This document provides information about the IWE earth fault relay, including its applications, operating principle, current transformer connections, connections and settings, functional check, and technical data. The relay is a definite time overcurrent relay suitable for earth fault protection of generators, motors, transformers, and radial feeders. It operates when the effective earth fault current exceeds the current setting for the set time delay. Examples are provided for using the relay for generator stator, system-wide, and back-up earth fault protection. Ring type and multiple current transformers can be used to measure earth fault current. The document explains how to connect, set, and check the functionality of the relay.
A Kelvin bridge, also called a Kelvin double bridge and in some countries a Thomson bridge, is a measuring instrument used to measure unknown electrical resistors below 1 ohm. It is specifically designed to measure resistors that are constructed as four terminal resistors.
PPT on earthing, grounding and isolation made by the students of SVIT,Vasad under the valuable guidance of the faculties teaching us Electronics and Electrical workshop(EEW) under the course of GTU.
Automation of capacitor banks based on MVAR RequirementAhmed Aslam
Power generation systems generate two power components, real power measured in watts, and reactive power measured in VARs. Both of these power components need to be produced and transmitted from the generator to the service customer. Real power flows from the generator to the load, and is used to drive loads such as electrical motors, create the heating effect in heaters, and the heating/lighting effect in lamps. Losses and associated voltage drops in the network are effected by the vector sum of real power and reactive power. Reactive power provided from a generation or capacitor source to the load is the component necessary for the operation of magnetizing currents in motors, transformers and solenoids which are part of a customer service load.
A capacitor bank is a grouping of several identical capacitors interconnected in parallel or in series with one another. These groups of capacitors are typically used to correct or counteract undesirable characteristics, such as power factor lag or phase shifts inherent in alternating current (AC) electrical power supplies. Shunt capacitor banks are used to an increasing extent at all voltage levels. There are a variety of reasons for this like the growing need for power transfer on existing lines while avoiding transfer of reactive power, better use of existing power systems, improving voltage stability, right-of-way and cost problems, voltage control and compensation of reactive loads. Three-phase capacitor bank sizes vary from a few tenths of MVAr to several hundreds of MVAr. Here we are using 25MVAR capacitor bank for this purpose.
Here, we have simulated an automatic scheme for switching of capacitor bank based on mvar requirement of the system. They automatically sense the voltage and reactive power using transducers. Output from these transducers are given to sensing circuit where it is compare with normal parameters (voltage and reactive power) of the system. If the condition satisfies it automatically switch on capacitor bank. And this normalises the system parameters.
A line reactor (also referred to as an electrical reactor or a choke) is a variable frequency drive (VFD) accessory that consists of a coil of wire that forms a magnetic field as current flows through it
An Auto Transformer is a transformer with only one winding wound on a laminated core. An auto transformer is similar to a two winding transformer but differ in the way the primary and secondary winding are interrelated. A part of the winding is common to both primary and secondary sides.
A Kelvin bridge, also called a Kelvin double bridge and in some countries a Thomson bridge, is a measuring instrument used to measure unknown electrical resistors below 1 ohm. It is specifically designed to measure resistors that are constructed as four terminal resistors.
PPT on earthing, grounding and isolation made by the students of SVIT,Vasad under the valuable guidance of the faculties teaching us Electronics and Electrical workshop(EEW) under the course of GTU.
Automation of capacitor banks based on MVAR RequirementAhmed Aslam
Power generation systems generate two power components, real power measured in watts, and reactive power measured in VARs. Both of these power components need to be produced and transmitted from the generator to the service customer. Real power flows from the generator to the load, and is used to drive loads such as electrical motors, create the heating effect in heaters, and the heating/lighting effect in lamps. Losses and associated voltage drops in the network are effected by the vector sum of real power and reactive power. Reactive power provided from a generation or capacitor source to the load is the component necessary for the operation of magnetizing currents in motors, transformers and solenoids which are part of a customer service load.
