Ferroresonance Conditions in Wind Parks
U. Karaagac, J. Mahseredjian, L. Cai
Abstract--Wind parks are made up of a large number of
saturable inductances (power transformers, inductive voltage
transformers (IVTs)), as well as capacitors (cables, wind turbine
harmonic filters, capacitor voltage transformers (CVTs), voltage
grading capacitors in circuit-breakers). Therefore, they may
present scenarios in which ferroresonance occurs. This paper
presents the scenarios that can lead to ferroresonant circuits in
doubly fed induction generator (DFIG) based wind parks.
Ferroresonance conditions and their consequences are
demonstrated by simulating the detailed model of the wind park
in EMTP-RV. The wind park simulation model includes detailed
models of wind turbines, medium voltage (MV) collector grid,
high voltage / medium voltage (HV/MV) wind park substation,
overvoltage, overcurrent and differential current protections,
current transformers (CTs), IVTs and CVTs.
Keywords: Ferroresonance, wind parks, power transformers,
inductive voltage transformers (IVTs), capacitor voltage
transformers (CVTs), overvoltage, overcurrent.
I. INTRODUCTION
ERRORESONANCE is an oscillatory phenomena caused
by the interaction of energy exchanged between the
nonlinear magnetizing inductances of the ferromagnetic cores
and the system capacitances. The main feature of this
phenomenon is the presence of at least two stable steady-state
operating points for a particular range of circuit parameters: a
ferroresonant operating point and a normal (non-
ferroresonant) operating point. Transient disturbances or
switching operations may initiate ferroresonance. The
response can suddenly jump from one normal operating point
(sinusoidal at the same frequency as the source) to another
ferroresonant operating point characterized by high
overvoltages and harmonic levels which may lead to excessive
heating and insulation failure in transformers as well as
significant disruptions in power system operation [1], [2].
This paper presents the scenarios that can lead to
ferroresonant circuits in an actual doubly fed induction
generator (DFIG) based wind park. Ferroresonance conditions
and their consequences are demonstrated by simulating the
detailed model of the wind park in EMTP-RV.
This work was supported by the German Federal Ministry for the
Environment, Nature Conservation, Building and Nuclear Safety, grant code:
032529.
U. Karaagac and J. Mahseredjian are with École Polytechnique de Montréal,
Campus Université de Montréal, 2900, Édouard-Montpetit, Montréal
(Québec), Canada, H3T 1J4.
L. Cai is with Senvion SE, Überseering 10, D-22297, Hamburg, Germany.
Paper submitted to the International Conference on Power Systems
Transients (IPST2015) in Cavtat, Croatia June 15-18, 2015
The first part of this paper presents the theoretical
principles of ferroresonance. The second part presents the
considered wind park and the electric configurations that can
lead to ferroresonant circuits. The simulation results are
presented in the last part.
II. FERRORESONANCE
In simple terms, ferroresonance can be described as a
nonlinear oscillation resulting from the interaction between a
nonlinear inductance and a capacitor. Like linear resonance,
depending on the connection between the capacitance and the
nonlinear inductance, ferroresonance may be series or parallel.
This paper analyzes only the series ferroresonance shown in
Fig. 1.
Fig. 1. Series ferroresonant circuit.
The graphical solution of the series resonant circuit is
shown in Fig. 2 for the lossless case (i.e. R = 0). The
intersection of “US + UC” line with the nonlinear US (I) curve
gives three possible operating points:
- Operating point (1): Non-ferroresonant stable
operating point in which the circuit is working in an
inductive mode, with lagging current and low
voltages.
- Operating point (2): Ferroresonant stable operating
point in which the circuit is working in a capacitive
mode, with leading current and high voltages.
- Operating point (3): Unstable operating point.
3 2 5 2 1 5 1 0 5 0 0 5 1 1 5 2
1
5
0
5
1
I
1
3
2
U
Fig. 2. Graphical solution of a series ferroresonant circuit (R = 0).
F
S
U
C
U
L
U
C
U L
U
S
U
S C
U U
( )L
U I
S
U

 R
U  C
U 
L
U


R C
L
It should be noted that, the deep analysis of the circuit
shown in Fig. 1 requires the solution of nonlinear differential
equations. The presence of nonlinearity introduces harmonics
in the voltage and current waveforms. However, in Fig.2, the
analysis of the circuit is simplified by limiting the calculations
to the power frequency and steady state in order to provide a
conceptual description of ferroresonance [3]-[5].
A. Effect of Source Voltage
The effect of the source voltage is illustrated in Fig. 3. As
the source voltage is increased, the “US +UC” line moves
upwards. When the source voltage is higher than US-critical (“US
+ UC” line tangent to the nonlinear US (I) curve), there is no
intersection in the first quadrant. In other words, the system
solution is always a ferroresonant situation.
As seen from Fig. 3, the ferroresonant oscillations can be
self-sustained when the circuit has no losses. In other words,
removing voltage source may not result in the elimination of
ferroresonance. The operating point simply slides to the right,
but remains in the saturated region. In reality, ferroresonant
oscillations cannot be self-sustained due to circuit losses.
3 2 5 2 1 5 1 0 5 0 0 5 1 1 5 2
1
5
0
5
1
I
U
Fig. 3. Graphical solution illustrating the effect of source voltage.
B. Effect of Circuit Capacitance
The effect of the circuit capacitance is illustrated in Fig. 4.
As the circuit capacitance is increased, the “US +UC” line
rotates clock-wise, i.e. its slope decreases. As seen from Fig.
4, ferroresonant situation can appear for a wide range of
capacitance values at a given frequency.
Fig. 5 illustrates the theoretical conditions to avoid periodic
ferroresonance. It can be observed when [1]
1
sat linearL L
C
 

  (1)
C. Effect of Circuit Losses
When the losses are considered, the equation describing the
steady-state behaviour of the circuit shown in Fig. 1 can be
written as
 22
( )L C SU I U U R I   (2)
The graphical solution is shown in Fig.6. For the low
circuit resistance (R1), there are three possible solutions.
Solutions (1) and (2) in Fig.6 correspond to the non-
ferroresonant and the ferroresonant situations, respectively. As
seen from Fig.6, the multiplicity of solutions can disappear
when the circuit losses increases.
3 2 5 2 1 5 1 0 5 0 0 5 1 1 5 2
1
5
0
5
1
I
U
Fig. 4. Graphical solution illustrating the effect of circuit capacitance.
0 0.2 0.4 0.6 0.8 1 1.2 1.4 1.6 1.8 2
0
0.2
0.4
0.6
0.8
1
1.2
Fig. 5. Periodic ferroresonance conditions.
0 0.5 1 1.5 2 2.5 3
0
0.05
0.1
0.15
0.2
0.25
0.3
0.35
0.4
0.45
1"
3'
2'
1'
1
I
U
23
Fig. 6. Graphical solution illustrating the effect of circuit losses (R1 > R2).
III. WIND PARK UNDER STUDY
The simplified single-line diagram of the wind park studied
in this paper is given in Fig. 7. The wind park collector grid is
composed of three radial 34.5 kV feeders and connected to
120 kV grid through a 120 MVA step-up transformer. The
collector grid feeders F1, F2 and F3 contain 15, 7 and 18
DFIG-type wind turbines (WTs), respectively. Each WT has 2
MW rating and connected to 34.5 kV collector grid through a
2.5 MVA ΔYg transformer. The EMTP-RV diagram of the
wind park substation is given in Fig. 8. The isolating switches
are not shown in in Fig. 8. The reader should refer to [6] for
detailed information regarding DFIG WTs and wind park
control.
L C
U U
2 2
(
1
)S
U R I
2 2
(
2
)S
U R I
S
U
1
linear
L
C



