This review article summarizes control and applications of modular multilevel converters (MMC). It describes the main switching module topologies used in MMC, including the standard half-bridge configuration and full-bridge topology that allows active fault current reduction. It also discusses methods for balancing capacitor voltages and the voltage and current modulation techniques used for MMC control. Finally, it outlines the main MMC applications in high voltage direct current transmission and offshore wind farms.
Fuzzy Logic Controller Based on Voltage Source Converter-HVDC with MMC TopologyIJMTST Journal
This paper presents Modular Multi Level Converters (MMC) are used for high voltage high power DC to AC conversion. The MMCs with increased number of levels offer close to sine wave operation with reduced THD on the AC side. This is a new type of voltage source converter (VSC) topology. The use of this converter in a high-voltage direct current (HVDC) system is called by a MMC-HVDC system. The MMC-HVDC has the advantage in terms of scalability, performance, and efficiency over two-and three-level VSC-HVDC. The proposed HVDC system offers the operational flexibility of VSC based systems in terms of active and reactive power control, in addition to improved ac fault ride-through capability and the unique feature of current-limiting capability during dc side faults. The proposed VSC-HVDC system, in this project assesses its dynamic performance during steady-state and network alternations, including its response to AC and DC side faults. In this project using a fuzzy controller and the proposed topology is implemented in MATLAB/SIMULINK environment and the simulation results are observed.
IRJET-Analysis and Rectification of Fault in Power System by Multilevel Modul...IRJET Journal
This document discusses modular multilevel converters (MMC) and their use in high voltage direct current (HVDC) power transmission systems. Key points:
- MMC topology offers advantages over traditional voltage source converters for HVDC, including higher voltage capability, modularity, improved reliability, and reduced filters/complexity.
- MMC works by connecting sub-modules containing switching elements in series. Controlling the number of inserted/bypassed sub-modules produces a stepped output voltage.
- Simulation results show the MMC can successfully control output power and maintain stable operation even during faults, by decoupling energy and current control loops through saturation limits.
1. HVDC transmission allows for more efficient long distance power transmission compared to AC transmission by reducing losses. It also allows for interconnection between different frequency AC systems.
2. The key components of an HVDC system are converter stations at each end containing thyristor valves to convert AC to DC or vice versa, transmission lines to carry DC power, and control systems.
3. There are three main conversion technologies: natural commutated converters using thyristors, capacitor commutated converters using thyristors and capacitors, and voltage source converters using devices like GTOs or IGBTs which allow for faster switching.
Implementation of DC voltage controllers on enhancing the stability of multi-...IJECEIAES
Because of the increasing penetration of intermittent green energy resources like offshore wind farms, solar photovoltaic, the multi-terminal DC grid using VSC technology is considered a promising solution for interconnecting these future energies. To improve the stability of the multi-terminal direct current (MTDC) network, DC voltage control strategies based on voltage margin and voltage droop technique have been developed and investigated in this article. These two control strategies are implemented in the proposed model, a ±400 kV meshed multi-terminal MTDC network based on VSC technology with four terminals during the outage converter. The simulation results include the comparison and analysis of both techniques under the outage converter equipped with constant DC voltage control, then the outage converter equipped with constant active power control. The simulation results confirm that the DC voltage droop technique has a better dynamic performance of power sharing and DC voltage regulation.
IRJET- Comparative Study of Carrier-Based Pwm Techniques for Control of Doubl...IRJET Journal
This document compares carrier-based PWM techniques for controlling a double-star modular multilevel converter (M2C) using half-bridge cells. It analyzes the total harmonic distortion of the output voltage and current for different PWM techniques. It also examines the influence of arm inductances on current and voltage THD and the allowable range of the modulation index for different techniques. The goal is to determine the most effective technique for capacitor balancing and lowest output distortion. Simulations in Matlab/Simulink will be used to compare the performance of different carrier-based PWM control methods for the M2C converter.
Coautor en Revista JCR, International Transactions on Electrical Energy Systems. Título; Analysis of the behavior of MVDC system in a distribution grid compared to a UPFC system
An Improved Repetitive Control for Circulating Current Restraining in MMC-MTDCTELKOMNIKA JOURNAL
The modular multilevel converter (MMC) is widely used in many important application fields such
as high voltage DC transmission system. And the multi-terminal architecture of it attracts many attentions.
However, the circulating current of MMC is an inherent problem which is mainly caused by the voltage
mismatch between arms and DC bus. In this paper, an advanced repetitive control method is proposed.
This method is based on the even-harmonic characteristic of the circulating current and the potential
feature of repetitive control that it has an internal integration part. The pole diagram of the closed loop
transform function of the proposed control system proves the stability of the proposed method. And
according to the simulation results of a three-terminal MMC-MTDC model in PSCAD/EMTDC, the
improved repetitive control presents better circulation repression ability and superior anti-interference
capability by comparing with traditional PI control method. Additionally, the simulation results also indicate
that the proposed repetitive controller can restrain the fluctuation of SM voltage more effectively than PI
control.
DG FED MULTILEVEL INVERTER BASED D-STATCOM FOR VARIOUS LOADING CONDITIONSIJCI JOURNAL
During the past few decades, power industries have proved that the adverse impacts on the PQ can be
mitigated or avoided by conventional means, and that technique using fast controlled force commutated
power electronics (PE) are even more effective. PQ compensators can be categorized into two main types.
One is shunt connected compensation device that effectively eliminates harmonics. The other is the series
connected device, which has an edge over the shunt type for correcting the distorted system side voltages
and voltage sags caused by power transmission system faults. The STATCOM used in distribution systems
is called DSTACOM (Distribution-STACOM) and its configuration is the same, but with small
modifications. Recent advances in the power-handling capabilities of static switch devices such as 3.3kV,
4.5kV, and 6.5kV Insulated Gate Bipolar Transistors (IGBTs) with voltage rating commercially available,
have made the use of the voltage source inverters (VSI) feasible for high-power applications. High power
and high-voltage conversion systems have become very important issues for the power electronic industry
handling the large ac drive and electrical power applications at both the transmission and distribution
levels. For these reasons, new families of multilevel inverters have emerged as the solution for working
with higher voltage levels. Multilevel inverters (MLI) include an array of power semiconductors and
capacitor voltage sources, the output of which generate voltages with stepped waveforms. These converter
topologies can generate high-quality voltage waveforms with power semiconductor switches operating at a
frequency near the fundamental. It significantly reduces the harmonics problem with reduced voltage stress
across the switch. This research work is mainly focusing on application of multilevel DSTATCOM for
power quality improvement in distribution system with integration of RES. Matlab/Simulink based model is
developed and simulation results are presented.
Fuzzy Logic Controller Based on Voltage Source Converter-HVDC with MMC TopologyIJMTST Journal
This paper presents Modular Multi Level Converters (MMC) are used for high voltage high power DC to AC conversion. The MMCs with increased number of levels offer close to sine wave operation with reduced THD on the AC side. This is a new type of voltage source converter (VSC) topology. The use of this converter in a high-voltage direct current (HVDC) system is called by a MMC-HVDC system. The MMC-HVDC has the advantage in terms of scalability, performance, and efficiency over two-and three-level VSC-HVDC. The proposed HVDC system offers the operational flexibility of VSC based systems in terms of active and reactive power control, in addition to improved ac fault ride-through capability and the unique feature of current-limiting capability during dc side faults. The proposed VSC-HVDC system, in this project assesses its dynamic performance during steady-state and network alternations, including its response to AC and DC side faults. In this project using a fuzzy controller and the proposed topology is implemented in MATLAB/SIMULINK environment and the simulation results are observed.
IRJET-Analysis and Rectification of Fault in Power System by Multilevel Modul...IRJET Journal
This document discusses modular multilevel converters (MMC) and their use in high voltage direct current (HVDC) power transmission systems. Key points:
- MMC topology offers advantages over traditional voltage source converters for HVDC, including higher voltage capability, modularity, improved reliability, and reduced filters/complexity.
- MMC works by connecting sub-modules containing switching elements in series. Controlling the number of inserted/bypassed sub-modules produces a stepped output voltage.
- Simulation results show the MMC can successfully control output power and maintain stable operation even during faults, by decoupling energy and current control loops through saturation limits.
1. HVDC transmission allows for more efficient long distance power transmission compared to AC transmission by reducing losses. It also allows for interconnection between different frequency AC systems.
2. The key components of an HVDC system are converter stations at each end containing thyristor valves to convert AC to DC or vice versa, transmission lines to carry DC power, and control systems.
3. There are three main conversion technologies: natural commutated converters using thyristors, capacitor commutated converters using thyristors and capacitors, and voltage source converters using devices like GTOs or IGBTs which allow for faster switching.
Implementation of DC voltage controllers on enhancing the stability of multi-...IJECEIAES
Because of the increasing penetration of intermittent green energy resources like offshore wind farms, solar photovoltaic, the multi-terminal DC grid using VSC technology is considered a promising solution for interconnecting these future energies. To improve the stability of the multi-terminal direct current (MTDC) network, DC voltage control strategies based on voltage margin and voltage droop technique have been developed and investigated in this article. These two control strategies are implemented in the proposed model, a ±400 kV meshed multi-terminal MTDC network based on VSC technology with four terminals during the outage converter. The simulation results include the comparison and analysis of both techniques under the outage converter equipped with constant DC voltage control, then the outage converter equipped with constant active power control. The simulation results confirm that the DC voltage droop technique has a better dynamic performance of power sharing and DC voltage regulation.
IRJET- Comparative Study of Carrier-Based Pwm Techniques for Control of Doubl...IRJET Journal
This document compares carrier-based PWM techniques for controlling a double-star modular multilevel converter (M2C) using half-bridge cells. It analyzes the total harmonic distortion of the output voltage and current for different PWM techniques. It also examines the influence of arm inductances on current and voltage THD and the allowable range of the modulation index for different techniques. The goal is to determine the most effective technique for capacitor balancing and lowest output distortion. Simulations in Matlab/Simulink will be used to compare the performance of different carrier-based PWM control methods for the M2C converter.
Coautor en Revista JCR, International Transactions on Electrical Energy Systems. Título; Analysis of the behavior of MVDC system in a distribution grid compared to a UPFC system
An Improved Repetitive Control for Circulating Current Restraining in MMC-MTDCTELKOMNIKA JOURNAL
The modular multilevel converter (MMC) is widely used in many important application fields such
as high voltage DC transmission system. And the multi-terminal architecture of it attracts many attentions.
However, the circulating current of MMC is an inherent problem which is mainly caused by the voltage
mismatch between arms and DC bus. In this paper, an advanced repetitive control method is proposed.
This method is based on the even-harmonic characteristic of the circulating current and the potential
feature of repetitive control that it has an internal integration part. The pole diagram of the closed loop
transform function of the proposed control system proves the stability of the proposed method. And
according to the simulation results of a three-terminal MMC-MTDC model in PSCAD/EMTDC, the
improved repetitive control presents better circulation repression ability and superior anti-interference
capability by comparing with traditional PI control method. Additionally, the simulation results also indicate
that the proposed repetitive controller can restrain the fluctuation of SM voltage more effectively than PI
control.
DG FED MULTILEVEL INVERTER BASED D-STATCOM FOR VARIOUS LOADING CONDITIONSIJCI JOURNAL
During the past few decades, power industries have proved that the adverse impacts on the PQ can be
mitigated or avoided by conventional means, and that technique using fast controlled force commutated
power electronics (PE) are even more effective. PQ compensators can be categorized into two main types.
One is shunt connected compensation device that effectively eliminates harmonics. The other is the series
connected device, which has an edge over the shunt type for correcting the distorted system side voltages
and voltage sags caused by power transmission system faults. The STATCOM used in distribution systems
is called DSTACOM (Distribution-STACOM) and its configuration is the same, but with small
modifications. Recent advances in the power-handling capabilities of static switch devices such as 3.3kV,
4.5kV, and 6.5kV Insulated Gate Bipolar Transistors (IGBTs) with voltage rating commercially available,
have made the use of the voltage source inverters (VSI) feasible for high-power applications. High power
and high-voltage conversion systems have become very important issues for the power electronic industry
handling the large ac drive and electrical power applications at both the transmission and distribution
levels. For these reasons, new families of multilevel inverters have emerged as the solution for working
with higher voltage levels. Multilevel inverters (MLI) include an array of power semiconductors and
capacitor voltage sources, the output of which generate voltages with stepped waveforms. These converter
topologies can generate high-quality voltage waveforms with power semiconductor switches operating at a
frequency near the fundamental. It significantly reduces the harmonics problem with reduced voltage stress
across the switch. This research work is mainly focusing on application of multilevel DSTATCOM for
power quality improvement in distribution system with integration of RES. Matlab/Simulink based model is
developed and simulation results are presented.
This document compares the performance of a star-connected cascaded STATCOM using five different PWM techniques: Sinusoidal Phase Shifted Carrier (SPSC) PWM, Sinusoidal Phase Disposition (SPD) PWM, Third Harmonic Injected Phase Shifted Carrier (THIPSC) PWM, Space Vector Phase Shifted Carrier (SVPSC) PWM, and Space Vector Phase Disposition (SVPD) PWM. The STATCOM performance is simulated in MATLAB for different load changes. Parameters like DC link voltage balancing, total harmonic distortion of STATCOM currents and voltages, and reactive power supplied by the STATCOM are compared for each control strategy.
This document summarizes a research paper that proposes a solid-state transformer (S2T) using a single phase matrix converter (SPMC). The S2T aims to address limitations of conventional transformers such as size, weight, environmental issues. The proposed S2T design uses two SPMCs - one operating at 1 kHz to generate high frequency current on the primary side, and the other at 50 Hz to produce low frequency voltage on the secondary side. A switching algorithm is presented to address commutation problems when using inductive loads. The S2T design and switching control are simulated in MATLAB/Simulink. Results show the S2T design can help minimize size and losses while achieving optimal efficiency compared to conventional approaches
Abstract- This paper presents a major revision of the Universal Four Leg ‘DC Grid Laboratory Experimental Setup’. This revision includes the reduction of current loops, the increase of efficiency in the power stage, the expansion of measurement possibilities and the re-specification of the input/output range.
To deal with an ever present complication in the world of measurements, simple fuse holders are converted into dedicated probe measurement connectors. These connectors reduce large ground loops to a minimum.
Key features include a clear board layout and silkscreen, a tremendous reduction of semiconductor losses resulting in a heatsink-less power stage and easy, reliable probe and power connections. Provisions are made for a Single Board Computer (SBC) to read and control the Universal Four Leg V4. The SBC can also be used to communicate with external devices to allow for remote control of the Universal Four Leg and the presentation of measurements performed.
The Universal Four Leg is a power management device with a wide range of applications in both higher educational laboratory courses, as well as a dedicated grid manager in low voltage DC-grids.
Average Phase-Leg Technique on Coupling Impedance Impact Modular Inverter Par...IJMTST Journal
This document discusses control methods for parallel-connected modular multilevel converters (parallel-MMCs). It proposes controlling the individual submodule voltages and average phase voltages to balance capacitor voltages across the MMCs. It also proposes using resonant controllers to mitigate circulating currents within and between the parallel-MMCs. The document discusses fault-tolerant control schemes to address open and short circuit switch faults without redundant hardware. Simulations and experimental results validate the control strategy's ability to balance voltages and attenuate circulating currents under normal and fault conditions.
Pwm control strategies for multilevel inverters based on carrier redistributi...IAEME Publication
This document summarizes a research paper that proposes three PWM control strategies for multilevel inverters based on carrier redistribution techniques. The strategies are Alternate Phase Opposition Disposition (APOD), Phase Opposition Disposition (POD), and Phase Disposition (PD). Simulation results show the performance of a seven-level diode-clamped inverter using the three carrier-based PWM strategies with sinusoidal PWM, third harmonic injection PWM, and modified space vector PWM modulation signals. The total harmonic distortion is evaluated and compared for each modulation scheme.
IRJET- Protection of VSC Controlled HVDCPlus System using PWM TechniqueIRJET Journal
This document provides an overview of HVDCPlus transmission systems which use voltage source converter (VSC) technology. Some key points:
- VSC technology provides advantages over conventional HVDC using thyristor technology, allowing operation in weak grid conditions and independent control of active and reactive power.
- The main components of an HVDCPlus system are the voltage source converters, transformers, high voltage DC circuit (including cables and storage capacitors), and connection to the AC system.
- Voltage source converters generate AC voltage from a DC voltage source using pulse width modulation techniques for sinusoidal current output.
- HVDCPlus systems provide benefits such as connecting remote loads, integrating offshore wind, and multi-
Svpwm based 3 level statcom for reactive power management under line-lineIAEME Publication
This document summarizes a research paper that analyzes the performance of a 3-level STATCOM for reactive power management under a line-line fault in a transmission line. The paper tests a line-line fault in an IEEE 14 bus system incorporating nonlinear loads. A 2-level and 3-level STATCOM using SVPWM control are placed at bus 14 to regulate the voltage. Simulation results show the effectiveness of the SVPWM control strategy in managing reactive power and voltage stability during steady state and transient operation for both the 2-level and 3-level STATCOM configurations.
