Electric Machines I
Three Phase Transformers
1
Dr. Firas Obeidat
2
Table of contents
1 • Introduction
2 • Wye-Wye Connection
3 • Wye-Delta Connection
4 • Delta-Wye Connection
5 • Delta-Delta Connection
6 • Polarity of a Transformer
7 • Parallel Operation of Transformers
8 • Transformer Vector Group
Dr. Firas Obeidat Faculty of Engineering Philadelphia University
3
Dr. Firas Obeidat Faculty of Engineering Philadelphia University
Introduction
 A three-phase power transformer is used at the
power generating station to step-up the voltage.
Whereas in the power distribution substation,
the three-phase voltage is again stepped down
through a three-phase distribution transformer.
 A three-phase transformer can be made either
by three windings wound on a common core or
by three single-phase transformer connected
together in a three-phase bank.
 The first approach is a cheaper one that results
in a transformer with smaller size and less
weight. The main disadvantage of the first
approach is that if one phase becomes defective,
then the whole transformer needs to be
replaced. Whereas in the second approach, if
one of the transformers becomes defective then
the system can be given power by an open delta
at a reduced capacity. In this case, the defective
transformer is normally replaced by a new one.
4
Dr. Firas Obeidat Faculty of Engineering Philadelphia University
Introduction
The primary and secondary windings of the transformer may be connected
in either by wye (Y) or delta (Δ).
Three-phase transformer connections
Y-Y
(Wye-Wye)
Y-Δ
(Wye-Delta)
Δ-Y
(Delta-Wye)
Δ-Δ
(Delta-Delta)
5
Dr. Firas Obeidat Faculty of Engineering Philadelphia University
Wye-Wye Connection
At the primary side, the phase voltage can be written as,
At the secondary side, the phase voltage can be written as,
The ratio of the primary
line voltage to the
secondary line voltage of
this connection is,
6
Dr. Firas Obeidat Faculty of Engineering Philadelphia University
Wye-Wye Connection
The Y- Y connection has two very serious problems
1) If loads on the transformer circuit are unbalanced, then the voltages on
the phases of the transformer can become severely unbalanced.
2) Third-harmonic voltages can be large.
If a three-phase set of voltages is applied to a Y- Y transformer, the voltages
in any phase will be 120o apart from the voltages in any other phase.
However, the third-harmonic components of each of the three phases will be
in phase with each other. There are always some third-harmonic components
in a transformer because of the nonlinearity of the core, and these
components add up. The result is a very large third-harmonic component of
voltage on top of the 50-ar 60-Hz fundamental voltage. This third-harmonic
voltage can be larger than the fundamental voltage itself.
This type of connection of a three-phase transformer is rarely used for large
amount of power transmission.
7
Dr. Firas Obeidat Faculty of Engineering Philadelphia University
Wye-Wye Connection
Unbalance problem and the third-harmonic problem can
be solved by:
• Solidly ground the neutrals of the transformers, especially the primary
winding's neutral. This connection permits the additive third-harmonic
components to cause a current flow in the neutral instead of building up
large voltages. The neutral also provides a return path for any current
imbalances in the load.
• Add a third (tertiary) winding connected in Δ to the transformer bank. If a
third Δ-connected winding is added to the transformer. then the third-
harmonic components of voltage in the Δ will add up, causing a circulating
current flow within the winding. This suppresses the third-harmonic
components of voltage in the same manner as grounding the transformer
neutrals. The Δ-connected tertiary windings need not even be brought out
of the transformer case, but they often are used to supply lights and
auxiliary power within the substation where it is located. The tertiary
windings must be large enough to handle the circulating currents, so they
are usually made about one-third the power rating of the two main
windings.
8
Dr. Firas Obeidat Faculty of Engineering Philadelphia University
Wye-Wye Connection
Advantages Disadvantages
Magnetizing current of transformer
has 3rd harmonic component
The third harmonic present in the
alternator voltage may appear on the
secondary side. This causes
distortion in the secondary phase
voltages
If the load on the secondary side
unbalanced then the shifting of
neutral point is possible
Less dielectric strength in insulating
materials
phase voltage is less
Cross section of winding is large i.e.
stronger to bear stress during short
circuit
Line current is equal to phase
current
Requires less turns per winding ie
cheaper
Phase voltage is 1/√3 times of line
voltage
9
Dr. Firas Obeidat Faculty of Engineering Philadelphia University
Wye-Delta Connection
The expression of the primary line voltage is
At the secondary side, the line voltage is
The ratio of primary phase voltage to secondary phase voltage is
The ratio of primary line voltage to secondary line voltage is
The primary phase current is
The turns ratio is
10
Dr. Firas Obeidat Faculty of Engineering Philadelphia University
Wye-Delta Connection
The expression of the secondary phase current is
The secondary line current is
 This connection does have one problem; Because of the connection, the
secondary voltage is shifted 30° relative to the primary voltage of the
transformer. The fact that a phase shift has occurred can cause problems in
paralleling the secondaries of two transformer banks together. The phase
angles of transformer secondaries must be equal if they are to be paralleled,
which means that attention must be paid to the direction of the 30o phase
shift occurring in each transformer bank to be paralleled together.
 The connection will cause the secondary voltage to be lagging if the system
phase sequence is abc. If the system phase sequence is acb, then the
connection will cause the secondary voltage to be leading the primary voltage
by 30o.
11
Dr. Firas Obeidat Faculty of Engineering Philadelphia University
Wye-Delta Connection
Advantages Disadvantages
12
Dr. Firas Obeidat Faculty of Engineering Philadelphia University
Delta-Wye Connection
The expression of the primary line voltage is
The line voltage at the secondary side is
The ratio of primary line voltage to secondary line voltage is
The phase current at the primary side is
For this connection, the turns ratio is
In this case, the secondary phase
current is
The secondary line current is
13
Dr. Firas Obeidat Faculty of Engineering Philadelphia University
Delta-Wye Connection
Advantages Disadvantages
14
Dr. Firas Obeidat Faculty of Engineering Philadelphia University
Delta-Delta Connection
The expression of the primary line voltage is
The line voltage at the secondary side is
The ratio of primary line voltage to secondary line voltage is
The secondary line current is
The output capacity in delta-delta
connection can be expressed as
and
𝑆 = 3𝑉𝐿𝐼𝐿 = 3𝑉
𝑝𝐼𝑝
𝑝 = 3𝑉𝐿𝐼𝐿𝑐𝑜𝑠θ = 3𝑉
𝑝𝐼𝑝𝑐𝑜𝑠θ
15
Dr. Firas Obeidat Faculty of Engineering Philadelphia University
Delta-Delta Connection
Advantages Disadvantages
16
Dr. Firas Obeidat Faculty of Engineering Philadelphia University
