The document reports experimental results for the total heat gain and radiant/convective split from various office, laboratory, and hospital equipment. It finds that:
1) The actual power consumption of equipment tested was significantly less than nameplate ratings, ranging from 14-36% of ratings.
2) The radiant portion of total heat gain ranged from 11-57%, depending on the equipment.
3) Nameplate power ratings should not be used for cooling load calculations as they tend to overestimate loads.
The primary objective of this report is to provide a convenient, consistent and accurate method of calculating heating and cooling loads and to enable the designer to select systems that meet the requirement for efficient utilization and are also responsive to environmental needs. The ability to estimate loads more accurately due to changes in the calculation procedure provides a lessened margin of error. Therefore, it becomes increasingly important to survey and check more carefully the load sources, each item in the load and the effect of the system type on the load. Junaid Hussain | Syed Abdul Gaffar "Heat Load Calculation" Published in International Journal of Trend in Scientific Research and Development (ijtsrd), ISSN: 2456-6470, Volume-3 | Issue-5 , August 2019, URL: https://www.ijtsrd.com/papers/ijtsrd26571.pdfPaper URL: https://www.ijtsrd.com/engineering/mechanical-engineering/26571/heat-load-calculation/junaid-hussain
The primary objective of this report is to provide a convenient, consistent and accurate method of calculating heating and cooling loads and to enable the designer to select systems that meet the requirement for efficient utilization and are also responsive to environmental needs. The ability to estimate loads more accurately due to changes in the calculation procedure provides a lessened margin of error. Therefore, it becomes increasingly important to survey and check more carefully the load sources, each item in the load and the effect of the system type on the load. Junaid Hussain | Syed Abdul Gaffar "Heat Load Calculation" Published in International Journal of Trend in Scientific Research and Development (ijtsrd), ISSN: 2456-6470, Volume-3 | Issue-5 , August 2019, URL: https://www.ijtsrd.com/papers/ijtsrd26571.pdfPaper URL: https://www.ijtsrd.com/engineering/mechanical-engineering/26571/heat-load-calculation/junaid-hussain
To design any air-conditioning unit, estimation of heating or cooling load is very important. It helps us in design different devices most importantly the humidifier (in case of winter) or de-humidifier (in case of summer).
Refrigeration and Air Conditioning
1.Refrigeration System
Two types of valves are used on machine air conditioning systems:
Internally-equalized valve - most common
Externally-equalized valve special control
Internally-Equalized Expansion Valve
The refrigerant enters the inlet and screen as a high-pressure liquid. The refrigerant flow is restricted by a metered orifice through which it must pass.
As the refrigerant passes through this orifice, it changes from a high-pressure liquid to a low-pressure liquid (or passes from the
high side to the low side of the system).
Let's review briefly what happens to the refrigerant as we change its pressure.
As a high-pressure liquid, the boiling point of the refrigerant has been raised in direct proportion to its pressure. This has concentrated its heat content into a small area, raising the temperature of the refrigerant higher than that of the air passing over the condenser. This heat will then transfer from the warmer refrigerant to the cooler air, which condenses the refrigerant to a liquid.
The heat transferred into the air is called latent heat of condensation. Four pounds (1.8 kg) of refrigerant flowing per minute through the orifice will result in 12,000 Btu (12.7 MJ) per hour transferred, which is designated a one-ton unit. Six pounds (2.7 kg) of flow per minute will result in 18,000 Btu (19.0 MJ) per hour, or a one and one-half ton unit.
Valve details
The refrigerant flow through the metered orifice is extremely important, anything restricting the flow will affect the entire system.
If the area cooled by the evaporator suddenly gets colder, the heat transfer requirements change. If the expansion valve continued to feed the same amount of refrigerant to the evaporator, the fins and coils would get colder until they eventually freeze over with ice and the air flow is stopped.
A thermal bulb has a small line filled with C02 is attached to the evaporator tailpipe. If the temperature on the tail pipe raises, the gas will expand and cause pressure against the diaphragm. This expansion will then move the seat away from the orifice,
Using the software e-QUEST, compute:
1. Plant Energy Utilization Summary
2. Monthly peak and total energy use
3. Monthly energy by end use
4. Energy peak breakdown by end use
For a modern two-story office building that is located in a city of your choice has a
building area 20000 sq.ft.
Beautiful Collection by Voylla for Lucknowi Nawabi look. In this collection you see beautiful Nose Rings, Hathphools, Nawabi Anguthi, Chaand balis, Jhumki and many more.
Mangalsutra is a word that brings with it traditional tie and a promise of longtime relationship. Among the solha-sringar of a married woman, Mangalsutra is the first and foremost jewelry, which marks the onset of a new relation.
To design any air-conditioning unit, estimation of heating or cooling load is very important. It helps us in design different devices most importantly the humidifier (in case of winter) or de-humidifier (in case of summer).
Refrigeration and Air Conditioning
1.Refrigeration System
Two types of valves are used on machine air conditioning systems:
Internally-equalized valve - most common
Externally-equalized valve special control
Internally-Equalized Expansion Valve
The refrigerant enters the inlet and screen as a high-pressure liquid. The refrigerant flow is restricted by a metered orifice through which it must pass.
As the refrigerant passes through this orifice, it changes from a high-pressure liquid to a low-pressure liquid (or passes from the
high side to the low side of the system).
Let's review briefly what happens to the refrigerant as we change its pressure.
As a high-pressure liquid, the boiling point of the refrigerant has been raised in direct proportion to its pressure. This has concentrated its heat content into a small area, raising the temperature of the refrigerant higher than that of the air passing over the condenser. This heat will then transfer from the warmer refrigerant to the cooler air, which condenses the refrigerant to a liquid.
The heat transferred into the air is called latent heat of condensation. Four pounds (1.8 kg) of refrigerant flowing per minute through the orifice will result in 12,000 Btu (12.7 MJ) per hour transferred, which is designated a one-ton unit. Six pounds (2.7 kg) of flow per minute will result in 18,000 Btu (19.0 MJ) per hour, or a one and one-half ton unit.
Valve details
The refrigerant flow through the metered orifice is extremely important, anything restricting the flow will affect the entire system.
If the area cooled by the evaporator suddenly gets colder, the heat transfer requirements change. If the expansion valve continued to feed the same amount of refrigerant to the evaporator, the fins and coils would get colder until they eventually freeze over with ice and the air flow is stopped.
A thermal bulb has a small line filled with C02 is attached to the evaporator tailpipe. If the temperature on the tail pipe raises, the gas will expand and cause pressure against the diaphragm. This expansion will then move the seat away from the orifice,
Using the software e-QUEST, compute:
1. Plant Energy Utilization Summary
2. Monthly peak and total energy use
3. Monthly energy by end use
4. Energy peak breakdown by end use
For a modern two-story office building that is located in a city of your choice has a
building area 20000 sq.ft.
Beautiful Collection by Voylla for Lucknowi Nawabi look. In this collection you see beautiful Nose Rings, Hathphools, Nawabi Anguthi, Chaand balis, Jhumki and many more.
