IMPEL - Ministry of Sustainable Development - DGPR / SRT / BARPI-DREAL Upper Normandy No. 36628
File last updated: May 2011 1
Diagram of the accident scene
Explosion of a sulphuric acid tank
4 August 2009
Gonfreville-l'Orcher
(Seine-Maritime)
France
THE FACILITIES INVOLVED
The site :
This plant, rated upper-tier SEVESO, was using naphtha and butane as inputs to produce the most widespread
intermediate chemical compounds in the petrochemical industry (i.e. ethylene, propylene, butadiene and benzene), for
subsequent input into plastics manufacturing processes.
The unit involved :
The accident occurred on a 100-m3
capacity tank (built in 1974) containing sulphuric acid concentrated to 96%. Installed
outdoors on piles above a retention basin lined with epoxy resin and part of the unit for treating sodium-bearing water,
this tank was used to supply :
• the neutralisation reactor for sodium water stemming from the absorption of hydrogen sulphide on the vapour
cracking unit ;
• demineralisation chains of water for boilers and cooling towers with sulphuric acid when the dedicated tank
was undergoing maintenance.
Chemistry
Sulphuric acid
Hydrogen
Explosion
Tank
Maintenance
Equipment defect
Organisation / controls
Neutralisation
drum for
sodium-
bearing water
Location after
the accident
Initial location
Retention
basin
IMPEL - Ministry of Sustainable Development - DGPR / SRT / BARPI-DREAL Upper Normandy No. 36628
File last updated: May 2011 2
This tank had already been repaired in 1989 following an incident that caused its delamination, yet without breaking any
fastenings, due to a release of carbonic gas during the sulphuric acid neutralisation step (ARIA 23705). A support
bracket had been added in response to this initial accident, and the cleaning procedure was also revised.
THE ACCIDENT, ITS CHRONOLOGY, EFFECTS AND CONSEQUENCES
The accident :
On 17 July 2009, a leak was detected on the F2 tank containing 70 m³ of concentrated sulphuric acid (caused by a 1-
mm hole). This leak was plugged on 18 July using a temporary sealant system following approvals delivered by the
onsite inspection department.
On Friday 31 July, the tank was emptied to a point of inducing pump cavitation. The remaining product was drained into
the retention basin and the tank was rinsed with water over the weekend. A scaffolding was set up to accomplish the rest
of the works programme.
On Monday 3 August, the rinsing water collected in the retention basin was conveyed to the water treatment plant.
On Tuesday 4 August, the task of chemical consignment (platinum plating) of the inventory was undertaken in order to
isolate the storage capacity. A member of the plant staff, accompanied by 2 subcontractor employees, climbed onto the
tank to open the manhole. An explosion occurred around 9:15 am when the plant technician used a grinder to shear the
seized bolts.
The F2 tank, empty at the time of the accident, was suddenly lifted 2 or 3 m high and then fell back to the ground on top
of a nearby drum. As it was falling, the tank brought down the scaffolding that had been installed for upcoming
maintenance.
The Internal Emergency Plan was activated. The site operator notified the local Prefecture, town halls and the general
public.
Consequences of this accident :
Three individuals were hurt, with two of the injuries serious.
Two subcontracted employees and a site technician were on the scaffolding at the top of the tank at the time of the
explosion. One subcontractor was ejected towards a neighbouring structure 5 metres aboveground when the tank
suddenly thrust upward. He landed back on the ground away from the scaffolding. The other subcontractor was pinned
in the scaffolding. The third victim (plant technician) took a hard fall and was found on the ground unconscious. Ten
other people were seen by the psychological response team at a treatment office opened onsite.
No environmental impact was reported and no hazardous substances released.
The damages were limited to destruction of the tank and all connecting piping; the unit was shut down. The tank was
torn apart over half the shell/bottom junction circumference. Its anchorages were also ripped out.
Photos courtesy of DREAL: Damaged tank
Concrete base where the tank was positioned
IMPEL - Ministry of Sustainable Development - DGPR / SRT / BARPI-DREAL Upper Normandy No. 36628
File last updated: May 2011 3
The European scale of industrial accidents
By applying the rating rules applicable to the 18 parameters of the scale officially adopted in February 1994 by the
Member States' Competent Authority Committee for implementing the ‘SEVESO’ directive on handling hazardous
substances, and in light of information available, this accident can be characterised by the four following indices:
As the accident unfolded, an explosion occurred that revealed the presence of a Seveso-listed substance, namely
hydrogen. Since the quantity was estimated at 200 g, the index relative to hazardous substances released was set equal
to 1 (see parameter Q1). Three injuries were reported, two of them serious, assigning the index relative to human and
social consequences a "2" score (parameter H4). No environmental consequence was identified, resulting in a "0" rating
for the environmental consequences index. Lastly, the cost due to property damage and operating losses was estimated
at €6 M, yielding a score of "3" for the index relative to economic consequences (parameters €15 and €16).
The parameters composing these indices and their corresponding rating protocol are available from the following
Website: http://www.aria.developpement-durable.gouv.fr.
THE ORIGIN, CAUSES AND CIRCUMSTANCES SURROUNDING THIS ACCIDENT
Insufficient rinsing of the tank (just a single rinsing
cycle was performed) combined with the presence
of a low concentration of sulphuric acid caused an
acid attack of the metal, leading to the formation
and accumulation of hydrogen at the top of the tank
(dome-shaped tank roof). The explosion occurred
by means of igniting the flammable mix created with
