Sizing	Generators	for	Leading	Power	Factor	
Allen	Windhorn	
Kato	Engineering	
24	February,	2014	
Generator	Operation	with	a	Leading	Power	Factor	
Generators operating with a leading power factor may experience unstable voltage regulation and
increased heating. The following paragraphs define power factor and describe various generator
characteristic that impact operation with a leading power factor load.
An understanding the load being powered by the generator allows the generator supplier to work
with the customer to choose a generator and system design that will provide trouble free
operation. Suggestions for specifying a generator for leading power factor operation are
provided.
Excitation	of	Synchronous	Machines	
Rotating electrical machines in general have a component that produces a magnetic field and a
component that interacts with the magnetic field. In synchronous generators a stator (armature)
winding produces voltage in response to a magnetic field produced when a rotor winding is
“excited” by field current. The field current is controlled by a voltage regulator. In the no-load
condition, increasing the magnetic field results in an increase in voltage. The generator field
current must increase and the voltage level must be maintained to provide power output.
Real	vs.	Reactive	power	
Electrical power is the product of volts and amperes. Over a complete cycle of AC waveform,
the voltage and current wave forms may not line up, resulting in the peak voltage occurring when
the current is less than its maximum, and vice-versa. In this case the average power calculated
over the complete cycle is less than the “apparent” power, which is the product of RMS voltage
and RMS current. This average power is the “real” or active power that produces useful work.
Real power is measured in watts and is the power that shows up on your electric bill.
To help understand this we divide the current flowing in a circuit two parts: the real current,
which is in-phase with the voltage and causes net average (real) power flow, and the reactive
current, which is 90° out of phase with the voltage and transfers no average (real) power. The
product of reactive current and voltage is sometimes called “reactive power” (though no actual
power is being supplied) or VARs for “volt-amperes reactive”. The relationship between active
(real), reactive, and apparent power is shown in the power right triangle (Figure 1). Apparent
power S = where P is active power (watts) and Q is reactive power (VARs).
Figure 1: Relationship between real, reactive, and apparent power (Power Right Triangle).
Power	Factor	
Power factor (PF) is defined as the ratio between the active (real) power (the average value of
instantaneous product of voltage and current, as measured by a wattmeter) and the apparent
power. Power factor is the cosine of the angle  as shown in Figure 1. Historically, power
factor less than unity was considered to be caused by a phase difference between voltage and
current. This is called “displacement” power factor. Displacement power factor is the primary
concern in this paper, although the definition of power factor includes other types of current that
do not produce real power, particularly harmonic current. The “harmonic” power factor has the
effect of extra heating in the damper cage of the machine but does not affect the excitation or
stability of the machine. Harmonic power factor will not be addressed.
In the following graphs [Error! Reference source not found.] red represents voltage and blue
represents current. In the first graph labeled “PF = 1.0”, the voltage and current are aligned (in
phase) and the average power is equal to the RMS voltage times the RMS current. The graph
directly below shows the power is flowing only in the positive direction. Moving to the right
each graph shows a decreasing power factor. As the power factor decreases the average power
decreases, and during part of the cycle the power flows in reverse, until at zero power factor, as
much power flows forward as backward, and no average power is delivered. In each case
Figure 2: Power factor illustrated
voltage, current, and apparent power are constant. These graphs are for lagging power factor.
Lagging	vs.	Leading	Power	Factor	
Inductive loads such as electrical motors, which make up a large part of the load on the grid,
draw lagging power. That is, the power factor is less than 1.0 (typically around 0.8), and the
current waveform lags the voltage – the peak of the current occurs after the peak of voltage. The
opposite is true of capacitive loads – in this case the power factor is less than 1.0 but the peak of
the current occurs before the peak of the voltage, and we call the power factor leading. In either
case the power factor is positive, but the direction of flow of reactive current is opposite. (The
term “negative power factor” does not apply as it would mean a reversal of real power flow.)
Effect	of	reactive	load	on	generator	excitation	
The current in a generator (rotor or stator) creates magnetic flux, and the voltage in the stator
coils is related to the rate of change of flux, so maximum voltage in a coil occurs when the flux
is changing most rapidly, which is when the stator coil is aligned with the space between two
adjacent poles. For operation at 1.0 PF, this occurs at approximately the instant the current is
maximum. So the flux created by in-phase (1.0 PF) current is aligned between the poles, where
there is the least sensitivity to the flux created. For this reason, in-phase current or real power
does not have a great effect on the field current required to produce rated voltage. On the other
hand, reactive power produces flux that is aligned with the poles, and depending on the polarity,
has either a magnetizing or demagnetizing effect. Leading power factor current produces a
magnetizing effect, which means that less field current is required to produce rated voltage.
Lagging power factor produces a demagnetizing effect, requiring additional field current to
maintain the magnetic field level and thus rated voltage. (This is why lagging power factor load
results in increased rotor heating.) The field excitation determines the peak torque the generator
can accept, and if it is reduced too much, the engine may try to supply more torque than the
generator can accept, leading to instability. [1]
Stability	in	Island	Operation	
In island operation, a generator is supplying power, by itself or in a small group of identical
generators, to a load that is not connected to the grid. In this configuration, the frequency is
determined by the speed setting of the engine governor, the voltage by the voltage regulator
controlling the generator excitation, and the load power and power factor are completely
determined by the load.
In island operation, the power factor of the connected load may be leading, and, if so, it will tend
to magnetize the rotor and so reduce the required excitation current of the generator. If the
excitation current is reduced to zero, the voltage regulator will have no more control over the
voltage, which will rise to a value determined by the saturation of the generator. Even if the
excitation is reduced close to zero, there may be insufficient torque capability for the applied
load power. In this case, the generator will operate as a very poor induction generator and the
voltage will drop until the regulator kicks in again. The voltage will surge and oscillate, leading
to overheating and rotor damage if it is not shut down.
Stability	in	Grid‐Connected	Operation	
In grid-connected operation, the generator is connected to a utility or to a large group of
generators approximating a utility. The frequency is set by the grid. The load real power is
completely determined by the engine governor, and the reactive power (i.e. power factor) is
determined by the excitation applied to the generator field.
Since the power factor is controlled by the generator in this mode of operation, the main concern
is to make sure that the excitation remains high enough that the generator can accept the torque
supplied by the engine. Many digital regulators have a minimum excitation setting that can
perform this function.
If the excitation does fall too low, the engine will cause the generator to “slip poles” and operate
at a speed higher than synchronous speed. This will cause harmful currents in the generator rotor
and large pulsating torque on the shaft, which can damage the generator, coupling, or engine
crankshaft.
Because the torque is the limiting factor for both modes, the limits of leading power factor
operation are effectively the same for either island or grid-connected operation.
Reactive	Capability	Curves	
The interaction between field current and output voltage and current is complex, especially when
saliency and saturation of the magnetic material are considered, so usually simplified but
conservative rules are used to determine generator sizing. For instance, a cylindrical rotor may
be assumed. The tool most commonly used to determine excitation limits is the reactive
capability curve, which is derived from these simplified rules.
The generator parameters that control this are saturated short-circuit ratio (SCR or, in Europe,
Kcc) and saturated synchronous impedance Xds. These both represent the same quantity and are
reciprocals of each other. High SCR and low Xds make the machine more stable. To a first
approximation, if Xds is less than 1, or SCR greater than 1, the machine will be stable with any
leading power factor down to zero. To achieve this usually requires a very oversize machine.
For larger values of leading power factor, the reactive capability curve should be consulted. This
curve gives the power factor or leading VAR limit for all values of real load. A sample
capability curve is shown in Figure 2. The same curve is often drawn with the axes swapped as
in Figure 3. These graphs are most useful when the axes are plotted at the same scale, since then
all the curves are arcs of circles.
With lagging power factor, the limits on generator output are caused by heating. At leading
power factor, on the other hand, the limits are concerned with the stability of the machine,
meaning its ability to supply power at a steady rate at constant speed and voltage.
Examining the two graphs illustrated, we see that the shapes of the leading portions of the curve
are quite different. Each manufacturer decides what criteria to use to draw this curve, and there
is no standard procedure. We will show some of the criteria here, based on Figure 2.
The right-hand part of the leading power factor curve is based on the 2600 kVA limit due to
stator heating.
The intersection of the leading power factor curve with the negative Y axis is located at about -
1430 kVAR, which is just the kVA rating (2600 kVA) times the short-circuit ratio SCR (0.55).
This represents the point where the excitation becomes zero with no real load. We will call this
point P. It is not a practical operating point, but with a modern digital regulator it is possible to
come close. The distance from P to the operating point, divided by the absolute value of Y at
point P, is approximately the per-unit excitation current (where 1 PU represents the no-load
unsaturated excitation). The diagram of Figure 4 shows an excitation limit of about 25% of the
no-load value.
With any real load above zero, the torque angle  is the limiting factor. A generator with
cylindrical rotor reaches the limit of its stable torque when  = 90°. Again, this is not a practical
operating condition, since any disturbance will cause the generator to lose sync. The torque
angle  is represented by the angle between the y axis and the line drawn from point P and the
operating point. Figure 4 shows a curve with a  limit of 75°, considered to be a practical limit.
The graph of Figure 2 has a curved line for the stability limit. This is meant to compensate for
external impedance between the load and grid for grid-parallel operation, and comes from a 1954
AIEE paper by Rubenstein and Temoshok [2].
Figure 2: Typical Reactive Capability Curve.
Figure 4: Illustration of Minimum Excitation and Angle .
-2000
-1800
-1600
-1400
-1200
-1000
-800
-600
-400
-200
0
0 500 1000 1500 2000 2500 3000
Leading
--
Reactive
Load
kVAR
Power (kW)

