SlideShare a Scribd company logo
1 of 28
PROTECTION OF
ALTERNATOR
• Abnormalities & Faults
• Circuit diagram with proper current direction of
Differential protection.
• Over current, earth fault, inter -turn fault, negative phase
sequence, over heating protection.
• Reverse power protections.
• Simple numerical on differential protection
INTRODUCTION
• Generator is a large machine and is connected to busbars. It is
accompanied by unit-transformers, auxiliary transformer and bus
system.
• It is accompanied by excitation system, prime mover, voltage
regulator, cooling system etc;
• Hence it is not a single equipment. The protection of generator
should be coordinated with associated equipment.
• It is a costly and important equipment. It should not be shut off
as far possible because that would result in power shortage and
emergency.
• Modern Turbo-generators have the following typical ratings!
60 MW 11.8 kV
120 MW 13.8 kV
500 MW 22 kV
• Generator unit up to 500 MW have been installed in India.
ABNORMALITIES & FAULTS
• Some of the important faults which may occur
on an alternator are :
i. Failure of prime-mover
ii. Failure of field
iii. Over current
iv. Over speed
v. Overvoltage
vi. unbalanced loading
vii. Stator winding faults
• Failure of prime-mover. When input to the prime-mover fails, the
alternator runs as a synchronous motor and draws some current from the
supply system. This motoring conditions is known as "inverted running".
• Protection against motoring is achieved by applying reverse power relays to
the alternators which isolate the latter during their motoring action.
• The chances of field failure of alternators are undoubtedly very rare.
• It is sufficient to rely on the control room attendant to disconnect the faulty
alternator manually from the system bus-bars. Therefore no need to provide
automatic protection against field failure.
• Over-current occurs mainly due to partial breakdown of winding
insulation or due to overload on the supply system.
• Alternators with very high values of internal impedance are designed so
that they will stand a complete short-circuit at their terminals for sufficient
time without serious overheating.
• Overload protection for alternators is that such a protection might
disconnect the alternators from the power plant bus on account of some
momentary troubles outside the plant
ABNORMALITIES & FAULTS
• Over-speed The chief cause of over-speed is the sudden loss of all or the
major part of load on the alternator.
• Alternators are usually provided with mechanical centrifugal devices
mounted on their driving shafts to trip the main valve of the prime-mover
when a dangerous over-speed occurs.
• Over-voltage The field excitation system of modern alternators is so
designed that over-voltage conditions at normal running speeds cannot
occur. However, overvoltage in an alternator occurs when speed of the
prime-mover increases due to sudden loss of the alternator load.
• a usual practice to provide over-voltage protection on hydro-generator
units.
• Over-voltage relays are operated from a voltage supply taken from the
generator terminals
• When the generated voltage rises 20% above the normal value, they
operate
ABNORMALITIES & FAULTS
• Unbalanced loading means that there are different phase currents in the
alternator.
• It arises from faults to earth or faults between phases on the circuit external
to the alternator.
• Severely burn the mechanical fixings of the rotor core or damage the field
winding
ABNORMALITIES & FAULTS
• Stator winding faults occur mainly due to the insulation failure of the
stator windings.
• The main types of stator winding faults, in order of importance are :
– Fault between phase and ground
– Fault between phases
– Inter-turn fault involving turns of the same phase winding
• For protection of alternators against such faults, differential method of
protection (also knows as Merz-Price system) is most commonly employed
due to its greater sensitivity and reliability
DIFFERENTIAL PROTECTION
OF ALTERNATORS
DIFFERENTIAL PROTECTION
OF ALTERNATORS
• Schematic arrangement. Above Fig. shows the schematic arrangement of
current differential protection for a 3-phase alternator.
• Identical current transformer pairs CT' and CT2 are placed on either side of
each phase of the stator windings.
• The secondary's of each set of current transformers are connected in star.
• The two neutral points and the corresponding terminals of the two star
groups being connected together by means of a four-core pilot cable.
• There is an independent path for the currents circulating in each pair of
current transformers and the corresponding pilot.
• The relay coils are connected in star,
• The neutral point of relay being connected to the current-transformer
common neutral and the outer ends one to each of the other three pilots.
• Operation. Under normal operating conditions, the current at both ends of
each winding will be equal and hence the currents in the secondary's of two
CTs connected in any phase will also be equal.
• Balanced circulating current in the pilot wires therefore no current flows
through the operating coils (R1, R2 and R3) of the relays.
• Suppose an earth fault occurs on phase R due to breakdown of its insulation
to earth as shown in fig.
• The current in the affected phase winding will flow through the core and
frame of the machine to earth, the circuit being completed through the
neutral earthing resistance.
• The currents in the secondaries of the two CTs in phase R will become
unequal and the difference of the two currents will flow through the corre-
sponding relay coil (i.E. R1),
• Returning via the neutral pilot. Consequently, the relay operates to trip the
circuit breaker.
DIFFERENTIAL PROTECTION
OF ALTERNATORS
DIFFERENTIAL PROTECTION
OF ALTERNATORS
• Imagine that now a short-circuit fault occurs between the phases Y and B as
shown in Fig. The short-circuit current circulates via the neutral end
connection through the two windings and through the fault as shown by the
dotted arrows.
• The currents in the secondaries of two CTs in each affected phase will
become unequal and the differ-ential current will flow through the
operating coils of the relays (i.e. R2 and R3) con-nected in these phases.
• The relay then closes its contacts to trip the circuit breaker.
If a fault occurs between two phases, the out of-balance current will circulate round the two
transformer secondary's via any two of the coils PA, BR, PC (the pair being decided by the two
phases that are faulty) without passing through the earth relay ER.
MODIFIED DIFFERENTIAL
PROTECTION FOR ALTERNATORS
• If the neutral point of a star-connected alternator is earthed through a high
resistance, protection schemes shown in Fig. it will not provide sufficient
sensitivity for earth-faults.
• It is because the high earthing resistance will limit the earth-fault currents
