The dynamic resistance measurement (DRM) was developed to analyze the switching process of on-load tap changers (OLTCs), which have a high failure rate of around 30%. DRM allows detection of issues like arcing contacts or switching interruptions by measuring the fast switching process. To properly analyze DRM results, it is important to know the OLTC type and construction. DRM analysis focuses on features of the current curve during switching, like amplitude, which indicates contact resistance, and timing, which may show mechanical problems. Proper test currents around 3-5A provide a stable measurement. Shorting the secondary side increases sensitivity. Switching direction and tap position can impact results due to differences in winding configuration.
This document provides information about the design and components of a 220kV switchyard. It discusses:
1. The double main bus with transfer bus scheme used, which has two main buses (Bus-1 and Bus-2) and one transfer bus for maintenance.
2. The key equipment used including circuit breakers, current transformers, capacitor voltage transformers, isolators, lightning arresters, and insulators.
3. The testing procedures for current transformers, which include insulation resistance testing, polarity testing, excitation testing, ratio testing, and winding resistance testing.
This document discusses the testing and maintenance of power transformers. It outlines the various routine tests performed on transformers according to standards, including winding resistance measurement, insulation resistance measurement, high voltage tests, no load and load loss measurements. It also describes type tests such as lightning impulse and short circuit tests. Finally, it discusses the importance of preventive maintenance through regular checks of oil levels, insulation resistance, bushings, connections and other components.
The document discusses substations and their components. It defines a substation as an assembly of apparatus that transforms electrical energy from one form to another, such as changing voltage levels. Substations contain step-up transformers to increase voltage for transmission and step-down transformers to decrease voltage for distribution to consumers. The document describes various types of substations and explains their functions. It also provides details about components within substations such as circuit breakers, transformers, buses, isolators and instrument transformers.
The document discusses components and operation of substations, including isolators, busbars, circuit breakers, power transformers, instrument transformers like current and potential transformers, Buchholz relay, earthing methods, and power line carrier communication. It provides details on classifications, principles, and purposes of these various components used in electricity distribution networks.
Test done on Power transformers.
Insulation Resistance test, Winding Resistance test, Ratio Measurements, Magnetic balance test, Tan delta test, DIssolved gas analysis for transformer, Sweep frequency response analysis.
Distribution transformers are used to transform power from high voltages on the distribution lines to lower voltages that can be used in homes and businesses. Routine maintenance and testing of distribution transformers is important to ensure proper functioning and protection. Key tests include measuring winding resistance, insulation levels, voltage ratios and losses to check for any issues. Proper oil levels, insulation and bushings must also be maintained. Protective devices like Buchholz relays and temperature indicators help monitor the transformer and prevent failures from overloading, faults or low oil levels.
1. The document discusses different types of transformers used in power plants including power transformers, service transformers, and measuring transformers.
2. It describes key components of transformers like the core, windings, cooling systems, and protections devices. Transformer connections, vector groups, and voltage classifications are also covered.
3. Various transformers used in thermal power plants are discussed including generator transformers, station transformers, unit auxiliary transformers, and those used for distribution within the plant.
This document provides information about the design and components of a 220kV switchyard. It discusses:
1. The double main bus with transfer bus scheme used, which has two main buses (Bus-1 and Bus-2) and one transfer bus for maintenance.
2. The key equipment used including circuit breakers, current transformers, capacitor voltage transformers, isolators, lightning arresters, and insulators.
3. The testing procedures for current transformers, which include insulation resistance testing, polarity testing, excitation testing, ratio testing, and winding resistance testing.
This document discusses the testing and maintenance of power transformers. It outlines the various routine tests performed on transformers according to standards, including winding resistance measurement, insulation resistance measurement, high voltage tests, no load and load loss measurements. It also describes type tests such as lightning impulse and short circuit tests. Finally, it discusses the importance of preventive maintenance through regular checks of oil levels, insulation resistance, bushings, connections and other components.
The document discusses substations and their components. It defines a substation as an assembly of apparatus that transforms electrical energy from one form to another, such as changing voltage levels. Substations contain step-up transformers to increase voltage for transmission and step-down transformers to decrease voltage for distribution to consumers. The document describes various types of substations and explains their functions. It also provides details about components within substations such as circuit breakers, transformers, buses, isolators and instrument transformers.
The document discusses components and operation of substations, including isolators, busbars, circuit breakers, power transformers, instrument transformers like current and potential transformers, Buchholz relay, earthing methods, and power line carrier communication. It provides details on classifications, principles, and purposes of these various components used in electricity distribution networks.
Test done on Power transformers.
Insulation Resistance test, Winding Resistance test, Ratio Measurements, Magnetic balance test, Tan delta test, DIssolved gas analysis for transformer, Sweep frequency response analysis.
Distribution transformers are used to transform power from high voltages on the distribution lines to lower voltages that can be used in homes and businesses. Routine maintenance and testing of distribution transformers is important to ensure proper functioning and protection. Key tests include measuring winding resistance, insulation levels, voltage ratios and losses to check for any issues. Proper oil levels, insulation and bushings must also be maintained. Protective devices like Buchholz relays and temperature indicators help monitor the transformer and prevent failures from overloading, faults or low oil levels.
1. The document discusses different types of transformers used in power plants including power transformers, service transformers, and measuring transformers.
2. It describes key components of transformers like the core, windings, cooling systems, and protections devices. Transformer connections, vector groups, and voltage classifications are also covered.
3. Various transformers used in thermal power plants are discussed including generator transformers, station transformers, unit auxiliary transformers, and those used for distribution within the plant.
This document is a project report submitted by Girish Gupta about his training at the 132 KV substation in Purukul, Dehradun. It includes an index listing the topics covered in the report such as the substation, transformers, circuit breakers, and protection systems. The report provides details about the Power Transmission Corporation of Uttarakhand Limited and describes the components and layout of the 132 KV substation in Purukul, including its two incoming transmission lines, transformers, buses, feeders, and capacitor bank. It also defines different types of substations and their characteristics.
Presentation on 132/33 KVSubstation Training Sakshi Rastogi
This is a presentation based on the 132/33 KV substation. At which I have done my vocational Training. this presentation uncovers all the aspects related to the substation.
Operation and maintenance of transformerKapil Singh
The document provides information on operation and maintenance of distribution transformers. It defines transformers and describes their working principle of mutual electromagnetic induction. It then discusses transformation ratios, the purposes of transformers, their advantages, types, parts, insulation, testing, and maintenance procedures. Key points covered include daily, quarterly and yearly maintenance checks, oil testing parameters, and common transformer tests like ratio, no load, short circuit and insulation tests.
This document provides guidance for carrying out pre-commissioning checks and tests for switchyard equipment at Power Grid Corporation of India Ltd. It outlines the constitution and responsibilities of the commissioning team, general safety procedures, documentation requirements, and pre-commissioning formats for recording test results. Specific guidance is provided for transformers, reactors, and other switchyard equipment such as circuit breakers, current transformers, surge arresters, and more. The aim is to ascertain the correctness and completeness of installation and healthiness of equipment before charging.
This document discusses transformer protection. Transformers are critical and expensive components that require protection to limit damage from faults. Protection methods include Buchholz relays, which detect gases from arcing; pressure relays, which detect pressure waves from arcing; and thermal relays, which monitor hot spot temperatures. Protection aims to quickly isolate transformers under abnormal conditions like faults, overloads, or overvoltages to prevent failures and simplify repairs.