Three Phase Transformers
Primary winding Secondary winding
Primary winding Secondary winding
Primary winding Secondary winding
Primary winding Secondary winding
√3V
I
V
aI
V/a
√3V/a
I
V
√3V
√3aI
V/a
aI
√3I
I
V
aI
V/a
√3V/a
√3I
I
V
√3aI
V/a
aI
The relations between three phase current/voltage and single phase current/voltage
17
Dr. Firas Obeidat Faculty of Engineering Philadelphia University
Three Phase Transformers
Example: A three-phase transformer is connected to an 11 kV supply and
draws 6 A current. Determine
(i) line voltage at the secondary side,
(ii) the line current in the secondary coil.
Consider the turns ratio of the transformer is 11.
Also, consider delta-wye and wye-delta connections.
1- For delta-wye connection
𝐼𝑝1 =
𝐼𝐿1
3
=
6
3
= 3.46 𝐴
18
Dr. Firas Obeidat Faculty of Engineering Philadelphia University
Three Phase Transformers
2- For wye-delta connection
𝐼𝐿2 = 𝐼𝑝2 = 𝑎𝐼𝑝1 = 11 × 3.46 = 38 𝐴
19
Dr. Firas Obeidat Faculty of Engineering Philadelphia University
Polarity of a Transformer
Polarity of a transformer is defined as the relative directions of induced
voltages between the high voltage and low voltage terminals.
 The polarity of a transformer is very
important to construct three-phase
transformer bank, parallel connection of
transformer, connection of current
transformer (CT) and potential transformer
(PT) power with metering device.
 Two polarities namely additive and
subtractive are used in the transformer.
 A polarity of a transformer is said to be an
additive if the measured voltage between the
high voltage and the low voltage terminals is
greater than the supply voltage at the high
voltage terminals.
 A polarity is said to be a subtractive if the
measured voltage between the high voltage
and the low voltage terminals is lower than the
supply voltage at the high voltage terminals.
Subtractive polarity
Additive polarity
20
Dr. Firas Obeidat Faculty of Engineering Philadelphia University
Polarity of a Transformer
 Consider a 220/110V single-phase
transformer with the high voltage
and the low voltage terminals for
testing polarities. The high voltage
terminal H1 is connected to the low
voltage terminal X1 by a cable. The
voltmeter is connected between H2
and X2. In this case, the turns ratio
of the transformer is,
V1/V2=220/110=2.
 A voltage of 110 V is applied to the
primary side. In this case, a voltage
of 55 V (110/2) will appear at the
secondary terminals. If the meter
read out the voltage of 165 V (110 +
55) then the transformer is said to
be in additive polarity.
 If the voltmeter reads the voltage of
55V (110−55) then the transformer
is said to be in subtractive polarity.
Testing for additive polarity
Testing for subtractive polarity
21
Dr. Firas Obeidat Faculty of Engineering Philadelphia University
Parallel Operation of Transformers
 For supplying a load in excess of the rating
of an existing transformer, two or more
transformers may be connected in parallel
with the existing transformer.
 The transformers are connected in
parallel when load on one of the
transformers is more than its capacity.
The reliability is increased with parallel
operation than to have single larger unit.
 The cost associated with maintaining the
spares is less when two transformers are
connected in parallel.
 It is usually economical to install another transformer in parallel instead of
replacing the existing transformer by a single larger unit. The cost of a spare
unit in the case of two parallel transformers (of equal rating) is also lower
than that of a single large transformer. In addition, it is preferable to have a
parallel transformer for the reason of reliability. With this at least half the
load can be supplied with one transformer out of service.
22
Dr. Firas Obeidat Faculty of Engineering Philadelphia University
Parallel Operation of Transformers
Advantages Disadvantages
the parallel transformers may have
very low impedance, which creates
the high short circuit currents
The bus ratings could be too high
The risk of circulating currents
running from one transformer to
another Transformer
Increasing short-circuit currents
that increase necessary breaker
capacity
Maximize electrical system
flexibility
Maximize power system reliability
Maximize electrical system
availability
Maximize electrical system
efficiency
23
Dr. Firas Obeidat Faculty of Engineering Philadelphia University
Parallel Operation of Transformers
Condition for Parallel Operation of Transformer:
1- The voltage rating of both primaries and secondaries should be identical,
i.e. the transformers should have the same turn ratio.
 If the transformers connected in parallel have slightly different voltage
ratios, then due to the inequality of induced emfs in the secondary
windings, a circulating current will flow in the loop formed by the
secondary windings under the no-load condition, which may be much
greater than the normal no-load current.
 The current will be quite high as the leakage impedance is low. When the
secondary windings are loaded, this circulating current will tend to
produce unequal loading on the two transformers, and it may not be
possible to take the full load from this group of two parallel transformers
(one of the transformers may get overloaded).
 A small voltage difference may cause sufficiently high circulating current
causing unnecessary extra I2R loss.
24
Dr. Firas Obeidat Faculty of Engineering Philadelphia University
Parallel Operation of Transformers
Condition for Parallel Operation of Transformer:
2- The percentage impedances should be equal in magnitude and have same
X/R ratio in order to avoid circulating currents and operation in different
power factor.
 If this condition is not satisfied then the impedance triangles are not
identical in shape and size, parallel operation will still be possible, but the
power factor at which the two transformers operate will be different (one
transformer will operate with higher power factor and the other with
lower power factor) from the power factor of the common load. In this
case the two transformers will not share the load in proportion to their
KVA ratings.
25
Dr. Firas Obeidat Faculty of Engineering Philadelphia University
Parallel Operation of Transformers
Condition for Parallel Operation of Transformer:
3- The polarity of the two transformers should be the same.
 Polarity of transformer means the instantaneous direction of induced emf
in secondary. If the instantaneous directions of induced secondary emf in
two transformers are opposite to each other when same input power is fed
to the both of the transformers, the transformers are said to be in opposite
polarity.
 The transformers should be properly connected with regard to their
polarity. If they are connected with incorrect polarities then the two emfs,
induced in the secondary windings which are in parallel, will act together
in the local secondary circuit and produce a short circuit.
 Polarity of all transformers run in parallel should be same otherwise huge
circulating current flows in the transformer but no load will be fed from
these transformers.
 If the instantaneous directions of induced secondary emf in two
