Strength Evaluation of Reinforced Concrete Columns Eccentrically
Concealed with CPVC and HDPE Rain Water Pipes
Himanshu Tamore1, Prof. Dipika Khandelwal2, Dr. Atul B. Pujari3
1PG Student, Department of Civil Engineering KJCOEMR, Pune, Maharashtra, India
2,3 Professor, Department of Civil Engineering KJCOEMR, Pune, Maharashtra, India
---------------------------------------------------------------------***---------------------------------------------------------------------
Abstract - Water plays a significant role in our lives since it
is a precious natural resource. Over the past few years, there
has been an increase in water shortages in several parts ofthe
country. Ideal measures should be taken to reduce the high
rate of water loss, one such measure is Rainwater Harvesting.
Rain water harvesting is nothing but the collection and
storage of rain water which runs off from roof tops, parks,
roads, open grounds, etc. This water run off can be either
stored or recharged into the ground water. In case of
buildings, the conveyance system that is required to carry the
water harvested from the catchment i.e the terraceareaofthe
building is done through a series of pipes. These pipelines
running through building facades are difficult to maintain
and over a period of time they cause damage to the elevation
of the building. Though rain water harvesting is a solution for
a bigger problem of water scarcity and cannot be done away
with, the damage to the elevation of any building structure
due to these pipelines needs to be solved. One ofthesolutionto
this is to conceal the pipes inside structural columns, however
the strength of columns is effected by reinforcing ratios and
cross sectional area which is reduced if pipes are placed in
these columns, In this paper, strength evaluationofreinforced
concrete columns eccentrically concealed with CVPC pipe and
HDPE pipe with a concrete grade of M30 is done to compare
its compressive strength and load carrying capability. The
results concluded that column with CPVC pipe has a superior
compressive strength and load carrying capability as
compared to column with HDPE pipe.
Key Words: Eccentrically Concealed column, CVPC pipe,
HDPE pipe
1. INTRODUCTION
Water is a precious, essential and an abiotic component of
the ecosystem. Today we all are heading toward the scarcity
of water and this is mainly because of the lack of water
conservation and pollution of water bodies.
Rain water harvesting is one measure through which
wastage of runoff water from rooftops can be saved but the
conveyance system which is used to transport theharvested
water from the catchment to therechargezoneisrequiredto
be placed all over building walls and this plumbing work on
the surface of building is not very desirable and all the key
players related to civil industry i.e architects, designers,
developers, engineers would prefer to avoid it as due to
weather conditions the deterioration of such plumbing
works is very rapid and thereby it badly affects the
elevational view of the building.
To solve this problem, these pipes can be concealed within
the structural members itself. In this paper, study is done on
effect of CPVC Pipe and HDPE pipe when positioned
eccentrically in a cross section of a column. Chlorinated
polyvinyl chloride (CPVC) is a thermoplastic made by
chlorinating polyvinyl chloride (PVC) resin. It is more
flexible and has a higher compressive strength than PVC. It
can also resist temperatures that are higher than
conventional PVC. HDPE pipe is a flexible plastic pipe that is
used to transport fluids and gases. HDPE (high-density
polyethylene) is a thermoplastic with a high level of
impermeability and a strong molecular bond,makingitideal
for high-pressure pipelines.
2. METHODOLOGY
The main objective of this study is to evaluate the load
carrying capacity and compressive strength of a square
reinforced short column with CPVC and HDPE pipes
positioned eccentrically on the cross section of the column
and compare it with a column that does not contain any
pipe.
3. MIX DESIGN FOR M30
Initiation Mix design of M-30 of concrete with 20mm
maximum size aggregate with medium workabilitybased on
IS 10262-2009 and IS 456-2000 was done and the ratio
obtained as mentioned in table 1 with a W/C ratio of 0.45.
Table -1: Mix design proportioning
Mix design
Cement Fine aggregate Coarse aggregate
1 1.89 3.37
4. CUBE TESTING
The cubes were cast on-site and tested on UTM as shown in
