IJRET: International Journal of Research in Engineering and Technology eISSN: 2319-1163 | pISSN: 2321-7308 
__________________________________________________________________________________________ 
Volume: 03 Special Issue: 03 | May-2014 | NCRIET-2014, Available @ http://www.ijret.org 380 
EVALUATION OF REACTANCES AND TIME CONSTANTS OF SYNCHRONOUS GENERATOR Shaheena Khanum1, K.L Ratnakar2, Ramesh K.N3, Ravi.R4 1PG Student, Department of Electrical and Electronics Engineering, Sri Siddhartha Academy of Higher Education, Tumkur, Karnataka, India 2Professor, Department of Electrical and Electronics Engineering, Sri Siddhartha Academy of Higher Education Tumkur, Karnataka, India 3Quality Assurance, TD Power Systems Limited, Dabaspet, Bangalore, Karnataka, India 4PG Student, Department of Electrical and Electronics Engineering, Sri Siddhartha Academy of Higher Education, Tumkur, Karnataka, India Abstract 
For any power equipment the control system and protection system plays an imperative role as the dependency on the power equipment in any industry will be very high. Thus for the Generator the Reactances and Time Constants becomes controlling parameter and hence protecting it is necessary for prolonged usage. In general reactance shall be defined as “non-resistive component of impedance in an AC circuit, arising from the effect of inductance or capacitance or both and causing the current to be out of phase with the electromotive force causing it”. In other word it can also be defined as the imaginary part of the impedance in any power circuit. There are various Reactances and Time Constants which contributes during the selection of control systems and protection scheme for any Generator. Therefore practical evaluation of those parameters shall also be super critical same as those are by calculation. More accurate measurement or the calculation of reactance shall certainly give us more stabilized error free system and hence ensuring a healthy control system. As there are different tests or different methods to measure and calculate the Reactances and Time Constants, in this context we are considering Line to Line fault (L-L fault), Double line to Ground fault and Sudden three phase short circuit fault to determine the Negative Sequence reactance, Zero Sequence reactance, Sub-transient and Transient reactance and time constants respectively. The fault condition will be demonstrated with the 40MW, 11KV, 2624A, 4pole, 50 Hz synchronous generator and above mentioned parameters are calculated based on references available. Keywords: Reactances, Time Constants, Testing of Alternator, Brushless Alternator. 
----------------------------------------------------------------------***------------------------------------------------------------------------ 1. INTRODUCTION 
The synchronous machine is an ac machine in which the rotor moves at a speed which bears a constant relationship to the frequency of currents, in the armature winding. A synchronous machine is one of the important types of electric machines. Large ac networks operating at constant frequency of 50 Hz or 60 Hz rely almost exclusively on synchronous generators, also called the alternators, for the supply of electrical energy, and may have synchronous compensators at key points for control of reactive power. Private stand-by and peak load plants with diesel or gas-turbine prime movers also have synchronous generators. Non-land-based synchronous plants are found on oil rings, on large air-crafts and constant speed industrial drives with the possibility of power factor correction, but are not often built in small ratings for which the induction motor is cheaper. Synchronous machines are generally constructed in larger sizes. Small size alternators are not economical. The modern trend is to build alternators of very large sizes capable of generating 500MVA or even more. An alternator works on the principle of Faraday’s laws of Electro-Magnetic Induction. ―Whenever a conductor/coil cuts the magnetic flux an EMF is induced in that conductor. The magnitude of EMF induced in the conductor/coil is directly proportional to the rate of change of flux and the number of conductors‖. The main component which effects the operation of alternator is resistance and reactances. The effective resistance of the armature winding is somewhat greater than the conductor resistance, called the dc resistance, as measured by direct current. This is due to additional loss over the purely I2R loss, inside and sometimes outside the conductor, owing to alternating current. The main sources of this additional loss are 
 Eddy current in the surrounding material, 
 Magnetic hysteresis in the surrounding material and 
 Eddy currents or unequal current distribution in the conductor itself. 
In many cases it is sufficiently accurate to measure the armature resistance by direct current and increase it to a fictitious value, called the effective resistance, Re which is large enough to take care of these additional losses. Effective resistance, Re can vary widely from 1.25 to 1.75 or more times
IJRET: International Journal of Research in Engineering and Technology eISSN: 2319-1163 | pISSN: 2321-7308 
__________________________________________________________________________________________ 
Volume: 03 Special Issue: 03 | May-2014 | NCRIET-2014, Available @ http://www.ijret.org 381 
the dc resistance, depending upon design. The EMF setup due to armature reaction MMF Fa is always in quadrature with the load current I and is proportional to it. Thus it is equivalent to an EMF induced in an inductive coil and the effect of armature reaction can, therefore, be considered equivalent to reactance drop IXa where Xa is the fictitious reactance which takes care of the armature reaction effect. The armature winding possesses a certain leakage reactance Xl. The sum of leakage reactance Xl and fictitious reactance Xa is called the synchronous reactance. 2. REACTANCES It can be defined as the imaginary part of the impedance in any power circuit. There are various Reactances and Time Constants which contribute during the selection of control systems and protection scheme for any Generator. Fig -1: Axes of Alternator The axis of symmetry of the north magnetic poles of the rotor is called the direct axis or d- axis. The axis of symmetry of the south magnetic poles is the negative d-axis. The axis of symmetry halfway between adjacent north and south poles is called the quadrature axis or q-axis. • Direct axis reactance (Xd): The quotient of the sustained value of that fundamental AC component of armature voltage, which is produced by the total direct-axis primary flux due to direct-axis armature current and the value of the fundamental AC component of this current, the machine running at rated speed. • Quadrature axis reactance (Xq): The quotient of the sustained value of that fundamental AC component of armature voltage, which is produced by the total quadrature- axis primary flux due to quadrature-axis armature current, and the value of the fundamental AC component of this current, the machine running at rated speed. • Direct-axis transient reactance (Xd’): The quotient of the initial value of a sudden change in that fundamental AC component of armature voltage, which is produced by the total direct-axis primary flux, and the value of the simultaneous change in fundamental AC component of direct-axis armature current, the machine running at rated speed and the high decrement components during the first cycles being excluded. 
• Direct axis sub-transient reactance (Xd”): The quotient of the initial value of a sudden change in that fundamental AC component of armature voltage, which is produced by the total direct-axis armature flux, and the value of the simultaneous change in fundamental AC component of direct-axis armature current, the machine running at rated speed. 
• Negative sequence reactance (X2): The quotient of the reactive fundamental component of negative sequence armature voltage, due to the presence of fundamental negative sequence armature current at rated frequency, by the value of that component of current, the machine running at rated speed. • Zero sequence reactance (Xo): The quotient of the reactive fundamental component of zero sequence armature voltage, due to the presence of fundamental zero sequence armature current at rated frequency, by the value of that component of current, the machine running at rated speed. 3. TIME CONSTANTS 
 Direct-axis transient short-circuit time constant (d): 
It is the time, in seconds, required for the transient alternating component of the short-circuit current to decrease to 1/ε0 or 0.368 times its initial value. 
 Direct-axis sub-transient short-circuit time constant (d): 
It is the time, in seconds, required for the sub-transient alternating component of the short-circuit current to decrease to 0.368 times its initial value. 
 Direct-axis transient open circuit time constant (do): 
It is the time, in seconds, required for the transient alternating component of the open-circuit current to decrease to 0.368 times its initial value. 4. TESTING OF SYNCHRONOUS GENERATOR In this paper, study of different types of testing is going to be done for an alternator. Testing is the practice of making objective judgments regarding the extent to which the product meets else fails to meet the specified objectives. In other words for any manufactured product or equipments it is essential that the evaluation of the product with reference to the specification and the applicable standards. It is also indispensable for any manufacturer to ensure their product is meeting all the requirements as per their design and by their processes. Testing of a Generator or an Alternator also play a vital role before it is being put in to continuous operation. As the manufacturing of Generator involves various crucial processes either it may be carried by machinery or by man or may be both put together and hence it becomes important to assess the work done at the end. Though each component and part of the Generator has undergone various tests it is necessary that the complete assembled Generator also shall undergo at least Routine (described later) tests to understand the basic performance. [1] 