Mangalsutra is a word that brings with it traditional tie and a promise of longtime relationship. Among the solha-sringar of a married woman, Mangalsutra is the first and foremost jewelry, which marks the onset of a new relation.
An overview of the Grow! Minnesota Service provided by the Minnesota Chamber of Commerce. Efforts to support Minnesotans and grow businesses in a "shaky" economy.
Excellent Varieties and Best Quality In Italian Tiles For Your Total Home Mak...EBEES DECOR
EBEESDECOR is supplier of best quality Italian Tiles. These tiles are of the best and finest quality. Bulk orders are solicited. "Give your place total makeover". We are one of the best interiors and decorators supported by some finest architects.
Comparison of Cooling Load Calculations by using Theoretical Analysis and E 2...ijtsrd
This paper provides the calculating of cooling load by using not only theoretical analysis and cooling load software E 20 for aesthetic clinic. According to the surveys and measurement, the materials used for this clinic are roof with steel sheet without insulation but with finished ceiling, 10 cm thickness single clear glass with interior curtain shades and wall with 10 cm common brick with 2.5 cm insulation are used. According to the theoretical analysis, the clinic required 124.53 KW while required 131 KW based on E 20 software. The values difference between theoretical analysis and E 20 software for this clinic is 5 . Aung Ko Ko Lwin | Dr. Soe Soe Nu "Comparison of Cooling Load Calculations by using Theoretical Analysis and E-20 Software for Aesthetic Clinic with Time Series" Published in International Journal of Trend in Scientific Research and Development (ijtsrd), ISSN: 2456-6470, Volume-5 | Issue-2 , February 2021, URL: https://www.ijtsrd.com/papers/ijtsrd38444.pdf Paper Url: https://www.ijtsrd.com/engineering/mechanical-engineering/38444/comparison-of-cooling-load-calculations-by-using-theoretical-analysis-and-e20-software-for-aesthetic-clinic-with-time-series/aung-ko-ko-lwin
Air Water System Design using Revit Mep for a Residential Buildingijtsrd
In this project we discussed the study and performance of air conditioner, air refrigeration and water conditioner system in a single unit. The main objective of this project is to develop the multifunctional system which can provide refrigeration effect, cold water and air conditioning effect with in regular air or space conditioning system. Air and water systems conditioning spaces by distributing the both conditioned air and water to the terminal units installed in the spaces for which the basic plan is given by civil department and the basic design is done by using REVIT MEP software. The air and water are heated or cooled in a central mechanical equipment room. The air supplied is termed as primary air to distinguish it from the recirculated or secondary room air. By using the peak cooling load values obtained in the heating and cooling load calculations the ton of refrigeration values for individual and total area is calculated which will be helpful for selection of accurate design for the residential building. B. Shushma | M. Uday Bhaskar | N. Balaji | G. Srujan Yadav ""Air-Water System Design using Revit Mep for a Residential Building"" Published in International Journal of Trend in Scientific Research and Development (ijtsrd), ISSN: 2456-6470, Volume-3 | Issue-3 , April 2019, URL: https://www.ijtsrd.com/papers/ijtsrd23314.pdf
Paper URL: https://www.ijtsrd.com/engineering/mechanical-engineering/23314/air-water-system-design-using-revit-mep-for-a-residential-building/b-shushma
PRACTICAL ISSUES ASSOICATED WITH THE USE OF INFRARED THERMOGRAPHY FOR DETECTI...John Kingsley
PRACTICAL ISSUES ASSOICATED WITH THE USE OF INFRARED
THERMOGRAPHY FOR DETECTION OF HEAT, AIR AND
MOISTURE DEFICIENCIES IN BUILDING ENVELOPES
DETECTING THERMAL ANOMALIES RELATED TO CONDUCTIVE HEAT TRANSFER
THERMAL ANALYSIS OF AIR FLOW IN A CPU CABINET WITH MOTHERBOARD AND HARD DISK ...IAEME Publication
The present work investigates the numerical simulation of thermal analysis of mixed convection air flow in a CPU Cabinet. The simulation is focused on the non-uniformly heated mother board temperature distribution. In the
present work three cases have been studied, 1) Placing the CPU in vertical position, 2) Placing the CPU in horizontal
position and 3) Providing exhaust fan on top. The work also includes studies of effectiveness of different inlets provided.
The temperature distribution of the components and streamlines were investigated in order to get a clear picture of which case is more effective for cooling of the mother board
Development of a Bench-Top Air-to-Water Heat Pump Experimental ApparatusCSCJournals
A bench-top air-to-water heat pump experimental apparatus was designed, developed, and constructed for instructional and demonstrative purposes. This air-to-water heat pump experimental apparatus is capable of demonstrating thermodynamics and heat transfer concepts and principles. This heat pump experimental setup was designed around the vapor compression refrigeration cycle. This experimental apparatus has an intuitive user interface, reliable, safe for student use, and portable. The interface is capable of allowing data acquisition by a computer. A PC-based control system which consists of LabVIEW and data acquisition unit is employed to monitor and control this experimental laboratory apparatus. This paper provides details about the development of this unit and the integration of the electrical/electronic component and the control system.
THERMAL ANALYSIS OF A HEAT SINK FOR ELECTRONICS COOLINGIAEME Publication
Heat transfer is a discipline of thermal engineering that concern the generation, use, conversion and exchange of thermal energy, heat between physical systems. Heat transfer is classified in to various mechanisms such as heat conduction, convection, thermal radiation & transfer of energy by phase change. Most of the electronic equipment are low power and produce negligible amount of heat in their operation. Some devices, such as power transistors, CPU's, & power diodes produce a significant amount of heat. so sufficient measures are need to be taken so as to prolong their working life and reliability.
Explore the innovative world of trenchless pipe repair with our comprehensive guide, "The Benefits and Techniques of Trenchless Pipe Repair." This document delves into the modern methods of repairing underground pipes without the need for extensive excavation, highlighting the numerous advantages and the latest techniques used in the industry.
Learn about the cost savings, reduced environmental impact, and minimal disruption associated with trenchless technology. Discover detailed explanations of popular techniques such as pipe bursting, cured-in-place pipe (CIPP) lining, and directional drilling. Understand how these methods can be applied to various types of infrastructure, from residential plumbing to large-scale municipal systems.
Ideal for homeowners, contractors, engineers, and anyone interested in modern plumbing solutions, this guide provides valuable insights into why trenchless pipe repair is becoming the preferred choice for pipe rehabilitation. Stay informed about the latest advancements and best practices in the field.