to a low value, necessitating relays with low current settings if adequate
portion of the generator winding is to be protected.
• Consist of two relays for phase-fault protection and the third for earth-fault
protection only.
• The two phase elements (PC and PA) and balancing resistance (BR) are
connected in star and the earth relay (ER) is connected between this star
point and the fourth wire of circulating current pilot-circuit.
• Under normal operating conditions, currents at the two ends of each stator
winding will be equal.
• Therefore, there is a balanced circulating current in the phase pilot wires
and no current flows through the operating coils of the relays.
• If an earth-fault occurs on any one phase, the out-of-balance secondary
current in CTs in that phase will flow through the earth relay ER and via
pilot S 1 or S2 to the neutral of the current transformers.
• This will cause the operation of earth relay only.
• If a fault occurs between two phases, the out of-balance current will
circulate round the two transformer secondary's via any two of the coils PA,
BR, PC (the pair being decided by the two phases that are faulty) without
passing through the earth relay ER.
• Therefore, only the phase-fault relays will operate.
MODIFIED DIFFERENTIAL
PROTECTION FOR ALTERNATORS
RESTRICTED EARTH FAULT RELAY
• With resistance earthing, it is not possible to
protect complete winding from earth-fault
and the % of winding protected depends on
the value of neutral earthing resistor
• Earth faults are not likely to occur near the
neutral point due to less voltage w.r.t. earth.
• It is a usual practice to protect about 80 to
85% of generator winding against earth-faults.
• The remaining 20 to 15% winding from neutral
side left un-protected by the differential
protection
• During earth-fault If in the alternator winding,
the current, If flows through a part of the
generator winding and neutral to ground
circuit. The corresponding secondary current
Is flows through the operating coil and
restricted earth-fault coil of the differential
protection.
• If point is nearer to terminal a (nearer to the
neutral point) the forcing voltage Vaf will be
relatively less. Hence earth fault current If will
reduce.
BALANCED EARTH-FAULT
PROTECTION
BALANCED EARTH-FAULT
PROTECTION
• It consists of three line current transformers, one mounted in
each phase, having their secondary's connected in parallel with
that of a single current transformer in the conductor joining the
star point of the alternator to earth.
• Under normal operating conditions, the currents flowing in the
alternator leads and hence the currents flowing in secondaries
of the line current transformers add to zero and no current
flows through the relay.
• Also under these conditions, the current in the neutral wire is
zero and the secondary of neutral current transformer supplies
no current to the relay.
• If an earth-fault develops at F2 external to the protected zone, the sum of
the currents at the terminals of the alternator is exactly equal to the current
in the neutral connection and hence no current flows through the relay.
• When an earth-fault occurs at F1 or within the protected zone, these
currents are no longer equal and the differential current flows through the
operating coil of the relay.
• The relay then closes its contacts to disconnect the alternator from the
system.
BALANCED EARTH-FAULT
PROTECTION
STATOR INTER-TURN
PROTECTION
• Merz-price circulating-current system protects
against phase-to-ground and phase-to-phase
faults. It does not protect against turn-to-turn
fault on the same phase winding of the stator.
• It is because the current that this type of fault
produces flows in a local circuit between the
turns involved
• Does not create a difference between the
currents entering and leaving the winding at its
two ends where current transformers are applied.
• In single turn generator (e.g. large steam-turbine
generators), there is no necessity of protection
against inter-turn faults.
• However, inter-turn protection is provided for
multi-turn generators such as hydro-electric
generators.
• These generators have double-winding
armatures (i.e. each phase winding is divided into
two halves) owing to the very heavy currents which
they have to carry.
STATOR INTER-TURN
PROTECTION
• Shows the duplicate stator windings Si and S2
of one phase only with a provision against
inter-turn faults.
• Two current transformers are connected on the
circulating-current principle.
• Under normal conditions, the currents in the
stator windings si and s2 are equal and so will
be the currents in the secondaries of the two
cts.
• The secondary current round the loop then is
the same at all ct points and no current flows
through the relay r1.
• If a short-circuit develops between adjacent
turns, say on si, the currents in the stator
windings si and s2 will no longer be equal.
• Therefore, unequal currents will be induced in
the secondaries of cts and the difference of
these two currents flows through the relay ri.
The relay then closes its contacts to clear the
generator from the system.
• In this case, the stator winding has two
separate parallel paths. The current
transformer primaries are inserted in these
paths and the secondaries are cross-
connected. During inter-turn fault in the
phase winding, the out-of balance current CT
secondaries flows through the relay. Such a
protection can be extremely sensitive.
However it can be employed to generators
with parallel winding for each phase.
NEGATIVE PHASE SEQUENCE
PROTECTION OF GENRATORS
• Unbalanced 3-phase stator
currents cause double frequency
currents to be induced in rotor.
• They cause heating of rotor and
also cause vibrations of stator.
• Unbalanced 3-phase stator
currents have negative sequence
component.
• This component rotates at
synchronous speed in a direction
opposite to the direction of
rotation of rotor.
• Negative sequence filter with over
current relay provide s protection
against un balanced loads.
NEGATIVE PHASE SEQUENCE
CIRCUIT
Auxiliary
CT’s
Auxiliary
CT’s
NEGATIVE PHASE SEQUENCE
CIRCUIT
• The twin windings of two auxiliary CT’s are connected to main (line) CT’s in
such a way that under normal balanced load conditions currents Ia Ib Ic flow in
the direction shown in the figure.
• Impedance Z1 and Z2 are connected across auxiliary CT’s T1 and T2.
• Load impedance ZL i.e. over current relay is connected across terminal XX.
• Under normal condition current through T1 Ib – Ic and T2 will be Ia – Ib.
• The values of Z1 and Z2 are such that under normal condition voltage at point
P and R remains same. i.e. the voltages across QR and QP is equal and
opposite.
• Under unbalanced conditions this voltage changes and a output voltage is
produced across XX so as to operate over current relay.
4 PROTECTION OF ALTERNATOR.pptx

