Case Study
Importance of Relay Selection in Grid
Connected Industries
Just like all other cases, we bring you one
more actual incident happened recently in
one of the Process Industry, connected with
GRID (State Utility). In our 18 years of service
to industries, we have come across many
abnormalities, incident and have resolved
them. Even we learn while solving the
issues or Tripping incidents but summation
of these many years of experience has
strengthen us to resolve this type of
incidents in time. However, this is the first
time we came across this kind of issue.
Then we asked Rare check. To change
the phase sequence of Incoming Voltage
supply in relay for all the combinations
as RYB, RBY, YRB, YBR, BYR, BRY.
To our surprise!!!!! With combination RBY,
relay contact got reset and plant was
started.
We also asked them to check with other
plant connected to GRID with same
feeders and found:
Their Motors were running in Reverse
direction and same has leads to certain
issues related to process. Adding
additional down time.
Same was issue with other plants as
well.
www.systemprotection.in +91-265-2225137
On a lighter note, to our knowledge, most of
the abnormalities, Tripping or operational
problems in Industries happens on Sunday
or Holidays only. Keeping legacy alive, this
also occurred on Sunday evening 4 PM in
the month of Feb 2019.
Here under is the summary:
It was planned shutdown from Grid side
for adding new 33 kV distribution line to
their substation. Same was informed to
all the consumers 2 weeks in advance
for this shutdown which was scheduled
for 2-3 hours in continuation.
All goes well as per schedule, Power
resumed within 2.5 hours but………….
Connected Industries failed to start.
Reason….? Unhealthy Voltage. And relay
blocked Circuit breakers to close
pertaining to Unhealthy Voltage.
Then started troubleshooting:
They checked PT supply, found healthy.
If during shutdown, any modification/s
OR Change/s made in the wiring? No,
everything was as it was.
They took all possible measures, but
waste. Relay keep issuing tripping
command.
Worried about the incident, we got
distressed call from user:
We enquired with them and asked
whether all necessary measures have
been taken.
We asked them to check in relay
configuration, but not necessarily plant
people knows it.
We even advised to reboot the relay, if in
case it may have hanged.
The problem was identified as change in
Phase sequence mistakenly by GRID side
during shutdown. We advised plant people
to keep the original wiring so that if this
happens again in future than same can be
identify and rectify.
Well, we got their appreciation as System
Protection has been involved in Selection
and Retrofitting of relays. If the plant has
been started with reverse direction more
revenue loss would have registered.
Proper Relay Selection for Equipment’s
play a key role in Protecting your plant
equipment in the best way.
The relay sensed the Phase Reversal as
unhealthy voltage and therefore, was giving
tripping commands. Under pressure,
maintenance engineer Bypassed
Undervoltage protection and charged the
panel as he was concerned about
production lost. But when Relay is at fault
you can't even change or disable setting,
and this is blessing in disguise.
Our team during annual Relay testing in
shutdown (July 2018), suggested and
enabled this setting.
We feel sorry for the other industries who
suffered due to improper relay selection.
Damage has already occurred. To avoid this
we strongly recommend, while selecting
protective relays either in Projects or
retrofitting, all the points must be
considered pertaining to protection and
process perspective.
CONTACT INFORMATION
301/2/306, Silverline Complex,Opposite BBC
Tower,Sayajigunj,Vadodara - 390 005,
Gujarat, India.
bdm@systemprotection.in
www.systemprotection.in
+91-265-2225137

More Related Content

What's hot

Protection of transformer
Protection of transformerProtection of transformer
Protection of transformer
Sumeet Ratnawat
 
Transformers Protection
Transformers ProtectionTransformers Protection
Transformers Protection
Power System Operation
 
Testing,maintenance&protection
Testing,maintenance&protectionTesting,maintenance&protection
Testing,maintenance&protection
Rakesh Joshi
 
Power transformer protection
Power transformer protectionPower transformer protection
Power transformer protection
michaeljmack
 
Testing of transformer
Testing of transformerTesting of transformer
Testing of transformer
SMRITI KESHARWANI
 
Generator protection calculations settings
Generator protection calculations settingsGenerator protection calculations settings
Generator protection calculations settings
michaeljmack
 
Power Transformer Protection
Power Transformer ProtectionPower Transformer Protection
Power Transformer Protection
Ang Sovann
 
Generator Protection Relay Setting Calculations
Generator Protection Relay Setting CalculationsGenerator Protection Relay Setting Calculations
Generator Protection Relay Setting Calculations
Power System Operation
 
Power transformer testing and commissioning guidelines r
Power transformer testing and commissioning guidelines rPower transformer testing and commissioning guidelines r
Power transformer testing and commissioning guidelines r
Ashish Patel
 
Transformer protection
Transformer protectionTransformer protection
Transformer protection
jawaharramaya
 
Sample calculation-for-differential-relays
Sample calculation-for-differential-relaysSample calculation-for-differential-relays
Sample calculation-for-differential-relays
Roberto Costa
 
Power Transformer Protection
Power Transformer ProtectionPower Transformer Protection
Power Transformer Protection
Power System Operation
 
