Experiment 01: Activation of Various Output Indicator Elements using Push buttons
Experiment 02: Activation of Indicator Light by series and Parallel switches
Experiment 03: Activation of Indicator Light by Coil activated Contact Switch
Experiment 04: Activating Indicator light using Circuit with Coil latch and Coil Unlatch
Experiment 05: Activation of Indicator light by Delay timer circuit
Experiment A: Control of double acting cylinder using Proximity sensors and Proximity Switch
Experiment B: Control of double acting cylinder using delay on and off timer and counter
Experiment C: Execute energized motor using Switches in Series or Parallel Circuit
Experiment D: Execute energized motor using Switches in Latching Circuit
Experiment E: Execute energized motor using Switches in Sequential O/P
Experiment F: Delay Control of Motors using Timer function
Experiment G: Control of Motors using Relay contact
Experiment H: Indirect Control of Forward and Reverse motion in Motor
Experiment I: Direct Control of Forward and Reverse motion in Motor
Vidya Vikas Polytechnic Laboratory Manual Elements of Industrial Automation
1. Vidya Vikas Educational Trust (R),
Vidya Vikas Polytechnic
27-128, Mysore - Bannur Road Alanahally,Alanahally Post, Mysuru, Karnataka 570028
Prepared by Mr. THANMAY J.S, HOD Mechanical, Vidya Vikas Polytechnic, Mysore. Page 1 of 17
Department of Mechanical Engineering
Laboratory Manual
Subject : Elements of Industrial Automation
Subject Code : 20ME44P
Semester : 4th
Semester
Branch : Mechanical Engineering [General]
Name of the Student: …………………………………………….
Register Number: …………………………………………….
2. Vidya Vikas Educational Trust (R),
Vidya Vikas Polytechnic
27-128, Mysore - Bannur Road Alanahally,Alanahally Post, Mysuru, Karnataka 570028
Prepared by Mr. THANMAY J.S, HOD Mechanical, Vidya Vikas Polytechnic, Mysore. Page 2 of 17
Syllabus
Section A
Experiment 01: Activation of Various Output Indicator Elements using Push buttons
Experiment 02: Activation of Indicator Light by series and Parallel switches
Experiment 03: Activation of Indicator Light by Coil activated Contact Switch
Experiment 04: Activating Indicator light using Circuit with Coil latch and Coil Unlatch
Experiment 05: Activation of Indicator light by Delay timer circuit
Section B
Experiment A: Control of double acting cylinder using Proximity sensors and Proximity Switch
Experiment B: Control of double acting cylinder using delay on and off timer and counter
Experiment C: Execute energized motor using Switches in Series or Parallel Circuit
Experiment D: Execute energized motor using Switches in Latching Circuit
Experiment E: Execute energized motor using Switches in Sequential O/P
Experiment F: Delay Control of Motors using Timer function
Experiment G: Control of Motors using Relay contact
Experiment H: Indirect Control of Forward and Reverse motion in Motor
Experiment I: Direct Control of Forward and Reverse motion in Motor
3. Vidya Vikas Educational Trust (R),
Vidya Vikas Polytechnic
27-128, Mysore - Bannur Road Alanahally,Alanahally Post, Mysuru, Karnataka 570028
Prepared by Mr. THANMAY J.S, HOD Mechanical, Vidya Vikas Polytechnic, Mysore. Page 3 of 17
Dear Students
Before we start to attain knowledge of great resource let me remind you to use the proper licensed version of
the Automation studio or Educational Edition of Automation Studio.
I have used Automation studio 3.0.5 Demo version for the manual.
You can download the latest version of Automation by using the link below based on your system
configurations:
https://www.famictech.com/en/Support/Automation-Studio/Downloads
If you insist on using the same version as mine download from any of the links below but be alert for virus
and pirated versions, try not to use crack use demo mode it works for every 90 minutes whenever you open it
also be cautious in x32 bit or x64 bit Installation:
https://allpcworlds.com/download-automation-studio-3-0-5-free/
https://getintopc.globalhow.com/blog/automation-studio-3-0-5-free-download/
https://webintopc.com/automation-studio-3-0-5-free-download/
I request all those who use this manual to support “Famic Technologies Inc” for their innovative software
Automation Studio.