This document summarizes a research paper on a bidirectional DC-DC converter with a Z-source network. The proposed converter aims to increase the output voltage level and regulation range compared to traditional bidirectional converters. It uses a fully bridge symmetrical circuit configuration with voltage and current sources. Simulation results using MATLAB show the converter can reduce current stress and improve efficiency for applications in hybrid electric vehicles and renewable energy systems. Key aspects analyzed include the converter's operating principles, voltage regulation model, and simulation circuit and results demonstrating operation in forward and reverse modes.
This paper presents the analysis study between multilevel inverters that are often classified into multilevel voltage source and multilevel current source inverters. For multilevel voltage source inverter (MVSI), the specific topology studied for this work is the Cascaded H-Bridge MVSI. Whereas, the multilevel current source inverter (MCSI) is based on Paralleled Inductor Configuration MCSI. For this study, the analysis between these converters are done with respect to the number of components, the advantages and disadvantages of each converters during performing inverter operation. In term of output voltage and current quality, the percentage of the Total Harmonic Distortion (THD) are measured and compared for both topologies. MATLAB/Simulink software has been used in this research to design and simulate in order to study the performances of both inverters.
IRJET- Improving Power Quality by using MC-UPQCIRJET Journal
This document discusses improving power quality by using a Multiconverter Unified Power Quality Conditioner (MC-UPQC). The MC-UPQC consists of one shunt voltage-source converter (VSC) and two or more series VSCs. It can be applied to adjacent feeders to simultaneously compensate for supply voltage imperfections and load current imperfections on the main feeder, as well as fully compensate supply voltage imperfections on other feeders. The converters are connected back-to-back on the DC side and share a common DC link capacitor, allowing power transfer between feeders. This configuration can compensate for sags/swells and interruptions in both feeders without battery storage. Simulation results will illustrate the performance
The slide is basically to show the general knowledge about the System Works for this Electrified Double Track Project between Ipoh & Padang Besar, the Equipments & its Functions.I have presented this slide to my college in Commercial Department and I want to share this little of my contribution to all linked in members.Hope we can get some benefit from this slide.Thank You
This document summarizes different configurations for industrial electrical networks. It describes:
1) Standard voltage ratings defined by IEC 38 for low, medium, and high voltage.
2) The general structure of private distribution networks which typically includes components like HV consumer substations, HV/MV transformers, MV switchboards, MV and LV networks and loads.
3) Common arrangements for HV consumer substations including single power supply, dual power supply, and dual fed double bus systems.
IRJET - Analysis of Carrier based PWM Controlled Modular Multilevel Conve...IRJET Journal
This document discusses a carrier-based PWM control technique for a modular multilevel converter (MMC) used in a variable frequency drive (VFD) without an intermediate DC bus. Key points:
1. An MMC-based VFD without a DC bus is proposed to improve efficiency over traditional VFD configurations with an intermediate DC link.
2. A phase-shift carrier PWM (PSCPWM) modulation technique is used to control the switching of converter cells.
3. A capacitor voltage balancing algorithm sorts capacitor voltages and activates submodules accordingly to maintain balanced voltages based on arm current direction.
This document discusses low power high performance baud rate generators using MTCMOS voltage interface circuits. It compares feedback based and multi-VTH based voltage level converters that are used in baud rate generators to interface between circuits operating at different voltage levels. The multi-VTH level converters are found to offer significant power savings compared to feedback based converters. A baud rate generator is designed and simulated using different level converters in 90nm CMOS technology. The multi-VTH level converter LC5 provides the lowest power when used in the baud rate generator.
Performance improvement of parallel active power filters using droop control ...Ghazal Falahi
In this paper, a new method based on droop control scheme is proposed for controlling parallel operation of active filters. The harmonic components of the load current are extracted by an enhanced phase-locked loop (EPLL). In the parallel group, each filter operates as a conductance and the harmonic workload is shared among them. A droop relationship between the conductance and non-fundamental apparent power controls the operation of each unit. The non-fundamental apparent power has been calculated based on IEEE Std 1459. Principles of operation are explained in this paper and simulation results which are presented approve the effectiveness of this method. The results indicate a significant reduction in Total Harmonic Distortion (THD) in a rectifier application.
IRJET- Designing and Simulation of Multilevel STATCOM on Cascaded TopologyIRJET Journal
This document summarizes the design and simulation of a cascaded multilevel STATCOM topology. It first discusses the need for reactive power compensation and control of power systems. It then describes the cascaded H-bridge multilevel inverter topology used for the STATCOM, noting its advantages over other multilevel inverter types. The document outlines the methodology, discussing control of the STATCOM using pulse width modulation techniques. It also reviews prior implementations of STATCOMs and issues with earlier converter configurations.
The slide is basically to show the general knowledge about the System Works for this Electrified Double Track Project between Ipoh & Padang Besar, the Equipments & its Functions.I have presented this slide to my college in Commercial Department and I want to share this little of my contribution to all linked in members.Hope we can get some benefit from this slide.Thank You
The document discusses the future of high voltage direct current (HVDC) power transmission grids in Europe. HVDC transmission can transmit electricity over long distances with lower costs than alternating current systems. It enables offshore wind farms to connect to land grids and asynchronous power systems to exchange power. The document envisions a pan-European HVDC grid that would allow large-scale renewable energy integration, cross-border electricity trading, and more efficient system operation. However, technological challenges around HVDC equipment and coordination between countries and power companies still need to be addressed for this vision to be fully realized.
Modular Multilevel Converters Part-I: A Review on Topologies, Modulation, Mod...IJPEDS-IAES
This article is devoted to the Multi-level inverters review and in particular to the form and function of modular multilevel inverters (MMI), with their different topologies, modulation, modeling and control schemes Detailed analysis with their functions of MMI has been made in comprehensive manner with existing literature available till date. All existing methods are compared in detail with proposal for the best methods available. The article has made strategic conclusions on MMI to make the system more robust in operation with less complexity in design and control.
Control of HVDC Transmission System Based on MMC with Three-Level Flying Capa...Anand Parakkat Parambil
The document contains a list of figures for chapters 3-5 of a thesis on controlling an HVDC transmission system based on modular multilevel converters (MMC) with three-level flying capacitor submodules. Chapter 3 describes the system and modeling of the MMC, including the topology and operation of the converter. Chapter 4 discusses the control and modulation of the MMC-HVDC system, including AC and DC current control loops for the two MMC stations and arm balancing control. Chapter 5 presents simulation results evaluating the system.
A Review on Performance Analysis of Matrix Converter Fed AC Motor DriveIAES-IJPEDS
This paper presents a review on the analysis of characteristics that determines
the performance of the Matrix Converter (MC) fed AC motor drive. Review
is made based on the analysis of the different characteristics achieved in the
literature. Different characteristic parameters considered in this paper are
total harmonic distortion, common mode voltage, voltage transfer ratio and
efficiency. Comparison and analysis of these characteristic parameters is
done based on various semi conductor switches, topology, and control and modulation techniques.
This document compares the performance of a star-connected cascaded STATCOM using five different PWM techniques: Sinusoidal Phase Shifted Carrier (SPSC) PWM, Sinusoidal Phase Disposition (SPD) PWM, Third Harmonic Injected Phase Shifted Carrier (THIPSC) PWM, Space Vector Phase Shifted Carrier (SVPSC) PWM, and Space Vector Phase Disposition (SVPD) PWM. The STATCOM performance is simulated in MATLAB for different load changes. Parameters like DC link voltage balancing, total harmonic distortion of STATCOM currents and voltages, and reactive power supplied by the STATCOM are compared for each control strategy.
This document summarizes a research paper that proposes a solid-state transformer (S2T) using a single phase matrix converter (SPMC). The S2T aims to address limitations of conventional transformers such as size, weight, environmental issues. The proposed S2T design uses two SPMCs - one operating at 1 kHz to generate high frequency current on the primary side, and the other at 50 Hz to produce low frequency voltage on the secondary side. A switching algorithm is presented to address commutation problems when using inductive loads. The S2T design and switching control are simulated in MATLAB/Simulink. Results show the S2T design can help minimize size and losses while achieving optimal efficiency compared to conventional approaches
Abstract- This paper presents a major revision of the Universal Four Leg ‘DC Grid Laboratory Experimental Setup’. This revision includes the reduction of current loops, the increase of efficiency in the power stage, the expansion of measurement possibilities and the re-specification of the input/output range.
To deal with an ever present complication in the world of measurements, simple fuse holders are converted into dedicated probe measurement connectors. These connectors reduce large ground loops to a minimum.
Key features include a clear board layout and silkscreen, a tremendous reduction of semiconductor losses resulting in a heatsink-less power stage and easy, reliable probe and power connections. Provisions are made for a Single Board Computer (SBC) to read and control the Universal Four Leg V4. The SBC can also be used to communicate with external devices to allow for remote control of the Universal Four Leg and the presentation of measurements performed.
The Universal Four Leg is a power management device with a wide range of applications in both higher educational laboratory courses, as well as a dedicated grid manager in low voltage DC-grids.
Average Phase-Leg Technique on Coupling Impedance Impact Modular Inverter Par...IJMTST Journal
This document discusses control methods for parallel-connected modular multilevel converters (parallel-MMCs). It proposes controlling the individual submodule voltages and average phase voltages to balance capacitor voltages across the MMCs. It also proposes using resonant controllers to mitigate circulating currents within and between the parallel-MMCs. The document discusses fault-tolerant control schemes to address open and short circuit switch faults without redundant hardware. Simulations and experimental results validate the control strategy's ability to balance voltages and attenuate circulating currents under normal and fault conditions.
Pwm control strategies for multilevel inverters based on carrier redistributi...IAEME Publication
This document summarizes a research paper that proposes three PWM control strategies for multilevel inverters based on carrier redistribution techniques. The strategies are Alternate Phase Opposition Disposition (APOD), Phase Opposition Disposition (POD), and Phase Disposition (PD). Simulation results show the performance of a seven-level diode-clamped inverter using the three carrier-based PWM strategies with sinusoidal PWM, third harmonic injection PWM, and modified space vector PWM modulation signals. The total harmonic distortion is evaluated and compared for each modulation scheme.
IRJET- Protection of VSC Controlled HVDCPlus System using PWM TechniqueIRJET Journal
This document provides an overview of HVDCPlus transmission systems which use voltage source converter (VSC) technology. Some key points:
- VSC technology provides advantages over conventional HVDC using thyristor technology, allowing operation in weak grid conditions and independent control of active and reactive power.
- The main components of an HVDCPlus system are the voltage source converters, transformers, high voltage DC circuit (including cables and storage capacitors), and connection to the AC system.
- Voltage source converters generate AC voltage from a DC voltage source using pulse width modulation techniques for sinusoidal current output.
- HVDCPlus systems provide benefits such as connecting remote loads, integrating offshore wind, and multi-
Svpwm based 3 level statcom for reactive power management under line-lineIAEME Publication
This document summarizes a research paper that analyzes the performance of a 3-level STATCOM for reactive power management under a line-line fault in a transmission line. The paper tests a line-line fault in an IEEE 14 bus system incorporating nonlinear loads. A 2-level and 3-level STATCOM using SVPWM control are placed at bus 14 to regulate the voltage. Simulation results show the effectiveness of the SVPWM control strategy in managing reactive power and voltage stability during steady state and transient operation for both the 2-level and 3-level STATCOM configurations.
This document summarizes a research paper on a bidirectional DC-DC converter with a Z-source network. The proposed converter aims to increase the output voltage level and regulation range compared to traditional bidirectional converters. It uses a fully bridge symmetrical circuit configuration with voltage and current sources. Simulation results using MATLAB show the converter can reduce current stress and improve efficiency for applications in hybrid electric vehicles and renewable energy systems. Key aspects analyzed include the converter's operating principles, voltage regulation model, and simulation circuit and results demonstrating operation in forward and reverse modes.
This paper presents the analysis study between multilevel inverters that are often classified into multilevel voltage source and multilevel current source inverters. For multilevel voltage source inverter (MVSI), the specific topology studied for this work is the Cascaded H-Bridge MVSI. Whereas, the multilevel current source inverter (MCSI) is based on Paralleled Inductor Configuration MCSI. For this study, the analysis between these converters are done with respect to the number of components, the advantages and disadvantages of each converters during performing inverter operation. In term of output voltage and current quality, the percentage of the Total Harmonic Distortion (THD) are measured and compared for both topologies. MATLAB/Simulink software has been used in this research to design and simulate in order to study the performances of both inverters.
IRJET- Improving Power Quality by using MC-UPQCIRJET Journal
This document discusses improving power quality by using a Multiconverter Unified Power Quality Conditioner (MC-UPQC). The MC-UPQC consists of one shunt voltage-source converter (VSC) and two or more series VSCs. It can be applied to adjacent feeders to simultaneously compensate for supply voltage imperfections and load current imperfections on the main feeder, as well as fully compensate supply voltage imperfections on other feeders. The converters are connected back-to-back on the DC side and share a common DC link capacitor, allowing power transfer between feeders. This configuration can compensate for sags/swells and interruptions in both feeders without battery storage. Simulation results will illustrate the performance
The slide is basically to show the general knowledge about the System Works for this Electrified Double Track Project between Ipoh & Padang Besar, the Equipments & its Functions.I have presented this slide to my college in Commercial Department and I want to share this little of my contribution to all linked in members.Hope we can get some benefit from this slide.Thank You
This document summarizes different configurations for industrial electrical networks. It describes:
1) Standard voltage ratings defined by IEC 38 for low, medium, and high voltage.
2) The general structure of private distribution networks which typically includes components like HV consumer substations, HV/MV transformers, MV switchboards, MV and LV networks and loads.
3) Common arrangements for HV consumer substations including single power supply, dual power supply, and dual fed double bus systems.
IRJET - Analysis of Carrier based PWM Controlled Modular Multilevel Conve...IRJET Journal
This document discusses a carrier-based PWM control technique for a modular multilevel converter (MMC) used in a variable frequency drive (VFD) without an intermediate DC bus. Key points:
1. An MMC-based VFD without a DC bus is proposed to improve efficiency over traditional VFD configurations with an intermediate DC link.
2. A phase-shift carrier PWM (PSCPWM) modulation technique is used to control the switching of converter cells.
3. A capacitor voltage balancing algorithm sorts capacitor voltages and activates submodules accordingly to maintain balanced voltages based on arm current direction.
This document discusses low power high performance baud rate generators using MTCMOS voltage interface circuits. It compares feedback based and multi-VTH based voltage level converters that are used in baud rate generators to interface between circuits operating at different voltage levels. The multi-VTH level converters are found to offer significant power savings compared to feedback based converters. A baud rate generator is designed and simulated using different level converters in 90nm CMOS technology. The multi-VTH level converter LC5 provides the lowest power when used in the baud rate generator.
Performance improvement of parallel active power filters using droop control ...Ghazal Falahi
In this paper, a new method based on droop control scheme is proposed for controlling parallel operation of active filters. The harmonic components of the load current are extracted by an enhanced phase-locked loop (EPLL). In the parallel group, each filter operates as a conductance and the harmonic workload is shared among them. A droop relationship between the conductance and non-fundamental apparent power controls the operation of each unit. The non-fundamental apparent power has been calculated based on IEEE Std 1459. Principles of operation are explained in this paper and simulation results which are presented approve the effectiveness of this method. The results indicate a significant reduction in Total Harmonic Distortion (THD) in a rectifier application.
IRJET- Designing and Simulation of Multilevel STATCOM on Cascaded TopologyIRJET Journal
This document summarizes the design and simulation of a cascaded multilevel STATCOM topology. It first discusses the need for reactive power compensation and control of power systems. It then describes the cascaded H-bridge multilevel inverter topology used for the STATCOM, noting its advantages over other multilevel inverter types. The document outlines the methodology, discussing control of the STATCOM using pulse width modulation techniques. It also reviews prior implementations of STATCOMs and issues with earlier converter configurations.
The slide is basically to show the general knowledge about the System Works for this Electrified Double Track Project between Ipoh & Padang Besar, the Equipments & its Functions.I have presented this slide to my college in Commercial Department and I want to share this little of my contribution to all linked in members.Hope we can get some benefit from this slide.Thank You
The document discusses the future of high voltage direct current (HVDC) power transmission grids in Europe. HVDC transmission can transmit electricity over long distances with lower costs than alternating current systems. It enables offshore wind farms to connect to land grids and asynchronous power systems to exchange power. The document envisions a pan-European HVDC grid that would allow large-scale renewable energy integration, cross-border electricity trading, and more efficient system operation. However, technological challenges around HVDC equipment and coordination between countries and power companies still need to be addressed for this vision to be fully realized.
Modular Multilevel Converters Part-I: A Review on Topologies, Modulation, Mod...IJPEDS-IAES
This article is devoted to the Multi-level inverters review and in particular to the form and function of modular multilevel inverters (MMI), with their different topologies, modulation, modeling and control schemes Detailed analysis with their functions of MMI has been made in comprehensive manner with existing literature available till date. All existing methods are compared in detail with proposal for the best methods available. The article has made strategic conclusions on MMI to make the system more robust in operation with less complexity in design and control.