NO1 Uk best vashikaran specialist in delhi vashikaran baba near me online vas...Amil Baba Dawood bangali
Contact with Dawood Bhai Just call on +92322-6382012 and we'll help you. We'll solve all your problems within 12 to 24 hours and with 101% guarantee and with astrology systematic. If you want to take any personal or professional advice then also you can call us on +92322-6382012 , ONLINE LOVE PROBLEM & Other all types of Daily Life Problem's.Then CALL or WHATSAPP us on +92322-6382012 and Get all these problems solutions here by Amil Baba DAWOOD BANGALI
#vashikaranspecialist #astrologer #palmistry #amliyaat #taweez #manpasandshadi #horoscope #spiritual #lovelife #lovespell #marriagespell#aamilbabainpakistan #amilbabainkarachi #powerfullblackmagicspell #kalajadumantarspecialist #realamilbaba #AmilbabainPakistan #astrologerincanada #astrologerindubai #lovespellsmaster #kalajaduspecialist #lovespellsthatwork #aamilbabainlahore#blackmagicformarriage #aamilbaba #kalajadu #kalailam #taweez #wazifaexpert #jadumantar #vashikaranspecialist #astrologer #palmistry #amliyaat #taweez #manpasandshadi #horoscope #spiritual #lovelife #lovespell #marriagespell#aamilbabainpakistan #amilbabainkarachi #powerfullblackmagicspell #kalajadumantarspecialist #realamilbaba #AmilbabainPakistan #astrologerincanada #astrologerindubai #lovespellsmaster #kalajaduspecialist #lovespellsthatwork #aamilbabainlahore #blackmagicforlove #blackmagicformarriage #aamilbaba #kalajadu #kalailam #taweez #wazifaexpert #jadumantar #vashikaranspecialist #astrologer #palmistry #amliyaat #taweez #manpasandshadi #horoscope #spiritual #lovelife #lovespell #marriagespell#aamilbabainpakistan #amilbabainkarachi #powerfullblackmagicspell #kalajadumantarspecialist #realamilbaba #AmilbabainPakistan #astrologerincanada #astrologerindubai #lovespellsmaster #kalajaduspecialist #lovespellsthatwork #aamilbabainlahore #Amilbabainuk #amilbabainspain #amilbabaindubai #Amilbabainnorway #amilbabainkrachi #amilbabainlahore #amilbabaingujranwalan #amilbabainislamabad
CFD Simulation of By-pass Flow in a HRSG module by R&R Consult.pptxR&R Consult
CFD analysis is incredibly effective at solving mysteries and improving the performance of complex systems!
Here's a great example: At a large natural gas-fired power plant, where they use waste heat to generate steam and energy, they were puzzled that their boiler wasn't producing as much steam as expected.
R&R and Tetra Engineering Group Inc. were asked to solve the issue with reduced steam production.
An inspection had shown that a significant amount of hot flue gas was bypassing the boiler tubes, where the heat was supposed to be transferred.
R&R Consult conducted a CFD analysis, which revealed that 6.3% of the flue gas was bypassing the boiler tubes without transferring heat. The analysis also showed that the flue gas was instead being directed along the sides of the boiler and between the modules that were supposed to capture the heat. This was the cause of the reduced performance.
Based on our results, Tetra Engineering installed covering plates to reduce the bypass flow. This improved the boiler's performance and increased electricity production.
It is always satisfying when we can help solve complex challenges like this. Do your systems also need a check-up or optimization? Give us a call!
Work done in cooperation with James Malloy and David Moelling from Tetra Engineering.
More examples of our work https://www.r-r-consult.dk/en/cases-en/
Student information management system project report ii.pdfKamal Acharya
Our project explains about the student management. This project mainly explains the various actions related to student details. This project shows some ease in adding, editing and deleting the student details. It also provides a less time consuming process for viewing, adding, editing and deleting the marks of the students.
Water scarcity is the lack of fresh water resources to meet the standard water demand. There are two type of water scarcity. One is physical. The other is economic water scarcity.
Hierarchical Digital Twin of a Naval Power SystemKerry Sado
A hierarchical digital twin of a Naval DC power system has been developed and experimentally verified. Similar to other state-of-the-art digital twins, this technology creates a digital replica of the physical system executed in real-time or faster, which can modify hardware controls. However, its advantage stems from distributing computational efforts by utilizing a hierarchical structure composed of lower-level digital twin blocks and a higher-level system digital twin. Each digital twin block is associated with a physical subsystem of the hardware and communicates with a singular system digital twin, which creates a system-level response. By extracting information from each level of the hierarchy, power system controls of the hardware were reconfigured autonomously. This hierarchical digital twin development offers several advantages over other digital twins, particularly in the field of naval power systems. The hierarchical structure allows for greater computational efficiency and scalability while the ability to autonomously reconfigure hardware controls offers increased flexibility and responsiveness. The hierarchical decomposition and models utilized were well aligned with the physical twin, as indicated by the maximum deviations between the developed digital twin hierarchy and the hardware.
Final project report on grocery store management system..pdfKamal Acharya
In today’s fast-changing business environment, it’s extremely important to be able to respond to client needs in the most effective and timely manner. If your customers wish to see your business online and have instant access to your products or services.
Online Grocery Store is an e-commerce website, which retails various grocery products. This project allows viewing various products available enables registered users to purchase desired products instantly using Paytm, UPI payment processor (Instant Pay) and also can place order by using Cash on Delivery (Pay Later) option. This project provides an easy access to Administrators and Managers to view orders placed using Pay Later and Instant Pay options.
In order to develop an e-commerce website, a number of Technologies must be studied and understood. These include multi-tiered architecture, server and client-side scripting techniques, implementation technologies, programming language (such as PHP, HTML, CSS, JavaScript) and MySQL relational databases. This is a project with the objective to develop a basic website where a consumer is provided with a shopping cart website and also to know about the technologies used to develop such a website.
This document will discuss each of the underlying technologies to create and implement an e- commerce website.
Cosmetic shop management system project report.pdfKamal Acharya
Buying new cosmetic products is difficult. It can even be scary for those who have sensitive skin and are prone to skin trouble. The information needed to alleviate this problem is on the back of each product, but it's thought to interpret those ingredient lists unless you have a background in chemistry.
Instead of buying and hoping for the best, we can use data science to help us predict which products may be good fits for us. It includes various function programs to do the above mentioned tasks.
Data file handling has been effectively used in the program.
The automated cosmetic shop management system should deal with the automation of general workflow and administration process of the shop. The main processes of the system focus on customer's request where the system is able to search the most appropriate products and deliver it to the customers. It should help the employees to quickly identify the list of cosmetic product that have reached the minimum quantity and also keep a track of expired date for each cosmetic product. It should help the employees to find the rack number in which the product is placed.It is also Faster and more efficient way.
Planning Of Procurement o different goods and services
Heat gain valuees foe equipment
1. THIS PREPRINT IS FOR DISCUSSION PURPOSES ONLY, FOR INCLUSION IN ASHRAE TRANSACTIONS 1999, V. 105, Pt. 2. Not to be reprinted in whole or in
part without written permission of the American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc., 1791 Tullie Circle, NE, Atlanta, GA 30329.
Opinions, findings, conclusions, or recommendations expressed in this paper are those of the author(s) and do not necessarily reflect the views of ASHRAE. Written
questions and comments regarding this paper should be received at ASHRAE no later than July 7, 1999.
