version
 
Types of relay
Types of relayTypes of relay
Types of relay
 
Blackout Avoidance & Undervoltage Load Shedding
Blackout Avoidance & Undervoltage Load SheddingBlackout Avoidance & Undervoltage Load Shedding
Blackout Avoidance & Undervoltage Load Shedding
 
Unit 4 Automatic Generation Control
Unit 4 Automatic Generation ControlUnit 4 Automatic Generation Control
Unit 4 Automatic Generation Control
 
Fault Calculations
Fault CalculationsFault Calculations
Fault Calculations
 
NGR & Zig-Zag Transformer.pptx
NGR & Zig-Zag Transformer.pptxNGR & Zig-Zag Transformer.pptx
NGR & Zig-Zag Transformer.pptx
 
Transformers protection, an introduction
Transformers protection, an introductionTransformers protection, an introduction
Transformers protection, an introduction
 
Design of substation
Design of substationDesign of substation
Design of substation
 
FUNDAMENTALS OF POWER SYSTEM PROTECTION
FUNDAMENTALS OF POWER SYSTEM PROTECTIONFUNDAMENTALS OF POWER SYSTEM PROTECTION
FUNDAMENTALS OF POWER SYSTEM PROTECTION
 
3. INTRODUCTION TO PROTECTIVE RELAYING.pptx
3. INTRODUCTION TO PROTECTIVE RELAYING.pptx3. INTRODUCTION TO PROTECTIVE RELAYING.pptx
3. INTRODUCTION TO PROTECTIVE RELAYING.pptx
 

Similar to 21955068-High-Low-Impedance-BusBar-Protection.ppt

Power factor corrector
Power factor correctorPower factor corrector
Power factor correctorJoeChueng
 
PCB Layout guidelines.pdf
PCB Layout guidelines.pdfPCB Layout guidelines.pdf
PCB Layout guidelines.pdfssuserf36d4d1
 
Tai lieu tong quan antena
Tai lieu tong quan antenaTai lieu tong quan antena
Tai lieu tong quan antenaVan Kiem Nguyen
 
Applying Digital Isolators in Motor Control
Applying Digital Isolators in Motor ControlApplying Digital Isolators in Motor Control
Applying Digital Isolators in Motor ControlAnalog Devices, Inc.
 
Comnet C2US Data Sheet
Comnet C2US Data SheetComnet C2US Data Sheet
Comnet C2US Data SheetJMAC Supply
 
ComNet C2US Data Sheet
ComNet C2US Data SheetComNet C2US Data Sheet
ComNet C2US Data SheetJMAC Supply
 
ComNet FDC8TM1 Data Sheet
ComNet FDC8TM1 Data SheetComNet FDC8TM1 Data Sheet
ComNet FDC8TM1 Data SheetJMAC Supply
 
Protección de barra distribuido concentrada
Protección de barra distribuido concentradaProtección de barra distribuido concentrada
Protección de barra distribuido concentradaAniela29
 
Webinar: Fontes chaveadas digitais inteligentes com USB-PD
Webinar: Fontes chaveadas digitais inteligentes com USB-PDWebinar: Fontes chaveadas digitais inteligentes com USB-PD
Webinar: Fontes chaveadas digitais inteligentes com USB-PDEmbarcados
 
Dienhathe.com mcb-5 sx
Dienhathe.com mcb-5 sxDienhathe.com mcb-5 sx
Dienhathe.com mcb-5 sxDien Ha The
 
Next105 Ases Power Point Presentation Internal Final
Next105 Ases Power Point Presentation Internal FinalNext105 Ases Power Point Presentation Internal Final
Next105 Ases Power Point Presentation Internal FinalNextronex Inc
 
CYCLO CONVERTER USING THYRISTORS
CYCLO CONVERTER USING THYRISTORSCYCLO CONVERTER USING THYRISTORS
CYCLO CONVERTER USING THYRISTORSKartik Bolar
 
Faculty of Engineering and Technology.pptx
Faculty of Engineering and Technology.pptxFaculty of Engineering and Technology.pptx
Faculty of Engineering and Technology.pptxanshumaansingh310
 
ComNet FDC8ISOTM1 Data Sheet
ComNet FDC8ISOTM1 Data SheetComNet FDC8ISOTM1 Data Sheet
ComNet FDC8ISOTM1 Data SheetJMAC Supply
 
Ericsson TN Cards in Details
Ericsson TN Cards in DetailsEricsson TN Cards in Details
Ericsson TN Cards in Detailsibrahimnabil17
 
Smart metering and conditional access control of electrical energy
Smart metering and conditional access control of electrical energySmart metering and conditional access control of electrical energy
Smart metering and conditional access control of electrical energykannansenthilkumar
 

Similar to 21955068-High-Low-Impedance-BusBar-Protection.ppt (20)

Power factor corrector
Power factor correctorPower factor corrector
Power factor corrector
 
PCB Layout guidelines.pdf
PCB Layout guidelines.pdfPCB Layout guidelines.pdf
PCB Layout guidelines.pdf
 
Tai lieu tong quan antena
Tai lieu tong quan antenaTai lieu tong quan antena
Tai lieu tong quan antena
 
Applying Digital Isolators in Motor Control
Applying Digital Isolators in Motor ControlApplying Digital Isolators in Motor Control
Applying Digital Isolators in Motor Control
 
Comnet C2US Data Sheet
Comnet C2US Data SheetComnet C2US Data Sheet
Comnet C2US Data Sheet
 
ComNet C2US Data Sheet
ComNet C2US Data SheetComNet C2US Data Sheet
ComNet C2US Data Sheet
 
ComNet FDC8TM1 Data Sheet
ComNet FDC8TM1 Data SheetComNet FDC8TM1 Data Sheet
ComNet FDC8TM1 Data Sheet
 
Protección de barra distribuido concentrada
Protección de barra distribuido concentradaProtección de barra distribuido concentrada
Protección de barra distribuido concentrada
 
Drive Training - Copy.pptx
Drive Training - Copy.pptxDrive Training - Copy.pptx
Drive Training - Copy.pptx
 
Webinar: Fontes chaveadas digitais inteligentes com USB-PD
Webinar: Fontes chaveadas digitais inteligentes com USB-PDWebinar: Fontes chaveadas digitais inteligentes com USB-PD
Webinar: Fontes chaveadas digitais inteligentes com USB-PD
 
Dienhathe.com mcb-5 sx
Dienhathe.com mcb-5 sxDienhathe.com mcb-5 sx
Dienhathe.com mcb-5 sx
 
Next105 Ases Power Point Presentation Internal Final
Next105 Ases Power Point Presentation Internal FinalNext105 Ases Power Point Presentation Internal Final
Next105 Ases Power Point Presentation Internal Final
 
CYCLO CONVERTER USING THYRISTORS
CYCLO CONVERTER USING THYRISTORSCYCLO CONVERTER USING THYRISTORS
CYCLO CONVERTER USING THYRISTORS
 
