Performance Evaluation of Synchronous
Generator under Sudden Loss of Excitation
1
Sohorab Hossain, 2
Subimal Roy Burman, 3
Sourish Sanyal, 4
Amaranth Sanyal,
5
Raju Basak
1
MCKV Institute of Engineering, 2
Additional Chief Engineer, WBSETCL, 3
Assoc. Professor, Techno India College,
4
Professor, CIEM, Kolkata, 5
Research Scholar, Jadavpur University
Abstract: Synchronous generators under sudden loss of excitation behave as an induction generator, supplying
active power to the system and absorbing reactive power from the system. In general the armature current exceeds
its rated value. Hence, the reference power is reduced in steps to keep the armature currents within limits. The
voltage profile around the faulty machine becomes unacceptably poor and in addition there is exchange of
pulsating power with the system. Hence, the general practice is to switch off the machine by the action of an offset
type MHO-relay. Recently, the capacitive VAR-generation of a H.T. system has gone up due to addition of
EHV/SHV lines, such that there is no or little problem in supplying the faulty machine with its required VAR.
Also, the magnetizing current drawn by modern turbo generators has reduced much due to the use of smaller air-
gaps for economic design of the rotor. The combined effect has been assessed, and it has been found that it is
permissible to run the machine for a relatively long duration under LOE without staking on its health. It may be
allowed to run the machine for 30-60 minutes under LOE, within which time the fault may be detected and
removed and the machine resynchronized. However, this is not possible for hydro-generators drawing large
magnetizing currents.
Keywords: Synchronous generator, Governor Action, Newton-Raphson method, Excitation system, Loss of
excitation, Mho-relay.
Symbols, abbreviation and subscripts:
,E V Induced voltage, Infinite bus voltage
,g aV I  Generator terminal voltage, armature
current
,d qX X D-axis/ Q-axis synchronous reactance
,md fX x D-axis magnetizing reactance, field
leakage reactance
,ax  Armature leakage reactance, angular
frequency in r/s
'
dX D-axis transient reactance
" "
,d qX X D-axis/Q-axis sub-transient reactance
,e er X External resistance, leakage reactance to
infinite bus
' '
,d doT T D-axis S.C./ O.C. transient time constant.
" "
,d doT T D-axis S.C./ O.C. sub transient time
constant
" "
,q qoT T Q-axis S.C./ O.C. sub transient time
constant
,f dr r Field/ field discharge resistance
,ref uP R Reference power-setting, Static droop
, ,P P P
s r
Total, synchronous, reluctance power
,as asT I Asynchronous torque/ current
,as asP Q Asynchronous active/reactive power
,s Power angle, slip
D,Q Direct/ quadrature
S.C./O.C. Short circuit/ open circuit
 Angle of lag of current behind voltage
ISSN 2349-7815
International Journal of Recent Research in Electrical and Electronics Engineering (IJRREEE)
Vol. 3, Issue 4, pp: (7-13), Month: October - December 2016, Available at: www.paperpublications.org
Page | 8
Paper Publications
1. INTRODUCTION TO LOE PHENOMENA
A synchronous generator is forced to asynchronous operation under sudden loss of excitation. Operation under LOE has
many undesirable effects e.g. thermal injury of the faulted machine, poor voltage profile in its neighbourhood, pulsations
in voltage and power etc. [1,2,3]. These effects are more pronounced for a salient pole hydrogenerator compared to a
cylindrical pole turbogenerator [1,4]. The equivalent circuit parameters of the 210 MW turbogenerator set of BHEL have
been computed [5,6]. Then it has been equivalenced with the generator transformer. On the basis of one machine on
infinite bus, the parameters and the time constants of the equivalenced machine have been modified [7,8] . Then the
machine variables under asynchronous condition have been computed. A comparison has been made between the field
directly short-circuited and the same closed through a properly chosen value of discharge resistance. It has been found
that the use of discharge resistance is beneficial, but the relay operates even in its absence.
2. BAD EFFECTS OF L.O.E. ON THE MACHINE AND THE SYSTEM
The undesirable and damaging effects of operating a generator under loss of excitation are listed below:
a) The alternator runs at a leading power factor. It draws large amount of reactive power from the system for its
excitation. The generator bus voltage cannot be held fixed- the bus gets converted to load bus with negative value of
active power.
b) The resulting stator current may be more than rated- its value depends on the network conditions and the bus voltage.
The over-current gives rise to overheating and thermal injury.
c) The reactive power burden on the neighbouring generators becomes very high. They run at a poor lagging power
factor, provided there is no capacitive support or FACTS-devices for the rescue.
d) Large amount of reactive power flows through the transmission links causing voltage dips in the neighbourhood of
the faulty machine. It makes the voltage profile unacceptable.
e) Loss of excitation is associated with exchange of pulsating power with the system due to saliency effect. It also
creates pulsation in voltage and slip.
f) The tip of the impedance phasor of the machine flies off from 1st
. quadrant to 4th
. quadrant. It can be sensed by
admittance relays and protective actions taken.
These effects are more pronounced for the salient pole hydro-alternators compared to turbo-alternators.
For all these reasons, the general practice is to shut down the generator on occurrence of loss of excitation. The bulk
power system reliability is adversely affected on L.O.E. of a generator, provided there is no reactive power support. Load
flow studies on the L.O.E.-faulted system of W.B. power grid revealed that the voltage collapse and resulting instability
could be avoided only against large scale capacitive support. But now the scenario has somewhat changed due to addition
of highly capacitive long EHV lines in our grid system. Asynchronous operation for a short time may be continued
without any capacitive support. Hence sufficient time delay can be given to the admittance relay without any risk.
3. CAPABILITY OF TURBO-GENERATOR SETS TO OPERATE UNDER LOE
The turbo-generators manufactured by BHEL are capable of sustained operation under LOE for limited time. On
occurrence of an L.O.E.-fault, the company has instructed to do the following:
 To disconnect the field circuit from the source immediately and short-circuit it, preferably through a discharge
resistance of appropriate value.
 To reduce the asynchronous power to 60% of rated power within 30 sec.
 To reduce it further to 40% within 90 sec.
 To continue for 15-20 minutes under asynchronous condition and try to resynchronize.
ISSN 2349-7815
International Journal of Recent Research in Electrical and Electronics Engineering (IJRREEE)
Vol. 3, Issue 4, pp: (7-13), Month: October - December 2016, Available at: www.paperpublications.org
Page | 9
Paper Publications
 To switch off the faulty machine, in case of failure to resynchronize within this time.
Following these instructions, the analysis has been made at first with field short-circuited directly and then short-circuited
through a discharge resistance. The reference power-setting has been reduced to 0.6 p.u. within 30 second and then
reduced further to 0.4 p.u. within 90 second.
4. THE MATHEMATICAL MODEL
The electromagnetically developed power in a synchronous generator connected to infinite bus is given as:
2
( / )sin ( / 2)(1/ 1/ )sin(2 )s r d q dP P P EV X V X X      (1)
Under L.O.E., the synchronous power falls to zero almost immediately. The relatively small reluctance power fails to
retain synchronism. The rotor gradually speeds up and eventually settles at a steady negative slip. The average slip is
determined by the reference power setting, the static droop and the machine parameters. A cyclic variation of slip is
superposed on it due to saliency. This is associated with exchange of pulsating power and current with the system at
double the line frequency (also at power frequency if the loss of excitation is partial). In terms of operational impedance
of an alternator, the average asynchronous torque is given as:
2
1 1
Re
2 ( ) ( )
as
d o q o
V
T
jX js jX js 
 
  
  
(2)
and the asynchronous active power is given as: (1 )as asP s T  (3)
The reactive power of the system is given as:
2
1 1
Im
2 ( ) ( )
as
d o q o
V
Q
jX js jX js 
 
  
  
(4)
It is not an easy task to calculate the asynchronous variables from this expression. Breaking up into fractions, we get a
more workable expression as given below:
"' "2
' ' 2 " ' " 2 " " 2
1 1 1 1 1 1
(1 )
2 1 ( ) 1 ( ) 1 ( )
qd d
as
d d d d d d q q q
TT TV
P s s
X X sT X X sT X X sT
     
                      
(5)
The corresponding value of the reactive power is given by the following expression (time constants are in radians):
" 2' 2 " 22
' ' 2 " ' " 2 " " 2
( )( ) ( )1 1 1 1 1 1
.
2 1 ( ) 1 ( ) 1 ( )
qd d
as
d d d d d d q q q
sTsT sTV
Q
X X sT X X sT X X sT
     
