Seismic Evaluation of Base Isolated Overhead Water Storage Tank
1Arfat Rafiq, 2Mir Tabish Altaf, 3Shahid Rafeeq, 4Dr. Mohammad Umair
1M Tech student, Department of Civil Engineering, Jamia Millia Islamia, New Delhi, India
2 M Tech student, Department of Civil Engineering, Jamia Millia Islamia, New Delhi, India
3 B E student, Department of Civil Engineering, Jadavpur University, Kolkata, India
4Assistant Professor, Department of Civil Engineering, Jamia Millia Islamia, New Delhi, India
---------------------------------------------------------------------***---------------------------------------------------------------------
Abstract - This paper presents the seismic analysis of
reinforced concrete overhead water tank. An overhead
water tank is analyzed for seismic zone V as per IS 1893:
2016 using SAP 2000 software. Non-linear time history
analysis has been conducted to evaluate the behavior the
OWT (Overhead Water Tank) at different water levels under
the base fixed condition and base isolated conditions. The
main parameters consider in this seismic analysis of OWT
are lateral displacement, base shear and time period. From
the analysis it is found that the response of the tank depends
upon the support conditions, type of the quake, depth of
water level in the tank and shows a complex behavior. The
tank with fully filled gives maximum displacement in both
the cases, maximum base shear and maximum time period.
Tank with 75% water gives less displacement as compared
to 50% water that is mainly due to strong sloshing effects in
case of tank containing 75% water. Base isolation of
overhead water tank does not give us rigid body motion of
superstructure. There is a large relative displace at the
staging levels.
Key Words: OWT (Overhead Water Tank), Earthquake,
SAP 2000, Time history analysis, Displacement, Time
periods, Base shear.
1.INTRODUCTION
Elevated reservoirs are considered important structures
that must continue to function as soon as a large
earthquake happens, among other reasons to aid in relief
operations and stop fires from spreading. The reservoirs
are raised by creating a circular shaft or by staging. The
columns and horizontal braces of the structural
framework used for staging normally transfer the load to
the foundation. Reinforced concrete elevated water tanks
were proven to perform poorly under jolts of earthquakes.
Previous earthquakes damaged the supports of multiple
tall water tanks despite their moderate magnitude and
large epicentral distances. Because of this, the columns
and braces are essential components of such structures
and are built to withstand loads from wind and
earthquakes.
Expected seismic load is dependent on a number of
factors, including the area's seismicity, the kind of soil, the
structure's dynamic properties, etc. The structure's
natural time period and damping, which have a significant
impact on the anticipated seismic load, are its dynamic
properties. The seismic code IS: 1893(Part I): 2016 states
that more than 60% of India is earthquake-prone.
Elevated water tanks' seismic analyses differ from those of
other structures in two ways:
(i) Other constructions are not subject to the
sloshing effects that occur when the fluid
inside the tank exerts hydrodynamic force on
the tank walls during seismic excitation.
(ii) Elevated liquid storage tanks require more
design seismic forces than other structures
because they are less ductile and redundant,
necessitating rigorous seismic analysis and
exact determination of the design earthquake
load.
It has been determined to implement the "Indian Institute
of Technology, Kanpur-Gujarat State Disaster Management
Act" because the Indian Standard (IS) code for seismic
design does not have a provision on the seismic design of
OWTs. (IITK-GSDMA 2007) guidelines for the seismic
design of overhead liquid storage tanks (Moslemia et al.
2019).
1.1 SPRING-MASS IDEALIZATION OF OVERHEAD
WATER TANK
The idealized two DOF systems for OWTs with and without
water is composed of the impulsive mode and convective
mode, as well as a single DOF. There won't be convective
mode in the empty tank. Figure 1.4 illustrates the OWT's
idealized structural design. When an OWT with enough
free surface and water for the entire height is subjected to
ground acceleration from an earthquake, the tank wall and
water will both be excited horizontally. The water present
in the tank's lower container will function as a mass that is
rigidly attached to the tank wall during the earthquake
excitation. It is known as impulsive mass. The sloshing
effects will have an impact on the water in the upper part
of the tank, and this mass is known as convective mass.
Impulsive hydrodynamic pressure and convective
hydrodynamic pressure, respectively, are terms used to
describe the hydrodynamic pressure caused by impulsive
mass and convective mass. When analyzing the modal
behavior of filled tanks, a two-DOF system is split into two
International Research Journal of Engineering and Technology (IRJET) e-ISSN: 2395-0056
Volume: 10 Issue: 06 | Jun 2023 www.irjet.net p-ISSN: 2395-0072
International Research Journal of Engineering and Technology (IRJET) e-ISSN: 2395-0056
Volume: 10 Issue: 06 | Jun 2023 www.irjet.net p-ISSN: 2395-0072
© 2023, IRJET | Impact Factor value: 8.226 | ISO 9001:2008 Certified Journal | Page 837
single-DOF systems, and the responses of the two systems
are computed independently. Using the SRSS combination
rule, they are combined to obtain the entire response.
Figure 1: Structural idealization of an overhead water
filled tank.
1.2 BASE ISOLATION
Base isolation systems' principal purpose is to separate
the superstructure from the substructure, which is mostly
exposed to seismic excitation. As a result, some of the
energy that would have been delivered to the
superstructure will be lost. The foundation slab's mass and
the isolation devices' lateral stiffness must be fixed as
necessary. When isolation is offered, displacement at the
level of the isolation devices will be extremely high, and
the behavior of the superstructure will appear to be that of
a rigid body. However, this rigid movement is
questionable in the case of a highly elevated water tank
since the bulk is concentrated at the top. This study's
primary goal is to examine how elevated water tanks
function during earthquakes, both with and without base
isolation, and how that performance varies over a
fundamentally natural time span.
2. OBJECTIVES
In the absence of soil structure interaction, an elevated
reservoir is modeled as having a fixed base. We'll analyses
the elevated reservoir with its fluctuating water level. The
finite element approach will be used to analyses the raised
storage reservoir because it is the most effective analytical
technique currently available. Any combination and type of
loading can be analyzed using this method. In light of these
realities, the ensuing goals have been proposed. To study
the dynamic response of elevated water reservoir.
1. By considering variations in water levels, such as
for tank empty condition, 25%, 50%, 75% water
levels, and for full tank condition, the elevated
reservoir in linked condition (fixed base) will be
analyzed for a Bhuj earthquake using SAP2000.
2. In order to determine the seismic behavior under
all the aforementioned situations, SAP2000 will
also be used to analyze the elevated reservoir in an
uncoupled condition (base isolated using a rubber
base isolator).
In order to compare the maximum base shear, maximum
displacement, relative displacement, and time for all the
aforementioned examples in both coupled and decoupled
settings.
3. STRUCTURAL MODELLING AND ANALYSIS
Table -1: Dimensions of Elevated Reservoir
Capacity (m3) 9000m3
Total height of tank(m) 29m
Diameter of tank vessel(m) 12m
Depth of vessel(m) 8m
Diameter at bottom of vessel(m) 8.60m
Diameter at ground level(m) 11.00m
Table -2: Height of Staging Beams w.r.t Ground Level.
Components Height w.r.t ground (m)
Staging beam 1 5
Staging beam2 10
Staging beam 3 15
Top ring beam 20
Table -3: Member Properties
Column 700mmx700mm
Staging beams 600mmx500mm
Top ring beam 600mmx400mm
Top container dimensions
Top slab thickness 200mm
Bottom slab thickness 250mm
Thickness of wall of vessel 250mm
International Research Journal of Engineering and Technology (IRJET) e-ISSN: 2395-0056
Volume: 10 Issue: 06 | Jun 2023 www.irjet.net p-ISSN: 2395-0072
© 2023, IRJET | Impact Factor value: 8.226 | ISO 9001:2008 Certified Journal | Page 838
Table -4: Seismic Properties
Properties Values
Seismic Zone V
Zone factor 0.36
Soil type II
Response reduction factor 2.5
Importance factor 1.5
Table -5: Material Properties
Grade of concrete M30 &M25
Grade of Rebar Fe550, Fe500
Table -6: Properties of Isolator
Type of isolator
Lead Rubber Bearing
(LRB)
Effective Stiffness in
vertical direction (U1)
18073.750 N/m
Effective stiffness in lateral
direction (U2)
1087.157 N/m
For Nonlinear Analysis
Stiffness (each column) 5561.2N/m
Yield strength 54004.6N
Figure 2: Model of overhead water tank with base Fixed
Figure 3: Plan of overhead water tank.
Figure 4: Assigning water pressure(25%full)
Figure 5: Assigning water pressure(75%full)
International Research Journal of Engineering and Technology (IRJET) e-ISSN: 2395-0056
Volume: 10 Issue: 06 | Jun 2023 www.irjet.net p-ISSN: 2395-0072
© 2023, IRJET | Impact Factor value: 8.226 | ISO 9001:2008 Certified Journal | Page 839
4.STRUCTURAL MODELLING AND ANALYSIS
4.1 BASE SHEAR (kN)
Table -7: Maximum Base shear in X-Direction
Base shear
(KN)
FULL
75%
FULL
50%
FULL
25%
FULL