Faculty of Engineering and Technology.pptx
Faculty of Engineering and Technology.pptxFaculty of Engineering and Technology.pptx
Faculty of Engineering and Technology.pptx
 
ComNet FDC8ISOTM1 Data Sheet
ComNet FDC8ISOTM1 Data SheetComNet FDC8ISOTM1 Data Sheet
ComNet FDC8ISOTM1 Data Sheet
 
07 - ELCB - Fuji Electric
07 - ELCB - Fuji Electric07 - ELCB - Fuji Electric
07 - ELCB - Fuji Electric
 
5 FINAL PROJECT REPORT
5 FINAL PROJECT REPORT5 FINAL PROJECT REPORT
5 FINAL PROJECT REPORT
 
Ericsson TN Cards in Details
Ericsson TN Cards in DetailsEricsson TN Cards in Details
Ericsson TN Cards in Details
 
Uno 2.0-2.5
Uno 2.0-2.5Uno 2.0-2.5
Uno 2.0-2.5
 
Smart metering and conditional access control of electrical energy
Smart metering and conditional access control of electrical energySmart metering and conditional access control of electrical energy
Smart metering and conditional access control of electrical energy
 

More from Thien Phan Bản

Breaker_Failure_Protection.ppt
Breaker_Failure_Protection.pptBreaker_Failure_Protection.ppt
Breaker_Failure_Protection.pptThien Phan Bản
 
'docslide.us_hv-testing.ppt
'docslide.us_hv-testing.ppt'docslide.us_hv-testing.ppt
'docslide.us_hv-testing.pptThien Phan Bản
 
megger-150210211712-conversion-gate01.ppt
megger-150210211712-conversion-gate01.pptmegger-150210211712-conversion-gate01.ppt
megger-150210211712-conversion-gate01.pptThien Phan Bản
 
Breaker_Failure_Protection.ppt
Breaker_Failure_Protection.pptBreaker_Failure_Protection.ppt
Breaker_Failure_Protection.pptThien Phan Bản
 
basic-partial-discharge.pdf
basic-partial-discharge.pdfbasic-partial-discharge.pdf
basic-partial-discharge.pdfThien Phan Bản
 
FUNDAMENTALS_OF_BUS_PROTECTION_Handouts.pdf
FUNDAMENTALS_OF_BUS_PROTECTION_Handouts.pdfFUNDAMENTALS_OF_BUS_PROTECTION_Handouts.pdf
FUNDAMENTALS_OF_BUS_PROTECTION_Handouts.pdfThien Phan Bản
 
High_Low_Impedance_BusBar_Protection.ppt
High_Low_Impedance_BusBar_Protection.pptHigh_Low_Impedance_BusBar_Protection.ppt
High_Low_Impedance_BusBar_Protection.pptThien Phan Bản
 
basicprotectionandrelayingbysomaliajaldas-121126030037-phpapp01.ppt
basicprotectionandrelayingbysomaliajaldas-121126030037-phpapp01.pptbasicprotectionandrelayingbysomaliajaldas-121126030037-phpapp01.ppt
basicprotectionandrelayingbysomaliajaldas-121126030037-phpapp01.pptThien Phan Bản
 
47526172-DIFFERENTIAL-PROTECTION-8.pptx
47526172-DIFFERENTIAL-PROTECTION-8.pptx47526172-DIFFERENTIAL-PROTECTION-8.pptx
47526172-DIFFERENTIAL-PROTECTION-8.pptxThien Phan Bản
 
14009762-ABB-Protection-Book.pdf
14009762-ABB-Protection-Book.pdf14009762-ABB-Protection-Book.pdf
14009762-ABB-Protection-Book.pdfThien Phan Bản
 
ppt100-110425022440-phpapp02.ppt
ppt100-110425022440-phpapp02.pptppt100-110425022440-phpapp02.ppt
ppt100-110425022440-phpapp02.pptThien Phan Bản
 
basicprotectionandrelayingbysomaliajaldas-121126030037-phpapp01.ppt
basicprotectionandrelayingbysomaliajaldas-121126030037-phpapp01.pptbasicprotectionandrelayingbysomaliajaldas-121126030037-phpapp01.ppt
basicprotectionandrelayingbysomaliajaldas-121126030037-phpapp01.pptThien Phan Bản
 
Basic_Protection_Theory_2013_BW.pdf
Basic_Protection_Theory_2013_BW.pdfBasic_Protection_Theory_2013_BW.pdf
Basic_Protection_Theory_2013_BW.pdfThien Phan Bản
 
17648889-Introduction-to-Power-System-Protection-Relays.pdf
17648889-Introduction-to-Power-System-Protection-Relays.pdf17648889-Introduction-to-Power-System-Protection-Relays.pdf
17648889-Introduction-to-Power-System-Protection-Relays.pdfThien Phan Bản
 
pptpdf-131117235616-phpapp02.pdf
pptpdf-131117235616-phpapp02.pdfpptpdf-131117235616-phpapp02.pdf
pptpdf-131117235616-phpapp02.pdfThien Phan Bản
 
protectionprimer-121228115656-phpapp01.ppt
protectionprimer-121228115656-phpapp01.pptprotectionprimer-121228115656-phpapp01.ppt
protectionprimer-121228115656-phpapp01.pptThien Phan Bản
 

More from Thien Phan Bản (20)

Breaker_Failure_Protection.ppt
Breaker_Failure_Protection.pptBreaker_Failure_Protection.ppt
Breaker_Failure_Protection.ppt
 
75181713.pdf
75181713.pdf75181713.pdf
75181713.pdf
 
'docslide.us_hv-testing.ppt
'docslide.us_hv-testing.ppt'docslide.us_hv-testing.ppt
'docslide.us_hv-testing.ppt
 
megger-150210211712-conversion-gate01.ppt
megger-150210211712-conversion-gate01.pptmegger-150210211712-conversion-gate01.ppt
megger-150210211712-conversion-gate01.ppt
 
Breaker_Failure_Protection.ppt
Breaker_Failure_Protection.pptBreaker_Failure_Protection.ppt
Breaker_Failure_Protection.ppt
 
basic-partial-discharge.pdf
basic-partial-discharge.pdfbasic-partial-discharge.pdf
basic-partial-discharge.pdf
 
FUNDAMENTALS_OF_BUS_PROTECTION_Handouts.pdf
FUNDAMENTALS_OF_BUS_PROTECTION_Handouts.pdfFUNDAMENTALS_OF_BUS_PROTECTION_Handouts.pdf
FUNDAMENTALS_OF_BUS_PROTECTION_Handouts.pdf
 
High_Low_Impedance_BusBar_Protection.ppt
High_Low_Impedance_BusBar_Protection.pptHigh_Low_Impedance_BusBar_Protection.ppt
High_Low_Impedance_BusBar_Protection.ppt
 
basicprotectionandrelayingbysomaliajaldas-121126030037-phpapp01.ppt
basicprotectionandrelayingbysomaliajaldas-121126030037-phpapp01.pptbasicprotectionandrelayingbysomaliajaldas-121126030037-phpapp01.ppt
basicprotectionandrelayingbysomaliajaldas-121126030037-phpapp01.ppt
 