More Related Content

What's hot

Power system protection topic 1
Power system protection topic 1Power system protection topic 1
Power system protection topic 1Siswoyo Edo
 
Generator Protection
Generator ProtectionGenerator Protection
Generator ProtectionPriten Vasa
 
Protection of transmission lines (distance)
Protection of transmission lines (distance)Protection of transmission lines (distance)
Protection of transmission lines (distance)Rohini Haridas
 
Tutorial on Distance and Over Current Protection
Tutorial on Distance and Over  Current ProtectionTutorial on Distance and Over  Current Protection
Tutorial on Distance and Over Current ProtectionSARAVANAN A
 
Transformer protection
Transformer protectionTransformer protection
Transformer protectionjawaharramaya
 
Understanding transformer vector group
Understanding transformer vector groupUnderstanding transformer vector group
Understanding transformer vector groupShyamkant Vasekar
 
Protective relay
Protective relay Protective relay
Protective relay Uday Wankar
 
Switchgear and protection 3
Switchgear and protection 3Switchgear and protection 3
Switchgear and protection 3Md Irshad Ahmad
 
Transformers protection, an introduction
Transformers protection, an introductionTransformers protection, an introduction
Transformers protection, an introductionH. Kheir
 
Power Transformer Protection
Power Transformer ProtectionPower Transformer Protection
Power Transformer ProtectionAng Sovann
 
importance of reactive power in power system
importance of reactive power in power systemimportance of reactive power in power system
importance of reactive power in power systemsneh pratap singh
 
220 KV Substation Operation & Maintenance
220 KV Substation Operation & Maintenance220 KV Substation Operation & Maintenance
220 KV Substation Operation & MaintenanceHimansu Pradhan
 
Firing angle control
Firing angle controlFiring angle control
Firing angle controljawaharramaya
 
Thyristor Characteristics, Two Transistor Model Of Thyristor & Thyrisror Turn...
Thyristor Characteristics, Two Transistor Model Of Thyristor & Thyrisror Turn...Thyristor Characteristics, Two Transistor Model Of Thyristor & Thyrisror Turn...
Thyristor Characteristics, Two Transistor Model Of Thyristor & Thyrisror Turn...University of Gujrat, Pakistan
 
Generator Protection By - Er Rahul Sharma
Generator Protection By - Er Rahul Sharma Generator Protection By - Er Rahul Sharma
Generator Protection By - Er Rahul Sharma Rahul Ruddra
 
Harmonics and mitigation techniques
Harmonics and mitigation techniquesHarmonics and mitigation techniques
Harmonics and mitigation techniquesrifat maryum
 
Er rahul sharma feeder protection
Er rahul sharma feeder protectionEr rahul sharma feeder protection
Er rahul sharma feeder protectionRahul Ruddra
 

What's hot (20)

Power system protection topic 1
Power system protection topic 1Power system protection topic 1
Power system protection topic 1
 
Generator Protection
Generator ProtectionGenerator Protection
Generator Protection
 
Fc tcr.newpptx
Fc tcr.newpptxFc tcr.newpptx
Fc tcr.newpptx
 
UPQC ppt main
UPQC ppt mainUPQC ppt main
UPQC ppt main
 
Protection of transmission lines (distance)
Protection of transmission lines (distance)Protection of transmission lines (distance)
Protection of transmission lines (distance)
 
Tutorial on Distance and Over Current Protection
Tutorial on Distance and Over  Current ProtectionTutorial on Distance and Over  Current Protection
Tutorial on Distance and Over Current Protection
 
Transformer protection
Transformer protectionTransformer protection
Transformer protection
 
Understanding transformer vector group
Understanding transformer vector groupUnderstanding transformer vector group
Understanding transformer vector group
 
Protective relay
Protective relay Protective relay
Protective relay
 
Overcurrent protection
Overcurrent protectionOvercurrent protection
Overcurrent protection
 
Switchgear and protection 3
Switchgear and protection 3Switchgear and protection 3
Switchgear and protection 3
 
Transformers protection, an introduction
Transformers protection, an introductionTransformers protection, an introduction
Transformers protection, an introduction
 
Power Transformer Protection
Power Transformer ProtectionPower Transformer Protection
Power Transformer Protection
 
importance of reactive power in power system
importance of reactive power in power systemimportance of reactive power in power system
importance of reactive power in power system
 
220 KV Substation Operation & Maintenance
220 KV Substation Operation & Maintenance220 KV Substation Operation & Maintenance
220 KV Substation Operation & Maintenance
 
Firing angle control
Firing angle controlFiring angle control
Firing angle control
 
Thyristor Characteristics, Two Transistor Model Of Thyristor & Thyrisror Turn...
Thyristor Characteristics, Two Transistor Model Of Thyristor & Thyrisror Turn...Thyristor Characteristics, Two Transistor Model Of Thyristor & Thyrisror Turn...
Thyristor Characteristics, Two Transistor Model Of Thyristor & Thyrisror Turn...
 