Figure 1. The cubes were kept in the curing tank for 28 days
after the formwork was removed, following result were
obtained and mix design was foundto besatisfactory, results
are shown in table 2
International Research Journal of Engineering and Technology (IRJET) e-ISSN: 2395-0056
Volume: 09 Issue: 05 | May 2022 www.irjet.net p-ISSN: 2395-0072
© 2022, IRJET | Impact Factor value: 7.529 | ISO 9001:2008 Certified Journal | Page 1908
Table -2: Trial Mix results of concrete cube of grade M30
Trial Mix results
Cube
No
Date of
casting
Date of
testing
Load
[KN]
Area
[mm2]
Compres
sive
Strength
[N/mm2]
Average
Compres
sive
Strength
[N/mm2]
1.
21/2/22 21/3/22
791.5 22500 35.1
34.24
2. 756.7 22500 33.6
3. 765.8 22500 34.3
Fig -1: Cube Testing
5. SPECIFICATION OF COLUMNS
Three Short Columns of cross section 200 mm X 200 mm
and length of 950 mm were designed, one was without any
placement of pipe, other one with a placement of CPVC pipe
of diameter 50 mm and last one with a placement of HDPE
pipe of diameter 50 mm. The pipes were positioned
eccentrically to the cross-section. The design Specificationof
the columns are asshown in table 3 and casting ofcolumnsis
shown in figure 2 and 3.
Table -3: Specification of columns
Specification of columns
Column
specimen
Dimension of
column(mm)
Pipe
diameterand
type
Vertical
reinforcement
Lateral
ties
C1 200 x 200 x 950 CPVC
50mm Ø
4 Nos of 12
mm Ø
8 mm Ø @
150 mm
c/c
C2 200 x 200 x 950 HDPE
50mm Ø
4 Nos of 12
mm Ø
8 mm Ø @
150 mm
c/c
C3 200 x 200 x 950 - 4 Nos of 12
mm Ø
8 mm Ø @
150 mm
c/c
Fig -2: Column formwork
Fig -3: Column casting with CPVC and HDPE pipe
6. CONCLUSIONS
The test resultsare shown in table 4 and testing procedureis
shown in figure 4, 5 and 6. The analysis reveals that inserting
an HDPE drain pipe inside the column considerably affects
the column's weight carrying capacity. When compared to a
column concealed with HDPEpipe,acolumnwithCPVCdrain
pipe and a solidcolumn has higher compressivestrengthand
load carrying capacity. CPVC Pipe can be used as an
alternative to PVC Pipe for concealing in a column as a
rainwater drain pipe. It can be concluded that column with
CPVC pipe has a superior compressive strength and load
carrying capability as compared to column with HDPE pipe.
International Research Journal of Engineering and Technology (IRJET) e-ISSN: 2395-0056
Volume: 09 Issue: 05 | May 2022 www.irjet.net p-ISSN: 2395-0072
© 2022, IRJET | Impact Factor value: 7.529 | ISO 9001:2008 Certified Journal | Page 1909
Table -4: Compressive Strength comparision
Compressive Strength comparision
Cracks
Formation
[KN]
Sustained
Compressive
Load [KN]
Failed at
Compressive
Load
[KN]
Column with
no pipe
500 666 670
Column with
CPCV pipe
183 914 915
Column with
HDPE pipe
175 598 591
Fig -4: Testing on column without pipe
Fig -5: Testing on column with CPVC pipe
Fig -6: Testing on column with HDPE pipe
REFERENCES
[1] K-S. Sona, K. Pilakoutasb K. Neocleousc “Behaviour of
Concrete Columns with Drilled Holes” Magazine of
Concrete Research, 58 (7), pp. 411-419
[2] J. Bakhteri,w. Omar,a.M.Makhtar“Acritical reviewof the
reinforced concrete columns and walls concealing rain
water pipe in multistorey buildings”, (journal of civil
engineering) vol. 15 no. 2, 2002
[3] J. Bakhteri, S. Iskandar“Experimentalstudyofreinforced
concrete columns concealingrain water pipe” pp 13-26
.2005
[4] P.Wilson, E.M.S. Nair “Investigation on reinforced
concrete columns with holes” Volume:04Issue05May -
2017
[5] A. S. Saadoon, N. A. Jasim “Empirical Design Equations
For PVCConcrete CompositeColumns”Pp71-78Volume
6 Issue 10- October 2017
[6] R. W. Poston, T. E. Gilliam, Y. Yamamoto, and J. E. Breen
“Hollow Concrete Bridge Pier Behavior”ACI Journal, pp
779-787, November december
[7] E.A. Rodriguesa ,O.L. Manzolib L.A.G. Bitencourt
Jr.,P.G.C.dosPrazeresa,T.N. Bittencourta “Failure
behavior modeling of slender reinforced concrete
columns subjected to eccentric load”.
[8] R.Kumutha ,.K.Vijai “External confinement of plain and
reinforced concrete columns using pvc pipes” 19th -
20th November 2016
[9] Mohanad M. Abdulazeez and Mohamed A. El Gawady
“Seismic Behavior of Hollow- Core Composite Bridge
Columns Having Slender Inner Steel Tubes” Volume:
117.Pg.143-158.
[10] Indian Standard IS 456: 2000, “Plane and Reinforced
concrete code of practice(Forth Revision)”
[11] Indian Standard IS 10262: 2019, “Concrete Mix
Proportioning – Guidelines (Second Revision)”

