Produced on 20/11/2007 with VRV Xpress V2.4.1 - database Central 5.4

Project name
Reference                  .
Client name                .

Selection parameters of the indoor units can be found under the chapter Indoor unit details
Selection parameters of the outdoor units can be found under the chapter Outdoor unit details
Only the data published in the data book are correct. This program uses close approximations of these data.


1. Material List
      Model            Qty                              Description
RXYQ12P7W1B                1 Heat pump VRV III P COMPACT
RXYQ14P7W1B                2 Heat pump VRV III P COMPACT
RXYQ18P7W1B                1 Heat pump VRV III P COMPACT
RXYQ20P7W1B                1 Heat pump VRV III P COMPACT
RXYQ5P7W1B                 1 Heat pump VRV III P COMPACT
RXYQ8P7W1B                 1 Heat pump VRV III P COMPACT
FXZQ50M8                 28 Z - 4-way blow ceiling mounted cassette (600x600)
VKM100GAV1                 1 GA - Ventilation Air Reclaim
VKM50GAV1                  1 GA - Ventilation Air Reclaim
VKM80GAMV1                 2 GAM - Ventilation Air Reclaim
VKM80GAV1                  7 GA - Ventilation Air Reclaim
KHRQ22M20T7                7 REFNET branch piping kit
KHRQ22M29T7              11 REFNET branch piping kit
KHRQ22M64T7              14 REFNET branch piping kit
DCS302B51                  1 Centralised
BRC1D527                 28 Wired remote control
BYFQ60BW1                28 Decoration panel
BHFQ22P1007                1 Outdoor unit multi connection piping kit for 2 outdoors

VKM devices are considered as indoor units. They have an influence on the selection of outdoor units, the piping
diagram, the wiring diagram and the centralized controller diagram.




The VRV Xpress Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Xpress Program.




                                                                                                                                                                Page 1
2. Indoor Unit Details
      2.1.Table of Abbreviations
Name      Logical name of the device                                       Rq HC       Required heating capacity
FCU       Device model name                                                HC          Available heating capacity (with freeze-up correction)
Tmp C     Indoor conditions in cooling (dry bulb temp. / RH)               Airflow     Supplied airflow at low and high fan speed
Rq TC     Required total cooling capacity                                  Sound       Sound pressure low and high
TC        Available total cooling capacity                                 MCA         Minimum Circuit Amps
Rq SC     Required sensible cooling capacity                               WxHxD       WidthxHeightxDepth
SC        Available sensible cooling capacity                              Wght        Weight of the device
Tmp H     Indoor temperature in heating




      2.2.Type A - Outdoor Unit - RXYQ20P7W1B
Actual capacity data at conditions and combination ratio (102%) as entered
        Name                  FCU               Tmp C          Rq TC       TC       Rq SC       SC       Tmp H      Rq HC        HC       Airflow      Sound       MCA       WxHxD
                                                     °C          kW        kW         kW        kW          °C         kW        kW         m³/h        dBA          A         mm
Type A - FCU 1        FXZQ50M8                 24,0 / 50%          n/a       4,4        n/a       3,4        20,0        n/a       4,5 600-840        33-41           0,9 575x286x575
Type A - FCU 2        FXZQ50M8                 24,0 / 50%          n/a       4,4        n/a       3,4        20,0        n/a       4,5 600-840        33-41           0,9 575x286x575
Type A - FCU 3        FXZQ50M8                 24,0 / 50%          n/a       4,4        n/a       3,4        20,0        n/a       4,5 600-840        33-41           0,9 575x286x575
Type A - FCU 4        FXZQ50M8                 24,0 / 50%          n/a       4,4        n/a       3,4        20,0        n/a       4,5 600-840        33-41           0,9 575x286x575
Type A - FCU 5        FXZQ50M8                 24,0 / 50%          n/a       4,4        n/a       3,4        20,0        n/a       4,5 600-840        33-41           0,9 575x286x575
Type A - FCU 6        FXZQ50M8                 24,0 / 50%          n/a       4,4        n/a       3,4        20,0        n/a       4,5 600-840        33-41           0,9 575x286x575
Type A - FCU 7        FXZQ50M8                 24,0 / 50%          n/a       4,4        n/a       3,4        20,0        n/a       4,5 600-840        33-41           0,9 575x286x575
Type A - VKM 1        VKM80GAMV1               24,0 / 50%          n/a       7,1        n/a       4,5        20,0        n/a       7,2 640-750        36-36           4,3 1764x387x12
Type A - VKM 2        VKM80GAMV1               24,0 / 50%          n/a       7,1        n/a       4,5        20,0        n/a       7,2 640-750        36-36           4,3 1764x387x12
Total                                                                       45,1                 33,1                             45,8



Diversified capacity data at conditions as entered and 100% combination ratio
        Name             TC        SC        HC
                         kW       kW        kW
Type A - FCU 1             4,4       3,5       4,6
Type A - FCU 2             4,4       3,5       4,6
Type A - FCU 3             4,4       3,5       4,6
Type A - FCU 4             4,4       3,5       4,6
Type A - FCU 5             4,4       3,5       4,6
Type A - FCU 6             4,4       3,5       4,6
Type A - FCU 7             4,4       3,5       4,6
Type A - VKM 1             7,1       4,5       7,3
Type A - VKM 2             7,1       4,5       7,3
Total                    45,3      33,2      46,6




The VRV Xpress Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Xpress Program.




                                                                                                                                                                Page 2
2.3.Type B - Outdoor Unit - RXYQ18P7W1B
Actual capacity data at conditions and combination ratio (102%) as entered
        Name                  FCU             Tmp C         Rq TC        TC      Rq SC        SC       Tmp H      Rq HC        HC       Airflow       Sound        MCA        WxHxD
                                                 °C           kW         kW        kW         kW         °C         kW         kW         m³/h          dBA          A          mm
Type B - FCU 1        FXZQ50M8               24,0 / 50%          n/a       4,3        n/a       3,4       20,0         n/a       4,1 600-840        33-41              0,9 575x286x57
Type B - FCU 2        FXZQ50M8               24,0 / 50%          n/a       4,3        n/a       3,4       20,0         n/a       4,1 600-840        33-41              0,9 575x286x57
Type B - FCU 3        FXZQ50M8               24,0 / 50%          n/a       4,3        n/a       3,4       20,0         n/a       4,1 600-840        33-41              0,9 575x286x57
Type B - FCU 4        FXZQ50M8               24,0 / 50%          n/a       4,3        n/a       3,4       20,0         n/a       4,1 600-840        33-41              0,9 575x286x57
Type B - FCU 5        FXZQ50M8               24,0 / 50%          n/a       4,3        n/a       3,4       20,0         n/a       4,1 600-840        33-41              0,9 575x286x57
Type B - FCU 6        FXZQ50M8               24,0 / 50%          n/a       4,3        n/a       3,4       20,0         n/a       4,1 600-840        33-41              0,9 575x286x57
Type B - VKM 1        VKM80GAV1              24,0 / 50%          n/a       6,9        n/a       4,4       20,0         n/a       6,6 640-750        37,5-37,5          4,3 1764x387x1
Type B - VKM 2        VKM80GAV1              24,0 / 50%          n/a       6,9        n/a       4,4       20,0         n/a       6,6 640-750        37,5-37,5          4,3 1764x387x1
Total                                                                    39,7                 29,2                             38,1



Diversified capacity data at conditions as entered and 100% combination ratio
        Name             TC         SC      HC
                        kW          kW      kW
Type B - FCU 1             4,3       3,4      4,2
Type B - FCU 2             4,3       3,4      4,2
Type B - FCU 3             4,3       3,4      4,2
Type B - FCU 4             4,3       3,4      4,2
Type B - FCU 5             4,3       3,4      4,2
Type B - FCU 6             4,3       3,4      4,2
Type B - VKM 1             6,9       4,4      6,8
Type B - VKM 2             6,9       4,4      6,8
Total                    39,9       29,3     39,0




The VRV Xpress Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Xpress Program.




                                                                                                                                                                Page 3
2.4.Type C - Outdoor Unit - RXYQ14P7W1B
Actual capacity data at conditions and combination ratio (100%) as entered
        Name                  FCU              Tmp C          Rq TC        TC      Rq SC        SC      Tmp H       Rq HC       HC       Airflow      Sound       MCA       WxHxD
                                                  °C            kW        kW         kW        kW          °C         kW        kW         m³/h         dBA         A         mm
Type C - FCU 1        FXZQ50M8                24,0 / 50%           n/a      4,7         n/a       3,6       20,0         n/a       4,9 600-840       33-41           0,9 575x286x575
Type C - FCU 2        FXZQ50M8                24,0 / 50%           n/a      4,7         n/a       3,6       20,0         n/a       4,9 600-840       33-41           0,9 575x286x575
Type C - FCU 3        FXZQ50M8                24,0 / 50%           n/a      4,7         n/a       3,6       20,0         n/a       4,9 600-840       33-41           0,9 575x286x575
Type C - FCU 4        FXZQ50M8                24,0 / 50%           n/a      4,7         n/a       3,6       20,0         n/a       4,9 600-840       33-41           0,9 575x286x575
Type C - FCU 5        FXZQ50M8                24,0 / 50%           n/a      4,7         n/a       3,6       20,0         n/a       4,9 600-840       33-41           0,9 575x286x575
Type C - VKM 1        VKM100GAV1              24,0 / 50%           n/a      9,3         n/a       5,9       20,0         n/a       9,8 820-950       38-38           4,3 1764x387x12
Total                                                                      32,7                 23,6                             34,2



Diversified capacity data at conditions as entered and 100% combination ratio
        Name             TC       SC        HC
                        kW        kW        kW
Type C - FCU 1             4,7       3,6      4,9
Type C - FCU 2             4,7       3,6      4,9
Type C - FCU 3             4,7       3,6      4,9
Type C - FCU 4             4,7       3,6      4,9
Type C - FCU 5             4,7       3,6      4,9
Type C - VKM 1             9,3       5,9      9,8
Total                    32,7       23,6     34,2




The VRV Xpress Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Xpress Program.




                                                                                                                                                                Page 4
2.5.Type D - Outdoor Unit - RXYQ14P7W1B
Actual capacity data at conditions and combination ratio (103%) as entered
        Name                  FCU             Tmp C         Rq TC        TC      Rq SC        SC       Tmp H      Rq HC        HC       Airflow       Sound        MCA        WxHxD
                                                 °C           kW         kW        kW         kW         °C         kW         kW         m³/h          dBA          A          mm
Type D - FCU 1        FXZQ50M8               24,0 / 50%          n/a       4,6        n/a       3,5       20,0         n/a       4,8 600-840        33-41              0,9 575x286x57
Type D - FCU 2        FXZQ50M8               24,0 / 50%          n/a       4,6        n/a       3,5       20,0         n/a       4,8 600-840        33-41              0,9 575x286x57
Type D - FCU 3        FXZQ50M8               24,0 / 50%          n/a       4,6        n/a       3,5       20,0         n/a       4,8 600-840        33-41              0,9 575x286x57
Type D - FCU 4        FXZQ50M8               24,0 / 50%          n/a       4,6        n/a       3,5       20,0         n/a       4,8 600-840        33-41              0,9 575x286x57
Type D - VKM 1        VKM80GAV1              24,0 / 50%          n/a       7,4        n/a       4,7       20,0         n/a       7,6 640-750        37,5-37,5          4,3 1764x387x1
Type D - VKM 2        VKM80GAV1              24,0 / 50%          n/a       7,4        n/a       4,7       20,0         n/a       7,6 640-750        37,5-37,5          4,3 1764x387x1
Total                                                                    33,4                 23,5                             34,3



Diversified capacity data at conditions as entered and 100% combination ratio
        Name             TC         SC      HC
                        kW          kW      kW
Type D - FCU 1             4,7       3,6      4,9
Type D - FCU 2             4,7       3,6      4,9
Type D - FCU 3             4,7       3,6      4,9
Type D - FCU 4             4,7       3,6      4,9
Type D - VKM 1             7,5       4,7      7,8
Type D - VKM 2             7,5       4,7      7,8
Total                    33,6       23,6     35,2




The VRV Xpress Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Xpress Program.