Generator Protection By - Er Rahul Sharma
Generator Protection By - Er Rahul Sharma Generator Protection By - Er Rahul Sharma
Generator Protection By - Er Rahul Sharma
 
Harmonics and mitigation techniques
Harmonics and mitigation techniquesHarmonics and mitigation techniques
Harmonics and mitigation techniques
 
Er rahul sharma feeder protection
Er rahul sharma feeder protectionEr rahul sharma feeder protection
Er rahul sharma feeder protection
 

Similar to 4 PROTECTION OF ALTERNATOR.pptx

Switch Gear & Protection (2170908) (Generator Protection)
Switch Gear & Protection (2170908) (Generator Protection)Switch Gear & Protection (2170908) (Generator Protection)
Switch Gear & Protection (2170908) (Generator Protection)Abhishek Choksi
 
Rotor earth fault protection of electric generator
Rotor earth fault protection of electric generatorRotor earth fault protection of electric generator
Rotor earth fault protection of electric generatorCS V
 
SGP-4 PROTECTION OF ALTRNTR.pptx
SGP-4 PROTECTION OF ALTRNTR.pptxSGP-4 PROTECTION OF ALTRNTR.pptx
SGP-4 PROTECTION OF ALTRNTR.pptxSHIVANICHAUUHAN1
 
Directional relay & Differential relay.pptx
Directional relay & Differential relay.pptxDirectional relay & Differential relay.pptx
Directional relay & Differential relay.pptxUtthejNani1
 
New Microsoft Word Document
New Microsoft Word DocumentNew Microsoft Word Document
New Microsoft Word DocumentBarunava Sikdar
 
protection of transformer
protection of transformerprotection of transformer
protection of transformergujjarsb
 
Equipment protection
Equipment protectionEquipment protection
Equipment protectionSlides Hub
 
Generator protection by a. kato
Generator protection by a. katoGenerator protection by a. kato
Generator protection by a. katoAgrey Kato
 
Unit 04 Protection of generators and transformers
Unit  04 Protection of generators and transformers Unit  04 Protection of generators and transformers
Unit 04 Protection of generators and transformers PremanandDesai
 
33/11 KV TRANSMISSION LINE
33/11 KV TRANSMISSION LINE 33/11 KV TRANSMISSION LINE
33/11 KV TRANSMISSION LINE Lalit Kumar
 
Generator protection by bhushan kumbhalkar
Generator protection by bhushan kumbhalkarGenerator protection by bhushan kumbhalkar
Generator protection by bhushan kumbhalkarBhushan Kumbhalkar
 
HVE UNIT IV MEASUREMENT OF HIGH VOLTAGES AND HIGH CURRENTS.pptx
HVE UNIT IV MEASUREMENT OF HIGH VOLTAGES AND HIGH CURRENTS.pptxHVE UNIT IV MEASUREMENT OF HIGH VOLTAGES AND HIGH CURRENTS.pptx
HVE UNIT IV MEASUREMENT OF HIGH VOLTAGES AND HIGH CURRENTS.pptxMuthuKumar158260
 
Unit 03 Protective relays
Unit  03 Protective relaysUnit  03 Protective relays
Unit 03 Protective relaysPremanandDesai
 
Microsoft PowerPoint - Unit II.pdf
Microsoft PowerPoint - Unit II.pdfMicrosoft PowerPoint - Unit II.pdf
Microsoft PowerPoint - Unit II.pdfsrevathiap
 
Electrical Basics-VBR
Electrical Basics-VBRElectrical Basics-VBR
Electrical Basics-VBRVijay Raskar
 
Voltage sag
Voltage sagVoltage sag
Voltage sagAJAL A J
 

Similar to 4 PROTECTION OF ALTERNATOR.pptx (20)

Switch Gear & Protection (2170908) (Generator Protection)
Switch Gear & Protection (2170908) (Generator Protection)Switch Gear & Protection (2170908) (Generator Protection)
Switch Gear & Protection (2170908) (Generator Protection)
 
Rotor earth fault protection of electric generator
Rotor earth fault protection of electric generatorRotor earth fault protection of electric generator
Rotor earth fault protection of electric generator
 
SGP-4 PROTECTION OF ALTRNTR.pptx
SGP-4 PROTECTION OF ALTRNTR.pptxSGP-4 PROTECTION OF ALTRNTR.pptx
SGP-4 PROTECTION OF ALTRNTR.pptx
 
Relay
RelayRelay
Relay
 
Directional relay & Differential relay.pptx
Directional relay & Differential relay.pptxDirectional relay & Differential relay.pptx
Directional relay & Differential relay.pptx
 
New Microsoft Word Document
New Microsoft Word DocumentNew Microsoft Word Document
New Microsoft Word Document
 
protection of transformer
protection of transformerprotection of transformer
protection of transformer
 