Transformer overcurrent
Transformer overcurrentTransformer overcurrent
Transformer overcurrent
michaeljmack
 
testing formats
testing formatstesting formats
testing formats
Abhishek Shukla
 
3. INTRODUCTION TO PROTECTIVE RELAYING.pptx
3. INTRODUCTION TO PROTECTIVE RELAYING.pptx3. INTRODUCTION TO PROTECTIVE RELAYING.pptx
3. INTRODUCTION TO PROTECTIVE RELAYING.pptx
Muhd Hafizi Idris
 
substation protection basics.ppt
substation protection basics.pptsubstation protection basics.ppt
substation protection basics.ppt
Salim Palayi
 
Tap changer
Tap changerTap changer
Tap changer
vivek1292
 
30, 31st July 2012 - The India Blackout
30, 31st July 2012 - The India Blackout30, 31st July 2012 - The India Blackout
30, 31st July 2012 - The India Blackoutgiridaran123
 
05 ETAP Harmonic Analysis.pptx
05 ETAP Harmonic Analysis.pptx05 ETAP Harmonic Analysis.pptx
05 ETAP Harmonic Analysis.pptx
Thabang3
 

What's hot (20)

Protection of transformer
Protection of transformerProtection of transformer
Protection of transformer
 
Transformers Protection
Transformers ProtectionTransformers Protection
Transformers Protection
 
Testing,maintenance&protection
Testing,maintenance&protectionTesting,maintenance&protection
Testing,maintenance&protection
 
Power transformer protection
Power transformer protectionPower transformer protection
Power transformer protection
 
Testing of transformer
Testing of transformerTesting of transformer
Testing of transformer
 
Generator protection calculations settings
Generator protection calculations settingsGenerator protection calculations settings
Generator protection calculations settings
 
Power Transformer Protection
Power Transformer ProtectionPower Transformer Protection
Power Transformer Protection
 
Generator Protection Relay Setting Calculations
Generator Protection Relay Setting CalculationsGenerator Protection Relay Setting Calculations
Generator Protection Relay Setting Calculations
 
Power transformer testing and commissioning guidelines r
Power transformer testing and commissioning guidelines rPower transformer testing and commissioning guidelines r
Power transformer testing and commissioning guidelines r
 
Transformer protection
Transformer protectionTransformer protection
Transformer protection
 
Sample calculation-for-differential-relays
Sample calculation-for-differential-relaysSample calculation-for-differential-relays
Sample calculation-for-differential-relays
 
Power Transformer Protection
Power Transformer ProtectionPower Transformer Protection
Power Transformer Protection
 
Transformer overcurrent
Transformer overcurrentTransformer overcurrent
Transformer overcurrent
 
testing formats
testing formatstesting formats
testing formats
 
3. INTRODUCTION TO PROTECTIVE RELAYING.pptx
3. INTRODUCTION TO PROTECTIVE RELAYING.pptx3. INTRODUCTION TO PROTECTIVE RELAYING.pptx
3. INTRODUCTION TO PROTECTIVE RELAYING.pptx
 
substation protection basics.ppt
substation protection basics.pptsubstation protection basics.ppt
substation protection basics.ppt
 
Tap changer
Tap changerTap changer
Tap changer
 
30, 31st July 2012 - The India Blackout
30, 31st July 2012 - The India Blackout30, 31st July 2012 - The India Blackout
30, 31st July 2012 - The India Blackout
 
Protection and Switchgear
Protection and SwitchgearProtection and Switchgear
Protection and Switchgear
 
05 ETAP Harmonic Analysis.pptx
05 ETAP Harmonic Analysis.pptx05 ETAP Harmonic Analysis.pptx
05 ETAP Harmonic Analysis.pptx
 

Similar to Case Study Importance of relay selection in grid connected industries

Importance of Relay Selection in Grid Connected Industries
Importance of Relay Selection in Grid Connected IndustriesImportance of Relay Selection in Grid Connected Industries
Importance of Relay Selection in Grid Connected Industries
System Protection
 
Case Study - How we saved a Process Plant from break-down
Case Study - How we saved a Process Plant from break-downCase Study - How we saved a Process Plant from break-down
Case Study - How we saved a Process Plant from break-down
System Protection
 
Case Study | How we solved an Earth-fault (mal)Tripping that was causing trip...
Case Study | How we solved an Earth-fault (mal)Tripping that was causing trip...Case Study | How we solved an Earth-fault (mal)Tripping that was causing trip...
Case Study | How we solved an Earth-fault (mal)Tripping that was causing trip...
System Protection
 
How we saved a Process Plant from break-down
How we saved a Process Plant from break-downHow we saved a Process Plant from break-down
How we saved a Process Plant from break-down
System Protection
 
Maintenance and Test Equipment Cyber Security
Maintenance and Test Equipment Cyber Security Maintenance and Test Equipment Cyber Security
Maintenance and Test Equipment Cyber Security
Michael Toecker
 
Tracking PV module degradation using SolarPulse
Tracking PV module degradation using SolarPulseTracking PV module degradation using SolarPulse
Tracking PV module degradation using SolarPulse
MachinePulse
 
Part 1: frequently asked electrical engineering interview questions
Part 1: frequently asked electrical engineering interview questionsPart 1: frequently asked electrical engineering interview questions
Part 1: frequently asked electrical engineering interview questions
Poonam Kherde
 
Continuity of Supply means Continuity of Production
Continuity of Supply means Continuity of ProductionContinuity of Supply means Continuity of Production
Continuity of Supply means Continuity of Production
Rusty Roar Enterprises
 
Case Study – How an Unchecked Capacitor can cause loss of revenue
Case Study – How an Unchecked Capacitor can cause loss of revenueCase Study – How an Unchecked Capacitor can cause loss of revenue
Case Study – How an Unchecked Capacitor can cause loss of revenue
System Protection
 