                                                                                                                                                                Page 5
2.6.Type E - Outdoor Unit - RXYQ12P7W1B
Actual capacity data at conditions and combination ratio (103%) as entered
        Name                 FCU             Tmp C          Rq TC        TC      Rq SC        SC      Tmp H       Rq HC        HC       Airflow       Sound        MCA       WxHxD
                                                 °C           kW         kW        kW         kW         °C         kW         kW        m³/h          dBA           A         mm
Type E - FCU 1        FXZQ50M8              24,0 / 50%           n/a       4,5        n/a       3,5       20,0         n/a       4,1 600-840       33-41              0,9 575x286x57
Type E - FCU 2        FXZQ50M8              24,0 / 50%           n/a       4,5        n/a       3,5       20,0         n/a       4,1 600-840       33-41              0,9 575x286x57
Type E - FCU 3        FXZQ50M8              24,0 / 50%           n/a       4,5        n/a       3,5       20,0         n/a       4,1 600-840       33-41              0,9 575x286x57
Type E - VKM 1        VKM80GAV1             24,0 / 50%           n/a       7,3        n/a       4,6       20,0         n/a       6,5 640-750       37,5-37,5          4,3 1764x387x1
Type E - VKM 2        VKM80GAV1             24,0 / 50%           n/a       7,3        n/a       4,6       20,0         n/a       6,5 640-750       37,5-37,5          4,3 1764x387x1
Total                                                                    28,1                 19,6                             25,1



Diversified capacity data at conditions as entered and 100% combination ratio
        Name            TC         SC       HC
                        kW         kW       kW
Type E - FCU 1            4,6       3,5       4,2
Type E - FCU 2            4,6       3,5       4,2
Type E - FCU 3            4,6       3,5       4,2
Type E - VKM 1            7,3       4,6       6,7
Type E - VKM 2            7,3       4,6       6,7
Total                    28,3      19,7      25,9




The VRV Xpress Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Xpress Program.




                                                                                                                                                                Page 6
2.7.Type F - Outdoor Unit - RXYQ8P7W1B
Actual capacity data at conditions and combination ratio (90%) as entered
        Name                 FCU             Tmp C          Rq TC        TC      Rq SC        SC      Tmp H       Rq HC        HC       Airflow       Sound        MCA       WxHxD
                                                 °C           kW         kW        kW         kW         °C         kW         kW        m³/h          dBA           A         mm
Type F - FCU 1        FXZQ50M8              24,0 / 50%           n/a       4,4        n/a       3,4       20,0         n/a       5,2 600-840       33-41              0,9 575x286x57
Type F - FCU 2        FXZQ50M8              24,0 / 50%           n/a       4,4        n/a       3,4       20,0         n/a       5,2 600-840       33-41              0,9 575x286x57
Type F - VKM 1        VKM80GAV1             24,0 / 50%           n/a       7,1        n/a       4,5       20,0         n/a       8,3 640-750       37,5-37,5          4,3 1764x387x1
Total                                                                    15,9                 11,4                             18,7



Diversified capacity data at conditions as entered and 100% combination ratio
        Name            TC         SC       HC
                        kW         kW       kW
Type F - FCU 1            4,4       3,4       5,2
Type F - FCU 2            4,4       3,4       5,2
Type F - VKM 1            7,1       4,5       8,3
Total                    15,9      11,4      18,7




The VRV Xpress Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Xpress Program.




                                                                                                                                                                Page 7
2.8.Type G - Outdoor Unit - RXYQ5P7W1B
Actual capacity data at conditions and combination ratio (80%) as entered
        Name                 FCU              Tmp C         Rq TC       TC      Rq SC      SC      Tmp H       Rq HC        HC      Airflow      Sound       MCA           WxHxD
                                                 °C           kW        kW        kW       kW         °C         kW         kW        m³/h         dBA         A            mm
Type G - FCU 1        FXZQ50M8              24,0 / 50%           n/a     4,2        n/a      3,3       20,0         n/a       5,4 600-840       33-41           0,9 575x286x575
Type F - VKM 1        VKM50GAV1             24,0 / 50%           n/a     4,2        n/a      2,7       20,0         n/a       5,4 440-500       36-36           4,3 1764x387x832
Total                                                                    8,4                 6,0                            10,8



Diversified capacity data at conditions as entered and 100% combination ratio
        Name            TC      SC       HC
                       kW       kW       kW
Type G - FCU 1           4,2     3,3       5,4
Type F - VKM 1           4,2     2,7       5,4
Total                    8,4     6,0      10,8




The VRV Xpress Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Xpress Program.




                                                                                                                                                                Page 8
3. Outdoor Unit Details
      3.1.Table of Abbreviations
Name      Logical name of the device                                       Refrig         Standard factory refrigerant charge (5m actual piping length),
Model     Device model name                                                               excluding extra refrigerant charge
Comb      Combination percentage                                                          For calculation of extra refrigerant charge refer to the VRV databook
Tmp C     Outdoor temperature in cooling (dry bulb)                        PS             Power supply (voltage and phases)
CC        Cooling capacity                                                 Run Amps       Running Amps
EER       EER at selection and nominal conditions                          St Curr        Starting current
Tmp H     Outdoor temperature in heating (dry bulb)                        Fuses          Fuses
HC        Heating capacity (with freeze-up correction)                     WxHxD          WidthxHeightxDepth
COP       COP at selection and nominal conditions                          Wght           Weight of the device
Piping    Largest distance from indoor unit to outdoor unit




      3.2.Outdoor Details
          Name                       Model             Comb        Tmp C          CC       EER         Tmp H        HC           COP       Piping      Refrig
                                                          %          °C           kW                     °C         kW                        m          kg
Type A - Outdoor Unit         RXYQ20P7W1B                  102        37,0        49,6    3,7 / 3,7        -7,0      45,8      3,1 / 4,1        45,0      16,3
                              * RXYQ12P7W1B
                              * RXYQ8P7W1B
Type B - Outdoor Unit         RXYQ18P7W1B                  102        37,0        43,5         3/3         -7,0      38,1      2,9 / 3,7        45,0      12,7
Type C - Outdoor Unit         RXYQ14P7W1B                  100        37,0        34,9    3,2 / 3,2        -7,0      34,2        2,8 / 4        45,0      12,3
Type D - Outdoor Unit         RXYQ14P7W1B                  103        37,0        35,7    3,2 / 3,2        -7,0      34,3        2,8 / 4        45,0      12,3
Type E - Outdoor Unit         RXYQ12P7W1B                  103        37,0        30,0    3,5 / 3,5        -7,0      25,1        3,1 / 4        45,0        8,6
Type F - Outdoor Unit         RXYQ8P7W1B                      90      37,0        19,5         4/4         -7,0      20,8      3,2 / 4,3        45,0        7,7
Type G - Outdoor Unit         RXYQ5P7W1B                      80      37,0        12,2         4/4         -7,0      13,5        2,9 / 4        45,0        6,2


          Name                       Model                  PS          Run Amps          St Curr             Fuses                    WxHxD             Wght
                                                                              A              A                                             mm              kg
Type A - Outdoor Unit         RXYQ20P7W1B             400V 3Nph                                                                  1860x1680x765              427
                              * RXYQ12P7W1B                                         14           75     cfr. local legislation
                              * RXYQ8P7W1B                                          7,5                 cfr. local legislation
Type B - Outdoor Unit         RXYQ18P7W1B             400V 3Nph                   24,2           85     cfr. local legislation 1240x1680x765                325
Type C - Outdoor Unit         RXYQ14P7W1B             400V 3Nph                   18,4           84     cfr. local legislation 1240x1680x765                317
Type D - Outdoor Unit         RXYQ14P7W1B             400V 3Nph                   18,4           84     cfr. local legislation 1240x1680x765                317
Type E - Outdoor Unit         RXYQ12P7W1B             400V 3Nph                     14           75     cfr. local legislation 930x1680x765                 240
Type F - Outdoor Unit         RXYQ8P7W1B              400V 3Nph                     7,5                 cfr. local legislation 930x1680x765                 187
Type G - Outdoor Unit         RXYQ5P7W1B              400V 3Nph                     5,1                 cfr. local legislation 635x1680x765                 159




The VRV Xpress Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Xpress Program.




                                                                                                                                                                  Page 9
4. Piping Diagrams
Pipes marked with * in the diagrams must be connected to the device with a reducing joint.

      4.1.Piping Type A - Outdoor Unit
 Ty pe A - Outdoor Unit                                                                   Ty pe A - FCU 1
                                                         15,9x28,6            6,4x12,7
    RXY Q20P7W1B                                                                             FXZQ50M8
                                                                        KHRQ22M64T7


    RXY Q12P7W1B          12,7x28,6                                                       Ty pe A - FCU 2
                                                         15,9x28,6            6,4x12,7
                                                                                             FXZQ50M8
                                  BHFQ22P1007                           KHRQ22M64T7


                                                                                          Ty pe A - FCU 3
                                                         12,7x28,6            6,4x12,7
                                                                                             FXZQ50M8
     RXY Q8P7W1B          9,5x19,1                                      KHRQ22M64T7


                                                                                          Ty pe A - FCU 4
                                                         12,7x28,6            6,4x12,7
                                                                                             FXZQ50M8
                                                                        KHRQ22M64T7


                                                                                          Ty pe A - FCU 5
                                                         12,7x28,6            6,4x12,7
                                                                                             FXZQ50M8
                                                                        KHRQ22M64T7


                                                                                          Ty pe A - FCU 6
                                                             9,5x22,2         6,4x12,7
                                                                                             FXZQ50M8
                                                                        KHRQ22M29T7


                                                                                          Ty pe A - FCU 7
                                                             9,5x22,2         6,4x12,7
                                                                                             FXZQ50M8
                                                                        KHRQ22M29T7


                                                                                          Ty pe A - VKM 1
                                                             9,5x19,1         6,4x12,7
                                                                                           VKM80GAMV1
                                                                        KHRQ22M20T7


                                                                                          Ty pe A - VKM 2
                                                                               6,4x12,7
                                                                                           VKM80GAMV1




      4.2.Piping Type B - Outdoor Unit
Ty pe B - Outdoor Unit                                       Ty pe B - FCU 1
                               15,9x28,6         6,4x12,7
   RXY Q18P7W1B                                                 FXZQ50M8
                                           KHRQ22M64T7


                                                             Ty pe B - FCU 2
                               12,7x28,6         6,4x12,7
                                                                FXZQ50M8
                                           KHRQ22M64T7


                                                             Ty pe B - FCU 3
                               12,7x28,6         6,4x12,7
                                                                FXZQ50M8
                                           KHRQ22M64T7


                                                             Ty pe B - FCU 4
                               12,7x28,6         6,4x12,7
                                                                FXZQ50M8
                                           KHRQ22M64T7


                                                             Ty pe B - FCU 5
                                9,5x22,2         6,4x12,7
                                                                FXZQ50M8
                                           KHRQ22M29T7


                                                             Ty pe B - FCU 6
                                9,5x22,2         6,4x12,7
                                                                FXZQ50M8
                                           KHRQ22M29T7


                                                             Ty pe B - VKM 1
                                9,5x19,1         6,4x12,7
                                                              VKM80GAV1
                                           KHRQ22M20T7


                                                             Ty pe B - VKM 2
                                                  6,4x12,7
                                                              VKM80GAV1




The VRV Xpress Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Xpress Program.