11042019104945.pdf
11042019104945.pdf11042019104945.pdf
11042019104945.pdf
 
47526172-DIFFERENTIAL-PROTECTION-8.pptx
47526172-DIFFERENTIAL-PROTECTION-8.pptx47526172-DIFFERENTIAL-PROTECTION-8.pptx
47526172-DIFFERENTIAL-PROTECTION-8.pptx
 
14009762-ABB-Protection-Book.pdf
14009762-ABB-Protection-Book.pdf14009762-ABB-Protection-Book.pdf
14009762-ABB-Protection-Book.pdf
 
ppt100-110425022440-phpapp02.ppt
ppt100-110425022440-phpapp02.pptppt100-110425022440-phpapp02.ppt
ppt100-110425022440-phpapp02.ppt
 
chuong_1.ppt
chuong_1.pptchuong_1.ppt
chuong_1.ppt
 
basicprotectionandrelayingbysomaliajaldas-121126030037-phpapp01.ppt
basicprotectionandrelayingbysomaliajaldas-121126030037-phpapp01.pptbasicprotectionandrelayingbysomaliajaldas-121126030037-phpapp01.ppt
basicprotectionandrelayingbysomaliajaldas-121126030037-phpapp01.ppt
 
Basic_Protection_Theory_2013_BW.pdf
Basic_Protection_Theory_2013_BW.pdfBasic_Protection_Theory_2013_BW.pdf
Basic_Protection_Theory_2013_BW.pdf
 
17649136-Relays.pdf
17649136-Relays.pdf17649136-Relays.pdf
17649136-Relays.pdf
 
17648889-Introduction-to-Power-System-Protection-Relays.pdf
17648889-Introduction-to-Power-System-Protection-Relays.pdf17648889-Introduction-to-Power-System-Protection-Relays.pdf
17648889-Introduction-to-Power-System-Protection-Relays.pdf
 
pptpdf-131117235616-phpapp02.pdf
pptpdf-131117235616-phpapp02.pdfpptpdf-131117235616-phpapp02.pdf
pptpdf-131117235616-phpapp02.pdf
 
protectionprimer-121228115656-phpapp01.ppt
protectionprimer-121228115656-phpapp01.pptprotectionprimer-121228115656-phpapp01.ppt
protectionprimer-121228115656-phpapp01.ppt
 

Recently uploaded

Call Girls Delhi {Jodhpur} 9711199012 high profile service
Call Girls Delhi {Jodhpur} 9711199012 high profile serviceCall Girls Delhi {Jodhpur} 9711199012 high profile service
Call Girls Delhi {Jodhpur} 9711199012 high profile servicerehmti665
 
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130Suhani Kapoor
 
Heart Disease Prediction using machine learning.pptx
Heart Disease Prediction using machine learning.pptxHeart Disease Prediction using machine learning.pptx
Heart Disease Prediction using machine learning.pptxPoojaBan
 
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...Soham Mondal
 
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...ranjana rawat
 
Artificial-Intelligence-in-Electronics (K).pptx
Artificial-Intelligence-in-Electronics (K).pptxArtificial-Intelligence-in-Electronics (K).pptx
Artificial-Intelligence-in-Electronics (K).pptxbritheesh05
 
HARMONY IN THE NATURE AND EXISTENCE - Unit-IV
HARMONY IN THE NATURE AND EXISTENCE - Unit-IVHARMONY IN THE NATURE AND EXISTENCE - Unit-IV
HARMONY IN THE NATURE AND EXISTENCE - Unit-IVRajaP95
 
CCS355 Neural Network & Deep Learning UNIT III notes and Question bank .pdf
CCS355 Neural Network & Deep Learning UNIT III notes and Question bank .pdfCCS355 Neural Network & Deep Learning UNIT III notes and Question bank .pdf
CCS355 Neural Network & Deep Learning UNIT III notes and Question bank .pdfAsst.prof M.Gokilavani
 
Past, Present and Future of Generative AI
Past, Present and Future of Generative AIPast, Present and Future of Generative AI
Past, Present and Future of Generative AIabhishek36461
 
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130Suhani Kapoor
 
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...Dr.Costas Sachpazis
 
VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...
VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...
VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...VICTOR MAESTRE RAMIREZ
 
chaitra-1.pptx fake news detection using machine learning
chaitra-1.pptx  fake news detection using machine learningchaitra-1.pptx  fake news detection using machine learning
chaitra-1.pptx fake news detection using machine learningmisbanausheenparvam
 
Internship report on mechanical engineering
Internship report on mechanical engineeringInternship report on mechanical engineering
Internship report on mechanical engineeringmalavadedarshan25
 
CCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdf
CCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdfCCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdf
CCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdfAsst.prof M.Gokilavani
 
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝soniya singh
 
Current Transformer Drawing and GTP for MSETCL
Current Transformer Drawing and GTP for MSETCLCurrent Transformer Drawing and GTP for MSETCL
Current Transformer Drawing and GTP for MSETCLDeelipZope
 
What are the advantages and disadvantages of membrane structures.pptx
What are the advantages and disadvantages of membrane structures.pptxWhat are the advantages and disadvantages of membrane structures.pptx
What are the advantages and disadvantages of membrane structures.pptxwendy cai
 

Recently uploaded (20)

Call Girls Delhi {Jodhpur} 9711199012 high profile service
Call Girls Delhi {Jodhpur} 9711199012 high profile serviceCall Girls Delhi {Jodhpur} 9711199012 high profile service
Call Girls Delhi {Jodhpur} 9711199012 high profile service
 
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130
 
Heart Disease Prediction using machine learning.pptx
Heart Disease Prediction using machine learning.pptxHeart Disease Prediction using machine learning.pptx
Heart Disease Prediction using machine learning.pptx
 
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
 
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
 
Artificial-Intelligence-in-Electronics (K).pptx
Artificial-Intelligence-in-Electronics (K).pptxArtificial-Intelligence-in-Electronics (K).pptx
Artificial-Intelligence-in-Electronics (K).pptx
 
Exploring_Network_Security_with_JA3_by_Rakesh Seal.pptx
Exploring_Network_Security_with_JA3_by_Rakesh Seal.pptxExploring_Network_Security_with_JA3_by_Rakesh Seal.pptx
Exploring_Network_Security_with_JA3_by_Rakesh Seal.pptx
 
HARMONY IN THE NATURE AND EXISTENCE - Unit-IV
HARMONY IN THE NATURE AND EXISTENCE - Unit-IVHARMONY IN THE NATURE AND EXISTENCE - Unit-IV
HARMONY IN THE NATURE AND EXISTENCE - Unit-IV
 
CCS355 Neural Network & Deep Learning UNIT III notes and Question bank .pdf
CCS355 Neural Network & Deep Learning UNIT III notes and Question bank .pdfCCS355 Neural Network & Deep Learning UNIT III notes and Question bank .pdf
CCS355 Neural Network & Deep Learning UNIT III notes and Question bank .pdf
 