linear
L
sat
L
1
sat
L
C



C
U
1 2S S S critical
U U U 

U
S critical C
U 

2S C
U U
( )L
U I
1S C
U U
1 2 3
C C C 3
U
S C
U 
2S C
U U
( )L
U I
1S C
U U
70 kV / 115 V
600A / 5A CT
To WPC
35 m cable
To WPC
trip signal from
protective relays
600A / 5A CT
To TR-1 input OCR
HV CB
To HV/MV transformer
differential protection
600A / 5A CT
ZnO arrester
50 m cable
ZnO arrester
120 kV / 34.5 kV
120 MVA
Transformer
To BUS-1 input OCR 2000A / 5A CT
2000A / 5A CT
To HV/MV transformer
differential protection
600A / 5A CT
10 ohm / phase
zig-zag transformer
secondary
short circuited
auxiliary service
transformer 60 m cable
2000A / 5A CT
2000A / 5A CTTo BUS-2 input OCR
To BUS-2
differential protection
To Feeder-1 OCR
1200A / 5A CT
135.5 ohm / phase
zig-zag transformer
200A / 5A CT
1200A / 5A CT
135.5 ohm / phase
zig-zag transformer
200A / 5A CT
FOR FUTURE EXPANSION
ZnO arrester
1200A / 5A CT
2000A / 5A CT
To Feeder-1 OCR
To BUS-2
differential protection
fuse
fuse
135.5 ohm / phase
zig-zag transformer
15 m cable
ZnO arrester
Feeder F1
trip signal from
protective relays
fuse To Feeder-2 OCR
1200A / 5A CT
2000A / 5A CT
To Feeder-2 OCR
To BUS-2
differential protection
135.5 ohm / phase
zig-zag transformer
15 m cable
ZnO arrester
Feeder F2
trip signal from
protective relays
fuse
To Feeder-3 OCR
1200A / 5A CT
2000A / 5A CT
To Feeder-3 OCR
To BUS-2
differential protection
135.5 ohm / phase
zig-zag transformer
15 m cable
ZnO arrester
Feeder F3
trip signal from
protective relays
fuse
trip signal from
protective relays
F1 CB F2 CB F3 CB
secondary
short circuited
secondary
short circuited
secondary
short circuited
BUS-2
BUS-1
BUS2 CB
20125V / 115V / 67.08V
fuse
To BUS-2 input OCR
fuse To measuring devices
20125V / 115V / 67.08V20125V / 115V / 67.08V20125V / 115V / 67.08V
20125V / 115V / 67.08V
IVT-1
IVT-2
IVT-F1 IVT-F2 IVT-F3
CVT
RL
+
Page
Page
Page
RL
+
Page
1
+30
X
Page
ZnO+
ZnO+
Page
Page
ZnO+
>e
P
S1
S2
12
-30
RL
+
Page
Page
Page
X
Page
Page
X
X
XRL
+
ZnO+
>e
Page
P
S1
S2
Page
Page
Page
XRL
+
ZnO+
>e
Page
P
S1
S2
Page
Page
Page
XRL
+
ZnO+
>e
Page
Page
P
S1
S2
Page
P
S1
S2
Page
Fig. 8. EMTP-RV diagram of the wind park substation
120 kV Grid
Feeder F1 (15 WTs)34.5 kV
Collector Bus
Feeder F2 (7 WTs)
Feeder F3 (18 WTs)
120 kV /34.5 kV
Wind Park
Transformer
Wind Park
Substation
RL
+
RL
+
RL
+
RL
+
RL
+
+30
X
X
X
X
Fig. 7. Simplified single-line diagram of the wind park.
There are several electric configurations that can lead to
ferroresonant circuits in power systems. In [7] seven different
classes or categories of electrical systems prone to
ferroresonance appearance are identified. The following three
electric configurations exist in the considered wind park.
1. Transformer supplied accidently on one or two
phases [8]-[10];
2. Inductive voltage transformer (IVT) energized
through the grading capacitance of one or more open
circuit breakers [11], [12];
3. Capacitor voltage transformer (CVT) [13], [14].
A. Transformer Supplied Accidently on One or Two
Phases
The DFIG transformers have delta primary connection and
ferroresonance may occur when they are supplied on one or
two phases. The ferroresonant circuit is created through the
phase-to ground capacitance(s) of the open phase(s) as shown
in Fig. 9. The following scenarios can be expected to cause
ferroresonance:
1. Energizing a DFIG transformer (via closing
associated MV load break switch) when one or two
phases of the feeder cable are live due to a stuck pole
or poles in the feeder circuit breaker,
2. Energizing collector grid feeder on one or two phases
due to a stuck pole or poles in the feeder circuit
breaker when the DFIG transformers (one or more)
are connected to the feeder to be energized,
3. A stuck pole (or poles) in the circuit breaker during
opening following nuisance operation of the
overcurrent relay (OCR).
It should be noted that, the feeder cables and DFIG
transformers are energized sequentially during startup.
Therefore, the second scenario cannot happen when the
startup procedure is followed.
Fig. 9. Ferroresonant circuit in a transformer with delta primary connection
[1].
B. Transformer Energized Through the Grading
Capacitance of One or More Open Circuit Breakers
This electrical configuration is shown in Fig. 10. Opening
of circuit-breaker initiates the phenomenon by causing
capacitance C to discharge through the IVT which is then
driven into saturation. The source delivers enough energy
through the circuit-breaker grading capacitance Cd to maintain
the oscillation [11], [15].
Fig. 10. IVT in series with an open circuit breaker [1].
In the considered wind park, the IVTs may form a
ferroresonant circuit with the grading capacitance of circuit-
breakers for the following scenarios:
1. BUS2 IVT and BUS2 input circuit breaker grading
capacitance (IVT-2 and BUS2 CB in Fig. 8) when
34.5 kV feeders are disconnected;
2. BUS1 IVT and 120 kV wind park transformer input
circuit breaker grading capacitance (IVT-1 and HV
CB in Fig. 8) when BUS-2 is disconnected.
C. Capacitive Voltage Transformer (CVT)
The structure of CVTs makes them particularly prone to
ferroresonance. Manufacturers are aware of this problem and
install various types of suppression circuits. These suppression
circuits should not affect either the transient response or the
accuracy of the transformer, but limiting the duration of the
ferroresonant oscillations [16]-[20]. As seen in Fig. 8, the
considered wind park has a CVT at 120 kV.
Fig. 11. Capacitive voltage transformer (CVT) [2].
IV. EMTP-RV SIMULATIONS
A. Simulation Model
The simulation model in [6] is used in this study. The
model includes detailed models of DFIG WTs, wind park
controller, MV collector grid, HV/MV wind park substation,
overvoltage protection, overcurrent and differential current
protections, current transformers, IVTs and CVTs. It should
be noted that, all simulation data is provided by the
manufacturer except the circuit breaker grading capacitances.
B. Simulation Results
1) Scenario S1
This scenario is energizing the feeder F1 (at t = 0.75 s) on
two phases due to a stuck pole (the pole on phase-c) in the
feeder F1 circuit breaker (F1 CB in Fig. 8) when all DFIG
transformers are connected to the feeder. This scenario is not
expected to happen as the feeder cables and DFIG
transformers are energized sequentially during startup and
presented only to demonstrate the ferroresonance
phenomenon.
It should be noted that energizing one of the DFIG
transformers with closing the associated MV load break
switch does not cause ferroresonance (when one or two phases
of the feeder F1 cable is live) even for 1.5 pu voltage at
collector grid. In the simulations, such large voltage profile in
collector grid is achieved by increasing DFIG output and
transmission system equivalent source voltages after
deactivating DFIG overvoltage protection and certain
controller limits.
The voltages at MV and LV sides of the DFIG-F104 (one
of the DFIGs on feeder F1) transformer are shown in Fig. 12
and in Fig. 13, respectively. The high overvoltage at
transformer terminals is due to ferroresonance. The voltage
waveforms at the other DFIG transformer terminals on feeder
F1 are similar to DFIG-F104 transformer terminals. The
energy absorptions of the surge arresters at the MV and the
LV sides of the DFIG-F104 transformer are given in Fig. 14
and Fig. 15, respectively. As the ferroresonance condition will
continue due to low damping (see Fig. 12 and Fig. 13), the
energy absorptions of the surge arresters will continue
increasing. The DFIG transformers and surge arresters are
subjected to this overvoltage.
This ferroresonance condition does not affect the operation
of the DFIGs on feeders F2 and F3 as it does not cause
overvoltage at their terminals as illustrated in Fig. 16.
The possibility of ferroresonance can be expected to
decrease with the decrease in the number of DFIG
transformers connected to the feeder to be energized.
0.8 1 1.2 1.4 1.6 1.8 2
-60
-40
-20
0
20
40
60
t (s)
Vabc(kV)
Fig. 12. Voltages at MV side of the DFIG-F104 transformer.
0.8 1 1.2 1.4 1.6 1.8 2
-1
-0.8
-0.6
-0.4
-0.2
0
0.2
0.4
0.6
t (s)
Vabc(kV)
Fig. 13. Voltages at LV side of the DFIG-F104 transformer.
0.8 1 1.2 1.4 1.6 1.8 2
0
2
4
6
8
10
t (s)
ArresterEnergy(kJ)
arrester on phase-b
arrester on phase-a
arrester on phase-c
Fig. 14. DFIG- F104 transformer MV arrester energy absorption.
0.8 1 1.2 1.4 1.6 1.8 2
0
5
10
15
20
25
30
35
40
t (s)
ArresterEnergy(J)
arrester on phase-c
arrester on phase-b
arrester on phase-a
Fig. 15. DFIG- F104 transformer LV arrester energy absorption.
0.7 0.75 0.8 0.85 0.9 0.95 1
-0.4
-0.2
0
0.2
0.4
0.6
t (s)
Vabc
(kV)
Fig. 16. Voltages at one of the DFIG terminals on feeder F2 (DFIG-F204).
2) Scenario S2:
This scenario is nuisance tripping of feeder F1 OCR and a
stuck pole (the pole on phase-c) in F1 CB. F1 CB operates at t
= 0.75 s in the simulation. The voltages at MV and LV sides
of the DFIG-F104 transformer are shown in Fig. 17 and in
Fig. 18, respectively. The high overvoltage at transformer
terminals is due to ferroresonance condition. DFIG-F104 trips
at 0.816 due to operation of overvoltage relay. The energy
absorptions of the surge arresters at the MV and the LV sides
of the DFIG-F104 transformer are given in Fig. 19 and Fig.
20, respectively. It should be noted that, resonance condition
occurs at all DFIG transformers on feeder F1. The voltage
waveforms of those DFIGs are similar to DFIG- F104. As the
ferroresonance condition will continue, the energy absorptions
of the surge arresters will continue increasing. The
transformers, surge arresters and line filters of the DFIGs on
feeder F1 are subjected to this overvoltage. Similar to the
previous simulation scenario, this ferroresonance condition
does not affect the operation of the DFIGs on feeders F2 and
F3 as it does not cause overvoltage at their terminals.
In Scenario S1, the OCR of feeder F1 and in Scenario S2,
the BUS2 input OCR of does not operate due to currents
resulting from ferroresonance. The overvoltage in Scenario S2