                       (6)
5. THE EFFECT OF TURBINE-GOVERNOR
The turbine-governor is set with a reference power by the speeder gear and a static droop which may vary from 3 to 4%.
Under synchronous condition, as refP P , where refP is the active power setting of the turbine-governor. But under
asynchronous condition, we have:
/as ref uP P s R  (7)
Now, the expression reduces to the following form:
( ) / 0as ref uf s P P s R    (8)
This equation can be solved by applying numerical methods like that of Newton-Raphson to find out the slip for specified
value of the active power (appendix-1).
ISSN 2349-7815
International Journal of Recent Research in Electrical and Electronics Engineering (IJRREEE)
Vol. 3, Issue 4, pp: (7-13), Month: October - December 2016, Available at: www.paperpublications.org
Page | 10
Paper Publications
6. INFINITE BUS ASSUMPTION - EFFECT OF SERIES REACTANCE AND DISCHARGE
RESISTANCE
As the rating of the machine is not comparable to the grid power, we treat it as one machine on infinite bus connected
through series impedance. The series impedance is the sum of the impedance of the transformer and that of the short
transmission line (if any) connecting the machine to the grid system. The line capacitance is neglected for a short line.
The schematic diagram of the idealized machine is given in fig. 1.
Fig. 1. A generator connected to infinite bus through a transformer and a transmission line
The effect of series impedance to infinite is beneficial as it reduces the magnetizing VAR drawn from the system. But it
also reduces the terminal voltage of the machine and hence increases the slip for a given reference power. It gives rise to
an increment in reactive power which partly offsets the saving in reactive power due to lower magnetizing current. The
series reactance modifies the reactances of the machine and the short-circuit time constants. The discharge resistance also
modifies the d-axis open circuit and short-circuits transient time constants. The resultant expressions are given below:
' ' " " " "
; ; ; ;de d e qe q e de d e de d e qe q eX X X X X X X X X X X X X X X          (9)
' ' ' " " ' " " " ' "
' ' ' ' '
" " " ' " " "
. / ; . / ; . / ;
. / ( ) ; . / ;
. / ; . /
do d d d do d d d qo q q q
dom do f f d d dom de de
d do de de q qo qe qe
T T X X T T X X T T X X
T T r r r T T X X
T T X X T T X X
  
  
 
(10)
The generator terminal voltage is given as:
( )g a e eV V I r jX    (11)
The voltage is normally depressed under LOE, to such an extent that under voltage relays may trip at many buses.
7. CASE-STUDIES ON ASYNCHRONOUS OPERATION
Now we shall undertake a no. of case studies on asynchronous variables under sudden loss of excitation. The alternator
under LOE is assumed to be on infinite bus through its transformer.
This programme computes asynchronous. torque and power for varying input voltage and fixed ref. power of BANDEL
TPS 5th unit, using N-R method. All quantities are in p.u. & time constants in sec. All quantities refer to the equivalent
machine including the generator transformer. The first case-study is being made for LOE with 60% power and the second
case study is being made for LOE with 40% rated power. The computer print outs converted to word-format are given
below:
The parameters and time constants:
Leakage reactance, ax = 0.152
D-axis syn. Reactance, dX = 2.3616
ISSN 2349-7815
International Journal of Recent Research in Electrical and Electronics Engineering (IJRREEE)
Vol. 3, Issue 4, pp: (7-13), Month: October - December 2016, Available at: www.paperpublications.org
Page | 11
Paper Publications
D-axis transient reactance, '
dX = 0.4416
D-axis subtransient reactance, "
dX = 0.3506
Q-axis syn. Reactance, qX = 2.2466
Q-axis subtransient reactance, "
qX = 0.4476
D-axis open circuit transient time constant, '
doT =0.7778
D-axis s.c. transient time constant, '
dT =0.1454
D-axis s.c. subtransient time constant, "
dT =0.1369
Q-axis short circuit subtransient time constant, "
qT = 0.1195407
Synchronous speed = 314.2 r/s
Reactance to infinite bus, eX = 0.1366
Discharge resistance, dR = 4 fr
Static droop in p.u., uR = 0.04
Case-I: The reference torque (or power) has been set at 60% of rated power = 0.6 x 0.85 = 0.51 p.u. by speeder gear
within 30 sec from the occurrence of fault and may be continued up to 90 sec.
Table-1: Reference torque = 0.51 p.u. asP (60% of rated power) (from 30 to 90 sec.)
Slip s Terminal
Voltage V
Asyn. reactive
Power QAS
Asyn apparent
power SAS
Asyn current
SAS
Pulsating power
Ppul
0.00344 1.00 0.62276 0.80494 0.80494 0.31929
0.00364 0.98 0.61588 0.79963 0.81595 0.32069
0.00386 0.96 0.61041 0.79543 0.82857 0.32225
0.00411 0.94 0.60569 0.79181 0.84235 0.32339
0.00440 0.92 0.60376 0.79033 0.85905 0.32539
0.00472 0.9 0.60335 0.79002 0.87780 0.32721
0.00512 0.88 0.60653 0.79245 0.90051 0.32987
0.00559 0.86 0.61259 0.79710 0.92686 0.33258
0.00618 0.84 0.62359 0.80558 0.95903 0.33593
0.00696 0.82 0.64163 0.81963 0.99955 0.33999
0.00803 0.8 0.66830 0.84067 1.050840 0.34397
Case-II The reference torque (or power) has been set at 40% of rated power = 0.4 x 0.85 = 0.34 p.u. by speeder gear
within 90 sec from the occurrence of fault and may be continued up to breaker operation..
Table- 2 : Reference power = 0.34 p.u. (40% of rated power) (after 90 sec.)
Slip s Terminal
Voltage V
Asyn. reactive
Power QAS
Asyn apparent
power SAS
Asyn current
SAS
Pulsating power
Ppul
0.00211 1.00 0.51306 0.61549 0.61549 0.20883
0.00221 0.98 0.49962 0.60434 0.61667 0.20932
0.00232 0.96 0.48675 0.59374 0.61848 0.20975
0.00242 0.94 0.47394 0.58329 0.62052 0.20954
0.00255 0.92 0.46250 0.57403 0.62394 0.21015
0.00270 0.90 0.45185 0.56548 0.62831 0.21084
ISSN 2349-7815
International Journal of Recent Research in Electrical and Electronics Engineering (IJRREEE)
Vol. 3, Issue 4, pp: (7-13), Month: October - December 2016, Available at: www.paperpublications.org
Page | 12
Paper Publications
0.00285 0.88 0.44198 0.55762 0.63366 0.21155
0.00301 0.86 0.43235 0.55003 0.63957 0.21174
0.00320 0.84 0.42438 0.54378 0.64736 0.21266
0.00341 0.82 0.41719 0.53189 0.65633 0.21342
0.0036 0.80 0.40822 0.53126 0.66408 0.21201
It may be noted from table-1 that the rating has not been exceeded for 60% of rated power except for V = 0.8 p.u. Such
an under-voltage is not likely to occur. From table-2 it may be noted that the asynchronous variables are well within
limits. Therefore, the instruction of BHEL may be followed to limit the power cut-off for at least half-an-hour safely.
8. CONCLUSION
The computation of asynchronous torque and power for a given load and a given terminal voltage is a formidable task. It
can be made by breaking up the formula for asynchronous power and applying computer iterative techniques to them. We
have used the Newton-Raphson method which fast converges to the solution.
It has been noted that a turbo generator under LOE-fault is quite safe at 60% of rated power for limited time and at 40%
power of rated power for unlimited time. Therefore, the instruction of BHEL to continue power supply under
asynchronous mode of operation for 20-30 minutes is quite justified. If the fault cannot be removed within this time then
the machine is to be switched off, as the pulsating power exchange and low voltage profile around the faulty machine is
not acceptable from the power quality point of view.
However, it is not admissible for hydro generators as the asynchronous variables are much larger for them, particularly
the pulsating power. So they must be switched off within 2-3 minutes.
By running turbo generators under LOE for some time, we can reduce the extent of load-shedding. This is possible only if
the system is rich in capacitive VARs, such that the voltage profile is not extremely poor..
REFERENCES
[1] A.N. Sanyal, S. Chowdhuri, and S. RoyBurman, “Effect of loss of excitation in interconnected power system”, CPRI
conference paper, 1988, IISC, Bangalore
[2] S.K. Sen, “Electric machinery, Khanna Publishers.
[3] A.Maity, K. Bhattacharya, A.N. Sanyal, “Asynchronous operation of synchronous generators under field failure",
IEEE Xplore, 2014, Digital Object Identifier: 10.1109/ACES.2014.6808006, Print ISBN: 978-1-4799- 3893-3, pp
1-6.
[4] P.M. Anderson and A.A. Fouad, “Power system control and stability”,Galgotia Publications.
[5] Literatures on 210 MW and 500 MW turbo generator sets published by BHEL.
[6] P.S.R. Murti, “Modeling of power system elements”, B.S. Publications.
[7] B. Adkins and R.G. Harley, “Generalized theory of A.C. machines”, Book, Chapman and Hall.
[8] V. Venikov, “Transient processes in electric power system”, Book, MIR Publishers.
[9] V. Rajaraman, “Computer-oriented numerical methods”, Prentice Hall of India.
[10] D.P. Kothari, I.J. Nagrath, “Power system engineering”, 2nd
. Ed., TMH
[11] P.J. Moore, A. Stangenberg, “An investigation into the impedance characteristics of a synchronous generator under
loss of excitation condition”, EMPD '98, 2 (1998), 619–624
[12] R. Conrad, St. Pierre, “Loss-of-excitation protection for synchronous generators on isolated systems”, IEEE
Transactions on Industry Applications, IA-21, 1985, No. 1
ISSN 2349-7815
International Journal of Recent Research in Electrical and Electronics Engineering (IJRREEE)
Vol. 3, Issue 4, pp: (7-13), Month: October - December 2016, Available at: www.paperpublications.org
Page | 13
Paper Publications
[13] J. Berdy, “Loss of excitation protection for modern synchronous generators”, IEEE Trans. on Power Apparatus and
Systems, 94, pp. 1457 – 1463, 1975
[14] L. Li, S. Caixin, M. Daohuai, “Study on the excitation protection and control of synchronous generator based on the
δ and s”, IEEE/PES(2005), 1–4
[15] D.C. Lee, P. Kundur, R.D. Brown, “A high speed discriminating generator loss of excitation protection”, IEEE
Transactions on Power Apparatus and Systems, PAS-98, 1979
[16] J. Berdy, “Loss of excitation protection for modern synchronous generators”, Schenectady, New York.
[17] P. Mahdi et al (University of Tehran, Iran) “Generator loss of field and its effects on voltage stability in power
systems”, paper no. O-130, International conference on Electrical Engineering, 2008.
APPENDIX - A
Algorithm:
Algorithm for numerical solution of eqn. 5 using Newton-Raphson method is given below:
Step-1:
' " " ' " "
Re , , , , , , , , , , , , , ,ref d d d q q d d q f d e uad P V X X X X X T T T f r r X R
Step-2:
' ' " " " "
; ; ; ;de d e qe q e de d e de d e qe q eX X X X X X X X X X X X X X X         
Step-3:
' ' ' " " ' " " " ' " ' '
. / ; . / ; . / ; . / ( )do d d d do d d d qo q q q dom do f f dT T X X T T X X T T X X T T r r r    
Step-4:
' ' ' " " " ' " " "
. / ; . / ; . /d dom de de d do de de q qo qe qeT T X X T T X X T T X X  
Step-5:
2 ' ' 2 " " ' 2 " "
1 2 3(1/ 1/ ) / 2; (1/ 1/ ) / 2; (1/ 1/ ) / 2d de de d de de q qe qek V T X X k V T X X k V T X X     
Step-6: max, .,max. . : , ,Initializeslip convergenceconst no of iteration s n
Step-7: 31 2
' 2 " 2 " 2
/ (1 )
1 ( ) 1 ( ) 1 ( )
ref u
d d q
kk k
f P s R s s
sT sT sT
 