                                                                                                                                                              Page 10
4.3.Piping Type C - Outdoor Unit
Ty pe C - Outdoor Unit                                  Ty pe C - FCU 1
                          12,7x28,6         6,4x12,7
   RXY Q14P7W1B                                            FXZQ50M8
                                      KHRQ22M64T7


                                                        Ty pe C - FCU 2
                          12,7x28,6         6,4x12,7
                                                           FXZQ50M8
                                      KHRQ22M64T7


                                                        Ty pe C - FCU 3
                           9,5x22,2         6,4x12,7
                                                           FXZQ50M8
                                      KHRQ22M29T7


                                                        Ty pe C - FCU 4
                           9,5x22,2         6,4x12,7
                                                           FXZQ50M8
                                      KHRQ22M29T7


                                                        Ty pe C - FCU 5
                           9,5x19,1         6,4x12,7
                                                           FXZQ50M8
                                      KHRQ22M20T7


                                                        Ty pe C - VKM 1
                                             6,4x12,7
                                                         VKM100GAV1




      4.4.Piping Type D - Outdoor Unit
Ty pe D - Outdoor Unit                                  Ty pe D - FCU 1
                          12,7x28,6         6,4x12,7
   RXY Q14P7W1B                                            FXZQ50M8
                                      KHRQ22M64T7


                                                        Ty pe D - FCU 2
                          12,7x28,6         6,4x12,7
                                                           FXZQ50M8
                                      KHRQ22M64T7


                                                        Ty pe D - FCU 3
                           9,5x22,2         6,4x12,7
                                                           FXZQ50M8
                                      KHRQ22M29T7


                                                        Ty pe D - FCU 4
                           9,5x22,2         6,4x12,7
                                                           FXZQ50M8
                                      KHRQ22M29T7


                                                        Ty pe D - VKM 1
                           9,5x19,1         6,4x12,7
                                                         VKM80GAV1
                                      KHRQ22M20T7


                                                        Ty pe D - VKM 2
                                             6,4x12,7
                                                         VKM80GAV1




      4.5.Piping Type E - Outdoor Unit
Ty pe E - Outdoor Unit                                  Ty pe E - FCU 1
                          12,7x28,6         6,4x12,7
   RXY Q12P7W1B                                            FXZQ50M8
                                      KHRQ22M64T7


                                                        Ty pe E - FCU 2
                           9,5x22,2         6,4x12,7
                                                           FXZQ50M8
                                      KHRQ22M29T7


                                                        Ty pe E - FCU 3
                           9,5x22,2         6,4x12,7
                                                           FXZQ50M8
                                      KHRQ22M29T7


                                                        Ty pe E - VKM 1
                           9,5x19,1         6,4x12,7
                                                         VKM80GAV1
                                      KHRQ22M20T7


                                                        Ty pe E - VKM 2
                                             6,4x12,7
                                                         VKM80GAV1




The VRV Xpress Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Xpress Program.




                                                                                                                                                              Page 11
4.6.Piping Type F - Outdoor Unit
Ty pe F - Outdoor Unit                                   Ty pe F - FCU 1
                            9,5x19,1         6,4x12,7
    RXY Q8P7W1B                                             FXZQ50M8
                                       KHRQ22M29T7


                                                         Ty pe F - FCU 2
                            9,5x15,9         6,4x12,7
                                                            FXZQ50M8
                                       KHRQ22M20T7


                                                         Ty pe F - VKM 1
                                              6,4x12,7
                                                          VKM80GAV1




        4.7.Piping Type G - Outdoor Unit
Ty pe G - Outdoor Unit                                   Ty pe G - FCU 1
                            9,5x15,9         6,4x12,7
    RXY Q5P7W1B                                             FXZQ50M8
                                       KHRQ22M20T7


                                                         Ty pe F - VKM 1
                                              6,4x12,7
                                                          VKM50GAV1




5. Wiring Diagrams
P1P2 = 16-2 AWG 2 core non screened stranded wire (non polarity wiring system)
F1F2 = 16-2 AWG 2 core non screened stranded wire (non polarity wiring system)

        5.1.Centralized Controllers
 centralised DCS302B51

     centralised                                                      Ty pe A - Outdoor Unit
                                                                         RXY Q20P7W1B
                    F1,F2                                     OUT F1,F2
  L,N
                                                                      Ty pe B - Outdoor Unit
                                                                         RXY Q18P7W1B
                                                              OUT F1,F2


                                                                       Ty pe C - Outdoor Unit
                                                                          RXY Q14P7W1B
                                                              OUT F1,F2

                                                                      Ty pe D - Outdoor Unit
                                                                         RXY Q14P7W1B
                                                              OUT F1,F2


                                                                      Ty pe E - Outdoor Unit
                                                                         RXY Q12P7W1B
                                                              OUT F1,F2

                                                                      Ty pe F - Outdoor Unit
                                                                          RXY Q8P7W1B
                                                              OUT F1,F2


                                                                      Ty pe G - Outdoor Unit
                                                                          RXY Q5P7W1B
                                                              OUT F1,F2




The VRV Xpress Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Xpress Program.




                                                                                                                                                              Page 12
5.2.Wiring Type A - Outdoor Unit
  to centralized controller
                                                                                   P1,P2                         14,9A 1ph
               Ty pe A - Outdoor Unit                            Ty pe A - FCU 1           BRC1D527
                  RXY Q20P7W1B                                      FXZQ50M8
   OUT F1,F2                            IN F1,F2         F1,F2                     L,N

                                                                                   P1,P2
                 RXY Q12P7W1B                                    Ty pe A - FCU 2           BRC1D527
                                                                    FXZQ50M8
       Q1,Q2                            L1,L2,L3,N       F1,F2                     L,N
                                        22,7A 3Nph
                                                                                   P1,P2
                                                                 Ty pe A - FCU 3           BRC1D527
                  RXY Q8P7W1B
                                                                    FXZQ50M8
                                                         F1,F2                     L,N
       Q1,Q2                            L1,L2,L3,N
                                        18,5A 3Nph                                 P1,P2
                                                                 Ty pe A - FCU 4           BRC1D527
                                                                    FXZQ50M8
                                                         F1,F2                     L,N

                                                                                   P1,P2
                                                                 Ty pe A - FCU 5           BRC1D527
                                                                    FXZQ50M8
                                                         F1,F2                     L,N

                                                                                   P1,P2
                                                                 Ty pe A - FCU 6           BRC1D527
                                                                    FXZQ50M8
                                                         F1,F2                     L,N

                                                                                   P1,P2
                                                                 Ty pe A - FCU 7           BRC1D527
                                                                    FXZQ50M8
                                                         F1,F2                     L,N


                                                                 Ty pe A - VKM 1
                                                                  VKM80GAMV1
                                                         F1,F2                     L,N


                                                                 Ty pe A - VKM 2
                                                                  VKM80GAMV1
                                                         F1,F2                     L,N




The VRV Xpress Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Xpress Program.




                                                                                                                                                              Page 13
5.3.Wiring Type B - Outdoor Unit
  to centralized controller
                                                                                   P1,P2                         14A 1ph
           Ty pe B - Outdoor Unit                                Ty pe B - FCU 1           BRC1D527
              RXY Q18P7W1B                                          FXZQ50M8
   OUT F1,F2                    IN F1,F2                 F1,F2                     L,N

                                                                                   P1,P2
                                                                 Ty pe B - FCU 2           BRC1D527
                                                                    FXZQ50M8
               L1,L2,L3,N     32,5A 3Nph
                                                         F1,F2                     L,N

                                                                                   P1,P2
                                                                 Ty pe B - FCU 3           BRC1D527
                                                                    FXZQ50M8
                                                         F1,F2                     L,N

                                                                                   P1,P2
                                                                 Ty pe B - FCU 4           BRC1D527
                                                                    FXZQ50M8
                                                         F1,F2                     L,N

                                                                                   P1,P2
                                                                 Ty pe B - FCU 5           BRC1D527
                                                                    FXZQ50M8
                                                         F1,F2                     L,N

                                                                                   P1,P2
                                                                 Ty pe B - FCU 6           BRC1D527
                                                                    FXZQ50M8
                                                         F1,F2                     L,N


                                                                 Ty pe B - VKM 1
                                                                  VKM80GAV1
                                                         F1,F2                     L,N


                                                                 Ty pe B - VKM 2
                                                                  VKM80GAV1
                                                         F1,F2                     L,N




The VRV Xpress Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Xpress Program.




                                                                                                                                                              Page 14
5.4.Wiring Type C - Outdoor Unit
  to centralized controller
                                                                                   P1,P2                         8,8A 1ph
           Ty pe C - Outdoor Unit                                Ty pe C - FCU 1           BRC1D527
              RXY Q14P7W1B                                          FXZQ50M8
   OUT F1,F2                    IN F1,F2                 F1,F2                     L,N

                                                                                   P1,P2
                                                                 Ty pe C - FCU 2           BRC1D527
                                                                    FXZQ50M8
               L1,L2,L3,N     31,5A 3Nph
                                                         F1,F2                     L,N

                                                                                   P1,P2
                                                                 Ty pe C - FCU 3           BRC1D527
                                                                    FXZQ50M8
                                                         F1,F2                     L,N

                                                                                   P1,P2
                                                                 Ty pe C - FCU 4           BRC1D527
                                                                    FXZQ50M8
                                                         F1,F2                     L,N

                                                                                   P1,P2
                                                                 Ty pe C - FCU 5           BRC1D527
                                                                    FXZQ50M8
                                                         F1,F2                     L,N


                                                                 Ty pe C - VKM 1
                                                                  VKM100GAV1
                                                         F1,F2                     L,N




      5.5.Wiring Type D - Outdoor Unit
  to centralized controller
                                                                                   P1,P2                         12,2A 1ph
           Ty pe D - Outdoor Unit                                Ty pe D - FCU 1           BRC1D527
              RXY Q14P7W1B                                          FXZQ50M8
   OUT F1,F2                    IN F1,F2                 F1,F2                     L,N

                                                                                   P1,P2
                                                                 Ty pe D - FCU 2           BRC1D527
                                                                    FXZQ50M8
               L1,L2,L3,N     31,5A 3Nph
                                                         F1,F2                     L,N

                                                                                   P1,P2
                                                                 Ty pe D - FCU 3           BRC1D527
                                                                    FXZQ50M8
                                                         F1,F2                     L,N

                                                                                   P1,P2
                                                                 Ty pe D - FCU 4           BRC1D527
                                                                    FXZQ50M8
                                                         F1,F2                     L,N


                                                                 Ty pe D - VKM 1
                                                                  VKM80GAV1
                                                         F1,F2                     L,N


                                                                 Ty pe D - VKM 2
                                                                  VKM80GAV1
                                                         F1,F2                     L,N




The VRV Xpress Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Xpress Program.




                                                                                                                                                              Page 15
5.6.Wiring Type E - Outdoor Unit
  to centralized controller
                                                                                   P1,P2                         11,3A 1ph
           Ty pe E - Outdoor Unit                                Ty pe E - FCU 1           BRC1D527
              RXY Q12P7W1B                                          FXZQ50M8
   OUT F1,F2                    IN F1,F2                 F1,F2                     L,N

                                                                                   P1,P2
                                                                 Ty pe E - FCU 2           BRC1D527
               L1,L2,L3,N     22,7A 3Nph
                                                                    FXZQ50M8
                                                         F1,F2                     L,N

                                                                                   P1,P2
                                                                 Ty pe E - FCU 3           BRC1D527
                                                                    FXZQ50M8
                                                         F1,F2                     L,N


                                                                 Ty pe E - VKM 1
                                                                  VKM80GAV1
                                                         F1,F2                     L,N


                                                                 Ty pe E - VKM 2
                                                                  VKM80GAV1
                                                         F1,F2                     L,N




      5.7.Wiring Type F - Outdoor Unit
  to centralized controller
                                                                                   P1,P2                         6,1A 1ph
           Ty pe F - Outdoor Unit                                Ty pe F - FCU 1           BRC1D527
               RXY Q8P7W1B                                          FXZQ50M8
   OUT F1,F2                    IN F1,F2                 F1,F2                     L,N

                                                                                   P1,P2
                                                                 Ty pe F - FCU 2           BRC1D527
               L1,L2,L3,N     18,5A 3Nph
                                                                    FXZQ50M8
                                                         F1,F2                     L,N


                                                                 Ty pe F - VKM 1
                                                                  VKM80GAV1
                                                         F1,F2                     L,N




      5.8.Wiring Type G - Outdoor Unit
  to centralized controller
                                                                                   P1,P2                         5,2A 1ph
           Ty pe G - Outdoor Unit                                Ty pe G - FCU 1           BRC1D527
               RXY Q5P7W1B                                          FXZQ50M8
   OUT F1,F2                    IN F1,F2                 F1,F2                     L,N

               L1,L2,L3,N     11,9A 3Nph
                                                                 Ty pe F - VKM 1
                                                                  VKM50GAV1
                                                         F1,F2                     L,N




The VRV Xpress Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Xpress Program.