is much higher than the overvoltage in Scenario S1. It should
be noted that, the ferroresonance resulting from nuisance
tripping of BUS2 input OCR and a stuck pole in BUS2 CB is
much higher than the overvoltage in Scenario S2.
0.8 1 1.2 1.4 1.6 1.8 2
-80
-60
-40
-20
0
20
40
60
80
t (s)
Vabc
(kV)
Fig. 17. Voltages at MV side of the DFIG-F104 transformer.
0.8 1 1.2 1.4 1.6 1.8 2
-1.5
-1
-0.5
0
0.5
1
1.5
t (s)
Vabc(kV)
Fig. 18. Voltages at LV side of the DFIG-F104 transformer.
0.8 1 1.2 1.4 1.6 1.8 2
0
20
40
60
80
t (s)
ArresterEnergy(kJ)
arrester on phase-a
arrester on phase-c
arrester on phase-b
Fig. 19. DFIG- F104 transformer MV arrester energy absorption.
0.8 1 1.2 1.4 1.6 1.8 2
0
100
200
300
400
500
600
t (s)
ArresterEnergy(J)
arrester on phase-b
arrester on phase-c
arrester on phase-a
Fig. 20. DFIG- F104 transformer LV arrester energy absorption
3) Scenario S3:
In this scenario BUS2 is de-energized at 0.1 s by the
operation of BUS2 CB when 34.5 kV feeders are
disconnected via isolating switch. Due to unavailability of the
data for the circuit breaker grading capacitances, simulations
are performed for a wide range of capacitance values (50, 100,
200, 500, 1000 and 2000 pF). Ferroresonance is observed for
the 2000 pF circuit breaker grading capacitance as shown in
Fig. 21. It should be noted that, with 1000 pF circuit breaker
grading capacitance, ferroresonance is not observed for 1.1 pu
source voltage and different de-energization instants.
4) Scenario S4:
In this scenario BUS1 is de-energized at 0.1 s by the
operation of wind park transformer input circuit breaker (HV
CB in Fig. 8) when BUS2 is disconnected via isolating switch.
The simulations are repeated for 5000, 10000, 20000, 50000
and 75000 pF circuit breaker grading capacitances.
Ferroresonance is observed for the 75000 pF circuit breaker
grading capacitance as shown in Fig. 22. It should be noted
that, with 50000 pF circuit breaker grading capacitance,
ferroresonance is not observed for 1.1 pu source voltage and
different de-energization instants.
The simulations in Scenario S3 and Scenario S4 are
performed to identify the critical circuit breaker grading
capacitance values for the ferroresonance in the inductive
voltage transformers. Therefore, the grading capacitance of
HV CB is increased to very large (unrealistic) values in
Scenario S4 for the ferroresonance in IVT-1.
0 0.05 0.1 0.15 0.2 0.25 0.3
-40
-20
0
20
40
t (s)
Vabc(kV)
Va
Vb Vc
Fig. 21. Voltages at BUS2.
0 0.05 0.1 0.15 0.2 0.25 0.3
-40
-20
0
20
40
t (s)
Vabc(kV)
Va
Vb Vc
Fig. 22. Voltages at BUS1.
5) Scenario S5:
The secondary side voltages of the CVTs are shown in
Fig.23, for one of the high voltage ride-through (HVRT)
capability test simulations in [6]. In the presented simulation,
the 120 kV bus voltage increases up to 1.4 pu for roughly
100ms following a voltage sag, and then reduces to 1 pu. As
seen from Fig.23, the ferroresonant oscillations are well
damped. However, when the suppression circuit of CVT is
deactivated, the ferroresonant oscillations (on phase-b) remain
as illustrated in Fig. 24. It should be noted that, the sampled
voltage on CVT is used by the wind park controller and/or by
the reactive power compensation device (if it exists). The
positive sequence voltage extracted by the measuring units of
these devices is shown in Fig. 25. It is obvious that, the
ferroresonant oscillations without suppression circuit scenario
will cause improper function of the wind park controller
and/or the reactive power compensation device. However, the
wind park controller can be expected to be less vulnerable to
those oscillations due to its slow response.
0.9 1 1.1 1.2 1.3 1.4 1.5
-300
-200
-100
0
100
200
300
t (s)
Vabc
(V)
VbVc
Va
Fig. 23. Voltage at 115 kV side of the CVT (with ferroresonance suppression
circuit)
0.9 1 1.1 1.2 1.3 1.4 1.5
-500
0
500
t (s)
Vabc
(V)
Va
Vc
Vb
Fig. 24. Voltage at 115 kV side of the CVT (without ferroresonance
suppression circuit)
0.9 1 1.1 1.2 1.3 1.4 1.5
0.4
0.6
0.8
1
1.2
1.4
1.6
t (s)
Vpos
(pu)
without
suppression
circuit
with
suppression
circuit
Fig. 25. Positive sequence voltage measured by the wind park controller
V. CONCLUSIONS
This paper presented the scenarios that can lead to
ferroresonant circuits in an actual doubly fed induction
generator (DFIG) based wind park. Ferroresonance conditions
and their consequences were demonstrated by simulating the
detailed model of the wind park in EMTP-RV.
EMTP-RV simulations demonstrated that, the DFIG
transformers and the collector grid may form a ferroresonant
circuit when the collector grid feeder cable and large number
of DFIG transformers are energized together on one or two
phases (due to a stuck pole or poles in the feeder circuit
breaker). However, this can be avoided with energizing the
collector grid feeder cable and the DFIG transformers
sequentially, i.e. following feeder energization procedure.
DFIG transformers and collector grid may also form a
ferroresonant circuit with nuisance tripping of feeder
overcurrent relay and a stuck pole in the feeder circuit
breaker. Simulation results demonstrated that, this condition
produces higher overvoltage compared to the previous one.
Stuck pole in the feeder circuit breaker can be detected with
“breaker pole failure relay” usage. However, the energy
absorption capability of the surge arresters should be
sufficient to withstand the overvoltage until the associated
circuit breakers operate.
In this study the critical grading capacitance values were
also identified with simulations for the ferroresonance in the
inductive voltage transformers of the wind park. Depending
on the manufacturer data, a ferroresonance mitigation study
might be required for the inductive voltage transformers.
Simulations also demonstrated that the ferroresonance
suppression circuit of CVT provides sufficient damping to
ferroresonant oscillations and avoids possible improper
operation of wind park and/or reactive power compensation
device controller.
VI. REFERENCES
[1] P. Ferracci,"Ferroresonance", Groupe Schneider: Cahier technique no
190, March 1998.
[2] V. Valverde, G. Buigues, A. J. Mazón, I. Zamora, I. Albizu,
“Ferroresonant Configurations in Power Systems”, International
Conference on Renewable Energies and Power Quality (ICREPQ)
Santiago de Compostela (Spain), March 2012.
[3] M. Rioual, J. Mahseredjian, “Ferrorésonance dans les réseaux –
Définition, description et classification”, Les Techniques de l'Ingénieur,
May 10, 2009, Dossier D91. 9 pages.
[4] M. Rioual, C. Kiény, J. Mahseredjian, “Ferrorésonance dans les réseaux
– Modélisation et applications aux typologies de circuit”, Les
Techniques de l'Ingénieur, August 10, 2009, Dossier D92, 15 pages.
[5] E. D. Price, “Voltage Transformer Ferroresonance in Transmission
Substations” proc. on Texas A&M 30th Annual Conference for
Protective Relay Engineers, Texas A&M University, April 1997.
[6] U. Karaagac, J. Mahseredjian, L. Cai, “High Voltage Ride-Through
Capability of DFIG-based Wind Parks with FACTS” 13th
International
Workshop on Large-Scale Integration of Wind Power into Power
Systems, Berlin, Germany, Nov. 2014.
[7] D. A. N. Jacobson, "Examples of ferroresonance in a high voltage power
system", in Proc. of IEEE-PES General Meeting, 2003, pp. 1206-1212.
[8] Hopkinson, R.,"Ferroresonant overvoltage control based on TNA tests
on three-phase delta-wye transformer banks", IEEE Trans. on Power
App. & Systems, Vol. 86, No. 10, pp. 289-293, Oct. 1967.
[9] Young, F., Schmid, R., Fergestad, P.,"A laboratory investigation of
ferroresonance in cable-connected transformers", IEEE Trans. on Power
App. & Systems, Vol. 87, No. 5, pp. 1240-1249, May 1968.
[10] Walling, R., Barker, K., Compton, T., and Zimmerman, L.,
"Ferroresonant overvoltages in grounded wye-wye padmount
transformers with low-loss silicon steel cores", IEEE Trans. on Power
Delivery, Vol. 8, No. 3, pp. 1647-1660, July 1993.
[11] D. A. N. Jacobson, D. R. Swatek, and R. W. Mazur, "Mitigating
potential transformer ferroresonance in a 230 kV converter station", in
Proc. of IEEE Transmission and Distribution Conference, 1996, pp.
269-275..
[12] D.A.N. Jacobson, and , R.W. Menzies,"Investigation of Station Service
Transformer Ferroresonance in Manitoba Hydro’s 230-kV Dorsey
Converter Station", Proc. of 2001 Intl. Conf. on Power Systems
Transients, June 24-28, Rio de Janeiro.
[13] L. Bolduc, B. Bouchard., and G. Beaulieu, "Capacitor divider
substation", IEEE Trans. Power Delivery, Vol. 12, No. 3, pp. 1202-
1209, July 1997.
[14] Iravani, M.R., Wang, X., Polishscuk, I., Ribeiro, J., Sarshar, A.,"Digital
Time-Domain Investigation of Transient Behaviour of Coupling
Capacitor Voltage Transformer", IEEE Trans. on Power Delivery, Vol.
13, No. 2 pp. 622-629, April 1998.
[15] R. G. Andrei and B. R. Halley, "Voltage transformer ferroresonance
from an energy transfer standpoint", Power Delivery, IEEE Transactions
on, vol. 4, pp. 1773- 1778, 1989
[16] S. K. Chakravarthy and C. V. Nayar, "Ferroresonant oscillations in
capacitor voltage transformers", in Proc of IEE Circuits, Devices and
Systems, vol. 142, pp. 30- 36, 1995.
[17] M. R. Iravani, X. Wang, I. Polishchuk, J. Ribeiro, and A. Sarshar,
"Digital time-domain investigation of transient behaviour of coupling
capacitor voltage transformer", Power Delivery, IEEE Transactions on,
vol. 13, pp. 622- 629, 1998.
[18] M. Graovac, R. Iravani, W. Xiaolin, and R. D. McTaggart, "Fast
ferroresonance suppression of coupling capacitor voltage
transformers", Power Delivery, IEEE Transactions on, vol. 18, pp. 158-
163, 2003.
[19] M. Sanaye-Pasand, A. Rezaei-Zare, H. Mohseni, S. Farhangi, and R.
Iravani, "Comparison of performance of various ferroresonance
suppressing methods in inductive and capacitive voltage transformers",
in Proc. of IEEE Power India Conference, 2006.
[20] F. B. Ajaei, M. Sanaye-Pasand, A. Rezaei-Zare, and R. Iravani,
"Analysis and Suppression of the Coupling Capacitor Voltage
Transformer Ferroresonance Phenomenon", Power Delivery, IEEE
Transactions on, vol. 24, pp. 1968-1977, 2009.