       
    
Step-8:
" 2' 2 " 2
3' 1 2
' 2 2 " 2 2 " 2 2
{1 2 ( ) }{1 2 ( ) } {1 2 ( ) }
1/
{1 ( ) } {1 ( ) } {1 ( ) }
qd d
u
d d q
k s sTk s sT k s sT
f R
sT sT sT
     
    
    
Step-9
'
/news s f f 
Step-10
14newIf s s then goto step 
Step-11 1count count 
Step-12 max 19If count n then goto step
Step-13 : 7news s goto step
Step-14 news s
Step-15 31 2
' 2 " 2 " 2
(1 )
1 ( ) 1 ( ) 1 ( )
as
d d q
kk k
P s s
sT sT sT
 
    
    
Step-16
"' "
31 2
' 2 " 2 " 2
1 ( ) 1 ( ) 1 ( )
qd d
as
d d q
k sTk sT k sT
Q s
sT sT sT
 
   
    
Step-17 2 2 1/2
( ) ; /as as as as asS P Q I S V  
Step-18 , , , , : 20as as as asprint s P Q S I goto step
Step-19 max' ' . .Noconvergencein n noof iterations Try againchanging initial value
Step-20 :stop end

More Related Content

What's hot

Estimation of Synchronous Generator Parameters from On-line Measurements
Estimation of Synchronous Generator Parameters from On-line MeasurementsEstimation of Synchronous Generator Parameters from On-line Measurements
Estimation of Synchronous Generator Parameters from On-line MeasurementsMohammadHasanmosadde
 
Generator Set Transient Performance
Generator Set Transient PerformanceGenerator Set Transient Performance
Generator Set Transient Performancemichaeljmack
 
Generator basic concepts
Generator basic conceptsGenerator basic concepts
Generator basic conceptsmichaeljmack
 
Sizing generators-for-leading-power-factor white-paper-24_feb14
Sizing generators-for-leading-power-factor white-paper-24_feb14Sizing generators-for-leading-power-factor white-paper-24_feb14
Sizing generators-for-leading-power-factor white-paper-24_feb14Insanul Aziz
 
Excitation System & capability curve of synchronous generator
Excitation System &  capability curve of synchronous generatorExcitation System &  capability curve of synchronous generator
Excitation System & capability curve of synchronous generatorMANOJ KUMAR MAHARANA
 
Lectures synchronous machines(1)
Lectures synchronous machines(1)Lectures synchronous machines(1)
Lectures synchronous machines(1)Leela Marigowda
 
Scherbius drive of electrical machines
Scherbius drive of electrical machinesScherbius drive of electrical machines
Scherbius drive of electrical machinesemredurna
 
DETERMINATION OF VOLTAGE REGULATION METHOD OF SYNCHRONOUS MACHINE
DETERMINATION OF VOLTAGE REGULATION METHOD OF SYNCHRONOUS MACHINEDETERMINATION OF VOLTAGE REGULATION METHOD OF SYNCHRONOUS MACHINE
DETERMINATION OF VOLTAGE REGULATION METHOD OF SYNCHRONOUS MACHINEvishalgohel12195
 
Automatic synch of gen
Automatic synch of genAutomatic synch of gen
Automatic synch of genmichaeljmack
 
Autotransformer and three phase transformer
Autotransformer and three phase transformerAutotransformer and three phase transformer
Autotransformer and three phase transformerRitu Rajan
 
A survey on Single Phase to Three Phase Cyclo-Converter fed Induction Motor
A survey on Single Phase to Three Phase Cyclo-Converter fed Induction MotorA survey on Single Phase to Three Phase Cyclo-Converter fed Induction Motor
A survey on Single Phase to Three Phase Cyclo-Converter fed Induction MotorIJSRD
 
Infinite bus bar in power system
Infinite bus bar in power systemInfinite bus bar in power system
Infinite bus bar in power systemEklavya Sharma
 
Overview of custom power devices
Overview of custom power devicesOverview of custom power devices
Overview of custom power devicesRaja Adapa
 
Single and three phase Transformers
Single and three phase TransformersSingle and three phase Transformers
Single and three phase TransformersMohammed Waris Senan
 

What's hot (20)

Estimation of Synchronous Generator Parameters from On-line Measurements
Estimation of Synchronous Generator Parameters from On-line MeasurementsEstimation of Synchronous Generator Parameters from On-line Measurements
Estimation of Synchronous Generator Parameters from On-line Measurements
 
Generator Set Transient Performance
Generator Set Transient PerformanceGenerator Set Transient Performance
Generator Set Transient Performance
 
Generator basic concepts
Generator basic conceptsGenerator basic concepts
Generator basic concepts
 
Sizing generators-for-leading-power-factor white-paper-24_feb14
Sizing generators-for-leading-power-factor white-paper-24_feb14Sizing generators-for-leading-power-factor white-paper-24_feb14
Sizing generators-for-leading-power-factor white-paper-24_feb14
 
RGPV EX503 UNIT III
RGPV EX503 UNIT IIIRGPV EX503 UNIT III
RGPV EX503 UNIT III
 
Excitation System & capability curve of synchronous generator
Excitation System &  capability curve of synchronous generatorExcitation System &  capability curve of synchronous generator
Excitation System & capability curve of synchronous generator
 
Lec # 01 synch generator introduction
Lec # 01 synch generator introductionLec # 01 synch generator introduction
Lec # 01 synch generator introduction
 
Lectures synchronous machines(1)
Lectures synchronous machines(1)Lectures synchronous machines(1)
Lectures synchronous machines(1)
 
Scherbius drive of electrical machines
Scherbius drive of electrical machinesScherbius drive of electrical machines
Scherbius drive of electrical machines
 
DETERMINATION OF VOLTAGE REGULATION METHOD OF SYNCHRONOUS MACHINE
DETERMINATION OF VOLTAGE REGULATION METHOD OF SYNCHRONOUS MACHINEDETERMINATION OF VOLTAGE REGULATION METHOD OF SYNCHRONOUS MACHINE
DETERMINATION OF VOLTAGE REGULATION METHOD OF SYNCHRONOUS MACHINE
 
Lec # 02 speed of rotation & internal generated voltage
Lec # 02 speed of rotation & internal generated voltageLec # 02 speed of rotation & internal generated voltage
Lec # 02 speed of rotation & internal generated voltage
 
Automatic synch of gen
Automatic synch of genAutomatic synch of gen
Automatic synch of gen
 
EMEC-II, unit 1
EMEC-II, unit 1EMEC-II, unit 1
EMEC-II, unit 1
 
Autotransformer and three phase transformer
Autotransformer and three phase transformerAutotransformer and three phase transformer
Autotransformer and three phase transformer
 
A survey on Single Phase to Three Phase Cyclo-Converter fed Induction Motor
A survey on Single Phase to Three Phase Cyclo-Converter fed Induction MotorA survey on Single Phase to Three Phase Cyclo-Converter fed Induction Motor
A survey on Single Phase to Three Phase Cyclo-Converter fed Induction Motor
 
Infinite bus bar in power system
Infinite bus bar in power systemInfinite bus bar in power system
Infinite bus bar in power system
 
Static kramer system
Static kramer systemStatic kramer system
Static kramer system
 
Lec # 03 equivalent circuit of a synchronous generator
Lec # 03 equivalent circuit of a synchronous generatorLec # 03 equivalent circuit of a synchronous generator
Lec # 03 equivalent circuit of a synchronous generator
 