Control of HVDC Transmission System Based on MMC with Three-Level Flying Capa...Anand Parakkat Parambil
The document contains a list of figures for chapters 3-5 of a thesis on controlling an HVDC transmission system based on modular multilevel converters (MMC) with three-level flying capacitor submodules. Chapter 3 describes the system and modeling of the MMC, including the topology and operation of the converter. Chapter 4 discusses the control and modulation of the MMC-HVDC system, including AC and DC current control loops for the two MMC stations and arm balancing control. Chapter 5 presents simulation results evaluating the system.
A Review on Performance Analysis of Matrix Converter Fed AC Motor DriveIAES-IJPEDS
This paper presents a review on the analysis of characteristics that determines
the performance of the Matrix Converter (MC) fed AC motor drive. Review
is made based on the analysis of the different characteristics achieved in the
literature. Different characteristic parameters considered in this paper are
total harmonic distortion, common mode voltage, voltage transfer ratio and
efficiency. Comparison and analysis of these characteristic parameters is
done based on various semi conductor switches, topology, and control and modulation techniques.
IRJET- Modular Multilevel Converter for Power Quality ImprovementIRJET Journal
The document discusses a modular multilevel converter (MMC) for improving power quality. The MMC uses identical individually controllable submodules to produce a stepped voltage waveform that is close to sinusoidal, resulting in low harmonic distortion. It has advantages over traditional converters like modular structure, transformerless operation, scalability, use of standard components, and excellent output waveform quality. The document presents the configuration and operation of the MMC, describes a proposed MMC model, and provides simulation results showing the MMC produces output voltages and currents with low total harmonic distortion of 3.66%.
This document summarizes a research paper on a high efficiency three phase nine level diode clamped multilevel inverter. The paper proposes a nine level diode clamped multilevel inverter (DCMLI) topology for medium voltage applications. It describes the working of the DCMLI, which uses nine levels of voltage from the DC supply to produce a nine step output voltage waveform with lower total harmonic distortion compared to other lower level inverters. Simulation results show that the nine level inverter produces a line voltage waveform with 7.84% THD, lower than the 10.47% THD of a seven level inverter. The paper concludes that increasing the number of levels in the DCMLI reduces the total harmonic distortion
This document presents a study on a nine-level diode-clamped multilevel inverter. A diode-clamped multilevel inverter uses multiple DC voltage levels from separate capacitors to generate stepped output voltages. The proposed nine-level inverter configuration is capable of producing nine distinct output voltage levels. Simulation results show that the total harmonic distortion of the nine-level inverter is 7.84%, lower than the 10.47% THD of a seven-level inverter. Pulse width modulation techniques are used to generate switching signals to control the inverter. The study concludes that increasing the number of voltage levels in a diode-clamped multilevel inverter reduces total harmonic distortion.
Comparative performance of modular with cascaded H-bridge three level invertersIJECEIAES
This document compares the modular multilevel inverter (MMC) and cascaded H-bridge (CHB) multilevel inverters for induction motor drive applications. It discusses the configuration, operation, advantages, and disadvantages of each inverter. Simulation results using MATLAB/Simulink are provided for the output voltage waveform, total harmonic distortion, and current drawn by the inverters under different load torques on the induction motor. The MMC and CHB inverters are simulated at three voltage levels to evaluate their performance for driving the induction motor.
The power electronics device which converts DC power to AC power at required output voltage and frequency level is known as inverter. Multilevel inverter is to synthesize a near sinusoidal voltage from several levels of dc voltages. In order to maintain the different voltage levels at appropriate intervals, the conduction time intervals of MOSFETS have been maintained by controlling the pulse width of gating pulses. In this paper single phase to three phase power conversion using PWM technique. The simulation is carried out in MATLAB/Simulink environment which demonstrate the feasibility of proposed scheme.
Control of a Modular Multilevel DC/DC Converter for Regenerative ApplicationsIRJET Journal
This document describes and compares different converter topologies for interfacing supercapacitors to a DC bus, including for regenerative applications. It finds that a modular multilevel DC/DC converter (MMC) has advantages over cascaded buck and boost converters in terms of reduced weight and volume of inductance. When using phase shifting modulation, the MMC can balance supercapacitor voltages through control of the output current. Simulation results show the MMC achieves lower current ripples and faster response times compared to the other topologies. Control methods are presented to regulate the output current and balance the supercapacitor voltages in the MMC.
The conventional transformer in power infrastructure should be capable of meeting the demand for the load. The conventional transformer is structured and designed to handle high power. Also, the overload capacity of conventional transformers depends on the highest temperature and short-term overload. This paper represents the construction and working of the solid-state transformer which consists of AC to DC and DC to AC conversion which has low overload capability as compared to conventional transformers. Solid-state transformer finding applications in Solar and wind power generation electric vehicle battery management systems because of high-frequency operation, which is not possible in case of conventional transformers also smart transformer, provides flexible control of electric power distribution.
Application of single phase matrix converter topology to an uninterruptible p...eSAT Publishing House
IJRET : International Journal of Research in Engineering and Technology is an international peer reviewed, online journal published by eSAT Publishing House for the enhancement of research in various disciplines of Engineering and Technology. The aim and scope of the journal is to provide an academic medium and an important reference for the advancement and dissemination of research results that support high-level learning, teaching and research in the fields of Engineering and Technology. We bring together Scientists, Academician, Field Engineers, Scholars and Students of related fields of Engineering and Technology
Voltage Balancing in Solar Based Dc Micro-Grid SystemIRJET Journal
This document summarizes a research paper on voltage balancing in solar-based DC micro-grid systems. It discusses how a dual buck half-bridge voltage balancer can convert a two-wire DC distribution system into a three-wire system with a neutral line. This helps address the "shoot-through" problem in bridge converters and allows supplying loads that require a neutral line. The voltage balancer topology and control strategy are presented, which respectively drive the two bridge legs to balance the voltages across unbalanced loads. Simulation results validate the analysis of current relationships and load transients under continuous and discontinuous conduction modes.
Digital Current Mode Controller for Buck ConverterIJMREMJournal
Power electronics applications are widely used in different fields of engineering like computer,
Telecommunication, electrical power and Mechanical), one of the most useful power electronics converters is
DC-DC buck converter. Owing to its numerous applications, its performance needs to be improved through a
suitable controller. In this Paper, A digital current mode controller is proposed and implemented for Buck
converter. Proposed current mode control technique is simulated in MATLAB/SIMULINK and results are
validated through hardware implementation. Both simulation and experimental analysis show effectiveness of
the proposed controller.
Comparison of an Isolated bidirectional Dc-Dc converter with and without a Fl...IOSR Journals
This document compares an isolated bidirectional DC-DC converter with and without a flyback snubber through simulation and hardware implementation. It begins with an introduction to isolated bidirectional converters and the problem of voltage spikes caused by transformer leakage inductance. It then describes the operation and components of the converter both with and without a flyback snubber. Simulation results show that the flyback snubber reduces voltage spikes by 78-80% by clamping the voltage. Hardware results for boost mode operation with a flyback snubber are also presented and agree with simulation.
Circulating current suppression and natural voltage balancing using phase-shi...IJECEIAES
The challenge of achieving a balanced capacitor voltage is one of the factors affecting the efficient operation of modular multilevel converters (MMC). This paper investigates this challenge through a proposed method that utilizes a high carrier frequency phase-shifted pulse width modulation (PS-PWM) scheme. This method aims to achieve natural balancing without the need for any additional control mechanisms. Moreover, the number of output voltage levels is affected by the phase shift between the carriers of the upper and lower arms. When there is no phase shift, N+1 discrete levels are achieved, but when there is a phase shift, the number of discrete levels increases to 2N+1. The proportional-resonant (PR) controller and moving average filter (MAF) are employed to decrease the capacitor voltage ripples by suppressing the fourth and second harmonics in the circulating currents. The MMC inverter structure is modeled and simulated in the PLECS and MATLAB/Simulink environments to evaluate the impact of this control scheme on the converter’s performance.
High Voltage Direct Current Transmission Systems 2Mark MaterialsSanthosh Kumar
The document provides information about HVDC transmission, including:
1. It lists two merits of AC transmission (power can be generated at high voltages, maintenance of AC substations is easy and cheaper) and two merits of DC transmission (it requires only two conductors, there is no skin effect).
2. It discusses types of DC link including monopolar, bipolar, and homopolar links.
3. It lists types of power devices used for HVDC transmission including thyristor, IGBT, GTO, LTT, and MCT.
4. It provides advantages and disadvantages of HVDC transmission such as full control over power, reduced transmission lines, and inability to change voltage
Topology and Modulation for a New Multilevel Diode-Clamped Matrix ConverterProjectsatbangalore
This document proposes a new three-level diode-clamped matrix converter topology and modulation scheme for high power applications. The topology combines a cascaded rectifier and three-level diode-clamped inverter. This overcomes voltage limits of power switches for high voltages. It provides bidirectional power flow, sinusoidal input/output currents, simple switch commutation, and avoids voltage balancing issues of other multilevel inverters. The functionality of the proposed topology and modulation scheme is verified through simulation and experimental results.
Application of soft switching in DC-DC converter has achieved a remarkable success in power electronics technology in terms of reduction in switching losses, improve in power density, minimization of electromagnetic interference (EMI) and reduction in the volume of DC-DC converters. Quite a number of soft switching techniques had been reported in the past four decades. This paper aims at providing a review of various soft switching techniques, based on topology, the location of the resonant network, performance characteristics, and principles of operation. In addition, converters area of application, advantages as well as limitations are also highlighted.
Comparative analysis of a cascaded seven level and five level mli based distr...IAEME Publication
This document summarizes a research paper that compares a cascaded seven-level and five-level multilevel inverter-based distribution static synchronous compensator (DSTATCOM) for compensating harmonics and reactive power using reference frame theory. The paper presents the configuration of a DSTATCOM using a cascaded multilevel inverter with five levels and seven levels. It describes the operation and switching states of the five-level and seven-level inverters. It also discusses the reference current control strategy used, which generates the reference currents required to compensate load current harmonics and reactive power based on instantaneous real-power theory. The control scheme aims to maintain the DC bus voltage constant. The proposed DSTATCOM system is
ACEP Magazine edition 4th launched on 05.06.2024Rahul
This document provides information about the third edition of the magazine "Sthapatya" published by the Association of Civil Engineers (Practicing) Aurangabad. It includes messages from current and past presidents of ACEP, memories and photos from past ACEP events, information on life time achievement awards given by ACEP, and a technical article on concrete maintenance, repairs and strengthening. The document highlights activities of ACEP and provides a technical educational article for members.
Harnessing WebAssembly for Real-time Stateless Streaming PipelinesChristina Lin
Traditionally, dealing with real-time data pipelines has involved significant overhead, even for straightforward tasks like data transformation or masking. However, in this talk, we’ll venture into the dynamic realm of WebAssembly (WASM) and discover how it can revolutionize the creation of stateless streaming pipelines within a Kafka (Redpanda) broker. These pipelines are adept at managing low-latency, high-data-volume scenarios.
Batteries -Introduction – Types of Batteries – discharging and charging of battery - characteristics of battery –battery rating- various tests on battery- – Primary battery: silver button cell- Secondary battery :Ni-Cd battery-modern battery: lithium ion battery-maintenance of batteries-choices of batteries for electric vehicle applications.
Fuel Cells: Introduction- importance and classification of fuel cells - description, principle, components, applications of fuel cells: H2-O2 fuel cell, alkaline fuel cell, molten carbonate fuel cell and direct methanol fuel cells.
Using recycled concrete aggregates (RCA) for pavements is crucial to achieving sustainability. Implementing RCA for new pavement can minimize carbon footprint, conserve natural resources, reduce harmful emissions, and lower life cycle costs. Compared to natural aggregate (NA), RCA pavement has fewer comprehensive studies and sustainability assessments.
Literature Review Basics and Understanding Reference Management.pptxDr Ramhari Poudyal
Three-day training on academic research focuses on analytical tools at United Technical College, supported by the University Grant Commission, Nepal. 24-26 May 2024
A review on techniques and modelling methodologies used for checking electrom...nooriasukmaningtyas
The proper function of the integrated circuit (IC) in an inhibiting electromagnetic environment has always been a serious concern throughout the decades of revolution in the world of electronics, from disjunct devices to today’s integrated circuit technology, where billions of transistors are combined on a single chip. The automotive industry and smart vehicles in particular, are confronting design issues such as being prone to electromagnetic interference (EMI). Electronic control devices calculate incorrect outputs because of EMI and sensors give misleading values which can prove fatal in case of automotives. In this paper, the authors have non exhaustively tried to review research work concerned with the investigation of EMI in ICs and prediction of this EMI using various modelling methodologies and measurement setups.
CHINA’S GEO-ECONOMIC OUTREACH IN CENTRAL ASIAN COUNTRIES AND FUTURE PROSPECTjpsjournal1
The rivalry between prominent international actors for dominance over Central Asia's hydrocarbon
reserves and the ancient silk trade route, along with China's diplomatic endeavours in the area, has been
referred to as the "New Great Game." This research centres on the power struggle, considering
geopolitical, geostrategic, and geoeconomic variables. Topics including trade, political hegemony, oil
politics, and conventional and nontraditional security are all explored and explained by the researcher.
Using Mackinder's Heartland, Spykman Rimland, and Hegemonic Stability theories, examines China's role
in Central Asia. This study adheres to the empirical epistemological method and has taken care of
objectivity. This study analyze primary and secondary research documents critically to elaborate role of
china’s geo economic outreach in central Asian countries and its future prospect. China is thriving in trade,
pipeline politics, and winning states, according to this study, thanks to important instruments like the
Shanghai Cooperation Organisation and the Belt and Road Economic Initiative. According to this study,
China is seeing significant success in commerce, pipeline politics, and gaining influence on other
governments. This success may be attributed to the effective utilisation of key tools such as the Shanghai
Cooperation Organisation and the Belt and Road Economic Initiative.
CHINA’S GEO-ECONOMIC OUTREACH IN CENTRAL ASIAN COUNTRIES AND FUTURE PROSPECT
Energies 10-01709-v2
1. energies
Review
Modular Multilevel Converters:
Control and Applications
Fernando Martinez-Rodrigo 1,* ID
, Dionisio Ramirez 2, Alexis B. Rey-Boue 3, Santiago de Pablo 4
and Luis Carlos Herrero-de Lucas 1
1 Department of Electronics Technology, University of Valladolid, 47014 Valladolid, Spain; lcherrer@tele.uva.es
2 Department of Automation, Electrical and Electronic Engineering and Industrial Computing,
Technical University of Madrid (UPM), 28006 Madrid, Spain; dionisio.ramirez@upm.es
3 Department of Electronics, Computers Technology and Projects, Universidad Politecnica de Cartagena,
30202 Cartagena, Murcia, Spain; Alexis.Rey@upct.es
4 Department of Electronics Technology, University of Valladolid, 47011 Valladolid, Spain; sanpab@eii.uva.es
* Correspondence: fer_mart@tele.uva.es; Tel.: +34-983-423-921
Received: 24 September 2017; Accepted: 23 October 2017; Published: 26 October 2017
Abstract: This review article is mainly oriented to the control and applications of modular multilevel
converters (MMC). The main topologies of the switching modules are presented, for normal operation
and for the elimination of DC faults. Methods to keep the capacitor voltage balanced are included.
The voltage and current modulators, that are the most internal loops of control, are detailed.
Voltage control and current control schemes are included which regulate DC link voltage and
reactive power. The cases of unbalanced and distorted networks are analyzed, and schemes are
proposed so that MMC contribute to improve the quality of the grid in these situations. The main
applications in high voltage direct current (HVDC) transmission along with other medium voltage
(MV) and low voltage (LV) applications are included. Finally, the application to offshore wind farms
is specifically analyzed.
Keywords: capacitor voltage balancing; current controlled converter; D-STATCOM; harmonics;
HVDC; modular multilevel converter (MMC); sinusoidal pulse-width modulation (PWM);
space-vector modulation (SVM); switching modules (SM) topologies; unbalanced compensation
1. Introduction
High voltage direct current (HVDC) transmission was historically performed using the
thyristor-controlled Line Commutated Converter (LCC) [1]. However, it has several limitations:
it uses semiconductors that cannot be switched off autonomously, external voltage must supply
reactive power to produce semiconductor switching, it only operates with a delay power factor and it
cannot be used in isolated systems [2].
Later, the Voltage Source Converter (VSC) [3], made with insulated gate bipolar transistors (IGBT),
was used. This has several advantages over LCC: it uses semiconductors that can be switched on and
off autonomously, the converter can supply reactive power, it can operate with a delay and advance
power factor and it can be used in isolated systems [2].
When the two level VSC topology is used, it presents several problems:
(1) Very high di/dt of the arms of the converter and the semiconductors.
(2) Great stress and over-voltages in the semiconductors.
(3) Emission of electromagnetic radiation and difficulties in the construction of the converter.
(4) With pulse-width modulation (PWM): great loss of power in the semiconductors and use of
voluminous and expensive passive filters.
Energies 2017, 10, 1709; doi:10.3390/en10111709 www.mdpi.com/journal/energies
2. Energies 2017, 10, 1709 2 of 26
(5) As capacity is concentrated, DC short-circuits are very difficult to limit.