ABSTRACT
Measurement of the heat loss from equipment in buildings
is necessary in order to make accurate assessments of its
impact on cooling loads. Recent advances in the design of
buildings and improvement of the thermal characteristics of
insulation materials and building envelope systems have
significantly reduced the cooling load from external sources;
however,theadditionofvarioustypesofoffice,laboratory,and
hospital equipment to buildings has become a major source of
internal cooling load. Unfortunately, accurate information on
the total heat gain from equipment is lacking in current hand-
books. Some equipment includes a nameplate rating showing
totalpowerconsumption,whileotherequipment does nothave
this. Some manufacturers measure maximum electric power
consumption by the equipment and list that as power ratings
on the nameplate or in the equipment literature, while some
otherslistthemaximumpowercapacityofthesystem.Sincethe
manufacturers’ power ratings, if reported, are usually based
on instantaneous measurement while equipment is working at
maximum capacity, use of equipment nameplate values for
cooling load calculations may lead to oversizing of air-condi-
tioning equipment, resulting in extra initial cost as well as
higheroperatingcosts.Ontheotherhand,underestimatingthe
cooling load may result in insufficient cooling capacity.
Another factor affecting calculation of cooling load is the
split between the radiant and convective heat load from the
equipment.Theconvectionportionoftheheattransferredfrom
the equipment to the surroundings is an instantaneous load,
since it is added to room air by natural or forced convection
without time delay, whereas the radiation portion is absorbed
bythesurfacesoftheroomandthendissipatedovertime.Accu-
ratedeterminationofcoolingloadisimportantinpropersizing
of air-conditioning equipment.
Thisarticlepresentsexperimentalresultsforthetotalheat
gain and radiant/convective split from equipment in offices,
hospitals, and laboratories. The nameplate vs. measured
values, peak vs. average values, operational vs. idle values,
andradiantvs.convectivevaluesarecomparedanddiscussed.
Furthermore, a brief guideline for use of the experimental
results by practicing engineers for estimating equipment cool-
ing load is presented.
INTRODUCTION
Measurement of the heat loss from office equipment and
other equipment in buildings is necessary in order to make
accurate assessments of its impact on cooling loads. Recent
advances in the design of buildings and improvement of the
thermal characteristics of insulation materials and building
envelope systems have significantly reduced the cooling load
from external sources; however, the addition of various types
of office, laboratory, and hospital equipment to buildings has
become a major source of internal cooling load. Unfortu-
nately, accurate information on the total heat gain of that
equipment is lacking in current handbooks. Some equipment
includes a nameplate rating showing e total power consump-
tion, while other equipment does not have this. Some manu-
facturers measure maximum electric power consumption by
the equipment and list that as power ratings on the nameplate
or in the equipment literature, while some others list the maxi-
mum power capacity of the system. Since the manufacturers’
power ratings, if reported, are usually based on instantaneous
measurement while equipment is working at maximum capac-
ity, use of equipment nameplate values for cooling load calcu-
Experimental Results for
Heat Gain and Radiant/Convective
Split from Equipment in Buildings
Mohammad H. Hosni, Ph.D. Byron W. Jones, Ph.D. Hanming Xu
Member ASHRAE Member ASHRAE Student Member ASHRAE
Mohammad H. Hosni is director and Hanming Xu is a graduate student at the Institute for Environmental Research, Kansas State University,
Manhattan, Kans. Byron W. Jones is associate dean of the College of Engineering at Kansas State.
SE-99-1-4 (RP-1055)
2. 2 SE-99-1-4 (RP-1055)
lations may lead to oversizing of air-conditioning equipment,
resulting in extra initial cost as well as higher operating costs.
On the other hand, underestimating the cooling load may
result in insufficient cooling capacity.
Another factor affecting cooling load calculation is the
split between the radiant and convective heat load from the
equipment. The convection portion of the heat transferred
from the equipment to the surroundings is an instantaneous
load, since it is added to room air by natural or forced convec-
tion without time delay, whereas the radiation portion is
absorbed by the surfaces of the room and then dissipated over
time.
Recognizing the lack of data on this subject and in order
to establish a database of heat gain and split between radia-
tion and convection, the American Society of Heating,
Refrigerating and Air-Conditioning Engineers sponsored the
research projects RP-822, “Test Method for Measuring the
Heat Gain and Radiant/Convective Split from Equipment in
Buildings,” in 1995 and RP-1055, “Measurement of Heat
Gain and Radiant/Convective Split from Equipment in
Buildings,” in 1998. This paper reports the results of the
latter project and includes experimental results from the
previous project as well. The main objective of this paper is
to present the experimental results for the total heat gain and
radiant/convective split from equipment in offices, hospitals,
and laboratories. The nameplate vs. measured values, peak
vs. average values, operational vs. idle values, and radiant vs.
convective values are compared and discussed. Furthermore,
a brief guideline for use of the experimental results by prac-
ticing engineers for estimating equipment cooling load is
presented.
BACKGROUND
Recent advances in calculation methods of solar heat gain
and improvements in thermal characteristics of building enve-
lope systems have improved estimation of external cooling
loads; however, the addition of various types of office, labo-
ratory, and hospital equipment in buildings has become a
major source of building internal cooling loads for which
accurate data are not available. The available information on
heat gain from office equipment is outdated and does not
provide an accurate split between convective and radiant
loads. The number of published technical articles related to
this topic is limited. Thus, a brief review of available relevant
literature is presented here.
Alereza and Breen (1984) reported results of their evalu-
ation of commercial appliances and equipment for heat gain
characteristics. Based on appliance manufactures’ input
ratings and adjustment factors, they obtained the rates of latent
and sensible heat for each item of equipment. They also eval-
uated an indirect method based on the voltage, amperage, and
phase inputto determineequipment powerratingequivalent to
the manufacturers’ input rating.
Wilkins et al. (1991) measured the heat generated by vari-
ous office items and compared the results with the manufac-
turers’ nameplate values and equipment literature to evaluate
the accuracy and the relevance of listed power ratings for
cooling load calculations. They obtained instantaneous and
average power consumption over a time period. They found
that the actual power consumption for a desktop computer was
20% to 30% of the rated power (450-900 watts) as reported by
the manufacturer. They also found that the usage factors for
different types of equipment varied significantly.
Wilkins and McGaffin (1994) presented actual energy
consumption data for different computers, monitors, and
printers for both idle and operational modes.
Hosni et al. (1998) reported results for total heat gain and
split between convection and radiation heat gain for typical
office and laboratory equipment, such as desktop computers,
monitors, a copier, a laser printer, and a biological incubator.
In addition, two standard objects with well-defined radiant
heat loss characteristics, a heated flat slab and a heated sphere,
were used by the authors to verify the accuracy of their
measurement and data reduction procedures. They found that
the total heat gain from office equipment tested was signifi-
cantly less than the nameplate ratings even when being oper-
ated continuously. The actual power consumption ranged
from 14% to 36% of the nameplate ratings. Thus, they
cautioned against the use of equipment nameplate ratings in
estimating total heat gain for air-conditioning equipment
sizing.