Generator testing shall be of two types i.e. Type test and Routine test. Type test is inclusive of all routine tests along with some additional tests. Routine test is compulsory to
IJRET: International Journal of Research in Engineering and Technology eISSN: 2319-1163 | pISSN: 2321-7308 
__________________________________________________________________________________________ 
Volume: 03 Special Issue: 03 | May-2014 | NCRIET-2014, Available @ http://www.ijret.org 382 
understand the elementary performance of the Generators which comes under serial production type. 4.1 Sudden Short Circuit Test 4.1.1 Circuit Fig-2: Sudden short circuit test setup 4.1.2 Procedure 1. Makes the connections as per the above diagram. 2. Run the generator to its rated speed. 3. Build up the voltage to 10% of the rated voltage. 4. Close the circuit breaker & check the waveforms. Check the waveform for the Clear identification of the amplitudes. (Should be 3 current & 1 voltage waveform) 5. If ok, then raise the voltage to 30% of the rated voltage then close the breaker, record the current and voltage waveforms. 6. Note down the steady state current, record & print waveforms. 4.2 Zero Sequence Test (Xo) 4.2.1 Circuit Fig-3: Zero sequence test setup 4.2.2 Procedure 1. Make the connections as per above circuit. 2. Run the machine to its rated speed 4. Record the values of current (I), voltage (V) and power. 5. Xo shall be calculated using measured values. 3. Increase the armature current in steps of 10%, 20%, 30 %, 40% and 50% of rated current. 
4.3 Negative Sequence Test 
4.3.1 Circuit Fig-4: Negative sequence test setup 4.3.2 Procedure 1. Make the connections as per above circuit. 2. Run the machine to its rated speed 3. Increase the armature current in steps of 10%, 20%, 30 %, 40% and 50% of rated current. 4. Record the values of current (I), voltage (V) and power. 5. X2 shall be calculated using measured values. 5. CALCULATIONS OF REACTANCES & TIME CONSTANTS 5.1 Three Phase Sudden Short Circuit Test and Determination of Characteristic Reactance and Time Constants. The synchronous reactance (Xd), transient reactance (X'd) and sub-transient reactance (X''d), and the transient short-circuit time constant (t'd) and sub-transient short circuit time constant (t''d) are used to describe and machine's behavior on sudden short-circuit. This can be done in accordance with the following equation for the AC RMS components of current following a three-phase short-circuit from no load neglecting armature-circuit resistances and assuming constant exciter voltage. [2] I (t) = (E/Xds) + ((E/Xd’ ) – (E/Xds)) ԑ (-t/Ʈd’ )+ (E/Xd’’ –E/ X’ d) ԑ (-t/Ʈd’’ ) Where, I (t): is the AC RMS short- circuit current, p.u. E: Is the AC RMS voltage before short circuit, p.u. t: is the time in seconds, measured from the instant of short circuit. 
In this expression, it is assumed that the current is composed of a constant term and two decaying exponential terms where the third term of the equation decays very much faster than the
IJRET: International Journal of Research in Engineering and Technology eISSN: 2319-1163 | pISSN: 2321-7308 
__________________________________________________________________________________________ 
Volume: 03 Special Issue: 03 | May-2014 | NCRIET-2014, Available @ http://www.ijret.org 383 
second. By subtracting the first (constant) term and plotting the remainder on semi-logarithmic paper as a function of time, the curve would appear as a straight line after the rapidly decaying term decreases to zero. The rapidly decaying portion of the curve is the sub-transient portion, while the straight line is the transient portion. 5.2 Evaluation (a) Measure the voltage from wave form recorded (pk-pk) & converts the same to RMS value Es = Epk-pk*(PT ratio) / (2*sqtr (2)) (b) Measure the mV drop of steady state current from the waveform recorded & convert the same to amperes (RMS value) Is = mVpk-pk*(Shunt ratio) / (2*sqtr (2)) (c) Peak to Peak value (mV) of the currents from the waveform recorded is measured & RMS value of the currents are calculated to first 50 to 60 cycles. (d) Subtract the steady state current from point (c) & plot the graph for the component currents (I'k+I''k) in the semi log sheet with current in on log scale & time on linear scale. (e) To separate transient & sub-transient components, extrapolation to zero time from the straight portion by neglecting the rapid variation of current in first few cycles will give the initial values of corresponding current. [7] (f) From the semi log sheet I'k: is the AC RMS short-circuit transient current component in ampere (RMS). I''k: is the AC RMS short-circuit sub-transient current component in ampere (RMS). Es : is the voltage before short circuit in RMS. Is : is the AC RMS short-circuit steady state current in ampere (RMS). 5.3 Determination of Direct Axis Sub-Transient Reactance & Short Circuit Time Constant (Xd'' & Td'') To calculate Xd'' in % Xd'' in % = (Es*100)/(1.732*Zs*(I'k+I''k+Is)) Where, Zs (Ω): Synchronous impedance of the machine = Rated Voltage / (1.732*Rated Current) To calculate Td'' in seconds Td'' is the time required to decrease the sub-transient component to 1/e i.e. 0.368 of its initial value. OR Time for Id'', where Id''=0.368*I''k 
5.4 Determination of Direct Axis Transient Reactance & Short-Circuit Time Constant (Xd' & Td') 
To calculate Xd' in % 
Xd' in % = (Es*100)/(1.732*Zs*(I'k+Is)) 
Where, Zs (Ω): Synchronous impedance of the machine = Rated Voltage/(1.732*Rated Current) To calculate Td' in seconds Td' is the time required to decrease the transient component to 1/e i.e. 0.368 of its initial value. OR Time for Id', where Id'=0.368*I'k 5.5 Determination of Direct Axis Synchronous Reactance (Xd) To calculate Xd in % Xd in % = (1/SCR)*100 Where, SCR: Short circuit ratio of the machine SCR = ( Ifoc/Ifsc) Ifoc: Field Current for rated voltage. Ifsc: Field Current for rated current. 5.6 Determination of Direct Axis Transient Open Circuit Time constant (Tdo') To calculate Tdo' in seconds Tdo' in seconds = (Xd*Td'/Xd') Fig-5: Analysis of ac component of short-circuit current (for one of three phases ) Fig-6: Transient & Sub-transien component of short-circuit
IJRET: International Journal of Research in Engineering and Technology eISSN: 2319-1163 | pISSN: 2321-7308 
__________________________________________________________________________________________ 
Volume: 03 Special Issue: 03 | May-2014 | NCRIET-2014, Available @ http://www.ijret.org 384 
6. EXPERIMENTAL RESULTS Fig-7: Voltage and Current Waveforms Table- 1: Values of Reactances 
Reactances 
Design value(%) 
Calculated value (%) 
Xd 
166 
161.3 
Xd’ 
29 
30.7 
Xd’’ 
23 
25.2 
X2 
30 
30.08 
X0 
17 
18.15 
Table- 2: Values of Time Constants 
As per the IEEE standards used the acceptable tolerance allowed is ±15% or 30% on one side. 7. CONCLUSIONS The above procedure and the calculation shall be used as a generalized method for calculation of Transient, sub-transient reactance X2, X0 and Time Constants for both cylindrical and salient pole type alternator of any rating. Though the Transient behavior involves tedious steps of calculation and deep analysis of the results, the above procedure helps in calculating the various parameters in easiest way with minimum calculation and time. ACKNOWLEDGEMENTS The authors express their sincere thanks to Dr. B. Rajesh Kamath, B.E., M.E., Ph.D., FIE., MISTE Head of the Dept. E&EE, SSIT, Tumkur for his many helpful suggestions. 
REFERENCES 
[1]. IEEE115 standards for ―Test procedure for synchronous machines‖. 
[2]. IEC60034 ―Methods for determining synchronous machine quantities from tests‖. 
[3]. Marxsen, A. L. and Morsztyn, K., "Analysis of Synchronous Machine Transient Tests Using a Microcomputer," Proceedings IEE, 124(4), pp. 377–380, 1977. [4]. C.Grantham, D. Sutanto, and B. M ismail, ―Steady-state and transient analysis of self-excited induction generators,‖ Proc Inst. Electrical Eng. B, vol. 136, no. 2, pp. 61–68, 1989. [5]. R. Leidhold, G. Garcia, and M. I. Valla, ―Field-oriented controlled induction generator with loss minimization,‖ IEEE Trans. Ind. Electron., vol. 49, pp. 147–155, Feb. 2002. [6]. Canay, I. M., "Causes of Discrepancies on Calculation of Rotor Quantities and Exact Equivalent Diagrams of the Synchronous Machine," IEEE Transactions on Power Apparatus and Systems, vol. PAS-88, pp. 1114–1120, July 1969. [7]. ―THE TRANSIENT REACTIONS OF ALTERNATORS‖ by William A Durgin and R. H. Whitehead, a paper to be presented at the 29th annual convention of the America Institute of Electrical Engineers, Boston, Mass., June 28, 1912. [8]. ―TRANSIENT PERFORMANCE OF THREE-PHASE INDUCTOR-TYPE SYNCHRONOUS GENERATORS: PAPER I- SYMMETRICAL SHORT CIRCUIT‖ By P.K. Dash, Regional Engineering College, Rourkele-8, Orissa, India. [9]. Coultes, M. E. and Watson, W., "Synchronous Machine Models by Standstill Frequency Response Tests," IEEE Transactions on Power Apparatus and Systems, vol. PAS-100, no. 4, pp. 1480–1489, April 1981. [10]. "Determination of Synchronous Machine Stability Study Constants"—EPRI Report EL 1424, vol. 1, Sept. 1980, Westinghouse Electric Corporation and vol. 2, Dec. 1980, Ontario Hydro. [Two of four reports on EPRI Project 997.] 
Time Constants 
Design value(sec) 
Calculated value (sec) 
Td’ 
0.82 
0.84 
Td’’ 
0.035 
0.035 
Td0’ 
4.69 
4.408