To improve these aspects, multi-level VSC has been used [4]. However, it has severe limitations
such as insufficient industrial scalability and limited number of voltage levels [5]. The modular
multilevel converter (MCC) (Figure 1), presented for the first time by Lesnicar and R. Marquardt [6],
improves these problems notably [7]:
(1) The arm current flows continuously, avoiding the high di/dt of the VSC switching.
(2) There is a great reduction of power losses and filtering needs.
(3) The capacity is distributed among the modules of each arm.
(4) The complexity does not increase substantially with the number of levels employed.
(5) The fault currents in the DC side are smaller, making them more suitable for multi-terminal
HVDC grids.
Energies 2017, 10, 1709 2 of 25
(4) With pulse-width modulation (PWM): great loss of power in the semiconductors and use of
voluminous and expensive passive filters.
(5) As capacity is concentrated, DC short-circuits are very difficult to limit.
To improve these aspects, multi-level VSC has been used [4]. However, it has severe limitations
such as insufficient industrial scalability and limited number of voltage levels [5]. The modular
multilevel converter (MCC) (Figure 1), presented for the first time by Lesnicar and R. Marquardt [6],
improves these problems notably [7]:
(1) The arm current flows continuously, avoiding the high di/dt of the VSC switching.
(2) There is a great reduction of power losses and filtering needs.
(3) The capacity is distributed among the modules of each arm.
(4) The complexity does not increase substantially with the number of levels employed.
(5) The fault currents in the DC side are smaller, making them more suitable for multi-terminal
HVDC grids.
Although publications on MMC have been made in very different orientations, this article is
oriented towards control and applications, so some important aspects such as reduction of
circulating currents [8–11] or modeling of the converter is not included [12–15].
Figure 1. Modular multilevel converter.
Since the MMC is a multi-level converter, the voltage harmonics generated are smaller than in a
two-level converter, thus reducing the values of the reactive components of the filter, which can
even be eliminated in some cases. When a large number of modules is used, the switching frequency
of the modules is reduced and the converter switching losses are minimized [16].
Figure 1. Modular multilevel converter.
Although publications on MMC have been made in very different orientations, this article is
oriented towards control and applications, so some important aspects such as reduction of circulating
currents [8–11] or modeling of the converter is not included [12–15].
Since the MMC is a multi-level converter, the voltage harmonics generated are smaller than in
a two-level converter, thus reducing the values of the reactive components of the filter, which can even
be eliminated in some cases. When a large number of modules is used, the switching frequency of the
modules is reduced and the converter switching losses are minimized [16].
3. Energies 2017, 10, 1709 3 of 26
When the distance is long (greater than 400–700 km on land, and 50–60 km at sea) DC transmission
is cheaper than AC transmission. DC transmission needs fewer cables, but requires the presence of
electronic converters. Another limitation of AC transmission is the reactive energy that consumes the
inductance of the line, which for long distance transmission becomes a fundamental factor. MMC was
first commercially used in the Trans Bay Cable project in San Francisco [16].
The article has been organized as follows. Section 2 is devoted to the topologies of the switching
modules. Section 3 is dedicated to the fundamental equations relating the voltages and currents of the
DC side, AC side, switching modules, arm inductances, and circulating currents. Section 4 is devoted
to the balancing of the capacitors of the switching modules. Section 5 includes voltage and current
modulators. Section 6 deals with the connection of the converter to balanced, unbalanced or distorted
grids. Section 7 includes high voltage (HV), medium voltage (MV), and low voltage (LV) applications.
Finally, Section 8 is devoted to the use of MMC in offshore wind farms.
2. Switching Module Topologies
The first topology of a switching module (SM) presented for MMC (by Lesnicar and Marquardt [6])
was the half bridge (HB) topology (Figure 2a), which has been the most used. It consists of two IGBTs,
two diodes, and one capacitor. The SM is ON when T1 is ON and T2 is OFF (Table 1), while SM is OFF
when T1 is OFF and T2 is ON. When the SM is ON, the SM voltage is the same as the SM capacitor
voltage, while when it is OFF the voltage is zero. According to the SM state and the direction of the
SM current, the current circulates through the capacitor producing its charge/discharge, or it does not
circulate through the capacitor, maintaining its voltage.
Energies 2017, 10, 1709 3 of 25
When the distance is long (greater than 400–700 km on land, and 50–60 km at sea) DC
transmission is cheaper than AC transmission. DC transmission needs fewer cables, but requires the
presence of electronic converters. Another limitation of AC transmission is the reactive energy that
consumes the inductance of the line, which for long distance transmission becomes a fundamental
factor. MMC was first commercially used in the Trans Bay Cable project in San Francisco [16].
The article has been organized as follows. Section 2 is devoted to the topologies of the switching
modules. Section 3 is dedicated to the fundamental equations relating the voltages and currents of
the DC side, AC side, switching modules, arm inductances, and circulating currents. Section 4 is
devoted to the balancing of the capacitors of the switching modules. Section 5 includes voltage and
current modulators. Section 6 deals with the connection of the converter to balanced, unbalanced or
distorted grids. Section 7 includes high voltage (HV), medium voltage (MV), and low voltage (LV)
applications. Finally, Section 8 is devoted to the use of MMC in offshore wind farms.
2. Switching Module Topologies
The first topology of a switching module (SM) presented for MMC (by Lesnicar and Marquardt
[6]) was the half bridge (HB) topology (Figure 2a), which has been the most used. It consists of two
IGBTs, two diodes, and one capacitor. The SM is ON when T1 is ON and T2 is OFF (Table 1), while
SM is OFF when T1 is OFF and T2 is ON. When the SM is ON, the SM voltage is the same as the SM
capacitor voltage, while when it is OFF the voltage is zero. According to the SM state and the
direction of the SM current, the current circulates through the capacitor producing its
charge/discharge, or it does not circulate through the capacitor, maintaining its voltage.
Figure 2. Switching module (SM) topologies: (a) half bridge; (b) full bridge.
Table 1. State of conduction, voltages and currents of the switching module (SM).
SM State State State ∆ Flows Through
ON ON OFF > 0 + D
ON ON OFF < 0 − T
OFF OFF ON > 0 0 T 0
OFF OFF ON < 0 0 D 0
In the case of a DC short circuit, the HB topology turns OFF all IGBTs, and a fault current
occurs, which is the quotient between the AC voltage and the impedance of the arm inductances.
The full bridge (FB) topology (Figure 2b) allows an active role in case of failure [5]. This topology
behaves just like the HB topology during normal operation. To set the SM to ON ( = ), IGBT 1
and 4 are turned ON. To set the SM to OFF ( = 0), there are two options, set T1 and T3 to ON, or
set T2 and T4 to ON. During the fault, a voltage of opposite sign can be introduced in series with that
fault to reduce and eliminate it. For example, if the fault current is positive with respect to the SM, T1
and T4 are set to ON so the SM voltage is positive, whereas if the current is negative, T2 and T3 are
set to ON so the SM voltage is negative. The problem with the FB topology is that, in order to be able
to eliminate faults, the price to be paid is to double the loss of power during normal operation.
Other topologies that include additional components have been introduced to handle short
circuits in the DC part. The Double Clamp Submodule Topology [5] (Figure 3a) is equivalent to two
Figure 2. Switching module (SM) topologies: (a) half bridge; (b) full bridge.
Table 1. State of conduction, voltages and currents of the switching module (SM).
SM State T1 State T2 State iSM ∆vC iSM Flows Through vSM
ON ON OFF > 0 + D1 vC
ON ON OFF < 0 − T1 vC
OFF OFF ON > 0 0 T2 0
OFF OFF ON < 0 0 D2 0
In the case of a DC short circuit, the HB topology turns OFF all IGBTs, and a fault current occurs,
which is the quotient between the AC voltage and the impedance of the arm inductances. The full
bridge (FB) topology (Figure 2b) allows an active role in case of failure [5]. This topology behaves just
like the HB topology during normal operation. To set the SM to ON (vSM = vC), IGBT 1 and 4 are
turned ON. To set the SM to OFF (vSM = 0), there are two options, set T1 and T3 to ON, or set T2 and
T4 to ON. During the fault, a voltage of opposite sign can be introduced in series with that fault to
reduce and eliminate it. For example, if the fault current is positive with respect to the SM, T1 and
T4 are set to ON so the SM voltage is positive, whereas if the current is negative, T2 and T3 are set
to ON so the SM voltage is negative. The problem with the FB topology is that, in order to be able to
eliminate faults, the price to be paid is to double the loss of power during normal operation.
4. Energies 2017, 10, 1709 4 of 26
Other topologies that include additional components have been introduced to handle short
circuits in the DC part. The Double Clamp Submodule Topology [5] (Figure 3a) is equivalent to two
half bridges, plus an additional IGBT T5. In normal operation, IGBT T5 is in conduction, but it is
switched off during the DC fault, allowing the two capacitors to oppose the fault.
Other topologies to reduce the impact of short duration of time DC short circuits have included
thyristors [17]. The first one includes a thyristor in parallel with D2 (Figure 3b), which is triggered
when the fault is detected. Then the current flows through the thyristor instead of D2, due to the higher
I2t of the thyristor. The problem is that there is a rectifier effect between the AC and the DC through
the diodes D2 of the SMs that feed the DC fault. To avoid this, the topology with two thyristors was
proposed (Figure 3c) that causes a short circuit in AC limited by branch inductances; when the DC
fault is cleared, the IGBTs take control again.
Energies 2017, 10, 1709 4 of 25
half bridges, plus an additional IGBT T5. In normal operation, IGBT T5 is in conduction, but it is
switched off during the DC fault, allowing the two capacitors to oppose the fault.
Other topologies to reduce the impact of short duration of time DC short circuits have included
thyristors [17]. The first one includes a thyristor in parallel with D2 (Figure 3b), which is triggered
when the fault is detected. Then the current flows through the thyristor instead of D2, due to the
higher I2t of the thyristor. The problem is that there is a rectifier effect between the AC and the DC
through the diodes D2 of the SMs that feed the DC fault. To avoid this, the topology with two
thyristors was proposed (Figure 3c) that causes a short circuit in AC limited by branch inductances;
when the DC fault is cleared, the IGBTs take control again.
Figure 3. SM topologies used to reduce DC short-circuits: (a) double clamp submodule; (b) topology
with a thyristor at the SM input; and (c) topology with two thyristors at the SM input [5,17].
3. Fundamental Equations
The SMs of each phase have been grouped into two blocks with voltages (upper arm) and
(lower arm) (Figure 4). The capacitor of each SM is kept charged with a voltage equal to the
DC voltage divided by the number of SMs of each arm , = . In order for the sum of the
voltages of the two arms of a phase to be equal to the DC voltage, the sum of the number of SMs in
the ON state in the upper arm and lower arm of each phase must be equal to :
+ = (1)
The equation relating the DC and AC voltage can be obtained through the upper arm, or the
lower arm:
=
2
− − (2)
= −
2
+ + (3)
Figure 3. SM topologies used to reduce DC short-circuits: (a) double clamp submodule; (b) topology
with a thyristor at the SM input; and (c) topology with two thyristors at the SM input [5,17].
3. Fundamental Equations
The SMs of each phase have been grouped into two blocks with voltages vupa (upper arm) and
vlowa (lower arm) (Figure 4). The capacitor of each SM is kept charged with a voltage equal to the
DC voltage VDC divided by the number of SMs of each arm n, vC = VDC
n . In order for the sum of the
voltages of the two arms of a phase to be equal to the DC voltage, the sum of the number of SMs in the
ON state in the upper arm nup and lower arm nlow of each phase must be equal to n:
nup + nlow = n (1)
The equation relating the DC and AC voltage can be obtained through the upper arm, or the
lower arm:
voa =
VDC
2
− vupa − L
diupa
dt
(2)
5. Energies 2017, 10, 1709 5 of 26
voa = −
VDC
2
+ vlowa + L
dilowa
dt
(3)
The voltage of each arm, vupa and vlowa, depends on the conduction state 1/0 of each SM, Supak,
and Slowak, and the voltage of each capacitor, vCupak, and vClowak, the sum of the voltages of the
modules being:
vupa =
n
∑
k=1
SupakvCupak (4)
vlowa =
n
∑
k=1
SlowakvClowak (5)
Energies 2017, 10, 1709 5 of 25
The voltage of each arm, and , depends on the conduction state 1/0 of each SM,
, and , and the voltage of each capacitor, , and , the sum of the voltages of
the modules being:
= (4)
= (5)
Figure 4. Modular multilevel converter (MMC) connected to a grid through three inductances; SMs
have been grouped into arms.
For each of the arms, a current (upper and lower ) is circulated equal to half the phase
current , plus a third of the DC current , plus the circulating current [13,18]:
=
2
+
3
+ (6)
= −
2
+
3
+ (7)
From (6) and (7) the circulating current can be obtained as:
=
+
2
−
3
(8)
The sum of the three circulating currents of the three arms/phases is zero:
+ + = 0 (9)
The output voltage of each AC phase can take + 1 different values; for example, if the
number of SMs per arm is = 5, the number of levels of the AC voltage is 6 and their values can be
seen in Table 2 as a function of the number of modules that are ON in each arm.
Figure 4. Modular multilevel converter (MMC) connected to a grid through three inductances;
SMs have been grouped into arms.
For each of the arms, a current (upper iupa and lower ilowa) is circulated equal to half the phase
current ia, plus a third of the DC current idc, plus the circulating current iza [13,18]:
iupa =
ia
2
+
idc
3
+ iza (6)
ilowa = −
ia
2
+
idc
3
+ iza (7)
From (6) and (7) the circulating current can be obtained as:
iza =
iupa + ilowa
2
−
idc
3
(8)
The sum of the three circulating currents of the three arms/phases is zero:
iza + izb + izc = 0 (9)
The output voltage of each AC phase can take n + 1 different values; for example, if the number
of SMs per arm is n = 5, the number of levels of the AC voltage is 6 and their values can be seen
in Table 2 as a function of the number of modules that are ON in each arm.
6. Energies 2017, 10, 1709 6 of 26
Table 2. AC voltages depending on the number of modules in ON state in each arm.
nup nlow voa
5 0 −VDC
2 + 0VDC
5
4 1 −VDC
2 + 1VDC
5
3 2 −VDC
2 + 2VDC
5
2 3 −VDC
2 + 3VDC
5
1 4 −VDC
2 + 4VDC
5
0 5 −VDC
2 + 5VDC
5
4. Capacitor Balancing
The capacitors of the SMs change their voltage depending on the current flowing through the
SM. The voltage of the SM should be kept approximately equal to its theoretical value VDC
n . For this,
the SM voltage must be measured and the appropriate measures to maintain the voltages in that value
must be taken. Otherwise, the capacitor voltages will become more and more unbalanced and the AC
output voltage cannot be controlled.
Different types of algorithms have been used to balance capacitor voltages. When a combination
of the averaged control and the balanced control is used, it is possible to balance the voltage of the
capacitors without using any external circuit [19]. A predictive control, based on minimizing a cost
function, allows the capacitor voltages to be balanced, circulating currents to be minimized and
the AC currents to be controlled, jointly, under various operating conditions [20]. A method that
does not need to measure the current in each arm eliminates current sensors, reducing costs and
simplifying the voltage balance control algorithm [21]. The most commonly used algorithm measures
the voltages of the capacitors and chooses the SMs that must be ON depending on the direction of
the current [7,18]. An example can be seen in Figure 5, in the case of arms with n = 5 SMs, where
the aim is for the capacitor voltages to remain at 800 V. Assuming that the desired output voltage
is −VDC
2 + 2VDC
5 = −4000
2 + 24000
5 = −400 V, nup = 3 and nlow = 2 are required. In the example,
the voltages of the upper arm will be balanced, while the lower arm will be balanced in the same way.
In the upper arm, three SMs must be set to ON, chosen according to the SM current iupa direction.
Depending on whether it is positive/negative, it increases/reduces the voltage of the SMs it circulates.
When it is positive, SMs that have less voltage are turned ON to charge, while if negative, the SMs that
have the highest voltage are turned ON to discharge.
Energies 2017, 10, 1709 6 of 25
Table 2. AC voltages depending on the number of modules in ON state in each arm.
5 0 −
2
+ 0
5
4 1 −
2
+ 1
5
3 2 −
2
+ 2
5
2 3 −
2
+ 3
5
1 4 −
2
+ 4
5
0 5 −
2
+ 5
5
4. Capacitor Balancing
The capacitors of the SMs change their voltage depending on the current flowing through the
SM. The voltage of the SM should be kept approximately equal to its theoretical value . For this,
the SM voltage must be measured and the appropriate measures to maintain the voltages in that
value must be taken. Otherwise, the capacitor voltages will become more and more unbalanced and
the AC output voltage cannot be controlled.
