The increase of nonlinear loads due to the proliferation of electronic equipment causes power quality in the power system to deteriorate. Harmonic current drawn from a supply by the nonlinear load results in the distortion of the supply voltage waveform at the point of common coupling (PCC) due to the source impedance. Both distorted current and voltage may cause end-user equipment to malfunction, conductors to overheat and may reduce the efficiency and life expectancy of the equipment connected at the PCC.
Power Quality Improvement in 3-Φ Power System with Shunt Active filter using ...AI Publications
Research paper focuses on enhancement of the power quality, Harmonic reduction and Reactive power compensation . Power quality problems became the foremost important concern now a days. Active filters with synchronous detection methodologies are vividly employed in distribution system to be sure that the harmonics generated by non-linear loads is reduced and leads to less voltage distortion and leads to lesser power superiority problems. The three physical characteristics that mostly underline the power quality and a power quality issues are Voltage, Current and Frequency. Harmonics is defined as a disturbance demonstrated in current or voltage or frequency waveforms which result in devastation, or failure of final equipment ..This paper examines the control of Shunt Active Power Filter with Synchronous Detection Method . Simulation results using MATLAB SIMULINK demonstrates the application of these methods to the control of Active Power Filter . Moreover, this work shows that how the power quality improvement in 3 phase is done with Synchronous Detection Method .
Simulation and Design of SRF based Control Algorithm for Three Phase Shunt Ac...idescitation
Active power filters are effective in mitigating line
current harmonics and compensating for the reactive power
in the line. There are basically two types of Active Power
Filters (APFs): shunt type and series type. Shunt active power
filters (SAPFs) represent the most important and most widely
used filters in industrial purposes, this is due not only to the
fact that eliminate the harmonic current but also they are
suitable for a wide range of power ratings. In this paper,
Synchronous Reference Frame (SRF) theory is employed to
calculate compensating currents while the three phase source
is feeding a highly non-linear load. The main objective is to
study and investigate the performance of Shunt active power
filter using SRF theory. The algorithm is simulated under
M ATLAB
7.8
environment
using
Simulinkand
SimPowerSystems toolbox. The results shown are within the
IEEE Standard 512-1992.
IJRET : International Journal of Research in Engineering and Technology is an international peer reviewed, online journal published by eSAT Publishing House for the enhancement of research in various disciplines of Engineering and Technology. The aim and scope of the journal is to provide an academic medium and an important reference for the advancement and dissemination of research results that support high-level learning, teaching and research in the fields of Engineering and Technology. We bring together Scientists, Academician, Field Engineers, Scholars and Students of related fields of Engineering and Technology
Power System Harmonic Compensation Using Shunt Active Power FilterIJERA Editor
This paper shows the method of improving the power quality using shunt active power filter. The proposedtopic comprises of PI controller, filter hysteresis current control loop, dc link capacitor. The switching signal generation for filter is fromhysteresis current controller techniques. With the all these element shunt active power filter reduce the total harmonic distortion. Thispaper represents the simulation and analysis of the using three phase three wire system active filter to compensate harmonics .Theproposed shunt active filter model uses balanced non-linear load. This paper successfully lowers the THD within IEEE norms and satisfactorily works to compensatecurrent harmonics.
The Shunt Active Power Filter to Compensate Reactive Power and Harmonics with...ijtsrd
In this paper is to study the denomination Power quality and large refers to maintaining a proximal sinusoidal power distribution bus voltage at rated magnitude and frequency. This is mainly affected by the generation of harmonics. Even though electronic and non-linear devices are flexible, economical and energy efficient, they may degrade power quality by creating harmonic currents and consuming excessive reactive power. This paper shows the method of improving the power quality using shunt active power filter with proposed optimized PI. The proposed topic comprises of PI controller, filter hysteresis current control loop, dc link capacitor. The switching signal generation for filter is from hysteresis current controller techniques. With the all these element shunt active power filter reduce the total harmonic distortion. Its source current, compensating current and THD values are studied, then PI control strategy is applied then the differences in THD are compared. The PI feedback compensation design starts with the small signal system' transfer function. Then an optimum constant of PI for a Shunt-APF is proposed and implemented to enhance its response to compensation of harmonics of linear and non-linear loads. The obtained results have demonstrated the ability to compensate the current harmonics effectively under distorted source conditions. The fluctuation in the dc bus voltage of the filter depends on the compensation speed of the outer loop that regulates the dc bus voltage. The proposed shunt active filter model uses balanced linear and non-linear load works successfully lowers the THD within IEEE norms and satisfactorily works to compensate current harmonics. The model is made in MATLAB SIMULINK and successfully reduces the harmonic in the source current. Mr. Amit Kumar Rajan | Dr. E Vijay Kumar"The Shunt Active Power Filter to Compensate Reactive Power and Harmonics with optimized PI controller in a 3 Phase 3 Wire Distribution System" Published in International Journal of Trend in Scientific Research and Development (ijtsrd), ISSN: 2456-6470, Volume-2 | Issue-5 , August 2018, URL: http://www.ijtsrd.com/papers/ijtsrd18196.pdf http://www.ijtsrd.com/engineering/electrical-engineering/18196/the-shunt-active-power-filter-to-compensate-reactive-power-and-harmonics-with-optimized-pi-controller-in-a-3-phase-3-wire-distribution-system/mr-amit-kumar-rajan
Power Quality Improvement in 3-Φ Power System with Shunt Active filter using ...AI Publications
Research paper focuses on enhancement of the power quality, Harmonic reduction and Reactive power compensation . Power quality problems became the foremost important concern now a days. Active filters with synchronous detection methodologies are vividly employed in distribution system to be sure that the harmonics generated by non-linear loads is reduced and leads to less voltage distortion and leads to lesser power superiority problems. The three physical characteristics that mostly underline the power quality and a power quality issues are Voltage, Current and Frequency. Harmonics is defined as a disturbance demonstrated in current or voltage or frequency waveforms which result in devastation, or failure of final equipment ..This paper examines the control of Shunt Active Power Filter with Synchronous Detection Method . Simulation results using MATLAB SIMULINK demonstrates the application of these methods to the control of Active Power Filter . Moreover, this work shows that how the power quality improvement in 3 phase is done with Synchronous Detection Method .
Simulation and Design of SRF based Control Algorithm for Three Phase Shunt Ac...idescitation
Active power filters are effective in mitigating line
current harmonics and compensating for the reactive power
in the line. There are basically two types of Active Power
Filters (APFs): shunt type and series type. Shunt active power
filters (SAPFs) represent the most important and most widely
used filters in industrial purposes, this is due not only to the
fact that eliminate the harmonic current but also they are
suitable for a wide range of power ratings. In this paper,
Synchronous Reference Frame (SRF) theory is employed to
calculate compensating currents while the three phase source
is feeding a highly non-linear load. The main objective is to
study and investigate the performance of Shunt active power
filter using SRF theory. The algorithm is simulated under
M ATLAB
7.8
environment
using
Simulinkand
SimPowerSystems toolbox. The results shown are within the
IEEE Standard 512-1992.