In-Country Training
On
Operation, Maintenance, Protection & Control of 33/11 kV Substation
Project Name: Design, Supply, Installation, Testing & Commissioning of 33/11 kV sub-stations with source end feeder bays.
Contract No: BREB/UREDS/W-01A-001/02/2016-2017
BREB/UREDS/W-01A-002/03/2016-2017
BREB/UREDS/W-01A-004/04/2016-2017
�The sample calculations shown here illustrate steps involved in calculating the relay settings for generator protection.
�Other methodologies and techniques may be applied to calculate relay settings based on specific applications.
The protections of generator are the most complex and elaborate due to the following reasons: Generator is a large machine, connected to bus-bars. It is accompanied by unit transformers, auxiliary transformers and a bus system. ... The protection of generator should be co-ordinate with associated equipment's.
Power transformer testing and commissioning guidelines rAshish Patel
1. The document provides guidelines for testing and commissioning power transformers, including pre-commissioning checks, electrical checks, and tests to be performed. It details tests such as ratio testing, vector grouping, no-load current, short-circuit current, insulation testing, and checks of protections like the Buchholz relay.
2. Key electrical checks include verifying the on-load tap changer operation, measuring no-load currents, performing short-circuit tests, and measuring insulation resistance. The transformer, oil, and protections must pass all tests before energization.
3. After energization, the transformer is monitored for 24 hours to check for abnormalities before full commissioning.
The document discusses copper contact busway and provides details on Schneider Electric's solution. Some key points include:
- Schneider Electric uses a laminated bimetal technology where a silver-plated copper plate is laminated to an aluminum conductor to address fretting corrosion issues with traditional aluminum busway.
- Benefits of the copper contact solution include improved safety, reliability, durability, and lower contact resistance compared to aluminum busway.
- The busway has undergone extensive testing and certification to various industry standards.
- Several major project references utilizing the copper contact busway solution are provided.
Practical handbook-for-relay-protection-engineersSARAVANAN A
The ‘Hand Book’ covers the Code of Practice in Protection Circuitry including standard lead and device numbers, mode of connections at terminal strips, colour codes in multicore cables, Dos and Donts in execution. Also, principles of various protective relays and schemes including special protection schemes like differential,
restricted, directional and distance relays are explained with sketches. The norms of protection of generators, transformers, lines & Capacitor Banks are also given.
This document discusses switchgear, its types and components, as well as maintenance procedures. It begins by defining switchgear and its purposes of controlling, protecting and isolating electrical equipment. It then discusses low voltage and medium voltage switchgear, and lists the basic functions of switchgear as electrical protection, safe isolation from live parts, and local or remote switching. The document goes on to discuss periodic and preventive maintenance of switchgear.
This document discusses fault level calculations in electric power systems. It explains that fault level calculations are necessary to select protective devices, circuit breakers, and equipment that can withstand short circuit currents. The document outlines the procedure for calculating fault levels, which involves representing the system with a single line diagram, choosing a base MVA, calculating per unit reactances, determining the equivalent reactance to the fault point, and using formulas to calculate fault MVA and current. It also discusses how current limiting reactors can be used to insert additional reactance and reduce short circuit currents to match circuit breaker ratings.
Voltages and currents present at the generator's rated voltage and current are provided as examples. Sample relay setting calculations are shown for generator protection elements including 59N neutral overvoltage, 27TN third harmonic undervoltage, 46 negative sequence overcurrent, and coordination between protective devices. Formulas for calculating voltage and current settings from generator nameplate data are demonstrated.
This document provides details on substation layout and busbar arrangements. Part A discusses substation layout, including a single line diagram and descriptions of common switchyard accessories like lightning arrestors, CVTs, isolators, circuit breakers, transformers, and other equipment. It also covers PLCC and SCADA systems. Part B covers various busbar arrangements like the single bus system, double bus system, one and a half breaker system, and ring main bus system. It discusses the advantages and disadvantages of each configuration. In summary, the document is a technical report that outlines and compares different substation and busbar designs.
This document provides an overview and layout of the 220kV switchyard for the 750MW Ca Mau 1 combined cycle power plant in Vietnam. It includes details on the double busbar system configuration with circuit breakers, disconnecting switches, transformers, surge arresters, control building, DC power system, switchboards, and computerized control and protection panels.
This document provides an overview of the EE2402 Protection & Switchgear course presented by C.Gokul. It includes the course syllabus, units covered, textbook references and introductory content on power system basics, components, faults, protection elements, relay terminology and essential qualities of protection systems. The key topics discussed are types of faults in power systems, importance of protective schemes, elements of a protection system including current transformers, voltage transformers, relays and circuit breakers. Neutral earthing methods with a focus on Peterson coil are also introduced.
This document provides an overview of the electrical equipment found in a switchyard at an NTPC power plant, including transformers, conductors, insulators, isolators, busbars, lightning arresters, circuit breakers, relays, and capacitor banks. It describes the purpose and basic functioning of each type of equipment, such as how transformers change voltage levels, current transformers reduce current readings, conductors transmit power, and relays and circuit breakers disconnect faulty circuits. The document also notes that new technologies like SCADA allow remote control and monitoring of substations.
1. The document discusses various acceptance criteria, interpretation, and analysis methods for transformer test results, including insulation resistance, impedance, tan delta, turns ratio, dissolved gas analysis (DGA), and frequency domain spectroscopy (FDS) moisture assessment.
2. It provides equations and standards for determining insulation resistance and lists IEEE recommended acceptance criteria for power factor in new vs aged transformers.
3. Guidelines are given for DGA gases levels according to IEEE standards and for physical properties of transformer oil like dielectric dissipation factor and water content.
ABB has extensive service experience with controlled switching, and the first generation of Switchsync™ controllers
was launched in 1986. Controlled switching is used for elimination of harmful electrical transients upon planned
switching of mainly capacitor banks, shunt reactors and power transformers. The method is also gaining acceptance
for reenergizing of EHV transmission lines, and replacing traditional pre-insertion resistors. Since 1986, thousands of
Switchsync™ controllers have been delivered all over the world.
ABB is at the forefront of development of controlled switching
and its applications, and has built up unique expertise
in switching transients and mitigation of related problems in
both main and secondary circuits. Our development program
is strongly focused on providing added value for our customers.
A key aspect of all controlled switching applications is the
precision achieved during making and breaking.
The live tank circuit breakers supplied by ABB are particularly
well suited for controlled switching due to their good stability
in regards to mechanical operating time and dynamic dielectric
behavior. In addition, the Switchsync™ controllers are equipped
with a special adaptive control, which compensates for any systematic
variations in operating time. Necessary signals for the
function are received from existing instrument transformers.
All controllers have provisions for adaptive input to compensate for systematic variations in operating time of the circuit breaker.
In addition, Switchsync™ F236, T183, and L183 have provisions for two external, predictive inputs (e.g. temperature variation,
control voltage). These functions make it possible to achieve added precision in the timing of the controlled circuit breaker.
They also have a data memory that stores information on switching times, thus permitting condition monitoring of the circuit
breaker. Sensors for compensation purposes and communication software for all controllers except E-models are accessories
that are ordered separately.
The
This document provides information about ABB's SwitchsyncTM controlled switching system. It discusses applications of controlled switching for shunt capacitor banks, shunt reactors, power transformers, and transmission lines. It explains concepts like reference points, targets, phase shifts, input commands, waiting times, output commands, and instrument transformers. It also describes ABB's different SwitchsyncTM controller models and their features, including adaptation, operating modes, remote communication, and monitoring capabilities. The document is intended as a buyer's guide and application guide for the SwitchsyncTM controlled switching system.
