International Journal of Engineering Research and Development
e-ISSN: 2278-067X, p-ISSN: 2278-800X, www.ijerd.com
Volume 7, Issue 12 (July 2013), PP. 18-24
18
Influence of Switching Elements on Harmonics and Power
Factor Improvement
1
A.Kumar, 2
Dr.G.R.Gurumurthy
B N M Institute of Technology, BSK
2nd
stage, Bangalore, India - 560070
Abstract:- Increasing demand for electrical energy by utilities has necessitated efficient utilization of available
power. Most of the loads in the industry and domestic applications are inductive in nature causing a lagging
power factor. This causes a reduction in the utilization of the power input. For the same power input the
utilization can be improved by improving the power factor. Further the presence of harmonics results in poor
quality of the power leading to losses. . In present days, solid state electronics control electric motors are
frequently used for drive control (speed and torque). This can introduce harmonics in current and voltages. The
general opinion among technologists is that improvement in power factor reduces losses in an electrical system.
Although this is true in a general way, it is not so in systems which use switched electronic devices that can
introduce large amount of harmonics [1].
The present work is aimed to study the effect of power factor correction on circuits consisting of power
semiconductor switching. Boost convertor supplied from an unregulated supply was considered for the analysis
of a static loading. The work also involved study of power factor improvement(PFI) for dynamic load. An
automatic power factor controller was designed and implemented induction motor load. The controller was
designed to sense the various parameters of the power and calculate the power factor. A rule-based table has
been developed based on the power factor input. The controller can sense this power factor and automatically
switch ON/OFF appropriate KVAR as per the programmed requirement. The results obtained are comparable
with that reported in several previous work done.[1-6]
Keywords:- Power factor improvement, Harmonics, THD, APFC, Filters
I. INTRODUCTION
Quantum of Energy generation is one of the metric for the measurement of a Nation’s development.
The requirement of energy is much more than the amount of power getting generated in developing countries
like India. Under these circumstances Demand side management (DSM) is one of the methods to improve the
utilization of energy. Most of the industrial and domestic loads are inductive in nature and hence the power
factor of the loads are very poor. An improvement in the power factor results in availability of more active
power for the same generated power. Power factor improvement is most commonly used in industrial units.
Automatic power factor controllers (APFC) are equipped with semiconductor devices, switching of capacitor
banks for the improvement of power factor. In present days, solid state electronics control for electric motors
are frequently used for drive control (speed and torque). This can introduce harmonics in current and voltages.
The general opinion among technologists is that improvement in power factor reduces losses in an electrical
system. Although this is true in a general way, it is not so in systems which use switched electronic devices that
can introduce large amount of harmonics.
a. Power factor:1. Concept of Power Factor
Power factor is defined as the ratio of active power to apparent power. i.e., PF = . It is also
defined as a cosine of the angle between voltage and current vectors in an electric network in which voltage
and current are sinusoidal parameters. i.e., PF = cos Φ, where Φ is the angle between voltage and current vector.
A poor power factor requires more apparent power for the same amount of active power consumed. It also
increases the current level of operation and thereby increases losses in the system. A poor power factor is
generally the result of inductive loads such as induction motor, welding set etc,. The poor power factor can also
be due to distortion in current waveform resulting from power electronic based converters like rectifier,
inverter etc,. used in the system.
II. BENEFITS OF POWER FACTOR IMPROVEMENT
The benefits that can be achieved by applying the correct power factor correction are:
1. Reduction of power consumption due to improved energy efficiency. Reduced power consumption reduces
green house emission and fossil fuel depletion.
Influence of Switching Elements on Harmonics and Power Factor Improvement
19
2. Extra power is available from the existing supply due to reduction of consumption in reactive KVA.
3. Reduced I2
R losses in machines and hence efficiency increases.
4. Voltage regulation improves due to reduced voltage drop in long cables & long lines.
5. The current drawn for the same load is lesser hence KVA loading of the machines reduce.
The figure 1.1 shows the power triangle.
Active power (kW)
Φ Reactive Power
Total power (kVAr)
(kVA)
Fig 1.1. Power triangle
III. POWER FACTOR IMPROVEMENT FOR INDUCTIVE LOADS
Power factor improvement is commonly adopted method for effective utilization of available power.
The various advantages of improving power factor have been discussed earlier. The power factor improvement
incorporates additional capacitive reactive power which compensates for the inductive reactive power of the
load and thus improving power factor [1]. The vector diagram showing the improvement in power factor using
capacitor bank is given in Fig.1.2
Ic
Reference Ic = capacitor compensation current
Φ2 Voltage I load1 = load current with pf=cosΦ1
Φ1 Iload2 = load current with pf=cosΦ2
ILoad2
ILoad1
Fig1.2: Vector showing power factor improvement using capacitor bank.
KVA saving by improving power factor from cos Φ1 to cos Φ2 can be obtained as given in the
expression below: saving in KVA = (KW / cos Φ2 ) - (KW / cos Φ1). For improvement of power factor in
large capacitive loads suitable inductors have to be used.
b. Harmonics:
Harmonics have existed for many years in the power lines of plants and factories. However only over
the last decade they have turned into a major problem to normal operations. This is largely due to the
proliferation of harmonic producing equipment and the increased sensitivity of certain types of equipment to
harmonics. The effects of harmonics can often be serious - computer systems may fail to operate properly;
capacitor banks, such as those used for power factor correction may fail prematurely (much before expected
life). The presence of harmonics increases losses in the system.
IV. CONCEPT OF HARMONICS:
Harmonics are distortions to the voltage and current waveforms from their normal sinusoidal shape. At the
power generating stations, a 50 Hertz (Hz) sine wave is generated and distributed to a large number of residential and
industrial loads. Certain types of loads distort the 50Hz wave by injecting additional signals of various magnitudes and
frequencies. These additional signals are also sinusoidal in shape but their frequencies are multiples of the original
waves for example, 150, 250 and 350Hz. These waves are called harmonics.
The frequency of the power systems parameter voltage and current waves are called the fundamental, which in our case
is 50Hz. Harmonics are expressed as integral multiples of fundamental frequency i.e., 2nd
, 3rd
, 4th
5th
etc orders. An
important feature of harmonics is that the magnitude of the harmonics normally decreases with increasing frequency.
Thus, only the first few orders usually need to be considered in examining the effects of harmonics on power system
components or equipment. Fig 1.3 shows a sample current wave with harmonics.
Influence of Switching Elements on Harmonics and Power Factor Improvement
20
Fig 1.3. Waveform showing a sample of distorted current waveform due to harmonics.
V. SOURCES OF HARMONICS:
The various sources of harmonics are discussed under:
1. Increase in use of Power converters which use controlled switching, such as rectifiers, inverters, and AC phase control
systems has increased harmonics due to switching action.
2. Motors: Asymmetrical air gaps, slight irregularities in mounting axes can cause motors in equipment such as
pumps, fans and compressors to produce harmonics.
3. APFC capacitors: Power Factor Correction Capacitors can magnify harmonics if not properly applied.
VI. PFI IN AN UNCONTROLLED RECTIFIER WITH BOOST CONVERTER
a. Introduction and Design
An uncontrolled single phase rectifier supplying a boost converter with duty cycle of 50% and 90%
was considered for investigation. The basic circuit used is given in Fig 2.1. For the design of the rectifier a
ripple factor of 1% was considered.
Considering the frequency of 50hz and CF = 250μF we get,
The ac input applied was 230v, 50Hz. The output of the rectifier was a DC of 325 V with 1% ripple. The boost
converter was designed with a switch at 50% Duty cycle(D). Therefore the expected output voltage is Vo = VS /
( 1 –D) = 325 / 0.5 = 650V. Also the boost converter was designed with a switch at 90% Duty cycle(D).
Therefore the expected output voltage is Vo = VS / ( 1 –D) = 325 / 0.1 = 3.25kV.
Fig 2.1 Uncontrolled rectifier with Boost converter.
The investigations were carried out using ORCAD PSpice Version 16.0 for duty cycle of 50% for the
buck converter. From the waveform of input current, the harmonic components and THD were estimated. The
Influence of Switching Elements on Harmonics and Power Factor Improvement
21
phase angle between fundamental components of voltages and current was considered as the power factor angle.
Using the actual current waveform, the power losses were determined.
b. Results:
Initial investigations were carried out for duty cycle of 50% with and without any harmonic filter.
Subsequently, simulations were carried out with duty cycle as 90% as per the circuit in Fig 2.2.
Fig 2.2 Uncontrolled rectifier with Boost converter with series reactors
The results obtained are tabulated below. Table 2.1 shows the results obtained by considering a series
reactor. Losses were calculated as Pin - Po
Table 2.1. Boost converter with series reactor in series with the supply (DC = 50%)
Sl
No.
VDC
(V)
Lse
mH
pf Pin watt Po
watt
ITHD
in
%
Loss (w)
1 632 0 0.71 5500 3300 40.3 2200
2 632 0.1 0.71 5500 3400 40.1 2100
3 632 0.5 0.72 5800 3480 40.6 2320
4 632 1 0.74 6000 3600 39.1 2400
5 632 3 0.83 7500 4700 39 2800
6 632 5 0.91 8200 5000 38.9 3200
7 632 7 0.96 8200 4880 38.6 3320
Table 2.2 shows the results obtained by considering a 90% duty cycle. Losses were calculated as Pin - Po
Table 2.2. Boost converter with series reactor filter in series with the supply (DC = 90%)
Sl
no.
VDC (V) Lse
mH
pf Pin watt Po watt ITHD
in %
Loss (w)
1 3300 0 0.91 16150 6460 7.3 9690
2 3300 0.1 0.93 16150 6460 7.1 9690
3 3300 0.5 0.94 17423 6960 7.15 10440
4 3300 1 0.98 18000 7200 6.7 10800
5 3300 3 0.99 22500 9000 6.5 13500
6 3300 5 0.993 24300 9720 6 14580
7 3300 7 0.997 24670 9870 5.8 14800
c. Discussions:
Analysis of variation of power factor, THD and losses have been carried out using Boost converter.
The input voltage used is unregulated. We observe from the results of simulation that the THD is enormously
high (Nearly 40%) for 50% duty cycle operation of Boost converter. However, when duty cycle is increased is
90%, the values of THD are considerably lower. The variation in THD, losses and power factor are observed to
(Tables 2.1 and 2.2) have the same trend which is that with increase in power factor, the losses are increasing
and THD is decreasing.
Influence of Switching Elements on Harmonics and Power Factor Improvement
22
VII. POWER FACTOR IMPROVEMENT EFFECT ON A DYNAMIC LOAD
a. Load description:
The load selected for the investigation of power factor improvement effect on dynamic load is a 3-
phase Induction motor with name plate details as below:
NAME PLATE DETAILS:
POWER OUTPUT =2.2KW, 3HP, VOLTAGE=415V, CURRENT=4.8A, EFFICIENCY=79%
CONNECTION TYPE: DELTA, FULL LOAD PF = 0.7, N = 1440 RPM
b. Reactive KVAR requirement for APFC:
The FL output of the motor is 2700w and at 0.72pf. The desired power factor was fixed for the APFC case at
0.99.
We know that the kVAR required for improvement is given by:
kVAR = P ( tanΦ1 - tanΦ2 ) where P = active power of the load. Φ1 = initial power factor angle
Φ2 = required power factor angle
kVAR = 2.700 ( tan(cosˉ1
0.72) – tan (cosˉ1
0.99)) = 2.5 kVAR
The capacitor bank is to be connected in star.
Therefore, Vph = VL / √3 = 415 / √3 = 239.6V.
ICph = (kVAR * 1000) / ( 3* Vph) = 2500 / (3*239.6) = 3.47A
Thus, XCph = (Vph / ICph ) = 239.6 / 3.47 = 69Ω.
Therefore Cph = 1 / ( 2*π* 50 * 69) = 46µF.
It was decided to use the required rating using 4 stages of capacitors.
The experiment was conducted after the calibration of the APFC under 2 cases. Case 1 was performed without
the APFC connected to get the base data which are as tabulated in Table3.1. The in case 2 the APFC was
connected and the data were obtained as tabulated in table 3.2.
Table 3.1: Experimental data without connecting APFC
Sl.
No.
VL
(v)
I
(A)
W
(Watts)
Torque
(kg-m) BHP o/p(w) pf %η ITHD
Losses
(w)
1 408 2.25 170 0 0 0 0.11 0 11.06 170
2. 400 2.4 800 0.3584 0.7356 541.1 0.5 67.64 10.04 258.9
3. 400 2.9 1440 0.7616 1.5419 1134.22 0.742 78.76 7.82 305.78
4. 394 3.4 1810 0.9856 1.9789 1455.67 0.78 80.42 7.3 354.33
5 394 3.9 2280 1.1984 2.382 1752.2 0.856 76.85 6.2 527.8
Table 3.2 : Experimental data with APFC
Sl.
No
.
VL
(v)
I
(A)
W
(Watts)
Torqu
e (kg-
m)
BHP o/p(w) pf %η ITHD
Losses
(w)
1. 400 0.4 170 0 0 0 0.7 0 11.82 170
2. 400 1.266 745.65 0.358 0.735 540.6 0.85 72.5 10.49 205.05
3 400 1.97 1299 0.65 1.33 978.215 0.95 75.3 7.6 320.785
4 400 3.2 2215.8 1.2 2.377 1748.3 0.99 78.9 5.5 467.5
Influence of Switching Elements on Harmonics and Power Factor Improvement
23
The images of the APFC and its connection to the circuit is shown in Fig 3.1
3.1 APFC with circuit connection for pf correction of an Induction motor
c. Discussions:
Variation of power factor and its effect have been analysed with incorporation of dynamic loads. A 3-
phase IM was selected as dynamic load. A 3-phase Automatic Power Factor Controller (APFC) has been
designed and constructed for studying the on-load performance. Also, the APFC has been calibrated using
accurate reading meters (Voltmeter, Ammeters and Watt meters). The inaccuracy indications of APFC are
within ±2%.
The results of experimental investigations using above APFC set up show that the power factor can be
improved up to 0.99. It was also observed that the trend with respect to the behaviour of THD and losses with
variation of power factor is same with and without APFC. With increase in power factor THD is decreasing.
Also, losses are increasing with increase in power factor & load.
VIII CONCLUSION
An uncontrolled boost converter supplied from uncontrolled rectified supply was simulated with and
without power factor improving capacitors. The effect of improving the power factor on the THD was studied
and the filters were incorporated to reduce the level of THD. In the second phase an 3-phase APFC was
designed and implemented for a dynamic load, a 3-phase IM. The APFC was calibrated and designed with very
high precision components to ensure proper operation. The machine was experimentally analyzed with and
without the APFC.
The performance verification of the simulation and hardware implementation has shown that:-
1. In case of circuits involving power electronic switching the even harmonic components, in particular the 2nd
harmonic component, was predominant.
2. The use of appropriate filters with the circuit at output and input results in reduction of THD in input current.
3. Passive filters have limitations and are not sufficient to reduce the THD below the IEEE-519 standards.
Active filters may be used in that case.
4. Results of experimental investigation using APFC shows that the power factor can be improved up to 0.99.
5. Increase in power factor in general decreases the THD.
6. At constant load, with increase in power factor, the losses are reduced.
7. Increase in power factor increases the losses. This is mainly due to increase in load current.
8. The trend with respect to the behavior of THD and losses with variation of power factor is same with and
without APFC. However, the magnitude of THD is considerably reduced with increase in load.
ACKNOWLEDGMENT
The authors of the paper would like to acknowledge the Management of BNMIT for providing the
necessary research facilities.
REFERENCES
[1] Francis.M.Fernandez, P.S.Chandramohanan Nair, “Influence of power factor compensating capacitor
on estimation of harmonic distortion”, 9th
International conference on Electrical power quality and
utilization” Barcelona, 9-11 October 2007.
[2] IEEE standard 519-1992 Recommended Practices and Requirements for Harmonic control in Electric
Power systems 1993.
[3] Lorenzo Cividino, “Power factor, Harmonic Distortion; Causes, Effects and Consideration “, IEEE
1992 Page 506-514
[4] Alexander Emanuel, Minghao Yang, “On the harmonic compensation in nonsinusoidal systems”, IEEE
transactions on Power Delivery, vol 8., No.1,
Influence of Switching Elements on Harmonics and Power Factor Improvement
24
[5] Fatih Basçiftçi and Ömer Faruk Hatay, “Microcontroller-controlled reactive power measurement and
saving circuit design for residences and small scale enterprises”, Scientific research and essays Vol
5(16), pp 2312 – 2317, 18-Aug-2010.
[6] K.Chatterjee, B.G.Fernandes and Gopal.K.Dubey, “An Instantaneous Reactive VA Compensator and
Harmonic Suppressor System” IEEE Transactions on Power Electronics, Vol 14, No.2, 1999, pp 381-
392.
[7] Nicola Locci, Carlo Muscas, Sara Sulis, “On the measurement of power quality indexes for Harmonic
distortion in the presence of capacitors”, IMTC – 2005 – Instrumentation and Measurement
Technology Conference Ottawa, Canada, pp. Vol 3 1600-1605,May 2005.
[8] “Operational Amplifiers and Linear IC” by Ramanand Gaekwad, PHI
[9] “Linear Integrated Circuits” by Roy Choudary, New Age Publications
[10] Renesas Electronics America Inc “ User manual for YMCRPRX62T – Microcontroller”.
[11] “SPICE for circuits and Electronics”, Muhammed H.Rashid, PHI, 2002
[12] “Power Electronics, Converters, Application and Design”, Ned Mohan, Undeland, Robbins Wiley.