Overview of custom power devices
Overview of custom power devicesOverview of custom power devices
Overview of custom power devices
 
Single and three phase Transformers
Single and three phase TransformersSingle and three phase Transformers
Single and three phase Transformers
 

Viewers also liked

Study and Simulation of Inccond Based Maximum Power Point Tracking (MPPT) Alg...
Study and Simulation of Inccond Based Maximum Power Point Tracking (MPPT) Alg...Study and Simulation of Inccond Based Maximum Power Point Tracking (MPPT) Alg...
Study and Simulation of Inccond Based Maximum Power Point Tracking (MPPT) Alg...paperpublications3
 
Study of Secondary Arc Current Suppression Effects under Different Fault Loca...
Study of Secondary Arc Current Suppression Effects under Different Fault Loca...Study of Secondary Arc Current Suppression Effects under Different Fault Loca...
Study of Secondary Arc Current Suppression Effects under Different Fault Loca...paperpublications3
 
AC-AC RESONANT BOOST CONVERTER FOR INDUCTION HEATING WITH CLOSED LOOP CONTROL
AC-AC RESONANT BOOST CONVERTER FOR INDUCTION HEATING WITH CLOSED LOOP CONTROLAC-AC RESONANT BOOST CONVERTER FOR INDUCTION HEATING WITH CLOSED LOOP CONTROL
AC-AC RESONANT BOOST CONVERTER FOR INDUCTION HEATING WITH CLOSED LOOP CONTROLpaperpublications3
 
A DUAL SWITCH BOOST CONVERTER WITH HIGH VOLTAGE GAIN
A DUAL SWITCH BOOST CONVERTER WITH HIGH VOLTAGE GAINA DUAL SWITCH BOOST CONVERTER WITH HIGH VOLTAGE GAIN
A DUAL SWITCH BOOST CONVERTER WITH HIGH VOLTAGE GAINpaperpublications3
 
An Overview of Different PWM Techniques to Reduce Total Harmonic Distortion o...
An Overview of Different PWM Techniques to Reduce Total Harmonic Distortion o...An Overview of Different PWM Techniques to Reduce Total Harmonic Distortion o...
An Overview of Different PWM Techniques to Reduce Total Harmonic Distortion o...paperpublications3
 
Investigating the Feasibility of Solar Wind Hybrid Systems for Off-Grid Rural...
Investigating the Feasibility of Solar Wind Hybrid Systems for Off-Grid Rural...Investigating the Feasibility of Solar Wind Hybrid Systems for Off-Grid Rural...
Investigating the Feasibility of Solar Wind Hybrid Systems for Off-Grid Rural...paperpublications3
 
Design of Compensator for Roll Control of Towing Air-Crafts
Design of Compensator for Roll Control of Towing Air-CraftsDesign of Compensator for Roll Control of Towing Air-Crafts
Design of Compensator for Roll Control of Towing Air-Craftspaperpublications3
 
POWER FACTOR IMPROVEMENT OF INDUSTRIAL LOAD BY MATLAB SIMULATION
POWER FACTOR IMPROVEMENT OF INDUSTRIAL LOAD BY MATLAB SIMULATIONPOWER FACTOR IMPROVEMENT OF INDUSTRIAL LOAD BY MATLAB SIMULATION
POWER FACTOR IMPROVEMENT OF INDUSTRIAL LOAD BY MATLAB SIMULATIONpaperpublications3
 
Design and Development of DVR model Using Fuzzy Logic Controller for Voltage ...
Design and Development of DVR model Using Fuzzy Logic Controller for Voltage ...Design and Development of DVR model Using Fuzzy Logic Controller for Voltage ...
Design and Development of DVR model Using Fuzzy Logic Controller for Voltage ...paperpublications3
 
Coilgun: Simulation and Analysis
Coilgun: Simulation and AnalysisCoilgun: Simulation and Analysis
Coilgun: Simulation and Analysispaperpublications3
 
Single-Stage Reluctance Type Coilgun
Single-Stage Reluctance Type CoilgunSingle-Stage Reluctance Type Coilgun
Single-Stage Reluctance Type Coilgunpaperpublications3
 
Analysis of Voltage Sag on Power Distribution Networks with Different Transfo...
Analysis of Voltage Sag on Power Distribution Networks with Different Transfo...Analysis of Voltage Sag on Power Distribution Networks with Different Transfo...
Analysis of Voltage Sag on Power Distribution Networks with Different Transfo...paperpublications3
 
A Comparative Analysis of MPWM & SPWM Techniques to Reduce Harmonic Distortio...
A Comparative Analysis of MPWM & SPWM Techniques to Reduce Harmonic Distortio...A Comparative Analysis of MPWM & SPWM Techniques to Reduce Harmonic Distortio...
A Comparative Analysis of MPWM & SPWM Techniques to Reduce Harmonic Distortio...paperpublications3
 
A Comparative Study of Various AC-DC Converters for Low Voltage Energy Harves...
A Comparative Study of Various AC-DC Converters for Low Voltage Energy Harves...A Comparative Study of Various AC-DC Converters for Low Voltage Energy Harves...
A Comparative Study of Various AC-DC Converters for Low Voltage Energy Harves...paperpublications3
 
A new approach for Reducing Noise in ECG signal employing Gradient Descent Me...
A new approach for Reducing Noise in ECG signal employing Gradient Descent Me...A new approach for Reducing Noise in ECG signal employing Gradient Descent Me...
A new approach for Reducing Noise in ECG signal employing Gradient Descent Me...paperpublications3
 
Bridgeless CUK Power Factor Corrector with Regulated Output Voltage
Bridgeless CUK Power Factor Corrector with Regulated Output VoltageBridgeless CUK Power Factor Corrector with Regulated Output Voltage
Bridgeless CUK Power Factor Corrector with Regulated Output Voltagepaperpublications3
 
Sign Language Recognition Using Image Processing For Mute People
Sign Language Recognition Using Image Processing For Mute PeopleSign Language Recognition Using Image Processing For Mute People
Sign Language Recognition Using Image Processing For Mute Peoplepaperpublications3
 
A Comparative Study of GA tuned and PSO tuned PI Controller Based Speed Contr...
A Comparative Study of GA tuned and PSO tuned PI Controller Based Speed Contr...A Comparative Study of GA tuned and PSO tuned PI Controller Based Speed Contr...
A Comparative Study of GA tuned and PSO tuned PI Controller Based Speed Contr...paperpublications3
 
Improved Spider Algorithm for Solving Optimal Reactive Power Dispatch Problem
Improved Spider Algorithm for Solving Optimal Reactive Power Dispatch ProblemImproved Spider Algorithm for Solving Optimal Reactive Power Dispatch Problem
Improved Spider Algorithm for Solving Optimal Reactive Power Dispatch Problempaperpublications3
 
The Harmonic Mitigation in Induction Furnace Using Hybrid Filter
The Harmonic Mitigation in Induction Furnace Using Hybrid FilterThe Harmonic Mitigation in Induction Furnace Using Hybrid Filter
The Harmonic Mitigation in Induction Furnace Using Hybrid Filterpaperpublications3
 

Viewers also liked (20)

Study and Simulation of Inccond Based Maximum Power Point Tracking (MPPT) Alg...
Study and Simulation of Inccond Based Maximum Power Point Tracking (MPPT) Alg...Study and Simulation of Inccond Based Maximum Power Point Tracking (MPPT) Alg...
Study and Simulation of Inccond Based Maximum Power Point Tracking (MPPT) Alg...
 
Study of Secondary Arc Current Suppression Effects under Different Fault Loca...
Study of Secondary Arc Current Suppression Effects under Different Fault Loca...Study of Secondary Arc Current Suppression Effects under Different Fault Loca...
Study of Secondary Arc Current Suppression Effects under Different Fault Loca...
 
AC-AC RESONANT BOOST CONVERTER FOR INDUCTION HEATING WITH CLOSED LOOP CONTROL
AC-AC RESONANT BOOST CONVERTER FOR INDUCTION HEATING WITH CLOSED LOOP CONTROLAC-AC RESONANT BOOST CONVERTER FOR INDUCTION HEATING WITH CLOSED LOOP CONTROL
AC-AC RESONANT BOOST CONVERTER FOR INDUCTION HEATING WITH CLOSED LOOP CONTROL
 
A DUAL SWITCH BOOST CONVERTER WITH HIGH VOLTAGE GAIN
A DUAL SWITCH BOOST CONVERTER WITH HIGH VOLTAGE GAINA DUAL SWITCH BOOST CONVERTER WITH HIGH VOLTAGE GAIN
A DUAL SWITCH BOOST CONVERTER WITH HIGH VOLTAGE GAIN
 
An Overview of Different PWM Techniques to Reduce Total Harmonic Distortion o...
An Overview of Different PWM Techniques to Reduce Total Harmonic Distortion o...An Overview of Different PWM Techniques to Reduce Total Harmonic Distortion o...
An Overview of Different PWM Techniques to Reduce Total Harmonic Distortion o...
 
Investigating the Feasibility of Solar Wind Hybrid Systems for Off-Grid Rural...
Investigating the Feasibility of Solar Wind Hybrid Systems for Off-Grid Rural...Investigating the Feasibility of Solar Wind Hybrid Systems for Off-Grid Rural...
Investigating the Feasibility of Solar Wind Hybrid Systems for Off-Grid Rural...
 