Past, Present and Future of Generative AI
Past, Present and Future of Generative AIPast, Present and Future of Generative AI
Past, Present and Future of Generative AI
 
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
 
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
 
VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...
VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...
VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...
 
chaitra-1.pptx fake news detection using machine learning
chaitra-1.pptx  fake news detection using machine learningchaitra-1.pptx  fake news detection using machine learning
chaitra-1.pptx fake news detection using machine learning
 
Internship report on mechanical engineering
Internship report on mechanical engineeringInternship report on mechanical engineering
Internship report on mechanical engineering
 
CCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdf
CCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdfCCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdf
CCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdf
 
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝
 
young call girls in Rajiv Chowk🔝 9953056974 🔝 Delhi escort Service
young call girls in Rajiv Chowk🔝 9953056974 🔝 Delhi escort Serviceyoung call girls in Rajiv Chowk🔝 9953056974 🔝 Delhi escort Service
young call girls in Rajiv Chowk🔝 9953056974 🔝 Delhi escort Service
 
Current Transformer Drawing and GTP for MSETCL
Current Transformer Drawing and GTP for MSETCLCurrent Transformer Drawing and GTP for MSETCL
Current Transformer Drawing and GTP for MSETCL
 
What are the advantages and disadvantages of membrane structures.pptx
What are the advantages and disadvantages of membrane structures.pptxWhat are the advantages and disadvantages of membrane structures.pptx
What are the advantages and disadvantages of membrane structures.pptx
 

