1. Applications & Tools
Answers for industry.
Cover
Communication between
SIMATIC S7-300 and Modicon M340 PLC
Modbus TCP Connection
Application Description January 2010
2. 2 Modbus TCP Connection
V 1.0, Entry ID: 38586568
CopyrightSiemensAG2009Allrightsreserved
Industry Automation and Drives Technologies Service & Support Portal
This article is taken from the Service Portal of Siemens AG, Industry Automation
and Drives Technologies. The following link takes you directly to the download
page of this document.
http://support.automation.siemens.com/WW/view/en/38586568
If you have any questions concerning this document please e-mail us to the
following address:
online-support.automation@siemens.com
3. Modbus TCP Connection
V 1.0, Entry ID: 38586568 3
CopyrightSiemensAG2009Allrightsreserved
SIMATIC
Modbus TCP Connection
Automation Task 1
Automation Solution 2
Basics 3
Function Mechanisms of
this Application 4
Installation 5
Startup of the Application 6
Operation of the
Application 7
Related Literature 8
History 9
4. Warranty and Liability
4 Modbus TCP Connection
V 1.0, Entry ID: 38586568
CopyrightSiemensAG2009Allrightsreserved
Warranty and Liability
Note The Application Examples are not binding and do not claim to be complete
regarding the circuits shown, equipping and any eventuality. The Application
Examples do not represent customer-specific solutions. They are only intended
to provide support for typical applications. You are responsible for ensuring that
the described products are used correctly. These application examples do not
relieve you of the responsibility to use safe practices in application, installation,
operation and maintenance. When using these Application Examples, you
recognize that we cannot be made liable for any damage/claims beyond the
liability clause described. We reserve the right to make changes to these
Application Examples at any time without prior notice.
If there are any deviations between the recommendations provided in these
application examples and other Siemens publications – e.g. Catalogs – the
contents of the other documents have priority.
We do not accept any liability for the information contained in this document.
Any claims against us – based on whatever legal reason – resulting from the use of
the examples, information, programs, engineering and performance data etc.,
described in this Application Example shall be excluded. Such an exclusion shall
not apply in the case of mandatory liability, e.g. under the German Product Liability
Act (“Produkthaftungsgesetz”), in case of intent, gross negligence, or injury of life,
body or health, guarantee for the quality of a product, fraudulent concealment of a
deficiency or breach of a condition which goes to the root of the contract
(“wesentliche Vertragspflichten”). The damages for a breach of a substantial
contractual obligation are, however, limited to the foreseeable damage, typical for
the type of contract, except in the event of intent or gross negligence or injury to
life, body or health. The above provisions do not imply a change of the burden of
proof to your detriment.
Any form of duplication or distribution of these Application Examples or excerpts
hereof is prohibited without the expressed consent of Siemens Industry Sector.
5. Table of Contents
Modbus TCP Connection
V 1.0, Entry ID: 38586568 5
CopyrightSiemensAG2009Allrightsreserved
Table of Contents
Warranty and Liability ................................................................................................. 4
1 Automation Task .................................................................................. 7
2 Automation Solution ............................................................................. 8
2.1 Overview of overall solution ................................................................. 8
2.2 Description of the core functionality ................................................... 10
2.3 Hardware and software components used......................................... 14
3 Basics................................................................................................. 16
3.1 Basics on Modbus TCP...................................................................... 16
3.2 S7 function blocks for Modbus TCP................................................... 20
4 Function Mechanisms of this Application........................................... 23
4.1 Program structure of S7 CPU and ET200S CPU with integrated
PN interface........................................................................................ 24
4.1.1 Program details on Modbus PN blocks.............................................. 24
4.1.2 Configuration explanations................................................................. 31
4.2 Program structure of S7 CPU with CP............................................... 32
4.2.1 Program details on MODBUS CP blocks........................................... 32
4.2.2 Configuration explanations................................................................. 40
4.3 Program structure of Modicon M340.................................................. 40
4.3.1 Program details on Modicon M340 blocks ......................................... 41
4.3.2 Configuration explanations................................................................. 41
5 Installation .......................................................................................... 42
5.1 Installation of the hardware................................................................ 42
6 Startup of the Application ................................................................... 45
6.1 Configuration of CPU319-3 PN/DP.................................................... 45
6.1.1 Hardware configuration ...................................................................... 45
6.1.2 Insert Modbus TCP blocks into project .............................................. 47
6.1.3 Configuring Modbus TCP connections............................................... 47
6.1.4 Project download................................................................................ 50
6.2 Configuration of IM151-8 PN/DP CPU............................................... 51
6.2.1 Hardware configuration ...................................................................... 51
6.3 Configuring the CPU315-2 PN/DP with CP343-1 Lean ..................... 53
6.3.1 Hardware configuration ...................................................................... 53
6.3.2 Creating a project for Modbus TCP.................................................... 56
6.3.3 Configuring Modbus TCP connections............................................... 57
6.3.4 Downloading project........................................................................... 59
6.4 Configuration of Modicon M340 ......................................................... 60
6.4.1 Using application example ................................................................. 60
6.4.2 Hardware configuration ...................................................................... 62
6.4.3 Configuring an Ethernet interface for Modbus TCP........................... 64
6.4.4 Creating a project for Modbus TCP.................................................... 66
7 Operation of the Application............................................................... 68
7.1 Operation of CPU319-3 PN/DP and IM151-8 PN/DP CPU................ 68
7.1.1 S7 station is client .............................................................................. 68
7.1.2 S7 station is server............................................................................. 71
7.2 71
7.3 Operation of CPU315-2 PN/DP + CP343-1 Lean .............................. 72
7.3.1 S7 station is client .............................................................................. 72
7.3.2 S7 station is server............................................................................. 74
7.4 Operation of Modicon M340............................................................... 76
7.4.1 Modicon M340 as client...................................................................... 76
7.4.2 Modicon M340 as server.................................................................... 77
8 Related Literature............................................................................... 79
6. Table of Contents
6 Modbus TCP Connection
V 1.0, Entry ID: 38586568
CopyrightSiemensAG2009Allrightsreserved
8.1 Bibliography........................................................................................ 79
8.2 Internet Links...................................................................................... 79
9 History ................................................................................................ 79
7. Automation Task
Overview of overall solution
Modbus TCP Connection
V 1.0, Entry ID: 38586568 7
CopyrightSiemensAG2009Allrightsreserved
1 Automation Task
Introduction
Protocols are necessary to exchange data between communication partners. One
of these protocols which is mainly used in the industrial environment, is Modbus
TCP. The specification of this protocol is open and can therefore be used by
anyone. Thus, there is a multitude of components from different manufacturers with
Modbus TCP interface.
To enable a simple and fast connection to such third-party devices they also have
to support Modbus TCP.
Overview of the automation task
The figure below provides an overview of the automation task.
Figure 1-1
S7 Controller External controller
Ethernet
Production plant 1 Production plant 2
Description of the automation task
There are two production plants in a product line which carry out intermediate and
final assembly of a serial production. Between those two manufacturing plants
production data is to be exchanged. One of the two plants is equipped with a
controller of a third-party manufacturer. For the communication with other
components this external controller offers a Modbus TCP interface. Data exchange
is to be realized via this interface.
The controllers of the two production plants and the panel are located in the same
IP subnet. Therefore a gateway is not needed.
Quantity frameworks of the data transmission
In the application example the volume of data which is transferred via Modbus TCP
is limited to 64 Bit. The transfer is word by word. I.e., per client job four words are
read from the server or are written into the server.
The table below shows the maximum possible data transfer per Modbus TCP job.
Table 1-1 : Maximum data volume per job
Transfer bit-by-bit Transfer word-by-word
Read job 250 Byte 250 Byte
Write job 100 Byte 200 Byte
8. Automation Solution
Overview of overall solution
8 Modbus TCP Connection
V 1.0, Entry ID: 38586568
CopyrightSiemensAG2009Allrightsreserved
2 Automation Solution
2.1 Overview of overall solution
There are several possibilities to link an external controller via Modbus TCP to a
SIMATIC system because there are different peers on the SIMATIC side which
support this protocol, using different function blocks for Modbus TCP. Below, on
the example of three different SIMATIC components it is shown how a link to an
external controller is realized via Modbus TCP.
Schematic layout
The figures below display the components of three different solution alternatives:
Figure 2-1 :Connection Modicon M340 with S7-CPUs
SIMATIC solution External
controller
SIMATIC S7 CPU
Production plant 1
Modicon M340Ethernet
Production plant 2
SCALANCE
X108
Modbus TCP
ET200S
IM151-8 PN/DP CPU
CPU319-3 PN/DP
CPU315-2DP
CP343-1 Lean
IP address:
192.168.1.1
IP address:
192.168.1.10
9. Automation Solution
Overview of overall solution
Modbus TCP Connection
V 1.0, Entry ID: 38586568 9
CopyrightSiemensAG2009Allrightsreserved
Design of the SIMATIC system
In each solution alternative the SIMATIC components are physically connected via
an industrial Ethernet cable. SCALANCE X108 enables the connection of the
PG/PC and the SIMATIC station, and the connection to the external system. Via
the physical connection, production data is exchanged with an external system,
using Modbus TCP. The PG/PC will be used to start the send and receive jobs.
The following SIMATIC stations are available:
CPU319-3 PN/DP
ET200S (IM151-8 PN/DP)
CPU315-2 PN/DP with CP 343-1 Lean
Design of the external system
The external system is a Modicon M340 controller. Via an industrial Ethernet cable
it is physically linked with the SCALANCE X108.
Topics not covered by this application
This application does not
contain an introduction to STEP7
contain an introduction to Unity Pro XL
contain an introduction to WinCC flexible
Basic knowledge of these topics is assumed.
Scope of the application example
This application example will describe:
basics on Modbus TCP
configuration and structure of a Modbus TCP connection between a CPU319-3
PN/DP and a Modicon M340, as well as data transmission via Modbus TCP
between the two peers (variant 1: Modicon M340 acts as client, CPU319-3
PN/DP acts as server; variant 2: Modicon M340 acts as server, CPU319-3
PN/DP acts as client)
configuration and structure of a Modbus TCP connection between an ET200S
(IM151-8 PN/DP) and a Modicon M340, as well as data transmission via
Modbus TCP between the two peers (variant 1: Modicon M340 acts as client,
ET200S acts as server; variant 2: Modicon M340 acts as server, ET200S acts
as client)
configuration and structure of a Modbus TCP connection between a CPU315-2
PN/DP with CP343-1 Lean and a Modicon M340, as well as data transmission
via Modbus TCP between the two peers (variant 1: Modicon M340 acts as
client, CPU315-2 PN/DP with CP acts as server; variant 2: Modicon M340 acts
as server, CPU315-2 PN/DP with CP acts as client)
handling of Modbus TCP Wizard
10. Automation Solution
Description of the core functionality
10 Modbus TCP Connection
V 1.0, Entry ID: 38586568
CopyrightSiemensAG2009Allrightsreserved
2.2 Description of the core functionality
Sequence of the core functionality
A Modbus TCP communication between a SIMATIC controller and a Modicon
M340 is created to exchange data between the two nodes afterwards. There are
different hardware solutions on the SIMATIC side that need different software
solutions for Modbus TCP. The SIMATIC station and Modicon M340 are alternately
client or server. I.e. when the SIMATIC station acts as server the Modicon M340
station is the client and visa versa.