IJRET : International Journal of Research in Engineering and Technology is an international peer reviewed, online journal published by eSAT Publishing House for the enhancement of research in various disciplines of Engineering and Technology. The aim and scope of the journal is to provide an academic medium and an important reference for the advancement and dissemination of research results that support high-level learning, teaching and research in the fields of Engineering and Technology. We bring together Scientists, Academician, Field Engineers, Scholars and Students of related fields of Engineering and Technology
Power System Harmonic Compensation Using Shunt Active Power FilterIJERA Editor
This paper shows the method of improving the power quality using shunt active power filter. The proposedtopic comprises of PI controller, filter hysteresis current control loop, dc link capacitor. The switching signal generation for filter is fromhysteresis current controller techniques. With the all these element shunt active power filter reduce the total harmonic distortion. Thispaper represents the simulation and analysis of the using three phase three wire system active filter to compensate harmonics .Theproposed shunt active filter model uses balanced non-linear load. This paper successfully lowers the THD within IEEE norms and satisfactorily works to compensatecurrent harmonics.
The Shunt Active Power Filter to Compensate Reactive Power and Harmonics with...ijtsrd
In this paper is to study the denomination Power quality and large refers to maintaining a proximal sinusoidal power distribution bus voltage at rated magnitude and frequency. This is mainly affected by the generation of harmonics. Even though electronic and non-linear devices are flexible, economical and energy efficient, they may degrade power quality by creating harmonic currents and consuming excessive reactive power. This paper shows the method of improving the power quality using shunt active power filter with proposed optimized PI. The proposed topic comprises of PI controller, filter hysteresis current control loop, dc link capacitor. The switching signal generation for filter is from hysteresis current controller techniques. With the all these element shunt active power filter reduce the total harmonic distortion. Its source current, compensating current and THD values are studied, then PI control strategy is applied then the differences in THD are compared. The PI feedback compensation design starts with the small signal system' transfer function. Then an optimum constant of PI for a Shunt-APF is proposed and implemented to enhance its response to compensation of harmonics of linear and non-linear loads. The obtained results have demonstrated the ability to compensate the current harmonics effectively under distorted source conditions. The fluctuation in the dc bus voltage of the filter depends on the compensation speed of the outer loop that regulates the dc bus voltage. The proposed shunt active filter model uses balanced linear and non-linear load works successfully lowers the THD within IEEE norms and satisfactorily works to compensate current harmonics. The model is made in MATLAB SIMULINK and successfully reduces the harmonic in the source current. Mr. Amit Kumar Rajan | Dr. E Vijay Kumar"The Shunt Active Power Filter to Compensate Reactive Power and Harmonics with optimized PI controller in a 3 Phase 3 Wire Distribution System" Published in International Journal of Trend in Scientific Research and Development (ijtsrd), ISSN: 2456-6470, Volume-2 | Issue-5 , August 2018, URL: http://www.ijtsrd.com/papers/ijtsrd18196.pdf http://www.ijtsrd.com/engineering/electrical-engineering/18196/the-shunt-active-power-filter-to-compensate-reactive-power-and-harmonics-with-optimized-pi-controller-in-a-3-phase-3-wire-distribution-system/mr-amit-kumar-rajan
presentation of Conference On Electrical And Electronic Engineering 2015sager alswed
The designed three phase SAPF based on instantaneous p-q theory was simulated in MATLAB /SIMULINK by using different load conditions i.e. R-L load, suddenly connected R-L load, and additional unbalance R load. Its application was successfully proved and the validity achieved by minimizing the harmonics and improving PF as summarized in Table 2. Consequently, the supply current is almost pure sinusoidal. THD observed was fund to be within the prescribed limits of 5% as recommended by IEEE-519 standard.
Improvement of the electric power quality usingVikram Rawani
A control algorithm for a three-phase hybrid power
filter is proposed.It is constituted by a series active filter and a passive filter connected in parallel with the load.
Performance analysis of three phase shunt hybrid active power filtereSAT Journals
Abstract Active filtering of electric power has now become a mature technology for harmonic and reactive power Compensation in AC networks. The past several years have seen a rapid increase of power electronics-based loads connected to low and medium voltage power distribution systems. These loads draw non-sinusoidal current from the mains, degrading the power quality by causing harmonic distortion. This paper proposes a three phase Shunt Hybrid Active Filter (SHAF) topology for harmonic reduction and power factor improvement in low voltage power distribution systems. The compensation current reference for the proposed SHAF topology is obtained by using synchronous reference frame theorem. This theorem simplifies the equations for the current reference estimation in d-q co-ordinates thus leading to a more efficient and fast computation. To generate the compensation current that follows the current reference, the hysteresis current control method is adopted for 2-level VSI in low voltage system, the system is verified by developing simulation model using MATLAB/Simulink simulation package and the results are presented. The performance of shunt active filter and the proposed shunt hybrid active filter topology in reducing total harmonic distortion (THD) is compared for low voltage distribution system. Keywords: SAPF, SHPF, PI control, THD, Hysteresis current pulse width modulation, D-Q reference frame theory.
IJRET : International Journal of Research in Engineering and Technology is an international peer reviewed, online journal published by eSAT Publishing House for the enhancement of research in various disciplines of Engineering and Technology. The aim and scope of the journal is to provide an academic medium and an important reference for the advancement and dissemination of research results that support high-level learning, teaching and research in the fields of Engineering and Technology. We bring together Scientists, Academician, Field Engineers, Scholars and Students of related fields of Engineering and Technology
Power Quality Improvement in Distribution System using ANN Based Shunt Active...IAES-IJPEDS
This paper focuses on an Artificial Neural Network (ANN) controller based Shunt Active Power Filter (SAPF) for mitigating the harmonics of the distribution system. To increase the performance of the conventional controller and take advantage of smart controllers, a feed forward-type (trained by a back propagation algorithm) ANN-based technique is implemented in shunt active power filters for producing the controlled pulses required for IGBT inverter. The proposed approach mainly work on the principle of capacitor energy to maintain the DC link voltage of a shunt connected filter and thus reduces the transient response time when there is abrupt variation in the load. The entire power system block set model of the proposed scheme has been developed in MATLAB environment. Simulations are carried out by using MATLAB, it is noticed that the %THD is reduced to 2.27% from 29.71% by ANN controlled filter. The simulated experimental results also show that the novel control method is not only easy to be computed and implemented, but also very successful in reducing harmonics.
Design of shunt active power filter to mitigate harmonicsager alswed
The designed three phase SAPF based on instantaneous p-q theory was simulated in MATLAB /SIMULINK by using different load conditions i.e. R-L load, suddenly connected R-L load, and additional unbalance R load. Its application was successfully proved and the validity achieved by minimizing the harmonics and improving PF as summarized in Table 2. Consequently, the supply current is almost pure sinusoidal. THD observed was fund to be within the prescribed limits of 5% as recommended by IEEE-519 standard.