transformers are same when same input power is fed to the both of the
transformers, the transformers are said to be in same polarity. Inside the
loop formed by the two secondaries the resulting voltage must be zero.
26
Dr. Firas Obeidat Faculty of Engineering Philadelphia University
Parallel Operation of Transformers
Condition for Parallel Operation of Transformer:
3- The polarity of the two transformers should be the same.
4- Phase sequences and phase angle shifts must be the same (for three-phase
transformer).
The transformer windings cab be connected in variety of ways which
produce different magnitudes and phase displacement of secondary voltages
27
Dr. Firas Obeidat Faculty of Engineering Philadelphia University
Parallel Operation of Transformers
Overall summary of different connection types of parallel transformers
Transformer
Parallel
Connection Types
Equal
Loading
Unequal
Loading
Overloading
Concerns
Circulating
Currents
Recommended
Connection
Equal impedances—
Equal ratios— Same kVA
Yes No No No Yes
Equal impedances—
Equal ratios— Different
kVA
No Yes No No Yes
Unequal impedances—
Equal ratios— Same kVA
No Yes Yes No No
Unequal impedances—
Equal ratios— Different
kVA
No Yes Yes No No
Unequal impedances—
Unequal ratios— Same
kVA
Yes No Yes Yes No
Unequal impedances—
Unequal ratios—
Different kVA
No Yes Yes Yes No
28
Dr. Firas Obeidat Faculty of Engineering Philadelphia University
Parallel Operation of Transformers
Case I: Equal Impedances-Equal Ratios-Same kVA
𝐼 = 𝐼𝐴 + 𝐼𝐵
𝐼𝐴 =
𝑍𝐵
𝑍𝐴 + 𝑍𝐵
𝐼
𝐼𝐵 =
𝑍𝐴
𝑍𝐴 + 𝑍𝐵
𝐼
𝑉2 = 𝐸 − 𝐼𝐴 𝑍𝐴 = 𝐸 − 𝐼𝐵𝑍𝐵 = 𝐸 − 𝐼𝑍𝐴𝐵
𝐼𝐴 𝑍𝐴 = 𝐼𝐵𝑍𝐵
𝐼𝐴
𝐼𝐵
=
𝑍𝐵
𝑍𝐴
Case II: Equal Impedances-Equal Ratios-Different kVA
29
Dr. Firas Obeidat Faculty of Engineering Philadelphia University
Parallel Operation of Transformers
Case I: Equal Impedances-Equal Ratios-Same kVA
𝐼𝐴 =
𝐾𝑉𝐴𝐴/%𝑍𝐴
𝐾𝑉𝐴𝐴/%𝑍𝐴 +𝐾𝑉𝐴𝐵/%𝑍𝐵
𝐼
𝐼𝐵 =
𝐾𝑉𝐴𝐵/%𝑍𝐵
𝐾𝑉𝐴𝐴/%𝑍𝐴 +𝐾𝑉𝐴𝐵/%𝑍𝐵
𝐼
𝐾𝑉𝐴𝐴 =
𝐾𝑉𝐴𝐴/%𝑍𝐴
𝐾𝑉𝐴𝐴/%𝑍𝐴 +𝐾𝑉𝐴𝐵/%𝑍𝐵
𝐾𝑉𝐴𝐿𝑜𝑎𝑑
𝐾𝑉𝐴𝐵 =
𝐾𝑉𝐴𝐵/%𝑍𝐵
𝐾𝑉𝐴𝐴/%𝑍𝐴 +𝐾𝑉𝐴𝐵/%𝑍𝐵
𝐾𝑉𝐴𝐿𝑜𝑎𝑑
%𝑍𝑇 =
𝑍𝑇𝐼𝑇
𝑉𝑇
× 100 =
𝑍𝑇
𝑉𝑇
2 𝑆𝑇 × 100
Where:
IA = load current from transformer A
IB = load current from transformer B
% ZA = % impedance of transformer A
% ZB = % impedance of transformer B
kVAA = kVA rating of transformer A
kVAB = kVA rating of transformer B
% ZT = % impedance of any transformer
IT = rated current of any transformer
VT = rated voltage of any transformer
ST = KVA rating of any transformer
Case II: Equal Impedances-Equal Ratios-Different kVA
30
Dr. Firas Obeidat Faculty of Engineering Philadelphia University
Parallel Operation of Transformers
Case III: Unequal Impedances-Equal Ratios-Same kVA
Case IV: Unequal Impedances-Equal Ratios-Different kVA
The equations for case III
and Case IV are the same
equations for case I and
case II.
31
Dr. Firas Obeidat Faculty of Engineering Philadelphia University
Parallel Operation of Transformers
Example: Connecting two 2000 kVA, 5.75% impedance transformers in
parallel, each with the same turn ratios to a 4000 kVA load. What is the
loading on the transformers?
𝐾𝑉𝐴𝐴 = 𝐾𝑉𝐴𝐵 =
𝐾𝑉𝐴𝐴/%𝑍𝐴
𝐾𝑉𝐴𝐴/%𝑍𝐴 +𝐾𝑉𝐴𝐵/%𝑍𝐵
𝐾𝑉𝐴𝐿𝑜𝑎𝑑
𝐾𝑉𝐴𝐴 = 𝐾𝑉𝐴𝐵 =
2000/5.75
2000/5.75+2000/5.75
× 4000 =
348
348+348
× 4000 = 2000 𝐾𝑉𝐴
Example: Connecting 3000 kVA and 1000 kVA transformers in parallel, each
with 5.75% impedance, each with the same turn ratios, connected to a
common 4000 kVA load. What is the loading on each transformer?
𝐾𝑉𝐴𝐴 =
𝐾𝑉𝐴𝐴/%𝑍𝐴
𝐾𝑉𝐴𝐴/%𝑍𝐴 +𝐾𝑉𝐴𝐵/%𝑍𝐵
𝐾𝑉𝐴𝐿𝑜𝑎𝑑
=
3000/5.75
3000/5.75+1000/5.75
× 4000 = 3000 𝐾𝑉𝐴
32
Dr. Firas Obeidat Faculty of Engineering Philadelphia University
Parallel Operation of Transformers
𝐾𝑉𝐴𝐵 =
𝐾𝑉𝐴𝐵/%𝑍𝐵
𝐾𝑉𝐴𝐴/%𝑍𝐴 +𝐾𝑉𝐴𝐵/%𝑍𝐵
𝐾𝑉𝐴𝐿𝑜𝑎𝑑
=
1000/5.75
3000/5.75+1000/5.75
× 4000 = 1000 𝐾𝑉𝐴
Example: Connecting two 2000 kVA transformers in parallel, one with 5.75%
impedance and the other with 4% impedance, each with the same turn ratios,
connected to a common 3500 kVA load. What is the loading on each
transformer?
𝐾𝑉𝐴𝐴 =
𝐾𝑉𝐴𝐴/%𝑍𝐴
𝐾𝑉𝐴𝐴/%𝑍𝐴 +𝐾𝑉𝐴𝐵/%𝑍𝐵
𝐾𝑉𝐴𝐿𝑜𝑎𝑑
=
2000/5.75
2000/5.75+2000/4
× 3500 = 1436 𝐾𝑉𝐴
𝐾𝑉𝐴𝐵 =
𝐾𝑉𝐴𝐵/%𝑍𝐵
𝐾𝑉𝐴𝐴/%𝑍𝐴 +𝐾𝑉𝐴𝐵/%𝑍𝐵
𝐾𝑉𝐴𝐿𝑜𝑎𝑑
=
2000/4
2000/5.75+2000/4
× 3500 = 2064 𝐾𝑉𝐴
The 4% impedance
transformer is overloaded
by 3.2%, while the 5.75%
impedance transformer is
loaded by 72%.
33
Dr. Firas Obeidat Faculty of Engineering Philadelphia University
Parallel Operation of Transformers
Example: Connecting two transformers in parallel with one 3000 kVA with
5.75% impedance, and the other a 1000 kVA with 4% impedance, each with
the same turn ratios, connected to a common 3500 kVA load. What is the
loading on each transformer?
𝐾𝑉𝐴𝐴 =
𝐾𝑉𝐴𝐴/%𝑍𝐴
𝐾𝑉𝐴𝐴/%𝑍𝐴 +𝐾𝑉𝐴𝐵/%𝑍𝐵
𝐾𝑉𝐴𝐿𝑜𝑎𝑑
=
3000/5.75
2000/5.75+2000/4
× 3500 = 2366 𝐾𝑉𝐴
𝐾𝑉𝐴𝐵 =
𝐾𝑉𝐴𝐵/%𝑍𝐵
𝐾𝑉𝐴𝐴/%𝑍𝐴 +𝐾𝑉𝐴𝐵/%𝑍𝐵
𝐾𝑉𝐴𝐿𝑜𝑎𝑑
=
1000/4
2000/5.75+2000/4
× 3500 = 1134 𝐾𝑉𝐴
The 4% impedance transformer is overloaded
by 13.4%, while the 5.75% impedance
transformer is loaded by 78.8%.
34
Dr. Firas Obeidat Faculty of Engineering Philadelphia University
Transformer Vector Group
 The primary and secondary windings of a three-phase transformer are
connected either in the same (delta-delta or star-star), or different (delta-
star or star-delta) configuration-pair.
 The secondary voltage waveforms of a three-phase transformer are in
phase with the primary waveforms when the primary and secondary
windings are connected in the same configuration. This condition is known
as ‘no phase shift’ condition.
 If the primary and secondary windings are connected in different
configuration pair then the secondary voltage waveforms will differ from
the corresponding primary voltage waveforms by 30 electrical degrees.
This condition is called a ‘30° phase shift’ condition.
 The windings and their position to each other are usually marked by
vector group. The vector group is used to identify the phase shift between
the primary and secondary windings. In the vector group, the secondary
voltage may have the phase shift of 30° lagging or leading, 0° i.e., no phase
shift or 180° reversal with respect to the primary voltage.
35
Dr. Firas Obeidat Faculty of Engineering Philadelphia University
Transformer Vector Group
 The transformer vector group is
labeled by capital and small letters
plus numbers from 1 to 12 in a
typical clock-like diagram.
 The capital letter indicates primary
winding and small letter represents
secondary winding.
 In the clock diagram, the minute
hand represents the primary line to
neutral line voltage, and its place is
always in the 12. The hour hand
represents the secondary line to
neutral voltage and its position in
the clock changes based on the
phase shift
36
Dr. Firas Obeidat Faculty of Engineering Philadelphia University
Vector Groups Used in the Three
Phase Transformer Connection
Group I
0 o’clock, zero
phase displacement
Yy0
Dd0
Dz0
Group II
6 o’clock, 180°
phase displacement
Yy6
Dd6
Dz6
Group III
1 o’clock, -30° lag
phase displacement
Dy1
Yd1
Yz1
Group IV
11 o’clock, 30° lead
phase displacement
Dy11
Yd11
Yz11
Transformer Vector Group
37
Dr. Firas Obeidat Faculty of Engineering Philadelphia University
Transformer Vector Group
38
Dr. Firas Obeidat Faculty of Engineering Philadelphia University
Transformer Vector Group
39
Dr. Firas Obeidat Faculty of Engineering Philadelphia University
Transformer Vector Group
40
Dr. Firas Obeidat Faculty of Engineering Philadelphia University
Transformer Vector Group
41