EMPTY
FIXED 847.6 823.9 815.9 795.3 754.7
ISOLATED 284.2 279.8 252.1 236.9 220.0
Graph1: Plot between base shear and water level in tank
4.2 MAXIMUM DISPLACEMENT (mm)
4.2.1 Base fixed
Maximum displacement is the measurement of the lateral
displacement that can occur along an elevation when a
lateral load is applied. Time history analysis is used to
determine the elevated tank's maximum displacement in
the X direction.
Table -8: Maximum displacement in the X direction
Joint
no.
Elevation
m
Full
mm
75%
full
mm
50%
full
mm
25%
full
mm
Empty
mm
4 28 34.4 28.5 32.8 32.9 21.2
3 22 36.4 29.9 34.6 34.7 21.9
2 20 36.9 30.5 35.2 35.2 22.1
190 15 29.5 24.5 28.2 28.5 18.1
182 10 17.6 14.9 17.1 17.3 11.7
174 5 6.1 5.3 5.9 6.1 4.5
1 0 0 0 0 0 0
Graph 2: Plot of Maximum Lateral Displacements (mm)
versus elevations
4.2.2 Base Isolated
Table -9: Maximum displacement in the X direction
Joint
no.
Elevation
(m)
Full
mm
75%
full
mm
50%
full
mm
25%
full
mm
Empty
mm
4 28 114.8 81.1 91.3 107.8 104.1
3 22 95.6 67.2 75.9 93.6 85.4
2 20 89.3 65.7 70.9 85.1 79.2
190 15 70.9 47.2 56.5 65.9 61.9
182 10 51.5 34.2 41.2 47.6 44.1
174 5 31.1 19.1 25.1 28.2 26.4
1 0 8.0 5.7 6.9 6.0 7.1
0
500
1000
FULL 75%FULL 50% FULL 25% FULL EMPTY
BASE
SHEAR
Plot of base shear (kN)
0 20 40
0
5
10
15
20
22
28
Displacement (mm)
Elevation
(m)
EMPTY
25% FULL
50% FULL
75% FULL
FULL
CONDITIONS
International Research Journal of Engineering and Technology (IRJET) e-ISSN: 2395-0056
Volume: 10 Issue: 06 | Jun 2023 www.irjet.net p-ISSN: 2395-0072
© 2023, IRJET | Impact Factor value: 8.226 | ISO 9001:2008 Certified Journal | Page 840
Graph 3: Plot of Maximum Lateral Displacements (mm)
versus elevations
4.3 TIME PERIOD (mm)
4.3.1 Base Fixed
Table -10: Time period (sec) for fixed base at different
filled conditions
MODE
SHAPES
FULL
75%
FULL
50%
FULL
25%
FULL
EMPTY
1 1.222367 1.106954 1.186606 0.909437 0.699998
2 1.222367 1.106954 1.186606 0.909437 0.699998
3 0.932209 0.85528 0.969135 0.702328 0.614996
4 0.18888 0.172141 0.174282 0.169879 0.16821
5 0.173292 0.172125 0.174266 0.169863 0.168194
6 0.173276 0.165701 0.140213 0.13839 0.13259
7 0.136432 0.135877 0.136656 0.134185 0.094457
8 0.133322 0.125749 0.132711 0.111601 0.094453
9 0.133307 0.125748 0.132697 0.111597 0.070637
10 0.088029 0.08056 0.088308 0.074178 0.070541
11 0.086878 0.07797 0.074685 0.07412 0.065851
12 0.086877 0.077957 0.074625 0.067512 0.063705
Graph 4: Time period of base fixed elevated water tank
4.3.2 Base Isolated
Table -11: Time period (sec) for base isolated tank at
different filled conditions
MODE
SHAPES
FULL
75%
FULL
50%
FULL
25% FULLEMPTY
1 4.969896 3.949627 3.601914 3.08715 2.809277
2 4.96971 3.729102 3.601657 2.912267 2.808933
3 2.751693 2.104742 2.012307 1.731251 1.704274
4 0.717368 0.642221 0.650298 0.618473 0.637443
5 0.705939 0.628704 0.64931 0.598503 0.636513
6 0.704874 0.546941 0.528231 0.435632 0.413725
7 0.281336 0.268785 0.265608 0.255758 0.252149
8 0.263346 0.232845 0.218478 0.197491 0.178578
9 0.262277 0.231853 0.218435 0.196742 0.178486
10 0.166644 0.143799 0.13506 0.132462 0.127978
11 0.136909 0.135149 0.134634 0.131706 0.127385
12 0.136502 0.134812 0.122312 0.10436 0.104484
0 50 100 150
0
5
10
15
20
22
28
DISPLACEMENT (MM)
ELEVATION
(M)
EMPTY
25% FULL
50% FULL
75% FULL
FULL
0
0.2
0.4
0.6
0.8
1
1.2
1.4
1 2 3 4 5 6 7 8 9 101112
Time
period
(sec)
MODE NUMBER
FULL
75% FULL
50% FULL
25% FULL
EMPTY
International Research Journal of Engineering and Technology (IRJET) e-ISSN: 2395-0056
Volume: 10 Issue: 06 | Jun 2023 www.irjet.net p-ISSN: 2395-0072
© 2023, IRJET | Impact Factor value: 8.226 | ISO 9001:2008 Certified Journal | Page 841
Graph 5: Time period of base isolated elevated water tank
3. CONCLUSIONS
Utilizing the technique of Time history Analysis, the
seismic performances of OWTs subjected to the Bhuj
earthquake have been examined. Different seismic
reaction characteristics, such as base shear, maximum
displacement, time period, etc., were considered. The
resulting results are as follows, which are presented.
 In the case of the basic fixed condition, the time
period is maximum for a fully filled above water
tank and asynchronous for other circumstances,
such as when the tank is only 75% full. This may
be mostly because the 75% full tank has severe
sloshing effects.
 When compared to a base fixed elevated
reservoir, the time period is longer in the case of a
base separated overhead water tank. The time
period likewise grows with the depth of the water
level in the base-isolated elevated water tank.
 In the case of a base-fixed elevated reservoir, the
base shear rises with tank depth; it is maximum
for fully filled tanks and minimum for empty ones.
 Although the base shear can be reduced by
utilizing a base isolator, the behavior is still
comparable to that of a base-fixed elevated
reservoir, i.e., maximal for a fully filled state and
decreasing with a drop in the tank's water level.
 In the case of a fixed support system, the location
where the supporting system joins the container
experiences the most displacement.
 In the case of a base-isolated overhead water
tank, the system's greatest displacement occurs at
the roof level, with maximum displacement
occurring in the full condition and decreasing
percentages of 25%, 50%, and 75% in that order.
 No stiff body movement was seen in the base
isolated OWT under earthquake excitation.
REFERENCES
[1] Sanket Nimbekar et al 2021 IOP Conf. Ser.: Mater.
Sci. Eng. 1197 012016 “Seismic Response Control of
Elevated Water Tank using Base Isolation: A Review.
Young, The Technical Writer’s Handbook. Mill Valley,
CA: University Science, 1989.
[2] Nayak et al 2012, “Seismic response of partially filled
rectangular liquid tank”, Fourth International
Congress on Computational Mechanics and
Simulation”, 9- 12 Dec 2012, Hyderabad, India. K.
Elissa, “Title of paper if known,” unpublished.
[3] F. Omidinasab et al KSCE Journal of Civil Engineering
(2012) 16(3):366-376, Seismic Response Evaluation
of the RC Elevated Water Tank with Fluid Structure
Interaction and Earthquake Ensemble.
[4] B. Waghmare and N. M. Kanhe, "Seismic Response of
Isolated Liquid Storage Tanks with Elastomeric
Bearings (2013)."
[5] Ankesh Birtharia and Sarvesh K Jain “SEISMIC
RESPONSE OF ELEVATED WATER TANKS: AN
OVERVIEW”, International Research Journal of
Engineering and Technology (IRJET) e-ISSN: 2395-
0056 Volume: 02 Issue: 04 | July-2015.
[6] S.C. Potnis et al, "Earthquake response of the liquid
storage tank with various isolation systems (2013)."
International Journal of Application or Innovation in
Engineering & Management (IJAIEM) ISSN 2319 –
4847 Volume 2, Issue 11, November 2013.
[7] Mrs. Meet Motwani, “Vibration Control of Elevated
Water Tank Using Different Seismic Control
Techniques – A Review”, International Journal of
Latest Engineering Research and Application (IJLERA)
ISSN: 2455-7137 Volume – 02, Issue – 05, May – 2017,
PP – 58-63.
[8] Nasser Dine et al, “International Journal of Innovative
Technology and Exploring Engineering (IJITEE) ISSN:
2278-3075, Volume-9 Issue-9, July 2020.
0
1
2
3
4
5
6
1 2 3 4 5 6 7 8 9 10 11 12
time
period
(sec)
MODE NUMBER
FULL
75%
FULL
50%
FULL
International Research Journal of Engineering and Technology (IRJET) e-ISSN: 2395-0056
Volume: 10 Issue: 06 | Jun 2023 www.irjet.net p-ISSN: 2395-0072
© 2023, IRJET | Impact Factor value: 8.226 | ISO 9001:2008 Certified Journal | Page 842
[9] Suyash Nerkar1 et al, “Seismic behavior of elevated
storage reservoir by finite element method’’,
International Journal of Advanced Technology in
Engineering and Science -Vol. No. 4 Special issue no.
01, March 2016. 41
[10] ] Ahmet H. Deringol & HuseyinBilgin 2018, ‘Effects of
the isolation parameters on the seismic response of
steel frames’, Earthquakes and Structures, An Int'l
Journal, vol. 15, no. 3.
[11] Anil K. Chopra 2012, ‘Dynamics of Structures’, Fourth
Edition, Dorling Kindersley (India) Private Limited,
New Delhi, India.
[12] Ahmet H. Deringol & HuseyinBilgin 2018, ‘Effects of
the isolation parameters on the seismic response of
steel frames’, Earthquakes and Structures, An Int'l
Journal, vol. 15, no. 3.
[13] Centre for Engineering Strong Motion Data (CESMD),
US Geology Survey
(https://www.strongmotioncenter.org/).
[14] Chen JZ & Kianoush MR 2009, ‘Generalized SDOF
System for Seismic Analysis of Concrete Rectangular
Liquid Storage Tanks’, Engineering Structures, vol. 31,
no. 10, pp. 2426-2435. [16] Claudia Mori, Stefano
Sorace & Gloria Terenzi 2015, ‘Seismic Assessment
and Retrofit of Two Heritage-Listed R/C Elevated
Water Storage Tanks’, Soil Dynamics and Earthquake
Engineering, vol. 77, pp. 123-136.
[15] Hashemi S, Saadatpour MM & Kianoush MR 2013,
‘Dynamic analysis of flexible rectangular fluid
containers subjected to horizontal ground motion’
Earthquake Engg Struct. Dym., vol. 10. [19] Houser
GW 1963b, ‘The dynamic behavior of water tanks’,
Bulletin of Seismological Society of America, vol. 53,
No. 2, pp. 381-387.
[16] Halil Sezen, Ramazan Livaoglu & Adem Dogangun
2008, ‘Dynamic analysis and seismic performance
evaluation of above-ground liquid-containing tanks’,
Engineering Structures, vol. 30, pp. 794-803.
BIOGRAPHIES
ARFAT RAFIQ,
MTech (Earthquake Engineering)
Dept. of Civil Engineering,
Jamia Millia Islamia, New Delhi.
MIR TABISH ALTAF,
MTech (Earthquake Engineering)
Dept. of Civil Engineering,
Jamia Millia Islamia, New Delhi.
SHAHID RAFEEQ,
B E (Civil Engineering)
Dept. of Civil Engineering,
Jadavpur university, Kolkata.
DR. MOHAMMAD UMAIR,
Assistant Professor
Dept. of Civil Engineering,
Jamia Millia Islamia, New Delhi.