Performance enhancement of shunt active power filter with fuzzy and hysteresi...Asoka Technologies
This paper proposes fuzzy and hysteresis controllers based three phase Shunt Active Power Filter
for current harmonic compensation to improve the performance of 3ɸ supply system feeding
non- linear loads. The Shunt Active Power Filter is used to eliminate current harmonics. The dc
link control strategy is based on the fuzzy logic controller. Gating pulses for the Shunt Active
Filter is generated using Hysteresis current controller based Pulse width modulation technique.
The proposed model is simulated in MATLAB/SIMULINK. Simulation results show that the
dynamic behavior is better than the conventional Proportional- Integral (PI) controller and is
found to be more robust for changes in load.
A study of hysteresis band current control scheme for shunt active power filt...Asoka Technologies
This paper gives an analysis of harmonic currents in power electronics equipment produced by nonlinear loads.. Shunt active power filters (APF) play a key role to reduce harmonics current generated by nonlinear loads. Impact of shunt active power filter (APF) for compensating the harmonics current has been examined and analyzed by using Hysteresis current control technique. In this paper, harmonic control strategy is applied to compensate the current harmonics in the system. A comparative study between PI, HCC, adaptive HCC for the harmonic current mitigation has been used using shunt active filter technique. Simulated results are analyzed using MATLAB
Harmonics created by nonlinear loads such as arc furnaces, cycloconverters and motor drives destroys the power quality in the system. They not only affect the working of adjacent loads but also shorten the life of power equipment by creating excessive losses. ‘Shunt Active Power Filter’ is a modern addition to family of compensating devices. It has superior qualities over its contemporaries namely SVCs and STATCOMs. It not only mitigates harmonics within the allowable limits defined by IEEE Std 519-1992, but also compensates unbalancing and reactive power in the system. Consequently, only active power is supplied by the source thus power factor approaches unity. A fully functional Simulink model of Shunt Active Power Filter has been designed based on ‘Instantaneous Power Theory’ or ‘p-q Theory’. The results of simulation comply with all the features described by the theory, justifying employment of SAPF in the industry.
entry level resume, i'll upload more formats
you modify it according to your skills don't add fake details because you may be trapped due to it all the best (Y)
ppt of Three phase fault analysis with auto reset for temporary fault and tri...Vikram Rawani
it's the final ppt which we have made for the project hope you will like it and make use most of it. it will definitely help you guys .
all the best (Y) :)
presentation of Conference On Electrical And Electronic Engineering 2015sager alswed
The designed three phase SAPF based on instantaneous p-q theory was simulated in MATLAB /SIMULINK by using different load conditions i.e. R-L load, suddenly connected R-L load, and additional unbalance R load. Its application was successfully proved and the validity achieved by minimizing the harmonics and improving PF as summarized in Table 2. Consequently, the supply current is almost pure sinusoidal. THD observed was fund to be within the prescribed limits of 5% as recommended by IEEE-519 standard.
Improvement of the electric power quality usingVikram Rawani
A control algorithm for a three-phase hybrid power
filter is proposed.It is constituted by a series active filter and a passive filter connected in parallel with the load.
Performance analysis of three phase shunt hybrid active power filtereSAT Journals
Abstract Active filtering of electric power has now become a mature technology for harmonic and reactive power Compensation in AC networks. The past several years have seen a rapid increase of power electronics-based loads connected to low and medium voltage power distribution systems. These loads draw non-sinusoidal current from the mains, degrading the power quality by causing harmonic distortion. This paper proposes a three phase Shunt Hybrid Active Filter (SHAF) topology for harmonic reduction and power factor improvement in low voltage power distribution systems. The compensation current reference for the proposed SHAF topology is obtained by using synchronous reference frame theorem. This theorem simplifies the equations for the current reference estimation in d-q co-ordinates thus leading to a more efficient and fast computation. To generate the compensation current that follows the current reference, the hysteresis current control method is adopted for 2-level VSI in low voltage system, the system is verified by developing simulation model using MATLAB/Simulink simulation package and the results are presented. The performance of shunt active filter and the proposed shunt hybrid active filter topology in reducing total harmonic distortion (THD) is compared for low voltage distribution system. Keywords: SAPF, SHPF, PI control, THD, Hysteresis current pulse width modulation, D-Q reference frame theory.
IJRET : International Journal of Research in Engineering and Technology is an international peer reviewed, online journal published by eSAT Publishing House for the enhancement of research in various disciplines of Engineering and Technology. The aim and scope of the journal is to provide an academic medium and an important reference for the advancement and dissemination of research results that support high-level learning, teaching and research in the fields of Engineering and Technology. We bring together Scientists, Academician, Field Engineers, Scholars and Students of related fields of Engineering and Technology
Power Quality Improvement in Distribution System using ANN Based Shunt Active...IAES-IJPEDS
This paper focuses on an Artificial Neural Network (ANN) controller based Shunt Active Power Filter (SAPF) for mitigating the harmonics of the distribution system. To increase the performance of the conventional controller and take advantage of smart controllers, a feed forward-type (trained by a back propagation algorithm) ANN-based technique is implemented in shunt active power filters for producing the controlled pulses required for IGBT inverter. The proposed approach mainly work on the principle of capacitor energy to maintain the DC link voltage of a shunt connected filter and thus reduces the transient response time when there is abrupt variation in the load. The entire power system block set model of the proposed scheme has been developed in MATLAB environment. Simulations are carried out by using MATLAB, it is noticed that the %THD is reduced to 2.27% from 29.71% by ANN controlled filter. The simulated experimental results also show that the novel control method is not only easy to be computed and implemented, but also very successful in reducing harmonics.
Design of shunt active power filter to mitigate harmonicsager alswed
The designed three phase SAPF based on instantaneous p-q theory was simulated in MATLAB /SIMULINK by using different load conditions i.e. R-L load, suddenly connected R-L load, and additional unbalance R load. Its application was successfully proved and the validity achieved by minimizing the harmonics and improving PF as summarized in Table 2. Consequently, the supply current is almost pure sinusoidal. THD observed was fund to be within the prescribed limits of 5% as recommended by IEEE-519 standard.
Performance enhancement of shunt active power filter with fuzzy and hysteresi...Asoka Technologies
This paper proposes fuzzy and hysteresis controllers based three phase Shunt Active Power Filter
for current harmonic compensation to improve the performance of 3ɸ supply system feeding
non- linear loads. The Shunt Active Power Filter is used to eliminate current harmonics. The dc
link control strategy is based on the fuzzy logic controller. Gating pulses for the Shunt Active
Filter is generated using Hysteresis current controller based Pulse width modulation technique.
The proposed model is simulated in MATLAB/SIMULINK. Simulation results show that the
dynamic behavior is better than the conventional Proportional- Integral (PI) controller and is
found to be more robust for changes in load.
