IOSR Journal of Electrical and Electronics Engineering (IOSR-JEEE)
e-ISSN: 2278-1676,p-ISSN: 2320-3331, Volume 6, Issue 5 (Jul. - Aug. 2013), PP 01-09
www.iosrjournals.org
www.iosrjournals.org 1 | Page
Power Quality Improvement in Faulty Conditions using Tuned
Harmonic Filters
Sumit Kanwar1
, Om Prakash Mahela2
, Devendra Mittal3
1
(Senior Lecturer, Department of Electrical Engineering, Asians Institute of Technology, Jaipur, India)
2
(Graduate Student Member IEEE & Junior Engineer-I, RRVPNL, Jodhpur, India)
3
(Assistant Professor, Department of Electrical Engineering, Jagannath University, Jaipur, India)
Abstract : The Electrical power quality has become an important topic of discussion and research these days.
As per IEEE 519 std. parameters of power quality measurement, are four in number, of which Total Harmonic
Distortion is most widely used. This paper proposes the optimal planning of passive tuned harmonic filters for
improvement of power quality in faulty conditions of electrical power system. The Total Harmonic Distortion
analysis of power quality disturbances is carried out in the faulty conditions and in the presence of single tuned
and double tuned harmonic filters. The four bus system having two load and two generator buses is modeled in
MATLAB/Simulink environment. A fault is created near the load bus and power quality disturbances are
detected near the generator bus and improved using single tuned and double tuned filters near the generator
bus under study. The Matlab results show the performance of double tuned filter in improvement of power
quality disturbances during faulty conditions.
Keywords – power quality disturbances, total harmonic distortion, power system fault, single tuned harmonic
filter, double tuned harmonic filter.
I. INTRODUCTION
The continuous monitoring of power quality (PQ) has become imperative as occurrences of PQ
disturbances are relatively sporadic and mostly unscheduled. Further when something goes wrong and the
source of the problem needs to be investigated, whether upstream or downstream of the issue, PQ data is an
absolute necessity [1]. Power quality is a term used to describe the most important aspect of the electricity
supply. Power quality can be defined as any problem manifested in voltage, current, or frequency deviation that
results in failure or mal-operation of electric equipment [2]. Poor quality of electric power is normally caused by
power line disturbances, such as impulses, notches, glitches, momentary interruption wave faults, voltage sag,
swell, harmonic distortion and flicker resulting in misoperation or failure of end use equipments [3]. Poor
quality may cause many problems that affect the load such as malfunction, instability, short lifetime and so on.
According to the survey by IEEE transactions on Industrial Applications, power quality disturbances lead to
losses of $4 billion to $10 billion in the USA alone [4]. In recent years, grid users have detected an increasing
number of drawbacks caused by electric power quality (PQ) variations and PQ problems have sharpened
because of the increased number of loads sensitive to PQ and have become more difficult to solve as the loads
themselves have become important causes of degradation of quality [5]. Transmission line relaying involves the
three major tasks: detection, classification, and location of the fault. It must be done as fast and accurate as
possible to de-energize the faulted line and protecting the system from the harmful effects of the fault. With the
wide application of high power electronics switchgears, problems of power quality are becoming more serious
day by day [6]-[7]. The power quality disturbances depend on amplitude or frequency or on both frequency and
amplitude. Based on duration of existence of PQ disturbances, events can be divided in short, medium or long
type. The classification and identification of each disturbance are usually carried out from standards and
recommendations depending on where the utilities operate (e.g. IEEE in the U.S.). Inigo Monedero et al. [8]
defined PQ disturbances, based on the UNE standard in Spain which defines the ideal signal as a single-phase or
three-phase sinusoidal voltage signal of 230 VRMS and 50Hz. D. Saxena et al. [9] classified various PQ events in
to five groups viz. short duration variation, long duration variation, transients, voltage imbalance and waveform
distortion. S.Edwin Jose et al. [10] classified PQ disturbances on basis of values of tails of histogram obtained
from simulation results. Haibo He et al.[11] proposed a novel approach for the power quality disturbances
classification based on the wavelet transform and self organizing learning array system. Devendra Mittal et al.
[12] presented a method for improvement of electrical power quality under faulty conditions in electrical power
system using three phase double tuned harmonic filter.
Most of papers published on power quality are concerned with the customer related issues and
classification of power quality disturbances. This paper aims improvement of power quality in faulty conditions
of power system using three phase single tuned and double tuned harmonic filters. The four bus system with two
load and two generator buses is simulated in MATLAB/Simulink environment. The power quality improvement
Power Quality Improvement in Faulty Conditions using Tuned Harmonic Filters
www.iosrjournals.org 2 | Page
using three phase harmonic filters connected at generator bus during LG fault, LL fault, LLG fault, LLL fault
and LLLG fault on the load bus has been studied. The analysis is carried out on the basis of Total harmonic
Distortion (THD). The results obtained after simulation demonstrate the performance of three phase harmonic
filters in improvement of power quality during faulty conditions of power system.
II. THREE-PHASE TUNED HARMONIC FILTERS
The passive harmonics filters are composed of passive elements: resistor (R), inductor (L) and
capacitor (C). The common types of passive filters include single-tuned and double tuned filters, second-order,
third-order and C-type damped filters. Three-phase harmonic filters are shunt elements that are used in power
systems for decreasing voltage distortion and for power factor correction. The three-phase harmonic filter is
built of RLC elements. The resistance, inductance and capacitance values are determined from the filter type,
reactive power at nominal voltage, tuning frequencies and quality factor. Passive filter has been widely used in
filtering harmonics in power system because it has a simple structure, low cost and high reliability. The single
tuned filter is the series combination of inductor (L) and capacitor (C) as shown in Fig. 1. Usually, there are
multiple frequency harmonics in a power system, so a group of parallel single tuned filters are needed to filter
harmonics. This filtering method covers a large area and has a high cost [13].
Fig. 1 Single tuned harmonic filter
Double tuned filter performs the same function as two single tuned filters connected in parallel
although it has certain advantages of lower cost, low losses and lower impedance magnitude at the frequency of
parallel resonance that arises between the two tuning frequencies [14]. Chih-Ju et al.[15] presented that double
tuned filter consists of a series LC circuit and a parallel RLC circuit as shown in Fig. 2. If f1 and f2 are the two
tuning frequencies, both the series circuit and parallel circuit are tuned to approximately the mean geometric
frequency given by the relation:
𝑓𝑚 = 𝑓1 × 𝑓2 (1)
The quality factor Q of the double tuned filter is defined as the quality factor of the parallel L, R elements at the
mean frequency fm:
𝑄 =
𝑅
𝐿 × 2𝜋𝑓𝑚
(2)
Fig. 2 Double tuned harmonic filter
III. TOTAL HARMONIC DISTORTION
Non-sinusoidal input, or supply, current is made up of fundamental current plus current components of
higher frequencies. The total harmonic distortion (THD) is equal to the rms value of all the harmonics divided
Power Quality Improvement in Faulty Conditions using Tuned Harmonic Filters
www.iosrjournals.org 3 | Page
by the rms value of fundamental component of the input current. Greater the value of THD greater is the
harmonic content and hence greater is the distortion of input supply current [16]. The THD is given by the
relation given below:-
𝑇𝐻𝐷 =
𝐼ℎ
𝐼𝑠1
=
𝐼𝑠
2 − 𝐼𝑠1
2
𝐼𝑠1
2 =
𝐼𝑠𝑛
∞
𝑛=2
𝐼𝑠1
(3)
Where Ih = rms value of all the harmonic components combined
Isn= rms value of nth harmonic content.
Is = rms value of supply phase current including fundamental and harmonics.
IV. PROPOSED POWER SYSTEM MODEL
For power quality improvement using three-phase single tuned and double tuned harmonic filters
during faulty conditions in the power system, the one line diagram of experimental set up consisting of four
buses shown in Fig. 3 is used [17]. The buses 1 & 2 are taken as generator buses and buses 3 & 4 are taken as
load buses. The line length of all the four π sections are taken as 100 Km. For simplicity the voltage levels at all
points of the power system are taken as 33 KV. The three-phase tuned harmonic filters are installed near the
generator bus 1 to protect the generator from power system disturbances during faulty conditions. The fault is
located at bus no. 4 in all faulty conditions considered in the study. All the measurement of the voltage signals
are taken on bus no. 1 at generating station.
Fig. 3 Proposed model of power system for improvement of PQ disturbances in faulty conditions using tuned harmonic filters
V. POWER SYSTEM SIMULATION AND DISCUSSION
Power system faults are abnormal events which are not part of normal operation and unwanted by the
network operator. After fault occurs in the power system, a non-linear signal of transient travelling wave is
generated and runs along faulted transmission line to both ends of the line. Those travelling waves contain
information about fault nature. The fault initial travelling wave has a wide frequency spectrum from DC
component to high frequencies. When such fault travelling wave arrives at the substation bus bar, it will change
incisively, i.e. travelling wave head will present the sudden change in the time-frequency diagram. In that way,
travelling wave arrival to the measuring point (usually the busbar voltage transformers) exactly a moment of
sudden change recorded on measuring substation [18]. For experimental improvement of power quality
disturbances to reduce the impact of PQ disturbances on the generators three-phase single tuned and double
tuned harmonic filter are used. The proposed model is simulated in MATLAB/Simulink environment for
analysis of improvement in the power quality disturbances. The analysis of power quality improvement in the
proposed model is based on the total harmonic distortion (THD). The simulation is carried out in three
conditions viz. faulty system before filtering, faulty system after filtering using single tuned harmonic filter and
faulty system after filtering using double tuned filter.
Filter
Bus 1 Bus 2
Bus 3 Bus 4
Fault Location Point
A
LoadLoad
G G
Power Quality Improvement in Faulty Conditions using Tuned Harmonic Filters
www.iosrjournals.org 4 | Page
V.1 LG Fault in Power System
The power system model shown in Fig. 3 is simulated in MATLAB/Simulink environment with line to
ground fault at bus no. 4 on phase-A. The THD analysis of voltage signal of phase-A during line to ground fault
before filtering is shown in Fig. 4. The higher order frequency of integral multiple of fundamental frequency up
to 500Hz is observed. The observed THD is 3.60%.
Fig. 4 THD in Phase-A during LG fault before filtering
The THD analysis of voltage signal of phase-A during line to ground fault after using single tuned filter
is shown in Fig. 5. The higher order frequency of integral multiple of fundamental frequency up to 900Hz is
observed. The observed THD is 2.65%.
Fig. 5 THD in Phase-A during LG fault after filtering using single tuned filter
The THD analysis of voltage signal of phase-A during line to ground fault after using double tuned
filter is shown in Fig. 6. The higher order frequency of integral multiple of fundamental frequency up to 850Hz
is observed. The observed THD is 1.26%.
Fig. 6 THD in Phase-A during LG fault after filtering using double tuned filter
V.2 LL Fault on Power System
The power system model shown in Fig. 3 is simulated in MATLAB/Simulink environment with double
line fault between phases A and B at bus no. 4. The THD analysis of voltage signal of phase-A during double
line fault before filtering is shown in Fig. 7. The higher order frequency of integral multiple of fundamental
frequency up to 750Hz is observed. The observed THD is 3.52%.
Power Quality Improvement in Faulty Conditions using Tuned Harmonic Filters