P
Minimum Excitation
Figure 3: Alternative Reactive Capability Curve Format.
Some generators have additional limitations on leading power factor operation due to end-turn
heating or other factors [3]. Other authors propose different safety factors, including fixed
torque margin or fixed excitation margin [3] [5] [6] [6], so the limits illustrated do not cover all
cases.
Effect	of	Transient	Performance	on	Stability	
A synchronous generator has a rotor field winding to provide magnetic flux during steady-state
operation, and typically a damper (amortisseur) winding, which consists of a number of
conducting bars embedded in the rotor pole face. The damper winding bars may only be
interconnected within each pole, or they may be also connected between poles [Figure 5].
Completely connecting the bars and poles together provides superior transient performance.
The rotor field winding and damper cage act to resist sudden changes in flux in the rotor. When
there is a sudden load change, the currents conducted in these circuits act in a manner to prevent
a corresponding sudden change in load angle or voltage. This helps to stabilize the system. The
cage currents decay very quickly (subtransient time constant) whereas the rotor currents persist
longer (transient time constant). The effect only persists until the transient period has passed (on
the order of a second or two), so it can prevent a brief event (e.g. a voltage dip or short-circuit)
from driving the system into instability, but it will have no effect on steady-state stability.
Nevertheless, a robust damper cage is an advantage in keeping the system stable.
Figure 5: Damper Windings.
Fully-Connected
Damper Cage
Interrupted Damper Cage
Effect	of	the	Regulator	on	Stability	
For the island mode case, the voltage regulator will generally be set for a fixed generator voltage
output, and will not affect steady-state stability. However, sudden application of a leading power
factor load may cause the regulator to shut off and produce a temporary undershoot of excitation,
which could cause transient instability. It will generally be advisable to set an underexcitation
limit to prevent this from happening.
In the case of a grid-connected generator, the voltage regulator in droop mode will cause much
the same effect as for island mode. On the other hand, if the regulator is set for power factor
control, addition of leading power factor load will cause an increase in excitation in order to
maintain constant power factor, so in this case the regulator will have a stabilizing effect. [8]
How	to	Specify	Generators	for	Leading	Power	Factor	
Ideally, the generator OEM and the user (or site engineer) should work together to select a
generator design that will meet the requirements of the site. In addition to the normal rating data,
the manufacturer will benefit from the following information:
 Whether the site will run in island or grid-connected mode, or both.
 In island mode, what sort of capacitive load will be connected, and how it will be
coordinated with other loading. For example, large UPS sets will generally have a fixed
capacitive reactance on the input due to the input filters, but these UPS sets will have
variable real power load depending on how their output is loaded. Other loads on the
circuit (e.g. chillers) may provide lagging load to counterbalance the leading load, but if
they are started after the leading load, the system must be stable without them.
 In grid-connected mode, the user has control over the VAR loading, but if leading power
factor operation is required (possibly for local voltage control at light load), the generator
manufacturer needs to know the possible range of real and reactive loading.
To meet the site requirements, the manufacturer may:
 Propose an oversize generator in order to keep the synchronous reactance low.
 Use a special design that is more saturated than normal for the same reason.
 Include special testing to insure that the generator will meet requirements.
 Propose additional protective relaying and controls to detect or prevent unstable
conditions.
At a minimum, a reactive capability curve as well as saturation curves and V-curves should be
requested for the proposed generator before ordering, and carefully examined by the site
engineer to make certain the generator will always operate within the safe region. Because the
leading power factor capability depends strongly on factors that vary by manufacturer, frame
size, pole count, and model, it is not possible to use a “rule of thumb” for sizing the generator.
The voltage regulator specified should have internal provision for over- and under-excitation
limits. If the generator is connected to the grid, the voltage regulator should also have power
factor control. Protective relaying should include over- and under-voltage as well as excitation
failure relays.
Bibliography: 
[1] T. Lipo, Analysis of synchronous machines, Madison, WI: Wisconsin Power Electronics
Research Center, University of Wisconsin, 2008.
[2] A. Rubenstein and M. Temoshok, "Underexcited Reactive Ampere Limit for Modern
Amplidyne Voltage Regulator," Trans. AIEE, no. December, pp. 1433-1438, 1954.
[3] G. Staats, "Eddy Currents in the End Portion of Turbine-Generator Stator Windings," Trans.
AIEE, no. June, pp. 384-391, 1957.
[4] W. Heffron, "A Simplified Approach to Steady-State Stability Limits," Trans. AIEE, no.
February, pp. 39-44, 1954.
[5] M. Adibi and D. Milanicz, "Reactive Capability Limitation of Power Systems," IEEE Trans.
on Power Systems, vol. 9, no. 1, pp. 29-40, 1994.
[6] N. Nilsson and J. Mercurio, "Synchronous Generator Capability Curve Testing and
Evaluation," IEEE Trans. on Power Delivery, vol. 9, no. 1, pp. 414-424, 1994.
[7] I. Nagy, "Analysis of Minimum Excitation Limits of Synchronous Machines," IEEE Trans.
on Power Apparatus and Systems, vol. 89, no. 6, pp. 1001-1008, 1970.
[8] L. Qiang, L. Yong-gang and L. Hai-bo, "Steady-State Stability Limit of Turbine-Generators
in Consideration of AVR," in International Conference on Electrical Machines and Systems,
Seoul, 2007.