A study of hysteresis band current control scheme for shunt active power filt...Asoka Technologies
This paper gives an analysis of harmonic currents in power electronics equipment produced by nonlinear loads.. Shunt active power filters (APF) play a key role to reduce harmonics current generated by nonlinear loads. Impact of shunt active power filter (APF) for compensating the harmonics current has been examined and analyzed by using Hysteresis current control technique. In this paper, harmonic control strategy is applied to compensate the current harmonics in the system. A comparative study between PI, HCC, adaptive HCC for the harmonic current mitigation has been used using shunt active filter technique. Simulated results are analyzed using MATLAB
Harmonics created by nonlinear loads such as arc furnaces, cycloconverters and motor drives destroys the power quality in the system. They not only affect the working of adjacent loads but also shorten the life of power equipment by creating excessive losses. ‘Shunt Active Power Filter’ is a modern addition to family of compensating devices. It has superior qualities over its contemporaries namely SVCs and STATCOMs. It not only mitigates harmonics within the allowable limits defined by IEEE Std 519-1992, but also compensates unbalancing and reactive power in the system. Consequently, only active power is supplied by the source thus power factor approaches unity. A fully functional Simulink model of Shunt Active Power Filter has been designed based on ‘Instantaneous Power Theory’ or ‘p-q Theory’. The results of simulation comply with all the features described by the theory, justifying employment of SAPF in the industry.
entry level resume, i'll upload more formats
you modify it according to your skills don't add fake details because you may be trapped due to it all the best (Y)
ppt of Three phase fault analysis with auto reset for temporary fault and tri...Vikram Rawani
it's the final ppt which we have made for the project hope you will like it and make use most of it. it will definitely help you guys .
all the best (Y) :)
Fault analysis on three phase system by auto reclosing mechanismeSAT Journals
Abstract In any electrical system, due to overvoltage or over current line--ground fault, line to line fault, line-line-line fault and line-line-line-ground faults occur. The electrical substation is supply the power to the consumers means industries or domestic can have failures due to any of the fault which can be temporary or permanent. These faults lead to damage to the power system equipment. In this work, effort has made to design an reclosing mechanism in case of permanent or temporary fault. The TimerIc-555 has been used to give the time duration of fault. Circuit breaker is used for disconnecting the line at fault instant and connecting on clearance of fault. Reclosing mechanism resets the supply line after small interruption in the event of temporary fault or it remains in tripped condition in case of permanent fault. Keywords: Fault Analysis, Timer 555, Auto Reclosing Mechanism
Three Phase Fault Analysis With Auto Reset On Temporary Fault And Permanent TripEdgefxkits & Solutions
This PPT explains about Three phase fault analysis. This is achieved by using star to delta conversions.
Edgefxkits.com has a wide range of electronic projects ideas that are primarily helpful for ECE, EEE and EIE students and the ideas can be applied for real life purposes as well.
http://www.edgefxkits.com/
Visit our page to get more ideas on popular electronic projects developed by professionals.
Edgefx provides free verified electronic projects kits around the world with abstracts, circuit diagrams, and free electronic software. We provide guidance manual for Do It Yourself Kits (DIY) with the modules at best price along with free shipping.
three phase fault analysis with auto reset for temporary fault and trip for p...Vikram Rawani
The project was aimed to prevent failures due to some faults which can be temporary or permanent in 3-phase power supply .
The purpose of our project was to develop an automatic tripping mechanism for the three phase supply system. The project output resets automatically after a brief interruption in the event temporary fault while it remains in tripped condition in case of permanent fault.
hey guys hello in my this upload it is of soft skills .
it will help you in cracking interviews.
so go through it because at the end you need job. so guys go for it go through it
ALL THE BEST (y) :)
What is a Smart Grid?
The Smart Grid Enables the ElectriNetSM
Local Energy Networks
Electric Transportation
Low-Carbon Central Generation
What Should Be the Attributes of the Smart Grid?
Why Do We Need a Smart Grid?
Is the Smart Grid a “Green Grid”?
Alternative Views of a Smart Grid
AUTOMATIC VOLTAGE CONTROL OF TRANSFORMER USING MICROCONTROLLER AND SCADA Ajesh Jacob
AUTOMATIC VOLTAGE CONTROL OF TRANSFORMER USING MICROCONTROLLER AND SCADA
LABVIEW PROJECT FINAL YEAR EEE
ABSTRACT: A tap changer control operates to connect appropriate tap position of winding in power transformers to maintain correct voltage level in the power transmission and distribution system. Automatic tap changing can be implemented by using µC. This improved tap-changing decision and operational flexibility of this new technique make it attractive for deployment in practical power system network. This paper deals with the implementation of µC based tap changer control practically, using special purpose digital hardware as a built-in semiconductor chip or software simulation in conventional computers. Two strategies are suggested for its implementation as a software module in the paper. One is to integrate it with the supervisory system in a substation control room operating in a LAN environment. In this configuration, the parallel transformers can be controlled locally. The other is to integrate it into the SCADA (Supervisory Control and Data Acquisition) system, which allows the transformers to be monitored and controlled remotely over a wide area of power-network. The implementation of µC based tap changer control needs interfacing between the power system and the control circuitry. µC s may need to interact with people for the purpose of configuration, alarm reporting or everyday control.
A human-machine interface (HMI) is employed for this purpose. An HMI is usually linked to the SCADA system’s databases and software programs, to provide trending, diagnostic data, and management information such as scheduled maintenance procedures, logistic information, detailed schematics for a particular sensor or machine, and expert-system troubleshooting guides.
OBJECTIVES: The original system can afford the following features:
- Complete information about the plant (circuit breakers status, source of feeding, and level of the consumed power).
- Information about the operating values of the voltage, operating values of the transformers, operating values of the medium voltage, load feeders, operating values of the generators. These values will assist in getting any action to return the plant to its normal operation by minimum costs.
- Information about the quality of the system (harmonics, current, voltages, power factors, flickers, etc.). These values will be very essential in case of future correction.
- Recorded information such case voltage spikes, reducing the voltage on the medium or current interruption.
- implementation of µC based tap changer control practically, using special purpose digital hardware as a built-in semiconductor chip or software simulation in conventional computers.
SIMULATION OF CASCADED H- BRIDGE MULTILEVEL INVERTER USING PD, POD, APOD TECH...ecij
Multilevel inverter (MLI) can achieve medium voltage high power efficiency inverters in industrial
application. It can generate stepped waveform by reducing harmonic distortion with increase in the
number of voltage level; a full bridge is known as H-bridge inverter because it shows alphabet ‘H’. In this
paper, Multicarrier PWM topologies and there Modulation schemes are discussed. Level Shifted [LS]
Scheme is applied to the Cascade H-bridge multilevel inverter and the complete analysis of THD to 9 levels
is done.
Engineering review on AC Power.
Presentation lecture for energy engineering class.
Course: MS in Renewable Energy Engineering, Oregon institute of technology
Analysis of Power Factor Improvement Techniques in case of Non Linear System ...Kaustubh Nande
The presentation provides a brief overview of the technology employed to eliminate the power factor reduction caused by non linear loads in the network.