The figures below show the solution variants of this application example.
Connection Modicon M340 CPU319-3 PN/DP
Figure 2-2: CPU319-3 PN/DP as Modbus TCP client; Modicon M340 as Modbus TCP server
CPU319-3 PN/DP Modicon M340
Ethernet
Scalance X108
IP address:
192.168.1.1
IP address:
192.168.1.10
Client: Modbus TCP Server: Modbus TCP
Protocoll: Modbus TCP
Figure 2-3: CPU319-3 PN/DP as Modbus TCP server; Modicon M340 as Modbus TCP client
CPU319-3 PN/DP Modicon M340
Ethernet
Scalance X108
IP address:
192.168.1.1
IP address:
192.168.1.10
Server: Modbus TCP Client: Modbus TCP
Protocol: Modbus TCP
11. Automation Solution
Description of the core functionality
Modbus TCP Connection
V 1.0, Entry ID: 38586568 11
CopyrightSiemensAG2009Allrightsreserved
Connection Modicon M340 CPU315-2 PN/DP + CP343-1 Lean
Figure 2-4: CPU315-2 PN/DP + CP343-1 Lean as Modbus TCP client; Modicon M340 as
Modbus TCP server
CPU315-2 PN/DP with
CP 343-1 Lean Modicon M340
Ethernet
Scalance X108
IP address:
192.168.1.1
IP address:
192.168.1.10
Client: Modbus TCP Server: Modbus TCP
Protocol: Modbus TCP
Figure 2-5: CPU315-2 PN/DP + CP343-1 Lean as Modbus TCP server; Modicon M340 as
Modbus TCP client
CPU315-2 PN/DP with
CP343-1 Lean Modicon M340
Ethernet
Scalance X108
IP address:
192.168.1.1
IP address:
192.168.1.10
Server: Modbus TCP Client: Modbus TCP
Protocol: Modbus TCP
12. Automation Solution
Description of the core functionality
12 Modbus TCP Connection
V 1.0, Entry ID: 38586568
CopyrightSiemensAG2009Allrightsreserved
Connection Modicon M340 IM151-8 PN/DP CPU
Figure 2-6: IM151-8 PN/DP CPU as Modbus TCP client; Modicon M340 as Modbus TCP
server
IM151-8 PN/DP CPU Modicon M340
Ethernet
Scalance X108
IP address:
192.168.1.1
IP address:
192.168.1.10
Client: Modbus TCP Server: Modbus TCP
Protocol: Modbus TCP
Figure 2-7: IM151-8 PN/DP CPU as Modbus TCP server; Modicon M340 as Modbus TCP
client
IM151-8 PN/DP CPU Modicon M340
Ethernet
Scalance X108
IP address:
192.168.1.1
IP address:
192.168.1.10
Server: Modbus TCP Client: Modbus TCP
Protocol: Modbus TCP
Advantages of this solution
The solution introduced here offers the following advantages:
option to connect Modbus TCP-capable external controllers
extensibility of existing systems with SIMATIC S7 modules
few changes necessary in SIMATIC component when exchanging a Modbus
TCP peer
option to select client or server functionality
13. Automation Solution
Description of the core functionality
Modbus TCP Connection
V 1.0, Entry ID: 38586568 13
CopyrightSiemensAG2009Allrightsreserved
Typical fields of application
The devices displayed here are typical Modbus TCP Siemens peers.
Table 2-1
Machine or branch Task Figure
Multi function measuring
instrument Sentron
PAC3200
U,I,R,f measurement
e.g. TP177B,
MP 277 8“,
MP 377 12" Touch
Visualization
Other Modbus TCP components by third-party manufacturers:
Modicon M340 by Schneider Electric
Modbus/TCP (UDP) bus link by Phoenix Contact
TwinCAT Modbus TCP server by Beckhoff
14. Automation Solution
Hardware and software components used
14 Modbus TCP Connection
V 1.0, Entry ID: 38586568
CopyrightSiemensAG2009Allrightsreserved
2.3 Hardware and software components used
The application was generated with the following components:
Hardware components
Table 2-2
Component No. MLFB / order number Note
CPU319-3 PN/DP 1 6ES7318-3EL00-0AB0
IM 151-8 PN/DP CPU 1 6ES7151-8AB00-0AB0
CPU315-2 PN/DP 1 6ES7315-2EG10-0AB0
CP343-1 Lean 1 6GK7343-1CX10-0XE0
SCALANCE X108 1 6GK5108-0AB00-2AA3
PS307 24 V/5 A 1 6ES7307-1EA00-0AA0
Modicon M340
CPS2010
1
P34 2030 1 Modicon M340
communication module
DDO 1602 1 Modicon M340 digital
output module
DDI 1602 1 Modicon M340 digital input
module
Standard software components
Table 2-3
Component No. MLFB / order number Note
SIMATIC Manager
V5.4+SP4
1 56ES7810-4CC08-0YA5 Configuration software for
S7 CPUs
UnityProXL 1 Configuration software for
Modicon M340
Modbus TCP Wizard 1 Program for configuring the
Modbus TCP
communication via PN -
CPUs
Function blocks for
Modbus TCP via PN
CPU
1 2XV9 450-1MB02 These function blocks are
not suitable for Modbus
TCP via CP
Function blocks for
Modbus TCP via CP
1 2XV9 450-1MB00 These function blocks are
not suitable for Modbus
TCP via PN CPU
15. Automation Solution
Hardware and software components used
Modbus TCP Connection
V 1.0, Entry ID: 38586568 15
CopyrightSiemensAG2009Allrightsreserved
Sample files and projects
The list below includes all files and projects used in this example. All program
samples include not licensed Modbus TCP blocks. You get a valid license on the
homepage of S7 OpenModbus/TCP (see 6).
Table 2-4
Component Note
38586568_Modbus_TCP_Kopplung_CODE_v11_de.zip
38586568_Modbus_TCP_Kopplung_Doku_v11_de.pdf
16. Basics
Basics on Modbus TCP
16 Modbus TCP Connection
V 1.0, Entry ID: 38586568
CopyrightSiemensAG2009Allrightsreserved
3 Basics
3.1 Basics on Modbus TCP
Modbus TCP is a client/server communication that uses the TCP/IP as
transmission medium. In this architecture the client establishes a connection and
sends request frames to the server. The server processes this request and sends
the appropriate answer to the request back to the client. Depending on the job,
data is either read from the memory area of the server or written into it. To be able
to distinguish the type of jobs and the memory areas, there are clearly defined
function codes for Modbus TCP. They are sent to the server by the client in the
request frame, including the address of the memory area, the so called register
address.
Frame structure
A Modbus frame consists of PDU (Protocol Data Unit) and ADU (Application Data
Unit). In the PDU, function code and data belonging to the function are transmitted.
ADU is for addressing and error detection. Whilst the PDU is identical for all
Modbus variants (Modbus TCP, Modbus RTU, etc.) there are some differences for
ADU. Addressing and error detection for Modbus TCP, for example, is undertaken
by the subordinate TCP protocol. At the same time the TCP protocol is responsible
for the integrity check of the data packets and if necessary also for troubleshooting.
The information for addressing and error detection is transferred in the "MBAP
Header" (Modbus Application Header).
Figure 3-11: Modbus standard frame
Figure 3-12: Modbus TCP frame
MBAP Header Function code Data
MODBUS TCP/IP ADU
PDU
Additional address Function code Data Error code
ADU
PDU
17. Basics
Basics on Modbus TCP
Modbus TCP Connection
V 1.0, Entry ID: 38586568 17
CopyrightSiemensAG2009Allrightsreserved
Modbus register and memory areas
Modbus is based on a series of memory areas with various characteristics. The
addresses within this memory area are called register. Depending on the Modbus
memory area these registers are either word- or bit-oriented. The table below
displays all memory areas a Modbus component may contain.
Table 3-6
Memory area Register size Access Note
Inputs 1 bit read can be changed by I/O
system
Coils
(outputs)
1 bit read and write can be changed by user
program
Input register
(input data)
16 bit word read can be changed by I/O
system
Holding register
(output data)
16 bit word read and write can be changed by user
program
Functions codes
In the Modbus frame, the function code defines whether it is a read or write job and
which memory area is to be accessed.
Precise addressing in the memory areas is via a register number and the number
of registers to be processed. This information is also contained in the Modbus
frame. The table below displays the function codes supported by S7 Modbus TCP.
All S7 MODBUS variants (PN-CPUs and TCP-CPs) support function codes 1, 2, 3,
4, 5, 6, 15 and 16.
Table 3-7
Function
code
Function Memory area
01 reads several bits Coils (outputs)
02 reads several bits Inputs
03 reads any number of
registers
Holding register
(output data)
04 reads any number of
registers
Input register (input
data)
05 writes individual bits Coils (outputs)
06 writes individual
register
Holding register
(output data)
15 writes several bits Coils (outputs)
16 writes more than one
register
Holding register
(output data)
18. Basics
Basics on Modbus TCP
18 Modbus TCP Connection
V 1.0, Entry ID: 38586568
CopyrightSiemensAG2009Allrightsreserved
Display of address
Modbus addresses can vary from the internal address of a Modbus component.
For this reason it is necessary to have information on the display of address. I.e. it
has to be known which Modbus address displays an internal address of a Modbus
component.
This is now explained using a simple example. This example shows the address
display between a Siemens and a Modicon controller during data exchange via a
holding register.
The Modbus register addresses are displayed in black. The internal addresses of
the controllers are diplayed in gray.
Figure 3-13:
SIMATIC Controller
DB 11
0
1
…
122
123
…
252
253
254
…
498
499
0.0
2.0
…
244.0
246.0
…
504.0
506.0
508.0
…
996.0
998.0
Modicon Controller
Holding Register
0
1
…
122
123
…
252
253
254
…
498
499
%MW 0
%MW 1
…
%MW 122
%MW 123
…
%MW 252
%MW 253
%MW 254
…
%MW 498
%MW 499
Modbus register address
Internal memory area
Another example shows the address display between a Siemens and a Modicon
controller during data exchange via coils.
19. Basics
Basics on Modbus TCP
Modbus TCP Connection
V 1.0, Entry ID: 38586568 19
CopyrightSiemensAG2009Allrightsreserved
The Modbus bit addresses are displayed in black. The internal addresses of the
controllers are displayed in gray.