air at the time of splitting the corroded bolts on the
dome manhole with a grinder.
The metallurgical assessment performed on this
tank indicated the presence of extensive internal
corrosion over the lower part of the structure. This
observation confirmed the sudden onset of
corrosion at the tank sidewall due to diluted acid,
thus generating a source of hydrogen production.
Photo courtesy of DREAL: The damaged tank
IMPEL - Ministry of Sustainable Development - DGPR / SRT / BARPI-DREAL Upper Normandy No. 36628
File last updated: May 2011 4
ACTIONS TAKEN
A lawsuit was filed against the site operator; a safety perimeter was set up around the installation on the day of the
accident.
On the day following the accident, an extraordinary session of the Committee for Hygiene, Safety and Working
Conditions (CHSCT) launched an investigation commission that held its first meeting on 13 August. An executive
summary of the accident analysis, accompanied by a set of guidelines (see below under "Lessons learnt"), was
presented at a second meeting of the full CHSCT body. This report stated the findings of a 200-g release of hydrogen
and the formation of a 4 to 6-m³ flammable gas cloud, in accordance with simulations run in-house when reproducing the
effects observed due to the presence of sulphuric acid at low concentrations inside the tank after failing to bleed the
tank.
The sodium water treatment facility remained idle for several weeks. Following its temporary storage (which entailed a
temporary authorisation, with renewal) within a bulk chemicals warehouse immediately adjacent to the site, the sodium
water was conveyed as waste to authorised treatment centres.
A temporary sulphuric acid storage unit was set up to allow restarting the sodium water treatment unit.
LESSONS LEARNT
Regarding risk identification and evaluation
Iron, like the primary common metals (zinc, aluminium), is attacked by diluted acids with hydrogen release, according to
the following reaction:
Fe + 2H
+
↔ Fe
2+
+ H2
Hydrogen is a highly flammable gas (4%-75% in air) at very low levels of ignition energy (0.02 mJ, vs. 0.29 mJ for
methane). The risk of a hydrogen explosion is present whenever an acid corrosion of metal has extended to a point of
being observable. In certain cases, the flow of fluid against a wall (through friction) or a shock can be of sufficient
magnitude to ignite.
A locally high hydrogen concentration (above 4% in air), e.g. in a dead air pocket or at the upper level of an enclosed
capacity, can engender an explosion risk when undertaking works on a tank. Such an event occurred in Saint Fons (69),
on 9 August, 1989 (ARIA 169), where preliminary flammability measurements conducted prior to the works phase had
not enabled detecting the presence of hydrogen at the top of the tank.
The feedback available included reports of several H2 explosions following an attack of diluted acid on steel tanks in a
number of facilities: ARIA 169, 22278, 31082 (detailed accident report).
Regarding feedback management, organisation and controls
A series of recommendations were issued before placing the installation back into operation:
− Design : The new tank would be fitted with a bleed valve that was both accessible and manoeuvrable.
− Tank availability (through steps of drainage and rinsing) was improved. The completed drainage step,
facilitated by tank design, was to be visually inspected by opening a manhole at a high point. This improved
accessibility will serve to minimise the quantity of residual acid to just drippings at the tank bottom and on its
sidewalls, in addition to enhancing not only acid neutralisation to return to a neutral pH but also tank rinsing.
Moreover, this operation avoids producing diluted acid and attacking the tank.
− The method for awarding hot-work permits was improved. Feedback mainly focused on building awareness
among onsite personnel of both the risks incurred and the atmospheric measurement methods to be
implemented (as regards positioning of the explosimeter probe).
− The tank was to be rebuilt using carbon steel; this solution was preferred over a composite so as to streamline
inspections.
− During the normal operations phase, a very minor hydrogen release into the tank remains a possibility.
Measures were taken to minimise hydrogen production and prevent its accumulation by means of :
• a vent positioned at a high point, with no internal tank structure causing evacuation of the hydrogen
eventually produced during operations and preparation;
• continuous flushing with dry air to allow hydrogen to evacuate and the tank to breathe; this feature serves
to prevent moist air from entering the tank (one possible cause of corrosion).
− The classified facilities inspectorate requested that the tank be made breakable at the shell-roof junction, so
that in case of an incident, the tank would remain in place and its contents not ejected.
IMPEL - Ministry of Sustainable Development - DGPR / SRT / BARPI-DREAL Upper Normandy No. 36628
File last updated: May 2011 5
Following this accident and several others during the same period within the chemical and petroleum industries as well
as in the transport of hazardous substances via pipeline, a meeting was organised in September 2009 between the
Secretary of State for Ecology and leading figures in these sectors to review the key challenges inherent in industrial
safety and environmental protection. Industry leaders forwarded a series of proposals intended to improve the safety of
their installations, with emphasis on strengthening controls dedicated to facility ageing and maintenance, while agreeing
to pay special attention to ecologically-sensitive zones with the aim of enhancing species protection or protecting
designated habitat. As part of the action plan intended to limit the risks tied to equipment ageing, launched on 13
January 2010, this resulted in the issuance of two administrative orders on 4-5 October 2010 relative to structural ageing
and technological risk, making it possible to incorporate ageing concerns into the site's safety management system
(SMS).