Different types of algorithms have been used to balance capacitor voltages. When a
combination of the averaged control and the balanced control is used, it is possible to balance the
voltage of the capacitors without using any external circuit [19]. A predictive control, based on
minimizing a cost function, allows the capacitor voltages to be balanced, circulating currents to be
minimized and the AC currents to be controlled, jointly, under various operating conditions [20]. A
method that does not need to measure the current in each arm eliminates current sensors, reducing
costs and simplifying the voltage balance control algorithm [21]. The most commonly used
algorithm measures the voltages of the capacitors and chooses the SMs that must be ON depending
on the direction of the current [7,18]. An example can be seen in Figure 5, in the case of arms with
= 5 SMs, where the aim is for the capacitor voltages to remain at 800 V. Assuming that the
desired output voltage is − + 2 = − + 2 = −400 V , = 3 and = 2 are
required. In the example, the voltages of the upper arm will be balanced, while the lower arm will be
balanced in the same way. In the upper arm, three SMs must be set to ON, chosen according to the
SM current direction. Depending on whether it is positive/negative, it increases/reduces the
voltage of the SMs it circulates. When it is positive, SMs that have less voltage are turned ON to
charge, while if negative, the SMs that have the highest voltage are turned ON to discharge.
Figure 5. Example of capacitor balancing.
Figure 5. Example of capacitor balancing.
7. Energies 2017, 10, 1709 7 of 26
5. Voltage and Current Modulators
The external control loop of the MMC has two Proportional-Integral (PI) regulators, one for the
DC voltage and one for the reactive power exchanged by the AC grid, which generate the grid current
references in dq axes. If current control is used, a current modulator is required for the MMC to follow
current references. If voltage control is used, two PI regulators are required to transform current
references into voltage references and, subsequently, a voltage modulator.
Four voltage modulators and two current modulators are presented in great detail. The former
are more commonly used. Their switching frequency is lower. The design of the AC filter is simpler
because the switching frequency is constant. The latter have been proposed for applications with
greater needs for speed of response.
5.1. Voltage Modulators
The voltage modulators are responsible for calculating the level of the output voltage at each
sampling time, depending on the value of the AC voltage reference. When the number of converter
levels is small, high-frequency modulation is often used, whereas when the number of levels is
high, low-frequency steps are often used. In the first case, the semiconductor switching losses are
high. In all cases, the goal is to eliminate or greatly reduce low frequency harmonics to facilitate the
filtering of the AC voltage, taking into account the fact that the type of modulation used determines,
in part, the harmonics of the generated voltage [22]. First, three voltage modulators using high
frequency modulation, phase disposition-sinusoidal PWM, multilevel PWM, and multilevel space
vector modulation (SVM) are presented. Finally, the step-level modulator called Near Level Control
(NLC) is presented.
The high frequency modulators are presented for the case where each arm consists of n = 5 SMs,
which causes the output voltage between phase and neutral voabc to have n + 1 = 6 levels. The result
of the calculation of the modulator will be the number of SMs in the ON state in the upper nup and
lower nlow arms and, therefore, the output voltage of the corresponding phase will be:
vo = −
VDC
2
+ nlowvC (10)
5.1.1. Phase Disposition–Sinusoidal PWM
This is a PWM similar to the one used in a classic two level inverter, but adapted to the case of
multilevel converters. In the former, a single high-frequency (carrier) triangle signal is used which
is compared to a low-frequency (modulator) sine wave signal. In the second, several high-frequency
triangular signals are used (see Figure 6) with a modulating signal to produce the output voltage. It is
a modulation that has not been used only in MMC but in multilevel inverters in general. According to
the offset between the carriers, there are several types of modulation called [23]: Alternative Phase
Opposition Disposition, Phase Disposition, Phase Opposition Disposition, Hybrid, Phase Shifted.
The one shown in Figure 6 is Phase Disposition (PD), in which the offset between the carriers is nill.
For the six-level case (Figure 6), the Phase disposition-sinusoidal PWM (PD-SPWM) uses five high
frequency carriers. The output voltage takes one of six possible values, −VDC
2 , −VDC
2 + VDC
5 , −VDC
2 +
2VDC
5 , −VDC
2 + 3VDC
5 , −VDC
2 + 4VDC
5 , VDC
2 , depending on whether the sinusoidal is higher or lower than
each of the triangular ones, as can be seen in the following equation:
voa =
VDC
2 , (vtri5 < voa
∗)
−VDC
2 + 4VDC
5 , (vtri4 < voa
∗ < vtri5)
−VDC
2 + 3VDC
5 , (vtri3 < voa
∗ < vtri4)
−VDC
2 + 2VDC
5 , (vtri2 < voa
∗ < vtri3)
−VDC
2 + VDC
5 , (vtri1 < voa
∗ < vtri2)
−VDC
2 , (voa
∗ < vtri1)
(11)
8. Energies 2017, 10, 1709 8 of 26
=
−
2
+
2
5
, < ∗
<
−
2
+
5
, < ∗
<
−
2
, ∗
<
(11)
Figure 6. Comparison of carrier signals and sinusoidal modulator signal to obtain the output voltage
of the MMC using phase disposition-sinusoidal pulse-width modulation (PD–SPWM) [23].
5.1.2. Multilevel PWM
Multilevel PWM is a PWM method that calculates a duty cycle every PWM period
[7]. The PWM period establishes the commutation period of the converter. The duty cycle is
calculated so the average values of the output converter voltage and its reference value ∗
will be the same in the PWM period , and ∗ respectively. The average value of the
reference ∗ is:
∗ =
1 ∗
(12)
The output voltage of the converter can take the instantaneous values − , − +
, − + , − + , − + , . For the time , where the voltage ∗
is within
the interval − + ; − + with 0 ≤ ≤ 4, the average value of the output
voltage is:
Figure 6. Comparison of carrier signals and sinusoidal modulator signal to obtain the output voltage
of the MMC using phase disposition-sinusoidal pulse-width modulation (PD–SPWM) [23].
5.1.2. Multilevel PWM
Multilevel PWM is a PWM method that calculates a duty cycle Dk every PWM period TPWM [7].
The PWM period establishes the commutation period of the converter. The duty cycle is calculated so
the average values of the output converter voltage voa and its reference value voa
∗ will be the same in
the PWM period k, voak and voak
∗ respectively. The average value of the reference voak
∗ is:
voak
∗ =
1
TPWM
tk+1
Z
tk
voa
∗
(t)dt (12)
The output voltage of the converter voa can take the instantaneous values −VDC
2 , −VDC
2 +
VDC
5 , −VDC
2 + 2VDC
5 , −VDC
2 + 3VDC
5 , −VDC
2 + 4VDC
5 , VDC
2 . For the time tk, where the voltage voak
∗ is within
the interval
n
−VDC
2 + mVDC
5 ; −VDC
2 + (m+1)VDC
5
o
with 0 ≤ m ≤ 4, the average value of the output
voltage voak is:
voak = 1
TPWM
h
DkTPWM
−VDC
2 + mVDC
5
+ (1 − Dk)TPWM
−VDC
2 + (m+1)VDC
5
i
= −VDC
2 + (m+1)VDC
5 − Dk
VDC
5
(13)
The value of the duty cycle Dk can be obtained by equating the values of voak
∗ and voak in (12)
and (13):
Dk = −
5
2
+ (m + 1) −
5
VDC
1
TPWM
tk+1
Z
tk
voa
∗
(t)dt
(14)
An example of duty cycle calculation can be seen in Figure 7. The values voa1
∗ and voa2
∗ are the
average values of voa
∗ during every PWM period TPWM (Figure 7a). The average values voa1
∗ and
voa2
∗ are obtained by means of the duty cycles D1 and D2 respectively (Figure 7b).
9. Energies 2017, 10, 1709 9 of 26
= −
5
2
+ + 1 −
5 1 ∗
(14)
An example of duty cycle calculation can be seen in Figure 7. The values ∗ and ∗ are
the average values of ∗
during every PWM period (Figure 7a). The average values ∗
and ∗ are obtained by means of the duty cycles and respectively (Figure 7b).
Figure 7. PWM control to match the average voltage in every period: (a) calculating the
average value of the reference ∗
; (b) duty cycle based on the average value of the reference ∗
[7].
5.1.3. Multilevel SVM
For MMC voltage control, the SVM algorithm can be used in its multilevel version, which has
already been used previously for multilevel inverters. In the two-level algorithm, the converter
voltage can take eight different values, including nill voltages (000) and (111). The input to the
algorithm is the voltage to be generated and the output is three vectors corresponding to inverter
voltages, for example (000) (100) (110), and the time each needs to be applied. As the number of
levels increases, the number of values that can take the converter voltage grows exponentially, so the
selection of the three vectors of the inverter output voltage is more difficult [24–29].
Figure 8 presents the basics of the multilevel SVM for the case of six levels. The aim is to
generate a reference voltage ∗ at the output of the MMC. The voltage values that the converter can
generate in an area of the space close to ∗ have been represented. The algorithm must be able to
determine in which triangle the reference voltage ∗ is located and, therefore, which three vectors
(220), (320), (330) (Figure 8a) need to be applied to the output voltage of the MMC to
generate, by linear combination, the voltage ∗. To calculate the application times of each of these
vectors ( , , ) (see Figure 8b), the distances ( , , ) are calculated in [24] and the times ,
, are proportional to these distances. Their sum must be equal to the switching period,
= + + .
Figure 7. PWM control to match the average voltage in every TPWM period: (a) calculating the average
value of the reference voa
∗; (b) duty cycle based on the average value of the reference voa
∗ [7].
5.1.3. Multilevel SVM
For MMC voltage control, the SVM algorithm can be used in its multilevel version, which has
already been used previously for multilevel inverters. In the two-level algorithm, the converter voltage
can take eight different values, including nill voltages (000) and (111). The input to the algorithm is the
voltage to be generated and the output is three vectors corresponding to inverter voltages, for example
(000) (100) (110), and the time each needs to be applied. As the number of levels increases, the number
of values that can take the converter voltage grows exponentially, so the selection of the three vectors
of the inverter output voltage is more difficult [24–29].
Figure 8 presents the basics of the multilevel SVM for the case of six levels. The aim is to generate
a reference voltage
→
vo
∗ at the output of the MMC. The voltage values that the converter can generate
in an area of the space close to
→
vo
∗ have been represented. The algorithm must be able to determine
in which triangle the reference voltage
→
vo
∗ is located and, therefore, which three vectors
→
vo1 (220),
→
vo2 (320),
→
vo3 (330) (Figure 8a) need to be applied to the output voltage of the MMC to generate,
by linear combination, the voltage
→
vo
∗. To calculate the application times of each of these vectors
(T1 , T2 , T3 ) (see Figure 8b), the distances (l1, l2, l3) are calculated in [24] and the times T1, T2, T3 are
proportional to these distances. Their sum must be equal to the switching period, TPWM = T1 + T2 + T3.
The output voltage vectors of the MMC
→
vo1 (220),
→
vo2 (320),
→
vo3 (330) correspond to the voltages of
the three output phases voa, vob, and voc whose values can be seen in Figure 8b.
10. Energies 2017, 10, 1709 10 of 26
Energies 2017, 10, 1709 10 of 25
The output voltage vectors of the MMC (220), (320), (330) correspond to the
voltages of the three output phases , , and whose values can be seen in Figure 8b.
Figure 8. Multilevel space-vector modulation (SVM) for the case of 6 levels: (a) selection of the output
voltage vectors of the MMC ( , and ) depending on the reference voltage ∗ ; (b)
waveform of the voltage of each output phase , , and .
5.1.4. Near Level Control
When the number of voltage levels is small, high-frequency modulation is used to generate the
voltage. This has the advantage of eliminating the low frequency harmonics and the filtering needs
in the AC side, but the disadvantage is the increase of losses by semiconductor switching. If the
number of AC voltage levels is high, due to the existence of a large number of SMs per arm, the AC
voltage is generated in the form of steps. This causes the semiconductors to have few commutations
and low switching losses. The low frequency harmonics are also very small if the number of steps is
high and, consequently, the filtering requirements are also small. This output voltage control system
is commonly referred to as NLC or sometimes Near Level Modulation (NLM).
NLC can have fixed or variable sampling period . In the first case (Figure 9), the variations in
the voltage steps occur with a fixed period regardless of the rate of change of the AC voltage [30].
When the number of levels is high, the sampling time must be sufficiently small so that the AC
Figure 8. Multilevel space-vector modulation (SVM) for the case of 6 levels: (a) selection of the output
voltage vectors of the MMC (
→
vo1,
→
vo2 and
→
vo3 ) depending on the reference voltage
→
vo
∗; (b) waveform of
the voltage of each output phase voa, vob, and voc.
5.1.4. Near Level Control
When the number of voltage levels is small, high-frequency modulation is used to generate the
voltage. This has the advantage of eliminating the low frequency harmonics and the filtering needs in
the AC side, but the disadvantage is the increase of losses by semiconductor switching. If the number
of AC voltage levels is high, due to the existence of a large number of SMs per arm, the AC voltage
is generated in the form of steps. This causes the semiconductors to have few commutations and
low switching losses. The low frequency harmonics are also very small if the number of steps is high
and, consequently, the filtering requirements are also small. This output voltage control system is
commonly referred to as NLC or sometimes Near Level Modulation (NLM).
NLC can have fixed or variable sampling period Ts. In the first case (Figure 9), the variations
in the voltage steps occur with a fixed period regardless of the rate of change of the AC voltage [30].
11. Energies 2017, 10, 1709 11 of 26
When the number of levels is high, the sampling time must be sufficiently small so that the AC voltage
varies only one level at each sampling, not several levels. The control rounds the reference voltage to
the values of the available levels.
Energies 2017, 10, 1709 11 of 25
voltage varies only one level at each sampling, not several levels. The control rounds the reference
voltage to the values of the available levels.
Figure 9. Near Level Control (NLC) with fixed sampling period: sinusoidal reference (blue) and
generated voltage (red).
The second option is for the sampling period to be variable. The control of the switches changes
from one level to the next when the reference voltage exceeds the intermediate value at these two
levels (Figure 10) [31]. An interesting variation of this method consists in making the upper and
lower arms commute out of phase , causing the number of levels to be multiplied by two [32].
Figure 10. NLC with variable sampling period: sinusoidal reference (blue) and generated voltage
(red).
5.2. Current Modulators
The input of the current modulator is the reference of the phase current, which is the output of
the PI regulators of the DC voltage and the reactive power . Current modulators control the
MMC output voltage to maintain the current of each phase within a certain hysteresis band. When
voltage modulators are used, two additional PI regulators are needed between the current reference
and the voltage modulator, which cause the response to be slower than in the case of current
modulators. A disadvantage of current modulators is that the switching frequency is not constant, so
the design of the filter is more difficult.
The MMC is considered to be coupled to the grid by an inductance (Figure 4), which has, on one
side, the output voltage of the MMC , and on the other side, the mains voltage . By variation of
, the aim is to maintain the phase current in a band of width 2 around the reference ∗
. Two
current modulators are presented; in the first, the voltage applied to the inductance is constant,
while in the second it is proportional to the desired effect [33].
Figure 9. Near Level Control (NLC) with fixed sampling period: sinusoidal reference (blue) and
generated voltage (red).
The second option is for the sampling period to be variable. The control of the switches changes
from one level to the next when the reference voltage exceeds the intermediate value at these two levels
(Figure 10) [31]. An interesting variation of this method consists in making the upper and lower arms
commute out of phase Ts
2 , causing the number of levels to be multiplied by two [32].
Energies 2017, 10, 1709 11 of 25
voltage varies only one level at each sampling, not several levels. The control rounds the reference
voltage to the values of the available levels.
Figure 9. Near Level Control (NLC) with fixed sampling period: sinusoidal reference (blue) and
generated voltage (red).
The second option is for the sampling period to be variable. The control of the switches changes
from one level to the next when the reference voltage exceeds the intermediate value at these two
levels (Figure 10) [31]. An interesting variation of this method consists in making the upper and
lower arms commute out of phase , causing the number of levels to be multiplied by two [32].
Figure 10. NLC with variable sampling period: sinusoidal reference (blue) and generated voltage
(red).
5.2. Current Modulators
The input of the current modulator is the reference of the phase current, which is the output of
the PI regulators of the DC voltage and the reactive power . Current modulators control the
MMC output voltage to maintain the current of each phase within a certain hysteresis band. When
voltage modulators are used, two additional PI regulators are needed between the current reference
and the voltage modulator, which cause the response to be slower than in the case of current
modulators. A disadvantage of current modulators is that the switching frequency is not constant, so
the design of the filter is more difficult.
The MMC is considered to be coupled to the grid by an inductance (Figure 4), which has, on one
side, the output voltage of the MMC , and on the other side, the mains voltage . By variation of
, the aim is to maintain the phase current in a band of width 2 around the reference ∗
. Two
current modulators are presented; in the first, the voltage applied to the inductance is constant,
while in the second it is proportional to the desired effect [33].
Figure 10. NLC with variable sampling period: sinusoidal reference (blue) and generated voltage (red).
5.2. Current Modulators
The input of the current modulator is the reference of the phase current, which is the output of the
PI regulators of the DC voltage VDC and the reactive power Q. Current modulators control the MMC
output voltage to maintain the current of each phase within a certain hysteresis band. When voltage
modulators are used, two additional PI regulators are needed between the current reference and the
voltage modulator, which cause the response to be slower than in the case of current modulators.
A disadvantage of current modulators is that the switching frequency is not constant, so the design of
the filter is more difficult.
The MMC is considered to be coupled to the grid by an inductance (Figure 4), which has, on one
side, the output voltage of the MMC voa, and on the other side, the mains voltage va. By variation of voa,
the aim is to maintain the phase current ia in a band of width 2ε around the reference ia
∗
. Two current
modulators are presented; in the first, the voltage applied to the inductance is constant, while in the
second it is proportional to the desired effect [33].