Figure 3-14:
SIMATIC Controller
DB 11
0
1
…
8
9
…
16
17
18
…
32
33
0.0
0.1
…
1.0
1.1
…
2.0
2.1
2.2
…
4.0
4.1
Modicon Controller
Coils
0
1
…
8
9
…
16
17
18
…
32
33
%M 0
%M 1
…
%M 8
%M 9
…
%M 16
%M 17
%M 18
…
%M 32
%M 33
Modbus bit address
Internal memory address
Configuring the Modbus addresses
When configuring the Modbus register addresses, attention has to be paid that
there is no overlap on the SIMATIC side in the data areas.
I.e. if there are, for example, two holding registers, one each configured in DB11
and DB12, no Modbus register addresses may be assigned twice.
The figure below shows the example of two DBs as holding register with clear
Modbus register addresses. Configuration is via the Modbus parameter DB
(MODBUS_PARAM) or the OB100.
20. Basics
S7 function blocks for Modbus TCP
20 Modbus TCP Connection
V 1.0, Entry ID: 38586568
CopyrightSiemensAG2009Allrightsreserved
Figure 3-15: Realization of address display by configuring the S7 Modbus TCP blocks
(parameters are displayed in simplified form)
Modbus TCP Parameter
11
160
660
12
20
100
0
0
0
0
DB 1
Start
End
DB 2
Start
End
DB 3
Start
End
Variable Value
DB 11
160
161
…
282
283
…
412
413
414
…
659
660
0.0
2.0
…
244.0
246.0
…
504.0
506.0
508.0
…
998.0
1000.0
DB 12
20
21
…
42
43
…
72
73
74
…
99
100
0.0
2.0
…
44.0
46.0
…
104.0
106.0
108.0
…
158.0
160.0
Data_type
Data_type
Data_type
3
3
3.2 S7 function blocks for Modbus TCP
There are several solutions for a S7 controller to communicate with an external
system which supports the Modbus TCP protocol. Each of these solutions is a
software product which differs depending on the existing Ethernet interface. For a
Modbus TCP communication via a CP (Communication Processor) a different
software product is necessary than for the Modbus TCP communication via the
integrated PN interface of a S7-CPU. This is due to the different internal data
processing between the interface used and the user program in the S7 CPU.
Each of these software solutions is basically a user program for a S7 CPU. This
user program consists of different function blocks and data blocks which can simply
be implemented in an existing S7 project.
The Modbus TCP Wizard is available for the configuration of a Modbus TCP
communication via integrated PN interface of a S7 CPU. The Modbus TCP
communication via a CP has to be configured manually.
Assigning a Modbus register address to an internal address of a SIMATIC CPU
data block depends on the respective configuration of the Modbus TCP function
blocks (MODBUS_PARAM or OB100).
21. Basics
S7 function blocks for Modbus TCP
Modbus TCP Connection
V 1.0, Entry ID: 38586568 21
CopyrightSiemensAG2009Allrightsreserved
Modbus TCP via CP
If an existing S7 CPU does not have an integrated PN interface, then it can be
connected to an existing Ethernet network using a CP.
Whilst the CP and the CPU, which are linked via a backplane bus, are exchanging
data with each other, the CP simultaneously handles communication to the other
Ethernet nodes.
For this hardware variant the Modbus TCP solution "S7 Open Modbus TCP via
CP343-1 and CP443-1" is available. This Modbus solution enables Modbus TCP
communication for S7-300 and S7-400 CPUs in combination with a CP.
The following hardware and software requirements are necessary for the use of the
Modbus TCP CP solution. There are no firmware restrictions.
Table 3-1
Hardware MLFB Firmware
CP343-1 6GK7 343-1CX00-0XE0
6GK7 343-1CX10-0XE0
6GK7 343-1EX11-0XE0
6GK7 343-1EX20-0XE0
6GK7 343-1EX21-0XE0
6GK7 343-1EX30-0XE0
6GK7 343-1GX11-0XE0
6GK7 343-1GX20-0XE0
6GK7 343-1GX21-0XE0
6GK7 343-1GX30-0XE0
CP443-1 6GK7 443-1EX11-0XE0
6GK7 443-1EX20-0XE0
6GK7 443-1EX40-0XE0
6GK7 443-1EX41-0XE0
6GK7 443-1GX11-0XE0
6GK7 443-1GX20-0XE0
Table 3-2
Software MLFB Version
SIMATIC Manager 6ES7810-4CC07-0YA5 as of version 5.3
22. Basics
S7 function blocks for Modbus TCP
22 Modbus TCP Connection
V 1.0, Entry ID: 38586568
CopyrightSiemensAG2009Allrightsreserved
Modbus TCP via integrated interface of a CPU
If the integrated interface of the S7-CPU is to be used instead of the CP, another
Modbus TCP solution is necessary, as already mentioned earlier. "S7 Open
Modbus TCP PN" enables the Modbus TCP communication via the integrated PN
interface for all S7-CPUs and ET200S-CPUs.
The following hardware and software requirements are necessary for the use of the
Modbus TCP PN solution.
Table 3-3
Hardware MLFB Firmware
CPU315-2 PN/DP 6ES7 315-2EH13-0AB0 V2.6.7
6ES7 315-2EG10-0AB0 V2.3.4
CPU317-2 PN/DP 6ES7317-2EJ10-0AB0 V2.3.4
6ES7317-2EK13-0AB0 V2.6.7
CPU319-3 PN/DP 6ES7319-3EL00-0AB0 V2.7.2
CPU414-3 PN/DP 6ES7414-3EM05-0AB0 V5.2
CPU416-3 PN/DP 6ES7416-3FR05-0AB0 V5.2
IM151-8 PN/DP 6ES7151-8AB00-0AB0 V2.7.1
Table 3-4
Software MLFB Version
SIMATIC Manager 56ES7810-4CC08-0YA5 as of version 5.4 SP4
23. Function Mechanisms of this Application
S7 function blocks for Modbus TCP
Modbus TCP Connection
V 1.0, Entry ID: 38586568 23
CopyrightSiemensAG2009Allrightsreserved
4 Function Mechanisms of this Application
This chapter shows the program structures of the S7 Modbus solution and the
Modicon M340.
The Modicon M340 controller can be used as Modbus server without additional
functions in the user program at any time. As soon as a Modbus request is
received, it is processed and immediately answered. A Modbus server usually
expects such a request on port 502. Several requests from different clients can
also be processed on this port.
If the Modicon M340 controller is to be used as client, different function calls are
necessary in the user program depending on the type of the job to be sent. Here, it
has to be distinguished whether it is a read or a write job.
When a SIMATIC S7 CPU is either Modbus server or Modbus client, all the
corresponding functions or function blocks have to be called in the user program. In
the process, a further call of the Modbus function block with individual instance and
the respective connection parameters is necessary for each Modbus connection.
As opposed to the M340 CPU the S7 Modbus server can only process one client
request per port. Therefore it is necessary that an extra server is to be configured
with another port for each extra client which is supposed to be connected
simultaneously with station S7 via Modbus TCP.
24. Function Mechanisms of this Application
Program structure of S7 CPU and ET200S CPU with integrated PN interface
24 Modbus TCP Connection
V 1.0, Entry ID: 38586568
CopyrightSiemensAG2009Allrightsreserved
4.1 Program structure of S7 CPU and ET200S CPU with
integrated PN interface
To be able to create one or several Modbus connections with a S7 CPU or an
ET200S CPU with integrated PN interface it is necessary to configure the calls of
the Modbus library blocks correctly. Doing this, a certain program structure has to
be met. This program structure is displayed for two connections in the figure below.
However, the application example only contains one Modbus TCP connection
since the connection to the touch panel is realized via a S7 communication.
Figure 4-1
FB 102
"MODBUSPN"
OB1
FB 65
"TCON"
Library blocks for
Modbus PN
FB 102
"MODBUSPN"
FB 66
"TDISCON"
FB 63
"TSEND"
FB 64
"TRECV"
FB 103
"TCP_COMM"
DB 11
"Data_Area_1"
DB
…
FB
…
IDB 2
IDB 1
OB100
OB121
Modbus-
parameter 1
Connection
parameter 1
MODBUS_PARAM
Send
data 1
Receive
data 1
Receive
data 2
Sende
data 2
Modbus
parameter 2
Connection
parameter 2
4.1.1 Program details on Modbus PN blocks
The Modbus PN blocks have a Modbus DB parameter (Modbus_Param). Each
Modbus connection is configured in this DB parameter and the Modbus register
addresses as well as the respective memory areas are assigned in S7 (e.g. DB11
"Data_Area_1"). The corresponding send and receive data of each connection is
also stored in this DB parameter.
To configure the DB parameter the Modbus TCP Wizard can be used or a direct
value input in DB.
A separate call of the "MODBUSPN" function block with individual DB instance is
necessary for each client or server connection. Please note that the call of the
"MODBUSPN" function block has to take place in OB1, OB100 and in OB121 with
the same DB instance per connection.
25. Function Mechanisms of this Application
Program structure of S7 CPU and ET200S CPU with integrated PN interface
Modbus TCP Connection
V 1.0, Entry ID: 38586568 25
CopyrightSiemensAG2009Allrightsreserved
Modbus PN library blocks
The figure below displays all S7 program blocks which are needed for Modbus
TCP via the integrated PN interface of a S7-CPU. They can be inserted and
configured in any project from the examples for Modbus TCP for PN CPUs or
directly from the Modbus TCP library for PN CPUs.
To be able to use Modbus TCP for PN CPUs in a program it is only necessary to
call the "MODBUSPN" function block. The call of the other blocks is internally in the
"MODBUSPN" function block.
Figure 4-17: Modbus TCP PN blocks from the sample program
OB1 call
In OB1 the cyclical calls of the "MODBUSPN" function block are made as well as of
other user specific functions and function blocks. This is where runtime parameters
are transferred to the "MODBUSPN" function block.
OB100 call
In OB100 the "MODBUSPN" function block is initialized. OB100 is completed once
when there is a STOP RUN transfer or when restarting the CPU in case of a
power failure.
26. Function Mechanisms of this Application
Program structure of S7 CPU and ET200S CPU with integrated PN interface
26 Modbus TCP Connection
V 1.0, Entry ID: 38586568
CopyrightSiemensAG2009Allrightsreserved
OB121 call
In this OB the "MODBUSPN" function block also has to be called.
The OB121 makes an entry in the diagnostic buffer when there is no valid licence.
Additionally, without a valid licence the SF (system error) error LED of the CPU will
flash. If OB121 was not configured the CPU will go to stop mode after start-up.
Structure of Modbus DB parameter
In the Modbus DB parameter the Modbus parameters, the send and receive data
buffer and the connection parameters for the TCP/IP connection are stored. These
four areas of the DB parameter can be seen in the table below.
For each Modbus connection all four areas each have to be created in the DB
parameter.
