Study of Secondary Arc Current Suppression
Effects under Different Fault Location on
Extra High Voltage Line
1
Shalini Chandel, 2
A. K. Sharma
1, 2
Electrical Engineering Department, Jabalpur Engineering College, Jabalpur, India
Abstract: Overhead transmission lines are an essential component of power systems, being the most economical
means of transmitting electricity from remote sources of generation to the customer. It is therefore, vital that they
be protected and maintained in service to ensure the security of the supply to the end-user, and to protect the
capital investment of the power companies. When single phase grounding fault occurs in high voltage transmission
line, secondary arc current and recovery voltage must be suppressed in order to ensure that single phase auto-
reclosing operates reliably and successfully. Automatic single phase reclosing is used to clear single-phase-to-
ground-faults, which are 80% of the transient faults. In order to have successful fast reclosing, different methods
are used to extinguish the arc. One of the common methods is to use a single-phase reactor in the neutral of shunt
reactor, when the transmission line is compensated with shunt reactors. In this paper, exact arc modeling is used
for transient simulation of neutral reactor and guidelines for selecting the appropriate amount for the neutral
reactor are proposed, then uses MATLAB software to simulate suppression effect about different fault point
locations towards an example of 735 KV double ended sources high voltage transmission line. According to the
simulation results, suppression effects about different locations are distinct.
Keywords: High voltage transmission, single phase auto reclosing, secondary arc current, shunt reactor, neutral
small reactor.
1. INTRODUCTION
There are two main types of arcs appearing on power systems: arcs in open air, such as those found on transmission lines,
and constrained switching arcs, such as those found in circuit breakers. The work in this thesis will be concentrated on
arcs in open air.
Arcing faults on transmission lines can be divided into two separate periods: the primary arc and the secondary arc. Soon
after the fault, the two line end breakers will open (faulted phase only in this case) to isolate the fault. However, the other
line( healthy phases) are still energized. There is inductive and capacitive coupling between the faulted line and the
healthy phases, as well as between other conductors of parallel circuits.
2. GENERATION THEORY OF SECONDARY ARC CURRENT
Secondary arc is an electromagnetic transient phenomenon generated in the process of single-phase autoreclosing
operation. In figure 1 when the single phase (i.e. phase C) to ground fault occurs, the breaker at both ends of the fault
phase will be tripping and short circuit current which is provided with power system from both ends to the fault point will
be cut off. But this time the sound phases (phase A and B) are still running. There are loads current (Ia, Ib) flows through
and two phases still keep working voltages(Ea, Eb). Due to the function of inter-phase capacitance Cm and mutual
inductance M, the secondary current Ic is generated at the fault point Q and it contains two parts : capacitive component
and inductive component.
ISSN 2349-7815
International Journal of Recent Research in Electrical and Electronics Engineering (IJRREEE)
Vol. 3, Issue 2, pp: (46-52), Month: April 2016 - June 2016, Available at: www.paperpublications.org
Page | 47
Paper Publications
Fig 1: single phase to ground fault and generation of Secondary Arc Current
3. METHODS OF SECONDARY ARC CURRENT EXTINCTION
Nowadays there are two main suppression measures applied for secondary arc extinction, first Shunt reactor with neutral
small reactor and second is High speed grounding switches. These methods are used for suppress secondary arc current
by reducing its amplitude and shortening its burning time. In Japan HSGS method is used because EHV lines are short
and the lines are not transposed, so it is not practical to use shunt reactor. Whereas Shunt reactor with neutral small
reactors have been widely used in many counties as well as in INDIA.
(1) Shunt Reactor
When transmission line is energized, large charging current can be generated by shunt capacitance which exists between
each phases of line and between phase conductors and ground [7]. Due to charging current, Ferranti phenomena, the
voltage of receiving end can be greater than that of sending end, can occur. To prevent Ferranti phenomena and
compensate the line, shunt reactor is used with transmission line.
Figure 2: Transmission Line with Shunt Reactor
As shown in Fig shunt reactors are connected to both ends of transmission line in parallel. When single phase to ground
fault occurs, shunt reactors can compensate voltage to line by providing lagging current. The reactor bank extinguishes
secondary arc by neutralizing the secondary arc current. In compensation scheme, compensation degree an important
factor because the capacity of reactor is decided by compensation degree.
(2) High Speed Grounding Switches:
HSGS can extinguish the secondary arc rapidly by using the grounding switch that has smaller impedance than that of
secondary arc path. However, HSGS has a disadvantage in cost aspects [9]. HSGS are installed at both ends of the UHV
transmission line shown in Figure1.17.
ISSN 2349-7815
International Journal of Recent Research in Electrical and Electronics Engineering (IJRREEE)
Vol. 3, Issue 2, pp: (46-52), Month: April 2016 - June 2016, Available at: www.paperpublications.org
Page | 48
Paper Publications
Fig 3: Transmission Line with HSGS
When single phase to ground fault occurs, HSGS grounds the fault phase and provides new path that arc current flows.
The operating sequence of HSGS is as follow:
1) Single phase to ground fault is occurred and primary arc is generated.
2) Circuit breakers of fault phase are tripped and secondary arc is generated.
3) Leader switch of HSGS closes, and then closed loop is formed through the arc path and electromagnetic induction
current (I1) flows in that path.
4) Follower switch of HSGS closes, and then another closed loop that electromagnetic induction current (I2) flows in is
formed.
5) HSGS are opened.
6) Circuit breakers are closed to recover the line.
4. ANALYSIS RESULT
Impact of change of Fault Location on secondary arc:
As the fault point varies from the beginning to the end of line, the final steady value of secondary arc current reduces at
first and then increases after the middle. It is clearly that when the fault occurs at two ends of line, the suppression effect
is a little worse. When the fault point locates in the middle of line, the effect reaches the best.
Fig 4: Waveform when Shunt Reactor is not connected
ISSN 2349-7815
International Journal of Recent Research in Electrical and Electronics Engineering (IJRREEE)
Vol. 3, Issue 2, pp: (46-52), Month: April 2016 - June 2016, Available at: www.paperpublications.org
Page | 49
Paper Publications
Fig 5: Waveform when fault location 15 km from point A
Fig 6: Waveform when fault location at 50 km from point A
Fig 7: Waveform when fault location at 80 km from point A
ISSN 2349-7815
International Journal of Recent Research in Electrical and Electronics Engineering (IJRREEE)
Vol. 3, Issue 2, pp: (46-52), Month: April 2016 - June 2016, Available at: www.paperpublications.org
Page | 50
Paper Publications
Fig 8: Waveform when fault location at 100 km from point A
Fig 9: Waveform when fault location at 130 km from point A
Fig 10: Waveform when fault location at 160 km from point A
ISSN 2349-7815
International Journal of Recent Research in Electrical and Electronics Engineering (IJRREEE)
Vol. 3, Issue 2, pp: (46-52), Month: April 2016 - June 2016, Available at: www.paperpublications.org
Page | 51
Paper Publications
Fig 11: Waveform when fault location at 180 km from point A
Secondary arc current values for different fault locations
Fault location from end A
Distance (km) 15 50 80 100 130 160 180
Secondary arc current first peak
Current (kA) 35 25 22 21 23 27 33
5. CONCLUSION
This work studies the suppression theory of shunt reactor with neutral small reactor towards secondary arc current, uses
MATLAB SIMULATION software to simulate the different suppression effects of varying locations and at different
phase angle, finally gets conclusion. Due to highly random and complex behavior of secondary arc it is very difficult to
reproduce the exact arc duration by digital simulation. First, the simulation model of secondary arc is established by
MATLAB Simulink software. Then faulted phase voltage and secondary arc are simulated in different close angle.
However the model elaborated in this work can be employed successfully to examine the performance of arc suppression
scheme in auto reclosure study. According to the simulation results, the suppression effects at different locations are
different. Moreover this measure can suppress secondary arc current effectively. It ensures success of single phase auto
reclosing operation and finally achieve security and stability of power system.
This system can be considered very efficient, because in this system secondary arc current gets suppressed in very short
time. This time is very less as compared to other system. So the protection scheme can be considered as much as faster.
REFERENCES
[1] IEEE Standard Common Format for Transient Data Exchange (COMTRADE) forPower Systems. IEEE Std
C37.111-1999. DOI: 10.1109/IEEESTD.1999.90571
[2] V. Terzija, N. Elkalashy, G. Preston, V. Stanojevic, G. Strbac. “Detection of ArcingFaults: Modelling, Simulation,
Testing and Algorithms Aspects”. IEEE Power Tech.Conference Lausanne 2007, pp 1147 – 1152. DOI:
10.1109/PCT.2007.4538477
[3] M. Kizilcay, T. Pniok. “Digital Simulation of Fault Arcs in Power Systems”. ETEPVol.1, No. 1, Jan/Feb 1991.
[4] V. Terzija, Z. Radojevic, M. Djuric. “A New Approach for Arcing Faults Detection andFault Distance Calculation
in Spectral Domain”. Transmission and DistributionConference Proceedings, 15-20 Sept. 1996. pp 573-578.
[5] A. Papoulis. „Probability, Random Variables and Stochastic Processes‟. 4th Ed.McGraw Hill. http://www.mhhe.
com/engcs/electrical/papoulis ISBN: 0073660116
ISSN 2349-7815
International Journal of Recent Research in Electrical and Electronics Engineering (IJRREEE)
Vol. 3, Issue 2, pp: (46-52), Month: April 2016 - June 2016, Available at: www.paperpublications.org
Page | 52
Paper Publications
[6] EMTP Simulation of the Secondary ArcExtinction at Overhead Transmission Linesunder Single Phase Automatic
Reclosing, 2005 IEEE St. Petersburg Power Tech Proceedings, June 27-30, 2005, Report №15.–ISBN 5-93208-034-
0
[7] Research on Suppression of Secondary Arc Current under Different Fault Locations for 500kV Transmission Line ,
Cui Ruochen, Yin Zhongdong, Wang Miaomiao, Li Ke, 978-1-4244-4813-5/10/2010 IEEE
[8] Modelling of Secondary Arc Using EMTP-RV, Yun-Sik Oh․ Sung-Bum Kang․ Hun-ChulSeo․Chul-Hwan Kim,
The Transactions of the Korean Institute of Electrical Engineers Vol. 61, No. 7, pp. 937~943, 2012
[9] Secondary arc extinction in extra high voltage systems using grounding switches, Qais M. Alias, Wafaa F. Tobia,
Diyala Journal of Engineering Sciences, Vol. 07, No. 01, pp. 81-93, March 2014
[10] Analysis of Secondary Arc Extinction Effects according to the Application of Shunt Reactor and High Speed
Grounding Switches in Transmission Systems, Seung-Hyun Sohn, Gyu-Jung Cho , Journal of International Council
on Electrical Engineering Vol. 4, No. 4, pp.324~329, 2014
[11] Research on Extinction of Secondary Arc in UHV Double-circuit Transmission Lines, Fu Dong dong and *Shang,
International Journal of Computer, Consumer and Control (IJ3C), Vol. 3, No.4 (2014)
[12] B.W. Swanson, R.M. Roidt, T.E. Brown. “Arc Cooling and Short Line FaultInterruption”. IEEE Transactions on
Power Apparatus and Systems, Vol.PAS-90, pp1094-1102, May 1971.

