Sag-Tension Analysis of AAAC Overhead
Transmission lines for Hilly Areas
Muhammad Zulqarnain Abbasi, M. Aamir Aman, Hamza Umar Afridi, Akhtar Khan
IQRA National University, Pakistan
Abstract—Power system is the transfer of electricity from
generation to the point of user location. Power system is
composed of generation of power, its transmission and
distribution. Transmission system is the main part out of these
three in which mostly losses occur. The unchanging factors of the
transmission line on which these losses depend are inductance,
resistance and capacitance. These constants or unchanging
factors play a vital role in the performance of transmission line.
For example the capacitance effect will be more and its
performance will be affected if the height of transmission line is
less from the ground. On the other hand its capacitance will be
less but tension will be high if the height of the transmission is
high. For this reason a transmission line is connected in a curved
or catenary shape known as sag. To minimize tension sag is
provided in a transmission line. Sag and tension must be adjusted
in safe limits. This immediate paper gives a simulation structure
to calculate sag and tension of AAAC (All Aluminum Alloy
Conductors of overhead transmission lines with same span length
for minimum operating temperature. Three different cases are
presented with different towers height and are explained in detail
for unequal level span. The results show that the tension and sag
increased with height. So great the height difference, higher
tensions upon higher towers.
This paper will be very helpful to find the sag-tension values of
AAAC conductor for Unequal level supports without calculating
it mathematically.
Keywords-component;sag;tension;transmission system
I. INTRODUCTION
System transferring electricity from generation to transmission
is known as transmission system. In transmission system
transmission lines and substations play a major role. In power
system network the biggest part is incorporated by the lines
transporting electricity. Designing and erecting transmission
system require proper construction or modeling of these lines.
A transmission systems successive execution depends on kind
of transmission model used in the system. Catenary is the term
given to the curve shape in which transmission lines are
connected between supportive towers or power. Transmission
line is never connected in straight line. To minimize the tension
in the transmission system sag is provided to the transmission
line. Similarly, if the tension is high in transmission line, sag
will be minimum and there is a possibility that the conductor
may break.
Sag and tension are inversely proportional to each other.
However, if sag increase the size of conductor used also
increases and the cost is raised. The distance between two
towers depends on the sag intensity. If the distance between
two towers is significant the sag will also be large.
Sag-Tension computations are aimed at fixing suitable
restrictions between sag and tension in order to continue or
steady uninterrupted power supply to the users.
With Sag-Tension calculations we can determine the conductor
temperature as well as ice and wind; load concurrently. Tension
is the limit of towers and conductor to keep the tension limited.
Sag clearance distance is dependent on line crossings and
ground. If the clearance distance is less than crossing distance
chances are that line faults may occur.
The “V” or “I” configuration also play important role for
calculating sag-tension along with quantity of insulator strings.
Naturally, insulator string possesses the attributes of an
element. Being element provides add up of great distance to
sag created by the conductor.
Considering bunch of conductors is also important in different
cases. For each phase two or more conductors are used. Extra
high voltage system may use two bunches of conductors per
phase. Occasionally, a substation that is accumulating power
from generating station may use three conductors or power
lines for each phase. Hence, the foundations regarding the sag-
tension approximation process are obligatory to examine and
guarantee or certify that the result match the true state.
Figure 1. Sag in Overhead Conductor
International Journal of Computer Science and Information Security (IJCSIS),
Vol. 16, No. 4, April 2018
111 https://sites.google.com/site/ijcsis/
ISSN 1947-5500
The above figure is showing that there are two equal supports
named as point A and B. while point O is the lowest point
between two supports. Similarly “S” is referred as sag which is
distance between the point of support and lowest point of
conductor.
II. CALCULATION OF SAG
In overhead transmission line designing, it is important to
keep sag under safe limit, and at same time tension running in
the conductor is also within safe limit. . As a matter of fact,
tension is administered by weight of conductor, ice load on
wires, temperature variation and effect of wind. According to
common practice, the tension of conductor is kept under 50%
of its ultimate tensile power. It means least factor of safety of a
conductor tension needs to be two. Now sag as well as tension
calculation of a conductor for Unequal support will be carry out
[8].
A. When supports are at Un- equal levels
In hilly areas, we generally come across conductors
Suspended between supports at unequal levels. Figure 2.
shows a conductor suspended between two supports A and B
Which are at different levels. The lowest point on the conductor
is O.
Let
l = Span length
h = Difference in levels between two supports
X 1 = Distance of support at lower level (i.e. A) from O
X2 = Distance of support at higher level (i.e. B) from O
T = Tension in the conductor
Figure 2. When supports are at Unequal levels
If w is the weight per unit length of the conductor, then
𝑆𝑎𝑔 𝑆1 =
𝑤𝑥1
2
2𝑇
and
𝑆𝑎𝑔 𝑆2 =
𝑤𝑥2
2
2𝑇
Also
𝑥1 + 𝑥2 = 𝑙 (𝒊)
Now
𝑆2 − 𝑆1 =
𝑤
2𝑇
(𝑥2
2
− 𝑥1
2
) =
𝑤
2𝑇
(𝑥2 + 𝑥1)(𝑥2 − 𝑥1)
𝑆2 − 𝑆1 =
𝑤𝑙
2𝑇
(𝑥2 − 𝑥1)
But
𝑆2 − 𝑆1 = ℎ
ℎ =
𝑤𝑙
2𝑇
(𝑥2 − 𝑥1)
𝑥2 − 𝑥1 =
2𝑇ℎ
𝑤𝑙
(𝒊𝒊)
Solving eq. (i) and (ii), we get
𝑥1 =
𝑙
2
−
𝑇ℎ
𝑤𝑙
𝑥2 =
𝑙
2
+
𝑇ℎ
𝑤𝑙
III. METHODOLOGY
For the result-oriented sag-tension of AAAC transmission
line considering different unequal span heights of minimum
operating condition are analyze in this research paper.
The tool used for the calculation is ETAP.The module ETAP
containing an analytical strength for Transmission and
Distribution Line Sag and Tension calculation. It is easily
available low cost simulation software to calculate the
appropriate sag & tension in order to ensure appropriate
operating conditions on the overhead transmission lines.
The spans length for all cases is same which are 200m and the
conductors configuration is set as horizontal.
Three Different cases i.e. 1, 2 & 3 are considered.
• In case 1 calculated sag-tension of AAAC
overhead transmission lines under minimum
operating condition with the height difference of
10m.
• In case 2 calculated sag-tension of AAAC