Design of Compensator for Roll Control of Towing Air-Crafts
Design of Compensator for Roll Control of Towing Air-CraftsDesign of Compensator for Roll Control of Towing Air-Crafts
Design of Compensator for Roll Control of Towing Air-Crafts
 
POWER FACTOR IMPROVEMENT OF INDUSTRIAL LOAD BY MATLAB SIMULATION
POWER FACTOR IMPROVEMENT OF INDUSTRIAL LOAD BY MATLAB SIMULATIONPOWER FACTOR IMPROVEMENT OF INDUSTRIAL LOAD BY MATLAB SIMULATION
POWER FACTOR IMPROVEMENT OF INDUSTRIAL LOAD BY MATLAB SIMULATION
 
Design and Development of DVR model Using Fuzzy Logic Controller for Voltage ...
Design and Development of DVR model Using Fuzzy Logic Controller for Voltage ...Design and Development of DVR model Using Fuzzy Logic Controller for Voltage ...
Design and Development of DVR model Using Fuzzy Logic Controller for Voltage ...
 
Coilgun: Simulation and Analysis
Coilgun: Simulation and AnalysisCoilgun: Simulation and Analysis
Coilgun: Simulation and Analysis
 
Single-Stage Reluctance Type Coilgun
Single-Stage Reluctance Type CoilgunSingle-Stage Reluctance Type Coilgun
Single-Stage Reluctance Type Coilgun
 
Analysis of Voltage Sag on Power Distribution Networks with Different Transfo...
Analysis of Voltage Sag on Power Distribution Networks with Different Transfo...Analysis of Voltage Sag on Power Distribution Networks with Different Transfo...
Analysis of Voltage Sag on Power Distribution Networks with Different Transfo...
 
A Comparative Analysis of MPWM & SPWM Techniques to Reduce Harmonic Distortio...
A Comparative Analysis of MPWM & SPWM Techniques to Reduce Harmonic Distortio...A Comparative Analysis of MPWM & SPWM Techniques to Reduce Harmonic Distortio...
A Comparative Analysis of MPWM & SPWM Techniques to Reduce Harmonic Distortio...
 
A Comparative Study of Various AC-DC Converters for Low Voltage Energy Harves...
A Comparative Study of Various AC-DC Converters for Low Voltage Energy Harves...A Comparative Study of Various AC-DC Converters for Low Voltage Energy Harves...
A Comparative Study of Various AC-DC Converters for Low Voltage Energy Harves...
 
A new approach for Reducing Noise in ECG signal employing Gradient Descent Me...
A new approach for Reducing Noise in ECG signal employing Gradient Descent Me...A new approach for Reducing Noise in ECG signal employing Gradient Descent Me...
A new approach for Reducing Noise in ECG signal employing Gradient Descent Me...
 
Bridgeless CUK Power Factor Corrector with Regulated Output Voltage
Bridgeless CUK Power Factor Corrector with Regulated Output VoltageBridgeless CUK Power Factor Corrector with Regulated Output Voltage
Bridgeless CUK Power Factor Corrector with Regulated Output Voltage
 
Sign Language Recognition Using Image Processing For Mute People
Sign Language Recognition Using Image Processing For Mute PeopleSign Language Recognition Using Image Processing For Mute People
Sign Language Recognition Using Image Processing For Mute People
 
A Comparative Study of GA tuned and PSO tuned PI Controller Based Speed Contr...
A Comparative Study of GA tuned and PSO tuned PI Controller Based Speed Contr...A Comparative Study of GA tuned and PSO tuned PI Controller Based Speed Contr...
A Comparative Study of GA tuned and PSO tuned PI Controller Based Speed Contr...
 
Improved Spider Algorithm for Solving Optimal Reactive Power Dispatch Problem
Improved Spider Algorithm for Solving Optimal Reactive Power Dispatch ProblemImproved Spider Algorithm for Solving Optimal Reactive Power Dispatch Problem
Improved Spider Algorithm for Solving Optimal Reactive Power Dispatch Problem
 
The Harmonic Mitigation in Induction Furnace Using Hybrid Filter
The Harmonic Mitigation in Induction Furnace Using Hybrid FilterThe Harmonic Mitigation in Induction Furnace Using Hybrid Filter
The Harmonic Mitigation in Induction Furnace Using Hybrid Filter
 

Similar to Performance Evaluation of Synchronous Generator under Sudden Loss of Excitation

Evaluation of reactances and time constants of synchronous generator
Evaluation of reactances and time constants of synchronous generatorEvaluation of reactances and time constants of synchronous generator
Evaluation of reactances and time constants of synchronous generatoreSAT Publishing House
 
C0212014018
C0212014018C0212014018
C0212014018theijes
 
[1339309 x journal of electrical engineering] loss of excitation of synchro...
[1339309 x   journal of electrical engineering] loss of excitation of synchro...[1339309 x   journal of electrical engineering] loss of excitation of synchro...
[1339309 x journal of electrical engineering] loss of excitation of synchro...Abraham Kv
 
Active and Reactive Power control operation of DFIG forWind Power Generation ...
Active and Reactive Power control operation of DFIG forWind Power Generation ...Active and Reactive Power control operation of DFIG forWind Power Generation ...
Active and Reactive Power control operation of DFIG forWind Power Generation ...IOSR Journals
 
Electrical Machines - II
Electrical Machines - IIElectrical Machines - II
Electrical Machines - IIkarthi1017
 
Short circuit test in brief
Short circuit test in briefShort circuit test in brief
Short circuit test in briefMuthar Hussain
 
symmetrical_fault_analysis.pdf
symmetrical_fault_analysis.pdfsymmetrical_fault_analysis.pdf
symmetrical_fault_analysis.pdfShanmukhSaiR
 
IRJET- PI Controller based Shunt Connected Three Phase Active Power Filter
IRJET- PI Controller based Shunt Connected Three Phase Active Power FilterIRJET- PI Controller based Shunt Connected Three Phase Active Power Filter
IRJET- PI Controller based Shunt Connected Three Phase Active Power FilterIRJET Journal
 
Armature reaction and parallel operation of a Syncronous generator
Armature reaction and parallel operation of a Syncronous generatorArmature reaction and parallel operation of a Syncronous generator
Armature reaction and parallel operation of a Syncronous generatorkarthi1017
 
New Microsoft Word Document
New Microsoft Word DocumentNew Microsoft Word Document
New Microsoft Word DocumentBarunava Sikdar
 
Improved Control Strategy for Low Voltage Ride Through Capability of DFIG wit...
Improved Control Strategy for Low Voltage Ride Through Capability of DFIG wit...Improved Control Strategy for Low Voltage Ride Through Capability of DFIG wit...
Improved Control Strategy for Low Voltage Ride Through Capability of DFIG wit...ecij
 
H7 SHORT-CIRCUIT EMERSON EDUARDO RODRIGUES.pdf
H7 SHORT-CIRCUIT EMERSON EDUARDO RODRIGUES.pdfH7 SHORT-CIRCUIT EMERSON EDUARDO RODRIGUES.pdf
H7 SHORT-CIRCUIT EMERSON EDUARDO RODRIGUES.pdfEMERSON EDUARDO RODRIGUES
 
196444650 ee-2257-control-system-lab-manual
196444650 ee-2257-control-system-lab-manual196444650 ee-2257-control-system-lab-manual
196444650 ee-2257-control-system-lab-manualhomeworkping3
 
Interturn short circuit analysis in an induction machine by fem
Interturn short circuit analysis in an induction machine by femInterturn short circuit analysis in an induction machine by fem
Interturn short circuit analysis in an induction machine by femDarío Díaz
 
Transient Stability Enhancement of a Multi-Machine System using Particle Swar...
Transient Stability Enhancement of a Multi-Machine System using Particle Swar...Transient Stability Enhancement of a Multi-Machine System using Particle Swar...
Transient Stability Enhancement of a Multi-Machine System using Particle Swar...IJERA Editor
 

Similar to Performance Evaluation of Synchronous Generator under Sudden Loss of Excitation (20)

Evaluation of reactances and time constants of synchronous generator
Evaluation of reactances and time constants of synchronous generatorEvaluation of reactances and time constants of synchronous generator
Evaluation of reactances and time constants of synchronous generator
 
C0212014018
C0212014018C0212014018
C0212014018
 
40220140505010
4022014050501040220140505010
40220140505010
 
Hr3513381342
Hr3513381342Hr3513381342
Hr3513381342
 
[1339309 x journal of electrical engineering] loss of excitation of synchro...
[1339309 x   journal of electrical engineering] loss of excitation of synchro...[1339309 x   journal of electrical engineering] loss of excitation of synchro...
[1339309 x journal of electrical engineering] loss of excitation of synchro...
 
Active and Reactive Power control operation of DFIG forWind Power Generation ...
Active and Reactive Power control operation of DFIG forWind Power Generation ...Active and Reactive Power control operation of DFIG forWind Power Generation ...
Active and Reactive Power control operation of DFIG forWind Power Generation ...
 