Ieee pes psrc
Ieee pes psrcIeee pes psrc
Ieee pes psrc
michaeljmack
 
How to tune PID loops
How to tune PID loopsHow to tune PID loops
How to tune PID loops
saeed shafiei
 
How to tune pid loops
How to tune pid loopsHow to tune pid loops
How to tune pid loops
saeed shafiei
 
NeuCo's MaintenanceOpt Great Catches
NeuCo's MaintenanceOpt Great Catches NeuCo's MaintenanceOpt Great Catches
NeuCo's MaintenanceOpt Great Catches
NeuCo, Inc
 
Is pat testing a legal requirement
Is pat testing a legal requirementIs pat testing a legal requirement
Is pat testing a legal requirement
Mirza Rihad Ali Sunny
 
How Auxiliary Contactors mounting may result into Mal-operation & hence tripp...
How Auxiliary Contactors mounting may result into Mal-operation & hence tripp...How Auxiliary Contactors mounting may result into Mal-operation & hence tripp...
How Auxiliary Contactors mounting may result into Mal-operation & hence tripp...
System Protection
 
Process Profiling: Investigation And Prediction Of Process Upsets With Advanc...
Process Profiling: Investigation And Prediction Of Process Upsets With Advanc...Process Profiling: Investigation And Prediction Of Process Upsets With Advanc...
Process Profiling: Investigation And Prediction Of Process Upsets With Advanc...
Jim Cahill
 
Risk management in complex changeovers through cfmea
Risk management in complex changeovers through cfmeaRisk management in complex changeovers through cfmea
Risk management in complex changeovers through cfmea
Dr. Bikram Jit Singh
 
How to Setup and Adjust the Dynamic Compensation of Feedforward Signals
How to Setup and Adjust the Dynamic Compensation of Feedforward SignalsHow to Setup and Adjust the Dynamic Compensation of Feedforward Signals
How to Setup and Adjust the Dynamic Compensation of Feedforward Signals
Jim Cahill
 

Similar to Case Study Importance of relay selection in grid connected industries (20)

Importance of Relay Selection in Grid Connected Industries
Importance of Relay Selection in Grid Connected IndustriesImportance of Relay Selection in Grid Connected Industries
Importance of Relay Selection in Grid Connected Industries
 
Case Study - How we saved a Process Plant from break-down
Case Study - How we saved a Process Plant from break-downCase Study - How we saved a Process Plant from break-down
Case Study - How we saved a Process Plant from break-down
 
Case Study | How we solved an Earth-fault (mal)Tripping that was causing trip...
Case Study | How we solved an Earth-fault (mal)Tripping that was causing trip...Case Study | How we solved an Earth-fault (mal)Tripping that was causing trip...
Case Study | How we solved an Earth-fault (mal)Tripping that was causing trip...
 
How we saved a Process Plant from break-down
How we saved a Process Plant from break-downHow we saved a Process Plant from break-down
How we saved a Process Plant from break-down
 
Maintenance and Test Equipment Cyber Security
Maintenance and Test Equipment Cyber Security Maintenance and Test Equipment Cyber Security
Maintenance and Test Equipment Cyber Security
 
Tracking PV module degradation using SolarPulse
Tracking PV module degradation using SolarPulseTracking PV module degradation using SolarPulse
Tracking PV module degradation using SolarPulse
 
Before and After Power Conditioner
Before and After Power ConditionerBefore and After Power Conditioner
Before and After Power Conditioner
 
Part 1: frequently asked electrical engineering interview questions
Part 1: frequently asked electrical engineering interview questionsPart 1: frequently asked electrical engineering interview questions
Part 1: frequently asked electrical engineering interview questions
 
Continuity of Supply means Continuity of Production
Continuity of Supply means Continuity of ProductionContinuity of Supply means Continuity of Production
Continuity of Supply means Continuity of Production
 
Case Study – How an Unchecked Capacitor can cause loss of revenue
Case Study – How an Unchecked Capacitor can cause loss of revenueCase Study – How an Unchecked Capacitor can cause loss of revenue
Case Study – How an Unchecked Capacitor can cause loss of revenue
 
Ieee pes psrc
Ieee pes psrcIeee pes psrc
Ieee pes psrc
 
How to tune PID loops
How to tune PID loopsHow to tune PID loops
How to tune PID loops
 
How to tune pid loops
How to tune pid loopsHow to tune pid loops
How to tune pid loops
 
NeuCo's MaintenanceOpt Great Catches
NeuCo's MaintenanceOpt Great Catches NeuCo's MaintenanceOpt Great Catches
NeuCo's MaintenanceOpt Great Catches
 
Is pat testing a legal requirement
Is pat testing a legal requirementIs pat testing a legal requirement
Is pat testing a legal requirement
 
How Auxiliary Contactors mounting may result into Mal-operation & hence tripp...
How Auxiliary Contactors mounting may result into Mal-operation & hence tripp...How Auxiliary Contactors mounting may result into Mal-operation & hence tripp...
How Auxiliary Contactors mounting may result into Mal-operation & hence tripp...
 
Process Profiling: Investigation And Prediction Of Process Upsets With Advanc...
Process Profiling: Investigation And Prediction Of Process Upsets With Advanc...Process Profiling: Investigation And Prediction Of Process Upsets With Advanc...
Process Profiling: Investigation And Prediction Of Process Upsets With Advanc...
 