overhead transmission lines with same
temperature as previous one but the height
difference is 30m.
• In case 3 calculated sag-tension of AAAC
overhead transmission lines under minimum
operating condition with maximum height
difference of 50m.
These calculations are for unequal level spans only and when
both the towers are at height difference of 10m, 30m and 50m
respectively.
International Journal of Computer Science and Information Security (IJCSIS),
Vol. 16, No. 4, April 2018
112 https://sites.google.com/site/ijcsis/
ISSN 1947-5500
The conductor used in this paper is AAAC (All Aluminum
Alloy Conductor) because:
These conductors are of high strength made of
Aluminum-Magnesium-Silicon alloy and are having better
ratio of strength to weight enabling the conductors to exhibit
more efficient electrical characteristic. They have excellent
sag-tension characteristics and superior corrosion resistance
when compared with other conductors.
Comparing with traditional ACSR, AAAC are lighter in
weight, are having lower electrical losses and comparable
strength and current carrying capacity.
IV. RESULTS AND DISCUSSION
A. Case 1
In the 1st
case, sag-tension under minimum operating
temperature i.e. 5˚C with a height difference of 10m is
analyzed. As in hilly areas towers are at different heights so in
this case we have considered only 10m height difference.
TABLE I. MINIMUM TEMPERATURE WITH 10M HEIGHT DIFFERENCE
Type of
Conductor
Minimum Temperature
(5 °C) and height (10m)
Tension Sag
Low
Tower
High
Tower
Low
Tower
High
Tower
AAAC 1697 1707 0 10
In the above table sag and tension results of minimum
operating temperature with 10m height difference is shown. As
it shows above that when support are at 10m height difference
the tension on high tower is 1707 while on low tower it is 1697.
Similarly incase of sag high tower has more sag 10m than the
lower tower. The results are also shown below with the help of
graph.
Figure 3. Sag-Tension Results with 10m height difference
B. Case 2
In this case temperature is same as the previous one but the
height difference is 30m. As mentioned earlier that hilly areas
have different heights for supporting towers so therefore in this
case we have consider 30m height difference.
TABLE II. MINIMUM TEMPERATURE WITH 30M HEIGHT DIFFERENCE
Type of
Conductor
Minimum Temperature (5°C) and
height (30m)
Tension Sag
Low
Tower
High
Tower
Low
Tower
High
Tower
AAAC 1711 1738 0 30
As from the above table sag and tension results of
minimum operating temperature with 30m height difference are
given. When supports are at 30m height difference the tension
on high tower is 1738 while on low tower is 1711. Similarly
incase of sag high tower has more sag 30m than the lower
tower because high tower exerts high tension. The results are
also shown below with the help of graph.
0
500
1000
1500
2000
High
tower
Low
tower
High
tower
Low
tower
Tension Sag
Series1
International Journal of Computer Science and Information Security (IJCSIS),
Vol. 16, No. 4, April 2018
113 https://sites.google.com/site/ijcsis/
ISSN 1947-5500
Figure 4. Sag-Tension Results with 30m height differnce
C. Case 3
In 3rd case, sag and tension with minimum operating
temperature and height difference of 50m is consider.
TABLE III. MINIMUM TEMPERATURE WITH 50M HEIGHT DIFFERENCE
Type of
Conductor
Minimum Temperature
(5 °C) and height (50m)
Tension Sag
Low
Tower
High
Tower
Low
Tower
High
Tower
AAAC 1747 1793 0 50
In the above table sag and tension results of minimum
operating temperature with 50m height difference is mention.
The above table shows that when support are at 50m height
difference the tension on high tower is 1793 while on low
tower is 1747. Similarly incase of sag high tower has more sag
50m than the lower tower. The results are also shown below
with the help of graph.
Figure 5. Sag-Tension Results with 50m height differnce
V. CONCLUSION AND FUTURE WORK
This research paper has three different cases which are
taken from analysis of sag and tension estimation for AAAC
Overhead transmission lines. Equal span length is considered
for all cases. Three different towers height were considered
with minimum operating conditions. From the results following
conclusion is drawn:
In 1st case the temperature is minimum but the height
difference was 10m. So when the height difference was
minimum (10m) the tension in higher tower is high than the
lower tower.
Similarly for 2nd case, the temperature was set same as the
previous case but the height difference increased from 10m to
30m. As the height increases the tension will act more force on
higher tower as compare to low tower.
In the 3rd case temperature was same again but the height
difference was maximum (50m). So due to high difference in
towers height the tension on higher tower is also greater due to
height. In AAAC the tension and sag increased with height. So
great the height difference, higher tensions upon higher towers.
From this paper, one can easily find the sag-tension values of
AAAC conductor for Unequal level supports without
calculating it mathematically.
In future, the sag-tension estimation of other conductors will
also be considered in ETAP.
REFERENCES
[1] I. Albizu, A. J. Mazon, and E. Fernandez (2011). “A method for the
Sag-tension, calculation in electrical overhead lines. International
Review of Electrical Engineering, volume 6, No. 3 pp. 1380-1389
[2] J. Quintana, V. Garza, C. Zamudio(2016). Sag-Tension Calculation
Program for Power Substations. IEEE PES Asia-Pacific Power and
Energy Conference- Xi’an-China.
[3] Maamar Taleb, Mohamed Jassim Ditto, Tahar Bouthiba (2006).
Performance of Short Transmission Lines Model . University of Bahrain
Department of Electrical and Electronics Engineering.
[4] Oluwajobi F. I., Ale O. S. and Ariyanninuola A (2012). Effect of Sag on
Transmission Line. Journal of Emerging Trends in Engineering and
Applied Sciences (JETEAS) 3 (4): 627-630 © Scholar link Research
Institute Journals, (ISSN: 2141-7016).
[5] R.G. Olsen, K.S Edward (2002) “A New method for Real Time
Monitoring of High Voltage Transmission line Conductor sag. IEEE
Transactions on Power Delivery Vol. 17, No. 4, pp 1142-1152.
[6] Sag-Tension Calculation Methods for Overhead Lines (2007). CIGRE
B2-12 Brochure (Ref. No. 324) pp. 31-43.
[7] Seppa T O, 1992, A Practical Approach For Increasing the Thermal
Capabilities of Transmission lines, IEEE/PES Summer Meeting, pp
1536-1542
[8] S. Kamboj R. Dahiya (2014) Case Study to Estimate Sag in Overhead
Conductors Using GPS to Observe the Effect of Span Length. 978-1-
4799-3656-4/14/$31.00 2014 IEEE
[9] V.K. Mehta and Rohit Mehta (2014). Principles Power System. S.
Chand and Company Pvt. Ltd. Ram Nagar New Delhi.
0
500
1000
1500
2000
High
tower
Low
tower
High
tower
Low
tower
Tension Sag
Series1
0
500
1000
1500
2000
High
tower
Low
tower
High
tower
Low
tower
Tension Sag
Series1
International Journal of Computer Science and Information Security (IJCSIS),
Vol. 16, No. 4, April 2018
114 https://sites.google.com/site/ijcsis/
ISSN 1947-5500