For contact and support use the links below:
https://www.famictech.com/en/contact
Thanking you all
With regards
THANMAY J S
4. Vidya Vikas Educational Trust (R),
Vidya Vikas Polytechnic
27-128, Mysore - Bannur Road Alanahally,Alanahally Post, Mysuru, Karnataka 570028
Prepared by Mr. THANMAY J.S, HOD Mechanical, Vidya Vikas Polytechnic, Mysore. Page 4 of 17
Experiment 01: Activation of Various Output Indicator Elements using Push buttons
Components Require Location Symbol
Indicator Light
Electric Control (US)> Output
Component > Indicator light
LED
Electric Control (US)> Output
Component > LED
Diode
Electric Control (US)> Output
Component > Diode
Power source / Zero volts
Electric Control (US)> Power
Source > Power supply 24 volts
Electric Control (US)> Power
Source > Common Zero Volt
Push Button
Electric Control (US)> Switches>
Push Button ON
Activating Indicator Light
Activating LED Light
Activating Diode
5. Vidya Vikas Educational Trust (R),
Vidya Vikas Polytechnic
27-128, Mysore - Bannur Road Alanahally,Alanahally Post, Mysuru, Karnataka 570028
Prepared by Mr. THANMAY J.S, HOD Mechanical, Vidya Vikas Polytechnic, Mysore. Page 5 of 17
Experiment 02: Activation of Indicator Light by Series and Parallel switches
Components Require Location Symbol
Power source / Zero volts
Electric Control (US)> Power
Source > Power supply 24 volts
Electric Control (US)> Power
Source > Common Zero Volt
Push Button
Electric Control (US)> Switches>
Push Button ON
Toggle Switch
Electric Control (US)> Switches>
Toggle Switch ON
Indicator Light
Electric Control (US)> Output
Component > Indicator light
Switches in Series
Switches in Parallel
6. Vidya Vikas Educational Trust (R),
Vidya Vikas Polytechnic
27-128, Mysore - Bannur Road Alanahally,Alanahally Post, Mysuru, Karnataka 570028
Prepared by Mr. THANMAY J.S, HOD Mechanical, Vidya Vikas Polytechnic, Mysore. Page 6 of 17
Experiment 03: Activation of Indicator Light by Coil activated Contact Switch
Components Require Location Symbol
Power source / Zero volts
Electric Control (US)> Power
Source > Power supply 24 volts
Electric Control (US)> Power
Source > Common Zero Volt
Push Button
Electric Control (US)> Switches>
Push Button ON
Indicator Light
Electric Control (US)> Output
Component > Indicator light
Coil
Electric Control (US)> Output
Component > Coil
Open Contact
Electric Control (US)> Contact >
Contact NO
7. Vidya Vikas Educational Trust (R),
Vidya Vikas Polytechnic
27-128, Mysore - Bannur Road Alanahally,Alanahally Post, Mysuru, Karnataka 570028
Prepared by Mr. THANMAY J.S, HOD Mechanical, Vidya Vikas Polytechnic, Mysore. Page 7 of 17
Experiment 04: Activating Indicator light using Circuit with Coil latch and Coil Unlatch
Components Require Location Symbol
Power source / Zero volts
Electric Control (US)> Power
Source > Power supply 24 volts
Electric Control (US)> Power
Source > Common Zero Volt
Toggle Switch
Electric Control (US)> Switches>
Toggle Switch ON
Coil Latch
Electric Control (US)> Output
Component > Coil Latch (Set)