BATHUSA RESUME 2
BATHUSA RESUME 2BATHUSA RESUME 2
BATHUSA RESUME 2
 
Risk management in complex changeovers through cfmea
Risk management in complex changeovers through cfmeaRisk management in complex changeovers through cfmea
Risk management in complex changeovers through cfmea
 
How to Setup and Adjust the Dynamic Compensation of Feedforward Signals
How to Setup and Adjust the Dynamic Compensation of Feedforward SignalsHow to Setup and Adjust the Dynamic Compensation of Feedforward Signals
How to Setup and Adjust the Dynamic Compensation of Feedforward Signals
 

More from System Protection

Transformer differential protection – SIEMENS Reyrolle 7SR54
Transformer differential protection – SIEMENS Reyrolle 7SR54Transformer differential protection – SIEMENS Reyrolle 7SR54
Transformer differential protection – SIEMENS Reyrolle 7SR54
System Protection
 
Mastering Motor Protection with SIEMENS Reyrolle 7SR17: Safeguarding Your Assets
Mastering Motor Protection with SIEMENS Reyrolle 7SR17: Safeguarding Your AssetsMastering Motor Protection with SIEMENS Reyrolle 7SR17: Safeguarding Your Assets
Mastering Motor Protection with SIEMENS Reyrolle 7SR17: Safeguarding Your Assets
System Protection
 
AC Digital Clamp Meter KEW 2204R Overview | System Protection
AC Digital Clamp Meter KEW 2204R Overview | System ProtectionAC Digital Clamp Meter KEW 2204R Overview | System Protection
AC Digital Clamp Meter KEW 2204R Overview | System Protection
System Protection
 
Digital Multimeter with AC/DC Clamp Sensor KEWMATE 2012RA | System Protection
Digital Multimeter with AC/DC Clamp Sensor KEWMATE 2012RA | System ProtectionDigital Multimeter with AC/DC Clamp Sensor KEWMATE 2012RA | System Protection
Digital Multimeter with AC/DC Clamp Sensor KEWMATE 2012RA | System Protection
System Protection
 
DIGITAL MULTIMETERS KEW 1052 | System Protection
DIGITAL MULTIMETERS KEW 1052 | System ProtectionDIGITAL MULTIMETERS KEW 1052 | System Protection
DIGITAL MULTIMETERS KEW 1052 | System Protection
System Protection
 
Kyoritsu Voltage Detector KEW 5711
Kyoritsu Voltage Detector KEW 5711Kyoritsu Voltage Detector KEW 5711
Kyoritsu Voltage Detector KEW 5711
System Protection
 
Earth Clamp Testing with the KEW 4202 | Ultimate Tool for Earth Clamp Testing
Earth Clamp Testing with the KEW 4202 | Ultimate Tool for Earth Clamp TestingEarth Clamp Testing with the KEW 4202 | Ultimate Tool for Earth Clamp Testing
Earth Clamp Testing with the KEW 4202 | Ultimate Tool for Earth Clamp Testing
System Protection
 
Kyoritsu Multi-Function Testers | KEW 6016
Kyoritsu Multi-Function Testers | KEW 6016Kyoritsu Multi-Function Testers | KEW 6016
Kyoritsu Multi-Function Testers | KEW 6016
System Protection
 
Honeywell | Overcoat | Fabric Composition (Patented)
Honeywell | Overcoat | Fabric Composition (Patented)Honeywell | Overcoat | Fabric Composition (Patented)
Honeywell | Overcoat | Fabric Composition (Patented)
System Protection
 
HONEYWELL - Electrical Safety Mat | HONEYWELL Insulating Rubber Mat
HONEYWELL - Electrical Safety Mat | HONEYWELL Insulating Rubber MatHONEYWELL - Electrical Safety Mat | HONEYWELL Insulating Rubber Mat
HONEYWELL - Electrical Safety Mat | HONEYWELL Insulating Rubber Mat
System Protection
 
Salisbury By Honeywell | 51511 Di – Electric Over Shoes
Salisbury By Honeywell | 51511 Di – Electric Over ShoesSalisbury By Honeywell | 51511 Di – Electric Over Shoes
Salisbury By Honeywell | 51511 Di – Electric Over Shoes
System Protection
 
Salisbury By Honeywell | 4556 Voltage Detector 240V to 230kV
Salisbury By Honeywell | 4556 Voltage Detector 240V to 230kVSalisbury By Honeywell | 4556 Voltage Detector 240V to 230kV
Salisbury By Honeywell | 4556 Voltage Detector 240V to 230kV
System Protection
 
LOGGER KEW 5020 | KYORITSU | System Protection
LOGGER KEW 5020 | KYORITSU | System ProtectionLOGGER KEW 5020 | KYORITSU | System Protection
LOGGER KEW 5020 | KYORITSU | System Protection
System Protection
 
PORTABLE APPLIANCE TESTER KEW 6205 | KYORITSU | System Protection
PORTABLE APPLIANCE TESTER KEW 6205 | KYORITSU | System ProtectionPORTABLE APPLIANCE TESTER KEW 6205 | KYORITSU | System Protection
PORTABLE APPLIANCE TESTER KEW 6205 | KYORITSU | System Protection
System Protection
 