More Related Content

Similar to Seismic Evaluation of Base Isolated Overhead Water Storage Tank

Seismic Performance of Reinforced Cement Concrete Structures with and Without...
Seismic Performance of Reinforced Cement Concrete Structures with and Without...Seismic Performance of Reinforced Cement Concrete Structures with and Without...
Seismic Performance of Reinforced Cement Concrete Structures with and Without...
ijtsrd
 
Time History Analysis of Circular and Rectangular Elevated Water Storage Tank...
Time History Analysis of Circular and Rectangular Elevated Water Storage Tank...Time History Analysis of Circular and Rectangular Elevated Water Storage Tank...
Time History Analysis of Circular and Rectangular Elevated Water Storage Tank...
Dr. Amarjeet Singh
 

Similar to Seismic Evaluation of Base Isolated Overhead Water Storage Tank (20)

Intze Tank : A Brief Survey
Intze Tank : A Brief SurveyIntze Tank : A Brief Survey
Intze Tank : A Brief Survey
 
RESPONSE OF ELEVATED WATER STORAGE TANKS UNDER SEISMIC EVENTS
RESPONSE OF ELEVATED WATER STORAGE TANKS UNDER SEISMIC EVENTSRESPONSE OF ELEVATED WATER STORAGE TANKS UNDER SEISMIC EVENTS
RESPONSE OF ELEVATED WATER STORAGE TANKS UNDER SEISMIC EVENTS
 
IRJET- Comparative Analysis of Effects of Base Isolator & Fluid Viscous Dampe...
IRJET- Comparative Analysis of Effects of Base Isolator & Fluid Viscous Dampe...IRJET- Comparative Analysis of Effects of Base Isolator & Fluid Viscous Dampe...
IRJET- Comparative Analysis of Effects of Base Isolator & Fluid Viscous Dampe...
 