More Related Content

What's hot

EE8402 Transmission and Distribution
EE8402 Transmission and DistributionEE8402 Transmission and Distribution
EE8402 Transmission and Distribution
rmkceteee
 
Objectives of shunt compensation
Objectives of shunt compensationObjectives of shunt compensation
Objectives of shunt compensation
Ayyarao T S L V
 
Voltage and power quality control in wind power applications by svc
Voltage and power quality control in wind power applications by svcVoltage and power quality control in wind power applications by svc
Voltage and power quality control in wind power applications by svc
Hari Prasath
 

What's hot (20)

Transient in Power system
Transient in Power systemTransient in Power system
Transient in Power system
 
EHV AC
EHV ACEHV AC
EHV AC
 
Power quality
Power qualityPower quality
Power quality
 
High voltage transmission
High voltage transmissionHigh voltage transmission
High voltage transmission
 
Implementation of Instantaneous Reactive Power Theory for Current Harmonic Re...
Implementation of Instantaneous Reactive Power Theory for Current Harmonic Re...Implementation of Instantaneous Reactive Power Theory for Current Harmonic Re...
Implementation of Instantaneous Reactive Power Theory for Current Harmonic Re...
 
Passive filters for minimum life cycle cost
Passive filters for minimum life cycle costPassive filters for minimum life cycle cost
Passive filters for minimum life cycle cost
 
Reactive power
Reactive powerReactive power
Reactive power
 
transmission line
transmission line transmission line
transmission line
 
Speed Control Of Separately Excited Dc Motor Using A High Efficiency Flyback ...
Speed Control Of Separately Excited Dc Motor Using A High Efficiency Flyback ...Speed Control Of Separately Excited Dc Motor Using A High Efficiency Flyback ...
Speed Control Of Separately Excited Dc Motor Using A High Efficiency Flyback ...
 
Effect of Switching angle on Magnetizing flux and Inrush current of a Transfo...
Effect of Switching angle on Magnetizing flux and Inrush current of a Transfo...Effect of Switching angle on Magnetizing flux and Inrush current of a Transfo...
Effect of Switching angle on Magnetizing flux and Inrush current of a Transfo...
 
Towards An Accurate Modeling of Frequency-dependent Wind Farm Components Unde...
Towards An Accurate Modeling of Frequency-dependent Wind Farm Components Unde...Towards An Accurate Modeling of Frequency-dependent Wind Farm Components Unde...
Towards An Accurate Modeling of Frequency-dependent Wind Farm Components Unde...
 
Neutral sizing in harmonic-rich installations
Neutral sizing in harmonic-rich installationsNeutral sizing in harmonic-rich installations
Neutral sizing in harmonic-rich installations
 
RGPV BE 104 Unit II
RGPV BE 104 Unit IIRGPV BE 104 Unit II
RGPV BE 104 Unit II
 
Introduction to Power Quality
Introduction to Power Quality Introduction to Power Quality
Introduction to Power Quality
 
EE8402 Transmission and Distribution
EE8402 Transmission and DistributionEE8402 Transmission and Distribution
EE8402 Transmission and Distribution
 
Power Quality Improvement using Passive shunt filters, TCR and TSC combination
Power Quality Improvement using Passive shunt filters, TCR and TSC combinationPower Quality Improvement using Passive shunt filters, TCR and TSC combination
Power Quality Improvement using Passive shunt filters, TCR and TSC combination
 
Chep 04 Harmonics
Chep 04 HarmonicsChep 04 Harmonics
Chep 04 Harmonics
 
Objectives of shunt compensation
Objectives of shunt compensationObjectives of shunt compensation
Objectives of shunt compensation
 
POWER LOSS REDUCTION IN ELECTRICAL DISTRIBUTION SYSTEMS USING CAPACITOR PLACE...
POWER LOSS REDUCTION IN ELECTRICAL DISTRIBUTION SYSTEMS USING CAPACITOR PLACE...POWER LOSS REDUCTION IN ELECTRICAL DISTRIBUTION SYSTEMS USING CAPACITOR PLACE...
POWER LOSS REDUCTION IN ELECTRICAL DISTRIBUTION SYSTEMS USING CAPACITOR PLACE...
 
Voltage and power quality control in wind power applications by svc
Voltage and power quality control in wind power applications by svcVoltage and power quality control in wind power applications by svc
Voltage and power quality control in wind power applications by svc
 

Viewers also liked

Performance Evaluation of Synchronous Generator under Sudden Loss of Excitation
Performance Evaluation of Synchronous Generator under Sudden Loss of ExcitationPerformance Evaluation of Synchronous Generator under Sudden Loss of Excitation
Performance Evaluation of Synchronous Generator under Sudden Loss of Excitation
paperpublications3
 
Study and Simulation of Inccond Based Maximum Power Point Tracking (MPPT) Alg...
Study and Simulation of Inccond Based Maximum Power Point Tracking (MPPT) Alg...Study and Simulation of Inccond Based Maximum Power Point Tracking (MPPT) Alg...
Study and Simulation of Inccond Based Maximum Power Point Tracking (MPPT) Alg...
paperpublications3
 
An Overview of Different PWM Techniques to Reduce Total Harmonic Distortion o...
An Overview of Different PWM Techniques to Reduce Total Harmonic Distortion o...An Overview of Different PWM Techniques to Reduce Total Harmonic Distortion o...
An Overview of Different PWM Techniques to Reduce Total Harmonic Distortion o...
paperpublications3
 
A Comparative Analysis of MPWM & SPWM Techniques to Reduce Harmonic Distortio...
A Comparative Analysis of MPWM & SPWM Techniques to Reduce Harmonic Distortio...A Comparative Analysis of MPWM & SPWM Techniques to Reduce Harmonic Distortio...
A Comparative Analysis of MPWM & SPWM Techniques to Reduce Harmonic Distortio...
paperpublications3
 
A new approach for Reducing Noise in ECG signal employing Gradient Descent Me...
A new approach for Reducing Noise in ECG signal employing Gradient Descent Me...A new approach for Reducing Noise in ECG signal employing Gradient Descent Me...
A new approach for Reducing Noise in ECG signal employing Gradient Descent Me...
paperpublications3
 
Sign Language Recognition Using Image Processing For Mute People
Sign Language Recognition Using Image Processing For Mute PeopleSign Language Recognition Using Image Processing For Mute People
Sign Language Recognition Using Image Processing For Mute People
paperpublications3
 

Viewers also liked (20)

Performance Evaluation of Synchronous Generator under Sudden Loss of Excitation
Performance Evaluation of Synchronous Generator under Sudden Loss of ExcitationPerformance Evaluation of Synchronous Generator under Sudden Loss of Excitation
Performance Evaluation of Synchronous Generator under Sudden Loss of Excitation
 
Study and Simulation of Inccond Based Maximum Power Point Tracking (MPPT) Alg...
Study and Simulation of Inccond Based Maximum Power Point Tracking (MPPT) Alg...Study and Simulation of Inccond Based Maximum Power Point Tracking (MPPT) Alg...
Study and Simulation of Inccond Based Maximum Power Point Tracking (MPPT) Alg...
 