RCD TESTER KEW 5410| KYORITSU | System Protection
RCD TESTER KEW 5410| KYORITSU | System ProtectionRCD TESTER KEW 5410| KYORITSU | System Protection
RCD TESTER KEW 5410| KYORITSU | System Protection
System Protection
 
Case Study | How your Motor Protection should designed when running in parall...
Case Study | How your Motor Protection should designed when running in parall...Case Study | How your Motor Protection should designed when running in parall...
Case Study | How your Motor Protection should designed when running in parall...
System Protection
 
Case Study | How we saved a Generator (in fact two), again!
Case Study | How we saved a Generator (in fact two), again!Case Study | How we saved a Generator (in fact two), again!
Case Study | How we saved a Generator (in fact two), again!
System Protection
 
AC/DC Digital Clamp Meters | KEW 2010 | Kyoritsu
AC/DC Digital Clamp Meters | KEW 2010 | KyoritsuAC/DC Digital Clamp Meters | KEW 2010 | Kyoritsu
AC/DC Digital Clamp Meters | KEW 2010 | Kyoritsu
System Protection
 
Digital Multimeters | KEW 1051 | Kyoritsu
Digital Multimeters | KEW 1051 | KyoritsuDigital Multimeters | KEW 1051 | Kyoritsu
Digital Multimeters | KEW 1051 | Kyoritsu
System Protection
 
Digital Multimeters | KEW 1020R | Kyoritsu
Digital Multimeters | KEW 1020R | KyoritsuDigital Multimeters | KEW 1020R | Kyoritsu
Digital Multimeters | KEW 1020R | Kyoritsu
System Protection
 

More from System Protection (20)

Transformer differential protection – SIEMENS Reyrolle 7SR54
Transformer differential protection – SIEMENS Reyrolle 7SR54Transformer differential protection – SIEMENS Reyrolle 7SR54
Transformer differential protection – SIEMENS Reyrolle 7SR54
 
Mastering Motor Protection with SIEMENS Reyrolle 7SR17: Safeguarding Your Assets
Mastering Motor Protection with SIEMENS Reyrolle 7SR17: Safeguarding Your AssetsMastering Motor Protection with SIEMENS Reyrolle 7SR17: Safeguarding Your Assets
Mastering Motor Protection with SIEMENS Reyrolle 7SR17: Safeguarding Your Assets
 
AC Digital Clamp Meter KEW 2204R Overview | System Protection
AC Digital Clamp Meter KEW 2204R Overview | System ProtectionAC Digital Clamp Meter KEW 2204R Overview | System Protection
AC Digital Clamp Meter KEW 2204R Overview | System Protection
 
Digital Multimeter with AC/DC Clamp Sensor KEWMATE 2012RA | System Protection
Digital Multimeter with AC/DC Clamp Sensor KEWMATE 2012RA | System ProtectionDigital Multimeter with AC/DC Clamp Sensor KEWMATE 2012RA | System Protection
Digital Multimeter with AC/DC Clamp Sensor KEWMATE 2012RA | System Protection
 
DIGITAL MULTIMETERS KEW 1052 | System Protection
DIGITAL MULTIMETERS KEW 1052 | System ProtectionDIGITAL MULTIMETERS KEW 1052 | System Protection
DIGITAL MULTIMETERS KEW 1052 | System Protection
 
Kyoritsu Voltage Detector KEW 5711
Kyoritsu Voltage Detector KEW 5711Kyoritsu Voltage Detector KEW 5711
Kyoritsu Voltage Detector KEW 5711
 
Earth Clamp Testing with the KEW 4202 | Ultimate Tool for Earth Clamp Testing
Earth Clamp Testing with the KEW 4202 | Ultimate Tool for Earth Clamp TestingEarth Clamp Testing with the KEW 4202 | Ultimate Tool for Earth Clamp Testing
Earth Clamp Testing with the KEW 4202 | Ultimate Tool for Earth Clamp Testing
 
Kyoritsu Multi-Function Testers | KEW 6016
Kyoritsu Multi-Function Testers | KEW 6016Kyoritsu Multi-Function Testers | KEW 6016
Kyoritsu Multi-Function Testers | KEW 6016
 
Honeywell | Overcoat | Fabric Composition (Patented)
Honeywell | Overcoat | Fabric Composition (Patented)Honeywell | Overcoat | Fabric Composition (Patented)
Honeywell | Overcoat | Fabric Composition (Patented)
 
HONEYWELL - Electrical Safety Mat | HONEYWELL Insulating Rubber Mat
HONEYWELL - Electrical Safety Mat | HONEYWELL Insulating Rubber MatHONEYWELL - Electrical Safety Mat | HONEYWELL Insulating Rubber Mat
HONEYWELL - Electrical Safety Mat | HONEYWELL Insulating Rubber Mat
 
Salisbury By Honeywell | 51511 Di – Electric Over Shoes
Salisbury By Honeywell | 51511 Di – Electric Over ShoesSalisbury By Honeywell | 51511 Di – Electric Over Shoes
Salisbury By Honeywell | 51511 Di – Electric Over Shoes
 
Salisbury By Honeywell | 4556 Voltage Detector 240V to 230kV
Salisbury By Honeywell | 4556 Voltage Detector 240V to 230kVSalisbury By Honeywell | 4556 Voltage Detector 240V to 230kV
Salisbury By Honeywell | 4556 Voltage Detector 240V to 230kV
 