Hosni et al. (1998) reported that the radiant portion of the
total heat gain ranged from a minimum of 11% for the laser
printer to a maximum of 57% for the incubator. The radiant
portion of heat gain from the heated surfaces was higher, at
about 60%.
Jones et al. (1998a) presented descriptions of a new
method for measuring radiant heat loss from equipment. They
reported the proposed measurement method, referred to as the
scanning radiometer method, which utilized a relatively inex-
pensive, off-the-shelf net radiometer to make the measure-
ments. The radiometer scans a hemispherical area about the
equipment being evaluated and, by integrating the net radiant
flux through this area, the total radiant flux from the equip-
ment to the room is measured. This method automatically
compensates for other radiant fluxes in the room. They recom-
mended this method for office equipment radiant heat gain
measurement.
Jones et al. (1998b) developed and applied infrared imag-
ining technique for measurement of radiant heat gain from
office equipment. The results from this method were
compared with those of the scanning radiometer technique.
This method was found applicable for radiant heat gain
measurements; however, the infrared imagining technique
requires a high level ofexpertise, is much more difficult to use,
and the equipment is much more expensive than the net radi-
ometer.
3. SE-99-1-4 (RP-1055) 3
EXPERIMENTAL TEST FACILITY,
MEASUREMENT EQUIPMENT, AND PROCEDURES
The radiant/convective split tests for all of the office
and laboratory equipment were conducted in an environ-
mental chamber, and the total power consumption measure-
ments for all equipment were conducted in the field. The
equipment being tested for radiant/convective split was
placed in an environmental chamber with well-controlled
temperature (70°F, 21.1°C), relative humidity (50%), and air
velocity (60 fpm, 0.3 m/s) conditions.
Under steady-state conditions, with no endothermic or
exothermic reactions involved in the equipment, the most
accurate method to determine the total heat output is by
measuring the total electric power input to the equipment.
Based on the conservation of energy principle, at steady-state
conditions the total heat output is equal to the total power
input. A watt-hour meter was used to measure the total power
consumed by the equipment being tested.
For total power consumption measurement, the equip-
ment to be tested was unplugged from the power outlet and
plugged into the watt-hour meter power inlet, then the watt-
hour meter was plugged into a power receptacle. The output
signal from the watt-hour meter corresponding to the equip-
ment power consumption was recorded every 30 seconds for
at least 30 minutes. To obtain the peak power consumption,
every consecutive six readings (at three-minutes intervals)
were averaged and recorded. The largest three-minute average
was considered as the peak power consumption. Large instan-
taneous readings that lasted less than three minutes were not
considered as peak power since those sudden increases do not
contribute to the heat gain in buildings. The average power
consumption for each equipment item was obtained by aver-
aging all readings for the entire test period.
The radiant heat loss from the equipment was measured
using a net radiometer that was mounted on a scanning arm.
This radiometer is accurate for radiation wavelengths from
0.3 to 60 microns and thus is suitable for the long-wave radi-
ation emitted by appliances. The radiometer was systemati-
cally moved in a semicircle about the appliance being tested.
The appliance was centered on a turntable so that it could be
rotated a full 360 degrees. The turntable, which was marked in
10-degree increments from 0 to 180 on its perimeter, was
covered by a radiant barrier material (emissivity < 0.05) to
ensure the downward radiation was reflected upward and
included in the measurement. Since the radiant heat flux from
the appliance normally is not uniform with respect to direc-
tions, the flux must be integrated over the entire spherical
solid angle surrounding the appliance. An accurate integration
requires many points. In this research, 51 points were used and
proved to provide satisfactory accuracy (Hosni et al. 1996). A
stepper motor and a control unit were used to remotely posi-
tion the net radiometer at various measuring positions. For
each equipment item tested, usually three data sets were
obtained and an average value was reported. The details of this
measurement technique are presented in Jones et al. (1998a).
TEST RESULTS
The total heat gain and radiant/convective split test results
for different office, laboratory, and hospital equipment are
presented and discussed here. The test results, including
description of objects tested, nameplate power rating, peak
power consumption, average power consumption, radiant and
convective heat gain, and operating mode, as well as usage
diversity, are summarized in Tables 1, 2, and 3. For office
equipment, the total power consumption and radiant/convec-
tive split for both idle and operational modes are presented.
However, total power consumption for laboratory and hospital
equipment and radiant/convective split for laboratory equip-
ment in only the operational mode are presented since these
items are usually turned on and used and not left in the idle
mode for extended periods. The radiant/convective split for
hospital equipment was not measured due to lack of portabil-
ity. Detailed discussions of the test results for each office,
laboratory, and hospital equipment item are presented in the
final research report for this project (Hosni et al. 1999). Space
limits prevent inclusion of all of these details in this paper.
SUMMARY AND GENERAL GUIDELINES
The individual data points that resulted from this study
should be quite useful for designers. However, equipment
changes quickly and the equipment items tested, although
extensive in number, are only a tiny fraction of the brands,
models, and types that exist. Only in a few special cases will
the designer know specifically what brand, make, and model
of equipment will be housed in a space. Even if they were so
lucky as to know this information and they happen to match
items reported in this study, it is likely that these furnishings
will change within a few years. For these reasons, the data
were assessed to determine if any general guidelines could be
developed. Three general questions were addressed.
1. Is it possible to make generalizations about the relationship
between nameplate data and actual power consumption?
2. Is it possible to generalize relationships regarding the radi-
ant/convective split of the heat loss from equipment?
3. Can useful ranges of heat load be estimated for categories
of equipment (computers in particular)?
Each of these questions is addressed in turn.
