International Journal of Applied Power Engineering (IJAPE)
Vol. 1, No. 3, December 2012, pp. 115~122
ISSN: 2252-8792 115
Journal homepage: http://iaesjournal.com/online/index.php/IJAPE
Voltage Stability Based Formation of Voltage Control Areas
Considering Impact of Contingencies
Tarun Martolia1
and M. K. Verma2
Department of Electrical Engineering, Indian Institute of Technology (Banaras Hindu University), Varanasi, India
Article Info ABSTRACT
Article history:
Received Jul 16, 2012
Revised Oct 11, 2012
Accepted Oct 20, 2012
Voltage instability has been considered as a major threat to power system
networks since last three decades. Frequent incidences of grid failures caused
by voltage instability have been observed in different parts of the world. Fast
voltage stability assessment of power system may be done by formation of
voltage control areas, clubbing group of buses in geographically compact
region having similar voltage instability problem. This paper presents a new
approach for formation of voltage control areas (VCAs) based on sensitivity
of reactive power generations with respect to reactive power demands,
together with bus voltage variations under voltage stability based critical
contingencies. The load buses in geographically compact region showing
similar sensitivity of reactive power demand to reactive generations have
been clubbed together to form voltage control areas. Since, voltage control
areas formed should remain valid under change in operating conditions and
network topology, the areas formed based on reactive power sensitivities
have been modified considering voltage variations at different loadings
points under voltage stability based critical contingencies. Voltage stability
based Critical contingencies have been selected based on maximum
loadability criterion. Case studies have been performed on IEEE 14-bus
system. Simulation results performed on IEEE 14-bus system validate VCAs
formed even under change in network topology caused by line outages and
change in operating conditions caused by variations in real and reactive
power demands. The VCAs formed by proposed method have been
compared with VCAs formed by few existing approaches. The superiority of
proposed approach of voltage control areas formation over few existing
approaches has been established on the test system considered.
Keyword:
Voltage control area
reactive power sensitivity
contingencies
maximum loadability
voltage stability
Copyright © 2012 Institute of Advanced Engineering and Science.
All rights reserved.
Corresponding Author:
Tarun Martolia
Department of Electrical Engineering, Indian Institute of Technology (Banaras Hindu University)
Varanasi-221005 (India)
e-mail: tarun.martolia.eee10@itbhu.ac.in,
1. INTRODUCTION
Power system stability has been recognized as an important problem for its secure operation since
1920s [1],[2]. Traditionally, the problem of stability has been one of maintaining the synchronous operation
of generators operating in parallel, known as rotor angle stability. The problem of rotor angle stability is well
understood and documented. With continuous increase in power demand, and due to limited expansion of
transmission systems, modern power system networks are being operated under highly stressed conditions.
This has imposed the threat of maintaining the required bus voltages, and thus the systems have been facing
voltage instability problem [3].
Voltage stability is the ability of a power system to maintain voltage magnitudes at all the buses in
the system within acceptable range after being subjected to a disturbance from a given initial operating
condition [3]. It depends on the ability to maintain/restore equilibrium between load demand and load supply
from the power system. Due to increase in power demand, modern power system networks are being
ISSN: 2252-8792
IJAPE Vol. 1, No. 3, December 2012 : 115 – 122
116
operated under highly stressed conditions. This has resulted into the difficulty in meeting reactive power
requirement, specially under contingencies, and hence maintaining the bus voltages within acceptable limits.
Voltage instability in the system, generally, occurs in the form of a progressive decay in voltage magnitude at
some of the buses. A possible outcome of voltage instability is loss of load in an area, or tripping of
transmission lines and other elements by their protective systems leading to cascaded outages and voltage
collapse in the system [3],[4]. Voltage collapse is the process by which the sequence of events,
accompanying voltage instability, leads to a blackout or abnormally low voltages in a significant part of a
power system [4]-[6]. Several incidences of voltage collapse have been observed, in past few decades, in
different parts of the world. Some of the incidences of voltage collapse are [6],[7]:
• New York Pool disturbance of September 22, 1970.
• Florida system disturbance of December 28, 1982.
• French system disturbances of December 19, 1978 and January 12, 1987.
• Northern Belgium system disturbance of August 4, 1982.
• Swedish system disturbance of December 27, 1983.
• Japanese system disturbance of July 23, 1983.
• Western Systems Co-ordination Council (WSCC) interconnected system (North America) disturbance of
July 2, 1996.
• Sri Lankan Power System disturbance of May 2, 1995.
• Northern grid disturbance in Indian Power System of December 1996.
• Punjab voltage collapse in Indian Power System on June 10, 2007.
The structural weakness of the power system, due to weak transmission boundaries between
different groups of buses, has also been considered a reason of voltage instability [8]. These groups of buses,
located in geographically compact region, have similar voltage changes for any outside disturbance. The bus
clusters so formed are called voltage control areas (VCAs) [8]. Due to weak transmission boundaries, loss of
voltage controls within a voltage control area may result in voltage collapse in that area since the voltage
controls in other voltage control areas may have relatively less impact in controlling voltages in that area. For
any external disturbance, each of the voltage control areas may be reduced to equivalent nodes by some
network reduction technique. Localization of voltage controls in critical areas together with reduction of
areas to equivalent nodes for external disturbances may be quite helpful in fast voltage stability assessment
and control of power system networks.
A number of methods have been suggested in literature for formation of voltage control areas.
Voltage control areas have been determined by eliminating smaller off-diagonal elements of normalized Q-V
Jacobian in [8].In order to consider the effect of Q-δ and P-V coupling, which are very much valid under
highly stressed conditions, this algorithm has been applied to full load flow Jacobian instead of decoupled Q-
V Jacobian in [9]. The methods suggested in [8], [9] requires proper selection of threshold (α) for elimination
of smaller off-diagonal elements, which is a difficult task since smaller values of α puts almost all the buses
in one cluster, whereas a larger value may make each bus a separate voltage control area. V-Q curve minima
based α-selection algorithm has been proposed in [10]. Formation of voltage control areas under
contingencies using an electrical distance concept and V-Q sensitivities of power flow Jacobian has been
suggested in [11]. Group of coherent buses have been formed in [12] using generator branch reactive power
flow sensitivities to reactive power injection at load buses. The buses having similar generator branch
sensitivity values within a reasonable limit of 5% have been clubbed to form voltage control areas.
Computations of generator branch sensitivities have been done at the base case operating point. However,
generator branch sensitivities are not expected to remain same for change in operating condition or network
topology. Voltage control areas have been formed based on Jacobian sensitivities together with voltage
variations under contingencies [13]. However, formation of voltage control areas has been done at the base
case operating point and V-Q curve minima have been used for selection of threshold only, for elimination of
weaker off-diagonal elements of Jacobian. In [13], contingencies have been selected randomly and no
specific criterion has been proposed for selection of critical contingencies to study voltage variations from
the base case value. Voltage control areas have been formed using bus participation factors corresponding to
zero eigen value at the nose point of P-V curve [14]. However, eigen analysis is a linear analysis and may not
always be suitable at the nose point of P-V curve. Formation of VCAs has been done based on individual
critical loading factor (maximum loadability) of various buses in the geographically compact region [15]. In
[15], the VCA with lowest range of maximum loading factor of buses has been considered as the most
critical area requiring attention, to reduce chances of voltage failures. However, occurrence of contingencies
may change individual critical loading factor (maximum loadability) of buses.
Difficulty in supply of reactive power to consumers has been considered as a major cause of voltage
instability in power systems. It is extremely vital to determine major reactive power sources supplying
IJAPE ISSN: 2252-8792
Voltage Stability Based Formation of Voltage Control Areas Considering Impact … (Tarun Martolia)
117
reactive power to a group of buses. The exhaustion of reactive reserves of these sources may cause voltage
instability in the group of load buses getting mainly reactive power supply from such sources [10]. This paper
presents a method that allows easier determination of a group of load buses being dependent on same set of
reactive power sources. Such groups of load buses have been clubbed together to form voltage control areas.
Sensitivities of reactive power generations to reactive power demands have been computed to determine
dependency of group of loads to group of reactive power sources.
Most of the work has concentrated formation of voltage control areas at the base case operating
point. Voltage control areas formed at the base case operating point are not expected to remain valid under
change in network topology and operating conditions. Very limited effort seems to be made in formation of
voltage control areas considering impact of change in network topology and operating conditions. In the
present work, the voltage control areas formed based on reactive power sensitivities have been modified by
considering bus voltage variations from the case value at different loadings under voltage stability based
critical contingencies to consider impact of change in operating conditions and network topology. Voltage
stability based critical contingencies have been selected based on maximum loadability criterion. Proposed
approach of voltage control areas formation has been tested on IEEE 14-bus system. Voltage control areas
formed by proposed method have been compared by areas formed by few existing approaches. It has been
observed on the test system that areas formed by proposed approach are more effective compared to
considered existing approaches, under change in network topology and operating conditions.
2. RESEARCH METHOD
In this work, voltage control areas have been formed based on sensitivity of reactive power
generations to reactive power demands. The sensitivity factor has been derived as per following.
The reactive power balance equation at all the buses ignoring Q-δ coupling can be given by;
൤
∆ܳீ
∆ܳ௅
൨ = ቎
డொಸ
డ௏ಽ
డொಽ
డ௏ಽ
቏ ሾ∆ܸ௅ሿ (1)
where,
ሾ∇ܳீሿ = Change in reactive power generations
ሾ∇ܳ௅ሿ = Change in reactive power demands
ሾ∇ܸ௅ሿ = Change in voltage magnitudes at load buses
Equation (1) may be rewritten as;
ሾ∆Qୋሿ=ሾSୋሿሾ∆V୐ሿ (2)
and,
ሾ∆Q୐ሿ=ሾS୐ሿሾ∆V୐ሿ (3)
where,
ሾܵீሿ = ቂ
డொಸ
డ௏ಽ
ቃ = Sensitivity of reactive power generations to voltage magnitudes at load buses
ሾܵ௅ሿ = ቂ
డொಽ
డ௏ಽ
ቃ = Sensitivity of reactive power demands to voltage magnitudes at load buses
From (2) and (3),
ሾ∆Qୋሿ = ሾSሿሾ∆Q୐ሿ (4)
where,
ሾܵሿ = ሾSୋሿሾS୐ሿିଵ
(5)
Elements of matrix [S] represent sensitivity of reactive power generations to reactive power
demands, and can be calculated using full Q-V Jacobian sub-matrix of Newton Raphson Load Flow. Load
buses having closer sensitivities to a group of generators are expected to have similar voltage instability
problem since hitting of reactive power limit of such generators will result in difficulty in meeting reactive
power demands of these load buses. Therefore, load buses having closer reactive power sensitivity values
have been clubbed together to form voltage control areas. However, voltage control areas so formed are not
expected to remain same with change in network topology and operating conditions. Therefore, voltage
control areas formed based on sensitivity of reactive power generations to reactive power demands have been
modified considering voltage variations from the base case value under critical contingencies at different
loading conditions. Critical contingencies have been obtained based on post-contingency saddle-node-
bifurcation points (maximum loadability points). For obtaining post-contingency saddle-node-bifurcation
points, real power output of generators (PG), real power demand (PD) and reactive power demand (QD) have
been varied using:
ISSN: 2252-8792
IJAPE Vol. 1, No. 3, December 2012 : 115 – 122
118
( )0
j j
PG =PG 1+λ (6)
( )0
j j
PD =PD 1+λ (7)
( )0
j j
QD =QD 1+λ (8)
where,λ represents system loading factor common to all the buses and, 0
j
PG , 0
j
PD , 0
j
QD are real power output
of generator and real and reactive power loads at bus-j at a base operating point (λ=0.0).
3. RESULTS AND ANALYSIS
The proposed method of formation of voltage control areas has been applied to IEEE 14-bus system