More Related Content

What's hot

Parallel operation of alternators 1
Parallel operation of alternators 1Parallel operation of alternators 1
Parallel operation of alternators 1Citharthan Durairaj
 
Parallel Operation on Alternators.
Parallel Operation on Alternators.Parallel Operation on Alternators.
Parallel Operation on Alternators.R-One Power
 
Excitation system for alternator
Excitation system for alternatorExcitation system for alternator
Excitation system for alternatorsantu sutradhar
 
Static excitation-system
Static excitation-systemStatic excitation-system
Static excitation-systemDeepak Jha
 
Synchronous generator
Synchronous generatorSynchronous generator
Synchronous generatorPrasant Kumar
 
Protection of alternator
Protection of alternatorProtection of alternator
Protection of alternatorBiswajit Pratihari
 
analysis of induction motor drive using slip power recovery scheme
analysis of induction motor drive using slip power recovery schemeanalysis of induction motor drive using slip power recovery scheme
analysis of induction motor drive using slip power recovery schemePrakash_13209
 
Power Plant Horror Stories
Power Plant Horror StoriesPower Plant Horror Stories
Power Plant Horror Storiesmichaeljmack
 
Motor bus transfer
Motor bus transferMotor bus transfer
Motor bus transfermichaeljmack
 
Speed control Of DC Machines
Speed control Of DC MachinesSpeed control Of DC Machines
Speed control Of DC MachinesDinesh Sharma
 
synchronous generator excitation
synchronous generator excitationsynchronous generator excitation
synchronous generator excitationMaria Romina Angustia
 
Automatic transfer switch (ats)
Automatic transfer switch (ats)Automatic transfer switch (ats)
Automatic transfer switch (ats)Mark Anthony Enoy
 
Synchronous machines
Synchronous machinesSynchronous machines
Synchronous machinesmichaeljmack
 
Generator protection gers
Generator protection gersGenerator protection gers
Generator protection gersHabudin Hassan
 
Sub station training ppt
Sub station training pptSub station training ppt
Sub station training pptsitesh95074
 
Facts on Grid Friendly Wind Plants
Facts on Grid Friendly Wind PlantsFacts on Grid Friendly Wind Plants
Facts on Grid Friendly Wind Plantsmichaeljmack
 
Equivalent Circuit, Phasor Diagram, Power Factor Control , V & Inverted V Cur...
Equivalent Circuit, Phasor Diagram, Power Factor Control , V & Inverted V Cur...Equivalent Circuit, Phasor Diagram, Power Factor Control , V & Inverted V Cur...
Equivalent Circuit, Phasor Diagram, Power Factor Control , V & Inverted V Cur...Citharthan Durairaj
 
Detection of Generator Loss of Excitation (LOE)
Detection of Generator Loss of Excitation (LOE)Detection of Generator Loss of Excitation (LOE)
Detection of Generator Loss of Excitation (LOE)Anmol Dwivedi
 

What's hot (20)

Parallel operation of alternators 1
Parallel operation of alternators 1Parallel operation of alternators 1
Parallel operation of alternators 1
 
Parallel Operation on Alternators.
Parallel Operation on Alternators.Parallel Operation on Alternators.
Parallel Operation on Alternators.
 
Excitation system for alternator
Excitation system for alternatorExcitation system for alternator
Excitation system for alternator
 
Lec # 07 parallel operation of synchronous generators
Lec # 07 parallel operation of synchronous generatorsLec # 07 parallel operation of synchronous generators
Lec # 07 parallel operation of synchronous generators
 
Static excitation-system
Static excitation-systemStatic excitation-system
Static excitation-system
 
Synchronous generator
Synchronous generatorSynchronous generator
Synchronous generator
 
Protection of alternator
Protection of alternatorProtection of alternator
Protection of alternator
 
analysis of induction motor drive using slip power recovery scheme
analysis of induction motor drive using slip power recovery schemeanalysis of induction motor drive using slip power recovery scheme
analysis of induction motor drive using slip power recovery scheme
 
Power Plant Horror Stories
Power Plant Horror StoriesPower Plant Horror Stories
Power Plant Horror Stories
 
Motor bus transfer
Motor bus transferMotor bus transfer
Motor bus transfer
 
Speed control Of DC Machines
Speed control Of DC MachinesSpeed control Of DC Machines
Speed control Of DC Machines
 
synchronous generator excitation
synchronous generator excitationsynchronous generator excitation
synchronous generator excitation
 
Automatic transfer switch (ats)
Automatic transfer switch (ats)Automatic transfer switch (ats)
Automatic transfer switch (ats)
 
Synchronous machines
Synchronous machinesSynchronous machines
Synchronous machines
 
Generator protection gers
Generator protection gersGenerator protection gers
Generator protection gers
 
Sub station training ppt
Sub station training pptSub station training ppt
Sub station training ppt
 
Facts on Grid Friendly Wind Plants
Facts on Grid Friendly Wind PlantsFacts on Grid Friendly Wind Plants
Facts on Grid Friendly Wind Plants
 
Equivalent Circuit, Phasor Diagram, Power Factor Control , V & Inverted V Cur...
Equivalent Circuit, Phasor Diagram, Power Factor Control , V & Inverted V Cur...Equivalent Circuit, Phasor Diagram, Power Factor Control , V & Inverted V Cur...
Equivalent Circuit, Phasor Diagram, Power Factor Control , V & Inverted V Cur...
 