www.iosrjournals.org 5 | Page
Fig. 7 THD in Phase-A during LL fault on phases A and B before filtering
The THD analysis of voltage signal of phase-A during double line fault after using single tuned filter is
shown in Fig. 8. The higher order frequency of integral multiple of fundamental frequency up to 800Hz is
observed. The observed THD is 1.35%.
Fig. 8 THD in Phase-A during LL fault on phases A and B after filtering using single tuned filter
The THD analysis of voltage signal of phase-A during double line fault after using double tuned filter
is shown in Fig. 9. The higher order frequency of integral multiple of fundamental frequency up to 950Hz is
observed. The observed THD is 1.14%.
Fig. 9 THD in Phase-A during LL fault on phases A and B after filtering using double tuned filter
V.3 LLG Fault on Power System
The power system model shown in Fig. 3 is simulated in MATLAB/Simulink environment with double
line to ground fault between phases A and B at bus no. 4. The THD analysis of voltage signal of phase-A during
double line to ground fault before filtering is shown in Fig. 10. The higher order frequency of integral multiple
of fundamental frequency up to 200 Hz is observed. The observed THD is 7.55%.
Fig. 10 THD in Phase-A during LLG fault on phases A and B before filtering
The THD analysis of voltage signal of phase-A during double line to ground fault after using single
tuned filter is shown in Fig. 11. The higher order frequency of integral multiple of fundamental frequency up to
650 Hz is observed. The observed THD is 2.01%.
Power Quality Improvement in Faulty Conditions using Tuned Harmonic Filters
www.iosrjournals.org 6 | Page
Fig. 11 THD in Phase-A during LLG fault on phases A and B after filtering using single tuned filter
The THD analysis of voltage signal of phase-A during double line to ground fault after using double
tuned filter is shown in Fig. 12. The higher order frequency of integral multiple of fundamental frequency up to
700 Hz is observed. The observed THD is 1.03%.
Fig. 12 THD in Phase-A during LL fault on phases A and B after filtering using double tuned filter
V.4 LLL Fault on Power System
The power system model shown in Fig. 3 is simulated in MATLAB/Simulink environment with three
phase fault at bus no. 4. The THD analysis of voltage signal of phase-A during three phase fault before filtering
is shown in Fig. 13. The higher order frequency of integral multiple of fundamental frequency up to 900 Hz is
observed. The observed THD is 6.40%.
Fig. 13 THD in Phase-A during LLL fault before filtering
The THD analysis of voltage signal of phase-A during three phase fault after using single tuned filter is
shown in Fig. 14. The higher order frequency of integral multiple of fundamental frequency up to 850 Hz is
observed. The observed THD is 1.46%.
Fig. 14 THD in Phase-A during LLL fault after filtering using single tuned filter
Power Quality Improvement in Faulty Conditions using Tuned Harmonic Filters
www.iosrjournals.org 7 | Page
The THD analysis of voltage signal of phase-A during three phase fault after using single tuned filter is
shown in Fig. 15. The higher order frequency of integral multiple of fundamental frequency up to 900 Hz is
observed. The observed THD is 1.55%.
Fig. 15 THD in Phase-A during LLL fault after filtering using double tuned filter
V.5 LLLG Fault on Power System
The power system model shown in Fig. 3 is simulated in MATLAB/Simulink environment with three
phase fault involving ground at bus no. 4. The THD analysis of voltage signal of phase-A during three phase
fault involving ground before filtering is shown in Fig. 16. The higher order frequency of integral multiple of
fundamental frequency up to 200 Hz is observed. The observed THD is 9.55%.
Fig. 16 THD in Phase-A during LLLG fault before filtering
The THD analysis of voltage signal of phase-A during three phase fault involving ground after using
single tuned filter is shown in Fig. 17. The higher order frequency of integral multiple of fundamental frequency
up to 350 Hz is observed. The observed THD is 6.70%.
Fig. 17 THD in Phase-A during LLLG fault after filtering using single tuned filter
The THD analysis of voltage signal of phase-A during three phase fault involving ground after using
single tuned filter is shown in Fig. 18. The higher order frequency of integral multiple of fundamental frequency
up to 950 Hz is observed. The observed THD is 3.19%.
Power Quality Improvement in Faulty Conditions using Tuned Harmonic Filters
www.iosrjournals.org 8 | Page
Fig. 18 THD in Phase-A during LLLG fault after filtering using double tuned filter
The total harmonic distortion (THD) of voltage signal at generator bus no. 1 of proposed power system
model during different faulty conditions when fault is created at bus no. 4 are shown in Table. 1. The three
conditions before filtering, after using single tuned filter and after using double tuned filter are discussed.
TABLE 1
TOTAL HARMONIC DISTORTION OF VOLTAGE SIGNAL IN FAULTY CONDITION
S.No. Type of Fault THD Before
Filtering
THD After
Using Single
Tuned Filter
THD After Using
Double Tuned
Filter
1 Line to Ground(LG) 3.60% 2.65% 1.26%
2 Double Line (LL) 3.52% 1.35% 1.14%
3 Double Line to Ground (LLG) 7.55% 2.01% 1.03%
4 Three Phase Fault (LLL) 6.40% 1.46% 1.55%
5 Three Phase Fault involving
ground (LLLG)
9.55% 6.70% 3.19%
VI. CONCLUSION
An efficient but simple technique has been developed for improvement of power quality disturbances
during faulty conditions using three phase tuned harmonic filters in the electrical power system. The proposed
model of four bus system is simulated in the MATLAB/Simulink environment. The analysis of improvement of
power quality during faulty conditions of power system using tuned harmonic filters is carried out using the total
harmonic distortion. The results show that three-phase harmonic filters are effective in improvement of power
quality in faulty conditions. The double tuned harmonic filter is comparatively more effective as compared to
the single tuned harmonic filter. The THD reduces in all faulty conditions while using single tuned filter which
further reduces on using double tuned filter. The tuned harmonic filters are effective in protecting the costly
equipment of power system transients during faulty conditions.
REFERENCES
[1] Manoj Gupta, Rajesh Kumar, and Ram Awtar Gupta, “Neural Network Based Indexing and Recognition of Power Quality
Disturbances,” TELKOMNIKA, Vol. 9, No.2, August 2011, pp. 227-236.
[2] R.Dugan, M. McGranaghan, and H. Wane Beaty, Electrical Power Systems Quality, McGraw-Hill, Ney York, 1996.
[3] Subhamita Roy, and Sudipta Nath, “Classification of power quality disturbances using features of signals,” International Journal of
Scientific and Research Publications, Vol. 2, Issue 11, November 2012, pp.01-09.
[4] He H., Shen X, and Starzyk J.A., “Power quality disturbances analysis based on EDMRA method,” Electrical Power and Energy
System, Vol. 31, pp. 258-268.
[5] P.Daponte, M.di Penta, and G. Mercurio, Transientmeter: A distuributed measurement system for power quality monitoring,”
Proceeding 9th
International Conference Harmonics and Quality of Power, 2000, Vo. 3, pp.1017-1022.
[6] M.Sushama, G.Tulasi Ram Das, and A.Jaya Laxmi, “Mitigation of voltage sags with dynamic voltage restorer using wavelets,”
Presented at the International Conference RACE 2007, March 22-24, 2007.
[7] Anoop Mathew, and Benisker Raja Singh D., “Image compression using lifting based DWT,” International Journal of Computers
Information Technology and Engineering, Vol. 3, January 2009, pp. 27-31.
[8] Inigo Monedero, Carlos Leon, Jorge Ropero, Antonio Garcia, Jose Manuel and Juan C. Montano, “Classification of Electrical
Disturbances in Real Time Using Neural Networks,” IEEE Transaction on Power Delivery, 2007, pp.1-9.
[9] D. Saxena, K.S. Verma and S.N. Singh, “Power quality event classification: an overview and key issues,” International Journal of
Engineering, Science and Technology, Vol. 2, No.3, 2010, pp. 186-199.
[10] S.Edwin Jose, and S.Titus, “Detection and classification of power quality using adaptive decomposition structure and neural
network,” European Journal of Scientific Research, Vol.89, No.3, October 2012, pp. 477-489.
[11] Haibo He, and Janusz A. Starzyk, “A self-organizing learning array system for power quality classification based on wavelet
transform,” IEEE Transaction on Power Delivery, Vol. 21, No. 1, January 2006, pp.286-295.
[12] Devendra Mittal, Om Prakash Mahela, and Rohit Jain, “Electrical power quality improvement in faulty conditions using three phase
double tuned harmonic filter,” International Journal of Innovative Research and development, Vol. 2, Issue 6, June 2013, pp.493-
509.
Power Quality Improvement in Faulty Conditions using Tuned Harmonic Filters
www.iosrjournals.org 9 | Page
[13] He Yi-hong, and SU Heng, “A new method of designing double tuned filter,” Proceedings of the 2nd
International Conference on
Computer Science and Electronics Engineering, ICCSEE 2013, Paris, France.
[14] Wang Zhaoan, and Yang Jun, Harmonic suppression and reactive power compensation, (Beijing: China Machine Press, 2010).
[15] Chih-Ju, and Chih-Wen Liu, “Optimal planning of large passive-harmonic filters set at high voltage level,” IEEE transactions on
Power Systems, Vol. 15, No. 1, February 2000, pp. 433-441.
[16] Dr. P.S. Bimbhra, Power Electronics, Khanna Publications, New Delhi, 2011.
[17] Devendra Mittal, Om Prakash Mahela, and Rohit Jain, “Detection and analysis of power quality disturbances under faulty
conditions in electrical power system,” IAEME-International Journal of Electrical Engineering & Technology, Vol. 4, Issue 2,
March-April 2013, pp. 25-36.
[18] Alen Bernadic, and Zbigniew Leonowicz, “Power line fault location using the complex space-phasor and Hilbert-huang transform,”
Przeglad Elektrotechniczny (Electrical Review), R.87 NR 5/2011, pp. 204-207.
BIOGRAPHIES
Sumit Kanwar studied at Rajasthan College of Engineering for Women and received the
B.Tech. in Electrical Engineering from Rajasthan Technical University, Kota, India, in
2010. She received Master’s degree in Electrical Engineering from the Jagannath
University, Jaipur, India in 2013 with specialization on Power System.
From 2010 to 2011, she was Assistant Professor with the Maharani Girls
Engineering College, Jaipur, India. Since 2011 she has been senior lecturer with the
Electrical Engineering department of the Asians Institute of Technology, Jaipur, India. Her
special fields of interest are power electronics in power system, applications of AI
techniques in power system and power quality.
Om Prakash Mahela was born in Sabalpura (Kuchaman City) in the Rajasthan state of
India, on April 11, 1977. He studied at Govt. College of Engineering and Technology
(CTAE), Udaipur, and received the electrical engineering degree from Maharana Pratap
University of Agriculture and Technology (MPUAT), Udaipur, India in 2002. He received
M.Tech.(Electrical Engineering) with power system specialization from Jagannath
University, Jaipur, India in 2013. He is currently pursuing PhD from Indian Institute of
Technology Jodhpur.
From 2002 to 2004, he was Assistant Professor with the RIET, Jaipur. Since 2004,
he has been Junior Engineer-I with the Rajasthan Rajya Vidhyut Prasaran Nigam Ltd., Jodhpur, India. His
special fields of interest are Transmission and Distribution (T&D) grid operations, Power Electronics in Power
System, Power Quality, Load Forecasting and Integration of Renewable Energy with Electric Transmission and
Distribution Grid, Applications of AI Techniques in power system. He is an author of 26 International Journals
and Conference papers. He is a Graduate Student Member of IEEE. He is member of IEEE Communications
Society. He is Member of IEEE Power & Energy Society. He is Fellow Member of IAEME. He is Reviewer of
TJPRC International Journal of Electrical and Electronics Engineering Research. Mr. Mahela is recipient of
University Rank certificate from MPUAT, Udaipur, India, in 2002. He is recipient of university first Rank in
M.Tech. from Jagannath University, Jaipur, India in 2013.
Devendra Mittal was born in Bhusawar in the Rajasthan state of India, on March 17, 1980.
He studied at IET, Alwar, and received the electrical engineering degree from Rajasthan
University, Jaipur, in 2003. He received M.Tech.(Power system) from MNIT, Jaipur, in
2007. He is currently pursuing Phd from Jagannath University, Jaipur.
From 2003 to 2008, he was Lecturer with Shankara Institute of Technology, Jaipur.
From 2008 to 2009, he was Lecturer with UDML Engineering College. Since 2009, he has
been Assistant Professor with Jagannath University, Jaipur, India. His special fields of
interest are Power Electronics and Power System.