                                                                                                                                                              Page 16
6. Device Options
      6.1.Outdoor Unit Options
      Model                                   Description                                                   Used by
BHFQ22P1007 Outdoor unit multi connection piping kit for 2 outdoors                     Type A - Outdoor Unit [RXYQ20P7W1B]




      6.2.Indoor Unit Options
     Model             Description                      Used by
BYFQ60BW1          Decoration panel        Type A - FCU 2 [FXZQ50M8]            Type A - FCU 3 [FXZQ50M8]             Type A - FCU 4 [FXZQ50M8]
                                           Type A - FCU 5 [FXZQ50M8]            Type A - FCU 6 [FXZQ50M8]             Type A - FCU 1 [FXZQ50M8]
                                           Type B - FCU 1 [FXZQ50M8]            Type B - FCU 2 [FXZQ50M8]             Type A - FCU 7 [FXZQ50M8]
                                           Type B - FCU 3 [FXZQ50M8]            Type B - FCU 4 [FXZQ50M8]             Type B - FCU 5 [FXZQ50M8]
                                           Type B - FCU 6 [FXZQ50M8]            Type C - FCU 1 [FXZQ50M8] Type C - FCU 2 [FXZQ50M8]
                                           Type C - FCU 3 [FXZQ50M8] Type C - FCU 4 [FXZQ50M8] Type C - FCU 5 [FXZQ50M8]
                                           Type D - FCU 1 [FXZQ50M8] Type D - FCU 2 [FXZQ50M8] Type D - FCU 3 [FXZQ50M8]
                                           Type D - FCU 4 [FXZQ50M8] Type E - FCU 1 [FXZQ50M8]                        Type E - FCU 2 [FXZQ50M8]
                                           Type E - FCU 3 [FXZQ50M8]            Type F - FCU 1 [FXZQ50M8]             Type F - FCU 2 [FXZQ50M8]
                                           Type G - FCU 1 [FXZQ50M8]




The VRV Xpress Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Xpress Program.




                                                                                                                                                              Page 17

More Related Content

Viewers also liked

Hvac made easy selection tips for chiller compressors
Hvac made easy   selection tips for chiller compressorsHvac made easy   selection tips for chiller compressors
Hvac made easy selection tips for chiller compressorsMazhar Sheikh
 
Homiletics: The Art of Preaching
Homiletics: The Art of PreachingHomiletics: The Art of Preaching
Homiletics: The Art of PreachingNeo Lamperouge
 
Homiletics Introduction
Homiletics IntroductionHomiletics Introduction
Homiletics IntroductionJerry Smith
 
Edus39 605 a-n vrv installation
Edus39 605 a-n vrv installationEdus39 605 a-n vrv installation
Edus39 605 a-n vrv installationHangkheang Khy
 
Making a sermon outline
Making a sermon outlineMaking a sermon outline
Making a sermon outlineKelvin Jones
 
Sermon Preparation Form
Sermon Preparation FormSermon Preparation Form
Sermon Preparation FormSermonOutlines
 
Free Sermon Outline - Hebrews 11:1-6 - A Matter of Faith
Free Sermon Outline - Hebrews 11:1-6 - A Matter of FaithFree Sermon Outline - Hebrews 11:1-6 - A Matter of Faith
Free Sermon Outline - Hebrews 11:1-6 - A Matter of FaithSermonOutlines
 
HVAC Air distribution fundamentals
HVAC Air distribution fundamentalsHVAC Air distribution fundamentals
HVAC Air distribution fundamentalsAp Naseem
 
Refrigration & air conditioning
Refrigration & air conditioningRefrigration & air conditioning
Refrigration & air conditioningSiddharth Bedarker
 
Water Chilled Airconditioning
Water Chilled AirconditioningWater Chilled Airconditioning
Water Chilled AirconditioningAljon Altiche
 
Hvac presentation for beginers
Hvac presentation for beginersHvac presentation for beginers
Hvac presentation for beginersguestf11b52
 
Chilled water piping basics
Chilled water piping basicsChilled water piping basics
Chilled water piping basicsAp Naseem
 

Viewers also liked (17)

Hvac made easy selection tips for chiller compressors
Hvac made easy   selection tips for chiller compressorsHvac made easy   selection tips for chiller compressors
Hvac made easy selection tips for chiller compressors
 
Homiletics: The Art of Preaching
Homiletics: The Art of PreachingHomiletics: The Art of Preaching
Homiletics: The Art of Preaching
 
Homiletics Introduction
Homiletics IntroductionHomiletics Introduction
Homiletics Introduction
 
Edus39 605 a-n vrv installation
Edus39 605 a-n vrv installationEdus39 605 a-n vrv installation
Edus39 605 a-n vrv installation
 
LG VRF MULTI V
LG VRF MULTI VLG VRF MULTI V
LG VRF MULTI V
 
Making a sermon outline
Making a sermon outlineMaking a sermon outline
Making a sermon outline
 
Sermon Preparation Form
Sermon Preparation FormSermon Preparation Form
Sermon Preparation Form
 
Free Sermon Outline - Hebrews 11:1-6 - A Matter of Faith
Free Sermon Outline - Hebrews 11:1-6 - A Matter of FaithFree Sermon Outline - Hebrews 11:1-6 - A Matter of Faith
Free Sermon Outline - Hebrews 11:1-6 - A Matter of Faith
 
HVAC Air distribution fundamentals
HVAC Air distribution fundamentalsHVAC Air distribution fundamentals
HVAC Air distribution fundamentals
 
VRF system presentation !
VRF system presentation !VRF system presentation !
VRF system presentation !
 
Duct design
Duct designDuct design
Duct design
 
Refrigration & air conditioning
Refrigration & air conditioningRefrigration & air conditioning
Refrigration & air conditioning
 
HVAC Sysems & AHU
HVAC Sysems & AHUHVAC Sysems & AHU
HVAC Sysems & AHU
 
HVAC Basic Concepts of Air Conditioning
HVAC Basic Concepts of Air ConditioningHVAC Basic Concepts of Air Conditioning
HVAC Basic Concepts of Air Conditioning
 
Water Chilled Airconditioning
Water Chilled AirconditioningWater Chilled Airconditioning
Water Chilled Airconditioning
 
Hvac presentation for beginers
Hvac presentation for beginersHvac presentation for beginers
Hvac presentation for beginers
 
Chilled water piping basics
Chilled water piping basicsChilled water piping basics
Chilled water piping basics
 

Similar to Larisa Vrv

Dienhathe.com catalogue epcos-capacitor_phicap_b32344d
Dienhathe.com catalogue epcos-capacitor_phicap_b32344dDienhathe.com catalogue epcos-capacitor_phicap_b32344d
Dienhathe.com catalogue epcos-capacitor_phicap_b32344dDien Ha The
 
Original High Current NPN Transistor BC639 639 TO-92 New ON Semiconductor
Original High Current NPN Transistor BC639 639 TO-92 New ON SemiconductorOriginal High Current NPN Transistor BC639 639 TO-92 New ON Semiconductor
Original High Current NPN Transistor BC639 639 TO-92 New ON SemiconductorAUTHELECTRONIC
 
Samsung tdb-dvm-s-water e-outdoor_dbeu-13082_da1
Samsung tdb-dvm-s-water e-outdoor_dbeu-13082_da1Samsung tdb-dvm-s-water e-outdoor_dbeu-13082_da1
Samsung tdb-dvm-s-water e-outdoor_dbeu-13082_da1Haluk TOSUN
 
Kollmorgen pma series_catalog
Kollmorgen  pma  series_catalogKollmorgen  pma  series_catalog
Kollmorgen pma series_catalogElectromate
 
Sb bora condensers-e-vap-ver.1.2_en
Sb bora condensers-e-vap-ver.1.2_enSb bora condensers-e-vap-ver.1.2_en
Sb bora condensers-e-vap-ver.1.2_enYury Naumov
 
Dienhathe.com catalogue epcos-capacitor_phasecap
Dienhathe.com catalogue epcos-capacitor_phasecapDienhathe.com catalogue epcos-capacitor_phasecap
Dienhathe.com catalogue epcos-capacitor_phasecapDien Ha The
 
CCD Series 2011 new-best.pdf
CCD Series 2011 new-best.pdfCCD Series 2011 new-best.pdf
CCD Series 2011 new-best.pdfCoollineAgency
 
Fujitsu J-II Series Sell Sheet
Fujitsu J-II Series Sell SheetFujitsu J-II Series Sell Sheet
Fujitsu J-II Series Sell SheetDavid Andrews
 
PDXE_PX3_SS6 8-22-14
PDXE_PX3_SS6 8-22-14PDXE_PX3_SS6 8-22-14
PDXE_PX3_SS6 8-22-14Zakir Hakim
 
Thomson roundrail 1_vc_continuously_supported_specsheet
Thomson roundrail 1_vc_continuously_supported_specsheetThomson roundrail 1_vc_continuously_supported_specsheet
Thomson roundrail 1_vc_continuously_supported_specsheetElectromate
 
Thomson Linear RoundRail 1VC Continuously Supported Specs
Thomson Linear RoundRail 1VC Continuously Supported SpecsThomson Linear RoundRail 1VC Continuously Supported Specs
Thomson Linear RoundRail 1VC Continuously Supported SpecsElectromate
 
JCB 3CX 20 BACKOHE LOADER Parts Catalogue Manual (Serial Number 00400000-0043...
JCB 3CX 20 BACKOHE LOADER Parts Catalogue Manual (Serial Number 00400000-0043...JCB 3CX 20 BACKOHE LOADER Parts Catalogue Manual (Serial Number 00400000-0043...
JCB 3CX 20 BACKOHE LOADER Parts Catalogue Manual (Serial Number 00400000-0043...jdjskdkdmmd
 
Pushover analysis-sacs
Pushover analysis-sacsPushover analysis-sacs
Pushover analysis-sacsHoàng Bkaero
 
[Tdb] vrf 360 cst for tk ver 1.0
[Tdb] vrf 360 cst for tk ver 1.0[Tdb] vrf 360 cst for tk ver 1.0
[Tdb] vrf 360 cst for tk ver 1.0Haluk TOSUN
 
M pact new air circuit breaker 400-4000 a
M pact  new air circuit breaker 400-4000 aM pact  new air circuit breaker 400-4000 a
M pact new air circuit breaker 400-4000 atwinkleerai
 
Original PNP Transistor A1020-Y A1020 1020 2SA1020 TO-92 New ON semiconductor
Original PNP Transistor A1020-Y A1020 1020 2SA1020 TO-92 New ON semiconductorOriginal PNP Transistor A1020-Y A1020 1020 2SA1020 TO-92 New ON semiconductor
Original PNP Transistor A1020-Y A1020 1020 2SA1020 TO-92 New ON semiconductorAUTHELECTRONIC
 
Product: UPS: UniStar VP
Product: UPS: UniStar VPProduct: UPS: UniStar VP
Product: UPS: UniStar VPStaco Energy
 