AC-AC RESONANT BOOST CONVERTER FOR INDUCTION HEATING WITH CLOSED LOOP CONTROL
AC-AC RESONANT BOOST CONVERTER FOR INDUCTION HEATING WITH CLOSED LOOP CONTROLAC-AC RESONANT BOOST CONVERTER FOR INDUCTION HEATING WITH CLOSED LOOP CONTROL
AC-AC RESONANT BOOST CONVERTER FOR INDUCTION HEATING WITH CLOSED LOOP CONTROL
 
A DUAL SWITCH BOOST CONVERTER WITH HIGH VOLTAGE GAIN
A DUAL SWITCH BOOST CONVERTER WITH HIGH VOLTAGE GAINA DUAL SWITCH BOOST CONVERTER WITH HIGH VOLTAGE GAIN
A DUAL SWITCH BOOST CONVERTER WITH HIGH VOLTAGE GAIN
 
Coilgun: Simulation and Analysis
Coilgun: Simulation and AnalysisCoilgun: Simulation and Analysis
Coilgun: Simulation and Analysis
 
An Overview of Different PWM Techniques to Reduce Total Harmonic Distortion o...
An Overview of Different PWM Techniques to Reduce Total Harmonic Distortion o...An Overview of Different PWM Techniques to Reduce Total Harmonic Distortion o...
An Overview of Different PWM Techniques to Reduce Total Harmonic Distortion o...
 
Investigating the Feasibility of Solar Wind Hybrid Systems for Off-Grid Rural...
Investigating the Feasibility of Solar Wind Hybrid Systems for Off-Grid Rural...Investigating the Feasibility of Solar Wind Hybrid Systems for Off-Grid Rural...
Investigating the Feasibility of Solar Wind Hybrid Systems for Off-Grid Rural...
 
Single-Stage Reluctance Type Coilgun
Single-Stage Reluctance Type CoilgunSingle-Stage Reluctance Type Coilgun
Single-Stage Reluctance Type Coilgun
 
POWER FACTOR IMPROVEMENT OF INDUSTRIAL LOAD BY MATLAB SIMULATION
POWER FACTOR IMPROVEMENT OF INDUSTRIAL LOAD BY MATLAB SIMULATIONPOWER FACTOR IMPROVEMENT OF INDUSTRIAL LOAD BY MATLAB SIMULATION
POWER FACTOR IMPROVEMENT OF INDUSTRIAL LOAD BY MATLAB SIMULATION
 
Design and Development of DVR model Using Fuzzy Logic Controller for Voltage ...
Design and Development of DVR model Using Fuzzy Logic Controller for Voltage ...Design and Development of DVR model Using Fuzzy Logic Controller for Voltage ...
Design and Development of DVR model Using Fuzzy Logic Controller for Voltage ...
 
Design of Compensator for Roll Control of Towing Air-Crafts
Design of Compensator for Roll Control of Towing Air-CraftsDesign of Compensator for Roll Control of Towing Air-Crafts
Design of Compensator for Roll Control of Towing Air-Crafts
 
Analysis of Voltage Sag on Power Distribution Networks with Different Transfo...
Analysis of Voltage Sag on Power Distribution Networks with Different Transfo...Analysis of Voltage Sag on Power Distribution Networks with Different Transfo...
Analysis of Voltage Sag on Power Distribution Networks with Different Transfo...
 
A Comparative Analysis of MPWM & SPWM Techniques to Reduce Harmonic Distortio...
A Comparative Analysis of MPWM & SPWM Techniques to Reduce Harmonic Distortio...A Comparative Analysis of MPWM & SPWM Techniques to Reduce Harmonic Distortio...
A Comparative Analysis of MPWM & SPWM Techniques to Reduce Harmonic Distortio...
 
A new approach for Reducing Noise in ECG signal employing Gradient Descent Me...
A new approach for Reducing Noise in ECG signal employing Gradient Descent Me...A new approach for Reducing Noise in ECG signal employing Gradient Descent Me...
A new approach for Reducing Noise in ECG signal employing Gradient Descent Me...
 
A Comparative Study of Various AC-DC Converters for Low Voltage Energy Harves...
A Comparative Study of Various AC-DC Converters for Low Voltage Energy Harves...A Comparative Study of Various AC-DC Converters for Low Voltage Energy Harves...
A Comparative Study of Various AC-DC Converters for Low Voltage Energy Harves...
 
Bridgeless CUK Power Factor Corrector with Regulated Output Voltage
Bridgeless CUK Power Factor Corrector with Regulated Output VoltageBridgeless CUK Power Factor Corrector with Regulated Output Voltage
Bridgeless CUK Power Factor Corrector with Regulated Output Voltage
 
Sign Language Recognition Using Image Processing For Mute People
Sign Language Recognition Using Image Processing For Mute PeopleSign Language Recognition Using Image Processing For Mute People
Sign Language Recognition Using Image Processing For Mute People
 
A Comparative Study of GA tuned and PSO tuned PI Controller Based Speed Contr...
A Comparative Study of GA tuned and PSO tuned PI Controller Based Speed Contr...A Comparative Study of GA tuned and PSO tuned PI Controller Based Speed Contr...
A Comparative Study of GA tuned and PSO tuned PI Controller Based Speed Contr...
 
Improved Spider Algorithm for Solving Optimal Reactive Power Dispatch Problem
Improved Spider Algorithm for Solving Optimal Reactive Power Dispatch ProblemImproved Spider Algorithm for Solving Optimal Reactive Power Dispatch Problem
Improved Spider Algorithm for Solving Optimal Reactive Power Dispatch Problem
 
The Harmonic Mitigation in Induction Furnace Using Hybrid Filter
The Harmonic Mitigation in Induction Furnace Using Hybrid FilterThe Harmonic Mitigation in Induction Furnace Using Hybrid Filter
The Harmonic Mitigation in Induction Furnace Using Hybrid Filter
 

Similar to Study of Secondary Arc Current Suppression Effects under Different Fault Location on Extra High Voltage Line

Power Quality Improvement in QUCEST Larkana Campus by Using Three Types of Po...
Power Quality Improvement in QUCEST Larkana Campus by Using Three Types of Po...Power Quality Improvement in QUCEST Larkana Campus by Using Three Types of Po...
Power Quality Improvement in QUCEST Larkana Campus by Using Three Types of Po...
International Journal of Power Electronics and Drive Systems
 
ANALYSIS AND SIMULATION OF HARMONICS FOR VARIOUS RESIDENTIAL LOADS USING SIMU...
ANALYSIS AND SIMULATION OF HARMONICS FOR VARIOUS RESIDENTIAL LOADS USING SIMU...ANALYSIS AND SIMULATION OF HARMONICS FOR VARIOUS RESIDENTIAL LOADS USING SIMU...
ANALYSIS AND SIMULATION OF HARMONICS FOR VARIOUS RESIDENTIAL LOADS USING SIMU...
ijiert bestjournal
 