A capacitor bank is a grouping of several identical capacitors interconnected in parallel or in series with one another. These groups of capacitors are typically used to correct or counteract undesirable characteristics, such as power factor lag or phase shifts inherent in alternating current (AC) electrical power supplies. Shunt capacitor banks are used to an increasing extent at all voltage levels. There are a variety of reasons for this like the growing need for power transfer on existing lines while avoiding transfer of reactive power, better use of existing power systems, improving voltage stability, right-of-way and cost problems, voltage control and compensation of reactive loads. Three-phase capacitor bank sizes vary from a few tenths of MVAr to several hundreds of MVAr. Here we are using 25MVAR capacitor bank for this purpose.
Here, we have simulated an automatic scheme for switching of capacitor bank based on mvar requirement of the system. They automatically sense the voltage and reactive power using transducers. Output from these transducers are given to sensing circuit where it is compare with normal parameters (voltage and reactive power) of the system. If the condition satisfies it automatically switch on capacitor bank. And this normalises the system parameters.
A line reactor (also referred to as an electrical reactor or a choke) is a variable frequency drive (VFD) accessory that consists of a coil of wire that forms a magnetic field as current flows through it
An Auto Transformer is a transformer with only one winding wound on a laminated core. An auto transformer is similar to a two winding transformer but differ in the way the primary and secondary winding are interrelated. A part of the winding is common to both primary and secondary sides.
Dalroad Norslo - Electric Equipment - Contactor training level 1 - LS Industr...Dalroad Norslo
Industrial and Electric Equipment training on Contactors & Overload Relays and Accessories.
LS Industrial Systems (former LG) introduces its range of Contactors and Overload Relays.
It is based on current transformer description
It's working and applications are present in it ,it also includes videos of it's windings and it's inrush ability of transformer, and also about instrument transformer and it's working with applications.Current transformers are used-in measuring high currents and connected with it in parallel to it
TEDx Manchester: AI & The Future of WorkVolker Hirsch
TEDx Manchester talk on artificial intelligence (AI) and how the ascent of AI and robotics impacts our future work environments.
The video of the talk is now also available here: https://youtu.be/dRw4d2Si8LA
The International Journal of Engineering & Science is aimed at providing a platform for researchers, engineers, scientists, or educators to publish their original research results, to exchange new ideas, to disseminate information in innovative designs, engineering experiences and technological skills. It is also the Journal's objective to promote engineering and technology education. All papers submitted to the Journal will be blind peer-reviewed. Only original articles will be published.
The papers for publication in The International Journal of Engineering& Science are selected through rigorous peer reviews to ensure originality, timeliness, relevance, and readability.
Reach and Operating Time Correction of Digital Distance Relay Yayah Zakaria
Current and voltage signals recieved from conventional iron core Current Transformer (CT) and Voltage Transformer plays very important role for correct operation of Distance Distance Relay (DDR). Increase in secondary burden connected to CT causes it to saturate at earlier stage. The saturated CT produces distorted secondary current, causing DDR to under reach and to operate by certain time delay. Rogowski Coils (RCs) are attaining increased acceptance and use in electrical power system due to their inherent linearity, greater accuracy and wide operating current range. This paper presents use of RC as an advanced measurement device suitable for DDR. Case study for validation of use of RC is carried out on low voltage system. The simulation results of Distance protection scheme used for protection of part of 220kV AC system shows excellent performance of RC over CT under abnormal conditions.
Reach and Operating Time Correction of Digital Distance Relay IJECEIAES
Current and voltage signals recieved from conventional iron core Current Transformer (CT) and Voltage Transformer plays very important role for correct operation of Distance Distance Relay (DDR). Increase in secondary burden connected to CT causes it to saturate at earlier stage. The saturated CT produces distorted secondary current, causing DDR to under reach and to operate by certain time delay. Rogowski Coils (RCs) are attaining increased acceptance and use in electrical power system due to their inherent linearity, greater accuracy and wide operating current range. This paper presents use of RC as an advanced measurement device suitable for DDR. Case study for validation of use of RC is carried out on low voltage system. The simulation results of Distance protection scheme used for protection of part of 220kV AC system shows excellent performance of RC over CT under abnormal conditions.