More Related Content

What's hot

PSIM Simulation Of Variable Duty Cycle Control DCM Boost PFC Converter to Ach...
PSIM Simulation Of Variable Duty Cycle Control DCM Boost PFC Converter to Ach...PSIM Simulation Of Variable Duty Cycle Control DCM Boost PFC Converter to Ach...
PSIM Simulation Of Variable Duty Cycle Control DCM Boost PFC Converter to Ach...IRJET Journal
 
Hardware Implementation of Single Phase Power Factor Correction System using ...
Hardware Implementation of Single Phase Power Factor Correction System using ...Hardware Implementation of Single Phase Power Factor Correction System using ...
Hardware Implementation of Single Phase Power Factor Correction System using ...IAES-IJPEDS
 
IRJET- Harmonic Elimination in Three Phase System by Means of Hybrid Active F...
IRJET- Harmonic Elimination in Three Phase System by Means of Hybrid Active F...IRJET- Harmonic Elimination in Three Phase System by Means of Hybrid Active F...
IRJET- Harmonic Elimination in Three Phase System by Means of Hybrid Active F...IRJET Journal
 
Harmonic Compensation for Non Linear Load Using PWM Based Active Filter
Harmonic Compensation for Non Linear Load Using PWM Based Active FilterHarmonic Compensation for Non Linear Load Using PWM Based Active Filter
Harmonic Compensation for Non Linear Load Using PWM Based Active Filteridescitation
 
Power-Quality-Improvement-Using-PI-and-Fuzzy-Logic-Controllers-Based-Shunt-Ac...
Power-Quality-Improvement-Using-PI-and-Fuzzy-Logic-Controllers-Based-Shunt-Ac...Power-Quality-Improvement-Using-PI-and-Fuzzy-Logic-Controllers-Based-Shunt-Ac...
Power-Quality-Improvement-Using-PI-and-Fuzzy-Logic-Controllers-Based-Shunt-Ac...Atul Sharma
 
IJERD (www.ijerd.com) International Journal of Engineering Research and Devel...
IJERD (www.ijerd.com) International Journal of Engineering Research and Devel...IJERD (www.ijerd.com) International Journal of Engineering Research and Devel...
IJERD (www.ijerd.com) International Journal of Engineering Research and Devel...IJERD Editor
 
IRJET- Inverter Power Control Based on DC-Link Voltage Regulation for IPMSM D...
IRJET- Inverter Power Control Based on DC-Link Voltage Regulation for IPMSM D...IRJET- Inverter Power Control Based on DC-Link Voltage Regulation for IPMSM D...
IRJET- Inverter Power Control Based on DC-Link Voltage Regulation for IPMSM D...IRJET Journal
 
IRJET- Low Cost Harmonic Measurement using Arduino UNO
IRJET-  	  Low Cost Harmonic Measurement using Arduino UNOIRJET-  	  Low Cost Harmonic Measurement using Arduino UNO
IRJET- Low Cost Harmonic Measurement using Arduino UNOIRJET Journal
 
Design of shunt hybrid active power filter for compensating harmonic currents...
Design of shunt hybrid active power filter for compensating harmonic currents...Design of shunt hybrid active power filter for compensating harmonic currents...
Design of shunt hybrid active power filter for compensating harmonic currents...TELKOMNIKA JOURNAL
 
Power Quality Improvement of Grid Interconnection of renewable Energy Based D...
Power Quality Improvement of Grid Interconnection of renewable Energy Based D...Power Quality Improvement of Grid Interconnection of renewable Energy Based D...
Power Quality Improvement of Grid Interconnection of renewable Energy Based D...IJERA Editor
 
An Analysis of Harmonic and Interharmonic Contribution of Electric Arc Furnac...
An Analysis of Harmonic and Interharmonic Contribution of Electric Arc Furnac...An Analysis of Harmonic and Interharmonic Contribution of Electric Arc Furnac...
An Analysis of Harmonic and Interharmonic Contribution of Electric Arc Furnac...IJECEIAES
 
International Journal of Engineering Research and Development (IJERD)
International Journal of Engineering Research and Development (IJERD)International Journal of Engineering Research and Development (IJERD)
International Journal of Engineering Research and Development (IJERD)IJERD Editor
 
Harmonic correction in power supplies feeding non linear loads
Harmonic correction in power supplies feeding non linear loadsHarmonic correction in power supplies feeding non linear loads
Harmonic correction in power supplies feeding non linear loadssouravsahoo28
 
Comparative Study of Three Phase Grid Connected Photovoltaic Inverter Using P...
Comparative Study of Three Phase Grid Connected Photovoltaic Inverter Using P...Comparative Study of Three Phase Grid Connected Photovoltaic Inverter Using P...
Comparative Study of Three Phase Grid Connected Photovoltaic Inverter Using P...IJPEDS-IAES
 

What's hot (20)

J0361059064
J0361059064J0361059064
J0361059064
 
El34831851
El34831851El34831851
El34831851
 
A review on different control techniques using DSTATCOM for distribution syst...
A review on different control techniques using DSTATCOM for distribution syst...A review on different control techniques using DSTATCOM for distribution syst...
A review on different control techniques using DSTATCOM for distribution syst...
 
PSIM Simulation Of Variable Duty Cycle Control DCM Boost PFC Converter to Ach...
PSIM Simulation Of Variable Duty Cycle Control DCM Boost PFC Converter to Ach...PSIM Simulation Of Variable Duty Cycle Control DCM Boost PFC Converter to Ach...
PSIM Simulation Of Variable Duty Cycle Control DCM Boost PFC Converter to Ach...
 