Coil Un Latch
Electric Control (US)> Output
Component > Coil Unlatch (Reset)
Open Contact
Electric Control (US)> Contact >
Contact NO
Indicator Light
Electric Control (US)> Output
Component > Indicator light
8. Vidya Vikas Educational Trust (R),
Vidya Vikas Polytechnic
27-128, Mysore - Bannur Road Alanahally,Alanahally Post, Mysuru, Karnataka 570028
Prepared by Mr. THANMAY J.S, HOD Mechanical, Vidya Vikas Polytechnic, Mysore. Page 8 of 17
Experiment 05: Activation of Indicator light by Delay timer circuit
Components Require Location Symbol
Power source / Zero volts
Electric Control (US)> Power
Source > Power supply 24 volts
Electric Control (US)> Power
Source > Common Zero Volt
Push Button
Electric Control (US)> Switches>
Push Button ON
Coil
Electric Control (US)> Output
Component > Coil
Open Contact
Electric Control (US)> Contact >
Contact NO
OFF Delay
Electric Control (US)> Contact >
Contact with off delay NO
ON Delay
Electric Control (US)> Contact >
Contact with on delay NO
ON/OFF Delay
Electric Control (US)> Contact >
Contact with on/off delay NO
Indicator Light
Electric Control (US)> Output
Component > Indicator light
9. Vidya Vikas Educational Trust (R),
Vidya Vikas Polytechnic
27-128, Mysore - Bannur Road Alanahally,Alanahally Post, Mysuru, Karnataka 570028
Prepared by Mr. THANMAY J.S, HOD Mechanical, Vidya Vikas Polytechnic, Mysore. Page 9 of 17
Experiment A: Control of double acting cylinder using Proximity sensors and Proximity Switch
Components Require Location Symbol
Double Acting Cylinder
Actuator
Pneumatic > Actuator > Double
Action (DA) Cylinder
5/2-way Directional Valve
with Single solenoid (spring
return) add solenoid to left
and spring to right side
Pneumatic > Directional Valve >
5/2-(14) Valve
Pressure Source / Exhaust
Pneumatic > Line > Pneumatic
Pressure Source.
Pneumatic > Line > Exhaust
Solenoid Switch
Electric Control (US)> Output
Component > Solenoid
Power source / Zero volts
Electric Control (US)> Power
Source > Power supply 24 volts
Electric Control (US)> Power
Source > Common Zero Volt
Push Button
Electric Control (US)> Switches>
Push Button ON
Solenoid Switch
Electric Control (US)> Output
Component > Solenoid
Proximity Sensors
Pneumatics>Sensors > Proximity
Sensors
Proximity Switch
Electric Control (US)> Switches >
Proximity Switch NO
10. Vidya Vikas Educational Trust (R),
Vidya Vikas Polytechnic
27-128, Mysore - Bannur Road Alanahally,Alanahally Post, Mysuru, Karnataka 570028
Prepared by Mr. THANMAY J.S, HOD Mechanical, Vidya Vikas Polytechnic, Mysore. Page 10 of 17
Experiment B: Control of double acting cylinder using delay on and off timer and counter
[C delay cycle count]
Components Require Location Symbol
Double Acting Cylinder
Actuator
Pneumatic > Actuator > Double
Action (DA) Cylinder
5/2-way Directional Valve
with Single solenoid (spring
return) add solenoid to left
and spring to right side
Pneumatic > Directional Valve >
5/2-(14) Valve
Pressure Source / Exhaust
Pneumatic > Line > Pneumatic
Pressure Source.