This document is a project report submitted by Girish Gupta about his training at the 132 KV substation in Purukul, Dehradun. It includes an index listing the topics covered in the report such as the substation, transformers, circuit breakers, and protection systems. The report provides details about the Power Transmission Corporation of Uttarakhand Limited and describes the components and layout of the 132 KV substation in Purukul, including its two incoming transmission lines, transformers, buses, feeders, and capacitor bank. It also defines different types of substations and their characteristics.
Presentation on 132/33 KVSubstation Training Sakshi Rastogi
This is a presentation based on the 132/33 KV substation. At which I have done my vocational Training. this presentation uncovers all the aspects related to the substation.
Operation and maintenance of transformerKapil Singh
The document provides information on operation and maintenance of distribution transformers. It defines transformers and describes their working principle of mutual electromagnetic induction. It then discusses transformation ratios, the purposes of transformers, their advantages, types, parts, insulation, testing, and maintenance procedures. Key points covered include daily, quarterly and yearly maintenance checks, oil testing parameters, and common transformer tests like ratio, no load, short circuit and insulation tests.
This document provides guidance for carrying out pre-commissioning checks and tests for switchyard equipment at Power Grid Corporation of India Ltd. It outlines the constitution and responsibilities of the commissioning team, general safety procedures, documentation requirements, and pre-commissioning formats for recording test results. Specific guidance is provided for transformers, reactors, and other switchyard equipment such as circuit breakers, current transformers, surge arresters, and more. The aim is to ascertain the correctness and completeness of installation and healthiness of equipment before charging.
This document discusses transformer protection. Transformers are critical and expensive components that require protection to limit damage from faults. Protection methods include Buchholz relays, which detect gases from arcing; pressure relays, which detect pressure waves from arcing; and thermal relays, which monitor hot spot temperatures. Protection aims to quickly isolate transformers under abnormal conditions like faults, overloads, or overvoltages to prevent failures and simplify repairs.
In-Country Training
On
Operation, Maintenance, Protection & Control of 33/11 kV Substation
Project Name: Design, Supply, Installation, Testing & Commissioning of 33/11 kV sub-stations with source end feeder bays.
Contract No: BREB/UREDS/W-01A-001/02/2016-2017
BREB/UREDS/W-01A-002/03/2016-2017
BREB/UREDS/W-01A-004/04/2016-2017
�The sample calculations shown here illustrate steps involved in calculating the relay settings for generator protection.
�Other methodologies and techniques may be applied to calculate relay settings based on specific applications.
The protections of generator are the most complex and elaborate due to the following reasons: Generator is a large machine, connected to bus-bars. It is accompanied by unit transformers, auxiliary transformers and a bus system. ... The protection of generator should be co-ordinate with associated equipment's.
Power transformer testing and commissioning guidelines rAshish Patel
1. The document provides guidelines for testing and commissioning power transformers, including pre-commissioning checks, electrical checks, and tests to be performed. It details tests such as ratio testing, vector grouping, no-load current, short-circuit current, insulation testing, and checks of protections like the Buchholz relay.
2. Key electrical checks include verifying the on-load tap changer operation, measuring no-load currents, performing short-circuit tests, and measuring insulation resistance. The transformer, oil, and protections must pass all tests before energization.
3. After energization, the transformer is monitored for 24 hours to check for abnormalities before full commissioning.
The document discusses copper contact busway and provides details on Schneider Electric's solution. Some key points include:
- Schneider Electric uses a laminated bimetal technology where a silver-plated copper plate is laminated to an aluminum conductor to address fretting corrosion issues with traditional aluminum busway.
- Benefits of the copper contact solution include improved safety, reliability, durability, and lower contact resistance compared to aluminum busway.
- The busway has undergone extensive testing and certification to various industry standards.
- Several major project references utilizing the copper contact busway solution are provided.
Practical handbook-for-relay-protection-engineersSARAVANAN A
The ‘Hand Book’ covers the Code of Practice in Protection Circuitry including standard lead and device numbers, mode of connections at terminal strips, colour codes in multicore cables, Dos and Donts in execution. Also, principles of various protective relays and schemes including special protection schemes like differential,
restricted, directional and distance relays are explained with sketches. The norms of protection of generators, transformers, lines & Capacitor Banks are also given.
This document discusses switchgear, its types and components, as well as maintenance procedures. It begins by defining switchgear and its purposes of controlling, protecting and isolating electrical equipment. It then discusses low voltage and medium voltage switchgear, and lists the basic functions of switchgear as electrical protection, safe isolation from live parts, and local or remote switching. The document goes on to discuss periodic and preventive maintenance of switchgear.
This document discusses fault level calculations in electric power systems. It explains that fault level calculations are necessary to select protective devices, circuit breakers, and equipment that can withstand short circuit currents. The document outlines the procedure for calculating fault levels, which involves representing the system with a single line diagram, choosing a base MVA, calculating per unit reactances, determining the equivalent reactance to the fault point, and using formulas to calculate fault MVA and current. It also discusses how current limiting reactors can be used to insert additional reactance and reduce short circuit currents to match circuit breaker ratings.
Voltages and currents present at the generator's rated voltage and current are provided as examples. Sample relay setting calculations are shown for generator protection elements including 59N neutral overvoltage, 27TN third harmonic undervoltage, 46 negative sequence overcurrent, and coordination between protective devices. Formulas for calculating voltage and current settings from generator nameplate data are demonstrated.
This document provides details on substation layout and busbar arrangements. Part A discusses substation layout, including a single line diagram and descriptions of common switchyard accessories like lightning arrestors, CVTs, isolators, circuit breakers, transformers, and other equipment. It also covers PLCC and SCADA systems. Part B covers various busbar arrangements like the single bus system, double bus system, one and a half breaker system, and ring main bus system. It discusses the advantages and disadvantages of each configuration. In summary, the document is a technical report that outlines and compares different substation and busbar designs.
This document provides an overview and layout of the 220kV switchyard for the 750MW Ca Mau 1 combined cycle power plant in Vietnam. It includes details on the double busbar system configuration with circuit breakers, disconnecting switches, transformers, surge arresters, control building, DC power system, switchboards, and computerized control and protection panels.
This document provides an overview of the EE2402 Protection & Switchgear course presented by C.Gokul. It includes the course syllabus, units covered, textbook references and introductory content on power system basics, components, faults, protection elements, relay terminology and essential qualities of protection systems. The key topics discussed are types of faults in power systems, importance of protective schemes, elements of a protection system including current transformers, voltage transformers, relays and circuit breakers. Neutral earthing methods with a focus on Peterson coil are also introduced.
This document provides an overview of the electrical equipment found in a switchyard at an NTPC power plant, including transformers, conductors, insulators, isolators, busbars, lightning arresters, circuit breakers, relays, and capacitor banks. It describes the purpose and basic functioning of each type of equipment, such as how transformers change voltage levels, current transformers reduce current readings, conductors transmit power, and relays and circuit breakers disconnect faulty circuits. The document also notes that new technologies like SCADA allow remote control and monitoring of substations.
1. The document discusses various acceptance criteria, interpretation, and analysis methods for transformer test results, including insulation resistance, impedance, tan delta, turns ratio, dissolved gas analysis (DGA), and frequency domain spectroscopy (FDS) moisture assessment.