Similar to Larisa Vrv (20)

Dienhathe.com catalogue epcos-capacitor_phicap_b32344d
Dienhathe.com catalogue epcos-capacitor_phicap_b32344dDienhathe.com catalogue epcos-capacitor_phicap_b32344d
Dienhathe.com catalogue epcos-capacitor_phicap_b32344d
 
Original High Current NPN Transistor BC639 639 TO-92 New ON Semiconductor
Original High Current NPN Transistor BC639 639 TO-92 New ON SemiconductorOriginal High Current NPN Transistor BC639 639 TO-92 New ON Semiconductor
Original High Current NPN Transistor BC639 639 TO-92 New ON Semiconductor
 
Samsung tdb-dvm-s-water e-outdoor_dbeu-13082_da1
Samsung tdb-dvm-s-water e-outdoor_dbeu-13082_da1Samsung tdb-dvm-s-water e-outdoor_dbeu-13082_da1
Samsung tdb-dvm-s-water e-outdoor_dbeu-13082_da1
 
Kollmorgen pma series_catalog
Kollmorgen  pma  series_catalogKollmorgen  pma  series_catalog
Kollmorgen pma series_catalog
 
784144_Thyrotronic_gb
784144_Thyrotronic_gb784144_Thyrotronic_gb
784144_Thyrotronic_gb
 
Sb bora condensers-e-vap-ver.1.2_en
Sb bora condensers-e-vap-ver.1.2_enSb bora condensers-e-vap-ver.1.2_en
Sb bora condensers-e-vap-ver.1.2_en
 
Dienhathe.com catalogue epcos-capacitor_phasecap
Dienhathe.com catalogue epcos-capacitor_phasecapDienhathe.com catalogue epcos-capacitor_phasecap
Dienhathe.com catalogue epcos-capacitor_phasecap
 
CCD Series 2011 new-best.pdf
CCD Series 2011 new-best.pdfCCD Series 2011 new-best.pdf
CCD Series 2011 new-best.pdf
 
Fujitsu J-II Series Sell Sheet
Fujitsu J-II Series Sell SheetFujitsu J-II Series Sell Sheet
Fujitsu J-II Series Sell Sheet
 
PDXE_PX3_SS6 8-22-14
PDXE_PX3_SS6 8-22-14PDXE_PX3_SS6 8-22-14
PDXE_PX3_SS6 8-22-14
 
Thomson roundrail 1_vc_continuously_supported_specsheet
Thomson roundrail 1_vc_continuously_supported_specsheetThomson roundrail 1_vc_continuously_supported_specsheet
Thomson roundrail 1_vc_continuously_supported_specsheet
 
Thomson Linear RoundRail 1VC Continuously Supported Specs
Thomson Linear RoundRail 1VC Continuously Supported SpecsThomson Linear RoundRail 1VC Continuously Supported Specs
Thomson Linear RoundRail 1VC Continuously Supported Specs
 
Gaku Shimada, Panasonic
Gaku Shimada, PanasonicGaku Shimada, Panasonic
Gaku Shimada, Panasonic
 
JCB 3CX 20 BACKOHE LOADER Parts Catalogue Manual (Serial Number 00400000-0043...
JCB 3CX 20 BACKOHE LOADER Parts Catalogue Manual (Serial Number 00400000-0043...JCB 3CX 20 BACKOHE LOADER Parts Catalogue Manual (Serial Number 00400000-0043...
JCB 3CX 20 BACKOHE LOADER Parts Catalogue Manual (Serial Number 00400000-0043...
 
Pushover analysis-sacs
Pushover analysis-sacsPushover analysis-sacs
Pushover analysis-sacs
 
[Tdb] vrf 360 cst for tk ver 1.0
[Tdb] vrf 360 cst for tk ver 1.0[Tdb] vrf 360 cst for tk ver 1.0
[Tdb] vrf 360 cst for tk ver 1.0
 
M pact new air circuit breaker 400-4000 a
M pact  new air circuit breaker 400-4000 aM pact  new air circuit breaker 400-4000 a
M pact new air circuit breaker 400-4000 a
 
Original PNP Transistor A1020-Y A1020 1020 2SA1020 TO-92 New ON semiconductor
Original PNP Transistor A1020-Y A1020 1020 2SA1020 TO-92 New ON semiconductorOriginal PNP Transistor A1020-Y A1020 1020 2SA1020 TO-92 New ON semiconductor
Original PNP Transistor A1020-Y A1020 1020 2SA1020 TO-92 New ON semiconductor
 
Product: UPS: UniStar VP
Product: UPS: UniStar VPProduct: UPS: UniStar VP
Product: UPS: UniStar VP
 
R gz7 v1-databook
R gz7 v1-databookR gz7 v1-databook
R gz7 v1-databook
 

Recently uploaded

zidauu _business communication.pptx /pdf
zidauu _business  communication.pptx /pdfzidauu _business  communication.pptx /pdf
zidauu _business communication.pptx /pdfzukhrafshabbir
 
Unlock Your TikTok Potential: Free TikTok Likes with InstBlast
Unlock Your TikTok Potential: Free TikTok Likes with InstBlastUnlock Your TikTok Potential: Free TikTok Likes with InstBlast
Unlock Your TikTok Potential: Free TikTok Likes with InstBlastInstBlast Marketing
 
Aptar Closures segment - Corporate Overview-India.pdf
Aptar Closures segment - Corporate Overview-India.pdfAptar Closures segment - Corporate Overview-India.pdf
Aptar Closures segment - Corporate Overview-India.pdfprchbhandari
 
Engagement Rings vs Promise Rings | Detailed Guide
Engagement Rings vs Promise Rings | Detailed GuideEngagement Rings vs Promise Rings | Detailed Guide
Engagement Rings vs Promise Rings | Detailed GuideCharleston Alexander
 
LinkedIn Masterclass Techweek 2024 v4.1.pptx
LinkedIn Masterclass Techweek 2024 v4.1.pptxLinkedIn Masterclass Techweek 2024 v4.1.pptx
LinkedIn Masterclass Techweek 2024 v4.1.pptxSymbio Agency Ltd
 
Elevate Your Online Presence with SEO Services
Elevate Your Online Presence with SEO ServicesElevate Your Online Presence with SEO Services
Elevate Your Online Presence with SEO ServicesHaseebBashir5
 
TriStar Gold Corporate Presentation May 2024
TriStar Gold Corporate Presentation May 2024TriStar Gold Corporate Presentation May 2024
TriStar Gold Corporate Presentation May 2024Adnet Communications
 
Equinox Gold Corporate Deck May 24th 2024
Equinox Gold Corporate Deck May 24th 2024Equinox Gold Corporate Deck May 24th 2024
Equinox Gold Corporate Deck May 24th 2024Equinox Gold Corp.
 
8 Questions B2B Commercial Teams Can Ask To Help Product Discovery
8 Questions B2B Commercial Teams Can Ask To Help Product Discovery8 Questions B2B Commercial Teams Can Ask To Help Product Discovery
8 Questions B2B Commercial Teams Can Ask To Help Product DiscoveryDesmond Leo
 
Toyota Kata Coaching for Agile Teams & Transformations
Toyota Kata Coaching for Agile Teams & TransformationsToyota Kata Coaching for Agile Teams & Transformations
Toyota Kata Coaching for Agile Teams & TransformationsStefan Wolpers
 
Stages of Startup Funding - An Explainer
Stages of Startup Funding - An ExplainerStages of Startup Funding - An Explainer
Stages of Startup Funding - An ExplainerAlejandro Cremades
 
MichaelStarkes_UncutGemsProjectSummary.pdf
MichaelStarkes_UncutGemsProjectSummary.pdfMichaelStarkes_UncutGemsProjectSummary.pdf
MichaelStarkes_UncutGemsProjectSummary.pdfmstarkes24
 
Blinkit: Revolutionizing the On-Demand Grocery Delivery Service.pptx
Blinkit: Revolutionizing the On-Demand Grocery Delivery Service.pptxBlinkit: Revolutionizing the On-Demand Grocery Delivery Service.pptx
Blinkit: Revolutionizing the On-Demand Grocery Delivery Service.pptxSaksham Gupta
 
FEXLE- Salesforce Field Service Lightning
FEXLE- Salesforce Field Service LightningFEXLE- Salesforce Field Service Lightning
FEXLE- Salesforce Field Service LightningFEXLE
 
What is social media.pdf Social media refers to digital platforms and applica...
What is social media.pdf Social media refers to digital platforms and applica...What is social media.pdf Social media refers to digital platforms and applica...
What is social media.pdf Social media refers to digital platforms and applica...AnaBeatriz125525
 
Event Report - IBM Think 2024 - It is all about AI and hybrid
Event Report - IBM Think 2024 - It is all about AI and hybridEvent Report - IBM Think 2024 - It is all about AI and hybrid
Event Report - IBM Think 2024 - It is all about AI and hybridHolger Mueller
 
Pitch Deck Teardown: Terra One's $7.5m Seed deck
Pitch Deck Teardown: Terra One's $7.5m Seed deckPitch Deck Teardown: Terra One's $7.5m Seed deck
Pitch Deck Teardown: Terra One's $7.5m Seed deckHajeJanKamps
 
New Product Development.kjiy7ggbfdsddggo9lo
New Product Development.kjiy7ggbfdsddggo9loNew Product Development.kjiy7ggbfdsddggo9lo
New Product Development.kjiy7ggbfdsddggo9logalbokkahewagenitash
 
Copyright: What Creators and Users of Art Need to Know
Copyright: What Creators and Users of Art Need to KnowCopyright: What Creators and Users of Art Need to Know
Copyright: What Creators and Users of Art Need to KnowMiriam Robeson
 
Inside the Black Box of Venture Capital (VC)
Inside the Black Box of Venture Capital (VC)Inside the Black Box of Venture Capital (VC)
Inside the Black Box of Venture Capital (VC)Alejandro Cremades
 

Recently uploaded (20)

zidauu _business communication.pptx /pdf
zidauu _business  communication.pptx /pdfzidauu _business  communication.pptx /pdf
zidauu _business communication.pptx /pdf
 
Unlock Your TikTok Potential: Free TikTok Likes with InstBlast
Unlock Your TikTok Potential: Free TikTok Likes with InstBlastUnlock Your TikTok Potential: Free TikTok Likes with InstBlast
Unlock Your TikTok Potential: Free TikTok Likes with InstBlast
 
Aptar Closures segment - Corporate Overview-India.pdf
Aptar Closures segment - Corporate Overview-India.pdfAptar Closures segment - Corporate Overview-India.pdf
Aptar Closures segment - Corporate Overview-India.pdf
 
Engagement Rings vs Promise Rings | Detailed Guide
Engagement Rings vs Promise Rings | Detailed GuideEngagement Rings vs Promise Rings | Detailed Guide
Engagement Rings vs Promise Rings | Detailed Guide
 
LinkedIn Masterclass Techweek 2024 v4.1.pptx
LinkedIn Masterclass Techweek 2024 v4.1.pptxLinkedIn Masterclass Techweek 2024 v4.1.pptx
LinkedIn Masterclass Techweek 2024 v4.1.pptx
 
Elevate Your Online Presence with SEO Services
Elevate Your Online Presence with SEO ServicesElevate Your Online Presence with SEO Services
Elevate Your Online Presence with SEO Services
 
TriStar Gold Corporate Presentation May 2024
TriStar Gold Corporate Presentation May 2024TriStar Gold Corporate Presentation May 2024
TriStar Gold Corporate Presentation May 2024
 
Equinox Gold Corporate Deck May 24th 2024
Equinox Gold Corporate Deck May 24th 2024Equinox Gold Corporate Deck May 24th 2024
Equinox Gold Corporate Deck May 24th 2024
 
8 Questions B2B Commercial Teams Can Ask To Help Product Discovery
8 Questions B2B Commercial Teams Can Ask To Help Product Discovery8 Questions B2B Commercial Teams Can Ask To Help Product Discovery
8 Questions B2B Commercial Teams Can Ask To Help Product Discovery
 
Toyota Kata Coaching for Agile Teams & Transformations
Toyota Kata Coaching for Agile Teams & TransformationsToyota Kata Coaching for Agile Teams & Transformations
Toyota Kata Coaching for Agile Teams & Transformations
 
Stages of Startup Funding - An Explainer
Stages of Startup Funding - An ExplainerStages of Startup Funding - An Explainer
Stages of Startup Funding - An Explainer
 
MichaelStarkes_UncutGemsProjectSummary.pdf
MichaelStarkes_UncutGemsProjectSummary.pdfMichaelStarkes_UncutGemsProjectSummary.pdf
MichaelStarkes_UncutGemsProjectSummary.pdf
 
Blinkit: Revolutionizing the On-Demand Grocery Delivery Service.pptx
Blinkit: Revolutionizing the On-Demand Grocery Delivery Service.pptxBlinkit: Revolutionizing the On-Demand Grocery Delivery Service.pptx
Blinkit: Revolutionizing the On-Demand Grocery Delivery Service.pptx
 
FEXLE- Salesforce Field Service Lightning
FEXLE- Salesforce Field Service LightningFEXLE- Salesforce Field Service Lightning
FEXLE- Salesforce Field Service Lightning
 
What is social media.pdf Social media refers to digital platforms and applica...
What is social media.pdf Social media refers to digital platforms and applica...What is social media.pdf Social media refers to digital platforms and applica...
What is social media.pdf Social media refers to digital platforms and applica...
 