Table 4-1
Address Comment
+0.0 Start of structure for connection 1
+0.0 Connection parameters
+64.0 Modbus parameters
+130.0 Internal send buffer
+390.0 Internal receive buffer
+650.0 End of structure for connection 1
+650.0 Start of structure for connection 2
+650.0 Connection parameters
+714.0 Modbus parameters
+780.0 Internal send buffer
+1040.0 Internal receive buffer
+1300.0 End of structure for connection 2
…
(i-1)*650 Start of structure for connection i
Connection parameters
Modbus parameters
Internal send buffer
Internal receive buffer
i*650 End of structure for connection i
27. Function Mechanisms of this Application
Program structure of S7 CPU and ET200S CPU with integrated PN interface
Modbus TCP Connection
V 1.0, Entry ID: 38586568 27
CopyrightSiemensAG2009Allrightsreserved
Parameters of "MODBUSPN" function block
The figure below shows all input and output parameters of the "MODBUSPN"
function block.
Figure 4-18
Table 4-2
Parameters Decl. Type Description Value range Initial-
ization
ID IN WORD Connection ID has to be
identical with corresponding
id parameter in DB parameter
MODBUS-PARAM
1 to 4095
W#16#1 to
W#16#FFF
yes
DB_PARAM IN BLOCK_
DB
Number of DB parameter
MODBUS_PARAM
CPU
dependent
yes
RECV_TIME IN TIME Monitoring time for the receipt
of data from peer
The minimum time that can
be set is 100ms
T#100ms to
T#+24d20h3
1m23s647ms
no
CONN_TIME IN TIME Monitoring time for setting or
clearing connection
The minimum time that can
be set is 100ms
T#100ms to
T#+24d20h3
1m23s647ms
no
KEEP_ALIVE IN TIME not used
ENQ_ENR IN BOOL S7 is client:
trigger job at positive edge
TRUE
FASLE
no
28. Function Mechanisms of this Application
Program structure of S7 CPU and ET200S CPU with integrated PN interface
28 Modbus TCP Connection
V 1.0, Entry ID: 38586568
CopyrightSiemensAG2009Allrightsreserved
Parameters Decl. Type Description Value range Initial-
ization
S7 is server:
ready to receive at positive
level
DISCONNECT IN BOOL S7 is client:
TRUE: after receiving the
response frame the
connection is cleared down
S7 is server:
TRUE: for ENQ_ENR =
FALSE the connection is to
be cleared down
TRUE
FALSE
no
REG_KEY IN STRING
[17]
Registration key (activation
code) for licencing
Character no
LICENSED OUT BOOL License status of block
Block is lincensed
Block is not licensed
TRUE
FALSE
no
BUSY OUT BOOL Processing status of T
functions (TCON, TDISCON,
TSEND or TRCV)
In process
Not in process TRUE
FALSE
no
CONN_ESTABLISHED OUT BOOL Connection established
Connection cleared down
TRUE
FASLE
no
DONE_NDR OUT BOOL S7 is client:
TRUE: enabled job was
completed without errors
S7 is server:
TRUE: requirement was
carried out and answered by
client
TRUE
FALSE
no
ERROR OUT BOOL An error has occurred.
There was no error
TRUE
FALSE
no
STATUS_MODBUS OUT WORD Error number for protocol
error for processing Modbus
frames
0 to FFFF no
STATUS_CONN OUT WORD Errror number for connection
error when processing T
blocks (TCON, TSEND,
TRCV, TDISCON)
0 to FFFF no
STATUS_FUNC OUT STRING
[8]
Name of function which
caused error on
STATUS_MODBUS or
STATUS_CONN
Character no
IDENT_CODE OUT STRING
[18]
Identification number for
licensing
With this identifier you can
apply for the REG_KEY
activation code for your
license.
Character no
UNIT IN/
OUT
BYTE Unit identifier
(INPUT for CLIENT function,
OUTPUT for server function)
0 to 255
B#16#0 to
B#16#FF
no
DATA_TYPE IN/ BYTE Data type to be processed: no
29. Function Mechanisms of this Application
Program structure of S7 CPU and ET200S CPU with integrated PN interface
Modbus TCP Connection
V 1.0, Entry ID: 38586568 29
CopyrightSiemensAG2009Allrightsreserved
Parameters Decl. Type Description Value range Initial-
ization
OUT (INPUT for CLIENT function,
OUTPUT for SERVER
function)
Coils
Inputs
Holding Register
Input register
1
2
3
4
START_ADDRESS IN/
OUT
WORD MODBUS start address
(INPUT for CLIENT function,
OUTPUT for SERVER
function)
0 to 65535
W#16#0000
to
W#16#FFFF
no
LENGTH IN/
OUT
WORD Number of values to be
processed
(INPUT for CLIENT function,
OUTPUT for SERVER
function)
Coils
read function
write function
Inputs
read function
Holding register
read function
write function
Input register
read function
1 to 2000
1 to 800
1 to 2000
1 to 125
1 to 100
1 to 125
no
TI IN/
OUT
WORD Transaction identifier
(INPUT for CLIENT function,
OUTPUT for server function)
0 to 65535
W#16#0 to
W#16#FFFF
no
WRITE_READ IN/
OUT
BOOL Write access or read access
(INPUT for CLIENT function,
OUTPUT for SERVER
function)
TRUE
FALSE
no
The parameters of the MODBUSPN function block are divided into two groups:
initialization parameters
runtime parameters
The initialization parameters are only evaluated for calls in OB100 and are
transferred to the instance DB. Initialization parameters are marked with "yes" in
the table above in the initialization column. A change of initialization parameters
during operation is of no consequence. When these parameters are changed, e.g.
during test mode, the instance DB (I-DB) of the CPU has to be reinitialized by
STOP -> RUN.
The runtime parameters can be changed during cyclical operation. However, in "S7
is client" mode, it does not make sense to change the input parameters while a job
is being processed. The preparations for the next job and the thus connected
changes of parameters should only be carried out when the previous job was
completed with DONE_NDR or ERROR. In the "S7 is server" mode the output
parameters can only be evaluated when DONE_NDR was set.
30. Function Mechanisms of this Application
Program structure of S7 CPU and ET200S CPU with integrated PN interface
30 Modbus TCP Connection
V 1.0, Entry ID: 38586568
CopyrightSiemensAG2009Allrightsreserved
Output parameters are dynamical displays and they are therefore only pending for
one CPU cycle. For possible further processing or for display in the variable table
they have to be copied to other memory areas.
The generation of the function code is via the parameters DATA_TYPE, LENGTH
and WRITE_READ. Possible combinations to generate a function code are shown
in the table below.
Table 4-3
Data type DATA_TYPE Function LENGTH WRITE_READ Function
code
Coils 1 read 1 to 2000 false 1
Coils 1 write 1 true 5
Coils 1 write 1 true 15
Coils 1 write >1 to 800 true 15
Inputs 2 read 1 to 2000 false 2
Holding register 3 read 1 to125 false 3
Holding register 3 write 1 true 6
Holding register 3 write 1 true 16
Holding register 3 write >1 to 100 true 16
Input register 4 read 1 to 125 false 4
31. Function Mechanisms of this Application
Program structure of S7 CPU and ET200S CPU with integrated PN interface
Modbus TCP Connection
V 1.0, Entry ID: 38586568 31
CopyrightSiemensAG2009Allrightsreserved
4.1.2 Configuration explanations
In this application example read and write data exchange is to be realized between
Modbus client and server. When the S7 CPU with integrated PN interface takes on
the client function, data is taken from the server via read access. This data is
copied internally to other memory spaces and then given back to the Modbus
server via write access.
When the S7 CPU with integrated PN interface takes on the server function,it’s not
possible to start client or server jobs. In this case the S7 CPU is waiting for
requests from the Modbus client (M340).
32. Function Mechanisms of this Application
Program structure of S7 CPU with CP
32 Modbus TCP Connection
V 1.0, Entry ID: 38586568
CopyrightSiemensAG2009Allrightsreserved
4.2 Program structure of S7 CPU with CP
The main difference of the program structure of the Modbus TCP solution via a CP
and the PN CPU is the configuration of the connection parameters. It is exclusively
done in STEP7 NetPro. There is no data structure in which the connection
parameters or the Modbus parameters could be entered. The Modbus parameters
are transferred in OB1.
Figure 4-19
FB 108
"MODBUSCP"
OB1
Netpro – setting
parameters for
connection
Library blocks
for Modbus CP
FB 108
"MODBUSCP"
SFC
…
Connection
parameter 2
Connection
parameter 1
Connection
parameter 3
Connection
parameter 4
Connection
parameter 5
…
OB100
IDB2
IDB1
FB 106
"MB_CPCLI"
FC 5
"AG_SEND"
FC 6
"AG_RECV"
DB 11
„DATA_AREA_1"
DB 12
„DATA_AREA_2"
DB 13
„DATA_AREA_3"
DB
…
OB121
4.2.1 Program details on MODBUS CP blocks
A separate call of the "MODBUSCP" function block with individual DB instance is
necessary for each connection. Please note that the call of the "MODBUSCP"
function block has to take place in OB1, OB121 and in OB100 with the same DB
instance per connection.
Modbus library blocks
The figure below displays all S7 program blocks which are necessary for Modbus
TCP via CP.
To be able to use Modbus TCP for CPs in a program, only the "MODBUSCP" block
has to be called. The other blocks are called internally in the "MODBUSCP"
function block.
33. Function Mechanisms of this Application
Program structure of S7 CPU with CP
Modbus TCP Connection
V 1.0, Entry ID: 38586568 33
CopyrightSiemensAG2009Allrightsreserved
Figure 4-20: Modbus TCP CP blocks from the sample program
OB1 call
In OB1 the cyclical calls of the "MODBUSCP" function block are made as well as of
other user specific functions and function blocks. This is where runtime parameters
are transferred to the "MODBUSCP" function block.
OB100 call
In OB100 the "MODBUSCP" function block is initialized. OB100 is completed once
when there is a STOP RUN transfer or when restarting the CPU in case of a
power failure.
OB121 call
In this OB the "MODBUSCP" function block also has to be called.
The OB121 makes an entry in the diagnostic buffer when there is no valid licence.
Additionally, without a valid licence the SF (system error) error LED of the CPU will
flash. If OB121 was not configured the CPU will go to stop mode after start-up.
34. Function Mechanisms of this Application
Program structure of S7 CPU with CP
34 Modbus TCP Connection
V 1.0, Entry ID: 38586568
CopyrightSiemensAG2009Allrightsreserved
Parameters of the "MODBUS" function block
This section describes the input and output parameters of the "MODBUSCP"
function block.