A Fault Current Limiter Circuit to Improve Transient Stability in Power System
A Fault Current Limiter Circuit to Improve Transient Stability in Power SystemA Fault Current Limiter Circuit to Improve Transient Stability in Power System
A Fault Current Limiter Circuit to Improve Transient Stability in Power System
IAES-IJPEDS
 

Similar to Study of Secondary Arc Current Suppression Effects under Different Fault Location on Extra High Voltage Line (20)

Me2420192024
Me2420192024Me2420192024
Me2420192024
 
Lightning protection for overhead distribution lines
Lightning protection for overhead distribution linesLightning protection for overhead distribution lines
Lightning protection for overhead distribution lines
 
ANALYSIS OF LIGHTNING STRIKE WITH CORONA ON OHTL NEAR THE SUBSTATION BY EMTP
ANALYSIS OF LIGHTNING STRIKE WITH CORONA ON OHTL NEAR THE SUBSTATION BY EMTP ANALYSIS OF LIGHTNING STRIKE WITH CORONA ON OHTL NEAR THE SUBSTATION BY EMTP
ANALYSIS OF LIGHTNING STRIKE WITH CORONA ON OHTL NEAR THE SUBSTATION BY EMTP
 
Calculation and comparison of circuit breaker parameters in Power World Simul...
Calculation and comparison of circuit breaker parameters in Power World Simul...Calculation and comparison of circuit breaker parameters in Power World Simul...
Calculation and comparison of circuit breaker parameters in Power World Simul...
 
Calculation and comparison of circuit breaker parameters in Power World Simul...
Calculation and comparison of circuit breaker parameters in Power World Simul...Calculation and comparison of circuit breaker parameters in Power World Simul...
Calculation and comparison of circuit breaker parameters in Power World Simul...
 
EXPERIMENTAL DETERMINATION AND ANALYSIS OF TRANSMISSION LINE PERFORMANCE
EXPERIMENTAL DETERMINATION AND ANALYSIS OF TRANSMISSION LINE PERFORMANCEEXPERIMENTAL DETERMINATION AND ANALYSIS OF TRANSMISSION LINE PERFORMANCE
EXPERIMENTAL DETERMINATION AND ANALYSIS OF TRANSMISSION LINE PERFORMANCE
 
Power Quality Improvement in QUCEST Larkana Campus by Using Three Types of Po...
Power Quality Improvement in QUCEST Larkana Campus by Using Three Types of Po...Power Quality Improvement in QUCEST Larkana Campus by Using Three Types of Po...
Power Quality Improvement in QUCEST Larkana Campus by Using Three Types of Po...
 
05617901
0561790105617901
05617901
 
Effect of Passive Damping on the Performance of Buck Converter for Magnet Load
Effect of Passive Damping on the Performance of Buck Converter for Magnet LoadEffect of Passive Damping on the Performance of Buck Converter for Magnet Load
Effect of Passive Damping on the Performance of Buck Converter for Magnet Load
 
ANALYSIS AND SIMULATION OF HARMONICS FOR VARIOUS RESIDENTIAL LOADS USING SIMU...
ANALYSIS AND SIMULATION OF HARMONICS FOR VARIOUS RESIDENTIAL LOADS USING SIMU...ANALYSIS AND SIMULATION OF HARMONICS FOR VARIOUS RESIDENTIAL LOADS USING SIMU...
ANALYSIS AND SIMULATION OF HARMONICS FOR VARIOUS RESIDENTIAL LOADS USING SIMU...
 
A Fault Current Limiter Circuit to Improve Transient Stability in Power System
A Fault Current Limiter Circuit to Improve Transient Stability in Power SystemA Fault Current Limiter Circuit to Improve Transient Stability in Power System
A Fault Current Limiter Circuit to Improve Transient Stability in Power System
 
Fea of pcb multilayer stack up high voltage planar transformer for aerospace...
Fea of  pcb multilayer stack up high voltage planar transformer for aerospace...Fea of  pcb multilayer stack up high voltage planar transformer for aerospace...
Fea of pcb multilayer stack up high voltage planar transformer for aerospace...
 
Interaction of the secondary arc
Interaction of the secondary arcInteraction of the secondary arc
Interaction of the secondary arc
 
ANALYSIS OF TUNED FILTERS FOR MITIGATION OF HARMONIC CURRENT DISTORTION OF R...
 ANALYSIS OF TUNED FILTERS FOR MITIGATION OF HARMONIC CURRENT DISTORTION OF R... ANALYSIS OF TUNED FILTERS FOR MITIGATION OF HARMONIC CURRENT DISTORTION OF R...
ANALYSIS OF TUNED FILTERS FOR MITIGATION OF HARMONIC CURRENT DISTORTION OF R...
 
Design of Shunt Active Power Filter to eliminate harmonics generated by CFL
Design of Shunt Active Power Filter to eliminate harmonics generated by CFLDesign of Shunt Active Power Filter to eliminate harmonics generated by CFL
Design of Shunt Active Power Filter to eliminate harmonics generated by CFL
 
Study of the operation of the output filter of a single-phase series active p...
Study of the operation of the output filter of a single-phase series active p...Study of the operation of the output filter of a single-phase series active p...
Study of the operation of the output filter of a single-phase series active p...
 
A Review on Suppression of Secondary Arc Current Trough Single-Phase Auto-Rec...
A Review on Suppression of Secondary Arc Current Trough Single-Phase Auto-Rec...A Review on Suppression of Secondary Arc Current Trough Single-Phase Auto-Rec...
A Review on Suppression of Secondary Arc Current Trough Single-Phase Auto-Rec...
 
TRANSMISSION LOSS MINIMIZATION USING ADVANCED UNIFIED POWER FLOW CONTROLLER (...
TRANSMISSION LOSS MINIMIZATION USING ADVANCED UNIFIED POWER FLOW CONTROLLER (...TRANSMISSION LOSS MINIMIZATION USING ADVANCED UNIFIED POWER FLOW CONTROLLER (...
TRANSMISSION LOSS MINIMIZATION USING ADVANCED UNIFIED POWER FLOW CONTROLLER (...
 