Detection of Generator Loss of Excitation (LOE)
Detection of Generator Loss of Excitation (LOE)Detection of Generator Loss of Excitation (LOE)
Detection of Generator Loss of Excitation (LOE)
 
Switch yard & Protection
Switch yard & ProtectionSwitch yard & Protection
Switch yard & Protection
 

Similar to Sizing generators-for-leading-power-factor white-paper-24_feb14

Asm exp.10
Asm exp.10Asm exp.10
Asm exp.10HittuKumar
 
Basic Physics
Basic PhysicsBasic Physics
Basic PhysicsThane Heins
 
Basic Physics Regenerative Acceleration Generator Technology
Basic Physics Regenerative Acceleration Generator TechnologyBasic Physics Regenerative Acceleration Generator Technology
Basic Physics Regenerative Acceleration Generator TechnologyThane Heins
 
Synchronous generators
Synchronous generatorsSynchronous generators
Synchronous generatorstes4
 
synchronous generators
synchronous generatorssynchronous generators
synchronous generatorsSouvik Dutta
 
Micro-controller based Automatic Power Factor Correction System Report
Micro-controller based Automatic Power Factor Correction System ReportMicro-controller based Automatic Power Factor Correction System Report
Micro-controller based Automatic Power Factor Correction System ReportTheory to Practical
 
P di regenerative acceleration generator (re genx) 2013 patent disclosure
P di regenerative acceleration generator (re genx) 2013 patent disclosureP di regenerative acceleration generator (re genx) 2013 patent disclosure
P di regenerative acceleration generator (re genx) 2013 patent disclosureThane Heins
 
PDi Regenerative Acceleration Generator (ReGenX) 2013 Patent Disclosure
PDi Regenerative Acceleration Generator (ReGenX) 2013 Patent DisclosurePDi Regenerative Acceleration Generator (ReGenX) 2013 Patent Disclosure
PDi Regenerative Acceleration Generator (ReGenX) 2013 Patent DisclosureThane Heins
 
Armature reaction and parallel operation of a Syncronous generator
Armature reaction and parallel operation of a Syncronous generatorArmature reaction and parallel operation of a Syncronous generator
Armature reaction and parallel operation of a Syncronous generatorkarthi1017
 
New microsoft word document
New microsoft word documentNew microsoft word document
New microsoft word documentjeevan_raju
 
Increase productivity and absorption of reactive power for power station with...
Increase productivity and absorption of reactive power for power station with...Increase productivity and absorption of reactive power for power station with...
Increase productivity and absorption of reactive power for power station with...IJITCA Journal
 
Power factor presentation
Power factor presentationPower factor presentation
Power factor presentationAzhar Abbas
 
Lab manual psd v sem experiment no 5
Lab manual psd v sem experiment no 5Lab manual psd v sem experiment no 5
Lab manual psd v sem experiment no 5Sachin Airan
 

Similar to Sizing generators-for-leading-power-factor white-paper-24_feb14 (20)

Asm exp.10
Asm exp.10Asm exp.10
Asm exp.10
 
Basic Physics
Basic PhysicsBasic Physics
Basic Physics
 
Basic Physics Regenerative Acceleration Generator Technology
Basic Physics Regenerative Acceleration Generator TechnologyBasic Physics Regenerative Acceleration Generator Technology
Basic Physics Regenerative Acceleration Generator Technology
 
8925273.ppt
8925273.ppt8925273.ppt
8925273.ppt
 
Synchronous generators
Synchronous generatorsSynchronous generators
Synchronous generators
 
ReGenX Generator Design Questions
ReGenX Generator Design QuestionsReGenX Generator Design Questions
ReGenX Generator Design Questions
 
ReGen-X Patent
ReGen-X PatentReGen-X Patent
ReGen-X Patent
 
4 ReGenX Generator Design Questions
4 ReGenX Generator Design Questions4 ReGenX Generator Design Questions
4 ReGenX Generator Design Questions
 
synchronous generators
synchronous generatorssynchronous generators
synchronous generators
 
Micro-controller based Automatic Power Factor Correction System Report
Micro-controller based Automatic Power Factor Correction System ReportMicro-controller based Automatic Power Factor Correction System Report
Micro-controller based Automatic Power Factor Correction System Report
 
P di regenerative acceleration generator (re genx) 2013 patent disclosure
P di regenerative acceleration generator (re genx) 2013 patent disclosureP di regenerative acceleration generator (re genx) 2013 patent disclosure
P di regenerative acceleration generator (re genx) 2013 patent disclosure
 
PDi Regenerative Acceleration Generator (ReGenX) 2013 Patent Disclosure
PDi Regenerative Acceleration Generator (ReGenX) 2013 Patent DisclosurePDi Regenerative Acceleration Generator (ReGenX) 2013 Patent Disclosure
PDi Regenerative Acceleration Generator (ReGenX) 2013 Patent Disclosure
 
Armature reaction and parallel operation of a Syncronous generator
Armature reaction and parallel operation of a Syncronous generatorArmature reaction and parallel operation of a Syncronous generator
Armature reaction and parallel operation of a Syncronous generator
 
Imagine_Power
Imagine_PowerImagine_Power
Imagine_Power
 
Lenz's Law & Heins' Law of induction for Electric Generators
Lenz's Law & Heins' Law of induction for Electric GeneratorsLenz's Law & Heins' Law of induction for Electric Generators
Lenz's Law & Heins' Law of induction for Electric Generators
 
New microsoft word document
New microsoft word documentNew microsoft word document
New microsoft word document
 
Increase productivity and absorption of reactive power for power station with...
Increase productivity and absorption of reactive power for power station with...Increase productivity and absorption of reactive power for power station with...
Increase productivity and absorption of reactive power for power station with...
 