More Related Content

What's hot

POWER QUALITY IMPROVEMENT BY SSSC AND STATCOM USING PI CONTROLLER
POWER QUALITY IMPROVEMENT BY SSSC AND STATCOM USING PI CONTROLLERPOWER QUALITY IMPROVEMENT BY SSSC AND STATCOM USING PI CONTROLLER
POWER QUALITY IMPROVEMENT BY SSSC AND STATCOM USING PI CONTROLLERJournal For Research
 
Active Reactive Power Flow Control Using Static Synchronous Series Compensato...
Active Reactive Power Flow Control Using Static Synchronous Series Compensato...Active Reactive Power Flow Control Using Static Synchronous Series Compensato...
Active Reactive Power Flow Control Using Static Synchronous Series Compensato...IOSR Journals
 
Control of Active And reactive power flow in transmission line and power Osci...
Control of Active And reactive power flow in transmission line and power Osci...Control of Active And reactive power flow in transmission line and power Osci...
Control of Active And reactive power flow in transmission line and power Osci...AM Publications
 
Control of HVDC Transmission System Based on MMC with Three-Level Flying Capa...
Control of HVDC Transmission System Based on MMC with Three-Level Flying Capa...Control of HVDC Transmission System Based on MMC with Three-Level Flying Capa...
Control of HVDC Transmission System Based on MMC with Three-Level Flying Capa...Anand Parakkat Parambil
 
static series synchronus compensator
static series synchronus compensatorstatic series synchronus compensator
static series synchronus compensatorbhupendra kumar
 
Power upgrading of transmission line by combining ac dc transmission
Power upgrading of transmission line by combining ac dc transmissionPower upgrading of transmission line by combining ac dc transmission
Power upgrading of transmission line by combining ac dc transmissionShailesh Senta
 
Power transmission(ppt)
Power transmission(ppt)Power transmission(ppt)
Power transmission(ppt)zeeshan715
 
FAULT DETECTION AND CLASSIFICATION ON TRANSMISSION OVERHEAD LINE USING BPP...
FAULT DETECTION AND CLASSIFICATION ON TRANSMISSION OVERHEAD LINE  USING BPP...FAULT DETECTION AND CLASSIFICATION ON TRANSMISSION OVERHEAD LINE  USING BPP...
FAULT DETECTION AND CLASSIFICATION ON TRANSMISSION OVERHEAD LINE USING BPP...Politeknik Negeri Ujung Pandang
 
Tranformerless H6 Grid Tied Inverter For Photovoltaic Generation
Tranformerless H6 Grid Tied Inverter For Photovoltaic GenerationTranformerless H6 Grid Tied Inverter For Photovoltaic Generation
Tranformerless H6 Grid Tied Inverter For Photovoltaic GenerationIJMER
 
Space Vector of Three Phase Three level Neutral Point Clamped Quasi Z Source ...
Space Vector of Three Phase Three level Neutral Point Clamped Quasi Z Source ...Space Vector of Three Phase Three level Neutral Point Clamped Quasi Z Source ...
Space Vector of Three Phase Three level Neutral Point Clamped Quasi Z Source ...IJTET Journal
 

What's hot (19)

POWER QUALITY IMPROVEMENT BY SSSC AND STATCOM USING PI CONTROLLER
POWER QUALITY IMPROVEMENT BY SSSC AND STATCOM USING PI CONTROLLERPOWER QUALITY IMPROVEMENT BY SSSC AND STATCOM USING PI CONTROLLER
POWER QUALITY IMPROVEMENT BY SSSC AND STATCOM USING PI CONTROLLER
 
Active Reactive Power Flow Control Using Static Synchronous Series Compensato...
Active Reactive Power Flow Control Using Static Synchronous Series Compensato...Active Reactive Power Flow Control Using Static Synchronous Series Compensato...
Active Reactive Power Flow Control Using Static Synchronous Series Compensato...
 
Control of Active And reactive power flow in transmission line and power Osci...
Control of Active And reactive power flow in transmission line and power Osci...Control of Active And reactive power flow in transmission line and power Osci...
Control of Active And reactive power flow in transmission line and power Osci...
 
6 PHASE TRANSMISSION SYSTEM
6 PHASE TRANSMISSION SYSTEM6 PHASE TRANSMISSION SYSTEM
6 PHASE TRANSMISSION SYSTEM
 
Electrical power system
Electrical power system Electrical power system
Electrical power system
 
EHV AC
EHV ACEHV AC
EHV AC
 
RGPV EX7102 unit I
RGPV EX7102 unit IRGPV EX7102 unit I
RGPV EX7102 unit I
 
Ehv ac transmission line
Ehv ac transmission lineEhv ac transmission line
Ehv ac transmission line
 
Control of HVDC Transmission System Based on MMC with Three-Level Flying Capa...
Control of HVDC Transmission System Based on MMC with Three-Level Flying Capa...Control of HVDC Transmission System Based on MMC with Three-Level Flying Capa...
Control of HVDC Transmission System Based on MMC with Three-Level Flying Capa...
 
K.Sravanthi.
K.Sravanthi.K.Sravanthi.
K.Sravanthi.
 
static series synchronus compensator
static series synchronus compensatorstatic series synchronus compensator
static series synchronus compensator
 
Power upgrading of transmission line by combining ac dc transmission
Power upgrading of transmission line by combining ac dc transmissionPower upgrading of transmission line by combining ac dc transmission
Power upgrading of transmission line by combining ac dc transmission
 
Power transmission(ppt)
Power transmission(ppt)Power transmission(ppt)
Power transmission(ppt)
 
FAULT DETECTION AND CLASSIFICATION ON TRANSMISSION OVERHEAD LINE USING BPP...
FAULT DETECTION AND CLASSIFICATION ON TRANSMISSION OVERHEAD LINE  USING BPP...FAULT DETECTION AND CLASSIFICATION ON TRANSMISSION OVERHEAD LINE  USING BPP...
FAULT DETECTION AND CLASSIFICATION ON TRANSMISSION OVERHEAD LINE USING BPP...
 
Performance Investigation of a Monopolar HVDC Transmission System Feeding a ...
Performance Investigation of a Monopolar HVDC Transmission  System Feeding a ...Performance Investigation of a Monopolar HVDC Transmission  System Feeding a ...
Performance Investigation of a Monopolar HVDC Transmission System Feeding a ...
 
Tranformerless H6 Grid Tied Inverter For Photovoltaic Generation
Tranformerless H6 Grid Tied Inverter For Photovoltaic GenerationTranformerless H6 Grid Tied Inverter For Photovoltaic Generation
Tranformerless H6 Grid Tied Inverter For Photovoltaic Generation
 
Space Vector of Three Phase Three level Neutral Point Clamped Quasi Z Source ...
Space Vector of Three Phase Three level Neutral Point Clamped Quasi Z Source ...Space Vector of Three Phase Three level Neutral Point Clamped Quasi Z Source ...
Space Vector of Three Phase Three level Neutral Point Clamped Quasi Z Source ...
 
Power systems İntroduction
Power systems İntroductionPower systems İntroduction
Power systems İntroduction
 
HVDC System
HVDC SystemHVDC System
HVDC System
 

Similar to Ferroresonance Conditions in Wind Parks Simulated

IRJET- Design and Implementation of Isolated Multi-Output Flyback Converter
IRJET- Design and Implementation of Isolated Multi-Output Flyback ConverterIRJET- Design and Implementation of Isolated Multi-Output Flyback Converter
IRJET- Design and Implementation of Isolated Multi-Output Flyback ConverterIRJET Journal
 
Towards An Accurate Modeling of Frequency-dependent Wind Farm Components Unde...
Towards An Accurate Modeling of Frequency-dependent Wind Farm Components Unde...Towards An Accurate Modeling of Frequency-dependent Wind Farm Components Unde...
Towards An Accurate Modeling of Frequency-dependent Wind Farm Components Unde...IJAPEJOURNAL
 
Analysis and Modeling of Transformerless Photovoltaic Inverter Systems
Analysis and Modeling of Transformerless Photovoltaic Inverter SystemsAnalysis and Modeling of Transformerless Photovoltaic Inverter Systems
Analysis and Modeling of Transformerless Photovoltaic Inverter SystemsIJMER
 
1 mrg000577 en_application_of_unit_protection_schemes_for_auto-transformers1
1 mrg000577 en_application_of_unit_protection_schemes_for_auto-transformers11 mrg000577 en_application_of_unit_protection_schemes_for_auto-transformers1
1 mrg000577 en_application_of_unit_protection_schemes_for_auto-transformers1NASSAR KALLIKETTIYAPURAKAL
 
IRJET- FPGA Controlled Three Level Diode Clamped Multilevel Inverter for Sola...
IRJET- FPGA Controlled Three Level Diode Clamped Multilevel Inverter for Sola...IRJET- FPGA Controlled Three Level Diode Clamped Multilevel Inverter for Sola...
IRJET- FPGA Controlled Three Level Diode Clamped Multilevel Inverter for Sola...IRJET Journal
 
Calculation of EAF
Calculation of EAFCalculation of EAF
Calculation of EAFtekhakko
 
DC GENERATOR EE8301 Electrical Machines 1
DC GENERATOR EE8301 Electrical Machines 1DC GENERATOR EE8301 Electrical Machines 1
DC GENERATOR EE8301 Electrical Machines 1SURESHKUMARG17
 
Soft Switched Multi-Output Flyback Converter with Voltage Doubler
Soft Switched Multi-Output Flyback Converter with Voltage DoublerSoft Switched Multi-Output Flyback Converter with Voltage Doubler
Soft Switched Multi-Output Flyback Converter with Voltage DoublerIJPEDS-IAES
 
IRJET- Simulation of Energization and De-Energization of Capacitor Banks and ...
IRJET- Simulation of Energization and De-Energization of Capacitor Banks and ...IRJET- Simulation of Energization and De-Energization of Capacitor Banks and ...
IRJET- Simulation of Energization and De-Energization of Capacitor Banks and ...IRJET Journal
 
International Journal of Engineering Research and Development
International Journal of Engineering Research and DevelopmentInternational Journal of Engineering Research and Development
International Journal of Engineering Research and DevelopmentIJERD Editor
 
overvoltage in distribution network
overvoltage in distribution networkovervoltage in distribution network
overvoltage in distribution networkmegala venkatesan
 
project report on plc based load sharing
project report on plc based load sharingproject report on plc based load sharing
project report on plc based load sharingVivek Arun
 