More Related Content

What's hot

Towards An Accurate Modeling of Frequency-dependent Wind Farm Components Unde...
Towards An Accurate Modeling of Frequency-dependent Wind Farm Components Unde...Towards An Accurate Modeling of Frequency-dependent Wind Farm Components Unde...
Towards An Accurate Modeling of Frequency-dependent Wind Farm Components Unde...IJAPEJOURNAL
 
Chapter 2 mukesh gurjar
Chapter 2 mukesh gurjarChapter 2 mukesh gurjar
Chapter 2 mukesh gurjarMukesh gurjar
 
Types of transmission lines
Types of transmission linesTypes of transmission lines
Types of transmission linesSelf-employed
 
Chapter 4 mechanical design of transmission lines
Chapter 4  mechanical design of transmission linesChapter 4  mechanical design of transmission lines
Chapter 4 mechanical design of transmission linesfiraoltemesgen1
 
EE8402 Transmission and Distribution
EE8402 Transmission and DistributionEE8402 Transmission and Distribution
EE8402 Transmission and Distributionrmkceteee
 
Chapter 2 transmission line parameters
Chapter 2  transmission line parametersChapter 2  transmission line parameters
Chapter 2 transmission line parametersfiraoltemesgen1
 
New generation of copper conductors for overhead lines
New generation of copper conductors for overhead linesNew generation of copper conductors for overhead lines
New generation of copper conductors for overhead linesLeonardo ENERGY
 
Capacitance on transmission line
Capacitance on transmission lineCapacitance on transmission line
Capacitance on transmission linevishalgohel12195
 
Concept of general terms pertaining to rotating machines
Concept of general terms pertaining to rotating machinesConcept of general terms pertaining to rotating machines
Concept of general terms pertaining to rotating machinesvishalgohel12195
 
Power capacity of transmission lines
Power capacity of transmission linesPower capacity of transmission lines
Power capacity of transmission linesAlexander Decker
 
Parallel Operation of a Single Phase Transformer
Parallel Operation of a Single Phase TransformerParallel Operation of a Single Phase Transformer
Parallel Operation of a Single Phase TransformerRidwanul Hoque
 
26 Transmission Lines
26 Transmission Lines26 Transmission Lines
26 Transmission LinesLee Jennings
 
Classification of transmission lines
Classification of transmission linesClassification of transmission lines
Classification of transmission linesHamzaAbbas43
 
short transmission line
short transmission lineshort transmission line
short transmission lineMohil Shah
 
Eet3082 binod kumar sahu lecture_30
Eet3082 binod kumar sahu lecture_30Eet3082 binod kumar sahu lecture_30
Eet3082 binod kumar sahu lecture_30BinodKumarSahu5
 
Transformer wikipedia, the free encyclopedia
Transformer   wikipedia, the free encyclopediaTransformer   wikipedia, the free encyclopedia
Transformer wikipedia, the free encyclopediaBibek Chouhan
 

What's hot (19)

Towards An Accurate Modeling of Frequency-dependent Wind Farm Components Unde...
Towards An Accurate Modeling of Frequency-dependent Wind Farm Components Unde...Towards An Accurate Modeling of Frequency-dependent Wind Farm Components Unde...
Towards An Accurate Modeling of Frequency-dependent Wind Farm Components Unde...
 
Chapter 2 mukesh gurjar
Chapter 2 mukesh gurjarChapter 2 mukesh gurjar
Chapter 2 mukesh gurjar
 
Types of transmission lines
Types of transmission linesTypes of transmission lines
Types of transmission lines
 
Chapter 4 mechanical design of transmission lines
Chapter 4  mechanical design of transmission linesChapter 4  mechanical design of transmission lines
Chapter 4 mechanical design of transmission lines
 
EE8402 Transmission and Distribution
EE8402 Transmission and DistributionEE8402 Transmission and Distribution
EE8402 Transmission and Distribution
 
Chapter 2 transmission line parameters
Chapter 2  transmission line parametersChapter 2  transmission line parameters
Chapter 2 transmission line parameters
 
Transformers
TransformersTransformers
Transformers
 
Transformers
TransformersTransformers
Transformers
 
New generation of copper conductors for overhead lines
New generation of copper conductors for overhead linesNew generation of copper conductors for overhead lines
New generation of copper conductors for overhead lines
 
Transmission lines
Transmission linesTransmission lines
Transmission lines
 
Capacitance on transmission line
Capacitance on transmission lineCapacitance on transmission line
Capacitance on transmission line
 
Concept of general terms pertaining to rotating machines
Concept of general terms pertaining to rotating machinesConcept of general terms pertaining to rotating machines
Concept of general terms pertaining to rotating machines
 
Power capacity of transmission lines
Power capacity of transmission linesPower capacity of transmission lines
Power capacity of transmission lines
 
Parallel Operation of a Single Phase Transformer
Parallel Operation of a Single Phase TransformerParallel Operation of a Single Phase Transformer
Parallel Operation of a Single Phase Transformer
 
26 Transmission Lines
26 Transmission Lines26 Transmission Lines
26 Transmission Lines
 
Classification of transmission lines
Classification of transmission linesClassification of transmission lines
Classification of transmission lines
 
short transmission line
short transmission lineshort transmission line
short transmission line
 
Eet3082 binod kumar sahu lecture_30
Eet3082 binod kumar sahu lecture_30Eet3082 binod kumar sahu lecture_30
Eet3082 binod kumar sahu lecture_30
 
Transformer wikipedia, the free encyclopedia
Transformer   wikipedia, the free encyclopediaTransformer   wikipedia, the free encyclopedia
Transformer wikipedia, the free encyclopedia
 