AC circuit
AC circuitAC circuit
AC circuit
 
Power factor presentation
Power factor presentationPower factor presentation
Power factor presentation
 
Lab manual psd v sem experiment no 5
Lab manual psd v sem experiment no 5Lab manual psd v sem experiment no 5
Lab manual psd v sem experiment no 5
 

More from Insanul Aziz

ARGeo-C7_Successful-Commissioning-ID-46811-.pdf
ARGeo-C7_Successful-Commissioning-ID-46811-.pdfARGeo-C7_Successful-Commissioning-ID-46811-.pdf
ARGeo-C7_Successful-Commissioning-ID-46811-.pdfInsanul Aziz
 
Elk 24-5-32-1410-127
Elk 24-5-32-1410-127Elk 24-5-32-1410-127
Elk 24-5-32-1410-127Insanul Aziz
 
Optimal and economic selection of ttr transformer using generator capability ...
Optimal and economic selection of ttr transformer using generator capability ...Optimal and economic selection of ttr transformer using generator capability ...
Optimal and economic selection of ttr transformer using generator capability ...Insanul Aziz
 
Ieee modeling of generator controls for coordinating generator relays draft 4...
Ieee modeling of generator controls for coordinating generator relays draft 4...Ieee modeling of generator controls for coordinating generator relays draft 4...
Ieee modeling of generator controls for coordinating generator relays draft 4...Insanul Aziz
 
Egu synch gen
Egu synch genEgu synch gen
Egu synch genInsanul Aziz
 
Voltage & reactive power regulation
Voltage & reactive power regulationVoltage & reactive power regulation
Voltage & reactive power regulationInsanul Aziz
 
Natf reference-document-reporting-and-verification-of-generating-unit-reactiv...
Natf reference-document-reporting-and-verification-of-generating-unit-reactiv...Natf reference-document-reporting-and-verification-of-generating-unit-reactiv...
Natf reference-document-reporting-and-verification-of-generating-unit-reactiv...Insanul Aziz
 
Dlscrib.com pdf-4-dissolved-gas-analysis-dl 6f9e36cf816d7748e2e2496e9a761671
Dlscrib.com pdf-4-dissolved-gas-analysis-dl 6f9e36cf816d7748e2e2496e9a761671Dlscrib.com pdf-4-dissolved-gas-analysis-dl 6f9e36cf816d7748e2e2496e9a761671
Dlscrib.com pdf-4-dissolved-gas-analysis-dl 6f9e36cf816d7748e2e2496e9a761671Insanul Aziz
 

More from Insanul Aziz (8)

ARGeo-C7_Successful-Commissioning-ID-46811-.pdf
ARGeo-C7_Successful-Commissioning-ID-46811-.pdfARGeo-C7_Successful-Commissioning-ID-46811-.pdf
ARGeo-C7_Successful-Commissioning-ID-46811-.pdf
 
Elk 24-5-32-1410-127
Elk 24-5-32-1410-127Elk 24-5-32-1410-127
Elk 24-5-32-1410-127
 
Optimal and economic selection of ttr transformer using generator capability ...
Optimal and economic selection of ttr transformer using generator capability ...Optimal and economic selection of ttr transformer using generator capability ...
Optimal and economic selection of ttr transformer using generator capability ...
 
Ieee modeling of generator controls for coordinating generator relays draft 4...
Ieee modeling of generator controls for coordinating generator relays draft 4...Ieee modeling of generator controls for coordinating generator relays draft 4...
Ieee modeling of generator controls for coordinating generator relays draft 4...
 
Egu synch gen
Egu synch genEgu synch gen
Egu synch gen
 
Voltage & reactive power regulation
Voltage & reactive power regulationVoltage & reactive power regulation
Voltage & reactive power regulation
 
Natf reference-document-reporting-and-verification-of-generating-unit-reactiv...
Natf reference-document-reporting-and-verification-of-generating-unit-reactiv...Natf reference-document-reporting-and-verification-of-generating-unit-reactiv...
Natf reference-document-reporting-and-verification-of-generating-unit-reactiv...
 
Dlscrib.com pdf-4-dissolved-gas-analysis-dl 6f9e36cf816d7748e2e2496e9a761671
Dlscrib.com pdf-4-dissolved-gas-analysis-dl 6f9e36cf816d7748e2e2496e9a761671Dlscrib.com pdf-4-dissolved-gas-analysis-dl 6f9e36cf816d7748e2e2496e9a761671
Dlscrib.com pdf-4-dissolved-gas-analysis-dl 6f9e36cf816d7748e2e2496e9a761671
 

Recently uploaded

(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escortsranjana rawat
 
🔝9953056974🔝!!-YOUNG call girls in Rajendra Nagar Escort rvice Shot 2000 nigh...
🔝9953056974🔝!!-YOUNG call girls in Rajendra Nagar Escort rvice Shot 2000 nigh...🔝9953056974🔝!!-YOUNG call girls in Rajendra Nagar Escort rvice Shot 2000 nigh...
🔝9953056974🔝!!-YOUNG call girls in Rajendra Nagar Escort rvice Shot 2000 nigh...9953056974 Low Rate Call Girls In Saket, Delhi NCR
 
Microscopic Analysis of Ceramic Materials.pptx
Microscopic Analysis of Ceramic Materials.pptxMicroscopic Analysis of Ceramic Materials.pptx
Microscopic Analysis of Ceramic Materials.pptxpurnimasatapathy1234
 
Current Transformer Drawing and GTP for MSETCL
Current Transformer Drawing and GTP for MSETCLCurrent Transformer Drawing and GTP for MSETCL
Current Transformer Drawing and GTP for MSETCLDeelipZope
 
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...ranjana rawat
 
Artificial-Intelligence-in-Electronics (K).pptx
Artificial-Intelligence-in-Electronics (K).pptxArtificial-Intelligence-in-Electronics (K).pptx
Artificial-Intelligence-in-Electronics (K).pptxbritheesh05
 
Study on Air-Water & Water-Water Heat Exchange in a Finned ďťżTube Exchanger
Study on Air-Water & Water-Water Heat Exchange in a Finned ďťżTube ExchangerStudy on Air-Water & Water-Water Heat Exchange in a Finned ďťżTube Exchanger
Study on Air-Water & Water-Water Heat Exchange in a Finned ďťżTube ExchangerAnamika Sarkar
 
IVE Industry Focused Event - Defence Sector 2024
IVE Industry Focused Event - Defence Sector 2024IVE Industry Focused Event - Defence Sector 2024
IVE Industry Focused Event - Defence Sector 2024Mark Billinghurst
 
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptxDecoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptxJoĂŁo Esperancinha
 