More Related Content

Similar to 3 three phase transformers.pdf

Transformer
TransformerTransformer
Transformer
stooty s
 

Similar to 3 three phase transformers.pdf (20)

Transformer_Parallel_opt_auto.ppt
Transformer_Parallel_opt_auto.pptTransformer_Parallel_opt_auto.ppt
Transformer_Parallel_opt_auto.ppt
 
Lecture (11.11.22).pptx
Lecture (11.11.22).pptxLecture (11.11.22).pptx
Lecture (11.11.22).pptx
 
Lecture 1.2.3.pptx
Lecture 1.2.3.pptxLecture 1.2.3.pptx
Lecture 1.2.3.pptx
 
Tansformer @dheeraj upadhyay
Tansformer @dheeraj upadhyayTansformer @dheeraj upadhyay
Tansformer @dheeraj upadhyay
 
Three Phase Transformer Connections.pptx
Three Phase Transformer Connections.pptxThree Phase Transformer Connections.pptx
Three Phase Transformer Connections.pptx
 
Xftheory
XftheoryXftheory
Xftheory
 
THREE PHASE TRANSFORMERS
THREE PHASE TRANSFORMERSTHREE PHASE TRANSFORMERS
THREE PHASE TRANSFORMERS
 
2.3, 2.8, 2.10, 2.11
2.3, 2.8, 2.10, 2.112.3, 2.8, 2.10, 2.11
2.3, 2.8, 2.10, 2.11
 
Protection of power transformer
Protection of power transformerProtection of power transformer
Protection of power transformer
 
High voltage transformers
High voltage transformersHigh voltage transformers
High voltage transformers
 
High Voltage Transformers
High Voltage TransformersHigh Voltage Transformers
High Voltage Transformers
 
Three phase transformers
Three phase transformersThree phase transformers
Three phase transformers
 
Full transformer
Full transformerFull transformer
Full transformer
 
Transformer
TransformerTransformer
Transformer
 
Transformer
TransformerTransformer
Transformer
 
Em manual 1
Em manual 1Em manual 1
Em manual 1
 
electrical system
electrical system electrical system
electrical system
 
Autotransformer electrical
Autotransformer  electricalAutotransformer  electrical
Autotransformer electrical
 
Transformer
TransformerTransformer
Transformer
 
Transformer
TransformerTransformer
Transformer
 

More from NANDHAKUMARA10

Earthing grounding protection Difference between earthing and grounding.pptx
Earthing  grounding protection Difference between earthing and grounding.pptxEarthing  grounding protection Difference between earthing and grounding.pptx
Earthing grounding protection Difference between earthing and grounding.pptx
NANDHAKUMARA10
 

More from NANDHAKUMARA10 (20)

Electromagnetic relays used for power system .pptx
Electromagnetic relays used for power system .pptxElectromagnetic relays used for power system .pptx
Electromagnetic relays used for power system .pptx
 
Block diagram reduction techniques in control systems.ppt
Block diagram reduction techniques in control systems.pptBlock diagram reduction techniques in control systems.ppt
Block diagram reduction techniques in control systems.ppt
 
Speed Control of three phase Induction motor.pptx
Speed Control of three phase Induction motor.pptxSpeed Control of three phase Induction motor.pptx
Speed Control of three phase Induction motor.pptx
 
Over load tap changer of Transformer.pptx
Over load tap changer of Transformer.pptxOver load tap changer of Transformer.pptx
Over load tap changer of Transformer.pptx
 
Starter for IM (DOL) for Three phase IM.pptx
Starter for IM (DOL) for Three phase IM.pptxStarter for IM (DOL) for Three phase IM.pptx
Starter for IM (DOL) for Three phase IM.pptx
 
Autotransformer starter for three phase IM.pptx
Autotransformer starter for three phase IM.pptxAutotransformer starter for three phase IM.pptx
Autotransformer starter for three phase IM.pptx
 
Transformer is a single phase device.pptx
Transformer is a single phase device.pptxTransformer is a single phase device.pptx
Transformer is a single phase device.pptx
 
Testing of DC machines using direct and indirect test.pptx
Testing of DC machines using direct and indirect test.pptxTesting of DC machines using direct and indirect test.pptx
Testing of DC machines using direct and indirect test.pptx
 
MONTHLY ELECTRICITY BILLING WITH BILL SMS USING PIC.pptx
MONTHLY ELECTRICITY BILLING WITH BILL SMS USING PIC.pptxMONTHLY ELECTRICITY BILLING WITH BILL SMS USING PIC.pptx
MONTHLY ELECTRICITY BILLING WITH BILL SMS USING PIC.pptx
 
phishing website detector. (user's identity)pptx
phishing website detector. (user's identity)pptxphishing website detector. (user's identity)pptx
phishing website detector. (user's identity)pptx
 
Air pollution and water monitoring system.pptx
Air pollution and water monitoring system.pptxAir pollution and water monitoring system.pptx
Air pollution and water monitoring system.pptx
 
Library Management System for book sorting-1.pptx
Library Management System for book sorting-1.pptxLibrary Management System for book sorting-1.pptx
Library Management System for book sorting-1.pptx
 
SMART INCUBATOR FOR INFANT MONITORING.pptx
SMART INCUBATOR FOR INFANT MONITORING.pptxSMART INCUBATOR FOR INFANT MONITORING.pptx
SMART INCUBATOR FOR INFANT MONITORING.pptx
 