Similar to Sag-Tension Analysis of AAAC Overhead Transmission Lines

ACSR Overhead Transmission lines Modeling Considering Sag-Tension Estimation ...
ACSR Overhead Transmission lines Modeling Considering Sag-Tension Estimation ...ACSR Overhead Transmission lines Modeling Considering Sag-Tension Estimation ...
ACSR Overhead Transmission lines Modeling Considering Sag-Tension Estimation ...IJCSIS Research Publications
 
Design aspects of high voltage transmission line
Design aspects of high voltage transmission lineDesign aspects of high voltage transmission line
Design aspects of high voltage transmission linejournalBEEI
 
Railroad Signal Protection: Planning New Power Transmission lines or Planning...
Railroad Signal Protection: Planning New Power Transmission lines or Planning...Railroad Signal Protection: Planning New Power Transmission lines or Planning...
Railroad Signal Protection: Planning New Power Transmission lines or Planning...Power System Operation
 
IRJET-Sensitivity Analysis of Maximum Overvoltage on Cables with Considering ...
IRJET-Sensitivity Analysis of Maximum Overvoltage on Cables with Considering ...IRJET-Sensitivity Analysis of Maximum Overvoltage on Cables with Considering ...
IRJET-Sensitivity Analysis of Maximum Overvoltage on Cables with Considering ...IRJET Journal
 
Design of 230 kV Twin Bundle Double Circuit Overhead Transmission Line
Design of 230 kV Twin Bundle Double Circuit Overhead Transmission LineDesign of 230 kV Twin Bundle Double Circuit Overhead Transmission Line
Design of 230 kV Twin Bundle Double Circuit Overhead Transmission Lineijtsrd
 
Chp 1 Intro to Transformers
Chp 1 Intro to TransformersChp 1 Intro to Transformers
Chp 1 Intro to Transformersable357
 
TRANSMISSION LINES and capacity.pptx
TRANSMISSION LINES and capacity.pptxTRANSMISSION LINES and capacity.pptx
TRANSMISSION LINES and capacity.pptxSatish Pydimarla
 
Determination of voltage regulation and power system losses
Determination of voltage regulation and power system lossesDetermination of voltage regulation and power system losses
Determination of voltage regulation and power system lossesManish Sadhu
 
Determination of Voltage Regulation and Power system losses
Determination of Voltage Regulation and Power system lossesDetermination of Voltage Regulation and Power system losses
Determination of Voltage Regulation and Power system lossesManish Sadhu
 
The sheath voltage_limiter
The sheath voltage_limiterThe sheath voltage_limiter
The sheath voltage_limiterGilberto Mejía
 
Transient voltage distribution in transformer winding (experimental investiga...
Transient voltage distribution in transformer winding (experimental investiga...Transient voltage distribution in transformer winding (experimental investiga...
Transient voltage distribution in transformer winding (experimental investiga...eSAT Publishing House
 
Transient voltage distribution in transformer winding (experimental investiga...
Transient voltage distribution in transformer winding (experimental investiga...Transient voltage distribution in transformer winding (experimental investiga...
Transient voltage distribution in transformer winding (experimental investiga...eSAT Journals
 
IJCER (www.ijceronline.com) International Journal of computational Engineerin...
IJCER (www.ijceronline.com) International Journal of computational Engineerin...IJCER (www.ijceronline.com) International Journal of computational Engineerin...
IJCER (www.ijceronline.com) International Journal of computational Engineerin...ijceronline
 
Stressanalysis linearityerror
Stressanalysis linearityerrorStressanalysis linearityerror
Stressanalysis linearityerrorNobantuNxumalo
 
Distortion Analysis of Differential Amplifier
Distortion Analysis of Differential AmplifierDistortion Analysis of Differential Amplifier
Distortion Analysis of Differential AmplifierIOSR Journals
 

Similar to Sag-Tension Analysis of AAAC Overhead Transmission Lines (20)

ACSR Overhead Transmission lines Modeling Considering Sag-Tension Estimation ...
ACSR Overhead Transmission lines Modeling Considering Sag-Tension Estimation ...ACSR Overhead Transmission lines Modeling Considering Sag-Tension Estimation ...
ACSR Overhead Transmission lines Modeling Considering Sag-Tension Estimation ...
 
H010526975
H010526975H010526975
H010526975
 
Design aspects of high voltage transmission line
Design aspects of high voltage transmission lineDesign aspects of high voltage transmission line
Design aspects of high voltage transmission line
 
Selection of transmission voltage
Selection of transmission voltageSelection of transmission voltage
Selection of transmission voltage
 
Railroad Signal Protection: Planning New Power Transmission lines or Planning...
Railroad Signal Protection: Planning New Power Transmission lines or Planning...Railroad Signal Protection: Planning New Power Transmission lines or Planning...
Railroad Signal Protection: Planning New Power Transmission lines or Planning...
 
S ag calc
S ag calcS ag calc
S ag calc
 
IRJET-Sensitivity Analysis of Maximum Overvoltage on Cables with Considering ...
IRJET-Sensitivity Analysis of Maximum Overvoltage on Cables with Considering ...IRJET-Sensitivity Analysis of Maximum Overvoltage on Cables with Considering ...
IRJET-Sensitivity Analysis of Maximum Overvoltage on Cables with Considering ...
 
05617901
0561790105617901
05617901
 
Design of 230 kV Twin Bundle Double Circuit Overhead Transmission Line
Design of 230 kV Twin Bundle Double Circuit Overhead Transmission LineDesign of 230 kV Twin Bundle Double Circuit Overhead Transmission Line
Design of 230 kV Twin Bundle Double Circuit Overhead Transmission Line
 
Chp 1 Intro to Transformers
Chp 1 Intro to TransformersChp 1 Intro to Transformers
Chp 1 Intro to Transformers
 
wireless power transfer
wireless power transferwireless power transfer
wireless power transfer
 
TRANSMISSION LINES and capacity.pptx
TRANSMISSION LINES and capacity.pptxTRANSMISSION LINES and capacity.pptx
TRANSMISSION LINES and capacity.pptx
 
Determination of voltage regulation and power system losses
Determination of voltage regulation and power system lossesDetermination of voltage regulation and power system losses
Determination of voltage regulation and power system losses
 
Determination of Voltage Regulation and Power system losses
Determination of Voltage Regulation and Power system lossesDetermination of Voltage Regulation and Power system losses
Determination of Voltage Regulation and Power system losses
 
The sheath voltage_limiter
The sheath voltage_limiterThe sheath voltage_limiter
The sheath voltage_limiter
 
Transient voltage distribution in transformer winding (experimental investiga...
Transient voltage distribution in transformer winding (experimental investiga...Transient voltage distribution in transformer winding (experimental investiga...
Transient voltage distribution in transformer winding (experimental investiga...
 