More Related Content

What's hot

Artificial neural network based unity power factor corrector for single phas...
Artificial neural network based unity power factor corrector  for single phas...Artificial neural network based unity power factor corrector  for single phas...
Artificial neural network based unity power factor corrector for single phas...IJECEIAES
 
A Comparative Analysis of Integrated Boost Flyback Converter using PID and Fu...
A Comparative Analysis of Integrated Boost Flyback Converter using PID and Fu...A Comparative Analysis of Integrated Boost Flyback Converter using PID and Fu...
A Comparative Analysis of Integrated Boost Flyback Converter using PID and Fu...IJPEDS-IAES
 
Power Quality Improvement of Grid Interconnection of renewable Energy Based D...
Power Quality Improvement of Grid Interconnection of renewable Energy Based D...Power Quality Improvement of Grid Interconnection of renewable Energy Based D...
Power Quality Improvement of Grid Interconnection of renewable Energy Based D...IJERA Editor
 
FC/PV Fed SAF with Fuzzy Logic Control for Power Quality Enhancement
FC/PV Fed SAF with Fuzzy Logic Control for Power Quality EnhancementFC/PV Fed SAF with Fuzzy Logic Control for Power Quality Enhancement
FC/PV Fed SAF with Fuzzy Logic Control for Power Quality EnhancementIJPEDS-IAES
 
International Journal of Engineering Research and Development
International Journal of Engineering Research and DevelopmentInternational Journal of Engineering Research and Development
International Journal of Engineering Research and DevelopmentIJERD Editor
 
Application of PI controller based active filter for harmonic mitigation of g...
Application of PI controller based active filter for harmonic mitigation of g...Application of PI controller based active filter for harmonic mitigation of g...
Application of PI controller based active filter for harmonic mitigation of g...journalBEEI
 