Modeling and Analysis of a 3-Phase 132kv GasInsulated Substation
Modeling and Analysis of a 3-Phase 132kv GasInsulated SubstationModeling and Analysis of a 3-Phase 132kv GasInsulated Substation
Modeling and Analysis of a 3-Phase 132kv GasInsulated SubstationIRJET Journal
 
Unit-III Waveform Generator
Unit-III Waveform GeneratorUnit-III Waveform Generator
Unit-III Waveform GeneratorDr.Raja R
 
final year project report
final year project reportfinal year project report
final year project reportAnuj Kumar
 
grid sub-station training Report
grid sub-station training Report grid sub-station training Report
grid sub-station training Report ravi kant
 
A High Step Up Hybrid Switch Converter Connected With PV Array For High Volta...
A High Step Up Hybrid Switch Converter Connected With PV Array For High Volta...A High Step Up Hybrid Switch Converter Connected With PV Array For High Volta...
A High Step Up Hybrid Switch Converter Connected With PV Array For High Volta...IJNLC Int.Jour on Natural Lang computing
 
Electric arc furnec
Electric arc furnecElectric arc furnec
Electric arc furnechoucin gue
 

Similar to Ferroresonance Conditions in Wind Parks Simulated (20)

IRJET- Design and Implementation of Isolated Multi-Output Flyback Converter
IRJET- Design and Implementation of Isolated Multi-Output Flyback ConverterIRJET- Design and Implementation of Isolated Multi-Output Flyback Converter
IRJET- Design and Implementation of Isolated Multi-Output Flyback Converter
 
Towards An Accurate Modeling of Frequency-dependent Wind Farm Components Unde...
Towards An Accurate Modeling of Frequency-dependent Wind Farm Components Unde...Towards An Accurate Modeling of Frequency-dependent Wind Farm Components Unde...
Towards An Accurate Modeling of Frequency-dependent Wind Farm Components Unde...
 
Analysis and Modeling of Transformerless Photovoltaic Inverter Systems
Analysis and Modeling of Transformerless Photovoltaic Inverter SystemsAnalysis and Modeling of Transformerless Photovoltaic Inverter Systems
Analysis and Modeling of Transformerless Photovoltaic Inverter Systems
 
1 mrg000577 en_application_of_unit_protection_schemes_for_auto-transformers1
1 mrg000577 en_application_of_unit_protection_schemes_for_auto-transformers11 mrg000577 en_application_of_unit_protection_schemes_for_auto-transformers1
1 mrg000577 en_application_of_unit_protection_schemes_for_auto-transformers1
 
IRJET- FPGA Controlled Three Level Diode Clamped Multilevel Inverter for Sola...
IRJET- FPGA Controlled Three Level Diode Clamped Multilevel Inverter for Sola...IRJET- FPGA Controlled Three Level Diode Clamped Multilevel Inverter for Sola...
IRJET- FPGA Controlled Three Level Diode Clamped Multilevel Inverter for Sola...
 
Calculation of EAF
Calculation of EAFCalculation of EAF
Calculation of EAF
 
DC GENERATOR EE8301 Electrical Machines 1
DC GENERATOR EE8301 Electrical Machines 1DC GENERATOR EE8301 Electrical Machines 1
DC GENERATOR EE8301 Electrical Machines 1
 
Soft Switched Multi-Output Flyback Converter with Voltage Doubler
Soft Switched Multi-Output Flyback Converter with Voltage DoublerSoft Switched Multi-Output Flyback Converter with Voltage Doubler
Soft Switched Multi-Output Flyback Converter with Voltage Doubler
 
Du36723729
Du36723729Du36723729
Du36723729
 
IRJET- Simulation of Energization and De-Energization of Capacitor Banks and ...
IRJET- Simulation of Energization and De-Energization of Capacitor Banks and ...IRJET- Simulation of Energization and De-Energization of Capacitor Banks and ...
IRJET- Simulation of Energization and De-Energization of Capacitor Banks and ...
 
International Journal of Engineering Research and Development
International Journal of Engineering Research and DevelopmentInternational Journal of Engineering Research and Development
International Journal of Engineering Research and Development
 
overvoltage in distribution network
overvoltage in distribution networkovervoltage in distribution network
overvoltage in distribution network
 
project report on plc based load sharing
project report on plc based load sharingproject report on plc based load sharing
project report on plc based load sharing
 
Modeling and Analysis of a 3-Phase 132kv GasInsulated Substation
Modeling and Analysis of a 3-Phase 132kv GasInsulated SubstationModeling and Analysis of a 3-Phase 132kv GasInsulated Substation
Modeling and Analysis of a 3-Phase 132kv GasInsulated Substation
 
Unit-III Waveform Generator
Unit-III Waveform GeneratorUnit-III Waveform Generator
Unit-III Waveform Generator
 
final year project report
final year project reportfinal year project report
final year project report
 
I010246467
I010246467I010246467
I010246467
 
grid sub-station training Report
grid sub-station training Report grid sub-station training Report
grid sub-station training Report
 
A High Step Up Hybrid Switch Converter Connected With PV Array For High Volta...
A High Step Up Hybrid Switch Converter Connected With PV Array For High Volta...A High Step Up Hybrid Switch Converter Connected With PV Array For High Volta...
A High Step Up Hybrid Switch Converter Connected With PV Array For High Volta...
 
Electric arc furnec
Electric arc furnecElectric arc furnec
Electric arc furnec
 

Recently uploaded

ZXCTN 5804 / ZTE PTN / ZTE POTN / ZTE 5804 PTN / ZTE POTN 5804 ( 100/200 GE Z...
ZXCTN 5804 / ZTE PTN / ZTE POTN / ZTE 5804 PTN / ZTE POTN 5804 ( 100/200 GE Z...ZXCTN 5804 / ZTE PTN / ZTE POTN / ZTE 5804 PTN / ZTE POTN 5804 ( 100/200 GE Z...
ZXCTN 5804 / ZTE PTN / ZTE POTN / ZTE 5804 PTN / ZTE POTN 5804 ( 100/200 GE Z...ZTE
 
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICSAPPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICSKurinjimalarL3
 
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝soniya singh
 
Call Girls Delhi {Jodhpur} 9711199012 high profile service
Call Girls Delhi {Jodhpur} 9711199012 high profile serviceCall Girls Delhi {Jodhpur} 9711199012 high profile service
Call Girls Delhi {Jodhpur} 9711199012 high profile servicerehmti665
 
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130Suhani Kapoor
 
Software Development Life Cycle By Team Orange (Dept. of Pharmacy)
Software Development Life Cycle By  Team Orange (Dept. of Pharmacy)Software Development Life Cycle By  Team Orange (Dept. of Pharmacy)
Software Development Life Cycle By Team Orange (Dept. of Pharmacy)Suman Mia
 
Study on Air-Water & Water-Water Heat Exchange in a Finned Tube Exchanger
Study on Air-Water & Water-Water Heat Exchange in a Finned Tube ExchangerStudy on Air-Water & Water-Water Heat Exchange in a Finned Tube Exchanger
Study on Air-Water & Water-Water Heat Exchange in a Finned Tube ExchangerAnamika Sarkar
 
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...ranjana rawat
 
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINE
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINEMANUFACTURING PROCESS-II UNIT-2 LATHE MACHINE
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINESIVASHANKAR N
 
GDSC ASEB Gen AI study jams presentation
GDSC ASEB Gen AI study jams presentationGDSC ASEB Gen AI study jams presentation
GDSC ASEB Gen AI study jams presentationGDSCAESB
 
Processing & Properties of Floor and Wall Tiles.pptx
Processing & Properties of Floor and Wall Tiles.pptxProcessing & Properties of Floor and Wall Tiles.pptx
Processing & Properties of Floor and Wall Tiles.pptxpranjaldaimarysona
 
College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service NashikCollege Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service NashikCall Girls in Nagpur High Profile
 
Coefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptxCoefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptxAsutosh Ranjan
 
Current Transformer Drawing and GTP for MSETCL
Current Transformer Drawing and GTP for MSETCLCurrent Transformer Drawing and GTP for MSETCL
Current Transformer Drawing and GTP for MSETCLDeelipZope
 
(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service
(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service
(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Serviceranjana rawat
 
Porous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writingPorous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writingrakeshbaidya232001
 
Introduction to Multiple Access Protocol.pptx
Introduction to Multiple Access Protocol.pptxIntroduction to Multiple Access Protocol.pptx
Introduction to Multiple Access Protocol.pptxupamatechverse
 
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130Suhani Kapoor
 
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur High Profile
 

Recently uploaded (20)

ZXCTN 5804 / ZTE PTN / ZTE POTN / ZTE 5804 PTN / ZTE POTN 5804 ( 100/200 GE Z...
ZXCTN 5804 / ZTE PTN / ZTE POTN / ZTE 5804 PTN / ZTE POTN 5804 ( 100/200 GE Z...ZXCTN 5804 / ZTE PTN / ZTE POTN / ZTE 5804 PTN / ZTE POTN 5804 ( 100/200 GE Z...
ZXCTN 5804 / ZTE PTN / ZTE POTN / ZTE 5804 PTN / ZTE POTN 5804 ( 100/200 GE Z...
 