More Related Content

What's hot

hot works for construction of temporary facilities
hot works for construction of temporary facilitieshot works for construction of temporary facilities
hot works for construction of temporary facilitiesFãrük Ñäzmî
 
HSE Monthly Dashboard February 2023.pdf
HSE Monthly Dashboard February 2023.pdfHSE Monthly Dashboard February 2023.pdf
HSE Monthly Dashboard February 2023.pdfremyaani
 
Crane Safety Awareness by University of Texas Arlington
Crane Safety Awareness by University of Texas ArlingtonCrane Safety Awareness by University of Texas Arlington
Crane Safety Awareness by University of Texas ArlingtonAtlantic Training, LLC.
 
2 Fire Risk Assessment Template Risk Assessment Templates.docx
2 Fire Risk Assessment Template Risk Assessment Templates.docx2 Fire Risk Assessment Template Risk Assessment Templates.docx
2 Fire Risk Assessment Template Risk Assessment Templates.docxDwarika Bhushan Sharma
 
EHS induction Presentation slides
EHS induction Presentation slidesEHS induction Presentation slides
EHS induction Presentation slidesMaffino
 
Process Safety | Process Safety Management | PSM | Gaurav Singh Rajput
Process Safety | Process Safety Management | PSM | Gaurav Singh RajputProcess Safety | Process Safety Management | PSM | Gaurav Singh Rajput
Process Safety | Process Safety Management | PSM | Gaurav Singh RajputGaurav Singh Rajput
 
Forklift Study Guide
Forklift Study GuideForklift Study Guide
Forklift Study GuideM.T.H Group
 
Quarterly QHSE Report Presentation 17 Slides.pptx
Quarterly QHSE Report Presentation 17 Slides.pptxQuarterly QHSE Report Presentation 17 Slides.pptx
Quarterly QHSE Report Presentation 17 Slides.pptxNezarKakhi
 
HSE Management Plan
HSE Management PlanHSE Management Plan
HSE Management PlanPhilip Hà
 
Fire & safety training
Fire & safety trainingFire & safety training
Fire & safety trainingVIBHASH SINGH
 
Crane Safety Training Presentation
Crane Safety Training PresentationCrane Safety Training Presentation
Crane Safety Training PresentationFAIZ FAREED
 
Risk assessment for testing & commissioning of cranes
Risk assessment for  testing & commissioning of cranesRisk assessment for  testing & commissioning of cranes
Risk assessment for testing & commissioning of cranesAzmeel Contracting Company
 

What's hot (20)

hot works for construction of temporary facilities
hot works for construction of temporary facilitieshot works for construction of temporary facilities
hot works for construction of temporary facilities
 
SAFETY AUDIT.pptx
SAFETY AUDIT.pptxSAFETY AUDIT.pptx
SAFETY AUDIT.pptx
 
Fire extinguisher monthly checklist report
Fire extinguisher monthly checklist reportFire extinguisher monthly checklist report
Fire extinguisher monthly checklist report
 
HSE Monthly Dashboard February 2023.pdf
HSE Monthly Dashboard February 2023.pdfHSE Monthly Dashboard February 2023.pdf
HSE Monthly Dashboard February 2023.pdf
 
Flixborough disaster
Flixborough disasterFlixborough disaster
Flixborough disaster
 
Piper alpha
Piper alphaPiper alpha
Piper alpha
 
Crane Safety Awareness by University of Texas Arlington
Crane Safety Awareness by University of Texas ArlingtonCrane Safety Awareness by University of Texas Arlington
Crane Safety Awareness by University of Texas Arlington
 
2 Fire Risk Assessment Template Risk Assessment Templates.docx
2 Fire Risk Assessment Template Risk Assessment Templates.docx2 Fire Risk Assessment Template Risk Assessment Templates.docx
2 Fire Risk Assessment Template Risk Assessment Templates.docx
 
H2S - Hydrogen Sulfide
H2S - Hydrogen Sulfide H2S - Hydrogen Sulfide
H2S - Hydrogen Sulfide
 
EHS induction Presentation slides
EHS induction Presentation slidesEHS induction Presentation slides
EHS induction Presentation slides
 
Process Safety | Process Safety Management | PSM | Gaurav Singh Rajput
Process Safety | Process Safety Management | PSM | Gaurav Singh RajputProcess Safety | Process Safety Management | PSM | Gaurav Singh Rajput
Process Safety | Process Safety Management | PSM | Gaurav Singh Rajput
 
Forklift Study Guide
Forklift Study GuideForklift Study Guide
Forklift Study Guide
 
Quarterly QHSE Report Presentation 17 Slides.pptx
Quarterly QHSE Report Presentation 17 Slides.pptxQuarterly QHSE Report Presentation 17 Slides.pptx
Quarterly QHSE Report Presentation 17 Slides.pptx
 
HSE Management Plan
HSE Management PlanHSE Management Plan
HSE Management Plan
 
Fire & safety training
Fire & safety trainingFire & safety training
Fire & safety training
 
Compressd gas
Compressd gasCompressd gas
Compressd gas
 
Crane Safety Training Presentation
Crane Safety Training PresentationCrane Safety Training Presentation
Crane Safety Training Presentation
 
Storage Tank Safety
Storage Tank SafetyStorage Tank Safety
Storage Tank Safety
 
Hazardous Area Classification
Hazardous Area ClassificationHazardous Area Classification
Hazardous Area Classification
 
Risk assessment for testing & commissioning of cranes
Risk assessment for  testing & commissioning of cranesRisk assessment for  testing & commissioning of cranes
Risk assessment for testing & commissioning of cranes
 

Similar to Explosion of a sulphuric acid tank

Liquid chlorine incident
Liquid chlorine incidentLiquid chlorine incident
Liquid chlorine incidentUsama Khan
 
Pressure Vessel Accidents: Safety Approach
Pressure Vessel Accidents: Safety ApproachPressure Vessel Accidents: Safety Approach
Pressure Vessel Accidents: Safety ApproachIRJET Journal
 
IRJET-Pressure Vessel Accidents: Safety Approach
IRJET-Pressure Vessel Accidents: Safety ApproachIRJET-Pressure Vessel Accidents: Safety Approach
IRJET-Pressure Vessel Accidents: Safety ApproachIRJET Journal
 
Planning to Avoid Failure Storage Tanks
Planning to Avoid Failure Storage TanksPlanning to Avoid Failure Storage Tanks
Planning to Avoid Failure Storage TanksOrlando Costa
 
Safty case study
Safty case studySafty case study
Safty case studyYhingying
 
Process safety management and business impact analysis
Process safety management and business impact analysisProcess safety management and business impact analysis
Process safety management and business impact analysisEduardo Teixeira Neto
 
Flixborough uk disaster (description)
Flixborough uk disaster (description)Flixborough uk disaster (description)
Flixborough uk disaster (description)amanshaikh89
 