More Related Content

What's hot

Instantaneous Reactive Power Theory And Its Applications
Instantaneous Reactive Power Theory And Its ApplicationsInstantaneous Reactive Power Theory And Its Applications
Instantaneous Reactive Power Theory And Its Applicationsarunj89
 
Reactive power compensation
Reactive power compensationReactive power compensation
Reactive power compensationcijogeorgep
 
Reactive Power : Problems and Solutions
Reactive Power : Problems and SolutionsReactive Power : Problems and Solutions
Reactive Power : Problems and SolutionsAbhinav Dubey
 
LOAD BALANCING AND POWER FACTOR CORRECTION FOR MULTIPHASE POWER
LOAD BALANCING AND POWER FACTOR CORRECTION FOR MULTIPHASE POWERLOAD BALANCING AND POWER FACTOR CORRECTION FOR MULTIPHASE POWER
LOAD BALANCING AND POWER FACTOR CORRECTION FOR MULTIPHASE POWERIAEME Publication
 
Electronic Measurement - Q Factor and Q Meter
Electronic Measurement - Q Factor and Q MeterElectronic Measurement - Q Factor and Q Meter
Electronic Measurement - Q Factor and Q MeterBurdwan University
 
Application of Active Power Filter for Power Factor Correction of Nonlinear L...
Application of Active Power Filter for Power Factor Correction of Nonlinear L...Application of Active Power Filter for Power Factor Correction of Nonlinear L...
Application of Active Power Filter for Power Factor Correction of Nonlinear L...Pravin Sonwane
 
Facts controllers for power flow control a brief review
Facts controllers for power flow control a brief reviewFacts controllers for power flow control a brief review
Facts controllers for power flow control a brief reviewDHEERAJ DHAKAR
 
Synchronous condensers
Synchronous condensersSynchronous condensers
Synchronous condensersujvnl
 
P.F.C. Methods in Non-Linear Loads
P.F.C. Methods in Non-Linear LoadsP.F.C. Methods in Non-Linear Loads
P.F.C. Methods in Non-Linear LoadsQasim AL Jubory
 
Reactive power compensation
Reactive power compensationReactive power compensation
Reactive power compensationVikas Saini
 
Active Power Filter
Active Power FilterActive Power Filter
Active Power FilterJawad Iqbal
 
International Journal of Engineering Research and Development (IJERD)
International Journal of Engineering Research and Development (IJERD)International Journal of Engineering Research and Development (IJERD)
International Journal of Engineering Research and Development (IJERD)IJERD Editor
 
Reactive power compensation
Reactive power compensationReactive power compensation
Reactive power compensationMohd Waseem
 
Power factor correction
Power factor correctionPower factor correction
Power factor correctionslmnsvn
 

What's hot (20)

Bh4201396402
Bh4201396402Bh4201396402
Bh4201396402
 
Short circuit followup[1]
Short circuit followup[1]Short circuit followup[1]
Short circuit followup[1]
 
Instantaneous Reactive Power Theory And Its Applications
Instantaneous Reactive Power Theory And Its ApplicationsInstantaneous Reactive Power Theory And Its Applications
Instantaneous Reactive Power Theory And Its Applications
 
Reactive power compensation
Reactive power compensationReactive power compensation
Reactive power compensation
 
Reactive Power : Problems and Solutions
Reactive Power : Problems and SolutionsReactive Power : Problems and Solutions
Reactive Power : Problems and Solutions
 
LOAD BALANCING AND POWER FACTOR CORRECTION FOR MULTIPHASE POWER
LOAD BALANCING AND POWER FACTOR CORRECTION FOR MULTIPHASE POWERLOAD BALANCING AND POWER FACTOR CORRECTION FOR MULTIPHASE POWER
LOAD BALANCING AND POWER FACTOR CORRECTION FOR MULTIPHASE POWER
 
Electronic Measurement - Q Factor and Q Meter
Electronic Measurement - Q Factor and Q MeterElectronic Measurement - Q Factor and Q Meter
Electronic Measurement - Q Factor and Q Meter
 
Application of Active Power Filter for Power Factor Correction of Nonlinear L...
Application of Active Power Filter for Power Factor Correction of Nonlinear L...Application of Active Power Filter for Power Factor Correction of Nonlinear L...
Application of Active Power Filter for Power Factor Correction of Nonlinear L...
 
Facts controllers for power flow control a brief review
Facts controllers for power flow control a brief reviewFacts controllers for power flow control a brief review
Facts controllers for power flow control a brief review
 
Synchronous condensers
Synchronous condensersSynchronous condensers
Synchronous condensers
 
P.F.C. Methods in Non-Linear Loads
P.F.C. Methods in Non-Linear LoadsP.F.C. Methods in Non-Linear Loads
P.F.C. Methods in Non-Linear Loads
 
Reactive power compensation
Reactive power compensationReactive power compensation
Reactive power compensation
 
Reactive power compensation
Reactive power compensationReactive power compensation
Reactive power compensation
 
Sapf2
Sapf2Sapf2
Sapf2
 
Active Power Filter
Active Power FilterActive Power Filter
Active Power Filter
 
International Journal of Engineering Research and Development (IJERD)
International Journal of Engineering Research and Development (IJERD)International Journal of Engineering Research and Development (IJERD)
International Journal of Engineering Research and Development (IJERD)
 
Reactive power compensation
Reactive power compensationReactive power compensation
Reactive power compensation
 
Facts unit-5_and_6
Facts  unit-5_and_6Facts  unit-5_and_6
Facts unit-5_and_6
 
Power factor correction
Power factor correctionPower factor correction
Power factor correction
 
Q meter ppt
Q meter pptQ meter ppt
Q meter ppt
 

Viewers also liked

Development of mobile surface water filtration system through simulation usin...
Development of mobile surface water filtration system through simulation usin...Development of mobile surface water filtration system through simulation usin...
Development of mobile surface water filtration system through simulation usin...eSAT Publishing House
 
Diabetic maculopathy detection using fundus fluorescein angiogram images a ...
Diabetic maculopathy detection using fundus fluorescein angiogram images   a ...Diabetic maculopathy detection using fundus fluorescein angiogram images   a ...
Diabetic maculopathy detection using fundus fluorescein angiogram images a ...eSAT Publishing House
 
Design of passengers vehicle body on fire accidents
Design of passengers vehicle body on fire accidentsDesign of passengers vehicle body on fire accidents
Design of passengers vehicle body on fire accidentseSAT Publishing House
 
Analysis of roucairol and carvalho approach in
Analysis of roucairol and carvalho approach inAnalysis of roucairol and carvalho approach in
Analysis of roucairol and carvalho approach ineSAT Publishing House
 
Radiation pattern of yagi uda antenna using usrp on gnu
Radiation pattern of yagi uda antenna using usrp on gnuRadiation pattern of yagi uda antenna using usrp on gnu
Radiation pattern of yagi uda antenna using usrp on gnueSAT Publishing House
 
The green aggregates for sustainable development in construction industry
The green aggregates for sustainable development in construction industryThe green aggregates for sustainable development in construction industry
The green aggregates for sustainable development in construction industryeSAT Publishing House
 
Conceptual design of injection mould tool for inlet
Conceptual design of injection mould tool for inletConceptual design of injection mould tool for inlet
Conceptual design of injection mould tool for inleteSAT Publishing House
 
Cyclone disaster on housing and coastal area
Cyclone disaster on housing and coastal areaCyclone disaster on housing and coastal area
Cyclone disaster on housing and coastal areaeSAT Publishing House
 
Redeeming of processor for cyber physical systems
Redeeming of processor for cyber physical systemsRedeeming of processor for cyber physical systems
Redeeming of processor for cyber physical systemseSAT Publishing House
 
Umts femto access point for higher data rate and better quality of service to...
Umts femto access point for higher data rate and better quality of service to...Umts femto access point for higher data rate and better quality of service to...
Umts femto access point for higher data rate and better quality of service to...eSAT Publishing House
 
A comparative study on the customer perception of the
A comparative study on the customer perception of theA comparative study on the customer perception of the
A comparative study on the customer perception of theeSAT Publishing House
 
Studies on effect of mineral admixtures on durability
Studies on effect of mineral admixtures on durabilityStudies on effect of mineral admixtures on durability
Studies on effect of mineral admixtures on durabilityeSAT Publishing House
 
Community detection in social networks an overview
Community detection in social networks an overviewCommunity detection in social networks an overview
Community detection in social networks an overvieweSAT Publishing House
 
Enhancement in power delay product by driver and interconnect optimization
Enhancement in power delay product by driver and interconnect optimizationEnhancement in power delay product by driver and interconnect optimization
Enhancement in power delay product by driver and interconnect optimizationeSAT Publishing House
 
Proposed aes for image steganography in different medias
Proposed aes for image steganography in different mediasProposed aes for image steganography in different medias
Proposed aes for image steganography in different mediaseSAT Publishing House
 
Influence of process parameters on depth of
Influence of process parameters on depth ofInfluence of process parameters on depth of
Influence of process parameters on depth ofeSAT Publishing House
 
A brief review of segmentation methods for medical
A brief review of segmentation methods for medicalA brief review of segmentation methods for medical
A brief review of segmentation methods for medicaleSAT Publishing House
 
Investigation into machining characteristics of trialumane
Investigation into machining characteristics of trialumaneInvestigation into machining characteristics of trialumane
Investigation into machining characteristics of trialumaneeSAT Publishing House
 
Compact quasi self complementary elliptical disc
Compact quasi self complementary elliptical discCompact quasi self complementary elliptical disc
Compact quasi self complementary elliptical disceSAT Publishing House
 
Fpga based low power and high performance address
Fpga based low power and high performance addressFpga based low power and high performance address
Fpga based low power and high performance addresseSAT Publishing House
 

Viewers also liked (20)

Development of mobile surface water filtration system through simulation usin...
Development of mobile surface water filtration system through simulation usin...Development of mobile surface water filtration system through simulation usin...
Development of mobile surface water filtration system through simulation usin...
 
Diabetic maculopathy detection using fundus fluorescein angiogram images a ...
Diabetic maculopathy detection using fundus fluorescein angiogram images   a ...Diabetic maculopathy detection using fundus fluorescein angiogram images   a ...
Diabetic maculopathy detection using fundus fluorescein angiogram images a ...
 