Relationship between Nameplate Rating
and Actual Power Consumption
In steady state, the total heat load generated is equal to the
electricalpowerconsumed for most equipment. The exception
is some laboratory equipment in which an endothermic or
exothermic reaction takes place. The power consumption for
all of the equipment tested is presented as a function of the
nameplate rating in Figure 1a. In Figure 1b, more limited
ranges of nameplate ratings are included so the individual data
points can be viewed more easily. The power consumption
data are all for continuous operation. In the case of items such
4. 4SE-99-1-4(RP-1055)
TABLE 1
Office Equipment
Equipment Description
Name-plate***
(W)
Idle Mode -
Power Consumption (W)
Operational Mode -
Power Consumption (W)
Fan UsagePeak Average Radiant Convective Peak Average Radiant Convective
Computer and Monitor Gateway 2000, Pentium-200 N/A 110 51 12
(24%)
39 (76%) 108 98 27 (27%) 71 (73%) Y Continuous
Monitor: Gateway 17" 220 N
Computer and Monitor** Pentium-200 575 133 30 (22%) 103 (78%) Y Continuous
17" monitor N
Computer and Monitor** 486DX33 420 125 36 (29%) 89 (71%) Y Continuous
15"monitor N
Computer and Monitor Dell Pentium-333 N/A 111 110 22
(20%)
88 (80%) 132 130 31 (24%) 99 (76%) Y Continuous
Monitor: Dell 19" 207 N
Computer only Micro Millenia
Pentium-200
759 53 35 54 53 Y Continuous
Computer only Gateway
4DX2-486
450 54 53 54 53 Y Continuous
Computer only Mech Professional
Pentium 200
165 39 35 53 52 Y Continuous
Computer only Gateway ATX Tower G6-400
Pentium-400
N/A 46 37 6 (15%) 31 (85%) 54 54 5 (10%) 49 (90%) Y Continuous
Copy Machine Canon NP6012
F132500
690 22 22 476 399
85*
16* (19%) 69* (81%) Y Intermittent
Copy Machine** 1320 133* 30* (22%) 103* (78%) Y Intermittent
Copy Machine Canon NP6045
F133900
1440 444 247 1140 1076 Y Intermittent
Copy Machine Canon NP6545
F137400
1440 463 267 1119 1065 Y Intermittent
Copy Machine Canon NP6050 1380 558 354 1223 1167 Y Intermittent
Electronic Image Scanner Scan Jet 3C C2520A 90 12 12 35 24 N Intermittent
Fax Machine HP Office Jet
LX C2890A
110 16 16 6 (38%) 10 (62%) 24 21
19*
6* (33%) 13* (67%) N Intermittent
Fax Machine Sharp F0-215 140 9 9 32 29 N Intermittent
Fax Machine Panafax UF-312 72 15 12 32 29 N Intermittent
Monitor 17" Acer 56L 340 58 57 25
(44%)
32 (56%) 67 65 27 (41%) 38 (59%) N Continuous
5. SE-99-1-4(RP-1055)5
Monitor 19" Dell Model D1226H 425 64 64 24
(38%)
40 (62%) N Continuous
Monitor 20" Hitachi Superscan Pro20 565 3 3 86 86 30 (35%) 56 (65%) N Continuous
Monitor 14" 1430VTM 168 51 51 53 53 N Intermittent
Monitor 17" Gateway 2000
CPD17F23 Resolution
1152 x 864
219 64 64 N Intermittent
Monitor 17" Gateway 2000
CPD17F23 Resolution
640 x 480
219 7 7 63 62 N Intermittent
Monitor 15"** Energy Saver Monitor 220 80 29 (36%) 51 (64%) N Intermittent
Plotter HP 7586E-size
8 pen type
<182W 86 82 120 112 N Intermittent
Plotter HP 7550A-size
8 pen type
<105W 30 30 43 41 N Intermittent
Dot Printer KXP 1124 420 16 16 5 (32%) 11 (68%) 56 43
31*
9* (31%) 22* (69%) N Intermittent
Dot Printer Star Gemini-10X 120 16 15 49 44 N Intermittent
Dot Printer Okidata Microline 182 48 9 8 31 30 N Intermittent
Laser Printer HP Laser Jet III 836 248* 27* (11%) 221* (89%) Y Intermittent
Laser Printer HP Laser Jet 4
C2001A
704 235 79
62*
5* (8%) 5* (92%) 332 208
101*
9* (9%) 92 (91%) Y Intermittent
Laser Printer HP Laser Jet 4P
C2005A
242 10 10 180 128
73*
16* (22%) 57* (78%) Y Intermittent
Laser Printer HP Laser Jet 6P
C3980A
419 6 6 266 217 Y Intermittent
Laser Printer HP Laser Jet 4M
C2039A
770 354 68 529 322 Y Intermittent
Laser Printer HP Laser Jet
5SiMX C3167A
1448 293 124 617 558 Y Intermittent
Network Server Tangent VL 306166 200 126 125 Y Continuous
Network Server SUN Sparc Station 10 680 340 336 Y Continuous
Notes:
* Intermittent printing/copying mode (one page per minute).
** Equipment tested in phase one of this project.
*** If the nameplate rating is given in terms of voltage and amperage, the wattage is listed as the product, i.e., power factor is approximated as unity.
TABLE 1 (Continued)
Office Equipment
6. 6SE-99-1-4(RP-1055)
TABLE 2
Laboratory Equipment
Equipment Description Name Plate*** (W)
Operational Mode-Power Consumption (W)
Fan UsagePeak Average Radiant Convective
Analytical Balance Mettle Toledo, PR 8002 7 7 7 N Intermittent
Centrifuge IEC HN-SII
Centrifuge
288 136 132
41*
14*
(34%)
27*
(66%)
N Intermittent
Centrifuge International Clinical Centrifuge 138 89 87 N Intermittent
Centrifuge IEC B-20A Centrifuge 5500 1176 730 N Intermittent
Electrochemical Analyzer Voltammetric Analyzer
CV-50W
50 45 44 N Intermittent
Electrochemical Analyzer Voltammetric Analyzer
BAS 100B
100 85 84 N Intermittent
Fluorescent Microscope Leica MZ 12 150 144 143 N Intermittent
Fluorescent Microscope Axioplan2 200 205 178 N Intermittent
Function Generator Interstate High Voltage
Function Generator-F41
58 29 29 N Intermittent
Incubator** 83 47 (57%) 36 (43%) N Intermittent
Incubator Lab-line Orbit Environ-Shaker
No. 3527
600 479 264
220*
68* (31%) 152*(69%) N Intermittent
Incubator Controlled Environment Incubator
Shaker G-28
3125 1335 1222 N Intermittent
Incubator National Incubator 3321 515 461 451 N Intermittent
Orbital Shaker VWR Scientific Orbital Shaker 100 16 16 N Intermittent
Oscilloscope BK Precision 20MHZ 2120 72 38 38 N Intermittent
Oscilloscope Nicolet Instrument Corp. 201 345 99 97 10 (10%) 87 (90%) Y Intermittent
Rotary Evaporator BUCHI Rotary 75 74 73 N Intermittent
7. SE-99-1-4(RP-1055)7
Rotary Evaporator BUCHI-RE121 Rotavapor 94 29 28 N Intermittent
Spectronics Spectronics 20 36 31 31 15 (49%) 16 (51%) N Intermittent
Spectrophotometer Hitachi U-2000 575 106 104 N Intermittent
Spectrophotometer Double Beam Spectrophoto-meter
Hitachi Perkin-Elmer
200 122 121 N Intermittent
Spectrophotometer Infrared Perkin-Elmer 1310 N/A 127 125 N Intermittent
Flame Photometer Atomic Absorption Spectometer 3110 180 107 105 N Intermittent
Spectro Fluorometer Spectro Fluorometer
Model 430
340 405 395 64 (16%) 331 (84%) N Intermittent
Tissue Culture Fisher Scientific CO2 Incubator 475 132 46 N Intermittent
Tissue Culture SteriGRAD HOOD VBM-600 2346
Peak & Ave.
in Idel mode at 53 W
1178 1146 Y Intermittent
Thermocycler Neslab RTE-221 1840 965 641
479
24 (5%) 455 (95%) Y Intermittent
Thermocycler DNA Thermo- cycler 480 N/A 233 198 Y Intermittent
Notes:
*400 rpm, i.e., 1/4 of the maximum rotation speed for centrifuge (1600 rpm), 200 rpm for shaker (i.e., 1/5 of max speed), and ½ max. temperature.