Hybrid energy storage system control analogous to power quality enhancement o...
Hybrid energy storage system control analogous to power quality enhancement o...Hybrid energy storage system control analogous to power quality enhancement o...
Hybrid energy storage system control analogous to power quality enhancement o...IJECEIAES
 
A New Approach to Powerflow Management in Transmission System Using Interline...
A New Approach to Powerflow Management in Transmission System Using Interline...A New Approach to Powerflow Management in Transmission System Using Interline...
A New Approach to Powerflow Management in Transmission System Using Interline...IJERA Editor
 
Harmonics Reduction and Power Factor Improvement of Switch Mode Power Supply ...
Harmonics Reduction and Power Factor Improvement of Switch Mode Power Supply ...Harmonics Reduction and Power Factor Improvement of Switch Mode Power Supply ...
Harmonics Reduction and Power Factor Improvement of Switch Mode Power Supply ...ijtsrd
 
Comparison of PI and ANN Control Techniques for Nine Switches UPQC to Improve...
Comparison of PI and ANN Control Techniques for Nine Switches UPQC to Improve...Comparison of PI and ANN Control Techniques for Nine Switches UPQC to Improve...
Comparison of PI and ANN Control Techniques for Nine Switches UPQC to Improve...MABUSUBANI SHAIK
 
Supply Power Factor Improvement in Ozone Generator System Using Active Power ...
Supply Power Factor Improvement in Ozone Generator System Using Active Power ...Supply Power Factor Improvement in Ozone Generator System Using Active Power ...
Supply Power Factor Improvement in Ozone Generator System Using Active Power ...IJPEDS-IAES
 
IJERD (www.ijerd.com) International Journal of Engineering Research and Devel...
IJERD (www.ijerd.com) International Journal of Engineering Research and Devel...IJERD (www.ijerd.com) International Journal of Engineering Research and Devel...
IJERD (www.ijerd.com) International Journal of Engineering Research and Devel...IJERD Editor
 
E021203026035
E021203026035E021203026035
E021203026035theijes
 
A CONTROL APPROACH FOR GRID INTERFACING INVERTER IN 3 PHASE 4 WIRE DISTRIBUT...
A CONTROL APPROACH FOR GRID INTERFACING  INVERTER IN 3 PHASE 4 WIRE DISTRIBUT...A CONTROL APPROACH FOR GRID INTERFACING  INVERTER IN 3 PHASE 4 WIRE DISTRIBUT...
A CONTROL APPROACH FOR GRID INTERFACING INVERTER IN 3 PHASE 4 WIRE DISTRIBUT...IJMER
 
IRJET- Power Quality Improvement using Active Power Filter
IRJET- Power Quality Improvement using Active Power FilterIRJET- Power Quality Improvement using Active Power Filter
IRJET- Power Quality Improvement using Active Power FilterIRJET Journal
 
IRJET - The Power Quality Improvement with Harmonic Reduction and Stabilizing...
IRJET - The Power Quality Improvement with Harmonic Reduction and Stabilizing...IRJET - The Power Quality Improvement with Harmonic Reduction and Stabilizing...
IRJET - The Power Quality Improvement with Harmonic Reduction and Stabilizing...IRJET Journal
 

What's hot (20)

Artificial neural network based unity power factor corrector for single phas...
Artificial neural network based unity power factor corrector  for single phas...Artificial neural network based unity power factor corrector  for single phas...
Artificial neural network based unity power factor corrector for single phas...
 
A Comparative Analysis of Integrated Boost Flyback Converter using PID and Fu...
A Comparative Analysis of Integrated Boost Flyback Converter using PID and Fu...A Comparative Analysis of Integrated Boost Flyback Converter using PID and Fu...
A Comparative Analysis of Integrated Boost Flyback Converter using PID and Fu...
 
Power Quality Improvement of Grid Interconnection of renewable Energy Based D...
Power Quality Improvement of Grid Interconnection of renewable Energy Based D...Power Quality Improvement of Grid Interconnection of renewable Energy Based D...
Power Quality Improvement of Grid Interconnection of renewable Energy Based D...
 
FC/PV Fed SAF with Fuzzy Logic Control for Power Quality Enhancement
FC/PV Fed SAF with Fuzzy Logic Control for Power Quality EnhancementFC/PV Fed SAF with Fuzzy Logic Control for Power Quality Enhancement
FC/PV Fed SAF with Fuzzy Logic Control for Power Quality Enhancement
 
A review on different control techniques using DSTATCOM for distribution syst...
A review on different control techniques using DSTATCOM for distribution syst...A review on different control techniques using DSTATCOM for distribution syst...
A review on different control techniques using DSTATCOM for distribution syst...
 
International Journal of Engineering Research and Development
International Journal of Engineering Research and DevelopmentInternational Journal of Engineering Research and Development
International Journal of Engineering Research and Development
 
Application of PI controller based active filter for harmonic mitigation of g...
Application of PI controller based active filter for harmonic mitigation of g...Application of PI controller based active filter for harmonic mitigation of g...
Application of PI controller based active filter for harmonic mitigation of g...
 
Hybrid energy storage system control analogous to power quality enhancement o...
Hybrid energy storage system control analogous to power quality enhancement o...Hybrid energy storage system control analogous to power quality enhancement o...
Hybrid energy storage system control analogous to power quality enhancement o...
 
A New Approach to Powerflow Management in Transmission System Using Interline...
A New Approach to Powerflow Management in Transmission System Using Interline...A New Approach to Powerflow Management in Transmission System Using Interline...
A New Approach to Powerflow Management in Transmission System Using Interline...
 
Harmonics Reduction and Power Factor Improvement of Switch Mode Power Supply ...
Harmonics Reduction and Power Factor Improvement of Switch Mode Power Supply ...Harmonics Reduction and Power Factor Improvement of Switch Mode Power Supply ...
Harmonics Reduction and Power Factor Improvement of Switch Mode Power Supply ...
 
Comparison of PI and ANN Control Techniques for Nine Switches UPQC to Improve...
Comparison of PI and ANN Control Techniques for Nine Switches UPQC to Improve...Comparison of PI and ANN Control Techniques for Nine Switches UPQC to Improve...
Comparison of PI and ANN Control Techniques for Nine Switches UPQC to Improve...
 
Supply Power Factor Improvement in Ozone Generator System Using Active Power ...
Supply Power Factor Improvement in Ozone Generator System Using Active Power ...Supply Power Factor Improvement in Ozone Generator System Using Active Power ...
Supply Power Factor Improvement in Ozone Generator System Using Active Power ...
 
IJERD (www.ijerd.com) International Journal of Engineering Research and Devel...
IJERD (www.ijerd.com) International Journal of Engineering Research and Devel...IJERD (www.ijerd.com) International Journal of Engineering Research and Devel...
IJERD (www.ijerd.com) International Journal of Engineering Research and Devel...
 
E021203026035
E021203026035E021203026035
E021203026035
 
A CONTROL APPROACH FOR GRID INTERFACING INVERTER IN 3 PHASE 4 WIRE DISTRIBUT...
A CONTROL APPROACH FOR GRID INTERFACING  INVERTER IN 3 PHASE 4 WIRE DISTRIBUT...A CONTROL APPROACH FOR GRID INTERFACING  INVERTER IN 3 PHASE 4 WIRE DISTRIBUT...
A CONTROL APPROACH FOR GRID INTERFACING INVERTER IN 3 PHASE 4 WIRE DISTRIBUT...
 
Analysis of High Voltage High Power Resonant Converters
Analysis of High Voltage High Power Resonant ConvertersAnalysis of High Voltage High Power Resonant Converters
Analysis of High Voltage High Power Resonant Converters
 
IRJET- Power Quality Improvement using Active Power Filter
IRJET- Power Quality Improvement using Active Power FilterIRJET- Power Quality Improvement using Active Power Filter
IRJET- Power Quality Improvement using Active Power Filter
 
Unified power quality conditioner supplied by fuel cell system via SEPIC conv...
Unified power quality conditioner supplied by fuel cell system via SEPIC conv...Unified power quality conditioner supplied by fuel cell system via SEPIC conv...
Unified power quality conditioner supplied by fuel cell system via SEPIC conv...
 
IRJET - The Power Quality Improvement with Harmonic Reduction and Stabilizing...
IRJET - The Power Quality Improvement with Harmonic Reduction and Stabilizing...IRJET - The Power Quality Improvement with Harmonic Reduction and Stabilizing...
IRJET - The Power Quality Improvement with Harmonic Reduction and Stabilizing...
 