Mitigation of the Harmonics under Reactive Power Compensation by SHPF-TCR Usi...IJERA Editor
In this paper, a combined system of a thyristor-controlled reactor (TCR) and a shunt hybrid power filter
(SHPF)has been designed by MATLAB/SIMULINK approach for harmonic and reactive power compensation.
The quality of the power is effected by many factors like harmonic contamination, due to the increment of nonlinear
loads, sag and swell due to the switching of the loads etc. Also control schemes based on PI and Fuzzy
logic controllers have been proposed to mitigate the harmonics and neutral current . The proposed methodology
not only reduces the complexity but also offers simplicity to implement and increases reliability of the system.
These control strategies also help in achieving a low cost highly effective control. The performance is also
observed under influence of utility side disturbances such as harmonics, flicker and spikes with Non-Linear and
Reactive Loads with different control strategies.
International Journal of Engineering Research and Applications (IJERA) is an open access online peer reviewed international journal that publishes research and review articles in the fields of Computer Science, Neural Networks, Electrical Engineering, Software Engineering, Information Technology, Mechanical Engineering, Chemical Engineering, Plastic Engineering, Food Technology, Textile Engineering, Nano Technology & science, Power Electronics, Electronics & Communication Engineering, Computational mathematics, Image processing, Civil Engineering, Structural Engineering, Environmental Engineering, VLSI Testing & Low Power VLSI Design etc.
A New Topology for Power Quality Improvement using 3-Phase 4-Wire UPQC with R...IJMTST Journal
This paper introduces a new concept of optimal utilization of a Unified power quality conditioner (UPQC).
The series inverter of UPQC is controlled to perform simultaneous Methods: voltage sag/swell compensation
and load reactive power sharing with the shunt inverter. The active power control approach is used to
compensate voltage sag/swell and is integrated with theory of power angle control (PAC) of UPQC to
coordinate the load reactive power between the two inverters. MATLAB/SIMULINK-based simulation results
are discussed to support the developed concept. Finally, the proposed UPQC concept is validated.
IJERA (International journal of Engineering Research and Applications) is International online, ... peer reviewed journal. For more detail or submit your article, please visit www.ijera.com
Harmonic Compensation for Non Linear Load Using PWM Based Active Filteridescitation
In this paper the elimination of the current harmon-
ics of injected by nonlinear loads is investigated. The active
power filter proposed in this study is a Single phase voltage
source inverter (VSI) connecting to the AC mains. The dspic
controller is used to control the operation of the switches of
the inverter. Active filtering is achieved through PWM in-
verter connected next to a given nonlinear load or at the point
of the common coupling (PCC). The simulation results show
that how well the filter eliminates the harmonics of the source
current.
In This paper we present experimental comparative study of feedBack Linearized and Proportional Integral (PI) Controller of the DC bus voltage of three phase shunt Active Power Filter (APF). The FeedBack Linearized and PI controllers are introduced to improve tracking performance characteristics, power quality and minimized consumption of the reactive power. The algorithm used to identify the reference currents is based on the Self Tuning Filter (STF). The firing pulses of the IGBTs inverter are generated using a hysteresis current controller; which is implemented on an analogue card. Finally, the above study, under steady state and transient conditions, is illustrated with signal-flow graphs and corresponding analysis. This study was verified by experimental tests on hardware prototype based on dSPACE-1104. The experimental results show the feasibility and the effectiveness of the designed active filter, associated with Feedback Linearized and PI controllers and are capability in meeting the IEEE 519-1992 recommended harmonic standard limits.
Comparative of Conventional and Intelligence Controller based Hybrid Generati...IJERD Editor
Harmonic pollution of the power supply system has risen significantly in recent years due primarily
to an increase of non-linear loads connected to the utility through residential, commercial and industrial
customers. This paper, proposed a solution to eliminate the harmonics introduced by the nonlinear loads in
steady and in transients. It presents a predictive current control strategy for achieving maximum benefits from
these grid-interfacing inverters implementing conventional DC link controller and intelligence controller, when
installed in 3-phase 4-leg voltage source inverter (VSI). The inverter is controlled to perform as a multi-function
device by incorporating active power filter functionality. The use of a four-leg voltage-source inverter allows
the compensation of current harmonic components, as well as unbalanced current generated by three-phase
nonlinear loads. Renewable energy resources (RES) are being increasingly connected in distribution systems
utilizing power electronic converters. The compensation performance of the proposed active power filter and the
associated hybrid PV/Wind system generation scheme with new control scheme is demonstrated to improve the
power quality features is simulated using MATLAB/SIMULINK.
Power Quality Improvement by UPQC based on Voltage Source ConvertersIJRST Journal
In modern power system consists of wide range of electrical, electronic and power electronic equipment in commercial and industrial applications. Since most of the electronic equipment’s are nonlinear in nature these will induce harmonics in the system, which affect the sensitive loads to be fed from the system. These problems are partially solved with the help of LC passive filters. However, this kind of filter cannot solve random variation in the load current wave form and voltage wave form. Active filters can resolve this problem. However, the cost of active filters is high. They are difficult to implement in large scale. Additionally, they also present lower efficiency than shunt passive filters. One of the many solutions is the use of a combined system of shunt and active series filters like Unified Power Quality Conditioner (UPQC) which aims at achieving a low cost under highly effective control. The UPQC device combines a shunt active filter together with a series active filter in a back-to-back configuration, to simultaneously compensate the supply voltage and the load current or to mitigate any type of voltage and current fluctuations and power factor correction in a power distribution network, such that improved power quality can be made available at the point of common coupling. The control strategies are modeled using MATLAB/SIMULINK. The performance is also observed under influence of utility side disturbances such as harmonics and voltage sags. The simulation results are compared without and with UPQC for the verification of results.
https://jst.org.in/index.html
Our journal has envision the collaborative future we're creating—one where engineering, management, science, and mathematics harmonize to shape a world defined by innovation and progress. Numbers tell stories, and in the world of research and development, mathematics is the universal language.
A Shunt Active Power Filter for 12 Pulse Converter Using Source Current Detec...IAES-IJPEDS
A shunt Active Power Filter (APF) with current detection at the source side
is considered as a closed-loop system from the view of the whole power
distribution system, which is expected with better harmonics filtering
performance compared with conventional current detection methods such as
load current detection and open loop control. This paper introduces an
efficient source current detection method (direct) control scheme to mitigate
the grid current harmonics generated by the twelve pulse converter. The
proposed system uses Control Rectifier (12 –pulse converter) which
efficiently regulates the DC voltage by varying the angle of each 6 pulse
converter. Moreover, the proposed system uses three winding transformer
which eliminates the harmonics during equal angles switching at each six
pulse converter which in turn simplifies the operation of the SAPF. The
proposed system is simulated in MATLAB SIMULINK to evaluate the
performance of the proposed system.