SPE171748 Surface Safety System for ZADCO (4).pdf
SPE171748 Surface Safety System for ZADCO (4).pdfSPE171748 Surface Safety System for ZADCO (4).pdf
SPE171748 Surface Safety System for ZADCO (4).pdfJalal Neshat
 
Unit VII Case StudyRead the incident scenario, and write a res.docx
Unit VII Case StudyRead the incident scenario, and write a res.docxUnit VII Case StudyRead the incident scenario, and write a res.docx
Unit VII Case StudyRead the incident scenario, and write a res.docxcargillfilberto
 
Exploitation of Source Rock Hydrocarbons through Propane Stimulation
Exploitation of Source Rock Hydrocarbons through Propane StimulationExploitation of Source Rock Hydrocarbons through Propane Stimulation
Exploitation of Source Rock Hydrocarbons through Propane StimulationecorpStim
 
Bhopal Gas Tragedy - 1984
Bhopal Gas Tragedy - 1984Bhopal Gas Tragedy - 1984
Bhopal Gas Tragedy - 1984Utkarsh Alset
 
Environmental Impact of Hydraulic Fracturing in Poland
Environmental Impact of Hydraulic Fracturing in PolandEnvironmental Impact of Hydraulic Fracturing in Poland
Environmental Impact of Hydraulic Fracturing in PolandMarcellus Drilling News
 

Similar to Explosion of a sulphuric acid tank (20)

Liquid chlorine incident
Liquid chlorine incidentLiquid chlorine incident
Liquid chlorine incident
 
Pressure Vessel Accidents: Safety Approach
Pressure Vessel Accidents: Safety ApproachPressure Vessel Accidents: Safety Approach
Pressure Vessel Accidents: Safety Approach
 
IRJET-Pressure Vessel Accidents: Safety Approach
IRJET-Pressure Vessel Accidents: Safety ApproachIRJET-Pressure Vessel Accidents: Safety Approach
IRJET-Pressure Vessel Accidents: Safety Approach
 
Chemical Disaster.pptx
Chemical Disaster.pptxChemical Disaster.pptx
Chemical Disaster.pptx
 
Planning to Avoid Failure Storage Tanks
Planning to Avoid Failure Storage TanksPlanning to Avoid Failure Storage Tanks
Planning to Avoid Failure Storage Tanks
 
Safty case study
Safty case studySafty case study
Safty case study
 
Fire accidents
Fire accidents Fire accidents
Fire accidents
 
British Petroleum oil spill
British Petroleum oil spillBritish Petroleum oil spill
British Petroleum oil spill
 
Process safety management and business impact analysis
Process safety management and business impact analysisProcess safety management and business impact analysis
Process safety management and business impact analysis
 
Flixborough uk disaster (description)
Flixborough uk disaster (description)Flixborough uk disaster (description)
Flixborough uk disaster (description)
 
Immobilisation and Storage of Nuclear Waste
Immobilisation and Storage of Nuclear WasteImmobilisation and Storage of Nuclear Waste
Immobilisation and Storage of Nuclear Waste
 
Immobilisation and Storage of Nuclear Waste
Immobilisation and Storage of Nuclear WasteImmobilisation and Storage of Nuclear Waste
Immobilisation and Storage of Nuclear Waste
 
SPE171748 Surface Safety System for ZADCO (4).pdf
SPE171748 Surface Safety System for ZADCO (4).pdfSPE171748 Surface Safety System for ZADCO (4).pdf
SPE171748 Surface Safety System for ZADCO (4).pdf
 
10 chemical accidents
10 chemical accidents10 chemical accidents
10 chemical accidents
 
Unit VII Case StudyRead the incident scenario, and write a res.docx
Unit VII Case StudyRead the incident scenario, and write a res.docxUnit VII Case StudyRead the incident scenario, and write a res.docx
Unit VII Case StudyRead the incident scenario, and write a res.docx
 
208_fullpaper_notes
208_fullpaper_notes208_fullpaper_notes
208_fullpaper_notes
 
Exploitation of Source Rock Hydrocarbons through Propane Stimulation
Exploitation of Source Rock Hydrocarbons through Propane StimulationExploitation of Source Rock Hydrocarbons through Propane Stimulation
Exploitation of Source Rock Hydrocarbons through Propane Stimulation
 
moc0828011.pdf
moc0828011.pdfmoc0828011.pdf
moc0828011.pdf
 
Bhopal Gas Tragedy - 1984
Bhopal Gas Tragedy - 1984Bhopal Gas Tragedy - 1984
Bhopal Gas Tragedy - 1984
 
Environmental Impact of Hydraulic Fracturing in Poland
Environmental Impact of Hydraulic Fracturing in PolandEnvironmental Impact of Hydraulic Fracturing in Poland
Environmental Impact of Hydraulic Fracturing in Poland
 

More from Usama Khan

The humble check_valve
The humble check_valveThe humble check_valve
The humble check_valveUsama Khan
 
British women chemists and world war 1
British women chemists and world war 1British women chemists and world war 1
British women chemists and world war 1Usama Khan
 
Oilivia gasolino upstream_en
Oilivia gasolino upstream_enOilivia gasolino upstream_en
Oilivia gasolino upstream_enUsama Khan
 
Results phe works 2.0 2
Results phe works 2.0 2Results phe works 2.0 2
Results phe works 2.0 2Usama Khan
 
A non-Iterative way for preliminary designing Plate & Frame Exchanger
A non-Iterative way for preliminary designing Plate & Frame ExchangerA non-Iterative way for preliminary designing Plate & Frame Exchanger
A non-Iterative way for preliminary designing Plate & Frame ExchangerUsama Khan
 
Storage container tank mathematics
Storage container tank mathematicsStorage container tank mathematics
Storage container tank mathematicsUsama Khan
 
Asahi AKC electrolyzer magazine
Asahi AKC electrolyzer magazineAsahi AKC electrolyzer magazine
Asahi AKC electrolyzer magazineUsama Khan
 