(shown in Figure-1) [16]. IEEE 14-bus system has 5 generators with 20 transmission lines (including 2
transformers and one phase shifting transformer). Loads have been connected at 11 buses including two
generator buses.
The sensitivity of reactive power generations to reactive power demands were calculated using (5) at
the base case operating point with the help of elements of Newton Raphson Load Flow Jacobian matrix. The
sensitivity values between different generator buses and load buses have been shown in Table-1. The
senstivity values shown in Table-1 represent dependency of load buses to reactive power sorces. If a group of
load buses (say Group-A) has high and similar dependency on a group of reactive power sources (say Group-
B), hitting of reactive power generation limit of generators in Group-B is expected to result in voltage
instability at all the load buses in Group-A. Therefore, all the load buses in Group-A are expected to face
similar voltage instability problem. Voltage control areas were formed clubbing load buses having closer
reactive power sensitivities to generators. The voltage control areas so formed have been shown in Table-2
and Figure-1.
Figure-1. VCAs for IEEE 14-bus system based on reactive power sensitivities
Table 1. Sensitivity of Reactive Power Generations to Reactive Power Demands (Sij) - 14-Bus System
Load bus no. Generator bus no.
1 2 3 6 8
4 -0.12038 -0.38004 -0.21604 -0.17201 -0.12044
5 -0.19713 -0.37703 -0.12872 -0.22221 -0.07176
7 -0.05366 -0.16941 -0.09630 -0.22054 -0.49275
9 -0.05211 -0.16451 -0.09352 -0.38568 -0.34688
10 -0.04380 -0.13829 -0.07861 -0.49828 -0.29159
11 -0.02265 -0.07152 -0.04066 -0.74709 -0.15080
12 -0.00335 -0.01057 -0.00601 -0.98826 -0.02228
13 -0.00809 -0.02555 -0.01452 -0.94007 -0.05386
14 -0.03442 -0.10868 -0.06178 -0.64634 -0.22916
Table 2. VCAs Formed Using Sij Values (IEEE 14-Bus System)
VCA no. Buses present
IJAPE ISSN: 2252-8792
Voltage Stability Based Formation of Voltage Control Areas Considering Impact … (Tarun Martolia)
119
1 12, 13
2 11, 14
3 9, 10
4 4, 5
5 7
Voltage control areas shown in Figure-1 and Table-2 represent areas for the intact system. The load
buses within the areas so formed are expected to have similar voltage instability problem. However, voltage
control areas so formed are expected to change under change in network topology and operating conditions,
since the sensitivity values are expected to change under change in network topology and operating
conditions. In order to consider impact of change in network topology and operating conditions, the voltage
control areas formed based on reactive power sensitivities were modified based on bus voltage variations
under voltage stability based critical contingencies at large number of new real and reactive power demands.
Voltage stability based most severe contingencies were selected based on post-contingency saddle-node-
bifurcation points (maximum loadability points) using continuation power flow based software package
UWPFLOW [17]. Voltage stability based contingency ranking has been shown in Table-3. Voltage
magnitude at all the load buses were calculated at the base case operating point, nose point (maximum
loadability point) and some of the intermediate loading points, under critical contingencies. The change in
voltage magnitude from the base case operating point value, of all the load buses, at some of the post-
contingency loadings have been shown in Table-4. The voltage control areas formed using reactive power
sensitivities (shown inTable-2 and Figure-1) were modified based on post-contingency voltage variations
from the case operating value, under different loadings. Modified voltage control areas have been shown in
Table-5 and Figure-2.
Table 3. Voltage Stability Based Contingency Ranking (IEEE 14-bus System)
Line outage Maximum loading factor (λmax) Contingency ranking
2-3 1.2747 1
5-6 1.3059 2
2-4 2.1463 3
6-13 2.2427 4
2-5 2.2465 5
12-13 2.2775 6
13-14 2.2799 7
1-5 2.4536 8
4-7 2.4978 9
7-9 2.7485 10
Table 4. Voltage Variations of Load Buses under Few Critical Contingencies with Increased Demands
(IEEE 14-bus System)
Line
outage
Loading
factor
Change in voltage magnitude (p.u.) from the base case operating point value of load buses
Bus-4 Bus-5 Bus-7 Bus-9 Bus-10 Bus-11 Bus-12 Bus-13 Bus-14
2-3 1.2747*
-0.193 -0.179 -0.107 -0.127 -0.111 -0.025 -0.002 -0.011 -0.109
5-6 1.3059*
-0.136 -0.109 -0.143 -0.170 -0.168 -0.096 -0.016 -0.037 -0.179
2-4 2.1463*
-0.284 -0.312 -0.180 -0.222 -0.200 -0.096 -0.022 -0.052 -0.205
6-13 2.2427*
-0.175 -0.177 -0.186 -0.280 -0.250 -0.123 -0.233 -0.491 -0.481
2-5 1.4750 -0.084 -0.093 -0.061 -0.082 -0.075 -0.028 +0.001 -0.014 -0.085
12-13 2.2775*
-0.056 -0.054 -0.183 -0.072 -0.066 -0.024 +0.017 -0.020 -0.082
13-14 2.2799*
-0.161 -0.156 -0.183 -0.284 -0.256 -0.127 +0.001 -0.001 -0.500
1-5 1.4144 -0.076 -0.079 -0.056 -0.075 -0.068 -0.025 +0.002 -0.011 -0.078
4-7 1.5335 -0.074 -0.075 -0.050 -0.098 -0.091 -0.040 -0.002 -0.020 -0.100
7-9 2.7485*
-0.289 -0.341 -0.119 -0.620 -0.543 -0.282 -0.067 -0.138 -0.504
*
Nose point
+
Voltage rise
-
Voltage drop
Table 5. VCAs Formed Based on Sij Values Together with Bus Voltages Variations under Critical
Contingencies (IEEE 14-Bus System)
ISSN: 2252-8792
IJAPE Vol. 1, No. 3, December 2012 : 115 – 122
120
VCA no. Buses present
1 12, 13
2 11
3 9, 10
4 4, 5
5 7
6 14
Figure-2. VCAs formed by proposed method (IEEE 14-bus System)
The maximum change in voltage from the base case operating point (considered as A in present
work) with bus number having maximum change in voltage, the minimum change in voltage from the base
case operating point (considered as B in present work) with bus number having minimum change in voltage,
and absolute value of difference between A and B (considered as C in present work), have been shown in
Table-6 for different voltage control areas under few critical contingencies at some of the loadings. It is
observed from Table-6 that voltage control areas formed by proposed approach consist of buses having very
small range of voltage variations with change in network topology caused by line outages and change in
operating conditions caused by change in demands.
The voltage control areas formed by proposed approach were compared with the methods of voltage
control areas formation suggested in Ref. [10], Ref. [13] and Ref. [15], respectively, based on lowest
maximum C value between all the voltage control areas formed. Table-7 shows maximum C for different
approaches under voltage stability based critical contingencies at some of the loading values. It is observed
from Table-7 that voltage control areas formed by proposed approach have lowest maximum C values
compared to voltage control areas formed using methods suggested in Ref. [10], Ref. [13] and Ref. [15],
under critical contingencies at different loadings, for most of the cases. Therefore, VCAs formed by proposed
approach remains valid under critical contingencies at different loadings. Due to lowest voltage variations
compared to three existing approaches, under voltage stability based critical contingencies at a set of real and
reactive power demands, the areas formed by proposed approach may be more efficient in voltage stability
assessment under change in operating conditions and network topology.
IJAPE ISSN: 2252-8792
Voltage Stability Based Formation of Voltage Control Areas Considering Impact … (Tarun Martolia)
121
4. CONCLUSION
A modified method for formation of voltage control areas has been presented in this paper. Proposed
method of VCAs formation first clubs load buses based on closer sensitivity of reactive power generations to
reactive power demands. The VCAs so formed have been modified based on voltage variations of load buses
under voltage stability based critical contingencies at a set of new loadings. Voltage stability based critical
contingencies have been obtained based on maximum loadability criterion. Proposed method of VCAs
formation has been tested on IEEE 14-bus system. Results obtained on the test system considered establish
better suitability of VCAs formation over some of the existing approaches under change in operating
conditions and network topology. Voltage control areas formed by proposed approach may be quite effective
in fast voltage stability assessment and control of power system networks. Since VCAs have been formed to
study voltage stability phenomenon, generator buses have not been considered for clustering in the present
work.
Table 6. Voltage Variations at Buses within VCAs Formed by the Proposed Approach (IEEE 14-bus System)
Line outage Loading factor VCA no. Maximum and minimum change in voltage magnitude (p.u.) from
the base case operating point at buses within VCAs, and absolute
value of difference (p.u.) between maximum voltage change and
minimum voltage change at buses within VCAs
A B C
1-5 1.4144 1 +0.002 (bus-12) -0.011 (bus-13) 0.013**
2 Contain only one load bus
3 -0.075 (bus-9) -0.068 (bus-10) 0.007
4 -0.079 (bus-5) -0.076 0.003
5 Contain only one load bus
6 Contain only one load bus
2-3 1.2747*
1 -0.011 (bus-13) --0.002 (bus-12) 0.009
2 Contain only one load bus
3 -0.127 (bus-9) -0.111 (bus-10) 0.006
4 -0.192 (bus-4) -0.179 (bus-5) 0.013**
5 Contain only one load bus
6 Contain only one load bus
6-13 2.2427*
1 -0.491 (bus-13) -0.233 (bus-12) 0.258**
2 Contain only one load bus
3 -0.280 (bus-9) -0.250 (bus-10) 0.030
4 -0.177 (bus-5) -0.175 (bus-4) 0.002
5 Contain only one load bus
6 Contain only one load bus
12-13 2.2775*
1 -0.020 (bus-13) +0.017 (bus-12) 0.037**
2 Contain only one load bus
3 -0.072 (bus-9) -0.066 (bus-10) 0.006
4 -0.056 (bus-4) -0.054 (bus-5) 0.002
5 Contain only one load bus
6 Contain only one load bus
*
Nose point
**
Maximum value of C between all the VCAs formed by the proposed method
+
Voltage rise
-
Voltage drop
A = Maximum change in voltage (in p.u.) from the base case operating point value occurring at one of the bus within VCA
B = Minimum change in voltage (in p.u.) from the base case operating point value occurring at one of the bus within VCA
C = Absolute value of difference between A and B
Table 7. Comparison of VCAs formed by different approaches
Line outage Loading Factor Maximum value of C between different VCAs fomed
ISSN: 2252-8792
IJAPE Vol. 1, No. 3, December 2012 : 115 – 122
122
VCAs formed by
method suggested in
Ref. [10]
VCAs formed by
method suggested in
Ref. [13]
VCAs formed by
method suggested in
Ref. [15]
VCAs formed by
proposed method
2-3 1.2747*
0.091 0.109 0.175 0.013**
5-6 1.3059*
0.191 0.143 0.143 0.021**
2-4 2.1463*
0.153 0.183 0.231 0.030**
6-13 2.2427*
0.110**
0.257 0.313 0.257
2-5 1.4750 0.071 0.085 0.008**
0.014
12-13 1.4862 0.062 0.062 0.062 0.037**
13-14 2.2799*
0.499 0.499 0.340 0.028**
1-5 1.4144 0.068 0.078 0.067 0.013**
4-7 1.5335 0.079 0.099 0.077 0.020**
7-9 2.7485*
0.365 0.501 0.501 0.077**
REFERENCE
[1] C. P. Steinmetz, “Power control and stability of electric generating stations”, AIEE Trans., Vol. XXXIX, Part II,
pp. 1215-1287, July 1920.
[2] AIEE Subcommittee on Interconnections and Stability Factors, “First report of power system stability”, AIEE
Trans., pp. 51-80, 1926.
[3] IEEE / CIGRE Joint Task Force on Stability Terms and Definitions, “Definition and classification of power system
stability”, IEEE Trans. on Power Systems, Vol. 19, No. 3, pp. 1387-1401, August 2004.
[4] IEEE System Dynamic Perfomance Subcommittee, “Voltage stability of power systems: Concepts, analytical tools
and industrial experience”, IEEE document 90TH0358-2-PWR-1990.
[5] C. W. Taylor, “Power system voltage stability”, Mc Graw Hill, New York, 1994.
[6] P. Kundur, “Power system stability and control”, Mc Graw Hill, New York, 1994.
[7] N. Mithulananthan and S. C. Srivastava, “Investigation of a voltage collapse incident in Sri Lanka’s power system
network”, Proc. of the EMPD’98, Singapore, IEEE Catalogue No. 98EX137, pp. 47-52, March 3-5, 1998.
[8] R. A. Schlueter, I. Hu , M. W. Chang, J. C. Lo, and A. Costi, “Methods for determining proximity to voltage
collapse,” IEEE Transactions on Power System, Vol. 6, No. 1, pp. 285–292, February 1991.
[9] Lie, T., Schlueter, R.A., Rusche, P.A., and Rhoades, R., “Method of identifying weak transmission network stability
boundaries”, IEEE Transactions on Power Systems, Vol. 8, No. 1, pp. 293-301, February 1993.
[10] R. A. Schlueter, “A voltage stability security assessment method,” IEEE Transactions on Power Systems, 1998, Vol.
13, No. 4, pp. 1423–1438, November 1998.
[11] H. Liu, A. Bose and V. Venkatasubramanian, “A fast voltage security assessment method using adaptive bounding,”
IEEE Transactions on Power Systems, Vol. 15, No. 3, pp. 1137–1141, August 2000.
[12] C. A. Aumuller and T. K. Saha, “Determination of power system coherent bus groups by novel sensitivity-based
method for voltage stability assessment,” IEEE Transactions on Power Systems, Vol. 18, No. 3, pp. 1157–1164,
August 2003.
[13] M. K. Verma and S. C. Srivastava, “Approach to determine voltage control areas considering impact of
contingencies”, IEE Proceedings, Part-C, Generation, Transmission and Distribution, Vol. 152, No. 3, pp. 342-350,
May 2005.
[14] K. Morison, X. Wang, A. Moshref, A. Edris, “Identification of voltage control areas and reactive power reserve; An
advancement in on-line voltage security assessment,” IEEE PES General meeting - Conversion and Delivery of
Electrical Energy in the 21st Century, Pittsburg (Canada), pp. 1 – 7, July 20-24, 2008.
[15] M. K. Verma, Dushyant Juneja, Manish Prasad, “An Approach for Formation of Voltage Control Areas based on
Voltage Stability Criterion”, 16th NATIONAL POWER SYSTEMS CONFERENCE, 15th-17th DECEMBER,
2010.
[16] “Power systems test case archieve” available at http://www.ee.washington.edu/research/pstca/pf14/pg_tca14bus.htm
[17] Software Package UWPFLOW available at http://www.power.uwaterloo.ca/~claudio/software/pflow.html.