Big Presentation
Big PresentationBig Presentation
Big Presentation
 

Similar to IJERD explores switching elements' impact on harmonics and power factors

MINOR PROJECT gb 08 (3).pdf
MINOR PROJECT gb 08 (3).pdfMINOR PROJECT gb 08 (3).pdf
MINOR PROJECT gb 08 (3).pdfDrSabhyataSoni
 
Power factor correction using bridgeless boost topology
Power factor correction using bridgeless boost topologyPower factor correction using bridgeless boost topology
Power factor correction using bridgeless boost topologyDHEERAJ DHAKAR
 
International Journal of Engineering and Science Invention (IJESI)
International Journal of Engineering and Science Invention (IJESI)International Journal of Engineering and Science Invention (IJESI)
International Journal of Engineering and Science Invention (IJESI)inventionjournals
 
Interleaved Boost Converter Fed with PV for Induction Motor/Agricultural Appl...
Interleaved Boost Converter Fed with PV for Induction Motor/Agricultural Appl...Interleaved Boost Converter Fed with PV for Induction Motor/Agricultural Appl...
Interleaved Boost Converter Fed with PV for Induction Motor/Agricultural Appl...IAES-IJPEDS
 
IRJET- Automated Energy Monitering System and Power Factor Improvement
IRJET-  	  Automated Energy Monitering System and Power Factor ImprovementIRJET-  	  Automated Energy Monitering System and Power Factor Improvement
IRJET- Automated Energy Monitering System and Power Factor ImprovementIRJET Journal
 
Fuzzy based control of Transformer less Coupled inductor based DC-DC converter
Fuzzy based control of Transformer less Coupled inductor based DC-DC converterFuzzy based control of Transformer less Coupled inductor based DC-DC converter
Fuzzy based control of Transformer less Coupled inductor based DC-DC converterIJERA Editor
 
Comparative of Conventional and Intelligence Controller based Hybrid Generati...
Comparative of Conventional and Intelligence Controller based Hybrid Generati...Comparative of Conventional and Intelligence Controller based Hybrid Generati...
Comparative of Conventional and Intelligence Controller based Hybrid Generati...IJERD Editor
 
Harmonic enhancement in microgrid with applications on sensitive loads
Harmonic enhancement in microgrid with applications on sensitive loadsHarmonic enhancement in microgrid with applications on sensitive loads
Harmonic enhancement in microgrid with applications on sensitive loadsIJECEIAES
 
PF correction using SEPIC
PF correction using SEPICPF correction using SEPIC
PF correction using SEPICSoumya Dash
 
IRJET- A Systematic Approach to Design Single Phase Transformer Less Inve...
IRJET-  	  A Systematic Approach to Design Single Phase Transformer Less Inve...IRJET-  	  A Systematic Approach to Design Single Phase Transformer Less Inve...
IRJET- A Systematic Approach to Design Single Phase Transformer Less Inve...IRJET Journal
 
Design and Simulation of PFC Circuit for AC/DC Converter Based on PWM Boost R...
Design and Simulation of PFC Circuit for AC/DC Converter Based on PWM Boost R...Design and Simulation of PFC Circuit for AC/DC Converter Based on PWM Boost R...
Design and Simulation of PFC Circuit for AC/DC Converter Based on PWM Boost R...IOSR Journals
 
Micro-controller based Automatic Power Factor Correction System Report
Micro-controller based Automatic Power Factor Correction System ReportMicro-controller based Automatic Power Factor Correction System Report
Micro-controller based Automatic Power Factor Correction System ReportTheory to Practical
 
Guiding Principles in Selecting AC To DC Converters For Power Factor Correcti...
Guiding Principles in Selecting AC To DC Converters For Power Factor Correcti...Guiding Principles in Selecting AC To DC Converters For Power Factor Correcti...
Guiding Principles in Selecting AC To DC Converters For Power Factor Correcti...IJERA Editor
 
automatic power factor correction report
automatic power factor correction reportautomatic power factor correction report
automatic power factor correction reportamaljo joju e
 

Similar to IJERD explores switching elements' impact on harmonics and power factors (20)

MINOR PROJECT gb 08 (3).pdf
MINOR PROJECT gb 08 (3).pdfMINOR PROJECT gb 08 (3).pdf
MINOR PROJECT gb 08 (3).pdf
 
47 51
47 5147 51
47 51
 
Power factor correction using bridgeless boost topology
Power factor correction using bridgeless boost topologyPower factor correction using bridgeless boost topology
Power factor correction using bridgeless boost topology
 
International Journal of Engineering and Science Invention (IJESI)
International Journal of Engineering and Science Invention (IJESI)International Journal of Engineering and Science Invention (IJESI)
International Journal of Engineering and Science Invention (IJESI)
 
Q44089196
Q44089196Q44089196
Q44089196
 
Om2423682376
Om2423682376Om2423682376
Om2423682376
 
Interleaved Boost Converter Fed with PV for Induction Motor/Agricultural Appl...
Interleaved Boost Converter Fed with PV for Induction Motor/Agricultural Appl...Interleaved Boost Converter Fed with PV for Induction Motor/Agricultural Appl...
Interleaved Boost Converter Fed with PV for Induction Motor/Agricultural Appl...
 
IRJET- Automated Energy Monitering System and Power Factor Improvement
IRJET-  	  Automated Energy Monitering System and Power Factor ImprovementIRJET-  	  Automated Energy Monitering System and Power Factor Improvement
IRJET- Automated Energy Monitering System and Power Factor Improvement
 
Investigation of Power Quality Improvement in Super Lift Luo Converter
Investigation of Power Quality Improvement in Super Lift Luo ConverterInvestigation of Power Quality Improvement in Super Lift Luo Converter
Investigation of Power Quality Improvement in Super Lift Luo Converter
 
Fuzzy based control of Transformer less Coupled inductor based DC-DC converter
Fuzzy based control of Transformer less Coupled inductor based DC-DC converterFuzzy based control of Transformer less Coupled inductor based DC-DC converter
Fuzzy based control of Transformer less Coupled inductor based DC-DC converter
 
Apfc project 2016 17
Apfc project 2016 17Apfc project 2016 17
Apfc project 2016 17
 
Comparative of Conventional and Intelligence Controller based Hybrid Generati...
Comparative of Conventional and Intelligence Controller based Hybrid Generati...Comparative of Conventional and Intelligence Controller based Hybrid Generati...
Comparative of Conventional and Intelligence Controller based Hybrid Generati...
 
Harmonic enhancement in microgrid with applications on sensitive loads
Harmonic enhancement in microgrid with applications on sensitive loadsHarmonic enhancement in microgrid with applications on sensitive loads
Harmonic enhancement in microgrid with applications on sensitive loads
 
PF correction using SEPIC
PF correction using SEPICPF correction using SEPIC
PF correction using SEPIC
 
Power factor
Power factorPower factor
Power factor
 
IRJET- A Systematic Approach to Design Single Phase Transformer Less Inve...
IRJET-  	  A Systematic Approach to Design Single Phase Transformer Less Inve...IRJET-  	  A Systematic Approach to Design Single Phase Transformer Less Inve...
IRJET- A Systematic Approach to Design Single Phase Transformer Less Inve...
 
Design and Simulation of PFC Circuit for AC/DC Converter Based on PWM Boost R...
Design and Simulation of PFC Circuit for AC/DC Converter Based on PWM Boost R...Design and Simulation of PFC Circuit for AC/DC Converter Based on PWM Boost R...
Design and Simulation of PFC Circuit for AC/DC Converter Based on PWM Boost R...
 
Micro-controller based Automatic Power Factor Correction System Report
Micro-controller based Automatic Power Factor Correction System ReportMicro-controller based Automatic Power Factor Correction System Report
Micro-controller based Automatic Power Factor Correction System Report
 
Guiding Principles in Selecting AC To DC Converters For Power Factor Correcti...
Guiding Principles in Selecting AC To DC Converters For Power Factor Correcti...Guiding Principles in Selecting AC To DC Converters For Power Factor Correcti...
Guiding Principles in Selecting AC To DC Converters For Power Factor Correcti...
 
automatic power factor correction report
automatic power factor correction reportautomatic power factor correction report
automatic power factor correction report
 

More from IJERD Editor

A Novel Method for Prevention of Bandwidth Distributed Denial of Service Attacks
A Novel Method for Prevention of Bandwidth Distributed Denial of Service AttacksA Novel Method for Prevention of Bandwidth Distributed Denial of Service Attacks
A Novel Method for Prevention of Bandwidth Distributed Denial of Service AttacksIJERD Editor
 
MEMS MICROPHONE INTERFACE
MEMS MICROPHONE INTERFACEMEMS MICROPHONE INTERFACE
MEMS MICROPHONE INTERFACEIJERD Editor
 
Influence of tensile behaviour of slab on the structural Behaviour of shear c...
Influence of tensile behaviour of slab on the structural Behaviour of shear c...Influence of tensile behaviour of slab on the structural Behaviour of shear c...
Influence of tensile behaviour of slab on the structural Behaviour of shear c...IJERD Editor
 
Gold prospecting using Remote Sensing ‘A case study of Sudan’
Gold prospecting using Remote Sensing ‘A case study of Sudan’Gold prospecting using Remote Sensing ‘A case study of Sudan’
Gold prospecting using Remote Sensing ‘A case study of Sudan’IJERD Editor
 
Reducing Corrosion Rate by Welding Design
Reducing Corrosion Rate by Welding DesignReducing Corrosion Rate by Welding Design
Reducing Corrosion Rate by Welding DesignIJERD Editor
 
Router 1X3 – RTL Design and Verification
Router 1X3 – RTL Design and VerificationRouter 1X3 – RTL Design and Verification
Router 1X3 – RTL Design and VerificationIJERD Editor
 
Active Power Exchange in Distributed Power-Flow Controller (DPFC) At Third Ha...
Active Power Exchange in Distributed Power-Flow Controller (DPFC) At Third Ha...Active Power Exchange in Distributed Power-Flow Controller (DPFC) At Third Ha...
Active Power Exchange in Distributed Power-Flow Controller (DPFC) At Third Ha...IJERD Editor
 
Mitigation of Voltage Sag/Swell with Fuzzy Control Reduced Rating DVR
Mitigation of Voltage Sag/Swell with Fuzzy Control Reduced Rating DVRMitigation of Voltage Sag/Swell with Fuzzy Control Reduced Rating DVR
Mitigation of Voltage Sag/Swell with Fuzzy Control Reduced Rating DVRIJERD Editor
 
Study on the Fused Deposition Modelling In Additive Manufacturing
Study on the Fused Deposition Modelling In Additive ManufacturingStudy on the Fused Deposition Modelling In Additive Manufacturing
Study on the Fused Deposition Modelling In Additive ManufacturingIJERD Editor
 
Spyware triggering system by particular string value
Spyware triggering system by particular string valueSpyware triggering system by particular string value
Spyware triggering system by particular string valueIJERD Editor
 