2. It provides equations and standards for determining insulation resistance and lists IEEE recommended acceptance criteria for power factor in new vs aged transformers.
3. Guidelines are given for DGA gases levels according to IEEE standards and for physical properties of transformer oil like dielectric dissipation factor and water content.
ABB has extensive service experience with controlled switching, and the first generation of Switchsync™ controllers
was launched in 1986. Controlled switching is used for elimination of harmful electrical transients upon planned
switching of mainly capacitor banks, shunt reactors and power transformers. The method is also gaining acceptance
for reenergizing of EHV transmission lines, and replacing traditional pre-insertion resistors. Since 1986, thousands of
Switchsync™ controllers have been delivered all over the world.
ABB is at the forefront of development of controlled switching
and its applications, and has built up unique expertise
in switching transients and mitigation of related problems in
both main and secondary circuits. Our development program
is strongly focused on providing added value for our customers.
A key aspect of all controlled switching applications is the
precision achieved during making and breaking.
The live tank circuit breakers supplied by ABB are particularly
well suited for controlled switching due to their good stability
in regards to mechanical operating time and dynamic dielectric
behavior. In addition, the Switchsync™ controllers are equipped
with a special adaptive control, which compensates for any systematic
variations in operating time. Necessary signals for the
function are received from existing instrument transformers.
All controllers have provisions for adaptive input to compensate for systematic variations in operating time of the circuit breaker.
In addition, Switchsync™ F236, T183, and L183 have provisions for two external, predictive inputs (e.g. temperature variation,
control voltage). These functions make it possible to achieve added precision in the timing of the controlled circuit breaker.
They also have a data memory that stores information on switching times, thus permitting condition monitoring of the circuit
breaker. Sensors for compensation purposes and communication software for all controllers except E-models are accessories
that are ordered separately.
The
This document provides information about ABB's SwitchsyncTM controlled switching system. It discusses applications of controlled switching for shunt capacitor banks, shunt reactors, power transformers, and transmission lines. It explains concepts like reference points, targets, phase shifts, input commands, waiting times, output commands, and instrument transformers. It also describes ABB's different SwitchsyncTM controller models and their features, including adaptation, operating modes, remote communication, and monitoring capabilities. The document is intended as a buyer's guide and application guide for the SwitchsyncTM controlled switching system.
This document discusses power transformer maintenance and field testing techniques. It provides an overview of various tests that can be performed on-site to evaluate the electrical and dielectric systems of power transformers, including no-load tests, load tests, winding resistance tests, frequency response analysis, insulation resistance tests, and partial discharge tests. These field tests allow monitoring the condition of transformers and detecting any issues in a non-intrusive manner, helping to optimize maintenance programs.
This document discusses power transformer maintenance through field testing. It describes several types of tests that can be performed, including no-load tests to measure turns ratio, polarity and excitation current. Load tests measure short circuit impedance. Winding resistance tests measure the resistance of each winding. Frequency response analysis testing provides information on the electric, dielectric, magnetic and mechanical condition by analyzing the transformer's frequency response signature. Regular field testing using these methods allows monitoring the transformer's condition over time to ensure safe and reliable operation.
Devlopement of the dynamic resistance measurement (drm) method for condition ...eSAT Publishing House
IJRET : International Journal of Research in Engineering and Technology is an international peer reviewed, online journal published by eSAT Publishing House for the enhancement of research in various disciplines of Engineering and Technology. The aim and scope of the journal is to provide an academic medium and an important reference for the advancement and dissemination of research results that support high-level learning, teaching and research in the fields of Engineering and Technology. We bring together Scientists, Academician, Field Engineers, Scholars and Students of related fields of Engineering and Technology
Concurrent Detection and Classification of Faults in Matrix Converter using T...IAES-IJPEDS
This paper presents a fault diagnostic algorithm for detecting and locating open-circuit and short-circiut faults in switching components of matrix converters (MCs) which can be effectively used to drive a permanent magnet synchronous motor for research in critical applications. The proposed method is based on monitoring the voltages and currents of the switches. These measurements are used to evaluate the forward trans-conductance of each transistor for different values of switch voltages. These trans-conductance values are then compared to the nominal values. Under healthy conditions, the values obtained for the fault signal is less than the tolerable value. Under the open/short-circuit conditions, the fault signal exceeds the threshold, hence enables the matrix converter drive to detect and exactly identify the location of the faulty IGBT. The main advantages of this diagnostic method include fast detection and locating of the faulty IGBT, easiness of implementation and independency of the modulation strategy of the converter.
A Resonant Converter with LLC for DC-to-DC Converter Based ApplicationsIJMTST Journal
This document discusses a current mode control scheme for LLC series resonant DC-to-DC converters used for electric vehicle battery chargers. The proposed current mode control employs feedback from the resonant tank current to nullify effects of changes in power stage dynamics, improving performance over conventional voltage mode control. The LLC converter has multiple resonant modes depending on operating frequency and load. Experimental results show the current mode control achieves 97.96% peak efficiency for a 6.6 kW, 390V to 250-450V converter. Future work will focus on design optimization and a simpler design procedure.
This document summarizes a study on using frequency response analysis (FRA) to detect damage in transformer tap changers. The study investigates a 500kVA distribution transformer with different tap changer conditions: normal, pitting, and coking. FRA measurements were taken in four configurations and showed that pitting had a slight influence on the frequency response, while coking showed a large variation in the low frequency response from 20Hz to 2kHz. Winding resistance measurements also supported the FRA results by indicating increased resistance from coking. The study demonstrates FRA can effectively detect faults in transformer tap changers.
Review of the DTC Controller and Estimation of Stator Resistance in IM DrivesIAES-IJPEDS
In recent years an advanced control method called direct torque control
(DTC) has gained importance due to its capability to produce fast torque
control of induction motor. Although in these systems such variables as
torque, flux modulus and flux sector are required, resulting DTC structure is
particularly simplistic. Conventional DTC does not require any mechanical
sensor or current regulator and coordinate transformation is not present, thus
reducing the complexity. Fast and good dynamic performances and
robustness has made DTC popular and is now used widely in all industrial
applications. Despite these advantages it has some disadvantages such as
high torque ripple and slow transient response to step changes during start
up. Torque ripple in DTC is because of hysteresis controller for stator flux
linkage and torque. The ripples can be reduced if the errors of the torque and
the flux linkage and the angular region of the flux linkage are subdivided into
several smaller subsections. Since the errors are divided into smaller sections
different voltage vector is selected for small difference in error, thus a more
accurate voltage vector is selected and hence the torque and flux linkage
errors are reduced. The stator resistance changes due to change in
temperature during the operation of machine. At high speeds, the stator
resistance drop is small and can be neglected. At low speeds, this drop
becomes dominant. Any change in stator resistance gives wrong estimation
of stator flux and consequently of the torque and flux. Therefore, it is
necessary to estimate the stator resistance correctly. This paper aims to
review some of the control techniques of DTC drives and stator resistance
estimation methods.
Tap changers are devices fitted to power transformers that allow for regulation of the output voltage. Voltage regulation is achieved by altering the number of turns in one winding of the transformer, which changes the transformer ratios. Tap changers offer variable control to keep the supply voltage within limits. They can be on load or off load tap changers. On load tap changers consist of a diverter switch and selector switch to transfer current between taps without interruption.