LOGGER KEW 5020 | KYORITSU | System Protection
LOGGER KEW 5020 | KYORITSU | System ProtectionLOGGER KEW 5020 | KYORITSU | System Protection
LOGGER KEW 5020 | KYORITSU | System Protection
 
PORTABLE APPLIANCE TESTER KEW 6205 | KYORITSU | System Protection
PORTABLE APPLIANCE TESTER KEW 6205 | KYORITSU | System ProtectionPORTABLE APPLIANCE TESTER KEW 6205 | KYORITSU | System Protection
PORTABLE APPLIANCE TESTER KEW 6205 | KYORITSU | System Protection
 
RCD TESTER KEW 5410| KYORITSU | System Protection
RCD TESTER KEW 5410| KYORITSU | System ProtectionRCD TESTER KEW 5410| KYORITSU | System Protection
RCD TESTER KEW 5410| KYORITSU | System Protection
 
Case Study | How your Motor Protection should designed when running in parall...
Case Study | How your Motor Protection should designed when running in parall...Case Study | How your Motor Protection should designed when running in parall...
Case Study | How your Motor Protection should designed when running in parall...
 
Case Study | How we saved a Generator (in fact two), again!
Case Study | How we saved a Generator (in fact two), again!Case Study | How we saved a Generator (in fact two), again!
Case Study | How we saved a Generator (in fact two), again!
 
AC/DC Digital Clamp Meters | KEW 2010 | Kyoritsu
AC/DC Digital Clamp Meters | KEW 2010 | KyoritsuAC/DC Digital Clamp Meters | KEW 2010 | Kyoritsu
AC/DC Digital Clamp Meters | KEW 2010 | Kyoritsu
 
Digital Multimeters | KEW 1051 | Kyoritsu
Digital Multimeters | KEW 1051 | KyoritsuDigital Multimeters | KEW 1051 | Kyoritsu
Digital Multimeters | KEW 1051 | Kyoritsu
 
Digital Multimeters | KEW 1020R | Kyoritsu
Digital Multimeters | KEW 1020R | KyoritsuDigital Multimeters | KEW 1020R | Kyoritsu
Digital Multimeters | KEW 1020R | Kyoritsu
 

Recently uploaded

Putting the SPARK into Virtual Training.pptx
Putting the SPARK into Virtual Training.pptxPutting the SPARK into Virtual Training.pptx
Putting the SPARK into Virtual Training.pptx
Cynthia Clay
 
Buy Verified PayPal Account | Buy Google 5 Star Reviews
Buy Verified PayPal Account | Buy Google 5 Star ReviewsBuy Verified PayPal Account | Buy Google 5 Star Reviews
Buy Verified PayPal Account | Buy Google 5 Star Reviews
usawebmarket
 
5 Things You Need To Know Before Hiring a Videographer
5 Things You Need To Know Before Hiring a Videographer5 Things You Need To Know Before Hiring a Videographer
5 Things You Need To Know Before Hiring a Videographer
ofm712785
 
RMD24 | Debunking the non-endemic revenue myth Marvin Vacquier Droop | First ...
RMD24 | Debunking the non-endemic revenue myth Marvin Vacquier Droop | First ...RMD24 | Debunking the non-endemic revenue myth Marvin Vacquier Droop | First ...
RMD24 | Debunking the non-endemic revenue myth Marvin Vacquier Droop | First ...
BBPMedia1
 
Memorandum Of Association Constitution of Company.ppt
Memorandum Of Association Constitution of Company.pptMemorandum Of Association Constitution of Company.ppt
Memorandum Of Association Constitution of Company.ppt
seri bangash
 
The Parable of the Pipeline a book every new businessman or business student ...
The Parable of the Pipeline a book every new businessman or business student ...The Parable of the Pipeline a book every new businessman or business student ...
The Parable of the Pipeline a book every new businessman or business student ...
awaisafdar
 
RMD24 | Retail media: hoe zet je dit in als je geen AH of Unilever bent? Heid...
RMD24 | Retail media: hoe zet je dit in als je geen AH of Unilever bent? Heid...RMD24 | Retail media: hoe zet je dit in als je geen AH of Unilever bent? Heid...
RMD24 | Retail media: hoe zet je dit in als je geen AH of Unilever bent? Heid...
BBPMedia1
 
CADAVER AS OUR FIRST TEACHER anatomt in your.pptx
CADAVER AS OUR FIRST TEACHER anatomt in your.pptxCADAVER AS OUR FIRST TEACHER anatomt in your.pptx
CADAVER AS OUR FIRST TEACHER anatomt in your.pptx
fakeloginn69
 
anas about venice for grade 6f about venice
anas about venice for grade 6f about veniceanas about venice for grade 6f about venice
anas about venice for grade 6f about venice
anasabutalha2013
 
Enterprise Excellence is Inclusive Excellence.pdf
Enterprise Excellence is Inclusive Excellence.pdfEnterprise Excellence is Inclusive Excellence.pdf
Enterprise Excellence is Inclusive Excellence.pdf
KaiNexus
 
Business Valuation Principles for Entrepreneurs
Business Valuation Principles for EntrepreneursBusiness Valuation Principles for Entrepreneurs
Business Valuation Principles for Entrepreneurs
Ben Wann
 
The-McKinsey-7S-Framework. strategic management
The-McKinsey-7S-Framework. strategic managementThe-McKinsey-7S-Framework. strategic management
The-McKinsey-7S-Framework. strategic management
Bojamma2
 