21955068-High-Low-Impedance-BusBar-Protection.ppt

  • 1. Fundamentals of Bus Bar Protection GE Multilin
  • 2. 2 GE Consumer & Industrial Multilin 29-Oct-22 Outline • Bus arrangements • Bus components • Bus protection techniques • CT Saturation • Application Considerations:  High impedance bus differential relaying  Low impedance bus differential relaying  Special topics
  • 3. 3 GE Consumer & Industrial Multilin 29-Oct-22 1 2 3 n-1 n ZONE 1 - - - - • Distribution and lower transmission voltage levels • No operating flexibility • Fault on the bus trips all circuit breakers Single bus - single breaker
  • 4. 4 GE Consumer & Industrial Multilin 29-Oct-22 ZONE 1 ZONE 2 • Distribution and lower transmission voltage levels • Limited operating flexibility Multiple bus sections - single breaker with bus tie
  • 5. 5 GE Consumer & Industrial Multilin 29-Oct-22 ZONE 1 ZONE 2 • Transmission and distribution voltage levels • Breaker maintenance without circuit removal • Fault on a bus disconnects only the circuits being connected to that bus Double bus - single breaker with bus tie
  • 6. 6 GE Consumer & Industrial Multilin 29-Oct-22 ZONE 1 MAIN BUS TRANFER BUS • Increased operating flexibility • A bus fault requires tripping all breakers • Transfer bus for breaker maintenance Main and transfer buses
  • 7. 7 GE Consumer & Industrial Multilin 29-Oct-22 ZONE 1 ZONE 2 • Very high operating flexibility • Transfer bus for breaker maintenance Double bus – single breaker w/ transfer bus
  • 8. 8 GE Consumer & Industrial Multilin 29-Oct-22 ZONE 1 ZONE 2 • High operating flexibility • Line protection covers bus section between two CTs • Fault on a bus does not disturb the power to circuits Double bus - double breaker
  • 9. 9 GE Consumer & Industrial Multilin 29-Oct-22 ZONE 1 ZONE 2 • Used on higher voltage levels • More operating flexibility • Requires more breakers • Middle bus sections covered by line or other equipment protection Breaker-and-a-half bus
  • 10. 10 GE Consumer & Industrial Multilin 29-Oct-22 • Higher voltage levels • High operating flexibility with minimum breakers • Separate bus protection not required at line positions B1 B2 TB1 L1 L2 L3 L4 TB1 Ring bus
  • 11. 11 GE Consumer & Industrial Multilin 29-Oct-22 Bus components breakers SF6, EHV & HV - Synchropuff Low Voltage circuit breakers BUS 2 CB 1 BUS 1 ISO 1 ISO 2 ISO 3 BYPASS
  • 12. 12 GE Consumer & Industrial Multilin 29-Oct-22 - + F1a F1c Contact Input F1a On Contact Input F1c On F1b ISOLATOR 1 ISOLATOR 1 OPEN 7B 7A BUS 1 - + F1a F1c Contact Input F1a On Contact Input F1c On F1b ISOLATOR 1 ISOLATOR 1 CLOSED 7B 7A BUS 1 Disconnect switches & auxiliary contacts BUS 2 CB 1 BUS 1 ISO 1 ISO 2 ISO 3 BYPASS
  • 13. 13 GE Consumer & Industrial Multilin 29-Oct-22 BUS 2 CB 1 BUS 1 ISO 1 ISO 2 ISO 3 BYPASS Current Transformers Oil insulated current transformer (35kV up to 800kV) Gas (SF6) insulated current transformer Bushing type (medium voltage switchgear)
  • 14. 14 GE Consumer & Industrial Multilin 29-Oct-22 Protection Requirements High bus fault currents due to large number of circuits connected: • CT saturation often becomes a problem as CTs may not be sufficiently rated for worst fault condition case • large dynamic forces associated with bus faults require fast clearing times in order to reduce equipment damage False trip by bus protection may create serious problems: • service interruption to a large number of circuits (distribution and sub- transmission voltage levels) • system-wide stability problems (transmission voltage levels) With both dependability and security important, preference is always given to security
  • 15. 15 GE Consumer & Industrial Multilin 29-Oct-22 Bus Protection Techniques • Interlocking schemes • Overcurrent (“unrestrained” or “unbiased”) differential • Overcurrent percent (“restrained” or “biased”) differential • Linear couplers • High-impedance bus differential schemes • Low-impedance bus differential schemes
  • 16. 16 GE Consumer & Industrial Multilin 29-Oct-22 Interlocking Schemes • Blocking scheme typically used • Short coordination time required • Care must be taken with possible saturation of feeder CTs • Blocking signal could be sent over communications ports (peer-to-peer) • This technique is limited to simple one-incomer distribution buses 50 50 50 50 50 50 BLOCK
  • 17. 17 GE Consumer & Industrial Multilin 29-Oct-22 Overcurrent (unrestrained) Differential • Differential signal formed by summation of all currents feeding the bus • CT ratio matching may be required • On external faults, saturated CTs yield spurious differential current • Time delay used to cope with CT saturation • Instantaneous differential OC function useful on integrated microprocessor-based relays 51
  • 18. 18 GE Consumer & Industrial Multilin 29-Oct-22 59 Linear Couplers ZC = 2  – 20  - typical coil impedance (5V per 1000Amps => 0.005 @ 60Hz ) If = 8000 A 40 V 10 V 10 V 0 V 20 V 2000 A 2000 A 4000 A 0 A 0 V External Fault
  • 19. 19 GE Consumer & Industrial Multilin 29-Oct-22 59 Linear Couplers Esec= Iprim*Xm - secondary voltage on relay terminals IR= Iprim*Xm /(ZR+ZC) – minimum operating current where, Iprim – primary current in each circuit Xm – liner coupler mutual reactance (5V per 1000Amps => 0.005 @ 60Hz ) ZR – relay tap impedance ZC – sum of all linear coupler self impedances If = 8000 A 0 A 0 V 10 V 10 V 0 V 20 V 40 V 2000 A 2000 A 4000 A 0 A Internal Bus Fault
  • 20. 20 GE Consumer & Industrial Multilin 29-Oct-22 • Fast, secure and proven • Require dedicated air gap CTs, which may not be used for any other protection • Cannot be easily applied to reconfigurable buses • The scheme uses a simple voltage detector – it does not provide benefits of a microprocessor-based relay (e.g. oscillography, breaker failure protection, other functions) Linear Couplers
  • 21. 21 GE Consumer & Industrial Multilin 29-Oct-22 High Impedance Differential • Operating signal created by connecting all CT secondaries in parallel o CTs must all have the same ratio o Must have dedicated CTs • Overvoltage element operates on voltage developed across resistor connected in secondary circuit o Requires varistors or AC shorting relays to limit energy during faults • Accuracy dependent on secondary circuit resistance o Usually requires larger CT cables to reduce errors  higher cost Cannot easily be applied to reconfigurable buses and offers no advanced functionality 59
  • 22. 22 GE Consumer & Industrial Multilin 29-Oct-22 Percent Differential • Percent characteristic used to cope with CT saturation and other errors • Restraining signal can be formed in a number of ways • No dedicated CTs needed • Used for protection of re- configurable buses possible 51 87 n DIF I I I I     ... 2 1 n RES I I I I     ... 2 1   n RES I I I I ..., , , max 2 1 
  • 23. 23 GE Consumer & Industrial Multilin 29-Oct-22 Low Impedance Percent Differential • Individual currents sampled by protection and summated digitally o CT ratio matching done internally (no auxiliary CTs) o Dedicated CTs not necessary • Additional algorithms improve security of percent differential characteristic during CT saturation • Dynamic bus replica allows application to reconfigurable buses o Done digitally with logic to add/remove current inputs from differential computation o Switching of CT secondary circuits not required • Low secondary burdens • Additional functionality available o Digital oscillography and monitoring of each circuit connected to bus zone o Time-stamped event recording o Breaker failure protection
  • 24. 24 GE Consumer & Industrial Multilin 29-Oct-22 Digital Differential Algorithm Goals • Improve the main differential algorithm operation o Better filtering o Faster response o Better restraint techniques o Switching transient blocking • Provide dynamic bus replica for reconfigurable bus bars • Dependably detect CT saturation in a fast and reliable manner, especially for external faults • Implement additional security to the main differential algorithm to prevent incorrect operation o External faults with CT saturation o CT secondary circuit trouble (e.g. short circuits)