12. Energies 2017, 10, 1709 12 of 26
5.2.1. Current Control with Constant Excitation
The coupling inductance has, at the ends, the inverter voa and grid va voltages (Figure 11a).
By changing the voltage voa, the current ia can be maintained within the hysteresis band
h
ia
∗
+ ε ia
∗
− ε
i
(Figure 11b). If the number of SMs per arm is n = 5, then the voltage voa can take
the six levels observed in Figure 11c, while the voltage va will have a sinusoidal form. Although other
options may be taken, it seems appropriate to choose the voltages voa adjacent to the instantaneous
value of the voltage va, −VDC
2 + (nlow + 1)VDC
5 , and −VDC
2 + nlow
VDC
5 (Figure 11d), where nlow is the
number of modules in the ON state of the lower arm. When the largest of these values is applied,
the voltage at the coupling inductance Lc is positive and the phase current ia increases (Figure 11b),
whereas when the smaller one is applied the opposite occurs. The variable nlow is calculated as
a function of the grid voltage voa by the equation:
k = f loor
va +
VDC
2
/vC
(15)
where “floor” means round to an integer towards negative infinity.
Energies 2017, 10, 1709 12 of 25
5.2.1. Current Control with Constant Excitation
The coupling inductance has, at the ends, the inverter and grid voltages (Figure 11a).
By changing the voltage , the current can be maintained within the hysteresis band
∗
+ ∗
− (Figure 11b). If the number of SMs per arm is = 5, then the voltage can take
the six levels observed in Figure 11c, while the voltage will have a sinusoidal form. Although
other options may be taken, it seems appropriate to choose the voltages adjacent to the
instantaneous value of the voltage , − + + 1 , and − + (Figure 11d),
where is the number of modules in the ON state of the lower arm. When the largest of these
values is applied, the voltage at the coupling inductance is positive and the phase current
increases (Figure 11b), whereas when the smaller one is applied the opposite occurs. The variable
is calculated as a function of the grid voltage by the equation:
= +
2
/ (15)
where “floor” means round to an integer towards negative infinity.
Figure 11. Current control with constant excitation: (a) coupling to the grid by means of an
inductance; (b) phase current switching in the band due to the action of the MMC voltage; (c) levels
of the MMC output voltage; and (d) output voltage levels adjacent to the grid voltage [33].
5.2.2. Current Control with Excitation Proportional to the Error
If the number of SMs is very high and the above algorithm is used, the inductance voltage may
be too small to be able to direct the phase current in the desired direction; then, a higher voltage
is needed. In this case, the values of the MMC voltage adjacent to the grid voltage would not
be used, but rather more distant values (Figure 12a) that would cause a faster change of the current
.
Figure 11. Current control with constant excitation: (a) coupling to the grid by means of an inductance;
(b) phase current switching in the band due to the action of the MMC voltage; (c) levels of the MMC
output voltage; and (d) output voltage levels adjacent to the grid voltage [33].
5.2.2. Current Control with Excitation Proportional to the Error
If the number of SMs is very high and the above algorithm is used, the inductance voltage may
be too small to be able to direct the phase current ia in the desired direction; then, a higher voltage is
13. Energies 2017, 10, 1709 13 of 26
needed. In this case, the values of the MMC voltage voa adjacent to the grid voltage va would not be
used, but rather more distant values (Figure 12a) that would cause a faster change of the current ia.
Values of voa which cause a voltage at the coupling inductance Lc proportional to the distance of
the current ia from the band above ia − (ia
∗
+ ε) or below (ia
∗
− ε) − ia (Figure 12b) must be chosen.
A hysteresis proportionality coefficient kh is defined which provides greater or lesser voltage in the
inductance for the same current error (or distance to the hysteresis band). This coefficient is used in the
calculation of the MMC output voltage to be applied when the current goes below the hysteresis band:
voa = −
VDC
2
+
nlow + 1 + f loor
kh
(ia
∗
− ε) − ia
ε
VDC
5
(16)
or above the hysteresis band:
voa = −
VDC
2
+
nlow − f loor
kh
ia − (ia
∗
+ ε)
ε
VDC
5
(17)
In Figure 12c the current control algorithm diagram with excitation proportional to the error can
be seen.
Energies 2017, 10, 1709 13 of 25
Values of which cause a voltage at the coupling inductance proportional to the distance
of the current from the band above − ∗
+ or below ∗
− − (Figure 12b) must be
chosen. A hysteresis proportionality coefficient is defined which provides greater or lesser
voltage in the inductance for the same current error (or distance to the hysteresis band). This
coefficient is used in the calculation of the MMC output voltage to be applied when the current goes
below the hysteresis band:
= −
2
+ + 1 +
∗
− −
5 (16)
or above the hysteresis band:
= −
2
+ −
− ∗
+
5 (17)
In Figure 12c the current control algorithm diagram with excitation proportional to the error
can be seen.
Figure 12. Current control with excitation proportional to the error: (a) converter voltage levels; (b)
changes in the MMC voltage to maintain current within the hysteresis band; (c) scheme of the
algorithm [33].
6. Grid Connection
The MMC has one DC side and one AC side. The DC side has a voltage that must be kept
constant, either by the MMC or by another converter, depending on the case. The AC side can be a
distribution grid (medium voltage) or transport grid (high voltage), or it can be an offshore wind
farm.
Figure 12. Current control with excitation proportional to the error: (a) converter voltage levels;
(b) changes in the MMC voltage to maintain current within the hysteresis band; (c) scheme of the
algorithm [33].
14. Energies 2017, 10, 1709 14 of 26
6. Grid Connection
The MMC has one DC side and one AC side. The DC side has a voltage that must be kept constant,
either by the MMC or by another converter, depending on the case. The AC side can be a distribution
grid (medium voltage) or transport grid (high voltage), or it can be an offshore wind farm.
Usually, the AC part is considered to be a balanced three-phase system containing only the
fundamental harmonic. During mains failures, the AC voltage behaves as an unbalanced system,
whose unbalance is greater or smaller depending on the distance at which the fault occurred and the
type of fault. The grid may also contain harmonics of several frequencies that affect the operation of
the converter and the current generated in AC. The following are schemes for controlling MMCs when
connecting to balanced, unbalanced, or distorted grids.
6.1. Balanced Grids
When the grid voltage is balanced, the MMC control has external and internal control loops.
The external control loop of the MMC can regulate two variables (Figure 13). The first can be the DC
voltage vDC or the active power P, while the second can be the reactive power Q or the AC voltage
vAC [34,35]. The outputs of the external control loops are the grid current references in dq axes, id
∗
and iq
∗
.
The internal control loop may be a current loop (Figure 13a) or a voltage loop (Figure 13b). In the
first case, from id
∗
and iq
∗
, the current references of the three phases ia
∗
, ib
∗
, and ic
∗
are generated,
which are the inputs of the current modulator. It calculates the number of SMs in the ON state in each
arm nup and nlow, so the ordering algorithm determines the ON/OFF state of each SM. In the second
case, two PI regulators and decoupling equations are used to generate the converter voltage references
in the dq axes, vd
∗ and vq
∗.
Energies 2017, 10, 1709 14 of 25
Usually, the AC part is considered to be a balanced three-phase system containing only the
fundamental harmonic. During mains failures, the AC voltage behaves as an unbalanced system,
whose unbalance is greater or smaller depending on the distance at which the fault occurred and the
type of fault. The grid may also contain harmonics of several frequencies that affect the operation of
the converter and the current generated in AC. The following are schemes for controlling MMCs
when connecting to balanced, unbalanced, or distorted grids.
6.1. Balanced Grids
When the grid voltage is balanced, the MMC control has external and internal control loops.
The external control loop of the MMC can regulate two variables (Figure 13). The first can be the DC
voltage or the active power , while the second can be the reactive power or the AC voltage
[34,35]. The outputs of the external control loops are the grid current references in axes, ∗
and ∗
.
The internal control loop may be a current loop (Figure 13a) or a voltage loop (Figure 13b). In
the first case, from ∗
and ∗
, the current references of the three phases ∗
, ∗
, and ∗
are
generated, which are the inputs of the current modulator. It calculates the number of SMs in the ON
state in each arm and , so the ordering algorithm determines the ON/OFF state of each SM.
In the second case, two PI regulators and decoupling equations are used to generate the converter
voltage references in the axes, ∗
and ∗
.
Figure 13. Control of MMC in balanced systems: (a) with current modulator; (b) with voltage
modulator.
Figure 13. Control of MMC in balanced systems: (a) with current modulator; (b) with voltage modulator.
15. Energies 2017, 10, 1709 15 of 26
6.2. Unbalanced Grids
When the grid voltage is unbalanced, the positive and negative sequence components must be
controlled separately and, finally, the result of each control must be added to obtain the converter
reference. According to whether this reference is a current or a voltage, a current or voltage modulator
will be used, respectively [36].
Voltage unbalances occur due to grid voltage failures. During them, the grid codes indicate that
active power cannot be injected into the grid, and reactive power can only be injected to support
the restoration of the grid voltage. Therefore, the control references, both with current modulator
(Figure 14) and with voltage modulator (Figure 15), will be:
(1) For positive sequence, active power Pp must be zero, so the reference of the positive sequence
current on the d axis must be zero, idp
∗
= 0.
(2) A PI regulator is used to try to reset the positive sequence grid voltage to its nominal value vp
∗,
by the action of the positive sequence reactive power Qp, which is controlled by the positive
sequence current in the q axis, iqp
∗
.
(3) For the negative sequence, the active power Pn must be zero, so the reference of the negative
sequence current on the d axis must be zero, idn
∗
= 0.
(4) A PI regulator is used to try to establish the negative-sequence grid voltage to zero, vn
∗ = 0,
by the action of the negative sequence reactive power Qn, which is controlled by the negative
sequence current on the q axis, iqn
∗
.
It is necessary to use an algorithm that calculates the positive and negative sequence components
of the grid voltages and currents (the latter only for the case of a voltage modulator), as well as the
angle θ of the positive sequence dq reference. An algorithm very usually used is the so called Delayed
Signal Cancellation (DSC) [37,38].
When a current modulator is used, the references of the positive (iap
∗
, ibp
∗
, icp
∗
) and negative
(ian
∗
, ibn
∗
, icn
∗
) sequences are added to obtain the current reference of each phase (ia
∗
, ib
∗
, ic
∗
)
(Figure 14). When a voltage modulator is used, current references must be converted to voltage
references, for positive and negative sequences, by two PI regulators and axis decoupling equations.
Finally, the voltage references of the three-phases, for positive (voap
∗, vobp
∗, vocp
∗) and negative
(voan
∗ , vobn
∗ , vocn
∗ ) sequences, are added to obtain the voltage reference of each phase (va
∗, vb
∗, vc
∗).
Energies 2017, 10, 1709 15 of 25
6.2. Unbalanced Grids
When the grid voltage is unbalanced, the positive and negative sequence components must be
controlled separately and, finally, the result of each control must be added to obtain the converter
reference. According to whether this reference is a current or a voltage, a current or voltage
modulator will be used, respectively [36].
Voltage unbalances occur due to grid voltage failures. During them, the grid codes indicate that
active power cannot be injected into the grid, and reactive power can only be injected to support the
restoration of the grid voltage. Therefore, the control references, both with current modulator
(Figure 14) and with voltage modulator (Figure 15), will be:
(1). For positive sequence, active power must be zero, so the reference of the positive sequence
current on the axis must be zero, ∗
= 0.
(2). A PI regulator is used to try to reset the positive sequence grid voltage to its nominal value ∗
,
by the action of the positive sequence reactive power , which is controlled by the positive
sequence current in the axis, ∗
.
(3). For the negative sequence, the active power must be zero, so the reference of the negative
sequence current on the axis must be zero, ∗
= 0.
(4). A PI regulator is used to try to establish the negative-sequence grid voltage to zero, ∗
= 0, by
the action of the negative sequence reactive power , which is controlled by the negative
sequence current on the axis, ∗
.
It is necessary to use an algorithm that calculates the positive and negative sequence
components of the grid voltages and currents (the latter only for the case of a voltage modulator), as
well as the angle of the positive sequence reference. An algorithm very usually used is the so
called Delayed Signal Cancellation (DSC) [37,38].
When a current modulator is used, the references of the positive ( ∗
, ∗
, ∗
) and negative
( ∗
, ∗
, ∗
) sequences are added to obtain the current reference of each phase ( ∗
, ∗
, ∗
)
(Figure 14). When a voltage modulator is used, current references must be converted to voltage
references, for positive and negative sequences, by two PI regulators and axis decoupling equations.
Finally, the voltage references of the three-phases, for positive ( ∗
, ∗
, ∗
) and negative
( ∗
, ∗
, ∗
) sequences, are added to obtain the voltage reference of each phase
( ∗
, ∗
, ∗
).
Figure 14. Control of MMC in unbalanced systems with current modulator [36].
Figure 14. Control of MMC in unbalanced systems with current modulator [36].
16. Energies 2017, 10, 1709 16 of 26
Energies 2017, 10, 1709 16 of 25
Figure 15. Control of the MMC in unbalanced systems with voltage modulator [36].
6.3. Distorted Grids
In a 3-phase grid-connected system with two degrees of freedom (three wire connection), and
the utility grid voltages with fundamental frequency and harmonics at 6 ± 1 , =
1,2,3,4, …, it is mandatory to implement a control strategy for the inner current loop that must be able
to track the fundamental frequency of the reference signal command and reject the harmonic
perturbations in order to attain a zero steady-state error.
When the sequence of the fundamental frequency is positive/negative, it is well-known that the
sequence of the harmonics 5 , 11 , 17 , etc., will be negative/positive, meanwhile the sequence
for the 7 , 13 , 19 , etc., ones will be positive/negative. In addition, knowing that this system
has two degrees of freedom, it can be transformed into a 2-phase system in the orthonormal and
axes so as to be able to exert a decoupled control of the instantaneous active and reactive powers
[39]. Then, the components of the output currents ( , ) will have the 6 harmonics, =
0,1,2,3,4, …, while the components ( , ) will have the same fundamental frequency and its
harmonics at 6 ± 1 , = 1,2,3,4, … [40].
According to the internal model principle (see Appendix C of [41]), and when the poles of the
closed-loop transfer function are in the left-half of the complex plane (stable system), a PI regulator
can only track DC reference signals and reject DC perturbations, while a Proportional-Resonant (PR)
regulator can track and reject sinusoidal signals with frequency ± , that is, of both positive and
negative sequence, if the resonant part of the PR regulator is tuned to . If the current control is
exerted in the axes using two PI regulators, the harmonic perturbations 6 ( = 1,2,3,4, …)
cannot be cancelled unless a feedforward scheme for the cross-coupling terms and the utility grid
voltage are used; but the feedforward scheme will work properly if the switching frequency of the
MMC is high enough to allow a higher controller bandwidth to avoid the delay effects.
Consequently, the cost of the electronic conditioner circuit will be increased and the use of a
powerful microcontroller will also be mandatory.
To deal with the restrictions of PI regulators mentioned above, several strategies can be used to
implement the inner current controller based on selective harmonic compensation schemes and
Figure 15. Control of the MMC in unbalanced systems with voltage modulator [36].
6.3. Distorted Grids
In a 3-phase grid-connected system with two degrees of freedom (three wire connection), and the
utility grid voltages with fundamental frequency ω1 and harmonics at (6n ± 1)ω1, n = 1, 2, 3, 4, . . ., it
is mandatory to implement a control strategy for the inner current loop that must be able to track the
fundamental frequency ω1 of the reference signal command and reject the harmonic perturbations in
order to attain a zero steady-state error.
When the sequence of the fundamental frequency is positive/negative, it is well-known that the
sequence of the harmonics 5ω1, 11ω1, 17ω1, etc., will be negative/positive, meanwhile the sequence
for the 7ω1, 13ω1, 19ω1, etc., ones will be positive/negative. In addition, knowing that this system has
two degrees of freedom, it can be transformed into a 2-phase system in the orthonormal dq and αβ
axes so as to be able to exert a decoupled control of the instantaneous active and reactive powers [39].
Then, the dq components of the output currents (id, iq) will have the 6nω1 harmonics, n = 0, 1, 2, 3, 4, . . .,
while the αβ components (iα, iβ) will have the same fundamental frequency ω1 and its harmonics at
(6n ± 1)ω1, n = 1, 2, 3, 4, . . . [40].
According to the internal model principle (see Appendix C of [41]), and when the poles of the
closed-loop transfer function are in the left-half of the complex plane (stable system), a PI regulator
can only track DC reference signals and reject DC perturbations, while a Proportional-Resonant (PR)
regulator can track and reject sinusoidal signals with frequency ±ωo, that is, of both positive and
negative sequence, if the resonant part of the PR regulator is tuned to ωo. If the current control is exerted
in the dq axes using two PI regulators, the harmonic perturbations 6nω1 (n = 1, 2, 3, 4, . . .) cannot be
cancelled unless a feedforward scheme for the cross-coupling terms and the utility grid voltage are
used; but the feedforward scheme will work properly if the switching frequency of the MMC is high
enough to allow a higher controller bandwidth to avoid the delay effects. Consequently, the cost of
the electronic conditioner circuit will be increased and the use of a powerful microcontroller will also
be mandatory.