2 twofold mode series echoing dc dc converter for ample loadchelliah paramasivan
The document describes a dual-mode full-bridge series resonant DC-DC converter that can operate at either a variable switching frequency or a fixed switching frequency with phase-shifted pulse width modulation to regulate the output voltage over a wide range of loads. The converter uses a series resonant tank consisting of an inductor and capacitor to achieve soft switching and zero voltage switching of the transistors. It can operate in a frequency modulation mode at high loads by varying the switching frequency, or in a phase modulation mode at light loads using a fixed high switching frequency and varying the duty cycle through phase-shifted pulse width modulation. This dual-mode operation provides high conversion efficiency across a wide range of loads.
1) The document presents a new zero-voltage switching (ZVS) topology for a three-phase grid-connected inverter. The topology uses an additional active clamping leg to achieve ZVS for all the main switches.
2) A new space vector modulation scheme is proposed to control the inverter such that the auxiliary switch operates at the same frequency as the main switches. This ensures ZVS turn-on of the main switches.
3) Simulation results on a 30kW prototype verify that the ZVS topology reduces switching losses, improves efficiency, and makes the inverter suitable for practical high power applications.
In real inverters' operations, it is essential to insert delay time in the pulses provided to the inverter switches to protect the DC link against the short circuits. From this situation, the dead time phenomenon is introduced that causes undesirable performance and distortion of the output signal. Previously, researchers have proposed various schemes for compensating or eliminating dead-time. In this paper, a new dead-time elimination (DTE) scheme is proposed with a guarantee algorithm to eliminate dead-time and overcome the issues produced at the zero-currents-crossing point (ZCC). This method does not require additional hardware or filters to determine the polarity of the output current, and its principle is very simple to implement. The developed DTE method completely removes the dead-time issues on the magnitude and phase of the output voltage, and avoid the problems which can be induced around the ZCC. The results confirm the effectiveness and safety of this method.
A Three Phase AC-AC ZCS Resonant Converter for Induction HeatingIJMTST Journal
Generally, domestic induction-heating technology requires a high output power levels with less number of
components in a compact size. To satisfy these requirements, the basic circuit configurations are considered
based on the combination of a rectifier and a inverter. The main disadvantage of this method has low-efficient
and economic problems. This paper proposes a new concept unlike previous method, i.e the direct conversion
of ac–ac converter for reducing the component count, reduce cost, improve reliability, and also efficiency.
Generally, the proposed converter is a voltage-source based series-resonant converter used for controlling
output power, and minimizing the control complexity. This paper also proposes a concept of AC-AC converter
based three phase Induction Heating applications.
Report On diode clamp three level inverterVinay Singh
three level diode clamp inverter. that converts any type of DC ( rectified, PV cell, battery etc.) to AC supply. we made by mosfet and ardiuno . in this ppt we present the Simulink model of a three-level inverter and the hardware reort of the inverter.
also discuss about other level inverter and there THD analysis, simulink model and detail. compression between another inverter.
Implementation and control of integral cycle controller for resistance spot w...eSAT Journals
Abstract: The Resistance Spot Welding (RSW) process requires simultaneous application of high electrical current and appropriate pressure over short periods in order to keep the molten material inside the weld zone. Values of these parameters vary in function of the characteristics of the materials to be welded. The application of the electrical current is by means of two copper electrodes brought in contact with the welded parts while the required pressure is applied by means of pneumatic or hydraulic systems. This paper presents the simulation, design, and control of resistance welding system which is used for performing a welding process. The paper is discussed about two aspects. First, simulation of the concept of ICC used for the specific application of RSW. Secondly, the critical factor and method employed for the implementation of the controller. This paper also discuss about the implementation methodology of the RSW. The simulation for the RSW is carried out in PROTEUS software.
Index Word: Constant Current Feedback, Integral Cycle Control (ICC), Resistance Spot Welding, Sequential Timer.
Closed Loop Analysis of Multilevel Inverter Fed Drives IJPEDS-IAES
This paper deals with the simulation and implementation of multilevel inverter for drives application. Here the focuses will be onimproving the efficiency of the multilevel inverter and quality of output voltage waveform. The circuit is developed towards high efficiency, high performance, and low cost, simple control scheme. Harmonics Elimination was implemented to reduce the Total Harmonics Distortion (THD) value which is achieved by selecting appropriate switching angles. In this paper to determine the performance of rectifier, steady state analysis is done. Furthermore, the merits of multilevel inverter topology are inherited.Closed loop control is done to analysis the stability of the system.
International Journal of Engineering Research and Applications (IJERA) is an open access online peer reviewed international journal that publishes research and review articles in the fields of Computer Science, Neural Networks, Electrical Engineering, Software Engineering, Information Technology, Mechanical Engineering, Chemical Engineering, Plastic Engineering, Food Technology, Textile Engineering, Nano Technology & science, Power Electronics, Electronics & Communication Engineering, Computational mathematics, Image processing, Civil Engineering, Structural Engineering, Environmental Engineering, VLSI Testing & Low Power VLSI Design etc.
This document provides information about transformer tests conducted at BEST Balıkesir Transformer Factory laboratories. It describes routine tests like winding resistance measurement, voltage ratio measurement and phase checking, as well as type tests and special tests. The routine tests section explains test procedures and equipment for various tests done on all transformers produced. These include impedance measurement, no-load loss tests, and tap changer tests. Type and special tests involve temperature rise testing, lightning impulse testing, and other advanced analyses. Laboratory equipment for performing over a dozen transformer tests is also listed.
Compensation for Inverter Nonlinearity Using Trapezoidal VoltageIJMER
The nonlinearity of an inverter can be considered as the voltage differences between the
voltage references and actual outputs of the voltage source inverter (VSI). In this paper, trapezoidal
voltages were utilized to compensate for the inverter nonlinearity. The harmonic distortions in the output
currents caused by the inverter nonlinearity can be controlled through the trapezoidal angle. Simulation
results are given to demonstrate the validity and features of this method.
Similar to Dynamic Analysis and Testing of on-load tap changer (20)
Optimizing Gradle Builds - Gradle DPE Tour Berlin 2024Sinan KOZAK
Sinan from the Delivery Hero mobile infrastructure engineering team shares a deep dive into performance acceleration with Gradle build cache optimizations. Sinan shares their journey into solving complex build-cache problems that affect Gradle builds. By understanding the challenges and solutions found in our journey, we aim to demonstrate the possibilities for faster builds. The case study reveals how overlapping outputs and cache misconfigurations led to significant increases in build times, especially as the project scaled up with numerous modules using Paparazzi tests. The journey from diagnosing to defeating cache issues offers invaluable lessons on maintaining cache integrity without sacrificing functionality.
Applications of artificial Intelligence in Mechanical Engineering.pdfAtif Razi
Historically, mechanical engineering has relied heavily on human expertise and empirical methods to solve complex problems. With the introduction of computer-aided design (CAD) and finite element analysis (FEA), the field took its first steps towards digitization. These tools allowed engineers to simulate and analyze mechanical systems with greater accuracy and efficiency. However, the sheer volume of data generated by modern engineering systems and the increasing complexity of these systems have necessitated more advanced analytical tools, paving the way for AI.
AI offers the capability to process vast amounts of data, identify patterns, and make predictions with a level of speed and accuracy unattainable by traditional methods. This has profound implications for mechanical engineering, enabling more efficient design processes, predictive maintenance strategies, and optimized manufacturing operations. AI-driven tools can learn from historical data, adapt to new information, and continuously improve their performance, making them invaluable in tackling the multifaceted challenges of modern mechanical engineering.