Figure 4-21: "MODBUSCP" function block call in STL
35. Function Mechanisms of this Application
Program structure of S7 CPU with CP
Modbus TCP Connection
V 1.0, Entry ID: 38586568 35
CopyrightSiemensAG2009Allrightsreserved
Table 4-15
Parameters Decl. Type Description Value range Initializ
ation
id IN WORD Connection ID in
accordance with the
configuration
1 to 64
W#16#1 to
W#16#40
yes
laddr IN WORD Input-Address of the CP in
HW Config
PLC
dependent
yes
MONITOR IN TIME Monitoring Time: Wait for
data from communication
partner
Shortest adjustable time is
20ms
T#20ms to
T#+24d20h31m2
3s647ms
no
REG_KEY IN STRING
[17]
Registration key to activate
the licence
Character no
server_client IN BOOL CP/FB operates in server
mode
CP/FB operates in client
modet
TRUE
FALSE
yes
single_write IN BOOL Write 1 Coil/Register:
Function code 5 or. 6
Function code 15 or. 16
TRUE
FALSE
yes
data_type_1 IN BYTE 1st data area: daten type
Coils
Inputs
Holding Register
Input Register
1
2
3
4
yes
db_1 IN WORD 1st data area: data block
number
1 to 65535
W#16#1 to
W#16#FFFF
yes
start_1 IN WORD 1st data area:
first Modbus address in this
DB
0 to 65535
W#16#0000 to
W#16#FFFF
yes
end_1 IN WORD 1st data area:
last Modbus address in this
DB
0 to 65535
W#16#0000 to
W#16#FFFF
yes
data_type_2 IN BYTE 2st data area: daten type
Coils
Inputs
Holding Register
Input Register
0 to 4 yes
db_2 IN WORD 2st data area: data block
number
1 to 65535
W#16#1 to
W#16#FFFF
yes
start_2 IN WORD 2st data area:
first Modbus address in this
DB
0 to 65535
W#16#0000 to
W#16#FFFF
yes
end_2 IN WORD 2st data area:
last Modbus address in this
DB
0 to 65535
W#16#0000 to
W#16#FFFF
yes
data_type_3 IN BYTE 3st data area: daten type
Coils
Inputs
0 to 4 yes
36. Function Mechanisms of this Application
Program structure of S7 CPU with CP
36 Modbus TCP Connection
V 1.0, Entry ID: 38586568
CopyrightSiemensAG2009Allrightsreserved
Parameters Decl. Type Description Value range Initializ
ation
Holding Register
Input Register
db_3 IN WORD 3st data area: data block
number
1 to 65535
W#16#1 to
W#16#FFFF
yes
start_3 IN WORD 3st data area:
first Modbus address in this
DB
0 to 65535
W#16#0000 to
W#16#FFFF
yes
end_3 IN WORD 3st data area:
last Modbus address in this
DB
0 to 65535
W#16#0000 to
W#16#FFFF
yes
data_type_4 IN BYTE 4st data area: daten type
Coils
Inputs
Holding Register
Input Register
0 to 4 yes
db_4 IN WORD 4st data area: data block
number
1 to 65535
W#16#1 to
W#16#FFFF
yes
start_4 IN WORD 4st data area:
first Modbus address in this
DB
0 to 65535
W#16#0000 to
W#16#FFFF
yes
end_4 IN WORD 4st data area:
last Modbus address in this
DB
0 to 65535
W#16#0000 to
W#16#FFFF
yes
data_type_5 IN BYTE 5st data area: daten type
Coils
Inputs
Holding Register
Input Register
0 to 4 yes
db_5 IN WORD 5st data area: data block
number
1 to 65535
W#16#1 to
W#16#FFFF
yes
start_5 IN WORD 5st data area:
first Modbus address in this
DB
0 to 65535
W#16#0000 bis
W#16#FFFF
yes
end_5 IN WORD 5st data area:
last Modbus address in this
DB
0 to 65535
W#16#0000 to
W#16#FFFF
yes
data_type_6 IN BYTE 6st data area: daten type
Coils
Inputs
Holding Register
Input Register
0 to 4 yes
db_6 IN WORD 6st data area: data block
number
1 to 65535
W#16#1 to
W#16#FFFF
yes
start_6 IN WORD 6st data area:
first Modbus address in this
DB
0 to 65535
W#16#0000 to
W#16#FFFF
yes
end_6 IN WORD 6st data area: 0 to 65535 yes
37. Function Mechanisms of this Application
Program structure of S7 CPU with CP
Modbus TCP Connection
V 1.0, Entry ID: 38586568 37
CopyrightSiemensAG2009Allrightsreserved
Parameters Decl. Type Description Value range Initializ
ation
last Modbus address in this
DB
W#16#0000 to
W#16#FFFF
data_type_7 IN BYTE 7st data area: daten type
Coils
Inputs
Holding Register
Input Register
0 to 4 yes
db_7 IN WORD 7st data area: data block
number
1 to 65535
W#16#1 to
W#16#FFFF
yes
start_7 IN WORD 7st data area:
first Modbus address in this
DB
0 to 65535
W#16#0000 to
W#16#FFFF
yes
end_7 IN WORD 7st data area:
last Modbus address in this
DB
0 to 65535
W#16#0000 to
W#16#FFFF
yes
data_type_8 IN BYTE 8st data area: daten type
Coils
Inputs
Holding Register
Input Register
0 to 4 yes
db_8 IN WORD 8st data area: data block
number
1 to 65535
W#16#1 to
W#16#FFFF
yes
start_8 IN WORD 8st data area:
first Modbus address in this
DB
0 to 65535
W#16#0000 to
W#16#FFFF
yes
end_8 IN WORD 8st data area:
last Modbus address in this
DB
0 to 65535
W#16#0000 to
W#16#FFFF
yes
ENQ_ENR IN BOOL CP is client: Initiate request
at TRUE signal
CP is server: Ready to
receive at TRUE signal
TRUE
FALSE
no
LICENSED OUT BOOL License state of the
function block:
Block is licensed
Block is not licensed
TRUE
FALSE
no
BUSY OUT BOOL Operating state of the
functions AG_SEND and
AG_RECV
Job processing
No job processing active
TRUE
FALSE
no
DONE_NDR OUT BOOL CP is client: Active request
finished without errors
CP is server: Request from
the client was executed
and answered
TRUE
FALSE
no
ERROR OUT BOOL An error has occurred:
yes: TRUE
FALSE
no
38. Function Mechanisms of this Application
Program structure of S7 CPU with CP
38 Modbus TCP Connection
V 1.0, Entry ID: 38586568
CopyrightSiemensAG2009Allrightsreserved
Parameters Decl. Type Description Value range Initializ
ation
no:
STATUS OUT WORD Error number 0 to FFFF no
STATUS_FUNC OUT STRING
[8]
Name of the function,
which causes the error at
STATUS
Character no
IDENT_CODE OUT STRING
[18]
Identification for licensing
Please order your license
with this identification
string.
Character no
UNIT IN/
OUT
BYTE Unit identification (INPUT if
in CLIENT mode, OUTPUT
if in SERVER mode)
0 to 255
B#16#0 to
B#16#FF
no
DATA_TYPE IN/
OUT
BYTE Data type to be accessed:
(INPUT if in CLIENT mode,
OUTPUT if in SERVER
mode)
Coils:
Inputs:
Holding registers:
Input registers:
1
2
3
4
no
START_
ADDRESS
IN/
OUT
WORD MODBUS start address
(INPUT if in CLIENT mode,
OUTPUT if in SERVER
mode)
0 to 65535 no
LENGTH IN/
OUT
WORD Number of registers to be
processed (INPUT if in
CLIENT mode, OUTPUT if
in SERVER mode)
Coils: reading function
writing function.
Inputs: reading function
Holding Reg.:
reading function
writing function.
Input Reg.:
reading function
1 to 2000
1 to 1968
1 to 2000
1 to 125
1 to 123
1 to 125
no
TI IN/
OUT
WORD Transaction Identifier
(INPUT if in CLIENT mode,
OUTPUT if in SERVER
mode)
0 to 65535 no
WRITE_READ IN/
OUT
BOOL INPUT if in CLIENT mode,
OUTPUT if in SERVER
mode:
Write access:
Read access:
TRUE
FALSE
no
39. Function Mechanisms of this Application
Program structure of S7 CPU with CP
Modbus TCP Connection
V 1.0, Entry ID: 38586568 39
CopyrightSiemensAG2009Allrightsreserved
The parameters of the “MODBUSCP” function block are divided into two groups:
initialization parameters
runtime parameters
The initialization parameters are only evaluated for the inital run of the
“MODBUSCP” function block and are transferred to the DB instance. Initialization
parameters are marked with "yes" in the table above in the initialization column. A
change of initialization parameters during operation is of no consequence. When
these parameters are changed, e.g. during test mode, the instance DB (I-DB) of
the CPU has to be reinitialized by STOP RUN.
Runtime parameters can be changed during cyclical operation. It is not advisable to
change the input parameters whilst a job is being processed. The preparations for
the next job and the thus connected changes of parameters should only be carried
out when the previous job was completed with DONE_NDR or ERROR. Output
parameters should only be evaluated with set DONE_NDR.
The generation of the function code is via the parameters LENGTH, single_write
and WRITE_READ. Possible combinations to generate a function code are shown
in the table below.
Table 4-4
Data type DATA_
TYPE
Function LENGTH WRITE_READ single_
write
Function
code
Coils 1 read 1 to 2000 false irrelevant 1
Coils 1 write 1 true TRUE 5
Coils 1 write 1 true FALSE 15
Coils 1 write >1 to 1968 true irrelevant 15
Inputs 2 read 1 to 2000 false irrelevant 2
Holding
Register
3 read 1 to 125 false irrelevant 3
Holding
Register
3 write 1 true TRUE 6
Holding
Register
3 write 1 true FALSE 16
Holding
Register
3 write >1 to 123 true irrelevant 16
Input
Register
4 read 1 to 125 false irrelevant 4
40. Function Mechanisms of this Application
Program structure of Modicon M340
40 Modbus TCP Connection
V 1.0, Entry ID: 38586568
CopyrightSiemensAG2009Allrightsreserved
4.2.2 Configuration explanations
In this application example read and write data exchange is to be realized between
Modbus client and server. When the S7 CPU with CP takes on the client function,
data is taken from the server via read access. This data is copied internally to other
memory spaces and then given back to the Modbus server via write access.
When the S7 CPU with CP takes on the server function,it’s not possible to start
client or server jobs. In this case the S7 CPU is waiting for requests from the
Modbus client (M340).
4.3 Program structure of Modicon M340
The following program structure only shows the Modbus client application of
Modicon M340. If the Modicon M340 is to act as Modbus server, no special block
call is necessary in the user program.
Figure 4-22
READ_VAR
WRITE_VAR
Connection
parameter
Sections
ADDM
41. Function Mechanisms of this Application
Program structure of Modicon M340
Modbus TCP Connection
V 1.0, Entry ID: 38586568 41
CopyrightSiemensAG2009Allrightsreserved
4.3.1 Program details on Modicon M340 blocks
READ_VAR
This function can read data from a Modbus server. The Modbus server is
addressed via IP address.
WRITE_VAR
The WRITE_VAR function can write data in a Modbus server. For this function the
IP address of the Modbus server is also necessary.
ADDM
This function changes a string to an address which can be used by communication
functions (READ_VAR, WRITE_VAR). The IP address is assigned to the string as
initial value in the variable declaration.
4.3.2 Configuration explanations
In this application example read and write data exchange is to be realized between
Modbus client and server. When the Modicon M340 takes on the client function,
data is taken from the server via read access. This data is copied internally to other
memory spaces and then given back to the Modbus server via write access.