PPT Format for Second Review is required for good Eunturpriner(2).pptx
PPT Format for Second Review is required for good Eunturpriner(2).pptxPPT Format for Second Review is required for good Eunturpriner(2).pptx
PPT Format for Second Review is required for good Eunturpriner(2).pptx
 
Earthing grounding protection Difference between earthing and grounding.pptx
Earthing  grounding protection Difference between earthing and grounding.pptxEarthing  grounding protection Difference between earthing and grounding.pptx
Earthing grounding protection Difference between earthing and grounding.pptx
 
Solar Module and solar part I solar energy resources.pptx
Solar Module and solar part I solar energy resources.pptxSolar Module and solar part I solar energy resources.pptx
Solar Module and solar part I solar energy resources.pptx
 
Time response of first order systems and second order systems
Time response of first order systems and second order systemsTime response of first order systems and second order systems
Time response of first order systems and second order systems
 
Switched reluctance motor used in automation systemptx
Switched reluctance motor used in automation systemptxSwitched reluctance motor used in automation systemptx
Switched reluctance motor used in automation systemptx
 
Solar Cells.pptx
Solar Cells.pptxSolar Cells.pptx
Solar Cells.pptx
 
Auto Transformer.pptx
Auto Transformer.pptxAuto Transformer.pptx
Auto Transformer.pptx
 

Recently uploaded

Call Girls in Ramesh Nagar Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
Call Girls in Ramesh Nagar Delhi 💯 Call Us 🔝9953056974 🔝 Escort ServiceCall Girls in Ramesh Nagar Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
Call Girls in Ramesh Nagar Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
9953056974 Low Rate Call Girls In Saket, Delhi NCR
 
AKTU Computer Networks notes --- Unit 3.pdf
AKTU Computer Networks notes ---  Unit 3.pdfAKTU Computer Networks notes ---  Unit 3.pdf
AKTU Computer Networks notes --- Unit 3.pdf
ankushspencer015
 
Call Girls In Bangalore ☎ 7737669865 🥵 Book Your One night Stand
Call Girls In Bangalore ☎ 7737669865 🥵 Book Your One night StandCall Girls In Bangalore ☎ 7737669865 🥵 Book Your One night Stand
Call Girls In Bangalore ☎ 7737669865 🥵 Book Your One night Stand
amitlee9823
 
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Christo Ananth
 

Recently uploaded (20)

Roadmap to Membership of RICS - Pathways and Routes
Roadmap to Membership of RICS - Pathways and RoutesRoadmap to Membership of RICS - Pathways and Routes
Roadmap to Membership of RICS - Pathways and Routes
 
UNIT - IV - Air Compressors and its Performance
UNIT - IV - Air Compressors and its PerformanceUNIT - IV - Air Compressors and its Performance
UNIT - IV - Air Compressors and its Performance
 
Top Rated Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...
Top Rated  Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...Top Rated  Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...
Top Rated Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...
 
University management System project report..pdf
University management System project report..pdfUniversity management System project report..pdf
University management System project report..pdf
 
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete RecordCCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
 
Call Girls in Ramesh Nagar Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
Call Girls in Ramesh Nagar Delhi 💯 Call Us 🔝9953056974 🔝 Escort ServiceCall Girls in Ramesh Nagar Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
Call Girls in Ramesh Nagar Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
 
Double Revolving field theory-how the rotor develops torque
Double Revolving field theory-how the rotor develops torqueDouble Revolving field theory-how the rotor develops torque
Double Revolving field theory-how the rotor develops torque
 
(INDIRA) Call Girl Aurangabad Call Now 8617697112 Aurangabad Escorts 24x7
(INDIRA) Call Girl Aurangabad Call Now 8617697112 Aurangabad Escorts 24x7(INDIRA) Call Girl Aurangabad Call Now 8617697112 Aurangabad Escorts 24x7
(INDIRA) Call Girl Aurangabad Call Now 8617697112 Aurangabad Escorts 24x7
 
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
 
The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...
The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...
The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...
 
AKTU Computer Networks notes --- Unit 3.pdf
AKTU Computer Networks notes ---  Unit 3.pdfAKTU Computer Networks notes ---  Unit 3.pdf
AKTU Computer Networks notes --- Unit 3.pdf
 
Generative AI or GenAI technology based PPT
Generative AI or GenAI technology based PPTGenerative AI or GenAI technology based PPT
Generative AI or GenAI technology based PPT
 
Thermal Engineering -unit - III & IV.ppt
Thermal Engineering -unit - III & IV.pptThermal Engineering -unit - III & IV.ppt
Thermal Engineering -unit - III & IV.ppt
 
NFPA 5000 2024 standard .
NFPA 5000 2024 standard                                  .NFPA 5000 2024 standard                                  .
NFPA 5000 2024 standard .
 
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
 
Call Girls In Bangalore ☎ 7737669865 🥵 Book Your One night Stand
Call Girls In Bangalore ☎ 7737669865 🥵 Book Your One night StandCall Girls In Bangalore ☎ 7737669865 🥵 Book Your One night Stand
Call Girls In Bangalore ☎ 7737669865 🥵 Book Your One night Stand
 
Java Programming :Event Handling(Types of Events)
Java Programming :Event Handling(Types of Events)Java Programming :Event Handling(Types of Events)
Java Programming :Event Handling(Types of Events)
 
Online banking management system project.pdf
Online banking management system project.pdfOnline banking management system project.pdf
Online banking management system project.pdf
 
Bhosari ( Call Girls ) Pune 6297143586 Hot Model With Sexy Bhabi Ready For ...
Bhosari ( Call Girls ) Pune  6297143586  Hot Model With Sexy Bhabi Ready For ...Bhosari ( Call Girls ) Pune  6297143586  Hot Model With Sexy Bhabi Ready For ...
Bhosari ( Call Girls ) Pune 6297143586 Hot Model With Sexy Bhabi Ready For ...
 