More Related Content

Similar to Strength Evaluation of Reinforced Concrete Columns Eccentrically Concealed with CPVC and HDPE Rain Water Pipes

Concrete filled steel tubes subjected to axial compression
Concrete filled steel tubes subjected to axial compressionConcrete filled steel tubes subjected to axial compression
Concrete filled steel tubes subjected to axial compression
eSAT Journals
 

Similar to Strength Evaluation of Reinforced Concrete Columns Eccentrically Concealed with CPVC and HDPE Rain Water Pipes (20)

IRJET- Retrofitting of Reinforced Concrete Beam using Carbon Fiber Reinforced...
IRJET- Retrofitting of Reinforced Concrete Beam using Carbon Fiber Reinforced...IRJET- Retrofitting of Reinforced Concrete Beam using Carbon Fiber Reinforced...
IRJET- Retrofitting of Reinforced Concrete Beam using Carbon Fiber Reinforced...
 
ANALYSIS & DESIGN OF CIRCULAR COMPONENTS OF WATER TREATMENT PLANT USING PREST...
ANALYSIS & DESIGN OF CIRCULAR COMPONENTS OF WATER TREATMENT PLANT USING PREST...ANALYSIS & DESIGN OF CIRCULAR COMPONENTS OF WATER TREATMENT PLANT USING PREST...
ANALYSIS & DESIGN OF CIRCULAR COMPONENTS OF WATER TREATMENT PLANT USING PREST...
 
IRJET- Sleeper Design using Fibre Reinforcement
IRJET- Sleeper Design using Fibre ReinforcementIRJET- Sleeper Design using Fibre Reinforcement
IRJET- Sleeper Design using Fibre Reinforcement
 
Structural performance of prefabricated cage reinforced concrete composite st...
Structural performance of prefabricated cage reinforced concrete composite st...Structural performance of prefabricated cage reinforced concrete composite st...
Structural performance of prefabricated cage reinforced concrete composite st...
 
IRJET- Comparative Analysis of Concrete Filled Steel Tubular Truss Bridge wit...
IRJET- Comparative Analysis of Concrete Filled Steel Tubular Truss Bridge wit...IRJET- Comparative Analysis of Concrete Filled Steel Tubular Truss Bridge wit...
IRJET- Comparative Analysis of Concrete Filled Steel Tubular Truss Bridge wit...
 
IRJET - Experimental and Analytical Study on Partial Replacement of Coarse Ag...
IRJET - Experimental and Analytical Study on Partial Replacement of Coarse Ag...IRJET - Experimental and Analytical Study on Partial Replacement of Coarse Ag...
IRJET - Experimental and Analytical Study on Partial Replacement of Coarse Ag...
 
An analytical and experimental study of concrete encased column
An analytical and experimental study of concrete encased columnAn analytical and experimental study of concrete encased column
An analytical and experimental study of concrete encased column
 
Analysis of different types of braces and chord connection in (CFST) k -joint...
Analysis of different types of braces and chord connection in (CFST) k -joint...Analysis of different types of braces and chord connection in (CFST) k -joint...
Analysis of different types of braces and chord connection in (CFST) k -joint...
 
IRJET- An Experimental Study on Flexural Strength of Bubble Deck Slab
IRJET- An Experimental Study on Flexural Strength of Bubble Deck SlabIRJET- An Experimental Study on Flexural Strength of Bubble Deck Slab
IRJET- An Experimental Study on Flexural Strength of Bubble Deck Slab
 
IRJET - Experimental Investigation of flexural member of Beam Opening in ...
IRJET -  	  Experimental Investigation of flexural member of Beam Opening in ...IRJET -  	  Experimental Investigation of flexural member of Beam Opening in ...
IRJET - Experimental Investigation of flexural member of Beam Opening in ...
 
IRJET- Effect of Web Openings of Constant Area in Beams of Different Shape in...
IRJET- Effect of Web Openings of Constant Area in Beams of Different Shape in...IRJET- Effect of Web Openings of Constant Area in Beams of Different Shape in...
IRJET- Effect of Web Openings of Constant Area in Beams of Different Shape in...
 
IRJET- Effect of Web Openings of Constant Depth in Beams of Different Sha...
IRJET-  	  Effect of Web Openings of Constant Depth in Beams of Different Sha...IRJET-  	  Effect of Web Openings of Constant Depth in Beams of Different Sha...
IRJET- Effect of Web Openings of Constant Depth in Beams of Different Sha...
 
Concrete filled steel tubes subjected to axial compression
Concrete filled steel tubes subjected to axial compressionConcrete filled steel tubes subjected to axial compression
Concrete filled steel tubes subjected to axial compression
 
Analytical Study on Concrete Filled Elliptical Steel Tubular Column
Analytical Study on Concrete Filled Elliptical Steel Tubular ColumnAnalytical Study on Concrete Filled Elliptical Steel Tubular Column
Analytical Study on Concrete Filled Elliptical Steel Tubular Column
 
IRJET - Repair and Rehabilitation of Reinforced Concrete Bridge
IRJET - Repair and Rehabilitation of Reinforced Concrete BridgeIRJET - Repair and Rehabilitation of Reinforced Concrete Bridge
IRJET - Repair and Rehabilitation of Reinforced Concrete Bridge
 
IRJET-V9I7186.pdfWeb Crippling Capacity of Cold Formed Steel Channel Sections...
IRJET-V9I7186.pdfWeb Crippling Capacity of Cold Formed Steel Channel Sections...IRJET-V9I7186.pdfWeb Crippling Capacity of Cold Formed Steel Channel Sections...
IRJET-V9I7186.pdfWeb Crippling Capacity of Cold Formed Steel Channel Sections...
 