Design and optimization of ion propulsion dronebjmsejournal
Electric propulsion technology is widely used in many kinds of vehicles in recent years, and aircrafts are no exception. Technically, UAVs are electrically propelled but tend to produce a significant amount of noise and vibrations. Ion propulsion technology for drones is a potential solution to this problem. Ion propulsion technology is proven to be feasible in the earth’s atmosphere. The study presented in this article shows the design of EHD thrusters and power supply for ion propulsion drones along with performance optimization of high-voltage power supply for endurance in earth’s atmosphere.
An improved modulation technique suitable for a three level flying capacitor ...IJECEIAES
This research paper introduces an innovative modulation technique for controlling a 3-level flying capacitor multilevel inverter (FCMLI), aiming to streamline the modulation process in contrast to conventional methods. The proposed
simplified modulation technique paves the way for more straightforward and
efficient control of multilevel inverters, enabling their widespread adoption and
integration into modern power electronic systems. Through the amalgamation of
sinusoidal pulse width modulation (SPWM) with a high-frequency square wave
pulse, this controlling technique attains energy equilibrium across the coupling
capacitor. The modulation scheme incorporates a simplified switching pattern
and a decreased count of voltage references, thereby simplifying the control
algorithm.
Comparative analysis between traditional aquaponics and reconstructed aquapon...bijceesjournal
The aquaponic system of planting is a method that does not require soil usage. It is a method that only needs water, fish, lava rocks (a substitute for soil), and plants. Aquaponic systems are sustainable and environmentally friendly. Its use not only helps to plant in small spaces but also helps reduce artificial chemical use and minimizes excess water use, as aquaponics consumes 90% less water than soil-based gardening. The study applied a descriptive and experimental design to assess and compare conventional and reconstructed aquaponic methods for reproducing tomatoes. The researchers created an observation checklist to determine the significant factors of the study. The study aims to determine the significant difference between traditional aquaponics and reconstructed aquaponics systems propagating tomatoes in terms of height, weight, girth, and number of fruits. The reconstructed aquaponics system’s higher growth yield results in a much more nourished crop than the traditional aquaponics system. It is superior in its number of fruits, height, weight, and girth measurement. Moreover, the reconstructed aquaponics system is proven to eliminate all the hindrances present in the traditional aquaponics system, which are overcrowding of fish, algae growth, pest problems, contaminated water, and dead fish.
Software Engineering and Project Management - Introduction, Modeling Concepts...Prakhyath Rai
Introduction, Modeling Concepts and Class Modeling: What is Object orientation? What is OO development? OO Themes; Evidence for usefulness of OO development; OO modeling history. Modeling
as Design technique: Modeling, abstraction, The Three models. Class Modeling: Object and Class Concept, Link and associations concepts, Generalization and Inheritance, A sample class model, Navigation of class models, and UML diagrams
Building the Analysis Models: Requirement Analysis, Analysis Model Approaches, Data modeling Concepts, Object Oriented Analysis, Scenario-Based Modeling, Flow-Oriented Modeling, class Based Modeling, Creating a Behavioral Model.
Discover the latest insights on Data Driven Maintenance with our comprehensive webinar presentation. Learn about traditional maintenance challenges, the right approach to utilizing data, and the benefits of adopting a Data Driven Maintenance strategy. Explore real-world examples, industry best practices, and innovative solutions like FMECA and the D3M model. This presentation, led by expert Jules Oudmans, is essential for asset owners looking to optimize their maintenance processes and leverage digital technologies for improved efficiency and performance. Download now to stay ahead in the evolving maintenance landscape.
Rainfall intensity duration frequency curve statistical analysis and modeling...bijceesjournal
Using data from 41 years in Patna’ India’ the study’s goal is to analyze the trends of how often it rains on a weekly, seasonal, and annual basis (1981−2020). First, utilizing the intensity-duration-frequency (IDF) curve and the relationship by statistically analyzing rainfall’ the historical rainfall data set for Patna’ India’ during a 41 year period (1981−2020), was evaluated for its quality. Changes in the hydrologic cycle as a result of increased greenhouse gas emissions are expected to induce variations in the intensity, length, and frequency of precipitation events. One strategy to lessen vulnerability is to quantify probable changes and adapt to them. Techniques such as log-normal, normal, and Gumbel are used (EV-I). Distributions were created with durations of 1, 2, 3, 6, and 24 h and return times of 2, 5, 10, 25, and 100 years. There were also mathematical correlations discovered between rainfall and recurrence interval.
Findings: Based on findings, the Gumbel approach produced the highest intensity values, whereas the other approaches produced values that were close to each other. The data indicates that 461.9 mm of rain fell during the monsoon season’s 301st week. However, it was found that the 29th week had the greatest average rainfall, 92.6 mm. With 952.6 mm on average, the monsoon season saw the highest rainfall. Calculations revealed that the yearly rainfall averaged 1171.1 mm. Using Weibull’s method, the study was subsequently expanded to examine rainfall distribution at different recurrence intervals of 2, 5, 10, and 25 years. Rainfall and recurrence interval mathematical correlations were also developed. Further regression analysis revealed that short wave irrigation, wind direction, wind speed, pressure, relative humidity, and temperature all had a substantial influence on rainfall.
Originality and value: The results of the rainfall IDF curves can provide useful information to policymakers in making appropriate decisions in managing and minimizing floods in the study area.
Dynamic Analysis and Testing of on-load tap changer
1. ABSTRACT
The dynamic resistance measurement
was developed as a supplementary
measurement in order to analyse the
switching process of the on-load tap
changer. The article considers the im-
portance of on-load tap changers and
their main testing methods with the
focus on dynamic resistance meas
urement.
KEYWORDS
power transformer, on-load tap
changer, OLTC, dynamic resistance
measurement, DRM
Dynamic analysis
and testing of
on-load tap changer
Dynamic resistance
measurement
EVENTS
104
DIAGNOSIS
TRANSFORMERS MAGAZINE | Volume 3, Issue 3
2. Figure 1. Failure location of substation transformers based on 536 failures [1]
Introduction
Power transformers represent the most
expensive link between generation and
utilization of electric power. One very im
portantcomponentofapowertransform
er is the on-load tap changer (OLTC). As
its name suggests, an OLTC permits tap
changing, and hence regulating voltage
without interrupting the load current.
This can be accomplished in various ways,
resulting in considerably diversified tap
changer designs. The two most common
ones are the so-called inductive and resist
ive type tap changers.
Studies, as shown in Figure 1, show that
about 30 % of reported failures of sub
stationpowertransformersarerelatedtothe
aging effects on OLTCs. Due to this high
failure rate, it is very important to monitor
the condition of the power transformer’s
OLTC closely. Unlike other more static
components in a transformer, the OLTC
consists of numerous moving parts. Manu
facturers typically recommend a main
tenance cycle that mostly depends on the
total number of switching operations.
1. Types of OLTCs
To analyse and assess the dynamic resist
ance measurement (DRM) in a proper
manner, it is important to know the type
and the construction of the OLTC. Ther
e
are two common OLTC technologies in
the market. The inductive ones, which
are typically used in the North America
on the low-voltage side, and the resistive
OLTCs, which are often used in the rest of
the world on the high-voltage side.
This article focuses on resistive type tap
changers. In general, there are two dif
ferent types of resistive tap changers: di
verter switch and selector switch type, as
shown in Figures 2 and 3.
The diverter switch types have two parts: a
tap selector at the top to select the next tap
within the main transformer tank, and a
diverter switch at the bottom to switch the
load current with its own oil volume. With
this OLTC type, the tap selector is switched
before the diverter switch, and the type is
mostly used in higher power ratings.