Electrical Machines - II
Electrical Machines - IIElectrical Machines - II
Electrical Machines - II
 
Short circuit test in brief
Short circuit test in briefShort circuit test in brief
Short circuit test in brief
 
symmetrical_fault_analysis.pdf
symmetrical_fault_analysis.pdfsymmetrical_fault_analysis.pdf
symmetrical_fault_analysis.pdf
 
1 8
1 81 8
1 8
 
IRJET- PI Controller based Shunt Connected Three Phase Active Power Filter
IRJET- PI Controller based Shunt Connected Three Phase Active Power FilterIRJET- PI Controller based Shunt Connected Three Phase Active Power Filter
IRJET- PI Controller based Shunt Connected Three Phase Active Power Filter
 
Armature reaction and parallel operation of a Syncronous generator
Armature reaction and parallel operation of a Syncronous generatorArmature reaction and parallel operation of a Syncronous generator
Armature reaction and parallel operation of a Syncronous generator
 
1 8
1 81 8
1 8
 
New Microsoft Word Document
New Microsoft Word DocumentNew Microsoft Word Document
New Microsoft Word Document
 
DFIG_report
DFIG_reportDFIG_report
DFIG_report
 
Improved Control Strategy for Low Voltage Ride Through Capability of DFIG wit...
Improved Control Strategy for Low Voltage Ride Through Capability of DFIG wit...Improved Control Strategy for Low Voltage Ride Through Capability of DFIG wit...
Improved Control Strategy for Low Voltage Ride Through Capability of DFIG wit...
 
H7 SHORT-CIRCUIT EMERSON EDUARDO RODRIGUES.pdf
H7 SHORT-CIRCUIT EMERSON EDUARDO RODRIGUES.pdfH7 SHORT-CIRCUIT EMERSON EDUARDO RODRIGUES.pdf
H7 SHORT-CIRCUIT EMERSON EDUARDO RODRIGUES.pdf
 
196444650 ee-2257-control-system-lab-manual
196444650 ee-2257-control-system-lab-manual196444650 ee-2257-control-system-lab-manual
196444650 ee-2257-control-system-lab-manual
 
Interturn short circuit analysis in an induction machine by fem
Interturn short circuit analysis in an induction machine by femInterturn short circuit analysis in an induction machine by fem
Interturn short circuit analysis in an induction machine by fem
 
Transient Stability Enhancement of a Multi-Machine System using Particle Swar...
Transient Stability Enhancement of a Multi-Machine System using Particle Swar...Transient Stability Enhancement of a Multi-Machine System using Particle Swar...
Transient Stability Enhancement of a Multi-Machine System using Particle Swar...
 

Recently uploaded

Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptxDecoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptxJoão Esperancinha
 
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...Soham Mondal
 
Porous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writingPorous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writingrakeshbaidya232001
 
HARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICS
HARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICSHARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICS
HARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICSRajkumarAkumalla
 
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...ranjana rawat
 
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLS
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLSMANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLS
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLSSIVASHANKAR N
 
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINE
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINEMANUFACTURING PROCESS-II UNIT-2 LATHE MACHINE
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINESIVASHANKAR N
 
Introduction to IEEE STANDARDS and its different types.pptx
Introduction to IEEE STANDARDS and its different types.pptxIntroduction to IEEE STANDARDS and its different types.pptx
Introduction to IEEE STANDARDS and its different types.pptxupamatechverse
 
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICSAPPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICSKurinjimalarL3
 
chaitra-1.pptx fake news detection using machine learning
chaitra-1.pptx  fake news detection using machine learningchaitra-1.pptx  fake news detection using machine learning
chaitra-1.pptx fake news detection using machine learningmisbanausheenparvam
 
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...ranjana rawat
 
What are the advantages and disadvantages of membrane structures.pptx
What are the advantages and disadvantages of membrane structures.pptxWhat are the advantages and disadvantages of membrane structures.pptx
What are the advantages and disadvantages of membrane structures.pptxwendy cai
 
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130Suhani Kapoor
 
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...ranjana rawat
 
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝soniya singh
 
Microscopic Analysis of Ceramic Materials.pptx
Microscopic Analysis of Ceramic Materials.pptxMicroscopic Analysis of Ceramic Materials.pptx
Microscopic Analysis of Ceramic Materials.pptxpurnimasatapathy1234
 
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur High Profile
 
Software Development Life Cycle By Team Orange (Dept. of Pharmacy)
Software Development Life Cycle By  Team Orange (Dept. of Pharmacy)Software Development Life Cycle By  Team Orange (Dept. of Pharmacy)
Software Development Life Cycle By Team Orange (Dept. of Pharmacy)Suman Mia
 

Recently uploaded (20)

Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptxDecoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
 
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
 
DJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINE
DJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINEDJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINE
DJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINE
 
Porous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writingPorous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writing
 
HARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICS
HARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICSHARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICS
HARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICS
 
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
 
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLS
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLSMANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLS
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLS
 
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINE
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINEMANUFACTURING PROCESS-II UNIT-2 LATHE MACHINE
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINE
 
9953056974 Call Girls In South Ex, Escorts (Delhi) NCR.pdf
9953056974 Call Girls In South Ex, Escorts (Delhi) NCR.pdf9953056974 Call Girls In South Ex, Escorts (Delhi) NCR.pdf
9953056974 Call Girls In South Ex, Escorts (Delhi) NCR.pdf
 
Introduction to IEEE STANDARDS and its different types.pptx
Introduction to IEEE STANDARDS and its different types.pptxIntroduction to IEEE STANDARDS and its different types.pptx
Introduction to IEEE STANDARDS and its different types.pptx
 
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICSAPPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
 
chaitra-1.pptx fake news detection using machine learning
chaitra-1.pptx  fake news detection using machine learningchaitra-1.pptx  fake news detection using machine learning
chaitra-1.pptx fake news detection using machine learning
 
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
 
What are the advantages and disadvantages of membrane structures.pptx
What are the advantages and disadvantages of membrane structures.pptxWhat are the advantages and disadvantages of membrane structures.pptx
What are the advantages and disadvantages of membrane structures.pptx
 
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
 
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
 
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝
 
Microscopic Analysis of Ceramic Materials.pptx
Microscopic Analysis of Ceramic Materials.pptxMicroscopic Analysis of Ceramic Materials.pptx
Microscopic Analysis of Ceramic Materials.pptx
 
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
 
Software Development Life Cycle By Team Orange (Dept. of Pharmacy)
Software Development Life Cycle By  Team Orange (Dept. of Pharmacy)Software Development Life Cycle By  Team Orange (Dept. of Pharmacy)
Software Development Life Cycle By Team Orange (Dept. of Pharmacy)
 