Power Flow Control In A Transmission Line Using Unified Power Flow ControllerIJMER
This paper concentrates on FACT device UPFC which is used for powerflow control in the
transmission side. With the growing demand of electricity, it is not possible to erect new lines to face the
situation. Flexible AC Transmission System (FACTS) makes use of the thyristor controlled devices and optimally
utilizes the existing transmission network. One of such device is Unified Power Flow Controller (UPFC) on
which the emphasis is given in this present work. Real, reactive power, and voltage balance of the unified
power-flow control (UPFC) system is analyzed. A novel coordination controller is proposed for the UPFC.
The basic control method is such that the shunt converter controls the transmission line reactive power
flow and the dc-link voltage. The series converter controls the real power flow in the transmission line and
the UPFC bus voltages. Experimental works have been conducted to verify the effectiveness of the
UPFC in power flow control in the transmission line. The simulation model was done in
MATLAB/SIMULINK platform.
NOVEL CONTROL STRATEGIES FOR DISTRIBUTED ACTIVE FILTER elelijjournal
ABSTRACT
This paper describes the implementation of Distributed Active Filters (DAFs). To share the workload of harmonic filtering, several Active Filter Units (AFUs) are placed on different locations which can perform the harmonic filtering without a direct communication. Different configurations of DAFs are described and are implemented using MATLAB /Simpower system Toolbox environment to observe their performances and comparison.
KEYWORDS
Distributed Active Filters (DAFs), Power Quality, Total Harmonic Distortion
Closed Loop Non Linear Control of Shunt Hybrid Power Filter for Harmonics Mit...IAES-IJPEDS
In recent years, the amount of non-linear loads has increased considerably since there were improvements in power electronic equipment (such as adjustable speed drives or converter ac-dc, ac-ac, dc-ac and dc-dc) in industrial sectors which cause deterioration of the quality of the electric power supply through distortion of supply voltage and supply current. This has led to improvement of many stringent needs regarding generation of harmonic current, which are found in IEEE519 and IEC61000 standards. This paper proposes a non-linear function based closed loop control strategy (without load current extraction) for three-phase Shunt Active Power Line Conditioner and LC passive filter to compensate harmonics, power factor improvement and enhance the dynamic performance of Shunt Hybrid Power Filter (SHPF). By using a PI controller the DC bus voltage of the Shunt Active Power Filter is maintained constant. Results obtained from simulation shows the performance of expected hybrid filter in transient and steady state operation . This indicates that the controller is able to compensate even under severe load current imbalances.
Similar to report of Improvement of the Electric Power Quality Using Series Active and Shunt Passive Filters (20)
Welcome to WIPAC Monthly the magazine brought to you by the LinkedIn Group Water Industry Process Automation & Control.
In this month's edition, along with this month's industry news to celebrate the 13 years since the group was created we have articles including
A case study of the used of Advanced Process Control at the Wastewater Treatment works at Lleida in Spain
A look back on an article on smart wastewater networks in order to see how the industry has measured up in the interim around the adoption of Digital Transformation in the Water Industry.
CFD Simulation of By-pass Flow in a HRSG module by R&R Consult.pptxR&R Consult
CFD analysis is incredibly effective at solving mysteries and improving the performance of complex systems!
Here's a great example: At a large natural gas-fired power plant, where they use waste heat to generate steam and energy, they were puzzled that their boiler wasn't producing as much steam as expected.
R&R and Tetra Engineering Group Inc. were asked to solve the issue with reduced steam production.
An inspection had shown that a significant amount of hot flue gas was bypassing the boiler tubes, where the heat was supposed to be transferred.
R&R Consult conducted a CFD analysis, which revealed that 6.3% of the flue gas was bypassing the boiler tubes without transferring heat. The analysis also showed that the flue gas was instead being directed along the sides of the boiler and between the modules that were supposed to capture the heat. This was the cause of the reduced performance.
Based on our results, Tetra Engineering installed covering plates to reduce the bypass flow. This improved the boiler's performance and increased electricity production.
It is always satisfying when we can help solve complex challenges like this. Do your systems also need a check-up or optimization? Give us a call!
Work done in cooperation with James Malloy and David Moelling from Tetra Engineering.
More examples of our work https://www.r-r-consult.dk/en/cases-en/
Final project report on grocery store management system..pdfKamal Acharya
In today’s fast-changing business environment, it’s extremely important to be able to respond to client needs in the most effective and timely manner. If your customers wish to see your business online and have instant access to your products or services.
Online Grocery Store is an e-commerce website, which retails various grocery products. This project allows viewing various products available enables registered users to purchase desired products instantly using Paytm, UPI payment processor (Instant Pay) and also can place order by using Cash on Delivery (Pay Later) option. This project provides an easy access to Administrators and Managers to view orders placed using Pay Later and Instant Pay options.
In order to develop an e-commerce website, a number of Technologies must be studied and understood. These include multi-tiered architecture, server and client-side scripting techniques, implementation technologies, programming language (such as PHP, HTML, CSS, JavaScript) and MySQL relational databases. This is a project with the objective to develop a basic website where a consumer is provided with a shopping cart website and also to know about the technologies used to develop such a website.
This document will discuss each of the underlying technologies to create and implement an e- commerce website.
Industrial Training at Shahjalal Fertilizer Company Limited (SFCL)MdTanvirMahtab2
This presentation is about the working procedure of Shahjalal Fertilizer Company Limited (SFCL). A Govt. owned Company of Bangladesh Chemical Industries Corporation under Ministry of Industries.
Overview of the fundamental roles in Hydropower generation and the components involved in wider Electrical Engineering.
This paper presents the design and construction of hydroelectric dams from the hydrologist’s survey of the valley before construction, all aspects and involved disciplines, fluid dynamics, structural engineering, generation and mains frequency regulation to the very transmission of power through the network in the United Kingdom.
Author: Robbie Edward Sayers
Collaborators and co editors: Charlie Sims and Connor Healey.
(C) 2024 Robbie E. Sayers
Hybrid optimization of pumped hydro system and solar- Engr. Abdul-Azeez.pdffxintegritypublishin
Advancements in technology unveil a myriad of electrical and electronic breakthroughs geared towards efficiently harnessing limited resources to meet human energy demands. The optimization of hybrid solar PV panels and pumped hydro energy supply systems plays a pivotal role in utilizing natural resources effectively. This initiative not only benefits humanity but also fosters environmental sustainability. The study investigated the design optimization of these hybrid systems, focusing on understanding solar radiation patterns, identifying geographical influences on solar radiation, formulating a mathematical model for system optimization, and determining the optimal configuration of PV panels and pumped hydro storage. Through a comparative analysis approach and eight weeks of data collection, the study addressed key research questions related to solar radiation patterns and optimal system design. The findings highlighted regions with heightened solar radiation levels, showcasing substantial potential for power generation and emphasizing the system's efficiency. Optimizing system design significantly boosted power generation, promoted renewable energy utilization, and enhanced energy storage capacity. The study underscored the benefits of optimizing hybrid solar PV panels and pumped hydro energy supply systems for sustainable energy usage. Optimizing the design of solar PV panels and pumped hydro energy supply systems as examined across diverse climatic conditions in a developing country, not only enhances power generation but also improves the integration of renewable energy sources and boosts energy storage capacities, particularly beneficial for less economically prosperous regions. Additionally, the study provides valuable insights for advancing energy research in economically viable areas. Recommendations included conducting site-specific assessments, utilizing advanced modeling tools, implementing regular maintenance protocols, and enhancing communication among system components.