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICSAPPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
 
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝
 
Call Girls Delhi {Jodhpur} 9711199012 high profile service
Call Girls Delhi {Jodhpur} 9711199012 high profile serviceCall Girls Delhi {Jodhpur} 9711199012 high profile service
Call Girls Delhi {Jodhpur} 9711199012 high profile service
 
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
 
Software Development Life Cycle By Team Orange (Dept. of Pharmacy)
Software Development Life Cycle By  Team Orange (Dept. of Pharmacy)Software Development Life Cycle By  Team Orange (Dept. of Pharmacy)
Software Development Life Cycle By Team Orange (Dept. of Pharmacy)
 
Study on Air-Water & Water-Water Heat Exchange in a Finned Tube Exchanger
Study on Air-Water & Water-Water Heat Exchange in a Finned Tube ExchangerStudy on Air-Water & Water-Water Heat Exchange in a Finned Tube Exchanger
Study on Air-Water & Water-Water Heat Exchange in a Finned Tube Exchanger
 
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
 
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINE
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINEMANUFACTURING PROCESS-II UNIT-2 LATHE MACHINE
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINE
 
GDSC ASEB Gen AI study jams presentation
GDSC ASEB Gen AI study jams presentationGDSC ASEB Gen AI study jams presentation
GDSC ASEB Gen AI study jams presentation
 
Processing & Properties of Floor and Wall Tiles.pptx
Processing & Properties of Floor and Wall Tiles.pptxProcessing & Properties of Floor and Wall Tiles.pptx
Processing & Properties of Floor and Wall Tiles.pptx
 
Call Us -/9953056974- Call Girls In Vikaspuri-/- Delhi NCR
Call Us -/9953056974- Call Girls In Vikaspuri-/- Delhi NCRCall Us -/9953056974- Call Girls In Vikaspuri-/- Delhi NCR
Call Us -/9953056974- Call Girls In Vikaspuri-/- Delhi NCR
 
College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service NashikCollege Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
 
Coefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptxCoefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptx
 
Current Transformer Drawing and GTP for MSETCL
Current Transformer Drawing and GTP for MSETCLCurrent Transformer Drawing and GTP for MSETCL
Current Transformer Drawing and GTP for MSETCL
 
(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service
(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service
(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service
 
Porous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writingPorous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writing
 
Introduction to Multiple Access Protocol.pptx
Introduction to Multiple Access Protocol.pptxIntroduction to Multiple Access Protocol.pptx
Introduction to Multiple Access Protocol.pptx
 