Equipment protection
Equipment protectionEquipment protection
Equipment protection
 
Generator protection by a. kato
Generator protection by a. katoGenerator protection by a. kato
Generator protection by a. kato
 
Power quality 2
Power quality 2Power quality 2
Power quality 2
 
Unit 04 Protection of generators and transformers
Unit  04 Protection of generators and transformers Unit  04 Protection of generators and transformers
Unit 04 Protection of generators and transformers
 
33/11 KV TRANSMISSION LINE
33/11 KV TRANSMISSION LINE 33/11 KV TRANSMISSION LINE
33/11 KV TRANSMISSION LINE
 
Generator protection by bhushan kumbhalkar
Generator protection by bhushan kumbhalkarGenerator protection by bhushan kumbhalkar
Generator protection by bhushan kumbhalkar
 
HVE UNIT IV MEASUREMENT OF HIGH VOLTAGES AND HIGH CURRENTS.pptx
HVE UNIT IV MEASUREMENT OF HIGH VOLTAGES AND HIGH CURRENTS.pptxHVE UNIT IV MEASUREMENT OF HIGH VOLTAGES AND HIGH CURRENTS.pptx
HVE UNIT IV MEASUREMENT OF HIGH VOLTAGES AND HIGH CURRENTS.pptx
 
Unit 03 Protective relays
Unit  03 Protective relaysUnit  03 Protective relays
Unit 03 Protective relays
 
Microsoft PowerPoint - Unit II.pdf
Microsoft PowerPoint - Unit II.pdfMicrosoft PowerPoint - Unit II.pdf
Microsoft PowerPoint - Unit II.pdf
 
Electrical Basics-VBR
Electrical Basics-VBRElectrical Basics-VBR
Electrical Basics-VBR
 
T&D_Unit V.pdf
T&D_Unit V.pdfT&D_Unit V.pdf
T&D_Unit V.pdf
 
AC Generators
AC GeneratorsAC Generators
AC Generators
 
Voltage sag
Voltage sagVoltage sag
Voltage sag
 

Recently uploaded

What are the advantages and disadvantages of membrane structures.pptx
What are the advantages and disadvantages of membrane structures.pptxWhat are the advantages and disadvantages of membrane structures.pptx
What are the advantages and disadvantages of membrane structures.pptxwendy cai
 
GDSC ASEB Gen AI study jams presentation
GDSC ASEB Gen AI study jams presentationGDSC ASEB Gen AI study jams presentation
GDSC ASEB Gen AI study jams presentationGDSCAESB
 
main PPT.pptx of girls hostel security using rfid
main PPT.pptx of girls hostel security using rfidmain PPT.pptx of girls hostel security using rfid
main PPT.pptx of girls hostel security using rfidNikhilNagaraju
 
chaitra-1.pptx fake news detection using machine learning
chaitra-1.pptx  fake news detection using machine learningchaitra-1.pptx  fake news detection using machine learning
chaitra-1.pptx fake news detection using machine learningmisbanausheenparvam
 
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...Dr.Costas Sachpazis
 
🔝9953056974🔝!!-YOUNG call girls in Rajendra Nagar Escort rvice Shot 2000 nigh...
🔝9953056974🔝!!-YOUNG call girls in Rajendra Nagar Escort rvice Shot 2000 nigh...🔝9953056974🔝!!-YOUNG call girls in Rajendra Nagar Escort rvice Shot 2000 nigh...
🔝9953056974🔝!!-YOUNG call girls in Rajendra Nagar Escort rvice Shot 2000 nigh...9953056974 Low Rate Call Girls In Saket, Delhi NCR
 
Software and Systems Engineering Standards: Verification and Validation of Sy...
Software and Systems Engineering Standards: Verification and Validation of Sy...Software and Systems Engineering Standards: Verification and Validation of Sy...
Software and Systems Engineering Standards: Verification and Validation of Sy...VICTOR MAESTRE RAMIREZ
 
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...Soham Mondal
 
Application of Residue Theorem to evaluate real integrations.pptx
Application of Residue Theorem to evaluate real integrations.pptxApplication of Residue Theorem to evaluate real integrations.pptx
Application of Residue Theorem to evaluate real integrations.pptx959SahilShah
 
microprocessor 8085 and its interfacing
microprocessor 8085  and its interfacingmicroprocessor 8085  and its interfacing
microprocessor 8085 and its interfacingjaychoudhary37
 
Call Girls Delhi {Jodhpur} 9711199012 high profile service
Call Girls Delhi {Jodhpur} 9711199012 high profile serviceCall Girls Delhi {Jodhpur} 9711199012 high profile service
Call Girls Delhi {Jodhpur} 9711199012 high profile servicerehmti665
 
IVE Industry Focused Event - Defence Sector 2024
IVE Industry Focused Event - Defence Sector 2024IVE Industry Focused Event - Defence Sector 2024
IVE Industry Focused Event - Defence Sector 2024Mark Billinghurst
 
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escortsranjana rawat
 
Artificial-Intelligence-in-Electronics (K).pptx
Artificial-Intelligence-in-Electronics (K).pptxArtificial-Intelligence-in-Electronics (K).pptx
Artificial-Intelligence-in-Electronics (K).pptxbritheesh05
 
Oxy acetylene welding presentation note.
Oxy acetylene welding presentation note.Oxy acetylene welding presentation note.
Oxy acetylene welding presentation note.eptoze12
 