Review of the DTC Controller and Estimation of Stator Resistance in IM DrivesIAES-IJPEDS
In recent years an advanced control method called direct torque control
(DTC) has gained importance due to its capability to produce fast torque
control of induction motor. Although in these systems such variables as
torque, flux modulus and flux sector are required, resulting DTC structure is
particularly simplistic. Conventional DTC does not require any mechanical
sensor or current regulator and coordinate transformation is not present, thus
reducing the complexity. Fast and good dynamic performances and
robustness has made DTC popular and is now used widely in all industrial
applications. Despite these advantages it has some disadvantages such as
high torque ripple and slow transient response to step changes during start
up. Torque ripple in DTC is because of hysteresis controller for stator flux
linkage and torque. The ripples can be reduced if the errors of the torque and
the flux linkage and the angular region of the flux linkage are subdivided into
several smaller subsections. Since the errors are divided into smaller sections
different voltage vector is selected for small difference in error, thus a more
accurate voltage vector is selected and hence the torque and flux linkage
errors are reduced. The stator resistance changes due to change in
temperature during the operation of machine. At high speeds, the stator
resistance drop is small and can be neglected. At low speeds, this drop
becomes dominant. Any change in stator resistance gives wrong estimation
of stator flux and consequently of the torque and flux. Therefore, it is
necessary to estimate the stator resistance correctly. This paper aims to
review some of the control techniques of DTC drives and stator resistance
estimation methods.
Limitations of DC injection into the AC network is an important operational requirement for grid connected photovoltaic systems. There is one way to ensure that this issue needs a power transformer as a connection to the AC network. However, this solution adds cost, volume, mass, and power losses. Ideally there shouldn't be any DC at the output of the inverter, but practically, a small amount of DC current is present. Therefore, in this paper there are techniques for the DC offset elimination are proposed. Some have drawbacks which was treated by another technique. Also there are best solutions for eliminating DC offset as in section 17, and 18 as it explains how to reduce the DC offset in a transformerless operation with reducing the power losses, mass and the cost effect.
Real time parameter estimation for power quality control and intelligent prot...EG TECHNOLOGIES
Real time parameter estimation for power quality control and intelligent protection of grid--Any details EG TECHNOLOGIES, ERODE,COIMBATORE, CHENNAI, SALEM, TIRUCHENGODE. call: 98422 38186.
Fuzzy Based Analysis of Inverter Fed Micro Grid in Islanding Operation-Experi...IJPEDS-IAES
Islanding operation in essence connotes isolating part of a power system not unlike distributed generation. This thesis puts forward fuzzy logic controller for inverter fed micro-grid in islanding operations which is assessed using hardware implementation. It’s assisted by power electronics which imparts the control and flexibility essential for the micro grid concept. A correctly designed controller guarantees that the micro grid can meet its utility’s demands. The efficacy and robustness is deliberated in the design of fuzzy system. The testing is performed by employing hardware components namelyATMEGA-328microcontroller, TLP250 opto-coupler and a MOSFET circuit. The test results demonstrate very good consistency and show noteworthy implications of the control of micro grid using inverters and fuzzy controllers.
Overview of the fundamental roles in Hydropower generation and the components involved in wider Electrical Engineering.
This paper presents the design and construction of hydroelectric dams from the hydrologist’s survey of the valley before construction, all aspects and involved disciplines, fluid dynamics, structural engineering, generation and mains frequency regulation to the very transmission of power through the network in the United Kingdom.
Author: Robbie Edward Sayers
Collaborators and co editors: Charlie Sims and Connor Healey.