Transient voltage distribution in transformer winding (experimental investiga...
Transient voltage distribution in transformer winding (experimental investiga...Transient voltage distribution in transformer winding (experimental investiga...
Transient voltage distribution in transformer winding (experimental investiga...
 
IJCER (www.ijceronline.com) International Journal of computational Engineerin...
IJCER (www.ijceronline.com) International Journal of computational Engineerin...IJCER (www.ijceronline.com) International Journal of computational Engineerin...
IJCER (www.ijceronline.com) International Journal of computational Engineerin...
 
Stressanalysis linearityerror
Stressanalysis linearityerrorStressanalysis linearityerror
Stressanalysis linearityerror
 
Distortion Analysis of Differential Amplifier
Distortion Analysis of Differential AmplifierDistortion Analysis of Differential Amplifier
Distortion Analysis of Differential Amplifier
 

Recently uploaded

Neo4j - How KGs are shaping the future of Generative AI at AWS Summit London ...
Neo4j - How KGs are shaping the future of Generative AI at AWS Summit London ...Neo4j - How KGs are shaping the future of Generative AI at AWS Summit London ...
Neo4j - How KGs are shaping the future of Generative AI at AWS Summit London ...Neo4j
 
Transcript: #StandardsGoals for 2024: What’s new for BISAC - Tech Forum 2024
Transcript: #StandardsGoals for 2024: What’s new for BISAC - Tech Forum 2024Transcript: #StandardsGoals for 2024: What’s new for BISAC - Tech Forum 2024
Transcript: #StandardsGoals for 2024: What’s new for BISAC - Tech Forum 2024BookNet Canada
 
Advanced Test Driven-Development @ php[tek] 2024
Advanced Test Driven-Development @ php[tek] 2024Advanced Test Driven-Development @ php[tek] 2024
Advanced Test Driven-Development @ php[tek] 2024Scott Keck-Warren
 
Next-generation AAM aircraft unveiled by Supernal, S-A2
Next-generation AAM aircraft unveiled by Supernal, S-A2Next-generation AAM aircraft unveiled by Supernal, S-A2
Next-generation AAM aircraft unveiled by Supernal, S-A2Hyundai Motor Group
 
Injustice - Developers Among Us (SciFiDevCon 2024)
Injustice - Developers Among Us (SciFiDevCon 2024)Injustice - Developers Among Us (SciFiDevCon 2024)
Injustice - Developers Among Us (SciFiDevCon 2024)Allon Mureinik
 
#StandardsGoals for 2024: What’s new for BISAC - Tech Forum 2024
#StandardsGoals for 2024: What’s new for BISAC - Tech Forum 2024#StandardsGoals for 2024: What’s new for BISAC - Tech Forum 2024
#StandardsGoals for 2024: What’s new for BISAC - Tech Forum 2024BookNet Canada
 
AI as an Interface for Commercial Buildings
AI as an Interface for Commercial BuildingsAI as an Interface for Commercial Buildings
AI as an Interface for Commercial BuildingsMemoori
 
Install Stable Diffusion in windows machine
Install Stable Diffusion in windows machineInstall Stable Diffusion in windows machine
Install Stable Diffusion in windows machinePadma Pradeep
 
Pigging Solutions in Pet Food Manufacturing
Pigging Solutions in Pet Food ManufacturingPigging Solutions in Pet Food Manufacturing
Pigging Solutions in Pet Food ManufacturingPigging Solutions
 
Hyderabad Call Girls Khairatabad ✨ 7001305949 ✨ Cheap Price Your Budget
Hyderabad Call Girls Khairatabad ✨ 7001305949 ✨ Cheap Price Your BudgetHyderabad Call Girls Khairatabad ✨ 7001305949 ✨ Cheap Price Your Budget
Hyderabad Call Girls Khairatabad ✨ 7001305949 ✨ Cheap Price Your BudgetEnjoy Anytime
 
Pigging Solutions Piggable Sweeping Elbows
Pigging Solutions Piggable Sweeping ElbowsPigging Solutions Piggable Sweeping Elbows
Pigging Solutions Piggable Sweeping ElbowsPigging Solutions
 
08448380779 Call Girls In Greater Kailash - I Women Seeking Men
08448380779 Call Girls In Greater Kailash - I Women Seeking Men08448380779 Call Girls In Greater Kailash - I Women Seeking Men
08448380779 Call Girls In Greater Kailash - I Women Seeking MenDelhi Call girls
 
Kotlin Multiplatform & Compose Multiplatform - Starter kit for pragmatics
Kotlin Multiplatform & Compose Multiplatform - Starter kit for pragmaticsKotlin Multiplatform & Compose Multiplatform - Starter kit for pragmatics
Kotlin Multiplatform & Compose Multiplatform - Starter kit for pragmaticscarlostorres15106
 
Integration and Automation in Practice: CI/CD in Mule Integration and Automat...
Integration and Automation in Practice: CI/CD in Mule Integration and Automat...Integration and Automation in Practice: CI/CD in Mule Integration and Automat...
Integration and Automation in Practice: CI/CD in Mule Integration and Automat...Patryk Bandurski
 
Automating Business Process via MuleSoft Composer | Bangalore MuleSoft Meetup...
Automating Business Process via MuleSoft Composer | Bangalore MuleSoft Meetup...Automating Business Process via MuleSoft Composer | Bangalore MuleSoft Meetup...
Automating Business Process via MuleSoft Composer | Bangalore MuleSoft Meetup...shyamraj55
 
My Hashitalk Indonesia April 2024 Presentation
My Hashitalk Indonesia April 2024 PresentationMy Hashitalk Indonesia April 2024 Presentation
My Hashitalk Indonesia April 2024 PresentationRidwan Fadjar
 
Human Factors of XR: Using Human Factors to Design XR Systems
Human Factors of XR: Using Human Factors to Design XR SystemsHuman Factors of XR: Using Human Factors to Design XR Systems
Human Factors of XR: Using Human Factors to Design XR SystemsMark Billinghurst
 
Azure Monitor & Application Insight to monitor Infrastructure & Application
Azure Monitor & Application Insight to monitor Infrastructure & ApplicationAzure Monitor & Application Insight to monitor Infrastructure & Application
Azure Monitor & Application Insight to monitor Infrastructure & ApplicationAndikSusilo4
 
CloudStudio User manual (basic edition):
CloudStudio User manual (basic edition):CloudStudio User manual (basic edition):
CloudStudio User manual (basic edition):comworks
 

Recently uploaded (20)

Neo4j - How KGs are shaping the future of Generative AI at AWS Summit London ...
Neo4j - How KGs are shaping the future of Generative AI at AWS Summit London ...Neo4j - How KGs are shaping the future of Generative AI at AWS Summit London ...
Neo4j - How KGs are shaping the future of Generative AI at AWS Summit London ...
 