Current Transformer Drawing and GTP for MSETCL
Current Transformer Drawing and GTP for MSETCLCurrent Transformer Drawing and GTP for MSETCL
Current Transformer Drawing and GTP for MSETCLDeelipZope
 
Introduction to Microprocesso programming and interfacing.pptx
Introduction to Microprocesso programming and interfacing.pptxIntroduction to Microprocesso programming and interfacing.pptx
Introduction to Microprocesso programming and interfacing.pptxvipinkmenon1
 
power system scada applications and uses
power system scada applications and usespower system scada applications and uses
power system scada applications and usesDevarapalliHaritha
 

Recently uploaded (20)

What are the advantages and disadvantages of membrane structures.pptx
What are the advantages and disadvantages of membrane structures.pptxWhat are the advantages and disadvantages of membrane structures.pptx
What are the advantages and disadvantages of membrane structures.pptx
 
GDSC ASEB Gen AI study jams presentation
GDSC ASEB Gen AI study jams presentationGDSC ASEB Gen AI study jams presentation
GDSC ASEB Gen AI study jams presentation
 
main PPT.pptx of girls hostel security using rfid
main PPT.pptx of girls hostel security using rfidmain PPT.pptx of girls hostel security using rfid
main PPT.pptx of girls hostel security using rfid
 
chaitra-1.pptx fake news detection using machine learning
chaitra-1.pptx  fake news detection using machine learningchaitra-1.pptx  fake news detection using machine learning
chaitra-1.pptx fake news detection using machine learning
 
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
 
🔝9953056974🔝!!-YOUNG call girls in Rajendra Nagar Escort rvice Shot 2000 nigh...
🔝9953056974🔝!!-YOUNG call girls in Rajendra Nagar Escort rvice Shot 2000 nigh...🔝9953056974🔝!!-YOUNG call girls in Rajendra Nagar Escort rvice Shot 2000 nigh...
🔝9953056974🔝!!-YOUNG call girls in Rajendra Nagar Escort rvice Shot 2000 nigh...
 
Software and Systems Engineering Standards: Verification and Validation of Sy...
Software and Systems Engineering Standards: Verification and Validation of Sy...Software and Systems Engineering Standards: Verification and Validation of Sy...
Software and Systems Engineering Standards: Verification and Validation of Sy...
 
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
 
Application of Residue Theorem to evaluate real integrations.pptx
Application of Residue Theorem to evaluate real integrations.pptxApplication of Residue Theorem to evaluate real integrations.pptx
Application of Residue Theorem to evaluate real integrations.pptx
 
9953056974 Call Girls In South Ex, Escorts (Delhi) NCR.pdf
9953056974 Call Girls In South Ex, Escorts (Delhi) NCR.pdf9953056974 Call Girls In South Ex, Escorts (Delhi) NCR.pdf
9953056974 Call Girls In South Ex, Escorts (Delhi) NCR.pdf
 
microprocessor 8085 and its interfacing
microprocessor 8085  and its interfacingmicroprocessor 8085  and its interfacing
microprocessor 8085 and its interfacing
 
Call Girls Delhi {Jodhpur} 9711199012 high profile service
Call Girls Delhi {Jodhpur} 9711199012 high profile serviceCall Girls Delhi {Jodhpur} 9711199012 high profile service
Call Girls Delhi {Jodhpur} 9711199012 high profile service
 
IVE Industry Focused Event - Defence Sector 2024
IVE Industry Focused Event - Defence Sector 2024IVE Industry Focused Event - Defence Sector 2024
IVE Industry Focused Event - Defence Sector 2024
 
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
 
Artificial-Intelligence-in-Electronics (K).pptx
Artificial-Intelligence-in-Electronics (K).pptxArtificial-Intelligence-in-Electronics (K).pptx
Artificial-Intelligence-in-Electronics (K).pptx
 
★ CALL US 9953330565 ( HOT Young Call Girls In Badarpur delhi NCR
★ CALL US 9953330565 ( HOT Young Call Girls In Badarpur delhi NCR★ CALL US 9953330565 ( HOT Young Call Girls In Badarpur delhi NCR
★ CALL US 9953330565 ( HOT Young Call Girls In Badarpur delhi NCR
 
Oxy acetylene welding presentation note.
Oxy acetylene welding presentation note.Oxy acetylene welding presentation note.
Oxy acetylene welding presentation note.
 
Current Transformer Drawing and GTP for MSETCL
Current Transformer Drawing and GTP for MSETCLCurrent Transformer Drawing and GTP for MSETCL
Current Transformer Drawing and GTP for MSETCL
 
Introduction to Microprocesso programming and interfacing.pptx
Introduction to Microprocesso programming and interfacing.pptxIntroduction to Microprocesso programming and interfacing.pptx
Introduction to Microprocesso programming and interfacing.pptx
 
power system scada applications and uses
power system scada applications and usespower system scada applications and uses
power system scada applications and uses
 