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130
 
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
 

Ferroresonance Conditions in Wind Parks Simulated

  • 1. Ferroresonance Conditions in Wind Parks U. Karaagac, J. Mahseredjian, L. Cai Abstract--Wind parks are made up of a large number of saturable inductances (power transformers, inductive voltage transformers (IVTs)), as well as capacitors (cables, wind turbine harmonic filters, capacitor voltage transformers (CVTs), voltage grading capacitors in circuit-breakers). Therefore, they may present scenarios in which ferroresonance occurs. This paper presents the scenarios that can lead to ferroresonant circuits in doubly fed induction generator (DFIG) based wind parks. Ferroresonance conditions and their consequences are demonstrated by simulating the detailed model of the wind park in EMTP-RV. The wind park simulation model includes detailed models of wind turbines, medium voltage (MV) collector grid, high voltage / medium voltage (HV/MV) wind park substation, overvoltage, overcurrent and differential current protections, current transformers (CTs), IVTs and CVTs. Keywords: Ferroresonance, wind parks, power transformers, inductive voltage transformers (IVTs), capacitor voltage transformers (CVTs), overvoltage, overcurrent. I. INTRODUCTION ERRORESONANCE is an oscillatory phenomena caused by the interaction of energy exchanged between the nonlinear magnetizing inductances of the ferromagnetic cores and the system capacitances. The main feature of this phenomenon is the presence of at least two stable steady-state operating points for a particular range of circuit parameters: a ferroresonant operating point and a normal (non- ferroresonant) operating point. Transient disturbances or switching operations may initiate ferroresonance. The response can suddenly jump from one normal operating point (sinusoidal at the same frequency as the source) to another ferroresonant operating point characterized by high overvoltages and harmonic levels which may lead to excessive heating and insulation failure in transformers as well as significant disruptions in power system operation [1], [2]. This paper presents the scenarios that can lead to ferroresonant circuits in an actual doubly fed induction generator (DFIG) based wind park. Ferroresonance conditions and their consequences are demonstrated by simulating the detailed model of the wind park in EMTP-RV. This work was supported by the German Federal Ministry for the Environment, Nature Conservation, Building and Nuclear Safety, grant code: 032529. U. Karaagac and J. Mahseredjian are with École Polytechnique de Montréal, Campus Université de Montréal, 2900, Édouard-Montpetit, Montréal (Québec), Canada, H3T 1J4. L. Cai is with Senvion SE, Überseering 10, D-22297, Hamburg, Germany. Paper submitted to the International Conference on Power Systems Transients (IPST2015) in Cavtat, Croatia June 15-18, 2015 The first part of this paper presents the theoretical principles of ferroresonance. The second part presents the considered wind park and the electric configurations that can lead to ferroresonant circuits. The simulation results are presented in the last part. II. FERRORESONANCE In simple terms, ferroresonance can be described as a nonlinear oscillation resulting from the interaction between a nonlinear inductance and a capacitor. Like linear resonance, depending on the connection between the capacitance and the nonlinear inductance, ferroresonance may be series or parallel. This paper analyzes only the series ferroresonance shown in Fig. 1. Fig. 1. Series ferroresonant circuit. The graphical solution of the series resonant circuit is shown in Fig. 2 for the lossless case (i.e. R = 0). The intersection of “US + UC” line with the nonlinear US (I) curve gives three possible operating points: - Operating point (1): Non-ferroresonant stable operating point in which the circuit is working in an inductive mode, with lagging current and low voltages. - Operating point (2): Ferroresonant stable operating point in which the circuit is working in a capacitive mode, with leading current and high voltages. - Operating point (3): Unstable operating point. 3 2 5 2 1 5 1 0 5 0 0 5 1 1 5 2 1 5 0 5 1 I 1 3 2 U Fig. 2. Graphical solution of a series ferroresonant circuit (R = 0). F S U C U L U C U L U S U S C U U ( )L U I S U   R U  C U  L U   R C L
  • 2. It should be noted that, the deep analysis of the circuit shown in Fig. 1 requires the solution of nonlinear differential equations. The presence of nonlinearity introduces harmonics in the voltage and current waveforms. However, in Fig.2, the analysis of the circuit is simplified by limiting the calculations to the power frequency and steady state in order to provide a conceptual description of ferroresonance [3]-[5]. A. Effect of Source Voltage The effect of the source voltage is illustrated in Fig. 3. As the source voltage is increased, the “US +UC” line moves upwards. When the source voltage is higher than US-critical (“US + UC” line tangent to the nonlinear US (I) curve), there is no intersection in the first quadrant. In other words, the system solution is always a ferroresonant situation. As seen from Fig. 3, the ferroresonant oscillations can be self-sustained when the circuit has no losses. In other words, removing voltage source may not result in the elimination of ferroresonance. The operating point simply slides to the right, but remains in the saturated region. In reality, ferroresonant oscillations cannot be self-sustained due to circuit losses. 3 2 5 2 1 5 1 0 5 0 0 5 1 1 5 2 1 5 0 5 1 I U Fig. 3. Graphical solution illustrating the effect of source voltage. B. Effect of Circuit Capacitance The effect of the circuit capacitance is illustrated in Fig. 4. As the circuit capacitance is increased, the “US +UC” line rotates clock-wise, i.e. its slope decreases. As seen from Fig. 4, ferroresonant situation can appear for a wide range of capacitance values at a given frequency. Fig. 5 illustrates the theoretical conditions to avoid periodic ferroresonance. It can be observed when [1] 1 sat linearL L C      (1) C. Effect of Circuit Losses When the losses are considered, the equation describing the steady-state behaviour of the circuit shown in Fig. 1 can be written as  22 ( )L C SU I U U R I   (2) The graphical solution is shown in Fig.6. For the low circuit resistance (R1), there are three possible solutions. Solutions (1) and (2) in Fig.6 correspond to the non- ferroresonant and the ferroresonant situations, respectively. As seen from Fig.6, the multiplicity of solutions can disappear when the circuit losses increases. 3 2 5 2 1 5 1 0 5 0 0 5 1 1 5 2 1 5 0 5 1 I U Fig. 4. Graphical solution illustrating the effect of circuit capacitance. 0 0.2 0.4 0.6 0.8 1 1.2 1.4 1.6 1.8 2 0 0.2 0.4 0.6 0.8 1 1.2 Fig. 5. Periodic ferroresonance conditions. 0 0.5 1 1.5 2 2.5 3 0 0.05 0.1 0.15 0.2 0.25 0.3 0.35 0.4 0.45 1" 3' 2' 1' 1 I U 23 Fig. 6. Graphical solution illustrating the effect of circuit losses (R1 > R2). III. WIND PARK UNDER STUDY The simplified single-line diagram of the wind park studied in this paper is given in Fig. 7. The wind park collector grid is composed of three radial 34.5 kV feeders and connected to 120 kV grid through a 120 MVA step-up transformer. The collector grid feeders F1, F2 and F3 contain 15, 7 and 18 DFIG-type wind turbines (WTs), respectively. Each WT has 2 MW rating and connected to 34.5 kV collector grid through a 2.5 MVA ΔYg transformer. The EMTP-RV diagram of the wind park substation is given in Fig. 8. The isolating switches are not shown in in Fig. 8. The reader should refer to [6] for detailed information regarding DFIG WTs and wind park control. L C U U 2 2 ( 1 )S U R I 2 2 ( 2 )S U R I S U 1 linear L C    linear L sat L 1 sat L C    C U 1 2S S S critical U U U   U S critical C U   2S C U U ( )L U I 1S C U U 1 2 3 C C C 3 U S C U  2S C U U ( )L U I 1S C U U
  • 3. 70 kV / 115 V 600A / 5A CT To WPC 35 m cable To WPC trip signal from protective relays 600A / 5A CT To TR-1 input OCR HV CB To HV/MV transformer differential protection 600A / 5A CT ZnO arrester 50 m cable ZnO arrester 120 kV / 34.5 kV 120 MVA Transformer To BUS-1 input OCR 2000A / 5A CT 2000A / 5A CT To HV/MV transformer differential protection 600A / 5A CT 10 ohm / phase zig-zag transformer secondary short circuited auxiliary service transformer 60 m cable 2000A / 5A CT 2000A / 5A CTTo BUS-2 input OCR To BUS-2 differential protection To Feeder-1 OCR 1200A / 5A CT 135.5 ohm / phase zig-zag transformer 200A / 5A CT 1200A / 5A CT 135.5 ohm / phase zig-zag transformer 200A / 5A CT FOR FUTURE EXPANSION ZnO arrester 1200A / 5A CT 2000A / 5A CT To Feeder-1 OCR To BUS-2 differential protection fuse fuse 135.5 ohm / phase zig-zag transformer 15 m cable ZnO arrester Feeder F1 trip signal from protective relays fuse To Feeder-2 OCR 1200A / 5A CT 2000A / 5A CT To Feeder-2 OCR To BUS-2 differential protection 135.5 ohm / phase zig-zag transformer 15 m cable ZnO arrester Feeder F2 trip signal from protective relays fuse To Feeder-3 OCR 1200A / 5A CT 2000A / 5A CT To Feeder-3 OCR To BUS-2 differential protection 135.5 ohm / phase zig-zag transformer 15 m cable ZnO arrester Feeder F3 trip signal from protective relays fuse trip signal from protective relays F1 CB F2 CB F3 CB secondary short circuited secondary short circuited secondary short circuited BUS-2 BUS-1 BUS2 CB 20125V / 115V / 67.08V fuse To BUS-2 input OCR fuse To measuring devices 20125V / 115V / 67.08V20125V / 115V / 67.08V20125V / 115V / 67.08V 20125V / 115V / 67.08V IVT-1 IVT-2 IVT-F1 IVT-F2 IVT-F3 CVT RL + Page Page Page RL + Page 1 +30 X Page ZnO+ ZnO+ Page Page ZnO+ >e P S1 S2 12 -30 RL + Page Page Page X Page Page X X XRL + ZnO+ >e Page P S1 S2 Page Page Page XRL + ZnO+ >e Page P S1 S2 Page Page Page XRL + ZnO+ >e Page Page P S1 S2 Page P S1 S2 Page Fig. 8. EMTP-RV diagram of the wind park substation 120 kV Grid Feeder F1 (15 WTs)34.5 kV Collector Bus Feeder F2 (7 WTs) Feeder F3 (18 WTs) 120 kV /34.5 kV Wind Park Transformer Wind Park Substation RL + RL + RL + RL + RL + +30 X X X X Fig. 7. Simplified single-line diagram of the wind park. There are several electric configurations that can lead to ferroresonant circuits in power systems. In [7] seven different classes or categories of electrical systems prone to ferroresonance appearance are identified. The following three electric configurations exist in the considered wind park. 1. Transformer supplied accidently on one or two phases [8]-[10]; 2. Inductive voltage transformer (IVT) energized through the grading capacitance of one or more open circuit breakers [11], [12]; 3. Capacitor voltage transformer (CVT) [13], [14]. A. Transformer Supplied Accidently on One or Two Phases The DFIG transformers have delta primary connection and ferroresonance may occur when they are supplied on one or two phases. The ferroresonant circuit is created through the phase-to ground capacitance(s) of the open phase(s) as shown in Fig. 9. The following scenarios can be expected to cause ferroresonance: 1. Energizing a DFIG transformer (via closing associated MV load break switch) when one or two phases of the feeder cable are live due to a stuck pole or poles in the feeder circuit breaker, 2. Energizing collector grid feeder on one or two phases due to a stuck pole or poles in the feeder circuit breaker when the DFIG transformers (one or more) are connected to the feeder to be energized, 3. A stuck pole (or poles) in the circuit breaker during opening following nuisance operation of the overcurrent relay (OCR).
  • 4. It should be noted that, the feeder cables and DFIG transformers are energized sequentially during startup. Therefore, the second scenario cannot happen when the startup procedure is followed. Fig. 9. Ferroresonant circuit in a transformer with delta primary connection [1]. B. Transformer Energized Through the Grading Capacitance of One or More Open Circuit Breakers This electrical configuration is shown in Fig. 10. Opening of circuit-breaker initiates the phenomenon by causing capacitance C to discharge through the IVT which is then driven into saturation. The source delivers enough energy through the circuit-breaker grading capacitance Cd to maintain the oscillation [11], [15]. Fig. 10. IVT in series with an open circuit breaker [1]. In the considered wind park, the IVTs may form a ferroresonant circuit with the grading capacitance of circuit- breakers for the following scenarios: 1. BUS2 IVT and BUS2 input circuit breaker grading capacitance (IVT-2 and BUS2 CB in Fig. 8) when 34.5 kV feeders are disconnected; 2. BUS1 IVT and 120 kV wind park transformer input circuit breaker grading capacitance (IVT-1 and HV CB in Fig. 8) when BUS-2 is disconnected. C. Capacitive Voltage Transformer (CVT) The structure of CVTs makes them particularly prone to ferroresonance. Manufacturers are aware of this problem and install various types of suppression circuits. These suppression circuits should not affect either the transient response or the accuracy of the transformer, but limiting the duration of the ferroresonant oscillations [16]-[20]. As seen in Fig. 8, the considered wind park has a CVT at 120 kV. Fig. 11. Capacitive voltage transformer (CVT) [2]. IV. EMTP-RV SIMULATIONS A. Simulation Model The simulation model in [6] is used in this study. The model includes detailed models of DFIG WTs, wind park controller, MV collector grid, HV/MV wind park substation, overvoltage protection, overcurrent and differential current protections, current transformers, IVTs and CVTs. It should be noted that, all simulation data is provided by the manufacturer except the circuit breaker grading capacitances. B. Simulation Results 1) Scenario S1 This scenario is energizing the feeder F1 (at t = 0.75 s) on two phases due to a stuck pole (the pole on phase-c) in the feeder F1 circuit breaker (F1 CB in Fig. 8) when all DFIG transformers are connected to the feeder. This scenario is not expected to happen as the feeder cables and DFIG transformers are energized sequentially during startup and presented only to demonstrate the ferroresonance phenomenon. It should be noted that energizing one of the DFIG transformers with closing the associated MV load break switch does not cause ferroresonance (when one or two phases of the feeder F1 cable is live) even for 1.5 pu voltage at collector grid. In the simulations, such large voltage profile in collector grid is achieved by increasing DFIG output and transmission system equivalent source voltages after deactivating DFIG overvoltage protection and certain controller limits. The voltages at MV and LV sides of the DFIG-F104 (one of the DFIGs on feeder F1) transformer are shown in Fig. 12 and in Fig. 13, respectively. The high overvoltage at transformer terminals is due to ferroresonance. The voltage waveforms at the other DFIG transformer terminals on feeder F1 are similar to DFIG-F104 transformer terminals. The energy absorptions of the surge arresters at the MV and the LV sides of the DFIG-F104 transformer are given in Fig. 14 and Fig. 15, respectively. As the ferroresonance condition will continue due to low damping (see Fig. 12 and Fig. 13), the energy absorptions of the surge arresters will continue increasing. The DFIG transformers and surge arresters are subjected to this overvoltage.