block diagram and signal flow graph representation
report of Improvement of the Electric Power Quality Using Series Active and Shunt Passive Filters
1. Improvement of the Electric Power Quality Using
Series Active and Shunt Passive Filters
REVA INSTITUTE OF TECHNOLOGY AND MANAGEMENT Page 1
CHAPTER 1
INTRODUCTION
INTRODUCTION
The increase of nonlinear loads due to the proliferation of electronic equipment causes power
quality in the power system to deteriorate. Harmonic current drawn from a supply by the
nonlinear load results in the distortion of the supply voltage waveform at the point of
common coupling (PCC) due to the source impedance. Both distorted current and voltage
may cause end-user equipment to malfunction, conductors to overheat and may reduce the
efficiency and life expectancy of the equipment connected at the PCC.
Harmonics and reactive power regulation and guidelines are upcoming issues and
increasingly being adopted in distributed power system and industries. Vital use of power
electronic appliances has made power management smart, flexible and efficient. But side by
side they are leading to power pollution due to injection of current and voltage harmonics.
Harmonic pollution creates problems in the integrated power systems. The researchers and
engineers have started giving effort to apply harmonic regulations through guidelines of IEEE
519-1992. Very soon customers have to pay and avail the facility for high performance, high
efficiency, energy saving, reliable, and compact power electronics technology. It is expected
that the continuous efforts by power electronics researchers and engineers will make it
possible to absorb the increased cost for solving the harmonic pollution. The thyristor
controlled reactors of various network configurations are widely used in industries and utility
systems for harmonic mitigation and dynamic power factor correction. These thyristor
controlled reactor operate as a variable reactance in both the inductive and capacitive
domains. By means these two parameters two types of problems are normally encountered.
The first problem is the reactive power (Var) that leads to poor power factor and the
harmonics appears due to presence of power converter devices and nonlinear loads for
example, electrics machines, fluctuating industrial loads, such as electric arc furnaces, rolling
mills, power converters etc. These types of heavy industrial loads are normally concentrated
in one plant and served from one network terminal, and therefore, can be handled best by a
local compensator connected to the same terminal.
The main emphasis of the investigation has been on compactness of configurations,
simplicity in control, reduction in rating of components, thus finally leading to saving in
overall cost. Based on these considerations, a wide range of configurations of power quality
mitigators are developed for providing a detailed exposure to the design engineer in selection
of a particular configuration for a specific application under the given constraints of economy
and the desired performance. Fig 1.1 shows a classical shunt passive filter is connected the
2. Improvement of the Electric Power Quality Using
Series Active and Shunt Passive Filters
REVA INSTITUTE OF TECHNOLOGY AND MANAGEMENT Page 2
power system through common coupling point (PCC). Because of using non-linear load, the
load current is highly non-linear in nature. The compensating current which is the output of
the shunt passive filter is injected in PCC, by this process the harmonic cancellation take
place and current between the sources is sinusoidal in nature. The passive filter is popular in
cancellation of harmonic current in power system.
Fig.1.1 The Classical Shunt Passive Filter.
To control this process, there are two ways i.e.
(i)Harmonic extraction technique
(ii)Current modulator
1.1.2 Harmonic Extraction
The harmonic extraction is the process in which, reference current is generated by using the
distorted waveform. Many theories have been developed such as p-q theory (instantaneous
reactive power theory), d-q theory, P-I controller, adaptive controller etc. Out of these
theories more than 60% research works have been consider p-q theory and d-q theory due to
their accuracy, robustness and easy calculation.
1.1.3 Current Modulator
Current modulator mainly provides the gate pulse to the ac-dc converter. There may be many
techniques used for giving the gate signals to PWM VSI or CSI such as sinusoidal PWM,
triangular PWM etc. The above described two control techniques (harmonic extraction
technique and current modulator technique) are main research foci of many researchers in
recent years. It may be noted that either harmonics extraction technique or the current
modulator can be used individually or both at a time. Apart from these two techniques, most
of the research works are directed also in dealing with multi-level rectifier control problems.
3. Improvement of the Electric Power Quality Using
Series Active and Shunt Passive Filters
REVA INSTITUTE OF TECHNOLOGY AND MANAGEMENT Page 3
1.2 SERIES ACTIVE POWER FILTER Series APF are operated mainly as a voltage
regulator and a harmonic isolator between the nonlinear load and the utility system. The
series connected filter protects benefit the consumer from an inadequate supply voltage
quality. This type of approach is mostly recommended for compensation of voltage
unbalances and voltage sags from the AC supply and for low applications and represents
economically attractive alternatives to utility power system, since no energy storage is energy
and the overall ratings of the components is smaller. The advantages of series active power
are- automatic compensation for varying loads, resonance free, does not affect power factor
and can be combined with passive filter network. inverter. The output of the series active
power filter is connected to the main lines through series transformers so as to make the load
voltage purely sinusoidal the harmonic voltage is absorbed or injected by the filter.
Fig.1.2 Circuit Configuration of Series active power filter (APF).
4. Improvement of the Electric Power Quality Using
Series Active and Shunt Passive Filters
REVA INSTITUTE OF TECHNOLOGY AND MANAGEMENT Page 4
2.1 Traditionally, a passive LC power filter is used to eliminate current harmonics when it is
connected in parallel with the load. This compensation equipment has some drawbacks due to
which the passive filter cannot provide a complete solution. These disadvantages are mainly
the following.
The compensation characteristics heavily depend on the system impedance because the filter
impedance has to be smaller than the source impedance in order to eliminate source current
harmonics. Overloads can happen in the passive filter due to the circulation of harmonics
coming from nonlinear loads connected near the connection point of the passive filter. They
are not suitable for variable loads, since, on one hand, they are designed for a specific
reactive power, and on the other hand, the variation of the load impedance can detune the
filter. Series and/or parallel resonances with the rest of the system can appear.
Fig. 2.1 Series active filter and parallel passive filter.
An active power filter, APF, typically consists of a threephase pulsewidth modulation (PWM)
voltage source inverter. When this equipment is connected in series to the ac source
impedance it is possible to improve the compensation characteristics of the passive filters in
parallel connection. This topology is shown in Fig. 2.1, where the active filter is represented
by a controlled source, where Vc is the voltage that the inverter should generate to achieve
the objective of the proposed control algorithm.