IRJET- Analysis of CR TOWER G+6 Buildings Having Top Rectangular Water Ta...
IRJET-  	  Analysis of CR TOWER G+6 Buildings Having Top Rectangular Water Ta...IRJET-  	  Analysis of CR TOWER G+6 Buildings Having Top Rectangular Water Ta...
IRJET- Analysis of CR TOWER G+6 Buildings Having Top Rectangular Water Ta...
 
SEISMIC ANALYSIS OF HYBRID STRUCTURAL CONTROL SYSTEM IN RC BUILDING
SEISMIC ANALYSIS OF HYBRID STRUCTURAL CONTROL SYSTEM IN RC BUILDINGSEISMIC ANALYSIS OF HYBRID STRUCTURAL CONTROL SYSTEM IN RC BUILDING
SEISMIC ANALYSIS OF HYBRID STRUCTURAL CONTROL SYSTEM IN RC BUILDING
 
IRJET- Comparison of Ductility of M20 and M25 Concrete in Elevated Tank Staging
IRJET- Comparison of Ductility of M20 and M25 Concrete in Elevated Tank StagingIRJET- Comparison of Ductility of M20 and M25 Concrete in Elevated Tank Staging
IRJET- Comparison of Ductility of M20 and M25 Concrete in Elevated Tank Staging
 
Performance Study of Elevated Water Tanks under Seismic Forces
Performance Study of Elevated Water Tanks under Seismic ForcesPerformance Study of Elevated Water Tanks under Seismic Forces
Performance Study of Elevated Water Tanks under Seismic Forces
 
SEISMIC RESPONSE STUDY OF MULTI-STORIED REINFORCED CONCRETE BUILDING WITH FLU...
SEISMIC RESPONSE STUDY OF MULTI-STORIED REINFORCED CONCRETE BUILDING WITH FLU...SEISMIC RESPONSE STUDY OF MULTI-STORIED REINFORCED CONCRETE BUILDING WITH FLU...
SEISMIC RESPONSE STUDY OF MULTI-STORIED REINFORCED CONCRETE BUILDING WITH FLU...
 
Design and analysis for supporting system of circular ESR for different seism...
Design and analysis for supporting system of circular ESR for different seism...Design and analysis for supporting system of circular ESR for different seism...
Design and analysis for supporting system of circular ESR for different seism...
 
A Review on Offshore Wind Turbine Foundations
A Review on Offshore Wind Turbine FoundationsA Review on Offshore Wind Turbine Foundations
A Review on Offshore Wind Turbine Foundations
 
IRJET- Time History Analysis of Multi Story Building with and without Base Is...
IRJET- Time History Analysis of Multi Story Building with and without Base Is...IRJET- Time History Analysis of Multi Story Building with and without Base Is...
IRJET- Time History Analysis of Multi Story Building with and without Base Is...
 
IRJET- Case study on Lead Rubber Isolation Bearing
IRJET- Case study on Lead Rubber Isolation BearingIRJET- Case study on Lead Rubber Isolation Bearing
IRJET- Case study on Lead Rubber Isolation Bearing
 
IRJET-Analysis of Offshore Jacket Structure
IRJET-Analysis of Offshore Jacket StructureIRJET-Analysis of Offshore Jacket Structure
IRJET-Analysis of Offshore Jacket Structure
 
Seismic Performance of Reinforced Cement Concrete Structures with and Without...
Seismic Performance of Reinforced Cement Concrete Structures with and Without...Seismic Performance of Reinforced Cement Concrete Structures with and Without...
Seismic Performance of Reinforced Cement Concrete Structures with and Without...
 
IRJET- Displacement & Cost Analysis of Bottom Ring Beam and Foundation of R.C...
IRJET- Displacement & Cost Analysis of Bottom Ring Beam and Foundation of R.C...IRJET- Displacement & Cost Analysis of Bottom Ring Beam and Foundation of R.C...
IRJET- Displacement & Cost Analysis of Bottom Ring Beam and Foundation of R.C...
 
IRJET- Analysis of Multi-Storey Buildings using Water Tank as a Liquid Damper...
IRJET- Analysis of Multi-Storey Buildings using Water Tank as a Liquid Damper...IRJET- Analysis of Multi-Storey Buildings using Water Tank as a Liquid Damper...
IRJET- Analysis of Multi-Storey Buildings using Water Tank as a Liquid Damper...
 
A Study of Dynamic Response of Circular Water Tank with Baffle Walls
A Study of Dynamic Response of Circular Water Tank with Baffle WallsA Study of Dynamic Response of Circular Water Tank with Baffle Walls
A Study of Dynamic Response of Circular Water Tank with Baffle Walls
 
IRJET- Estimation of Intze Water Tank by User Graphical Interface
IRJET- Estimation of Intze Water Tank by User Graphical InterfaceIRJET- Estimation of Intze Water Tank by User Graphical Interface
IRJET- Estimation of Intze Water Tank by User Graphical Interface
 
Time History Analysis of Circular and Rectangular Elevated Water Storage Tank...
Time History Analysis of Circular and Rectangular Elevated Water Storage Tank...Time History Analysis of Circular and Rectangular Elevated Water Storage Tank...
Time History Analysis of Circular and Rectangular Elevated Water Storage Tank...
 
IRJET- Dynamic Analysis of Rectangular and Circular RCC Silos
IRJET- Dynamic Analysis of Rectangular and Circular RCC SilosIRJET- Dynamic Analysis of Rectangular and Circular RCC Silos
IRJET- Dynamic Analysis of Rectangular and Circular RCC Silos
 

More from IRJET Journal

More from IRJET Journal (20)

TUNNELING IN HIMALAYAS WITH NATM METHOD: A SPECIAL REFERENCES TO SUNGAL TUNNE...
TUNNELING IN HIMALAYAS WITH NATM METHOD: A SPECIAL REFERENCES TO SUNGAL TUNNE...TUNNELING IN HIMALAYAS WITH NATM METHOD: A SPECIAL REFERENCES TO SUNGAL TUNNE...
TUNNELING IN HIMALAYAS WITH NATM METHOD: A SPECIAL REFERENCES TO SUNGAL TUNNE...
 
STUDY THE EFFECT OF RESPONSE REDUCTION FACTOR ON RC FRAMED STRUCTURE
STUDY THE EFFECT OF RESPONSE REDUCTION FACTOR ON RC FRAMED STRUCTURESTUDY THE EFFECT OF RESPONSE REDUCTION FACTOR ON RC FRAMED STRUCTURE
STUDY THE EFFECT OF RESPONSE REDUCTION FACTOR ON RC FRAMED STRUCTURE
 
A COMPARATIVE ANALYSIS OF RCC ELEMENT OF SLAB WITH STARK STEEL (HYSD STEEL) A...
A COMPARATIVE ANALYSIS OF RCC ELEMENT OF SLAB WITH STARK STEEL (HYSD STEEL) A...A COMPARATIVE ANALYSIS OF RCC ELEMENT OF SLAB WITH STARK STEEL (HYSD STEEL) A...
A COMPARATIVE ANALYSIS OF RCC ELEMENT OF SLAB WITH STARK STEEL (HYSD STEEL) A...
 
Effect of Camber and Angles of Attack on Airfoil Characteristics
Effect of Camber and Angles of Attack on Airfoil CharacteristicsEffect of Camber and Angles of Attack on Airfoil Characteristics
Effect of Camber and Angles of Attack on Airfoil Characteristics
 
A Review on the Progress and Challenges of Aluminum-Based Metal Matrix Compos...
A Review on the Progress and Challenges of Aluminum-Based Metal Matrix Compos...A Review on the Progress and Challenges of Aluminum-Based Metal Matrix Compos...
A Review on the Progress and Challenges of Aluminum-Based Metal Matrix Compos...
 