IRJET- Enhancement of Power Flow Capability in Power System using UPFC- A RevieW
IRJET- Enhancement of Power Flow Capability in Power System using UPFC- A RevieWIRJET- Enhancement of Power Flow Capability in Power System using UPFC- A RevieW
IRJET- Enhancement of Power Flow Capability in Power System using UPFC- A RevieW
 
Three-phase-to-ground fault and its impact on voltage magnitude
Three-phase-to-ground fault and its impact on voltage magnitudeThree-phase-to-ground fault and its impact on voltage magnitude
Three-phase-to-ground fault and its impact on voltage magnitude
 

Recently uploaded

Standard vs Custom Battery Packs - Decoding the Power Play
Standard vs Custom Battery Packs - Decoding the Power PlayStandard vs Custom Battery Packs - Decoding the Power Play
Standard vs Custom Battery Packs - Decoding the Power Play
Epec Engineered Technologies
 
Call Girls in South Ex (delhi) call me [🔝9953056974🔝] escort service 24X7
Call Girls in South Ex (delhi) call me [🔝9953056974🔝] escort service 24X7Call Girls in South Ex (delhi) call me [🔝9953056974🔝] escort service 24X7
Call Girls in South Ex (delhi) call me [🔝9953056974🔝] escort service 24X7
9953056974 Low Rate Call Girls In Saket, Delhi NCR
 
DeepFakes presentation : brief idea of DeepFakes
DeepFakes presentation : brief idea of DeepFakesDeepFakes presentation : brief idea of DeepFakes
DeepFakes presentation : brief idea of DeepFakes
MayuraD1
 
Hospital management system project report.pdf
Hospital management system project report.pdfHospital management system project report.pdf
Hospital management system project report.pdf
Kamal Acharya
 
"Lesotho Leaps Forward: A Chronicle of Transformative Developments"
"Lesotho Leaps Forward: A Chronicle of Transformative Developments""Lesotho Leaps Forward: A Chronicle of Transformative Developments"
"Lesotho Leaps Forward: A Chronicle of Transformative Developments"
mphochane1998
 

Recently uploaded (20)

Tamil Call Girls Bhayandar WhatsApp +91-9930687706, Best Service
Tamil Call Girls Bhayandar WhatsApp +91-9930687706, Best ServiceTamil Call Girls Bhayandar WhatsApp +91-9930687706, Best Service
Tamil Call Girls Bhayandar WhatsApp +91-9930687706, Best Service
 
kiln thermal load.pptx kiln tgermal load
kiln thermal load.pptx kiln tgermal loadkiln thermal load.pptx kiln tgermal load
kiln thermal load.pptx kiln tgermal load
 
Computer Networks Basics of Network Devices
Computer Networks  Basics of Network DevicesComputer Networks  Basics of Network Devices
Computer Networks Basics of Network Devices
 
Standard vs Custom Battery Packs - Decoding the Power Play
Standard vs Custom Battery Packs - Decoding the Power PlayStandard vs Custom Battery Packs - Decoding the Power Play
Standard vs Custom Battery Packs - Decoding the Power Play
 
Employee leave management system project.
Employee leave management system project.Employee leave management system project.
Employee leave management system project.
 
Call Girls in South Ex (delhi) call me [🔝9953056974🔝] escort service 24X7
Call Girls in South Ex (delhi) call me [🔝9953056974🔝] escort service 24X7Call Girls in South Ex (delhi) call me [🔝9953056974🔝] escort service 24X7
Call Girls in South Ex (delhi) call me [🔝9953056974🔝] escort service 24X7
 
Computer Lecture 01.pptxIntroduction to Computers
Computer Lecture 01.pptxIntroduction to ComputersComputer Lecture 01.pptxIntroduction to Computers
Computer Lecture 01.pptxIntroduction to Computers
 
DeepFakes presentation : brief idea of DeepFakes
DeepFakes presentation : brief idea of DeepFakesDeepFakes presentation : brief idea of DeepFakes
DeepFakes presentation : brief idea of DeepFakes
 
HOA1&2 - Module 3 - PREHISTORCI ARCHITECTURE OF KERALA.pptx
HOA1&2 - Module 3 - PREHISTORCI ARCHITECTURE OF KERALA.pptxHOA1&2 - Module 3 - PREHISTORCI ARCHITECTURE OF KERALA.pptx
HOA1&2 - Module 3 - PREHISTORCI ARCHITECTURE OF KERALA.pptx
 
Hospital management system project report.pdf
Hospital management system project report.pdfHospital management system project report.pdf
Hospital management system project report.pdf
 
FEA Based Level 3 Assessment of Deformed Tanks with Fluid Induced Loads
FEA Based Level 3 Assessment of Deformed Tanks with Fluid Induced LoadsFEA Based Level 3 Assessment of Deformed Tanks with Fluid Induced Loads
FEA Based Level 3 Assessment of Deformed Tanks with Fluid Induced Loads
 
AIRCANVAS[1].pdf mini project for btech students
AIRCANVAS[1].pdf mini project for btech studentsAIRCANVAS[1].pdf mini project for btech students
AIRCANVAS[1].pdf mini project for btech students
 
"Lesotho Leaps Forward: A Chronicle of Transformative Developments"
"Lesotho Leaps Forward: A Chronicle of Transformative Developments""Lesotho Leaps Forward: A Chronicle of Transformative Developments"
"Lesotho Leaps Forward: A Chronicle of Transformative Developments"
 
Wadi Rum luxhotel lodge Analysis case study.pptx
Wadi Rum luxhotel lodge Analysis case study.pptxWadi Rum luxhotel lodge Analysis case study.pptx
Wadi Rum luxhotel lodge Analysis case study.pptx
 
Navigating Complexity: The Role of Trusted Partners and VIAS3D in Dassault Sy...
Navigating Complexity: The Role of Trusted Partners and VIAS3D in Dassault Sy...Navigating Complexity: The Role of Trusted Partners and VIAS3D in Dassault Sy...
Navigating Complexity: The Role of Trusted Partners and VIAS3D in Dassault Sy...
 