More Related Content

What's hot

Modeling of BESS for Blackstart System Restoration Studies
Modeling of BESS for Blackstart System Restoration StudiesModeling of BESS for Blackstart System Restoration Studies
Modeling of BESS for Blackstart System Restoration StudiesPower System Operation
 
Power Quality Improvement in Power System using UPFC
Power Quality Improvement in Power System using UPFCPower Quality Improvement in Power System using UPFC
Power Quality Improvement in Power System using UPFCijtsrd
 
A Voltage Controlled Dstatcom for Power Quality Improvement
A Voltage Controlled Dstatcom for Power Quality ImprovementA Voltage Controlled Dstatcom for Power Quality Improvement
A Voltage Controlled Dstatcom for Power Quality Improvementiosrjce
 
Controllers For A VSC-HVDC Link Connected To A Weak AC System
Controllers For A VSC-HVDC Link Connected To A Weak AC SystemControllers For A VSC-HVDC Link Connected To A Weak AC System
Controllers For A VSC-HVDC Link Connected To A Weak AC SystemIOSR Journals
 
Implementation of UPFC for Improvement of Power Stability
Implementation of UPFC for Improvement of Power StabilityImplementation of UPFC for Improvement of Power Stability
Implementation of UPFC for Improvement of Power StabilityIOSR Journals
 
FACTS DEVICES AND POWER SYSTEM STABILITY ppt
FACTS DEVICES AND POWER SYSTEM STABILITY pptFACTS DEVICES AND POWER SYSTEM STABILITY ppt
FACTS DEVICES AND POWER SYSTEM STABILITY pptMamta Bagoria
 
Assessment of the Static Stability Margin and Voltage Profile Improvement in ...
Assessment of the Static Stability Margin and Voltage Profile Improvement in ...Assessment of the Static Stability Margin and Voltage Profile Improvement in ...
Assessment of the Static Stability Margin and Voltage Profile Improvement in ...Dr. Amarjeet Singh
 
Performance Comparison of VSI Based DSTATCOM and ZSI Based DSTATCOM in A Dist...
Performance Comparison of VSI Based DSTATCOM and ZSI Based DSTATCOM in A Dist...Performance Comparison of VSI Based DSTATCOM and ZSI Based DSTATCOM in A Dist...
Performance Comparison of VSI Based DSTATCOM and ZSI Based DSTATCOM in A Dist...ruban8
 
Modeling Optimization Voltage Index Unified Power Flow Controller Equivalent ...
Modeling Optimization Voltage Index Unified Power Flow Controller Equivalent ...Modeling Optimization Voltage Index Unified Power Flow Controller Equivalent ...
Modeling Optimization Voltage Index Unified Power Flow Controller Equivalent ...IJMTST Journal
 
IRJET- Improving Power Quality by using MC-UPQC
IRJET- Improving Power Quality by using MC-UPQCIRJET- Improving Power Quality by using MC-UPQC
IRJET- Improving Power Quality by using MC-UPQCIRJET Journal
 
6.flexible d statcom performance as a flexible distributed generation in miti...
6.flexible d statcom performance as a flexible distributed generation in miti...6.flexible d statcom performance as a flexible distributed generation in miti...
6.flexible d statcom performance as a flexible distributed generation in miti...Hemanth Yadavalli
 
LOW VOLTAGE RIDE - THROUGH CAPABILITY OF WIND FARMS
LOW VOLTAGE RIDE - THROUGH CAPABILITY OF WIND FARMSLOW VOLTAGE RIDE - THROUGH CAPABILITY OF WIND FARMS
LOW VOLTAGE RIDE - THROUGH CAPABILITY OF WIND FARMSEditor IJMTER
 
International Journal of Engineering Research and Development
International Journal of Engineering Research and DevelopmentInternational Journal of Engineering Research and Development
International Journal of Engineering Research and DevelopmentIJERD Editor
 
Power factor improvement using upfc
Power factor improvement using upfcPower factor improvement using upfc
Power factor improvement using upfcUday Wankar
 
Steady State Operation And Enhancement Of Transient Stability In Hydel Power...
Steady State Operation And Enhancement Of Transient Stability  In Hydel Power...Steady State Operation And Enhancement Of Transient Stability  In Hydel Power...
Steady State Operation And Enhancement Of Transient Stability In Hydel Power...IJMER
 
An introduction to FACTS Technology
An introduction to FACTS TechnologyAn introduction to FACTS Technology
An introduction to FACTS TechnologyAyyarao T S L V
 
Enhancement of power quality in distribution system by using D-STATCOM
Enhancement of power quality in distribution system by using D-STATCOMEnhancement of power quality in distribution system by using D-STATCOM
Enhancement of power quality in distribution system by using D-STATCOMEng Ahmed Salad Osman
 
Stability Modeling Of Storage Devices In FACTS Applications
Stability Modeling Of Storage Devices In FACTS ApplicationsStability Modeling Of Storage Devices In FACTS Applications
Stability Modeling Of Storage Devices In FACTS Applicationspreeti naga
 

What's hot (20)

Modeling of BESS for Blackstart System Restoration Studies
Modeling of BESS for Blackstart System Restoration StudiesModeling of BESS for Blackstart System Restoration Studies
Modeling of BESS for Blackstart System Restoration Studies
 
Power Quality Improvement in Power System using UPFC
Power Quality Improvement in Power System using UPFCPower Quality Improvement in Power System using UPFC
Power Quality Improvement in Power System using UPFC
 
A Voltage Controlled Dstatcom for Power Quality Improvement
A Voltage Controlled Dstatcom for Power Quality ImprovementA Voltage Controlled Dstatcom for Power Quality Improvement
A Voltage Controlled Dstatcom for Power Quality Improvement
 
Controllers For A VSC-HVDC Link Connected To A Weak AC System
Controllers For A VSC-HVDC Link Connected To A Weak AC SystemControllers For A VSC-HVDC Link Connected To A Weak AC System
Controllers For A VSC-HVDC Link Connected To A Weak AC System
 
Implementation of UPFC for Improvement of Power Stability
Implementation of UPFC for Improvement of Power StabilityImplementation of UPFC for Improvement of Power Stability
Implementation of UPFC for Improvement of Power Stability
 
FACTS DEVICES AND POWER SYSTEM STABILITY ppt
FACTS DEVICES AND POWER SYSTEM STABILITY pptFACTS DEVICES AND POWER SYSTEM STABILITY ppt
FACTS DEVICES AND POWER SYSTEM STABILITY ppt
 
Assessment of the Static Stability Margin and Voltage Profile Improvement in ...
Assessment of the Static Stability Margin and Voltage Profile Improvement in ...Assessment of the Static Stability Margin and Voltage Profile Improvement in ...
Assessment of the Static Stability Margin and Voltage Profile Improvement in ...
 
Performance Comparison of VSI Based DSTATCOM and ZSI Based DSTATCOM in A Dist...
Performance Comparison of VSI Based DSTATCOM and ZSI Based DSTATCOM in A Dist...Performance Comparison of VSI Based DSTATCOM and ZSI Based DSTATCOM in A Dist...
Performance Comparison of VSI Based DSTATCOM and ZSI Based DSTATCOM in A Dist...
 