17. Energies 2017, 10, 1709 17 of 26
To deal with the restrictions of PI regulators mentioned above, several strategies can be used to
implement the inner current controller based on selective harmonic compensation schemes and using
low-cost commercial microcontrollers [42]. Among them, two strategies capable of tracking sinusoidal
reference signals and cancelling sinusoidal perturbations are explained below. Both strategies employ
resonant filters tuned at the frequencies to be compensated:
(1) Control in αβ − dq axes: In this control, PR regulators are applied to the current errors in αβ
axes (eαβ) to track the fundamental reference signal, while the compensation of the harmonics
6nω1 (n = 1, 2, 3, 4, . . .) is exerted on the current errors in the dq axes (edq, where the αβ → dq
transformation is applied), cascading several resonant filters tuned to these harmonic frequencies.
After the application of the inverse transform dq → αβ, all the αβ signals are added to obtain the
reference output voltages (voα
∗, voβ
∗) to feed the VSC modulator [43] (see Figure 16a).
(2) Control in αβ axes: For this, two PR regulators are used for the current errors (eαβ) to track the
reference signal with the fundamental frequency ω1, and several resonant filters tuned to the
harmonics to be compensated (6n ± 1)ω1, n = 1, 2, 3, 4, . . ., are cascaded in each axis. The output
of both the PR regulators and the resonant filters in the αβ axes are added to obtain the reference
output voltages (voα
∗, voβ
∗) needed to feed the VSC modulator [44,45] (see Figure 16b).
Energies 2017, 10, 1709 17 of 25
using low-cost commercial microcontrollers [42]. Among them, two strategies capable of tracking
sinusoidal reference signals and cancelling sinusoidal perturbations are explained below. Both
strategies employ resonant filters tuned at the frequencies to be compensated:
(1) Control in − axes: In this control, PR regulators are applied to the current errors in
axes ( ) to track the fundamental reference signal, while the compensation of the harmonics
6 ( = 1,2,3,4, …) is exerted on the current errors in the axes ( , where the →
transformation is applied), cascading several resonant filters tuned to these harmonic
frequencies. After the application of the inverse transform → , all the signals are
added to obtain the reference output voltages ( ∗
, ∗
) to feed the VSC modulator [43] (see
Figure 16a).
(2) Control in axes: For this, two PR regulators are used for the current errors ( ) to track the
reference signal with the fundamental frequency , and several resonant filters tuned to the
harmonics to be compensated 6 ± 1 , = 1,2,3,4, …, are cascaded in each axis. The output
of both the PR regulators and the resonant filters in the axes are added to obtain the
reference output voltages ( ∗
, ∗
) needed to feed the VSC modulator [44,45] (see Figure
16b).
(a)
(b)
Figure 16. Control of the MMC in a distorted grid: (a) in αβ − dq axes; (b) in αβ axes.
18. Energies 2017, 10, 1709 18 of 26
Finally, it is worth noting that the above strategies have a similar performance regarding their
harmonic compensation capability. So, the ease of implementation, together with the execution time of
the corresponding discrete algorithms, will lead to the best solution [42].
7. Applications
The main application of the MMC is HVDC transmission, although it has also been used in
other applications such as the distribution static synchronous compensator (D-STATCOM) and low
voltage inverter.
7.1. HVDC
The converter topologies used in HVDC were LCC first and later VSC. MMCs are currently
being used, and they are being installed by major power companies such as Siemens [16], ABB [46] or
Alstom [47]. HVDCs are used for the interconnection of high voltage AC grids and the connection of
offshore wind farms to land (the latter subject will be looked at later).
Table 3 shows some of the projects that use MMC technology, including Trans Bay Cable, which
was the first HVDC project to use MMC. Most converters use a topology with a large number of
cascaded HB-SMs in a symmetrical monopolar configuration. The vast majority of offshore applications
created or planned in recent years have been in Germany, linked to the creation of numerous offshore
wind farms. For an HVDC voltage level of ±320 kV, as in DolWin1 (Figure 17), n = 38 HF-SM (formed
by IGBT) per arm are usually required. Each SM switches to a low frequency of approximately 150 Hz
so the losses are small, but the stepwise switching of the SMs makes the effective frequency per phase
greater than 10 kHz, greatly reducing the filtering needs in AC.
The connection of AC grids through HVDC occurs in several circumstances:
(1) Connection of different frequency grids (50 and 60 Hz).
(2) Connecting asynchronous grids.
(3) Connecting islands with the mainland.
(4) Connection of continental grids that have less distance by sea than by land.
(5) Connection of weak grids in which the converters provide grid support service by reactive
power injection.
Energies 2017, 10, 1709 18 of 25
Figure 16. Control of the MMC in a distorted grid: (a) in − axes; (b) in axes.
Finally, it is worth noting that the above strategies have a similar performance regarding their
harmonic compensation capability. So, the ease of implementation, together with the execution time
of the corresponding discrete algorithms, will lead to the best solution [42].
7. Applications
The main application of the MMC is HVDC transmission, although it has also been used in
other applications such as the distribution static synchronous compensator (D-STATCOM) and low
voltage inverter.
7.1. HVDC
The converter topologies used in HVDC were LCC first and later VSC. MMCs are currently
being used, and they are being installed by major power companies such as Siemens [16], ABB [46]
or Alstom [47]. HVDCs are used for the interconnection of high voltage AC grids and the connection
of offshore wind farms to land (the latter subject will be looked at later).
Table 3 shows some of the projects that use MMC technology, including Trans Bay Cable, which
was the first HVDC project to use MMC. Most converters use a topology with a large number of
cascaded HB-SMs in a symmetrical monopolar configuration. The vast majority of offshore
applications created or planned in recent years have been in Germany, linked to the creation of
numerous offshore wind farms. For an HVDC voltage level of ±320 kV, as in DolWin1 (Figure 17), n
= 38 HF-SM (formed by IGBT) per arm are usually required. Each SM switches to a low frequency of
approximately 150 Hz so the losses are small, but the stepwise switching of the SMs makes the
effective frequency per phase greater than 10 kHz, greatly reducing the filtering needs in AC.
The connection of AC grids through HVDC occurs in several circumstances:
(1) Connection of different frequency grids (50 and 60 Hz).
(2) Connecting asynchronous grids.
(3) Connecting islands with the mainland.
(4) Connection of continental grids that have less distance by sea than by land.
(5) Connection of weak grids in which the converters provide grid support service by reactive
power injection.
Figure 17. Overview of the DolWin1 project.
Table 3. Projects using modular multilevel converter (MMC) technology.
Project Year
Power
(MW)
DC
(kV)
AC (kV) Application Manufacturers
Trans Bay
Cable
2010 400 ±200 230 Grid connection Siemens
COBRAcable 2019 700 ±320 400 Grid connection Siemens
North Sea Link 2021 1400 ±525
Kvilldal: 420
Blyth: 400
Grid connection ABB
Caithness 2018 1200 ±320 Spittal: 275 Grid connection ABB
Figure 17. Overview of the DolWin1 project.
19. Energies 2017, 10, 1709 19 of 26
Table 3. Projects using modular multilevel converter (MMC) technology.
Project Year Power (MW) DC (kV) AC (kV) Application Manufacturers
Trans Bay Cable 2010 400 ±200 230 Grid connection Siemens
COBRAcable 2019 700 ±320 400 Grid connection Siemens
North Sea Link 2021 1400 ±525
Kvilldal: 420
Blyth: 400
Grid connection ABB
Caithness Moray 2018 1200 ±320
Spittal: 275
Blackhillock: 400
Grid connection ABB
BorWin1 2011 400 ±150
Platform BorWin Alpha: 170
Diele: 380
Offshore wind farm ABB
BorWin2 2015 800 ±300
Onshore: 380
Offshore: 155
Offshore wind farm Siemens
BorWin3 2019 900 ±320 - Offshore wind farm Siemens
DolWin1 2015 800 ±320
Dörpen West: 380
Dolwin Alpha: 155
Offshore wind farm ABB
DolWin2 2016 916 ±320
Dörpen West: 380
DolWin Beta: 155
Offshore wind farm ABB
DolWin3 2017 900 ±320 - Offshore wind farm GE-Alstom
HelWin1 2015 576 ±250
Onshore: 380
Offshore: 155
Offshore wind farm Siemens
HelWin2 2015 690 ±320 400 Offshore wind farm Siemens
SylWin1 2015 864 ±320 400 Offshore wind farm Siemens
ULTRANET 2019 2000 ±380 400 Grid connection Siemens
INELFE 2015 2000 ±320 400 Grid connection Siemens
Skagerrak Pole4 2014 700 ±500 700 Grid connection ABB
7.2. D-STATCOM
Medium voltage distribution lines frequently have problems of reactive compensation, voltage
variations, unbalances, and harmonics. Voltage variations occur in weak lines due to the starting
or stopping of large motors or to load excess/defect. The unbalances are due to the application of
single-phase loads and asymmetric faults. The harmonics are motivated by the presence of nonlinear
loads and the saturation of transformers. The D-STATCOM is used to improve this situation through
its great capacity for reactive compensation and voltage regulation.
The H-bridge topology has usually been used for D-STATCOM due to the ease of obtaining a high
number of levels, but it has limitations in situations of load or network unbalances. Therefore, solutions
based on MMC have been proposed as they have more degrees of freedom to carry out the control and
greater capacity of power [48,49].
The use of an MMC with a large number of levels allows coupling to the grid without the need
of a transformer (Figure 18). An external capacitor that maintains the DC voltage is not necessary, as
that function is carried out by SM capacitors. An interesting concrete application for the MMC-based
D-STATCOM could be the improvement of power quality in railway traction systems.
20. Energies 2017, 10, 1709 20 of 26
solutions based on MMC have been proposed as they have more degrees of freedom to carry out the
control and greater capacity of power [48,49].
The use of an MMC with a large number of levels allows coupling to the grid without the need
of a transformer (Figure 18). An external capacitor that maintains the DC voltage is not necessary, as
that function is carried out by SM capacitors. An interesting concrete application for the MMC-based
D-STATCOM could be the improvement of power quality in railway traction systems.
Figure 18. MMC distribution static synchronous compensator (D-STATCOM) coupled to the grid
without transformer.
Figure 18. MMC distribution static synchronous compensator (D-STATCOM) coupled to the grid
without transformer.
7.3. Low Voltage Multi-Level Inverter
MMCs have been used in low voltage DC (LVDC) applications and generator drives.
Some applications such as electrical supply, recharging of electric vehicles, and aerospace require high
levels of performance, power quality, and electro-magnetic interference (EMI). They can be achieved
by MMCs made with silicon carbide metal-oxide semiconductor field-effect transistor (SiC MOSFET)
and Si MOSFET [50]. The use of MOSFET instead of IGBT is able to reduce switching losses, while
the use of synchronous rectification reduces conduction losses [51]. In [52], an MMC has been used
as an interface with the power grid of a Smart Home that includes photovoltaic generation, energy
storage, and recharging of electric vehicle, all connected to a DC bus. The MOSFET MMC topology has
been compared with the classic multilevel topologies, with advantages such as filter reduction, simpler
redundancy, and reduced power losses, making it a more appropriate topology for Smart Homes.
In [53], an MMC has been used as AC/DC converter to control a wind generator without gear box.
Multilevel converters are suitable for this application because of their lower harmonic content, as well
as the reduction of semiconductor stress and electromagnetic disturbances. MMC has such advantages
over classical multilevel topologies as its modular design, simple structure, ease of increasing the
number of levels, faster replacement of faulty modules, and reduced number of semiconductors.
8. Integration of Offshore Wind Farms
8.1. Global Control of the HVDC MMC
In an HVDC system, the control of each converter interacts with the other, although they are
different [36,54]. Whereas the grid side MMC has to keep the DC voltage within a range of values,
the wind farm side MMC has to get the maximum power from the wind park, where other electronic
converters take the wind turbines to the optimum operation points for each type of wind.
There are two possibilities to implement the control of an HVDC system: using or not using
communications. Using communications is the preferable solution in multiterminal HVDC networks
because it enables complex coordinated control systems to carry out the necessary tasks, taking into
account a number of voltages and currents.
In point to point topology, a simpler control strategy, with no communications, can be chosen;
this can be used even with multiterminal topologies [54]. In this strategy, the control of the grid side
21. Energies 2017, 10, 1709 21 of 26
MMC is based on a droop technique: as the DC voltage increases, the electric current injected into the
grid also increases, so as to keep the voltage within a range of values. The limit is the semiconductors
rated current.
The control of the wind park side MMC works by extracting the whole electric power generated
by the wind farm for every wind speed, within two limits: the semiconductor rated current and the
maximum DC bus voltage. The former cannot be exceeded in any case, whereas the latter forces the
current taken from the wind park to reduce progressively once a certain limit of DC voltage is reached,
once again using a droop based technique.
8.2. Power Collection in Wind Farms
The electric circuit used in wind farms to collect the energy generated by wind turbines comprises
several feeders connected to a MV hub in several possible configurations. Also, wind generators are
often connected to each other to form a string. The whole system is known as a collection system.
A number of collection systems have been proposed in the technical literature for offshore applications,
making use of different wind generator arrangements, such as radial, single-sided ring, double-sided
ring, star, etc.
8.2.1. Radial Arrangement
This configuration, Figure 19a is the simplest possible arrangement of wind generators. In this
set up, the wind generators within the same feeder are connected in series, making up a string.
The maximum number of generators that can be connected to each feeder depends on the submarine
cable cross-section and the generators’ rated power. The main advantage is the low cost, while the
main drawback comes from the fact that, if a generator close to the MV hub fails, the whole string is
disconnected, losing the power generated by all the generators that make up the string [55,56].
Energies 2017, 10, 1709 21 of 25
8.2.1. Radial Arrangement
This configuration, Figure 19a, is the simplest possible arrangement of wind generators. In this
set up, the wind generators within the same feeder are connected in series, making up a string. The
maximum number of generators that can be connected to each feeder depends on the submarine
cable cross-section and the generators’ rated power. The main advantage is the low cost, while the
main drawback comes from the fact that, if a generator close to the MV hub fails, the whole string is
disconnected, losing the power generated by all the generators that make up the string [55,56].
Figure 19. Collection systems for offshore applications: (a) radial collection configuration; (b)
single-sided ring configuration; (c) double-sided ring configuration; and (d) star configuration.
8.2.2. Single-Sided Ring Arrangement
By using an additional cable run, an extra security measure can be added to the radial setup at
the expense of a long return cable of a large cross-section, capable of transporting all the electric
power generated in the string, Figure 19b. The new cable connects the outermost wind generator to
the MV hub. In case of a cable failure, or when a circuit breaker opens the ring, the electric power
generated in the rest of the wind turbines can be transported to the MV hub using the return cable.
8.2.3. Double-Sided Ring Arrangement
In this configuration, Figure 19c, the last wind generator belonging to a string is connected to
the last wind generator of the next string. In case of a cable failure, or when the string is opened by a
circuit breaker, the total power generated by the remaining connected generators has to be
Figure 19. Collection systems for offshore applications: (a) radial collection configuration;
(b) single-sided ring configuration; (c) double-sided ring configuration; and (d) star configuration.
8.2.2. Single-Sided Ring Arrangement
By using an additional cable run, an extra security measure can be added to the radial setup at
the expense of a long return cable of a large cross-section, capable of transporting all the electric power
generated in the string, Figure 19b. The new cable connects the outermost wind generator to the MV
22. Energies 2017, 10, 1709 22 of 26
hub. In case of a cable failure, or when a circuit breaker opens the ring, the electric power generated in
the rest of the wind turbines can be transported to the MV hub using the return cable.
8.2.3. Double-Sided Ring Arrangement
In this configuration, Figure 19c, the last wind generator belonging to a string is connected to the
last wind generator of the next string. In case of a cable failure, or when the string is opened by a circuit
breaker, the total power generated by the remaining connected generators has to be transported
through the other string to the MV hub. In consequence, the rated current of both cable strings must
be oversized to allow bidirectional power flow in case of cable failure [55–57].
The redundancy feature provided by ring configurations makes sense, particularly in offshore
installations, where the repair downtimes are significantly longer when compared to those onshore
and the repair costs are much higher.
8.2.4. Star Arrangement
This configuration, Figure 19d, is intended to reduce the cable ratings and provide the wind farm
with high reliability (in case of a cable failure, only one wind generator is lost). The most important
drawback is the complex switchgear requirement at the center of the star [55–57].
All the aforementioned AC collection systems use utility frequency transformers on the off-shore
transmission platform. This might be a drawback, since they are big, heavy, and require a large support
structure, which entails a high transport and installation cost. AC collection systems also need reactive
power compensation devices and power quality filters, which take up a lot of space on the offshore
platform [58].
New developments are taking DC collector systems into consideration in wind and wave
farms [58–60]. They present some advantages, such as needing less space for the DC cables on
the platform and a lower weight than for those of the equivalent AC cables; in addition, they do not
need reactors for reactive power compensation either. The intermediate DC link also decouples the
wind farm from the mainland grid, thus increasing the capability of the wind turbines to withstand
faults. However, DC collector systems, as well as AC systems, present some drawbacks, such as, for
example, DC protection is still expensive.