  • 25. 25 GE Consumer & Industrial Multilin 29-Oct-22 Low Impedance Differential (Distributed) • Data Acquisition Units (DAUs) installed in bays • Central Processing Unit (CPU) processes all data from DAUs • Communications between DAUs and CPU over fiber using proprietary protocol • Sampling synchronisation between DAUs is required • Perceived less reliable (more hardware needed) • Difficult to apply in retrofit applications 52 DAU 52 DAU 52 DAU CU copper fiber
  • 26. 26 GE Consumer & Industrial Multilin 29-Oct-22 Low Impedance Differential (Centralized) • All currents applied to a single central processor • No communications, external sampling synchronisation necessary • Perceived more reliable (less hardware needed) • Well suited to both new and retrofit applications. 52 52 52 CU copper
  • 27. 27 GE Consumer & Industrial Multilin 29-Oct-22 CT Saturation
  • 28. 28 GE Consumer & Industrial Multilin 29-Oct-22 CT Saturation Concepts • CT saturation depends on a number of factors o Physical CT characteristics (size, rating, winding resistance, saturation voltage) o Connected CT secondary burden (wires + relays) o Primary current magnitude, DC offset (system X/R) o Residual flux in CT core • Actual CT secondary currents may not behave in the same manner as the ratio (scaled primary) current during faults • End result is spurious differential current appearing in the summation of the secondary currents which may cause differential elements to operate if additional security is not applied
  • 29. 29 GE Consumer & Industrial Multilin 29-Oct-22 CT Saturation Ratio Current CT Current Ratio Current CT Current No DC Offset • Waveform remains fairly symmetrical With DC Offset • Waveform starts off being asymmetrical, then symmetrical in steady state
  • 30. 30 GE Consumer & Industrial Multilin 29-Oct-22 External Fault & Ideal CTs • Fault starts at t0 • Steady-state fault conditions occur at t1 differential restraining t0 t1 Ideal CTs have no saturation or mismatch errors thus produce no differential current
  • 31. 31 GE Consumer & Industrial Multilin 29-Oct-22 External Fault & Actual CTs • Fault starts at t0 • Steady-state fault conditions occur at t1 differential restraining t0 t1 Actual CTs do introduce errors, producing some differential current (without CT saturation)
  • 32. 32 GE Consumer & Industrial Multilin 29-Oct-22 External Fault with CT Saturation • Fault starts at t0, CT begins to saturate at t1 • CT fully saturated at t2 differential restraining t0 t1 t2 CT saturation causes increasing differential current that may enter the differential element operate region.
  • 33. 33 GE Consumer & Industrial Multilin 29-Oct-22 Some Methods of Securing Bus Differential • Block the bus differential for a period of time (intentional delay) o Increases security as bus zone will not trip when CT saturation is present o Prevents high-speed clearance for internal faults with CT saturation or evolving faults • Change settings of the percent differential characteristic (usually Slope 2) o Improves security of differential element by increasing the amount of spurious differential current needed to incorrectly trip o Difficult to explicitly develop settings (Is 60% slope enough? Should it be 75%?) • Apply directional (phase comparison) supervision o Improves security by requiring all currents flow into the bus zone before asserting the differential element o Easy to implement and test o Stable even under severe CT saturation during external faults
  • 34. 34 GE Consumer & Industrial Multilin 29-Oct-22 High-Impedance Bus Differential Considerations
  • 35. 35 GE Consumer & Industrial Multilin 29-Oct-22 High Impedance Voltage-operated Relay External Fault • 59 element set above max possible voltage developed across relay during external fault causing worst case CT saturation • For internal faults, extremely high voltages (well above 59 element pickup) will develop across relay
  • 36. 36 GE Consumer & Industrial Multilin 29-Oct-22 High Impedance Voltage Operated Relay Ratio matching with Multi-ratio CTs • Application of high impedance differential relays with CTs of different ratios but ratio matching taps is possible, but could lead to voltage magnification. • Voltage developed across full winding of tapped CT does not exceed CT rating, terminal blocks, etc.
  • 37. 37 GE Consumer & Industrial Multilin 29-Oct-22 High Impedance Voltage Operated Relay Ratio matching with Multi-ratio CTs • Use of auxiliary CTs to obtain correct ratio matching is also possible, but these CTs must be able to deliver enough voltage necessary to produce relay operation for internal faults.
  • 38. 38 GE Consumer & Industrial Multilin 29-Oct-22 Electromechanical High Impedance Bus Differential Relays • Single phase relays • High-speed • High impedance voltage sensing • High seismic IOC unit
  • 39. 39 GE Consumer & Industrial Multilin 29-Oct-22 Operating time: 20 – 30ms @ I > 1.5xPKP P -based High-Impedance Bus Differential Protection Relays
  • 40. 40 GE Consumer & Industrial Multilin 29-Oct-22 RST = 2000 - stabilizing resistor to limit the current through the relay, and force it to the lower impedance CT windings. MOV – Metal Oxide Varistor to limit the voltage to 1900 Volts 86 – latching contact preventing the resistors from overheating after the fault is detected High Impedance Module for Digital Relays
  • 41. 41 GE Consumer & Industrial Multilin 29-Oct-22 High-Impedance Module + Overcurrent Relay
  • 42. 42 GE Consumer & Industrial Multilin 29-Oct-22 • Fast, secure and proven • Requires dedicated CTs, preferably with the same CT ratio and using full tap • Can be applied to small buses • Depending on bus internal and external fault currents, high impedance bus diff may not provide adequate settings for both sensitivity and security • Cannot be easily applied to reconfigurable buses • Require voltage limiting varistor capable of absorbing significant energy • May require auxiliary CTs • Do not provide full benefits of microprocessor-based relay system (e.g. metering, monitoring, oscillography, etc.) High Impedance Bus Protection - Summary
  • 43. 43 GE Consumer & Industrial Multilin 29-Oct-22 Low-Impedance Bus Differential Considerations
  • 44. 44 GE Consumer & Industrial Multilin 29-Oct-22 P-based Low-Impedance Relays • No need for dedicated CTs • Internal CT ratio mismatch compensation • Advanced algorithms supplement percent differential protection function making the relay very secure • Dynamic bus replica (bus image) principle is used in protection of reconfigurable bus bars, eliminating the need for switching physically secondary current circuits • Integrated Breaker Failure (BF) function can provide optimal tripping strategy depending on the actual configuration of a bus bar
  • 45. 45 GE Consumer & Industrial Multilin 29-Oct-22 • Up to 24 Current Inputs • 4 Zones • Zone 1 = Phase A • Zone 2 = Phase B • Zone 3 = Phase C • Zone 4 = Not used • Different CT Ratio Capability for Each Circuit • Largest CT Primary is Base in Relay 2-8 Circuit Applications Small Bus Applications
  • 46. 46 GE Consumer & Industrial Multilin 29-Oct-22 • Relay 1 - 24 Current Inputs • 4 Zones • Zone 1 = Phase A (12 currents) • Zone 2 = Phase B (12 currents) • Zone 3 = Not used • Zone 4 = Not used CB 12 CB 11 • Different CT Ratio Capability for Each Circuit • Largest CT Primary is Base in Relay • Relay 2 - 24 Current Inputs • 4 Zones • Zone 1 = Not used • Zone 2 = Not used • Zone 3 = Phase C (12 currents) • Zone 4 = Not used 9-12 Circuit Applications Medium to Large Bus Applications
  • 47. 47 GE Consumer & Industrial Multilin 29-Oct-22 Large Bus Applications 87B phase A 87B phase B 87B phase C Logic relay (switch status, optional BF)
  • 48. 48 GE Consumer & Industrial Multilin 29-Oct-22 Large Bus Applications For buses with up to 24 circuits
  • 49. 49 GE Consumer & Industrial Multilin 29-Oct-22 Summing External Currents Not Recommended for Low-Z 87B relays • Relay becomes combination of restrained and unrestrained elements •In order to parallel CTs: • CT performance must be closely matched o Any errors will appear as differential currents • Associated feeders must be radial o No backfeeds possible • Pickup setting must be raised to accommodate any errors CT-1 CT-2 CT-3 CT-4 I 3 = 0 I 2 = 0 I 1 = Error IDIFF = Error IREST = Error Maloperation if Error > PICKUP