A Study of Dynamic Response of Circular Water Tank with Baffle Walls
A Study of Dynamic Response of Circular Water Tank with Baffle WallsA Study of Dynamic Response of Circular Water Tank with Baffle Walls
A Study of Dynamic Response of Circular Water Tank with Baffle Walls
 
Comparative Study on Flexural Strength of M-40 Grade with Lapping of Bars
Comparative Study on Flexural Strength of M-40 Grade with Lapping of BarsComparative Study on Flexural Strength of M-40 Grade with Lapping of Bars
Comparative Study on Flexural Strength of M-40 Grade with Lapping of Bars
 
Performance based design of Tall RC Structures considering Uncertainty in pla...
Performance based design of Tall RC Structures considering Uncertainty in pla...Performance based design of Tall RC Structures considering Uncertainty in pla...
Performance based design of Tall RC Structures considering Uncertainty in pla...
 
FEA OF DIFFERENT CONFIGURATIONS OF RECTANGULAR HOLLOW FLANGE CHANNEL BEAM (RH...
FEA OF DIFFERENT CONFIGURATIONS OF RECTANGULAR HOLLOW FLANGE CHANNEL BEAM (RH...FEA OF DIFFERENT CONFIGURATIONS OF RECTANGULAR HOLLOW FLANGE CHANNEL BEAM (RH...
FEA OF DIFFERENT CONFIGURATIONS OF RECTANGULAR HOLLOW FLANGE CHANNEL BEAM (RH...
 

More from IRJET Journal

More from IRJET Journal (20)

TUNNELING IN HIMALAYAS WITH NATM METHOD: A SPECIAL REFERENCES TO SUNGAL TUNNE...
TUNNELING IN HIMALAYAS WITH NATM METHOD: A SPECIAL REFERENCES TO SUNGAL TUNNE...TUNNELING IN HIMALAYAS WITH NATM METHOD: A SPECIAL REFERENCES TO SUNGAL TUNNE...
TUNNELING IN HIMALAYAS WITH NATM METHOD: A SPECIAL REFERENCES TO SUNGAL TUNNE...
 
STUDY THE EFFECT OF RESPONSE REDUCTION FACTOR ON RC FRAMED STRUCTURE
STUDY THE EFFECT OF RESPONSE REDUCTION FACTOR ON RC FRAMED STRUCTURESTUDY THE EFFECT OF RESPONSE REDUCTION FACTOR ON RC FRAMED STRUCTURE
STUDY THE EFFECT OF RESPONSE REDUCTION FACTOR ON RC FRAMED STRUCTURE
 
A COMPARATIVE ANALYSIS OF RCC ELEMENT OF SLAB WITH STARK STEEL (HYSD STEEL) A...
A COMPARATIVE ANALYSIS OF RCC ELEMENT OF SLAB WITH STARK STEEL (HYSD STEEL) A...A COMPARATIVE ANALYSIS OF RCC ELEMENT OF SLAB WITH STARK STEEL (HYSD STEEL) A...
A COMPARATIVE ANALYSIS OF RCC ELEMENT OF SLAB WITH STARK STEEL (HYSD STEEL) A...
 
Effect of Camber and Angles of Attack on Airfoil Characteristics
Effect of Camber and Angles of Attack on Airfoil CharacteristicsEffect of Camber and Angles of Attack on Airfoil Characteristics
Effect of Camber and Angles of Attack on Airfoil Characteristics
 
A Review on the Progress and Challenges of Aluminum-Based Metal Matrix Compos...
A Review on the Progress and Challenges of Aluminum-Based Metal Matrix Compos...A Review on the Progress and Challenges of Aluminum-Based Metal Matrix Compos...
A Review on the Progress and Challenges of Aluminum-Based Metal Matrix Compos...
 
Dynamic Urban Transit Optimization: A Graph Neural Network Approach for Real-...
Dynamic Urban Transit Optimization: A Graph Neural Network Approach for Real-...Dynamic Urban Transit Optimization: A Graph Neural Network Approach for Real-...
Dynamic Urban Transit Optimization: A Graph Neural Network Approach for Real-...
 
Structural Analysis and Design of Multi-Storey Symmetric and Asymmetric Shape...
Structural Analysis and Design of Multi-Storey Symmetric and Asymmetric Shape...Structural Analysis and Design of Multi-Storey Symmetric and Asymmetric Shape...
Structural Analysis and Design of Multi-Storey Symmetric and Asymmetric Shape...
 