Transcript: #StandardsGoals for 2024: What’s new for BISAC - Tech Forum 2024
Transcript: #StandardsGoals for 2024: What’s new for BISAC - Tech Forum 2024Transcript: #StandardsGoals for 2024: What’s new for BISAC - Tech Forum 2024
Transcript: #StandardsGoals for 2024: What’s new for BISAC - Tech Forum 2024
 
Advanced Test Driven-Development @ php[tek] 2024
Advanced Test Driven-Development @ php[tek] 2024Advanced Test Driven-Development @ php[tek] 2024
Advanced Test Driven-Development @ php[tek] 2024
 
Next-generation AAM aircraft unveiled by Supernal, S-A2
Next-generation AAM aircraft unveiled by Supernal, S-A2Next-generation AAM aircraft unveiled by Supernal, S-A2
Next-generation AAM aircraft unveiled by Supernal, S-A2
 
Injustice - Developers Among Us (SciFiDevCon 2024)
Injustice - Developers Among Us (SciFiDevCon 2024)Injustice - Developers Among Us (SciFiDevCon 2024)
Injustice - Developers Among Us (SciFiDevCon 2024)
 
#StandardsGoals for 2024: What’s new for BISAC - Tech Forum 2024
#StandardsGoals for 2024: What’s new for BISAC - Tech Forum 2024#StandardsGoals for 2024: What’s new for BISAC - Tech Forum 2024
#StandardsGoals for 2024: What’s new for BISAC - Tech Forum 2024
 
AI as an Interface for Commercial Buildings
AI as an Interface for Commercial BuildingsAI as an Interface for Commercial Buildings
AI as an Interface for Commercial Buildings
 
E-Vehicle_Hacking_by_Parul Sharma_null_owasp.pptx
E-Vehicle_Hacking_by_Parul Sharma_null_owasp.pptxE-Vehicle_Hacking_by_Parul Sharma_null_owasp.pptx
E-Vehicle_Hacking_by_Parul Sharma_null_owasp.pptx
 
Install Stable Diffusion in windows machine
Install Stable Diffusion in windows machineInstall Stable Diffusion in windows machine
Install Stable Diffusion in windows machine
 
Pigging Solutions in Pet Food Manufacturing
Pigging Solutions in Pet Food ManufacturingPigging Solutions in Pet Food Manufacturing
Pigging Solutions in Pet Food Manufacturing
 
Hyderabad Call Girls Khairatabad ✨ 7001305949 ✨ Cheap Price Your Budget
Hyderabad Call Girls Khairatabad ✨ 7001305949 ✨ Cheap Price Your BudgetHyderabad Call Girls Khairatabad ✨ 7001305949 ✨ Cheap Price Your Budget
Hyderabad Call Girls Khairatabad ✨ 7001305949 ✨ Cheap Price Your Budget
 
Pigging Solutions Piggable Sweeping Elbows
Pigging Solutions Piggable Sweeping ElbowsPigging Solutions Piggable Sweeping Elbows
Pigging Solutions Piggable Sweeping Elbows
 
08448380779 Call Girls In Greater Kailash - I Women Seeking Men
08448380779 Call Girls In Greater Kailash - I Women Seeking Men08448380779 Call Girls In Greater Kailash - I Women Seeking Men
08448380779 Call Girls In Greater Kailash - I Women Seeking Men
 
Kotlin Multiplatform & Compose Multiplatform - Starter kit for pragmatics
Kotlin Multiplatform & Compose Multiplatform - Starter kit for pragmaticsKotlin Multiplatform & Compose Multiplatform - Starter kit for pragmatics
Kotlin Multiplatform & Compose Multiplatform - Starter kit for pragmatics
 
Integration and Automation in Practice: CI/CD in Mule Integration and Automat...
Integration and Automation in Practice: CI/CD in Mule Integration and Automat...Integration and Automation in Practice: CI/CD in Mule Integration and Automat...
Integration and Automation in Practice: CI/CD in Mule Integration and Automat...
 
Automating Business Process via MuleSoft Composer | Bangalore MuleSoft Meetup...
Automating Business Process via MuleSoft Composer | Bangalore MuleSoft Meetup...Automating Business Process via MuleSoft Composer | Bangalore MuleSoft Meetup...
Automating Business Process via MuleSoft Composer | Bangalore MuleSoft Meetup...
 
My Hashitalk Indonesia April 2024 Presentation
My Hashitalk Indonesia April 2024 PresentationMy Hashitalk Indonesia April 2024 Presentation
My Hashitalk Indonesia April 2024 Presentation
 
Human Factors of XR: Using Human Factors to Design XR Systems
Human Factors of XR: Using Human Factors to Design XR SystemsHuman Factors of XR: Using Human Factors to Design XR Systems
Human Factors of XR: Using Human Factors to Design XR Systems
 
Azure Monitor & Application Insight to monitor Infrastructure & Application
Azure Monitor & Application Insight to monitor Infrastructure & ApplicationAzure Monitor & Application Insight to monitor Infrastructure & Application
Azure Monitor & Application Insight to monitor Infrastructure & Application
 
CloudStudio User manual (basic edition):
CloudStudio User manual (basic edition):CloudStudio User manual (basic edition):
CloudStudio User manual (basic edition):
 