Dynamic Urban Transit Optimization: A Graph Neural Network Approach for Real-...
Dynamic Urban Transit Optimization: A Graph Neural Network Approach for Real-...Dynamic Urban Transit Optimization: A Graph Neural Network Approach for Real-...
Dynamic Urban Transit Optimization: A Graph Neural Network Approach for Real-...
 
Structural Analysis and Design of Multi-Storey Symmetric and Asymmetric Shape...
Structural Analysis and Design of Multi-Storey Symmetric and Asymmetric Shape...Structural Analysis and Design of Multi-Storey Symmetric and Asymmetric Shape...
Structural Analysis and Design of Multi-Storey Symmetric and Asymmetric Shape...
 
A Review of “Seismic Response of RC Structures Having Plan and Vertical Irreg...
A Review of “Seismic Response of RC Structures Having Plan and Vertical Irreg...A Review of “Seismic Response of RC Structures Having Plan and Vertical Irreg...
A Review of “Seismic Response of RC Structures Having Plan and Vertical Irreg...
 
A REVIEW ON MACHINE LEARNING IN ADAS
A REVIEW ON MACHINE LEARNING IN ADASA REVIEW ON MACHINE LEARNING IN ADAS
A REVIEW ON MACHINE LEARNING IN ADAS
 
Long Term Trend Analysis of Precipitation and Temperature for Asosa district,...
Long Term Trend Analysis of Precipitation and Temperature for Asosa district,...Long Term Trend Analysis of Precipitation and Temperature for Asosa district,...
Long Term Trend Analysis of Precipitation and Temperature for Asosa district,...
 
P.E.B. Framed Structure Design and Analysis Using STAAD Pro
P.E.B. Framed Structure Design and Analysis Using STAAD ProP.E.B. Framed Structure Design and Analysis Using STAAD Pro
P.E.B. Framed Structure Design and Analysis Using STAAD Pro
 
A Review on Innovative Fiber Integration for Enhanced Reinforcement of Concre...
A Review on Innovative Fiber Integration for Enhanced Reinforcement of Concre...A Review on Innovative Fiber Integration for Enhanced Reinforcement of Concre...
A Review on Innovative Fiber Integration for Enhanced Reinforcement of Concre...
 
Survey Paper on Cloud-Based Secured Healthcare System
Survey Paper on Cloud-Based Secured Healthcare SystemSurvey Paper on Cloud-Based Secured Healthcare System
Survey Paper on Cloud-Based Secured Healthcare System
 
Review on studies and research on widening of existing concrete bridges
Review on studies and research on widening of existing concrete bridgesReview on studies and research on widening of existing concrete bridges
Review on studies and research on widening of existing concrete bridges
 
React based fullstack edtech web application
React based fullstack edtech web applicationReact based fullstack edtech web application
React based fullstack edtech web application
 
A Comprehensive Review of Integrating IoT and Blockchain Technologies in the ...
A Comprehensive Review of Integrating IoT and Blockchain Technologies in the ...A Comprehensive Review of Integrating IoT and Blockchain Technologies in the ...
A Comprehensive Review of Integrating IoT and Blockchain Technologies in the ...
 
A REVIEW ON THE PERFORMANCE OF COCONUT FIBRE REINFORCED CONCRETE.
A REVIEW ON THE PERFORMANCE OF COCONUT FIBRE REINFORCED CONCRETE.A REVIEW ON THE PERFORMANCE OF COCONUT FIBRE REINFORCED CONCRETE.
A REVIEW ON THE PERFORMANCE OF COCONUT FIBRE REINFORCED CONCRETE.
 
Optimizing Business Management Process Workflows: The Dynamic Influence of Mi...
Optimizing Business Management Process Workflows: The Dynamic Influence of Mi...Optimizing Business Management Process Workflows: The Dynamic Influence of Mi...
Optimizing Business Management Process Workflows: The Dynamic Influence of Mi...
 
Multistoried and Multi Bay Steel Building Frame by using Seismic Design
Multistoried and Multi Bay Steel Building Frame by using Seismic DesignMultistoried and Multi Bay Steel Building Frame by using Seismic Design
Multistoried and Multi Bay Steel Building Frame by using Seismic Design
 
Cost Optimization of Construction Using Plastic Waste as a Sustainable Constr...
Cost Optimization of Construction Using Plastic Waste as a Sustainable Constr...Cost Optimization of Construction Using Plastic Waste as a Sustainable Constr...
Cost Optimization of Construction Using Plastic Waste as a Sustainable Constr...
 

Recently uploaded

"Lesotho Leaps Forward: A Chronicle of Transformative Developments"
"Lesotho Leaps Forward: A Chronicle of Transformative Developments""Lesotho Leaps Forward: A Chronicle of Transformative Developments"
"Lesotho Leaps Forward: A Chronicle of Transformative Developments"
mphochane1998
 
Kuwait City MTP kit ((+919101817206)) Buy Abortion Pills Kuwait
Kuwait City MTP kit ((+919101817206)) Buy Abortion Pills KuwaitKuwait City MTP kit ((+919101817206)) Buy Abortion Pills Kuwait
Kuwait City MTP kit ((+919101817206)) Buy Abortion Pills Kuwait
jaanualu31
 
DeepFakes presentation : brief idea of DeepFakes
DeepFakes presentation : brief idea of DeepFakesDeepFakes presentation : brief idea of DeepFakes
DeepFakes presentation : brief idea of DeepFakes
MayuraD1
 

Recently uploaded (20)

Thermal Engineering -unit - III & IV.ppt
Thermal Engineering -unit - III & IV.pptThermal Engineering -unit - III & IV.ppt
Thermal Engineering -unit - III & IV.ppt
 
"Lesotho Leaps Forward: A Chronicle of Transformative Developments"
"Lesotho Leaps Forward: A Chronicle of Transformative Developments""Lesotho Leaps Forward: A Chronicle of Transformative Developments"
"Lesotho Leaps Forward: A Chronicle of Transformative Developments"
 
Minimum and Maximum Modes of microprocessor 8086
Minimum and Maximum Modes of microprocessor 8086Minimum and Maximum Modes of microprocessor 8086
Minimum and Maximum Modes of microprocessor 8086
 
Hazard Identification (HAZID) vs. Hazard and Operability (HAZOP): A Comparati...
Hazard Identification (HAZID) vs. Hazard and Operability (HAZOP): A Comparati...Hazard Identification (HAZID) vs. Hazard and Operability (HAZOP): A Comparati...
Hazard Identification (HAZID) vs. Hazard and Operability (HAZOP): A Comparati...
 
data_management_and _data_science_cheat_sheet.pdf
data_management_and _data_science_cheat_sheet.pdfdata_management_and _data_science_cheat_sheet.pdf
data_management_and _data_science_cheat_sheet.pdf
 
Block diagram reduction techniques in control systems.ppt
Block diagram reduction techniques in control systems.pptBlock diagram reduction techniques in control systems.ppt
Block diagram reduction techniques in control systems.ppt
 
Introduction to Serverless with AWS Lambda
Introduction to Serverless with AWS LambdaIntroduction to Serverless with AWS Lambda
Introduction to Serverless with AWS Lambda
 
DC MACHINE-Motoring and generation, Armature circuit equation
DC MACHINE-Motoring and generation, Armature circuit equationDC MACHINE-Motoring and generation, Armature circuit equation
DC MACHINE-Motoring and generation, Armature circuit equation
 
Thermal Engineering Unit - I & II . ppt
Thermal Engineering  Unit - I & II . pptThermal Engineering  Unit - I & II . ppt
Thermal Engineering Unit - I & II . ppt
 