Design of passengers vehicle body on fire accidents
Design of passengers vehicle body on fire accidentsDesign of passengers vehicle body on fire accidents
Design of passengers vehicle body on fire accidents
 
Analysis of roucairol and carvalho approach in
Analysis of roucairol and carvalho approach inAnalysis of roucairol and carvalho approach in
Analysis of roucairol and carvalho approach in
 
Radiation pattern of yagi uda antenna using usrp on gnu
Radiation pattern of yagi uda antenna using usrp on gnuRadiation pattern of yagi uda antenna using usrp on gnu
Radiation pattern of yagi uda antenna using usrp on gnu
 
The green aggregates for sustainable development in construction industry
The green aggregates for sustainable development in construction industryThe green aggregates for sustainable development in construction industry
The green aggregates for sustainable development in construction industry
 
Conceptual design of injection mould tool for inlet
Conceptual design of injection mould tool for inletConceptual design of injection mould tool for inlet
Conceptual design of injection mould tool for inlet
 
Cyclone disaster on housing and coastal area
Cyclone disaster on housing and coastal areaCyclone disaster on housing and coastal area
Cyclone disaster on housing and coastal area
 
Redeeming of processor for cyber physical systems
Redeeming of processor for cyber physical systemsRedeeming of processor for cyber physical systems
Redeeming of processor for cyber physical systems
 
Umts femto access point for higher data rate and better quality of service to...
Umts femto access point for higher data rate and better quality of service to...Umts femto access point for higher data rate and better quality of service to...
Umts femto access point for higher data rate and better quality of service to...
 
A comparative study on the customer perception of the
A comparative study on the customer perception of theA comparative study on the customer perception of the
A comparative study on the customer perception of the
 
Studies on effect of mineral admixtures on durability
Studies on effect of mineral admixtures on durabilityStudies on effect of mineral admixtures on durability
Studies on effect of mineral admixtures on durability
 
Community detection in social networks an overview
Community detection in social networks an overviewCommunity detection in social networks an overview
Community detection in social networks an overview
 
Enhancement in power delay product by driver and interconnect optimization
Enhancement in power delay product by driver and interconnect optimizationEnhancement in power delay product by driver and interconnect optimization
Enhancement in power delay product by driver and interconnect optimization
 
Proposed aes for image steganography in different medias
Proposed aes for image steganography in different mediasProposed aes for image steganography in different medias
Proposed aes for image steganography in different medias
 
Influence of process parameters on depth of
Influence of process parameters on depth ofInfluence of process parameters on depth of
Influence of process parameters on depth of
 
A brief review of segmentation methods for medical
A brief review of segmentation methods for medicalA brief review of segmentation methods for medical
A brief review of segmentation methods for medical
 
Investigation into machining characteristics of trialumane
Investigation into machining characteristics of trialumaneInvestigation into machining characteristics of trialumane
Investigation into machining characteristics of trialumane
 
Compact quasi self complementary elliptical disc
Compact quasi self complementary elliptical discCompact quasi self complementary elliptical disc
Compact quasi self complementary elliptical disc
 
Fpga based low power and high performance address
Fpga based low power and high performance addressFpga based low power and high performance address
Fpga based low power and high performance address
 

Similar to Evaluation of reactances and time constants of synchronous generator

Performance Evaluation of Synchronous Generator under Sudden Loss of Excitation
Performance Evaluation of Synchronous Generator under Sudden Loss of ExcitationPerformance Evaluation of Synchronous Generator under Sudden Loss of Excitation
Performance Evaluation of Synchronous Generator under Sudden Loss of Excitationpaperpublications3
 
IRJET-Management of power factor and harmonic
IRJET-Management of power factor and harmonicIRJET-Management of power factor and harmonic
IRJET-Management of power factor and harmonicIRJET Journal
 
Implementation and control of integral cycle controller for resistance spot w...
Implementation and control of integral cycle controller for resistance spot w...Implementation and control of integral cycle controller for resistance spot w...
Implementation and control of integral cycle controller for resistance spot w...eSAT Journals
 
Calculation and comparison of circuit breaker parameters in Power World Simul...
Calculation and comparison of circuit breaker parameters in Power World Simul...Calculation and comparison of circuit breaker parameters in Power World Simul...
Calculation and comparison of circuit breaker parameters in Power World Simul...IJERA Editor
 
Calculation and comparison of circuit breaker parameters in Power World Simul...
Calculation and comparison of circuit breaker parameters in Power World Simul...Calculation and comparison of circuit breaker parameters in Power World Simul...
Calculation and comparison of circuit breaker parameters in Power World Simul...IJERA Editor
 
IRJET- Generation and Control of Transient Overvoltages in Power System Networks
IRJET- Generation and Control of Transient Overvoltages in Power System NetworksIRJET- Generation and Control of Transient Overvoltages in Power System Networks
IRJET- Generation and Control of Transient Overvoltages in Power System NetworksIRJET Journal
 
POWER QUALITY ENHANCEMENT USING UPQC
POWER QUALITY ENHANCEMENT USING UPQCPOWER QUALITY ENHANCEMENT USING UPQC
POWER QUALITY ENHANCEMENT USING UPQCIRJET Journal
 
Power quality enhancement by improving voltage stability using dstatcom
Power quality enhancement by improving voltage stability using dstatcomPower quality enhancement by improving voltage stability using dstatcom
Power quality enhancement by improving voltage stability using dstatcomeSAT Publishing House
 
POWER QUALITY ISSUE WITH GRID CONNECTED WIND ENERGY SYSTRM
POWER QUALITY ISSUE WITH GRID CONNECTED WIND ENERGY SYSTRMPOWER QUALITY ISSUE WITH GRID CONNECTED WIND ENERGY SYSTRM
POWER QUALITY ISSUE WITH GRID CONNECTED WIND ENERGY SYSTRMRavijesh Kumar
 
IRJET- Automated Energy Monitering System and Power Factor Improvement
IRJET-  	  Automated Energy Monitering System and Power Factor ImprovementIRJET-  	  Automated Energy Monitering System and Power Factor Improvement
IRJET- Automated Energy Monitering System and Power Factor ImprovementIRJET Journal
 
Power Quality Improvement by SRF Based Control using D-STATCOM
Power Quality Improvement by  SRF Based Control using D-STATCOMPower Quality Improvement by  SRF Based Control using D-STATCOM
Power Quality Improvement by SRF Based Control using D-STATCOMIRJET Journal
 
Mitigation of Voltage and Current Harmonics using UPQC Base on Synchronous Re...
Mitigation of Voltage and Current Harmonics using UPQC Base on Synchronous Re...Mitigation of Voltage and Current Harmonics using UPQC Base on Synchronous Re...
Mitigation of Voltage and Current Harmonics using UPQC Base on Synchronous Re...IRJET Journal
 
IRJET- Reactive Power Management using TSC-TCR
IRJET-  	  Reactive Power Management using TSC-TCRIRJET-  	  Reactive Power Management using TSC-TCR
IRJET- Reactive Power Management using TSC-TCRIRJET Journal
 
POWER QUALITY IMPROVEMENT AND FAULT RIDE THROUGH OF GRID CONNECTED WIND ENE...
POWER QUALITY IMPROVEMENT AND FAULT RIDE THROUGH OF   GRID CONNECTED WIND ENE...POWER QUALITY IMPROVEMENT AND FAULT RIDE THROUGH OF   GRID CONNECTED WIND ENE...
POWER QUALITY IMPROVEMENT AND FAULT RIDE THROUGH OF GRID CONNECTED WIND ENE...Bharadwaj S
 
fault ride through- doubly fed induction generator
fault ride through- doubly fed induction generatorfault ride through- doubly fed induction generator
fault ride through- doubly fed induction generatorsnh2k19
 
IRJET- PI Controller based Shunt Connected Three Phase Active Power Filter
IRJET- PI Controller based Shunt Connected Three Phase Active Power FilterIRJET- PI Controller based Shunt Connected Three Phase Active Power Filter
IRJET- PI Controller based Shunt Connected Three Phase Active Power FilterIRJET Journal
 
Power Quality Improvement using DVR (Dynamic Voltage Restorer) Under Various ...
Power Quality Improvement using DVR (Dynamic Voltage Restorer) Under Various ...Power Quality Improvement using DVR (Dynamic Voltage Restorer) Under Various ...
Power Quality Improvement using DVR (Dynamic Voltage Restorer) Under Various ...IRJET Journal
 
Performance, Modelling & Simulation of Frequency Relays for Distributed Gener...
Performance, Modelling & Simulation of Frequency Relays for Distributed Gener...Performance, Modelling & Simulation of Frequency Relays for Distributed Gener...
Performance, Modelling & Simulation of Frequency Relays for Distributed Gener...Niraj Solanki
 

Similar to Evaluation of reactances and time constants of synchronous generator (20)

Performance Evaluation of Synchronous Generator under Sudden Loss of Excitation
Performance Evaluation of Synchronous Generator under Sudden Loss of ExcitationPerformance Evaluation of Synchronous Generator under Sudden Loss of Excitation
Performance Evaluation of Synchronous Generator under Sudden Loss of Excitation
 
IRJET-Management of power factor and harmonic
IRJET-Management of power factor and harmonicIRJET-Management of power factor and harmonic
IRJET-Management of power factor and harmonic
 
Implementation and control of integral cycle controller for resistance spot w...
Implementation and control of integral cycle controller for resistance spot w...Implementation and control of integral cycle controller for resistance spot w...
Implementation and control of integral cycle controller for resistance spot w...
 
Calculation and comparison of circuit breaker parameters in Power World Simul...
Calculation and comparison of circuit breaker parameters in Power World Simul...Calculation and comparison of circuit breaker parameters in Power World Simul...
Calculation and comparison of circuit breaker parameters in Power World Simul...
 