(C) 2024 Robbie E. Sayers
Hybrid optimization of pumped hydro system and solar- Engr. Abdul-Azeez.pdffxintegritypublishin
Advancements in technology unveil a myriad of electrical and electronic breakthroughs geared towards efficiently harnessing limited resources to meet human energy demands. The optimization of hybrid solar PV panels and pumped hydro energy supply systems plays a pivotal role in utilizing natural resources effectively. This initiative not only benefits humanity but also fosters environmental sustainability. The study investigated the design optimization of these hybrid systems, focusing on understanding solar radiation patterns, identifying geographical influences on solar radiation, formulating a mathematical model for system optimization, and determining the optimal configuration of PV panels and pumped hydro storage. Through a comparative analysis approach and eight weeks of data collection, the study addressed key research questions related to solar radiation patterns and optimal system design. The findings highlighted regions with heightened solar radiation levels, showcasing substantial potential for power generation and emphasizing the system's efficiency. Optimizing system design significantly boosted power generation, promoted renewable energy utilization, and enhanced energy storage capacity. The study underscored the benefits of optimizing hybrid solar PV panels and pumped hydro energy supply systems for sustainable energy usage. Optimizing the design of solar PV panels and pumped hydro energy supply systems as examined across diverse climatic conditions in a developing country, not only enhances power generation but also improves the integration of renewable energy sources and boosts energy storage capacities, particularly beneficial for less economically prosperous regions. Additionally, the study provides valuable insights for advancing energy research in economically viable areas. Recommendations included conducting site-specific assessments, utilizing advanced modeling tools, implementing regular maintenance protocols, and enhancing communication among system components.
Cosmetic shop management system project report.pdfKamal Acharya
Buying new cosmetic products is difficult. It can even be scary for those who have sensitive skin and are prone to skin trouble. The information needed to alleviate this problem is on the back of each product, but it's thought to interpret those ingredient lists unless you have a background in chemistry.
Instead of buying and hoping for the best, we can use data science to help us predict which products may be good fits for us. It includes various function programs to do the above mentioned tasks.
Data file handling has been effectively used in the program.
The automated cosmetic shop management system should deal with the automation of general workflow and administration process of the shop. The main processes of the system focus on customer's request where the system is able to search the most appropriate products and deliver it to the customers. It should help the employees to quickly identify the list of cosmetic product that have reached the minimum quantity and also keep a track of expired date for each cosmetic product. It should help the employees to find the rack number in which the product is placed.It is also Faster and more efficient way.
Saudi Arabia stands as a titan in the global energy landscape, renowned for its abundant oil and gas resources. It's the largest exporter of petroleum and holds some of the world's most significant reserves. Let's delve into the top 10 oil and gas projects shaping Saudi Arabia's energy future in 2024.
CFD Simulation of By-pass Flow in a HRSG module by R&R Consult.pptxR&R Consult
CFD analysis is incredibly effective at solving mysteries and improving the performance of complex systems!
Here's a great example: At a large natural gas-fired power plant, where they use waste heat to generate steam and energy, they were puzzled that their boiler wasn't producing as much steam as expected.
R&R and Tetra Engineering Group Inc. were asked to solve the issue with reduced steam production.
An inspection had shown that a significant amount of hot flue gas was bypassing the boiler tubes, where the heat was supposed to be transferred.
R&R Consult conducted a CFD analysis, which revealed that 6.3% of the flue gas was bypassing the boiler tubes without transferring heat. The analysis also showed that the flue gas was instead being directed along the sides of the boiler and between the modules that were supposed to capture the heat. This was the cause of the reduced performance.
Based on our results, Tetra Engineering installed covering plates to reduce the bypass flow. This improved the boiler's performance and increased electricity production.
It is always satisfying when we can help solve complex challenges like this. Do your systems also need a check-up or optimization? Give us a call!
Work done in cooperation with James Malloy and David Moelling from Tetra Engineering.
More examples of our work https://www.r-r-consult.dk/en/cases-en/
Sachpazis:Terzaghi Bearing Capacity Estimation in simple terms with Calculati...Dr.Costas Sachpazis
Terzaghi's soil bearing capacity theory, developed by Karl Terzaghi, is a fundamental principle in geotechnical engineering used to determine the bearing capacity of shallow foundations. This theory provides a method to calculate the ultimate bearing capacity of soil, which is the maximum load per unit area that the soil can support without undergoing shear failure. The Calculation HTML Code included.
3. 3
Contents
Page No.