Online food ordering system project report.pdf
Online food ordering system project report.pdfOnline food ordering system project report.pdf
Online food ordering system project report.pdf
 
Kuwait City MTP kit ((+919101817206)) Buy Abortion Pills Kuwait
Kuwait City MTP kit ((+919101817206)) Buy Abortion Pills KuwaitKuwait City MTP kit ((+919101817206)) Buy Abortion Pills Kuwait
Kuwait City MTP kit ((+919101817206)) Buy Abortion Pills Kuwait
 
Unleashing the Power of the SORA AI lastest leap
Unleashing the Power of the SORA AI lastest leapUnleashing the Power of the SORA AI lastest leap
Unleashing the Power of the SORA AI lastest leap
 
kiln thermal load.pptx kiln tgermal load
kiln thermal load.pptx kiln tgermal loadkiln thermal load.pptx kiln tgermal load
kiln thermal load.pptx kiln tgermal load
 
AIRCANVAS[1].pdf mini project for btech students
AIRCANVAS[1].pdf mini project for btech studentsAIRCANVAS[1].pdf mini project for btech students
AIRCANVAS[1].pdf mini project for btech students
 
Design For Accessibility: Getting it right from the start
Design For Accessibility: Getting it right from the startDesign For Accessibility: Getting it right from the start
Design For Accessibility: Getting it right from the start
 
Double Revolving field theory-how the rotor develops torque
Double Revolving field theory-how the rotor develops torqueDouble Revolving field theory-how the rotor develops torque
Double Revolving field theory-how the rotor develops torque
 
Computer Lecture 01.pptxIntroduction to Computers
Computer Lecture 01.pptxIntroduction to ComputersComputer Lecture 01.pptxIntroduction to Computers
Computer Lecture 01.pptxIntroduction to Computers
 
A Study of Urban Area Plan for Pabna Municipality
A Study of Urban Area Plan for Pabna MunicipalityA Study of Urban Area Plan for Pabna Municipality
A Study of Urban Area Plan for Pabna Municipality
 
DeepFakes presentation : brief idea of DeepFakes
DeepFakes presentation : brief idea of DeepFakesDeepFakes presentation : brief idea of DeepFakes
DeepFakes presentation : brief idea of DeepFakes
 
Learn the concepts of Thermodynamics on Magic Marks
Learn the concepts of Thermodynamics on Magic MarksLearn the concepts of Thermodynamics on Magic Marks
Learn the concepts of Thermodynamics on Magic Marks
 