Sag-Tension Analysis of AAAC Overhead Transmission Lines

  • 1. Sag-Tension Analysis of AAAC Overhead Transmission lines for Hilly Areas Muhammad Zulqarnain Abbasi, M. Aamir Aman, Hamza Umar Afridi, Akhtar Khan IQRA National University, Pakistan Abstract—Power system is the transfer of electricity from generation to the point of user location. Power system is composed of generation of power, its transmission and distribution. Transmission system is the main part out of these three in which mostly losses occur. The unchanging factors of the transmission line on which these losses depend are inductance, resistance and capacitance. These constants or unchanging factors play a vital role in the performance of transmission line. For example the capacitance effect will be more and its performance will be affected if the height of transmission line is less from the ground. On the other hand its capacitance will be less but tension will be high if the height of the transmission is high. For this reason a transmission line is connected in a curved or catenary shape known as sag. To minimize tension sag is provided in a transmission line. Sag and tension must be adjusted in safe limits. This immediate paper gives a simulation structure to calculate sag and tension of AAAC (All Aluminum Alloy Conductors of overhead transmission lines with same span length for minimum operating temperature. Three different cases are presented with different towers height and are explained in detail for unequal level span. The results show that the tension and sag increased with height. So great the height difference, higher tensions upon higher towers. This paper will be very helpful to find the sag-tension values of AAAC conductor for Unequal level supports without calculating it mathematically. Keywords-component;sag;tension;transmission system I. INTRODUCTION System transferring electricity from generation to transmission is known as transmission system. In transmission system transmission lines and substations play a major role. In power system network the biggest part is incorporated by the lines transporting electricity. Designing and erecting transmission system require proper construction or modeling of these lines. A transmission systems successive execution depends on kind of transmission model used in the system. Catenary is the term given to the curve shape in which transmission lines are connected between supportive towers or power. Transmission line is never connected in straight line. To minimize the tension in the transmission system sag is provided to the transmission line. Similarly, if the tension is high in transmission line, sag will be minimum and there is a possibility that the conductor may break. Sag and tension are inversely proportional to each other. However, if sag increase the size of conductor used also increases and the cost is raised. The distance between two towers depends on the sag intensity. If the distance between two towers is significant the sag will also be large. Sag-Tension computations are aimed at fixing suitable restrictions between sag and tension in order to continue or steady uninterrupted power supply to the users. With Sag-Tension calculations we can determine the conductor temperature as well as ice and wind; load concurrently. Tension is the limit of towers and conductor to keep the tension limited. Sag clearance distance is dependent on line crossings and ground. If the clearance distance is less than crossing distance chances are that line faults may occur. The “V” or “I” configuration also play important role for calculating sag-tension along with quantity of insulator strings. Naturally, insulator string possesses the attributes of an element. Being element provides add up of great distance to sag created by the conductor. Considering bunch of conductors is also important in different cases. For each phase two or more conductors are used. Extra high voltage system may use two bunches of conductors per phase. Occasionally, a substation that is accumulating power from generating station may use three conductors or power lines for each phase. Hence, the foundations regarding the sag- tension approximation process are obligatory to examine and guarantee or certify that the result match the true state. Figure 1. Sag in Overhead Conductor International Journal of Computer Science and Information Security (IJCSIS), Vol. 16, No. 4, April 2018 111 https://sites.google.com/site/ijcsis/ ISSN 1947-5500
  • 2. The above figure is showing that there are two equal supports named as point A and B. while point O is the lowest point between two supports. Similarly “S” is referred as sag which is distance between the point of support and lowest point of conductor. II. CALCULATION OF SAG In overhead transmission line designing, it is important to keep sag under safe limit, and at same time tension running in the conductor is also within safe limit. . As a matter of fact, tension is administered by weight of conductor, ice load on wires, temperature variation and effect of wind. According to common practice, the tension of conductor is kept under 50% of its ultimate tensile power. It means least factor of safety of a conductor tension needs to be two. Now sag as well as tension calculation of a conductor for Unequal support will be carry out [8]. A. When supports are at Un- equal levels In hilly areas, we generally come across conductors Suspended between supports at unequal levels. Figure 2. shows a conductor suspended between two supports A and B Which are at different levels. The lowest point on the conductor is O. Let l = Span length h = Difference in levels between two supports X 1 = Distance of support at lower level (i.e. A) from O X2 = Distance of support at higher level (i.e. B) from O T = Tension in the conductor Figure 2. When supports are at Unequal levels If w is the weight per unit length of the conductor, then 𝑆𝑎𝑔 𝑆1 = 𝑤𝑥1 2 2𝑇 and 𝑆𝑎𝑔 𝑆2 = 𝑤𝑥2 2 2𝑇 Also 𝑥1 + 𝑥2 = 𝑙 (𝒊) Now 𝑆2 − 𝑆1 = 𝑤 2𝑇 (𝑥2 2 − 𝑥1 2 ) = 𝑤 2𝑇 (𝑥2 + 𝑥1)(𝑥2 − 𝑥1) 𝑆2 − 𝑆1 = 𝑤𝑙 2𝑇 (𝑥2 − 𝑥1) But 𝑆2 − 𝑆1 = ℎ ℎ = 𝑤𝑙 2𝑇 (𝑥2 − 𝑥1) 𝑥2 − 𝑥1 = 2𝑇ℎ 𝑤𝑙 (𝒊𝒊) Solving eq. (i) and (ii), we get 𝑥1 = 𝑙 2 − 𝑇ℎ 𝑤𝑙 𝑥2 = 𝑙 2 + 𝑇ℎ 𝑤𝑙 III. METHODOLOGY For the result-oriented sag-tension of AAAC transmission line considering different unequal span heights of minimum operating condition are analyze in this research paper. The tool used for the calculation is ETAP.The module ETAP containing an analytical strength for Transmission and Distribution Line Sag and Tension calculation. It is easily available low cost simulation software to calculate the appropriate sag & tension in order to ensure appropriate operating conditions on the overhead transmission lines. The spans length for all cases is same which are 200m and the conductors configuration is set as horizontal. Three Different cases i.e. 1, 2 & 3 are considered. • In case 1 calculated sag-tension of AAAC overhead transmission lines under minimum operating condition with the height difference of 10m. • In case 2 calculated sag-tension of AAAC overhead transmission lines with same temperature as previous one but the height difference is 30m. • In case 3 calculated sag-tension of AAAC overhead transmission lines under minimum operating condition with maximum height difference of 50m. These calculations are for unequal level spans only and when both the towers are at height difference of 10m, 30m and 50m respectively. International Journal of Computer Science and Information Security (IJCSIS), Vol. 16, No. 4, April 2018 112 https://sites.google.com/site/ijcsis/ ISSN 1947-5500