Hardware Implementation of Single Phase Power Factor Correction System using ...
Hardware Implementation of Single Phase Power Factor Correction System using ...Hardware Implementation of Single Phase Power Factor Correction System using ...
Hardware Implementation of Single Phase Power Factor Correction System using ...
 
A011140104
A011140104A011140104
A011140104
 
Experimental Comparative Study of Feedback Linearized Controller and Proporti...
Experimental Comparative Study of Feedback Linearized Controller and Proporti...Experimental Comparative Study of Feedback Linearized Controller and Proporti...
Experimental Comparative Study of Feedback Linearized Controller and Proporti...
 
IRJET- Harmonic Elimination in Three Phase System by Means of Hybrid Active F...
IRJET- Harmonic Elimination in Three Phase System by Means of Hybrid Active F...IRJET- Harmonic Elimination in Three Phase System by Means of Hybrid Active F...
IRJET- Harmonic Elimination in Three Phase System by Means of Hybrid Active F...
 
Harmonic Compensation for Non Linear Load Using PWM Based Active Filter
Harmonic Compensation for Non Linear Load Using PWM Based Active FilterHarmonic Compensation for Non Linear Load Using PWM Based Active Filter
Harmonic Compensation for Non Linear Load Using PWM Based Active Filter
 
Power-Quality-Improvement-Using-PI-and-Fuzzy-Logic-Controllers-Based-Shunt-Ac...
Power-Quality-Improvement-Using-PI-and-Fuzzy-Logic-Controllers-Based-Shunt-Ac...Power-Quality-Improvement-Using-PI-and-Fuzzy-Logic-Controllers-Based-Shunt-Ac...
Power-Quality-Improvement-Using-PI-and-Fuzzy-Logic-Controllers-Based-Shunt-Ac...
 
Bb4102386391
Bb4102386391Bb4102386391
Bb4102386391
 
IJERD (www.ijerd.com) International Journal of Engineering Research and Devel...
IJERD (www.ijerd.com) International Journal of Engineering Research and Devel...IJERD (www.ijerd.com) International Journal of Engineering Research and Devel...
IJERD (www.ijerd.com) International Journal of Engineering Research and Devel...
 
IRJET- Inverter Power Control Based on DC-Link Voltage Regulation for IPMSM D...
IRJET- Inverter Power Control Based on DC-Link Voltage Regulation for IPMSM D...IRJET- Inverter Power Control Based on DC-Link Voltage Regulation for IPMSM D...
IRJET- Inverter Power Control Based on DC-Link Voltage Regulation for IPMSM D...
 
IRJET- Low Cost Harmonic Measurement using Arduino UNO
IRJET-  	  Low Cost Harmonic Measurement using Arduino UNOIRJET-  	  Low Cost Harmonic Measurement using Arduino UNO
IRJET- Low Cost Harmonic Measurement using Arduino UNO
 
Design of shunt hybrid active power filter for compensating harmonic currents...
Design of shunt hybrid active power filter for compensating harmonic currents...Design of shunt hybrid active power filter for compensating harmonic currents...
Design of shunt hybrid active power filter for compensating harmonic currents...
 
Power Quality Improvement of Grid Interconnection of renewable Energy Based D...
Power Quality Improvement of Grid Interconnection of renewable Energy Based D...Power Quality Improvement of Grid Interconnection of renewable Energy Based D...
Power Quality Improvement of Grid Interconnection of renewable Energy Based D...
 
An Analysis of Harmonic and Interharmonic Contribution of Electric Arc Furnac...
An Analysis of Harmonic and Interharmonic Contribution of Electric Arc Furnac...An Analysis of Harmonic and Interharmonic Contribution of Electric Arc Furnac...
An Analysis of Harmonic and Interharmonic Contribution of Electric Arc Furnac...
 
International Journal of Engineering Research and Development (IJERD)
International Journal of Engineering Research and Development (IJERD)International Journal of Engineering Research and Development (IJERD)
International Journal of Engineering Research and Development (IJERD)
 
Harmonic correction in power supplies feeding non linear loads
Harmonic correction in power supplies feeding non linear loadsHarmonic correction in power supplies feeding non linear loads
Harmonic correction in power supplies feeding non linear loads
 
Comparative Study of Three Phase Grid Connected Photovoltaic Inverter Using P...
Comparative Study of Three Phase Grid Connected Photovoltaic Inverter Using P...Comparative Study of Three Phase Grid Connected Photovoltaic Inverter Using P...
Comparative Study of Three Phase Grid Connected Photovoltaic Inverter Using P...
 

Viewers also liked

Lc ftu hcmc best finance award
Lc ftu hcmc  best finance awardLc ftu hcmc  best finance award
Lc ftu hcmc best finance awardManh Cuong Chau
 
Security in MANET based on PKI using fuzzy function
Security in MANET based on PKI using fuzzy functionSecurity in MANET based on PKI using fuzzy function
Security in MANET based on PKI using fuzzy functionIOSR Journals
 
Performance analysis of Data Mining algorithms in Weka
Performance analysis of Data Mining algorithms in WekaPerformance analysis of Data Mining algorithms in Weka
Performance analysis of Data Mining algorithms in WekaIOSR Journals
 
A middleware approach for high level overlay network
A middleware approach for high level overlay networkA middleware approach for high level overlay network
A middleware approach for high level overlay networkIOSR Journals
 
Mobile Networking and Ad hoc routing protocols validation
Mobile Networking and Ad hoc routing protocols validationMobile Networking and Ad hoc routing protocols validation
Mobile Networking and Ad hoc routing protocols validationIOSR Journals
 
Fuzzy Logic Controller Based ZVT-ZCT PWM Boost Converter Using Renewable Ener...
Fuzzy Logic Controller Based ZVT-ZCT PWM Boost Converter Using Renewable Ener...Fuzzy Logic Controller Based ZVT-ZCT PWM Boost Converter Using Renewable Ener...
Fuzzy Logic Controller Based ZVT-ZCT PWM Boost Converter Using Renewable Ener...IOSR Journals
 
Итоговое сочинение - 2015
Итоговое сочинение - 2015Итоговое сочинение - 2015
Итоговое сочинение - 2015Natalya Dyrda
 
Evaluation of Biocontrol agents against Lasiodiplodia theobromae causing Infl...
Evaluation of Biocontrol agents against Lasiodiplodia theobromae causing Infl...Evaluation of Biocontrol agents against Lasiodiplodia theobromae causing Infl...
Evaluation of Biocontrol agents against Lasiodiplodia theobromae causing Infl...IOSR Journals
 
EPiServer 7.5 Commerce
EPiServer 7.5 CommerceEPiServer 7.5 Commerce
EPiServer 7.5 CommerceBeth McEnery
 
Enhanced Clustering Algorithm for Processing Online Data
Enhanced Clustering Algorithm for Processing Online DataEnhanced Clustering Algorithm for Processing Online Data
Enhanced Clustering Algorithm for Processing Online DataIOSR Journals
 
Analysis of Technical, Economic and Allocative Efficiencies of CassavaProduct...
Analysis of Technical, Economic and Allocative Efficiencies of CassavaProduct...Analysis of Technical, Economic and Allocative Efficiencies of CassavaProduct...
Analysis of Technical, Economic and Allocative Efficiencies of CassavaProduct...IOSR Journals
 
Belgium's Social Media and Netlog
Belgium's Social Media and NetlogBelgium's Social Media and Netlog
Belgium's Social Media and NetlogKatherine Witsman
 

Viewers also liked (20)

Lc ftu hcmc best finance award
Lc ftu hcmc  best finance awardLc ftu hcmc  best finance award
Lc ftu hcmc best finance award
 
Security in MANET based on PKI using fuzzy function
Security in MANET based on PKI using fuzzy functionSecurity in MANET based on PKI using fuzzy function
Security in MANET based on PKI using fuzzy function
 
F0411925
F0411925F0411925
F0411925
 
A0350104
A0350104A0350104
A0350104
 
B0451217
B0451217B0451217
B0451217
 
Performance analysis of Data Mining algorithms in Weka
Performance analysis of Data Mining algorithms in WekaPerformance analysis of Data Mining algorithms in Weka
Performance analysis of Data Mining algorithms in Weka
 
A middleware approach for high level overlay network
A middleware approach for high level overlay networkA middleware approach for high level overlay network
A middleware approach for high level overlay network
 
Mobile Networking and Ad hoc routing protocols validation
Mobile Networking and Ad hoc routing protocols validationMobile Networking and Ad hoc routing protocols validation
Mobile Networking and Ad hoc routing protocols validation
 
Media genre
Media genreMedia genre
Media genre
 
Fuzzy Logic Controller Based ZVT-ZCT PWM Boost Converter Using Renewable Ener...
Fuzzy Logic Controller Based ZVT-ZCT PWM Boost Converter Using Renewable Ener...Fuzzy Logic Controller Based ZVT-ZCT PWM Boost Converter Using Renewable Ener...
Fuzzy Logic Controller Based ZVT-ZCT PWM Boost Converter Using Renewable Ener...
 
Итоговое сочинение - 2015
Итоговое сочинение - 2015Итоговое сочинение - 2015
Итоговое сочинение - 2015
 
Evaluation of Biocontrol agents against Lasiodiplodia theobromae causing Infl...
Evaluation of Biocontrol agents against Lasiodiplodia theobromae causing Infl...Evaluation of Biocontrol agents against Lasiodiplodia theobromae causing Infl...
Evaluation of Biocontrol agents against Lasiodiplodia theobromae causing Infl...
 