1 .1 .1 .1 .1 . ApplicationApplicationApplicationApplicationApplication 44444
2 .2 .2 .2 .2 . Operating PrincipleOperating PrincipleOperating PrincipleOperating PrincipleOperating Principle 44444
3 .3 .3 .3 .3 . Current TCurrent TCurrent TCurrent TCurrent Transformer Connectionsransformer Connectionsransformer Connectionsransformer Connectionsransformer Connections 55555
4 .4 .4 .4 .4 . Connections, Contact Arrangement and Setting AdjustmentsConnections, Contact Arrangement and Setting AdjustmentsConnections, Contact Arrangement and Setting AdjustmentsConnections, Contact Arrangement and Setting AdjustmentsConnections, Contact Arrangement and Setting Adjustments 77777
5 .5 .5 .5 .5 . Functional CheckFunctional CheckFunctional CheckFunctional CheckFunctional Check 88888
6 .6 .6 .6 .6 . TTTTTechnical Dataechnical Dataechnical Dataechnical Dataechnical Data 99999
7 .7 .7 .7 .7 . Information Required with OrderInformation Required with OrderInformation Required with OrderInformation Required with OrderInformation Required with Order 1 11 11 11 11 1
4. 4
1. Application
The IWEIWEIWEIWEIWE relay is a definite time relay suitable for earth
fault protection of generators, motors, transformers,
capacitor banks, shunt reactors and radial feeders in
distribution networks.
Examples of the application of non-directional earth
fault protection using the relay type IWE are shown
below.
Example 1: Generator Stator Earth Fault
Protection.
With the generator neutral point earthed as shown in
Fig.1, the earth fault relay type IWEIWEIWEIWEIWE responds only to
phase-earth faults between the generator and the
location of the current transformers supplying the relay.
Earth faults beyond the current transformer, i.e. on the
consumer or line side, will not be detected.
Fig. 1Fig. 1Fig. 1Fig. 1Fig. 1
Example 2 : System Earth Fault Protection.
With the generator neutral point earthed as shown in
Fig.2, the earth fault relay type IWEIWEIWEIWEIWE responds only to
earth faults in the power system connected to the
generator. It does not respond to earth faults on the
generator terminals or in the generator stator.
Fig. 2Fig. 2Fig. 2Fig. 2Fig. 2
Example 3 : Back-up Earth Fault Proteciton
With the earth fault relay type IWEIWEIWEIWEIWE connected as shown
in fig.3 it responds to any earth fault on the generator
(or transformer) or on the network. In order to
discriminate with other system earth fault protection
the relay type IWE must have a tripping delay time
which is longer than all other system earth fault
protection devices.
Fig. 3Fig. 3Fig. 3Fig. 3Fig. 3
2. Operating Principle
The earth fault relay type IWEIWEIWEIWEIWE is a definite time over
current relay with an additional low-pass filter.
Fig. 4 Relay characteristicFig. 4 Relay characteristicFig. 4 Relay characteristicFig. 4 Relay characteristicFig. 4 Relay characteristic
It comprises a current input circuit, an electronic
current measuring circuit and a time delay unit. It also
includes a low pass filter which blocks higher harmonic
currents such as third, fifth, seventh etc. Third and
triple harmonics (e.g. 9th, 27th etc.) are of particular
importance when applying earth fault protection since
these harmonics are additive and co-phasal in a three
phase system and thus appear in the system neutral or
in an earth fault relay as zero sequence (or earth fault)
current. Such a current would be detected by an earth
fault relay and may cause unwanted tripping. The relay
measuring system responds and initiates a timing
circuit, if the effective current exceeds the relay current
setting. If the earth fault current remains above the
IE
5. 5
setting for the set time delay the output tripping contacts
operates.
The tripping time delay is independent of the current
level. When applied in a power system the relay time
delay must be selected so that it coordinates with other
earth fault relays.
Fig.5a and 5b illustrate the operating characteristic of
the relay. Consider a relay with a current setting IE
=1.5
A and a time delay setting tE
=0.8s:
Fig.5a:Fig.5a:Fig.5a:Fig.5a:Fig.5a:
At t=0.4s, the current exceeds the relay current setting
and initiates the time delay circuit. The indicating LED
“I” on the relay fascia is illuminated.