  • 3. The conductor used in this paper is AAAC (All Aluminum Alloy Conductor) because: These conductors are of high strength made of Aluminum-Magnesium-Silicon alloy and are having better ratio of strength to weight enabling the conductors to exhibit more efficient electrical characteristic. They have excellent sag-tension characteristics and superior corrosion resistance when compared with other conductors. Comparing with traditional ACSR, AAAC are lighter in weight, are having lower electrical losses and comparable strength and current carrying capacity. IV. RESULTS AND DISCUSSION A. Case 1 In the 1st case, sag-tension under minimum operating temperature i.e. 5˚C with a height difference of 10m is analyzed. As in hilly areas towers are at different heights so in this case we have considered only 10m height difference. TABLE I. MINIMUM TEMPERATURE WITH 10M HEIGHT DIFFERENCE Type of Conductor Minimum Temperature (5 °C) and height (10m) Tension Sag Low Tower High Tower Low Tower High Tower AAAC 1697 1707 0 10 In the above table sag and tension results of minimum operating temperature with 10m height difference is shown. As it shows above that when support are at 10m height difference the tension on high tower is 1707 while on low tower it is 1697. Similarly incase of sag high tower has more sag 10m than the lower tower. The results are also shown below with the help of graph. Figure 3. Sag-Tension Results with 10m height difference B. Case 2 In this case temperature is same as the previous one but the height difference is 30m. As mentioned earlier that hilly areas have different heights for supporting towers so therefore in this case we have consider 30m height difference. TABLE II. MINIMUM TEMPERATURE WITH 30M HEIGHT DIFFERENCE Type of Conductor Minimum Temperature (5°C) and height (30m) Tension Sag Low Tower High Tower Low Tower High Tower AAAC 1711 1738 0 30 As from the above table sag and tension results of minimum operating temperature with 30m height difference are given. When supports are at 30m height difference the tension on high tower is 1738 while on low tower is 1711. Similarly incase of sag high tower has more sag 30m than the lower tower because high tower exerts high tension. The results are also shown below with the help of graph. 0 500 1000 1500 2000 High tower Low tower High tower Low tower Tension Sag Series1 International Journal of Computer Science and Information Security (IJCSIS), Vol. 16, No. 4, April 2018 113 https://sites.google.com/site/ijcsis/ ISSN 1947-5500
  • 4. Figure 4. Sag-Tension Results with 30m height differnce C. Case 3 In 3rd case, sag and tension with minimum operating temperature and height difference of 50m is consider. TABLE III. MINIMUM TEMPERATURE WITH 50M HEIGHT DIFFERENCE Type of Conductor Minimum Temperature (5 °C) and height (50m) Tension Sag Low Tower High Tower Low Tower High Tower AAAC 1747 1793 0 50 In the above table sag and tension results of minimum operating temperature with 50m height difference is mention. The above table shows that when support are at 50m height difference the tension on high tower is 1793 while on low tower is 1747. Similarly incase of sag high tower has more sag 50m than the lower tower. The results are also shown below with the help of graph. Figure 5. Sag-Tension Results with 50m height differnce V. CONCLUSION AND FUTURE WORK This research paper has three different cases which are taken from analysis of sag and tension estimation for AAAC Overhead transmission lines. Equal span length is considered for all cases. Three different towers height were considered with minimum operating conditions. From the results following conclusion is drawn: In 1st case the temperature is minimum but the height difference was 10m. So when the height difference was minimum (10m) the tension in higher tower is high than the lower tower. Similarly for 2nd case, the temperature was set same as the previous case but the height difference increased from 10m to 30m. As the height increases the tension will act more force on higher tower as compare to low tower. In the 3rd case temperature was same again but the height difference was maximum (50m). So due to high difference in towers height the tension on higher tower is also greater due to height. In AAAC the tension and sag increased with height. So great the height difference, higher tensions upon higher towers. From this paper, one can easily find the sag-tension values of AAAC conductor for Unequal level supports without calculating it mathematically. In future, the sag-tension estimation of other conductors will also be considered in ETAP. REFERENCES [1] I. Albizu, A. J. Mazon, and E. Fernandez (2011). “A method for the Sag-tension, calculation in electrical overhead lines. International Review of Electrical Engineering, volume 6, No. 3 pp. 1380-1389 [2] J. Quintana, V. Garza, C. Zamudio(2016). Sag-Tension Calculation Program for Power Substations. IEEE PES Asia-Pacific Power and Energy Conference- Xi’an-China. [3] Maamar Taleb, Mohamed Jassim Ditto, Tahar Bouthiba (2006). Performance of Short Transmission Lines Model . University of Bahrain Department of Electrical and Electronics Engineering. [4] Oluwajobi F. I., Ale O. S. and Ariyanninuola A (2012). Effect of Sag on Transmission Line. Journal of Emerging Trends in Engineering and Applied Sciences (JETEAS) 3 (4): 627-630 © Scholar link Research Institute Journals, (ISSN: 2141-7016). [5] R.G. Olsen, K.S Edward (2002) “A New method for Real Time Monitoring of High Voltage Transmission line Conductor sag. IEEE Transactions on Power Delivery Vol. 17, No. 4, pp 1142-1152. [6] Sag-Tension Calculation Methods for Overhead Lines (2007). CIGRE B2-12 Brochure (Ref. No. 324) pp. 31-43. [7] Seppa T O, 1992, A Practical Approach For Increasing the Thermal Capabilities of Transmission lines, IEEE/PES Summer Meeting, pp 1536-1542 [8] S. Kamboj R. Dahiya (2014) Case Study to Estimate Sag in Overhead Conductors Using GPS to Observe the Effect of Span Length. 978-1- 4799-3656-4/14/$31.00 2014 IEEE [9] V.K. Mehta and Rohit Mehta (2014). Principles Power System. S. Chand and Company Pvt. Ltd. Ram Nagar New Delhi. 0 500 1000 1500 2000 High tower Low tower High tower Low tower Tension Sag Series1 0 500 1000 1500 2000 High tower Low tower High tower Low tower Tension Sag Series1 International Journal of Computer Science and Information Security (IJCSIS), Vol. 16, No. 4, April 2018 114 https://sites.google.com/site/ijcsis/ ISSN 1947-5500