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130Suhani Kapoor
 
Call Girls Delhi {Jodhpur} 9711199012 high profile service
Call Girls Delhi {Jodhpur} 9711199012 high profile serviceCall Girls Delhi {Jodhpur} 9711199012 high profile service
Call Girls Delhi {Jodhpur} 9711199012 high profile servicerehmti665
 
ZXCTN 5804 / ZTE PTN / ZTE POTN / ZTE 5804 PTN / ZTE POTN 5804 ( 100/200 GE Z...
ZXCTN 5804 / ZTE PTN / ZTE POTN / ZTE 5804 PTN / ZTE POTN 5804 ( 100/200 GE Z...ZXCTN 5804 / ZTE PTN / ZTE POTN / ZTE 5804 PTN / ZTE POTN 5804 ( 100/200 GE Z...
ZXCTN 5804 / ZTE PTN / ZTE POTN / ZTE 5804 PTN / ZTE POTN 5804 ( 100/200 GE Z...ZTE
 
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escortsranjana rawat
 
Gurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort service
Gurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort serviceGurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort service
Gurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort servicejennyeacort
 
College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service NashikCollege Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service NashikCall Girls in Nagpur High Profile
 
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur High Profile
 
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝soniya singh
 
main PPT.pptx of girls hostel security using rfid
main PPT.pptx of girls hostel security using rfidmain PPT.pptx of girls hostel security using rfid
main PPT.pptx of girls hostel security using rfidNikhilNagaraju
 

Recently uploaded (20)

(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
 
🔝9953056974🔝!!-YOUNG call girls in Rajendra Nagar Escort rvice Shot 2000 nigh...
🔝9953056974🔝!!-YOUNG call girls in Rajendra Nagar Escort rvice Shot 2000 nigh...🔝9953056974🔝!!-YOUNG call girls in Rajendra Nagar Escort rvice Shot 2000 nigh...
🔝9953056974🔝!!-YOUNG call girls in Rajendra Nagar Escort rvice Shot 2000 nigh...
 
Microscopic Analysis of Ceramic Materials.pptx
Microscopic Analysis of Ceramic Materials.pptxMicroscopic Analysis of Ceramic Materials.pptx
Microscopic Analysis of Ceramic Materials.pptx
 
Current Transformer Drawing and GTP for MSETCL
Current Transformer Drawing and GTP for MSETCLCurrent Transformer Drawing and GTP for MSETCL
Current Transformer Drawing and GTP for MSETCL
 
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
 
Artificial-Intelligence-in-Electronics (K).pptx
Artificial-Intelligence-in-Electronics (K).pptxArtificial-Intelligence-in-Electronics (K).pptx
Artificial-Intelligence-in-Electronics (K).pptx
 
Study on Air-Water & Water-Water Heat Exchange in a Finned ďťżTube Exchanger
Study on Air-Water & Water-Water Heat Exchange in a Finned ďťżTube ExchangerStudy on Air-Water & Water-Water Heat Exchange in a Finned ďťżTube Exchanger
Study on Air-Water & Water-Water Heat Exchange in a Finned ďťżTube Exchanger
 
IVE Industry Focused Event - Defence Sector 2024
IVE Industry Focused Event - Defence Sector 2024IVE Industry Focused Event - Defence Sector 2024
IVE Industry Focused Event - Defence Sector 2024
 
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptxDecoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
 
Call Us -/9953056974- Call Girls In Vikaspuri-/- Delhi NCR
Call Us -/9953056974- Call Girls In Vikaspuri-/- Delhi NCRCall Us -/9953056974- Call Girls In Vikaspuri-/- Delhi NCR
Call Us -/9953056974- Call Girls In Vikaspuri-/- Delhi NCR
 
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130
 
Call Girls Delhi {Jodhpur} 9711199012 high profile service
Call Girls Delhi {Jodhpur} 9711199012 high profile serviceCall Girls Delhi {Jodhpur} 9711199012 high profile service
Call Girls Delhi {Jodhpur} 9711199012 high profile service
 
ZXCTN 5804 / ZTE PTN / ZTE POTN / ZTE 5804 PTN / ZTE POTN 5804 ( 100/200 GE Z...
ZXCTN 5804 / ZTE PTN / ZTE POTN / ZTE 5804 PTN / ZTE POTN 5804 ( 100/200 GE Z...ZXCTN 5804 / ZTE PTN / ZTE POTN / ZTE 5804 PTN / ZTE POTN 5804 ( 100/200 GE Z...
ZXCTN 5804 / ZTE PTN / ZTE POTN / ZTE 5804 PTN / ZTE POTN 5804 ( 100/200 GE Z...
 
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
 
9953056974 Call Girls In South Ex, Escorts (Delhi) NCR.pdf
9953056974 Call Girls In South Ex, Escorts (Delhi) NCR.pdf9953056974 Call Girls In South Ex, Escorts (Delhi) NCR.pdf
9953056974 Call Girls In South Ex, Escorts (Delhi) NCR.pdf
 
Gurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort service
Gurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort serviceGurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort service
Gurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort service
 
College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service NashikCollege Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
 
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
 
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝
 
main PPT.pptx of girls hostel security using rfid
main PPT.pptx of girls hostel security using rfidmain PPT.pptx of girls hostel security using rfid
main PPT.pptx of girls hostel security using rfid
 