At t=1s the earth fault current drops below the current
setting. The LED “I” extinguishes and the time delay
circuit reset to zero. There is no trip output.
Fig. 5b:Fig. 5b:Fig. 5b:Fig. 5b:Fig. 5b:
At t=0.4s the current exceeds the relay current setting
and initiates the relay time delay circuit as in the
example described above and illustrated in fig.5a.
At t=1.2s, e.g. 0.8s, after the current exceeded the
relay setting the time delay has elapsed and the “TRIP”
LED is illuminated. The relay produces a trip output and
the relay current is interrupted.
Fig. 5a and 5bFig. 5a and 5bFig. 5a and 5bFig. 5a and 5bFig. 5a and 5b
3. Current Transformer Connections
Current transformer must be arranged so that the
relay type IWEIWEIWEIWEIWE measures zero sequences (or earth
fault) currents as indicated schematically in figs. 1 and
2.
This can be achieved by using several current
transformers connected suitable or by using a single
ring type current transformer.
Earth fault measurement using several currentEarth fault measurement using several currentEarth fault measurement using several currentEarth fault measurement using several currentEarth fault measurement using several current
transformerstransformerstransformerstransformerstransformers
The arrangement shown in figs. 6 and 7 should be
used only where significant levels of earth fault current
are available (e.g. in solidly earthed or low impedance
earthed networks) since the errors associated with each
current transformer are additive and these are
recognized by the relay as zero sequence current.
Such an arrangement can therefore only be used
where the relay current setting is in excess of the sum
of the CT errors.
Guide for dimensioning of CT’s arrangementGuide for dimensioning of CT’s arrangementGuide for dimensioning of CT’s arrangementGuide for dimensioning of CT’s arrangementGuide for dimensioning of CT’s arrangement
as shown in figs. 6 and 7as shown in figs. 6 and 7as shown in figs. 6 and 7as shown in figs. 6 and 7as shown in figs. 6 and 7
CT’s must be matched and have the same current
ration, accuracy class, rated output, secondary
winding resistance and magnetising
characteristic.
The current ratio and primary current withstand
should be selected according to the maximum
rated current of the circuit.
The combination of rated output, overcurrent
factor and secondary winding resistance should
be chosen such that a CT does not saturate at the
maximum short circuit current. If this combination
is not correct the CT may saturate under external
phase fault conditions (i.e. for a 2 or 3 phase
fault which the relay should remains unoperated).
In this case the several line CT’s may saturate
unequally. Therefore the sum of the secondary
currents in no longer zero and the relay
maloperates.
Relay output contacts
operate. Circuit
breaker tripped.
I
/A
1
0
Dt = 0.2s
1 2
2
-1.6AIE
3
4
t
/s
Dt = <0.2s
t
/s20 1
1
2
3
4
I
/A
l
/A
l
/A
6. 6
Fig. 6 and 7Fig. 6 and 7Fig. 6 and 7Fig. 6 and 7Fig. 6 and 7
Relationship between CT actual overcurrent factor,
rated overcurrent factor rated output, connected
burden and secondary winding resistance.
If the burden connected to the secondary winding of a
current transformer does not match exactly the rated
burden, the actual overcurrent factor of the CT will no
longer be equal to the rated overcurrent factor.
For example, if the total connected burden is less than
the rated output of the CT, the actual overcurrent factor
will be greater than the rated overcurrent factor.
Conversely, if the total connected burden is greater
than the rated output the CT, the actual overcurrent
factor will be less than the rated overcurrent factor.
Actual overcurrent factors can be calculated as follows:
n’= n
where
n’ = actual overcurrent factor
n = rated overcurrent factor
PN
= Nominal rated output of CT (VA)
PE
= Burden of secondary winding resistance of CT
rated current
= IN
2
RCT
(VA)
PN
-PE
PB
-PE
PB
= Burden connected to CT secondary circuit (VA)
Earth fault current measuring using ring type CT’sEarth fault current measuring using ring type CT’sEarth fault current measuring using ring type CT’sEarth fault current measuring using ring type CT’sEarth fault current measuring using ring type CT’s
The use of ring type current transformers for supplying
earth fault relays as shown in fig. 8 and 9 is preferred
wherever possible to the arrangement using separate
CT’s connected in parallel as indicated in figs. 6 and 7.