N0567379
N0567379N0567379
N0567379
 
EPiServer 7.5 Commerce
EPiServer 7.5 CommerceEPiServer 7.5 Commerce
EPiServer 7.5 Commerce
 
Enhanced Clustering Algorithm for Processing Online Data
Enhanced Clustering Algorithm for Processing Online DataEnhanced Clustering Algorithm for Processing Online Data
Enhanced Clustering Algorithm for Processing Online Data
 
H0545156
H0545156H0545156
H0545156
 
F0513644
F0513644F0513644
F0513644
 
E0952731
E0952731E0952731
E0952731
 
Analysis of Technical, Economic and Allocative Efficiencies of CassavaProduct...
Analysis of Technical, Economic and Allocative Efficiencies of CassavaProduct...Analysis of Technical, Economic and Allocative Efficiencies of CassavaProduct...
Analysis of Technical, Economic and Allocative Efficiencies of CassavaProduct...
 
Belgium's Social Media and Netlog
Belgium's Social Media and NetlogBelgium's Social Media and Netlog
Belgium's Social Media and Netlog
 

Similar to Power Quality Improvement in Faulty Conditions using Tuned Harmonic Filters

Paper id 29201412
Paper id 29201412Paper id 29201412
Paper id 29201412IJRAT
 
Comparative of Conventional and Intelligence Controller based Hybrid Generati...
Comparative of Conventional and Intelligence Controller based Hybrid Generati...Comparative of Conventional and Intelligence Controller based Hybrid Generati...
Comparative of Conventional and Intelligence Controller based Hybrid Generati...IJERD Editor
 
Power quality improvement in a weak bus system using facts controller
Power quality improvement in a weak bus system using facts controllerPower quality improvement in a weak bus system using facts controller
Power quality improvement in a weak bus system using facts controllereSAT Journals
 
Power quality improvement in a weak bus system using
Power quality improvement in a weak bus system usingPower quality improvement in a weak bus system using
Power quality improvement in a weak bus system usingeSAT Publishing House
 
Harmonic analysis and Power factor improvement with UPQC under two Novel cont...
Harmonic analysis and Power factor improvement with UPQC under two Novel cont...Harmonic analysis and Power factor improvement with UPQC under two Novel cont...
Harmonic analysis and Power factor improvement with UPQC under two Novel cont...IJERA Editor
 
IRJET- A Review on Distribution System with Harmonic Reduction
IRJET- A Review on Distribution System with Harmonic ReductionIRJET- A Review on Distribution System with Harmonic Reduction
IRJET- A Review on Distribution System with Harmonic ReductionIRJET Journal
 
Dynamic Power Factor Correction in a Non Linear Environment
Dynamic Power Factor Correction in a Non Linear EnvironmentDynamic Power Factor Correction in a Non Linear Environment
Dynamic Power Factor Correction in a Non Linear Environmentiosrjce
 
Closed Loop Non Linear Control of Shunt Hybrid Power Filter for Harmonics Mit...
Closed Loop Non Linear Control of Shunt Hybrid Power Filter for Harmonics Mit...Closed Loop Non Linear Control of Shunt Hybrid Power Filter for Harmonics Mit...
Closed Loop Non Linear Control of Shunt Hybrid Power Filter for Harmonics Mit...IAES-IJPEDS
 
A Novel Approach of Harmonic Reduction with Transformer Connected 3-Phase Mul...
A Novel Approach of Harmonic Reduction with Transformer Connected 3-Phase Mul...A Novel Approach of Harmonic Reduction with Transformer Connected 3-Phase Mul...
A Novel Approach of Harmonic Reduction with Transformer Connected 3-Phase Mul...IJMER
 
The Harmonic Mitigation in Induction Furnace Using Hybrid Filter
The Harmonic Mitigation in Induction Furnace Using Hybrid FilterThe Harmonic Mitigation in Induction Furnace Using Hybrid Filter
The Harmonic Mitigation in Induction Furnace Using Hybrid Filterpaperpublications3
 
INSTANTANEOUS POWER AND CURRENT STRATEGIES FOR CURRENT HARMONICS CANCELLATION...
INSTANTANEOUS POWER AND CURRENT STRATEGIES FOR CURRENT HARMONICS CANCELLATION...INSTANTANEOUS POWER AND CURRENT STRATEGIES FOR CURRENT HARMONICS CANCELLATION...
INSTANTANEOUS POWER AND CURRENT STRATEGIES FOR CURRENT HARMONICS CANCELLATION...ijiert bestjournal
 
Analysis and mitigation of unbalance due to load in distribution system by us...
Analysis and mitigation of unbalance due to load in distribution system by us...Analysis and mitigation of unbalance due to load in distribution system by us...
Analysis and mitigation of unbalance due to load in distribution system by us...eSAT Journals
 
Analysis and mitigation of unbalance due to load in
Analysis and mitigation of unbalance due to load inAnalysis and mitigation of unbalance due to load in
Analysis and mitigation of unbalance due to load ineSAT Publishing House
 
ANALYSIS OF TUNED FILTERS FOR MITIGATION OF HARMONIC CURRENT DISTORTION OF R...
 ANALYSIS OF TUNED FILTERS FOR MITIGATION OF HARMONIC CURRENT DISTORTION OF R... ANALYSIS OF TUNED FILTERS FOR MITIGATION OF HARMONIC CURRENT DISTORTION OF R...
ANALYSIS OF TUNED FILTERS FOR MITIGATION OF HARMONIC CURRENT DISTORTION OF R...ijiert bestjournal
 
Application of passive harmonic filters to mitigate
Application of passive harmonic filters to mitigateApplication of passive harmonic filters to mitigate
Application of passive harmonic filters to mitigateeSAT Publishing House
 
report of Improvement of the Electric Power Quality Using Series Active and S...
report of Improvement of the Electric Power Quality Using Series Active and S...report of Improvement of the Electric Power Quality Using Series Active and S...
report of Improvement of the Electric Power Quality Using Series Active and S...Vikram Rawani
 

Similar to Power Quality Improvement in Faulty Conditions using Tuned Harmonic Filters (20)

Paper id 29201412
Paper id 29201412Paper id 29201412
Paper id 29201412
 
Comparative of Conventional and Intelligence Controller based Hybrid Generati...
Comparative of Conventional and Intelligence Controller based Hybrid Generati...Comparative of Conventional and Intelligence Controller based Hybrid Generati...
Comparative of Conventional and Intelligence Controller based Hybrid Generati...
 
Me2420192024
Me2420192024Me2420192024
Me2420192024
 
Power quality improvement in a weak bus system using facts controller
Power quality improvement in a weak bus system using facts controllerPower quality improvement in a weak bus system using facts controller
Power quality improvement in a weak bus system using facts controller
 
Power quality improvement in a weak bus system using
Power quality improvement in a weak bus system usingPower quality improvement in a weak bus system using
Power quality improvement in a weak bus system using
 
Ijetr012048
Ijetr012048Ijetr012048
Ijetr012048
 
Harmonic analysis and Power factor improvement with UPQC under two Novel cont...
Harmonic analysis and Power factor improvement with UPQC under two Novel cont...Harmonic analysis and Power factor improvement with UPQC under two Novel cont...
Harmonic analysis and Power factor improvement with UPQC under two Novel cont...
 
IRJET- A Review on Distribution System with Harmonic Reduction
IRJET- A Review on Distribution System with Harmonic ReductionIRJET- A Review on Distribution System with Harmonic Reduction
IRJET- A Review on Distribution System with Harmonic Reduction
 
Dynamic Power Factor Correction in a Non Linear Environment
Dynamic Power Factor Correction in a Non Linear EnvironmentDynamic Power Factor Correction in a Non Linear Environment
Dynamic Power Factor Correction in a Non Linear Environment
 
H010615159
H010615159H010615159
H010615159
 
Closed Loop Non Linear Control of Shunt Hybrid Power Filter for Harmonics Mit...
Closed Loop Non Linear Control of Shunt Hybrid Power Filter for Harmonics Mit...Closed Loop Non Linear Control of Shunt Hybrid Power Filter for Harmonics Mit...
Closed Loop Non Linear Control of Shunt Hybrid Power Filter for Harmonics Mit...
 
A Novel Approach of Harmonic Reduction with Transformer Connected 3-Phase Mul...
A Novel Approach of Harmonic Reduction with Transformer Connected 3-Phase Mul...A Novel Approach of Harmonic Reduction with Transformer Connected 3-Phase Mul...
A Novel Approach of Harmonic Reduction with Transformer Connected 3-Phase Mul...
 
The Harmonic Mitigation in Induction Furnace Using Hybrid Filter
The Harmonic Mitigation in Induction Furnace Using Hybrid FilterThe Harmonic Mitigation in Induction Furnace Using Hybrid Filter
The Harmonic Mitigation in Induction Furnace Using Hybrid Filter
 
INSTANTANEOUS POWER AND CURRENT STRATEGIES FOR CURRENT HARMONICS CANCELLATION...
INSTANTANEOUS POWER AND CURRENT STRATEGIES FOR CURRENT HARMONICS CANCELLATION...INSTANTANEOUS POWER AND CURRENT STRATEGIES FOR CURRENT HARMONICS CANCELLATION...
INSTANTANEOUS POWER AND CURRENT STRATEGIES FOR CURRENT HARMONICS CANCELLATION...
 
Analysis and mitigation of unbalance due to load in distribution system by us...
Analysis and mitigation of unbalance due to load in distribution system by us...Analysis and mitigation of unbalance due to load in distribution system by us...
Analysis and mitigation of unbalance due to load in distribution system by us...
 
Analysis and mitigation of unbalance due to load in
Analysis and mitigation of unbalance due to load inAnalysis and mitigation of unbalance due to load in
Analysis and mitigation of unbalance due to load in
 
ANALYSIS OF TUNED FILTERS FOR MITIGATION OF HARMONIC CURRENT DISTORTION OF R...
 ANALYSIS OF TUNED FILTERS FOR MITIGATION OF HARMONIC CURRENT DISTORTION OF R... ANALYSIS OF TUNED FILTERS FOR MITIGATION OF HARMONIC CURRENT DISTORTION OF R...
ANALYSIS OF TUNED FILTERS FOR MITIGATION OF HARMONIC CURRENT DISTORTION OF R...
 