9. Conclusions
MMC technology has shifted towards the classical topologies of LCC and VSC, and has been
established as a preferred solution for carrying out HVDC links by the main installation companies.
It has also been proposed, however, as a solution for the realization of multilevel converters in MV and
LV. The most important high voltage applications are the connection of electric energy transport grids
and the connection of large offshore wind farms to the terrestrial grid. The increase of its implantation
in applications of MV and LV is predictable in the future, due to its good characteristics.
Although the topology commonly used for SMs is HB, it does not have the capability to reduce
DC short-circuits. The FB topology, also used by the manufacturers, has the ability to eliminate DC
faults, with other topologies that can be used for this purpose. This will become of great importance in
the future when building multi-terminal HVDC grids.
For the correct operation of MMC, the capacitor voltage of the SMs must remain constant.
The capacitors can be charged or discharged by arm currents, by turning ON the appropriate SM.
The most commonly used balancing method was explained in detail. Other methods that can be found
in the literature were briefly presented.
The voltage or current modulators are responsible for making the voltage or current of the
converter follow their references. Four voltage modulators and two current modulators were presented
in detail. The former are more commonly used because they require a lower switching frequency and
allow the design of the AC filter to be simpler. The latter have been proposed for applications in which
the speed of response is more important.
23. Energies 2017, 10, 1709 23 of 26
The external loop regulates DC link voltage and reactive power, using voltage control or current
control schemes. When imbalances occur, the regulation prevents the injection of active power and
allows the injection of reactive power to help restore the mains voltage. The low order harmonics
of the mains voltages will be introduced into the internal current loop in the form of disturbances,
distorting the output currents. To avoid this, proportional-resonant regulators tuned to the frequency
of the fundamental, as well as to the frequencies of the harmonics (or their equivalents in dq axes) have
been proposed.
The most important application of the MMC is in HVDC transmission, to make marine
connections (land to land, wind farm to land), and the interconnection of different frequency grids
and asynchronous grids. Other applications of MV and LV were also presented. In the future, it is
expected that MMC will be the technology used in new HVDC installations, that it will greatly increase
its presence in commercial MV applications, and that it will increase its presence in LV applications at
the research level.
A very important application is the connection of offshore wind farms to the transmission grid.
End stations can be synchronized using communication systems or work independently following
specific rules. In the future, research on how to connect individual turbines and turbine groups to
obtain HVDC is foreseeable.
As the penetration of the HVDC transmission increases, the need for research on multi-terminal
grid connection, oriented to the control of load flow and to the protection against faults, will increase.
Author Contributions: All authors contributed collectively to the manuscript preparation and approved the
final manuscript.
Conflicts of Interest: The authors declare no conflict of interest.
References
1. Montilla-DJesus, M.; Santos-Martin, D.; Arnaltes, S.; Castronuovo, E.D. Optimal reactive power allocation in
an offshore wind farms with LCC-HVdc link connection. Renew. Energy 2012, 40, 157–166. [CrossRef]
2. Larruskain, D.M.; Zamora, I.; Abarrategui, O.; Iturregi, A. VSC-HVDC configurations for converting AC
distribution lines into DC lines. Int. J. Electr. Power Energy Syst. 2014, 54, 589–597. [CrossRef]
3. Aragues-Penalba, M.; Egea-Alvarez, A.; Gomis-Bellmunt, O.; Sumper, A. Optimum voltage control for loss
minimization in HVDC multi-terminal transmission systems for large offshore wind farms. Electr. Power
Syst. Res. 2012, 89, 54–63. [CrossRef]
4. Chaves, M.; Margato, E.; Silva, J.F.; Pinto, S.F.; Santana, J. HVDC transmission systems: Bipolar back-to-back
diode clamped multilevel converter with fast optimum-predictive control and capacitor balancing strategy.
Electr. Power Syst. Res. 2011, 81, 1436–1445. [CrossRef]
5. Marquardt, R. Modular Multilevel Converter topologies with DC-Short circuit current limitation.
In Proceedings of the 8th International Conference on Power Electronics—ECCE Asia, Jeju, Korea,
30 May–3 June·2011; pp. 1425–1431.
6. Lesnicar, A.; Marquardt, R. An innovative modular multilevel converter topology suitable for a wide power
range. In Proceedings of the Power Tech Conference, Bologna, Italy, 23–26 June 2003.
7. Rohner, S.; Bernet, S.; Hiller, M.; Sommer, R. Modulation, losses, and semiconductor requirements of modular
multilevel converters. IEEE Trans. Ind. Electron. 2010, 57, 2633–2642. [CrossRef]
8. Zhang, M.; Huang, L.; Yao, W.; Lu, Z. Circulating harmonic current elimination of a CPS-PWM-based
modular multilevel converter with a plug-in repetitive controller. IEEE Trans. Power Electron. 2014, 29,
2083–2097. [CrossRef]
9. Song, Q.; Liu, W.; Li, X.; Rao, H.; Xu, S.; Li, L. A steady-state analysis method for a modular multilevel
converter. IEEE Trans. Power Electron. 2013, 28, 3702–3713. [CrossRef]
10. Moon, J.W.; Kim, C.S.; Park, J.W.; Kang, D.W.; Kim, J.M. Circulating current control in MMC under the
unbalanced voltage. IEEE Trans. Power Deliv. 2013, 28, 1952–1959. [CrossRef]
11. Moranchel, M.; Bueno, E.; Sanz, I.; Rodríguez, F.J. New approaches to circulating current controllers for
modular multilevel converters. Energies 2017, 10, 86. [CrossRef]
24. Energies 2017, 10, 1709 24 of 26
12. Saad, H.; Peralta, J.; Dennetière, S.; Mahseredjian, J.; Jatskevich, J.; Martinez, J.A.; Davoudi, A.; Saeedifard, M.;
Sood, V.; Wang, X.; et al. Dynamic averaged and simplified models for MMC-based HVDC transmission
systems. IEEE Trans. Power Deliv. 2013, 28, 1723–1730. [CrossRef]
13. Peralta, J.; Saad, H.; Dennetière, S.; Mahseredjian, J.; Nguefeu, S. Detailed and averaged models for a 401-level
MMC–HVDC system. IEEE Trans. Power Deliv. 2012, 27, 1501–1508. [CrossRef]
14. Gnanarathna, U.N.; Gole, A.M.; Jayasinghe, R.P. Efficient modeling of modular multilevel HVDC converters
(MMC) on electromagnetic transient simulation programs. IEEE Trans. Power Deliv. 2011, 26, 316–324.
[CrossRef]
15. Liu, C.; Lin, X.; Li, H.; Cheng, X.; Li, G. Sub-module component developed in CBuilder for MMC control
and protection test in RTDS. Int. J. Electr. Power Energy Syst. 2014, 56, 198–208.
16. Davies, M.; Dommaschk, M.; Dorn, J.; Lang, J.; Retzmann, D.; Soerangr, D. HVDC PLUS—Basics and Principle
of Operation. Available online: https://www.energy.siemens.com/br/pool/br/transmissao-de-energia/
transformadores/hvdc-plus-basics-and-principle-of-operation.pdf (accessed on 11 September 2017).
17. Li, X.; Song, Q.; Liu, W.; Rao, H.; Xu, S.; Li, L. Protection of Nonpermanent Faults on DC Overhead Lines in
MMC-Based HVDC Systems. IEEE Trans. Power Deliv. 2013, 28, 483–490. [CrossRef]
18. Saeedifard, M.; Iravani, R. Dynamic performance of a modular multilevel back-to-back HVDC system.
IEEE Trans. Power Deliv. 2010, 25, 2903–2912. [CrossRef]
19. Hagiwara, M.; Akagi, H. Control and experiment of pulsewidth-modulated modular multilevel converters.
IEEE Trans. Power Electron. 2009, 24, 1737–1746. [CrossRef]
20. Qin, J.; Saeedifard, M. Predictive control of a modular multilevel converter for a back-to-back HVDC system.
IEEE Trans. Power Deliv. 2012, 27, 1538–1547.
21. Deng, F.; Chen, Z. A control method for voltage balancing in modular multilevel converters. IEEE Trans.
Power Electron. 2014, 29, 66–76. [CrossRef]
22. Moranchel, M.; Huerta, F.; Sanz, I.; Bueno, E.; Rodríguez, F.J. A comparison of modulation techniques for
modular multilevel converters. Energies 2016, 9, 1091. [CrossRef]
23. Agelidis, V.; Calais, M. Application specific harmonic performance evaluation of multicarrier PWM
techniques. In Proceedings of the 29th Annual IEEE Power Electronics Specialists Conference, Fukuoka,
Japan, 17–22 May 1998; Volume 1, pp. 172–178.
24. De Pablo, S.; Rey-Boué, A.B.; Herrero, L.C.; Martínez, F. Hexagon based algorithm for space vector
modulation on multilevel voltage source inverters. In Proceedings of the IEEE International Symposium on
Industrial Electronics (ISIE), Bari, Italy, 4–7 July 2010.
25. Celanovic, N.; Boroyevich, D. A fast space-vector modulation algorithm for multilevel three-phase converters.
IEEE Trans. Ind. Appl. 2001, 37, 637–641. [CrossRef]
26. Yao, W.; Hu, H.; Lu, Z. Comparisons of Space-Vector Modulation and Carrier-Based Modulation of Multilevel
Inverter. IEEE Trans. Power Electron. 2008, 23, 45–51. [CrossRef]
27. Saeedifard, M.; Iravani, R.; Pou, J. A Space Vector Modulation Strategy for a Back-to-Back Five-Level HVDC
Converter System. IEEE Trans. Ind. Electron. 2009, 56, 452–466. [CrossRef]
28. Deng, Y.; Harley, R.G. Space-Vector Versus Nearest-Level Pulse Width Modulation for Multilevel Converters.
IEEE Trans. Power Electron. 2015, 30, 2962–2974. [CrossRef]
29. Deng, Y.; Wang, Y.; Teo, K.H.; Harley, R.G. A Simplified Space Vector Modulation Scheme for Multilevel
Converters. IEEE Trans. Power Electron. 2016, 31, 1873–1886. [CrossRef]
30. Tu, Q.; Xu, Z. Impact of Sampling Frequency on Harmonic Distortion for Modular Multilevel Converter.
IEEE Trans. Power Deliv. 2011, 26, 298–306. [CrossRef]
31. Meshram, P.M.; Borghate, V.B. A Simplified Nearest Level Control (NLC) Voltage Balancing Method for
Modular Multilevel Converter (MMC). IEEE Trans. Power Electron. 2015, 30, 450–462. [CrossRef]
32. Hu, P.; Jiang, D. A Level-Increased Nearest Level Modulation Method for Modular Multilevel Converters.
IEEE Trans. Power Electron. 2015, 30, 1836–1842. [CrossRef]
33. Martinez-Rodrigo, F.; de Pablo, S.; Herrero-de Lucas, L.C. Current control of a modular multilevel converter
for HVDC applications. Renew. Energy 2015, 83, 318–331. [CrossRef]
34. Abildgaard, E.N.; Molinas, M. Modelling and Control of the Modular Multilevel Converter (MMC).
Energy Procedia 2012, 20, 227–236. [CrossRef]
35. Kim, S.K.; Jeon, J.H.; Ahn, J.B.; Lee, B.; Kwon, S.H. Frequency-Shift Acceleration Control for Anti-Islanding
of a Distributed-Generation Inverter. IEEE Trans. Ind. Electron. 2010, 57, 494–504. [CrossRef]
25. Energies 2017, 10, 1709 25 of 26
36. Ramirez, D.; Martinez-Rodrigo, F.; de Pablo, S.; Herrero-de Lucas, L.C. Assessment of a non linear current
control technique applied to MMC-HVDC during grid disturbances. Renew. Energy 2017, 101, 945–963.
[CrossRef]
37. Le, T.N. Kompensation schnell veränderlicher Blindströme eines Drehstromverbrauchers (In German).
ETZ Arch. 1989, 11, 249–253.
38. Awad, H.; Svensson, J.; Bollen, M. Mitigation of unbalanced voltage dips using static series compensator.
IEEE Trans. Power Electron. 2004, 19, 837–846. [CrossRef]
39. Akagi, H.; Kanazawa, Y.; Nabae, A. Instantaneous reactive power compensators comprising switching
devices without energy storage components. IEEE Trans. Ind. Appl. 1984, 20, 625–630. [CrossRef]
40. Guerrero-Rodríguez, N.F.; Herrero-de Lucas, L.C.; de Pablo-Gómez, S.; Rey-Boué, A.B. Performance study of
a synchronization algorithm for a 3-phasephotovoltaic grid-connected system under harmonic distortions
and unbalances. Electr. Power Syst. Res. 2014, 116, 252–265. [CrossRef]
41. Teodorescu, R.; Liserre, M.; Rodriguez, P. Grid Converters for Photovoltaic and Wind Power Systems; John Wiley
Sons: Chichester, UK, 2011.
42. Limongi, L.R.; Bojoi, R.; Griva, G.; Tenconi, A. Digital Current-Control Schemes. IEEE Ind. Electr. Mag. 2009,
3, 20–31. [CrossRef]
43. Bojoi, R.I.; Griva, G.; Bostan, V.; Guerriero, M.; Farina, F.; Profumo, F. Current Control Strategy for
Power Conditioners Using Sinusoidal Signal Integrators in Synchronous Reference Frame. IEEE Trans.
Power Electron. 2005, 20, 1402–1412. [CrossRef]
44. Teodorescu, R.; Blaabjerg, F.; Liserre, M.; Loh, P.C. Proportional-resonant controllers and filters for
grid-connected voltage-source converters. IEE Proc. Electr. Power Appl. 2006, 153, 750–762. [CrossRef]
45. Guerrero-Rodríguez, N.F.; Rey-Boué, A.B. Modelling, simulation and experimental verification for
renewable agents connected to a distorted utility grid using a Real-Time Digital Simulation Platform.
Energy Convers. Manag. 2014, 84, 108–121. [CrossRef]
46. Mahimkar, N.; Persson, G.; Westerlind, C. HVDC Technology for Large Scale Offshore Wind Connections.
Available online: https://library.e.abb.com/public/ee95e738f283d4ecc1257b710048fa14/HVDC%
20Technology%20for%20Large%20Scale%20Offshore%20Wind%20Connections_ABB_Smartelec2013.pdf
(accessed on 11 September 2017).
47. HVDC-VSC: Transmission Technology of the Future. Alstom Grid, 2011. Available online: http://www.
tresamigasllc.com/docs/ThinkGrid08-06-Chapter1-Art1%20VSC_EN.pdf (accessed on 11 September 2017).
48. Du, S.; Liu, J. A Study on DC Voltage Control for Chopper-Cell-Based Modular Multilevel Converters in
D-STATCOM Application. IEEE Trans. Power Deliv. 2013, 28, 2030–2038. [CrossRef]
49. Mohammadi, P.H.; Bina, M.T. A Transformerless Medium-Voltage STATCOM Topology Based on Extended
Modular Multilevel Converters. IEEE Trans. Power Electron. 2011, 26, 1534–1545.
50. Roscoe, N.M.; Zhong, Y.; Finney, S.J. Comparing SiC MOSFET, IGBT and Si MOSFET in LV distribution
inverters. In Proceedings of the 41st Annual Conference of the IEEE Industrial Electronics Society, Yokohama,
Japan, 9–12 November 2015; pp. 743–748.
51. Zhong, Y.; Holliday, D.; Finney, S.J. High-efficiency MOSFET-based MMC for LVDC distribution systems.
In Proceedings of the IEEE Energy Conversion Congress and Exposition (ECCE), Montreal, QC, Canada,
20–24 September 2015; pp. 6691–6697.
52. Ghazanfari, A.; Mohamed, Y.A.R.I. Decentralized Cooperative Control for Smart DC Home with DC Fault
Handling Capability. IEEE Trans. Smart Grid 2017, 99. [CrossRef]
53. Gangui, Y.; Jigang, L.; Gang, M.U.; Yu, L.; Yang, L.; Wei, S. Research on Modular Multilevel Converter
Suitable for Direct-drive Wind Power System. Energy Procedia 2012, 17, 1497–1506. [CrossRef]
54. Gomis-Bellmunta, O.; Liangc, J.; Ekanayakec, J.; Jenkinsc, N. Voltage–current characteristics of multiterminal
HVDC-VSC for offshore wind farms. Electr. Power Syst. Res. 2011, 81, 440–450. [CrossRef]
55. Van Hertem, D.; Gomis-Bellmunt, O.; Liang, J. HVDC Grids: For Offshore and Supergrid of the Future;
John Wiley Sons: Hoboken, NJ, USA, 2016.
56. Ng, C.; Ran, L. Offshore Wind Farms: Technologies, Design and Operation; Woodhead Publishing: Cambridge,
UK, 2016.
57. Quinonez-Varela, G.; Ault, G.W.; Anaya-Lara, O.; McDonald, J.R. Electrical collector system options for large
offshore wind farms. IET Renew. Power Gener. 2007, 1, 107–114. [CrossRef]