Such an arrangement is particularly recommended for
earth fault protection on high impedance earthed
systems where the level of earth fault current is low.
A ring type CT comprises a single magnetic core which
surrounds all conductors and therefore under normal
load conditions, or during two or three phase fault
conditions, the resultant magnetic flux is zero and the
CT produces no secondary current. Only in the
presence of zero sequence current is the resultant flux
not equal to zero and the CT produces a secondary
current. Therefore, unlike the arrangement which
summates, the secondary currents from several CT’s
under normal load and other non earth fault
conditions, and which is the therefore sensitive to
individual CT errors, a single ring type CT is not subject
to the same errors and a very high degree of sensivity
can be achieved.
Fig. 8 and 9Fig. 8 and 9Fig. 8 and 9Fig. 8 and 9Fig. 8 and 9
76 1211
IWE
Fig. 9
Measurement of earth fault
current in a three phase,
four wire system using a
Ring type CT
Fig. 8
Measurement of earth fault
current in a three phase,
three wire system using a
Ring type CT
43ba
L3
L2
L1
N
76 1211
43ba
IWE
L3
L2
L1
E E
L1
L2
N
ba
IWE
Fig. 7
Three Phase, four
wire system
Fig. 6
Holmgreen connection,
three phase three wire
system
43
6 7 1211
L3
L1
L2
L3
IWE
43ba
6 7 1211
E E
7. 7
Guide for Dimensioning of Ring Type CT’s
• The inside diameter of the CT must be large
enough to slide over the cable.
•
The primary rated current of the CT should match
the maximum earth fault current in the case of
high impedance earthed system.
•
The rated secondary current is generally 1A or
5A.
•
the case of a feeder comprising several cables in
parallel, a ring CT can be fitted to each cable.
The CT secondary windings should then be
connected in parallel and connected to a single
earth fault relay type IWE. CT’s should have
identical magnetising characteristic, ratio, rated
output, accuracy class etc.
4. Connections, Contact Arrangement
and Setting Adjustments
Fig.10 shows the main connections to the relay type
IWE. The auxiliary supply should be connected to
terminals “a” and “6” and should be a secure supply
with a variation of not greater than 10 per cent.
Fig. 10 Relay connectionsFig. 10 Relay connectionsFig. 10 Relay connectionsFig. 10 Relay connectionsFig. 10 Relay connections
If a ring type CT is used, it is important to ensure that
the cable and CT are installed precisely as shows in fig.
11 and cable gland must be insulated from the cable
terminating box, and the cable sheath and armour
must be earthed by taking the earth connection back
through the CT as shown. If the earth lead is not
connected as shown, the earth return current in the
cable sheath or armour sets up a magnetic flux which
cancels the flux produced by the earth current in the
cable, and therefore the relay would not operate
during an earth fault.
Fig. 11Fig. 11Fig. 11Fig. 11Fig. 11 Cable and earthing arrangementsCable and earthing arrangementsCable and earthing arrangementsCable and earthing arrangementsCable and earthing arrangements
when using Ring type CTwhen using Ring type CTwhen using Ring type CTwhen using Ring type CTwhen using Ring type CT
Fig.12Fig.12Fig.12Fig.12Fig.12 shows the position of the relay contacts. Under
normal healthy conditions, or with no auxiliary voltage
supplied the contacts are as shown in position 1. With
the relay operated after the set time delay has elapsed,
the contacts are shown as in position 2.
76
auxiliary
supply voltage
CT
secondary
current
S (I)2
S1 (k)
1211
IWE
43ba
L1 L2 L3
cable gland to be
insulated from earth
cable
earth
connection
Ring type CT
E
8. 8
Fig. 12 Contact positionsFig. 12 Contact positionsFig. 12 Contact positionsFig. 12 Contact positionsFig. 12 Contact positions
Fig. 13 Front cover of unitFig. 13 Front cover of unitFig. 13 Front cover of unitFig. 13 Front cover of unitFig. 13 Front cover of unit IWEIWEIWEIWEIWE
5. Functional Check
A simple functional check can be made with the aid of
a secondary injection test set and an ammeter as
follows:
Connect rated auxiliary supply voltage to terminal
“a” and “6”.