A Blind Steganalysis on JPEG Gray Level Image Based on Statistical Features a...
A Blind Steganalysis on JPEG Gray Level Image Based on Statistical Features a...A Blind Steganalysis on JPEG Gray Level Image Based on Statistical Features a...
A Blind Steganalysis on JPEG Gray Level Image Based on Statistical Features a...IJERD Editor
 
Secure Image Transmission for Cloud Storage System Using Hybrid Scheme
Secure Image Transmission for Cloud Storage System Using Hybrid SchemeSecure Image Transmission for Cloud Storage System Using Hybrid Scheme
Secure Image Transmission for Cloud Storage System Using Hybrid SchemeIJERD Editor
 
Application of Buckley-Leverett Equation in Modeling the Radius of Invasion i...
Application of Buckley-Leverett Equation in Modeling the Radius of Invasion i...Application of Buckley-Leverett Equation in Modeling the Radius of Invasion i...
Application of Buckley-Leverett Equation in Modeling the Radius of Invasion i...IJERD Editor
 
Gesture Gaming on the World Wide Web Using an Ordinary Web Camera
Gesture Gaming on the World Wide Web Using an Ordinary Web CameraGesture Gaming on the World Wide Web Using an Ordinary Web Camera
Gesture Gaming on the World Wide Web Using an Ordinary Web CameraIJERD Editor
 
Hardware Analysis of Resonant Frequency Converter Using Isolated Circuits And...
Hardware Analysis of Resonant Frequency Converter Using Isolated Circuits And...Hardware Analysis of Resonant Frequency Converter Using Isolated Circuits And...
Hardware Analysis of Resonant Frequency Converter Using Isolated Circuits And...IJERD Editor
 
Simulated Analysis of Resonant Frequency Converter Using Different Tank Circu...
Simulated Analysis of Resonant Frequency Converter Using Different Tank Circu...Simulated Analysis of Resonant Frequency Converter Using Different Tank Circu...
Simulated Analysis of Resonant Frequency Converter Using Different Tank Circu...IJERD Editor
 
Moon-bounce: A Boon for VHF Dxing
Moon-bounce: A Boon for VHF DxingMoon-bounce: A Boon for VHF Dxing
Moon-bounce: A Boon for VHF DxingIJERD Editor
 
“MS-Extractor: An Innovative Approach to Extract Microsatellites on „Y‟ Chrom...
“MS-Extractor: An Innovative Approach to Extract Microsatellites on „Y‟ Chrom...“MS-Extractor: An Innovative Approach to Extract Microsatellites on „Y‟ Chrom...
“MS-Extractor: An Innovative Approach to Extract Microsatellites on „Y‟ Chrom...IJERD Editor
 
Importance of Measurements in Smart Grid
Importance of Measurements in Smart GridImportance of Measurements in Smart Grid
Importance of Measurements in Smart GridIJERD Editor
 
Study of Macro level Properties of SCC using GGBS and Lime stone powder
Study of Macro level Properties of SCC using GGBS and Lime stone powderStudy of Macro level Properties of SCC using GGBS and Lime stone powder
Study of Macro level Properties of SCC using GGBS and Lime stone powderIJERD Editor
 

More from IJERD Editor (20)

A Novel Method for Prevention of Bandwidth Distributed Denial of Service Attacks
A Novel Method for Prevention of Bandwidth Distributed Denial of Service AttacksA Novel Method for Prevention of Bandwidth Distributed Denial of Service Attacks
A Novel Method for Prevention of Bandwidth Distributed Denial of Service Attacks
 
MEMS MICROPHONE INTERFACE
MEMS MICROPHONE INTERFACEMEMS MICROPHONE INTERFACE
MEMS MICROPHONE INTERFACE
 
Influence of tensile behaviour of slab on the structural Behaviour of shear c...
Influence of tensile behaviour of slab on the structural Behaviour of shear c...Influence of tensile behaviour of slab on the structural Behaviour of shear c...
Influence of tensile behaviour of slab on the structural Behaviour of shear c...
 
Gold prospecting using Remote Sensing ‘A case study of Sudan’
Gold prospecting using Remote Sensing ‘A case study of Sudan’Gold prospecting using Remote Sensing ‘A case study of Sudan’
Gold prospecting using Remote Sensing ‘A case study of Sudan’
 
Reducing Corrosion Rate by Welding Design
Reducing Corrosion Rate by Welding DesignReducing Corrosion Rate by Welding Design
Reducing Corrosion Rate by Welding Design
 
Router 1X3 – RTL Design and Verification
Router 1X3 – RTL Design and VerificationRouter 1X3 – RTL Design and Verification
Router 1X3 – RTL Design and Verification
 
Active Power Exchange in Distributed Power-Flow Controller (DPFC) At Third Ha...
Active Power Exchange in Distributed Power-Flow Controller (DPFC) At Third Ha...Active Power Exchange in Distributed Power-Flow Controller (DPFC) At Third Ha...
Active Power Exchange in Distributed Power-Flow Controller (DPFC) At Third Ha...
 
Mitigation of Voltage Sag/Swell with Fuzzy Control Reduced Rating DVR
Mitigation of Voltage Sag/Swell with Fuzzy Control Reduced Rating DVRMitigation of Voltage Sag/Swell with Fuzzy Control Reduced Rating DVR
Mitigation of Voltage Sag/Swell with Fuzzy Control Reduced Rating DVR
 
Study on the Fused Deposition Modelling In Additive Manufacturing
Study on the Fused Deposition Modelling In Additive ManufacturingStudy on the Fused Deposition Modelling In Additive Manufacturing
Study on the Fused Deposition Modelling In Additive Manufacturing
 
Spyware triggering system by particular string value
Spyware triggering system by particular string valueSpyware triggering system by particular string value
Spyware triggering system by particular string value
 
A Blind Steganalysis on JPEG Gray Level Image Based on Statistical Features a...
A Blind Steganalysis on JPEG Gray Level Image Based on Statistical Features a...A Blind Steganalysis on JPEG Gray Level Image Based on Statistical Features a...
A Blind Steganalysis on JPEG Gray Level Image Based on Statistical Features a...
 
Secure Image Transmission for Cloud Storage System Using Hybrid Scheme
Secure Image Transmission for Cloud Storage System Using Hybrid SchemeSecure Image Transmission for Cloud Storage System Using Hybrid Scheme
Secure Image Transmission for Cloud Storage System Using Hybrid Scheme
 
Application of Buckley-Leverett Equation in Modeling the Radius of Invasion i...
Application of Buckley-Leverett Equation in Modeling the Radius of Invasion i...Application of Buckley-Leverett Equation in Modeling the Radius of Invasion i...
Application of Buckley-Leverett Equation in Modeling the Radius of Invasion i...
 
Gesture Gaming on the World Wide Web Using an Ordinary Web Camera
Gesture Gaming on the World Wide Web Using an Ordinary Web CameraGesture Gaming on the World Wide Web Using an Ordinary Web Camera
Gesture Gaming on the World Wide Web Using an Ordinary Web Camera
 
Hardware Analysis of Resonant Frequency Converter Using Isolated Circuits And...
Hardware Analysis of Resonant Frequency Converter Using Isolated Circuits And...Hardware Analysis of Resonant Frequency Converter Using Isolated Circuits And...
Hardware Analysis of Resonant Frequency Converter Using Isolated Circuits And...
 
Simulated Analysis of Resonant Frequency Converter Using Different Tank Circu...
Simulated Analysis of Resonant Frequency Converter Using Different Tank Circu...Simulated Analysis of Resonant Frequency Converter Using Different Tank Circu...
Simulated Analysis of Resonant Frequency Converter Using Different Tank Circu...
 
Moon-bounce: A Boon for VHF Dxing
Moon-bounce: A Boon for VHF DxingMoon-bounce: A Boon for VHF Dxing
Moon-bounce: A Boon for VHF Dxing
 
“MS-Extractor: An Innovative Approach to Extract Microsatellites on „Y‟ Chrom...
“MS-Extractor: An Innovative Approach to Extract Microsatellites on „Y‟ Chrom...“MS-Extractor: An Innovative Approach to Extract Microsatellites on „Y‟ Chrom...
“MS-Extractor: An Innovative Approach to Extract Microsatellites on „Y‟ Chrom...
 
Importance of Measurements in Smart Grid
Importance of Measurements in Smart GridImportance of Measurements in Smart Grid
Importance of Measurements in Smart Grid
 
Study of Macro level Properties of SCC using GGBS and Lime stone powder
Study of Macro level Properties of SCC using GGBS and Lime stone powderStudy of Macro level Properties of SCC using GGBS and Lime stone powder
Study of Macro level Properties of SCC using GGBS and Lime stone powder
 

Recently uploaded

The CMO Survey - Highlights and Insights Report - Spring 2024
The CMO Survey - Highlights and Insights Report - Spring 2024The CMO Survey - Highlights and Insights Report - Spring 2024
The CMO Survey - Highlights and Insights Report - Spring 2024christinemoorman
 
Creating Low-Code Loan Applications using the Trisotech Mortgage Feature Set
Creating Low-Code Loan Applications using the Trisotech Mortgage Feature SetCreating Low-Code Loan Applications using the Trisotech Mortgage Feature Set
Creating Low-Code Loan Applications using the Trisotech Mortgage Feature SetDenis Gagné
 
The Coffee Bean & Tea Leaf(CBTL), Business strategy case study
The Coffee Bean & Tea Leaf(CBTL), Business strategy case studyThe Coffee Bean & Tea Leaf(CBTL), Business strategy case study
The Coffee Bean & Tea Leaf(CBTL), Business strategy case studyEthan lee
 
Eni 2024 1Q Results - 24.04.24 business.
Eni 2024 1Q Results - 24.04.24 business.Eni 2024 1Q Results - 24.04.24 business.
Eni 2024 1Q Results - 24.04.24 business.Eni
 