Premium MEAN Stack Development Solutions for Modern Businesses
Premium MEAN Stack Development Solutions for Modern BusinessesPremium MEAN Stack Development Solutions for Modern Businesses
Premium MEAN Stack Development Solutions for Modern Businesses
SynapseIndia
 
The effects of customers service quality and online reviews on customer loyal...
The effects of customers service quality and online reviews on customer loyal...The effects of customers service quality and online reviews on customer loyal...
The effects of customers service quality and online reviews on customer loyal...
balatucanapplelovely
 
amptalk_RecruitingDeck_english_2024.06.05
amptalk_RecruitingDeck_english_2024.06.05amptalk_RecruitingDeck_english_2024.06.05
amptalk_RecruitingDeck_english_2024.06.05
marketing317746
 
Search Disrupted Google’s Leaked Documents Rock the SEO World.pdf
Search Disrupted Google’s Leaked Documents Rock the SEO World.pdfSearch Disrupted Google’s Leaked Documents Rock the SEO World.pdf
Search Disrupted Google’s Leaked Documents Rock the SEO World.pdf
Arihant Webtech Pvt. Ltd
 
The Influence of Marketing Strategy and Market Competition on Business Perfor...
The Influence of Marketing Strategy and Market Competition on Business Perfor...The Influence of Marketing Strategy and Market Competition on Business Perfor...
The Influence of Marketing Strategy and Market Competition on Business Perfor...
Adam Smith
 
Maksym Vyshnivetskyi: PMO Quality Management (UA)
Maksym Vyshnivetskyi: PMO Quality Management (UA)Maksym Vyshnivetskyi: PMO Quality Management (UA)
Maksym Vyshnivetskyi: PMO Quality Management (UA)
Lviv Startup Club
 
Kseniya Leshchenko: Shared development support service model as the way to ma...
Kseniya Leshchenko: Shared development support service model as the way to ma...Kseniya Leshchenko: Shared development support service model as the way to ma...
Kseniya Leshchenko: Shared development support service model as the way to ma...
Lviv Startup Club
 
What are the main advantages of using HR recruiter services.pdf
What are the main advantages of using HR recruiter services.pdfWhat are the main advantages of using HR recruiter services.pdf
What are the main advantages of using HR recruiter services.pdf
HumanResourceDimensi1
 

Recently uploaded (20)

Putting the SPARK into Virtual Training.pptx
Putting the SPARK into Virtual Training.pptxPutting the SPARK into Virtual Training.pptx
Putting the SPARK into Virtual Training.pptx
 
Buy Verified PayPal Account | Buy Google 5 Star Reviews
Buy Verified PayPal Account | Buy Google 5 Star ReviewsBuy Verified PayPal Account | Buy Google 5 Star Reviews
Buy Verified PayPal Account | Buy Google 5 Star Reviews
 
5 Things You Need To Know Before Hiring a Videographer
5 Things You Need To Know Before Hiring a Videographer5 Things You Need To Know Before Hiring a Videographer
5 Things You Need To Know Before Hiring a Videographer
 
RMD24 | Debunking the non-endemic revenue myth Marvin Vacquier Droop | First ...
RMD24 | Debunking the non-endemic revenue myth Marvin Vacquier Droop | First ...RMD24 | Debunking the non-endemic revenue myth Marvin Vacquier Droop | First ...
RMD24 | Debunking the non-endemic revenue myth Marvin Vacquier Droop | First ...
 
Memorandum Of Association Constitution of Company.ppt
Memorandum Of Association Constitution of Company.pptMemorandum Of Association Constitution of Company.ppt
Memorandum Of Association Constitution of Company.ppt
 
The Parable of the Pipeline a book every new businessman or business student ...
The Parable of the Pipeline a book every new businessman or business student ...The Parable of the Pipeline a book every new businessman or business student ...
The Parable of the Pipeline a book every new businessman or business student ...
 
RMD24 | Retail media: hoe zet je dit in als je geen AH of Unilever bent? Heid...
RMD24 | Retail media: hoe zet je dit in als je geen AH of Unilever bent? Heid...RMD24 | Retail media: hoe zet je dit in als je geen AH of Unilever bent? Heid...
RMD24 | Retail media: hoe zet je dit in als je geen AH of Unilever bent? Heid...
 
CADAVER AS OUR FIRST TEACHER anatomt in your.pptx
CADAVER AS OUR FIRST TEACHER anatomt in your.pptxCADAVER AS OUR FIRST TEACHER anatomt in your.pptx
CADAVER AS OUR FIRST TEACHER anatomt in your.pptx
 
anas about venice for grade 6f about venice
anas about venice for grade 6f about veniceanas about venice for grade 6f about venice
anas about venice for grade 6f about venice
 
Enterprise Excellence is Inclusive Excellence.pdf
Enterprise Excellence is Inclusive Excellence.pdfEnterprise Excellence is Inclusive Excellence.pdf
Enterprise Excellence is Inclusive Excellence.pdf
 
Business Valuation Principles for Entrepreneurs
Business Valuation Principles for EntrepreneursBusiness Valuation Principles for Entrepreneurs
Business Valuation Principles for Entrepreneurs
 
The-McKinsey-7S-Framework. strategic management
The-McKinsey-7S-Framework. strategic managementThe-McKinsey-7S-Framework. strategic management
The-McKinsey-7S-Framework. strategic management
 