4 PROTECTION OF ALTERNATOR.pptx

  • 1. PROTECTION OF ALTERNATOR • Abnormalities & Faults • Circuit diagram with proper current direction of Differential protection. • Over current, earth fault, inter -turn fault, negative phase sequence, over heating protection. • Reverse power protections. • Simple numerical on differential protection
  • 2. INTRODUCTION • Generator is a large machine and is connected to busbars. It is accompanied by unit-transformers, auxiliary transformer and bus system. • It is accompanied by excitation system, prime mover, voltage regulator, cooling system etc; • Hence it is not a single equipment. The protection of generator should be coordinated with associated equipment. • It is a costly and important equipment. It should not be shut off as far possible because that would result in power shortage and emergency. • Modern Turbo-generators have the following typical ratings! 60 MW 11.8 kV 120 MW 13.8 kV 500 MW 22 kV • Generator unit up to 500 MW have been installed in India.
  • 3. ABNORMALITIES & FAULTS • Some of the important faults which may occur on an alternator are : i. Failure of prime-mover ii. Failure of field iii. Over current iv. Over speed v. Overvoltage vi. unbalanced loading vii. Stator winding faults
  • 4. • Failure of prime-mover. When input to the prime-mover fails, the alternator runs as a synchronous motor and draws some current from the supply system. This motoring conditions is known as "inverted running". • Protection against motoring is achieved by applying reverse power relays to the alternators which isolate the latter during their motoring action. • The chances of field failure of alternators are undoubtedly very rare. • It is sufficient to rely on the control room attendant to disconnect the faulty alternator manually from the system bus-bars. Therefore no need to provide automatic protection against field failure. • Over-current occurs mainly due to partial breakdown of winding insulation or due to overload on the supply system. • Alternators with very high values of internal impedance are designed so that they will stand a complete short-circuit at their terminals for sufficient time without serious overheating. • Overload protection for alternators is that such a protection might disconnect the alternators from the power plant bus on account of some momentary troubles outside the plant
  • 5. ABNORMALITIES & FAULTS • Over-speed The chief cause of over-speed is the sudden loss of all or the major part of load on the alternator. • Alternators are usually provided with mechanical centrifugal devices mounted on their driving shafts to trip the main valve of the prime-mover when a dangerous over-speed occurs. • Over-voltage The field excitation system of modern alternators is so designed that over-voltage conditions at normal running speeds cannot occur. However, overvoltage in an alternator occurs when speed of the prime-mover increases due to sudden loss of the alternator load. • a usual practice to provide over-voltage protection on hydro-generator units. • Over-voltage relays are operated from a voltage supply taken from the generator terminals • When the generated voltage rises 20% above the normal value, they operate
  • 6. ABNORMALITIES & FAULTS • Unbalanced loading means that there are different phase currents in the alternator. • It arises from faults to earth or faults between phases on the circuit external to the alternator. • Severely burn the mechanical fixings of the rotor core or damage the field winding
  • 7. ABNORMALITIES & FAULTS • Stator winding faults occur mainly due to the insulation failure of the stator windings. • The main types of stator winding faults, in order of importance are : – Fault between phase and ground – Fault between phases – Inter-turn fault involving turns of the same phase winding • For protection of alternators against such faults, differential method of protection (also knows as Merz-Price system) is most commonly employed due to its greater sensitivity and reliability
  • 9. DIFFERENTIAL PROTECTION OF ALTERNATORS • Schematic arrangement. Above Fig. shows the schematic arrangement of current differential protection for a 3-phase alternator. • Identical current transformer pairs CT' and CT2 are placed on either side of each phase of the stator windings. • The secondary's of each set of current transformers are connected in star. • The two neutral points and the corresponding terminals of the two star groups being connected together by means of a four-core pilot cable. • There is an independent path for the currents circulating in each pair of current transformers and the corresponding pilot. • The relay coils are connected in star, • The neutral point of relay being connected to the current-transformer common neutral and the outer ends one to each of the other three pilots.
  • 10. • Operation. Under normal operating conditions, the current at both ends of each winding will be equal and hence the currents in the secondary's of two CTs connected in any phase will also be equal. • Balanced circulating current in the pilot wires therefore no current flows through the operating coils (R1, R2 and R3) of the relays. • Suppose an earth fault occurs on phase R due to breakdown of its insulation to earth as shown in fig. • The current in the affected phase winding will flow through the core and frame of the machine to earth, the circuit being completed through the neutral earthing resistance. • The currents in the secondaries of the two CTs in phase R will become unequal and the difference of the two currents will flow through the corre- sponding relay coil (i.E. R1), • Returning via the neutral pilot. Consequently, the relay operates to trip the circuit breaker. DIFFERENTIAL PROTECTION OF ALTERNATORS
  • 11. DIFFERENTIAL PROTECTION OF ALTERNATORS • Imagine that now a short-circuit fault occurs between the phases Y and B as shown in Fig. The short-circuit current circulates via the neutral end connection through the two windings and through the fault as shown by the dotted arrows. • The currents in the secondaries of two CTs in each affected phase will become unequal and the differ-ential current will flow through the operating coils of the relays (i.e. R2 and R3) con-nected in these phases. • The relay then closes its contacts to trip the circuit breaker.
  • 12. If a fault occurs between two phases, the out of-balance current will circulate round the two transformer secondary's via any two of the coils PA, BR, PC (the pair being decided by the two phases that are faulty) without passing through the earth relay ER.