Modeling Optimization Voltage Index Unified Power Flow Controller Equivalent ...
Modeling Optimization Voltage Index Unified Power Flow Controller Equivalent ...Modeling Optimization Voltage Index Unified Power Flow Controller Equivalent ...
Modeling Optimization Voltage Index Unified Power Flow Controller Equivalent ...
 
IRJET- Improving Power Quality by using MC-UPQC
IRJET- Improving Power Quality by using MC-UPQCIRJET- Improving Power Quality by using MC-UPQC
IRJET- Improving Power Quality by using MC-UPQC
 
6.flexible d statcom performance as a flexible distributed generation in miti...
6.flexible d statcom performance as a flexible distributed generation in miti...6.flexible d statcom performance as a flexible distributed generation in miti...
6.flexible d statcom performance as a flexible distributed generation in miti...
 
LOW VOLTAGE RIDE - THROUGH CAPABILITY OF WIND FARMS
LOW VOLTAGE RIDE - THROUGH CAPABILITY OF WIND FARMSLOW VOLTAGE RIDE - THROUGH CAPABILITY OF WIND FARMS
LOW VOLTAGE RIDE - THROUGH CAPABILITY OF WIND FARMS
 
International Journal of Engineering Research and Development
International Journal of Engineering Research and DevelopmentInternational Journal of Engineering Research and Development
International Journal of Engineering Research and Development
 
Power factor improvement using upfc
Power factor improvement using upfcPower factor improvement using upfc
Power factor improvement using upfc
 
Steady State Operation And Enhancement Of Transient Stability In Hydel Power...
Steady State Operation And Enhancement Of Transient Stability  In Hydel Power...Steady State Operation And Enhancement Of Transient Stability  In Hydel Power...
Steady State Operation And Enhancement Of Transient Stability In Hydel Power...
 
Power Quality Problems and Solutions
Power Quality Problems and Solutions Power Quality Problems and Solutions
Power Quality Problems and Solutions
 
An introduction to FACTS Technology
An introduction to FACTS TechnologyAn introduction to FACTS Technology
An introduction to FACTS Technology
 
Effect of Carrier Frequency in Grid Inter Connected Wind System With SSFC Con...
Effect of Carrier Frequency in Grid Inter Connected Wind System With SSFC Con...Effect of Carrier Frequency in Grid Inter Connected Wind System With SSFC Con...
Effect of Carrier Frequency in Grid Inter Connected Wind System With SSFC Con...
 
Enhancement of power quality in distribution system by using D-STATCOM
Enhancement of power quality in distribution system by using D-STATCOMEnhancement of power quality in distribution system by using D-STATCOM
Enhancement of power quality in distribution system by using D-STATCOM
 
Stability Modeling Of Storage Devices In FACTS Applications
Stability Modeling Of Storage Devices In FACTS ApplicationsStability Modeling Of Storage Devices In FACTS Applications
Stability Modeling Of Storage Devices In FACTS Applications
 

Similar to Voltage Stability Based Formation of Voltage Control Areas Considering Impact of Contingencies

International Journal of Computational Engineering Research(IJCER)
International Journal of Computational Engineering Research(IJCER)International Journal of Computational Engineering Research(IJCER)
International Journal of Computational Engineering Research(IJCER)ijceronline
 
Influence of Static VAR Compensator for Undervoltage Load Shedding to Avoid V...
Influence of Static VAR Compensator for Undervoltage Load Shedding to Avoid V...Influence of Static VAR Compensator for Undervoltage Load Shedding to Avoid V...
Influence of Static VAR Compensator for Undervoltage Load Shedding to Avoid V...IJAPEJOURNAL
 
A Review on Power System Voltage Stability and Optimization Techniques
A Review on Power System Voltage Stability and Optimization TechniquesA Review on Power System Voltage Stability and Optimization Techniques
A Review on Power System Voltage Stability and Optimization TechniquesIJERA Editor
 
Online voltage stability margin assessment
Online voltage stability margin assessmentOnline voltage stability margin assessment
Online voltage stability margin assessmentNaganathan G Sesaiyan
 
Investigation and Comparison of the Effect of Facts Devices, Capacitors and L...
Investigation and Comparison of the Effect of Facts Devices, Capacitors and L...Investigation and Comparison of the Effect of Facts Devices, Capacitors and L...
Investigation and Comparison of the Effect of Facts Devices, Capacitors and L...IJAPEJOURNAL
 
Enhancement of Voltage Stability on IEEE 14 Bus Systems Using Static Var Comp...
Enhancement of Voltage Stability on IEEE 14 Bus Systems Using Static Var Comp...Enhancement of Voltage Stability on IEEE 14 Bus Systems Using Static Var Comp...
Enhancement of Voltage Stability on IEEE 14 Bus Systems Using Static Var Comp...paperpublications3
 
Comparison of upqc and dvr in wind turbine fed fsig under asymmetric faults
Comparison of upqc and dvr in wind turbine fed fsig under asymmetric faultsComparison of upqc and dvr in wind turbine fed fsig under asymmetric faults
Comparison of upqc and dvr in wind turbine fed fsig under asymmetric faultselelijjournal
 
Dual-Level Adaptive Supply Voltage System with Bandgap Reference MPR for Vari...
Dual-Level Adaptive Supply Voltage System with Bandgap Reference MPR for Vari...Dual-Level Adaptive Supply Voltage System with Bandgap Reference MPR for Vari...
Dual-Level Adaptive Supply Voltage System with Bandgap Reference MPR for Vari...IJERA Editor
 
Location of Shunt FACTS Devices for First-Swing Stability Enhancement in Inte...
Location of Shunt FACTS Devices for First-Swing Stability Enhancement in Inte...Location of Shunt FACTS Devices for First-Swing Stability Enhancement in Inte...
Location of Shunt FACTS Devices for First-Swing Stability Enhancement in Inte...Editor IJMTER
 
Identification of Weak and Critical Buses in Electrical Power System
Identification of Weak and Critical Buses in Electrical Power SystemIdentification of Weak and Critical Buses in Electrical Power System
Identification of Weak and Critical Buses in Electrical Power SystemIRJET Journal
 
Influencing Power Flow and Transient Stability by Static Synchronous Series C...
Influencing Power Flow and Transient Stability by Static Synchronous Series C...Influencing Power Flow and Transient Stability by Static Synchronous Series C...
Influencing Power Flow and Transient Stability by Static Synchronous Series C...ijeei-iaes
 
Load Flow and PV Curve Analysis of a 220kV Substation
Load Flow and PV Curve Analysis of a 220kV SubstationLoad Flow and PV Curve Analysis of a 220kV Substation
Load Flow and PV Curve Analysis of a 220kV SubstationIRJET Journal
 
Reparation of Inductive Power in Power System by the use of FACTS devices
Reparation of Inductive Power in Power System by the use of FACTS devicesReparation of Inductive Power in Power System by the use of FACTS devices
Reparation of Inductive Power in Power System by the use of FACTS devicesIJMTST Journal
 
IRJET-Identification of Weak Bus using Load Variation
IRJET-Identification of Weak Bus using Load VariationIRJET-Identification of Weak Bus using Load Variation
IRJET-Identification of Weak Bus using Load VariationIRJET Journal
 
Techno economic study of series current limiting reactor and its impact in th...
Techno economic study of series current limiting reactor and its impact in th...Techno economic study of series current limiting reactor and its impact in th...
Techno economic study of series current limiting reactor and its impact in th...Alexander Decker
 
Matlab Simulink in Three-Phase Fault Analysis on Transmission line
Matlab Simulink in Three-Phase Fault Analysis on Transmission lineMatlab Simulink in Three-Phase Fault Analysis on Transmission line
Matlab Simulink in Three-Phase Fault Analysis on Transmission linepamu17
 
Under voltage load shedding for contingency analysis to optimize power loss ...
Under voltage load shedding for contingency analysis to  optimize power loss ...Under voltage load shedding for contingency analysis to  optimize power loss ...
Under voltage load shedding for contingency analysis to optimize power loss ...elelijjournal
 
A detailed analysis on the performance
A detailed analysis on the performanceA detailed analysis on the performance
A detailed analysis on the performanceprj_publication
 
Selective localization of capacitor banks considering stability aspects in po...
Selective localization of capacitor banks considering stability aspects in po...Selective localization of capacitor banks considering stability aspects in po...
Selective localization of capacitor banks considering stability aspects in po...IAEME Publication
 

Similar to Voltage Stability Based Formation of Voltage Control Areas Considering Impact of Contingencies (20)

International Journal of Computational Engineering Research(IJCER)
International Journal of Computational Engineering Research(IJCER)International Journal of Computational Engineering Research(IJCER)
International Journal of Computational Engineering Research(IJCER)
 
Influence of Static VAR Compensator for Undervoltage Load Shedding to Avoid V...
Influence of Static VAR Compensator for Undervoltage Load Shedding to Avoid V...Influence of Static VAR Compensator for Undervoltage Load Shedding to Avoid V...
Influence of Static VAR Compensator for Undervoltage Load Shedding to Avoid V...
 
A Review on Power System Voltage Stability and Optimization Techniques
A Review on Power System Voltage Stability and Optimization TechniquesA Review on Power System Voltage Stability and Optimization Techniques
A Review on Power System Voltage Stability and Optimization Techniques
 
Online voltage stability margin assessment
Online voltage stability margin assessmentOnline voltage stability margin assessment
Online voltage stability margin assessment
 
Investigation and Comparison of the Effect of Facts Devices, Capacitors and L...
Investigation and Comparison of the Effect of Facts Devices, Capacitors and L...Investigation and Comparison of the Effect of Facts Devices, Capacitors and L...
Investigation and Comparison of the Effect of Facts Devices, Capacitors and L...
 
Enhancement of Voltage Stability on IEEE 14 Bus Systems Using Static Var Comp...
Enhancement of Voltage Stability on IEEE 14 Bus Systems Using Static Var Comp...Enhancement of Voltage Stability on IEEE 14 Bus Systems Using Static Var Comp...
Enhancement of Voltage Stability on IEEE 14 Bus Systems Using Static Var Comp...
 
Comparison of upqc and dvr in wind turbine fed fsig under asymmetric faults
Comparison of upqc and dvr in wind turbine fed fsig under asymmetric faultsComparison of upqc and dvr in wind turbine fed fsig under asymmetric faults
Comparison of upqc and dvr in wind turbine fed fsig under asymmetric faults
 
Dual-Level Adaptive Supply Voltage System with Bandgap Reference MPR for Vari...
Dual-Level Adaptive Supply Voltage System with Bandgap Reference MPR for Vari...Dual-Level Adaptive Supply Voltage System with Bandgap Reference MPR for Vari...
Dual-Level Adaptive Supply Voltage System with Bandgap Reference MPR for Vari...
 
Location of Shunt FACTS Devices for First-Swing Stability Enhancement in Inte...
Location of Shunt FACTS Devices for First-Swing Stability Enhancement in Inte...Location of Shunt FACTS Devices for First-Swing Stability Enhancement in Inte...
Location of Shunt FACTS Devices for First-Swing Stability Enhancement in Inte...
 
Identification of Weak and Critical Buses in Electrical Power System
Identification of Weak and Critical Buses in Electrical Power SystemIdentification of Weak and Critical Buses in Electrical Power System
Identification of Weak and Critical Buses in Electrical Power System
 
Influencing Power Flow and Transient Stability by Static Synchronous Series C...
Influencing Power Flow and Transient Stability by Static Synchronous Series C...Influencing Power Flow and Transient Stability by Static Synchronous Series C...
Influencing Power Flow and Transient Stability by Static Synchronous Series C...
 