Application of passive harmonic filters to mitigate
Application of passive harmonic filters to mitigateApplication of passive harmonic filters to mitigate
Application of passive harmonic filters to mitigate
 
Effects of power electronics devices on the energy quality of an administrati...
Effects of power electronics devices on the energy quality of an administrati...Effects of power electronics devices on the energy quality of an administrati...
Effects of power electronics devices on the energy quality of an administrati...
 
report of Improvement of the Electric Power Quality Using Series Active and S...
report of Improvement of the Electric Power Quality Using Series Active and S...report of Improvement of the Electric Power Quality Using Series Active and S...
report of Improvement of the Electric Power Quality Using Series Active and S...
 

More from IOSR Journals (20)

A011140104
A011140104A011140104
A011140104
 
M0111397100
M0111397100M0111397100
M0111397100
 
L011138596
L011138596L011138596
L011138596
 
K011138084
K011138084K011138084
K011138084
 
J011137479
J011137479J011137479
J011137479
 
I011136673
I011136673I011136673
I011136673
 
G011134454
G011134454G011134454
G011134454
 
H011135565
H011135565H011135565
H011135565
 
F011134043
F011134043F011134043
F011134043
 
E011133639
E011133639E011133639
E011133639
 
D011132635
D011132635D011132635
D011132635
 
C011131925
C011131925C011131925
C011131925
 
B011130918
B011130918B011130918
B011130918
 
A011130108
A011130108A011130108
A011130108
 
I011125160
I011125160I011125160
I011125160
 
H011124050
H011124050H011124050
H011124050
 
G011123539
G011123539G011123539
G011123539
 
F011123134
F011123134F011123134
F011123134
 
E011122530
E011122530E011122530
E011122530
 
D011121524
D011121524D011121524
D011121524
 

Recently uploaded

HARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICS
HARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICSHARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICS
HARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICSRajkumarAkumalla
 
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...ranjana rawat
 
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLS
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLSMANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLS
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLSSIVASHANKAR N
 
Introduction and different types of Ethernet.pptx
Introduction and different types of Ethernet.pptxIntroduction and different types of Ethernet.pptx
Introduction and different types of Ethernet.pptxupamatechverse
 
Introduction to Multiple Access Protocol.pptx
Introduction to Multiple Access Protocol.pptxIntroduction to Multiple Access Protocol.pptx
Introduction to Multiple Access Protocol.pptxupamatechverse
 
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...ranjana rawat
 
(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service
(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service
(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Serviceranjana rawat
 
GDSC ASEB Gen AI study jams presentation
GDSC ASEB Gen AI study jams presentationGDSC ASEB Gen AI study jams presentation
GDSC ASEB Gen AI study jams presentationGDSCAESB
 
Architect Hassan Khalil Portfolio for 2024
Architect Hassan Khalil Portfolio for 2024Architect Hassan Khalil Portfolio for 2024
Architect Hassan Khalil Portfolio for 2024hassan khalil
 
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...ranjana rawat
 
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICSAPPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICSKurinjimalarL3
 
Extrusion Processes and Their Limitations
Extrusion Processes and Their LimitationsExtrusion Processes and Their Limitations
Extrusion Processes and Their Limitations120cr0395
 
main PPT.pptx of girls hostel security using rfid
main PPT.pptx of girls hostel security using rfidmain PPT.pptx of girls hostel security using rfid
main PPT.pptx of girls hostel security using rfidNikhilNagaraju
 
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escortsranjana rawat
 
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝soniya singh
 
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...ranjana rawat
 
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...ranjana rawat
 

Recently uploaded (20)

HARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICS
HARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICSHARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICS
HARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICS
 
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
 
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLS
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLSMANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLS
MANUFACTURING PROCESS-II UNIT-5 NC MACHINE TOOLS
 
Introduction and different types of Ethernet.pptx
Introduction and different types of Ethernet.pptxIntroduction and different types of Ethernet.pptx
Introduction and different types of Ethernet.pptx
 
Introduction to Multiple Access Protocol.pptx
Introduction to Multiple Access Protocol.pptxIntroduction to Multiple Access Protocol.pptx
Introduction to Multiple Access Protocol.pptx
 
★ CALL US 9953330565 ( HOT Young Call Girls In Badarpur delhi NCR
★ CALL US 9953330565 ( HOT Young Call Girls In Badarpur delhi NCR★ CALL US 9953330565 ( HOT Young Call Girls In Badarpur delhi NCR
★ CALL US 9953330565 ( HOT Young Call Girls In Badarpur delhi NCR
 
Call Us -/9953056974- Call Girls In Vikaspuri-/- Delhi NCR
Call Us -/9953056974- Call Girls In Vikaspuri-/- Delhi NCRCall Us -/9953056974- Call Girls In Vikaspuri-/- Delhi NCR
Call Us -/9953056974- Call Girls In Vikaspuri-/- Delhi NCR
 
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
 
(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service
(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service
(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service
 
GDSC ASEB Gen AI study jams presentation
GDSC ASEB Gen AI study jams presentationGDSC ASEB Gen AI study jams presentation
GDSC ASEB Gen AI study jams presentation
 
Architect Hassan Khalil Portfolio for 2024
Architect Hassan Khalil Portfolio for 2024Architect Hassan Khalil Portfolio for 2024
Architect Hassan Khalil Portfolio for 2024
 
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
 
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICSAPPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
 
Exploring_Network_Security_with_JA3_by_Rakesh Seal.pptx
Exploring_Network_Security_with_JA3_by_Rakesh Seal.pptxExploring_Network_Security_with_JA3_by_Rakesh Seal.pptx
Exploring_Network_Security_with_JA3_by_Rakesh Seal.pptx
 
Extrusion Processes and Their Limitations
Extrusion Processes and Their LimitationsExtrusion Processes and Their Limitations
Extrusion Processes and Their Limitations
 
main PPT.pptx of girls hostel security using rfid
main PPT.pptx of girls hostel security using rfidmain PPT.pptx of girls hostel security using rfid
main PPT.pptx of girls hostel security using rfid
 