Sizing generators-for-leading-power-factor white-paper-24_feb14

  • 1. Sizing Generators for Leading Power Factor Allen Windhorn Kato Engineering 24 February, 2014 Generator Operation with a Leading Power Factor Generators operating with a leading power factor may experience unstable voltage regulation and increased heating. The following paragraphs define power factor and describe various generator characteristic that impact operation with a leading power factor load. An understanding the load being powered by the generator allows the generator supplier to work with the customer to choose a generator and system design that will provide trouble free operation. Suggestions for specifying a generator for leading power factor operation are provided. Excitation of Synchronous Machines Rotating electrical machines in general have a component that produces a magnetic field and a component that interacts with the magnetic field. In synchronous generators a stator (armature) winding produces voltage in response to a magnetic field produced when a rotor winding is “excited” by field current. The field current is controlled by a voltage regulator. In the no-load condition, increasing the magnetic field results in an increase in voltage. The generator field current must increase and the voltage level must be maintained to provide power output. Real vs. Reactive power Electrical power is the product of volts and amperes. Over a complete cycle of AC waveform, the voltage and current wave forms may not line up, resulting in the peak voltage occurring when the current is less than its maximum, and vice-versa. In this case the average power calculated over the complete cycle is less than the “apparent” power, which is the product of RMS voltage and RMS current. This average power is the “real” or active power that produces useful work. Real power is measured in watts and is the power that shows up on your electric bill. To help understand this we divide the current flowing in a circuit two parts: the real current, which is in-phase with the voltage and causes net average (real) power flow, and the reactive current, which is 90° out of phase with the voltage and transfers no average (real) power. The product of reactive current and voltage is sometimes called “reactive power” (though no actual power is being supplied) or VARs for “volt-amperes reactive”. The relationship between active (real), reactive, and apparent power is shown in the power right triangle (Figure 1). Apparent power S = where P is active power (watts) and Q is reactive power (VARs).
  • 2. Figure 1: Relationship between real, reactive, and apparent power (Power Right Triangle). Power Factor Power factor (PF) is defined as the ratio between the active (real) power (the average value of instantaneous product of voltage and current, as measured by a wattmeter) and the apparent power. Power factor is the cosine of the angle  as shown in Figure 1. Historically, power factor less than unity was considered to be caused by a phase difference between voltage and current. This is called “displacement” power factor. Displacement power factor is the primary concern in this paper, although the definition of power factor includes other types of current that do not produce real power, particularly harmonic current. The “harmonic” power factor has the effect of extra heating in the damper cage of the machine but does not affect the excitation or stability of the machine. Harmonic power factor will not be addressed. In the following graphs [Error! Reference source not found.] red represents voltage and blue represents current. In the first graph labeled “PF = 1.0”, the voltage and current are aligned (in phase) and the average power is equal to the RMS voltage times the RMS current. The graph directly below shows the power is flowing only in the positive direction. Moving to the right each graph shows a decreasing power factor. As the power factor decreases the average power decreases, and during part of the cycle the power flows in reverse, until at zero power factor, as much power flows forward as backward, and no average power is delivered. In each case Figure 2: Power factor illustrated
  • 3. voltage, current, and apparent power are constant. These graphs are for lagging power factor. Lagging vs. Leading Power Factor Inductive loads such as electrical motors, which make up a large part of the load on the grid, draw lagging power. That is, the power factor is less than 1.0 (typically around 0.8), and the current waveform lags the voltage – the peak of the current occurs after the peak of voltage. The opposite is true of capacitive loads – in this case the power factor is less than 1.0 but the peak of the current occurs before the peak of the voltage, and we call the power factor leading. In either case the power factor is positive, but the direction of flow of reactive current is opposite. (The term “negative power factor” does not apply as it would mean a reversal of real power flow.) Effect of reactive load on generator excitation The current in a generator (rotor or stator) creates magnetic flux, and the voltage in the stator coils is related to the rate of change of flux, so maximum voltage in a coil occurs when the flux is changing most rapidly, which is when the stator coil is aligned with the space between two adjacent poles. For operation at 1.0 PF, this occurs at approximately the instant the current is maximum. So the flux created by in-phase (1.0 PF) current is aligned between the poles, where there is the least sensitivity to the flux created. For this reason, in-phase current or real power does not have a great effect on the field current required to produce rated voltage. On the other hand, reactive power produces flux that is aligned with the poles, and depending on the polarity, has either a magnetizing or demagnetizing effect. Leading power factor current produces a magnetizing effect, which means that less field current is required to produce rated voltage. Lagging power factor produces a demagnetizing effect, requiring additional field current to maintain the magnetic field level and thus rated voltage. (This is why lagging power factor load results in increased rotor heating.) The field excitation determines the peak torque the generator can accept, and if it is reduced too much, the engine may try to supply more torque than the generator can accept, leading to instability. [1] Stability in Island Operation In island operation, a generator is supplying power, by itself or in a small group of identical generators, to a load that is not connected to the grid. In this configuration, the frequency is determined by the speed setting of the engine governor, the voltage by the voltage regulator controlling the generator excitation, and the load power and power factor are completely determined by the load. In island operation, the power factor of the connected load may be leading, and, if so, it will tend to magnetize the rotor and so reduce the required excitation current of the generator. If the excitation current is reduced to zero, the voltage regulator will have no more control over the voltage, which will rise to a value determined by the saturation of the generator. Even if the excitation is reduced close to zero, there may be insufficient torque capability for the applied load power. In this case, the generator will operate as a very poor induction generator and the voltage will drop until the regulator kicks in again. The voltage will surge and oscillate, leading to overheating and rotor damage if it is not shut down.
  • 4. Stability in Grid‐Connected Operation In grid-connected operation, the generator is connected to a utility or to a large group of generators approximating a utility. The frequency is set by the grid. The load real power is completely determined by the engine governor, and the reactive power (i.e. power factor) is determined by the excitation applied to the generator field. Since the power factor is controlled by the generator in this mode of operation, the main concern is to make sure that the excitation remains high enough that the generator can accept the torque supplied by the engine. Many digital regulators have a minimum excitation setting that can perform this function. If the excitation does fall too low, the engine will cause the generator to “slip poles” and operate at a speed higher than synchronous speed. This will cause harmful currents in the generator rotor and large pulsating torque on the shaft, which can damage the generator, coupling, or engine crankshaft. Because the torque is the limiting factor for both modes, the limits of leading power factor operation are effectively the same for either island or grid-connected operation. Reactive Capability Curves The interaction between field current and output voltage and current is complex, especially when saliency and saturation of the magnetic material are considered, so usually simplified but conservative rules are used to determine generator sizing. For instance, a cylindrical rotor may be assumed. The tool most commonly used to determine excitation limits is the reactive capability curve, which is derived from these simplified rules. The generator parameters