Performance Evaluation of Synchronous Generator under Sudden Loss of Excitation

  • 1. ISSN 2349-7815 International Journal of Recent Research in Electrical and Electronics Engineering (IJRREEE) Vol. 3, Issue 4, pp: (7-13), Month: October - December 2016, Available at: www.paperpublications.org Page | 7 Paper Publications Performance Evaluation of Synchronous Generator under Sudden Loss of Excitation 1 Sohorab Hossain, 2 Subimal Roy Burman, 3 Sourish Sanyal, 4 Amaranth Sanyal, 5 Raju Basak 1 MCKV Institute of Engineering, 2 Additional Chief Engineer, WBSETCL, 3 Assoc. Professor, Techno India College, 4 Professor, CIEM, Kolkata, 5 Research Scholar, Jadavpur University Abstract: Synchronous generators under sudden loss of excitation behave as an induction generator, supplying active power to the system and absorbing reactive power from the system. In general the armature current exceeds its rated value. Hence, the reference power is reduced in steps to keep the armature currents within limits. The voltage profile around the faulty machine becomes unacceptably poor and in addition there is exchange of pulsating power with the system. Hence, the general practice is to switch off the machine by the action of an offset type MHO-relay. Recently, the capacitive VAR-generation of a H.T. system has gone up due to addition of EHV/SHV lines, such that there is no or little problem in supplying the faulty machine with its required VAR. Also, the magnetizing current drawn by modern turbo generators has reduced much due to the use of smaller air- gaps for economic design of the rotor. The combined effect has been assessed, and it has been found that it is permissible to run the machine for a relatively long duration under LOE without staking on its health. It may be allowed to run the machine for 30-60 minutes under LOE, within which time the fault may be detected and removed and the machine resynchronized. However, this is not possible for hydro-generators drawing large magnetizing currents. Keywords: Synchronous generator, Governor Action, Newton-Raphson method, Excitation system, Loss of excitation, Mho-relay. Symbols, abbreviation and subscripts: ,E V Induced voltage, Infinite bus voltage ,g aV I  Generator terminal voltage, armature current ,d qX X D-axis/ Q-axis synchronous reactance ,md fX x D-axis magnetizing reactance, field leakage reactance ,ax  Armature leakage reactance, angular frequency in r/s ' dX D-axis transient reactance " " ,d qX X D-axis/Q-axis sub-transient reactance ,e er X External resistance, leakage reactance to infinite bus ' ' ,d doT T D-axis S.C./ O.C. transient time constant. " " ,d doT T D-axis S.C./ O.C. sub transient time constant " " ,q qoT T Q-axis S.C./ O.C. sub transient time constant ,f dr r Field/ field discharge resistance ,ref uP R Reference power-setting, Static droop , ,P P P s r Total, synchronous, reluctance power ,as asT I Asynchronous torque/ current ,as asP Q Asynchronous active/reactive power ,s Power angle, slip D,Q Direct/ quadrature S.C./O.C. Short circuit/ open circuit  Angle of lag of current behind voltage
  • 2. ISSN 2349-7815 International Journal of Recent Research in Electrical and Electronics Engineering (IJRREEE) Vol. 3, Issue 4, pp: (7-13), Month: October - December 2016, Available at: www.paperpublications.org Page | 8 Paper Publications 1. INTRODUCTION TO LOE PHENOMENA A synchronous generator is forced to asynchronous operation under sudden loss of excitation. Operation under LOE has many undesirable effects e.g. thermal injury of the faulted machine, poor voltage profile in its neighbourhood, pulsations in voltage and power etc. [1,2,3]. These effects are more pronounced for a salient pole hydrogenerator compared to a cylindrical pole turbogenerator [1,4]. The equivalent circuit parameters of the 210 MW turbogenerator set of BHEL have been computed [5,6]. Then it has been equivalenced with the generator transformer. On the basis of one machine on infinite bus, the parameters and the time constants of the equivalenced machine have been modified [7,8] . Then the machine variables under asynchronous condition have been computed. A comparison has been made between the field directly short-circuited and the same closed through a properly chosen value of discharge resistance. It has been found that the use of discharge resistance is beneficial, but the relay operates even in its absence. 2. BAD EFFECTS OF L.O.E. ON THE MACHINE AND THE SYSTEM The undesirable and damaging effects of operating a generator under loss of excitation are listed below: a) The alternator runs at a leading power factor. It draws large amount of reactive power from the system for its excitation. The generator bus voltage cannot be held fixed- the bus gets converted to load bus with negative value of active power. b) The resulting stator current may be more than rated- its value depends on the network conditions and the bus voltage. The over-current gives rise to overheating and thermal injury. c) The reactive power burden on the neighbouring generators becomes very high. They run at a poor lagging power factor, provided there is no capacitive support or FACTS-devices for the rescue. d) Large amount of reactive power flows through the transmission links causing voltage dips in the neighbourhood of the faulty machine. It makes the voltage profile unacceptable. e) Loss of excitation is associated with exchange of pulsating power with the system due to saliency effect. It also creates pulsation in voltage and slip. f) The tip of the impedance phasor of the machine flies off from 1st . quadrant to 4th . quadrant. It can be sensed by admittance relays and protective actions taken. These effects are more pronounced for the salient pole hydro-alternators compared to turbo-alternators. For all these reasons, the general practice is to shut down the generator on occurrence of loss of excitation. The bulk power system reliability is adversely affected on L.O.E. of a generator, provided there is no reactive power support. Load flow studies on the L.O.E.-faulted system of W.B. power grid revealed that the voltage collapse and resulting instability could be avoided only against large scale capacitive support. But now the scenario has somewhat changed due to addition of highly capacitive long EHV lines in our grid system. Asynchronous operation for a short time may be continued without any capacitive support. Hence sufficient time delay can be given to the admittance relay without any risk. 3. CAPABILITY OF TURBO-GENERATOR SETS TO OPERATE UNDER LOE The turbo-generators manufactured by BHEL are capable of sustained operation under LOE for limited time. On occurrence of an L.O.E.-fault, the company has instructed to do the following:  To disconnect the field circuit from the source immediately and short-circuit it, preferably through a discharge resistance of appropriate value.  To reduce the asynchronous power to 60% of rated power within 30 sec.  To reduce it further to 40% within 90 sec.  To continue for 15-20 minutes under asynchronous condition and try to resynchronize.
  • 3. ISSN 2349-7815 International Journal of Recent Research in Electrical and Electronics Engineering (IJRREEE) Vol. 3, Issue 4, pp: (7-13), Month: October - December 2016, Available at: www.paperpublications.org Page | 9 Paper Publications  To switch off the faulty machine, in case of failure to resynchronize within this time. Following these instructions, the analysis has been made at first with field short-circuited directly and then short-circuited through a discharge resistance. The reference power-setting has been reduced to 0.6 p.u. within 30 second and then reduced further to 0.4 p.u. within 90 second. 4. THE MATHEMATICAL MODEL The electromagnetically developed power in a synchronous generator connected to infinite bus is given as: 2 ( / )sin ( / 2)(1/ 1/ )sin(2 )s r d q dP P P EV X V X X      (1) Under L.O.E., the synchronous power falls to zero almost immediately. The relatively small reluctance power fails to retain synchronism. The rotor gradually speeds up and eventually settles at a steady negative slip. The average slip is determined by the reference power setting, the static droop and the machine parameters. A cyclic variation of slip is superposed on it due to saliency. This is associated with exchange of pulsating power and current with the system at double the line frequency (also at power frequency if the loss of excitation is partial). In terms of operational impedance of an alternator, the average asynchronous torque is given as: 2 1 1 Re 2 ( ) ( ) as d o q o V T jX js jX js          (2) and the asynchronous active power is given as: (1 )as asP s T  (3) The reactive power of the system is given as: 2 1 1 Im 2 ( ) ( ) as d o q o V Q jX js jX js          (4) It is not an easy task to calculate the asynchronous variables from this expression. Breaking up into fractions, we get a more workable expression as given below: "' "2 ' ' 2 " ' " 2 " " 2 1 1 1 1 1 1 (1 ) 2 1 ( ) 1 ( ) 1 ( ) qd d as d d d d d d q q q TT TV P s s X X sT X X sT X X sT                              (5) The corresponding value of the reactive power is given by the following expression (time constants are in radians): " 2' 2 " 22 ' ' 2 " ' " 2 " " 2 ( )( ) ( )1 1 1 1 1 1 . 2 1 ( ) 1 ( ) 1 ( ) qd d as d d d d d d q q q sTsT sTV Q X X sT X X sT X X sT                              (6) 5. THE EFFECT OF TURBINE-GOVERNOR The turbine-governor is set with a reference power by the speeder gear and a static droop which may vary from 3 to 4%. Under synchronous condition, as refP P , where refP is the active power setting of the turbine-governor. But under asynchronous condition, we have: /as ref uP P s R  (7) Now, the expression reduces to the following form: ( ) / 0as ref uf s P P s R    (8) This equation can be solved by applying numerical methods like that of Newton-Raphson to find out the slip for specified value of the active power (appendix-1).