Premium MEAN Stack Development Solutions for Modern Businesses
Premium MEAN Stack Development Solutions for Modern BusinessesPremium MEAN Stack Development Solutions for Modern Businesses
Premium MEAN Stack Development Solutions for Modern Businesses
 
The effects of customers service quality and online reviews on customer loyal...
The effects of customers service quality and online reviews on customer loyal...The effects of customers service quality and online reviews on customer loyal...
The effects of customers service quality and online reviews on customer loyal...
 
amptalk_RecruitingDeck_english_2024.06.05
amptalk_RecruitingDeck_english_2024.06.05amptalk_RecruitingDeck_english_2024.06.05
amptalk_RecruitingDeck_english_2024.06.05
 
Search Disrupted Google’s Leaked Documents Rock the SEO World.pdf
Search Disrupted Google’s Leaked Documents Rock the SEO World.pdfSearch Disrupted Google’s Leaked Documents Rock the SEO World.pdf
Search Disrupted Google’s Leaked Documents Rock the SEO World.pdf
 
The Influence of Marketing Strategy and Market Competition on Business Perfor...
The Influence of Marketing Strategy and Market Competition on Business Perfor...The Influence of Marketing Strategy and Market Competition on Business Perfor...
The Influence of Marketing Strategy and Market Competition on Business Perfor...
 
Maksym Vyshnivetskyi: PMO Quality Management (UA)
Maksym Vyshnivetskyi: PMO Quality Management (UA)Maksym Vyshnivetskyi: PMO Quality Management (UA)
Maksym Vyshnivetskyi: PMO Quality Management (UA)
 
Kseniya Leshchenko: Shared development support service model as the way to ma...
Kseniya Leshchenko: Shared development support service model as the way to ma...Kseniya Leshchenko: Shared development support service model as the way to ma...
Kseniya Leshchenko: Shared development support service model as the way to ma...
 
What are the main advantages of using HR recruiter services.pdf
What are the main advantages of using HR recruiter services.pdfWhat are the main advantages of using HR recruiter services.pdf
What are the main advantages of using HR recruiter services.pdf
 

Case Study Importance of relay selection in grid connected industries

  • 1. www.systemprotection.in +91-265-2225137 ISO 9001:2015 ISO 45001:2015 (OH & S) Certified Company Case Study Importance of Relay Selection in Grid Connected Industries
  • 2. Just like all other cases, we bring you one more actual incident happened recently in one of the Process Industry, connected with GRID (State Utility). In our 18 years of service to industries, we have come across many abnormalities, incident and have resolved them. Even we learn while solving the issues or Tripping incidents but summation of these many years of experience has strengthen us to resolve this type of incidents in time. However, this is the first time we came across this kind of issue. Then we asked Rare check. To change the phase sequence of Incoming Voltage supply in relay for all the combinations as RYB, RBY, YRB, YBR, BYR, BRY. To our surprise!!!!! With combination RBY, relay contact got reset and plant was started. We also asked them to check with other plant connected to GRID with same feeders and found: Their Motors were running in Reverse direction and same has leads to certain issues related to process. Adding additional down time. Same was issue with other plants as well. www.systemprotection.in +91-265-2225137 On a lighter note, to our knowledge, most of the abnormalities, Tripping or operational problems in Industries happens on Sunday or Holidays only. Keeping legacy alive, this also occurred on Sunday evening 4 PM in the month of Feb 2019. Here under is the summary: It was planned shutdown from Grid side for adding new 33 kV distribution line to their substation. Same was informed to all the consumers 2 weeks in advance for this shutdown which was scheduled for 2-3 hours in continuation. All goes well as per schedule, Power resumed within 2.5 hours but…………. Connected Industries failed to start. Reason….? Unhealthy Voltage. And relay blocked Circuit breakers to close pertaining to Unhealthy Voltage. Then started troubleshooting: They checked PT supply, found healthy. If during shutdown, any modification/s OR Change/s made in the wiring? No, everything was as it was. They took all possible measures, but waste. Relay keep issuing tripping command. Worried about the incident, we got distressed call from user: We enquired with them and asked whether all necessary measures have been taken. We asked them to check in relay configuration, but not necessarily plant people knows it. We even advised to reboot the relay, if in case it may have hanged. The problem was identified as change in Phase sequence mistakenly by GRID side during shutdown. We advised plant people to keep the original wiring so that if this happens again in future than same can be identify and rectify. Well, we got their appreciation as System Protection has been involved in Selection and Retrofitting of relays. If the plant has been started with reverse direction more revenue loss would have registered. Proper Relay Selection for Equipment’s play a key role in Protecting your plant equipment in the best way. The relay sensed the Phase Reversal as unhealthy voltage and therefore, was giving tripping commands. Under pressure, maintenance engineer Bypassed Undervoltage protection and charged the panel as he was concerned about production lost. But when Relay is at fault you can't even change or disable setting, and this is blessing in disguise. Our team during annual Relay testing in shutdown (July 2018), suggested and enabled this setting. We feel sorry for the other industries who suffered due to improper relay selection. Damage has already occurred. To avoid this we strongly recommend, while selecting protective relays either in Projects or retrofitting, all the points must be considered pertaining to protection and process perspective.
  • 3. CONTACT INFORMATION 301/2/306, Silverline Complex,Opposite BBC Tower,Sayajigunj,Vadodara - 390 005, Gujarat, India. bdm@systemprotection.in www.systemprotection.in +91-265-2225137