Understanding units of gas concentration
Understanding units of gas concentrationUnderstanding units of gas concentration
Understanding units of gas concentrationUsama Khan
 
The psychrometric chart theory and application
The psychrometric chart theory and applicationThe psychrometric chart theory and application
The psychrometric chart theory and applicationUsama Khan
 
Wet Binary Hydrogen & Chlorine
Wet Binary Hydrogen & ChlorineWet Binary Hydrogen & Chlorine
Wet Binary Hydrogen & ChlorineUsama Khan
 
VLE VAPOR LIQUID EQUILIBRIUM - Introduction
VLE VAPOR LIQUID EQUILIBRIUM -  Introduction VLE VAPOR LIQUID EQUILIBRIUM -  Introduction
VLE VAPOR LIQUID EQUILIBRIUM - Introduction Usama Khan
 
Kf units Electrolytic Cell Volt Regression
Kf units Electrolytic Cell Volt RegressionKf units Electrolytic Cell Volt Regression
Kf units Electrolytic Cell Volt RegressionUsama Khan
 
Vocabulary For Engineering Resumes
Vocabulary For Engineering ResumesVocabulary For Engineering Resumes
Vocabulary For Engineering ResumesUsama Khan
 
Compressor Polytropic Efficiency Calculation
Compressor Polytropic Efficiency CalculationCompressor Polytropic Efficiency Calculation
Compressor Polytropic Efficiency CalculationUsama Khan
 
details_calculated
details_calculateddetails_calculated
details_calculatedUsama Khan
 

More from Usama Khan (16)

The humble check_valve
The humble check_valveThe humble check_valve
The humble check_valve
 
British women chemists and world war 1
British women chemists and world war 1British women chemists and world war 1
British women chemists and world war 1
 
Oilivia gasolino upstream_en
Oilivia gasolino upstream_enOilivia gasolino upstream_en
Oilivia gasolino upstream_en
 
Results phe works 2.0 2
Results phe works 2.0 2Results phe works 2.0 2
Results phe works 2.0 2
 
A non-Iterative way for preliminary designing Plate & Frame Exchanger
A non-Iterative way for preliminary designing Plate & Frame ExchangerA non-Iterative way for preliminary designing Plate & Frame Exchanger
A non-Iterative way for preliminary designing Plate & Frame Exchanger
 
Storage container tank mathematics
Storage container tank mathematicsStorage container tank mathematics
Storage container tank mathematics
 
Asahi AKC electrolyzer magazine
Asahi AKC electrolyzer magazineAsahi AKC electrolyzer magazine
Asahi AKC electrolyzer magazine
 
Understanding units of gas concentration
Understanding units of gas concentrationUnderstanding units of gas concentration
Understanding units of gas concentration
 
The psychrometric chart theory and application
The psychrometric chart theory and applicationThe psychrometric chart theory and application
The psychrometric chart theory and application
 
Wet Binary Hydrogen & Chlorine
Wet Binary Hydrogen & ChlorineWet Binary Hydrogen & Chlorine
Wet Binary Hydrogen & Chlorine
 
VLE VAPOR LIQUID EQUILIBRIUM - Introduction
VLE VAPOR LIQUID EQUILIBRIUM -  Introduction VLE VAPOR LIQUID EQUILIBRIUM -  Introduction
VLE VAPOR LIQUID EQUILIBRIUM - Introduction
 
Kf units Electrolytic Cell Volt Regression
Kf units Electrolytic Cell Volt RegressionKf units Electrolytic Cell Volt Regression
Kf units Electrolytic Cell Volt Regression
 
Vocabulary For Engineering Resumes
Vocabulary For Engineering ResumesVocabulary For Engineering Resumes
Vocabulary For Engineering Resumes
 
Compressor Polytropic Efficiency Calculation
Compressor Polytropic Efficiency CalculationCompressor Polytropic Efficiency Calculation
Compressor Polytropic Efficiency Calculation
 
Folders
FoldersFolders
Folders
 
details_calculated
details_calculateddetails_calculated
details_calculated
 

Recently uploaded

Electronically Controlled suspensions system .pdf
Electronically Controlled suspensions system .pdfElectronically Controlled suspensions system .pdf
Electronically Controlled suspensions system .pdfme23b1001
 
Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...
Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...
Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...srsj9000
 
Software and Systems Engineering Standards: Verification and Validation of Sy...
Software and Systems Engineering Standards: Verification and Validation of Sy...Software and Systems Engineering Standards: Verification and Validation of Sy...
Software and Systems Engineering Standards: Verification and Validation of Sy...VICTOR MAESTRE RAMIREZ
 
Internship report on mechanical engineering
Internship report on mechanical engineeringInternship report on mechanical engineering
Internship report on mechanical engineeringmalavadedarshan25
 
Work Experience-Dalton Park.pptxfvvvvvvv
Work Experience-Dalton Park.pptxfvvvvvvvWork Experience-Dalton Park.pptxfvvvvvvv
Work Experience-Dalton Park.pptxfvvvvvvvLewisJB
 
UNIT III ANALOG ELECTRONICS (BASIC ELECTRONICS)
UNIT III ANALOG ELECTRONICS (BASIC ELECTRONICS)UNIT III ANALOG ELECTRONICS (BASIC ELECTRONICS)
UNIT III ANALOG ELECTRONICS (BASIC ELECTRONICS)Dr SOUNDIRARAJ N
 
An experimental study in using natural admixture as an alternative for chemic...
An experimental study in using natural admixture as an alternative for chemic...An experimental study in using natural admixture as an alternative for chemic...
An experimental study in using natural admixture as an alternative for chemic...Chandu841456
 
main PPT.pptx of girls hostel security using rfid
main PPT.pptx of girls hostel security using rfidmain PPT.pptx of girls hostel security using rfid
main PPT.pptx of girls hostel security using rfidNikhilNagaraju
 