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
 

3 three phase transformers.pdf

  • 1. Electric Machines I Three Phase Transformers 1 Dr. Firas Obeidat
  • 2. 2 Table of contents 1 • Introduction 2 • Wye-Wye Connection 3 • Wye-Delta Connection 4 • Delta-Wye Connection 5 • Delta-Delta Connection 6 • Polarity of a Transformer 7 • Parallel Operation of Transformers 8 • Transformer Vector Group Dr. Firas Obeidat Faculty of Engineering Philadelphia University
  • 3. 3 Dr. Firas Obeidat Faculty of Engineering Philadelphia University Introduction  A three-phase power transformer is used at the power generating station to step-up the voltage. Whereas in the power distribution substation, the three-phase voltage is again stepped down through a three-phase distribution transformer.  A three-phase transformer can be made either by three windings wound on a common core or by three single-phase transformer connected together in a three-phase bank.  The first approach is a cheaper one that results in a transformer with smaller size and less weight. The main disadvantage of the first approach is that if one phase becomes defective, then the whole transformer needs to be replaced. Whereas in the second approach, if one of the transformers becomes defective then the system can be given power by an open delta at a reduced capacity. In this case, the defective transformer is normally replaced by a new one.
  • 4. 4 Dr. Firas Obeidat Faculty of Engineering Philadelphia University Introduction The primary and secondary windings of the transformer may be connected in either by wye (Y) or delta (Δ). Three-phase transformer connections Y-Y (Wye-Wye) Y-Δ (Wye-Delta) Δ-Y (Delta-Wye) Δ-Δ (Delta-Delta)
  • 5. 5 Dr. Firas Obeidat Faculty of Engineering Philadelphia University Wye-Wye Connection At the primary side, the phase voltage can be written as, At the secondary side, the phase voltage can be written as, The ratio of the primary line voltage to the secondary line voltage of this connection is,
  • 6. 6 Dr. Firas Obeidat Faculty of Engineering Philadelphia University Wye-Wye Connection The Y- Y connection has two very serious problems 1) If loads on the transformer circuit are unbalanced, then the voltages on the phases of the transformer can become severely unbalanced. 2) Third-harmonic voltages can be large. If a three-phase set of voltages is applied to a Y- Y transformer, the voltages in any phase will be 120o apart from the voltages in any other phase. However, the third-harmonic components of each of the three phases will be in phase with each other. There are always some third-harmonic components in a transformer because of the nonlinearity of the core, and these components add up. The result is a very large third-harmonic component of voltage on top of the 50-ar 60-Hz fundamental voltage. This third-harmonic voltage can be larger than the fundamental voltage itself. This type of connection of a three-phase transformer is rarely used for large amount of power transmission.
  • 7. 7 Dr. Firas Obeidat Faculty of Engineering Philadelphia University Wye-Wye Connection Unbalance problem and the third-harmonic problem can be solved by: • Solidly ground the neutrals of the transformers, especially the primary winding's neutral. This connection permits the additive third-harmonic components to cause a current flow in the neutral instead of building up large voltages. The neutral also provides a return path for any current imbalances in the load. • Add a third (tertiary) winding connected in Δ to the transformer bank. If a third Δ-connected winding is added to the transformer. then the third- harmonic components of voltage in the Δ will add up, causing a circulating current flow within the winding. This suppresses the third-harmonic components of voltage in the same manner as grounding the transformer neutrals. The Δ-connected tertiary windings need not even be brought out of the transformer case, but they often are used to supply lights and auxiliary power within the substation where it is located. The tertiary windings must be large enough to handle the circulating currents, so they are usually made about one-third the power rating of the two main windings.
  • 8. 8 Dr. Firas Obeidat Faculty of Engineering Philadelphia University Wye-Wye Connection Advantages Disadvantages Magnetizing current of transformer has 3rd harmonic component The third harmonic present in the alternator voltage may appear on the secondary side. This causes distortion in the secondary phase voltages If the load on the secondary side unbalanced then the shifting of neutral point is possible Less dielectric strength in insulating materials phase voltage is less Cross section of winding is large i.e. stronger to bear stress during short circuit Line current is equal to phase current Requires less turns per winding ie cheaper Phase voltage is 1/√3 times of line voltage
  • 9. 9 Dr. Firas Obeidat Faculty of Engineering Philadelphia University Wye-Delta Connection The expression of the primary line voltage is At the secondary side, the line voltage is The ratio of primary phase voltage to secondary phase voltage is The ratio of primary line voltage to secondary line voltage is The primary phase current is The turns ratio is
  • 10. 10 Dr. Firas Obeidat Faculty of Engineering Philadelphia University Wye-Delta Connection The expression of the secondary phase current is The secondary line current is  This connection does have one problem; Because of the connection, the secondary voltage is shifted 30° relative to the primary voltage of the transformer. The fact that a phase shift has occurred can cause problems in paralleling the secondaries of two transformer banks together. The phase angles of transformer secondaries must be equal if they are to be paralleled, which means that attention must be paid to the direction of the 30o phase shift occurring in each transformer bank to be paralleled together.  The connection will cause the secondary voltage to be lagging if the system phase sequence is abc. If the system phase sequence is acb, then the connection will cause the secondary voltage to be leading the primary voltage by 30o.
  • 11. 11 Dr. Firas Obeidat Faculty of Engineering Philadelphia University Wye-Delta Connection Advantages Disadvantages
  • 12. 12 Dr. Firas Obeidat Faculty of Engineering Philadelphia University Delta-Wye Connection The expression of the primary line voltage is The line voltage at the secondary side is The ratio of primary line voltage to secondary line voltage is The phase current at the primary side is For this connection, the turns ratio is In this case, the secondary phase current is The secondary line current is
  • 13. 13 Dr. Firas Obeidat Faculty of Engineering Philadelphia University Delta-Wye Connection Advantages Disadvantages
  • 14. 14 Dr. Firas Obeidat Faculty of Engineering Philadelphia University Delta-Delta Connection The expression of the primary line voltage is The line voltage at the secondary side is The ratio of primary line voltage to secondary line voltage is The secondary line current is The output capacity in delta-delta connection can be expressed as and 𝑆 = 3𝑉𝐿𝐼𝐿 = 3𝑉 𝑝𝐼𝑝 𝑝 = 3𝑉𝐿𝐼𝐿𝑐𝑜𝑠θ = 3𝑉 𝑝𝐼𝑝𝑐𝑜𝑠θ
  • 15. 15 Dr. Firas Obeidat Faculty of Engineering Philadelphia University Delta-Delta Connection Advantages Disadvantages