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
 
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝
 
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
 
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
 

Power Quality Improvement in Faulty Conditions using Tuned Harmonic Filters

  • 1. IOSR Journal of Electrical and Electronics Engineering (IOSR-JEEE) e-ISSN: 2278-1676,p-ISSN: 2320-3331, Volume 6, Issue 5 (Jul. - Aug. 2013), PP 01-09 www.iosrjournals.org www.iosrjournals.org 1 | Page Power Quality Improvement in Faulty Conditions using Tuned Harmonic Filters Sumit Kanwar1 , Om Prakash Mahela2 , Devendra Mittal3 1 (Senior Lecturer, Department of Electrical Engineering, Asians Institute of Technology, Jaipur, India) 2 (Graduate Student Member IEEE & Junior Engineer-I, RRVPNL, Jodhpur, India) 3 (Assistant Professor, Department of Electrical Engineering, Jagannath University, Jaipur, India) Abstract : The Electrical power quality has become an important topic of discussion and research these days. As per IEEE 519 std. parameters of power quality measurement, are four in number, of which Total Harmonic Distortion is most widely used. This paper proposes the optimal planning of passive tuned harmonic filters for improvement of power quality in faulty conditions of electrical power system. The Total Harmonic Distortion analysis of power quality disturbances is carried out in the faulty conditions and in the presence of single tuned and double tuned harmonic filters. The four bus system having two load and two generator buses is modeled in MATLAB/Simulink environment. A fault is created near the load bus and power quality disturbances are detected near the generator bus and improved using single tuned and double tuned filters near the generator bus under study. The Matlab results show the performance of double tuned filter in improvement of power quality disturbances during faulty conditions. Keywords – power quality disturbances, total harmonic distortion, power system fault, single tuned harmonic filter, double tuned harmonic filter. I. INTRODUCTION The continuous monitoring of power quality (PQ) has become imperative as occurrences of PQ disturbances are relatively sporadic and mostly unscheduled. Further when something goes wrong and the source of the problem needs to be investigated, whether upstream or downstream of the issue, PQ data is an absolute necessity [1]. Power quality is a term used to describe the most important aspect of the electricity supply. Power quality can be defined as any problem manifested in voltage, current, or frequency deviation that results in failure or mal-operation of electric equipment [2]. Poor quality of electric power is normally caused by power line disturbances, such as impulses, notches, glitches, momentary interruption wave faults, voltage sag, swell, harmonic distortion and flicker resulting in misoperation or failure of end use equipments [3]. Poor quality may cause many problems that affect the load such as malfunction, instability, short lifetime and so on. According to the survey by IEEE transactions on Industrial Applications, power quality disturbances lead to losses of $4 billion to $10 billion in the USA alone [4]. In recent years, grid users have detected an increasing number of drawbacks caused by electric power quality (PQ) variations and PQ problems have sharpened because of the increased number of loads sensitive to PQ and have become more difficult to solve as the loads themselves have become important causes of degradation of quality [5]. Transmission line relaying involves the three major tasks: detection, classification, and location of the fault. It must be done as fast and accurate as possible to de-energize the faulted line and protecting the system from the harmful effects of the fault. With the wide application of high power electronics switchgears, problems of power quality are becoming more serious day by day [6]-[7]. The power quality disturbances depend on amplitude or frequency or on both frequency and amplitude. Based on duration of existence of PQ disturbances, events can be divided in short, medium or long type. The classification and identification of each disturbance are usually carried out from standards and recommendations depending on where the utilities operate (e.g. IEEE in the U.S.). Inigo Monedero et al. [8] defined PQ disturbances, based on the UNE standard in Spain which defines the ideal signal as a single-phase or three-phase sinusoidal voltage signal of 230 VRMS and 50Hz. D. Saxena et al. [9] classified various PQ events in to five groups viz. short duration variation, long duration variation, transients, voltage imbalance and waveform distortion. S.Edwin Jose et al. [10] classified PQ disturbances on basis of values of tails of histogram obtained from simulation results. Haibo He et al.[11] proposed a novel approach for the power quality disturbances classification based on the wavelet transform and self organizing learning array system. Devendra Mittal et al. [12] presented a method for improvement of electrical power quality under faulty conditions in electrical power system using three phase double tuned harmonic filter. Most of papers published on power quality are concerned with the customer related issues and classification of power quality disturbances. This paper aims improvement of power quality in faulty conditions of power system using three phase single tuned and double tuned harmonic filters. The four bus system with two load and two generator buses is simulated in MATLAB/Simulink environment. The power quality improvement
  • 2. Power Quality Improvement in Faulty Conditions using Tuned Harmonic Filters www.iosrjournals.org 2 | Page using three phase harmonic filters connected at generator bus during LG fault, LL fault, LLG fault, LLL fault and LLLG fault on the load bus has been studied. The analysis is carried out on the basis of Total harmonic Distortion (THD). The results obtained after simulation demonstrate the performance of three phase harmonic filters in improvement of power quality during faulty conditions of power system. II. THREE-PHASE TUNED HARMONIC FILTERS The passive harmonics filters are composed of passive elements: resistor (R), inductor (L) and capacitor (C). The common types of passive filters include single-tuned and double tuned filters, second-order, third-order and C-type damped filters. Three-phase harmonic filters are shunt elements that are used in power systems for decreasing voltage distortion and for power factor correction. The three-phase harmonic filter is built of RLC elements. The resistance, inductance and capacitance values are determined from the filter type, reactive power at nominal voltage, tuning frequencies and quality factor. Passive filter has been widely used in filtering harmonics in power system because it has a simple structure, low cost and high reliability. The single tuned filter is the series combination of inductor (L) and capacitor (C) as shown in Fig. 1. Usually, there are multiple frequency harmonics in a power system, so a group of parallel single tuned filters are needed to filter harmonics. This filtering method covers a large area and has a high cost [13]. Fig. 1 Single tuned harmonic filter Double tuned filter performs the same function as two single tuned filters connected in parallel although it has certain advantages of lower cost, low losses and lower impedance magnitude at the frequency of parallel resonance that arises between the two tuning frequencies [14]. Chih-Ju et al.[15] presented that double tuned filter consists of a series LC circuit and a parallel RLC circuit as shown in Fig. 2. If f1 and f2 are the two tuning frequencies, both the series circuit and parallel circuit are tuned to approximately the mean geometric frequency given by the relation: 𝑓𝑚 = 𝑓1 × 𝑓2 (1) The quality factor Q of the double tuned filter is defined as the quality factor of the parallel L, R elements at the mean frequency fm: 𝑄 = 𝑅 𝐿 × 2𝜋𝑓𝑚 (2) Fig. 2 Double tuned harmonic filter III. TOTAL HARMONIC DISTORTION Non-sinusoidal input, or supply, current is made up of fundamental current plus current components of higher frequencies. The total harmonic distortion (THD) is equal to the rms value of all the harmonics divided
  • 3. Power Quality Improvement in Faulty Conditions using Tuned Harmonic Filters www.iosrjournals.org 3 | Page by the rms value of fundamental component of the input current. Greater the value of THD greater is the harmonic content and hence greater is the distortion of input supply current [16]. The THD is given by the relation given below:- 𝑇𝐻𝐷 = 𝐼ℎ 𝐼𝑠1 = 𝐼𝑠 2 − 𝐼𝑠1 2 𝐼𝑠1 2 = 𝐼𝑠𝑛 ∞ 𝑛=2 𝐼𝑠1 (3) Where Ih = rms value of all the harmonic components combined Isn= rms value of nth harmonic content. Is = rms value of supply phase current including fundamental and harmonics. IV. PROPOSED POWER SYSTEM MODEL For power quality improvement using three-phase single tuned and double tuned harmonic filters during faulty conditions in the power system, the one line diagram of experimental set up consisting of four buses shown in Fig. 3 is used [17]. The buses 1 & 2 are taken as generator buses and buses 3 & 4 are taken as load buses. The line length of all the four π sections are taken as 100 Km. For simplicity the voltage levels at all points of the power system are taken as 33 KV. The three-phase tuned harmonic filters are installed near the generator bus 1 to protect the generator from power system disturbances during faulty conditions. The fault is located at bus no. 4 in all faulty conditions considered in the study. All the measurement of the voltage signals are taken on bus no. 1 at generating station. Fig. 3 Proposed model of power system for improvement of PQ disturbances in faulty conditions using tuned harmonic filters V. POWER SYSTEM SIMULATION AND DISCUSSION Power system faults are abnormal events which are not part of normal operation and unwanted by the network operator. After fault occurs in the power system, a non-linear signal of transient travelling wave is generated and runs along faulted transmission line to both ends of the line. Those travelling waves contain information about fault nature. The fault initial travelling wave has a wide frequency spectrum from DC component to high frequencies. When such fault travelling wave arrives at the substation bus bar, it will change incisively, i.e. travelling wave head will present the sudden change in the time-frequency diagram. In that way, travelling wave arrival to the measuring point (usually the busbar voltage transformers) exactly a moment of sudden change recorded on measuring substation [18]. For experimental improvement of power quality disturbances to reduce the impact of PQ disturbances on the generators three-phase single tuned and double tuned harmonic filter are used. The proposed model is simulated in MATLAB/Simulink environment for analysis of improvement in the power quality disturbances. The analysis of power quality improvement in the proposed model is based on the total harmonic distortion (THD). The simulation is carried out in three conditions viz. faulty system before filtering, faulty system after filtering using single tuned harmonic filter and faulty system after filtering using double tuned filter. Filter Bus 1 Bus 2 Bus 3 Bus 4 Fault Location Point A LoadLoad G G
  • 4. Power Quality Improvement in Faulty Conditions using Tuned Harmonic Filters www.iosrjournals.org 4 | Page V.1 LG Fault in Power System The power system model shown in Fig. 3 is simulated in MATLAB/Simulink environment with line to ground fault at bus no. 4 on phase-A. The THD analysis of voltage signal of phase-A during line to ground fault before filtering is shown in Fig. 4. The higher order frequency of integral multiple of fundamental frequency up to 500Hz is observed. The observed THD is 3.60%. Fig. 4 THD in Phase-A during LG fault before filtering The THD analysis of voltage signal of phase-A during line to ground fault after using single tuned filter is shown in Fig. 5. The higher order frequency of integral multiple of fundamental frequency up to 900Hz is observed. The observed THD is 2.65%. Fig. 5 THD in Phase-A during LG fault after filtering using single tuned filter The THD analysis of voltage signal of phase-A during line to ground fault after using double tuned filter is shown in Fig. 6. The higher order frequency of integral multiple of fundamental frequency up to 850Hz is observed. The observed THD is 1.26%. Fig. 6 THD in Phase-A during LG fault after filtering using double tuned filter V.2 LL Fault on Power System The power system model shown in Fig. 3 is simulated in MATLAB/Simulink environment with double line fault between phases A and B at bus no. 4. The THD analysis of voltage signal of phase-A during double line fault before filtering is shown in Fig. 7. The higher order frequency of integral multiple of fundamental frequency up to 750Hz is observed. The observed THD is 3.52%.