Seismic Evaluation of Base Isolated Overhead Water Storage Tank

  • 1. © 2023, IRJET | Impact Factor value: 8.226 | ISO 9001:2008 Certified Journal | Page 836 Seismic Evaluation of Base Isolated Overhead Water Storage Tank 1Arfat Rafiq, 2Mir Tabish Altaf, 3Shahid Rafeeq, 4Dr. Mohammad Umair 1M Tech student, Department of Civil Engineering, Jamia Millia Islamia, New Delhi, India 2 M Tech student, Department of Civil Engineering, Jamia Millia Islamia, New Delhi, India 3 B E student, Department of Civil Engineering, Jadavpur University, Kolkata, India 4Assistant Professor, Department of Civil Engineering, Jamia Millia Islamia, New Delhi, India ---------------------------------------------------------------------***--------------------------------------------------------------------- Abstract - This paper presents the seismic analysis of reinforced concrete overhead water tank. An overhead water tank is analyzed for seismic zone V as per IS 1893: 2016 using SAP 2000 software. Non-linear time history analysis has been conducted to evaluate the behavior the OWT (Overhead Water Tank) at different water levels under the base fixed condition and base isolated conditions. The main parameters consider in this seismic analysis of OWT are lateral displacement, base shear and time period. From the analysis it is found that the response of the tank depends upon the support conditions, type of the quake, depth of water level in the tank and shows a complex behavior. The tank with fully filled gives maximum displacement in both the cases, maximum base shear and maximum time period. Tank with 75% water gives less displacement as compared to 50% water that is mainly due to strong sloshing effects in case of tank containing 75% water. Base isolation of overhead water tank does not give us rigid body motion of superstructure. There is a large relative displace at the staging levels. Key Words: OWT (Overhead Water Tank), Earthquake, SAP 2000, Time history analysis, Displacement, Time periods, Base shear. 1.INTRODUCTION Elevated reservoirs are considered important structures that must continue to function as soon as a large earthquake happens, among other reasons to aid in relief operations and stop fires from spreading. The reservoirs are raised by creating a circular shaft or by staging. The columns and horizontal braces of the structural framework used for staging normally transfer the load to the foundation. Reinforced concrete elevated water tanks were proven to perform poorly under jolts of earthquakes. Previous earthquakes damaged the supports of multiple tall water tanks despite their moderate magnitude and large epicentral distances. Because of this, the columns and braces are essential components of such structures and are built to withstand loads from wind and earthquakes. Expected seismic load is dependent on a number of factors, including the area's seismicity, the kind of soil, the structure's dynamic properties, etc. The structure's natural time period and damping, which have a significant impact on the anticipated seismic load, are its dynamic properties. The seismic code IS: 1893(Part I): 2016 states that more than 60% of India is earthquake-prone. Elevated water tanks' seismic analyses differ from those of other structures in two ways: (i) Other constructions are not subject to the sloshing effects that occur when the fluid inside the tank exerts hydrodynamic force on the tank walls during seismic excitation. (ii) Elevated liquid storage tanks require more design seismic forces than other structures because they are less ductile and redundant, necessitating rigorous seismic analysis and exact determination of the design earthquake load. It has been determined to implement the "Indian Institute of Technology, Kanpur-Gujarat State Disaster Management Act" because the Indian Standard (IS) code for seismic design does not have a provision on the seismic design of OWTs. (IITK-GSDMA 2007) guidelines for the seismic design of overhead liquid storage tanks (Moslemia et al. 2019). 1.1 SPRING-MASS IDEALIZATION OF OVERHEAD WATER TANK The idealized two DOF systems for OWTs with and without water is composed of the impulsive mode and convective mode, as well as a single DOF. There won't be convective mode in the empty tank. Figure 1.4 illustrates the OWT's idealized structural design. When an OWT with enough free surface and water for the entire height is subjected to ground acceleration from an earthquake, the tank wall and water will both be excited horizontally. The water present in the tank's lower container will function as a mass that is rigidly attached to the tank wall during the earthquake excitation. It is known as impulsive mass. The sloshing effects will have an impact on the water in the upper part of the tank, and this mass is known as convective mass. Impulsive hydrodynamic pressure and convective hydrodynamic pressure, respectively, are terms used to describe the hydrodynamic pressure caused by impulsive mass and convective mass. When analyzing the modal behavior of filled tanks, a two-DOF system is split into two International Research Journal of Engineering and Technology (IRJET) e-ISSN: 2395-0056 Volume: 10 Issue: 06 | Jun 2023 www.irjet.net p-ISSN: 2395-0072
  • 2. International Research Journal of Engineering and Technology (IRJET) e-ISSN: 2395-0056 Volume: 10 Issue: 06 | Jun 2023 www.irjet.net p-ISSN: 2395-0072 © 2023, IRJET | Impact Factor value: 8.226 | ISO 9001:2008 Certified Journal | Page 837 single-DOF systems, and the responses of the two systems are computed independently. Using the SRSS combination rule, they are combined to obtain the entire response. Figure 1: Structural idealization of an overhead water filled tank. 1.2 BASE ISOLATION Base isolation systems' principal purpose is to separate the superstructure from the substructure, which is mostly exposed to seismic excitation. As a result, some of the energy that would have been delivered to the superstructure will be lost. The foundation slab's mass and the isolation devices' lateral stiffness must be fixed as necessary. When isolation is offered, displacement at the level of the isolation devices will be extremely high, and the behavior of the superstructure will appear to be that of a rigid body. However, this rigid movement is questionable in the case of a highly elevated water tank since the bulk is concentrated at the top. This study's primary goal is to examine how elevated water tanks function during earthquakes, both with and without base isolation, and how that performance varies over a fundamentally natural time span. 2. OBJECTIVES In the absence of soil structure interaction, an elevated reservoir is modeled as having a fixed base. We'll analyses the elevated reservoir with its fluctuating water level. The finite element approach will be used to analyses the raised storage reservoir because it is the most effective analytical technique currently available. Any combination and type of loading can be analyzed using this method. In light of these realities, the ensuing goals have been proposed. To study the dynamic response of elevated water reservoir. 1. By considering variations in water levels, such as for tank empty condition, 25%, 50%, 75% water levels, and for full tank condition, the elevated reservoir in linked condition (fixed base) will be analyzed for a Bhuj earthquake using SAP2000. 2. In order to determine the seismic behavior under all the aforementioned situations, SAP2000 will also be used to analyze the elevated reservoir in an uncoupled condition (base isolated using a rubber base isolator). In order to compare the maximum base shear, maximum displacement, relative displacement, and time for all the aforementioned examples in both coupled and decoupled settings. 3. STRUCTURAL MODELLING AND ANALYSIS Table -1: Dimensions of Elevated Reservoir Capacity (m3) 9000m3 Total height of tank(m) 29m Diameter of tank vessel(m) 12m Depth of vessel(m) 8m Diameter at bottom of vessel(m) 8.60m Diameter at ground level(m) 11.00m Table -2: Height of Staging Beams w.r.t Ground Level. Components Height w.r.t ground (m) Staging beam 1 5 Staging beam2 10 Staging beam 3 15 Top ring beam 20 Table -3: Member Properties Column 700mmx700mm Staging beams 600mmx500mm Top ring beam 600mmx400mm Top container dimensions Top slab thickness 200mm Bottom slab thickness 250mm Thickness of wall of vessel 250mm
  • 3. International Research Journal of Engineering and Technology (IRJET) e-ISSN: 2395-0056 Volume: 10 Issue: 06 | Jun 2023 www.irjet.net p-ISSN: 2395-0072 © 2023, IRJET | Impact Factor value: 8.226 | ISO 9001:2008 Certified Journal | Page 838 Table -4: Seismic Properties Properties Values Seismic Zone V Zone factor 0.36 Soil type II Response reduction factor 2.5 Importance factor 1.5 Table -5: Material Properties Grade of concrete M30 &M25 Grade of Rebar Fe550, Fe500 Table -6: Properties of Isolator Type of isolator Lead Rubber Bearing (LRB) Effective Stiffness in vertical direction (U1) 18073.750 N/m Effective stiffness in lateral direction (U2) 1087.157 N/m For Nonlinear Analysis Stiffness (each column) 5561.2N/m Yield strength 54004.6N Figure 2: Model of overhead water tank with base Fixed Figure 3: Plan of overhead water tank. Figure 4: Assigning water pressure(25%full) Figure 5: Assigning water pressure(75%full)