A Review of “Seismic Response of RC Structures Having Plan and Vertical Irreg...
A Review of “Seismic Response of RC Structures Having Plan and Vertical Irreg...A Review of “Seismic Response of RC Structures Having Plan and Vertical Irreg...
A Review of “Seismic Response of RC Structures Having Plan and Vertical Irreg...
 
A REVIEW ON MACHINE LEARNING IN ADAS
A REVIEW ON MACHINE LEARNING IN ADASA REVIEW ON MACHINE LEARNING IN ADAS
A REVIEW ON MACHINE LEARNING IN ADAS
 
Long Term Trend Analysis of Precipitation and Temperature for Asosa district,...
Long Term Trend Analysis of Precipitation and Temperature for Asosa district,...Long Term Trend Analysis of Precipitation and Temperature for Asosa district,...
Long Term Trend Analysis of Precipitation and Temperature for Asosa district,...
 
P.E.B. Framed Structure Design and Analysis Using STAAD Pro
P.E.B. Framed Structure Design and Analysis Using STAAD ProP.E.B. Framed Structure Design and Analysis Using STAAD Pro
P.E.B. Framed Structure Design and Analysis Using STAAD Pro
 
A Review on Innovative Fiber Integration for Enhanced Reinforcement of Concre...
A Review on Innovative Fiber Integration for Enhanced Reinforcement of Concre...A Review on Innovative Fiber Integration for Enhanced Reinforcement of Concre...
A Review on Innovative Fiber Integration for Enhanced Reinforcement of Concre...
 
Survey Paper on Cloud-Based Secured Healthcare System
Survey Paper on Cloud-Based Secured Healthcare SystemSurvey Paper on Cloud-Based Secured Healthcare System
Survey Paper on Cloud-Based Secured Healthcare System
 
Review on studies and research on widening of existing concrete bridges
Review on studies and research on widening of existing concrete bridgesReview on studies and research on widening of existing concrete bridges
Review on studies and research on widening of existing concrete bridges
 
React based fullstack edtech web application
React based fullstack edtech web applicationReact based fullstack edtech web application
React based fullstack edtech web application
 
A Comprehensive Review of Integrating IoT and Blockchain Technologies in the ...
A Comprehensive Review of Integrating IoT and Blockchain Technologies in the ...A Comprehensive Review of Integrating IoT and Blockchain Technologies in the ...
A Comprehensive Review of Integrating IoT and Blockchain Technologies in the ...
 
A REVIEW ON THE PERFORMANCE OF COCONUT FIBRE REINFORCED CONCRETE.
A REVIEW ON THE PERFORMANCE OF COCONUT FIBRE REINFORCED CONCRETE.A REVIEW ON THE PERFORMANCE OF COCONUT FIBRE REINFORCED CONCRETE.
A REVIEW ON THE PERFORMANCE OF COCONUT FIBRE REINFORCED CONCRETE.
 
Optimizing Business Management Process Workflows: The Dynamic Influence of Mi...
Optimizing Business Management Process Workflows: The Dynamic Influence of Mi...Optimizing Business Management Process Workflows: The Dynamic Influence of Mi...
Optimizing Business Management Process Workflows: The Dynamic Influence of Mi...
 
Multistoried and Multi Bay Steel Building Frame by using Seismic Design
Multistoried and Multi Bay Steel Building Frame by using Seismic DesignMultistoried and Multi Bay Steel Building Frame by using Seismic Design
Multistoried and Multi Bay Steel Building Frame by using Seismic Design
 
Cost Optimization of Construction Using Plastic Waste as a Sustainable Constr...
Cost Optimization of Construction Using Plastic Waste as a Sustainable Constr...Cost Optimization of Construction Using Plastic Waste as a Sustainable Constr...
Cost Optimization of Construction Using Plastic Waste as a Sustainable Constr...
 

Recently uploaded

Introduction to Robotics in Mechanical Engineering.pptx
Introduction to Robotics in Mechanical Engineering.pptxIntroduction to Robotics in Mechanical Engineering.pptx
Introduction to Robotics in Mechanical Engineering.pptx
hublikarsn
 
Kuwait City MTP kit ((+919101817206)) Buy Abortion Pills Kuwait
Kuwait City MTP kit ((+919101817206)) Buy Abortion Pills KuwaitKuwait City MTP kit ((+919101817206)) Buy Abortion Pills Kuwait
Kuwait City MTP kit ((+919101817206)) Buy Abortion Pills Kuwait
jaanualu31
 
scipt v1.pptxcxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxx...
scipt v1.pptxcxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxx...scipt v1.pptxcxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxx...
scipt v1.pptxcxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxx...
HenryBriggs2
 