Enhancing and Restoring Safety & Quality Cultures - Dave Litwiller - May 2024...
Enhancing and Restoring Safety & Quality Cultures - Dave Litwiller - May 2024...Enhancing and Restoring Safety & Quality Cultures - Dave Litwiller - May 2024...
Enhancing and Restoring Safety & Quality Cultures - Dave Litwiller - May 2024...Dave Litwiller
 
Call Girls in Gomti Nagar - 7388211116 - With room Service
Call Girls in Gomti Nagar - 7388211116  - With room ServiceCall Girls in Gomti Nagar - 7388211116  - With room Service
Call Girls in Gomti Nagar - 7388211116 - With room Servicediscovermytutordmt
 
Call Girls Navi Mumbai Just Call 9907093804 Top Class Call Girl Service Avail...
Call Girls Navi Mumbai Just Call 9907093804 Top Class Call Girl Service Avail...Call Girls Navi Mumbai Just Call 9907093804 Top Class Call Girl Service Avail...
Call Girls Navi Mumbai Just Call 9907093804 Top Class Call Girl Service Avail...Dipal Arora
 
VIP Call Girls In Saharaganj ( Lucknow ) 🔝 8923113531 🔝 Cash Payment (COD) 👒
VIP Call Girls In Saharaganj ( Lucknow  ) 🔝 8923113531 🔝  Cash Payment (COD) 👒VIP Call Girls In Saharaganj ( Lucknow  ) 🔝 8923113531 🔝  Cash Payment (COD) 👒
VIP Call Girls In Saharaganj ( Lucknow ) 🔝 8923113531 🔝 Cash Payment (COD) 👒anilsa9823
 
Russian Faridabad Call Girls(Badarpur) : ☎ 8168257667, @4999
Russian Faridabad Call Girls(Badarpur) : ☎ 8168257667, @4999Russian Faridabad Call Girls(Badarpur) : ☎ 8168257667, @4999
Russian Faridabad Call Girls(Badarpur) : ☎ 8168257667, @4999Tina Ji
 
It will be International Nurses' Day on 12 May
It will be International Nurses' Day on 12 MayIt will be International Nurses' Day on 12 May
It will be International Nurses' Day on 12 MayNZSG
 
Cash Payment 9602870969 Escort Service in Udaipur Call Girls
Cash Payment 9602870969 Escort Service in Udaipur Call GirlsCash Payment 9602870969 Escort Service in Udaipur Call Girls
Cash Payment 9602870969 Escort Service in Udaipur Call GirlsApsara Of India
 
Progress Report - Oracle Database Analyst Summit
Progress  Report - Oracle Database Analyst SummitProgress  Report - Oracle Database Analyst Summit
Progress Report - Oracle Database Analyst SummitHolger Mueller
 
BEST ✨ Call Girls In Indirapuram Ghaziabad ✔️ 9871031762 ✔️ Escorts Service...
BEST ✨ Call Girls In  Indirapuram Ghaziabad  ✔️ 9871031762 ✔️ Escorts Service...BEST ✨ Call Girls In  Indirapuram Ghaziabad  ✔️ 9871031762 ✔️ Escorts Service...
BEST ✨ Call Girls In Indirapuram Ghaziabad ✔️ 9871031762 ✔️ Escorts Service...noida100girls
 
Regression analysis: Simple Linear Regression Multiple Linear Regression
Regression analysis:  Simple Linear Regression Multiple Linear RegressionRegression analysis:  Simple Linear Regression Multiple Linear Regression
Regression analysis: Simple Linear Regression Multiple Linear RegressionRavindra Nath Shukla
 
Ensure the security of your HCL environment by applying the Zero Trust princi...
Ensure the security of your HCL environment by applying the Zero Trust princi...Ensure the security of your HCL environment by applying the Zero Trust princi...
Ensure the security of your HCL environment by applying the Zero Trust princi...Roland Driesen
 
Call Girls In DLf Gurgaon ➥99902@11544 ( Best price)100% Genuine Escort In 24...
Call Girls In DLf Gurgaon ➥99902@11544 ( Best price)100% Genuine Escort In 24...Call Girls In DLf Gurgaon ➥99902@11544 ( Best price)100% Genuine Escort In 24...
Call Girls In DLf Gurgaon ➥99902@11544 ( Best price)100% Genuine Escort In 24...lizamodels9
 
GD Birla and his contribution in management
GD Birla and his contribution in managementGD Birla and his contribution in management
GD Birla and his contribution in managementchhavia330
 
Pharma Works Profile of Karan Communications
Pharma Works Profile of Karan CommunicationsPharma Works Profile of Karan Communications
Pharma Works Profile of Karan Communicationskarancommunications
 
Lucknow 💋 Escorts in Lucknow - 450+ Call Girl Cash Payment 8923113531 Neha Th...
Lucknow 💋 Escorts in Lucknow - 450+ Call Girl Cash Payment 8923113531 Neha Th...Lucknow 💋 Escorts in Lucknow - 450+ Call Girl Cash Payment 8923113531 Neha Th...
Lucknow 💋 Escorts in Lucknow - 450+ Call Girl Cash Payment 8923113531 Neha Th...anilsa9823
 
Call Girls Pune Just Call 9907093804 Top Class Call Girl Service Available
Call Girls Pune Just Call 9907093804 Top Class Call Girl Service AvailableCall Girls Pune Just Call 9907093804 Top Class Call Girl Service Available
Call Girls Pune Just Call 9907093804 Top Class Call Girl Service AvailableDipal Arora
 

Recently uploaded (20)

The CMO Survey - Highlights and Insights Report - Spring 2024
The CMO Survey - Highlights and Insights Report - Spring 2024The CMO Survey - Highlights and Insights Report - Spring 2024
The CMO Survey - Highlights and Insights Report - Spring 2024
 
Creating Low-Code Loan Applications using the Trisotech Mortgage Feature Set
Creating Low-Code Loan Applications using the Trisotech Mortgage Feature SetCreating Low-Code Loan Applications using the Trisotech Mortgage Feature Set
Creating Low-Code Loan Applications using the Trisotech Mortgage Feature Set
 
The Coffee Bean & Tea Leaf(CBTL), Business strategy case study
The Coffee Bean & Tea Leaf(CBTL), Business strategy case studyThe Coffee Bean & Tea Leaf(CBTL), Business strategy case study
The Coffee Bean & Tea Leaf(CBTL), Business strategy case study
 
Eni 2024 1Q Results - 24.04.24 business.
Eni 2024 1Q Results - 24.04.24 business.Eni 2024 1Q Results - 24.04.24 business.
Eni 2024 1Q Results - 24.04.24 business.
 
Enhancing and Restoring Safety & Quality Cultures - Dave Litwiller - May 2024...
Enhancing and Restoring Safety & Quality Cultures - Dave Litwiller - May 2024...Enhancing and Restoring Safety & Quality Cultures - Dave Litwiller - May 2024...
Enhancing and Restoring Safety & Quality Cultures - Dave Litwiller - May 2024...
 
Call Girls in Gomti Nagar - 7388211116 - With room Service
Call Girls in Gomti Nagar - 7388211116  - With room ServiceCall Girls in Gomti Nagar - 7388211116  - With room Service
Call Girls in Gomti Nagar - 7388211116 - With room Service
 
Call Girls Navi Mumbai Just Call 9907093804 Top Class Call Girl Service Avail...
Call Girls Navi Mumbai Just Call 9907093804 Top Class Call Girl Service Avail...Call Girls Navi Mumbai Just Call 9907093804 Top Class Call Girl Service Avail...
Call Girls Navi Mumbai Just Call 9907093804 Top Class Call Girl Service Avail...
 
VIP Call Girls In Saharaganj ( Lucknow ) 🔝 8923113531 🔝 Cash Payment (COD) 👒
VIP Call Girls In Saharaganj ( Lucknow  ) 🔝 8923113531 🔝  Cash Payment (COD) 👒VIP Call Girls In Saharaganj ( Lucknow  ) 🔝 8923113531 🔝  Cash Payment (COD) 👒
VIP Call Girls In Saharaganj ( Lucknow ) 🔝 8923113531 🔝 Cash Payment (COD) 👒
 
Russian Faridabad Call Girls(Badarpur) : ☎ 8168257667, @4999
Russian Faridabad Call Girls(Badarpur) : ☎ 8168257667, @4999Russian Faridabad Call Girls(Badarpur) : ☎ 8168257667, @4999
Russian Faridabad Call Girls(Badarpur) : ☎ 8168257667, @4999
 
It will be International Nurses' Day on 12 May
It will be International Nurses' Day on 12 MayIt will be International Nurses' Day on 12 May
It will be International Nurses' Day on 12 May
 
Cash Payment 9602870969 Escort Service in Udaipur Call Girls
Cash Payment 9602870969 Escort Service in Udaipur Call GirlsCash Payment 9602870969 Escort Service in Udaipur Call Girls
Cash Payment 9602870969 Escort Service in Udaipur Call Girls
 
Progress Report - Oracle Database Analyst Summit
Progress  Report - Oracle Database Analyst SummitProgress  Report - Oracle Database Analyst Summit
Progress Report - Oracle Database Analyst Summit
 
BEST ✨ Call Girls In Indirapuram Ghaziabad ✔️ 9871031762 ✔️ Escorts Service...
BEST ✨ Call Girls In  Indirapuram Ghaziabad  ✔️ 9871031762 ✔️ Escorts Service...BEST ✨ Call Girls In  Indirapuram Ghaziabad  ✔️ 9871031762 ✔️ Escorts Service...
BEST ✨ Call Girls In Indirapuram Ghaziabad ✔️ 9871031762 ✔️ Escorts Service...
 