Double Revolving field theory-how the rotor develops torque
Double Revolving field theory-how the rotor develops torqueDouble Revolving field theory-how the rotor develops torque
Double Revolving field theory-how the rotor develops torque
 
GEAR TRAIN- BASIC CONCEPTS AND WORKING PRINCIPLE
GEAR TRAIN- BASIC CONCEPTS AND WORKING PRINCIPLEGEAR TRAIN- BASIC CONCEPTS AND WORKING PRINCIPLE
GEAR TRAIN- BASIC CONCEPTS AND WORKING PRINCIPLE
 
COST-EFFETIVE and Energy Efficient BUILDINGS ptx
COST-EFFETIVE  and Energy Efficient BUILDINGS ptxCOST-EFFETIVE  and Energy Efficient BUILDINGS ptx
COST-EFFETIVE and Energy Efficient BUILDINGS ptx
 
Block diagram reduction techniques in control systems.ppt
Block diagram reduction techniques in control systems.pptBlock diagram reduction techniques in control systems.ppt
Block diagram reduction techniques in control systems.ppt
 
Thermal Engineering -unit - III & IV.ppt
Thermal Engineering -unit - III & IV.pptThermal Engineering -unit - III & IV.ppt
Thermal Engineering -unit - III & IV.ppt
 

Study of Secondary Arc Current Suppression Effects under Different Fault Location on Extra High Voltage Line