Integrated Test Rig For HTFE-25 - Neometrix
Integrated Test Rig For HTFE-25 - NeometrixIntegrated Test Rig For HTFE-25 - Neometrix
Integrated Test Rig For HTFE-25 - Neometrix
Neometrix_Engineering_Pvt_Ltd
 

Recently uploaded (20)

Ground Improvement Technique: Earth Reinforcement
Ground Improvement Technique: Earth ReinforcementGround Improvement Technique: Earth Reinforcement
Ground Improvement Technique: Earth Reinforcement
 
Introduction to Robotics in Mechanical Engineering.pptx
Introduction to Robotics in Mechanical Engineering.pptxIntroduction to Robotics in Mechanical Engineering.pptx
Introduction to Robotics in Mechanical Engineering.pptx
 
Kuwait City MTP kit ((+919101817206)) Buy Abortion Pills Kuwait
Kuwait City MTP kit ((+919101817206)) Buy Abortion Pills KuwaitKuwait City MTP kit ((+919101817206)) Buy Abortion Pills Kuwait
Kuwait City MTP kit ((+919101817206)) Buy Abortion Pills Kuwait
 
Introduction to Artificial Intelligence ( AI)
Introduction to Artificial Intelligence ( AI)Introduction to Artificial Intelligence ( AI)
Introduction to Artificial Intelligence ( AI)
 
Design For Accessibility: Getting it right from the start
Design For Accessibility: Getting it right from the startDesign For Accessibility: Getting it right from the start
Design For Accessibility: Getting it right from the start
 
School management system project Report.pdf
School management system project Report.pdfSchool management system project Report.pdf
School management system project Report.pdf
 
Post office management system project ..pdf
Post office management system project ..pdfPost office management system project ..pdf
Post office management system project ..pdf
 
S1S2 B.Arch MGU - HOA1&2 Module 3 -Temple Architecture of Kerala.pptx
S1S2 B.Arch MGU - HOA1&2 Module 3 -Temple Architecture of Kerala.pptxS1S2 B.Arch MGU - HOA1&2 Module 3 -Temple Architecture of Kerala.pptx
S1S2 B.Arch MGU - HOA1&2 Module 3 -Temple Architecture of Kerala.pptx
 
8th International Conference on Soft Computing, Mathematics and Control (SMC ...
8th International Conference on Soft Computing, Mathematics and Control (SMC ...8th International Conference on Soft Computing, Mathematics and Control (SMC ...
8th International Conference on Soft Computing, Mathematics and Control (SMC ...
 
scipt v1.pptxcxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxx...
scipt v1.pptxcxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxx...scipt v1.pptxcxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxx...
scipt v1.pptxcxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxx...
 
Basic Electronics for diploma students as per technical education Kerala Syll...
Basic Electronics for diploma students as per technical education Kerala Syll...Basic Electronics for diploma students as per technical education Kerala Syll...
Basic Electronics for diploma students as per technical education Kerala Syll...
 
Path loss model, OKUMURA Model, Hata Model
Path loss model, OKUMURA Model, Hata ModelPath loss model, OKUMURA Model, Hata Model
Path loss model, OKUMURA Model, Hata Model
 
Integrated Test Rig For HTFE-25 - Neometrix
Integrated Test Rig For HTFE-25 - NeometrixIntegrated Test Rig For HTFE-25 - Neometrix
Integrated Test Rig For HTFE-25 - Neometrix
 
8086 Microprocessor Architecture: 16-bit microprocessor
8086 Microprocessor Architecture: 16-bit microprocessor8086 Microprocessor Architecture: 16-bit microprocessor
8086 Microprocessor Architecture: 16-bit microprocessor
 
Danikor Product Catalog- Screw Feeder.pdf
Danikor Product Catalog- Screw Feeder.pdfDanikor Product Catalog- Screw Feeder.pdf
Danikor Product Catalog- Screw Feeder.pdf
 
NO1 Top No1 Amil Baba In Azad Kashmir, Kashmir Black Magic Specialist Expert ...
NO1 Top No1 Amil Baba In Azad Kashmir, Kashmir Black Magic Specialist Expert ...NO1 Top No1 Amil Baba In Azad Kashmir, Kashmir Black Magic Specialist Expert ...
NO1 Top No1 Amil Baba In Azad Kashmir, Kashmir Black Magic Specialist Expert ...
 
Worksharing and 3D Modeling with Revit.pptx
Worksharing and 3D Modeling with Revit.pptxWorksharing and 3D Modeling with Revit.pptx
Worksharing and 3D Modeling with Revit.pptx
 
Convergence of Robotics and Gen AI offers excellent opportunities for Entrepr...
Convergence of Robotics and Gen AI offers excellent opportunities for Entrepr...Convergence of Robotics and Gen AI offers excellent opportunities for Entrepr...
Convergence of Robotics and Gen AI offers excellent opportunities for Entrepr...
 