** Equipment tested in phase one of this project.
*** If the nameplate rating is given in terms of voltage and amperage, the wattage is listed as the product, i.e., power factor is approximated as unity.
TABLE 2 (Continued)
Laboratory Equipment
8. 8SE-99-1-4(RP-1055)
TABLE 3
Hospital Equipment
Equipment Description Nameplate* (W)
Operational Mode-Power Consumption
(W)
Fan UsagePeak Average
Anesthesia System Detex Anethesia System 250 177 166 N Intermittent
Blood Warmer Hotline Fluid Warmer 360 204 114 N Intermittent
Blood Pressure Meter Critikon Vital Sign Monitor 1846SX 180 33 29 N Intermittent
Blanket Warmer Blanket Warmer Model 7923SS 500 504 221 N Intermittent
Endoscope Olympus Endoscope 1688 605 596 N Intermittent
Electrosurgery Valleylab Force2
Electrosurgical Generator
1000 147 109 N Intermittent
ECG/RESP Spacelab ECG/RESP
Model 90621
1440 54 50 N Intermittent
Harmonical Scalpel Harmonical Scalpel Model G110 230 60 59 Y Intermittent
Hysteroscopic Pump Zimmer Controlled Distention Irrigation System 180 35 34 N Intermittent
Laser Sonics Laser Sonics Model:
Illumina 730
1200 256 229 N Intermittent
Optical Microscope Zeiss opMi-1 330 65 63 N Intermittent
Pulse Oximeter Nellor Pulse Oximeter, Model N10C 72 21 20 N Intermittent
Stress Treadmill EIS PRECOR
(walking speed -3 m.p.h.)
N/A 198 173 N Intermittent
X-ray System Mobil C-Arm X-Ray Sys, Model 9400 system 1725 534 480 N Intermittent
X-ray System Parorex X-ray
GX-PAN
968 nominal
110 continuous
82 N Intermittent
X-ray System Portable X-ray System
Model: 11CE8A
2070
momentary
18 N Intermittent
Vacuum Suction Berkeley VC-7 Vacuum Suction 621 337 302 N Intermittent
Ultrasound System Ultramark9 Ultrasound system UM9-HDI 1440 continuous
1800 intermittent
1063 1050 N Intermittent
Note:
* If the nameplate rating is given in terms of voltage and amperage, the wattage is listed as the product, i.e., power factor is approximated as unity.
9. SE-99-1-4 (RP-1055) 9
as printers and copiers where the power consumption may
depend on the throughput, these data are for the maximum
throughput. A substantial majority of the equipment operates
at a power level at or below 50% of the nameplate rating.
Figures 2a and 2b present only the office equipment using
the same format. Here, some general guidance may be possi-
ble. With the exception of some of the higher powered items
with nameplate ratings above 1000 watts, the actual power
consumption is typically 25% to 50% of the nameplate value.
Additionally, much of the equipment does not operate contin-
uously or operates at less than maximum levels. Where no
other information is available regarding the actual power
consumption of office equipment, the following guideline is
recommended:
A conservative estimate for the heat load of a diverse set
of office equipment with nameplate ratings less than 1000 W
is 50% of the nameplate rating. A “best” estimate for the heat
load in such cases is 25% of the nameplate rating.
Note that the guideline is predicated on a diverse set of
equipment where no one item dominates. It should not be
applied to a room full of identical computers, for example.
Figures 3a and 3b present the data for the laboratory
equipment using the same format. The power consumption of
the laboratory equipment tends to be much closer to the name-
plate rating than does the office equipment. There are a
number of exceptions, however. Also, some laboratory items
operate a low portion of the time. It is difficult to associate a
usage level with a specific piece of equipment. Rather, the
usage has much more to do with the nature of the laboratory.
An item that is operated essentially continuously in a “produc-
tion” laboratory may only run infrequently and for short peri-
ods of time in a research laboratory. Thus, a designer needs to
ascertain, if possible, the nature of the laboratory. While we
hesitate to suggest a guideline, it would appear that a reason-
able estimate of the heat load for a diverse set of laboratory
equipment with nameplate ratings less than 1000 W would be
Figure 1a Power consumption with continuous operation,
all data.
Figure 1b Power consumption with continuous operation,
all data.
Figure 2a Power consumption with continuous operation,
office equipment.
Figure 2b Power consumption with continuous operation,
office equipment.
10. 10 SE-99-1-4 (RP-1055)
70% of the nameplate. This estimate should only be used if no
other information is available. All of the laboratory equipment
with nameplate ratings greater than 1000 W consume less than
50% of the name plate rating. However, it would be dangerous
to make general conclusions based on four data points.
The data for hospital equipment are shown in Figures 4a
and 4b. They appear fairly similar to the office equipment and
the same guideline should be satisfactory. Hospital equip-
ment, like laboratory equipment, can vary tremendously in the
level of usage and the designer should endeavor to evaluate
what usage levels to expect for a given space.
Radiant/Convective Split
The data for the split of the heat loss between radiant and
convective modes are shown in Figure 5a. While there is still
considerable variation, these data are far more consistent than
the data for actual consumption versus nameplate rating and
the following guideline is offered:
Where no other information is available, total heat loss
can be estimated as 20% by radiation and 80% by convection.
The data are divided into two categories in Figures 5b and
5c according to whether or not the primary heat source is
cooled by a fan. The presence of a cooling fan would be
expected to reduce the radiant portion and increase the
convection portion. The data are consistent with this expecta-
tion. There is some uncertainty about how computer systems
should be classified. Monitors generally do not include a fan,
but the central processing units (CPU) do. Where data were
collected separately for these components, the results are
graphed accordingly. Complete systems, however, have both.
Since the monitor typically is the larger power consumer,
complete systems are graphed as not having a fan. A second
guideline is offered based on the data in Figures 5b and 5c:
For equipment with a cooling fan for the primary heat
source, total heat loss can be estimated as 10% by radiation
and 90% by convection. For equipment with no cooling fan on
the primary heat source, total heat loss can be estimated as
30% by radiation and 70% by convection.
All of the equipment included in this study had no
exposed surfaces with highly elevated temperatures. That is,
no exposed surfaces would cause significant discomfort upon
Figure 3a Power consumption with continuous operation,
laboratory equipment.
Figure 3b Power consumption with continuous operation,
laboratory equipment.
Figure 4a Power consumption with continuous operation,
hospital equipment.
Figure 4b Power consumption with continuous operation,
hospital equipment.
11. SE-99-1-4 (RP-1055) 11
direct contact with a person’s exposed skin. Essentially all
office equipment is purposely designed with this feature and
the same is true for the vast majority of laboratory and hospital
equipment. It is possible, however, that some special purpose
equipment may include surfaces with much higher tempera-
tures. The radiant portion of the heat loss will be higher for
such equipment and the above guidelines should not be
applied.