that control this are saturated short-circuit ratio (SCR or, in Europe, Kcc) and saturated synchronous impedance Xds. These both represent the same quantity and are reciprocals of each other. High SCR and low Xds make the machine more stable. To a first approximation, if Xds is less than 1, or SCR greater than 1, the machine will be stable with any leading power factor down to zero. To achieve this usually requires a very oversize machine. For larger values of leading power factor, the reactive capability curve should be consulted. This curve gives the power factor or leading VAR limit for all values of real load. A sample capability curve is shown in Figure 2. The same curve is often drawn with the axes swapped as in Figure 3. These graphs are most useful when the axes are plotted at the same scale, since then all the curves are arcs of circles. With lagging power factor, the limits on generator output are caused by heating. At leading power factor, on the other hand, the limits are concerned with the stability of the machine, meaning its ability to supply power at a steady rate at constant speed and voltage. Examining the two graphs illustrated, we see that the shapes of the leading portions of the curve are quite different. Each manufacturer decides what criteria to use to draw this curve, and there is no standard procedure. We will show some of the criteria here, based on Figure 2. The right-hand part of the leading power factor curve is based on the 2600 kVA limit due to stator heating.
  • 5. The intersection of the leading power factor curve with the negative Y axis is located at about - 1430 kVAR, which is just the kVA rating (2600 kVA) times the short-circuit ratio SCR (0.55). This represents the point where the excitation becomes zero with no real load. We will call this point P. It is not a practical operating point, but with a modern digital regulator it is possible to come close. The distance from P to the operating point, divided by the absolute value of Y at point P, is approximately the per-unit excitation current (where 1 PU represents the no-load unsaturated excitation). The diagram of Figure 4 shows an excitation limit of about 25% of the no-load value. With any real load above zero, the torque angle  is the limiting factor. A generator with cylindrical rotor reaches the limit of its stable torque when  = 90°. Again, this is not a practical operating condition, since any disturbance will cause the generator to lose sync. The torque angle  is represented by the angle between the y axis and the line drawn from point P and the operating point. Figure 4 shows a curve with a  limit of 75°, considered to be a practical limit. The graph of Figure 2 has a curved line for the stability limit. This is meant to compensate for external impedance between the load and grid for grid-parallel operation, and comes from a 1954 AIEE paper by Rubenstein and Temoshok [2]. Figure 2: Typical Reactive Capability Curve.
  • 6. Figure 4: Illustration of Minimum Excitation and Angle . -2000 -1800 -1600 -1400 -1200 -1000 -800 -600 -400 -200 0 0 500 1000 1500 2000 2500 3000 Leading -- Reactive Load kVAR Power (kW)  P Minimum Excitation Figure 3: Alternative Reactive Capability Curve Format.
  • 7. Some generators have additional limitations on leading power factor operation due to end-turn heating or other factors [3]. Other authors propose different safety factors, including fixed torque margin or fixed excitation margin [3] [5] [6] [6], so the limits illustrated do not cover all cases. Effect of Transient Performance on Stability A synchronous generator has a rotor field winding to provide magnetic flux during steady-state operation, and typically a damper (amortisseur) winding, which consists of a number of conducting bars embedded in the rotor pole face. The damper winding bars may only be interconnected within each pole, or they may be also connected between poles [Figure 5]. Completely connecting the bars and poles together provides superior transient performance. The rotor field winding and damper cage act to resist sudden changes in flux in the rotor. When there is a sudden load change, the currents conducted in these circuits act in a manner to prevent a corresponding sudden change in load angle or voltage. This helps to stabilize the system. The cage currents decay very quickly (subtransient time constant) whereas the rotor currents persist longer (transient time constant). The effect only persists until the transient period has passed (on the order of a second or two), so it can prevent a brief event (e.g. a voltage dip or short-circuit) from driving the system into instability, but it will have no effect on steady-state stability. Nevertheless, a robust damper cage is an advantage in keeping the system stable. Figure 5: Damper Windings. Fully-Connected Damper Cage Interrupted Damper Cage
  • 8. Effect of the Regulator on Stability For the island mode case, the voltage regulator will generally be set for a fixed generator voltage output, and will not affect steady-state stability. However, sudden application of a leading power factor load may cause the regulator to shut off and produce a temporary undershoot of excitation, which could cause transient instability. It will generally be advisable to set an underexcitation limit to prevent this from happening. In the case of a grid-connected generator, the voltage regulator in droop mode will cause much the same effect as for island mode. On the other hand, if the regulator is set for power factor control, addition of leading power factor load will cause an increase in excitation in order to maintain constant power factor, so in this case the regulator will have a stabilizing effect. [8] How to Specify Generators for Leading Power Factor Ideally, the generator OEM and the user (or site engineer) should work together to select a generator design that will meet the requirements of the site. In addition to the normal rating data, the manufacturer will benefit from the following information:  Whether the site will run in island or grid-connected mode, or both.  In island mode, what sort of capacitive load will be connected, and how it will be coordinated with other loading. For example, large UPS sets will generally have a fixed capacitive reactance on the input due to the input filters, but these UPS sets will have variable real power load depending on how their output is loaded. Other loads on the circuit (e.g. chillers) may provide lagging load to counterbalance the leading load, but if they are started after the leading load, the system must be stable without them.  In grid-connected mode, the user has control over the VAR loading, but if leading power factor operation is required (possibly for local voltage control at light load), the generator manufacturer needs to know the possible range of real and reactive loading. To meet the site requirements, the manufacturer may:  Propose an oversize generator in order to keep the synchronous reactance low.  Use a special design that is more saturated than normal for the same reason.  Include special testing to insure that the generator will meet requirements.  Propose additional protective relaying and controls to detect or prevent unstable conditions. At a minimum, a reactive capability curve as well as saturation curves and V-curves should be requested for the proposed generator before ordering, and carefully examined by the site engineer to make certain the generator will always operate within the safe region. Because the leading power factor capability depends strongly on factors that vary by manufacturer, frame size, pole count, and model, it is not possible to use a “rule of thumb” for sizing the generator. The voltage regulator specified should have internal provision for over- and under-excitation limits. If the generator is connected to the grid, the voltage regulator should also have power factor control. Protective relaying should include over- and under-voltage as well as excitation failure relays.
  • 9. Bibliography:  [1] T. Lipo, Analysis of synchronous machines, Madison, WI: Wisconsin Power Electronics Research Center, University of Wisconsin, 2008. [2] A. Rubenstein and M. Temoshok, "Underexcited Reactive Ampere Limit for Modern Amplidyne Voltage Regulator," Trans. AIEE, no. December, pp. 1433-1438, 1954. [3] G. Staats, "Eddy Currents in the End Portion of Turbine-Generator Stator Windings," Trans. AIEE, no. June, pp. 384-391, 1957. [4] W. Heffron, "A Simplified Approach to Steady-State Stability Limits," Trans. AIEE, no. February, pp. 39-44, 1954. [5] M. Adibi and D. Milanicz, "Reactive Capability Limitation of Power Systems," IEEE Trans. on Power Systems, vol. 9, no. 1, pp. 29-40, 1994. [6] N. Nilsson and J. Mercurio, "Synchronous Generator Capability Curve Testing and Evaluation," IEEE Trans. on Power Delivery, vol. 9, no. 1, pp. 414-424, 1994. [7] I. Nagy, "Analysis of Minimum Excitation Limits of Synchronous Machines," IEEE Trans. on Power Apparatus and Systems, vol. 89, no. 6, pp. 1001-1008, 1970. [8] L. Qiang, L. Yong-gang and L. Hai-bo, "Steady-State Stability Limit of Turbine-Generators in Consideration of AVR," in International Conference on Electrical Machines and Systems, Seoul, 2007.