5. Improvement of the Electric Power Quality Using
Series Active and Shunt Passive Filters
REVA INSTITUTE OF TECHNOLOGY AND MANAGEMENT Page 5
Different techniques have been applied to obtain a control signal for the active filter One such
is the generation of a voltage proportional to the source current harmonics. With this control
algorithm, the elimination of series and/or parallel resonances with the rest of the system is
possible. The active filter can prevent the passive filter becoming a harmonics drain on the
close loads. Additionally, it can prevent the compensation features depending on the system
impedance. From the theoretical point of view, the ideal situation would be that the
proportionality constant, k, between the active filter output voltage and source current
harmonics, had a high value. However, at the limit this would be an infinite value and would
mean that the control objective was impossible to achieve. The chosen k value is usually
small so as to avoid high power active filters and instabilities in the system. However, the
choice of the appropriate k value is an unsolved question since it is related to the passive
filter and the source impedance values. Besides, this strategy is not suitable for use in systems
with variable loads because the passive filter reactive power is constant, and therefore, the set
compensation equipment and load has a variable power factor. In another proposed control
technique, the APF generates a voltage waveform similar to the voltage harmonics at the load
side but in opposition. This strategy only prevents the parallel passive filter depending on the
source impedance; the other limitations of the passive filter nevertheless remain.
Fig. 2.2 Transformation from the phase reference system (abc) to the 0αβ system.
6. Improvement of the Electric Power Quality Using
Series Active and Shunt Passive Filters
REVA INSTITUTE OF TECHNOLOGY AND MANAGEMENT Page 6
Fig. 3.1. Three-phase system.
3.THE DUAL INSTANTANEOUS REACTIVE POWER THEORY
The instantaneous reactive power theory is the most widely used as a control strategy for the
APF. It is mainly applied to Fig. 3. Three-phase system. compensation equipment in parallel
connection. This theory is based on a Clarke coordinate transformation from the phase
coordinates (see Fig. 2.2).
In a three-phase system such as that presented in Fig.3, voltage and current vectors can be
defined by
The vector transformations from the phase reference system a-b-c to α-β-0 coordinates can be
obtained, thus
The instantaneous real power in the α-β-0 frame is calculated as follows:
7. Improvement of the Electric Power Quality Using
Series Active and Shunt Passive Filters
REVA INSTITUTE OF TECHNOLOGY AND MANAGEMENT Page 7
Fig 3.2. Dual instantaneous power theory
In this case, the nonlinear load consists of an uncontrolled three-phase rectifier with an
inductance of 55 mH and a 25 resistor connected in series on the dc side. Fig. 7 shows the
phase “a” load current. The load current total harmonics distortion (THD) is 18.6% and the
power factor 0.947, when the system is not compensated. The 5th and 7th harmonics are the
most important in the current waveform. They are 16.3% and 8.4% of the fundamental
harmonic, respectively. Two LC branches were connected to mitigate the fifth and seventh
harmonics. The source current waveform with the passive filter connected is shown in Fig. 8.
The THD falls to 4.7%. The 5th and 7th harmonics decrease to 3.6% and 0.9%, respectively.
8. Improvement of the Electric Power Quality Using
Series Active and Shunt Passive Filters
REVA INSTITUTE OF TECHNOLOGY AND MANAGEMENT Page 8
4. SIMULATION RESULTS
The system shown in Fig. 6 has been simulated in the Matlab- Simulink platform to verify the
proposed control. Each power device has been modeled using the SimPowerSystem toolbox
library. The power circuit is a three-phase system supplied by a sinusoidal balanced three-
phase 100-V source with a source inductance of 5.8 mH and a source resistance of 3.6ohm.
The inverter consists of an Insulated Gate Bipolar Transistor (IGBT) bridge. On the dc side,
two 100-V dc sources are connected. An LC filter has been included to eliminate the high
frequency components at the output of the inverter. This set is connected to the power system
by means of three single-phase transformers with a turn ratio of 1:1.
Fig. 4. Series active power and passive filter topology.
The passive filter is constituted by two LC branches tuned to the fifth and seventh harmonics.
Each element value is included in Table I.
9. Improvement of the Electric Power Quality Using
Series Active and Shunt Passive Filters
REVA INSTITUTE OF TECHNOLOGY AND MANAGEMENT Page 9
CHAPTER 2
RESULTS AND DISCUSSIONS
Here simulation has been carried out for series active, shunt active, shunt passive, filters, by
using MATLAB SIMULINK.FFT analysis is done, THD is observed for various circuits.
Fig 5.FTT analysis of compensating voltage wave form
Fig 6: Representation of each and every harmonic
10. Improvement of the Electric Power Quality Using
Series Active and Shunt Passive Filters
REVA INSTITUTE OF TECHNOLOGY AND MANAGEMENT Page 10
Fig 7: FFT analysis of compensating current.
. Fig 8: FFT analysis of Compensating voltage wave form at PCC
11. Improvement of the Electric Power Quality Using
Series Active and Shunt Passive Filters
REVA INSTITUTE OF TECHNOLOGY AND MANAGEMENT Page 11
Simulation
Output waveform
12. Improvement of the Electric Power Quality Using
Series Active and Shunt Passive Filters
REVA INSTITUTE OF TECHNOLOGY AND MANAGEMENT Page 12
CHAPTER 3
CONCLUSION & REFERENCE
CONCLUSION
A control algorithm for a hybrid power filter constituted by a series active filter and a
passive filter connected in parallel with the load is proposed. The control strategy is
based on the dual vectorial theory of electric power. The new control approach
achieves the following targets. The compensation characteristics of the hybrid
compensator do not depend on the system impedance. The set hybrid filter and load
presents a resistive behavior. This fact eliminates the risk of overload due to the
current harmonics of nonlinear loads close to the compensated system.
This compensator can be applied to loads with random power variation as it is not
affected by changes in the tuning frequency of the passive filter. Furthermore, the
reactive power variation is compensated by the active filter. Series and/or parallel
resonances with the rest of the system are avoided because compensation equipment
and load presents resistive behavior. Therefore, with the proposed control algorithm,
the active filter improves the harmonic compensation features of the passive filter and
the power factor of the load.
REFERENCES
Author(s)
1. P.Salmeron
Electric Engineering Department, Huelva Univ., Huelva, Spain
S. P. Litran
2. F. Z. Peng and D. J. Adams, “Harmonics sources and filtering approaches,in Proc.
Industry Applications Conf., Oct. 1999, vol. 1, pp. 448–455.
3. J. C. Das, “Passive filters-potentialities and limitations,” IEEE Trans. Ind. Appli., vol.
40, no. 1, pp. 232–241, Jan. 2004.
4. H. L. Ginn, III and L. S. Czarnecki, “An optimization based method for selection of
resonant harmonic filter branch parameters,” IEEE Trans.Power Del., vol. 21, no. 3,
pp. 1445–1451, Jul. 2006.
5. ieeexplore.ieee.org/iel5/61/5437451/05361356.pdf?arnumber.
6. www.ijmer.com
Feb. 2004.