Connect the injection test set output current
terminals via an ammeter to the relay terminals
“7” and “b”.
Note that the injected current should be kept less
than the rated current of the relay i.e. less than
1A or 5A as appropriate.
Adjust the time delay setting potentiometer to
t=0s.
With the current setting potentiometer set to a
suitable value increase the current from the test
set until the relay LED “I” is illuminated. This
indicates that the relay has picked up. Since the
set time delay t=0s, the tripping LED “TRIP” will
be illuminated simultaneously. Check that the pick
up current is within 5 per cent of the current
setting on the relay. Switch off the test current.
Adjust the time delay setting potentiometer to the
required time delay.
Switch on the test set, increase the test current to
a value which is higher than the current setting.
The relay will only operate and produce a trip
output after the set time delay has elapsed.
Contact position 2Contact position 1
Protected system healthy
Relay non-operated
No auxiliary voltage
Relay operated
Tripping
1211
43
1211
43
DC/ACDC/ACDC/AC
EARTH FAULT CURRENT RELAY
current time
S
I> ba 3 4
12117
I
k
6
TRIP
IWE
A
9570
9. 9
6. Technical Data
IWE-Earth Fault Current Relay
General Data
Design : electronic state definite time overcurrent relay with low-pass filter
Maintenance : none
Permissible operating time : continuous
Mounting position : independent
Auxiliary Supply Voltages
Supply Voltage : 24 V, 110 V d.c
Own consumption : 2.5 W
Permissible voltage variation : ± 10%
Measuring circuit
Rated current IN
: 1 A or 5 A
Rated frequency : 50 Hz or 60 Hz
Burden of current circuit : 0.5 VA at rated current
Short time current setting : 20.IN
for max. 1S
Current settings : 1 A relay: 0 - 100 mA/ 0-0.5 A
5A relay: 0 - 2A / 0 -4A
Time delay settings : 0.2-2s/0.5-4s
Reset radio : 99.5 %
Output Circuits
Contacts : 1 NC, 1 NO potential free
Breaking capacity : 1000 VA at 250 V AC 2 A at 24 V dc
Contact life : greater than 106
switching operations
Terminals : M4, wire termination max. conductor 2.5mm2
Ambient Conditions
Ambient temperature range:
•
for storage : -40 0
C up to +70 0
C
•
for operation within claimed
accuracy : -200
C up to +600
C
10. 10
Accuracy
Effect of temperature : ± 1% of the setting over the range 00
C < V < 600
C
Case, Dimensions,
Weight and Installation
Case : CSPCCSPCCSPCCSPCCSPC standard case
Material : track resistant moulded base and transparent cover
Height *width*depth : 142 mm*105 mm * 90 mm
Weight : 0.4 kg (approx.)
Mounting : Flush mounting
Protection class case : IP20
terminals : IP00
Dimensions and
drill-holes
(dimensions in mm)
105
91
98.5
86
52.5
19
4.5
a
105
6
Freespace for bolts
6.5
4.5
Dm-3.8mm
Dm-4.2mm
15
26
111
126.5
136.5
141
34
b 1 2 3 4
6 7 8 10 11 12
a
11. 11
7. Information required with order
When placing an order, please fill in the form on the
right.
Earth fault relay IWE
Rated Current 1A 11111
Rated Current 5A 55555
Current ranges 1A (0 - 0.1 A) 0.10.10.10.10.1
(0 - 0.5 A) 0.50.50.50.50.5
5A (0 - 2 A) 2.02.02.02.02.0
(0 - 4 A) 4.04.04.04.04.0
Time Ranges 0.2 - 2 sec. 22222
0.5 - 4 sec. 44444
Auxiliary Voltage 24 V DC 2424242424
110 V DC 110110110110110