When the Modicon M340 takes on the server function,it’s not possible to start client
or server jobs. In this case the M340 is waiting for requests from the Modbus client
(S7).
42. Installation
Installation of the hardware
42 Modbus TCP Connection
V 1.0, Entry ID: 38586568
CopyrightSiemensAG2009Allrightsreserved
5 Installation
This chapter describes which hardware and software components have to be
installed. It is essential to read the instructions, manuals and any delivery
information supplied with the respective products.
5.1 Installation of the hardware
For the required hardware components, please refer to chapter 2.3 "Hardware and
software components used”. The table below gives an overview of the IP
addresses as well as the devices which are used in the hardware setup of the
application. Both S7 CPUs with integrated PN interface and the S7 CPU with CP
have the same IP address. These components are never connected to the
Ethernet network at the same time.
Table 5-17
Device IP address
CPU319-3 PN/DP 192.168.1.1
IM 151-8 PN/DP CPU 192.168.1.1
CPU315-2 PN/DP none
CP343-1 Lean 192.168.1.1
SCALANCE X108 none
PS307 24 V/5 A none
Modicon M340 192.168.1.10
PG/PC 192.168.1.55
43. Installation
Installation of the hardware
Modbus TCP Connection
V 1.0, Entry ID: 38586568 43
CopyrightSiemensAG2009Allrightsreserved
For the hardware configuration, please follow the instructions listed in the table
below:
Table 5-1
No. Instruction Comment
1 Mount the modules on a DIN rail
2 Connect the CPU315-2PN/DP with
the CP343-1 lean via the backplane
bus
3 Connect all modules with 24V power
supply
If necessary use terminal strips or several power supplies
4 Connect the following modules via
Ethernet:
* CP343-1 Lean or CPU319-3
PN/DP or IM 151-8 PN/DP CPU with
Scalance X108
*Modicon M340 with Scalance X108
*PG/PC with Scalance X108
Use the corresponding S7 CPU depending on the
application example.
5 Assign the following IP address
192.168.1.55 (Subnet mask:
255.255.255.0) to the Ethernet
interface of the PG/PC.
Start Settings Control
Panel Network
Connections LAN
Properties TCP/IP
Properties
6 Start the SIMATIC manager and
select the TCP/IP interface
Options Set PG/PC
interface
7 Assign the IP addresses from table
5-15 to the S7 CPUs.
To do this, use the SIMATIC
manager and search the available
nodes in the menu "PLC Edit
Ethernet Node".
Note The guidelines for the components used here always have to be met.
44. Installation
Installation of the hardware
44 Modbus TCP Connection
V 1.0, Entry ID: 38586568
CopyrightSiemensAG2009Allrightsreserved
Installation of the software
Table 5-19
No. Instruction Remarks
1 Installing STEP7 Installation is automatic. Follow
the setup instructions. Installation
of STEP7 is also described in the
manual "Programming with STEP7
V5.4" (see 3).
2 Installing the Modbus TCP library Installation is automatic. Follow
the setup instructions. A
description of the installation of the
Modbus TCP library can also be
found in the manuals for Modbus
TCP (see 4).
3 Installing the Modbus TCP Wizard In the manual of the Modbus TCP
Wizards you will find information
on installing and configuring a
Modbus TCP communication (see
5).
4 Installing of Unity Pro XL Installation is automatic. Follow
the setup instructions.
45. Startup of the Application
Configuration of CPU319-3 PN/DP
Modbus TCP Connection
V 1.0, Entry ID: 38586568 45
CopyrightSiemensAG2009Allrightsreserved
6 Startup of the Application
6.1 Configuration of CPU319-3 PN/DP
This chapter describes the configuration of the CPU319-3 PN/DP. Using this
configuration description you can configure the application examples of the
CPU319-3 PN/DP yourself and start up the CPU.
6.1.1 Hardware configuration
Table 6-20
No. Instruction Comment
1 Create a new project in the SIMATIC
manager.
Filenew
2 Right click the just created project
and insert the SIMATIC 300 station
via the menu "Insert New
Object SIMATIC 300
Station".
3 Right click "Hardware" and select
"Open Object" to open the
hardware configuration
46. Startup of the Application
Configuration of CPU319-3 PN/DP
46 Modbus TCP Connection
V 1.0, Entry ID: 38586568
CopyrightSiemensAG2009Allrightsreserved
No. Instruction Comment
4 Insert a rack in the hardware
configuration via drag&drop from the
hardware catalog.
5 Insert a CPU319-3 PN/DP V2.7 from
the hardware catalog via drag&drop
on slot 2 of the rack.
Hardware catalog:
SIMATIC 300CPU 300CPU319-3 PN/DP6ES7 318-
3EL00-0AB0V2.7
6 Configure the Ethernet interface of
the CPU319-3 PN/DP:
- Assign
IP Address
192.168.1.1
- create new
Ethernet network
Note: this menu opens automatically
after inserting the module.
A Profibus network does not need to
be created.
7 Compile and save the hardware
configuration.
47. Startup of the Application
Configuration of CPU319-3 PN/DP
Modbus TCP Connection
V 1.0, Entry ID: 38586568 47
CopyrightSiemensAG2009Allrightsreserved
6.1.2 Insert Modbus TCP blocks into project
Table 6-21
No. Instruction Comment
1 Open the Modbus TCP examples
from the library for PN CPUs: File
Open Sample projects
2 Insert S7 300 CPU library blocks into
S7 project (depending whether S7
CPU is to be client or server, FB104
or FB105 has to be copied)
In the sample project the blocks can
be marked and inserted in the block
container of your S7 Modbus project
via drag&drop.
OB1 in the S7 Modbus project has to
be overwritten with OB1 of the
sample project.
6.1.3 Configuring Modbus TCP connections
The Modbus TCP connection can either be configured with the Modbus TCP
Wizard or by manually processing the DB parameter (MODBUS_PARAM). Manual
processing of MODBUS_PARAM is described in the Modbus TCP manual for PN
CPUs (see 4).
Modbus TCP Wizard
This section explains how a Modbus connection for S7 CPUs with integrated PN
interface is configured with the aid of the Modbus TCP Wizard. When using the
Wizard, please make sure that the Modbus (MODBUS_PARAM) DB parameter is
not open in the SIMATIC manager.
48. Startup of the Application
Configuration of CPU319-3 PN/DP
48 Modbus TCP Connection
V 1.0, Entry ID: 38586568
CopyrightSiemensAG2009Allrightsreserved
Table 6-22
No. Instruction Comment
1 Start the Modbus TCP Wizard
(Start SIMATIC
ModbusTCPWizard) and click the
"Next" button to get to the "STEP 7
project" menu.
In this dialog you select the S7
project just created.
2 Read existing project
Click the "upload" button to load a
configured connection of your project
into the Modbus TCP Wizard.
You can process this connection by
enabling the "Change" option.
3 Select client/server mode
Enable the function "SIMATIC S7
acts as server" when the S7
CPU is to act as Modbus TCP
server.
Enable the "connect at
startup" function so that the CPU
can automatically create a Modbus
TCP connection to the remote
communication partner after startup.
49. Startup of the Application
Configuration of CPU319-3 PN/DP
Modbus TCP Connection
V 1.0, Entry ID: 38586568 49
CopyrightSiemensAG2009Allrightsreserved
No. Instruction Comment
4 Select the Modbus TCP partner and
the internal interface (select your
hardware: e.g.: Integrated 319)
Client application:
enter the remote IP address
(192.168.1.10). The client is always
the active partner.
Server application:
the server is configured as passive
communication partner. Doing this,
each client can connect with the
server when an unspecified
connection partner was selected.
5 Selection of port
Client application:
selection of remote port (port 502 for
Modicon M340)
Server application:
selection of local port (port: 502)
6 Definition of Modbus register
Client application:
1 Holding Registers from 100 to 399
2 Input Registers from 400 to 600
Server application:
1 Holding Registers from 0 to 500
2 Holding Registers from 720 to 900
50. Startup of the Application
Configuration of CPU319-3 PN/DP
50 Modbus TCP Connection
V 1.0, Entry ID: 38586568
CopyrightSiemensAG2009Allrightsreserved
No. Instruction Comment
7 Transfer Modbus TCP parameters to
MODBUS_PARAM
Click the "Next" button to get to the dialogs that follow.
With one click on the "Next" button in the "Connection
list" dialog the Modbus TCP data is transferred to the
MODBUS_PARAM DB.
After transfer click the "Finish" button to exit the wizard.
8 Now you have to adjust the DBs for
the Modbus data areas in the S7
project.
Client application:
DB11 ARRAY[0…300]
DB12 ARRAY[0…300]
Server application:
DB11 ARRAY[0…600]
DB12 ARRAY[0…300]
6.1.4 Project download
Table 6-23
No. Instruction Comment
1 Mark the SIMATIC 300 station in the
SIMATIC manager and load the
project into the controller.
51. Startup of the Application
Configuration of IM151-8 PN/DP CPU
Modbus TCP Connection
V 1.0, Entry ID: 38586568 51
CopyrightSiemensAG2009Allrightsreserved
6.2 Configuration of IM151-8 PN/DP CPU
The configuration of the ET200S (IM151-8 PN/DP CPU) is similar to the
configuration of the CPU319-3 PN/DP. This is why this chapter only deals with the
hardware configuration of the ET200S. Creating and configuring a Modbus TCP
project for the ET200S is analog to the project of the CPU319-3 PN/DP.
When configuring the MODBUS_PARAM the respective local interface for the
ET200S has to be selected in the Modbus TCP Wizard! The other configuration
steps in the Modbus TCP wizard do not change.
6.2.1 Hardware configuration
Table 6-24
No. Instruction Comment
1 Create a new project in the SIMATIC
manager.
File New
2 Right click the STEP7 project and
insert the SIMATIC 300 station via
the menu "Insert New Object".
3 Right click "Hardware" and select
"Open Object" to open the
hardware configuration of the S7-300
station.
52. Startup of the Application
Configuration of IM151-8 PN/DP CPU
52 Modbus TCP Connection
V 1.0, Entry ID: 38586568
CopyrightSiemensAG2009Allrightsreserved
No. Instruction Comment
4 Add the IM151-8 PN/DP CPU from
the hardware catalog via drag&drop.
Hardware catalog:
SIMATIC 300 PROFINET IO
I/O ET200S IM151-8 PN/DP
CPU
5 Configure the Ethernet interface of
ET200S:
assign the IP address 192.168.1.1
and create a
new Ethernet network
Note: this menu opens automatically
after inserting the module.
53. Startup of the Application
Configuring the CPU315-2 PN/DP with CP343-1 Lean
Modbus TCP Connection
V 1.0, Entry ID: 38586568 53
CopyrightSiemensAG2009Allrightsreserved
No. Instruction Comment
6 Compile and save the hardware
configuration.
6.3 Configuring the CPU315-2 PN/DP with CP343-1 Lean
6.3.1 Hardware configuration
Table 6-25
No. Instruction Comment
1 Create a new project in the SIMATIC
manager.