The selector switch type combines the
function of the diverter switch and the
tap selector, within its own oil volume,
separated from the oil of the main trans
former tank.
2. Common methods for
OLTC testing
Power transformer OLTCs need close
monitoring of their condition due to their
high failure rate. As a basis for the ana
lysis, the following diagnostic methods
can be used:
• Static winding resistance
measurement of the individual
taps (offline)
The static winding resistance measure
ment is a very important diagnostic meas
urement tool and the most commonly
used testing method. A conventional
s
tatic resistance measurement can be
used to check the winding as well as all of
the internal connections, such as the con
nection from the bushings and the tap
changer mobile contacts to the wind
ing,
the contacts of the tap selector and the
main contacts of the diverter switch. An
assessment can be made by comparing
the results with the factory report or by
calculating the deviation from the aver
age of the three phases.
• Vibro-acoustic measurements
by using acceleration sensors
(offline/online)
The vibro-acoustic method is used to
detect acoustical signals caused by mech
anical movement. The recorded profiles,
which range up to 10 seconds and bet
ween 10 Hz – 100 kHz in time and fre
quency domain are compared with exist
ing reference profiles to identify certain
failure modes [3].
• Position and torque measurement
on the drive axis (offline/online)
The OLTC’s drive mechanism, compris
ing of a motor, drive shaft and gear, oper
ates the selector switch while charging a
spring to actuate the diverter or selector
switch, respectively. The position and
torque measurement uses motor supply
parameters (current and voltage) to de
tect mechanical problems and aging of
the drive mechanism. The results can be
compared with a reference profile or bet
ween the taps.
• Dissolved Gas Analysis (DGA)
of the oil in the tap changer
compartment (offline/online)
The DGA in the OLTC compartment
has become more common. During the
switching process of an OLTC, discharge
and heating occurs which generally leads
to a higher concentration of gasses in the
The dynamic resistance measurement was
developed in order to analyse the dynamic
switching process of on-load tap changers
To analyse and assess
the DRM measurement
in a proper manner, it
is important to know
the type and the con
struction of the OLTC
www.transformers-magazine.com 105
Cornelius PLATH, Markus PÜTTER…
3. Current curve
The current curve, as seen in Figure 4b, is
the most common way to interpret DRM
measurements, as it is widely used for
static resistance measurement and gives
the possibility to detect current interrup
tions.
By applying a short circuit to the opposite
side of the transformer, the current signal
becomes more sensitive, as the current
drop (ripple) increases as shown in Fig
ures 7 and 8. This is a result of a lower time
constant due to the shorted main induct
ance. A direct comparison of the current
signal is difficult when measuring with
different test equipment, as the ripple is
dependent on the dynamic properties of
the current source. But the principle and
the different stages of the switching pro
cess are always visible, regardless of the
source parameters.
Voltage curve
Alternative to the current signal, the dy
namic behaviour can also be assessed
tap changer compartment compared to
the main tank during normal operation.
Thus the interpretation of gas levels sig
nificantly varies from the interpretation
of gas levels obtained from the main tank
of the power transformer [4].
Each measurement method is important
to analyse the condition of OLTCs.
3. Dynamic Resistance
Measurement (DRM)
Typical switching times of the diverter
or selector switch between 40 and 60 ms
make it difficult to detect any effects dur
ing the switching process using a con
ventional static winding resistance meas
urement, which might take a few minutes.
Therefore, the principal of the DRM was
developed as a supplementary diagnostic
method for this specific use.
Using the same setup (Figure 4a), the dy
namic resistance measurement measures
the fast switching process of the diverter
switch. DRM can detect arcing contacts,
switching times of the diverter switch,
switching interruptions, due to broken
commutating resistors or broken leads for
example, and the complete wear of con
tacts. Therefore, it provides a deeper in
sight into the OLTC’s dynamic condition.
By analysing the recordings, it is possible
to draw a number of conclusions related
to the condition of the OLTC. There are
three different ways to display the dynam
ic behaviour of the diverter switch:
(1) Current curve
(2) Voltage curve
(3) Resistance curve
In further contemplation we will refer
only to the current curve.
Table 1. Common methods for OLTC testing [5]
The DGA in the OLTC
compartment has be-
come more common
Figure 2. Diverter switch with two resistance contacts [2] Figure 3. Selector switch with two resistance contacts [2]
Measurement method Application/ purpose Problems
Static winding resistance Check the windings as well Contacts alignment, contact wear
as the internal connections
Vibro-acoustic Detect acoustical signals Linkage/gears, Timing/Sequence,
caused by mechanical movement contacts alignment, arcing,
overheating/coking, contact wear, transition
Position and torque Detect mechanical problems and Linkage/gears, control/relays, motor,
aging of the drive mechanism brake, lubrication, contacts alignment
Dissolved gas analysis Detect higher concentration of gasses Arcing, overheating/coking
in the tap changer compartment
Dynamic resistance Measure the fast switching process Timing/sequence, contact wear, transition
of the diverter switch
TRANSFORMERS MAGAZINE | Volume 3, Issue 3
106
DIAGNOSIS
4. decrease the time constant of the system.
In addition, a high stray inductance may
causeasignificantinductivevoltage,which
cannotbeseparatedfromtheresistivevolt
age part using the setup shown in Figure 5.
To compensate for this effect, a method to
determine the inductive part of the voltage
by simultaneously measuring the voltage
on the opposite winding was introduced
several years ago [6].
using the voltage or resistance curve. By
injecting a DC current, as shown in Fig
ure 5, the recorded voltage signal seen in
Figure 6A can be obtained. When using
the voltage curve, however, it is crucial
to make sure that the voltage signal does
not get cut off due to a voltage limiter of
the source, which would make it difficult
to analyse the signal. In addition to the
cut-off voltage, transients as shown in the
example of Figure 6A between stage 1 and
2wouldnotbeseenasclearlyifthevoltage
limit was reached. Analog to the current
curve, a direct comparison of the meas
ured curves is not possible when meas
uring with different test instruments.
Resistance curve
The resistance curve, as seen in Figure 6B
cannotbemeasureddirectly,butisacalcu
lation derived from the measured voltage
and current based on the setup shown in
Figure 5. A short circuit on the opposite
transformer terminals can be applied to
The current curve is the most common way to
interpretDRMmeasurements,asitiswidelyused
for static resistance measurement and gives the
possibility to detect current interruptions
Figure 4b. Typical dynamic behaviour of the diverter switch in operation – current curve
Figure 6. Typical dynamic behaviour of the diverter switch in operation – voltage and resistance
curve
Figure 4a. Typical measurement setup of DRM
– current curve
Figure5.TypicalmeasurementsetupofDRM–
voltage and resistance curve
www.transformers-magazine.com 107
5. windings. As the resistance measurement
is temperature-dependent, this could lead
to inaccuracies in the measured resistance
[8]. In general, these considerations also
apply to DRM measurements including
the following:
Test currents below 3 A or 1 A have
shown to be more sensitive to contact
bouncing, which can lead to false inter
pretation of the results. A common effect
which can be observed is that a residual
oil coating on the contacts causes the
current to interrupt several times during
the test. These oil residues are usually not
considered problematic when the OLTC
operates under normal load conditions.
In turn, test currents in this range may be
able to indicate long-term aging effects
such as coking at an earlier stage, but
t
hese advantages still have to be investi
gated further by conducting additional
case studies.