Regression analysis: Simple Linear Regression Multiple Linear Regression
Regression analysis:  Simple Linear Regression Multiple Linear RegressionRegression analysis:  Simple Linear Regression Multiple Linear Regression
Regression analysis: Simple Linear Regression Multiple Linear Regression
 
Ensure the security of your HCL environment by applying the Zero Trust princi...
Ensure the security of your HCL environment by applying the Zero Trust princi...Ensure the security of your HCL environment by applying the Zero Trust princi...
Ensure the security of your HCL environment by applying the Zero Trust princi...
 
Call Girls In DLf Gurgaon ➥99902@11544 ( Best price)100% Genuine Escort In 24...
Call Girls In DLf Gurgaon ➥99902@11544 ( Best price)100% Genuine Escort In 24...Call Girls In DLf Gurgaon ➥99902@11544 ( Best price)100% Genuine Escort In 24...
Call Girls In DLf Gurgaon ➥99902@11544 ( Best price)100% Genuine Escort In 24...
 
GD Birla and his contribution in management
GD Birla and his contribution in managementGD Birla and his contribution in management
GD Birla and his contribution in management
 
Pharma Works Profile of Karan Communications
Pharma Works Profile of Karan CommunicationsPharma Works Profile of Karan Communications
Pharma Works Profile of Karan Communications
 
Lucknow 💋 Escorts in Lucknow - 450+ Call Girl Cash Payment 8923113531 Neha Th...
Lucknow 💋 Escorts in Lucknow - 450+ Call Girl Cash Payment 8923113531 Neha Th...Lucknow 💋 Escorts in Lucknow - 450+ Call Girl Cash Payment 8923113531 Neha Th...
Lucknow 💋 Escorts in Lucknow - 450+ Call Girl Cash Payment 8923113531 Neha Th...
 
Call Girls Pune Just Call 9907093804 Top Class Call Girl Service Available
Call Girls Pune Just Call 9907093804 Top Class Call Girl Service AvailableCall Girls Pune Just Call 9907093804 Top Class Call Girl Service Available
Call Girls Pune Just Call 9907093804 Top Class Call Girl Service Available
 