  • 50. 50 GE Consumer & Industrial Multilin 29-Oct-22 Definitions of Restraint Signals “maximum of” “geometrical average” “scaled sum of” “sum of” n R i i i i i      ... 3 2 1   n R i i i i n i      ... 1 3 2 1   n R i i i i Max i ,..., , , 3 2 1  n n R i i i i i      ... 3 2 1
  • 51. 51 GE Consumer & Industrial Multilin 29-Oct-22 “Sum Of” vs. “Max Of” Restraint Methods “Sum Of” Approach • More restraint on external faults; less sensitive for internal faults • “Scaled-Sum Of” approach takes into account number of connected circuits and may increase sensitivity • Breakpoint settings for the percent differential characteristic more difficult to set “Max Of” Approach • Less restraint on external faults; more sensitive for internal faults • Breakpoint settings for the percent differential characteristic easier to set • Better handles situation where one CT may saturate completely (99% slope settings possible)
  • 52. 52 GE Consumer & Industrial Multilin 29-Oct-22 Bus Differential Adaptive Approach differential restraining Region 1 (low differential currents) Region 2 (high differential currents)
  • 53. 53 GE Consumer & Industrial Multilin 29-Oct-22 Bus Differential Adaptive Logic Diagram DIFL DIR SAT DIFH OR AND OR 87B BIASED OP AND
  • 54. 54 GE Consumer & Industrial Multilin 29-Oct-22 Phase Comparison Principle • Internal Faults: All fault (“large”) currents are approximately in phase. • External Faults: One fault (“large”) current will be out of phase • No Voltages are required or needed Secondary Current of Faulted Circuit (Severe CT Saturation)
  • 55. 55 GE Consumer & Industrial Multilin 29-Oct-22 Phase Comparison Principle Continued… BLOCK OPERATE BLOCK          p D p I I I real          p D p I I I imag Ip ID - Ip External Fault Conditions OPERATE BLOCK BLOCK          p D p I I I real          p D p I I I imag Ip ID - Ip Internal Fault Conditions OPERATE OPERATE
  • 56. 56 GE Consumer & Industrial Multilin 29-Oct-22 CT Saturation • Fault starts at t0, CT begins to saturate at t1 • CT fully saturated at t2 differential restraining t0 t1 t2
  • 57. 57 GE Consumer & Industrial Multilin 29-Oct-22 CT Saturation Detector State Machine NORMAL SAT := 0 EXTERNAL FAULT SAT := 1 EXTERNAL FAULT & CT SATURATION SAT := 1 The differential characteristic entered The differential- restraining trajectory out of the differential characteristic for certain period of time saturation condition The differential current below the first slope for certain period of time
  • 58. 58 GE Consumer & Industrial Multilin 29-Oct-22 CT Saturation Detector Operating Principles • The 87B SAT flag WILL NOT be set during internal faults, regardless of whether or not any of the CTs saturate. • The 87B SAT flag WILL be set during external faults, regardless of whether or not any of the CTs saturate. • By design, the 87B SAT flag WILL force the relay to use the additional 87B DIR phase comparison for Region 2 The Saturation Detector WILL NOT Block the Operation of the Differential Element – it will only Force 2-out-of-2 Operation
  • 59. 59 GE Consumer & Industrial Multilin 29-Oct-22 CT Saturation Detector - Examples • The oscillography records on the next two slides were captured from a B30 relay under test on a real-time digital power system simulator • First slide shows an external fault with deep CT saturation (~1.5 msec of good CT performance) o SAT saturation detector flag asserts prior to BIASED PKP bus differential pickup o DIR directional flag does not assert (one current flows out of zone), so even though bus differential picks up, no trip results • Second slide shows an internal fault with mild CT saturation o BIASED PKP and BIASED OP both assert before DIR asserts o CT saturation does not block bus differential • More examples available (COMTRADE files) upon request
  • 60. 60 GE Consumer & Industrial Multilin 29-Oct-22 The bus differential protection element picks up due to heavy CT saturation The CT saturation flag is set safely before the pickup flag The directional flag is not set The element does not maloperate Despite heavy CT saturation the external fault current is seen in the opposite direction CT Saturation Example – External Fault 0.06 0.07 0.08 0.09 0.1 0.11 0.12 -200 -150 -100 -50 0 50 100 150 200 time, sec current, A ~1 ms
  • 61. 61 GE Consumer & Industrial Multilin 29-Oct-22 The bus differential protection element picks up The saturation flag is not set - no directional decision required The element operates in 10ms The directional flag is set All the fault currents are seen in one direction CT Saturation – Internal Fault Example
  • 62. 62 GE Consumer & Industrial Multilin 29-Oct-22 Applying Low-Impedance Differential Relays for Busbar Protection Basic Topics • Configure physical CT Inputs • Configure Bus Zone and Dynamic Bus Replica • Calculating Bus Differential Element settings Advanced Topics • Isolator switch monitoring for reconfigurable buses • Differential Zone CT Trouble • Integrated Breaker Failure protection
  • 63. 63 GE Consumer & Industrial Multilin 29-Oct-22 Configuring CT Inputs • For each connected CT circuit enter Primary rating and select Secondary rating. • Each 3-phase bank of CT inputs must be assigned to a Signal Source that is used to define the Bus Zone and Dynamic Bus Replica Some relays define 1 p.u. as the maximum primary current of all of the CTs connected in the given Bus Zone
  • 64. 64 GE Consumer & Industrial Multilin 29-Oct-22 Per-Unit Current Definition - Example Current Channel Primary Secondary Zone CT-1 F1 3200 A 1 A 1 CT-2 F2 2400 A 5 A 1 CT-3 F3 1200 A 1 A 1 CT-4 F4 3200 A 1 A 2 CT-5 F5 1200 A 5 A 2 CT-6 F6 5000 A 5 A 2 • For Zone 1, 1 p.u. = 3200 AP • For Zone 2, 1 p.u. = 5000 AP
  • 65. 65 GE Consumer & Industrial Multilin 29-Oct-22 Configuration of Bus Zone • Dynamic Bus Replica associates a status signal with each current in the Bus Differential Zone • Status signal can be any logic operand o Status signals can be developed in programmable logic to provide additional checks or security as required o Status signal can be set to ‘ON’ if current is always in the bus zone or ‘OFF’ if current is never in the bus zone • CT connections/polarities for a particular bus zone must be properly configured in the relay, via either hardwire or software
  • 66. 66 GE Consumer & Industrial Multilin 29-Oct-22 Configuring the Bus Differential Zone 1. Configure the physical CT Inputs o CT Primary and Secondary values o Both 5 A and 1 A inputs are supported by the UR hardware o Ratio compensation done automatically for CT ratio differences up to 32:1 2. Configure AC Signal Sources 3. Configure Bus Zone with Dynamic Bus Replica Bus Zone settings defines the boundaries of the Differential Protection and CT Trouble Monitoring.
  • 67. 67 GE Consumer & Industrial Multilin 29-Oct-22 Dual Percent Differential Characteristic High Breakpoint Low Breakpoint Low Slope High Slope High Set (Unrestrained) Min Pickup
  • 68. 68 GE Consumer & Industrial Multilin 29-Oct-22 Calculating Bus Differential Settings • The following Bus Zone Differential element parameters need to be set: o Differential Pickup o Restraint Low Slope o Restraint Low Break Point o Restraint High Breakpoint o Restraint High Slope o Differential High Set (if needed) • All settings entered in per unit (maximum CT primary in the zone) • Slope settings entered in percent • Low Slope, High Slope and High Breakpoint settings are used by the CT Saturation Detector and define the Region 1 Area (2-out-of-2 operation with Directional)
  • 69. 69 GE Consumer & Industrial Multilin 29-Oct-22 Calculating Bus Differential Settings – Minimum Pickup • Defines the minimum differential current required for operation of the Bus Zone Differential element • Must be set above maximum leakage current not zoned off in the bus differential zone • May also be set above maximum load conditions for added security in case of CT trouble, but better alternatives exist