  • 13. MODIFIED DIFFERENTIAL PROTECTION FOR ALTERNATORS • If the neutral point of a star-connected alternator is earthed through a high resistance, protection schemes shown in Fig. it will not provide sufficient sensitivity for earth-faults. • It is because the high earthing resistance will limit the earth-fault currents to a low value, necessitating relays with low current settings if adequate portion of the generator winding is to be protected. • Consist of two relays for phase-fault protection and the third for earth-fault protection only. • The two phase elements (PC and PA) and balancing resistance (BR) are connected in star and the earth relay (ER) is connected between this star point and the fourth wire of circulating current pilot-circuit.
  • 14. • Under normal operating conditions, currents at the two ends of each stator winding will be equal. • Therefore, there is a balanced circulating current in the phase pilot wires and no current flows through the operating coils of the relays. • If an earth-fault occurs on any one phase, the out-of-balance secondary current in CTs in that phase will flow through the earth relay ER and via pilot S 1 or S2 to the neutral of the current transformers. • This will cause the operation of earth relay only. • If a fault occurs between two phases, the out of-balance current will circulate round the two transformer secondary's via any two of the coils PA, BR, PC (the pair being decided by the two phases that are faulty) without passing through the earth relay ER. • Therefore, only the phase-fault relays will operate. MODIFIED DIFFERENTIAL PROTECTION FOR ALTERNATORS
  • 16. • With resistance earthing, it is not possible to protect complete winding from earth-fault and the % of winding protected depends on the value of neutral earthing resistor • Earth faults are not likely to occur near the neutral point due to less voltage w.r.t. earth. • It is a usual practice to protect about 80 to 85% of generator winding against earth-faults. • The remaining 20 to 15% winding from neutral side left un-protected by the differential protection
  • 17. • During earth-fault If in the alternator winding, the current, If flows through a part of the generator winding and neutral to ground circuit. The corresponding secondary current Is flows through the operating coil and restricted earth-fault coil of the differential protection. • If point is nearer to terminal a (nearer to the neutral point) the forcing voltage Vaf will be relatively less. Hence earth fault current If will reduce.
  • 18.
  • 20. BALANCED EARTH-FAULT PROTECTION • It consists of three line current transformers, one mounted in each phase, having their secondary's connected in parallel with that of a single current transformer in the conductor joining the star point of the alternator to earth. • Under normal operating conditions, the currents flowing in the alternator leads and hence the currents flowing in secondaries of the line current transformers add to zero and no current flows through the relay. • Also under these conditions, the current in the neutral wire is zero and the secondary of neutral current transformer supplies no current to the relay.
  • 21. • If an earth-fault develops at F2 external to the protected zone, the sum of the currents at the terminals of the alternator is exactly equal to the current in the neutral connection and hence no current flows through the relay. • When an earth-fault occurs at F1 or within the protected zone, these currents are no longer equal and the differential current flows through the operating coil of the relay. • The relay then closes its contacts to disconnect the alternator from the system. BALANCED EARTH-FAULT PROTECTION
  • 22. STATOR INTER-TURN PROTECTION • Merz-price circulating-current system protects against phase-to-ground and phase-to-phase faults. It does not protect against turn-to-turn fault on the same phase winding of the stator. • It is because the current that this type of fault produces flows in a local circuit between the turns involved • Does not create a difference between the currents entering and leaving the winding at its two ends where current transformers are applied. • In single turn generator (e.g. large steam-turbine generators), there is no necessity of protection against inter-turn faults. • However, inter-turn protection is provided for multi-turn generators such as hydro-electric generators. • These generators have double-winding armatures (i.e. each phase winding is divided into two halves) owing to the very heavy currents which they have to carry.
  • 23. STATOR INTER-TURN PROTECTION • Shows the duplicate stator windings Si and S2 of one phase only with a provision against inter-turn faults. • Two current transformers are connected on the circulating-current principle. • Under normal conditions, the currents in the stator windings si and s2 are equal and so will be the currents in the secondaries of the two cts. • The secondary current round the loop then is the same at all ct points and no current flows through the relay r1. • If a short-circuit develops between adjacent turns, say on si, the currents in the stator windings si and s2 will no longer be equal. • Therefore, unequal currents will be induced in the secondaries of cts and the difference of these two currents flows through the relay ri. The relay then closes its contacts to clear the generator from the system.
  • 24. • In this case, the stator winding has two separate parallel paths. The current transformer primaries are inserted in these paths and the secondaries are cross- connected. During inter-turn fault in the phase winding, the out-of balance current CT secondaries flows through the relay. Such a protection can be extremely sensitive. However it can be employed to generators with parallel winding for each phase.
  • 25. NEGATIVE PHASE SEQUENCE PROTECTION OF GENRATORS • Unbalanced 3-phase stator currents cause double frequency currents to be induced in rotor. • They cause heating of rotor and also cause vibrations of stator. • Unbalanced 3-phase stator currents have negative sequence component. • This component rotates at synchronous speed in a direction opposite to the direction of rotation of rotor. • Negative sequence filter with over current relay provide s protection against un balanced loads.
  • 27. NEGATIVE PHASE SEQUENCE CIRCUIT • The twin windings of two auxiliary CT’s are connected to main (line) CT’s in such a way that under normal balanced load conditions currents Ia Ib Ic flow in the direction shown in the figure. • Impedance Z1 and Z2 are connected across auxiliary CT’s T1 and T2. • Load impedance ZL i.e. over current relay is connected across terminal XX. • Under normal condition current through T1 Ib – Ic and T2 will be Ia – Ib. • The values of Z1 and Z2 are such that under normal condition voltage at point P and R remains same. i.e. the voltages across QR and QP is equal and opposite. • Under unbalanced conditions this voltage changes and a output voltage is produced across XX so as to operate over current relay.