IJERD explores switching elements' impact on harmonics and power factors

  • 1. International Journal of Engineering Research and Development e-ISSN: 2278-067X, p-ISSN: 2278-800X, www.ijerd.com Volume 7, Issue 12 (July 2013), PP. 18-24 18 Influence of Switching Elements on Harmonics and Power Factor Improvement 1 A.Kumar, 2 Dr.G.R.Gurumurthy B N M Institute of Technology, BSK 2nd stage, Bangalore, India - 560070 Abstract:- Increasing demand for electrical energy by utilities has necessitated efficient utilization of available power. Most of the loads in the industry and domestic applications are inductive in nature causing a lagging power factor. This causes a reduction in the utilization of the power input. For the same power input the utilization can be improved by improving the power factor. Further the presence of harmonics results in poor quality of the power leading to losses. . In present days, solid state electronics control electric motors are frequently used for drive control (speed and torque). This can introduce harmonics in current and voltages. The general opinion among technologists is that improvement in power factor reduces losses in an electrical system. Although this is true in a general way, it is not so in systems which use switched electronic devices that can introduce large amount of harmonics [1]. The present work is aimed to study the effect of power factor correction on circuits consisting of power semiconductor switching. Boost convertor supplied from an unregulated supply was considered for the analysis of a static loading. The work also involved study of power factor improvement(PFI) for dynamic load. An automatic power factor controller was designed and implemented induction motor load. The controller was designed to sense the various parameters of the power and calculate the power factor. A rule-based table has been developed based on the power factor input. The controller can sense this power factor and automatically switch ON/OFF appropriate KVAR as per the programmed requirement. The results obtained are comparable with that reported in several previous work done.[1-6] Keywords:- Power factor improvement, Harmonics, THD, APFC, Filters I. INTRODUCTION Quantum of Energy generation is one of the metric for the measurement of a Nation’s development. The requirement of energy is much more than the amount of power getting generated in developing countries like India. Under these circumstances Demand side management (DSM) is one of the methods to improve the utilization of energy. Most of the industrial and domestic loads are inductive in nature and hence the power factor of the loads are very poor. An improvement in the power factor results in availability of more active power for the same generated power. Power factor improvement is most commonly used in industrial units. Automatic power factor controllers (APFC) are equipped with semiconductor devices, switching of capacitor banks for the improvement of power factor. In present days, solid state electronics control for electric motors are frequently used for drive control (speed and torque). This can introduce harmonics in current and voltages. The general opinion among technologists is that improvement in power factor reduces losses in an electrical system. Although this is true in a general way, it is not so in systems which use switched electronic devices that can introduce large amount of harmonics. a. Power factor:1. Concept of Power Factor Power factor is defined as the ratio of active power to apparent power. i.e., PF = . It is also defined as a cosine of the angle between voltage and current vectors in an electric network in which voltage and current are sinusoidal parameters. i.e., PF = cos Φ, where Φ is the angle between voltage and current vector. A poor power factor requires more apparent power for the same amount of active power consumed. It also increases the current level of operation and thereby increases losses in the system. A poor power factor is generally the result of inductive loads such as induction motor, welding set etc,. The poor power factor can also be due to distortion in current waveform resulting from power electronic based converters like rectifier, inverter etc,. used in the system. II. BENEFITS OF POWER FACTOR IMPROVEMENT The benefits that can be achieved by applying the correct power factor correction are: 1. Reduction of power consumption due to improved energy efficiency. Reduced power consumption reduces green house emission and fossil fuel depletion.
  • 2. Influence of Switching Elements on Harmonics and Power Factor Improvement 19 2. Extra power is available from the existing supply due to reduction of consumption in reactive KVA. 3. Reduced I2 R losses in machines and hence efficiency increases. 4. Voltage regulation improves due to reduced voltage drop in long cables & long lines. 5. The current drawn for the same load is lesser hence KVA loading of the machines reduce. The figure 1.1 shows the power triangle. Active power (kW) Φ Reactive Power Total power (kVAr) (kVA) Fig 1.1. Power triangle III. POWER FACTOR IMPROVEMENT FOR INDUCTIVE LOADS Power factor improvement is commonly adopted method for effective utilization of available power. The various advantages of improving power factor have been discussed earlier. The power factor improvement incorporates additional capacitive reactive power which compensates for the inductive reactive power of the load and thus improving power factor [1]. The vector diagram showing the improvement in power factor using capacitor bank is given in Fig.1.2 Ic Reference Ic = capacitor compensation current Φ2 Voltage I load1 = load current with pf=cosΦ1 Φ1 Iload2 = load current with pf=cosΦ2 ILoad2 ILoad1 Fig1.2: Vector showing power factor improvement using capacitor bank. KVA saving by improving power factor from cos Φ1 to cos Φ2 can be obtained as given in the expression below: saving in KVA = (KW / cos Φ2 ) - (KW / cos Φ1). For improvement of power factor in large capacitive loads suitable inductors have to be used. b. Harmonics: Harmonics have existed for many years in the power lines of plants and factories. However only over the last decade they have turned into a major problem to normal operations. This is largely due to the proliferation of harmonic producing equipment and the increased sensitivity of certain types of equipment to harmonics. The effects of harmonics can often be serious - computer systems may fail to operate properly; capacitor banks, such as those used for power factor correction may fail prematurely (much before expected life). The presence of harmonics increases losses in the system. IV. CONCEPT OF HARMONICS: Harmonics are distortions to the voltage and current waveforms from their normal sinusoidal shape. At the power generating stations, a 50 Hertz (Hz) sine wave is generated and distributed to a large number of residential and industrial loads. Certain types of loads distort the 50Hz wave by injecting additional signals of various magnitudes and frequencies. These additional signals are also sinusoidal in shape but their frequencies are multiples of the original waves for example, 150, 250 and 350Hz. These waves are called harmonics. The frequency of the power systems parameter voltage and current waves are called the fundamental, which in our case is 50Hz. Harmonics are expressed as integral multiples of fundamental frequency i.e., 2nd , 3rd , 4th 5th etc orders. An important feature of harmonics is that the magnitude of the harmonics normally decreases with increasing frequency. Thus, only the first few orders usually need to be considered in examining the effects of harmonics on power system components or equipment. Fig 1.3 shows a sample current wave with harmonics.
  • 3. Influence of Switching Elements on Harmonics and Power Factor Improvement 20 Fig 1.3. Waveform showing a sample of distorted current waveform due to harmonics. V. SOURCES OF HARMONICS: The various sources of harmonics are discussed under: 1. Increase in use of Power converters which use controlled switching, such as rectifiers, inverters, and AC phase control systems has increased harmonics due to switching action. 2. Motors: Asymmetrical air gaps, slight irregularities in mounting axes can cause motors in equipment such as pumps, fans and compressors to produce harmonics. 3. APFC capacitors: Power Factor Correction Capacitors can magnify harmonics if not properly applied. VI. PFI IN AN UNCONTROLLED RECTIFIER WITH BOOST CONVERTER a. Introduction and Design An uncontrolled single phase rectifier supplying a boost converter with duty cycle of 50% and 90% was considered for investigation. The basic circuit used is given in Fig 2.1. For the design of the rectifier a ripple factor of 1% was considered. Considering the frequency of 50hz and CF = 250μF we get, The ac input applied was 230v, 50Hz. The output of the rectifier was a DC of 325 V with 1% ripple. The boost converter was designed with a switch at 50% Duty cycle(D). Therefore the expected output voltage is Vo = VS / ( 1 –D) = 325 / 0.5 = 650V. Also the boost converter was designed with a switch at 90% Duty cycle(D). Therefore the expected output voltage is Vo = VS / ( 1 –D) = 325 / 0.1 = 3.25kV. Fig 2.1 Uncontrolled rectifier with Boost converter. The investigations were carried out using ORCAD PSpice Version 16.0 for duty cycle of 50% for the buck converter. From the waveform of input current, the harmonic components and THD were estimated. The
  • 4. Influence of Switching Elements on Harmonics and Power Factor Improvement 21 phase angle between fundamental components of voltages and current was considered as the power factor angle. Using the actual current waveform, the power losses were determined. b. Results: Initial investigations were carried out for duty cycle of 50% with and without any harmonic filter. Subsequently, simulations were carried out with duty cycle as 90% as per the circuit in Fig 2.2. Fig 2.2 Uncontrolled rectifier with Boost converter with series reactors The results obtained are tabulated below. Table 2.1 shows the results obtained by considering a series reactor. Losses were calculated as Pin - Po Table 2.1. Boost converter with series reactor in series with the supply (DC = 50%) Sl No. VDC (V) Lse mH pf Pin watt Po watt ITHD in % Loss (w) 1 632 0 0.71 5500 3300 40.3 2200 2 632 0.1 0.71 5500 3400 40.1 2100 3 632 0.5 0.72 5800 3480 40.6 2320 4 632 1 0.74 6000 3600 39.1 2400 5 632 3 0.83 7500 4700 39 2800 6 632 5 0.91 8200 5000 38.9 3200 7 632 7 0.96 8200 4880 38.6 3320 Table 2.2 shows the results obtained by considering a 90% duty cycle. Losses were calculated as Pin - Po Table 2.2. Boost converter with series reactor filter in series with the supply (DC = 90%) Sl no. VDC (V) Lse mH pf Pin watt Po watt ITHD in % Loss (w) 1 3300 0 0.91 16150 6460 7.3 9690 2 3300 0.1 0.93 16150 6460 7.1 9690 3 3300 0.5 0.94 17423 6960 7.15 10440 4 3300 1 0.98 18000 7200 6.7 10800 5 3300 3 0.99 22500 9000 6.5 13500 6 3300 5 0.993 24300 9720 6 14580 7 3300 7 0.997 24670 9870 5.8 14800 c. Discussions: Analysis of variation of power factor, THD and losses have been carried out using Boost converter. The input voltage used is unregulated. We observe from the results of simulation that the THD is enormously high (Nearly 40%) for 50% duty cycle operation of Boost converter. However, when duty cycle is increased is 90%, the values of THD are considerably lower. The variation in THD, losses and power factor are observed to (Tables 2.1 and 2.2) have the same trend which is that with increase in power factor, the losses are increasing and THD is decreasing.
  • 5. Influence of Switching Elements on Harmonics and Power Factor Improvement 22 VII. POWER FACTOR IMPROVEMENT EFFECT ON A DYNAMIC LOAD a. Load description: The load selected for the investigation of power factor improvement effect on dynamic load is a 3- phase Induction motor with name plate details as below: NAME PLATE DETAILS: POWER OUTPUT =2.2KW, 3HP, VOLTAGE=415V, CURRENT=4.8A, EFFICIENCY=79% CONNECTION TYPE: DELTA, FULL LOAD PF = 0.7, N = 1440 RPM b. Reactive KVAR requirement for APFC: The FL output of the motor is 2700w and at 0.72pf. The desired power factor was fixed for the APFC case at 0.99. We know that the kVAR required for improvement is given by: kVAR = P ( tanΦ1 - tanΦ2 ) where P = active power of the load. Φ1 = initial power factor angle Φ2 = required power factor angle kVAR = 2.700 ( tan(cosˉ1 0.72) – tan (cosˉ1 0.99)) = 2.5 kVAR The capacitor bank is to be connected in star. Therefore, Vph = VL / √3 = 415 / √3 = 239.6V. ICph = (kVAR * 1000) / ( 3* Vph) = 2500 / (3*239.6) = 3.47A Thus, XCph = (Vph / ICph ) = 239.6 / 3.47 = 69Ω. Therefore Cph = 1 / ( 2*π* 50 * 69) = 46µF. It was decided to use the required rating using 4 stages of capacitors. The experiment was conducted after the calibration of the APFC under 2 cases. Case 1 was performed without the APFC connected to get the base data which are as tabulated in Table3.1. The in case 2 the APFC was connected and the data were obtained as tabulated in table 3.2. Table 3.1: Experimental data without connecting APFC Sl. No. VL (v) I (A) W (Watts) Torque (kg-m) BHP o/p(w) pf %η ITHD Losses (w) 1 408 2.25 170 0 0 0 0.11 0 11.06 170 2. 400 2.4 800 0.3584 0.7356 541.1 0.5 67.64 10.04 258.9 3. 400 2.9 1440 0.7616 1.5419 1134.22 0.742 78.76 7.82 305.78 4. 394 3.4 1810 0.9856 1.9789 1455.67 0.78 80.42 7.3 354.33 5 394 3.9 2280 1.1984 2.382 1752.2 0.856 76.85 6.2 527.8 Table 3.2 : Experimental data with APFC Sl. No . VL (v) I (A) W (Watts) Torqu e (kg- m) BHP o/p(w) pf %η ITHD Losses (w) 1. 400 0.4 170 0 0 0 0.7 0 11.82 170 2. 400 1.266 745.65 0.358 0.735 540.6 0.85 72.5 10.49 205.05 3 400 1.97 1299 0.65 1.33 978.215 0.95 75.3 7.6 320.785 4 400 3.2 2215.8 1.2 2.377 1748.3 0.99 78.9 5.5 467.5
  • 6. Influence of Switching Elements on Harmonics and Power Factor Improvement 23 The images of the APFC and its connection to the circuit is shown in Fig 3.1 3.1 APFC with circuit connection for pf correction of an Induction motor c. Discussions: Variation of power factor and its effect have been analysed with incorporation of dynamic loads. A 3- phase IM was selected as dynamic load. A 3-phase Automatic Power Factor Controller (APFC) has been designed and constructed for studying the on-load performance. Also, the APFC has been calibrated using accurate reading meters (Voltmeter, Ammeters and Watt meters). The inaccuracy indications of APFC are within ±2%. The results of experimental investigations using above APFC set up show that the power factor can be improved up to 0.99. It was also observed that the trend with respect to the behaviour of THD and losses with variation of power factor is same with and without APFC. With increase in power factor THD is decreasing. Also, losses are increasing with increase in power factor & load. VIII CONCLUSION An uncontrolled boost converter supplied from uncontrolled rectified supply was simulated with and without power factor improving capacitors. The effect of improving the power factor on the THD was studied and the filters were incorporated to reduce the level of THD. In the second phase an 3-phase APFC was designed and implemented for a dynamic load, a 3-phase IM. The APFC was calibrated and designed with very high precision components to ensure proper operation. The machine was experimentally analyzed with and without the APFC. The performance verification of the simulation and hardware implementation has shown that:- 1. In case of circuits involving power electronic switching the even harmonic components, in particular the 2nd harmonic component, was predominant. 2. The use of appropriate filters with the circuit at output and input results in reduction of THD in input current. 3. Passive filters have limitations and are not sufficient to reduce the THD below the IEEE-519 standards. Active filters may be used in that case. 4. Results of experimental investigation using APFC shows that the power factor can be improved up to 0.99. 5. Increase in power factor in general decreases the THD. 6. At constant load, with increase in power factor, the losses are reduced. 7. Increase in power factor increases the losses. This is mainly due to increase in load current. 8. The trend with respect to the behavior of THD and losses with variation of power factor is same with and without APFC. However, the magnitude of THD is considerably reduced with increase in load. ACKNOWLEDGMENT The authors of the paper would like to acknowledge the Management of BNMIT for providing the necessary research facilities. REFERENCES [1] Francis.M.Fernandez, P.S.Chandramohanan Nair, “Influence of power factor compensating capacitor on estimation of harmonic distortion”, 9th International conference on Electrical power quality and utilization” Barcelona, 9-11 October 2007. [2] IEEE standard 519-1992 Recommended Practices and Requirements for Harmonic control in Electric Power systems 1993. [3] Lorenzo Cividino, “Power factor, Harmonic Distortion; Causes, Effects and Consideration “, IEEE 1992 Page 506-514 [4] Alexander Emanuel, Minghao Yang, “On the harmonic compensation in nonsinusoidal systems”, IEEE transactions on Power Delivery, vol 8., No.1,
  • 7. Influence of Switching Elements on Harmonics and Power Factor Improvement 24 [5] Fatih Basçiftçi and Ömer Faruk Hatay, “Microcontroller-controlled reactive power measurement and saving circuit design for residences and small scale enterprises”, Scientific research and essays Vol 5(16), pp 2312 – 2317, 18-Aug-2010. [6] K.Chatterjee, B.G.Fernandes and Gopal.K.Dubey, “An Instantaneous Reactive VA Compensator and Harmonic Suppressor System” IEEE Transactions on Power Electronics, Vol 14, No.2, 1999, pp 381- 392. [7] Nicola Locci, Carlo Muscas, Sara Sulis, “On the measurement of power quality indexes for Harmonic distortion in the presence of capacitors”, IMTC – 2005 – Instrumentation and Measurement Technology Conference Ottawa, Canada, pp. Vol 3 1600-1605,May 2005. [8] “Operational Amplifiers and Linear IC” by Ramanand Gaekwad, PHI [9] “Linear Integrated Circuits” by Roy Choudary, New Age Publications [10] Renesas Electronics America Inc “ User manual for YMCRPRX62T – Microcontroller”. [11] “SPICE for circuits and Electronics”, Muhammed H.Rashid, PHI, 2002 [12] “Power Electronics, Converters, Application and Design”, Ned Mohan, Undeland, Robbins Wiley.