Calculation and comparison of circuit breaker parameters in Power World Simul...
Calculation and comparison of circuit breaker parameters in Power World Simul...Calculation and comparison of circuit breaker parameters in Power World Simul...
Calculation and comparison of circuit breaker parameters in Power World Simul...
 
IRJET- Generation and Control of Transient Overvoltages in Power System Networks
IRJET- Generation and Control of Transient Overvoltages in Power System NetworksIRJET- Generation and Control of Transient Overvoltages in Power System Networks
IRJET- Generation and Control of Transient Overvoltages in Power System Networks
 
POWER QUALITY ENHANCEMENT USING UPQC
POWER QUALITY ENHANCEMENT USING UPQCPOWER QUALITY ENHANCEMENT USING UPQC
POWER QUALITY ENHANCEMENT USING UPQC
 
Power quality enhancement by improving voltage stability using dstatcom
Power quality enhancement by improving voltage stability using dstatcomPower quality enhancement by improving voltage stability using dstatcom
Power quality enhancement by improving voltage stability using dstatcom
 
POWER QUALITY ISSUE WITH GRID CONNECTED WIND ENERGY SYSTRM
POWER QUALITY ISSUE WITH GRID CONNECTED WIND ENERGY SYSTRMPOWER QUALITY ISSUE WITH GRID CONNECTED WIND ENERGY SYSTRM
POWER QUALITY ISSUE WITH GRID CONNECTED WIND ENERGY SYSTRM
 
IRJET- Automated Energy Monitering System and Power Factor Improvement
IRJET-  	  Automated Energy Monitering System and Power Factor ImprovementIRJET-  	  Automated Energy Monitering System and Power Factor Improvement
IRJET- Automated Energy Monitering System and Power Factor Improvement
 
H45014650
H45014650H45014650
H45014650
 
Power Quality Improvement by SRF Based Control using D-STATCOM
Power Quality Improvement by  SRF Based Control using D-STATCOMPower Quality Improvement by  SRF Based Control using D-STATCOM
Power Quality Improvement by SRF Based Control using D-STATCOM
 
Mitigation of Voltage and Current Harmonics using UPQC Base on Synchronous Re...
Mitigation of Voltage and Current Harmonics using UPQC Base on Synchronous Re...Mitigation of Voltage and Current Harmonics using UPQC Base on Synchronous Re...
Mitigation of Voltage and Current Harmonics using UPQC Base on Synchronous Re...
 
IRJET- Reactive Power Management using TSC-TCR
IRJET-  	  Reactive Power Management using TSC-TCRIRJET-  	  Reactive Power Management using TSC-TCR
IRJET- Reactive Power Management using TSC-TCR
 
POWER QUALITY IMPROVEMENT AND FAULT RIDE THROUGH OF GRID CONNECTED WIND ENE...
POWER QUALITY IMPROVEMENT AND FAULT RIDE THROUGH OF   GRID CONNECTED WIND ENE...POWER QUALITY IMPROVEMENT AND FAULT RIDE THROUGH OF   GRID CONNECTED WIND ENE...
POWER QUALITY IMPROVEMENT AND FAULT RIDE THROUGH OF GRID CONNECTED WIND ENE...
 
fault ride through- doubly fed induction generator
fault ride through- doubly fed induction generatorfault ride through- doubly fed induction generator
fault ride through- doubly fed induction generator
 
Gr3412151231
Gr3412151231Gr3412151231
Gr3412151231
 
IRJET- PI Controller based Shunt Connected Three Phase Active Power Filter
IRJET- PI Controller based Shunt Connected Three Phase Active Power FilterIRJET- PI Controller based Shunt Connected Three Phase Active Power Filter
IRJET- PI Controller based Shunt Connected Three Phase Active Power Filter
 
Power Quality Improvement using DVR (Dynamic Voltage Restorer) Under Various ...
Power Quality Improvement using DVR (Dynamic Voltage Restorer) Under Various ...Power Quality Improvement using DVR (Dynamic Voltage Restorer) Under Various ...
Power Quality Improvement using DVR (Dynamic Voltage Restorer) Under Various ...
 
Performance, Modelling & Simulation of Frequency Relays for Distributed Gener...
Performance, Modelling & Simulation of Frequency Relays for Distributed Gener...Performance, Modelling & Simulation of Frequency Relays for Distributed Gener...
Performance, Modelling & Simulation of Frequency Relays for Distributed Gener...
 

More from eSAT Publishing House

Likely impacts of hudhud on the environment of visakhapatnam
Likely impacts of hudhud on the environment of visakhapatnamLikely impacts of hudhud on the environment of visakhapatnam
Likely impacts of hudhud on the environment of visakhapatnameSAT Publishing House
 
Impact of flood disaster in a drought prone area – case study of alampur vill...
Impact of flood disaster in a drought prone area – case study of alampur vill...Impact of flood disaster in a drought prone area – case study of alampur vill...
Impact of flood disaster in a drought prone area – case study of alampur vill...eSAT Publishing House
 
Hudhud cyclone – a severe disaster in visakhapatnam
Hudhud cyclone – a severe disaster in visakhapatnamHudhud cyclone – a severe disaster in visakhapatnam
Hudhud cyclone – a severe disaster in visakhapatnameSAT Publishing House
 
Groundwater investigation using geophysical methods a case study of pydibhim...
Groundwater investigation using geophysical methods  a case study of pydibhim...Groundwater investigation using geophysical methods  a case study of pydibhim...
Groundwater investigation using geophysical methods a case study of pydibhim...eSAT Publishing House
 
Flood related disasters concerned to urban flooding in bangalore, india
Flood related disasters concerned to urban flooding in bangalore, indiaFlood related disasters concerned to urban flooding in bangalore, india
Flood related disasters concerned to urban flooding in bangalore, indiaeSAT Publishing House
 
Enhancing post disaster recovery by optimal infrastructure capacity building
Enhancing post disaster recovery by optimal infrastructure capacity buildingEnhancing post disaster recovery by optimal infrastructure capacity building
Enhancing post disaster recovery by optimal infrastructure capacity buildingeSAT Publishing House
 
Effect of lintel and lintel band on the global performance of reinforced conc...
Effect of lintel and lintel band on the global performance of reinforced conc...Effect of lintel and lintel band on the global performance of reinforced conc...
Effect of lintel and lintel band on the global performance of reinforced conc...eSAT Publishing House
 
Wind damage to trees in the gitam university campus at visakhapatnam by cyclo...
Wind damage to trees in the gitam university campus at visakhapatnam by cyclo...Wind damage to trees in the gitam university campus at visakhapatnam by cyclo...
Wind damage to trees in the gitam university campus at visakhapatnam by cyclo...eSAT Publishing House
 
Wind damage to buildings, infrastrucuture and landscape elements along the be...
Wind damage to buildings, infrastrucuture and landscape elements along the be...Wind damage to buildings, infrastrucuture and landscape elements along the be...
Wind damage to buildings, infrastrucuture and landscape elements along the be...eSAT Publishing House
 
Shear strength of rc deep beam panels – a review
Shear strength of rc deep beam panels – a reviewShear strength of rc deep beam panels – a review
Shear strength of rc deep beam panels – a revieweSAT Publishing House
 
Role of voluntary teams of professional engineers in dissater management – ex...
Role of voluntary teams of professional engineers in dissater management – ex...Role of voluntary teams of professional engineers in dissater management – ex...
Role of voluntary teams of professional engineers in dissater management – ex...eSAT Publishing House
 
Risk analysis and environmental hazard management
Risk analysis and environmental hazard managementRisk analysis and environmental hazard management
Risk analysis and environmental hazard managementeSAT Publishing House
 
Review study on performance of seismically tested repaired shear walls
Review study on performance of seismically tested repaired shear wallsReview study on performance of seismically tested repaired shear walls
Review study on performance of seismically tested repaired shear wallseSAT Publishing House
 
Monitoring and assessment of air quality with reference to dust particles (pm...
Monitoring and assessment of air quality with reference to dust particles (pm...Monitoring and assessment of air quality with reference to dust particles (pm...
Monitoring and assessment of air quality with reference to dust particles (pm...eSAT Publishing House
 
Low cost wireless sensor networks and smartphone applications for disaster ma...
Low cost wireless sensor networks and smartphone applications for disaster ma...Low cost wireless sensor networks and smartphone applications for disaster ma...
Low cost wireless sensor networks and smartphone applications for disaster ma...eSAT Publishing House
 
Coastal zones – seismic vulnerability an analysis from east coast of india
Coastal zones – seismic vulnerability an analysis from east coast of indiaCoastal zones – seismic vulnerability an analysis from east coast of india
Coastal zones – seismic vulnerability an analysis from east coast of indiaeSAT Publishing House
 
Can fracture mechanics predict damage due disaster of structures
Can fracture mechanics predict damage due disaster of structuresCan fracture mechanics predict damage due disaster of structures
Can fracture mechanics predict damage due disaster of structureseSAT Publishing House
 
Assessment of seismic susceptibility of rc buildings
Assessment of seismic susceptibility of rc buildingsAssessment of seismic susceptibility of rc buildings
Assessment of seismic susceptibility of rc buildingseSAT Publishing House
 
A geophysical insight of earthquake occurred on 21 st may 2014 off paradip, b...
A geophysical insight of earthquake occurred on 21 st may 2014 off paradip, b...A geophysical insight of earthquake occurred on 21 st may 2014 off paradip, b...
A geophysical insight of earthquake occurred on 21 st may 2014 off paradip, b...eSAT Publishing House
 
Effect of hudhud cyclone on the development of visakhapatnam as smart and gre...
Effect of hudhud cyclone on the development of visakhapatnam as smart and gre...Effect of hudhud cyclone on the development of visakhapatnam as smart and gre...
Effect of hudhud cyclone on the development of visakhapatnam as smart and gre...eSAT Publishing House
 

More from eSAT Publishing House (20)

Likely impacts of hudhud on the environment of visakhapatnam
Likely impacts of hudhud on the environment of visakhapatnamLikely impacts of hudhud on the environment of visakhapatnam
Likely impacts of hudhud on the environment of visakhapatnam
 
Impact of flood disaster in a drought prone area – case study of alampur vill...
Impact of flood disaster in a drought prone area – case study of alampur vill...Impact of flood disaster in a drought prone area – case study of alampur vill...
Impact of flood disaster in a drought prone area – case study of alampur vill...
 