  • 70. 70 GE Consumer & Industrial Multilin 29-Oct-22 Calculating Bus Differential Settings – Low Slope • Defines the percent bias for the restraint currents from IREST=0 to IREST=Low Breakpoint • Setting determines the sensitivity of the differential element for low-current internal faults • Must be set above maximum error introduced by the CTs in their normal linear operating mode • Range: 15% to 100% in 1%. increments
  • 71. 71 GE Consumer & Industrial Multilin 29-Oct-22 Calculating Bus Differential Settings – Low Breakpoint • Defines the upper limit to restraint currents that will be biased according to the Low Slope setting • Should be set to be above the maximum load but not more than the maximum current where the CTs still operate linearly (including residual flux) • Assumption is that the CTs will be operating linearly (no significant saturation effects up to 80% residual flux) up to the Low Breakpoint setting
  • 72. 72 GE Consumer & Industrial Multilin 29-Oct-22 Calculating Bus Differential Settings – High Breakpoint • Defines the minimum restraint currents that will be biased according to the High Slope setting • Should be set to be below the minimum current where the weakest CT will saturate with no residual flux • Assumption is that the CTs will be operating linearly (no significant saturation effects up to 80% residual flux) up to the Low Breakpoint setting
  • 73. 73 GE Consumer & Industrial Multilin 29-Oct-22 Calculating Bus Differential Settings – High Slope • Defines the percent bias for the restraint currents IRESTHigh Breakpoint • Setting determines the stability of the differential element for high current external faults • Traditionally, should be set high enough to accommodate the spurious differential current resulting from saturation of the CTs during heavy external faults • Setting can be relaxed in favour of sensitivity and speed as the relay detects CT saturation and applies the directional principle to prevent maloperation • Range: 50% to 100% in 1%. increments
  • 74. 74 GE Consumer & Industrial Multilin 29-Oct-22 Calculating Unrestrained Bus Differential Settings • Defines the minimum differential current for unrestrained operation • Should be set to be above the maximum differential current under worst case CT saturation • Range: 2.00 to 99.99 p.u. in 0.01 p.u. increments • Can be effectively disabled by setting to 99.99 p.u.
  • 75. 75 GE Consumer & Industrial Multilin 29-Oct-22 Dual Percent Differential Characteristic High Breakpoint Low Breakpoint Low Slope High Slope High Set (Unrestrained) Min Pickup
  • 76. 76 GE Consumer & Industrial Multilin 29-Oct-22 NORTH BUS SOUTH BUS CT-8 B-5 B-6 CT-5 CT-6 S-5 S-6 B-4 CT-4 S-3 S-4 B-3 CT-3 S-1 S-2 B-2 CT-2 CT-1 B-1 C-1 C-2 C-4 C-3 C-5 CT-7 B-7 Protecting re-configurable buses Reconfigurable Buses
  • 77. 77 GE Consumer & Industrial Multilin 29-Oct-22 NORTH BUS SOUTH BUS CT-7 CT-8 B-7 B-5 B-6 CT-5 CT-6 S-5 S-6 B-4 CT-4 S-3 S-4 B-3 CT-3 S-1 S-2 B-2 CT-2 CT-1 B-1 C-1 C-2 C-4 C-3 C-5 Protecting re-configurable buses Reconfigurable Buses
  • 78. 78 GE Consumer & Industrial Multilin 29-Oct-22 NORTH BUS SOUTH BUS CT-7 CT-8 B-7 B-5 B-6 CT-5 CT-6 S-5 S-6 B-4 CT-4 S-3 S-4 B-3 CT-3 S-1 S-2 B-2 CT-2 CT-1 B-1 C-1 C-2 C-4 C-3 C-5 Protecting re-configurable buses Reconfigurable Buses
  • 79. 79 GE Consumer & Industrial Multilin 29-Oct-22 NORTH BUS SOUTH BUS CT-8 B-5 B-6 CT-5 CT-6 S-5 S-6 B-4 CT-4 S-3 S-4 B-3 CT-3 S-1 S-2 B-2 CT-2 CT-1 B-1 C-1 C-2 C-4 C-3 C-5 CT-7 B-7 Protecting re-configurable buses Reconfigurable Buses
  • 80. 80 GE Consumer & Industrial Multilin 29-Oct-22 Isolators • Reliable “Isolator Closed” signals are needed for the Dynamic Bus Replica • In simple applications, a single normally closed contact may be sufficient • For maximum safety: o Both N.O. and N.C. contacts should be used o Isolator Alarm should be established and non-valid combinations (open-open, closed-closed) should be sorted out o Switching operations should be inhibited until bus image is recognized with 100% accuracy o Optionally block 87B operation from Isolator Alarm • Each isolator position signal decides: o Whether or not the associated current is to be included in the differential calculations o Whether or not the associated breaker is to be tripped
  • 81. 81 GE Consumer & Industrial Multilin 29-Oct-22 Isolator – Typical Open/Closed Connections
  • 82. 82 GE Consumer & Industrial Multilin 29-Oct-22 Isolator Open Auxiliary Contact Isolator Closed Auxiliary Contact Isolator Position Alarm Block Switching Off On CLOSED No No Off Off LAST VALID After time delay until acknowledged Until Isolator Position is valid On On CLOSED On Off OPEN No No NOTE: Isolator monitoring function may be a built-in feature or user- programmable in low impedance bus differential digital relays Switch Status Logic and Dyanamic Bus Replica
  • 83. 83 GE Consumer & Industrial Multilin 29-Oct-22 Differential Zone CT Trouble • Each Bus Differential Zone may a dedicated CT Trouble Monitor • Definite time delay overcurrent element operating on the zone differential current, based on the configured Dynamic Bus Replica • Three strategies to deal with CT problems: 1. Trip the bus zone as the problem with a CT will likely evolve into a bus fault anyway 2. Do not trip the bus, raise an alarm and try to correct the problem manually 3. Switch to setting group with 87B minimum pickup setting above the maximum load current.
  • 84. 84 GE Consumer & Industrial Multilin 29-Oct-22 • Strategies 2 and 3 can be accomplished by:  Using undervoltage supervision to ride through the period from the beginning of the problem with a CT until declaring a CT trouble condition  Using an external check zone to supervise the 87B function  Using CT Trouble to prevent the Bus Differential tripping (2)  Using setting groups to increase the pickup value for the 87B function (3) Differential Zone CT Trouble
  • 85. 85 GE Consumer & Industrial Multilin 29-Oct-22 Differential Zone CT Trouble – Strategy #2 Example • CT Trouble operand is used to rise an alarm • The 87B trip is inhibited after CT Trouble element operates • The relay may misoperate if an external fault occurs after CT trouble but before the CT trouble condition is declared (double-contingency) 87B operates Undervoltage condition CT OK
  • 86. 86 GE Consumer & Industrial Multilin 29-Oct-22 Example Architecture for Large Busbars Dual (redundant) fiber with 3msec delivery time between neighbouring IEDs. Up to 8 relays in the ring Phase A AC signals and trip contacts Phase B AC signals and trip contacts Phase C AC signals and trip contacts Digital Inputs for isolator monitoring and BF
  • 87. 87 GE Consumer & Industrial Multilin 29-Oct-22 Phase A AC signals wired here, bus replica configured here Phase B AC signals wired here, bus replica configured here Phase C AC signals wired here, bus replica configured here Auxuliary switches wired here; Isolator Monitoring function configured here Example Architecture – Dynamic Bus Replica and Isolator Position
  • 88. 88 GE Consumer & Industrial Multilin 29-Oct-22 Phase A AC signals wired here, current status monitored here Phase B AC signals wired here, current status monitored here Phase C AC signals wired here, current status monitored here Breaker Failure elements configured here Example Architecture – BF Initiation & Current Supervision
  • 89. 89 GE Consumer & Industrial Multilin 29-Oct-22 Phase A AC signals wired here, current status monitored here Phase B AC signals wired here, current status monitored here Phase C AC signals wired here, current status monitored here Breaker Fail Op command generated here and send to trip appropriate breakers Trip Trip Trip Example Architecture – Breaker Failure Tripping Trip
  • 90. 90 GE Consumer & Industrial Multilin 29-Oct-22 IEEE 37.234 • “Guide for Protective Relay Applications to Power System Buses” is currently being revised by the K14 Working Group of the IEEE Power System Relaying Committee.
  • 91. 91 GE Consumer & Industrial Multilin 29-Oct-22