Pneumatic > Line > Exhaust
Power source / Zero volts
Electric Control (US)> Power
Source > Power supply 24 volts
Electric Control (US)> Power
Source > Common Zero Volt
Toggle Switch
Electric Control (US)> Switches>
Toggle Switch NC
Solenoid Switch
Electric Control (US)> Output
Component > Solenoid
Coil
Electric Control (US)> Output
Control> Coil
Delay Switch
Electric Control (US)> Switches >
Contact with ON/OFF Delay NC
11. Vidya Vikas Educational Trust (R),
Vidya Vikas Polytechnic
27-128, Mysore - Bannur Road Alanahally,Alanahally Post, Mysuru, Karnataka 570028
Prepared by Mr. THANMAY J.S, HOD Mechanical, Vidya Vikas Polytechnic, Mysore. Page 11 of 17
Experiment C: Execute energized motor using Switches in Series or Parallel Circuit
Components Require Location Symbol
Power source / Zero volts
Electric Control (US)> Power
Source > Power supply 24 volts
Electric Control (US)> Power
Source > Common Zero Volt
Electric Control (US)> Power
Source > Power supply 1 (L1)
Electric Control (US)> Power
Source > Neutral
Single Phase Motor
Electric Control (US)> Output
Control > Single Phase Motor
Toggle Switch
Electric Control (US)> Switches>
Toggle Switch ON
Coil
Electric Control (US)> Output
Control> Coil
Open Contact
Electric Control (US)> Contact >
Contact NO
Series Switch in Energizing Motor
Parallel Switch in Energizing Motor
12. Vidya Vikas Educational Trust (R),
Vidya Vikas Polytechnic
27-128, Mysore - Bannur Road Alanahally,Alanahally Post, Mysuru, Karnataka 570028
Prepared by Mr. THANMAY J.S, HOD Mechanical, Vidya Vikas Polytechnic, Mysore. Page 12 of 17
Experiment D: Execute energized motor using Switches in Latching Circuit
Components Require Location Symbol
Power source / Zero volts
Electric Control (US)> Power
Source > Power supply 24 volts
Electric Control (US)> Power
Source > Common Zero Volt
Single Phase Motor
Electric Control (US)> Output
Control > Single Phase Motor
Push Button
Electric Control (US)> Switches>
Push Button ON
Toggle Switch
Electric Control (US)> Switches>
Toggle Switch ON
Coil Latch
Electric Control (US)> Output
Component > Coil Latch (Set)
Coil Un Latch
Electric Control (US)> Output
Component > Coil Unlatch (Reset)
Open Contact
Electric Control (US)> Contact >
Contact NO
Indicator Light
Electric Control (US)> Output
Component > Indicator light
13. Vidya Vikas Educational Trust (R),
Vidya Vikas Polytechnic
27-128, Mysore - Bannur Road Alanahally,Alanahally Post, Mysuru, Karnataka 570028
Prepared by Mr. THANMAY J.S, HOD Mechanical, Vidya Vikas Polytechnic, Mysore. Page 13 of 17
Experiment E: Execute energized motor using Switches in Sequential O/P
Components Require Location Symbol
Power source / Zero volts
Electric Control (US)> Power
Source > Power supply 24 volts
Electric Control (US)> Power
Source > Common Zero Volt
Electric Control (US)> Power
Source > Power supply 1 (L1)
Electric Control (US)> Power
Source > Power supply 2 (L2)
Electric Control (US)> Power
Source > Power supply 3 (L3)
Three Phase Motor
Electric Control (US)> Output
Control > Three Phase Motor
Toggle Switch
Electric Control (US)> Switches>
Toggle Switch ON
Coil
Electric Control (US)> Output
Control> Coil
Open Contact
Electric Control (US)> Contact >
Contact NO
Indicator Light
Electric Control (US)> Output
Component > Indicator light
14. Vidya Vikas Educational Trust (R),
Vidya Vikas Polytechnic
27-128, Mysore - Bannur Road Alanahally,Alanahally Post, Mysuru, Karnataka 570028
Prepared by Mr. THANMAY J.S, HOD Mechanical, Vidya Vikas Polytechnic, Mysore. Page 14 of 17
Experiment F: Delay Control of Motors using Timer function