Hudhud cyclone – a severe disaster in visakhapatnam
Hudhud cyclone – a severe disaster in visakhapatnamHudhud cyclone – a severe disaster in visakhapatnam
Hudhud cyclone – a severe disaster in visakhapatnam
 
Groundwater investigation using geophysical methods a case study of pydibhim...
Groundwater investigation using geophysical methods  a case study of pydibhim...Groundwater investigation using geophysical methods  a case study of pydibhim...
Groundwater investigation using geophysical methods a case study of pydibhim...
 
Flood related disasters concerned to urban flooding in bangalore, india
Flood related disasters concerned to urban flooding in bangalore, indiaFlood related disasters concerned to urban flooding in bangalore, india
Flood related disasters concerned to urban flooding in bangalore, india
 
Enhancing post disaster recovery by optimal infrastructure capacity building
Enhancing post disaster recovery by optimal infrastructure capacity buildingEnhancing post disaster recovery by optimal infrastructure capacity building
Enhancing post disaster recovery by optimal infrastructure capacity building
 
Effect of lintel and lintel band on the global performance of reinforced conc...
Effect of lintel and lintel band on the global performance of reinforced conc...Effect of lintel and lintel band on the global performance of reinforced conc...
Effect of lintel and lintel band on the global performance of reinforced conc...
 
Wind damage to trees in the gitam university campus at visakhapatnam by cyclo...
Wind damage to trees in the gitam university campus at visakhapatnam by cyclo...Wind damage to trees in the gitam university campus at visakhapatnam by cyclo...
Wind damage to trees in the gitam university campus at visakhapatnam by cyclo...
 
Wind damage to buildings, infrastrucuture and landscape elements along the be...
Wind damage to buildings, infrastrucuture and landscape elements along the be...Wind damage to buildings, infrastrucuture and landscape elements along the be...
Wind damage to buildings, infrastrucuture and landscape elements along the be...
 
Shear strength of rc deep beam panels – a review
Shear strength of rc deep beam panels – a reviewShear strength of rc deep beam panels – a review
Shear strength of rc deep beam panels – a review
 
Role of voluntary teams of professional engineers in dissater management – ex...
Role of voluntary teams of professional engineers in dissater management – ex...Role of voluntary teams of professional engineers in dissater management – ex...
Role of voluntary teams of professional engineers in dissater management – ex...
 
Risk analysis and environmental hazard management
Risk analysis and environmental hazard managementRisk analysis and environmental hazard management
Risk analysis and environmental hazard management
 
Review study on performance of seismically tested repaired shear walls
Review study on performance of seismically tested repaired shear wallsReview study on performance of seismically tested repaired shear walls
Review study on performance of seismically tested repaired shear walls
 
Monitoring and assessment of air quality with reference to dust particles (pm...
Monitoring and assessment of air quality with reference to dust particles (pm...Monitoring and assessment of air quality with reference to dust particles (pm...
Monitoring and assessment of air quality with reference to dust particles (pm...
 
Low cost wireless sensor networks and smartphone applications for disaster ma...
Low cost wireless sensor networks and smartphone applications for disaster ma...Low cost wireless sensor networks and smartphone applications for disaster ma...
Low cost wireless sensor networks and smartphone applications for disaster ma...
 
Coastal zones – seismic vulnerability an analysis from east coast of india
Coastal zones – seismic vulnerability an analysis from east coast of indiaCoastal zones – seismic vulnerability an analysis from east coast of india
Coastal zones – seismic vulnerability an analysis from east coast of india
 
Can fracture mechanics predict damage due disaster of structures
Can fracture mechanics predict damage due disaster of structuresCan fracture mechanics predict damage due disaster of structures
Can fracture mechanics predict damage due disaster of structures
 
Assessment of seismic susceptibility of rc buildings
Assessment of seismic susceptibility of rc buildingsAssessment of seismic susceptibility of rc buildings
Assessment of seismic susceptibility of rc buildings
 
A geophysical insight of earthquake occurred on 21 st may 2014 off paradip, b...
A geophysical insight of earthquake occurred on 21 st may 2014 off paradip, b...A geophysical insight of earthquake occurred on 21 st may 2014 off paradip, b...
A geophysical insight of earthquake occurred on 21 st may 2014 off paradip, b...
 
Effect of hudhud cyclone on the development of visakhapatnam as smart and gre...
Effect of hudhud cyclone on the development of visakhapatnam as smart and gre...Effect of hudhud cyclone on the development of visakhapatnam as smart and gre...
Effect of hudhud cyclone on the development of visakhapatnam as smart and gre...
 

Recently uploaded

Porous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writingPorous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writingrakeshbaidya232001
 
College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service NashikCollege Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service NashikCall Girls in Nagpur High Profile
 
SPICE PARK APR2024 ( 6,793 SPICE Models )
SPICE PARK APR2024 ( 6,793 SPICE Models )SPICE PARK APR2024 ( 6,793 SPICE Models )
SPICE PARK APR2024 ( 6,793 SPICE Models )Tsuyoshi Horigome
 
Call Girls Delhi {Jodhpur} 9711199012 high profile service
Call Girls Delhi {Jodhpur} 9711199012 high profile serviceCall Girls Delhi {Jodhpur} 9711199012 high profile service
Call Girls Delhi {Jodhpur} 9711199012 high profile servicerehmti665
 
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur High Profile
 
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...ranjana rawat
 
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur High Profile
 
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...ranjana rawat
 
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLS
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLSMANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLS
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLSSIVASHANKAR N
 
the ladakh protest in leh ladakh 2024 sonam wangchuk.pptx
the ladakh protest in leh ladakh 2024 sonam wangchuk.pptxthe ladakh protest in leh ladakh 2024 sonam wangchuk.pptx
the ladakh protest in leh ladakh 2024 sonam wangchuk.pptxhumanexperienceaaa
 
Coefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptxCoefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptxAsutosh Ranjan
 
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptxDecoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptxJoão Esperancinha
 
HARMONY IN THE NATURE AND EXISTENCE - Unit-IV
HARMONY IN THE NATURE AND EXISTENCE - Unit-IVHARMONY IN THE NATURE AND EXISTENCE - Unit-IV
HARMONY IN THE NATURE AND EXISTENCE - Unit-IVRajaP95
 
Software Development Life Cycle By Team Orange (Dept. of Pharmacy)
Software Development Life Cycle By  Team Orange (Dept. of Pharmacy)Software Development Life Cycle By  Team Orange (Dept. of Pharmacy)
Software Development Life Cycle By Team Orange (Dept. of Pharmacy)Suman Mia
 
Introduction and different types of Ethernet.pptx
Introduction and different types of Ethernet.pptxIntroduction and different types of Ethernet.pptx
Introduction and different types of Ethernet.pptxupamatechverse
 
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...ranjana rawat
 
Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...
Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...
Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...srsj9000
 

Recently uploaded (20)

Porous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writingPorous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writing
 
9953056974 Call Girls In South Ex, Escorts (Delhi) NCR.pdf
9953056974 Call Girls In South Ex, Escorts (Delhi) NCR.pdf9953056974 Call Girls In South Ex, Escorts (Delhi) NCR.pdf
9953056974 Call Girls In South Ex, Escorts (Delhi) NCR.pdf
 
College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service NashikCollege Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
 
SPICE PARK APR2024 ( 6,793 SPICE Models )
SPICE PARK APR2024 ( 6,793 SPICE Models )SPICE PARK APR2024 ( 6,793 SPICE Models )
SPICE PARK APR2024 ( 6,793 SPICE Models )
 
Call Girls Delhi {Jodhpur} 9711199012 high profile service
Call Girls Delhi {Jodhpur} 9711199012 high profile serviceCall Girls Delhi {Jodhpur} 9711199012 high profile service
Call Girls Delhi {Jodhpur} 9711199012 high profile service
 
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
Call Girls in Nagpur Suman Call 7001035870 Meet With Nagpur Escorts
 
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
 
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
 
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
 
Roadmap to Membership of RICS - Pathways and Routes
Roadmap to Membership of RICS - Pathways and RoutesRoadmap to Membership of RICS - Pathways and Routes
Roadmap to Membership of RICS - Pathways and Routes
 
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLS
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLSMANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLS
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLS
 
★ CALL US 9953330565 ( HOT Young Call Girls In Badarpur delhi NCR
★ CALL US 9953330565 ( HOT Young Call Girls In Badarpur delhi NCR★ CALL US 9953330565 ( HOT Young Call Girls In Badarpur delhi NCR
★ CALL US 9953330565 ( HOT Young Call Girls In Badarpur delhi NCR
 
the ladakh protest in leh ladakh 2024 sonam wangchuk.pptx
the ladakh protest in leh ladakh 2024 sonam wangchuk.pptxthe ladakh protest in leh ladakh 2024 sonam wangchuk.pptx
the ladakh protest in leh ladakh 2024 sonam wangchuk.pptx
 
Coefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptxCoefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptx
 
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptxDecoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
 
HARMONY IN THE NATURE AND EXISTENCE - Unit-IV
HARMONY IN THE NATURE AND EXISTENCE - Unit-IVHARMONY IN THE NATURE AND EXISTENCE - Unit-IV
HARMONY IN THE NATURE AND EXISTENCE - Unit-IV
 
Software Development Life Cycle By Team Orange (Dept. of Pharmacy)
Software Development Life Cycle By  Team Orange (Dept. of Pharmacy)Software Development Life Cycle By  Team Orange (Dept. of Pharmacy)
Software Development Life Cycle By Team Orange (Dept. of Pharmacy)
 
Introduction and different types of Ethernet.pptx
Introduction and different types of Ethernet.pptxIntroduction and different types of Ethernet.pptx
Introduction and different types of Ethernet.pptx
 
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
 
Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...
Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...
Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...
 