Load Flow and PV Curve Analysis of a 220kV Substation
Load Flow and PV Curve Analysis of a 220kV SubstationLoad Flow and PV Curve Analysis of a 220kV Substation
Load Flow and PV Curve Analysis of a 220kV Substation
 
Reparation of Inductive Power in Power System by the use of FACTS devices
Reparation of Inductive Power in Power System by the use of FACTS devicesReparation of Inductive Power in Power System by the use of FACTS devices
Reparation of Inductive Power in Power System by the use of FACTS devices
 
IRJET-Identification of Weak Bus using Load Variation
IRJET-Identification of Weak Bus using Load VariationIRJET-Identification of Weak Bus using Load Variation
IRJET-Identification of Weak Bus using Load Variation
 
Techno economic study of series current limiting reactor and its impact in th...
Techno economic study of series current limiting reactor and its impact in th...Techno economic study of series current limiting reactor and its impact in th...
Techno economic study of series current limiting reactor and its impact in th...
 
Matlab Simulink in Three-Phase Fault Analysis on Transmission line
Matlab Simulink in Three-Phase Fault Analysis on Transmission lineMatlab Simulink in Three-Phase Fault Analysis on Transmission line
Matlab Simulink in Three-Phase Fault Analysis on Transmission line
 
Under voltage load shedding for contingency analysis to optimize power loss ...
Under voltage load shedding for contingency analysis to  optimize power loss ...Under voltage load shedding for contingency analysis to  optimize power loss ...
Under voltage load shedding for contingency analysis to optimize power loss ...
 
A detailed analysis on the performance
A detailed analysis on the performanceA detailed analysis on the performance
A detailed analysis on the performance
 
Under voltage load shedding
Under voltage load sheddingUnder voltage load shedding
Under voltage load shedding
 
Selective localization of capacitor banks considering stability aspects in po...
Selective localization of capacitor banks considering stability aspects in po...Selective localization of capacitor banks considering stability aspects in po...
Selective localization of capacitor banks considering stability aspects in po...
 

More from IJAPEJOURNAL

Effects of the Droop Speed Governor and Automatic Generation Control AGC on G...
Effects of the Droop Speed Governor and Automatic Generation Control AGC on G...Effects of the Droop Speed Governor and Automatic Generation Control AGC on G...
Effects of the Droop Speed Governor and Automatic Generation Control AGC on G...IJAPEJOURNAL
 
Underwater Target Tracking Using Unscented Kalman Filter
Underwater Target Tracking Using Unscented Kalman FilterUnderwater Target Tracking Using Unscented Kalman Filter
Underwater Target Tracking Using Unscented Kalman FilterIJAPEJOURNAL
 
Investigation of Dependent Rikitake System to Initiation Point
Investigation of Dependent Rikitake System to Initiation PointInvestigation of Dependent Rikitake System to Initiation Point
Investigation of Dependent Rikitake System to Initiation PointIJAPEJOURNAL
 
Optimization of Economic Load Dispatch with Unit Commitment on Multi Machine
Optimization of Economic Load Dispatch with Unit Commitment on Multi MachineOptimization of Economic Load Dispatch with Unit Commitment on Multi Machine
Optimization of Economic Load Dispatch with Unit Commitment on Multi MachineIJAPEJOURNAL
 
Impact of Buried Conductor Length on Computation of Earth Grid Resistance
Impact of Buried Conductor Length on Computation of Earth Grid ResistanceImpact of Buried Conductor Length on Computation of Earth Grid Resistance
Impact of Buried Conductor Length on Computation of Earth Grid ResistanceIJAPEJOURNAL
 
Enhancing Photoelectric Conversion Efficiency of Solar Panel by Water Cooling
Enhancing Photoelectric Conversion Efficiency of Solar Panel by Water CoolingEnhancing Photoelectric Conversion Efficiency of Solar Panel by Water Cooling
Enhancing Photoelectric Conversion Efficiency of Solar Panel by Water CoolingIJAPEJOURNAL
 
PMU-Based Transmission Line Parameter Identification at China Southern Power ...
PMU-Based Transmission Line Parameter Identification at China Southern Power ...PMU-Based Transmission Line Parameter Identification at China Southern Power ...
PMU-Based Transmission Line Parameter Identification at China Southern Power ...IJAPEJOURNAL
 
Investigation of Electric Field Distribution Inside 500/220 kV Transformation...
Investigation of Electric Field Distribution Inside 500/220 kV Transformation...Investigation of Electric Field Distribution Inside 500/220 kV Transformation...
Investigation of Electric Field Distribution Inside 500/220 kV Transformation...IJAPEJOURNAL
 
Economic Load Dispatch for Multi-Generator Systems with Units Having Nonlinea...
Economic Load Dispatch for Multi-Generator Systems with Units Having Nonlinea...Economic Load Dispatch for Multi-Generator Systems with Units Having Nonlinea...
Economic Load Dispatch for Multi-Generator Systems with Units Having Nonlinea...IJAPEJOURNAL
 
Improving Light-Load Efficiency by Eliminating Interaction Effect in the Grid...
Improving Light-Load Efficiency by Eliminating Interaction Effect in the Grid...Improving Light-Load Efficiency by Eliminating Interaction Effect in the Grid...
Improving Light-Load Efficiency by Eliminating Interaction Effect in the Grid...IJAPEJOURNAL
 
An Application of Ulam-Hyers Stability in DC Motors
An Application of Ulam-Hyers Stability in DC MotorsAn Application of Ulam-Hyers Stability in DC Motors
An Application of Ulam-Hyers Stability in DC MotorsIJAPEJOURNAL
 
Implementation of Hybrid Generation Power System in Pakistan
Implementation of Hybrid Generation Power System in PakistanImplementation of Hybrid Generation Power System in Pakistan
Implementation of Hybrid Generation Power System in PakistanIJAPEJOURNAL
 
Modeling and Simulation of SVPWM Based Application
Modeling and Simulation of SVPWM Based ApplicationModeling and Simulation of SVPWM Based Application
Modeling and Simulation of SVPWM Based ApplicationIJAPEJOURNAL
 
Comparison of FACTS Devices for Two Area Power System Stability Enhancement u...
Comparison of FACTS Devices for Two Area Power System Stability Enhancement u...Comparison of FACTS Devices for Two Area Power System Stability Enhancement u...
Comparison of FACTS Devices for Two Area Power System Stability Enhancement u...IJAPEJOURNAL
 
Assessment of Electric Field Distribution Inside 500/220 kV Open Distribution...
Assessment of Electric Field Distribution Inside 500/220 kV Open Distribution...Assessment of Electric Field Distribution Inside 500/220 kV Open Distribution...
Assessment of Electric Field Distribution Inside 500/220 kV Open Distribution...IJAPEJOURNAL
 
Towards An Accurate Modeling of Frequency-dependent Wind Farm Components Unde...
Towards An Accurate Modeling of Frequency-dependent Wind Farm Components Unde...Towards An Accurate Modeling of Frequency-dependent Wind Farm Components Unde...
Towards An Accurate Modeling of Frequency-dependent Wind Farm Components Unde...IJAPEJOURNAL
 
Hybrid Generation Power System for Domestic Applications
Hybrid Generation Power System for Domestic ApplicationsHybrid Generation Power System for Domestic Applications
Hybrid Generation Power System for Domestic ApplicationsIJAPEJOURNAL
 
Ash Cooler Heat Recovery Under Energy Conservation Scheme
Ash Cooler Heat Recovery Under Energy Conservation SchemeAsh Cooler Heat Recovery Under Energy Conservation Scheme
Ash Cooler Heat Recovery Under Energy Conservation SchemeIJAPEJOURNAL
 
Harmonic Voltage Distortions in Power Systems Due to Non Linear Loads
Harmonic Voltage Distortions in Power Systems Due to Non Linear LoadsHarmonic Voltage Distortions in Power Systems Due to Non Linear Loads
Harmonic Voltage Distortions in Power Systems Due to Non Linear LoadsIJAPEJOURNAL
 
A Survey on Quality Changes in Positive, Negative and Combined Switching Stra...
A Survey on Quality Changes in Positive, Negative and Combined Switching Stra...A Survey on Quality Changes in Positive, Negative and Combined Switching Stra...
A Survey on Quality Changes in Positive, Negative and Combined Switching Stra...IJAPEJOURNAL
 

More from IJAPEJOURNAL (20)

Effects of the Droop Speed Governor and Automatic Generation Control AGC on G...
Effects of the Droop Speed Governor and Automatic Generation Control AGC on G...Effects of the Droop Speed Governor and Automatic Generation Control AGC on G...
Effects of the Droop Speed Governor and Automatic Generation Control AGC on G...
 
Underwater Target Tracking Using Unscented Kalman Filter
Underwater Target Tracking Using Unscented Kalman FilterUnderwater Target Tracking Using Unscented Kalman Filter
Underwater Target Tracking Using Unscented Kalman Filter
 
Investigation of Dependent Rikitake System to Initiation Point
Investigation of Dependent Rikitake System to Initiation PointInvestigation of Dependent Rikitake System to Initiation Point
Investigation of Dependent Rikitake System to Initiation Point
 
Optimization of Economic Load Dispatch with Unit Commitment on Multi Machine
Optimization of Economic Load Dispatch with Unit Commitment on Multi MachineOptimization of Economic Load Dispatch with Unit Commitment on Multi Machine
Optimization of Economic Load Dispatch with Unit Commitment on Multi Machine
 
Impact of Buried Conductor Length on Computation of Earth Grid Resistance
Impact of Buried Conductor Length on Computation of Earth Grid ResistanceImpact of Buried Conductor Length on Computation of Earth Grid Resistance
Impact of Buried Conductor Length on Computation of Earth Grid Resistance
 
Enhancing Photoelectric Conversion Efficiency of Solar Panel by Water Cooling
Enhancing Photoelectric Conversion Efficiency of Solar Panel by Water CoolingEnhancing Photoelectric Conversion Efficiency of Solar Panel by Water Cooling
Enhancing Photoelectric Conversion Efficiency of Solar Panel by Water Cooling
 
PMU-Based Transmission Line Parameter Identification at China Southern Power ...
PMU-Based Transmission Line Parameter Identification at China Southern Power ...PMU-Based Transmission Line Parameter Identification at China Southern Power ...
PMU-Based Transmission Line Parameter Identification at China Southern Power ...
 
Investigation of Electric Field Distribution Inside 500/220 kV Transformation...
Investigation of Electric Field Distribution Inside 500/220 kV Transformation...Investigation of Electric Field Distribution Inside 500/220 kV Transformation...
Investigation of Electric Field Distribution Inside 500/220 kV Transformation...
 
Economic Load Dispatch for Multi-Generator Systems with Units Having Nonlinea...
Economic Load Dispatch for Multi-Generator Systems with Units Having Nonlinea...Economic Load Dispatch for Multi-Generator Systems with Units Having Nonlinea...
Economic Load Dispatch for Multi-Generator Systems with Units Having Nonlinea...
 