Heat Load Estimates by Categories
Ideally, a designer would like to be able to identify a piece
of equipment in general terms (office copy machine) and then
be able to make a reasonable estimate of the heat load gener-
ated by that equipment. The laboratory and hospital equip-
ment items are so diverse and individually so unique that it
does not appear possible to derive this level of information
from the data set. However, it is possible to draw some general
guidance for the office equipment. In particular, we have
attempted to develop general guidelines for office computers
and printers, copiers, and fax machines. Each will be
addressed in turn.
Computers. A desktop computer generally consists of a
monitor and central processing unit (CPU). The four CPUs
tested ranged from a 4DX2-486 to a Pentium 400 and all
consumed essentially the same amount of power during oper-
ation (53-54 W). The power required forthe pentiums dropped
by about 18 W in the idle mode while the 486 did not change.
A total of six monitors were tested. The power consumption
during operation appears to be strongly influenced by the
monitor size, as shown in Figure 6. The power consumption of
a monitor can be estimated by the following relationship:
P = 5 × S − 20
where P is power in watts and S is the monitor size in inches
and the relationship is valid for 14 < S < 20 inches. Two of the
monitors tested were so-called energy-saver monitors. That is,
these monitors go into a standby mode if they are not used for
a period of time. The power dropped to insignificant levels
Figure 5a Radiant and convective heat loss in steady-state
operation.
Figure 5b Radiant and convective heat loss, no fan on
primary heat source.
Figure 5c Radiant and convective heat loss, with fan on
primary heat source.
Figure 6 Relationship between monitor size and power
consumption.
12. 12 SE-99-1-4 (RP-1055)
when in the standby mode. For continuous operation of all
desktop computers, the following relation applies where Q is
the heat load in watts and S is the monitor size in inches (this
relation applies to 486 and standard monitors during idle
mode as well):
Q = 5 × S + 35
For a pentium computer with a standard monitor in the
idle mode,
Q = 5 × S + 15
For a pentium computer with an energy-saver monitor in
the idle mode,
Q = 40
Printers. The power consumed by the laser printers
tested depends largely on the level of throughput for which the
printer is designed. The lower end of the laser printers tested
was a minimal desktop unit intended for the individual user.
Such a printer is seldom used to run large print jobs and is in
the idle mode much of the time. The other end of the spectrum
is a high-end printer intended for a computer center or other
facility where the printer may run continuously for hours at a
time. The table below summarizes the results based on the
class of laser printer.
For continuous use, the numbers can be rounded and
combined to make a general guideline as follows:
It is unrealistic, however, to expect continuous use of at
least the first two classes of printers listed above. They simply
are not cost-effective at high production rates and would rarely
be used in that mode. The power consumption for the standby
mode ranges from near zero for the so-called energy-saver
printers to about one-third of the continuous consumption. A
reasonable estimate of the actual heat load for the first two
classes is about one-half of the continuous value for the
conventional printer and perhaps about one-fourth of the
continuous value for the energy-saver printers. For the office-
grade printers, the continuous value is recommended for
design calculations. Thus, our final recommendations for
printer heat load estimates are as follows:
Three dot matrix printers were tested as well. While there
are still many of these printers in use, they are generally used
for low print volume applications. For these applications, the
idle mode will dominate and should be used for heat load esti-
mates. In the idle mode, the dot matrix printers generate little
heat and 20 watts is a reasonable estimate that includes the
higher power consumption from the occasional use they expe-
rience.
Copiers. Of the four copy machines tested, one was a
small desktop unit and the other three were typical of copy
machines used in larger offices. The results of the tests are
summarized below.
The desktop unit would be typical of the type used inter-
mittently, while the larger office machines may well operate at
near maximum capacity for hours at a time. All of these copi-
ers are 110 V, single-phase machines and are not representa-
tive of very large machines used for production work. The
larger machines could result in heat loads several times the
amounts listed above. For heat load estimates, it is recom-
mended that the continuous mode value above be used for
large office machines. The actual heat load from the desktop
unit is unlikely to exceed 100 watts.
Fax Machines. The three fax machines evaluated are all
typical of machines that serve a small to medium-sized office.
The power consumption of these machines is not large even in
continuous operation. A design heat load of 25 watts for these
machines is appropriate.
ACKNOWLEDGMENTS
The work reported in this paper was sponsored by
ASHRAE under research project RP-1055, “Measurement of
Heat Gain and Radiant/Convective Split from Equipment in
Buildings.” The authors gratefully acknowledge this support
and also thank the members of ASHRAE Technical Commit-
tee 4.1 (Load Calculation Data and Procedures) for their
Class
IdleMode
(W)
Continuous Mode
(W)
Minimal desktop 10 128
High-grade desktop 6 217
High-grade desktop 79 208
Small office (multiple users) 68 322
Computer center (many users) 124 558
Minimal desktop 130 W
High-grade desktop 215 W
Small office 320 W
Large office/computer center 550 W
Minimal desktop 65 W
High-grade desktop 110 W
Small office 320 W
Large office/computer center 550 W
Copier Idle Mode Continuous Mode
Desktop 20 W 400 W
Large office 300 W 1100 W
13. SE-99-1-4 (RP-1055) 13
support of this project. Special thanks go to the Project Moni-
toring Committee members, Chip Barnaby, Robert Hopper,
Curt Pedersen, and Christopher Wilkins (chair) for their
efforts in coordinating the research activities and continued
input throughout the course of the project.
REFERENCES
Alereza, T., and J.P. Breen III. 1984. Estimates of recom-
mended heat gains due to commercial appliances and
equipment. ASHRAE Transactions, 90 (2A): 25-58.
Hosni, M.H., B.W. Jones, J.M. Sipes, and Y. Xu. 1996. Test
method for measuring the heat gain and radiant/convec-
tive split from equipment in buildings. ASHRAE Final
Report for Research Project 822-RP.
Hosni, M.H., B.W. Jones, and H. Xu. 1999. Measurement of
heat gain and radiant/convective split from equipment in
buildings. ASHRAE Final Report for Research Project
1055-RP.
Hosni, M.H., B.W. Jones, J.M. Sipes, and Y. Xu. 1998. Total
heat gain and the split between radiant and convective
heat gain from office and laboratory equipment in build-
ings. ASHRAE Transactions 104 (1A): 356-365.
Jones, B.W., M.H. Hosni, and J. M. Sipes. 1998a. Measure-
ment of radiant heat gain from office equipment using a
scanning radiometer. ASHRAE Transactions 104 (1B):
1775-1783.
Jones, B.W., M.H. Hosni, and J. M. Sipes. 1998b. Measure-
ment of radiant heat gain from office equipment using
an infrared imagining technique. Proceedings of the
International Conference on Energy Research and
Development (ICERD), Kuwait City, Kuwait.
Wilkins, C.K., R. Kosonen, and T. Laine. 1991. An analysis
of office equipment load factors. ASHRAE Journal, 33
(9): 38-44.
Wilkins, C.K. and N. McGaffin. 1994. Measuring computer
equipment loads in office buildings ASHRAE Journal,
36 (8): 21-24.