  • 5. This ferroresonance condition does not affect the operation of the DFIGs on feeders F2 and F3 as it does not cause overvoltage at their terminals as illustrated in Fig. 16. The possibility of ferroresonance can be expected to decrease with the decrease in the number of DFIG transformers connected to the feeder to be energized. 0.8 1 1.2 1.4 1.6 1.8 2 -60 -40 -20 0 20 40 60 t (s) Vabc(kV) Fig. 12. Voltages at MV side of the DFIG-F104 transformer. 0.8 1 1.2 1.4 1.6 1.8 2 -1 -0.8 -0.6 -0.4 -0.2 0 0.2 0.4 0.6 t (s) Vabc(kV) Fig. 13. Voltages at LV side of the DFIG-F104 transformer. 0.8 1 1.2 1.4 1.6 1.8 2 0 2 4 6 8 10 t (s) ArresterEnergy(kJ) arrester on phase-b arrester on phase-a arrester on phase-c Fig. 14. DFIG- F104 transformer MV arrester energy absorption. 0.8 1 1.2 1.4 1.6 1.8 2 0 5 10 15 20 25 30 35 40 t (s) ArresterEnergy(J) arrester on phase-c arrester on phase-b arrester on phase-a Fig. 15. DFIG- F104 transformer LV arrester energy absorption. 0.7 0.75 0.8 0.85 0.9 0.95 1 -0.4 -0.2 0 0.2 0.4 0.6 t (s) Vabc (kV) Fig. 16. Voltages at one of the DFIG terminals on feeder F2 (DFIG-F204). 2) Scenario S2: This scenario is nuisance tripping of feeder F1 OCR and a stuck pole (the pole on phase-c) in F1 CB. F1 CB operates at t = 0.75 s in the simulation. The voltages at MV and LV sides of the DFIG-F104 transformer are shown in Fig. 17 and in Fig. 18, respectively. The high overvoltage at transformer terminals is due to ferroresonance condition. DFIG-F104 trips at 0.816 due to operation of overvoltage relay. The energy absorptions of the surge arresters at the MV and the LV sides of the DFIG-F104 transformer are given in Fig. 19 and Fig. 20, respectively. It should be noted that, resonance condition occurs at all DFIG transformers on feeder F1. The voltage waveforms of those DFIGs are similar to DFIG- F104. As the ferroresonance condition will continue, the energy absorptions of the surge arresters will continue increasing. The transformers, surge arresters and line filters of the DFIGs on feeder F1 are subjected to this overvoltage. Similar to the previous simulation scenario, this ferroresonance condition does not affect the operation of the DFIGs on feeders F2 and F3 as it does not cause overvoltage at their terminals. In Scenario S1, the OCR of feeder F1 and in Scenario S2, the BUS2 input OCR of does not operate due to currents resulting from ferroresonance. The overvoltage in Scenario S2 is much higher than the overvoltage in Scenario S1. It should be noted that, the ferroresonance resulting from nuisance tripping of BUS2 input OCR and a stuck pole in BUS2 CB is much higher than the overvoltage in Scenario S2.
  • 6. 0.8 1 1.2 1.4 1.6 1.8 2 -80 -60 -40 -20 0 20 40 60 80 t (s) Vabc (kV) Fig. 17. Voltages at MV side of the DFIG-F104 transformer. 0.8 1 1.2 1.4 1.6 1.8 2 -1.5 -1 -0.5 0 0.5 1 1.5 t (s) Vabc(kV) Fig. 18. Voltages at LV side of the DFIG-F104 transformer. 0.8 1 1.2 1.4 1.6 1.8 2 0 20 40 60 80 t (s) ArresterEnergy(kJ) arrester on phase-a arrester on phase-c arrester on phase-b Fig. 19. DFIG- F104 transformer MV arrester energy absorption. 0.8 1 1.2 1.4 1.6 1.8 2 0 100 200 300 400 500 600 t (s) ArresterEnergy(J) arrester on phase-b arrester on phase-c arrester on phase-a Fig. 20. DFIG- F104 transformer LV arrester energy absorption 3) Scenario S3: In this scenario BUS2 is de-energized at 0.1 s by the operation of BUS2 CB when 34.5 kV feeders are disconnected via isolating switch. Due to unavailability of the data for the circuit breaker grading capacitances, simulations are performed for a wide range of capacitance values (50, 100, 200, 500, 1000 and 2000 pF). Ferroresonance is observed for the 2000 pF circuit breaker grading capacitance as shown in Fig. 21. It should be noted that, with 1000 pF circuit breaker grading capacitance, ferroresonance is not observed for 1.1 pu source voltage and different de-energization instants. 4) Scenario S4: In this scenario BUS1 is de-energized at 0.1 s by the operation of wind park transformer input circuit breaker (HV CB in Fig. 8) when BUS2 is disconnected via isolating switch. The simulations are repeated for 5000, 10000, 20000, 50000 and 75000 pF circuit breaker grading capacitances. Ferroresonance is observed for the 75000 pF circuit breaker grading capacitance as shown in Fig. 22. It should be noted that, with 50000 pF circuit breaker grading capacitance, ferroresonance is not observed for 1.1 pu source voltage and different de-energization instants. The simulations in Scenario S3 and Scenario S4 are performed to identify the critical circuit breaker grading capacitance values for the ferroresonance in the inductive voltage transformers. Therefore, the grading capacitance of HV CB is increased to very large (unrealistic) values in Scenario S4 for the ferroresonance in IVT-1. 0 0.05 0.1 0.15 0.2 0.25 0.3 -40 -20 0 20 40 t (s) Vabc(kV) Va Vb Vc Fig. 21. Voltages at BUS2. 0 0.05 0.1 0.15 0.2 0.25 0.3 -40 -20 0 20 40 t (s) Vabc(kV) Va Vb Vc Fig. 22. Voltages at BUS1.
  • 7. 5) Scenario S5: The secondary side voltages of the CVTs are shown in Fig.23, for one of the high voltage ride-through (HVRT) capability test simulations in [6]. In the presented simulation, the 120 kV bus voltage increases up to 1.4 pu for roughly 100ms following a voltage sag, and then reduces to 1 pu. As seen from Fig.23, the ferroresonant oscillations are well damped. However, when the suppression circuit of CVT is deactivated, the ferroresonant oscillations (on phase-b) remain as illustrated in Fig. 24. It should be noted that, the sampled voltage on CVT is used by the wind park controller and/or by the reactive power compensation device (if it exists). The positive sequence voltage extracted by the measuring units of these devices is shown in Fig. 25. It is obvious that, the ferroresonant oscillations without suppression circuit scenario will cause improper function of the wind park controller and/or the reactive power compensation device. However, the wind park controller can be expected to be less vulnerable to those oscillations due to its slow response. 0.9 1 1.1 1.2 1.3 1.4 1.5 -300 -200 -100 0 100 200 300 t (s) Vabc (V) VbVc Va Fig. 23. Voltage at 115 kV side of the CVT (with ferroresonance suppression circuit) 0.9 1 1.1 1.2 1.3 1.4 1.5 -500 0 500 t (s) Vabc (V) Va Vc Vb Fig. 24. Voltage at 115 kV side of the CVT (without ferroresonance suppression circuit) 0.9 1 1.1 1.2 1.3 1.4 1.5 0.4 0.6 0.8 1 1.2 1.4 1.6 t (s) Vpos (pu) without suppression circuit with suppression circuit Fig. 25. Positive sequence voltage measured by the wind park controller V. CONCLUSIONS This paper presented the scenarios that can lead to ferroresonant circuits in an actual doubly fed induction generator (DFIG) based wind park. Ferroresonance conditions and their consequences were demonstrated by simulating the detailed model of the wind park in EMTP-RV. EMTP-RV simulations demonstrated that, the DFIG transformers and the collector grid may form a ferroresonant circuit when the collector grid feeder cable and large number of DFIG transformers are energized together on one or two phases (due to a stuck pole or poles in the feeder circuit breaker). However, this can be avoided with energizing the collector grid feeder cable and the DFIG transformers sequentially, i.e. following feeder energization procedure. DFIG transformers and collector grid may also form a ferroresonant circuit with nuisance tripping of feeder overcurrent relay and a stuck pole in the feeder circuit breaker. Simulation results demonstrated that, this condition produces higher overvoltage compared to the previous one. Stuck pole in the feeder circuit breaker can be detected with “breaker pole failure relay” usage. However, the energy absorption capability of the surge arresters should be sufficient to withstand the overvoltage until the associated circuit breakers operate. In this study the critical grading capacitance values were also identified with simulations for the ferroresonance in the inductive voltage transformers of the wind park. Depending on the manufacturer data, a ferroresonance mitigation study might be required for the inductive voltage transformers. Simulations also demonstrated that the ferroresonance suppression circuit of CVT provides sufficient damping to ferroresonant oscillations and avoids possible improper operation of wind park and/or reactive power compensation device controller. VI. REFERENCES [1] P. Ferracci,"Ferroresonance", Groupe Schneider: Cahier technique no 190, March 1998. [2] V. Valverde, G. Buigues, A. J. Mazón, I. Zamora, I. Albizu, “Ferroresonant Configurations in Power Systems”, International
  • 8. Conference on Renewable Energies and Power Quality (ICREPQ) Santiago de Compostela (Spain), March 2012. [3] M. Rioual, J. Mahseredjian, “Ferrorésonance dans les réseaux – Définition, description et classification”, Les Techniques de l'Ingénieur, May 10, 2009, Dossier D91. 9 pages. [4] M. Rioual, C. Kiény, J. Mahseredjian, “Ferrorésonance dans les réseaux – Modélisation et applications aux typologies de circuit”, Les Techniques de l'Ingénieur, August 10, 2009, Dossier D92, 15 pages. [5] E. D. Price, “Voltage Transformer Ferroresonance in Transmission Substations” proc. on Texas A&M 30th Annual Conference for Protective Relay Engineers, Texas A&M University, April 1997. [6] U. Karaagac, J. Mahseredjian, L. Cai, “High Voltage Ride-Through Capability of DFIG-based Wind Parks with FACTS” 13th International Workshop on Large-Scale Integration of Wind Power into Power Systems, Berlin, Germany, Nov. 2014. [7] D. A. N. Jacobson, "Examples of ferroresonance in a high voltage power system", in Proc. of IEEE-PES General Meeting, 2003, pp. 1206-1212. [8] Hopkinson, R.,"Ferroresonant overvoltage control based on TNA tests on three-phase delta-wye transformer banks", IEEE Trans. on Power App. & Systems, Vol. 86, No. 10, pp. 289-293, Oct. 1967. [9] Young, F., Schmid, R., Fergestad, P.,"A laboratory investigation of ferroresonance in cable-connected transformers", IEEE Trans. on Power App. & Systems, Vol. 87, No. 5, pp. 1240-1249, May 1968. [10] Walling, R., Barker, K., Compton, T., and Zimmerman, L., "Ferroresonant overvoltages in grounded wye-wye padmount transformers with low-loss silicon steel cores", IEEE Trans. on Power Delivery, Vol. 8, No. 3, pp. 1647-1660, July 1993. [11] D. A. N. Jacobson, D. R. Swatek, and R. W. Mazur, "Mitigating potential transformer ferroresonance in a 230 kV converter station", in Proc. of IEEE Transmission and Distribution Conference, 1996, pp. 269-275.. [12] D.A.N. Jacobson, and , R.W. Menzies,"Investigation of Station Service Transformer Ferroresonance in Manitoba Hydro’s 230-kV Dorsey Converter Station", Proc. of 2001 Intl. Conf. on Power Systems Transients, June 24-28, Rio de Janeiro. [13] L. Bolduc, B. Bouchard., and G. Beaulieu, "Capacitor divider substation", IEEE Trans. Power Delivery, Vol. 12, No. 3, pp. 1202- 1209, July 1997. [14] Iravani, M.R., Wang, X., Polishscuk, I., Ribeiro, J., Sarshar, A.,"Digital Time-Domain Investigation of Transient Behaviour of Coupling Capacitor Voltage Transformer", IEEE Trans. on Power Delivery, Vol. 13, No. 2 pp. 622-629, April 1998. [15] R. G. Andrei and B. R. Halley, "Voltage transformer ferroresonance from an energy transfer standpoint", Power Delivery, IEEE Transactions on, vol. 4, pp. 1773- 1778, 1989 [16] S. K. Chakravarthy and C. V. Nayar, "Ferroresonant oscillations in capacitor voltage transformers", in Proc of IEE Circuits, Devices and Systems, vol. 142, pp. 30- 36, 1995. [17] M. R. Iravani, X. Wang, I. Polishchuk, J. Ribeiro, and A. Sarshar, "Digital time-domain investigation of transient behaviour of coupling capacitor voltage transformer", Power Delivery, IEEE Transactions on, vol. 13, pp. 622- 629, 1998. [18] M. Graovac, R. Iravani, W. Xiaolin, and R. D. McTaggart, "Fast ferroresonance suppression of coupling capacitor voltage transformers", Power Delivery, IEEE Transactions on, vol. 18, pp. 158- 163, 2003. [19] M. Sanaye-Pasand, A. Rezaei-Zare, H. Mohseni, S. Farhangi, and R. Iravani, "Comparison of performance of various ferroresonance suppressing methods in inductive and capacitive voltage transformers", in Proc. of IEEE Power India Conference, 2006. [20] F. B. Ajaei, M. Sanaye-Pasand, A. Rezaei-Zare, and R. Iravani, "Analysis and Suppression of the Coupling Capacitor Voltage Transformer Ferroresonance Phenomenon", Power Delivery, IEEE Transactions on, vol. 24, pp. 1968-1977, 2009.