Evaluation of reactances and time constants of synchronous generator

  • 1. IJRET: International Journal of Research in Engineering and Technology eISSN: 2319-1163 | pISSN: 2321-7308 __________________________________________________________________________________________ Volume: 03 Special Issue: 03 | May-2014 | NCRIET-2014, Available @ http://www.ijret.org 380 EVALUATION OF REACTANCES AND TIME CONSTANTS OF SYNCHRONOUS GENERATOR Shaheena Khanum1, K.L Ratnakar2, Ramesh K.N3, Ravi.R4 1PG Student, Department of Electrical and Electronics Engineering, Sri Siddhartha Academy of Higher Education, Tumkur, Karnataka, India 2Professor, Department of Electrical and Electronics Engineering, Sri Siddhartha Academy of Higher Education Tumkur, Karnataka, India 3Quality Assurance, TD Power Systems Limited, Dabaspet, Bangalore, Karnataka, India 4PG Student, Department of Electrical and Electronics Engineering, Sri Siddhartha Academy of Higher Education, Tumkur, Karnataka, India Abstract For any power equipment the control system and protection system plays an imperative role as the dependency on the power equipment in any industry will be very high. Thus for the Generator the Reactances and Time Constants becomes controlling parameter and hence protecting it is necessary for prolonged usage. In general reactance shall be defined as “non-resistive component of impedance in an AC circuit, arising from the effect of inductance or capacitance or both and causing the current to be out of phase with the electromotive force causing it”. In other word it can also be defined as the imaginary part of the impedance in any power circuit. There are various Reactances and Time Constants which contributes during the selection of control systems and protection scheme for any Generator. Therefore practical evaluation of those parameters shall also be super critical same as those are by calculation. More accurate measurement or the calculation of reactance shall certainly give us more stabilized error free system and hence ensuring a healthy control system. As there are different tests or different methods to measure and calculate the Reactances and Time Constants, in this context we are considering Line to Line fault (L-L fault), Double line to Ground fault and Sudden three phase short circuit fault to determine the Negative Sequence reactance, Zero Sequence reactance, Sub-transient and Transient reactance and time constants respectively. The fault condition will be demonstrated with the 40MW, 11KV, 2624A, 4pole, 50 Hz synchronous generator and above mentioned parameters are calculated based on references available. Keywords: Reactances, Time Constants, Testing of Alternator, Brushless Alternator. ----------------------------------------------------------------------***------------------------------------------------------------------------ 1. INTRODUCTION The synchronous machine is an ac machine in which the rotor moves at a speed which bears a constant relationship to the frequency of currents, in the armature winding. A synchronous machine is one of the important types of electric machines. Large ac networks operating at constant frequency of 50 Hz or 60 Hz rely almost exclusively on synchronous generators, also called the alternators, for the supply of electrical energy, and may have synchronous compensators at key points for control of reactive power. Private stand-by and peak load plants with diesel or gas-turbine prime movers also have synchronous generators. Non-land-based synchronous plants are found on oil rings, on large air-crafts and constant speed industrial drives with the possibility of power factor correction, but are not often built in small ratings for which the induction motor is cheaper. Synchronous machines are generally constructed in larger sizes. Small size alternators are not economical. The modern trend is to build alternators of very large sizes capable of generating 500MVA or even more. An alternator works on the principle of Faraday’s laws of Electro-Magnetic Induction. ―Whenever a conductor/coil cuts the magnetic flux an EMF is induced in that conductor. The magnitude of EMF induced in the conductor/coil is directly proportional to the rate of change of flux and the number of conductors‖. The main component which effects the operation of alternator is resistance and reactances. The effective resistance of the armature winding is somewhat greater than the conductor resistance, called the dc resistance, as measured by direct current. This is due to additional loss over the purely I2R loss, inside and sometimes outside the conductor, owing to alternating current. The main sources of this additional loss are  Eddy current in the surrounding material,  Magnetic hysteresis in the surrounding material and  Eddy currents or unequal current distribution in the conductor itself. In many cases it is sufficiently accurate to measure the armature resistance by direct current and increase it to a fictitious value, called the effective resistance, Re which is large enough to take care of these additional losses. Effective resistance, Re can vary widely from 1.25 to 1.75 or more times
  • 2. IJRET: International Journal of Research in Engineering and Technology eISSN: 2319-1163 | pISSN: 2321-7308 __________________________________________________________________________________________ Volume: 03 Special Issue: 03 | May-2014 | NCRIET-2014, Available @ http://www.ijret.org 381 the dc resistance, depending upon design. The EMF setup due to armature reaction MMF Fa is always in quadrature with the load current I and is proportional to it. Thus it is equivalent to an EMF induced in an inductive coil and the effect of armature reaction can, therefore, be considered equivalent to reactance drop IXa where Xa is the fictitious reactance which takes care of the armature reaction effect. The armature winding possesses a certain leakage reactance Xl. The sum of leakage reactance Xl and fictitious reactance Xa is called the synchronous reactance. 2. REACTANCES It can be defined as the imaginary part of the impedance in any power circuit. There are various Reactances and Time Constants which contribute during the selection of control systems and protection scheme for any Generator. Fig -1: Axes of Alternator The axis of symmetry of the north magnetic poles of the rotor is called the direct axis or d- axis. The axis of symmetry of the south magnetic poles is the negative d-axis. The axis of symmetry halfway between adjacent north and south poles is called the quadrature axis or q-axis. • Direct axis reactance (Xd): The quotient of the sustained value of that fundamental AC component of armature voltage, which is produced by the total direct-axis primary flux due to direct-axis armature current and the value of the fundamental AC component of this current, the machine running at rated speed. • Quadrature axis reactance (Xq): The quotient of the sustained value of that fundamental AC component of armature voltage, which is produced by the total quadrature- axis primary flux due to quadrature-axis armature current, and the value of the fundamental AC component of this current, the machine running at rated speed. • Direct-axis transient reactance (Xd’): The quotient of the initial value of a sudden change in that fundamental AC component of armature voltage, which is produced by the total direct-axis primary flux, and the value of the simultaneous change in fundamental AC component of direct-axis armature current, the machine running at rated speed and the high decrement components during the first cycles being excluded. • Direct axis sub-transient reactance (Xd”): The quotient of the initial value of a sudden change in that fundamental AC component of armature voltage, which is produced by the total direct-axis armature flux, and the value of the simultaneous change in fundamental AC component of direct-axis armature current, the machine running at rated speed. • Negative sequence reactance (X2): The quotient of the reactive fundamental component of negative sequence armature voltage, due to the presence of fundamental negative sequence armature current at rated frequency, by the value of that component of current, the machine running at rated speed. • Zero sequence reactance (Xo): The quotient of the reactive fundamental component of zero sequence armature voltage, due to the presence of fundamental zero sequence armature current at rated frequency, by the value of that component of current, the machine running at rated speed. 3. TIME CONSTANTS  Direct-axis transient short-circuit time constant (d): It is the time, in seconds, required for the transient alternating component of the short-circuit current to decrease to 1/ε0 or 0.368 times its initial value.  Direct-axis sub-transient short-circuit time constant (d): It is the time, in seconds, required for the sub-transient alternating component of the short-circuit current to decrease to 0.368 times its initial value.  Direct-axis transient open circuit time constant (do): It is the time, in seconds, required for the transient alternating component of the open-circuit current to decrease to 0.368 times its initial value. 4. TESTING OF SYNCHRONOUS GENERATOR In this paper, study of different types of testing is going to be done for an alternator. Testing is the practice of making objective judgments regarding the extent to which the product meets else fails to meet the specified objectives. In other words for any manufactured product or equipments it is essential that the evaluation of the product with reference to the specification and the applicable standards. It is also indispensable for any manufacturer to ensure their product is meeting all the requirements as per their design and by their processes. Testing of a Generator or an Alternator also play a vital role before it is being put in to continuous operation. As the manufacturing of Generator involves various crucial processes either it may be carried by machinery or by man or may be both put together and hence it becomes important to assess the work done at the end. Though each component and part of the Generator has undergone various tests it is necessary that the complete assembled Generator also shall undergo at least Routine (described later) tests to understand the basic performance. [1] Generator testing shall be of two types i.e. Type test and Routine test. Type test is inclusive of all routine tests along with some additional tests. Routine test is compulsory to