Electromagnetic relays used for power system .pptx
Electromagnetic relays used for power system .pptxElectromagnetic relays used for power system .pptx
Electromagnetic relays used for power system .pptx
 
Online food ordering system project report.pdf
Online food ordering system project report.pdfOnline food ordering system project report.pdf
Online food ordering system project report.pdf
 

Strength Evaluation of Reinforced Concrete Columns Eccentrically Concealed with CPVC and HDPE Rain Water Pipes

  • 1. International Research Journal of Engineering and Technology (IRJET) e-ISSN: 2395-0056 Volume: 09 Issue: 05 | May 2022 www.irjet.net p-ISSN: 2395-0072 © 2022, IRJET | Impact Factor value: 7.529 | ISO 9001:2008 Certified Journal | Page 1907 Strength Evaluation of Reinforced Concrete Columns Eccentrically Concealed with CPVC and HDPE Rain Water Pipes Himanshu Tamore1, Prof. Dipika Khandelwal2, Dr. Atul B. Pujari3 1PG Student, Department of Civil Engineering KJCOEMR, Pune, Maharashtra, India 2,3 Professor, Department of Civil Engineering KJCOEMR, Pune, Maharashtra, India ---------------------------------------------------------------------***--------------------------------------------------------------------- Abstract - Water plays a significant role in our lives since it is a precious natural resource. Over the past few years, there has been an increase in water shortages in several parts ofthe country. Ideal measures should be taken to reduce the high rate of water loss, one such measure is Rainwater Harvesting. Rain water harvesting is nothing but the collection and storage of rain water which runs off from roof tops, parks, roads, open grounds, etc. This water run off can be either stored or recharged into the ground water. In case of buildings, the conveyance system that is required to carry the water harvested from the catchment i.e the terraceareaofthe building is done through a series of pipes. These pipelines running through building facades are difficult to maintain and over a period of time they cause damage to the elevation of the building. Though rain water harvesting is a solution for a bigger problem of water scarcity and cannot be done away with, the damage to the elevation of any building structure due to these pipelines needs to be solved. One ofthesolutionto this is to conceal the pipes inside structural columns, however the strength of columns is effected by reinforcing ratios and cross sectional area which is reduced if pipes are placed in these columns, In this paper, strength evaluationofreinforced concrete columns eccentrically concealed with CVPC pipe and HDPE pipe with a concrete grade of M30 is done to compare its compressive strength and load carrying capability. The results concluded that column with CPVC pipe has a superior compressive strength and load carrying capability as compared to column with HDPE pipe. Key Words: Eccentrically Concealed column, CVPC pipe, HDPE pipe 1. INTRODUCTION Water is a precious, essential and an abiotic component of the ecosystem. Today we all are heading toward the scarcity of water and this is mainly because of the lack of water conservation and pollution of water bodies. Rain water harvesting is one measure through which wastage of runoff water from rooftops can be saved but the conveyance system which is used to transport theharvested water from the catchment to therechargezoneisrequiredto be placed all over building walls and this plumbing work on the surface of building is not very desirable and all the key players related to civil industry i.e architects, designers, developers, engineers would prefer to avoid it as due to weather conditions the deterioration of such plumbing works is very rapid and thereby it badly affects the elevational view of the building. To solve this problem, these pipes can be concealed within the structural members itself. In this paper, study is done on effect of CPVC Pipe and HDPE pipe when positioned eccentrically in a cross section of a column. Chlorinated polyvinyl chloride (CPVC) is a thermoplastic made by chlorinating polyvinyl chloride (PVC) resin. It is more flexible and has a higher compressive strength than PVC. It can also resist temperatures that are higher than conventional PVC. HDPE pipe is a flexible plastic pipe that is used to transport fluids and gases. HDPE (high-density polyethylene) is a thermoplastic with a high level of impermeability and a strong molecular bond,makingitideal for high-pressure pipelines. 2. METHODOLOGY The main objective of this study is to evaluate the load carrying capacity and compressive strength of a square reinforced short column with CPVC and HDPE pipes positioned eccentrically on the cross section of the column and compare it with a column that does not contain any pipe. 3. MIX DESIGN FOR M30 Initiation Mix design of M-30 of concrete with 20mm maximum size aggregate with medium workabilitybased on IS 10262-2009 and IS 456-2000 was done and the ratio obtained as mentioned in table 1 with a W/C ratio of 0.45. Table -1: Mix design proportioning Mix design Cement Fine aggregate Coarse aggregate 1 1.89 3.37 4. CUBE TESTING The cubes were cast on-site and tested on UTM as shown in Figure 1. The cubes were kept in the curing tank for 28 days after the formwork was removed, following result were obtained and mix design was foundto besatisfactory, results are shown in table 2