Components Require Location Symbol
Power source / Zero volts
Electric Control (US)> Power
Source > Power supply 24 volts
Electric Control (US)> Power
Source > Common Zero Volt
Single Phase Motor
Electric Control (US)> Output
Control > Single Phase Motor
Open Contact
Electric Control (US)> Contact >
Contact NO
Push Button
Electric Control (US)> Switches>
Push Button ON
Fuse Electric Control (US)> Line > Fuse
Toggle Switch
Electric Control (US)> Switches>
Toggle Switch NC
Coil
Electric Control (US)> Output
Control> Coil
Delay Switch
Electric Control (US)> Switches >
Contact with ON/OFF Delay NC
15. Vidya Vikas Educational Trust (R),
Vidya Vikas Polytechnic
27-128, Mysore - Bannur Road Alanahally,Alanahally Post, Mysuru, Karnataka 570028
Prepared by Mr. THANMAY J.S, HOD Mechanical, Vidya Vikas Polytechnic, Mysore. Page 15 of 17
Experiment G: Control of Motors using Relay contact
Components Require Location Symbol
Power source
Electric Control (US)> Power
Source > Power supply 1 (L1)
Electric Control (US)> Power
Source > Power supply 2 (L2)
Electric Control (US)> Power
Source > Power supply 3 (L3)
Electric Control (US)> Power
Source > Neutral
Three Phase Motor
Electric Control (US)> Output
Control > Three Phase Motor
Open Contact
Electric Control (US)> Contact >
Contact NO
Push Button
Electric Control (US)> Switches>
Push Button ON
Close Contact
Electric Control (US)> Contact >
Contact NC
Relay
Electric Control (US)> Output
Control> Overload Relay
Toggle Switch
Electric Control (US)> Switches>
Toggle Switch NC
Coil
Electric Control (US)> Output
Control> Coil
16. Vidya Vikas Educational Trust (R),
Vidya Vikas Polytechnic
27-128, Mysore - Bannur Road Alanahally,Alanahally Post, Mysuru, Karnataka 570028
Prepared by Mr. THANMAY J.S, HOD Mechanical, Vidya Vikas Polytechnic, Mysore. Page 16 of 17
Experiment H: Indirect Control of Forward and Reverse motion in Motor
Components Require Location Symbol
Power source
Electric Control (US)> Power
Source > Power supply 1 (L1)
Electric Control (US)> Power
Source > Power supply 2 (L2)
Electric Control (US)> Power
Source > Power supply 3 (L3)
Three Phase Motor
Electric Control (US)> Output
Control > Three Phase Motor
Open Contact
Electric Control (US)> Contact >
Contact NO
Push Button
Electric Control (US)> Switches>
Push Button ON
Close Contact
Electric Control (US)> Contact >
Contact NC
Relay
Electric Control (US)> Output
Control> Overload Relay
Toggle Switch
Electric Control (US)> Switches>
Toggle Switch NC
Coil
Electric Control (US)> Output
Control> Coil
17. Vidya Vikas Educational Trust (R),
Vidya Vikas Polytechnic
27-128, Mysore - Bannur Road Alanahally,Alanahally Post, Mysuru, Karnataka 570028
Prepared by Mr. THANMAY J.S, HOD Mechanical, Vidya Vikas Polytechnic, Mysore. Page 17 of 17
Experiment I: Direct Control of Forward and Reverse motion in Motor
Components Require Location Symbol
Power source
Electric Control (US)> Power
Source > Power supply 1 (L1)
Electric Control (US)> Power
Source > Power supply 2 (L2)
Electric Control (US)> Power
Source > Power supply 3 (L3)
Three Phase Motor
Electric Control (US)> Output
Control > Three Phase Motor
Open Contact
Electric Control (US)> Contact >
Contact NO
Push Button
Electric Control (US)> Switches>
Push Button ON
Close Contact
Electric Control (US)> Contact >
Contact NC
Relay
Electric Control (US)> Output
Control> Overload Relay
Toggle Switch
Electric Control (US)> Switches>
Toggle Switch NC
Coil
Electric Control (US)> Output
Control> Coil
Step Down Transformer
Electric Control (US)> Power
Source > Transformer
Grounding
Electric Control (US)> Power
Source > Ground