  • 3. IJRET: International Journal of Research in Engineering and Technology eISSN: 2319-1163 | pISSN: 2321-7308 __________________________________________________________________________________________ Volume: 03 Special Issue: 03 | May-2014 | NCRIET-2014, Available @ http://www.ijret.org 382 understand the elementary performance of the Generators which comes under serial production type. 4.1 Sudden Short Circuit Test 4.1.1 Circuit Fig-2: Sudden short circuit test setup 4.1.2 Procedure 1. Makes the connections as per the above diagram. 2. Run the generator to its rated speed. 3. Build up the voltage to 10% of the rated voltage. 4. Close the circuit breaker & check the waveforms. Check the waveform for the Clear identification of the amplitudes. (Should be 3 current & 1 voltage waveform) 5. If ok, then raise the voltage to 30% of the rated voltage then close the breaker, record the current and voltage waveforms. 6. Note down the steady state current, record & print waveforms. 4.2 Zero Sequence Test (Xo) 4.2.1 Circuit Fig-3: Zero sequence test setup 4.2.2 Procedure 1. Make the connections as per above circuit. 2. Run the machine to its rated speed 4. Record the values of current (I), voltage (V) and power. 5. Xo shall be calculated using measured values. 3. Increase the armature current in steps of 10%, 20%, 30 %, 40% and 50% of rated current. 4.3 Negative Sequence Test 4.3.1 Circuit Fig-4: Negative sequence test setup 4.3.2 Procedure 1. Make the connections as per above circuit. 2. Run the machine to its rated speed 3. Increase the armature current in steps of 10%, 20%, 30 %, 40% and 50% of rated current. 4. Record the values of current (I), voltage (V) and power. 5. X2 shall be calculated using measured values. 5. CALCULATIONS OF REACTANCES & TIME CONSTANTS 5.1 Three Phase Sudden Short Circuit Test and Determination of Characteristic Reactance and Time Constants. The synchronous reactance (Xd), transient reactance (X'd) and sub-transient reactance (X''d), and the transient short-circuit time constant (t'd) and sub-transient short circuit time constant (t''d) are used to describe and machine's behavior on sudden short-circuit. This can be done in accordance with the following equation for the AC RMS components of current following a three-phase short-circuit from no load neglecting armature-circuit resistances and assuming constant exciter voltage. [2] I (t) = (E/Xds) + ((E/Xd’ ) – (E/Xds)) ԑ (-t/Ʈd’ )+ (E/Xd’’ –E/ X’ d) ԑ (-t/Ʈd’’ ) Where, I (t): is the AC RMS short- circuit current, p.u. E: Is the AC RMS voltage before short circuit, p.u. t: is the time in seconds, measured from the instant of short circuit. In this expression, it is assumed that the current is composed of a constant term and two decaying exponential terms where the third term of the equation decays very much faster than the
  • 4. IJRET: International Journal of Research in Engineering and Technology eISSN: 2319-1163 | pISSN: 2321-7308 __________________________________________________________________________________________ Volume: 03 Special Issue: 03 | May-2014 | NCRIET-2014, Available @ http://www.ijret.org 383 second. By subtracting the first (constant) term and plotting the remainder on semi-logarithmic paper as a function of time, the curve would appear as a straight line after the rapidly decaying term decreases to zero. The rapidly decaying portion of the curve is the sub-transient portion, while the straight line is the transient portion. 5.2 Evaluation (a) Measure the voltage from wave form recorded (pk-pk) & converts the same to RMS value Es = Epk-pk*(PT ratio) / (2*sqtr (2)) (b) Measure the mV drop of steady state current from the waveform recorded & convert the same to amperes (RMS value) Is = mVpk-pk*(Shunt ratio) / (2*sqtr (2)) (c) Peak to Peak value (mV) of the currents from the waveform recorded is measured & RMS value of the currents are calculated to first 50 to 60 cycles. (d) Subtract the steady state current from point (c) & plot the graph for the component currents (I'k+I''k) in the semi log sheet with current in on log scale & time on linear scale. (e) To separate transient & sub-transient components, extrapolation to zero time from the straight portion by neglecting the rapid variation of current in first few cycles will give the initial values of corresponding current. [7] (f) From the semi log sheet I'k: is the AC RMS short-circuit transient current component in ampere (RMS). I''k: is the AC RMS short-circuit sub-transient current component in ampere (RMS). Es : is the voltage before short circuit in RMS. Is : is the AC RMS short-circuit steady state current in ampere (RMS). 5.3 Determination of Direct Axis Sub-Transient Reactance & Short Circuit Time Constant (Xd'' & Td'') To calculate Xd'' in % Xd'' in % = (Es*100)/(1.732*Zs*(I'k+I''k+Is)) Where, Zs (Ω): Synchronous impedance of the machine = Rated Voltage / (1.732*Rated Current) To calculate Td'' in seconds Td'' is the time required to decrease the sub-transient component to 1/e i.e. 0.368 of its initial value. OR Time for Id'', where Id''=0.368*I''k 5.4 Determination of Direct Axis Transient Reactance & Short-Circuit Time Constant (Xd' & Td') To calculate Xd' in % Xd' in % = (Es*100)/(1.732*Zs*(I'k+Is)) Where, Zs (Ω): Synchronous impedance of the machine = Rated Voltage/(1.732*Rated Current) To calculate Td' in seconds Td' is the time required to decrease the transient component to 1/e i.e. 0.368 of its initial value. OR Time for Id', where Id'=0.368*I'k 5.5 Determination of Direct Axis Synchronous Reactance (Xd) To calculate Xd in % Xd in % = (1/SCR)*100 Where, SCR: Short circuit ratio of the machine SCR = ( Ifoc/Ifsc) Ifoc: Field Current for rated voltage. Ifsc: Field Current for rated current. 5.6 Determination of Direct Axis Transient Open Circuit Time constant (Tdo') To calculate Tdo' in seconds Tdo' in seconds = (Xd*Td'/Xd') Fig-5: Analysis of ac component of short-circuit current (for one of three phases ) Fig-6: Transient & Sub-transien component of short-circuit
  • 5. IJRET: International Journal of Research in Engineering and Technology eISSN: 2319-1163 | pISSN: 2321-7308 __________________________________________________________________________________________ Volume: 03 Special Issue: 03 | May-2014 | NCRIET-2014, Available @ http://www.ijret.org 384 6. EXPERIMENTAL RESULTS Fig-7: Voltage and Current Waveforms Table- 1: Values of Reactances Reactances Design value(%) Calculated value (%) Xd 166 161.3 Xd’ 29 30.7 Xd’’ 23 25.2 X2 30 30.08 X0 17 18.15 Table- 2: Values of Time Constants As per the IEEE standards used the acceptable tolerance allowed is ±15% or 30% on one side. 7. CONCLUSIONS The above procedure and the calculation shall be used as a generalized method for calculation of Transient, sub-transient reactance X2, X0 and Time Constants for both cylindrical and salient pole type alternator of any rating. Though the Transient behavior involves tedious steps of calculation and deep analysis of the results, the above procedure helps in calculating the various parameters in easiest way with minimum calculation and time. ACKNOWLEDGEMENTS The authors express their sincere thanks to Dr. B. Rajesh Kamath, B.E., M.E., Ph.D., FIE., MISTE Head of the Dept. E&EE, SSIT, Tumkur for his many helpful suggestions. REFERENCES [1]. IEEE115 standards for ―Test procedure for synchronous machines‖. [2]. IEC60034 ―Methods for determining synchronous machine quantities from tests‖. [3]. Marxsen, A. L. and Morsztyn, K., "Analysis of Synchronous Machine Transient Tests Using a Microcomputer," Proceedings IEE, 124(4), pp. 377–380, 1977. [4]. C.Grantham, D. Sutanto, and B. M ismail, ―Steady-state and transient analysis of self-excited induction generators,‖ Proc Inst. Electrical Eng. B, vol. 136, no. 2, pp. 61–68, 1989. [5]. R. Leidhold, G. Garcia, and M. I. Valla, ―Field-oriented controlled induction generator with loss minimization,‖ IEEE Trans. Ind. Electron., vol. 49, pp. 147–155, Feb. 2002. [6]. Canay, I. M., "Causes of Discrepancies on Calculation of Rotor Quantities and Exact Equivalent Diagrams of the Synchronous Machine," IEEE Transactions on Power Apparatus and Systems, vol. PAS-88, pp. 1114–1120, July 1969. [7]. ―THE TRANSIENT REACTIONS OF ALTERNATORS‖ by William A Durgin and R. H. Whitehead, a paper to be presented at the 29th annual convention of the America Institute of Electrical Engineers, Boston, Mass., June 28, 1912. [8]. ―TRANSIENT PERFORMANCE OF THREE-PHASE INDUCTOR-TYPE SYNCHRONOUS GENERATORS: PAPER I- SYMMETRICAL SHORT CIRCUIT‖ By P.K. Dash, Regional Engineering College, Rourkele-8, Orissa, India. [9]. Coultes, M. E. and Watson, W., "Synchronous Machine Models by Standstill Frequency Response Tests," IEEE Transactions on Power Apparatus and Systems, vol. PAS-100, no. 4, pp. 1480–1489, April 1981. [10]. "Determination of Synchronous Machine Stability Study Constants"—EPRI Report EL 1424, vol. 1, Sept. 1980, Westinghouse Electric Corporation and vol. 2, Dec. 1980, Ontario Hydro. [Two of four reports on EPRI Project 997.] Time Constants Design value(sec) Calculated value (sec) Td’ 0.82 0.84 Td’’ 0.035 0.035 Td0’ 4.69 4.408