Filenew
2 Right click the STEP7 project and
insert the SIMATIC 300 station via
the menu "Insert New Object".
3 Right click "Hardware" and select
"Open Object" to open the
hardware configuration of the S7-300
station.
54. Startup of the Application
Configuring the CPU315-2 PN/DP with CP343-1 Lean
54 Modbus TCP Connection
V 1.0, Entry ID: 38586568
CopyrightSiemensAG2009Allrightsreserved
No. Instruction Comment
4 Insert a SIMATIC 300 via drag&drop.
5 Insert a CPU315-2 PN/DP from the
hardware catalog via drag&drop on
slot 2 of the rack.
There is no need to define CPU
interfaces. Close the configuration
dialogs which open automatically
after inserted the CPU.
Hardware catalog:
SIMATIC 300 CPU-300
CPU315-2 PN/DP 6ES7 315-
2EG10-0AB0 V2.3
6 Now insert the CP343-1.
Hardware catalog:
SIMATIC 300 CP-300
Industrial Ethernet CP343-1 Lean
6GK7 343-1CX10-0XE0 V2.0
55. Startup of the Application
Configuring the CPU315-2 PN/DP with CP343-1 Lean
Modbus TCP Connection
V 1.0, Entry ID: 38586568 55
CopyrightSiemensAG2009Allrightsreserved
No. Instruction Comment
7 Configure the Ethernet interface of
the CP343-1:
assign the IP address 192.168.1.1
and create a
new Ethernet network
Note: this menu opens automatically
after inserting the module.
8 Compile and save the hardware
configuration.
56. Startup of the Application
Configuring the CPU315-2 PN/DP with CP343-1 Lean
56 Modbus TCP Connection
V 1.0, Entry ID: 38586568
CopyrightSiemensAG2009Allrightsreserved
6.3.2 Creating a project for Modbus TCP
Table 6-26
No. Instruction Comment
1 Open the sample projects for
Modbus TCP CP via the “File
Open” menu.
2 Copy the blocks from the sample
projects for a server or client
application and insert it in your
Modbus project
Overwrite the already existing OB1.
57. Startup of the Application
Configuring the CPU315-2 PN/DP with CP343-1 Lean
Modbus TCP Connection
V 1.0, Entry ID: 38586568 57
CopyrightSiemensAG2009Allrightsreserved
6.3.3 Configuring Modbus TCP connections
Table 6-27
No. Instruction Comment
1 Open the OB100 and process the
initialization parameters to adapt the
Modbus data areas.
For the application example
described here the following
parameters have to be assigned
(see figure). For areas not used
enter a zero.
Client:
1. DB: DB11 area: 100 – 399
as Holding register
(data_type = 3)
2. DB: DB12 area: 400 – 600
as Input register
(data_type = 4)
3. – 8. DB: not necessary
Server:
1. DB: DB11 area: 0 – 500
as Holding register
(data_type = 3)
2. DB: DB12 area: 720 – 900
as Holding register
(data_type = 3)
3. – 8. DB: not necessary
2 Adapt DBs for Modbus data areas in
S7 project
Client application:
DB11 ARRAY[0…300]
DB12 ARRAY[0…300]
Server application:
DB11 ARRAY[0…600]
DB12 ARRAY[0…300]
3 Open NetPro.
4 Insert a new connection and
configure it in a way so that it can be
used for the Modbus TCP
communication to Modicon M340.
58. Startup of the Application
Configuring the CPU315-2 PN/DP with CP343-1 Lean
58 Modbus TCP Connection
V 1.0, Entry ID: 38586568
CopyrightSiemensAG2009Allrightsreserved
No. Instruction Comment
5 In the dialog field "Insert New
Connection".select "TCP
connection".
Under "Connection Partner"
select "Unspecified".
Note: once this has been confirmed
the properties window of this
connection will open automatically.
6 Assign an unambiguous name for
the connection in the properties
dialog of the TCP connection (e.g.
Modbus TCP to Modicon).
If the S7 CPU is the Modbus client
enable the function "Active
connection establishment".
59. Startup of the Application
Configuring the CPU315-2 PN/DP with CP343-1 Lean
Modbus TCP Connection
V 1.0, Entry ID: 38586568 59
CopyrightSiemensAG2009Allrightsreserved
No. Instruction Comment
7 Once the active connection
establishment was selected an IP
address and a port number of the
communication partner (Modicon
M340) has to be known. The local
port is of no significance in this case.
In the case of a passive connection
establishment, IP address or port of
the communication partner does not
need to be known. Only the local
port has to be configured. A
connection query from a remote
communication partner has to take
place on this port (local port: 502).
Confirm the entry by clicking "OK".
8 Save and compile the changes made
and afterwards exit NetPro.
6.3.4 Downloading project
Table 6-28
No. Instruction Comment
1 Mark the SIMATIC 300 station in the
SIMATIC manager and load the
project into the controller.
Note:
if asked via which interface you
would like to created the connection
to the CPU315 you have to select
the IP of the CP.
60. Startup of the Application
Configuration of Modicon M340
60 Modbus TCP Connection
V 1.0, Entry ID: 38586568
CopyrightSiemensAG2009Allrightsreserved
6.4 Configuration of Modicon M340
To be able to better comprehend the application example, the following points will
explain how the Modicon M340 has to be configured to allow a Modbus TCP
connection with a SIMATIC station.
In the application examples included these steps do not need to be carried out
anymore.
6.4.1 Using application example
Table 6-29
No. Instruction Comment
1 Open client or server application.
In the steps that follow, open the
application example included in
delivery for the Modicon. M340.
Client: „m340_client_s7_server.stu“
Server:„ m340_server_s7_client.stu“
File Open…
2 Open the already created user
program in the menu "Section".
A sample program with the corresponding data areas
already exists.
3 Rebuild all project.
4 Create an online connection
between PG/PC and Modicon M340.
5 Transfer the server or client program
in the Modicon M340.
6 Start the CPU
61. Startup of the Application
Configuration of Modicon M340
Modbus TCP Connection
V 1.0, Entry ID: 38586568 61
CopyrightSiemensAG2009Allrightsreserved
62. Startup of the Application
Configuration of Modicon M340
62 Modbus TCP Connection
V 1.0, Entry ID: 38586568
CopyrightSiemensAG2009Allrightsreserved
6.4.2 Hardware configuration
Execute the following steps to configure the Modicon M340 hardware.
The table deals with the hardware of the application example. If you are using a
different hardware, you have to adjust the configuration accordingly.
Table 6-30
No. Instruction Comment
1 Create a new project in Unity Pro XL FileNew
2 Select the hardware.
3 Configure the project settings under
"Tools Project Settings
Build":
63. Startup of the Application
Configuration of Modicon M340
Modbus TCP Connection
V 1.0, Entry ID: 38586568 63
CopyrightSiemensAG2009Allrightsreserved
No. Instruction Comment
4 Configure the project settings under
"Tools Project Settings
Language extensions":
5 Open the hardware configuration by
double-clicking "PLC bus" in the
"Project Browser" menu.
6 The hardware configuration is
already equipped with power supply
and the communication module.
Right click onto a free slot in the rack
to add I/Os.
Insert a DDO1602 in position 1 and a
DDI1602 in position 2.
Change the PLC BUS to BMX P34
2030 01.00.
64. Startup of the Application
Configuration of Modicon M340
64 Modbus TCP Connection
V 1.0, Entry ID: 38586568
CopyrightSiemensAG2009Allrightsreserved
No. Instruction Comment
7 Right click the rack to adjust the
existing hardware.
In the application example a rack
with 4 slots is used. Therefore the
rack with 7 slots configured here has
to be exchanged for a rack with 4
slots.
6.4.3 Configuring an Ethernet interface for Modbus TCP
Table 6-31
No. Instruction Comment
1 Right click “Networks” in the
“Project Browser“ under
“Communication“ and select the
“New Network“ menu to insert a
new network.
2 Select Ethernet as network and
assign the name “Ethernet_1“.
65. Startup of the Application
Configuration of Modicon M340
Modbus TCP Connection
V 1.0, Entry ID: 38586568 65
CopyrightSiemensAG2009Allrightsreserved
No. Instruction Comment
3 Now the local Ethernet interface has
to be configured.
You get to this menu by left double-
clicking on the just created network
“Ethernet_1“ under the
“Networks“ menu
Change the "Model Family" to
"CPU2020, CPU2030“ and assign
the IP address as well as the subnet
mask.
IP address: 192.168.1.10
Subnetwork mask: 255.255.255.0
After successful configuration exit
this menu and accept the changes.
4 The newly created network now has
to be assigned to the hardware.
For this purpose open the Ethernet
interface in the hardware
configuration by double-clicking it
“Project Browser Project
Configuration PLC bus
BMX XBP 0400 BMX P34
2030 Ethernet".
5 Double-click the "Channel 3“ field
in the Window just opened up
“0.0:Ethernet“
Select "Function“ ETH TCP IP
from the drop-down list of the menu.
In the "NET Link“ menu select the
previously configured netzwork
“Ethernet_1“ from the drop-down
list.
Close the window and accept the
changes.
66. Startup of the Application
Configuration of Modicon M340
66 Modbus TCP Connection
V 1.0, Entry ID: 38586568
CopyrightSiemensAG2009Allrightsreserved
6.4.4 Creating a project for Modbus TCP
Table 6-32
No. Instruction Comment
1 Create a new section.
Project Browser Station
Program Tasks MAST
Sections right mouse
click
2 Define a structure in the "Derived
Data Types" menu. This predefined
structure can be used for the
declaration of variables.
Project Browser Station
Derived Data Types
3 Only in client application:
create a variable with the initial value
"Ethernet_1{192.168.1.1}" from data
type string[32].
Project Browser
Variables & FB instances
Elementary Variables
Note: this variable is necessary for
addressing the communication
partner (S7 station) of Modicon
M340.
4 Only in client application:
for the READ_VAR and
WRITE_VAR functions variables are
necessary which also serve as send
or receive memory. Create the
displayed variables for Modicon
M340 as client:
Project Browser
Variables & FB instances
Derived Variables
5 Only in server application:
declare variables in the server which
can be accessed by a Modbus client.
Read zone: from %MW400
67. Startup of the Application
Configuration of Modicon M340
Modbus TCP Connection
V 1.0, Entry ID: 38586568 67
CopyrightSiemensAG2009Allrightsreserved
No. Instruction Comment
Write zone: %MW100 - %MW399
Project Browser
Variables & FB instances
Derived Variables
6 Only in client application:
with the aid of the FBB Input
Assistant the functions "READ_VAR,
WRITE_VAR and ADDM" are
inserted.
Right click an opened section in the
editor program to open the assistant.
Server application:
the blocks are not needed.