  • 1. ISSN 2349-7815 International Journal of Recent Research in Electrical and Electronics Engineering (IJRREEE) Vol. 3, Issue 2, pp: (46-52), Month: April 2016 - June 2016, Available at: www.paperpublications.org Page | 46 Paper Publications Study of Secondary Arc Current Suppression Effects under Different Fault Location on Extra High Voltage Line 1 Shalini Chandel, 2 A. K. Sharma 1, 2 Electrical Engineering Department, Jabalpur Engineering College, Jabalpur, India Abstract: Overhead transmission lines are an essential component of power systems, being the most economical means of transmitting electricity from remote sources of generation to the customer. It is therefore, vital that they be protected and maintained in service to ensure the security of the supply to the end-user, and to protect the capital investment of the power companies. When single phase grounding fault occurs in high voltage transmission line, secondary arc current and recovery voltage must be suppressed in order to ensure that single phase auto- reclosing operates reliably and successfully. Automatic single phase reclosing is used to clear single-phase-to- ground-faults, which are 80% of the transient faults. In order to have successful fast reclosing, different methods are used to extinguish the arc. One of the common methods is to use a single-phase reactor in the neutral of shunt reactor, when the transmission line is compensated with shunt reactors. In this paper, exact arc modeling is used for transient simulation of neutral reactor and guidelines for selecting the appropriate amount for the neutral reactor are proposed, then uses MATLAB software to simulate suppression effect about different fault point locations towards an example of 735 KV double ended sources high voltage transmission line. According to the simulation results, suppression effects about different locations are distinct. Keywords: High voltage transmission, single phase auto reclosing, secondary arc current, shunt reactor, neutral small reactor. 1. INTRODUCTION There are two main types of arcs appearing on power systems: arcs in open air, such as those found on transmission lines, and constrained switching arcs, such as those found in circuit breakers. The work in this thesis will be concentrated on arcs in open air. Arcing faults on transmission lines can be divided into two separate periods: the primary arc and the secondary arc. Soon after the fault, the two line end breakers will open (faulted phase only in this case) to isolate the fault. However, the other line( healthy phases) are still energized. There is inductive and capacitive coupling between the faulted line and the healthy phases, as well as between other conductors of parallel circuits. 2. GENERATION THEORY OF SECONDARY ARC CURRENT Secondary arc is an electromagnetic transient phenomenon generated in the process of single-phase autoreclosing operation. In figure 1 when the single phase (i.e. phase C) to ground fault occurs, the breaker at both ends of the fault phase will be tripping and short circuit current which is provided with power system from both ends to the fault point will be cut off. But this time the sound phases (phase A and B) are still running. There are loads current (Ia, Ib) flows through and two phases still keep working voltages(Ea, Eb). Due to the function of inter-phase capacitance Cm and mutual inductance M, the secondary current Ic is generated at the fault point Q and it contains two parts : capacitive component and inductive component.
  • 2. ISSN 2349-7815 International Journal of Recent Research in Electrical and Electronics Engineering (IJRREEE) Vol. 3, Issue 2, pp: (46-52), Month: April 2016 - June 2016, Available at: www.paperpublications.org Page | 47 Paper Publications Fig 1: single phase to ground fault and generation of Secondary Arc Current 3. METHODS OF SECONDARY ARC CURRENT EXTINCTION Nowadays there are two main suppression measures applied for secondary arc extinction, first Shunt reactor with neutral small reactor and second is High speed grounding switches. These methods are used for suppress secondary arc current by reducing its amplitude and shortening its burning time. In Japan HSGS method is used because EHV lines are short and the lines are not transposed, so it is not practical to use shunt reactor. Whereas Shunt reactor with neutral small reactors have been widely used in many counties as well as in INDIA. (1) Shunt Reactor When transmission line is energized, large charging current can be generated by shunt capacitance which exists between each phases of line and between phase conductors and ground [7]. Due to charging current, Ferranti phenomena, the voltage of receiving end can be greater than that of sending end, can occur. To prevent Ferranti phenomena and compensate the line, shunt reactor is used with transmission line. Figure 2: Transmission Line with Shunt Reactor As shown in Fig shunt reactors are connected to both ends of transmission line in parallel. When single phase to ground fault occurs, shunt reactors can compensate voltage to line by providing lagging current. The reactor bank extinguishes secondary arc by neutralizing the secondary arc current. In compensation scheme, compensation degree an important factor because the capacity of reactor is decided by compensation degree. (2) High Speed Grounding Switches: HSGS can extinguish the secondary arc rapidly by using the grounding switch that has smaller impedance than that of secondary arc path. However, HSGS has a disadvantage in cost aspects [9]. HSGS are installed at both ends of the UHV transmission line shown in Figure1.17.