Event Report - IBM Think 2024 - It is all about AI and hybrid
Event Report - IBM Think 2024 - It is all about AI and hybridEvent Report - IBM Think 2024 - It is all about AI and hybrid
Event Report - IBM Think 2024 - It is all about AI and hybrid
 
Pitch Deck Teardown: Terra One's $7.5m Seed deck
Pitch Deck Teardown: Terra One's $7.5m Seed deckPitch Deck Teardown: Terra One's $7.5m Seed deck
Pitch Deck Teardown: Terra One's $7.5m Seed deck
 
New Product Development.kjiy7ggbfdsddggo9lo
New Product Development.kjiy7ggbfdsddggo9loNew Product Development.kjiy7ggbfdsddggo9lo
New Product Development.kjiy7ggbfdsddggo9lo
 
Copyright: What Creators and Users of Art Need to Know
Copyright: What Creators and Users of Art Need to KnowCopyright: What Creators and Users of Art Need to Know
Copyright: What Creators and Users of Art Need to Know
 
Inside the Black Box of Venture Capital (VC)
Inside the Black Box of Venture Capital (VC)Inside the Black Box of Venture Capital (VC)
Inside the Black Box of Venture Capital (VC)
 

Larisa Vrv

  • 1. Produced on 20/11/2007 with VRV Xpress V2.4.1 - database Central 5.4 Project name Reference . Client name . Selection parameters of the indoor units can be found under the chapter Indoor unit details Selection parameters of the outdoor units can be found under the chapter Outdoor unit details Only the data published in the data book are correct. This program uses close approximations of these data. 1. Material List Model Qty Description RXYQ12P7W1B 1 Heat pump VRV III P COMPACT RXYQ14P7W1B 2 Heat pump VRV III P COMPACT RXYQ18P7W1B 1 Heat pump VRV III P COMPACT RXYQ20P7W1B 1 Heat pump VRV III P COMPACT RXYQ5P7W1B 1 Heat pump VRV III P COMPACT RXYQ8P7W1B 1 Heat pump VRV III P COMPACT FXZQ50M8 28 Z - 4-way blow ceiling mounted cassette (600x600) VKM100GAV1 1 GA - Ventilation Air Reclaim VKM50GAV1 1 GA - Ventilation Air Reclaim VKM80GAMV1 2 GAM - Ventilation Air Reclaim VKM80GAV1 7 GA - Ventilation Air Reclaim KHRQ22M20T7 7 REFNET branch piping kit KHRQ22M29T7 11 REFNET branch piping kit KHRQ22M64T7 14 REFNET branch piping kit DCS302B51 1 Centralised BRC1D527 28 Wired remote control BYFQ60BW1 28 Decoration panel BHFQ22P1007 1 Outdoor unit multi connection piping kit for 2 outdoors VKM devices are considered as indoor units. They have an influence on the selection of outdoor units, the piping diagram, the wiring diagram and the centralized controller diagram. The VRV Xpress Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Xpress Program. Page 1
  • 2. 2. Indoor Unit Details 2.1.Table of Abbreviations Name Logical name of the device Rq HC Required heating capacity FCU Device model name HC Available heating capacity (with freeze-up correction) Tmp C Indoor conditions in cooling (dry bulb temp. / RH) Airflow Supplied airflow at low and high fan speed Rq TC Required total cooling capacity Sound Sound pressure low and high TC Available total cooling capacity MCA Minimum Circuit Amps Rq SC Required sensible cooling capacity WxHxD WidthxHeightxDepth SC Available sensible cooling capacity Wght Weight of the device Tmp H Indoor temperature in heating 2.2.Type A - Outdoor Unit - RXYQ20P7W1B Actual capacity data at conditions and combination ratio (102%) as entered Name FCU Tmp C Rq TC TC Rq SC SC Tmp H Rq HC HC Airflow Sound MCA WxHxD °C kW kW kW kW °C kW kW m³/h dBA A mm Type A - FCU 1 FXZQ50M8 24,0 / 50% n/a 4,4 n/a 3,4 20,0 n/a 4,5 600-840 33-41 0,9 575x286x575 Type A - FCU 2 FXZQ50M8 24,0 / 50% n/a 4,4 n/a 3,4 20,0 n/a 4,5 600-840 33-41 0,9 575x286x575 Type A - FCU 3 FXZQ50M8 24,0 / 50% n/a 4,4 n/a 3,4 20,0 n/a 4,5 600-840 33-41 0,9 575x286x575 Type A - FCU 4 FXZQ50M8 24,0 / 50% n/a 4,4 n/a 3,4 20,0 n/a 4,5 600-840 33-41 0,9 575x286x575 Type A - FCU 5 FXZQ50M8 24,0 / 50% n/a 4,4 n/a 3,4 20,0 n/a 4,5 600-840 33-41 0,9 575x286x575 Type A - FCU 6 FXZQ50M8 24,0 / 50% n/a 4,4 n/a 3,4 20,0 n/a 4,5 600-840 33-41 0,9 575x286x575 Type A - FCU 7 FXZQ50M8 24,0 / 50% n/a 4,4 n/a 3,4 20,0 n/a 4,5 600-840 33-41 0,9 575x286x575 Type A - VKM 1 VKM80GAMV1 24,0 / 50% n/a 7,1 n/a 4,5 20,0 n/a 7,2 640-750 36-36 4,3 1764x387x12 Type A - VKM 2 VKM80GAMV1 24,0 / 50% n/a 7,1 n/a 4,5 20,0 n/a 7,2 640-750 36-36 4,3 1764x387x12 Total 45,1 33,1 45,8 Diversified capacity data at conditions as entered and 100% combination ratio Name TC SC HC kW kW kW Type A - FCU 1 4,4 3,5 4,6 Type A - FCU 2 4,4 3,5 4,6 Type A - FCU 3 4,4 3,5 4,6 Type A - FCU 4 4,4 3,5 4,6 Type A - FCU 5 4,4 3,5 4,6 Type A - FCU 6 4,4 3,5 4,6 Type A - FCU 7 4,4 3,5 4,6 Type A - VKM 1 7,1 4,5 7,3 Type A - VKM 2 7,1 4,5 7,3 Total 45,3 33,2 46,6 The VRV Xpress Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Xpress Program. Page 2
  • 3. 2.3.Type B - Outdoor Unit - RXYQ18P7W1B Actual capacity data at conditions and combination ratio (102%) as entered Name FCU Tmp C Rq TC TC Rq SC SC Tmp H Rq HC HC Airflow Sound MCA WxHxD °C kW kW kW kW °C kW kW m³/h dBA A mm Type B - FCU 1 FXZQ50M8 24,0 / 50% n/a 4,3 n/a 3,4 20,0 n/a 4,1 600-840 33-41 0,9 575x286x57 Type B - FCU 2 FXZQ50M8 24,0 / 50% n/a 4,3 n/a 3,4 20,0 n/a 4,1 600-840 33-41 0,9 575x286x57 Type B - FCU 3 FXZQ50M8 24,0 / 50% n/a 4,3 n/a 3,4 20,0 n/a 4,1 600-840 33-41 0,9 575x286x57 Type B - FCU 4 FXZQ50M8 24,0 / 50% n/a 4,3 n/a 3,4 20,0 n/a 4,1 600-840 33-41 0,9 575x286x57 Type B - FCU 5 FXZQ50M8 24,0 / 50% n/a 4,3 n/a 3,4 20,0 n/a 4,1 600-840 33-41 0,9 575x286x57 Type B - FCU 6 FXZQ50M8 24,0 / 50% n/a 4,3 n/a 3,4 20,0 n/a 4,1 600-840 33-41 0,9 575x286x57 Type B - VKM 1 VKM80GAV1 24,0 / 50% n/a 6,9 n/a 4,4 20,0 n/a 6,6 640-750 37,5-37,5 4,3 1764x387x1 Type B - VKM 2 VKM80GAV1 24,0 / 50% n/a 6,9 n/a 4,4 20,0 n/a 6,6 640-750 37,5-37,5 4,3 1764x387x1 Total 39,7 29,2 38,1 Diversified capacity data at conditions as entered and 100% combination ratio Name TC SC HC kW kW kW Type B - FCU 1 4,3 3,4 4,2 Type B - FCU 2 4,3 3,4 4,2 Type B - FCU 3 4,3 3,4 4,2 Type B - FCU 4 4,3 3,4 4,2 Type B - FCU 5 4,3 3,4 4,2 Type B - FCU 6 4,3 3,4 4,2 Type B - VKM 1 6,9 4,4 6,8 Type B - VKM 2 6,9 4,4 6,8 Total 39,9 29,3 39,0 The VRV Xpress Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Xpress Program. Page 3
  • 4. 2.4.Type C - Outdoor Unit - RXYQ14P7W1B Actual capacity data at conditions and combination ratio (100%) as entered Name FCU Tmp C Rq TC TC Rq SC SC Tmp H Rq HC HC Airflow Sound MCA WxHxD °C kW kW kW kW °C kW kW m³/h dBA A mm Type C - FCU 1 FXZQ50M8 24,0 / 50% n/a 4,7 n/a 3,6 20,0 n/a 4,9 600-840 33-41 0,9 575x286x575 Type C - FCU 2 FXZQ50M8 24,0 / 50% n/a 4,7 n/a 3,6 20,0 n/a 4,9 600-840 33-41 0,9 575x286x575 Type C - FCU 3 FXZQ50M8 24,0 / 50% n/a 4,7 n/a 3,6 20,0 n/a 4,9 600-840 33-41 0,9 575x286x575 Type C - FCU 4 FXZQ50M8 24,0 / 50% n/a 4,7 n/a 3,6 20,0 n/a 4,9 600-840 33-41 0,9 575x286x575 Type C - FCU 5 FXZQ50M8 24,0 / 50% n/a 4,7 n/a 3,6 20,0 n/a 4,9 600-840 33-41 0,9 575x286x575 Type C - VKM 1 VKM100GAV1 24,0 / 50% n/a 9,3 n/a 5,9 20,0 n/a 9,8 820-950 38-38 4,3 1764x387x12 Total 32,7 23,6 34,2 Diversified capacity data at conditions as entered and 100% combination ratio Name TC SC HC kW kW kW Type C - FCU 1 4,7 3,6 4,9 Type C - FCU 2 4,7 3,6 4,9 Type C - FCU 3 4,7 3,6 4,9 Type C - FCU 4 4,7 3,6 4,9 Type C - FCU 5 4,7 3,6 4,9 Type C - VKM 1 9,3 5,9 9,8 Total 32,7 23,6 34,2 The VRV Xpress Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Xpress Program. Page 4