  • 4. International Research Journal of Engineering and Technology (IRJET) e-ISSN: 2395-0056 Volume: 10 Issue: 06 | Jun 2023 www.irjet.net p-ISSN: 2395-0072 © 2023, IRJET | Impact Factor value: 8.226 | ISO 9001:2008 Certified Journal | Page 839 4.STRUCTURAL MODELLING AND ANALYSIS 4.1 BASE SHEAR (kN) Table -7: Maximum Base shear in X-Direction Base shear (KN) FULL 75% FULL 50% FULL 25% FULL EMPTY FIXED 847.6 823.9 815.9 795.3 754.7 ISOLATED 284.2 279.8 252.1 236.9 220.0 Graph1: Plot between base shear and water level in tank 4.2 MAXIMUM DISPLACEMENT (mm) 4.2.1 Base fixed Maximum displacement is the measurement of the lateral displacement that can occur along an elevation when a lateral load is applied. Time history analysis is used to determine the elevated tank's maximum displacement in the X direction. Table -8: Maximum displacement in the X direction Joint no. Elevation m Full mm 75% full mm 50% full mm 25% full mm Empty mm 4 28 34.4 28.5 32.8 32.9 21.2 3 22 36.4 29.9 34.6 34.7 21.9 2 20 36.9 30.5 35.2 35.2 22.1 190 15 29.5 24.5 28.2 28.5 18.1 182 10 17.6 14.9 17.1 17.3 11.7 174 5 6.1 5.3 5.9 6.1 4.5 1 0 0 0 0 0 0 Graph 2: Plot of Maximum Lateral Displacements (mm) versus elevations 4.2.2 Base Isolated Table -9: Maximum displacement in the X direction Joint no. Elevation (m) Full mm 75% full mm 50% full mm 25% full mm Empty mm 4 28 114.8 81.1 91.3 107.8 104.1 3 22 95.6 67.2 75.9 93.6 85.4 2 20 89.3 65.7 70.9 85.1 79.2 190 15 70.9 47.2 56.5 65.9 61.9 182 10 51.5 34.2 41.2 47.6 44.1 174 5 31.1 19.1 25.1 28.2 26.4 1 0 8.0 5.7 6.9 6.0 7.1 0 500 1000 FULL 75%FULL 50% FULL 25% FULL EMPTY BASE SHEAR Plot of base shear (kN) 0 20 40 0 5 10 15 20 22 28 Displacement (mm) Elevation (m) EMPTY 25% FULL 50% FULL 75% FULL FULL CONDITIONS
  • 5. International Research Journal of Engineering and Technology (IRJET) e-ISSN: 2395-0056 Volume: 10 Issue: 06 | Jun 2023 www.irjet.net p-ISSN: 2395-0072 © 2023, IRJET | Impact Factor value: 8.226 | ISO 9001:2008 Certified Journal | Page 840 Graph 3: Plot of Maximum Lateral Displacements (mm) versus elevations 4.3 TIME PERIOD (mm) 4.3.1 Base Fixed Table -10: Time period (sec) for fixed base at different filled conditions MODE SHAPES FULL 75% FULL 50% FULL 25% FULL EMPTY 1 1.222367 1.106954 1.186606 0.909437 0.699998 2 1.222367 1.106954 1.186606 0.909437 0.699998 3 0.932209 0.85528 0.969135 0.702328 0.614996 4 0.18888 0.172141 0.174282 0.169879 0.16821 5 0.173292 0.172125 0.174266 0.169863 0.168194 6 0.173276 0.165701 0.140213 0.13839 0.13259 7 0.136432 0.135877 0.136656 0.134185 0.094457 8 0.133322 0.125749 0.132711 0.111601 0.094453 9 0.133307 0.125748 0.132697 0.111597 0.070637 10 0.088029 0.08056 0.088308 0.074178 0.070541 11 0.086878 0.07797 0.074685 0.07412 0.065851 12 0.086877 0.077957 0.074625 0.067512 0.063705 Graph 4: Time period of base fixed elevated water tank 4.3.2 Base Isolated Table -11: Time period (sec) for base isolated tank at different filled conditions MODE SHAPES FULL 75% FULL 50% FULL 25% FULLEMPTY 1 4.969896 3.949627 3.601914 3.08715 2.809277 2 4.96971 3.729102 3.601657 2.912267 2.808933 3 2.751693 2.104742 2.012307 1.731251 1.704274 4 0.717368 0.642221 0.650298 0.618473 0.637443 5 0.705939 0.628704 0.64931 0.598503 0.636513 6 0.704874 0.546941 0.528231 0.435632 0.413725 7 0.281336 0.268785 0.265608 0.255758 0.252149 8 0.263346 0.232845 0.218478 0.197491 0.178578 9 0.262277 0.231853 0.218435 0.196742 0.178486 10 0.166644 0.143799 0.13506 0.132462 0.127978 11 0.136909 0.135149 0.134634 0.131706 0.127385 12 0.136502 0.134812 0.122312 0.10436 0.104484 0 50 100 150 0 5 10 15 20 22 28 DISPLACEMENT (MM) ELEVATION (M) EMPTY 25% FULL 50% FULL 75% FULL FULL 0 0.2 0.4 0.6 0.8 1 1.2 1.4 1 2 3 4 5 6 7 8 9 101112 Time period (sec) MODE NUMBER FULL 75% FULL 50% FULL 25% FULL EMPTY
  • 6. International Research Journal of Engineering and Technology (IRJET) e-ISSN: 2395-0056 Volume: 10 Issue: 06 | Jun 2023 www.irjet.net p-ISSN: 2395-0072 © 2023, IRJET | Impact Factor value: 8.226 | ISO 9001:2008 Certified Journal | Page 841 Graph 5: Time period of base isolated elevated water tank 3. CONCLUSIONS Utilizing the technique of Time history Analysis, the seismic performances of OWTs subjected to the Bhuj earthquake have been examined. Different seismic reaction characteristics, such as base shear, maximum displacement, time period, etc., were considered. The resulting results are as follows, which are presented.  In the case of the basic fixed condition, the time period is maximum for a fully filled above water tank and asynchronous for other circumstances, such as when the tank is only 75% full. This may be mostly because the 75% full tank has severe sloshing effects.  When compared to a base fixed elevated reservoir, the time period is longer in the case of a base separated overhead water tank. The time period likewise grows with the depth of the water level in the base-isolated elevated water tank.  In the case of a base-fixed elevated reservoir, the base shear rises with tank depth; it is maximum for fully filled tanks and minimum for empty ones.  Although the base shear can be reduced by utilizing a base isolator, the behavior is still comparable to that of a base-fixed elevated reservoir, i.e., maximal for a fully filled state and decreasing with a drop in the tank's water level.  In the case of a fixed support system, the location where the supporting system joins the container experiences the most displacement.  In the case of a base-isolated overhead water tank, the system's greatest displacement occurs at the roof level, with maximum displacement occurring in the full condition and decreasing percentages of 25%, 50%, and 75% in that order.  No stiff body movement was seen in the base isolated OWT under earthquake excitation. REFERENCES [1] Sanket Nimbekar et al 2021 IOP Conf. Ser.: Mater. Sci. Eng. 1197 012016 “Seismic Response Control of Elevated Water Tank using Base Isolation: A Review. Young, The Technical Writer’s Handbook. Mill Valley, CA: University Science, 1989. [2] Nayak et al 2012, “Seismic response of partially filled rectangular liquid tank”, Fourth International Congress on Computational Mechanics and Simulation”, 9- 12 Dec 2012, Hyderabad, India. K. Elissa, “Title of paper if known,” unpublished. [3] F. Omidinasab et al KSCE Journal of Civil Engineering (2012) 16(3):366-376, Seismic Response Evaluation of the RC Elevated Water Tank with Fluid Structure Interaction and Earthquake Ensemble. [4] B. Waghmare and N. M. Kanhe, "Seismic Response of Isolated Liquid Storage Tanks with Elastomeric Bearings (2013)." [5] Ankesh Birtharia and Sarvesh K Jain “SEISMIC RESPONSE OF ELEVATED WATER TANKS: AN OVERVIEW”, International Research Journal of Engineering and Technology (IRJET) e-ISSN: 2395- 0056 Volume: 02 Issue: 04 | July-2015. [6] S.C. Potnis et al, "Earthquake response of the liquid storage tank with various isolation systems (2013)." International Journal of Application or Innovation in Engineering & Management (IJAIEM) ISSN 2319 – 4847 Volume 2, Issue 11, November 2013. [7] Mrs. Meet Motwani, “Vibration Control of Elevated Water Tank Using Different Seismic Control Techniques – A Review”, International Journal of Latest Engineering Research and Application (IJLERA) ISSN: 2455-7137 Volume – 02, Issue – 05, May – 2017, PP – 58-63. [8] Nasser Dine et al, “International Journal of Innovative Technology and Exploring Engineering (IJITEE) ISSN: 2278-3075, Volume-9 Issue-9, July 2020. 0 1 2 3 4 5 6 1 2 3 4 5 6 7 8 9 10 11 12 time period (sec) MODE NUMBER FULL 75% FULL 50% FULL
  • 7. International Research Journal of Engineering and Technology (IRJET) e-ISSN: 2395-0056 Volume: 10 Issue: 06 | Jun 2023 www.irjet.net p-ISSN: 2395-0072 © 2023, IRJET | Impact Factor value: 8.226 | ISO 9001:2008 Certified Journal | Page 842 [9] Suyash Nerkar1 et al, “Seismic behavior of elevated storage reservoir by finite element method’’, International Journal of Advanced Technology in Engineering and Science -Vol. No. 4 Special issue no. 01, March 2016. 41 [10] ] Ahmet H. Deringol & HuseyinBilgin 2018, ‘Effects of the isolation parameters on the seismic response of steel frames’, Earthquakes and Structures, An Int'l Journal, vol. 15, no. 3. [11] Anil K. Chopra 2012, ‘Dynamics of Structures’, Fourth Edition, Dorling Kindersley (India) Private Limited, New Delhi, India. [12] Ahmet H. Deringol & HuseyinBilgin 2018, ‘Effects of the isolation parameters on the seismic response of steel frames’, Earthquakes and Structures, An Int'l Journal, vol. 15, no. 3. [13] Centre for Engineering Strong Motion Data (CESMD), US Geology Survey (https://www.strongmotioncenter.org/). [14] Chen JZ & Kianoush MR 2009, ‘Generalized SDOF System for Seismic Analysis of Concrete Rectangular Liquid Storage Tanks’, Engineering Structures, vol. 31, no. 10, pp. 2426-2435. [16] Claudia Mori, Stefano Sorace & Gloria Terenzi 2015, ‘Seismic Assessment and Retrofit of Two Heritage-Listed R/C Elevated Water Storage Tanks’, Soil Dynamics and Earthquake Engineering, vol. 77, pp. 123-136. [15] Hashemi S, Saadatpour MM & Kianoush MR 2013, ‘Dynamic analysis of flexible rectangular fluid containers subjected to horizontal ground motion’ Earthquake Engg Struct. Dym., vol. 10. [19] Houser GW 1963b, ‘The dynamic behavior of water tanks’, Bulletin of Seismological Society of America, vol. 53, No. 2, pp. 381-387. [16] Halil Sezen, Ramazan Livaoglu & Adem Dogangun 2008, ‘Dynamic analysis and seismic performance evaluation of above-ground liquid-containing tanks’, Engineering Structures, vol. 30, pp. 794-803. BIOGRAPHIES ARFAT RAFIQ, MTech (Earthquake Engineering) Dept. of Civil Engineering, Jamia Millia Islamia, New Delhi. MIR TABISH ALTAF, MTech (Earthquake Engineering) Dept. of Civil Engineering, Jamia Millia Islamia, New Delhi. SHAHID RAFEEQ, B E (Civil Engineering) Dept. of Civil Engineering, Jadavpur university, Kolkata. DR. MOHAMMAD UMAIR, Assistant Professor Dept. of Civil Engineering, Jamia Millia Islamia, New Delhi.