  • 3. ISSN 2349-7815 International Journal of Recent Research in Electrical and Electronics Engineering (IJRREEE) Vol. 3, Issue 2, pp: (46-52), Month: April 2016 - June 2016, Available at: www.paperpublications.org Page | 48 Paper Publications Fig 3: Transmission Line with HSGS When single phase to ground fault occurs, HSGS grounds the fault phase and provides new path that arc current flows. The operating sequence of HSGS is as follow: 1) Single phase to ground fault is occurred and primary arc is generated. 2) Circuit breakers of fault phase are tripped and secondary arc is generated. 3) Leader switch of HSGS closes, and then closed loop is formed through the arc path and electromagnetic induction current (I1) flows in that path. 4) Follower switch of HSGS closes, and then another closed loop that electromagnetic induction current (I2) flows in is formed. 5) HSGS are opened. 6) Circuit breakers are closed to recover the line. 4. ANALYSIS RESULT Impact of change of Fault Location on secondary arc: As the fault point varies from the beginning to the end of line, the final steady value of secondary arc current reduces at first and then increases after the middle. It is clearly that when the fault occurs at two ends of line, the suppression effect is a little worse. When the fault point locates in the middle of line, the effect reaches the best. Fig 4: Waveform when Shunt Reactor is not connected
  • 4. ISSN 2349-7815 International Journal of Recent Research in Electrical and Electronics Engineering (IJRREEE) Vol. 3, Issue 2, pp: (46-52), Month: April 2016 - June 2016, Available at: www.paperpublications.org Page | 49 Paper Publications Fig 5: Waveform when fault location 15 km from point A Fig 6: Waveform when fault location at 50 km from point A Fig 7: Waveform when fault location at 80 km from point A
  • 5. ISSN 2349-7815 International Journal of Recent Research in Electrical and Electronics Engineering (IJRREEE) Vol. 3, Issue 2, pp: (46-52), Month: April 2016 - June 2016, Available at: www.paperpublications.org Page | 50 Paper Publications Fig 8: Waveform when fault location at 100 km from point A Fig 9: Waveform when fault location at 130 km from point A Fig 10: Waveform when fault location at 160 km from point A
  • 6. ISSN 2349-7815 International Journal of Recent Research in Electrical and Electronics Engineering (IJRREEE) Vol. 3, Issue 2, pp: (46-52), Month: April 2016 - June 2016, Available at: www.paperpublications.org Page | 51 Paper Publications Fig 11: Waveform when fault location at 180 km from point A Secondary arc current values for different fault locations Fault location from end A Distance (km) 15 50 80 100 130 160 180 Secondary arc current first peak Current (kA) 35 25 22 21 23 27 33 5. CONCLUSION This work studies the suppression theory of shunt reactor with neutral small reactor towards secondary arc current, uses MATLAB SIMULATION software to simulate the different suppression effects of varying locations and at different phase angle, finally gets conclusion. Due to highly random and complex behavior of secondary arc it is very difficult to reproduce the exact arc duration by digital simulation. First, the simulation model of secondary arc is established by MATLAB Simulink software. Then faulted phase voltage and secondary arc are simulated in different close angle. However the model elaborated in this work can be employed successfully to examine the performance of arc suppression scheme in auto reclosure study. According to the simulation results, the suppression effects at different locations are different. Moreover this measure can suppress secondary arc current effectively. It ensures success of single phase auto reclosing operation and finally achieve security and stability of power system. This system can be considered very efficient, because in this system secondary arc current gets suppressed in very short time. This time is very less as compared to other system. So the protection scheme can be considered as much as faster. REFERENCES [1] IEEE Standard Common Format for Transient Data Exchange (COMTRADE) forPower Systems. IEEE Std C37.111-1999. DOI: 10.1109/IEEESTD.1999.90571 [2] V. Terzija, N. Elkalashy, G. Preston, V. Stanojevic, G. Strbac. “Detection of ArcingFaults: Modelling, Simulation, Testing and Algorithms Aspects”. IEEE Power Tech.Conference Lausanne 2007, pp 1147 – 1152. DOI: 10.1109/PCT.2007.4538477 [3] M. Kizilcay, T. Pniok. “Digital Simulation of Fault Arcs in Power Systems”. ETEPVol.1, No. 1, Jan/Feb 1991. [4] V. Terzija, Z. Radojevic, M. Djuric. “A New Approach for Arcing Faults Detection andFault Distance Calculation in Spectral Domain”. Transmission and DistributionConference Proceedings, 15-20 Sept. 1996. pp 573-578. [5] A. Papoulis. „Probability, Random Variables and Stochastic Processes‟. 4th Ed.McGraw Hill. http://www.mhhe. com/engcs/electrical/papoulis ISBN: 0073660116
  • 7. ISSN 2349-7815 International Journal of Recent Research in Electrical and Electronics Engineering (IJRREEE) Vol. 3, Issue 2, pp: (46-52), Month: April 2016 - June 2016, Available at: www.paperpublications.org Page | 52 Paper Publications [6] EMTP Simulation of the Secondary ArcExtinction at Overhead Transmission Linesunder Single Phase Automatic Reclosing, 2005 IEEE St. Petersburg Power Tech Proceedings, June 27-30, 2005, Report №15.–ISBN 5-93208-034- 0 [7] Research on Suppression of Secondary Arc Current under Different Fault Locations for 500kV Transmission Line , Cui Ruochen, Yin Zhongdong, Wang Miaomiao, Li Ke, 978-1-4244-4813-5/10/2010 IEEE [8] Modelling of Secondary Arc Using EMTP-RV, Yun-Sik Oh․ Sung-Bum Kang․ Hun-ChulSeo․Chul-Hwan Kim, The Transactions of the Korean Institute of Electrical Engineers Vol. 61, No. 7, pp. 937~943, 2012 [9] Secondary arc extinction in extra high voltage systems using grounding switches, Qais M. Alias, Wafaa F. Tobia, Diyala Journal of Engineering Sciences, Vol. 07, No. 01, pp. 81-93, March 2014 [10] Analysis of Secondary Arc Extinction Effects according to the Application of Shunt Reactor and High Speed Grounding Switches in Transmission Systems, Seung-Hyun Sohn, Gyu-Jung Cho , Journal of International Council on Electrical Engineering Vol. 4, No. 4, pp.324~329, 2014 [11] Research on Extinction of Secondary Arc in UHV Double-circuit Transmission Lines, Fu Dong dong and *Shang, International Journal of Computer, Consumer and Control (IJ3C), Vol. 3, No.4 (2014) [12] B.W. Swanson, R.M. Roidt, T.E. Brown. “Arc Cooling and Short Line FaultInterruption”. IEEE Transactions on Power Apparatus and Systems, Vol.PAS-90, pp1094-1102, May 1971.