INFLUENCE OF NANOSILICA ON THE PROPERTIES OF CONCRETE
INFLUENCE OF NANOSILICA ON THE PROPERTIES OF CONCRETEINFLUENCE OF NANOSILICA ON THE PROPERTIES OF CONCRETE
INFLUENCE OF NANOSILICA ON THE PROPERTIES OF CONCRETEroselinkalist12
 
Churning of Butter, Factors affecting .
Churning of Butter, Factors affecting  .Churning of Butter, Factors affecting  .
Churning of Butter, Factors affecting .Satyam Kumar
 
Biology for Computer Engineers Course Handout.pptx
Biology for Computer Engineers Course Handout.pptxBiology for Computer Engineers Course Handout.pptx
Biology for Computer Engineers Course Handout.pptxDeepakSakkari2
 
Gurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort service
Gurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort serviceGurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort service
Gurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort servicejennyeacort
 
CCS355 Neural Network & Deep Learning UNIT III notes and Question bank .pdf
CCS355 Neural Network & Deep Learning UNIT III notes and Question bank .pdfCCS355 Neural Network & Deep Learning UNIT III notes and Question bank .pdf
CCS355 Neural Network & Deep Learning UNIT III notes and Question bank .pdfAsst.prof M.Gokilavani
 
Call Girls Delhi {Jodhpur} 9711199012 high profile service
Call Girls Delhi {Jodhpur} 9711199012 high profile serviceCall Girls Delhi {Jodhpur} 9711199012 high profile service
Call Girls Delhi {Jodhpur} 9711199012 high profile servicerehmti665
 
Oxy acetylene welding presentation note.
Oxy acetylene welding presentation note.Oxy acetylene welding presentation note.
Oxy acetylene welding presentation note.eptoze12
 
pipeline in computer architecture design
pipeline in computer architecture  designpipeline in computer architecture  design
pipeline in computer architecture designssuser87fa0c1
 
CCS355 Neural Networks & Deep Learning Unit 1 PDF notes with Question bank .pdf
CCS355 Neural Networks & Deep Learning Unit 1 PDF notes with Question bank .pdfCCS355 Neural Networks & Deep Learning Unit 1 PDF notes with Question bank .pdf
CCS355 Neural Networks & Deep Learning Unit 1 PDF notes with Question bank .pdfAsst.prof M.Gokilavani
 

Recently uploaded (20)

Electronically Controlled suspensions system .pdf
Electronically Controlled suspensions system .pdfElectronically Controlled suspensions system .pdf
Electronically Controlled suspensions system .pdf
 
Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...
Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...
Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...
 
Software and Systems Engineering Standards: Verification and Validation of Sy...
Software and Systems Engineering Standards: Verification and Validation of Sy...Software and Systems Engineering Standards: Verification and Validation of Sy...
Software and Systems Engineering Standards: Verification and Validation of Sy...
 
Internship report on mechanical engineering
Internship report on mechanical engineeringInternship report on mechanical engineering
Internship report on mechanical engineering
 
young call girls in Rajiv Chowk🔝 9953056974 🔝 Delhi escort Service
young call girls in Rajiv Chowk🔝 9953056974 🔝 Delhi escort Serviceyoung call girls in Rajiv Chowk🔝 9953056974 🔝 Delhi escort Service
young call girls in Rajiv Chowk🔝 9953056974 🔝 Delhi escort Service
 
Work Experience-Dalton Park.pptxfvvvvvvv
Work Experience-Dalton Park.pptxfvvvvvvvWork Experience-Dalton Park.pptxfvvvvvvv
Work Experience-Dalton Park.pptxfvvvvvvv
 
UNIT III ANALOG ELECTRONICS (BASIC ELECTRONICS)
UNIT III ANALOG ELECTRONICS (BASIC ELECTRONICS)UNIT III ANALOG ELECTRONICS (BASIC ELECTRONICS)
UNIT III ANALOG ELECTRONICS (BASIC ELECTRONICS)
 
An experimental study in using natural admixture as an alternative for chemic...
An experimental study in using natural admixture as an alternative for chemic...An experimental study in using natural admixture as an alternative for chemic...
An experimental study in using natural admixture as an alternative for chemic...
 
main PPT.pptx of girls hostel security using rfid
main PPT.pptx of girls hostel security using rfidmain PPT.pptx of girls hostel security using rfid
main PPT.pptx of girls hostel security using rfid
 
Call Us -/9953056974- Call Girls In Vikaspuri-/- Delhi NCR
Call Us -/9953056974- Call Girls In Vikaspuri-/- Delhi NCRCall Us -/9953056974- Call Girls In Vikaspuri-/- Delhi NCR
Call Us -/9953056974- Call Girls In Vikaspuri-/- Delhi NCR
 
INFLUENCE OF NANOSILICA ON THE PROPERTIES OF CONCRETE
INFLUENCE OF NANOSILICA ON THE PROPERTIES OF CONCRETEINFLUENCE OF NANOSILICA ON THE PROPERTIES OF CONCRETE
INFLUENCE OF NANOSILICA ON THE PROPERTIES OF CONCRETE
 
Churning of Butter, Factors affecting .
Churning of Butter, Factors affecting  .Churning of Butter, Factors affecting  .
Churning of Butter, Factors affecting .
 