Improving Light-Load Efficiency by Eliminating Interaction Effect in the Grid...
Improving Light-Load Efficiency by Eliminating Interaction Effect in the Grid...Improving Light-Load Efficiency by Eliminating Interaction Effect in the Grid...
Improving Light-Load Efficiency by Eliminating Interaction Effect in the Grid...
 
An Application of Ulam-Hyers Stability in DC Motors
An Application of Ulam-Hyers Stability in DC MotorsAn Application of Ulam-Hyers Stability in DC Motors
An Application of Ulam-Hyers Stability in DC Motors
 
Implementation of Hybrid Generation Power System in Pakistan
Implementation of Hybrid Generation Power System in PakistanImplementation of Hybrid Generation Power System in Pakistan
Implementation of Hybrid Generation Power System in Pakistan
 
Modeling and Simulation of SVPWM Based Application
Modeling and Simulation of SVPWM Based ApplicationModeling and Simulation of SVPWM Based Application
Modeling and Simulation of SVPWM Based Application
 
Comparison of FACTS Devices for Two Area Power System Stability Enhancement u...
Comparison of FACTS Devices for Two Area Power System Stability Enhancement u...Comparison of FACTS Devices for Two Area Power System Stability Enhancement u...
Comparison of FACTS Devices for Two Area Power System Stability Enhancement u...
 
Assessment of Electric Field Distribution Inside 500/220 kV Open Distribution...
Assessment of Electric Field Distribution Inside 500/220 kV Open Distribution...Assessment of Electric Field Distribution Inside 500/220 kV Open Distribution...
Assessment of Electric Field Distribution Inside 500/220 kV Open Distribution...
 
Towards An Accurate Modeling of Frequency-dependent Wind Farm Components Unde...
Towards An Accurate Modeling of Frequency-dependent Wind Farm Components Unde...Towards An Accurate Modeling of Frequency-dependent Wind Farm Components Unde...
Towards An Accurate Modeling of Frequency-dependent Wind Farm Components Unde...
 
Hybrid Generation Power System for Domestic Applications
Hybrid Generation Power System for Domestic ApplicationsHybrid Generation Power System for Domestic Applications
Hybrid Generation Power System for Domestic Applications
 
Ash Cooler Heat Recovery Under Energy Conservation Scheme
Ash Cooler Heat Recovery Under Energy Conservation SchemeAsh Cooler Heat Recovery Under Energy Conservation Scheme
Ash Cooler Heat Recovery Under Energy Conservation Scheme
 
Harmonic Voltage Distortions in Power Systems Due to Non Linear Loads
Harmonic Voltage Distortions in Power Systems Due to Non Linear LoadsHarmonic Voltage Distortions in Power Systems Due to Non Linear Loads
Harmonic Voltage Distortions in Power Systems Due to Non Linear Loads
 
A Survey on Quality Changes in Positive, Negative and Combined Switching Stra...
A Survey on Quality Changes in Positive, Negative and Combined Switching Stra...A Survey on Quality Changes in Positive, Negative and Combined Switching Stra...
A Survey on Quality Changes in Positive, Negative and Combined Switching Stra...
 

Recently uploaded

High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur High Profile
 
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escortsranjana rawat
 
Software Development Life Cycle By Team Orange (Dept. of Pharmacy)
Software Development Life Cycle By  Team Orange (Dept. of Pharmacy)Software Development Life Cycle By  Team Orange (Dept. of Pharmacy)
Software Development Life Cycle By Team Orange (Dept. of Pharmacy)Suman Mia
 
What are the advantages and disadvantages of membrane structures.pptx
What are the advantages and disadvantages of membrane structures.pptxWhat are the advantages and disadvantages of membrane structures.pptx
What are the advantages and disadvantages of membrane structures.pptxwendy cai
 
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINE
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINEMANUFACTURING PROCESS-II UNIT-2 LATHE MACHINE
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINESIVASHANKAR N
 
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptxDecoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptxJoão Esperancinha
 
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...ranjana rawat
 
College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service NashikCollege Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service NashikCall Girls in Nagpur High Profile
 
SPICE PARK APR2024 ( 6,793 SPICE Models )
SPICE PARK APR2024 ( 6,793 SPICE Models )SPICE PARK APR2024 ( 6,793 SPICE Models )
SPICE PARK APR2024 ( 6,793 SPICE Models )Tsuyoshi Horigome
 
Current Transformer Drawing and GTP for MSETCL
Current Transformer Drawing and GTP for MSETCLCurrent Transformer Drawing and GTP for MSETCL
Current Transformer Drawing and GTP for MSETCLDeelipZope
 
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130Suhani Kapoor
 
Microscopic Analysis of Ceramic Materials.pptx
Microscopic Analysis of Ceramic Materials.pptxMicroscopic Analysis of Ceramic Materials.pptx
Microscopic Analysis of Ceramic Materials.pptxpurnimasatapathy1234
 
Introduction to Multiple Access Protocol.pptx
Introduction to Multiple Access Protocol.pptxIntroduction to Multiple Access Protocol.pptx
Introduction to Multiple Access Protocol.pptxupamatechverse
 
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...ranjana rawat
 
Architect Hassan Khalil Portfolio for 2024
Architect Hassan Khalil Portfolio for 2024Architect Hassan Khalil Portfolio for 2024
Architect Hassan Khalil Portfolio for 2024hassan khalil
 
247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).ppt
247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).ppt247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).ppt
247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).pptssuser5c9d4b1
 
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICSAPPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICSKurinjimalarL3
 
Call Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur Escorts
Call Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur EscortsCall Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur Escorts
Call Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur High Profile
 
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130Suhani Kapoor
 

Recently uploaded (20)

High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
 
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
 
Software Development Life Cycle By Team Orange (Dept. of Pharmacy)
Software Development Life Cycle By  Team Orange (Dept. of Pharmacy)Software Development Life Cycle By  Team Orange (Dept. of Pharmacy)
Software Development Life Cycle By Team Orange (Dept. of Pharmacy)
 
What are the advantages and disadvantages of membrane structures.pptx
What are the advantages and disadvantages of membrane structures.pptxWhat are the advantages and disadvantages of membrane structures.pptx
What are the advantages and disadvantages of membrane structures.pptx
 
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINE
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINEMANUFACTURING PROCESS-II UNIT-2 LATHE MACHINE
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINE
 
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptxDecoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
 
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
 
College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service NashikCollege Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
 
SPICE PARK APR2024 ( 6,793 SPICE Models )
SPICE PARK APR2024 ( 6,793 SPICE Models )SPICE PARK APR2024 ( 6,793 SPICE Models )
SPICE PARK APR2024 ( 6,793 SPICE Models )
 
Current Transformer Drawing and GTP for MSETCL
Current Transformer Drawing and GTP for MSETCLCurrent Transformer Drawing and GTP for MSETCL
Current Transformer Drawing and GTP for MSETCL
 
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130
 
Exploring_Network_Security_with_JA3_by_Rakesh Seal.pptx
Exploring_Network_Security_with_JA3_by_Rakesh Seal.pptxExploring_Network_Security_with_JA3_by_Rakesh Seal.pptx
Exploring_Network_Security_with_JA3_by_Rakesh Seal.pptx
 
Microscopic Analysis of Ceramic Materials.pptx
Microscopic Analysis of Ceramic Materials.pptxMicroscopic Analysis of Ceramic Materials.pptx
Microscopic Analysis of Ceramic Materials.pptx
 
Introduction to Multiple Access Protocol.pptx
Introduction to Multiple Access Protocol.pptxIntroduction to Multiple Access Protocol.pptx
Introduction to Multiple Access Protocol.pptx
 
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
 
Architect Hassan Khalil Portfolio for 2024
Architect Hassan Khalil Portfolio for 2024Architect Hassan Khalil Portfolio for 2024
Architect Hassan Khalil Portfolio for 2024
 
247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).ppt
247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).ppt247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).ppt
247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).ppt
 
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICSAPPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
 
Call Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur Escorts
Call Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur EscortsCall Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur Escorts
Call Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur Escorts
 
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
 

Voltage Stability Based Formation of Voltage Control Areas Considering Impact of Contingencies