  • 16. 16 Dr. Firas Obeidat Faculty of Engineering Philadelphia University Three Phase Transformers Primary winding Secondary winding Primary winding Secondary winding Primary winding Secondary winding Primary winding Secondary winding √3V I V aI V/a √3V/a I V √3V √3aI V/a aI √3I I V aI V/a √3V/a √3I I V √3aI V/a aI The relations between three phase current/voltage and single phase current/voltage
  • 17. 17 Dr. Firas Obeidat Faculty of Engineering Philadelphia University Three Phase Transformers Example: A three-phase transformer is connected to an 11 kV supply and draws 6 A current. Determine (i) line voltage at the secondary side, (ii) the line current in the secondary coil. Consider the turns ratio of the transformer is 11. Also, consider delta-wye and wye-delta connections. 1- For delta-wye connection 𝐼𝑝1 = 𝐼𝐿1 3 = 6 3 = 3.46 𝐴
  • 18. 18 Dr. Firas Obeidat Faculty of Engineering Philadelphia University Three Phase Transformers 2- For wye-delta connection 𝐼𝐿2 = 𝐼𝑝2 = 𝑎𝐼𝑝1 = 11 × 3.46 = 38 𝐴
  • 19. 19 Dr. Firas Obeidat Faculty of Engineering Philadelphia University Polarity of a Transformer Polarity of a transformer is defined as the relative directions of induced voltages between the high voltage and low voltage terminals.  The polarity of a transformer is very important to construct three-phase transformer bank, parallel connection of transformer, connection of current transformer (CT) and potential transformer (PT) power with metering device.  Two polarities namely additive and subtractive are used in the transformer.  A polarity of a transformer is said to be an additive if the measured voltage between the high voltage and the low voltage terminals is greater than the supply voltage at the high voltage terminals.  A polarity is said to be a subtractive if the measured voltage between the high voltage and the low voltage terminals is lower than the supply voltage at the high voltage terminals. Subtractive polarity Additive polarity
  • 20. 20 Dr. Firas Obeidat Faculty of Engineering Philadelphia University Polarity of a Transformer  Consider a 220/110V single-phase transformer with the high voltage and the low voltage terminals for testing polarities. The high voltage terminal H1 is connected to the low voltage terminal X1 by a cable. The voltmeter is connected between H2 and X2. In this case, the turns ratio of the transformer is, V1/V2=220/110=2.  A voltage of 110 V is applied to the primary side. In this case, a voltage of 55 V (110/2) will appear at the secondary terminals. If the meter read out the voltage of 165 V (110 + 55) then the transformer is said to be in additive polarity.  If the voltmeter reads the voltage of 55V (110−55) then the transformer is said to be in subtractive polarity. Testing for additive polarity Testing for subtractive polarity
  • 21. 21 Dr. Firas Obeidat Faculty of Engineering Philadelphia University Parallel Operation of Transformers  For supplying a load in excess of the rating of an existing transformer, two or more transformers may be connected in parallel with the existing transformer.  The transformers are connected in parallel when load on one of the transformers is more than its capacity. The reliability is increased with parallel operation than to have single larger unit.  The cost associated with maintaining the spares is less when two transformers are connected in parallel.  It is usually economical to install another transformer in parallel instead of replacing the existing transformer by a single larger unit. The cost of a spare unit in the case of two parallel transformers (of equal rating) is also lower than that of a single large transformer. In addition, it is preferable to have a parallel transformer for the reason of reliability. With this at least half the load can be supplied with one transformer out of service.
  • 22. 22 Dr. Firas Obeidat Faculty of Engineering Philadelphia University Parallel Operation of Transformers Advantages Disadvantages the parallel transformers may have very low impedance, which creates the high short circuit currents The bus ratings could be too high The risk of circulating currents running from one transformer to another Transformer Increasing short-circuit currents that increase necessary breaker capacity Maximize electrical system flexibility Maximize power system reliability Maximize electrical system availability Maximize electrical system efficiency
  • 23. 23 Dr. Firas Obeidat Faculty of Engineering Philadelphia University Parallel Operation of Transformers Condition for Parallel Operation of Transformer: 1- The voltage rating of both primaries and secondaries should be identical, i.e. the transformers should have the same turn ratio.  If the transformers connected in parallel have slightly different voltage ratios, then due to the inequality of induced emfs in the secondary windings, a circulating current will flow in the loop formed by the secondary windings under the no-load condition, which may be much greater than the normal no-load current.  The current will be quite high as the leakage impedance is low. When the secondary windings are loaded, this circulating current will tend to produce unequal loading on the two transformers, and it may not be possible to take the full load from this group of two parallel transformers (one of the transformers may get overloaded).  A small voltage difference may cause sufficiently high circulating current causing unnecessary extra I2R loss.
  • 24. 24 Dr. Firas Obeidat Faculty of Engineering Philadelphia University Parallel Operation of Transformers Condition for Parallel Operation of Transformer: 2- The percentage impedances should be equal in magnitude and have same X/R ratio in order to avoid circulating currents and operation in different power factor.  If this condition is not satisfied then the impedance triangles are not identical in shape and size, parallel operation will still be possible, but the power factor at which the two transformers operate will be different (one transformer will operate with higher power factor and the other with lower power factor) from the power factor of the common load. In this case the two transformers will not share the load in proportion to their KVA ratings.
  • 25. 25 Dr. Firas Obeidat Faculty of Engineering Philadelphia University Parallel Operation of Transformers Condition for Parallel Operation of Transformer: 3- The polarity of the two transformers should be the same.  Polarity of transformer means the instantaneous direction of induced emf in secondary. If the instantaneous directions of induced secondary emf in two transformers are opposite to each other when same input power is fed to the both of the transformers, the transformers are said to be in opposite polarity.  The transformers should be properly connected with regard to their polarity. If they are connected with incorrect polarities then the two emfs, induced in the secondary windings which are in parallel, will act together in the local secondary circuit and produce a short circuit.  Polarity of all transformers run in parallel should be same otherwise huge circulating current flows in the transformer but no load will be fed from these transformers.  If the instantaneous directions of induced secondary emf in two transformers are same when same input power is fed to the both of the transformers, the transformers are said to be in same polarity. Inside the loop formed by the two secondaries the resulting voltage must be zero.