  • 5. 2.5.Type D - Outdoor Unit - RXYQ14P7W1B Actual capacity data at conditions and combination ratio (103%) as entered Name FCU Tmp C Rq TC TC Rq SC SC Tmp H Rq HC HC Airflow Sound MCA WxHxD °C kW kW kW kW °C kW kW m³/h dBA A mm Type D - FCU 1 FXZQ50M8 24,0 / 50% n/a 4,6 n/a 3,5 20,0 n/a 4,8 600-840 33-41 0,9 575x286x57 Type D - FCU 2 FXZQ50M8 24,0 / 50% n/a 4,6 n/a 3,5 20,0 n/a 4,8 600-840 33-41 0,9 575x286x57 Type D - FCU 3 FXZQ50M8 24,0 / 50% n/a 4,6 n/a 3,5 20,0 n/a 4,8 600-840 33-41 0,9 575x286x57 Type D - FCU 4 FXZQ50M8 24,0 / 50% n/a 4,6 n/a 3,5 20,0 n/a 4,8 600-840 33-41 0,9 575x286x57 Type D - VKM 1 VKM80GAV1 24,0 / 50% n/a 7,4 n/a 4,7 20,0 n/a 7,6 640-750 37,5-37,5 4,3 1764x387x1 Type D - VKM 2 VKM80GAV1 24,0 / 50% n/a 7,4 n/a 4,7 20,0 n/a 7,6 640-750 37,5-37,5 4,3 1764x387x1 Total 33,4 23,5 34,3 Diversified capacity data at conditions as entered and 100% combination ratio Name TC SC HC kW kW kW Type D - FCU 1 4,7 3,6 4,9 Type D - FCU 2 4,7 3,6 4,9 Type D - FCU 3 4,7 3,6 4,9 Type D - FCU 4 4,7 3,6 4,9 Type D - VKM 1 7,5 4,7 7,8 Type D - VKM 2 7,5 4,7 7,8 Total 33,6 23,6 35,2 The VRV Xpress Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Xpress Program. Page 5
  • 6. 2.6.Type E - Outdoor Unit - RXYQ12P7W1B Actual capacity data at conditions and combination ratio (103%) as entered Name FCU Tmp C Rq TC TC Rq SC SC Tmp H Rq HC HC Airflow Sound MCA WxHxD °C kW kW kW kW °C kW kW m³/h dBA A mm Type E - FCU 1 FXZQ50M8 24,0 / 50% n/a 4,5 n/a 3,5 20,0 n/a 4,1 600-840 33-41 0,9 575x286x57 Type E - FCU 2 FXZQ50M8 24,0 / 50% n/a 4,5 n/a 3,5 20,0 n/a 4,1 600-840 33-41 0,9 575x286x57 Type E - FCU 3 FXZQ50M8 24,0 / 50% n/a 4,5 n/a 3,5 20,0 n/a 4,1 600-840 33-41 0,9 575x286x57 Type E - VKM 1 VKM80GAV1 24,0 / 50% n/a 7,3 n/a 4,6 20,0 n/a 6,5 640-750 37,5-37,5 4,3 1764x387x1 Type E - VKM 2 VKM80GAV1 24,0 / 50% n/a 7,3 n/a 4,6 20,0 n/a 6,5 640-750 37,5-37,5 4,3 1764x387x1 Total 28,1 19,6 25,1 Diversified capacity data at conditions as entered and 100% combination ratio Name TC SC HC kW kW kW Type E - FCU 1 4,6 3,5 4,2 Type E - FCU 2 4,6 3,5 4,2 Type E - FCU 3 4,6 3,5 4,2 Type E - VKM 1 7,3 4,6 6,7 Type E - VKM 2 7,3 4,6 6,7 Total 28,3 19,7 25,9 The VRV Xpress Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Xpress Program. Page 6
  • 7. 2.7.Type F - Outdoor Unit - RXYQ8P7W1B Actual capacity data at conditions and combination ratio (90%) as entered Name FCU Tmp C Rq TC TC Rq SC SC Tmp H Rq HC HC Airflow Sound MCA WxHxD °C kW kW kW kW °C kW kW m³/h dBA A mm Type F - FCU 1 FXZQ50M8 24,0 / 50% n/a 4,4 n/a 3,4 20,0 n/a 5,2 600-840 33-41 0,9 575x286x57 Type F - FCU 2 FXZQ50M8 24,0 / 50% n/a 4,4 n/a 3,4 20,0 n/a 5,2 600-840 33-41 0,9 575x286x57 Type F - VKM 1 VKM80GAV1 24,0 / 50% n/a 7,1 n/a 4,5 20,0 n/a 8,3 640-750 37,5-37,5 4,3 1764x387x1 Total 15,9 11,4 18,7 Diversified capacity data at conditions as entered and 100% combination ratio Name TC SC HC kW kW kW Type F - FCU 1 4,4 3,4 5,2 Type F - FCU 2 4,4 3,4 5,2 Type F - VKM 1 7,1 4,5 8,3 Total 15,9 11,4 18,7 The VRV Xpress Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Xpress Program. Page 7
  • 8. 2.8.Type G - Outdoor Unit - RXYQ5P7W1B Actual capacity data at conditions and combination ratio (80%) as entered Name FCU Tmp C Rq TC TC Rq SC SC Tmp H Rq HC HC Airflow Sound MCA WxHxD °C kW kW kW kW °C kW kW m³/h dBA A mm Type G - FCU 1 FXZQ50M8 24,0 / 50% n/a 4,2 n/a 3,3 20,0 n/a 5,4 600-840 33-41 0,9 575x286x575 Type F - VKM 1 VKM50GAV1 24,0 / 50% n/a 4,2 n/a 2,7 20,0 n/a 5,4 440-500 36-36 4,3 1764x387x832 Total 8,4 6,0 10,8 Diversified capacity data at conditions as entered and 100% combination ratio Name TC SC HC kW kW kW Type G - FCU 1 4,2 3,3 5,4 Type F - VKM 1 4,2 2,7 5,4 Total 8,4 6,0 10,8 The VRV Xpress Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Xpress Program. Page 8
  • 9. 3. Outdoor Unit Details 3.1.Table of Abbreviations Name Logical name of the device Refrig Standard factory refrigerant charge (5m actual piping length), Model Device model name excluding extra refrigerant charge Comb Combination percentage For calculation of extra refrigerant charge refer to the VRV databook Tmp C Outdoor temperature in cooling (dry bulb) PS Power supply (voltage and phases) CC Cooling capacity Run Amps Running Amps EER EER at selection and nominal conditions St Curr Starting current Tmp H Outdoor temperature in heating (dry bulb) Fuses Fuses HC Heating capacity (with freeze-up correction) WxHxD WidthxHeightxDepth COP COP at selection and nominal conditions Wght Weight of the device Piping Largest distance from indoor unit to outdoor unit 3.2.Outdoor Details Name Model Comb Tmp C CC EER Tmp H HC COP Piping Refrig % °C kW °C kW m kg Type A - Outdoor Unit RXYQ20P7W1B 102 37,0 49,6 3,7 / 3,7 -7,0 45,8 3,1 / 4,1 45,0 16,3 * RXYQ12P7W1B * RXYQ8P7W1B Type B - Outdoor Unit RXYQ18P7W1B 102 37,0 43,5 3/3 -7,0 38,1 2,9 / 3,7 45,0 12,7 Type C - Outdoor Unit RXYQ14P7W1B 100 37,0 34,9 3,2 / 3,2 -7,0 34,2 2,8 / 4 45,0 12,3 Type D - Outdoor Unit RXYQ14P7W1B 103 37,0 35,7 3,2 / 3,2 -7,0 34,3 2,8 / 4 45,0 12,3 Type E - Outdoor Unit RXYQ12P7W1B 103 37,0 30,0 3,5 / 3,5 -7,0 25,1 3,1 / 4 45,0 8,6 Type F - Outdoor Unit RXYQ8P7W1B 90 37,0 19,5 4/4 -7,0 20,8 3,2 / 4,3 45,0 7,7 Type G - Outdoor Unit RXYQ5P7W1B 80 37,0 12,2 4/4 -7,0 13,5 2,9 / 4 45,0 6,2 Name Model PS Run Amps St Curr Fuses WxHxD Wght A A mm kg Type A - Outdoor Unit RXYQ20P7W1B 400V 3Nph 1860x1680x765 427 * RXYQ12P7W1B 14 75 cfr. local legislation * RXYQ8P7W1B 7,5 cfr. local legislation Type B - Outdoor Unit RXYQ18P7W1B 400V 3Nph 24,2 85 cfr. local legislation 1240x1680x765 325 Type C - Outdoor Unit RXYQ14P7W1B 400V 3Nph 18,4 84 cfr. local legislation 1240x1680x765 317 Type D - Outdoor Unit RXYQ14P7W1B 400V 3Nph 18,4 84 cfr. local legislation 1240x1680x765 317 Type E - Outdoor Unit RXYQ12P7W1B 400V 3Nph 14 75 cfr. local legislation 930x1680x765 240 Type F - Outdoor Unit RXYQ8P7W1B 400V 3Nph 7,5 cfr. local legislation 930x1680x765 187 Type G - Outdoor Unit RXYQ5P7W1B 400V 3Nph 5,1 cfr. local legislation 635x1680x765 159 The VRV Xpress Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Xpress Program. Page 9
  • 10. 4. Piping Diagrams Pipes marked with * in the diagrams must be connected to the device with a reducing joint. 4.1.Piping Type A - Outdoor Unit Ty pe A - Outdoor Unit Ty pe A - FCU 1 15,9x28,6 6,4x12,7 RXY Q20P7W1B FXZQ50M8 KHRQ22M64T7 RXY Q12P7W1B 12,7x28,6 Ty pe A - FCU 2 15,9x28,6 6,4x12,7 FXZQ50M8 BHFQ22P1007 KHRQ22M64T7 Ty pe A - FCU 3 12,7x28,6 6,4x12,7 FXZQ50M8 RXY Q8P7W1B 9,5x19,1 KHRQ22M64T7 Ty pe A - FCU 4 12,7x28,6 6,4x12,7 FXZQ50M8 KHRQ22M64T7 Ty pe A - FCU 5 12,7x28,6 6,4x12,7 FXZQ50M8 KHRQ22M64T7 Ty pe A - FCU 6 9,5x22,2 6,4x12,7 FXZQ50M8 KHRQ22M29T7 Ty pe A - FCU 7 9,5x22,2 6,4x12,7 FXZQ50M8 KHRQ22M29T7 Ty pe A - VKM 1 9,5x19,1 6,4x12,7 VKM80GAMV1 KHRQ22M20T7 Ty pe A - VKM 2 6,4x12,7 VKM80GAMV1 4.2.Piping Type B - Outdoor Unit Ty pe B - Outdoor Unit Ty pe B - FCU 1 15,9x28,6 6,4x12,7 RXY Q18P7W1B FXZQ50M8 KHRQ22M64T7 Ty pe B - FCU 2 12,7x28,6 6,4x12,7 FXZQ50M8 KHRQ22M64T7 Ty pe B - FCU 3 12,7x28,6 6,4x12,7 FXZQ50M8 KHRQ22M64T7 Ty pe B - FCU 4 12,7x28,6 6,4x12,7 FXZQ50M8 KHRQ22M64T7 Ty pe B - FCU 5 9,5x22,2 6,4x12,7 FXZQ50M8 KHRQ22M29T7 Ty pe B - FCU 6 9,5x22,2 6,4x12,7 FXZQ50M8 KHRQ22M29T7 Ty pe B - VKM 1 9,5x19,1 6,4x12,7 VKM80GAV1 KHRQ22M20T7 Ty pe B - VKM 2 6,4x12,7 VKM80GAV1 The VRV Xpress Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Xpress Program. Page 10