Higher test currents in the range of
3-5 A were, in most cases, sufficient to
achieve a stable measurement of the
switching process. In these cases, minor
discontinuities, for example due to oil
coating on the contacts, did not affect
the results. Field tests did not reveal any
differences when further increasing the
current to 10 A or 15 A.
vary during the switching process. In ad
dition, contact resistance, contact move
ment, interruptions, winding inductance,
arcing and bouncing of the contacts may
influence the amplitude.
• Timing:
Differences in timing may indicate mech
anical problems, excessive wear of con
tacts and/or contact bouncing. A certain
difference may be acceptable and will
greatly depend on the design and model
of the OLTC.
5. Variation in the dynamic
resistance results
5.1 Choosing the correct test current
When measuring the static resistance,
lower test currents in the range of sev
eral amperes are preferred, especially for
HV windings [7]. Although testing of
low impedance LV windings may require
test currents in the range of 10-20 A, it is
recommended that currents should not
exceed 15 % of the rated current of the
winding. Larger currents may heat up the
The resistive curve has a big advantage
of being independent from the current
source used. Another advantage is that
the v
alues of the commutating resistors
can be determined directly. As the in
duced voltage on the secondary side could
be very high, it requires special protection
mechanisms for the testing device.
As the current curve is currently the most
commonly used way to perform DRM
measurements, the following sections
will focus on this method in more detail.
4. Analysis of measurement
results
Basedonthisnon-invasivetestingmethod,
failures can be detected without opening
the OLTC compartment. The type and the
construction of the OLTC must be known
to be able to analyse and assess the DRM
measurement in a proper manner. A refe
rence “fingerprint” measurement, which
is taken after commissioning or when the
diverter switch is known to be in a good
condition, allows efficient analysis.
In general, two types of information can
be interpreted when looking at the cur
rent profile:
• Amplitude:
Transition resistors cause the current to
DRM is a non-invasive testing method whereby
failures can be detected without opening the
OLTC compartment
Test currents in the range of 3-5 A were, in
most cases, sufficient to achieve a stable
measurement of the switching process
Figure 7. Difference in the DRM when switching up and down1
1
Measured on MR Type DIII-200-14 27 3 GF, 1966
Figure 8. Difference in the DRM when switching the diverter switch in
alternating directions1
TRANSFORMERS MAGAZINE | Volume 3, Issue 3
108
DIAGNOSIS
6. 5.2 Secondary short circuit
Shorting the secondary side of the trans
former can have two positive effects. First,
if the current is interrupted during switch
ing, the energy stored in the magnetic core
may not be released, and the fast change
in the current will not generate such a
high voltage on the opposite winding.
The other positive effect is that the cur
rent drop (ripple) while switching was in
most cases observed to be twice as high,
because the main inductance was short
ed. This makes the DRM a more sensi
tive
m
ethod, but also has an impact on the
curves, making them more significant.
5.3 Switching process from tap to tap
When analysing and comparing different
taps, it needs to be considered whether the
curvesdifferincaseoftheOLTCswitching
up or down. This is important because in
the former case some windings are added
to the circuit, while in the latter, case wind
ings are subtracted based on the trans
former tap winding and OLTC winding,
so the wiring diagram could be different
for different transformers. If windings are
added, the additional inductance needs to
be loaded with energy, and if they are sub
tracted, the loaded energy in the induct
ance is released. This effect is much more
likely if the secondary side is not shorted,
as seen in Figure 7.
The measured curves also differ when
switching from an odd to an even tap pos
ition, as the diverter switch is rotating in
alternating directions (Figure 8). This
can usually be seen as different switching
times of the individual stages. In addition,
bouncing of contacts can sometimes only
be seen in one direction.
An example of software which allows
analysis and comparison of static and dy
namic resistance measurements is Prima
ry Test Manager (PTM). PTM shows the
switching process of the individual taps in
a single diagram, so that they can be com
pared amongst each other easily. As the
current signatures of many OLTC designs
may vary by their phase and switching di
rection, the PTM software offers unique
filtering options to compare up and down
operations for even and odd positions and
all three phases. This enables the user to
analyse measurement results for a com
prehensive failure diagnosis.
Conclusion
A conventional static resistance measure
ment can be used to test the winding as
well as all of the fixed internal connec
tions. In some cases, however, it is not
possible to detect defects using the stand
ard winding resistance measurement [9].
Therefore, the DRM as a supplementary
measurement has proved to be benefi
cial for analysing the switching process
and mobile contacts of OLTCs on power
transformers. By using the same test setup
as for static resistance, the DRM function
enables insight into the fast switching
process of the diverter switch to detect
mechanical wear-and-tear of the contacts,
leads and commutating resistors without
additional wiring effort. As a result, the
reliability of the OLTC assessment can be
improved; maintenance costs can be re
duced; and most importantly, unexpected
and expensive outages can be avoided.
Bibliography
[1] Cigré Working Group A2.3, 2015, TB 642 -
TransformerReliabilitySurvey
[2] Rudolf Klaus, 50 Jahre VDE Bezirksverein
Nordbayern, Die Entwicklung von Stufen-
schaltern für Hochspannungstransformatoren
[3]K.Viereck,A.Saveliev,Acoustic Tap-Chan-
ger Monitoring using Wavelet Analyses, ISH
2015,Pilsen,2015
[4] IEEE Guide for Dissolved Gas Analysis
in Transformer Load Tap Changers, IEEE
C57.139-2010
[5] Jur Erbrink, Edward Gulski, Johan Smit,
Rory Leich, 20th International Conference on
Electricity Distribution, Experimental Model
for diagnosing on-load tap changer contact
aging with dynamic resistance measure-
ments,2009
[6] E. Woschnagg und H. Koglek, Zum Prob-
lem der Widerstandsmessung von niederoh-
migen Transformatorwicklungen,1977
[7] OMICRON, Standard electrical tests for
power transformers, www.omicron.at
[8] IEEE Standard Test Code for Liquid-Im
mersed Distribution, Power and Regulating
TransformersandIEEEGuideforShort-Circuit
Testing of Distribution and Power Transfor
mers,IEEEC57.12.90–2006
[9] Raka Levi, Budo Milovic, TechCon 2011,
OLTC Dynamic testing
DRMhasprovedtobebeneficialforanalysing
the switching process and mobile contacts
of OLTCs on power transformers
Authors
Cornelius Plath graduated with a Master’s degree in Electrical
Power Engineering and Business Administration from the RWTH
Aachen University in Germany. During his studies he was involved
with several industry funded research projects on the condition
assessment of electrical power apparatuses at the Institute of High
Voltage Technology. He joined OMICRON in 2010 as an Applica
tion Engineer, and currently holds a Product Manager position. He
has extensive international application experience, specializing in the electrical diag
nostics of circuit breakers and power transformers.
Markus Pütter studied electrical Engineering at the University
of Paderborn and graduated in 1997. From 1999 he worked for
OMICRON electronics, first as an electrical engineer in the field of
transformer diagnostics, and from 2008 onwards as product man
ager for testing and diagnostic solutions for primary assets. In his
roleasproductmanager,hefocusedondevelopinginnovativesolu
tions for power transformer testing. Markus Pütter was a member
of the IEC TC14 transformer committee and the Cigre Working Group A1.39. He was
also actively involved in an AM Forum working group focusing on Dynamic Resistance
Measurement on on-load tap changers (DRM on OLTCs). Markus passed away in June
2015 following a tragic accident.
www.transformers-magazine.com 109