  • 26. 26 Dr. Firas Obeidat Faculty of Engineering Philadelphia University Parallel Operation of Transformers Condition for Parallel Operation of Transformer: 3- The polarity of the two transformers should be the same. 4- Phase sequences and phase angle shifts must be the same (for three-phase transformer). The transformer windings cab be connected in variety of ways which produce different magnitudes and phase displacement of secondary voltages
  • 27. 27 Dr. Firas Obeidat Faculty of Engineering Philadelphia University Parallel Operation of Transformers Overall summary of different connection types of parallel transformers Transformer Parallel Connection Types Equal Loading Unequal Loading Overloading Concerns Circulating Currents Recommended Connection Equal impedances— Equal ratios— Same kVA Yes No No No Yes Equal impedances— Equal ratios— Different kVA No Yes No No Yes Unequal impedances— Equal ratios— Same kVA No Yes Yes No No Unequal impedances— Equal ratios— Different kVA No Yes Yes No No Unequal impedances— Unequal ratios— Same kVA Yes No Yes Yes No Unequal impedances— Unequal ratios— Different kVA No Yes Yes Yes No
  • 28. 28 Dr. Firas Obeidat Faculty of Engineering Philadelphia University Parallel Operation of Transformers Case I: Equal Impedances-Equal Ratios-Same kVA 𝐼 = 𝐼𝐴 + 𝐼𝐵 𝐼𝐴 = 𝑍𝐵 𝑍𝐴 + 𝑍𝐵 𝐼 𝐼𝐵 = 𝑍𝐴 𝑍𝐴 + 𝑍𝐵 𝐼 𝑉2 = 𝐸 − 𝐼𝐴 𝑍𝐴 = 𝐸 − 𝐼𝐵𝑍𝐵 = 𝐸 − 𝐼𝑍𝐴𝐵 𝐼𝐴 𝑍𝐴 = 𝐼𝐵𝑍𝐵 𝐼𝐴 𝐼𝐵 = 𝑍𝐵 𝑍𝐴 Case II: Equal Impedances-Equal Ratios-Different kVA
  • 29. 29 Dr. Firas Obeidat Faculty of Engineering Philadelphia University Parallel Operation of Transformers Case I: Equal Impedances-Equal Ratios-Same kVA 𝐼𝐴 = 𝐾𝑉𝐴𝐴/%𝑍𝐴 𝐾𝑉𝐴𝐴/%𝑍𝐴 +𝐾𝑉𝐴𝐵/%𝑍𝐵 𝐼 𝐼𝐵 = 𝐾𝑉𝐴𝐵/%𝑍𝐵 𝐾𝑉𝐴𝐴/%𝑍𝐴 +𝐾𝑉𝐴𝐵/%𝑍𝐵 𝐼 𝐾𝑉𝐴𝐴 = 𝐾𝑉𝐴𝐴/%𝑍𝐴 𝐾𝑉𝐴𝐴/%𝑍𝐴 +𝐾𝑉𝐴𝐵/%𝑍𝐵 𝐾𝑉𝐴𝐿𝑜𝑎𝑑 𝐾𝑉𝐴𝐵 = 𝐾𝑉𝐴𝐵/%𝑍𝐵 𝐾𝑉𝐴𝐴/%𝑍𝐴 +𝐾𝑉𝐴𝐵/%𝑍𝐵 𝐾𝑉𝐴𝐿𝑜𝑎𝑑 %𝑍𝑇 = 𝑍𝑇𝐼𝑇 𝑉𝑇 × 100 = 𝑍𝑇 𝑉𝑇 2 𝑆𝑇 × 100 Where: IA = load current from transformer A IB = load current from transformer B % ZA = % impedance of transformer A % ZB = % impedance of transformer B kVAA = kVA rating of transformer A kVAB = kVA rating of transformer B % ZT = % impedance of any transformer IT = rated current of any transformer VT = rated voltage of any transformer ST = KVA rating of any transformer Case II: Equal Impedances-Equal Ratios-Different kVA
  • 30. 30 Dr. Firas Obeidat Faculty of Engineering Philadelphia University Parallel Operation of Transformers Case III: Unequal Impedances-Equal Ratios-Same kVA Case IV: Unequal Impedances-Equal Ratios-Different kVA The equations for case III and Case IV are the same equations for case I and case II.
  • 31. 31 Dr. Firas Obeidat Faculty of Engineering Philadelphia University Parallel Operation of Transformers Example: Connecting two 2000 kVA, 5.75% impedance transformers in parallel, each with the same turn ratios to a 4000 kVA load. What is the loading on the transformers? 𝐾𝑉𝐴𝐴 = 𝐾𝑉𝐴𝐵 = 𝐾𝑉𝐴𝐴/%𝑍𝐴 𝐾𝑉𝐴𝐴/%𝑍𝐴 +𝐾𝑉𝐴𝐵/%𝑍𝐵 𝐾𝑉𝐴𝐿𝑜𝑎𝑑 𝐾𝑉𝐴𝐴 = 𝐾𝑉𝐴𝐵 = 2000/5.75 2000/5.75+2000/5.75 × 4000 = 348 348+348 × 4000 = 2000 𝐾𝑉𝐴 Example: Connecting 3000 kVA and 1000 kVA transformers in parallel, each with 5.75% impedance, each with the same turn ratios, connected to a common 4000 kVA load. What is the loading on each transformer? 𝐾𝑉𝐴𝐴 = 𝐾𝑉𝐴𝐴/%𝑍𝐴 𝐾𝑉𝐴𝐴/%𝑍𝐴 +𝐾𝑉𝐴𝐵/%𝑍𝐵 𝐾𝑉𝐴𝐿𝑜𝑎𝑑 = 3000/5.75 3000/5.75+1000/5.75 × 4000 = 3000 𝐾𝑉𝐴
  • 32. 32 Dr. Firas Obeidat Faculty of Engineering Philadelphia University Parallel Operation of Transformers 𝐾𝑉𝐴𝐵 = 𝐾𝑉𝐴𝐵/%𝑍𝐵 𝐾𝑉𝐴𝐴/%𝑍𝐴 +𝐾𝑉𝐴𝐵/%𝑍𝐵 𝐾𝑉𝐴𝐿𝑜𝑎𝑑 = 1000/5.75 3000/5.75+1000/5.75 × 4000 = 1000 𝐾𝑉𝐴 Example: Connecting two 2000 kVA transformers in parallel, one with 5.75% impedance and the other with 4% impedance, each with the same turn ratios, connected to a common 3500 kVA load. What is the loading on each transformer? 𝐾𝑉𝐴𝐴 = 𝐾𝑉𝐴𝐴/%𝑍𝐴 𝐾𝑉𝐴𝐴/%𝑍𝐴 +𝐾𝑉𝐴𝐵/%𝑍𝐵 𝐾𝑉𝐴𝐿𝑜𝑎𝑑 = 2000/5.75 2000/5.75+2000/4 × 3500 = 1436 𝐾𝑉𝐴 𝐾𝑉𝐴𝐵 = 𝐾𝑉𝐴𝐵/%𝑍𝐵 𝐾𝑉𝐴𝐴/%𝑍𝐴 +𝐾𝑉𝐴𝐵/%𝑍𝐵 𝐾𝑉𝐴𝐿𝑜𝑎𝑑 = 2000/4 2000/5.75+2000/4 × 3500 = 2064 𝐾𝑉𝐴 The 4% impedance transformer is overloaded by 3.2%, while the 5.75% impedance transformer is loaded by 72%.
  • 33. 33 Dr. Firas Obeidat Faculty of Engineering Philadelphia University Parallel Operation of Transformers Example: Connecting two transformers in parallel with one 3000 kVA with 5.75% impedance, and the other a 1000 kVA with 4% impedance, each with the same turn ratios, connected to a common 3500 kVA load. What is the loading on each transformer? 𝐾𝑉𝐴𝐴 = 𝐾𝑉𝐴𝐴/%𝑍𝐴 𝐾𝑉𝐴𝐴/%𝑍𝐴 +𝐾𝑉𝐴𝐵/%𝑍𝐵 𝐾𝑉𝐴𝐿𝑜𝑎𝑑 = 3000/5.75 2000/5.75+2000/4 × 3500 = 2366 𝐾𝑉𝐴 𝐾𝑉𝐴𝐵 = 𝐾𝑉𝐴𝐵/%𝑍𝐵 𝐾𝑉𝐴𝐴/%𝑍𝐴 +𝐾𝑉𝐴𝐵/%𝑍𝐵 𝐾𝑉𝐴𝐿𝑜𝑎𝑑 = 1000/4 2000/5.75+2000/4 × 3500 = 1134 𝐾𝑉𝐴 The 4% impedance transformer is overloaded by 13.4%, while the 5.75% impedance transformer is loaded by 78.8%.
  • 34. 34 Dr. Firas Obeidat Faculty of Engineering Philadelphia University Transformer Vector Group  The primary and secondary windings of a three-phase transformer are connected either in the same (delta-delta or star-star), or different (delta- star or star-delta) configuration-pair.  The secondary voltage waveforms of a three-phase transformer are in phase with the primary waveforms when the primary and secondary windings are connected in the same configuration. This condition is known as ‘no phase shift’ condition.  If the primary and secondary windings are connected in different configuration pair then the secondary voltage waveforms will differ from the corresponding primary voltage waveforms by 30 electrical degrees. This condition is called a ‘30° phase shift’ condition.  The windings and their position to each other are usually marked by vector group. The vector group is used to identify the phase shift between the primary and secondary windings. In the vector group, the secondary voltage may have the phase shift of 30° lagging or leading, 0° i.e., no phase shift or 180° reversal with respect to the primary voltage.
  • 35. 35 Dr. Firas Obeidat Faculty of Engineering Philadelphia University Transformer Vector Group  The transformer vector group is labeled by capital and small letters plus numbers from 1 to 12 in a typical clock-like diagram.  The capital letter indicates primary winding and small letter represents secondary winding.  In the clock diagram, the minute hand represents the primary line to neutral line voltage, and its place is always in the 12. The hour hand represents the secondary line to neutral voltage and its position in the clock changes based on the phase shift
  • 36. 36 Dr. Firas Obeidat Faculty of Engineering Philadelphia University Vector Groups Used in the Three Phase Transformer Connection Group I 0 o’clock, zero phase displacement Yy0 Dd0 Dz0 Group II 6 o’clock, 180° phase displacement Yy6 Dd6 Dz6 Group III 1 o’clock, -30° lag phase displacement Dy1 Yd1 Yz1 Group IV 11 o’clock, 30° lead phase displacement Dy11 Yd11 Yz11 Transformer Vector Group
  • 37. 37 Dr. Firas Obeidat Faculty of Engineering Philadelphia University Transformer Vector Group
  • 38. 38 Dr. Firas Obeidat Faculty of Engineering Philadelphia University Transformer Vector Group
  • 39. 39 Dr. Firas Obeidat Faculty of Engineering Philadelphia University Transformer Vector Group
  • 40. 40 Dr. Firas Obeidat Faculty of Engineering Philadelphia University Transformer Vector Group
  • 41. 41