  • 5. Power Quality Improvement in Faulty Conditions using Tuned Harmonic Filters www.iosrjournals.org 5 | Page Fig. 7 THD in Phase-A during LL fault on phases A and B before filtering The THD analysis of voltage signal of phase-A during double line fault after using single tuned filter is shown in Fig. 8. The higher order frequency of integral multiple of fundamental frequency up to 800Hz is observed. The observed THD is 1.35%. Fig. 8 THD in Phase-A during LL fault on phases A and B after filtering using single tuned filter The THD analysis of voltage signal of phase-A during double line fault after using double tuned filter is shown in Fig. 9. The higher order frequency of integral multiple of fundamental frequency up to 950Hz is observed. The observed THD is 1.14%. Fig. 9 THD in Phase-A during LL fault on phases A and B after filtering using double tuned filter V.3 LLG Fault on Power System The power system model shown in Fig. 3 is simulated in MATLAB/Simulink environment with double line to ground fault between phases A and B at bus no. 4. The THD analysis of voltage signal of phase-A during double line to ground fault before filtering is shown in Fig. 10. The higher order frequency of integral multiple of fundamental frequency up to 200 Hz is observed. The observed THD is 7.55%. Fig. 10 THD in Phase-A during LLG fault on phases A and B before filtering The THD analysis of voltage signal of phase-A during double line to ground fault after using single tuned filter is shown in Fig. 11. The higher order frequency of integral multiple of fundamental frequency up to 650 Hz is observed. The observed THD is 2.01%.
  • 6. Power Quality Improvement in Faulty Conditions using Tuned Harmonic Filters www.iosrjournals.org 6 | Page Fig. 11 THD in Phase-A during LLG fault on phases A and B after filtering using single tuned filter The THD analysis of voltage signal of phase-A during double line to ground fault after using double tuned filter is shown in Fig. 12. The higher order frequency of integral multiple of fundamental frequency up to 700 Hz is observed. The observed THD is 1.03%. Fig. 12 THD in Phase-A during LL fault on phases A and B after filtering using double tuned filter V.4 LLL Fault on Power System The power system model shown in Fig. 3 is simulated in MATLAB/Simulink environment with three phase fault at bus no. 4. The THD analysis of voltage signal of phase-A during three phase fault before filtering is shown in Fig. 13. The higher order frequency of integral multiple of fundamental frequency up to 900 Hz is observed. The observed THD is 6.40%. Fig. 13 THD in Phase-A during LLL fault before filtering The THD analysis of voltage signal of phase-A during three phase fault after using single tuned filter is shown in Fig. 14. The higher order frequency of integral multiple of fundamental frequency up to 850 Hz is observed. The observed THD is 1.46%. Fig. 14 THD in Phase-A during LLL fault after filtering using single tuned filter
  • 7. Power Quality Improvement in Faulty Conditions using Tuned Harmonic Filters www.iosrjournals.org 7 | Page The THD analysis of voltage signal of phase-A during three phase fault after using single tuned filter is shown in Fig. 15. The higher order frequency of integral multiple of fundamental frequency up to 900 Hz is observed. The observed THD is 1.55%. Fig. 15 THD in Phase-A during LLL fault after filtering using double tuned filter V.5 LLLG Fault on Power System The power system model shown in Fig. 3 is simulated in MATLAB/Simulink environment with three phase fault involving ground at bus no. 4. The THD analysis of voltage signal of phase-A during three phase fault involving ground before filtering is shown in Fig. 16. The higher order frequency of integral multiple of fundamental frequency up to 200 Hz is observed. The observed THD is 9.55%. Fig. 16 THD in Phase-A during LLLG fault before filtering The THD analysis of voltage signal of phase-A during three phase fault involving ground after using single tuned filter is shown in Fig. 17. The higher order frequency of integral multiple of fundamental frequency up to 350 Hz is observed. The observed THD is 6.70%. Fig. 17 THD in Phase-A during LLLG fault after filtering using single tuned filter The THD analysis of voltage signal of phase-A during three phase fault involving ground after using single tuned filter is shown in Fig. 18. The higher order frequency of integral multiple of fundamental frequency up to 950 Hz is observed. The observed THD is 3.19%.
  • 8. Power Quality Improvement in Faulty Conditions using Tuned Harmonic Filters www.iosrjournals.org 8 | Page Fig. 18 THD in Phase-A during LLLG fault after filtering using double tuned filter The total harmonic distortion (THD) of voltage signal at generator bus no. 1 of proposed power system model during different faulty conditions when fault is created at bus no. 4 are shown in Table. 1. The three conditions before filtering, after using single tuned filter and after using double tuned filter are discussed. TABLE 1 TOTAL HARMONIC DISTORTION OF VOLTAGE SIGNAL IN FAULTY CONDITION S.No. Type of Fault THD Before Filtering THD After Using Single Tuned Filter THD After Using Double Tuned Filter 1 Line to Ground(LG) 3.60% 2.65% 1.26% 2 Double Line (LL) 3.52% 1.35% 1.14% 3 Double Line to Ground (LLG) 7.55% 2.01% 1.03% 4 Three Phase Fault (LLL) 6.40% 1.46% 1.55% 5 Three Phase Fault involving ground (LLLG) 9.55% 6.70% 3.19% VI. CONCLUSION An efficient but simple technique has been developed for improvement of power quality disturbances during faulty conditions using three phase tuned harmonic filters in the electrical power system. The proposed model of four bus system is simulated in the MATLAB/Simulink environment. The analysis of improvement of power quality during faulty conditions of power system using tuned harmonic filters is carried out using the total harmonic distortion. The results show that three-phase harmonic filters are effective in improvement of power quality in faulty conditions. The double tuned harmonic filter is comparatively more effective as compared to the single tuned harmonic filter. The THD reduces in all faulty conditions while using single tuned filter which further reduces on using double tuned filter. The tuned harmonic filters are effective in protecting the costly equipment of power system transients during faulty conditions. REFERENCES [1] Manoj Gupta, Rajesh Kumar, and Ram Awtar Gupta, “Neural Network Based Indexing and Recognition of Power Quality Disturbances,” TELKOMNIKA, Vol. 9, No.2, August 2011, pp. 227-236. [2] R.Dugan, M. McGranaghan, and H. Wane Beaty, Electrical Power Systems Quality, McGraw-Hill, Ney York, 1996. [3] Subhamita Roy, and Sudipta Nath, “Classification of power quality disturbances using features of signals,” International Journal of Scientific and Research Publications, Vol. 2, Issue 11, November 2012, pp.01-09. [4] He H., Shen X, and Starzyk J.A., “Power quality disturbances analysis based on EDMRA method,” Electrical Power and Energy System, Vol. 31, pp. 258-268. [5] P.Daponte, M.di Penta, and G. Mercurio, Transientmeter: A distuributed measurement system for power quality monitoring,” Proceeding 9th International Conference Harmonics and Quality of Power, 2000, Vo. 3, pp.1017-1022. [6] M.Sushama, G.Tulasi Ram Das, and A.Jaya Laxmi, “Mitigation of voltage sags with dynamic voltage restorer using wavelets,” Presented at the International Conference RACE 2007, March 22-24, 2007. [7] Anoop Mathew, and Benisker Raja Singh D., “Image compression using lifting based DWT,” International Journal of Computers Information Technology and Engineering, Vol. 3, January 2009, pp. 27-31. [8] Inigo Monedero, Carlos Leon, Jorge Ropero, Antonio Garcia, Jose Manuel and Juan C. Montano, “Classification of Electrical Disturbances in Real Time Using Neural Networks,” IEEE Transaction on Power Delivery, 2007, pp.1-9. [9] D. Saxena, K.S. Verma and S.N. Singh, “Power quality event classification: an overview and key issues,” International Journal of Engineering, Science and Technology, Vol. 2, No.3, 2010, pp. 186-199. [10] S.Edwin Jose, and S.Titus, “Detection and classification of power quality using adaptive decomposition structure and neural network,” European Journal of Scientific Research, Vol.89, No.3, October 2012, pp. 477-489. [11] Haibo He, and Janusz A. Starzyk, “A self-organizing learning array system for power quality classification based on wavelet transform,” IEEE Transaction on Power Delivery, Vol. 21, No. 1, January 2006, pp.286-295. [12] Devendra Mittal, Om Prakash Mahela, and Rohit Jain, “Electrical power quality improvement in faulty conditions using three phase double tuned harmonic filter,” International Journal of Innovative Research and development, Vol. 2, Issue 6, June 2013, pp.493- 509.
  • 9. Power Quality Improvement in Faulty Conditions using Tuned Harmonic Filters www.iosrjournals.org 9 | Page [13] He Yi-hong, and SU Heng, “A new method of designing double tuned filter,” Proceedings of the 2nd International Conference on Computer Science and Electronics Engineering, ICCSEE 2013, Paris, France. [14] Wang Zhaoan, and Yang Jun, Harmonic suppression and reactive power compensation, (Beijing: China Machine Press, 2010). [15] Chih-Ju, and Chih-Wen Liu, “Optimal planning of large passive-harmonic filters set at high voltage level,” IEEE transactions on Power Systems, Vol. 15, No. 1, February 2000, pp. 433-441. [16] Dr. P.S. Bimbhra, Power Electronics, Khanna Publications, New Delhi, 2011. [17] Devendra Mittal, Om Prakash Mahela, and Rohit Jain, “Detection and analysis of power quality disturbances under faulty conditions in electrical power system,” IAEME-International Journal of Electrical Engineering & Technology, Vol. 4, Issue 2, March-April 2013, pp. 25-36. [18] Alen Bernadic, and Zbigniew Leonowicz, “Power line fault location using the complex space-phasor and Hilbert-huang transform,” Przeglad Elektrotechniczny (Electrical Review), R.87 NR 5/2011, pp. 204-207. BIOGRAPHIES Sumit Kanwar studied at Rajasthan College of Engineering for Women and received the B.Tech. in Electrical Engineering from Rajasthan Technical University, Kota, India, in 2010. She received Master’s degree in Electrical Engineering from the Jagannath University, Jaipur, India in 2013 with specialization on Power System. From 2010 to 2011, she was Assistant Professor with the Maharani Girls Engineering College, Jaipur, India. Since 2011 she has been senior lecturer with the Electrical Engineering department of the Asians Institute of Technology, Jaipur, India. Her special fields of interest are power electronics in power system, applications of AI techniques in power system and power quality. Om Prakash Mahela was born in Sabalpura (Kuchaman City) in the Rajasthan state of India, on April 11, 1977. He studied at Govt. College of Engineering and Technology (CTAE), Udaipur, and received the electrical engineering degree from Maharana Pratap University of Agriculture and Technology (MPUAT), Udaipur, India in 2002. He received M.Tech.(Electrical Engineering) with power system specialization from Jagannath University, Jaipur, India in 2013. He is currently pursuing PhD from Indian Institute of Technology Jodhpur. From 2002 to 2004, he was Assistant Professor with the RIET, Jaipur. Since 2004, he has been Junior Engineer-I with the Rajasthan Rajya Vidhyut Prasaran Nigam Ltd., Jodhpur, India. His special fields of interest are Transmission and Distribution (T&D) grid operations, Power Electronics in Power System, Power Quality, Load Forecasting and Integration of Renewable Energy with Electric Transmission and Distribution Grid, Applications of AI Techniques in power system. He is an author of 26 International Journals and Conference papers. He is a Graduate Student Member of IEEE. He is member of IEEE Communications Society. He is Member of IEEE Power & Energy Society. He is Fellow Member of IAEME. He is Reviewer of TJPRC International Journal of Electrical and Electronics Engineering Research. Mr. Mahela is recipient of University Rank certificate from MPUAT, Udaipur, India, in 2002. He is recipient of university first Rank in M.Tech. from Jagannath University, Jaipur, India in 2013. Devendra Mittal was born in Bhusawar in the Rajasthan state of India, on March 17, 1980. He studied at IET, Alwar, and received the electrical engineering degree from Rajasthan University, Jaipur, in 2003. He received M.Tech.(Power system) from MNIT, Jaipur, in 2007. He is currently pursuing Phd from Jagannath University, Jaipur. From 2003 to 2008, he was Lecturer with Shankara Institute of Technology, Jaipur. From 2008 to 2009, he was Lecturer with UDML Engineering College. Since 2009, he has been Assistant Professor with Jagannath University, Jaipur, India. His special fields of interest are Power Electronics and Power System.