Biology for Computer Engineers Course Handout.pptx
Biology for Computer Engineers Course Handout.pptxBiology for Computer Engineers Course Handout.pptx
Biology for Computer Engineers Course Handout.pptx
 
Gurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort service
Gurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort serviceGurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort service
Gurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort service
 
CCS355 Neural Network & Deep Learning UNIT III notes and Question bank .pdf
CCS355 Neural Network & Deep Learning UNIT III notes and Question bank .pdfCCS355 Neural Network & Deep Learning UNIT III notes and Question bank .pdf
CCS355 Neural Network & Deep Learning UNIT III notes and Question bank .pdf
 
Call Girls Delhi {Jodhpur} 9711199012 high profile service
Call Girls Delhi {Jodhpur} 9711199012 high profile serviceCall Girls Delhi {Jodhpur} 9711199012 high profile service
Call Girls Delhi {Jodhpur} 9711199012 high profile service
 
Exploring_Network_Security_with_JA3_by_Rakesh Seal.pptx
Exploring_Network_Security_with_JA3_by_Rakesh Seal.pptxExploring_Network_Security_with_JA3_by_Rakesh Seal.pptx
Exploring_Network_Security_with_JA3_by_Rakesh Seal.pptx
 
Oxy acetylene welding presentation note.
Oxy acetylene welding presentation note.Oxy acetylene welding presentation note.
Oxy acetylene welding presentation note.
 
pipeline in computer architecture design
pipeline in computer architecture  designpipeline in computer architecture  design
pipeline in computer architecture design
 
CCS355 Neural Networks & Deep Learning Unit 1 PDF notes with Question bank .pdf
CCS355 Neural Networks & Deep Learning Unit 1 PDF notes with Question bank .pdfCCS355 Neural Networks & Deep Learning Unit 1 PDF notes with Question bank .pdf
CCS355 Neural Networks & Deep Learning Unit 1 PDF notes with Question bank .pdf
 