  • 4. ISSN 2349-7815 International Journal of Recent Research in Electrical and Electronics Engineering (IJRREEE) Vol. 3, Issue 4, pp: (7-13), Month: October - December 2016, Available at: www.paperpublications.org Page | 10 Paper Publications 6. INFINITE BUS ASSUMPTION - EFFECT OF SERIES REACTANCE AND DISCHARGE RESISTANCE As the rating of the machine is not comparable to the grid power, we treat it as one machine on infinite bus connected through series impedance. The series impedance is the sum of the impedance of the transformer and that of the short transmission line (if any) connecting the machine to the grid system. The line capacitance is neglected for a short line. The schematic diagram of the idealized machine is given in fig. 1. Fig. 1. A generator connected to infinite bus through a transformer and a transmission line The effect of series impedance to infinite is beneficial as it reduces the magnetizing VAR drawn from the system. But it also reduces the terminal voltage of the machine and hence increases the slip for a given reference power. It gives rise to an increment in reactive power which partly offsets the saving in reactive power due to lower magnetizing current. The series reactance modifies the reactances of the machine and the short-circuit time constants. The discharge resistance also modifies the d-axis open circuit and short-circuits transient time constants. The resultant expressions are given below: ' ' " " " " ; ; ; ;de d e qe q e de d e de d e qe q eX X X X X X X X X X X X X X X          (9) ' ' ' " " ' " " " ' " ' ' ' ' ' " " " ' " " " . / ; . / ; . / ; . / ( ) ; . / ; . / ; . / do d d d do d d d qo q q q dom do f f d d dom de de d do de de q qo qe qe T T X X T T X X T T X X T T r r r T T X X T T X X T T X X         (10) The generator terminal voltage is given as: ( )g a e eV V I r jX    (11) The voltage is normally depressed under LOE, to such an extent that under voltage relays may trip at many buses. 7. CASE-STUDIES ON ASYNCHRONOUS OPERATION Now we shall undertake a no. of case studies on asynchronous variables under sudden loss of excitation. The alternator under LOE is assumed to be on infinite bus through its transformer. This programme computes asynchronous. torque and power for varying input voltage and fixed ref. power of BANDEL TPS 5th unit, using N-R method. All quantities are in p.u. & time constants in sec. All quantities refer to the equivalent machine including the generator transformer. The first case-study is being made for LOE with 60% power and the second case study is being made for LOE with 40% rated power. The computer print outs converted to word-format are given below: The parameters and time constants: Leakage reactance, ax = 0.152 D-axis syn. Reactance, dX = 2.3616
  • 5. ISSN 2349-7815 International Journal of Recent Research in Electrical and Electronics Engineering (IJRREEE) Vol. 3, Issue 4, pp: (7-13), Month: October - December 2016, Available at: www.paperpublications.org Page | 11 Paper Publications D-axis transient reactance, ' dX = 0.4416 D-axis subtransient reactance, " dX = 0.3506 Q-axis syn. Reactance, qX = 2.2466 Q-axis subtransient reactance, " qX = 0.4476 D-axis open circuit transient time constant, ' doT =0.7778 D-axis s.c. transient time constant, ' dT =0.1454 D-axis s.c. subtransient time constant, " dT =0.1369 Q-axis short circuit subtransient time constant, " qT = 0.1195407 Synchronous speed = 314.2 r/s Reactance to infinite bus, eX = 0.1366 Discharge resistance, dR = 4 fr Static droop in p.u., uR = 0.04 Case-I: The reference torque (or power) has been set at 60% of rated power = 0.6 x 0.85 = 0.51 p.u. by speeder gear within 30 sec from the occurrence of fault and may be continued up to 90 sec. Table-1: Reference torque = 0.51 p.u. asP (60% of rated power) (from 30 to 90 sec.) Slip s Terminal Voltage V Asyn. reactive Power QAS Asyn apparent power SAS Asyn current SAS Pulsating power Ppul 0.00344 1.00 0.62276 0.80494 0.80494 0.31929 0.00364 0.98 0.61588 0.79963 0.81595 0.32069 0.00386 0.96 0.61041 0.79543 0.82857 0.32225 0.00411 0.94 0.60569 0.79181 0.84235 0.32339 0.00440 0.92 0.60376 0.79033 0.85905 0.32539 0.00472 0.9 0.60335 0.79002 0.87780 0.32721 0.00512 0.88 0.60653 0.79245 0.90051 0.32987 0.00559 0.86 0.61259 0.79710 0.92686 0.33258 0.00618 0.84 0.62359 0.80558 0.95903 0.33593 0.00696 0.82 0.64163 0.81963 0.99955 0.33999 0.00803 0.8 0.66830 0.84067 1.050840 0.34397 Case-II The reference torque (or power) has been set at 40% of rated power = 0.4 x 0.85 = 0.34 p.u. by speeder gear within 90 sec from the occurrence of fault and may be continued up to breaker operation.. Table- 2 : Reference power = 0.34 p.u. (40% of rated power) (after 90 sec.) Slip s Terminal Voltage V Asyn. reactive Power QAS Asyn apparent power SAS Asyn current SAS Pulsating power Ppul 0.00211 1.00 0.51306 0.61549 0.61549 0.20883 0.00221 0.98 0.49962 0.60434 0.61667 0.20932 0.00232 0.96 0.48675 0.59374 0.61848 0.20975 0.00242 0.94 0.47394 0.58329 0.62052 0.20954 0.00255 0.92 0.46250 0.57403 0.62394 0.21015 0.00270 0.90 0.45185 0.56548 0.62831 0.21084
  • 6. ISSN 2349-7815 International Journal of Recent Research in Electrical and Electronics Engineering (IJRREEE) Vol. 3, Issue 4, pp: (7-13), Month: October - December 2016, Available at: www.paperpublications.org Page | 12 Paper Publications 0.00285 0.88 0.44198 0.55762 0.63366 0.21155 0.00301 0.86 0.43235 0.55003 0.63957 0.21174 0.00320 0.84 0.42438 0.54378 0.64736 0.21266 0.00341 0.82 0.41719 0.53189 0.65633 0.21342 0.0036 0.80 0.40822 0.53126 0.66408 0.21201 It may be noted from table-1 that the rating has not been exceeded for 60% of rated power except for V = 0.8 p.u. Such an under-voltage is not likely to occur. From table-2 it may be noted that the asynchronous variables are well within limits. Therefore, the instruction of BHEL may be followed to limit the power cut-off for at least half-an-hour safely. 8. CONCLUSION The computation of asynchronous torque and power for a given load and a given terminal voltage is a formidable task. It can be made by breaking up the formula for asynchronous power and applying computer iterative techniques to them. We have used the Newton-Raphson method which fast converges to the solution. It has been noted that a turbo generator under LOE-fault is quite safe at 60% of rated power for limited time and at 40% power of rated power for unlimited time. Therefore, the instruction of BHEL to continue power supply under asynchronous mode of operation for 20-30 minutes is quite justified. If the fault cannot be removed within this time then the machine is to be switched off, as the pulsating power exchange and low voltage profile around the faulty machine is not acceptable from the power quality point of view. However, it is not admissible for hydro generators as the asynchronous variables are much larger for them, particularly the pulsating power. So they must be switched off within 2-3 minutes. By running turbo generators under LOE for some time, we can reduce the extent of load-shedding. This is possible only if the system is rich in capacitive VARs, such that the voltage profile is not extremely poor.. REFERENCES [1] A.N. Sanyal, S. Chowdhuri, and S. RoyBurman, “Effect of loss of excitation in interconnected power system”, CPRI conference paper, 1988, IISC, Bangalore [2] S.K. Sen, “Electric machinery, Khanna Publishers. [3] A.Maity, K. Bhattacharya, A.N. Sanyal, “Asynchronous operation of synchronous generators under field failure", IEEE Xplore, 2014, Digital Object Identifier: 10.1109/ACES.2014.6808006, Print ISBN: 978-1-4799- 3893-3, pp 1-6. [4] P.M. Anderson and A.A. Fouad, “Power system control and stability”,Galgotia Publications. [5] Literatures on 210 MW and 500 MW turbo generator sets published by BHEL. [6] P.S.R. Murti, “Modeling of power system elements”, B.S. Publications. [7] B. Adkins and R.G. Harley, “Generalized theory of A.C. machines”, Book, Chapman and Hall. [8] V. Venikov, “Transient processes in electric power system”, Book, MIR Publishers. [9] V. Rajaraman, “Computer-oriented numerical methods”, Prentice Hall of India. [10] D.P. Kothari, I.J. Nagrath, “Power system engineering”, 2nd . Ed., TMH [11] P.J. Moore, A. Stangenberg, “An investigation into the impedance characteristics of a synchronous generator under loss of excitation condition”, EMPD '98, 2 (1998), 619–624 [12] R. Conrad, St. Pierre, “Loss-of-excitation protection for synchronous generators on isolated systems”, IEEE Transactions on Industry Applications, IA-21, 1985, No. 1
  • 7. ISSN 2349-7815 International Journal of Recent Research in Electrical and Electronics Engineering (IJRREEE) Vol. 3, Issue 4, pp: (7-13), Month: October - December 2016, Available at: www.paperpublications.org Page | 13 Paper Publications [13] J. Berdy, “Loss of excitation protection for modern synchronous generators”, IEEE Trans. on Power Apparatus and Systems, 94, pp. 1457 – 1463, 1975 [14] L. Li, S. Caixin, M. Daohuai, “Study on the excitation protection and control of synchronous generator based on the δ and s”, IEEE/PES(2005), 1–4 [15] D.C. Lee, P. Kundur, R.D. Brown, “A high speed discriminating generator loss of excitation protection”, IEEE Transactions on Power Apparatus and Systems, PAS-98, 1979 [16] J. Berdy, “Loss of excitation protection for modern synchronous generators”, Schenectady, New York. [17] P. Mahdi et al (University of Tehran, Iran) “Generator loss of field and its effects on voltage stability in power systems”, paper no. O-130, International conference on Electrical Engineering, 2008. APPENDIX - A Algorithm: Algorithm for numerical solution of eqn. 5 using Newton-Raphson method is given below: Step-1: ' " " ' " " Re , , , , , , , , , , , , , ,ref d d d q q d d q f d e uad P V X X X X X T T T f r r X R Step-2: ' ' " " " " ; ; ; ;de d e qe q e de d e de d e qe q eX X X X X X X X X X X X X X X          Step-3: ' ' ' " " ' " " " ' " ' ' . / ; . / ; . / ; . / ( )do d d d do d d d qo q q q dom do f f dT T X X T T X X T T X X T T r r r     Step-4: ' ' ' " " " ' " " " . / ; . / ; . /d dom de de d do de de q qo qe qeT T X X T T X X T T X X   Step-5: 2 ' ' 2 " " ' 2 " " 1 2 3(1/ 1/ ) / 2; (1/ 1/ ) / 2; (1/ 1/ ) / 2d de de d de de q qe qek V T X X k V T X X k V T X X      Step-6: max, .,max. . : , ,Initializeslip convergenceconst no of iteration s n Step-7: 31 2 ' 2 " 2 " 2 / (1 ) 1 ( ) 1 ( ) 1 ( ) ref u d d q kk k f P s R s s sT sT sT                Step-8: " 2' 2 " 2 3' 1 2 ' 2 2 " 2 2 " 2 2 {1 2 ( ) }{1 2 ( ) } {1 2 ( ) } 1/ {1 ( ) } {1 ( ) } {1 ( ) } qd d u d d q k s sTk s sT k s sT f R sT sT sT                 Step-9 ' /news s f f  Step-10 14newIf s s then goto step  Step-11 1count count  Step-12 max 19If count n then goto step Step-13 : 7news s goto step Step-14 news s Step-15 31 2 ' 2 " 2 " 2 (1 ) 1 ( ) 1 ( ) 1 ( ) as d d q kk k P s s sT sT sT             Step-16 "' " 31 2 ' 2 " 2 " 2 1 ( ) 1 ( ) 1 ( ) qd d as d d q k sTk sT k sT Q s sT sT sT            Step-17 2 2 1/2 ( ) ; /as as as as asS P Q I S V   Step-18 , , , , : 20as as as asprint s P Q S I goto step Step-19 max' ' . .Noconvergencein n noof iterations Try againchanging initial value Step-20 :stop end