7 Only in client application:
insert READ_VAR and supply with
parameters:
ADR address
OBJ object type
NUM first object
NB object number
GEST management_param
RECP receiving array
8 Only in client application:
insert WRITE_VAR and supply with
parameters
ADR address
OBJ object type
NUM first object
NB object number
EMIS data to write
GEST management parameter
9 Only in client application:
insert ADDM and supply with
parameters
IN address string
OUT connect to ADR parameter
68. Operation of the Application
Operation of CPU319-3 PN/DP and IM151-8 PN/DP CPU
68 Modbus TCP Connection
V 1.0, Entry ID: 38586568
CopyrightSiemensAG2009Allrightsreserved
7 Operation of the Application
The following chapter describes the operation of the application examples included
in delivery.
7.1 Operation of CPU319-3 PN/DP and IM151-8 PN/DP CPU
For the CPU319-3 PN/DP and the IM151-8 PN/DP CPU the Modbus TCP client
jobs are triggerd via PG/PC. For this purpose the variable tables are used which
enable control of individual DB variables.
When the S7 stations are configured as server the job only has to be started once.
The server will then constantly monitor the configured port and will wait for an
arriving client job.
For the S7 client and server application there is the option to change the Modbus
TCP data via a variable table ("VAT_DB11-15“ ).
7.1.1 S7 station is client
Reading data from the server
To be able to read data from the Modicon M340 via Modbus TCP follow the
instructions of the table below.
Table 7-33: Reading data from the server
No. Instruction Comment
1 Open the variable table
"Client_read_from_
server"
2 In the menu bar click the
“Monitor variable“
icon to change to the online
view.
3 Modify the variables
displayed in the screenshot
Right mouse click
Modify
DB1.DBB 69 B#16#04
DB1.DBW 70 400
DB1.DBW 72 4
…
DB1.DBX 76.0 false
69. Operation of the Application
Operation of CPU319-3 PN/DP and IM151-8 PN/DP CPU
Modbus TCP Connection
V 1.0, Entry ID: 38586568 69
CopyrightSiemensAG2009Allrightsreserved
No. Instruction Comment
4 Modify ENQ_ENR
Right mouse click
Modify to 1
5 Display received data
Open the variable table
"VAT_DB11-15" and
change to the online view.
Writing data in the server
To be able to write data from the client in the Modbus TCP server (Modicon M340),
please follow the instructions in the table below.
Table 7-34: Writing data in the server
No. Instruction Comment
1 Open the variable table
"Client_write_to_server"
2 In the menu bar click the
“Monitor variable“
icon to change to the online
view.
3 Modify the variables
displayed in the screenshot
Right mouse click
Modify
DB1.DBB 69 B#16#03
DB1.DBW 70 100
DB1.DBW 72 4
…
DB1.DBX 76.0 true
70. Operation of the Application
Operation of CPU319-3 PN/DP and IM151-8 PN/DP CPU
70 Modbus TCP Connection
V 1.0, Entry ID: 38586568
CopyrightSiemensAG2009Allrightsreserved
No. Instruction Comment
4 Modify send data in DB11
Open the variable table
"VAT_DB11-15" and
change to the online view.
Modify the variables that
are marked in screenshot.
5 Open the variable table
“Client_write_to_server”
again.
Modify ENQ_ENR to send
the data from DB11 to the
Modbus TCP server.
Right mouse click
Modify to 1
71. Operation of the Application
Modbus TCP Connection
V 1.0, Entry ID: 38586568 71
CopyrightSiemensAG2009Allrightsreserved
7.1.2 S7 station is server
The following steps describe how to modify the data from the S7 Modbus TCP
server. This data is read by the Modbus TCP client (Modicon M340).
Table 7-35
No. Instruction Comment
1 Open the variable table
“VAT_DB11-15"
2 In the menu bar click the
“Monitor variable“
icon to change to the online
view.
3 Modify the variables
displayed in the screenshot
Right mouse click
Modify
DB11.DBW 0
W#16#3412
DB11.DBW 2
W#16#5678
DB11.DBW 4
W#16#90AB
DB11.DBW 6
W#16#CDEF
These values are read from
the Modicon M340 via
Modbus TCP.
4 In the opened variable
table you can also check
the data that is written in
the server by the client.
7.2
72. Operation of the Application
Operation of CPU315-2 PN/DP + CP343-1 Lean
72 Modbus TCP Connection
V 1.0, Entry ID: 38586568
CopyrightSiemensAG2009Allrightsreserved
7.3 Operation of CPU315-2 PN/DP + CP343-1 Lean
For the CPU315-2 PN/DP + CP343-1 Lean the Modbus TCP client jobs are also
triggered via PG/PC. Variable tables are also used which enable control of
individual DB variables.
When the S7 stations are configured as server the job only has to be started once.
The server will then constantly monitor the configured port and will wait for an
arriving client job.
For the server application there is the option to change the Modbus TCP data via
variable table.
7.3.1 S7 station is client
Reading data from the server
To be able to read data from the Modicon M340 via Modbus TCP follow the
instructions of the table below.
Table 7-36: Reading data from the server
No. Instruction Comment
1 Open the variable table
"Client_read_from_server"
2 In the menu bar click the
“Monitor variable“ icon to
change to the online view.
3 Modify the variables displayed
in the screenshot
Right mouse click
Modify
DB1.DBB 126 B#16#01
DB1.DBB 127 B#16#04
DB1.DBW 128
W#16#0190
DB1.DBW 130 4
…
DB1.DBX 134.0 false
4 Modify ENQ_ENR (DB1.DBX
92.0)
Right mouse click
Modify to 1
73. Operation of the Application
Operation of CPU315-2 PN/DP + CP343-1 Lean
Modbus TCP Connection
V 1.0, Entry ID: 38586568 73
CopyrightSiemensAG2009Allrightsreserved
No. Instruction Comment
5 Display received data
Open the variable table
"VAT_DB11-15" and change to
the online view.
Writing data in the server
To be able to write data from the client in the Modbus TCP server (Modicon M340),
please follow the instructions in the table below.
Table 7-37: Writing data in the server
No. Instruction Comment
1 Open the variable table
"Client_write_to_server"
2 In the menu bar click the
“Monitor variable“ icon to
change to the online view.
3 Modify the variables displayed
in the screenshot
Right mouse click
Modify
DB1.DBB 126 B#16#01
DB1.DBB 127 B#16#03
DB1.DBW 128 W#16#0064
DB1.DBW 130 4
…
DB1.DBX 134.0 true
4 Modify send data in DB11
Open the variable table
"VAT_DB11-15" and change to
the online view.
Modify the variables that are
marked in the screenshot.
74. Operation of the Application
Operation of CPU315-2 PN/DP + CP343-1 Lean
74 Modbus TCP Connection
V 1.0, Entry ID: 38586568
CopyrightSiemensAG2009Allrightsreserved
No. Instruction Comment
5 Open the variable table
“Client_write_to_server” again.
Modify ENQ_ENR
Right mouse click
Modify to 1
7.3.2 S7 station is server
The following steps describe how to modify the data from the S7 Modbus TCP
server.
This data is read by the Modbus TCP client (Modicon M340).
Table 7-38: Viewing Modbus TCP server data
No. Instruction Comment
1 Open variable table
"VAT_DB11-15"
2 In the menu bar click the
“Monitor variable“
icon to change to the online
view.
3 Modify the variables
displayed in the screenshot
Right mouse click
Modify
DB11.DBW 0
W#16#3412
DB11.DBW 2
W#16#5678
DB11.DBW 4
W#16#90AB
DB11.DBW 6
W#16#CDEF
75. Operation of the Application
Operation of CPU315-2 PN/DP + CP343-1 Lean
Modbus TCP Connection
V 1.0, Entry ID: 38586568 75
CopyrightSiemensAG2009Allrightsreserved
No. Instruction Comment
4 In the opened variable
table you can also check
the data that is written in
the server by the client.
76. Operation of the Application
Operation of Modicon M340
76 Modbus TCP Connection
V 1.0, Entry ID: 38586568
CopyrightSiemensAG2009Allrightsreserved
7.4 Operation of Modicon M340
7.4.1 Modicon M340 as client
Reading data from the server and writing to the server
The following steps describe, how to view the Modicon M340 data, which will be
read from and written to the S7. In the program of the Modicon M340 all the
received data will be copied directly onto the sent data. If you want to modify the
sent data yourself, you must delete the copy instructions in the M340 program,
recompile the program and download it to the M340 PLC again.
Tabelle 7-39: Reading data from the server
No. Instruction Comment
1 Open the variable table
„Animation Tables
Table“
2 In the menu bar click the
“Connect“ icon to change
to the online view.
3 Viewing the received data
That data are read from the
server(S7) by the client
(M340)
77. Operation of the Application
Operation of Modicon M340
Modbus TCP Connection
V 1.0, Entry ID: 38586568 77
CopyrightSiemensAG2009Allrightsreserved
No. Instruction Comment
4 Viewing the sent data
That data are written to the
server (S7) by the client.
(M340).
7.4.2 Modicon M340 as server
The following steps describe, how to change the data of the Modicon M340. These
data will be read from the server (M340) by the client (S7). Furthermore you can
view the data which are written to the server (M340) by the client (S7).
Tabelle 7-40: Viewing the Modbus TCP server data
No. Instruction Comment
1 Open the variable table
„Animation Tables
Table“
2 In the menu bar click the
“Connect“ icon to change
to the online view.
3 Viewing the received data
That data are written to the
server (M340) by the client.
(S7).
78. Operation of the Application
Operation of Modicon M340
78 Modbus TCP Connection
V 1.0, Entry ID: 38586568
CopyrightSiemensAG2009Allrightsreserved
No. Instruction Comment
4 Viewing the sent data
That data are read from the
server (M340) by the client
(S7).
5 Switch on variable send
data
Click the button
„Modification“ and set
the variable %M5 to the
value 1.
79. Related Literature
Bibliography
Modbus TCP Connection
V 1.0, Entry ID: 38586568 79
CopyrightSiemensAG2009Allrightsreserved
8 Related Literature
8.1 Bibliography
This list is not complete and only represents a selection of relevant literature.
Table 8-41 Bibliography
Topic Title
/1/ STEP7 Automating with STEP7 in STL und SCL
Hans Berger
Publisher: Vch Pub
ISBN-10 3895783412
ISBN-13 9783895783418
8.2 Internet Links
This list is not complete and only represents a selection of relevant information.
Table 8-42 Internet links
Topic Title
1 Reference to the entry 6http://support.automation.siemens.com/WW/view/e
n/38586568
2 Siemens I IA/DT Customer
Support
6http://support.automation.siemens.com
3 Programming with STEP 7
V5.4
6http://support.automation.siemens.com/WW/view/e
n/18652056
4 Information OPEN
MODBUS / TCP
6http://support.automation.siemens.com/WW/view/e
n/22660304
5 Modbus TCP Wizard 6http://support.automation.siemens.com/WW/view/e
n/31535566
6 S7 OpenModbus/TCP
license/downloads
http://www.industry.siemens.com/industrial-
services/it/de/products/simatic_add_ons/s7_o
pen_modbus_tcp.htm
9 History
Table 9-43 History
Version Date Modifications
V1.1 29.01.2010 Second version