Explosion of a sulphuric acid tank

  • 1. IMPEL - Ministry of Sustainable Development - DGPR / SRT / BARPI-DREAL Upper Normandy No. 36628 File last updated: May 2011 1 Diagram of the accident scene Explosion of a sulphuric acid tank 4 August 2009 Gonfreville-l'Orcher (Seine-Maritime) France THE FACILITIES INVOLVED The site : This plant, rated upper-tier SEVESO, was using naphtha and butane as inputs to produce the most widespread intermediate chemical compounds in the petrochemical industry (i.e. ethylene, propylene, butadiene and benzene), for subsequent input into plastics manufacturing processes. The unit involved : The accident occurred on a 100-m3 capacity tank (built in 1974) containing sulphuric acid concentrated to 96%. Installed outdoors on piles above a retention basin lined with epoxy resin and part of the unit for treating sodium-bearing water, this tank was used to supply : • the neutralisation reactor for sodium water stemming from the absorption of hydrogen sulphide on the vapour cracking unit ; • demineralisation chains of water for boilers and cooling towers with sulphuric acid when the dedicated tank was undergoing maintenance. Chemistry Sulphuric acid Hydrogen Explosion Tank Maintenance Equipment defect Organisation / controls Neutralisation drum for sodium- bearing water Location after the accident Initial location Retention basin
  • 2. IMPEL - Ministry of Sustainable Development - DGPR / SRT / BARPI-DREAL Upper Normandy No. 36628 File last updated: May 2011 2 This tank had already been repaired in 1989 following an incident that caused its delamination, yet without breaking any fastenings, due to a release of carbonic gas during the sulphuric acid neutralisation step (ARIA 23705). A support bracket had been added in response to this initial accident, and the cleaning procedure was also revised. THE ACCIDENT, ITS CHRONOLOGY, EFFECTS AND CONSEQUENCES The accident : On 17 July 2009, a leak was detected on the F2 tank containing 70 m³ of concentrated sulphuric acid (caused by a 1- mm hole). This leak was plugged on 18 July using a temporary sealant system following approvals delivered by the onsite inspection department. On Friday 31 July, the tank was emptied to a point of inducing pump cavitation. The remaining product was drained into the retention basin and the tank was rinsed with water over the weekend. A scaffolding was set up to accomplish the rest of the works programme. On Monday 3 August, the rinsing water collected in the retention basin was conveyed to the water treatment plant. On Tuesday 4 August, the task of chemical consignment (platinum plating) of the inventory was undertaken in order to isolate the storage capacity. A member of the plant staff, accompanied by 2 subcontractor employees, climbed onto the tank to open the manhole. An explosion occurred around 9:15 am when the plant technician used a grinder to shear the seized bolts. The F2 tank, empty at the time of the accident, was suddenly lifted 2 or 3 m high and then fell back to the ground on top of a nearby drum. As it was falling, the tank brought down the scaffolding that had been installed for upcoming maintenance. The Internal Emergency Plan was activated. The site operator notified the local Prefecture, town halls and the general public. Consequences of this accident : Three individuals were hurt, with two of the injuries serious. Two subcontracted employees and a site technician were on the scaffolding at the top of the tank at the time of the explosion. One subcontractor was ejected towards a neighbouring structure 5 metres aboveground when the tank suddenly thrust upward. He landed back on the ground away from the scaffolding. The other subcontractor was pinned in the scaffolding. The third victim (plant technician) took a hard fall and was found on the ground unconscious. Ten other people were seen by the psychological response team at a treatment office opened onsite. No environmental impact was reported and no hazardous substances released. The damages were limited to destruction of the tank and all connecting piping; the unit was shut down. The tank was torn apart over half the shell/bottom junction circumference. Its anchorages were also ripped out. Photos courtesy of DREAL: Damaged tank Concrete base where the tank was positioned
  • 3. IMPEL - Ministry of Sustainable Development - DGPR / SRT / BARPI-DREAL Upper Normandy No. 36628 File last updated: May 2011 3 The European scale of industrial accidents By applying the rating rules applicable to the 18 parameters of the scale officially adopted in February 1994 by the Member States' Competent Authority Committee for implementing the ‘SEVESO’ directive on handling hazardous substances, and in light of information available, this accident can be characterised by the four following indices: As the accident unfolded, an explosion occurred that revealed the presence of a Seveso-listed substance, namely hydrogen. Since the quantity was estimated at 200 g, the index relative to hazardous substances released was set equal to 1 (see parameter Q1). Three injuries were reported, two of them serious, assigning the index relative to human and social consequences a "2" score (parameter H4). No environmental consequence was identified, resulting in a "0" rating for the environmental consequences index. Lastly, the cost due to property damage and operating losses was estimated at €6 M, yielding a score of "3" for the index relative to economic consequences (parameters €15 and €16). The parameters composing these indices and their corresponding rating protocol are available from the following Website: http://www.aria.developpement-durable.gouv.fr. THE ORIGIN, CAUSES AND CIRCUMSTANCES SURROUNDING THIS ACCIDENT Insufficient rinsing of the tank (just a single rinsing cycle was performed) combined with the presence of a low concentration of sulphuric acid caused an acid attack of the metal, leading to the formation and accumulation of hydrogen at the top of the tank (dome-shaped tank roof). The explosion occurred by means of igniting the flammable mix created with air at the time of splitting the corroded bolts on the dome manhole with a grinder. The metallurgical assessment performed on this tank indicated the presence of extensive internal corrosion over the lower part of the structure. This observation confirmed the sudden onset of corrosion at the tank sidewall due to diluted acid, thus generating a source of hydrogen production. Photo courtesy of DREAL: The damaged tank
  • 4. IMPEL - Ministry of Sustainable Development - DGPR / SRT / BARPI-DREAL Upper Normandy No. 36628 File last updated: May 2011 4 ACTIONS TAKEN A lawsuit was filed against the site operator; a safety perimeter was set up around the installation on the day of the accident. On the day following the accident, an extraordinary session of the Committee for Hygiene, Safety and Working Conditions (CHSCT) launched an investigation commission that held its first meeting on 13 August. An executive summary of the accident analysis, accompanied by a set of guidelines (see below under "Lessons learnt"), was presented at a second meeting of the full CHSCT body. This report stated the findings of a 200-g release of hydrogen and the formation of a 4 to 6-m³ flammable gas cloud, in accordance with simulations run in-house when reproducing the effects observed due to the presence of sulphuric acid at low concentrations inside the tank after failing to bleed the tank. The sodium water treatment facility remained idle for several weeks. Following its temporary storage (which entailed a temporary authorisation, with renewal) within a bulk chemicals warehouse immediately adjacent to the site, the sodium water was conveyed as waste to authorised treatment centres. A temporary sulphuric acid storage unit was set up to allow restarting the sodium water treatment unit. LESSONS LEARNT Regarding risk identification and evaluation Iron, like the primary common metals (zinc, aluminium), is attacked by diluted acids with hydrogen release, according to the following reaction: Fe + 2H + ↔ Fe 2+ + H2 Hydrogen is a highly flammable gas (4%-75% in air) at very low levels of ignition energy (0.02 mJ, vs. 0.29 mJ for methane). The risk of a hydrogen explosion is present whenever an acid corrosion of metal has extended to a point of being observable. In certain cases, the flow of fluid against a wall (through friction) or a shock can be of sufficient magnitude to ignite. A locally high hydrogen concentration (above 4% in air), e.g. in a dead air pocket or at the upper level of an enclosed capacity, can engender an explosion risk when undertaking works on a tank. Such an event occurred in Saint Fons (69), on 9 August, 1989 (ARIA 169), where preliminary flammability measurements conducted prior to the works phase had not enabled detecting the presence of hydrogen at the top of the tank. The feedback available included reports of several H2 explosions following an attack of diluted acid on steel tanks in a number of facilities: ARIA 169, 22278, 31082 (detailed accident report). Regarding feedback management, organisation and controls A series of recommendations were issued before placing the installation back into operation: − Design : The new tank would be fitted with a bleed valve that was both accessible and manoeuvrable. − Tank availability (through steps of drainage and rinsing) was improved. The completed drainage step, facilitated by tank design, was to be visually inspected by opening a manhole at a high point. This improved accessibility will serve to minimise the quantity of residual acid to just drippings at the tank bottom and on its sidewalls, in addition to enhancing not only acid neutralisation to return to a neutral pH but also tank rinsing. Moreover, this operation avoids producing diluted acid and attacking the tank. − The method for awarding hot-work permits was improved. Feedback mainly focused on building awareness among onsite personnel of both the risks incurred and the atmospheric measurement methods to be implemented (as regards positioning of the explosimeter probe). − The tank was to be rebuilt using carbon steel; this solution was preferred over a composite so as to streamline inspections. − During the normal operations phase, a very minor hydrogen release into the tank remains a possibility. Measures were taken to minimise hydrogen production and prevent its accumulation by means of : • a vent positioned at a high point, with no internal tank structure causing evacuation of the hydrogen eventually produced during operations and preparation; • continuous flushing with dry air to allow hydrogen to evacuate and the tank to breathe; this feature serves to prevent moist air from entering the tank (one possible cause of corrosion). − The classified facilities inspectorate requested that the tank be made breakable at the shell-roof junction, so that in case of an incident, the tank would remain in place and its contents not ejected.
  • 5. IMPEL - Ministry of Sustainable Development - DGPR / SRT / BARPI-DREAL Upper Normandy No. 36628 File last updated: May 2011 5 Following this accident and several others during the same period within the chemical and petroleum industries as well as in the transport of hazardous substances via pipeline, a meeting was organised in September 2009 between the Secretary of State for Ecology and leading figures in these sectors to review the key challenges inherent in industrial safety and environmental protection. Industry leaders forwarded a series of proposals intended to improve the safety of their installations, with emphasis on strengthening controls dedicated to facility ageing and maintenance, while agreeing to pay special attention to ecologically-sensitive zones with the aim of enhancing species protection or protecting designated habitat. As part of the action plan intended to limit the risks tied to equipment ageing, launched on 13 January 2010, this resulted in the issuance of two administrative orders on 4-5 October 2010 relative to structural ageing and technological risk, making it possible to incorporate ageing concerns into the site's safety management system (SMS).