  • 2. International Research Journal of Engineering and Technology (IRJET) e-ISSN: 2395-0056 Volume: 09 Issue: 05 | May 2022 www.irjet.net p-ISSN: 2395-0072 © 2022, IRJET | Impact Factor value: 7.529 | ISO 9001:2008 Certified Journal | Page 1908 Table -2: Trial Mix results of concrete cube of grade M30 Trial Mix results Cube No Date of casting Date of testing Load [KN] Area [mm2] Compres sive Strength [N/mm2] Average Compres sive Strength [N/mm2] 1. 21/2/22 21/3/22 791.5 22500 35.1 34.24 2. 756.7 22500 33.6 3. 765.8 22500 34.3 Fig -1: Cube Testing 5. SPECIFICATION OF COLUMNS Three Short Columns of cross section 200 mm X 200 mm and length of 950 mm were designed, one was without any placement of pipe, other one with a placement of CPVC pipe of diameter 50 mm and last one with a placement of HDPE pipe of diameter 50 mm. The pipes were positioned eccentrically to the cross-section. The design Specificationof the columns are asshown in table 3 and casting ofcolumnsis shown in figure 2 and 3. Table -3: Specification of columns Specification of columns Column specimen Dimension of column(mm) Pipe diameterand type Vertical reinforcement Lateral ties C1 200 x 200 x 950 CPVC 50mm Ø 4 Nos of 12 mm Ø 8 mm Ø @ 150 mm c/c C2 200 x 200 x 950 HDPE 50mm Ø 4 Nos of 12 mm Ø 8 mm Ø @ 150 mm c/c C3 200 x 200 x 950 - 4 Nos of 12 mm Ø 8 mm Ø @ 150 mm c/c Fig -2: Column formwork Fig -3: Column casting with CPVC and HDPE pipe 6. CONCLUSIONS The test resultsare shown in table 4 and testing procedureis shown in figure 4, 5 and 6. The analysis reveals that inserting an HDPE drain pipe inside the column considerably affects the column's weight carrying capacity. When compared to a column concealed with HDPEpipe,acolumnwithCPVCdrain pipe and a solidcolumn has higher compressivestrengthand load carrying capacity. CPVC Pipe can be used as an alternative to PVC Pipe for concealing in a column as a rainwater drain pipe. It can be concluded that column with CPVC pipe has a superior compressive strength and load carrying capability as compared to column with HDPE pipe.
  • 3. International Research Journal of Engineering and Technology (IRJET) e-ISSN: 2395-0056 Volume: 09 Issue: 05 | May 2022 www.irjet.net p-ISSN: 2395-0072 © 2022, IRJET | Impact Factor value: 7.529 | ISO 9001:2008 Certified Journal | Page 1909 Table -4: Compressive Strength comparision Compressive Strength comparision Cracks Formation [KN] Sustained Compressive Load [KN] Failed at Compressive Load [KN] Column with no pipe 500 666 670 Column with CPCV pipe 183 914 915 Column with HDPE pipe 175 598 591 Fig -4: Testing on column without pipe Fig -5: Testing on column with CPVC pipe Fig -6: Testing on column with HDPE pipe REFERENCES [1] K-S. Sona, K. Pilakoutasb K. Neocleousc “Behaviour of Concrete Columns with Drilled Holes” Magazine of Concrete Research, 58 (7), pp. 411-419 [2] J. Bakhteri,w. Omar,a.M.Makhtar“Acritical reviewof the reinforced concrete columns and walls concealing rain water pipe in multistorey buildings”, (journal of civil engineering) vol. 15 no. 2, 2002 [3] J. Bakhteri, S. Iskandar“Experimentalstudyofreinforced concrete columns concealingrain water pipe” pp 13-26 .2005 [4] P.Wilson, E.M.S. Nair “Investigation on reinforced concrete columns with holes” Volume:04Issue05May - 2017 [5] A. S. Saadoon, N. A. Jasim “Empirical Design Equations For PVCConcrete CompositeColumns”Pp71-78Volume 6 Issue 10- October 2017 [6] R. W. Poston, T. E. Gilliam, Y. Yamamoto, and J. E. Breen “Hollow Concrete Bridge Pier Behavior”ACI Journal, pp 779-787, November december [7] E.A. Rodriguesa ,O.L. Manzolib L.A.G. Bitencourt Jr.,P.G.C.dosPrazeresa,T.N. Bittencourta “Failure behavior modeling of slender reinforced concrete columns subjected to eccentric load”. [8] R.Kumutha ,.K.Vijai “External confinement of plain and reinforced concrete columns using pvc pipes” 19th - 20th November 2016 [9] Mohanad M. Abdulazeez and Mohamed A. El Gawady “Seismic Behavior of Hollow- Core Composite Bridge Columns Having Slender Inner Steel Tubes” Volume: 117.Pg.143-158. [10] Indian Standard IS 456: 2000, “Plane and Reinforced concrete code of practice(Forth Revision)” [11] Indian Standard IS 10262: 2019, “Concrete Mix Proportioning – Guidelines (Second Revision)”