  • 1. International Journal of Applied Power Engineering (IJAPE) Vol. 1, No. 3, December 2012, pp. 115~122 ISSN: 2252-8792 115 Journal homepage: http://iaesjournal.com/online/index.php/IJAPE Voltage Stability Based Formation of Voltage Control Areas Considering Impact of Contingencies Tarun Martolia1 and M. K. Verma2 Department of Electrical Engineering, Indian Institute of Technology (Banaras Hindu University), Varanasi, India Article Info ABSTRACT Article history: Received Jul 16, 2012 Revised Oct 11, 2012 Accepted Oct 20, 2012 Voltage instability has been considered as a major threat to power system networks since last three decades. Frequent incidences of grid failures caused by voltage instability have been observed in different parts of the world. Fast voltage stability assessment of power system may be done by formation of voltage control areas, clubbing group of buses in geographically compact region having similar voltage instability problem. This paper presents a new approach for formation of voltage control areas (VCAs) based on sensitivity of reactive power generations with respect to reactive power demands, together with bus voltage variations under voltage stability based critical contingencies. The load buses in geographically compact region showing similar sensitivity of reactive power demand to reactive generations have been clubbed together to form voltage control areas. Since, voltage control areas formed should remain valid under change in operating conditions and network topology, the areas formed based on reactive power sensitivities have been modified considering voltage variations at different loadings points under voltage stability based critical contingencies. Voltage stability based Critical contingencies have been selected based on maximum loadability criterion. Case studies have been performed on IEEE 14-bus system. Simulation results performed on IEEE 14-bus system validate VCAs formed even under change in network topology caused by line outages and change in operating conditions caused by variations in real and reactive power demands. The VCAs formed by proposed method have been compared with VCAs formed by few existing approaches. The superiority of proposed approach of voltage control areas formation over few existing approaches has been established on the test system considered. Keyword: Voltage control area reactive power sensitivity contingencies maximum loadability voltage stability Copyright © 2012 Institute of Advanced Engineering and Science. All rights reserved. Corresponding Author: Tarun Martolia Department of Electrical Engineering, Indian Institute of Technology (Banaras Hindu University) Varanasi-221005 (India) e-mail: tarun.martolia.eee10@itbhu.ac.in, 1. INTRODUCTION Power system stability has been recognized as an important problem for its secure operation since 1920s [1],[2]. Traditionally, the problem of stability has been one of maintaining the synchronous operation of generators operating in parallel, known as rotor angle stability. The problem of rotor angle stability is well understood and documented. With continuous increase in power demand, and due to limited expansion of transmission systems, modern power system networks are being operated under highly stressed conditions. This has imposed the threat of maintaining the required bus voltages, and thus the systems have been facing voltage instability problem [3]. Voltage stability is the ability of a power system to maintain voltage magnitudes at all the buses in the system within acceptable range after being subjected to a disturbance from a given initial operating condition [3]. It depends on the ability to maintain/restore equilibrium between load demand and load supply from the power system. Due to increase in power demand, modern power system networks are being
  • 2. ISSN: 2252-8792 IJAPE Vol. 1, No. 3, December 2012 : 115 – 122 116 operated under highly stressed conditions. This has resulted into the difficulty in meeting reactive power requirement, specially under contingencies, and hence maintaining the bus voltages within acceptable limits. Voltage instability in the system, generally, occurs in the form of a progressive decay in voltage magnitude at some of the buses. A possible outcome of voltage instability is loss of load in an area, or tripping of transmission lines and other elements by their protective systems leading to cascaded outages and voltage collapse in the system [3],[4]. Voltage collapse is the process by which the sequence of events, accompanying voltage instability, leads to a blackout or abnormally low voltages in a significant part of a power system [4]-[6]. Several incidences of voltage collapse have been observed, in past few decades, in different parts of the world. Some of the incidences of voltage collapse are [6],[7]: • New York Pool disturbance of September 22, 1970. • Florida system disturbance of December 28, 1982. • French system disturbances of December 19, 1978 and January 12, 1987. • Northern Belgium system disturbance of August 4, 1982. • Swedish system disturbance of December 27, 1983. • Japanese system disturbance of July 23, 1983. • Western Systems Co-ordination Council (WSCC) interconnected system (North America) disturbance of July 2, 1996. • Sri Lankan Power System disturbance of May 2, 1995. • Northern grid disturbance in Indian Power System of December 1996. • Punjab voltage collapse in Indian Power System on June 10, 2007. The structural weakness of the power system, due to weak transmission boundaries between different groups of buses, has also been considered a reason of voltage instability [8]. These groups of buses, located in geographically compact region, have similar voltage changes for any outside disturbance. The bus clusters so formed are called voltage control areas (VCAs) [8]. Due to weak transmission boundaries, loss of voltage controls within a voltage control area may result in voltage collapse in that area since the voltage controls in other voltage control areas may have relatively less impact in controlling voltages in that area. For any external disturbance, each of the voltage control areas may be reduced to equivalent nodes by some network reduction technique. Localization of voltage controls in critical areas together with reduction of areas to equivalent nodes for external disturbances may be quite helpful in fast voltage stability assessment and control of power system networks. A number of methods have been suggested in literature for formation of voltage control areas. Voltage control areas have been determined by eliminating smaller off-diagonal elements of normalized Q-V Jacobian in [8].In order to consider the effect of Q-δ and P-V coupling, which are very much valid under highly stressed conditions, this algorithm has been applied to full load flow Jacobian instead of decoupled Q- V Jacobian in [9]. The methods suggested in [8], [9] requires proper selection of threshold (α) for elimination of smaller off-diagonal elements, which is a difficult task since smaller values of α puts almost all the buses in one cluster, whereas a larger value may make each bus a separate voltage control area. V-Q curve minima based α-selection algorithm has been proposed in [10]. Formation of voltage control areas under contingencies using an electrical distance concept and V-Q sensitivities of power flow Jacobian has been suggested in [11]. Group of coherent buses have been formed in [12] using generator branch reactive power flow sensitivities to reactive power injection at load buses. The buses having similar generator branch sensitivity values within a reasonable limit of 5% have been clubbed to form voltage control areas. Computations of generator branch sensitivities have been done at the base case operating point. However, generator branch sensitivities are not expected to remain same for change in operating condition or network topology. Voltage control areas have been formed based on Jacobian sensitivities together with voltage variations under contingencies [13]. However, formation of voltage control areas has been done at the base case operating point and V-Q curve minima have been used for selection of threshold only, for elimination of weaker off-diagonal elements of Jacobian. In [13], contingencies have been selected randomly and no specific criterion has been proposed for selection of critical contingencies to study voltage variations from the base case value. Voltage control areas have been formed using bus participation factors corresponding to zero eigen value at the nose point of P-V curve [14]. However, eigen analysis is a linear analysis and may not always be suitable at the nose point of P-V curve. Formation of VCAs has been done based on individual critical loading factor (maximum loadability) of various buses in the geographically compact region [15]. In [15], the VCA with lowest range of maximum loading factor of buses has been considered as the most critical area requiring attention, to reduce chances of voltage failures. However, occurrence of contingencies may change individual critical loading factor (maximum loadability) of buses. Difficulty in supply of reactive power to consumers has been considered as a major cause of voltage instability in power systems. It is extremely vital to determine major reactive power sources supplying
  • 3. IJAPE ISSN: 2252-8792 Voltage Stability Based Formation of Voltage Control Areas Considering Impact … (Tarun Martolia) 117 reactive power to a group of buses. The exhaustion of reactive reserves of these sources may cause voltage instability in the group of load buses getting mainly reactive power supply from such sources [10]. This paper presents a method that allows easier determination of a group of load buses being dependent on same set of reactive power sources. Such groups of load buses have been clubbed together to form voltage control areas. Sensitivities of reactive power generations to reactive power demands have been computed to determine dependency of group of loads to group of reactive power sources. Most of the work has concentrated formation of voltage control areas at the base case operating point. Voltage control areas formed at the base case operating point are not expected to remain valid under change in network topology and operating conditions. Very limited effort seems to be made in formation of voltage control areas considering impact of change in network topology and operating conditions. In the present work, the voltage control areas formed based on reactive power sensitivities have been modified by considering bus voltage variations from the case value at different loadings under voltage stability based critical contingencies to consider impact of change in operating conditions and network topology. Voltage stability based critical contingencies have been selected based on maximum loadability criterion. Proposed approach of voltage control areas formation has been tested on IEEE 14-bus system. Voltage control areas formed by proposed method have been compared by areas formed by few existing approaches. It has been observed on the test system that areas formed by proposed approach are more effective compared to considered existing approaches, under change in network topology and operating conditions. 2. RESEARCH METHOD In this work, voltage control areas have been formed based on sensitivity of reactive power generations to reactive power demands. The sensitivity factor has been derived as per following. The reactive power balance equation at all the buses ignoring Q-δ coupling can be given by; ൤ ∆ܳீ ∆ܳ௅ ൨ = ቎ డொಸ డ௏ಽ డொಽ డ௏ಽ ቏ ሾ∆ܸ௅ሿ (1) where, ሾ∇ܳீሿ = Change in reactive power generations ሾ∇ܳ௅ሿ = Change in reactive power demands ሾ∇ܸ௅ሿ = Change in voltage magnitudes at load buses Equation (1) may be rewritten as; ሾ∆Qୋሿ=ሾSୋሿሾ∆V୐ሿ (2) and, ሾ∆Q୐ሿ=ሾS୐ሿሾ∆V୐ሿ (3) where, ሾܵீሿ = ቂ డொಸ డ௏ಽ ቃ = Sensitivity of reactive power generations to voltage magnitudes at load buses ሾܵ௅ሿ = ቂ డொಽ డ௏ಽ ቃ = Sensitivity of reactive power demands to voltage magnitudes at load buses From (2) and (3), ሾ∆Qୋሿ = ሾSሿሾ∆Q୐ሿ (4) where, ሾܵሿ = ሾSୋሿሾS୐ሿିଵ (5) Elements of matrix [S] represent sensitivity of reactive power generations to reactive power demands, and can be calculated using full Q-V Jacobian sub-matrix of Newton Raphson Load Flow. Load buses having closer sensitivities to a group of generators are expected to have similar voltage instability problem since hitting of reactive power limit of such generators will result in difficulty in meeting reactive power demands of these load buses. Therefore, load buses having closer reactive power sensitivity values have been clubbed together to form voltage control areas. However, voltage control areas so formed are not expected to remain same with change in network topology and operating conditions. Therefore, voltage control areas formed based on sensitivity of reactive power generations to reactive power demands have been modified considering voltage variations from the base case value under critical contingencies at different loading conditions. Critical contingencies have been obtained based on post-contingency saddle-node- bifurcation points (maximum loadability points). For obtaining post-contingency saddle-node-bifurcation points, real power output of generators (PG), real power demand (PD) and reactive power demand (QD) have been varied using:
  • 4. ISSN: 2252-8792 IJAPE Vol. 1, No. 3, December 2012 : 115 – 122 118 ( )0 j j PG =PG 1+λ (6) ( )0 j j PD =PD 1+λ (7) ( )0 j j QD =QD 1+λ (8) where,λ represents system loading factor common to all the buses and, 0 j PG , 0 j PD , 0 j QD are real power output of generator and real and reactive power loads at bus-j at a base operating point (λ=0.0). 3. RESULTS AND ANALYSIS The proposed method of formation of voltage control areas has been applied to IEEE 14-bus system (shown in Figure-1) [16]. IEEE 14-bus system has 5 generators with 20 transmission lines (including 2 transformers and one phase shifting transformer). Loads have been connected at 11 buses including two generator buses. The sensitivity of reactive power generations to reactive power demands were calculated using (5) at the base case operating point with the help of elements of Newton Raphson Load Flow Jacobian matrix. The sensitivity values between different generator buses and load buses have been shown in Table-1. The senstivity values shown in Table-1 represent dependency of load buses to reactive power sorces. If a group of load buses (say Group-A) has high and similar dependency on a group of reactive power sources (say Group- B), hitting of reactive power generation limit of generators in Group-B is expected to result in voltage instability at all the load buses in Group-A. Therefore, all the load buses in Group-A are expected to face similar voltage instability problem. Voltage control areas were formed clubbing load buses having closer reactive power sensitivities to generators. The voltage control areas so formed have been shown in Table-2 and Figure-1. Figure-1. VCAs for IEEE 14-bus system based on reactive power sensitivities Table 1. Sensitivity of Reactive Power Generations to Reactive Power Demands (Sij) - 14-Bus System Load bus no. Generator bus no. 1 2 3 6 8 4 -0.12038 -0.38004 -0.21604 -0.17201 -0.12044 5 -0.19713 -0.37703 -0.12872 -0.22221 -0.07176 7 -0.05366 -0.16941 -0.09630 -0.22054 -0.49275 9 -0.05211 -0.16451 -0.09352 -0.38568 -0.34688 10 -0.04380 -0.13829 -0.07861 -0.49828 -0.29159 11 -0.02265 -0.07152 -0.04066 -0.74709 -0.15080 12 -0.00335 -0.01057 -0.00601 -0.98826 -0.02228 13 -0.00809 -0.02555 -0.01452 -0.94007 -0.05386 14 -0.03442 -0.10868 -0.06178 -0.64634 -0.22916 Table 2. VCAs Formed Using Sij Values (IEEE 14-Bus System) VCA no. Buses present
  • 5. IJAPE ISSN: 2252-8792 Voltage Stability Based Formation of Voltage Control Areas Considering Impact … (Tarun Martolia) 119 1 12, 13 2 11, 14 3 9, 10 4 4, 5 5 7 Voltage control areas shown in Figure-1 and Table-2 represent areas for the intact system. The load buses within the areas so formed are expected to have similar voltage instability problem. However, voltage control areas so formed are expected to change under change in network topology and operating conditions, since the sensitivity values are expected to change under change in network topology and operating conditions. In order to consider impact of change in network topology and operating conditions, the voltage control areas formed based on reactive power sensitivities were modified based on bus voltage variations under voltage stability based critical contingencies at large number of new real and reactive power demands. Voltage stability based most severe contingencies were selected based on post-contingency saddle-node- bifurcation points (maximum loadability points) using continuation power flow based software package UWPFLOW [17]. Voltage stability based contingency ranking has been shown in Table-3. Voltage magnitude at all the load buses were calculated at the base case operating point, nose point (maximum loadability point) and some of the intermediate loading points, under critical contingencies. The change in voltage magnitude from the base case operating point value, of all the load buses, at some of the post- contingency loadings have been shown in Table-4. The voltage control areas formed using reactive power sensitivities (shown inTable-2 and Figure-1) were modified based on post-contingency voltage variations from the case operating value, under different loadings. Modified voltage control areas have been shown in Table-5 and Figure-2. Table 3. Voltage Stability Based Contingency Ranking (IEEE 14-bus System) Line outage Maximum loading factor (λmax) Contingency ranking 2-3 1.2747 1 5-6 1.3059 2 2-4 2.1463 3 6-13 2.2427 4 2-5 2.2465 5 12-13 2.2775 6 13-14 2.2799 7 1-5 2.4536 8 4-7 2.4978 9 7-9 2.7485 10 Table 4. Voltage Variations of Load Buses under Few Critical Contingencies with Increased Demands (IEEE 14-bus System) Line outage Loading factor Change in voltage magnitude (p.u.) from the base case operating point value of load buses Bus-4 Bus-5 Bus-7 Bus-9 Bus-10 Bus-11 Bus-12 Bus-13 Bus-14 2-3 1.2747* -0.193 -0.179 -0.107 -0.127 -0.111 -0.025 -0.002 -0.011 -0.109 5-6 1.3059* -0.136 -0.109 -0.143 -0.170 -0.168 -0.096 -0.016 -0.037 -0.179 2-4 2.1463* -0.284 -0.312 -0.180 -0.222 -0.200 -0.096 -0.022 -0.052 -0.205 6-13 2.2427* -0.175 -0.177 -0.186 -0.280 -0.250 -0.123 -0.233 -0.491 -0.481 2-5 1.4750 -0.084 -0.093 -0.061 -0.082 -0.075 -0.028 +0.001 -0.014 -0.085 12-13 2.2775* -0.056 -0.054 -0.183 -0.072 -0.066 -0.024 +0.017 -0.020 -0.082 13-14 2.2799* -0.161 -0.156 -0.183 -0.284 -0.256 -0.127 +0.001 -0.001 -0.500 1-5 1.4144 -0.076 -0.079 -0.056 -0.075 -0.068 -0.025 +0.002 -0.011 -0.078 4-7 1.5335 -0.074 -0.075 -0.050 -0.098 -0.091 -0.040 -0.002 -0.020 -0.100 7-9 2.7485* -0.289 -0.341 -0.119 -0.620 -0.543 -0.282 -0.067 -0.138 -0.504 * Nose point + Voltage rise - Voltage drop Table 5. VCAs Formed Based on Sij Values Together with Bus Voltages Variations under Critical Contingencies (IEEE 14-Bus System)
  • 6. ISSN: 2252-8792 IJAPE Vol. 1, No. 3, December 2012 : 115 – 122 120 VCA no. Buses present 1 12, 13 2 11 3 9, 10 4 4, 5 5 7 6 14 Figure-2. VCAs formed by proposed method (IEEE 14-bus System) The maximum change in voltage from the base case operating point (considered as A in present work) with bus number having maximum change in voltage, the minimum change in voltage from the base case operating point (considered as B in present work) with bus number having minimum change in voltage, and absolute value of difference between A and B (considered as C in present work), have been shown in Table-6 for different voltage control areas under few critical contingencies at some of the loadings. It is observed from Table-6 that voltage control areas formed by proposed approach consist of buses having very small range of voltage variations with change in network topology caused by line outages and change in operating conditions caused by change in demands. The voltage control areas formed by proposed approach were compared with the methods of voltage control areas formation suggested in Ref. [10], Ref. [13] and Ref. [15], respectively, based on lowest maximum C value between all the voltage control areas formed. Table-7 shows maximum C for different approaches under voltage stability based critical contingencies at some of the loading values. It is observed from Table-7 that voltage control areas formed by proposed approach have lowest maximum C values compared to voltage control areas formed using methods suggested in Ref. [10], Ref. [13] and Ref. [15], under critical contingencies at different loadings, for most of the cases. Therefore, VCAs formed by proposed approach remains valid under critical contingencies at different loadings. Due to lowest voltage variations compared to three existing approaches, under voltage stability based critical contingencies at a set of real and reactive power demands, the areas formed by proposed approach may be more efficient in voltage stability assessment under change in operating conditions and network topology.
  • 7. IJAPE ISSN: 2252-8792 Voltage Stability Based Formation of Voltage Control Areas Considering Impact … (Tarun Martolia) 121 4. CONCLUSION A modified method for formation of voltage control areas has been presented in this paper. Proposed method of VCAs formation first clubs load buses based on closer sensitivity of reactive power generations to reactive power demands. The VCAs so formed have been modified based on voltage variations of load buses under voltage stability based critical contingencies at a set of new loadings. Voltage stability based critical contingencies have been obtained based on maximum loadability criterion. Proposed method of VCAs formation has been tested on IEEE 14-bus system. Results obtained on the test system considered establish better suitability of VCAs formation over some of the existing approaches under change in operating conditions and network topology. Voltage control areas formed by proposed approach may be quite effective in fast voltage stability assessment and control of power system networks. Since VCAs have been formed to study voltage stability phenomenon, generator buses have not been considered for clustering in the present work. Table 6. Voltage Variations at Buses within VCAs Formed by the Proposed Approach (IEEE 14-bus System) Line outage Loading factor VCA no. Maximum and minimum change in voltage magnitude (p.u.) from the base case operating point at buses within VCAs, and absolute value of difference (p.u.) between maximum voltage change and minimum voltage change at buses within VCAs A B C 1-5 1.4144 1 +0.002 (bus-12) -0.011 (bus-13) 0.013** 2 Contain only one load bus 3 -0.075 (bus-9) -0.068 (bus-10) 0.007 4 -0.079 (bus-5) -0.076 0.003 5 Contain only one load bus 6 Contain only one load bus 2-3 1.2747* 1 -0.011 (bus-13) --0.002 (bus-12) 0.009 2 Contain only one load bus 3 -0.127 (bus-9) -0.111 (bus-10) 0.006 4 -0.192 (bus-4) -0.179 (bus-5) 0.013** 5 Contain only one load bus 6 Contain only one load bus 6-13 2.2427* 1 -0.491 (bus-13) -0.233 (bus-12) 0.258** 2 Contain only one load bus 3 -0.280 (bus-9) -0.250 (bus-10) 0.030 4 -0.177 (bus-5) -0.175 (bus-4) 0.002 5 Contain only one load bus 6 Contain only one load bus 12-13 2.2775* 1 -0.020 (bus-13) +0.017 (bus-12) 0.037** 2 Contain only one load bus 3 -0.072 (bus-9) -0.066 (bus-10) 0.006 4 -0.056 (bus-4) -0.054 (bus-5) 0.002 5 Contain only one load bus 6 Contain only one load bus * Nose point ** Maximum value of C between all the VCAs formed by the proposed method + Voltage rise - Voltage drop A = Maximum change in voltage (in p.u.) from the base case operating point value occurring at one of the bus within VCA B = Minimum change in voltage (in p.u.) from the base case operating point value occurring at one of the bus within VCA C = Absolute value of difference between A and B Table 7. Comparison of VCAs formed by different approaches Line outage Loading Factor Maximum value of C between different VCAs fomed
  • 8. ISSN: 2252-8792 IJAPE Vol. 1, No. 3, December 2012 : 115 – 122 122 VCAs formed by method suggested in Ref. [10] VCAs formed by method suggested in Ref. [13] VCAs formed by method suggested in Ref. [15] VCAs formed by proposed method 2-3 1.2747* 0.091 0.109 0.175 0.013** 5-6 1.3059* 0.191 0.143 0.143 0.021** 2-4 2.1463* 0.153 0.183 0.231 0.030** 6-13 2.2427* 0.110** 0.257 0.313 0.257 2-5 1.4750 0.071 0.085 0.008** 0.014 12-13 1.4862 0.062 0.062 0.062 0.037** 13-14 2.2799* 0.499 0.499 0.340 0.028** 1-5 1.4144 0.068 0.078 0.067 0.013** 4-7 1.5335 0.079 0.099 0.077 0.020** 7-9 2.7485* 0.365 0.501 0.501 0.077** REFERENCE [1] C. P. Steinmetz, “Power control and stability of electric generating stations”, AIEE Trans., Vol. XXXIX, Part II, pp. 1215-1287, July 1920. [2] AIEE Subcommittee on Interconnections and Stability Factors, “First report of power system stability”, AIEE Trans., pp. 51-80, 1926. [3] IEEE / CIGRE Joint Task Force on Stability Terms and Definitions, “Definition and classification of power system stability”, IEEE Trans. on Power Systems, Vol. 19, No. 3, pp. 1387-1401, August 2004. [4] IEEE System Dynamic Perfomance Subcommittee, “Voltage stability of power systems: Concepts, analytical tools and industrial experience”, IEEE document 90TH0358-2-PWR-1990. [5] C. W. Taylor, “Power system voltage stability”, Mc Graw Hill, New York, 1994. [6] P. Kundur, “Power system stability and control”, Mc Graw Hill, New York, 1994. [7] N. Mithulananthan and S. C. Srivastava, “Investigation of a voltage collapse incident in Sri Lanka’s power system network”, Proc. of the EMPD’98, Singapore, IEEE Catalogue No. 98EX137, pp. 47-52, March 3-5, 1998. [8] R. A. Schlueter, I. Hu , M. W. Chang, J. C. Lo, and A. Costi, “Methods for determining proximity to voltage collapse,” IEEE Transactions on Power System, Vol. 6, No. 1, pp. 285–292, February 1991. [9] Lie, T., Schlueter, R.A., Rusche, P.A., and Rhoades, R., “Method of identifying weak transmission network stability boundaries”, IEEE Transactions on Power Systems, Vol. 8, No. 1, pp. 293-301, February 1993. [10] R. A. Schlueter, “A voltage stability security assessment method,” IEEE Transactions on Power Systems, 1998, Vol. 13, No. 4, pp. 1423–1438, November 1998. [11] H. Liu, A. Bose and V. Venkatasubramanian, “A fast voltage security assessment method using adaptive bounding,” IEEE Transactions on Power Systems, Vol. 15, No. 3, pp. 1137–1141, August 2000. [12] C. A. Aumuller and T. K. Saha, “Determination of power system coherent bus groups by novel sensitivity-based method for voltage stability assessment,” IEEE Transactions on Power Systems, Vol. 18, No. 3, pp. 1157–1164, August 2003. [13] M. K. Verma and S. C. Srivastava, “Approach to determine voltage control areas considering impact of contingencies”, IEE Proceedings, Part-C, Generation, Transmission and Distribution, Vol. 152, No. 3, pp. 342-350, May 2005. [14] K. Morison, X. Wang, A. Moshref, A. Edris, “Identification of voltage control areas and reactive power reserve; An advancement in on-line voltage security assessment,” IEEE PES General meeting - Conversion and Delivery of Electrical Energy in the 21st Century, Pittsburg (Canada), pp. 1 – 7, July 20-24, 2008. [15] M. K. Verma, Dushyant Juneja, Manish Prasad, “An Approach for Formation of Voltage Control Areas based on Voltage Stability Criterion”, 16th NATIONAL POWER SYSTEMS CONFERENCE, 15th-17th DECEMBER, 2010. [16] “Power systems test case archieve” available at http://www.ee.washington.edu/research/pstca/pf14/pg_tca14bus.htm [17] Software Package UWPFLOW available at http://www.power.uwaterloo.ca/~claudio/software/pflow.html.