  • 11. 4.3.Piping Type C - Outdoor Unit Ty pe C - Outdoor Unit Ty pe C - FCU 1 12,7x28,6 6,4x12,7 RXY Q14P7W1B FXZQ50M8 KHRQ22M64T7 Ty pe C - FCU 2 12,7x28,6 6,4x12,7 FXZQ50M8 KHRQ22M64T7 Ty pe C - FCU 3 9,5x22,2 6,4x12,7 FXZQ50M8 KHRQ22M29T7 Ty pe C - FCU 4 9,5x22,2 6,4x12,7 FXZQ50M8 KHRQ22M29T7 Ty pe C - FCU 5 9,5x19,1 6,4x12,7 FXZQ50M8 KHRQ22M20T7 Ty pe C - VKM 1 6,4x12,7 VKM100GAV1 4.4.Piping Type D - Outdoor Unit Ty pe D - Outdoor Unit Ty pe D - FCU 1 12,7x28,6 6,4x12,7 RXY Q14P7W1B FXZQ50M8 KHRQ22M64T7 Ty pe D - FCU 2 12,7x28,6 6,4x12,7 FXZQ50M8 KHRQ22M64T7 Ty pe D - FCU 3 9,5x22,2 6,4x12,7 FXZQ50M8 KHRQ22M29T7 Ty pe D - FCU 4 9,5x22,2 6,4x12,7 FXZQ50M8 KHRQ22M29T7 Ty pe D - VKM 1 9,5x19,1 6,4x12,7 VKM80GAV1 KHRQ22M20T7 Ty pe D - VKM 2 6,4x12,7 VKM80GAV1 4.5.Piping Type E - Outdoor Unit Ty pe E - Outdoor Unit Ty pe E - FCU 1 12,7x28,6 6,4x12,7 RXY Q12P7W1B FXZQ50M8 KHRQ22M64T7 Ty pe E - FCU 2 9,5x22,2 6,4x12,7 FXZQ50M8 KHRQ22M29T7 Ty pe E - FCU 3 9,5x22,2 6,4x12,7 FXZQ50M8 KHRQ22M29T7 Ty pe E - VKM 1 9,5x19,1 6,4x12,7 VKM80GAV1 KHRQ22M20T7 Ty pe E - VKM 2 6,4x12,7 VKM80GAV1 The VRV Xpress Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Xpress Program. Page 11
  • 12. 4.6.Piping Type F - Outdoor Unit Ty pe F - Outdoor Unit Ty pe F - FCU 1 9,5x19,1 6,4x12,7 RXY Q8P7W1B FXZQ50M8 KHRQ22M29T7 Ty pe F - FCU 2 9,5x15,9 6,4x12,7 FXZQ50M8 KHRQ22M20T7 Ty pe F - VKM 1 6,4x12,7 VKM80GAV1 4.7.Piping Type G - Outdoor Unit Ty pe G - Outdoor Unit Ty pe G - FCU 1 9,5x15,9 6,4x12,7 RXY Q5P7W1B FXZQ50M8 KHRQ22M20T7 Ty pe F - VKM 1 6,4x12,7 VKM50GAV1 5. Wiring Diagrams P1P2 = 16-2 AWG 2 core non screened stranded wire (non polarity wiring system) F1F2 = 16-2 AWG 2 core non screened stranded wire (non polarity wiring system) 5.1.Centralized Controllers centralised DCS302B51 centralised Ty pe A - Outdoor Unit RXY Q20P7W1B F1,F2 OUT F1,F2 L,N Ty pe B - Outdoor Unit RXY Q18P7W1B OUT F1,F2 Ty pe C - Outdoor Unit RXY Q14P7W1B OUT F1,F2 Ty pe D - Outdoor Unit RXY Q14P7W1B OUT F1,F2 Ty pe E - Outdoor Unit RXY Q12P7W1B OUT F1,F2 Ty pe F - Outdoor Unit RXY Q8P7W1B OUT F1,F2 Ty pe G - Outdoor Unit RXY Q5P7W1B OUT F1,F2 The VRV Xpress Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Xpress Program. Page 12
  • 13. 5.2.Wiring Type A - Outdoor Unit to centralized controller P1,P2 14,9A 1ph Ty pe A - Outdoor Unit Ty pe A - FCU 1 BRC1D527 RXY Q20P7W1B FXZQ50M8 OUT F1,F2 IN F1,F2 F1,F2 L,N P1,P2 RXY Q12P7W1B Ty pe A - FCU 2 BRC1D527 FXZQ50M8 Q1,Q2 L1,L2,L3,N F1,F2 L,N 22,7A 3Nph P1,P2 Ty pe A - FCU 3 BRC1D527 RXY Q8P7W1B FXZQ50M8 F1,F2 L,N Q1,Q2 L1,L2,L3,N 18,5A 3Nph P1,P2 Ty pe A - FCU 4 BRC1D527 FXZQ50M8 F1,F2 L,N P1,P2 Ty pe A - FCU 5 BRC1D527 FXZQ50M8 F1,F2 L,N P1,P2 Ty pe A - FCU 6 BRC1D527 FXZQ50M8 F1,F2 L,N P1,P2 Ty pe A - FCU 7 BRC1D527 FXZQ50M8 F1,F2 L,N Ty pe A - VKM 1 VKM80GAMV1 F1,F2 L,N Ty pe A - VKM 2 VKM80GAMV1 F1,F2 L,N The VRV Xpress Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Xpress Program. Page 13
  • 14. 5.3.Wiring Type B - Outdoor Unit to centralized controller P1,P2 14A 1ph Ty pe B - Outdoor Unit Ty pe B - FCU 1 BRC1D527 RXY Q18P7W1B FXZQ50M8 OUT F1,F2 IN F1,F2 F1,F2 L,N P1,P2 Ty pe B - FCU 2 BRC1D527 FXZQ50M8 L1,L2,L3,N 32,5A 3Nph F1,F2 L,N P1,P2 Ty pe B - FCU 3 BRC1D527 FXZQ50M8 F1,F2 L,N P1,P2 Ty pe B - FCU 4 BRC1D527 FXZQ50M8 F1,F2 L,N P1,P2 Ty pe B - FCU 5 BRC1D527 FXZQ50M8 F1,F2 L,N P1,P2 Ty pe B - FCU 6 BRC1D527 FXZQ50M8 F1,F2 L,N Ty pe B - VKM 1 VKM80GAV1 F1,F2 L,N Ty pe B - VKM 2 VKM80GAV1 F1,F2 L,N The VRV Xpress Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Xpress Program. Page 14
  • 15. 5.4.Wiring Type C - Outdoor Unit to centralized controller P1,P2 8,8A 1ph Ty pe C - Outdoor Unit Ty pe C - FCU 1 BRC1D527 RXY Q14P7W1B FXZQ50M8 OUT F1,F2 IN F1,F2 F1,F2 L,N P1,P2 Ty pe C - FCU 2 BRC1D527 FXZQ50M8 L1,L2,L3,N 31,5A 3Nph F1,F2 L,N P1,P2 Ty pe C - FCU 3 BRC1D527 FXZQ50M8 F1,F2 L,N P1,P2 Ty pe C - FCU 4 BRC1D527 FXZQ50M8 F1,F2 L,N P1,P2 Ty pe C - FCU 5 BRC1D527 FXZQ50M8 F1,F2 L,N Ty pe C - VKM 1 VKM100GAV1 F1,F2 L,N 5.5.Wiring Type D - Outdoor Unit to centralized controller P1,P2 12,2A 1ph Ty pe D - Outdoor Unit Ty pe D - FCU 1 BRC1D527 RXY Q14P7W1B FXZQ50M8 OUT F1,F2 IN F1,F2 F1,F2 L,N P1,P2 Ty pe D - FCU 2 BRC1D527 FXZQ50M8 L1,L2,L3,N 31,5A 3Nph F1,F2 L,N P1,P2 Ty pe D - FCU 3 BRC1D527 FXZQ50M8 F1,F2 L,N P1,P2 Ty pe D - FCU 4 BRC1D527 FXZQ50M8 F1,F2 L,N Ty pe D - VKM 1 VKM80GAV1 F1,F2 L,N Ty pe D - VKM 2 VKM80GAV1 F1,F2 L,N The VRV Xpress Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Xpress Program. Page 15
  • 16. 5.6.Wiring Type E - Outdoor Unit to centralized controller P1,P2 11,3A 1ph Ty pe E - Outdoor Unit Ty pe E - FCU 1 BRC1D527 RXY Q12P7W1B FXZQ50M8 OUT F1,F2 IN F1,F2 F1,F2 L,N P1,P2 Ty pe E - FCU 2 BRC1D527 L1,L2,L3,N 22,7A 3Nph FXZQ50M8 F1,F2 L,N P1,P2 Ty pe E - FCU 3 BRC1D527 FXZQ50M8 F1,F2 L,N Ty pe E - VKM 1 VKM80GAV1 F1,F2 L,N Ty pe E - VKM 2 VKM80GAV1 F1,F2 L,N 5.7.Wiring Type F - Outdoor Unit to centralized controller P1,P2 6,1A 1ph Ty pe F - Outdoor Unit Ty pe F - FCU 1 BRC1D527 RXY Q8P7W1B FXZQ50M8 OUT F1,F2 IN F1,F2 F1,F2 L,N P1,P2 Ty pe F - FCU 2 BRC1D527 L1,L2,L3,N 18,5A 3Nph FXZQ50M8 F1,F2 L,N Ty pe F - VKM 1 VKM80GAV1 F1,F2 L,N 5.8.Wiring Type G - Outdoor Unit to centralized controller P1,P2 5,2A 1ph Ty pe G - Outdoor Unit Ty pe G - FCU 1 BRC1D527 RXY Q5P7W1B FXZQ50M8 OUT F1,F2 IN F1,F2 F1,F2 L,N L1,L2,L3,N 11,9A 3Nph Ty pe F - VKM 1 VKM50GAV1 F1,F2 L,N The VRV Xpress Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Xpress Program. Page 16
  • 17. 6. Device Options 6.1.Outdoor Unit Options Model Description Used by BHFQ22P1007 Outdoor unit multi connection piping kit for 2 outdoors Type A - Outdoor Unit [RXYQ20P7W1B] 6.2.Indoor Unit Options Model Description Used by BYFQ60BW1 Decoration panel Type A - FCU 2 [FXZQ50M8] Type A - FCU 3 [FXZQ50M8] Type A - FCU 4 [FXZQ50M8] Type A - FCU 5 [FXZQ50M8] Type A - FCU 6 [FXZQ50M8] Type A - FCU 1 [FXZQ50M8] Type B - FCU 1 [FXZQ50M8] Type B - FCU 2 [FXZQ50M8] Type A - FCU 7 [FXZQ50M8] Type B - FCU 3 [FXZQ50M8] Type B - FCU 4 [FXZQ50M8] Type B - FCU 5 [FXZQ50M8] Type B - FCU 6 [FXZQ50M8] Type C - FCU 1 [FXZQ50M8] Type C - FCU 2 [FXZQ50M8] Type C - FCU 3 [FXZQ50M8] Type C - FCU 4 [FXZQ50M8] Type C - FCU 5 [FXZQ50M8] Type D - FCU 1 [FXZQ50M8] Type D - FCU 2 [FXZQ50M8] Type D - FCU 3 [FXZQ50M8] Type D - FCU 4 [FXZQ50M8] Type E - FCU 1 [FXZQ50M8] Type E - FCU 2 [FXZQ50M8] Type E - FCU 3 [FXZQ50M8] Type F - FCU 1 [FXZQ50M8] Type F - FCU 2 [FXZQ50M8] Type G - FCU 1 [FXZQ50M8] The VRV Xpress Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the VRV Xpress Program. Page 17